Академический Документы
Профессиональный Документы
Культура Документы
L & T LIMITED
EPCS CONSULTANT:
DocumentNo:L570000-YT01-00-GNB-150010
Package:ETP
ThisDocumentisApprovedforDMPlant.
Therefore,thesamemaybeApprovedforETP.
INST TYPE
DESCRIPTION
FLUID
CALIBRATION
UNIT
PRESSURE TRANSMITTER
OILY WASTE
0-4
KG/CM2 (g)
MAX DIFF.
PARENT TAG
0GND05BR001
PROCESS PARAMETER
3
45
240
25
200
60
300
AREA
ACCESSORIES
MAKE
MODEL
P&ID NO.
CERTIFICATION
PROCESS
FLANGE
FLANGE
REV.
REMARKS
SAFE
FLANGE +
CAPILLARY
REFER DS
REFER DS
L570000-XG02-00-GNB-120001
REV C
REFER DS
FLANGED
CSRL
150
DIA SEAL
0GND20CP101
PRESSURE TRANSMITTER
SLUDGE
0-4
KG/CM2 (g)
0GND20BR003
3.1
45
100
2.5
25
75
60
120
SAFE
FLANGE +
CAPILLARY
REFER DS
REFER DS
L570000-XG02-00-GNB-120001
REV C
REFER DS
FLANGED
CSRL
150
DIA SEAL
0GND36CP101
PRESSURE TRANSMITTER
EFFLUENT
0-4
KG/CM2 (g)
0GND36BR001
2.4
45
950
25
860
60
1150
SAFE
FLANGE +
CAPILLARY
REFER DS
REFER DS
L570000-XG02-00-GNB-120001
REV C
REFER DS
FLANGED
CSRL
150
DIA SEAL
0GND16CP101
PRESSURE TRANSMITTER
WATER
0-4
KG/CM2 (g)
0GND16BR101
3.3
45
220
25
200
60
250
SAFE
FLANGE +
CAPILLARY
REFER DS
REFER DS
L570000-XG02-00-GNB-120001
REV C
REFER DS
FLANGED
CSRL
150
DIA SEAL
AIR
0-2
KG/CM2 (g)
0GND25BR003
1.4
45
1650
0.4
25
1630
60
1700
SAFE
2 VALVE MANIFOLD
REFER DS
REFER DS
L570000-XG02-00-GNB-120001
REV C
REFER DS
NA
NA
GAUGE PR
AIR
0-2
KG/CM2 (g)
0GND21BR003
1.4
45
130
0.4
25
115
60
150
SAFE
2 VALVE MANIFOLD
REFER DS
REFER DS
L570000-XG02-00-GNB-120001
REV C
REFER DS
NA
NA
GAUGE PR
0GND25CP101
PRESSURE TRANSMITTER
0GND21CP101
PRESSURE TRANSMITTER
INST TYPE
DESCRIPTION
FLUID
CALIBRATION
UNIT
AREA
ACCESSORIES
MAKE
MODEL
P&ID NO.
CERTIFICATION
PROCESS
FLANGE
FLANGE
REV.
REMARKS
0GND56CP101
PRESSURE TRANSMITTER
WATER
0-8
KG/CM2 (g)
MAX DIFF.
0GND56BR001
PARENT TAG
5.7
45
900
PROCESS PARAMETER
5
25
800
60
1050
SAFE
2 VALVE MANIFOLD
REFER DS
REFER DS
L570000-XG02-00-GNB-120001
REV C
REFER DS
NA
NA
GAUGE PR
0GND62CP101
PRESSURE TRANSMITTER
WATER
0-4
KG/CM2 (g)
0GND62BR001
2.3
45
170
25
150
60
200
SAFE
2 VALVE MANIFOLD
REFER DS
REFER DS
L570000-XG02-00-GNB-120001
REV C
REFER DS
NA
NA
GAUGE PR
L & T LIMITED
EPCS CONSULTANT:
DATASHEET&GAFORPRESSURETRANSMITTER
DOC/DRG NO. :
150035
L570000YT0100GCF
REV: C
DATE
31-05-2013
APPROVED
Action B
Action C
Action D
DISAPPROVED
Action E
E-MAIL REF.
Through t-bits
SIGNATURE
AKA/ARU
Drawing/Document reviewed only for general compliance with specifications. Action shown above is
subject to the terms and conditions of contract and does not relieve the Contractor from his obligations
under the contract including design and detailing.
REVISION RECORDS
C
Rev
No
20/03/2013
THIRD SUBMISSION
PSV
PC
AKO
DATE
REVISION SUMMERY
PREPARED
REVIEWED
APPROVED
Purpose
Date
Reviewed
Inst.
Appd.
Mech.
PRESSURE TRANSMITTER
Tag No.:Ref Annexure
5
7
9
11
13
15
17
GENERAL
Emerson (Rosemount)
Ref Annexure
2
4
Measurement Principle
Piezoresistive
6
8
10
12
14
16
18
Design Temp.
Max Operating Temp
Ref Annexure
Ref Annexure
Ref Annexure
Ref Annexure
Ref Annexure
19
Mounting
20
Safe Area
21
22
Sensing Element
Diaphragm
23
Flange Material
N/A
24
SS 316
Flange Rating
N/A
26
Entry Position
Side
28
SS 316
2
Yes
Digital LCD Type
100 : 1
+/- 0.2% (FS)
600 Ohms(Max) at 24 V DC
100 msec
Manifold
Integral Manifold
27
CONSTRUCTION
25
PROCESS
Design Pressure
Max. Operating Pressure
Range
SS
30
Bodyy Rating
g
Over-Range Protection
Enclosure Protection
Transmitter Output
Power Supply
Accuracy
Repeatability
Transmitter Span
Diaphragm Seal
Diaphragm Seal Type
No
N/A
32
34
36
38
40
42
44
46
48
50
52
54
56
57
58
Manifold Material
SS 316
59
61
63
SS 316
SS 316L
SS 316
60
62
64
Manifold Connection
O-Ring
O-Ring Material
1/2" NPT(F)
Yes
Neoprene
Filling Fluid
Silicone Oil
66
Flushing Connection
Yes
68
65
67
69
ACCESSORIES
31
33
35
37
39
41
43
45
47
49
51
53
55
CHARACTERISTICS
29
71
73
77
79
81
83
85
87
OPTIONS
75
Flushing Connection
Quantity
70
72
Name Plate
SS
74
Mounting Accessories
Yes
Certification
Transient Surge Protector
Capillary Type
N/A
Capillary length
N/A
No
Yes
76
78
80
82
84
86
88
DOCUMENT NO.:
REV :
DATE:
INSTRUMENT LIST
INST TYPE
DESCRIPTION
FLUID
RANGE
UNIT
DIFF. PRESS
(METER
RANGE)
(mmWC)
PARENT TAG NO
PROCESS PARAMETER
NORMAL
MAXIMUM
PRESS
kg/cm2(g)
TEMP (Deg
C)
FLOW
(M3/hr)
PRESS
kg/cm2(g)
TEMP (Deg
C)
FLOW
(M3/hr)
DESIGN
PRESS
kg/cm2(g)
TEMP (Deg
C)
FLOW
(M3/hr)
AREA
ACCESSORI
CLASSIFICATI
ES
ON
MAKE
MODEL
P&ID NO.
CERTIFICATION
PROCESS
CONNECTION
FLANGE
MATERIAL
FLANGE
RATING
(#)
REV.
NO
0GCF12CP101
GAUGE PRESSURE
TRANSMITTER
WATER
0-8
KG/CM2
NA
NA
0GCF12BR001
4.4
32
400
27
393
40
410
SAFE
REFER DS
Emerson
(Rosemount)
2051TG2A2B21KB4M5D4Q4
L570000-XG02-00-GCF-120001
CATALOGUE
NA
NA
0GCF42CP105
GAUGE PRESSURE
TRANSMITTER
WATER
0-6
KG/CM2
NA
NA
0GCF42BR002
3.9
32
385
3.5
27
375
4.2
40
400
SAFE
REFER DS
Emerson
(Rosemount)
2051TG2A2B21KB4M5D4Q4
L570000-XG02-00-GCF-120001
CATALOGUE
NA
NA
0GCF38CP105
GAUGE PRESSURE
TRANSMITTER
WATER
0-6
KG/CM2
NA
NA
0GCF38BR001
3.9
32
45
3.5
27
40
4.2
40
50
SAFE
REFER DS
Emerson
(Rosemount)
2051TG2A2B21KB4M5D4Q4
L570000-XG02-00-GCF-120001
CATALOGUE
NA
NA
0CGP60CP101
GAUGE PRESSURE
TRANSMITTER
WATER
0-3
KG/CM2
NA
NA
0GCF60BR0010
2.1
32
160
1.5
27
150
2.5
40
165
SAFE
REFER DS
Emerson
(Rosemount)
2051TG2A2B21KB4M5D4Q4
L570000-XG02-00-GCF-120001
CATALOGUE
NA
NA
0GCF33CP108
GAUGE PRESSURE
TRANSMITTER
AIR
0-12
KG/CM2
NA
NA
0GCF33BR001
50
30
32
25
10
60
30
SAFE
REFER DS
Emerson
(Rosemount)
2051TG3A2B21KB4M5D4Q4
L570000-XG02-00-GCF-120001
CATALOGUE
NA
NA
0GCF92CP101
GAUGE PRESSURE
TRANSMITTER
WATER
0-6
KG/CM2
NA
NA
0GCF92BR001
32
210
2.5
27
200
3.5
40
215
SAFE
REFER DS
Emerson
(Rosemount)
2051TG2A2B21KB4M5D4Q4
L570000-XG02-00-GCF-120001
CATALOGUE
NA
NA
PREPARED BY:
REVIEWED BY:
APPROVED BY:
PAGE: 1 OF 1
REMARKS
DOCUMENT NO.:
REV :
DATE:
INSTRUMENT LIST
SR
NO
INST TYPE
DESCRIPTION
FLUID
0GKB07CP101
PRESSURE
TRANSMITTER
WATER
0-6
KG/CM2
NA
NA
0GKB09CP101
PRESSURE
TRANSMITTER
WATER
0-10
KG/CM2
NA
NA
PREPARED BY:
REVIEWED BY:
APPROVED BY:
RANGE
UNIT
PARENT TAG NO
PROCESS PARAMETER
NORMAL
MAXIMUM
TEMP (Deg
C)
FLOW
(M3/hr)
DESIGN
PRESS
kg/cm2(g)
TEMP (Deg
C)
FLOW
(M3/hr)
PRESS
kg/cm2(g)
0GKB07BR001
3.85
32
5.5
3.5
27
40
SAFE
0GKB09BR001
32
25
27
20
40
30
SAFE
PAGE: 1 OF 1
TEMP (Deg
C)
FLOW
(M3/hr)
MAKE
MODEL
P&ID NO.
CERTIFICATION
PROCESS
CONNECTION
FLANGE
MATERIAL
FLANGE
RATING
(#)
REFER DS
Emerson
(Rosemount )
2051TG2A2B21KB4M5D4Q4
L570000-XG02-00-GCF-120001
CATALOGUE
NA
NA
REFER DS
Emerson
(Rosemount )
2051TG3A2B21KB4M5D4Q4
L570000-XG02-00-GCF-120001
CATALOGUE
NA
NA
AREA
ACCESSORIES
CLASSIFICATION
PRESS
kg/cm2(g)
REV.
REMARKS
NO
DOCUMENT NO.:
REV :
DATE:
INSTRUMENT LIST
INST TYPE
DESCRIPTION
FLUID
RANGE
UNIT
0GBD25CP101
GAUGE PRESSURE
TRANSMITTER
AIR
0-2
KG/CM2
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DIFF. PRESS
(METER
RANGE)
(mmWC)
NA
NA
PARENT TAG NO
0GBD25BR001
PRESS
kg/cm2(g)
MAXIMUM
TEMP (Deg
C)
FLOW
(M3/hr)
50
420
PROCESS PARAMETER
NORMAL
PRESS
TEMP (Deg
FLOW
kg/cm2(g)
C)
(M3/hr)
0.5
32
400
PRESS
kg/cm2(g)
DESIGN
TEMP (Deg
C)
FLOW
(M3/hr)
50
420
PAGE: 1 OF 1
AREA
CLASSIFICATI ACCESSORIES
ON
SAFE
REFER DS
MAKE
MODEL
P&ID NO.
CERTIFICATION
PROCESS CONNECTION
FLANGE
MATERIAL
FLANGE
RATING
(#)
Emerson
(Rosemount )
2051TG2A2B21KB4M5D4Q4
L570000-XG02-00-GBD-120001
CATALOGUE
NA
NA
REV.
REMARKS
NO
DOCUMENT NO.:
REV :
DATE:
INSTRUMENT LIST
INST TYPE
DESCRIPTION
FLUID
RANGE
UNIT
0GBD41CP101
GAUGE PRESSURE
TRANSMITTER
LIME
0-3
KG/CM2
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DIFF. PRESS
(METER
RANGE)
(mmWC)
NA
NA
PARENT TAG NO
0GBD41BR001
PROCESS PARAMETER
NORMAL
MAXIMUM
DESIGN
PRESS
kg/cm2(g)
TEMP (Deg
C)
FLOW
(M3/hr)
PRESS
kg/cm2(g)
TEMP (Deg
C)
FLOW
(M3/hr)
PRESS
kg/cm2(g)
TEMP (Deg
C)
FLOW
(M3/hr)
1.75
50
12
1.5
35
10
2.5
60
12
PAGE: 1 OF 1
AREA
CLASSIFICATION
ACCESSORIES
MAKE
MODEL
P&ID NO.
CERTIFICATION
PROCESS
CONNECTION
FLANGE
MATERIAL
FLANGE
RATING
(#)
SAFE
REFER DS
Emerson
(Rosemount )
2051TG2A2B21KB4M5D4Q4
L570000-XG02-00GBD-120002
CATALOGUE
CS
NA
REV.
REMARKS
NO
Date
Purpose
Reviewed
Inst.
Appd.
Mech.
5
7
9
11
13
15
17
GENERAL
Emerson (Rosemount)
Ref Annexure
2
4
Measurement Principle
Piezoresistive
6
8
10
12
14
16
18
Design Temp.
Max Operating Temp
Ref Annexure
Ref Annexure
Ref Annexure
Ref Annexure
Ref Annexure
19
Mounting
20
Safe Area
21
3" Flanged
22
Sensing Element
Diaphragm
23
Flange Material
N/A
24
SS 316
Flange Rating
N/A
26
Entry Position
Side
28
SS 316
2
Yes
Digital LCD Type
29
31
33
35
37
39
41
43
45
47
49
51
53
55
CONSTRUCTION
27
CHARACTERISTICS
25
PROCESS
Design Pressure
Max. Operating Pressure
Range
SS
30
Bodyy Rating
g
Over-Range Protection
Enclosure Protection
Transmitter Output
Power Supply
Accuracy
Repeatability
Transmitter Span
100 : 1
+/- 0.2% (FS)
600 Ohms(Max) at 24 V DC
100 msec
Diaphragm Seal
Diaphragm Seal Type
Yes
Remote
32
34
36
38
40
42
44
46
48
50
52
54
56
Manifold
Integral Manifold
N/A
No
58
Manifold Material
N/A
N/A
Yes
Neoprene
59
61
63
N/A
SS 316L
SS 316
60
62
64
Manifold Connection
O-Ring
O-Ring Material
Filling Fluid
Silicone Oil
66
Flushing Connection
Yes
68
65
67
69
ACCESSORIES
57
71
73
77
79
81
83
85
87
OPTIONS
75
Flushing Connection
Quantity
70
72
Name Plate
SS
74
Mounting Accessories
Yes
Certification
Transient Surge Protector
Capillary Type
Capillary length
5 Mtrs
No
Yes
76
78
80
82
84
86
88
DOCUMENT NO.:
REV :
DATE:
INSTRUMENT LIST
INST TYPE
DESCRIPTION
FLUID
RANGE
UNIT
0GCF76CP101
GAUGE PRESSURE
TRANSMITTER (DIA
SEAL)
INLET OF UF TRAIN A
WATER
0-6
KG/CM2
NA
NA
0GCF78CP101
GAUGE PRESSURE
TRANSMITTER (DIA
SEAL)
INLET OF UF TRAIN B
WATER
0-6
KG/CM2
NA
0GCF80CP101
GAUGE PRESSURE
TRANSMITTER (DIA
SEAL)
INLET OF UF TRAIN C
WATER
0-6
KG/CM2
NA
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DIFF. PRESS
(METER
RANGE)
(mmWC)
SR
NO
PARENT TAG NO
PROCESS PARAMETER
NORMAL
MAXIMUM
DESIGN
AREA
ACCESSORI
CLASSIFICATI
ES
ON
MAKE
MODEL
P&ID NO.
CERTIFICATION
PROCESS
CONNECTION
FLANGE
MATERIAL
FLANGE
RATING
(#)
REV.
NO
REFER DS
Emerson
(Rosemount)
2051TG2A2B21KS1B4M5D4Q4 +
1199WDB59AFFW71DAA3
L570000-XG02-00-GCF-120001
CATALOGUE
3" Flanged
SS316
150#
SAFE
REFER DS
Emerson
(Rosemount)
2051TG2A2B21KS1B4M5D4Q4 +
1199WDB59AFFW71DAA3
L570000-XG02-00-GCF-120001
CATALOGUE
3" Flanged
SS316
150#
SAFE
REFER DS
Emerson
(Rosemount)
2051TG2A2B21KS1B4M5D4Q4 +
1199WDB59AFFW71DAA3
L570000-XG02-00-GCF-120001
CATALOGUE
3" Flanged
SS316
150#
PRESS
kg/cm2(g)
TEMP (Deg
C)
FLOW
(M3/hr)
PRESS
kg/cm2(g)
TEMP (Deg
C)
FLOW
(M3/hr)
PRESS
kg/cm2(g)
TEMP (Deg
C)
FLOW
(M3/hr)
0GCF76BR001
3.9
32
130
3.5
27
125
4.2
40
135
SAFE
NA
0GCF78BR001
3.9
32
130
3.5
27
125
4.2
40
135
NA
0GCF80BR001
3.9
32
130
3.5
27
125
4.2
40
135
PAGE: 1 OF 1
REMARKS
DOCUMENT NO.:
REV :
DATE:
INSTRUMENT LIST
INST TYPE
0GBD13CP101
GAUGE PRESSURE
TRANSMITTER
PREPARED BY:
REVIEWED BY:
APPROVED BY:
DESCRIPTION
FLUID
RANGE
UNIT
0-10
KG/CM2
DIFF. PRESS
(METER
RANGE)
(mmWC)
NA
NA
PARENT TAG NO
0GBD13BR001
PRESS
kg/cm2(g)
MAXIMUM
TEMP (Deg
C)
FLOW
(M3/hr)
6.5
32
420
PROCESS PARAMETER
NORMAL
PRESS
TEMP (Deg
FLOW
kg/cm2(g)
C)
(M3/hr)
5
27
400
PRESS
kg/cm2(g)
DESIGN
TEMP (Deg
C)
FLOW
(M3/hr)
40
420
PAGE: 1 OF 1
AREA
CLASSIFICATI ACCESSORIES
ON
SAFE
REFER DS
MAKE
MODEL
P&ID NO.
CERTIFICATION
PROCESS CONNECTION
FLANGE
MATERIAL
FLANGE
RATING
(#)
Emerson
(Rosemount )
2051TG3A2B21KS1B4M5D4Q4 +
1199WDB59AFFW71DAA3
L570000-XG02-00-GBD-120001
CATALOGUE
NA
NA
REV.
REMARKS
NO
Rosemount 2051
Contents
Product Offering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Product Certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 12
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 18
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 26
www.rosemount.com
Rosemount 2051
Rosemount 2051
Product Offering
Rosemount 2051
Specifications
PERFORMANCE SPECIFICATIONS
For zero based spans, reference conditions, silicone oil fill, SST materials, Coplanar flange (2051C) or 1/2 in. - 14 NPT (2051T) process connections,
digital trim values set to equal range points.
Reference Accuracy(1)
Models(1)
Standard
Performance Option, P8
0.075% of span
For spans less than 10:1, accuracy =
Ranges 2-5
2051C
Ranges 2-5
URL
0.025 + 0.005 --------------- % of Span
Span
Range 1
0.10% of span
For spans less than 15:1, accuracy =
URL % of Span
0.025 + 0.005 ------------- Span-
2051T
Ranges 1-4
0.075% of span
For spans less than 10:1, accuracy =
Ranges 1-4
URL % of Span
0.0075 ------------- Span-
Range 5
2051L
Ranges 2-4
0.075% of span
For spans less than 10:1, accuracy =
URL
0.025 + 0.005 --------------- % of Span
Span
(1) For FOUNDATION fieldbus transmitters, use calibrated range in place of span.
Rosemount 2051
Standard
Performance Option, P8
(1)
2051C
2051CD
Range 1 0.2% of URL for 1 year
2051T(1)
Ranges 1-5 0.1% of URL for 2 years
(1) 50 F (28 C) temperature changes, and up to 1000 psi (6,9 MPa) line pressure.
Dynamic Performance
4 - 20 mA HART(1)
Total Response Time (Td + Tc)
2051C, Range 3-5:
Range 1:
Range 2:
2051T:
2051L:
Dead Time (Td)
Update Rate
Fieldbus(3)
(2)
:
115 milliseconds
270 milliseconds
130 milliseconds
100 milliseconds
See Instrument Toolkit
60 milliseconds (nominal)
22 times per second
152 milliseconds
307 milliseconds
152 milliseconds
152 milliseconds
See Instrument Toolkit
97 milliseconds
22 times per second
Tc
Td = Dead Time
Tc = Time Constant
Response Time = Td +Tc
63.2% of Total
Step Change
36.8%
(1) Dead time and update rate apply to all models and ranges; analog output only
(2) Nominal total response time at 75 F (24 C) reference conditions.
(3) Transmitter fieldbus output only, segment macro-cycle not included.
0%
Time
2051CD
Zero Error(1)
0.1% of URL/1000 psi (68,9 bar) for line pressures from 0 to 2000 psi (0 to 13,7 MPa)
0.5% of URL/1000 psi (68,9 bar)
Span Error
0.1% of reading/1000 psi (68,9 bar)
0.4% of reading/1000 psi (68,9 bar)
Ranges 2-3
Range 1
Ranges 2-3
Range 1
Rosemount 2051
00813-0100-4101, Rev AA
March 2008
2051C
Ranges 2-5 (0.025% URL + 0.125% span) from 1:1 to 5:1
(0.05% URL + 0.25% span) from 5:1 to 100:1
Range 1 (0.2% URL + 0.5% span) from 1:1 to 50:1
2051T
2051L
2051C
2051T
2051L
Zero shifts up to 1.25 inH2O (3,11 mbar), which can be calibrated out. No span effect.
Zero shifts up to 2.5 inH2O (6,22 mbar), which can be calibrated out. No span effect.
With liquid level diaphragm in vertical plane, zero shift of up to 1 inH2O (2,49 mbar). With diaphragm in
horizontal plane, zero shift of up to 5 inH2O (12,43 mbar) plus extension length on extended units. Zero
shifts can be calibrated out. No span effect.
Vibration Effect
Less than 0.1% of URL when tested per the requirements of
IEC60770-1 field or pipeline with high vibration level (10-60 Hz
0.21mm displacement peak amplitude / 60-2000 Hz 3g).
Rosemount 2051
FUNCTIONAL SPECIFICATIONS
Range and Sensor Limits
Range
1
2
3
4
5
Upper (URL)
2051C Differential
2051C Gage
2051L Differential
2051L Gage
0.5 inH2O
(1,2 mbar)
2.5 inH2O
(6,2 mbar)
10 inH2O
(24,9 mbar)
3 psi
(0,207 bar)
20 psi
(1,38 bar)
25 inH2O
(62,3 mbar)
250 inH2O
(0,62 bar)
1000 inH2O
(2,49 bar)
300 psi
(20,6 bar)
2000 psi
(137,9 bar)
25 inH2O
(62,1 mbar)
250 inH2O
(0,62 bar)
1000 inH2O
(2,49 bar)
300 psi
(20,6 bar)
2000 psi
(137,9 bar)
25 inH2O
(62,1 mbar)
250 inH2O
(0,62 bar)
0.5 psia
(34,5 mbar abs)
0.5 psia
(34,5 mbar abs)
0.5 psia
(34,5 mbar abs)
N/A
N/A
250 inH2O
(0,62 bar)
1000 inH2O
(2,49 bar)
300 psi
(20,7 bar)
N/A
250 inH2O
(0,62 bar)
0.5 psia
(34,5 mbar abs)
0.5 psia
(34,5 mbar abs)
N/A
Range
2051T
1
2
3
4
5
Upper
(URL)
Lower
(LRL) (Abs)
Lower(1)
(LRL) (Gage)
0.3 psi
(20,6 mbar)
1.5 psi
(0,103 bar)
8 psi
(0,55 bar)
40 psi
(2,76 bar)
2000 psi
(137,9 bar)
30 psi
(2,06 bar)
150 psi
(10,3 bar)
800 psi
(55,2 bar)
4000 psi
(275,8 bar)
10000 psi
(689,4 bar)
0 psia
(0 bar)
0 psia
(0 bar)
0 psia
(0 bar)
0 psia
(0 bar)
0 psia
(0 bar)
14.7 psig
(1,01 bar)
14.7 psig
(1,01 bar)
14.7 psig
(1,01 bar)
14.7 psig
(1,01 bar)
14.7 psig
(1,01 bar)
Rosemount 2051
Service
Protocols
Transducer Block
Output
Two-wire 420 mA, user-selectable for linear or square root
output. Digital process variable superimposed on 420 mA
signal, available to any host that conforms to the HART
protocol.
Power Supply
LCD Block
Configures the local display.
2 Analog Input Blocks
Processes the measurements for input into other function
blocks. The output value is in engineering units or custom
and contains a status indicating measurement quality.
PID Block
Load Limitations
Load (Ohms)
1387
1000
Output
500
Operating
Region
0
10.5
20
30
Voltage (V dc)
42.4
Power Supply
External power supply required. Standard transmitter operates
on 9 to 28 Vdc with no load.
Power Consumption
3.0 mA, 2784 mW
Power Supply
External power supply required; transmitters operate on 9.0 to
32.0 V dc transmitter terminal voltage.
Current Draw
17.5 mA for all configurations (including LCD display option)
FOUNDATION fieldbus Function Block Execution Times
Block
Execution Time
Resource
Transducer
LCD Block
Analog Input 1, 2
PID
100 k or greater
Overpressure Limits
Transmitters withstand the following limits without damage:
2051C
Ranges 25: 3626 psig (250 bar)
4500 psig (310,3 bar) for option code P9
30 milliseconds
45 milliseconds
Output Load
2051T
Range 1: 750 psi (51,7 bar)
Range 2: 1500 psi (103,4 bar)
7 (max.)
20 (max.)
12 (max.)
Rosemount 2051
2051L
Type
2051C
CS Rating SST Rating
ANSI/ASME
Class 150
285 psig
275 psig
ANSI/ASME
Class 300
740 psig
720 psig
At 100 F (38 C), the rating decreases with
increasing temperature.
DIN
PN 1040
40 bar
40 bar
DIN
PN 10/16
16 bar
16 bar
At 248 F (120 C), the rating decreases
with increasing temperature.
Range 1: 0.5 psia to 2000 psig (34 mbar and 137,9 bar)
2051T
Temperature Limits
Ambient
40 to 185 F (40 to 85 C)
With LCD display(1): 40 to 175 F (20 to 80 C)
Storage
50 to 230 F (46 to 110 C)
With LCD display: 40 to 185 F (40 to 85 C)
(1) LCD display may not be readable and LCD updates will be slower
at temperatures below -4 F (-20 C).
Humidity Limits
0100% relative humidity
Turn-On Time
Performance within specifications less than 2.0 seconds after
power is applied to the transmitter
Volumetric Displacement
Less than 0.005 in3 (0,08 cm3)
Damping
Analog output response to a step input change is user-selectable
from 0 to 25.6 seconds for one time constant. This software
damping is in addition to sensor module response time.
Rosemount 2051
Failure Mode Alarm
Drain/Vent Valves
Output Code
Linear Output
3.9 I 20.8
0.97 V 5.2
S
M
Fail High
Fail Low
I 21.75 mA
V 5.4 V
I 3.75 mA
V 0.95V
Wetted O-rings
Glass-filled PTFE or Graphite-filled PTFE
Linear Output
3.8 I 20.5
Fail Low
I 22.5 mA
I 3.6 mA
Output Code F
If self-diagnostics detect a gross transmitter failure, that
information gets passed as a status along with the process
variable.
PHYSICAL SPECIFICATIONS
Electrical Connections
1/214
Process Connections
2051C
Extension
Mounting Flange
2051T
1
2051L
High pressure side: 2-in.(50.8mm), 3-in. (72 mm), or 4-in.
(102mm), ASME B 16.5 (ANSI) Class 150 or 300 flange;
50, 80 or 100 mm, DIN 2501 PN 40 or 10/16 flange
Low pressure side: 1/418 NPT on flange, 1/214 NPT on
process adapter
10
Rosemount 2051
Shipping Weights
TABLE 3. Transmitter Weights without Options
Transmitter
lb. (kg)
2051C
2051L
2051T
6.0 (2,7)
Table 4 below
3.0 (1,4)
Bolts
ASTM A449, Type 1 (zinc-cobalt plated carbon steel)
ASTM F593G, Condition CW1 (Austenitic 316 SST)
ASTM A193, Grade B7M (zinc plated alloy steel)
Paint
Polyurethane
Flange
2-in., 150
3-in., 150
4-in., 150
2-in., 300
3-in., 300
4-in., 300
DN 50/PN 40
DN 80/PN 40
DN 100/
PN 10/16
DN 100/
PN 40
2-in. Ext.
lb (kg)
4-in. Ext.
lb (kg)
6-in. Ext.
lb (kg)
12.5 (5,7)
17.5 (7,9)
19.5 (8,8)
20.5 (9,3)
23.5 (10,7) 26.5 (12,0) 28.5 (12,9)
17.5 (7,9)
19.5 (8,8)
21.5 (9,7) 22.5 (10,2)
17.8 (8,1)
19.8 (9,0)
20.8 (9,5)
21.5 (9,7)
30.5 (13,8)
26.5 (12,0)
39.5 (17,9)
23.5 (10,6)
21.8 (9,9)
23.2 (10,5)
27.2 (12,3)
25.2 (11,5)
26.2 (11,9)
Cover O-rings
Buna-N
Option
Stainless Steel Housing
LCD display for Aluminum Housing
SST Mounting Bracket for Coplanar Flange
Mounting Bracket for Traditional Flange
Mounting Bracket for Traditional Flange
SST Bracket for Traditional Flange
Traditional Flange
Traditional Flange
Traditional Flange
Traditional Flange
Level Flange3 in., 150
Level Flange3 in., 300
Level Flange2 in., 150
Level Flange2 in., 300
DIN Level Flange, SST, DN 50, PN 40
DIN Level Flange, SST, DN 80, PN 40
Add
lb (kg)
3.9 (1,8)
0.5 (0,2)
1.0 (0,5)
2.3 (1,0)
2.3 (1,0)
2.3 (1,0)
2.4 (1,1)
2.7 (1,2)
2.6 (1,2)
2.5 (1,1)
10.8 (4,9)
14.3 (6,5)
10.7 (4,8)
14.0 (6,3)
8.3 (3,8)
13.7 (6,2)
11