1MRS757058 A
Issued: 2010-06-11
Contents
1. Description...........................................................3
2. Standard configurations.......................................3
3. Protection functions.............................................6
18. Communication.................................................15
4. Application...........................................................8
6. Control................................................................12
7. Measurement.....................................................12
8. Disturbance recorder..........................................13
9. Event log.............................................................13
25. Tools..................................................................53
27. References........................................................58
13. Self-supervision.................................................14
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes
no responsibility for any errors that may appear in this document.
Copyright 2010 ABB Oy.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or product names mentioned in this document may be trademarks or
registered trademarks of their respective holders.
ABB
1. Description
The voltage protection and control IED,
REU615 is available in two standard
configurations, denoted A and B.
Configuration A is preadapted for voltage and
frequency-based protection schemes in utility
and industrial power systems and distribution
systems including networks with distributed
power generation. The B configuration is
designed for automatic voltage regulation of
power transformers equipped with an onload tap-changer. Both configurations also
feature additional CB control, measuring and
supervising functions. REU615 is a member
of ABBs Relion product family and part of
its 615 protection and control product series.
The 615 series IEDs are characterized by their
compactness and withdrawableunit design.
Re-engineered from the ground up, the 615
series has been designed to unleash the full
potential of the IEC 61850 standard for
communication and interoperability between
substation automation devices. Once the
standard configuration IED has been given
the application-specific settings, it can
directly be put into service.
1MRS757058 A
Issued: 2010-06-11
Revision: A
The 615 series IEDs support a range of
communication protocols including IEC
61850 with GOOSE messaging, IEC
60870-5-103, Modbus and DNP3.
2. Standard
configurations
REU615 is available in two standard
configurations. The standard signal
configuration can be altered by means of the
graphical signal matrix or the optional
graphical application functionality of the
Protection and Control IED Manager PCM600.
Further, the application configuration
functionality of PCM600 supports the creation
of multi-layer logic functions using various
logical elements, including timers and flipflops. By combining protection functions with
logic function blocks, the IED configuration
can be adapted to user-specific application
requirements.
ABB
Std.conf.
1MRS757058 A
Issued: 2010-06-11
3)
3)
3)
o4)
o4)
Protection1)2)
ABB
1MRS757058 A
Issued: 2010-06-11
o4)
Circuit-breaker control
Disturbance recorder
Control
Condition Monitoring
Measurement
ABB
1MRS757058 A
Issued: 2010-06-11
RTD/mA measurement
Frequency measurement
3. Protection functions
Standard configuration A
Standard configuration A is intended for
busbar voltage supervision, load shedding
(disconnection) and restoration
(reconnection) applications. It is also used for
overfrequency and underfrequency protection
of power generators and for other AC
equipment, e.g. capacitor banks, requiring
three-phase overvoltage protection, threephase undervoltage protection, residual
overvoltage protection, positive phase
sequence undervoltage protection, negative
phase sequence overvoltage protection and
frequency supervision.
The integrated load shedding and restoration
functionality offers five instances for
disconnection and reconnection of lessimportant loads in network overload
situations. The five instances enable the
connected feeders to be more thoroughly
prioritized and grouped thus facilitating the
securing of critical applications.
If the restoration process is coordinated by
an automation system or process control
system, the IEDs load shedding and
restoration function can send a signal to the
ABB
1MRS757058 A
Issued: 2010-06-11
GUID-5E258DF3-B410-4FEE-9925-A8FC9C3617CE V1 EN
GUID-DCA293F5-58D2-4CE8-9602-842A6498F9ED V1 EN
ABB
4. Application
Standard configuration A
The A configuration of REU615 is intended to
be used in medium voltage switchgear,
supplied with a dedicated voltage
measurement cubicle. The A configuration of
REU615 provides busbar overvoltage and
undervoltage supervision, network residual
overvoltage supervision and frequency
supervision. REU615 offers the functionality
needed to provide load shedding or
generation rejection to enhance network
stability. In generator and motor applications
REU615 provides supplementary protection
by detecting any deviation from the permitted
frequency and voltage values. An integrated
synchro-check function ensures a
synchronized connection of the equipment
1MRS757058 A
Issued: 2010-06-11
ABB
1MRS757058 A
Issued: 2010-06-11
GUID-CA7B4D3E-1269-450F-A061-5A404FF52455 V1 EN
Figure 3. Busbar protection and supervision using REU615 with the standard configuration A.
The arc protection schemes of REU615 and REF615 are employed for busbar
protection for the voltage measurement bay and related parts of the busbar. Apart
from the busbar protection and supervision the REU615 IED is utilized for
centralized load shedding (disconnection) and restoration (reconnection) of one of
the outgoing feeders. The synchro-check and energizing check functions incorporated
in REU615 are employed for ensuring a safe connection of the outgoing feeder,
including distributed generation, to the network.
ABB
1MRS757058 A
Issued: 2010-06-11
GUID-A90B4035-68B9-4264-83C5-DD791DDEDAB0 V1 EN
Figure 4. Tap changer control and power transformer thermal overload protection using
REU615 with the standard configuration B. The tap changer position information is
received as a mA-signal from the tap changer operation mechanism. The position
value is sent to the transformer differential protection function of the RET615 IED
using GOOSE messaging. Further, the analog GOOSE messaging enables the tap
changer control of two parallel running power transformers. The RTD inputs
complement the thermal overload protection by measuring the oil and ambient
temperature of the power transformer.
5. Supported ABB
solutions
ABBs 615 series protection and control IEDs
together with the COM600 Station
Automation device constitute a genuine IEC
61850 solution for reliable power distribution
in utility and industrial power systems. To
facilitate and streamline the system
engineering ABBs IEDs are supplied with
Connectivity Packages containing a
compilation of software and IED-specific
information including single-line diagram
templates, a full IED data model including
event and parameter lists. By utilizing the
Connectivity Packages the IEDs can be
readily configured via the PCM600 Protection
and Control IED Manager and integrated with
the COM600 Station Automation device or the
10
1MRS757058 A
Issued: 2010-06-11
Version
3.4 or later
MicroSCADA Pro
System 800xA
ABB
MicroSCADA
IEC 60870-5-104
COM600
Web HMI
COM600
Web HMI
COM600
COM600
Ethernet switch
Analog and binary horizontal
GOOSE communication
PCM600
Ethernet switch
Analog and binary horizontal
GOOSE communication
IEC 61850
PCM600
IEC 61850
Binary signal
transfer
REU615
REF615
RET615
RED615
Line differential
communication
RED615
RET615
REF615
REU615
GUID-66EB52A0-21A1-4D1F-A1EF-61060B371384 V2 EN
Figure 5. Utility power distribution network example using 615 series IEDs, Station
Automation COM600 and MicroSCADA Pro
ABB
11
1MRS757058 A
Issued: 2010-06-11
ABB
System 800xA
OPC
COM600
Web HMI
COM600
Web HMI
COM600
COM600
Ethernet switch
Analog and binary horizontal
GOOSE communication
PCM600
Ethernet switch
Analog and binary horizontal
GOOSE communication
IEC 61850
PCM600
IEC 61850
Binary signal
transfer
REU615
REF615
RET615
REM615
RED615
Line differential
communication RED615
REM615
RET615
REF615
REU615
GUID-6984D893-45D5-427A-BABF-F1E1015C18E2 V2 EN
Figure 6. Industrial power system example using 615 series IEDs, Station Automation COM600
and System 800xA
6. Control
7. Measurement
12
ABB
8. Disturbance recorder
The IED is provided with a disturbance
recorder featuring up to 12 analog and 64
binary signal channels. The analog channels
can be set to record either the waveform or
the trend of the currents and voltage
measured.
The analog channels can be set to trigger the
recording function when the measured value
falls below or exceeds the set values. The
binary signal channels can be set to start a
recording on the rising or the falling edge of
the binary signal or both.
By default, the binary channels are set to
record external or internal IED signals, for
example the start or trip signals of the IED
stages, or external blocking or control
signals. Binary IED signals such as a
protection start or trip signal, or an external
IED control signal over a binary input can be
set to trigger the recording. The recorded
information is stored in a non-volatile
memory and can be uploaded for subsequent
fault analysis.
9. Event log
1MRS757058 A
Issued: 2010-06-11
13
12. Trip-circuit
supervision
The trip-circuit supervision continuously
monitors the availability and operability of
the trip circuit. It provides open-circuit
monitoring both when the circuit breaker is
in its closed and in its open position. It also
detects loss of circuit-breaker control voltage.
13. Self-supervision
The IEDs built-in self-supervision system
continuously monitors the state of the IED
hardware and the operation of the IED
software. Any fault or malfunction detected
will be used for alerting the operator.
A permanent IED fault will block the
protection functions to prevent incorrect
operation.
14
1MRS757058 A
Issued: 2010-06-11
1MRS757058 A
Issued: 2010-06-11
Analog inputs
Binary inputs/outputs
CT
VT
RTD
inputs
mA inputs
BI
BO
12
10
B1)
62)
22)
8 (14)3)
10 (13)3)
1) The optional I/O module and the optional RTD/mA modules are mutually exclusive
2) Optional
3) With optional binary I/O module ( )
18. Communication
15
1MRS757058 A
Issued: 2010-06-11
16
ABB
1MRS757058 A
Issued: 2010-06-11
Client A
Client B
Network
Network
RED615
REM615
REU615
RET615
REF615
GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V1 EN
Ethernet
Serial
100BASE-TX
RJ-45
100BASE-FX LC
RS-232/RS-485
Fibre-optic ST
IEC 61850
MODBUS RTU/
ASCII
MODBUS TCP/
IP
DNP3 (serial)
DNP3 TCP/IP
IEC 60870-5-103
= Supported
ABB
17
1MRS757058 A
Issued: 2010-06-11
Value
Width
frame
177 mm
case
164 mm
frame
177 mm (4U)
case
160 mm
Height
Depth
Weight
4.1 kg
2.1 kg
Type 1
Type 2
Uauxnominal
Start-up threshold
Burden of auxiliary
voltage supply under
quiescent (Pq)/operating
condition
Maximum interruption
time in the auxiliary DC
voltage without resetting
the IED
30 ms at Vnrated
Fuse type
T4A/250 V
18
ABB
1MRS757058 A
Issued: 2010-06-11
Value
Operating range
Rated voltage
24...250 V DC
Current drain
1.6...1.9 mA
Power consumption
31.0...570.0 mW
Threshold voltage
18...176 V DC
Reaction time
3 ms
Value
Supported RTD
sensors
Supported
resistance range
100 platinum
250 platinum
100 nickel
120 nickel
250 nickel
10 copper
TCR
TCR
TCR
TCR
TCR
TCR
0...2 k
Maximum lead
resistance (threewire
measurement)
25 per lead
Isolation
Response time
<4 s
RTD/resistance
sensing current
Operation
accuracy
mA inputs
Temperature
2.0% or 1
1C
10 copper: 2C
Supported
current range
020 mA
Current input
impedance
44 0.1%
Operation
accuracy
ABB
Resistance
Resistance
0.5% or 0.01 mA
19
1MRS757058 A
Issued: 2010-06-11
Value
Rated voltage
250 V AC/DC
5A
10 A
15 A
100 mA at 24 V AC/DC
Value
Rated voltage
250 V AC/DC
8A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
20...250 V AC/DC
~1.5 mA
20 V AC/DC (15...20 V)
20
ABB
1MRS757058 A
Issued: 2010-06-11
Value
Rated voltage
250 V AC/DC
5A
15 A
30 A
100 mA at 24 V AC/DC
Protocol
Cable
Data transfer
rate
Front
TCP/IP
protocol
10 MBits/s
Fibre type1)
Wave
length
Max.
distance
Permitted path
attenuation2)
LC
MM 62.5/125 m
glass fibre core
1300 nm
2 km
<8 dB
LC
SM 9/125 m
1300 nm
2-20 km
<8 dB
ST
MM 62.5/125 m
glass fibre core
820-900 nm
1 km
<11 dB
Value
B004, B0051)
Isolation
500V 1 min.
Modulation
Unmodulated
Logic level
TTL Level
Current consumption
2...4 mA
Power consumption
10...20 mW
ABB
21
1MRS757058 A
Issued: 2010-06-11
Table 16. Lens sensor and optical fibre for arc protection
Description
Value
+140C
100 mm
Value
Front side
IP 54
IP 20
Value
-25...+55C (continuous)
<93%, non-condensing
Atmospheric pressure
86...106 kPa
Altitude
Up to 2000 m
-40...+85C
Reference
96 h at +55C
16 h at +85C1)
IEC 60068-2-2
96 h at -25C
16 h at -40C
IEC 60068-2-1
6 cycles (12 h + 12 h) at
IEC 60068-2-30
+25C+55C, humidity >93%
Storage test
96 h at -40C
96 h at +85C
IEC 60068-2-48
1) For IEDs with an LC communication interface the maximum operating temperature is +70oC
22
ABB
1MRS757058 A
Issued: 2010-06-11
Reference
IEC 61000-4-18
IEC 60255-22-1, class III
IEEE C37.90.1-2002
Common mode
2.5 kV
Differential mode
2.5 kV
IEC 61000-4-2
IEC 60255-22-2
IEEE C37.90.3-2001
Contact discharge
8 kV
Air discharge
15 kV
10 V/m (rms)
f=80-2700 MHz
IEC 61000-4-3
IEC 60255-22-3, class III
10 V/m
f=900 MHz
ENV 50204
IEC 60255-22-3, class III
20 V/m (rms)
f=80-1000 MHz
IEEE C37.90.2-2004
IEC 61000-4-4
IEC 60255-22-4
IEEE C37.90.1-2002
4kV
IEC 61000-4-5
IEC 60255-22-5
Communication
1 kV, line-to-earth
Other ports
4 kV, line-to-earth
2 kV, line-to-line
ABB
IEC 61000-4-8
300 A/m
1000 A/m
23
1MRS757058 A
Issued: 2010-06-11
Reference
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 61000-4-11
IEC 61000-4-16
IEC 60255-22-7, class A
Common mode
Differential mode
300 V rms
150 V rms
Emission tests:
EN 55011, class A
IEC 60255-25
Conducted
0.15-0.50 MHz
0.5-30 MHz
Radiated
30-230 MHz
230-1000 MHz
24
ABB
1MRS757058 A
Issued: 2010-06-11
Reference
Dielectric tests
Test voltage
Insulation resistance
measurements
Isolation resistance
Protective bonding
resistance
Resistance
IEC 60255-27
<0.1 , 4 A, 60 s
Reference
Requirement
Class 2
Class 2
Seismic test
IEC 60255-21-3
Class 2
ABB
Description
Reference
LV directive
2006/95/EC
Standard
EN 60255-27 (2005)
EN 60255-1 (2009)
25
1MRS757058 A
Issued: 2010-06-11
Reference
EMC directive
2004/108/EC
Standard
EN 50263 (2000)
EN 60255-26 (2007)
26
ABB
1MRS757058 A
Issued: 2010-06-11
Protection functions
Table 26. Three-phase non-directional overcurrent protection (PHxPTOC)
Characteristic
Value
Operation accuracy
Start time
PHLPTOC
PHHPTOC
and
PHIPTOC
1)2)
PHIPTOC:
IFault = 2 x set Start
value
IFault = 10 x set Start
value
PHHPTOC and
PHLPTOC:
IFault = 2 x set Start
value
Minimum
Typical
Maximum
16 ms
19 ms
23 ms
11 ms
12 ms
14 ms
22 ms
24 ms
25 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 30 ms
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n x fn, where n = 2, 3, 4, 5,
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
3)
1) Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on
stage), current before fault = 0.0 x In, fn = 50 Hz, fault current in one phase with nominal frequency injected
from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Includes the delay of the heavy-duty output contact
ABB
27
1MRS757058 A
Issued: 2010-06-11
Function
Value (Range)
Step
Start Value
PHLPTOC
0.05...5.00 x In
0.01
PHHPTOC
0.10...40.00 x In
0.01
PHIPTOC
1.00...40.00 x In
0.01
PHLPTOC
0.05...15.00
0.05
PHHPTOC
0.05...15.00
0.05
PHLPTOC
40...200000 ms
10
PHHPTOC
40...200000 ms
10
PHIPTOC
20...200000 ms
10
PHLPTOC
PHHPTOC
PHIPTOC
Definite time
Time multiplier
Operating curve
type1)
28
ABB
1MRS757058 A
Issued: 2010-06-11
Value
Operation accuracy
Start time1)2)
UFault = 1.1 x set Start
value
Minimum
Typical
Maximum
22 ms
24 ms
26 ms
Reset time
< 40 ms
Reset ratio
Retardation time
< 35 ms
Suppression of harmonics
1) Start value = 1.0 x Un, Voltage before fault = 0.9 x Un, fn = 50 Hz, overvoltage in one phase-to-phase with
nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 1.20 x Un, Start value multiples in range of 1.10 to 2.00
Function
Value (Range)
Step
Start value
PHPTOV
0.05...1.60 x Un
0.01
Time multiplier
PHPTOV
0.05...15.00
0.05
PHPTOV
40...300000 ms
10
Operating curve
type1)
PHPTOV
ABB
29
1MRS757058 A
Issued: 2010-06-11
Value
Operation accuracy
Start time1)2)
UFault = 0.9 x set
Start value
Minimum
Typical
Maximum
62 ms
64 ms
66 ms
Reset time
< 40 ms
Reset ratio
Retardation time
< 35 ms
Suppression of harmonics
1) Start value = 1.0 x Un, Voltage before fault = 1.1 x Un, fn = 50 Hz, undervoltage in one phase-to-phase with
nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Minimum Start value = 0.50, Start value multiples in range of 0.90 to 0.20
Function
Value (Range)
Step
Start value
PHPTUV
0.05...1.20 x Un
0.01
Time multiplier
PHPTUV
0.05...15.00
0.05
PHPTUV
60...300000 ms
10
Operating curve
type1)
PHPTUV
30
ABB
1MRS757058 A
Issued: 2010-06-11
Value
Operation accuracy
Start time1)2)
UFault = 0.99 x set
Start value
UFault = 0.9 x set Start
value
Minimum
Typical
Maximum
51 ms
43 ms
53 ms
45 ms
54 ms
46 ms
Reset time
< 40 ms
Reset ratio
Retardation time
< 35 ms
Suppression of harmonics
1) Start value = 1.0 x Un, Positive sequence voltage before fault = 1.1 x Un, fn = 50 Hz, positive sequence
undervoltage with nominal frequency injected from random phase angle, results based on statistical distribution
of 1000 measurements
2) Includes the delay of the signal output contact
ABB
Parameter
Function
Value (Range)
Step
Start value
PSPTUV
0.010...1.200 x Un
0.001
PSPTUV
40...120000 ms
10
PSPTUV
0.01...1.0 x Un
0.01
31
1MRS757058 A
Issued: 2010-06-11
Value
Operation accuracy
Start time1)2)
UFault = 1.1 set
Start value
UFault = 2.0 set
Start value
Minimum
Typical
Maximum
33 ms
24 ms
35 ms
26 ms
37 ms
28 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Suppression of harmonics
1) Negative-sequence voltage before fault = 0.0 Un, fn = 50 Hz, negative-sequence overvoltage with nominal
frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
Function
Value (Range)
Step
Start value
NSPTOV
0.010...1.000 x Un
0.001
NSPTOV
40...120000 ms
32
ABB
1MRS757058 A
Issued: 2010-06-11
Start time
ABB
Value
f>/f<
10 mHz
df/dt
f>/f<
< 80 ms
df/dt
< 120 ms
Reset time
< 150 ms
33
1MRS757058 A
Issued: 2010-06-11
Values
(Range)
Unit
Operation mode
1=Freq<
2=Freq>
3=df/dt
4=Freq< + df/dt
5=Freq> + df/dt
6=Freq< OR df/
dt
7=Freq> OR df/
dt
0.900...1.200
xFn
0.800...1.100
Step
Default
Description
1=Freq<
Frequency
protection
operation mode
selection
0.001
1.050
Frequency start
value
overfrequency
xFn
0.001
0.950
Frequency start
value
underfrequency
-0.200...0.200
xFn /s
0.005
0.010
Frequency start
value rate of
change
Operate Tm Freq
80...200000
ms
10
200
Operate delay
time for
frequency
Operate Tm df/dt
120...200000
ms
10
400
Operate delay
time for
frequency rate
of change
Value
Operation accuracy
34
ABB
1MRS757058 A
Issued: 2010-06-11
Table 39. Thermal overload for protection, two time constants (T2PTTR) main settings
Parameter
Function
Value (Range)
Step
Temperature rise
T2PTTR
0.0...200.0oC
0.1
Max temperature
T2PTTR
0.0...200.0oC
0.1
Operate temperature
T2PTTR
80.0...120.0 %
0.1
Weighting factor p
T2PTTR
0.00...1.00
0.01
T2PTTR
6...60000 s
Current reference
T2PTTR
0.05...4.00 x In
0.01
Operation
T2PTTR
Off
On
Value
Operation accuracy
Start time1)2)
UFault = 1.1 x set
Start value
Minimum
Typical
Maximum
55 ms
56 ms
58 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Suppression of harmonics
1) Residual voltage before fault = 0.0 x Un, fn = 50 Hz, residual voltage with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
ABB
Parameter
Function
Value (Range)
Step
Start value
ROVPTOV
0.010...1.000 x Un
0.001
ROVPTOV
40...300000 ms
35
1MRS757058 A
Issued: 2010-06-11
Value
Operation accuracy
Operate time
Minimum
Typical
Maximum
9 ms
10 ms
12 ms
Operation mode =
"Light only"
< 40 ms
Reset time
Reset ratio
Typical 0.96
Function
Value (Range)
Step
ARCSARC
0.50...40.00 x In
0.01
ARCSARC
0.05...8.00 x In
0.01
Operation mode
ARCSARC
2=Light only
3=BI controlled
Value
Operation accuracy
Function
Value (Range)
Step
Start value
MAPGAPC
-10000.0...10000.0
0.1
MAPGAPC
0...200000 ms
100
Operation mode
MAPGAPC
Over
Under
36
ABB
1MRS757058 A
Issued: 2010-06-11
Start time
Value
f<
10 mHz
df/dt
f<
< 80 ms
df/dt
< 120 ms
Reset time
< 150 ms
ABB
Parameter
Function
Value (Range)
Step
LSHDPFRQ
Freq<
Freq< AND df/dt
Freq< OR df/dt
Restore mode
LSHDPFRQ
Disabled
Auto
Manual
LSHDPFRQ
0.800...1.200 x Fn
0.001
LSHDPFRQ
-0.200...-0.005 x Fn
0.005
Operate Tm Freq
LSHDPFRQ
80...200000 ms
10
Operate Tm df/dt
LSHDPFRQ
120...200000 ms
10
LSHDPFRQ
0.800...1.200 x Fn
0.001
LSHDPFRQ
80...200000 ms
10
37
1MRS757058 A
Issued: 2010-06-11
Values (Range)
Control functions
Table 49. Synchrocheck (SECRSYN)
Characteristic
Value
Operation accuracy
Reset time
< 50 ms
Reset ratio
Typical 0.96
38
ABB
1MRS757058 A
Issued: 2010-06-11
ABB
Parameter
Values (Range)
Unit
Live dead
mode
-1=Off
1=Both Dead
2=Live L, Dead B
3=Dead L, Live B
4=Dead Bus, L
Any
5=Dead L, Bus
Any
6=One Live,
Dead
7=Not Both Live
Difference
voltage
0.01...0.50
xUn
Difference
frequency
0.001...0.100
Difference
angle
5...90
Synchrocheck
mode
Step
Default
Description
1=Both Dead
Energizing
check mode
0.01
0.05
Maximum
voltage
difference
limit
xFn
0.001
0.001
Maximum
frequency
difference
limit
deg
Maximum
angle
difference
limit
1=Off
2=Synchronous
3=Asynchronous
2=Synchronous
Synchrocheck
operation
mode
Control mode
1=Continuous
2=Command
1=Continuous
Selection of
the
synchrocheck
command or
continuous
control mode
Dead line
value
0.1...0.8
xUn
0.1
0.2
xUn
0.1
0.5
39
1MRS757058 A
Issued: 2010-06-11
Table 50. Synchronism and energizing check (SECRSYN) main settings, continued
Parameter
Values (Range)
Unit
Step
Default
Description
Close pulse
200...60000
ms
10
200
Breakerclosing pulse
duration
Max
energizing V
0.50...1.15
xUn
0.01
1.05
Maximum
voltage for
energizing
Phase shift
-180...180
deg
180
Correction of
phase
difference
between
measured
U_BUS and
U_LINE
Minimum Syn
time
0...60000
ms
10
Minimum
time to accept
synchronizing
ms
10
2000
Maximum
time to accept
synchronizing
Energizing
time
100...60000
ms
10
100
Time delay
for energizing
check
Closing time
of CB
40...250
ms
10
60
Closing time
of the breaker
40
ABB
1MRS757058 A
Issued: 2010-06-11
Value
Operation accuracy1)
Operate time accuracy in definite time mode2) + 4.0% / - 0% of the set value
Operate time accuracy in inverse time mode2) + 8.5% / - 0% of the set value
(at theoretical B in range of 1.15.0)
Also note fixed minimum operate time
(IDMT) 1 s.
Reset ratio for control operation
Reset ratio for analogue based blockings
(except run back raise voltage blocking)
ABB
41
1MRS757058 A
Issued: 2010-06-11
Table 52. On-load tap changer control with voltage regulator (OLATCC) main settings
Parameter
Function
Value (Range)
Step
OLATCC
0.000...2.000 x Un
0.001
OLATCC
1000...300000 ms
100
OLATCC
1000...300000 ms
100
OLATCC
0.0...25.0 %
0.1
OLATCC
0.0...25.0 %
0.1
OLATCC
-89...89 deg
Stability factor
OLATCC
0.0...70.0 %
0.1
OLATCC
Auto master
Auto follower
NRP
MCC
Operation mode
OLATCC
Manual
Auto single
Auto parallel
Input control
Delay characteristics
OLATCC
Inverse time
Definite time
OLATCC
500...10000 ms
100
OLATCC
1.20...18.00 % Un
0.01
1=Custom disabled
2=OC
3=UV
4=OC, UV
5=EXT
6=OC, EXT
7=UV, EXT
8=OC, UV, EXT
OLATCC
0.10...5.00 x In
0.01
OLATCC
0.10...1.20 x Un
0.01
OLATCC
0.80...2.40 x In
0.01
OLATCC
0.10...5.00 x In
0.01
OLATCC
-36...36
OLATCC
-36...36
42
ABB
1MRS757058 A
Issued: 2010-06-11
Table 52. On-load tap changer control with voltage regulator (OLATCC) main settings,
continued
Parameter
Function
Value (Range)
Step
LDC limit
OLATCC
0.00...2.00 x Un
0.01
LDC enable
OLATCC
False
True
OLATTC
6...20 s
Measurement functions
Table 53. Three-phase current measurement (CMMXU)
Characteristic
Value
Operation accuracy
Suppression of harmonics
RMS: No suppression
Value
Operation accuracy
Suppression of harmonics
ABB
43
1MRS757058 A
Issued: 2010-06-11
Value
Operation accuracy
Suppression of harmonics
RMS: No suppression
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
44
ABB
1MRS757058 A
Issued: 2010-06-11
Value
Supported RTD
sensors
Supported
resistance range
100 platinum
250 platinum
100 nickel
120 nickel
250 nickel
10 copper
TCR
TCR
TCR
TCR
TCR
TCR
0...2 k
Maximum lead
resistance (threewire
measurement)
25 per lead
Isolation
Response time
<4 s
RTD/resistance
sensing current
Operation
accuracy
mA inputs
Resistance
Temperature
2.0% or 1
1C
10 copper: 2C
Supported
current range
020 mA
Current input
impedance
44 0.1%
Operation
accuracy
Resistance
0.5% or 0.01 mA
ABB
Characteristic
Value
Operation accuracy
10 mHz
(in measurement range 35 - 75 Hz)
45
1MRS757058 A
Issued: 2010-06-11
Supervision functions
Table 60. Current circuit supervision (CCRDIF)
Characteristic
Value
Operate time1)
< 30 ms
Values (Range)
Unit
Description
Start value
0.05...0.20
x In
Minimum operate
current differential
level
Maximum operate
current
1.00...5.00
x In
Value
Operate time1)
NPS function
Delta function
< 33 ms
< 18 ms
U = 1.1 x set
Voltage change rate
< 30 ms
U = 2.0 x set
Voltage change rate
< 24 ms
1) Includes the delay of the signal output contact, fn = 50 Hz, fault voltage with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
46
ABB
1MRS757058 A
Issued: 2010-06-11
IECA070904 V3 EN
IECA070901 V3 EN
20
8 or more
ABB
47
1MRS757058 A
Issued: 2010-06-11
Character size1)
10
20
8 or more
Mounting methods:
Flush mounting
Semi-flush mounting
Semi-flush mounting in a 25 tilt
Rack mounting
Wall mounting
Mounting to a 19" equipment frame
Mounting with a RTXP 18 test switch to a
19" rack
Panel cut-out for flush mounting:
Height: 161.51 mm
Width: 165.51 mm
190
186
177
177
230
177
160
160
25
98
10 7
13 3
1 03
153
48
IECA070900 V3 EN
48
IECA070903 V3 EN
IECA070902 V3 EN
ABB
1MRS757058 A
Issued: 2010-06-11
DESCRIPTION
IED
615 series IED (including case)
Standard
IEC
Main application
Voltage protection and control
U
GUID-AD8D5903-41C6-4187-A02A-1F5C3407E335 V1 EN
ABB
49
1MRS757058 A
Issued: 2010-06-11
H B U B C CAH B C C 1 B B N 1 X D
# DESCRIPTION
4-8
A = Voltage and frequency based protection and measurement
functions, synchro-check and load shedding
B = Automatic voltage regulator
Std conf A: 5U + 12 BI + 10 BO
AEAAD
BCAAH
BCABB
BCCAH
GUID-D50DDBD0-0BBE-4347-9FBB-1BFD2BE7ECB5 V1 EN
DESCRIPTION
Communication modules (Serial/Ethernet)
AA
AB
AN
BN
BB
BD
(3 x RJ-45)
and -FX (2 x RJ-45 + 1 x LC)
Ethernet 100Base-FX (1 x LC)
Ethernet 100Base-TX (1 x RJ-45)
Ethernet 100Base-TX (2 x RJ-45 + 1 x LC)
Ethernet 100Base-TX (3 x RJ-45)
No communication module
BC
NA
NB
NC
ND
NN
50
ABB
1MRS757058 A
Issued: 2010-06-11
H B U B C CAH B C C 1 B B N 1 X D
#
11
DESCRIPTION
Communication protocols
IEC 61850
(for Ethernet communication modules and IEDs
without a communication module )
Modbus
(for Ethernet/serial or Ethernet + serial communication modules)
IEC 61850 + Modbus
(for Ethernet or serial + Ethernet communication
modules)
IEC 60870-5-103
(for serial or Ethernet + serial communication
modules)
DNP3
(for Ethernet/serial or Ethernet + serial communication modules)
GUID-5B4CE02E-BA34-4AA7-A6E6-8408A3C1763D V1 EN
H B U B C CAH B C C 1 B B N 1 X D
#
12
13
14
15
DESCRIPTION
Language
English
Front panel
Small LCD
Option 1
Arc protection (only for std conf A, requires a communication module, cannot be combined with communication modules BN or BB)
None
Option 2
None
16
17
24...60 V DC
Vacant digit
Vacant
18
Power supply
Version
Version 3.0
D
GUID-AC8BE0B1-072C-4907-92D3-3720E344F94E V1 EN
ABB
51
1MRS757058 A
Issued: 2010-06-11
Example code: H B U B C C A H B C C 1 B B N 1 X D
Your ordering code:
Digit (#)
Code
10
11
12
13
14
15
16
17
18
GUID-28A75E3D-BF45-42F0-90D8-B142E3EA28F3 V1 EN
Order number
1MRS120534-1.5
1MRS120534-3.0
1MRS120534-5.0
Order number
1MRS050696
1MRS050697
1MRS050831
1MRS050694
1MRS050695
Mounting bracket for one IED with test switch RTXP in 4U Combiflex
(RHGT 19 variant C)
2RCA022642P0001
2RCA022643P0001
19 rack mounting kit for one IED and one RTXP18 test switch (the
test switch is not included in the delivery)
2RCA021952A0003
19 rack mounting kit for one IED and one RTXP24 test switch (the
test switch is not included in the delivery)
2RCA022561A0003
52
ABB
25. Tools
The IED is delivered as a pre-configured unit.
The default parameter setting values can be
changed from the front-panel user interface,
the web-browser based user interface
(WebHMI) or the PCM600 tool in
combination with the IED-specific
connectivity package.
The Protection and Control IED Manager
PCM600 is available in three different
variants, that is PCM600, PCM600
Engineering and PCM600 Engineering Pro.
Depending on the chosen variant, PCM600
offers extensive IED configuration functions
such as IED signal configuration, application
configuration, graphical display configuration
including single line diagram configuration,
and IEC 61850 communication configuration
including horizontal GOOSE communication.
When the web-browser based user interface
is used, the IED can be accessed either
1MRS757058 A
Issued: 2010-06-11
ABB
Version
2.3
IE 7.0 or later
3.0 or later
53
1MRS757058 A
Issued: 2010-06-11
WebHMI
PCM600
PCM600
Engineering
PCM600
Engineering
Pro
Saving of IED
parameter settings in
the IED
Signal monitoring
Disturbance recorder
handling
Access control
management
IED signal
configuration (signal
matrix)
Modbus
communication
configuration
(communication
management)
DNP3 communication
configuration
(communication
management)
IEC 60870-5-103
communication
configuration
(communication
management)
Saving of IED
parameter settings in
the tool
Disturbance record
analysis
XRIO parameter
export/import
Graphical display
configuration
54
ABB
1MRS757058 A
Issued: 2010-06-11
WebHMI
PCM600
PCM600
Engineering
PCM600
Engineering
Pro
Application
configuration
IEC 61850
communication
configuration, GOOSE
(communication
configuration)
Phasor diagram
viewing
Event viewing
= Supported
ABB
55
1MRS757058 A
Issued: 2010-06-11
GUID-B89BFFF3-08F0-40D3-8F12-99FB21B3900F V1 EN
56
ABB
1MRS757058 A
Issued: 2010-06-11
GUID-E5FA44B9-524F-4B19-A002-49D39DF6D6D5 V1 EN
ABB
57
1MRS757058 A
Issued: 2010-06-11
The www.abb.com/substationautomation
portal offers you information about the
distribution automation product and service
range.
27. References
58
ABB
1MRS757058 A
Issued: 2010-06-11
IEC 61850
IEC 60617
IEC-ANSI
Three-phase non-directional
overcurrent protection, low
stage, instance 1
PHLPTOC1
3I> (1)
51P-1 (1)
Three-phase non-directional
overcurrent protection, high
stage, instance 1
PHHPTOC1
3I>> (1)
51P-2 (1)
Three-phase non-directional
overcurrent protection,
instantaneous stage, instance 1
PHIPTOC1
3I>>> (1)
50P/51P (1)
ROVPTOV1
Uo> (1)
59G (1)
ROVPTOV2
Uo> (2)
59G (2)
ROVPTOV3
Uo> (3)
59G (3)
Three-phase undervoltage
protection, instance 1
PHPTUV1
3U< (1)
27 (1)
Three-phase undervoltage
protection, instance 2
PHPTUV2
3U< (2)
27 (2)
Three-phase undervoltage
protection, instance 3
PHPTUV3
3U< (3)
27 (3)
Three-phase overvoltage
protection, instance 1
PHPTOV1
3U> (1)
59 (1)
Three-phase overvoltage
protection, instance 2
PHPTOV2
3U> (2)
59 (2)
Three-phase overvoltage
protection, instance 3
PHPTOV3
3U> (3)
59 (3)
Positive-sequence undervoltage
protection, instance 1
PSPTUV1
U1< (1)
47U+ (1)
Positive-sequence undervoltage
protection, instance 2
PSPTUV2
U1< (2)
47U+ (2)
Negative-sequence overvoltage
protection, instance 1
NSPTOV1
U2> (1)
47O- (1)
Protection
ABB
59
1MRS757058 A
Issued: 2010-06-11
IEC 61850
IEC 60617
IEC-ANSI
Negative-sequence overvoltage
protection, instance 2
NSPTOV2
U2> (2)
47O- (2)
f>/f<,df/dt (1)
81 (1)
f>/f<,df/dt (2)
81 (2)
f>/f<,df/dt (3)
81 (3)
f>/f<,df/dt (4)
81 (4)
f>/f<,df/dt (5)
81 (5)
f>/f<,df/dt (6)
81 (6)
3Ith>T
49T
TRPPTRC1
94/86 (1)
TRPPTRC2
94/86 (2)
ARCSARC1
ARC (1)
50L/50NL (1)
ARCSARC2
ARC (2)
50L/50NL (2)
ARCSARC3
ARC (3)
50L/50NL (3)
Multi-purpose protection,
instance 11)
MAPGAPC1
MAP (1)
MAP (1)
Multi-purpose protection,
instance 21)
MAPGAPC2
MAP (2)
MAP (2)
Multi-purpose protection,
instance 31)
MAPGAPC3
MAP (3)
MAP (3)
LSHDPFRQ1
UFLS/R (1)
81LSH (1)
LSHDPFRQ2
UFLS/R (2)
81LSH (2)
LSHDPFRQ3
UFLS/R (3)
81LSH (3)
LSHDPFRQ4
UFLS/R (4)
81LSH (4)
LSHDPFRQ5
UFLS/R (5)
81LSH (5)
Control
60
ABB
1MRS757058 A
Issued: 2010-06-11
IEC 61850
IEC 60617
IEC-ANSI
Circuit-breaker control
CBXCBR1
I <-> O CB
I <-> O CB
Disconnector position
indication, instance 1
DCSXSWI1
I <-> O DC (1)
I <-> O DC (1)
Disconnector position
indication, instance 2
DCSXSWI2
I <-> O DC (2)
I <-> O DC (2)
Disconnector position
indication, instance 3
DCSXSWI3
I <-> O DC (3)
I <-> O DC (3)
ESSXSWI1
I <-> O ES
I <-> O ES
TPOSSLTC1
TPOSM
84M
OLATCC1
COLTC
90V
SECRSYN1
SYNC
25
TCS (1)
TCM (1)
TCS (2)
TCM (2)
CCRDIF1
MCS 3I
MCS 3I
SEQRFUF1
FUSEF
60
Disturbance recorder
RDRE1
Three-phase current
measurement, instance 1
CMMXU1
3I
3I
CSMSQI1
I1, I2, I0
I1, I2, I0
Three-phase voltage
measurement
VMMXU1
3U
3U
RESVMMXU1
Uo
Vn
VSMSQI1
U1, U2, U0
U1, U2, U0
Condition monitoring
Measurement
ABB
61
1MRS757058 A
Issued: 2010-06-11
IEC 61850
IEC 60617
IEC-ANSI
PEMMXU1
P, E
P, E
RTD/mA measurement
XRGGIO130
X130 (RTD)
X130 (RTD)
Frequency measurement
FMMXU1
Product version
History
A/2010-06-11
3.0
First release
62
ABB
63
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone
+358 10 22 11
Fax
+358 10 22 41094
www.abb.com/substationautomation
Contact us