Вы находитесь на странице: 1из 28

EndorsementSheet

2 700 MW RAJPURA THERMAL POWER PROJECT, PUNJAB


OWNER:

NABHA POWER LIMITED


OWNERS CONSULTANT:

TATA CONSULTING ENGINEERS LIMITED


EPC CONTRACTOR:

L & T LIMITED
EPCS CONSULTANT:

L&T-SARGENT & LUNDY LIMITED

ION EXCHANGE INDIA LTD


L&T-S&L JOB NO.: L570000

Title:DATASHEET OF PRESSURE TRANSMITTER

DocumentNo:L570000-YT01-00-GNB-150010
Package:ETP

ThisDocumentisApprovedforDMPlant.
Therefore,thesamemaybeApprovedforETP.

L&T LTD JOB NO. : C31001

INSTRUMENT LIST OF EFFLUENT TREATMENT PLANT


SR
1

INST KKS TAG


0GND05CP101

INST TYPE

DESCRIPTION

FLUID

CALIBRATION

UNIT

PRESSURE TRANSMITTER

COMMON DISCHARGE OF OILY WASTE TRANSFER


PUMPS P2 A/B/C

OILY WASTE

0-4

KG/CM2 (g)

MAX DIFF.

PARENT TAG
0GND05BR001

PROCESS PARAMETER
3

45

240

25

200

60

300

AREA

ACCESSORIES

MAKE

MODEL

P&ID NO.

CERTIFICATION

PROCESS

FLANGE

FLANGE

REV.

REMARKS

SAFE

FLANGE +
CAPILLARY

REFER DS

REFER DS

L570000-XG02-00-GNB-120001
REV C

REFER DS

FLANGED

CSRL

150

DIA SEAL

0GND20CP101

PRESSURE TRANSMITTER

COMMON DISCHARGE OF SLUDGE TRANSFER


PUMPS P24 A/B

SLUDGE

0-4

KG/CM2 (g)

0GND20BR003

3.1

45

100

2.5

25

75

60

120

SAFE

FLANGE +
CAPILLARY

REFER DS

REFER DS

L570000-XG02-00-GNB-120001
REV C

REFER DS

FLANGED

CSRL

150

DIA SEAL

0GND36CP101

PRESSURE TRANSMITTER

COMMON DISCHARGE OF EFFLUENT TRANSFER


PUMPS P1 A/B/C/D

EFFLUENT

0-4

KG/CM2 (g)

0GND36BR001

2.4

45

950

25

860

60

1150

SAFE

FLANGE +
CAPILLARY

REFER DS

REFER DS

L570000-XG02-00-GNB-120001
REV C

REFER DS

FLANGED

CSRL

150

DIA SEAL

0GND16CP101

PRESSURE TRANSMITTER

COMMON DISCHARGE OF OVERFLOW WATER


TRANSFER PUMP P3 A/B

WATER

0-4

KG/CM2 (g)

0GND16BR101

3.3

45

220

25

200

60

250

SAFE

FLANGE +
CAPILLARY

REFER DS

REFER DS

L570000-XG02-00-GNB-120001
REV C

REFER DS

FLANGED

CSRL

150

DIA SEAL

AIR

0-2

KG/CM2 (g)

0GND25BR003

1.4

45

1650

0.4

25

1630

60

1700

SAFE

2 VALVE MANIFOLD

REFER DS

REFER DS

L570000-XG02-00-GNB-120001
REV C

REFER DS

1/2" NPT (F)

NA

NA

GAUGE PR

AIR

0-2

KG/CM2 (g)

0GND21BR003

1.4

45

130

0.4

25

115

60

150

SAFE

2 VALVE MANIFOLD

REFER DS

REFER DS

L570000-XG02-00-GNB-120001
REV C

REFER DS

1/2" NPT (F)

NA

NA

GAUGE PR

0GND25CP101

PRESSURE TRANSMITTER

COMMON DISCHARGE OF AIR BLOWERS B1 A/B FOR


COWRP

0GND21CP101

PRESSURE TRANSMITTER

COMMON DISCHARGE OF AIR BLOWERS B2 A/B FOR


SLUDGE SUMP

INSTRUMENT LIST OF EFFLUENT TREATMENT PLANT


SR

INST KKS TAG

INST TYPE

DESCRIPTION

FLUID

CALIBRATION

UNIT

AREA

ACCESSORIES

MAKE

MODEL

P&ID NO.

CERTIFICATION

PROCESS

FLANGE

FLANGE

REV.

REMARKS

0GND56CP101

PRESSURE TRANSMITTER

COMMON DISCHARGE OF RO PLANT FEED PUMPS P4


A/B/C/D

WATER

0-8

KG/CM2 (g)

MAX DIFF.

0GND56BR001

PARENT TAG
5.7

45

900

PROCESS PARAMETER
5

25

800

60

1050

SAFE

2 VALVE MANIFOLD

REFER DS

REFER DS

L570000-XG02-00-GNB-120001
REV C

REFER DS

1/2" NPT (F)

NA

NA

GAUGE PR

0GND62CP101

PRESSURE TRANSMITTER

COMMON DISCHARGE OF CHP DUST SUPRESSION


PUMPS P5 A/B

WATER

0-4

KG/CM2 (g)

0GND62BR001

2.3

45

170

25

150

60

200

SAFE

2 VALVE MANIFOLD

REFER DS

REFER DS

L570000-XG02-00-GNB-120001
REV C

REFER DS

1/2" NPT (F)

NA

NA

GAUGE PR

2 700 MW RAJPURA THERMAL POWER PROJECT, PUNJAB


OWNER:

NABHA POWER LIMITED


OWNERS CONSULTANT:

TATA CONSULTING ENGINEERS LIMITED


EPC CONTRACTOR:

L & T LIMITED
EPCS CONSULTANT:

L&T-SARGENT & LUNDY LIMITED


ION EXCHANGE INDIA LTD
L&T-S&L JOB NO.: L570000

L&T LTD JOB NO. : C31001

DATASHEET&GAFORPRESSURETRANSMITTER

DOC/DRG NO. :

150035

L570000YT0100GCF

TOTAL NO. OF PAGES : 022


TOTAL NO. OF ANNEXURES : 00

REV: C

L&T-SARGENT & LUNDY LIMITED


ACTION
X Action A

DATE

31-05-2013

APPROVED

Action B

APPROVED SUBJECT TO INCORPORATION OF COMMENTS

Action C

COMMENTED, RESUBMISSION REQUIRED

Action D

DISAPPROVED

Action E

FOR INFORMATION / REFERENCE ONLY

E-MAIL REF.

Through t-bits

SIGNATURE

AKA/ARU

Drawing/Document reviewed only for general compliance with specifications. Action shown above is
subject to the terms and conditions of contract and does not relieve the Contractor from his obligations
under the contract including design and detailing.

REVISION RECORDS

C
Rev
No

20/03/2013

THIRD SUBMISSION

PSV

PC

AKO

DATE

REVISION SUMMERY

PREPARED

REVIEWED

APPROVED

NABHA POWER LIMITED


2 700 MW RAJPURA THERMAL POWER PROJECT, PUNJAB
Rev.

Purpose

Date

Proj. No. L570000

Spec. No. L570000-DC01-00-QH-310001

Page: x of y Data sht. No:


Prep.

Reviewed
Inst.

Appd.

Mech.

PRESSURE TRANSMITTER
Tag No.:Ref Annexure

P&ID No.: L570000-XG02-00-GCF-120001

5
7
9
11
13
15
17

GENERAL

Fluid : Ref Annexure


Manufacturer
1
Model No.
3
Serial No.

Service: Water Treatment package

Emerson (Rosemount)
Ref Annexure

2
4

Measurement Principle

Piezoresistive

Emerson will provide after


manufacturing

6
8
10
12
14
16
18

Design Temp.
Max Operating Temp

Ref Annexure
Ref Annexure

Ref Annexure
Ref Annexure
Ref Annexure

19

Mounting

2 " Pipe Mounted

20

Hazardous Area Classification

Safe Area

21

Process Connection & Size

1/2" NPT (F)

22

Sensing Element

Diaphragm

23

Flange Material

N/A

24

Sensing Element material

SS 316

Flange Rating

N/A

26

Sensor Over range Protection

2051TG2 : 103 bar


2051TG3 : 110 bar

Entry Position

Side

28

Wetted part material

SS 316

Cable Entry connection with


Cable gland / Conduit
Connector

M20 1.5 (CM20) conduit.

Number of Cable Entryy


Digital Indicator
Indicator Type

2
Yes
Digital LCD Type

Turn Down Ratio


Stability Over 6 Months
Load Resistance
Response Time

100 : 1
+/- 0.2% (FS)
600 Ohms(Max) at 24 V DC
100 msec

Manifold
Integral Manifold

2 Valve Integral Manifold


Yes

27

CONSTRUCTION

25

PROCESS

Design Pressure
Max. Operating Pressure
Range

SS

30

Bodyy Rating
g
Over-Range Protection
Enclosure Protection

150% of Max. Pressure


125% of Max Pressure
IP 67

Transmitter Output
Power Supply
Accuracy
Repeatability
Transmitter Span

4-20 mA (2-wire) with HART


12-48 V DC
+/- 0.1% of Span
+/- 0.1% of Span
2051TG2: 0-10.5 kg/cm2
2051TG3: 0-55 kg/cm2

Diaphragm Seal
Diaphragm Seal Type

No
N/A

32
34
36
38
40
42
44
46
48
50
52
54
56

57

Diaphragm Seal Connection N/A

58

Manifold Material

SS 316

59
61
63

Lower Housing material


Diaphragm material
Upper Housing material

SS 316
SS 316L
SS 316

60
62
64

Manifold Connection
O-Ring
O-Ring Material

1/2" NPT(F)
Yes
Neoprene

Filling Fluid

Silicone Oil

66

Cable Gland/Conduit Connector Yes

Flushing Connection

Yes

68

Cable Gland Type

Single Compression type

Conduit connector / Cable


Gland Material

Nickel-Plated brass with Sleeves

65
67
69

ACCESSORIES

31
33
35
37
39
41
43
45
47
49
51
53
55

CHARACTERISTICS

Housing (Body Material)

29

71
73
77
79
81
83
85
87

OPTIONS

75

Flushing Connection
Quantity

70

Flushing Connection Size

1/4 inch NPT(F)

72

Name Plate

SS

74

Mounting Accessories

Yes

Certification
Transient Surge Protector

Refer Instrument List


No

Capillary Type

N/A

Capillary length

N/A

Hand held Calibrator


Self Diagnostic Feature

No
Yes

76
78
80
82
84
86
88

L&T-SARGENT & LUNDY LTD.

DOCUMENT NO.:
REV :
DATE:

INSTRUMENT LIST

INSTRUMENT LIST OF DM PLANT


SR
NO

INST TAG NUMBER

INST TYPE

DESCRIPTION

FLUID

RANGE

UNIT

DIFF. PRESS
(METER
RANGE)
(mmWC)

PARENT TAG NO

PROCESS PARAMETER
NORMAL

MAXIMUM
PRESS
kg/cm2(g)

TEMP (Deg
C)

FLOW
(M3/hr)

PRESS
kg/cm2(g)

TEMP (Deg
C)

FLOW
(M3/hr)

DESIGN
PRESS
kg/cm2(g)

TEMP (Deg
C)

FLOW
(M3/hr)

AREA
ACCESSORI
CLASSIFICATI
ES
ON

MAKE

MODEL

P&ID NO.

CERTIFICATION

PROCESS
CONNECTION

FLANGE
MATERIAL

FLANGE
RATING
(#)

REV.
NO

0GCF12CP101

GAUGE PRESSURE
TRANSMITTER

COMMON DISCHARGE OF DG WATER TRANSFER


PUMP P1 A/B/C/D

WATER

0-8

KG/CM2

NA

NA

0GCF12BR001

4.4

32

400

27

393

40

410

SAFE

REFER DS

Emerson
(Rosemount)

2051TG2A2B21KB4M5D4Q4

L570000-XG02-00-GCF-120001

CATALOGUE

1/2" NPT (F)

NA

NA

0GCF42CP105

GAUGE PRESSURE
TRANSMITTER

COMMON DISCHARGE OF UF FEED PUMPS P2


A/B/C/D

WATER

0-6

KG/CM2

NA

NA

0GCF42BR002

3.9

32

385

3.5

27

375

4.2

40

400

SAFE

REFER DS

Emerson
(Rosemount)

2051TG2A2B21KB4M5D4Q4

L570000-XG02-00-GCF-120001

CATALOGUE

1/2" NPT (F)

NA

NA

0GCF38CP105

GAUGE PRESSURE
TRANSMITTER

COMMON DISCHARGE OF DM REGENERATION


PUMPS P3 A/B

WATER

0-6

KG/CM2

NA

NA

0GCF38BR001

3.9

32

45

3.5

27

40

4.2

40

50

SAFE

REFER DS

Emerson
(Rosemount)

2051TG2A2B21KB4M5D4Q4

L570000-XG02-00-GCF-120001

CATALOGUE

1/2" NPT (F)

NA

NA

0CGP60CP101

GAUGE PRESSURE
TRANSMITTER

COMMON DISCHARGE OF NEUTRALISED EFFLUENT


DISPOSAL PUMPS P6 A/B

WATER

0-3

KG/CM2

NA

NA

0GCF60BR0010

2.1

32

160

1.5

27

150

2.5

40

165

SAFE

REFER DS

Emerson
(Rosemount)

2051TG2A2B21KB4M5D4Q4

L570000-XG02-00-GCF-120001

CATALOGUE

1/2" NPT (F)

NA

NA

0GCF33CP108

GAUGE PRESSURE
TRANSMITTER

ON INSTRUMENT AIR HEADER

AIR

0-12

KG/CM2

NA

NA

0GCF33BR001

50

30

32

25

10

60

30

SAFE

REFER DS

Emerson
(Rosemount)

2051TG3A2B21KB4M5D4Q4

L570000-XG02-00-GCF-120001

CATALOGUE

1/2" NPT (F)

NA

NA

0GCF92CP101

GAUGE PRESSURE
TRANSMITTER

COMMON DISCHARGE OF UF BACKFLUSH


PUMPS P4 A/B

WATER

0-6

KG/CM2

NA

NA

0GCF92BR001

32

210

2.5

27

200

3.5

40

215

SAFE

REFER DS

Emerson
(Rosemount)

2051TG2A2B21KB4M5D4Q4

L570000-XG02-00-GCF-120001

CATALOGUE

1/2" NPT (F)

NA

NA

PREPARED BY:
REVIEWED BY:
APPROVED BY:

PAGE: 1 OF 1

REMARKS

L&T-SARGENT & LUNDY LTD.

DOCUMENT NO.:
REV :
DATE:

INSTRUMENT LIST

INSTRUMENT LIST OF POTABLE DMF PLANT


DIFF. PRESS
(METER
RANGE)
(mmWC)

SR
NO

INST TAG NUMBER

INST TYPE

DESCRIPTION

FLUID

0GKB07CP101

PRESSURE
TRANSMITTER

COMMON DISCHARGE OF POTABLE WATER PUMPS


FOR DM PLANT P7 A/B

WATER

0-6

KG/CM2

NA

NA

0GKB09CP101

PRESSURE
TRANSMITTER

COMMON DISCHARGE OF POTABLE WATER PUMPS


FOR COLONY P8 C/D

WATER

0-10

KG/CM2

NA

NA

PREPARED BY:
REVIEWED BY:
APPROVED BY:

RANGE

UNIT

PARENT TAG NO

PROCESS PARAMETER
NORMAL

MAXIMUM

TEMP (Deg
C)

FLOW
(M3/hr)

DESIGN
PRESS
kg/cm2(g)

TEMP (Deg
C)

FLOW
(M3/hr)

PRESS
kg/cm2(g)

0GKB07BR001

3.85

32

5.5

3.5

27

40

SAFE

0GKB09BR001

32

25

27

20

40

30

SAFE

PAGE: 1 OF 1

TEMP (Deg
C)

FLOW
(M3/hr)

MAKE

MODEL

P&ID NO.

CERTIFICATION

PROCESS
CONNECTION

FLANGE
MATERIAL

FLANGE
RATING
(#)

REFER DS

Emerson
(Rosemount )

2051TG2A2B21KB4M5D4Q4

L570000-XG02-00-GCF-120001

CATALOGUE

1/2" NPT (F)

NA

NA

REFER DS

Emerson
(Rosemount )

2051TG3A2B21KB4M5D4Q4

L570000-XG02-00-GCF-120001

CATALOGUE

1/2" NPT (F)

NA

NA

AREA
ACCESSORIES
CLASSIFICATION

PRESS
kg/cm2(g)

REV.
REMARKS
NO

L&T-SARGENT & LUNDY LTD.

DOCUMENT NO.:
REV :
DATE:

INSTRUMENT LIST

INSTRUMENT LIST OF PRETREATMENT PLANT


SR
NO

INST TAG NUMBER

INST TYPE

DESCRIPTION

FLUID

RANGE

UNIT

0GBD25CP101

GAUGE PRESSURE
TRANSMITTER

AT COMMON DISCHARGE OF SLUDGE SUMP AIR


BLOWERS B1 A/B

AIR

0-2

KG/CM2

PREPARED BY:
REVIEWED BY:
APPROVED BY:

DIFF. PRESS
(METER
RANGE)
(mmWC)
NA

NA

PARENT TAG NO

0GBD25BR001

PRESS
kg/cm2(g)

MAXIMUM
TEMP (Deg
C)

FLOW
(M3/hr)

50

420

PROCESS PARAMETER
NORMAL
PRESS
TEMP (Deg
FLOW
kg/cm2(g)
C)
(M3/hr)
0.5

32

400

PRESS
kg/cm2(g)

DESIGN
TEMP (Deg
C)

FLOW
(M3/hr)

50

420

PAGE: 1 OF 1

AREA
CLASSIFICATI ACCESSORIES
ON
SAFE

REFER DS

MAKE

MODEL

P&ID NO.

CERTIFICATION

PROCESS CONNECTION

FLANGE
MATERIAL

FLANGE
RATING
(#)

Emerson
(Rosemount )

2051TG2A2B21KB4M5D4Q4

L570000-XG02-00-GBD-120001

CATALOGUE

1/2" NPT (F)

NA

NA

REV.
REMARKS
NO

L&T-SARGENT & LUNDY LTD.

DOCUMENT NO.:
REV :
DATE:

INSTRUMENT LIST

INSTRUMENT LIST OF PRETREATMENT DOSING PLANT


SR
NO

INST TAG NUMBER

INST TYPE

DESCRIPTION

FLUID

RANGE

UNIT

0GBD41CP101

GAUGE PRESSURE
TRANSMITTER

COMMON DISCHARGE OF LIME RECIRCULATION CUM


DOSING PUMPS DP2 A/B

LIME

0-3

KG/CM2

PREPARED BY:
REVIEWED BY:
APPROVED BY:

DIFF. PRESS
(METER
RANGE)
(mmWC)
NA

NA

PARENT TAG NO

0GBD41BR001

PROCESS PARAMETER
NORMAL

MAXIMUM

DESIGN

PRESS
kg/cm2(g)

TEMP (Deg
C)

FLOW
(M3/hr)

PRESS
kg/cm2(g)

TEMP (Deg
C)

FLOW
(M3/hr)

PRESS
kg/cm2(g)

TEMP (Deg
C)

FLOW
(M3/hr)

1.75

50

12

1.5

35

10

2.5

60

12

PAGE: 1 OF 1

AREA
CLASSIFICATION

ACCESSORIES

MAKE

MODEL

P&ID NO.

CERTIFICATION

PROCESS
CONNECTION

FLANGE
MATERIAL

FLANGE
RATING
(#)

SAFE

REFER DS

Emerson
(Rosemount )

2051TG2A2B21KB4M5D4Q4

L570000-XG02-00GBD-120002

CATALOGUE

1/2" NPT (F)

CS

NA

REV.
REMARKS
NO

NABHA POWER LIMITED


2 700 MW RAJPURA THERMAL POWER PROJECT, PUNJAB
Rev.

Date

Purpose

Proj. No. L570000

Spec. No. L570000-DC01-00-QH-310001

Page: x of y Data sht. No:


Prep.

Reviewed
Inst.

Appd.

Mech.

PRESSURE TRANSMITTER- DIAPHRAGM SEAL


Tag No.:Ref Annexure

P&ID No.: L570000-XG02-00-GCF-120001

5
7
9
11
13
15
17

GENERAL

Fluid : Ref Annexure


Manufacturer
1
Model No.
3
Serial No.

Service: Water Treatment package

Emerson (Rosemount)
Ref Annexure

2
4

Measurement Principle

Piezoresistive

Emerson will provide after


manufacturing

6
8
10
12
14
16
18

Design Temp.
Max Operating Temp

Ref Annexure
Ref Annexure

Ref Annexure
Ref Annexure
Ref Annexure

19

Mounting

2 " Pipe Mounted

20

Hazardous Area Classification

Safe Area

21

Process Connection & Size

3" Flanged

22

Sensing Element

Diaphragm

23

Flange Material

N/A

24

Sensing Element material

SS 316

Flange Rating

N/A

26

Sensor Over range Protection

2051TG2 : 103 bar


2051TG3 : 110 bar

Entry Position

Side

28

Wetted part material

SS 316

Cable Entry connection with


Cable gland / Conduit
Connector

M20 1.5 (CM20) conduit.

Number of Cable Entryy


Digital Indicator
Indicator Type

2
Yes
Digital LCD Type

29
31
33
35
37
39
41
43
45
47
49
51
53
55

CONSTRUCTION

27

CHARACTERISTICS

25

PROCESS

Design Pressure
Max. Operating Pressure
Range

Housing (Body Material)

SS

30

Bodyy Rating
g
Over-Range Protection
Enclosure Protection

150% of Max. Pressure


125% of Max Pressure
IP 67

Transmitter Output
Power Supply
Accuracy
Repeatability
Transmitter Span

4-20 mA (2-wire) with HART


12-48 V DC
+/- 0.1% of Span
+/- 0.1% of Span
2051TG2: 0-10.5 kg/cm2
2051TG3: 0-55 kg/cm2

Turn Down Ratio


Stability Over 6 Months
Load Resistance
Response Time

100 : 1
+/- 0.2% (FS)
600 Ohms(Max) at 24 V DC
100 msec

Diaphragm Seal
Diaphragm Seal Type

Yes
Remote

32
34
36
38
40
42
44
46
48
50
52
54
56

Manifold
Integral Manifold

N/A
No

58

Manifold Material

N/A
N/A
Yes
Neoprene

Diaphragm Seal Connection Flanged: 3"

59
61
63

Lower Housing material


Diaphragm material
Upper Housing material

N/A
SS 316L
SS 316

60
62
64

Manifold Connection
O-Ring
O-Ring Material

Filling Fluid

Silicone Oil

66

Cable Gland/Conduit Connector Yes

Flushing Connection

Yes

68

Cable Gland Type

Single Compression type


Nickel-Plated brass with Sleeves

65
67
69

ACCESSORIES

57

71
73
77
79
81
83
85
87

OPTIONS

75

Flushing Connection
Quantity

70

Conduit connector / Cable


Gland Material

Flushing Connection Size

1/4 inch NPT(F)

72

Name Plate

SS

74

Mounting Accessories

Yes

Certification
Transient Surge Protector

Refer Instrument List


No

Capillary Type

316 SST Armoured Sleeving

Capillary length

5 Mtrs

Hand held Calibrator


Self Diagnostic Feature

No
Yes

76
78
80
82
84
86
88

L&T-SARGENT & LUNDY LTD.

DOCUMENT NO.:
REV :
DATE:

INSTRUMENT LIST

INSTRUMENT LIST OF DM PLANT


INST TAG NUMBER

INST TYPE

DESCRIPTION

FLUID

RANGE

UNIT

0GCF76CP101

GAUGE PRESSURE
TRANSMITTER (DIA
SEAL)

INLET OF UF TRAIN A

WATER

0-6

KG/CM2

NA

NA

0GCF78CP101

GAUGE PRESSURE
TRANSMITTER (DIA
SEAL)

INLET OF UF TRAIN B

WATER

0-6

KG/CM2

NA

0GCF80CP101

GAUGE PRESSURE
TRANSMITTER (DIA
SEAL)

INLET OF UF TRAIN C

WATER

0-6

KG/CM2

NA

PREPARED BY:
REVIEWED BY:
APPROVED BY:

DIFF. PRESS
(METER
RANGE)
(mmWC)

SR
NO

PARENT TAG NO

PROCESS PARAMETER
NORMAL

MAXIMUM

DESIGN

AREA
ACCESSORI
CLASSIFICATI
ES
ON

MAKE

MODEL

P&ID NO.

CERTIFICATION

PROCESS
CONNECTION

FLANGE
MATERIAL

FLANGE
RATING
(#)

REV.
NO

REFER DS

Emerson
(Rosemount)

2051TG2A2B21KS1B4M5D4Q4 +
1199WDB59AFFW71DAA3

L570000-XG02-00-GCF-120001

CATALOGUE

3" Flanged

SS316

150#

SAFE

REFER DS

Emerson
(Rosemount)

2051TG2A2B21KS1B4M5D4Q4 +
1199WDB59AFFW71DAA3

L570000-XG02-00-GCF-120001

CATALOGUE

3" Flanged

SS316

150#

SAFE

REFER DS

Emerson
(Rosemount)

2051TG2A2B21KS1B4M5D4Q4 +
1199WDB59AFFW71DAA3

L570000-XG02-00-GCF-120001

CATALOGUE

3" Flanged

SS316

150#

PRESS
kg/cm2(g)

TEMP (Deg
C)

FLOW
(M3/hr)

PRESS
kg/cm2(g)

TEMP (Deg
C)

FLOW
(M3/hr)

PRESS
kg/cm2(g)

TEMP (Deg
C)

FLOW
(M3/hr)

0GCF76BR001

3.9

32

130

3.5

27

125

4.2

40

135

SAFE

NA

0GCF78BR001

3.9

32

130

3.5

27

125

4.2

40

135

NA

0GCF80BR001

3.9

32

130

3.5

27

125

4.2

40

135

PAGE: 1 OF 1

REMARKS

L&T-SARGENT & LUNDY LTD.

DOCUMENT NO.:
REV :
DATE:

INSTRUMENT LIST

INSTRUMENT LIST OF PRETREATMENT PLANT


SR
NO

INST TAG NUMBER

INST TYPE

0GBD13CP101

GAUGE PRESSURE
TRANSMITTER

PREPARED BY:
REVIEWED BY:
APPROVED BY:

DESCRIPTION

FLUID

COMMON DISCHARGE OF SLUDGE TRANSFER PUMPS


SLUDGE
P1 A/B

RANGE

UNIT

0-10

KG/CM2

DIFF. PRESS
(METER
RANGE)
(mmWC)
NA

NA

PARENT TAG NO

0GBD13BR001

PRESS
kg/cm2(g)

MAXIMUM
TEMP (Deg
C)

FLOW
(M3/hr)

6.5

32

420

PROCESS PARAMETER
NORMAL
PRESS
TEMP (Deg
FLOW
kg/cm2(g)
C)
(M3/hr)
5

27

400

PRESS
kg/cm2(g)

DESIGN
TEMP (Deg
C)

FLOW
(M3/hr)

40

420

PAGE: 1 OF 1

AREA
CLASSIFICATI ACCESSORIES
ON
SAFE

REFER DS

MAKE

MODEL

P&ID NO.

CERTIFICATION

PROCESS CONNECTION

FLANGE
MATERIAL

FLANGE
RATING
(#)

Emerson
(Rosemount )

2051TG3A2B21KS1B4M5D4Q4 +
1199WDB59AFFW71DAA3

L570000-XG02-00-GBD-120001

CATALOGUE

1/2" NPT (F)

NA

NA

REV.
REMARKS
NO

Product Data Sheet


00813-0100-4101, Rev AA
March 2008

Rosemount 2051

Rosemount 2051 Pressure Transmitter


Reference Accuracy of 0.075%
Rangeability of 100:1
Protocols available include 4-20 mA HART,
FOUNDATION fieldbus, 1-5 Vdc HART Low
Power
Coplanar platform enables integration of
primary elements, manifolds, and diaphragm
seal solutions
Complete pressure transmitter family to meet
your pressure, level, and flow needs

Contents
Product Offering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Product Certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 12
Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 18
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 26

www.rosemount.com

Product Data Sheet


00813-0100-4101, Rev AA
March 2008

Rosemount 2051

Meeting Your Pressure Measurement Needs


Confidence in your measurement
The 2051 capabilities are designed to meet a wide
range of applications. Combining 0.075% reference
accuracy, 100:1 rangedown, and extended two-year
stability provides confidence in your pressure
measurements.

Output protocols enable easy integration


The 2051 is available in 4-20mA HART, Low Power
HART, or FOUNDATION fieldbus output protocols.
Easily integrate the 2051 into existing or new
installations.

Coplanar platform enables integrated


solutions
The versatile Coplanar platform design enables the
best process connection for pressure, flow, and level
applications. The final 2051 assembly arrives factory
calibrated, pressure-tested, and ready to install. The
flexible design reduces engineering and inventory
costs.

Complete pressure offering


The 2051 family of pressure transmitters offers
differential, gage, and absolute pressure
measurements. The complete offering ensures the
2051 meets your measurement needs.

Rosemount Pressure Solutions


Rosemount 3051S Series of Instrumentation
Highest performing scalable pressure, flow and level
measurement solutions drive better plant efficiency and more
productivity. Innovative features include wireless, advanced
diagnostics, and multivariable technologies.

Rosemount 3095 Mass Flow Transmitter


Accurately measures differential pressure, static pressure and
process temperature to dynamically calculate fully compensated
mass flow.

Rosemount 3051 Pressure Transmitter Family


Proven industry standard performance and reliability to increase
plant profitability. Includes the most comprehensive offering to
meet all application needs.

Rosemount 305, 306 and 304 Manifolds


Factory-assembled, calibrated and seal-tested
transmitter-to-manifold assemblies reduce installation costs.

Rosemount 1199 Diaphragm Seals


Provides reliable, remote measurements of process pressure and
protects the transmitter from hot, corrosive, or viscous fluids.

Orifice Plate Primary Element Systems: Rosemount


1495 and 1595 Orifice Plates, 1496 Flange Unions and
1497 Meter Sections
A comprehensive offering of orifice plates, flange unions and
meter sections that are easy to specify and order. The 1595
Conditioning Orifice provides superior performance in tight fit
applications.

Annubar Flowmeter Series: Rosemount 3051SFA


ProBar, 3095MFA Mass ProBar, and 485
The state-of-the-art, fifth generation Rosemount 485 Annubar
combined with the 3051S or 3095 MultiVariable transmitter creates
an accurate, repeatable and dependable insertion-type flowmeter.

Compact Orifice Flowmeter Series: Rosemount


3051SFC, 3095MFC, and 405
Compact Orifice Flowmeters can be installed between existing
flanges, up to a Class 600 (PN100) rating. In tight fit applications,
a conditioning orifice plate version is available, requiring only two
diameters of straight run upstream and two downstream.

ProPlate Flowmeter Series: Rosemount 3051SFP


ProPlate, 3095MFP Mass ProPlate, and 1195
These integral orifice flowmeters eliminate the inaccuracies that
become more pronounced in small orifice line installations. The
completely assembled, ready to install flowmeters reduce cost and
simplify installation.

Product Data Sheet


00813-0100-4101, Rev AA
March 2008

Rosemount 2051
Product Offering

Rosemount 2051C Differential and Gage


See ordering information on page 26.

Performance of 0.075% accuracy, optional 0.065%

Two-year stability of 0.10%, optional five-year stability

Coplanar platform enables integrated manifold,


primary element and diaphragm seal solutions

Calibrated spans/ranges from 0.5 inH2O to 2000 psi


(1,2 mbar to 276 bar)

316L SST and Alloy C-276 process wetted parts

Rosemount 2051T Gage and Absolute


See ordering information on page 30.
Performance of 0.075% accuracy, optional 0.065%
Two-year stability of 0.10%, optional
five-year stability
Calibrated spans/ranges from 0.3 to 10000 psi
(10,3 mbar to 689 bar)
Multiple process connections available
316L SST and Alloy C-276 process wetted parts

Rosemount 2051L Liquid Level


See ordering information on page 33.

Performance of 0.075% accuracy

Welded fill fluid system provides


best-in-class system reliability

Flush and extended diaphragms

Multiple fill fluids and process wetted


materials available

Product Data Sheet


00813-0100-4101, Rev AA
March 2008

Rosemount 2051
Specifications
PERFORMANCE SPECIFICATIONS

For zero based spans, reference conditions, silicone oil fill, SST materials, Coplanar flange (2051C) or 1/2 in. - 14 NPT (2051T) process connections,
digital trim values set to equal range points.

Conformance To Specification (3 (Sigma))


Technology leadership, advanced manufacturing techniques and statistical process control ensure specification conformance to at least 3.

Reference Accuracy(1)
Models(1)

Standard

Performance Option, P8

0.075% of span
For spans less than 10:1, accuracy =

Ranges 2-5

2051C
Ranges 2-5

URL
0.025 + 0.005 --------------- % of Span
Span
Range 1

High Accuracy Option, P8


0.065% of span
For spans less than 10:1, accuracy =
URL
0.015 + 0.005 --------------- % of Span
Span

0.10% of span
For spans less than 15:1, accuracy =
URL % of Span
0.025 + 0.005 ------------- Span-

2051T
Ranges 1-4

0.075% of span
For spans less than 10:1, accuracy =

Ranges 1-4

URL % of Span
0.0075 ------------- Span-

Range 5

0.075% of span for spans greater than 5:1

2051L
Ranges 2-4

0.075% of span
For spans less than 10:1, accuracy =
URL
0.025 + 0.005 --------------- % of Span
Span

(1) For FOUNDATION fieldbus transmitters, use calibrated range in place of span.

High Accuracy Option, P8


0.065% of span
For spans less than 10:1, accuracy =
URL
0.0075 --------------- % of Span
Span

Product Data Sheet


00813-0100-4101, Rev AA
March 2008

Rosemount 2051

Long Term Stability


Models

Standard

Performance Option, P8

(1)

2051C

Ranges 2-5 0.1% of URL for 2 years

0.125% of URL for 5 years

2051CD
Range 1 0.2% of URL for 1 year
2051T(1)
Ranges 1-5 0.1% of URL for 2 years

0.125% of URL for 5 years

(1) 50 F (28 C) temperature changes, and up to 1000 psi (6,9 MPa) line pressure.

Dynamic Performance
4 - 20 mA HART(1)
Total Response Time (Td + Tc)
2051C, Range 3-5:
Range 1:
Range 2:
2051T:
2051L:
Dead Time (Td)
Update Rate

Fieldbus(3)

Typical HART Transmitter Response Time

(2)

:
115 milliseconds
270 milliseconds
130 milliseconds
100 milliseconds
See Instrument Toolkit
60 milliseconds (nominal)
22 times per second

152 milliseconds
307 milliseconds
152 milliseconds
152 milliseconds
See Instrument Toolkit
97 milliseconds
22 times per second

Transmitter Output vs. Time


Pressure Released
Td
100%

Tc

Td = Dead Time
Tc = Time Constant
Response Time = Td +Tc
63.2% of Total
Step Change

36.8%

(1) Dead time and update rate apply to all models and ranges; analog output only
(2) Nominal total response time at 75 F (24 C) reference conditions.
(3) Transmitter fieldbus output only, segment macro-cycle not included.

0%

Time

Line Pressure Effect per 1000 psi (6,9 MPa)


For line pressures above 2000 psi (13,7 MPa) and Ranges 4-5, see user manual (Rosemount publication number 00809-0100-4101).
Models

Line Pressure Effect

2051CD

Zero Error(1)
0.1% of URL/1000 psi (68,9 bar) for line pressures from 0 to 2000 psi (0 to 13,7 MPa)
0.5% of URL/1000 psi (68,9 bar)
Span Error
0.1% of reading/1000 psi (68,9 bar)
0.4% of reading/1000 psi (68,9 bar)

Ranges 2-3
Range 1
Ranges 2-3
Range 1

(1) Can be calibrated out at line pressure.

Product Data Sheet

Rosemount 2051

00813-0100-4101, Rev AA
March 2008

Ambient Temperature Effect per 50F (28C)


Models

Ambient Temperature Effect

2051C
Ranges 2-5 (0.025% URL + 0.125% span) from 1:1 to 5:1
(0.05% URL + 0.25% span) from 5:1 to 100:1
Range 1 (0.2% URL + 0.5% span) from 1:1 to 50:1
2051T

2051L

Range 2-4 (0.05% URL + 0.25% span) from 1:1 to 30:1


(0.07% URL + 0.25% span) from 30:1 to 100:1
Range 1 (0.05% URL + 0.25% span) from 1:1 to 10:1
(0.10% URL + 0.25% span) from 10:1 to 100:1
Range 5 (0.2% URL + 0.3% span)
See Instrument Toolkit

Mounting Position Effects


Models

Mounting Position Effects

2051C
2051T
2051L

Zero shifts up to 1.25 inH2O (3,11 mbar), which can be calibrated out. No span effect.
Zero shifts up to 2.5 inH2O (6,22 mbar), which can be calibrated out. No span effect.
With liquid level diaphragm in vertical plane, zero shift of up to 1 inH2O (2,49 mbar). With diaphragm in
horizontal plane, zero shift of up to 5 inH2O (12,43 mbar) plus extension length on extended units. Zero
shifts can be calibrated out. No span effect.

Vibration Effect
Less than 0.1% of URL when tested per the requirements of
IEC60770-1 field or pipeline with high vibration level (10-60 Hz
0.21mm displacement peak amplitude / 60-2000 Hz 3g).

Power Supply Effect


All Models
Less than 0.005% of calibrated span per volt.

Electromagnetic Compatibility (EMC)


All Models
Meets all relevant requirements of EN 61326 and NAMUR NE-21.

Transient Protection (Option Code T1)


All Models:
Meets IEEE C62.41, Category Location B
6 kV crest (0.5 s - 100 kHz)
3 kV crest (8 20 microseconds)
6 kV crest (1.2 50 microseconds)
Meets IEEE C37.90.1, Surge Withstand Capability
SWC 2.5 kV crest, 1.0 MHz wave form

Product Data Sheet


00813-0100-4101, Rev AA
March 2008

Rosemount 2051

FUNCTIONAL SPECIFICATIONS
Range and Sensor Limits

Range

2051CD, 2051CG, 2051L

1
2
3
4
5

Range and Sensor Limits


Lower (LRL)
Minimum Span

Upper (URL)

2051C Differential

2051C Gage

2051L Differential

2051L Gage

0.5 inH2O
(1,2 mbar)
2.5 inH2O
(6,2 mbar)
10 inH2O
(24,9 mbar)
3 psi
(0,207 bar)
20 psi
(1,38 bar)

25 inH2O
(62,3 mbar)
250 inH2O
(0,62 bar)
1000 inH2O
(2,49 bar)
300 psi
(20,6 bar)
2000 psi
(137,9 bar)

25 inH2O
(62,1 mbar)
250 inH2O
(0,62 bar)
1000 inH2O
(2,49 bar)
300 psi
(20,6 bar)
2000 psi
(137,9 bar)

25 inH2O
(62,1 mbar)
250 inH2O
(0,62 bar)
0.5 psia
(34,5 mbar abs)
0.5 psia
(34,5 mbar abs)
0.5 psia
(34,5 mbar abs)

N/A

N/A

250 inH2O
(0,62 bar)
1000 inH2O
(2,49 bar)
300 psi
(20,7 bar)
N/A

250 inH2O
(0,62 bar)
0.5 psia
(34,5 mbar abs)
0.5 psia
(34,5 mbar abs)
N/A

Range

2051T

1
2
3
4
5

Range and Sensor Limits


Minimum
Span

Upper
(URL)

Lower
(LRL) (Abs)

Lower(1)
(LRL) (Gage)

0.3 psi
(20,6 mbar)
1.5 psi
(0,103 bar)
8 psi
(0,55 bar)
40 psi
(2,76 bar)
2000 psi
(137,9 bar)

30 psi
(2,06 bar)
150 psi
(10,3 bar)
800 psi
(55,2 bar)
4000 psi
(275,8 bar)
10000 psi
(689,4 bar)

0 psia
(0 bar)
0 psia
(0 bar)
0 psia
(0 bar)
0 psia
(0 bar)
0 psia
(0 bar)

14.7 psig
(1,01 bar)
14.7 psig
(1,01 bar)
14.7 psig
(1,01 bar)
14.7 psig
(1,01 bar)
14.7 psig
(1,01 bar)

(1) Assumes atmospheric pressure of 14.7 psig.

Product Data Sheet


00813-0100-4101, Rev AA
March 2008

Rosemount 2051
Service

Standard Function Blocks


Resource Block

Liquid, gas, and vapor applications

Contains hardware, electronics, and diagnostic information.

Protocols

Transducer Block

420 mA HART (Output Code A)

Contains actual sensor measurement data including the


sensor diagnostics and the ability to trim the pressure
sensor or recall factory defaults.

Output
Two-wire 420 mA, user-selectable for linear or square root
output. Digital process variable superimposed on 420 mA
signal, available to any host that conforms to the HART
protocol.
Power Supply

LCD Block
Configures the local display.
2 Analog Input Blocks
Processes the measurements for input into other function
blocks. The output value is in engineering units or custom
and contains a status indicating measurement quality.

External power supply required. Standard transmitter operates


on 10.5 to 42.4 V dc with no load.

PID Block

Load Limitations

Contains all logic to perform PID control in the field including


cascade and feedforward.

Maximum loop resistance is determined by the voltage level of


the external power supply, as described by:

Backup Link Active Scheduler (LAS)

Maximum Loop Resistance = 43.5 * (Power Supply Voltage 10.5)

Load (Ohms)

1387

The transmitter can function as a Link Active Scheduler if the


current link master device fails or is removed from the
segment.

1-5 Vdc HART Low Power (Output Code M)

1000

Output
500

Operating
Region

Three wire 15 Vdc output, user-selectable for linear or


square root output. Digital process variable superimposed on
voltage signal, available to any host conforming to the HART
protocol.

0
10.5

20
30
Voltage (V dc)

42.4

The HART communicator requires a minimum


loop resistance of 250 for communication.

FOUNDATION fieldbus (Output Code F)

Power Supply
External power supply required. Standard transmitter operates
on 9 to 28 Vdc with no load.
Power Consumption
3.0 mA, 2784 mW

Power Supply
External power supply required; transmitters operate on 9.0 to
32.0 V dc transmitter terminal voltage.
Current Draw
17.5 mA for all configurations (including LCD display option)
FOUNDATION fieldbus Function Block Execution Times
Block
Execution Time
Resource
Transducer
LCD Block
Analog Input 1, 2
PID

100 k or greater

Overpressure Limits
Transmitters withstand the following limits without damage:

2051C
Ranges 25: 3626 psig (250 bar)
4500 psig (310,3 bar) for option code P9

30 milliseconds
45 milliseconds

FOUNDATION fieldbus Parameters


Schedule Entries
Links
Virtual Communications Relationships (VCR)

Output Load

Range 1: 2000 psig (137,9 bar)

2051T
Range 1: 750 psi (51,7 bar)
Range 2: 1500 psi (103,4 bar)
7 (max.)
20 (max.)
12 (max.)

Range 3: 1600 psi (110,3 bar)


Range 4: 6000 psi (413,7 bar)
Range 5: 15000 psi (1034,2 bar)

Product Data Sheet


00813-0100-4101, Rev AA
March 2008

Rosemount 2051

2051L

Process Temperature Limits

Limit is flange rating or sensor rating, whichever is lower (see


Table 1).

At atmospheric pressures and above.

TABLE 1. 2051L Flange Rating


Standard

Type

2051C
CS Rating SST Rating

ANSI/ASME
Class 150
285 psig
275 psig
ANSI/ASME
Class 300
740 psig
720 psig
At 100 F (38 C), the rating decreases with
increasing temperature.
DIN
PN 1040
40 bar
40 bar
DIN
PN 10/16
16 bar
16 bar
At 248 F (120 C), the rating decreases
with increasing temperature.

Static Pressure Limit


2051CD
Operates within specifications between static line pressures of
-14.2 psig (0.034 bar) and 3626 psig (250 bar)

TABLE 2. 2051 Process Temperature Limits

For Option Code P9, 4500 psig (310,3 bar)

Range 1: 0.5 psia to 2000 psig (34 mbar and 137,9 bar)

Burst Pressure Limits


2051C Coplanar or traditional process flange
10000 psig (689,5 bar)

2051T

Silicone Fill Sensor(1)


with Coplanar Flange
40 to 250 F (40 to 121 C)(2)
with Traditional Flange
40 to 300 F (40 to 149 C)(2)
with Level Flange
40 to 300 F (40 to 149 C)(2)
with 305 Integral Manifold 40 to 300 F (40 to 149 C)(2)
Inert Fill Sensor(1)
0 to 185 F (18 to 85 C)(3)
2051T (Process Fill Fluid)
Silicone Fill Sensor(1)
40 to 250 F (40 to 121 C)(2)
(1)
Inert Fill Sensor
22 to 250 F (30 to 121 C)(2)
2051L Low-Side Temperature Limits
Silicone Fill Sensor(1)
40 to 250 F (40 to 121 C)(2)
(1)
Inert Fill Sensor
0 to 185 F (18 to 85 C) (2)
2051L High-Side Temperature Limits (Process Fill Fluid)
Syltherm XLT
D.C. Silicone 704
D.C. Silicone 200
Inert
Glycerin and Water
Neobee M-20
Propylene Glycol and
Water

100 to 300 F (73 to 149 C)


32 to 400 F (0 to 205 C)
40 to 400 F (40 to 205 C)
50 to 350 F (45 to 177 C)
0 to 200 F (18 to 93 C)
0 to 400 F (18 to 205 C)
0 to 200 F (18 to 93 C)

(1) Process temperatures above 185 F (85 C) require derating


the ambient limits by a 1.5:1 ratio.

Ranges 14: 11000 psi (758,4 bar)

(2) 220 F (104 C) limit in vacuum service; 130 F (54 C) for


pressures below 0.5 psia.

Range 5: 26000 psi (1792,64 bar)

(3) 160 F (71 C) limit in vacuum service.

Temperature Limits
Ambient
40 to 185 F (40 to 85 C)
With LCD display(1): 40 to 175 F (20 to 80 C)

Storage
50 to 230 F (46 to 110 C)
With LCD display: 40 to 185 F (40 to 85 C)
(1) LCD display may not be readable and LCD updates will be slower
at temperatures below -4 F (-20 C).

Humidity Limits
0100% relative humidity

Turn-On Time
Performance within specifications less than 2.0 seconds after
power is applied to the transmitter

Volumetric Displacement
Less than 0.005 in3 (0,08 cm3)

Damping
Analog output response to a step input change is user-selectable
from 0 to 25.6 seconds for one time constant. This software
damping is in addition to sensor module response time.

Product Data Sheet


00813-0100-4101, Rev AA
March 2008

Rosemount 2051
Failure Mode Alarm

2051C Process Wetted Parts

If self-diagnostics detect a sensor or microprocessor failure, the


analog signal is driven either high or low to alert the user. High or
low failure mode is user-selectable with a jumper on the
transmitter. The values to which the transmitter drives its output in
failure mode depend on whether it is factory-configured to
standard or NAMUR-compliant operation. The values for each are
as follows:
Standard Operation

Drain/Vent Valves

Output Code

Linear Output
3.9 I 20.8
0.97 V 5.2

S
M

Fail High

Fail Low

I 21.75 mA
V 5.4 V

I 3.75 mA
V 0.95V

316 SST or Alloy C-276

Process Flanges and Adapters


Plated carbon steel, SST CF-8M (cast version of 316 SST,
material per ASTM-A743), or CW12MW (cast version of Alloy
C-276)

Wetted O-rings
Glass-filled PTFE or Graphite-filled PTFE

Process Isolating Diaphragms


NAMUR-Compliant Operation
Output Code

Linear Output
3.8 I 20.5

316L SST or Alloy C-276


Fail High

Fail Low

I 22.5 mA

I 3.6 mA

2051T Process Wetted Parts


Process Connections

Output Code F
If self-diagnostics detect a gross transmitter failure, that
information gets passed as a status along with the process
variable.

316L SST or Alloy C-276

Process Isolating Diaphragms


316L SST or Alloy C-276

PHYSICAL SPECIFICATIONS

2051L Process Wetted Parts

Electrical Connections
1/214

NPT, G1/2, and M20 1.5 (CM20) conduit.

Flanged Process Connection (Transmitter High Side)


Process Diaphragms, Including Process Gasket Surface

Process Connections

2051C

316L SST or Alloy C-276

Extension

1/418 NPT on 21/8-in. centers


1/214 NPT and RC 1/2 on 2-in.(50.8mm), 21/8-in. (54.0 mm),
or 21/4-in. (57.2mm) centers (process adapters)

CF-3M (Cast version of 316L SST, material per


ASTM-A743), or Cast C-276. Fits schedule 40 and 80
pipe.

Mounting Flange

2051T
1

/214 NPT female

Zinc-cobalt plated CS or SST

G /2 A DIN 16288 Male (available in SST for Range 14


transmitters only)
9

Autoclave type F-250-C (Pressure relieved /1618 gland


thread; 1/4 OD high pressure tube 60 cone; available in SST
for Range 5 transmitters only)

Reference Process Connection (Transmitter Low Side)


Isolating Diaphragms

316L SST or Alloy C-276

Reference Flange and Adapter

2051L
High pressure side: 2-in.(50.8mm), 3-in. (72 mm), or 4-in.
(102mm), ASME B 16.5 (ANSI) Class 150 or 300 flange;
50, 80 or 100 mm, DIN 2501 PN 40 or 10/16 flange
Low pressure side: 1/418 NPT on flange, 1/214 NPT on
process adapter

10

CF-8M (Cast version of 316 SST, material per


ASTM-A743)

Product Data Sheet


00813-0100-4101, Rev AA
March 2008

Non-Wetted Parts for 2051C/T/L


Electronics Housing
Low-copper aluminum or CF-8M (Cast version of 316 SST).
Enclosure Type 4X, IP 65, IP 66, IP68

Coplanar Sensor Module Housing

Rosemount 2051
Shipping Weights
TABLE 3. Transmitter Weights without Options
Transmitter

lb. (kg)

2051C
2051L
2051T

6.0 (2,7)
Table 4 below
3.0 (1,4)

CF-3M (Cast version of 316L SST)

Bolts
ASTM A449, Type 1 (zinc-cobalt plated carbon steel)
ASTM F593G, Condition CW1 (Austenitic 316 SST)
ASTM A193, Grade B7M (zinc plated alloy steel)

Sensor Module Fill Fluid


Silicone oil (D.C. 200) or Fluorocarbon oil (Halocarbon or
Fluorinert FC-43 for 2051T)

Process Fill Fluid (2051L only)


Syltherm XLT, D.C. Silicone 704,
D.C. Silicone 200, inert, glycerin and water, Neobee M-20 or
propylene glycol and water

Paint
Polyurethane

TABLE 4. 2051L Weights without Options


Flush
lb. (kg)

Flange
2-in., 150
3-in., 150
4-in., 150
2-in., 300
3-in., 300
4-in., 300
DN 50/PN 40
DN 80/PN 40
DN 100/
PN 10/16
DN 100/
PN 40

2-in. Ext.
lb (kg)

4-in. Ext.
lb (kg)

6-in. Ext.
lb (kg)

12.5 (5,7)

17.5 (7,9)
19.5 (8,8)
20.5 (9,3)
23.5 (10,7) 26.5 (12,0) 28.5 (12,9)
17.5 (7,9)

22.5 (10,2) 24.5 (11,1) 25.5 (11,6)


32.5 (14,7) 35.5 (16,1) 37.5 (17,0)
13.8 (6,2)

19.5 (8,8)
21.5 (9,7) 22.5 (10,2)
17.8 (8,1)
19.8 (9,0)
20.8 (9,5)

21.5 (9,7)
30.5 (13,8)

26.5 (12,0)
39.5 (17,9)

23.5 (10,6)
21.8 (9,9)

23.2 (10,5)

27.2 (12,3)

25.2 (11,5)

26.2 (11,9)

Cover O-rings
Buna-N

TABLE 5. Transmitter Options Weights


Code
J, K, L, M
M5
B4
B1 B2 B3
B7 B8 B9
BA, BC
H2
H3
H4
H7
FC
FD
FA
FB
FP
FQ

Option
Stainless Steel Housing
LCD display for Aluminum Housing
SST Mounting Bracket for Coplanar Flange
Mounting Bracket for Traditional Flange
Mounting Bracket for Traditional Flange
SST Bracket for Traditional Flange
Traditional Flange
Traditional Flange
Traditional Flange
Traditional Flange
Level Flange3 in., 150
Level Flange3 in., 300
Level Flange2 in., 150
Level Flange2 in., 300
DIN Level Flange, SST, DN 50, PN 40
DIN Level Flange, SST, DN 80, PN 40

Add
lb (kg)
3.9 (1,8)
0.5 (0,2)
1.0 (0,5)
2.3 (1,0)
2.3 (1,0)
2.3 (1,0)
2.4 (1,1)
2.7 (1,2)
2.6 (1,2)
2.5 (1,1)
10.8 (4,9)
14.3 (6,5)
10.7 (4,8)
14.0 (6,3)
8.3 (3,8)
13.7 (6,2)

11

Вам также может понравиться