SION Vacuum
Circuit-Breakers
3AE5 and 3AE1
Medium-Voltage Equipment
Catalog HG 11.02 2014
Invalid:
Catalog HG 11.02 2013
Page
Description
General
12
13
Equipment Selection
15
16
Conguration example
17
18
Secondary equipment
33
Additional equipment
39
41
Technical Data
47
48
Dimension drawings
72
80
80
Circuit diagrams
82
Annex
89
Inquiry form
90
Conguration instructions
91
Conguration aid
Foldout page
R-HG11-357.tif
Description
Contents
Contents
Page
Description
General
Construction and mode of operation
R-HG11-174.tif
Switching medium
Pole assemblies
Operating mechanism
Trip-free mechanism
Releases
Interlocking
Low-voltage interface
Withdrawable module
10
Withdrawable module
with make-proof earthing switch
10
Circuit-breaker on truck
for retrotting 8B switchgear
10
Standards
11
Maintenance-free design
11
Interlocking
11
12
12
Dielectric strength
12
Basic equipment
13
13
Description
General
R-HG11-381.eps
R-HG11-373.tif
Description
General
R-HG11-375.tif
R-HG11-376.eps
R-HG11-362.tif
R-HG11-363.eps
Description
Construction and mode of operation
Switching medium
3AE5
Pole assemblies
HG11-2501 eps
1 Cover of
low-voltage interface
4
5
Pole structure
3 Separating shell
to the operating
mechanism
4 Upper connection
5 Vacuum interrupter
6 Pole shell
7 Lower connection
8 Insulator
Operating mechanism
3AE1 without cover
9 Mechanism
mounting plate
10
10 Auxiliary switch
11 1st release
11
12 Terminal strip
13 Motor
HG11-2502b eps
2 Central control
board
Front view
Operating mechanism
The whole operating mechanism with motor (13), releases
(11), indicators and actuating devices is mounted on the
mechanism mounting plate (9). This compact design enables
very fast operating times.
HG11-2500a eps
14 Closing solenoid
15 Closing spring
16 Gear
17 Opening spring
Trip-free mechanism
SION vacuum circuit-breakers have a trip-free mechanism. In
the event of an opening command being given after a closing operation has been initiated, the moving contacts return
to the open position and remain there even if the closing
command is sustained. This means that the contacts of the
vacuum circuit-breakers are momentarily in the closed position, which is permissible.
For charging the closing spring (15), the motor (13) operates in short-time duty. Therefore the voltage and power
consumption might differ from the data of the motor rating
plate.
9
12
10
13
11
HG11-2839a eps
3AE1
HG11-2838 eps
The vacuum switching technology, proven and fully developed for more than 40 years, serves as arc-quenching principle by using vacuum interrupters.
Operating mechanism
3AE5 without cover
9 Mechanism
mounting plate
10 Auxiliary switch
14
11 1st release
15
12 Terminal strip
16
17
13 Motor
14 Closing solenoid
15 Closing spring
16 Gear
17 Opening spring
Description
Construction and mode of operation
Releases
Closing solenoid
Shunt releases are used for automatic tripping of the circuitbreaker by suitable protection relays and for deliberate tripping by electrical means. They are intended for connection to
an external power supply (DC or AC voltage).
At the interface of the mechanical interlocking of the circuitbreaker, sensors on the switchgear side can check the switch
position and prevent the associated disconnector from being
operated while the circuit-breaker is closed. The system also
prevents the circuit-breaker from being closed while the
associated disconnector is in a faulty position.
Current-transformer operated releases comprise a storedenergy mechanism, an unlatching mechanism, and an electromagnetic system. They are used when there is no external
source of auxiliary power (e.g. a battery). Tripping is effected
by means of a protection relay (e.g. overcurrent-time protection) acting on the current-transformer operated release.
Undervoltage releases
Undervoltage releases comprise a stored-energy mechanism,
an unlatching mechanism and an electromagnetic system
which is permanently connected to the secondary or auxiliary voltage while the circuit-breaker is closed. If the voltage
falls below a predetermined value, unlatching of the release
is enabled and the circuit-breaker is opened via the storedenergy mechanism.
The maximum possible equipment are two releases according to page 34. The consumption data of the releases is
listed on pages 80 / 81.
Closing and anti-pumping
In the standard version, the circuit-breakers can be remoteclosed electrically. In addition, they can be mechanically
closed locally by direct unlatching of the closing spring.
If constant electrical signals for CLOSE and OPEN commands
are present at the circuit-breaker at the same time, the circuitbreaker will carry out an OPEN-CLOSE-OPEN or a CLOSE-OPEN
operating sequence. A new CLOSE command is given only
following a short-time interruption of the closing signal. In
this manner, continuous closing and opening (= pumping)
is prevented.
Interlocking
Mechanical interlocking
Description
Construction and mode of operation
Withdrawable module
Withdrawable module 3AE1
1
1 Fixed contact
2 Bushing
3 Shutter
4 Contact
5 Contact arm
HG11-2815 eps
6 Cartridge
7 Low-voltage
interface
8 Circuit-breaker
9 Withdrawable part
Retrot
10
R-HG11-364.eps
The withdrawable module contains all necessary components for the circuit-breaker compartment of a switchgear
panel. It consists of the circuit-breaker mounted on a withdrawable part, with contact arms, tted in a cartridge with
side and rear walls. The withdrawable module is equipped
with bushings, xed contacts, shutters and shutter mechanism. The side and rear walls form the tested connection
compartment.
Description
Standards, maintenance-free design and interlocking
Standards
The circuit-breakers conform to the following standards:
IEC 62271-1
IEC 62271-100
All circuit-breakers full the endurance classes C2, E2, M2
and S1 according to IEC 62271-100.
Fixed-mounted
OPEN
CLOSED
Disconnecting
CLOSED
on withdrawable part
and in withdrawable
module
OPEN
OPEN
CLOSED
on withdrawable part,
in withdrawable
module and with
earthing switch
OPEN
Earthing
on withdrawable part,
in withdrawable
module and with
earthing switch
OPEN
CLOSED
CLOSED or
OPEN
CLOSED or
OPEN
Interlocking of
earthing switch
against closing
Interlockable
Active
Active
Active
Active
CLOSED
Disconnecting
Interlocking of
Interlocking of
Interlocking of
vacuum circuitracking the
withdrawable part
breaker against
in the switchgear withdrawable part
closing (optionally panel (latching of
(between
with key-operated locking handles)
disconnected,
interlock)
test and service
in disconnected
position)
position
Switching state
of earthing
switch
Switching state
of vacuum
circuit-breaker
Service position
Racking
Vacuum
circuit-breaker
Disconnected
position
Interlocking
Active
Active
OPEN
OPEN
Active
Active
Active
Active
OPEN
Active
OPEN
Active
OPEN
Active
OPEN
11
Description
Ambient conditions, current carrying capacity and dielectric strength
Ambient conditions
The circuit-breakers are designed for the normal operating
conditions dened in IEC 62271-100. Condensation can
occasionally occur under the ambient conditions shown
opposite.
40C
HG11-2515b_en.eps
-5C
Class 3K4 1)
Class 3B1
Class 3M2
Class 3C2 3)
Class 3S2 2)
2
Example
Site altitude H
12
Description
Basic equipment, product range overview
Basic equipment
Equipment
Minimum equipment
Alternative equipment
Remarks
Operating mechanism
Closing
None
None
1st release
2nd release
Varistor circuit
Auxiliary switch
Plug connection
Anti-pumping
Circuit-breaker tripping
signal
Operations counter
Position switches for
withdrawable part
Mechanical interlocking
Installation accessories
Undervoltage release, c.t.-operated release For SION 3AE5, only shunt releases are possible
Shunt release, undervoltage release,
Combination of 2 undervoltage releases or 2 c.t.c.t.-operated release
operated releases is not possible. For SION 3AE5,
the combination of undervoltage and c.t.-operated
releases is not possible either
None
For limiting switching overvoltages
12 NO + 12 NC
24-pole plug,
64-pole plug
None
Possible
12 NO + 12 NC not available
with 24-pole plug
None
None
contact, xed contacts and bushings, complete withdrawable module with and without
make-proof earthing switch
Rated
voltage
Rated
normal current
Type
kV
kA
3AE10 / 3AE50
3AE50
3AE10
7.2
7.2
7.2
16 / 20 / 25 / 31.5
16 / 20 / 25 / 31.5
25
31.5
3AE11/ 3AE51
3AE51
3AE11
12
12
12
3AE13
24
800 / 1250
1600
2000
2000 / 2500
1250 / 2000
40
2500 / 3150
16 / 20 / 25 / 31.5
800 / 1250
16 / 20 / 25 / 31.5
1600
25
2000 / 2500
31.5
2000 / 2500
1250 / 2000
40
2500 / 3150
12.5 / 16 / 25
800 / 1250
12.5 / 16 / 25
1600
25
2000 / 2500
31.5
800 / 1250
31.5
2000 / 2500
1250 / 2000 /
40
2500 / 3150
12.5
800 / 1250
16
800 / 1250 / 2000
800 / 1250 /
20
2000 / 2500
800 / 1250 /
25
2000 / 2500
160
210
275
275
310
205
275
310
205
275
310
310
Note: The circuit-breaker is available with various installation accessories: These versions can be congured from page 18.
13
R-HG11-377.tif
14
Equipment Selection
Contents
Contents
Page
Equipment Selection
15
16
Conguration example
17
18
Voltage level 12 kV
22
28
Voltage level 24 kV
32
Secondary equipment
R-HG11-378.tif
Release combination
33
33
34
34
35
36
37
38
Additional equipment
39
Accessories catalog
41
R-HG11-176.eps
Rating plate
15
Equipment Selection
Order number structure
Special versions ()
In case of special versions, -Z is added to the order number and a descriptive order code follows. If several special
versions are required, the sufx -Z is listed only once. If a
requested special version is not in the catalog and can therefore not be ordered via order code, it has to be identied
with Y 9 9 after consultation. The agreement hereto is made
directly between your responsible sales partner and the
order processing department at Siemens.
Order codes
Individual equipment versions, marked with 9 or Z in the
9th to 16th position, are explained more in detail by a 3-digit
order code. Several order codes can be added to the order
number in succession and in any sequence.
a: alphabetical
Position:
Order No.:
1st position
Primary part
Superior group
Switching devices
2nd position
Main group
Circuit-breaker
3rd position
Subgroup
Circuit-breaker type series
4th position
Circuit-breaker version
5th position
6th position
7th
position
8th position
Secondary part
Secondary equipment, operating mechanism,
releases, operating voltages and
further auxiliary equipment
Order codes
Groups of 3 after the Order No.
Format: a n a
Special versions ()
Initiated with -Z
Groups of 3 after the Order No.
Format: a n n
16
n: numerical
10 11 12
13 14 15 16
3 A
Order codes
Equipment Selection
Conguration example
Conguration example
In order to simplify the selection of the correct order number for the requested circuit-breaker type, you will nd two
conguration examples below. Two complete circuit-breakers
have been congured as an example.
Conguration example 1: SION 3AE5 vacuum withdrawable module (vacuum circuit-breaker on withdrawable part in cartridge)
Position:
Order No.:
3 A
10 11 12
13 14 15 16
Order codes
3 A
Conguration example
SION vacuum circuit-breaker
Rated voltage Ur = 12 kV, 50 / 60 Hz
Rated lightning impulse withstand voltage Up = 75 kV
Rated short-circuit breaking current ISC = 25 kA
Rated normal current Ir = 1250 A
With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug
Frequency of the operating voltage 50 Hz and DC, operating instructions and rating plate in english
Hand crank
Example for Order No.:
Order codes:
2 A C
K N 2
10 11 12
13 14 15 16
Order No.:
3 A
Order codes
3 A
Conguration example
SION vacuum circuit-breaker
Rated voltage Ur = 17.5 kV, 50 / 60 Hz
Rated lightning impulse withstand voltage Up = 95 kV
Rated short-circuit breaking current ISC = 25 kA
Rated normal current Ir = 1250 A
Pole-center distance = 210 mm
Width across ats = 310 mm
With mechanical interlocking, circuit-breaker tripping signal, auxiliary switch 12 NO + 12 NC and 64-pole plug
Frequency of the operating voltage 50 Hz and DC, operating instructions and rating plate in english
Hand crank
Example for Order No.:
2 A C
Order codes:
K N 2
17
Equipment Selection
Circuit-breaker and equipment package
7.2 kV
Position:
Order No.:
3 A
8 9 12
14 16
Order codes
16
40/42
210
2
160
150
7.2
60
20
20
50/52
210
160
150
Special version Ud = 32 kV
Legend:
18
310
800
3 A
2 1
310
1250
3 A
2 2
310
1600
3 A
2 3
275
800
3 A
2 1
275
1250
3 A
2 2
205
800
3 A
2 1
205
1250
3 A
2 2
310
800
3 A
2 1
310
1250
3 A
2 2
310
1600
3 A
2 3
275
800
3 A
2 1
275
1250
3 A
2 2
205
800
3 A
2 1
205
1250
3 A
2 2
310
800
3 A
2 1
310
1250
3 A
2 2
310
1600
3 A
2 3
275
800
3 A
2 1
275
1250
3 A
2 2
205
800
3 A
2 1
205
1250
3 A
2 2
310
800
3 A
3 1
310
1250
3 A
3 2
310
1600
3 A
3 3
275
800
3 A
3 1
275
1250
3 A
3 2
205
800
3 A
3 1
205
1250
3 A
3 2
310
800
3 A
3 1
310
1250
3 A
3 2
310
1600
3 A
3 3
275
800
3 A
3 1
275
1250
3 A
3 2
205
800
3 A
3 1
205
1250
3 A
3 2
310
800
3 A
3 1
310
1250
3 A
3 2
310
1600
3 A
3 3
275
800
3 A
3 1
275
1250
3 A
3 2
205
800
3 A
3 1
205
1250
3 A
3 2
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
See page 39
20
See pages 36 to 38
60
Retrot
7.2
Ir
mm
mm
On withdrawable part
with complete contact system *
kA
On withdrawable part
Ima
Pole-center distance
ISC
kA
Ud
kV
Up
kV
Ur
kV
Rated voltage
for 50 / 60 Hz
Orderable versions
Equipment Selection
Position:
Order No.:
3 A
8 9 12
14 16
See page 39
7.2 kV
See pages 36 to 38
Order codes
60
20
25
63/65
210
310
310
310
275
275
205
205
310
310
310
275
275
205
205
310
310
310
275
275
205
205
310
310
310
275
275
205
205
310
310
310
275
275
205
205
310
310
310
275
275
205
205
800
1250
1600
800
1250
800
1250
800
1250
1600
800
1250
800
1250
800
1250
1600
800
1250
800
1250
800
1250
1600
800
1250
800
1250
800
1250
1600
800
1250
800
1250
800
1250
1600
800
1250
800
1250
160
150
7.2
60
20
31.5
80/82
210
160
150
Special version Ud = 32 kV
Isc **) = 26.3 kA
Legend:
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
8
8
8
7
7
6
6
5
5
5
4
4
3
3
2
2
2
1
1
0
0
8
8
8
7
7
6
6
5
5
5
4
4
3
3
2
2
2
1
1
0
0
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
1
2
3
1
2
1
2
1
2
3
1
2
1
2
1
2
3
1
2
1
2
1
2
3
1
2
1
2
1
2
3
1
2
1
2
1
2
3
1
2
1
2
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
Retrot
7.2
Ir
mm
mm
On withdrawable part
with complete contact system *
kA
On withdrawable part
Ima
Pole-center distance
Isc
kA
Ud
kV
Up
kV
Ur
kV
Rated voltage
for 50 / 60 Hz
Orderable versions
Z
Z
E
E
1
4
6
6
19
Equipment Selection
Circuit-breaker and equipment package
7.2 kV
Position:
Order No.:
3 A
8 9 12
14 16
Order codes
16
40/42
210
2
160
150
7.2
60
20
20
50/52
210
160
150
Special version Ud = 32 kV
Legend:
20
310
800
3 A
2 1
310
1250
3 A
2 2
275
800
3 A
2 1
275
1250
3 A
2 2
205
800
3 A
2 1
205
1250
3 A
2 2
310
800
3 A
2 1
310
1250
3 A
2 2
275
800
3 A
2 1
275
1250
3 A
2 2
205
800
3 A
2 1
205
1250
3 A
2 2
310
800
3 A
2 1
310
1250
3 A
2 2
275
800
3 A
2 1
275
1250
3 A
2 2
205
800
3 A
2 1
205
1250
3 A
2 2
310
800
3 A
3 1
310
1250
3 A
3 2
275
800
3 A
3 1
275
1250
3 A
3 2
205
800
3 A
3 1
205
1250
3 A
3 2
310
800
3 A
3 1
310
1250
3 A
3 2
275
800
3 A
3 1
275
1250
3 A
3 2
205
800
3 A
3 1
205
1250
3 A
3 2
310
800
3 A
3 1
310
1250
3 A
3 2
275
800
3 A
3 1
275
1250
3 A
3 2
205
800
3 A
3 1
205
1250
3 A
3 2
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
See page 39
20
See pages 36 to 38
60
Retrot
7.2
Ir
mm
mm
On withdrawable part
with complete contact system *
kA
On withdrawable part
Ima
Pole-center distance
ISC
kA
Ud
kV
Up
kV
Ur
kV
Rated voltage
for 50 / 60 Hz
Orderable versions
Equipment Selection
Position:
Order No.:
3 A
8 9 12
14 16
See page 39
7.2 kV
See pages 36 to 38
Order codes
60
20
25
63/65
210
310
310
310
275
275
205
205
310
310
275
275
205
205
310
310
275
275
205
205
310
310
310
310
275
275
205
205
310
310
275
275
205
205
310
310
275
275
205
205
310
310
310
310
800
1250
2000
800
1250
800
1250
800
1250
800
1250
800
1250
800
1250
800
1250
800
1250
800
1250
2000
2500
800
1250
800
1250
800
1250
800
1250
800
1250
800
1250
800
1250
800
1250
1250
2000
2500
3150
160
150
7.2
60
20
31.5
80/82
210
160
150
7.2
60
20
40
100/104
Special version Ud = 32 kV
Legend:
210
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
3
3
3
3
3
3
3
3
3
3
A
A
A
A
A
A
A
A
A
A
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
8
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1
1
0
0
8
8
8
8
7
7
6
6
5
5
4
4
3
3
2
2
1
1
0
0
8
8
8
8
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
6
6
6
6
1
2
4
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
4
6
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
2
4
6
7
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
Retrot
7.2
Ir
mm
mm
On withdrawable part
with complete contact system *
kA
On withdrawable part
Ima
Pole-center distance
ISC
kA
Ud
kV
Up
kV
Ur
kV
Rated voltage
for 50 / 60 Hz
Orderable versions
21
Equipment Selection
Circuit-breaker and equipment package
12 kV
Position:
Order No.:
3 A
8 9 12
14 16
Order codes
28
16
40/42
210
2
160
150
12
75
28
20
50/52
210
160
150
Special version Ud = 42 kV
Up = 95 kV
Legend:
22
800
2 1
1250
2 2
310
1600
2 3
275
800
2 1
275
1250
2 2
205
800
2 1
205
1250
2 2
310
800
2 1
310
1250
2 2
310
1600
2 3
275
800
2 1
275
1250
2 2
205
800
2 1
205
1250
2 2
310
800
2 1
310
1250
2 2
310
1600
2 3
275
800
2 1
275
1250
2 2
205
800
2 1
205
1250
2 2
310
800
3 1
310
1250
3 2
310
1600
3 3
275
800
3 1
275
1250
3 2
205
800
3 1
205
1250
3 2
310
800
3 1
310
1250
3 2
310
1600
3 3
275
800
3 1
275
1250
3 2
205
800
3 1
205
1250
3 2
310
800
3 1
310
1250
3 2
310
1600
3 3
275
800
3 1
275
1250
3 2
205
800
3 1
205
1250
3 2
310
310
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
See page 39
75
See pages 36 to 38
12
Ir
Retrot
mm
mm
kA
On withdrawable part
with complete contact system *
Ima
On withdrawable part
Pole-center distance
Isc
kA
Ud
kV
Up
kV
Ur
kV
Rated voltage
for 50 / 60 Hz
Orderable versions
Z
Z
E
E
1
9
3
5
Equipment Selection
Position:
Order No.:
3 A
8 9 12
14 16
See page 39
12 kV
See pages 36 to 38
Order codes
75
28
25
63/65
210
160
150
Special version Ud = 42 kV
800
3 A
4 1
1250
4 2
310
1600
4 3
275
800
4 1
275
1250
4 2
205
800
4 1
205
1250
4 2
310
800
4 1
310
1250
4 2
310
1600
4 3
275
800
4 1
275
1250
4 2
205
800
4 1
205
1250
4 2
310
800
4 1
310
1250
4 2
310
1600
4 3
275
800
4 1
275
1250
4 2
205
800
4 1
205
1250
4 2
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
Up = 95 kV
310
310
Retrot
12
Ir
mm
mm
On withdrawable part
with complete contact system *
kA
On withdrawable part
Ima
Pole-center distance
Isc
kA
Ud
kV
Up
kV
Ur
kV
Rated voltage
for 50 / 60 Hz
Orderable versions
23
Equipment Selection
Circuit-breaker and equipment package
12 kV
Position:
Order No.:
3 A
8 9 12
14 16
Order codes
31.5
80/82
210
2
160
150
310
800
3 A
5 1
310
1250
3 A
5 2
310
1600
3 A
5 3
275
800
3 A
5 1
275
1250
3 A
5 2
205
800
3 A
5 1
205
1250
3 A
5 2
310
800
3 A
5 1
310
1250
3 A
5 2
310
1600
3 A
5 3
275
800
3 A
5 1
275
1250
3 A
5 2
205
800
3 A
5 1
205
1250
3 A
5 2
310
800
3 A
5 1
310
1250
3 A
5 2
310
1600
3 A
5 3
275
800
3 A
5 1
275
800
3 A
5 2
205
1250
3 A
5 1
205
1250
3 A
5 2
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
See page 39
28
See pages 36 to 38
75
Retrot
12
Ir
mm
mm
On withdrawable part
with complete contact system *
kA
On withdrawable part
Ima
Pole-center distance
Isc
kA
Ud
kV
Up
kV
Ur
kV
Rated voltage
for 50 / 60 Hz
Orderable versions
Special version Ud = 42 kV
Up = 95 kV
75
275
800
3 A
4 1
W 6
275
1250
3 A
4 2
W 6
210
275
1600
3 A
4 3
W 6
160
275
800
3 A
5 1
W 6
275
1250
3 A
5 2
W 6
275
1600
3 A
5 3
W 6
Up = 95 kV
28
25
31.5
63/65
80/82
160
210
Special version Ud = 42 kV
24
Equipment Selection
Position:
Order No.:
3 A
8 9 12
14 16
See page 39
12 kV
See pages 36 to 38
Order codes
12
75
28
16
40/42
210
160
150
12
75
28
20
50/52
210
160
150
Special version Ud = 42 kV
Legend:
800
3 A
2 1
1250
3 A
2 2
275
800
3 A
2 1
275
1250
3 A
2 2
205
800
3 A
2 1
205
1250
3 A
2 2
310
800
3 A
2 1
310
1250
3 A
2 2
275
800
3 A
2 1
275
1250
3 A
2 2
205
800
3 A
2 1
205
1250
3 A
2 2
310
800
3 A
2 1
310
1250
3 A
2 2
275
800
3 A
2 1
275
1250
3 A
2 2
205
800
3 A
2 1
205
1250
3 A
2 2
310
800
3 A
3 1
310
1250
3 A
3 2
275
800
3 A
3 1
275
1250
3 A
3 2
205
800
3 A
3 1
205
1250
3 A
3 2
310
800
3 A
3 1
310
1250
3 A
3 2
275
800
3 A
3 1
275
1250
3 A
3 2
205
800
3 A
3 1
205
1250
3 A
3 2
310
800
3 A
3 1
310
1250
3 A
3 2
275
800
3 A
3 1
275
1250
3 A
3 2
205
800
3 A
3 1
205
1250
3 A
3 2
310
310
Ir
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
Retrot
mm
mm
kA
On withdrawable part
with complete contact system *
Ima
On withdrawable part
Pole-center distance
ISC
kA
Ud
kV
Up
kV
Ur
kV
Rated voltage
for 50 / 60 Hz
Orderable versions
25
Equipment Selection
Circuit-breaker and equipment package
12 kV
Position:
Order No.:
3 A
8 9 12
14 16
Order codes
25
63/65
210
2
160
150
12
75
28
31.5
80/82
210
160
150
Special version Ud = 42 kV
Legend:
26
310
800
3 A
4 1
310
1250
3 A
4 2
310
2000
3 A
4 4
310
2500
3 A
4 6
275
800
3 A
4 1
275
1250
3 A
4 2
205
800
3 A
4 1
205
1250
3 A
4 2
310
800
3 A
4 1
310
1250
3 A
4 2
275
800
3 A
4 1
275
1250
3 A
4 2
205
800
3 A
4 1
205
1250
3 A
4 2
310
800
3 A
4 1
310
1250
3 A
4 2
275
800
3 A
4 1
275
1250
3 A
4 2
205
800
3 A
4 1
205
1250
3 A
4 2
310
800
3 A
5 1
310
1250
3 A
5 2
310
2000
3 A
5 4
310
2500
3 A
5 6
275
800
3 A
5 1
275
1250
3 A
5 2
205
800
3 A
5 1
205
1250
3 A
5 2
310
800
3 A
5 1
310
1250
3 A
5 2
275
800
3 A
5 1
275
1250
3 A
5 2
205
800
3 A
5 1
205
1250
3 A
5 2
310
800
3 A
5 1
310
1250
3 A
5 2
275
800
3 A
5 1
275
1250
3 A
5 2
205
800
3 A
5 1
205
1250
3 A
5 2
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
See page 39
28
See pages 36 to 38
75
Retrot
12
Ir
mm
mm
On withdrawable part
with complete contact system *
kA
On withdrawable part
Ima
Pole-center distance
ISC
kA
Ud
kV
Up
kV
Ur
kV
Rated voltage
for 50 / 60 Hz
Orderable versions
Equipment Selection
Position:
Order No.:
3 A
8 9 12
14 16
See page 39
12 kV
See pages 36 to 38
Order codes
40
28
On withdrawable part
with complete contact system *
75
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
100/104 210
310
1250
3 A
6 2
310
2000
3 A
6 4
310
2500
3 A
6 6
310
3150
3 A
6 7
275
800
3 A
5 1
W 6
275
1250
3 A
5 2
W 6
275
1250
3 A
5 2
W 6
275
2500
3 A
5 6
W 6
275
1250
3 A
6 2
W 6
275
2500
3 A
6 6
W 6
275
3150
3 A
6 7
W 6
Ir
Retrot
mm
On withdrawable part
12
mm
kA
Ima
ISC
kA
Pole-center distance
Ud
kV
Up
kV
Ur
kV
Rated voltage
for 50 / 60 Hz
Orderable versions
160
210
40
100/104 210
Special version Ud = 42 kV
1) W63 is absolutely necessary as order code
Legend:
27
Equipment Selection
Position:
Order No.:
3 A
8 9 12
14 16
See page 39
17.5 kV
See pages 36 to 38
Order codes
On withdrawable part
17.5
95
38
12.5
31/33
210
310
800
3 A
1 1
310
1250
3 A
1 2
310
1600
3 A
1 3
275
800
3 A
1 1
275
1250
3 A
1 2
205
800
3 A
1 1
205
1250
3 A
1 2
310
800
3 A
1 1
310
1250
3 A
1 2
310
1600
3 A
1 3
275
800
3 A
1 1
275
1250
3 A
1 2
205
800
3 A
1 1
205
1250
3 A
1 2
310
800
3 A
1 1
310
1250
3 A
1 2
310
1600
3 A
1 3
275
800
3 A
1 1
275
1250
3 A
1 2
205
800
3 A
1 1
205
1250
3 A
1 2
310
800
3 A
2 1
310
1250
3 A
2 2
310
1600
3 A
2 3
275
800
3 A
2 1
275
1250
3 A
2 2
205
800
3 A
2 1
205
1250
3 A
2 2
310
800
3 A
2 1
310
1250
3 A
2 2
310
1600
3 A
2 3
275
800
3 A
2 1
275
1250
3 A
2 2
205
800
3 A
2 1
205
1250
3 A
2 2
310
800
3 A
2 1
310
1250
3 A
2 2
310
1600
3 A
2 3
275
800
3 A
2 1
275
1250
3 A
2 2
205
800
3 A
2 1
205
1250
3 A
2 2
Ir
2
160
150
17.5
95
38
16
40/42
210
160
150
Legend:
28
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
Retrot
mm
mm
kA
Ima
On withdrawable part
with complete contact system *
Pole-center distance
ISC
kA
Ud
kV
Up
kV
Ur
kV
Rated voltage
for 50 / 60 Hz
Orderable versions
Equipment Selection
Position:
Order No.:
3 A
8 9 12
14 16
See page 39
17.5 kV
See pages 36 to 38
Order codes
On withdrawable part
17.5
95
38
25
63/65
210
310
800
3 A
4 1
310
1250
3 A
4 2
310
1600
3 A
4 3
275
800
3 A
4 1
275
1250
3 A
4 2
205
800
3 A
4 1
205
1250
3 A
4 2
310
800
3 A
4 1
310
1250
3 A
4 2
310
1600
3 A
4 3
275
800
3 A
4 1
275
1250
3 A
4 2
205
800
3 A
4 1
205
1250
3 A
4 2
310
800
3 A
4 1
310
1250
3 A
4 2
310
1600
3 A
4 3
275
800
3 A
4 1
275
1250
3 A
4 2
205
800
3 A
4 1
205
1250
3 A
4 2
275
800
3 A
4 1
W 6
275
1250
3 A
4 2
W 6
275
1600
3 A
4 3
W 6
Ir
160
150
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
Retrot
mm
mm
kA
Ima
On withdrawable part
with complete contact system *
Pole-center distance
ISC
kA
Ud
kV
Up
kV
Ur
kV
Rated voltage
for 50 / 60 Hz
Orderable versions
95
38
25
63/65
160
210
29
Equipment Selection
Position:
Order No.:
3 A
8 9 12
14 16
See page 39
17.5 kV
See pages 36 to 38
Order codes
95
38
12.5
31/33
210
2
160
150
17.5
95
38
16
40/42
210
160
150
17.5
Legend:
30
95
38
25
63/65
210
310
800
3 A
1 1
310
1250
3 A
1 2
275
800
3 A
1 1
275
1250
3 A
1 2
205
800
3 A
1 1
205
1250
3 A
1 2
310
800
3 A
1 1
310
1250
3 A
1 2
275
800
3 A
1 1
275
1250
3 A
1 2
205
800
3 A
1 1
205
1250
3 A
1 2
310
800
3 A
1 1
310
1250
3 A
1 2
275
800
3 A
1 1
275
1250
3 A
1 2
205
800
3 A
1 1
205
1250
3 A
1 2
310
800
3 A
2 1
310
1250
3 A
2 2
275
800
3 A
2 1
275
1250
3 A
2 2
205
800
3 A
2 1
205
1250
3 A
2 2
310
800
3 A
2 1
310
1250
3 A
2 2
275
800
3 A
2 1
275
1250
3 A
2 2
205
800
3 A
2 1
205
1250
3 A
2 2
310
800
3 A
2 1
310
1250
3 A
2 2
275
800
3 A
2 1
275
1250
3 A
2 2
205
800
3 A
2 1
205
1250
3 A
2 2
310
800
3 A
4 1
310
1250
3 A
4 2
310
2000
3 A
4 4
310
2500
3 A
4 6
275
800
4 1
275
1250
4 2
205
800
4 1
205
1250
4 2
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
Retrot
17.5
Ir
mm
mm
On withdrawable part
with complete contact system *
kA
On withdrawable part
Ima
Pole-center distance
ISC
kA
Ud
kV
Up
kV
Ur
kV
Rated voltage
for 50 / 60 Hz
Orderable versions
*) Can also be ordered without withdrawable part, see page 35, 13th position
Equipment Selection
Position:
Order No.:
3 A
8 9 12
14 16
See page 39
17.5 kV
See pages 36 to 38
Order codes
On withdrawable part
17.5
95
38
25
63/65
160
310
800
4 1
310
1250
4 2
275
800
4 1
275
1250
4 2
205
800
4 1
205
1250
4 2
310
800
4 1
310
1250
4 2
275
800
4 1
275
1250
4 2
205
800
4 1
205
1250
4 2
310
800
5 1
310
1250
5 2
310
2000
5 4
310
2500
5 6
275
800
5 1
275
1250
5 2
205
800
5 1
205
1250
5 2
310
800
5 1
310
1250
5 2
275
800
5 1
275
1250
5 2
205
800
5 1
205
1250
5 2
310
800
5 1
310
1250
5 2
275
800
5 1
275
1250
5 2
205
800
5 1
205
1250
5 2
310
1250
6 2
310
2000
6 4
310
2500
6 6
310
3150
6 7
Ir
150
17.5
95
38
31.5
80/82
210
160
150
17.5
95
38
40
100/104 210
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
Retrot
mm
mm
kA
Ima
On withdrawable part
with complete contact system *
Pole-center distance
ISC
kA
Ud
kV
Up
kV
Ur
kV
Rated voltage
for 50 / 60 Hz
Orderable versions
2
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
Legend:
100/104 210
275
800
3 A
5 1
W 6
275
1250
3 A
5 2
W 6
275
1250
3 A
5 2
W 6
275
2500
3 A
5 6
W 6
275
1250
3 A
6 2
W 6
275
2500
3 A
6 6
W 6
275
3150
3 A
6 7
W 6
*) Can also be ordered without withdrawable part, see page 35, 13th position
31
Equipment Selection
Circuit-breaker and equipment package
24 kV
Position:
Order No.:
3 A
8 9 12
14 16
Order codes
12.5
31/33
210
24
125
50
16
40/42
210
310
310
310
310
310
310
310
310
310
310
310
310
310
310
310
310
310
310
310
310
310
310
310
310
800
1250
800
1250
2000
800
1250
2000
800
1250
2000
2500
800
1250
2000
2500
800
1250
2000
2500
800
1250
2000
2500
275
24
125
50
20
50/52
210
275
24
125
50
25
63/65
210
275
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
2
2
2
2
2
5
5
5
2
2
2
2
5
5
5
5
2
2
2
2
5
5
5
5
1
1
2
2
2
2
2
2
3
3
3
3
3
3
3
3
4
4
4
4
4
4
4
4
1
2
1
2
4
1
2
4
1
2
4
6
1
2
4
6
1
2
4
6
1
2
4
6
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
V
See page 39
50
See pages 36 to 38
125
Retrot
24
Ir
mm
mm
On withdrawable part
with complete contact system *
kA
On withdrawable part
Ima
Pole-center distance
ISC
kA
Ud
kV
Up
kV
Ur
kV
Rated voltage
for 50 / 60 Hz
Orderable versions
Special version Ud = 55 kV
1)
Special version Ud = 65 kV
2)
125
50
25
63/65
210
320
1250
3 A
4 2
W 6
275
320
2000
3 A
4 4
W 6
320
2500
3 A
4 6
W 6
5 1)
Special version Ud = 55 kV
1) With special version E55 (selection is possible
if 13th position 0, 1, 2, 3 and 5)
2) With special version E65 (selection is possible
if 13th position 0 and 1)
3) W63 is absolutely necessary as order code
Legend:
32
Equipment Selection
Secondary equipment
I
I
10 11 12
13 14 15 16
Order codes
See page 39
See page 38
See page 37
See page 36
3 A
C.t.-operated release
with tripping pulse
0.1 Ws (20 )
C.t.-operated release
with tripping pulse
0.1 Ws (10 )
C.t.-operated
release 1.0 A
C.t.-operated
release 0.5 A 2)
Undervoltage release
Order No.:
See page 34
Position:
Release combination 1)
See page 34
9th position
A
II
II
II
II
G
II
II
I
I
II
II
II
I
I
I
I
10th position
Operating voltage of the closing solenoid
Standard voltages
Special voltages
24 V DC
48 V DC
60 V DC
110 V DC
220 V DC
100 V AC
50 / 60 Hz 3)
110 V AC
50 / 60 Hz 3)
230 V AC
50 / 60 Hz 3)
30 V DC
32 V DC
120 V DC
125 V DC
127 V DC
240 V DC
120 V AC
S
50 / 60 Hz 3)
125 V AC
50 / 60 Hz 3)
240 V AC
50 / 60 Hz 3)
33
Equipment Selection
Secondary equipment
10 11 12
13 14 15 16
Special voltages
C.t.-operated release
24 V DC
48 V DC
60 V DC
110 V DC
220 V DC
Order codes
See page 39
3 A
See page 36
Standard voltages
Order No.:
See page 38
Position:
See page 37
11th position
100 V AC
50 / 60 Hz 1)
110 V AC
50 / 60 Hz 1)
230 V AC
50 / 60 Hz 1)
8
30 V DC
32 V DC
120 V DC
125 V DC
127 V DC
240 V DC
120 V AC
50 / 60 Hz 1)
125 V AC
50 / 60 Hz 1)
240 V AC
50 / 60 Hz 1)
1 M
12th position
Operating voltage of the 2nd release
Standard voltages
Special voltages
24 V DC
48 V DC
60 V DC
110 V DC
220 V DC
100 V AC
50 / 60 Hz 1)
110 V AC
50 / 60 Hz 1)
230 V AC
50 / 60 Hz 1)
8
30 V DC
M 1
32 V DC
M 1
120 V DC
M 1
125 V DC
M 1
127 V DC
M 1
240 V DC
M 1
120 V AC
50 / 60 Hz 1)
M 1
125 V AC
50 / 60 Hz 1)
M 1
240 V AC
50 / 60 Hz 1)
M 1 M
34
Equipment Selection
Secondary equipment
10 11 12
13 14 15 16
Order codes
Options
See page 39
3 A
See page 36
Order No.:
See page 38
Position:
See page 37
13th position
M 2 2
M 2 3
Withdrawable module
Circuit-breaker on withdrawable part, with cartridge, contact arm,
contact 1), xed contacts, bushing, shutters
Retrot 8B
Circuit-breaker on truck for retrotting 8B switchgear,
see next page
R-HG11-362.eps
R-HG11-376.tif
R-HG11-375.tif
R-HG11-379.tif
35
Equipment Selection
Secondary equipment
13th position
Position:
10 11 12
13 14 15 16
Order codes
3 A
E
E
1
1
1
1
8
8
4
4
2
4
See page 39
Options
See page 38
Order No.:
See page 37
Circuit-breaker on truck
for retrotting 8B switchgear
Order number
14th
7.2 12 kV
12.5 25 kA
630 1250 A
7.2 12 kV
12.5 25 kA
1600 A
3 A
3 A
7.2 12 kV
12.5 25 kA
2000 A
3 A
7.2 12 kV
12.5 25 kA
2500 A
3 A
12 kV
29 (10 kV)
630 1250 A
3 A
7.2 12 kV
31.5 kA
630 1250 A
3 A
12 kV
29 (10 kV)
1600 A
3 A
7.2 12 kV
31.5 kA
3 A
15 kV
12.5 25 kA
630 1250 A
3 A
17.5 kV
8 25 kA
630 1250 A
3 A
15 17.5 kV
20 25 kA
2000 A
3 A
15 kV
25 kA
2500 A
3 A
15 kV
31.5 kA
630 1250 A
3 A
15 kV
31.5 kA
3 A
24 kV
8 20 kA
630 1250 A
3 A
24 kV
12.5 kA
1600 A
3 A
24 kV
12.5 kA
1600 A
3 A
24 kV
20 kA
2000 A
3 A
24 kV
25 kA
1250 A
24 kV
25 kA
2000 A
Contact arm including contact
3 A
3 A
E
E
1
1
3
3
2
2
4
4
2
4
7
7
Z
Z
R
R
3
4
9
0
Type
Fixed contact 10 mm
665 mm
Fixed contact 15 mm
665 mm
Fixed contact 10 mm
598 mm
Fixed contact 15 mm
598 mm
position
24 V DC 1)
48 V DC
60 V DC
110 V DC
220 V DC
100 V AC 50 / 60 Hz 2)
110 V AC 50 / 60 Hz 2)
230 V AC 50 / 60 Hz 2)
K
30 V DC 1)
32 V DC 1)
120 V DC
125 V DC
127 V DC
240 V DC
120 V AC 50 / 60 Hz 2)
125 V AC 50 / 60 Hz 2)
240 V AC 50 / 60 Hz 2)
V
W
36
S. page 39
Special voltages
S. page 38
Standard voltages
S. page 37
Equipment Selection
Secondary equipment
15th position
Position:
Order No.:
10 11 12
13 14 15 16
Order codes
See page 39
See page 38
64-poliger
Stecker 2)
24-poliger
Stecker 1)
Niederspannungsschnittstelle
Circuit-breaker
tripping signal
12 NO + 12 NC
6 NO + 6 NC
Mechanical
interlocking
Auxiliary switch
3 A
P
not for 3AE5
3)
U 3)
if the 13th position is
selected: only 0 is possible
Special versions
Auxiliary switch contacts 6 NO + 6 NC and pins
of the 24-pole plug connector gold-plated (not for retrot)
1) Electrical devices are wired to the lower part of a plug through the terminal strip.
The free auxiliary switch connections are not wired.
2) Electrical devices are wired to the lower part of a plug through the terminal strip.
The auxiliary switches are wired to the lower part of the plug according to the circuit diagrams.
3) Standard for NXAIR World.
37
Equipment Selection
Secondary equipment
16th position
Position:
10 11 12
13 14 15 16
Order codes
3
4
1
2
See page 39
60 Hz
DC or AC 50 Hz
3 A
Frequency selection
Spanish
French
English
German
Language selection
Order No.:
5
6
Special versions
Portuguese, DC or AC 50 Hz
Portuguese, 60 Hz
Italian, DC or AC 50 Hz
Russian, DC or AC 50 Hz
Russian, 60 Hz
Polish, DC or AC 50 Hz
38
Equipment Selection
Additional equipment
Additional equipment
Position:
C.t.-operated release 5 A
10 11 12
13 14 15 16
Order codes
3AE5
3 A
3AE1
Options
Circuit-breaker
13th pos. = 0, 1, 2, 3
Withdrawable module
13th position = 5, 6
Retrot
13th position = 7
Order No.:
Z
Z
A
A
0
1
5
0
Z
Z
Z
Z
Z
D
D
D
D
D
2
2
2
5
5
2
3
4
5
6
On request
1) AC voltage refers to the secondary side and not to the primary part of the circuit-breaker
39
Equipment Selection
Additional equipment
Additional equipment
Position:
10 11 12
13 14 15 16
Order codes
3 A
3AE5
3AE1
Options
Circuit-breaker
13th pos. = 0, 1, 2, 3
Withdrawable module
13th position = 5, 6
Retrot
13th position = 7
Order No.:
W 7
Warranty 36 months
W 7
Warranty 60 months
Other not listed special design (only after
consultation with Order Execution at Switchgear Factory Berlin). Specications additionally
in clear text
W 7
40
M 1
M 3
Equipment Selection
Accessories and spare parts
Retrotting
Rating plate
2
2014
Note:
For any query regarding spare parts, subsequent deliveries,
etc., the following 3 details are necessary:
Type designation
Serial no.
Year of manufacture
Position:
19
Designation
Description
Handles
3AX15 30-2B
3AX14 30-2B
3AX14 30-2C
3AX14 30-2D
3AX14 30-3D
3AX11 33-3H
3AX11 33-3E
1 kg of Molykote grease
3AX14 33-2L
Lubricant
Operating solenoid
Feature
Order No.
24 V DC
3AY15 10-5K
For 3AE1
30/32 V DC
3AY15 10-5M
For 3AE1
48 V DC
3AY15 10-5C
For 3AE1
60 V DC
3AY15 10-5D
For 3AE1
100/124 V DC
3AY15 10-5E
For 3AE1
125/144 V DC
3AY15 10-5L
For 3AE1
220/250 V DC
3AY15 10-5F
For 3AE1
3AY15 10-5E
For 3AE1
3AY15 10-5F
41
Equipment Selection
Position:
Designation
2
Mounting parts
Description
Feature
Order No.
For 3AE5
24 V DC
3AY14 10-0B
For 3AE5
30/32 V DC
3AY14 10-0M
For 3AE5
48 V DC
3AY14 10-0C
For 3AE5
60 V DC
3AY14 10-0D
For 3AE5
100/124 V DC
3AY14 10-0E
For 3AE5
125/144 V DC
3AY14 10-0N
For 3AE5
220/250 V DC
3AY14 10-0F
For 3AE5
For 3AE5
3AY14 10-0E
3AY14 10-0F
24 32 V DC
48 60 V DC
3AX11 01-2B
3AX11 01-2C
110 127 V DC
3AX11 01-2E
220 240 V DC
3AX11 01-2F
3AX11 01-2G
3AX11 01-2J
3AX11 01-3G
3AX11 01-3J
3AX14 11-2A
For 3AE5
3AX14 11-5A
Current-transformer
3AX11 02-2A
operated release
3AX11 02-2B
3AX11 02-2C
For tripping pulseW0.1Ws, 20 for protection relay 7SJ45 For 3AE1 and 3AE5
3AX11 04-2B
For 3AE1
3AX14 02-2D
For 3AE5
3AX14 02-2E
For 3AE1
For 3AE5
3AX14 11-2A
3AX14 11-5A
Mounting parts
Undervoltage release
Mounting parts
Drive motor
42
19
24 V DC
30/32 V DC
3AX11 03-2B
3AX11 03-2L
48 V DC
3AX11 03-2C
60 V DC
3AX11 03-2D
110 V DC
3AX11 03-2E
120/127 V DC
3AX11 03-2N
220 V DC
3AX11 03-2F
240 V DC
3AX11 03-2P
100 V AC, 50 Hz
3AX11 03-2G
110/125 V AC, 50 Hz
3AX11 03-2H
230 V AC, 50 Hz
3AX11 03-2J
240 V AC, 50 Hz
3AX11 03-2M
100 V AC, 60 Hz
3AX11 03-3G
110/125 V AC, 60 Hz
3AX11 03-3H
230 V AC, 60 Hz
3AX11 03-3J
240 V AC, 60 Hz
3AX11 03-3M
For 3AE1
For 3AE5
3AX14 13-2A
3AX14 13-5A
For 3AE1
For 3AE1
24/30/32 V DC
48 V DC
3AY17 11-2B
3AY17 11-2C
For 3AE1
60 V DC
3AY17 11-2D
For 3AE1
For 3AE1
100/110/125 V DC/AC
220 V DC/230 V AC
3AY17 11-2E
3AY17 11-2F
For 3AE5
For 3AE5
24/30/32 V DC
48 V DC
3AY14 11-0B
3AY14 11-0C
For 3AE5
60 V DC
3AY14 11-0C
For 3AE5
100/110/125 V DC/AC
3AY14 11-0E
For 3AE5
220 V DC/230 V AC
3AY14 11-0F
Equipment Selection
Accessories and spare parts
Position:
Designation
Description
Auxiliary contactor
Type 3RH11 22
For anti-pumping
Electronic module
For 3AE5
Position switch
Feature
Order No.
For 3AE1
24 V DC
SWB: 55656
For 3AE1
30/32 V DC
SWB: 55658
For 3AE1
48 V DC
SWB: 55659
For 3AE1
60 V DC
SWB: 55660
For 3AE1
110 V DC
SWB: 55661
For 3AE1
120/127 V DC
SWB: 55662
For 3AE1
220 V DC
SWB: 55663
For 3AE1
240/250 V DC
SWB: 55665
For 3AE1
SWB: 55666
For 3AE1
SWB: 55667
For 3AE1
SWB: 55668
For 3AE1
SWB: 55669
For 3AE1
SWB: 55670
24 V 60 V
3AY14 20-0B
110 V 230 V
3AY14 20-0E
3AX42 06-0A
Used for:
Nos.
10
6 NO + 6 NC
3SV92 73-2AA0
12 NO + 12 NC
Mechanical interlocking
Key-operated interlocking
Accessories for
plug connector
19
3SV92 74-2AA0
For 3AE1
3AX14 20-2A
For 3AE1
3AX14 37-2A
24-pole
3AX11 34-3A
64-pole
3AX11 34-4B
64-pole
3AX11 34-4C
Crimping pliers
Disassembly tool
24-pole
64-pole
3AX11 34-6A
Electrical
For 3AE1
24 V DC
3AX14 05-2B
closing lock-out
For 3AE1
30/32 V DC
3AX14 05-2K
For 3AE1
48 V DC
3AX14 05-2C
For 3AE1
60 V DC
3AX14 05-2D
For 3AE1
100/127 V DC
3AX14 05-2E
For 3AE1
220/240 V DC
3AX14 05-2F
For 3AE1
3AX14 05-2G
For 3AE1
3AX14 05-2H
For 3AE1
3AX14 05-2J
Mounting parts
3AX11 34-4D
3AX11 34-4G
3AX11 34-7A
For 3AE1
3AX14 15-2A
For 3AE1
Bushing
3AX14 16-2A
3AX14 51-2A
3AX14 51-2B
For 3AE1
24 kV to 2500 A
3AX14 51-2B
43
Equipment Selection
Accessories and spare parts
Position:
19
Designation
Description
Separating shell
For 3AE1
3AX14 38-2E
For 3AE1
3AX14 38-2A
For 3AE1
7.2 to 17.5 kV
3AX14 38-2C
circuit-breakers only
For 3AE1
7.2 to 17.5 kV
3AX14 38-2D
For 3AE5
7.2 to 12 kV
3AX14 38-5A
in case of narrow
For 3AE5
7.2 to 12 kV
3AX14 38-5C
installation conditions
For 3AE5
7.2 to 12 kV
3AX14 38-5D
For 3AE5
3AX14 38-5K
For 3AE5
3AX14 38-5J
For 3AE5
3AX14 38-5H
For 3AE1
24 kV
3AX14 38-2B
For 3AE1
24 kV
3AX14 38-3B
Feature
Short version
Order No.
3AX14 52-2B
Cartridge
For 3AE1 and 3AE5
3AX14 42-2A
3AX14 42-2B
3AX14 42-2C
3AX14 42-2D
3AX14 43-2A
3AX14 43-2B
3AX14 43-2C
3AX14 43-2D
3AX14 43-2E
3AX14 43-2F
3AX14 43-2G
3AX14 43-2H
3AX14 43-2J
3AX14 43-2K
3AX14 44-2A
3AX14 44-2B
3AX14 44-2A
3AX14 44-2C
Contact system
Fixed contact
Conductor bars
3AX14 55-2A
earthing switch
3AX14 55-2A
connection
3AX14 55-2B
3AX14 55-2C
3AX14 55-2D
3AX14 55-2E
3AX14 55-2F
3AX14 55-2G
3AX14 55-2H
For 3AE5
3AX14 56-0A
(IP plate)
For 3AE5
3AX14 56-0B
For 3AE5
3AX14 56-0C
Operating shaft
For 3AE5
3AX14 66-0A
Cover
For 3AE5
3AX14 66-0B
Cable gland
44
3AX14 58-0A
Equipment Selection
Accessories and spare parts
Position:
Description
Withdrawable part
ISC
kA
Ur
kV
Travel / feature
Pole-center distance
Rated voltage
for 50 / 60 Hz
Designation
mm
mm
19
Order No.
10
Language code *
Ir
17.5
150/160
3AX71 12-2A
17.5
150/160
3AX71 12-3A
17.5
150/160
3AX71 12-4A
17.5
210
3AX71 12-2B
17.5
210
3AX71 12-3B
17.5
210
3AX71 12-4B
24
210
3AX71 12-2C
24
210
3AX71 12-3C
24
275
3AX71 12-2D
24
275
3AX71 12-3D
17.5
150/160
3AX71 12-2E
17.5
150/160
3AX71 12-3E
17.5
150/160
3AX71 12-4E
17.5
210
3AX71 12-2F
17.5
210
3AX71 12-3F
17.5
210
3AX71 12-4F
17.5
31.5
150
275
1250
3AX71 11-5A
switch
17.5
31.5
150
310
1250
3AX71 11-5B
17.5
31.5
210
275
1250
3AX71 11-5C
17.5
31.5
210
310
1250
3AX71 11-5D
17.5
31.5
210
310
> 1250
3AX71 11-5G
17.5
40
210
310
all Ir
3AX71 11-5H
24
25
210
310
1250
3AX71 11-5E
24
25
275
310
1250
3AX71 11-5F
24
25
210
310
> 1250
3AX71 11-5J
24
25
275
310
> 1250
3AX71 11-5K
17.5
31.5
150
275
3AX71 11-6A
switch
17.5
31.5
150
310
3AX71 11-6B
17.5
31.5
210
275
3AX71 11-6C
17.5
31.5
210
310
3AX71 11-6D
17.5
31.5
210
310
3AX71 11-6G
17.5
40
210
310
all Ir
24
25
210
310
24
25
275
310
3AX71 11-6J
24
25
210
310
3AX71 11-6F
24
25
275
310
3AX71 11-6K
without partition
3AX71 11-6H
3AX71 11-6E
*) The language of the rating plate is given in the table. The individual code has to be added to the order number.
A
B
C
D
E
F
G
H
Z
German
English
French
Spanish
Italian
Russian
Portuguese
Polish
Open with Z = ...
45
R-HG11-Titel-SION.psd
46
Technical Data
Contents
Contents
Page
Technical Data
47
48
54
Voltage level 12 kV
55
62
63
69
Voltage level 24 kV
70
71
R-HG11-380.tif
Dimension drawings
72
80
80
80
Circuit diagrams
Standard scheme for plug connector for 3AE1
82
82
83
83
84
85
85
86
86
87
R-HG11-375.tif
47
Technical Data
16
50
17.9 40/42
60
20
93
245
93
97
49/
A7E44202010
16
50
17.9 40/42
60
20
93
245
93
97
49/
A7E44202010
Up
Ud
kA
kV
kV
mV
3AE5 002-1...
mm mm
Isc
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
Ima
7.2 kV
mm mm mm mm
kg
20
50
22.4 50/52
60
20
93
245
93
97
49/
A7E44202010
20
50
22.4 50/52
60
20
93
245
93
97
49/
A7E44202010
25
50
28
63/65
60
20
93
245
93
97
49/
A7E44202010
3a
25
50
28
63/65
60
20
93
245
93
97
49/
A7E44202010
3a
31.5
50
35.4 80/82
60
20
2.5
90
255
98
122
53.5/
A7E44202010
4a
31.5
50
35.4 80/82
60
20
2.5
90
255
98
122
53.5/
A7E442020210
4a
16
50
17.9 40/42
60
20
93
245
93
97
49/85
A7E44202011
16
50
17.9 40/42
60
20
93
245
93
97
49/85
A7E44202011
20
50
22.4 50/52
60
20
93
245
93
97
49/85
A7E44202011
20
50
22.4 50/52
60
20
93
245
93
97
49/85
A7E44202011
3AE5 003-1...
3AE5 004-1...
3AE5 005-1...
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
3AE5 012-1...
3AE5 013-1...
25
50
28
63/65
60
20
93
245
93
97
49/85
A7E44202011
3a
25
50
28
63/65
60
20
93
245
93
97
49/85
A7E44202011
3a
31.5
50
35.4 80/82
60
20
2.5
90
255
98
122 53.5/89.5
A7E442020211
4a
31.5
50
35.4 80/82
60
20
2.5
90
255
98
122 53.5/89.5
A7E442020211
4a
16
50
17.9 40/42
60
20
93
245
93
97
49/85
A7E44202012
16
50
17.9 40/42
60
20
93
245
93
97
49/85
A7E44202012
16
50
17.9 40/42
60
20
2.5
90
255
98
122 59.5/95.5
A7E442020211
1a
20
50
22.4 50/52
60
20
93
245
93
97
49/85
A7E44202012
20
50
22.4 50/52
60
20
93
245
93
97
49/85
A7E44202012
20
50
22.4 50/52
60
20
2.5
90
255
98
122 59.5/95.5
A7E442020212
2a
3AE5 014-1...
3AE5 015-1...
3AE5 022-1...
3AE5 023-1...
25
50
28
63/65
60
20
93
245
93
97
49/85
A7E44202012
3a
25
50
28
63/65
60
20
93
245
93
97
49/85
A7E44202012
3a
25
50
28
63/65
60
20
2.5
90
255
98
122 59.5/95.5
A7E442020212
3b
31.5
50
35.4 80/82
60
20
2.5
90
255
98
122 53.5/89.5
A7E442020212
4a
31.5
50
35.4 80/82
60
20
2.5
90
255
98
122 53.5/89.5
A7E442020212
4a
31.5
50
35.4 80/82
60
20
2.5
90
255
98
122 59.5/95.5
A7E442020212
4a
3AE5 024-1...
3AE5 025-1...
48
Technical Data
16
50 17.9 40/42
60
20
93
245
93
129
49/
A7E44202016
16
50 17.9 40/42
60
20
93
245
93
129
49/
A7E44202016
Ima
Up
Ud
kA
kV
kV
mV
7.2 kV
3AE5 032-1...
mm mm
Isc
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
mm mm mm mm
kg
20
50 22.4 50/52
60
20
93
245
93
129
49/
A7E44202016
20
50 22.4 50/52
60
20
93
245
93
129
49/
A7E44202016
25
50
28
63/65
60
20
93
245
93
129
49/
A7E44202016
3a
25
50
28
63/65
60
20
93
245
93
129
49/
A7E44202016
3a
60
20
2.5
90
255
98
122
53.5/
A7E442020216
4a
60
20
2.5
90
255
98
122
53.5/
A7E442020216
4a
16
50 17.9 40/42
60
20
93
245
93
129
49/
A7E44202017
16
50 17.9 40/42
60
20
93
245
93
129
49/
A7E44202017
20
50 22.4 50/52
60
20
93
245
93
129
49/
A7E44202017
20
50 22.4 50/52
60
20
93
245
93
129
49/
A7E44202017
3AE5 033-1...
3AE5 034-1...
3AE5 035-1...
3AE5 042-1...
3AE5 043-1...
25
50
28
63/65
60
20
93
245
93
129
49/
A7E44202017
3a
25
50
28
63/65
60
20
93
245
93
129
49/
A7E44202017
3a
60
20
2.5
90
255
98
122
53.5/
A7E442020217
4a
60
20
2.5
90
255
98
122
53.5/
A7E442020217
4a
16
50 17.9 40/42
60
20
93
245
93
129
49/
A7E44202018
16
50 17.9 40/42
60
20
93
245
93
129
49/
A7E44202018
16
50 17.9 40/42
60
20
2.5
90
255
98
122
59.5/
A7E442020218
1a
20
50 22.4 50/52
60
20
93
245
93
129
49/
A7E44202018
20
50 22.4 50/52
60
20
93
245
93
129
49/
A7E44202018
20
50 22.4 50/52
60
20
2.5
90
255
98
122
59.5/
A7E442020218
2a
3AE5 044-1...
3AE5 045-1...
3AE5 052-1...
3AE5 053-1...
25
50
28
63/65
60
20
93
245
93
129
49/
A7E44202018
3a
25
50
28
63/65
60
20
93
245
93
129
49/
A7E44202018
3a
25
50
28
63/65
60
20
2.5
90
255
98
122
59.5/
A7E442020218
3b
60
20
2.5
90
255
98
122
53.5/
A7E442020218
4a
60
20
2.5
90
255
98
122
53.5/
A7E442020218
4a
60
20
2.5
90
255
98
122
59.5/
A7E442020218
4a
3AE5 054-1...
3AE5 055-1...
49
Technical Data
16
50
17.9 40/42
60
20
93
245
93
129 51.5/91.5
A7E44202022
16
50
17.9 40/42
60
20
93
245
93
129 51.5/91.5
A7E44202022
Up
Ud
kA
kV
kV
mV
3AE5 062-1...
mm mm
Isc
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
Ima
7.2 kV
mm mm mm mm
kg
20
50
22.4 50/52
60
20
93
245
93
129
51.5/
A7E44202022
20
50
22.4 50/52
60
20
93
245
93
129
51.5/
A7E44202022
25
50
28
63/65
60
20
93
245
93
129
51.5/
A7E44202022
3a
25
50
28
63/65
60
20
93
245
93
129
51.5/
A7E44202022
3a
31.5
50
35.4 80/82
60
20
2.5
90
255
98
122
56.5/
A7E44202022
4a
31.5
50
35.4 80/82
60
20
2.5
90
255
98
122
56.5/
A7E44202022
4a
16
50
17.9 40/42
60
20
93
245
93
129 51.5/91.5
A7E44202023
16
50
17.9 40/42
60
20
93
245
93
129 51.5/91.5
A7E44202023
20
50
22.4 50/52
60
20
93
245
93
129 51.5/91.5
A7E44202023
20
50
22.4 50/52
60
20
93
245
93
129 51.5/91.5
A7E44202023
3AE5 063-1...
3AE5 064-1...
3AE5 065-1...
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
3AE5 072-1...
3AE5 073-1...
25
50
28
63/65
60
20
93
245
93
129 51.5/91.5
A7E44202023
3a
25
50
28
63/65
60
20
93
245
93
129 51.5/91.5
A7E44202023
3a
31.5
50
35.4 80/82
60
20
2.5
90
255
98
122 56.5/96.5
A7E442020223
4a
31.5
50
35.4 80/82
60
20
2.5
90
255
98
122 56.5/96.5
A7E442020223
4a
16
50
17.9 40/42
60
20
93
245
93
129 51.5/91.5
A7E44202024
16
50
17.9 40/42
60
20
93
245
93
129 51.5/91.5
A7E44202024
16
50
17.9 40/42
60
20
2.5
90
255
98
122 62.5/102.5
A7E442020224
1a
20
50
22.4 50/52
60
20
93
245
93
129 51.5/91.5
A7E44202024
20
50
22.4 50/52
60
20
93
245
93
129 51.5/91.5
A7E44202024
20
50
22.4 50/52
60
20
2.5
90
255
98
122 62.5/102.5
A7E442020224
2a
3AE5 074-1...
3AE5 075-1...
3AE5 082-1...
3AE5 083-1...
25
50
28
63/65
60
20
93
245
93
129 51.5/91.5
A7E44202024
3a
25
50
28
63/65
60
20
93
245
93
129 51.5/91.5
A7E44202024
3a
25
50
28
63/65
60
20
2.5
90
255
98
122 62.5/102.5
A7E442020224
3b
31.5
50
35.4 80/82
60
20
2.5
90
255
98
122 56.5/96.5
A7E442020224
4a
31.5
50
35.4 80/82
60
20
2.5
90
255
98
122 56.5/96.5
A7E442020224
4a
31.5
50
35.4 80/82
60
20
2.5
90
255
98
122 62.5/102.5
A7E442020224
4a
3AE5 084-1...
3AE5 085-1
50
Technical Data
16
36
17.9 40/42
60
20
2.1
75
67/
A7E44202010
16
36
17.9 40/42
60
20
2.1
75
67/
A7E44202010
20
36
22.4 50/52
60
20
2.1
75
67/
A7E44202010
20
36
22.4 50/52
60
20
2.1
75
67/
A7E44202010
25
36
28
63/65
60
20
2.1
75
67/
A7E44202010
3a
25
36
28
63/65
60
20
2.1
75
67/
A7E44202010
3a
31.5
36
35.4 80/82
60
20
2.1
75
80/
A7E44202010
31.5
36
35.4 80/82
60
20
2.1
75
80/
A7E44202010
16
36
17.9 40/42
60
20
2.1
75
67/103
A7E44202011
16
36
17.9 40/42
60
20
2.1
75
67/103
A7E44202011
20
36
22.4 50/52
60
20
2.1
75
67/103
A7E44202011
20
36
22.4 50/52
60
20
2.1
75
67/103
A7E44202011
25
36
28
63/65
60
20
2.1
75
67/103
A7E44202011
3a
25
36
28
63/65
60
20
2.1
75
67/103
A7E44202011
3a
31.5
36
35.4 80/82
60
20
2.1
75
80/120
A7E44202011
31.5
36
35.4 80/82
60
20
2.1
75
80/120
A7E44202011
16
36
17.9 40/42
60
20
2.1
75
67/103
A7E44202012
16
36
17.9 40/42
60
20
2.1
75
67/103
A7E44202012
20
36
22.4 50/52
60
20
2.1
75
67/103
A7E44202012
20
36
22.4 50/52
60
20
2.1
75
67/103
A7E44202012
25
36
28
63/65
60
20
2.1
75
67/103
A7E44202012
3a
25
36
28
63/65
60
20
2.1
75
67/103
A7E44202012
3a
31.5
36
35.4 80/82
60
20
2.1
75
80/120
A7E44202012
31.5
36
35.4 80/82
60
20
2.1
75
80/120
A7E44202012
Ima
Up
Ud
kA
kV
kV
mV
mm mm mm mm
7.2 kV
3AE1 002-1...
3AE1 003-1...
3AE1 004-1...
3AE1 005-1...
3AE1 012-1...
3AE1 013-1...
3AE1 014-1...
3AE1 015-1...
3AE1 022-1...
3AE1 023-1...
3AE1 024-1...
3AE1 025-1...
mm mm
Isc
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
kg
51
Technical Data
16
36
17.9 40/42
60
20
2.1
75
67/
A7E44202016
16
36
17.9 40/42
60
20
2.1
75
67/
A7E44202016
20
36
22.4 50/52
60
20
2.1
75
67/
A7E44202016
20
36
22.4 50/52
60
20
2.1
75
67/
A7E44202016
25
36
28
63/65
60
20
2.1
75
67/
A7E44202016
3a
25
36
28
63/65
60
20
2.1
75
67/
A7E44202016
3a
31.5
36
35.4 80/82
60
20
2.1
75
80/
A7E44202016
31.5
36
35.4 80/82
60
20
2.1
75
80/
A7E44202016
16
36
17.9 40/42
60
20
2.1
75
67/
A7E44202017
16
36
17.9 40/42
60
20
2.1
75
67/
A7E44202017
20
36
22.4 50/52
60
20
2.1
75
67/
A7E44202017
20
36
22.4 50/52
60
20
2.1
75
67/
A7E44202017
25
36
28
63/65
60
20
2.1
75
67/
A7E44202017
3a
25
36
28
63/65
60
20
2.1
75
67/
A7E44202017
3a
31.5
36
35.4 80/82
60
20
2.1
75
80/
A7E44202017
31.5
36
35.4 80/82
60
20
2.1
75
80/
A7E44202017
16
36
17.9 40/42
60
20
2.1
75
67
A7E44202018
16
36
17.9 40/42
60
20
2.1
75
67
A7E44202018
20
36
22.4 50/52
60
20
2.1
75
67
A7E44202018
20
36
22.4 50/52
60
20
2.1
75
67
A7E44202018
25
36
28
63/65
60
20
2.1
75
67
A7E44202018
3a
25
36
28
63/65
60
20
2.1
75
67
A7E44202018
3a
31.5
36
35.4 80/82
60
20
2.1
75
80
A7E44202018
31.5
36
35.4 80/82
60
20
2.1
75
80
A7E44202018
16
36
17.9 40/42
60
20
2.1
75
67/
A7E44202022
16
36
17.9 40/42
60
20
2.1
75
67/
A7E44202022
Up
Ud
kA
kV
kV
mV
mm mm mm mm
3AE1 032-1...
3AE1 033-1...
3AE1 034-1...
3AE1 035-1...
3AE1 042-1...
3AE1 043-1...
3AE1 044-1...
3AE1 045-1...
3AE1 052-1...
3AE1 053-1...
3AE1 054-1...
3AE1 055-1...
3AE1 062-1...
mm mm
ISC
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
Ima
7.2 kV
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
kg
52
Technical Data
20
36
22.4 50/52
60
20
2.1
75
67/
A7E44202022
20
36
22.4 50/52
60
20
2.1
75
67/
A7E44202022
25
36
28
63/65
60
20
2.1
75
67/
A7E44202022
3a
25
36
28
63/65
60
20
2.1
75
67/
A7E44202022
3a
31.5
36
35.4 80/82
60
20
2.1
75
90/
A7E44202022
31.5
36
35.4 80/82
60
20
2.1
75
90/
A7E44202022
16
36
17.9 40/42
60
20
2.1
75
67/103
A7E44202023
16
36
17.9 40/42
60
20
2.1
75
67/103
A7E44202023
20
36
22.4 50/52
60
20
2.1
75
67/103
A7E44202023
20
36
22.4 50/52
60
20
2.1
75
67/103
A7E44202023
25
36
28
63/65
60
20
2.1
75
67/103
A7E44202023
3a
25
36
28
63/65
60
20
2.1
75
67/103
A7E44202023
3a
31.5
36
35.4 80/82
60
20
2.1
75
90/130
A7E44202023
31.5
36
35.4 80/82
60
20
2.1
75
90/130
A7E44202023
16
36
17.9 40/42
60
20
2.1
75
67/103
A7E44202024
16
36
17.9 40/42
60
20
2.1
75
67/103
A7E44202024
20
36
22.4 50/52
60
20
2.1
75
67/103
A7E44202024
20
36
22.4 50/52
60
20
2.1
75
67/103
A7E44202024
25
36
28
63/65
60
20
2.1
75
67/103
A7E44202024
3a
25
36
28
63/65
60
20
2.1
75
67/103
A7E44202024
3a
25
36
28
63/65
60
20
1.5
A7E44202028
31.5
36
35.4 80/82
60
20
2.1
75
90/130
A7E44202024
31.5
36
35.4 80/82
60
20
2.1
75
90/130
A7E44202024
31.5
36
35.4 80/82
60
20
1.5
A7E44202028
31.5
36
35.4 80/82
60
20
1.5
A7E44202028
Ima
Up
Ud
kA
kV
kV
mV
mm mm mm mm
7.2 kV
3AE1 063-1...
3AE1 064-1...
3AE1 065-1...
3AE1 072-1...
3AE1 073-1...
3AE1 074-1...
3AE1 075-1...
3AE1 082-1...
3AE1 083-1...
3AE1 084-1...
3AE1 085-1...
mm mm
ISC
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
kg
53
Technical Data
Ima
Up
Ud
kA
kV
kV
mV
mm mm mm mm
40
36
44.9 100/104 60
20
1.7
A7E44202070
40
36
44.9 100/104 60
20
1.0
A7E44202071
40
36
44.9 100/104 60
20
1.0
A7E44202071
40
36
44.9 100/104 60
20
1.0
A7E44202071
mm mm
tk
ISC
kA
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
7.2 kV
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
kg
3
Operating cycle diagrams for 7.2 kV
HG11-2540d_en eps
20 000
5 000
2 000
1 000
10 000
5 000
2 000
1 000
2 000
1 000
500
500
200
200
200
100
80
50
100
70
46
30
3a
1a 3b
2a 4a
20
2
10
0.5
54
5 000
500
100
70
46
30
20
1
16 25 kA 50
20
Breaking current (r.m.s. value)
2
10
HG11-2539d_en eps
20 000
10 000
10 000
HG11-2888_en eps
20 000
10
0.5
16 25 kA 50
20 31.5
Breaking current (r.m.s. value)
2
10
20
10
0.5
3
1
10 kA 20 25 40 50
31.5
Breaking current (r.m.s. value)
2
of the breaking current (r.m.s. value). All SION vacuum circuit-breakers full
average experience data. The number of operating cycles that can actually
the endurance classes E2, M2 and C2 according to IEC 62271-100. The curve
Technical Data
16
50
17.9 40/42
75
28
93
245
93
129
49/
A7E44202010
16
50
17.9 40/42
75
28
93
245
93
129
49/
A7E44202010
20
50
22.4 50/52
75
28
93
245
93
129
49/
A7E44202010
20
50
22.4 50/52
75
28
93
245
93
129
49/
A7E44202010
25
50
28
63/65
75
28
93
245
93
129
49/
A7E44202010
8a
25
50
28
63/65
75
28
93
245
93
129
49/
A7E44202010
8a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122
53.5/
A7E44202010
9a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122
53.5/
A7E44202010
9a
16
50
17.9 40/42
75
28
93
245
93
129
49/85
A7E44202011
16
50
17.9 40/42
75
28
93
245
93
129
49/85
A7E44202011
20
50
22.4 50/52
75
28
93
245
93
129
49/85
A7E44202011
20
50
22.4 50/52
75
28
93
245
93
129
49/85
A7E44202011
25
50
28
63/65
75
28
93
245
93
129
49/85
A7E44202011
8a
25
50
28
63/65
75
28
93
245
93
129
49/85
A7E44202011
8a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122 53.5/89.5
A7E44202011
9a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122 53.5/89.5
A7E44202011
9a
16
50
17.9 40/42
75
28
93
245
93
129
49/85
A7E44202012
16
50
17.9 40/42
75
28
93
245
93
129
49/85
A7E44202012
16
50
17.9 40/42
75
28
2.5
90
255
98
122 59.5/95.5
A7E44202012
6a
20
50
22.4 50/52
75
28
93
245
93
129
49/85
A7E44202012
20
50
22.4 50/52
75
28
93
245
93
129
49/85
A7E44202012
20
50
22.4 50/52
75
28
2.5
90
255
98
122 59.5/95.5
A7E44202012
7a
25
50
28
63/65
75
28
93
245
93
129
49/85
A7E44202012
8a
25
50
28
63/65
75
28
93
245
93
129
49/85
A7E44202012
8a
25
50
28
63/65
75
28
2.5
90
255
98
122 59.5/95.5
A7E44202012
8b
Ima
Up
Ud
kA
kV
kV
mV
12 kV
3AE5 102-1...
3AE5 103-1...
3AE5 104-1...
3AE5 105-1...
3AE5 112-1...
3AE5 113-1...
3AE5 114-1...
3AE5 115-1...
3AE5 122-1...
3AE5 123-1...
3AE5 124-1...
mm mm
Isc
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
mm mm mm mm
kg
55
Technical Data
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122 53.5/89.5
A7E44202012
9a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122 53.5/89.5
A7E44202012
9a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122 59.5/95.5
A7E44202012
9a
16
50
17.9 40/42
75
28
93
245
93
129
49/
A7E44202016
16
50
17.9 40/42
75
28
93
245
93
129
49/
A7E44202016
20
50
22.4 50/52
75
28
93
245
93
129
49/
A7E44202016
20
50
22.4 50/52
75
28
93
245
93
129
49/
A7E44202016
25
50
28
63/65
75
28
93
245
93
129
49/
A7E44202016
8a
25
50
28
63/65
75
28
93
245
93
129
49/
A7E44202016
8a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122
53.5/
A7E44202016
9a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122
53.5/
A7E44202016
9a
16
50
17.9 40/42
75
28
93
245
93
129
49/
A7E44202017
16
50
17.9 40/42
75
28
93
245
93
129
49/
A7E44202017
20
50
22.4 50/52
75
28
93
245
93
129
49/
A7E44202017
20
50
22.4 50/52
75
28
93
245
93
129
49/
A7E44202017
25
50
28
63/65
75
28
93
245
93
129
49/
A7E44202017
8a
25
50
28
63/65
75
28
93
245
93
129
49/
A7E44202017
8a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122
53.5/-
A7E44202017
9a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122
53.5/-
A7E44202017
9a
16
50
17.9 40/42
75
28
93
245
93
129
49/
A7E44202018
16
50
17.9 40/42
75
28
93
245
93
129
49/
A7E44202018
16
50
17.9 40/42
75
28
2.5
90
255
98
122
59.5/
A7E44202018
6a
20
50
22.4 50/52
75
28
93
245
93
129
49/
A7E44202018
20
50
22.4 50/52
75
28
93
245
93
129
49/
A7E44202018
20
50
22.4 50/52
75
28
2.5
90
255
98
122
59.5/
A7E44202018
7a
Up
Ud
kA
kV
kV
mV
3AE5 125-1...
3AE5 132-1...
3AE5 133-1...
3AE5 134-1...
3AE5 135-1...
3AE5 142-1...
3AE5 143-1...
3AE5 144-1...
3AE5 145-1...
3AE5 152-1...
3AE5 153-1...
mm mm
Isc
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
Ima
12 kV
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
mm mm mm mm
kg
56
Technical Data
25
50
28
63/65
75
28
93
245
93
129
49/
A7E44202018
8a
25
50
28
63/65
75
28
93
245
93
129
49/
A7E44202018
8a
25
50
28
63/65
75
28
2.5
90
255
98
122
59.5/
A7E44202018
8b
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122
53.5/
A7E44202018
9a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122
53.5/
A7E44202018
9a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122
59.5/
A7E44202018
9a
16
50
17.9 40/42
75
28
93
245
93
129
51.5/
A7E44202022
16
50
17.9 40/42
75
28
93
245
93
129
51.5/
A7E44202022
20
50
22.4 50/52
75
28
93
245
93
129
51.5/
A7E44202022
20
50
22.4 50/52
75
28
93
245
93
129
51.5/
A7E44202022
25
50
28
63/65
75
28
93
245
93
129
49/
A7E44202022
8a
25
50
28
63/65
75
28
93
245
93
129
49/
A7E44202022
8a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122
56.5/
A7E44202022
9a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122
56.5/
A7E44202022
9a
16
50
17.9 40/42
75
28
93
245
93
129 51.5/91.5
A7E44202023
16
50
17.9 40/42
75
28
93
245
93
129 51.5/91.5
A7E44202023
20
50
22.4 50/52
75
28
93
245
93
129 51.5/91.5
A7E44202023
20
50
22.4 50/52
75
28
93
245
93
129 51.5/91.5
A7E44202023
25
50
28
63/65
75
28
93
245
93
129 51.5/91.5
A7E44202023
8a
25
50
28
63/65
75
28
93
245
93
129 51.5/91.5
A7E44202023
8a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122 56.5/96.5
A7E44202023
9a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122 56.5/96.5
A7E44202023
9a
16
50
17.9 40/42
75
28
93
245
93
129 51.5/91.5
A7E44202024
16
50
17.9 40/42
75
28
93
245
93
129 51.5/91.5
A7E44202024
16
50
17.9 40/42
75
28
2.5
90
255
98
122 62.5/102.5
A7E44202024
6a
Ima
Up
Ud
kA
kA
kV
kV
mV
12 kV
3AE5 154-1...
3AE5 155-1...
3AE5 162-1...
3AE5 163-1...
3AE5 164-1...
3AE5 165-1...
3AE5 172-1...
3AE5 173-1...
3AE5 174-1...
3AE5 175-1
3AE5 182-1...
mm mm
Isc
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
mm mm mm mm
kg
57
Technical Data
20
50
22.4 50/52
75
28
93
245
93
129 51.5/91.5
A7E44202024
20
50
22.4 50/52
75
28
93
245
93
129 51.5/91.5
A7E44202024
20
50
22.4 50/52
75
28
2.5
90
255
98
122 62.5/102.5
A7E44202024
7a
25
50
28
63/65
75
28
93
245
93
129 51.5/91.5
A7E44202024
8a
25
50
28
63/65
75
28
93
245
93
129 51.5/91.5
A7E44202024
8a
25
50
28
63/65
75
28
2.5
90
255
98
122 62.5/102.5
A7E44202024
8b
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122 56.5/96.5
A7E44202024
9a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122 56.5/96.5
A7E44202024
9a
31.5
50
35.4 80/82
75
28
2.5
90
255
98
122 62.5/102.5
A7E44202024
9a
25
50
44.9 63/65
75
28
93
245
93
129
49/
A7E44202024
8a
25
50
44.9 63/65
75
28
93
245
93
129
49/
A7E44202024
8a
31.5
50
35.4 80/82
75
28
2.5
90
66.5/
A7E44202038
31.5
50
35.4 80/82
75
28
2.5
90
66.5/
A7E44202038
31.5
50
35.4 80/82
75
28
2.5
90
69.5/
A7E44202040
31.5
50
35.4 80/82
75
28
2.5
90
74.5/
A7E44202040
Up
Ud
kA
kV
kV
mV
3AE5 183-1...
3AE5 184-1...
3AE5 185-1
3AE5 554-1...
3AE5 555-1
mm mm
Isc
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
Ima
12 kV
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
mm mm mm mm
kg
58
Technical Data
16
36
17.9 40/42
75
28
2.1
75
67/
A7E44202010
16
36
17.9 40/42
75
28
2.1
75
67/
A7E44202010
20
36
22.4 50/52
75
28
2.1
75
67/
A7E44202010
20
36
22.4 50/52
75
28
2.1
75
67/
A7E44202010
25
36
28
63/65
75
28
2.1
75
67/
A7E44202010
8a
25
36
28
63/65
75
28
2.1
75
67/
A7E44202010
8a
31.5
36
35.4 80/82
75
28
2.1
75
80/
A7E44202010
31.5
36
35.4 80/82
75
28
2.1
75
80/
A7E44202010
16
36
17.9 40/42
75
28
2.1
75
67/103
A7E44202011
16
36
17.9 40/42
75
28
2.1
75
67/103
A7E44202011
20
36
22.4 50/52
75
28
2.1
75
67/103
A7E44202011
20
36
22.4 50/52
75
28
2.1
75
67/103
A7E44202011
25
36
28
63/65
75
28
2.1
75
67/103
A7E44202011
8a
25
36
28
63/65
75
28
2.1
75
67/103
A7E44202011
8a
31.5
36
35.4 80/82
75
28
2.1
75
80/120
A7E44202011
31.5
36
35.4 80/82
75
28
2.1
75
80/120
A7E44202011
16
36
17.9 40/42
75
28
2.1
75
67/103
A7E44202012
16
36
17.9 40/42
75
28
2.1
75
67/103
A7E44202012
20
36
22.4 50/52
75
28
2.1
75
67/103
A7E44202012
20
36
22.4 50/52
75
28
2.1
75
67/103
A7E44202012
25
36
28
63/65
75
28
2.1
75
67/103
A7E44202012
8a
25
36
28
63/65
75
28
2.1
75
67/103
A7E44202012
8a
31.5
36
35.4 80/82
75
28
2.1
75
80/120
A7E44202012
31.5
36
35.4 80/82
75
28
2.1
75
80/120
A7E44202012
16
36
17.9 40/42
75
28
2.1
75
67/
A7E44202016
16
36
17.9 40/42
75
28
2.1
75
67/
A7E44202016
Ima
Up
Ud
kA
kV
kV
mV
mm mm mm mm
12 kV
3AE1 102-1...
3AE1 103-1...
3AE1 104-1...
3AE1 105-1...
3AE1 112-1...
3AE1 113-1...
3AE1 114-1...
3AE1 115-1...
3AE1 122-1...
3AE1 123-1...
3AE1 124-1...
3AE1 125-1...
3AE1 132-1...
mm mm
ISC
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
kg
59
Technical Data
20
36
22.4 50/52
75
28
2.1
75
67/
A7E44202016
20
36
22.4 50/52
75
28
2.1
75
67/
A7E44202016
25
36
28
63/65
75
28
2.1
75
67/
A7E44202016
8a
25
36
28
63/65
75
28
2.1
75
67/
A7E44202016
8a
31.5
36
35.4 80/82
75
28
2.1
75
80/
A7E44202016
31.5
36
35.4 80/82
75
28
2.1
75
80/
A7E44202016
16
36
17.9 40/42
75
28
2.1
75
67/
A7E44202017
16
36
17.9 40/42
75
28
2.1
75
67/
A7E44202017
20
36
22.4 50/52
75
28
2.1
75
67/
A7E44202017
20
36
22.4 50/52
75
28
2.1
75
67/
A7E44202017
25
36
28
63/65
75
28
2.1
75
67/
A7E44202017
8a
25
36
28
63/65
75
28
2.1
75
67/
A7E44202017
8a
31.5
36
35.4 80/82
75
28
2.1
75
80/
A7E44202017
31.5
36
35.4 80/82
75
28
2.1
75
80/
A7E44202017
16
36
17.9 40/42
75
28
2.1
75
67/
A7E44202018
16
36
17.9 40/42
75
28
2.1
75
67/
A7E44202018
20
36
22.4 50/52
75
28
2.1
75
67/
A7E44202018
20
36
22.4 50/52
75
28
2.1
75
67/
A7E44202018
25
36
28
63/65
75
28
2.1
75
67/
A7E44202018
8a
25
36
28
63/65
75
28
2.1
75
67/
A7E44202018
8a
31.5
36
35.4 80/82
75
28
2.1
75
80/
A7E44202018
31.5
36
35.4 80/82
75
28
2.1
75
80/
A7E44202018
16
36
17.9 40/42
75
28
2.1
75
67/
A7E44202022
16
36
17.9 40/42
75
28
2.1
75
67/
A7E44202022
20
36
22.4 50/52
75
28
2.1
75
67/
A7E44202022
20
36
22.4 50/52
75
28
2.1
75
67/
A7E44202022
Up
Ud
kA
kV
kV
mV
mm mm mm mm
3AE1 133-1...
3AE1 134-1...
3AE1 135-1...
3AE1 142-1...
3AE1 143-1...
3AE1 144-1...
3AE1 145-1...
3AE1 152-1...
3AE1 153-1...
3AE1 154-1...
3AE1 155-1...
3AE1 162-1...
3AE1 163-1...
mm mm
ISC
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
Ima
12 kV
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
kg
60
Technical Data
25
36
28
63/65
75
28
2.1
75
67/
A7E44202022
8a
25
36
28
63/65
75
28
2.1
75
67/
A7E44202022
8a
31.5
36
35.4 80/82
75
28
2.1
75
90/
A7E44202022
31.5
36
35.4 80/82
75
28
2.1
75
90/
A7E44202022
16
36
17.9 40/42
75
28
2.1
75
67/103
A7E44202023
16
36
17.9 40/42
75
28
2.1
75
67/103
A7E44202023
20
36
22.4 50/52
75
28
2.1
75
67/103
A7E44202023
20
36
22.4 50/52
75
28
2.1
75
67/103
A7E44202023
25
36
28
63/65
75
28
2.1
75
67/103
A7E44202023
8a
25
36
28
63/65
75
28
2.1
75
67/103
A7E44202023
8a
31.5
36
35.4 80/82
75
28
2.1
75
90/130
A7E44202023
31.5
36
35.4 80/82
75
28
2.1
75
90/130
A7E44202023
16
36
17.9 40/42
75
28
2.1
75
67/103
A7E44202024
16
36
17.9 40/42
75
28
2.1
75
67/103
A7E44202024
20
36
22.4 50/52
75
28
2.1
75
67/103
A7E44202024
20
36
22.4 50/52
75
28
2.1
75
67/103
A7E44202024
25
36
28
63/65
75
28
2.1
75
67/103
A7E44202024
8a
25
36
28
63/65
75
28
2.1
75
67/103
A7E44202024
8a
25
36
28
63/65
75
28
1.5
A7E44202028
25
36
28
63/65
75
28
1.5
A7E44202028
31.5
36
35.4 80/82
75
28
2.1
75
90/130
A7E44202024
31.5
36
35.4 80/82
75
28
2.1
75
90/130
A7E44202024
31.5
36
35.4 80/82
75
28
1.5
A7E44202028
31.5
36
35.4 80/82
75
28
1.5
A7E44202028
40
36
44.9 100/104 75
28
1.7
A7E44202070
10
40
36
44.9 100/104 75
28
1.0
A7E44202071
10
Ima
Up
Ud
kA
kA
kV
kV
mV
mm mm mm mm
12 kV
3AE1 164-1...
3AE1 165-1...
3AE1 172-1...
3AE1 173-1...
3AE1 174-1...
3AE1 175-1...
3AE1 182-1...
3AE1 183-1...
3AE1 184-1...
3AE1 185-1...
mm mm
ISC
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
kg
61
Technical Data
Ima
Up
Ud
kA
kV
kV
mV
mm mm mm mm
40
36
44.9 100/104 75
28
1.0
A7E44202071
10
40
36
44.9 100/104 75
28
1.0
A7E44202071
10
tk
ISC
kA
Ir
A
kg
25
36
44.9 63/65
75
28
2.1
75
67/
8a
25
36
44.9 63/65
75
28
2.1
75
67/
8a
31.5
36
44.9 80/82
75
28
2.1
75
80/
31.5
36
44.9 80/82
75
28
2.1
75
80/
31.5
36
44.9 80/82
75
28
2.1
75
90/
31.5
36
44.9 80/82
75
28
40
36
44.9 100/104 75
28
1.7
120/
10
40
36
44.9 100/104 75
28
1.0
160/
10
40
36
44.9 100/104 75
28
1.0
160/
10
3AE1 554-1...
3AE1 555-1...
20 000
1 000
10 000
2 000
5 000
2 000
1 000
5 000
2 000
1 000
500
500
500
200
200
200
100
70
46
30
20
10
0.5
8a
6
7
1
16 25 kA 50
20
Breaking current (r.m.s. value)
10
100
70
46
30
80
50
6a 8b
7a 9a
20
10
0.5
HG11-2734b_en eps
20 000
10 000
5 000
62
HG11-2889_en eps
20 000
10 000
mm mm
DC component in % of the
rated short-circuit breaking current
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
12 kV
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
16 25 kA 50
20 31.5
Breaking current (r.m.s. value)
10
100
20
10
0.5
8
1
10 kA 20 25 40 50
31.5
Breaking current (r.m.s. value)
2
of the breaking current (r.m.s. value). All SION vacuum circuit-breakers full
average experience data. The number of operating cycles that can actually
the endurance classes E2, M2 and C2 according to IEC 62271-100. The curve
10
Technical Data
12.5
50
14.9 31/33
95
38
2.5
54/
A7E44202010
11a
12.5
50
14.9 31/33
95
38
2.5
54/
A7E44202010
11a
16
50
17.9 40/42
95
38
2.5
54/
A7E44202010
12a
16
50
17.9 40/42
95
38
2.5
54/
A7E44202010
12a
25
50
28
63/65
95
38
2.5
54/
A7E44202010
13a
25
50
28
63/65
95
38
2.5
54/
A7E44202010
13a
12.5
50
14.9 31/33
95
38
2.5
54/94
A7E44202011
11a
12.5
50
14.9 31/33
95
38
2.5
54/94
A7E44202011
11a
16
50
17.9 40/42
95
38
2.5
54/94
A7E44202011
12a
16
50
17.9 40/42
95
38
2.5
54/94
A7E44202011
12a
25
50
28
63/65
95
38
2.5
54/94
A7E44202011
13a
25
50
28
63/65
95
38
2.5
54/94
A7E44202011
13a
12.5
50
14.9 31/33
95
38
2.5
54/94
A7E44202012
11a
12.5
50
14.9 31/33
95
38
2.5
54/94
A7E44202012
11a
12.5
50
14.9 31/33
95
38
2.5
60/100
A7E44202012
11a
16
50
17.9 40/42
95
38
2.5
54/94
A7E44202012
12a
16
50
17.9 40/42
95
38
2.5
54/94
A7E44202012
12a
16
50
17.9 40/42
95
38
2.5
60/100
A7E44202012
12a
25
50
28
63/65
95
38
2.5
54/94
A7E44202012
13a
25
50
28
63/65
95
38
2.5
54/94
A7E44202012
13a
25
50
28
63/65
95
38
2.5
60/100
A7E44202012
13a
12.5
50
14.9 31/33
95
38
2.5
54/
A7E44202016
11a
12.5
50
14.9 31/33
95
38
2.5
54/
A7E44202016
11a
16
50
17.9 40/42
95
38
2.5
54/
A7E44202016
12a
16
50
17.9 40/42
95
38
2.5
54/
A7E44202016
12a
25
50
28
63/65
95
38
2.5
54/
A7E44202016
13a
25
50
28
63/65
95
38
2.5
54/
A7E44202016
13a
Ima
Up
Ud
kA
kV
kV
mV
mm mm mm mm
kg
17.5 kV
3AE5 201-1...
3AE5 202-1...
3AE5 204-1...
3AE5 211-1...
3AE5 212-1...
3AE5 214-1...
3AE5 221-1...
3AE5 222-1...
3AE5 224-1...
3AE5 231-1...
3AE5 232-1...
3AE5 234-1...
mm mm
ISC
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
63
Technical Data
12.5
50
14.9 31/33
95
38
2.5
54/
A7E44202017
11a
12.5
50
14.9 31/33
95
38
2.5
54/
A7E44202017
11a
16
50
17.9 40/42
95
38
2.5
54/
A7E44202017
12a
16
50
17.9 40/42
95
38
2.5
54/
A7E44202017
12a
25
50
28
63/65
95
38
2.5
54/
A7E44202017
13a
25
50
28
63/65
95
38
2.5
54/
A7E44202017
13a
12.5
50
14.9 31/33
95
38
2.5
54/
A7E44202018
11a
12.5
50
14.9 31/33
95
38
2.5
54/
A7E44202018
11a
12.5
50
14.9 31/33
95
38
2.5
60/
A7E44202018
11a
16
50
17.9 40/42
95
38
2.5
54/
A7E44202018
12a
16
50
17.9 40/42
95
38
2.5
54/
A7E44202018
12a
16
50
17.9 40/42
95
38
2.5
60/
A7E44202018
12a
25
50
28
63/65
95
38
2.5
54/
A7E44202018
13a
25
50
28
63/65
95
38
2.5
54/
A7E44202018
13a
25
50
28
63/65
95
38
2.5
60/
A7E44202018
13a
12.5
50
14.9 31/33
95
38
2.5
57/
A7E44202022
11a
12.5
50
14.9 31/33
95
38
2.5
57/
A7E44202022
11a
16
50
17.9 40/42
95
38
2.5
57/
A7E44202022
12a
16
50
17.9 40/42
95
38
2.5
57/
A7E44202022
12a
25
50
28
63/65
95
38
2.5
57/
A7E44202022
13a
25
50
28
63/65
95
38
2.5
57/
A7E44202022
13a
12.5
50
14.9 31/33
95
38
2.5
57/97
A7E44202023
11a
12.5
50
14.9 31/33
95
38
2.5
57/97
A7E44202023
11a
16
50
17.9 40/42
95
38
2.5
57/97
A7E44202023
12a
16
50
17.9 40/42
95
38
2.5
57/97
A7E44202023
12a
25
50
28
63/65
95
38
2.5
57/97
A7E44202023
13a
25
50
28
63/65
95
38
2.5
57/97
A7E44202023
13a
Up
Ud
kA
kV
kV
mV
mm mm mm mm
kg
3AE5 241-1...
3AE5 242-1...
3AE5 244-1...
3AE5 251-1...
3AE5 252-1...
3AE5 254-1...
3AE5 261-1...
3AE5 262-1...
3AE5 264-1...
3AE5 271-1
3AE5 272-1
3AE5 274-1
mm mm
ISC
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
Ima
17.5 kV
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
64
Technical Data
12.5
50
14.9 31/33
95
38
2.5
57/97
A7E44202024
11a
12.5
50
14.9 31/33
95
38
2.5
57/97
A7E44202024
11a
12.5
50
14.9 31/33
95
38
2.5
63/103
A7E44202024
11a
16
50
17.9 40/42
95
38
2.5
57/97
A7E44202024
12a
16
50
17.9 40/42
95
38
2.5
57/97
A7E44202024
12a
16
50
17.9 40/42
95
38
2.5
63/103
A7E44202024
12a
25
50
28
63/65
95
38
2.5
57/97
A7E44202024
13a
25
50
28
63/65
95
38
2.5
57/97
A7E44202024
13a
25
50
28
63/65
95
38
2.5
63/103
A7E44202024
13a
25
50
28
63/65
95
38
2.5
67/
A7E44202038
25
50
28
63/65
95
38
2.5
67/
A7E44202038
25
50
28
63/65
95
38
2.5
70/
A7E44202040
25
50
28
63/65
95
38
2.5
75/
A7E44202040
Ima
Up
Ud
kA
kV
kV
mV
mm mm mm mm
kg
3AE5 281-1
3AE5 282-1
3AE5 284-1
3AE5 624-1
mm mm
tk
ISC
kA
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
and NXAIR
kA
17.5 kV
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
65
Technical Data
12.5
36
14.9 31/33
95
38
2.1
80/
A7E44202013
11
12.5
36
14.9 31/33
95
38
2.1
80/
A7E44202013
11
16
36
17.9 40/42
95
38
2.1
80/
A7E44202013
12
16
36
17.9 40/42
95
38
2.1
80/
A7E44202013
12
25
36
28
63/65
95
38
2.1
80/
A7E44202013
13
25
36
28
63/65
95
38
2.1
80/
A7E44202013
13
31.5
36
35.4 80/82
95
38
2.1
80/
A7E44202013
14
31.5
36
35.4 80/82
95
38
2.1
80/
A7E44202013
14
12.5
36
14.9 31/33
95
38
2.1
A7E44202014
11
12.5
36
14.9 31/33
95
38
2.1
A7E44202014
11
16
36
17.9 40/42
95
38
2.1
A7E44202014
12
16
36
17.9 40/42
95
38
2.1
A7E44202014
12
25
36
28
63/65
95
38
2.1
A7E44202014
13
25
36
28
63/65
95
38
2.1
A7E44202014
13
31.5
36
35.4 80/82
95
38
2.1
A7E44202014
14
31.5
36
35.4 80/82
95
38
2.1
A7E44202014
14
12.5
36
14.9 31/33
95
38
2.1
A7E44202015
11
12.5
36
14.9 31/33
95
38
2.1
A7E44202015
11
16
36
17.9 40/42
95
38
2.1
A7E44202015
12
16
36
17.9 40/42
95
38
2.1
A7E44202015
12
25
36
28
63/65
95
38
2.1
A7E44202015
13
25
36
28
63/65
95
38
2.1
A7E44202015
13
31.5
36
35.4 80/82
95
38
2.1
A7E44202015
14
31.5
36
35.4 80/82
95
38
2.1
A7E44202015
14
12.5
36
14.9 31/33
95
38
2.1
80/
A7E44202019
11
12.5
36
14.9 31/33
95
38
2.1
80/
A7E44202019
11
Up
Ud
kA
kV
kV
mV
mm mm mm mm
kg
3AE1 201-1...
3AE1 202-1...
3AE1 204-1...
3AE1 205-1...
3AE1 211-1...
3AE1 212-1...
3AE1 214-1...
3AE1 215-1...
3AE1 221-1...
3AE1 222-1...
3AE1 224-1...
3AE1 225-1...
3AE1 231-1...
mm mm
ISC
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
Ima
17.5 kV
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
66
Technical Data
16
36
17.9 40/42
95
38
2.1
80/
A7E44202019
12
16
36
17.9 40/42
95
38
2.1
80/
A7E44202019
12
25
36
28
63/65
95
38
2.1
80/
A7E44202019
13
25
36
28
63/65
95
38
2.1
80/
A7E44202019
13
31.5
36
35.4 80/82
95
38
2.1
80/
A7E44202019
14
31.5
36
35.4 80/82
95
38
2.1
80/
A7E44202019
14
12.5
36
14.9 31/33
95
38
2.1
80/
A7E44202020
11
12.5
36
14.9 31/33
95
38
2.1
80/
A7E44202020
11
16
36
17.9 40/42
95
38
2.1
80/
A7E44202020
12
16
36
17.9 40/42
95
38
2.1
80/
A7E44202020
12
25
36
28
63/65
95
38
2.1
80/
A7E44202020
13
25
36
28
63/65
95
38
2.1
80/
A7E44202020
13
31.5
36
35.4 80/82
95
38
2.1
80/
A7E44202020
14
31.5
36
35.4 80/82
95
38
2.1
80/
A7E44202020
14
12.5
36
14.9 31/33
95
38
2.1
80/
A7E44202021
11
12.5
36
14.9 31/33
95
38
2.1
80/
A7E44202021
11
16
36
17.9 40/42
95
38
2.1
80/
A7E44202021
12
16
36
17.9 40/42
95
38
2.1
80/
A7E44202021
12
25
36
28
63/65
95
38
2.1
80/
A7E44202021
13
25
36
28
63/65
95
38
2.1
80/
A7E44202021
13
31.5
36
35.4 80/82
95
38
2.1
80/
A7E44202021
14
31.5
36
35.4 80/82
95
38
2.1
80/
A7E44202021
14
12.5
36
14.9 31/33
95
38
2.1
90/
A7E44202025
11
12.5
36
14.9 31/33
95
38
2.1
90/
A7E44202025
11
16
36
17.9 40/42
95
38
2.1
90/
A7E44202025
12
16
36
17.9 40/42
95
38
2.1
90/
A7E44202025
12
Ima
Up
Ud
kA
kV
kV
mV
mm mm mm mm
kg
17.5 kV
3AE1 232-1...
3AE1 234-1...
3AE1 235-1...
3AE1 241-1...
3AE1 242-1...
3AE1 244-1...
3AE1 245-1...
3AE1 251-1...
3AE1 252-1...
3AE1 254-1...
3AE1 255-1...
3AE1 261-1...
3AE1 262-1...
mm mm
ISC
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
67
Technical Data
25
36
28
63/65
95
38
2.1
90/
A7E44202025
13
25
36
28
63/65
95
38
2.1
90/
A7E44202025
13
31.5
36
35.4 80/82
95
38
2.1
90/
A7E44202025
14
31.5
36
35.4 80/82
95
38
2.1
90/
A7E44202025
14
12.5
36
14.9 31/33
95
38
2.1
A7E44202026
11
12.5
36
14.9 31/33
95
38
2.1
A7E44202026
11
16
36
17.9 40/42
95
38
2.1
A7E44202026
12
16
36
17.9 40/42
95
38
2.1
A7E44202026
12
25
36
28
63/65
95
38
2.1
A7E44202026
13
25
36
28
63/65
95
38
2.1
A7E44202026
13
31.5
36
35.4 80/82
95
38
2.1
A7E44202026
14
31.5
36
35.4 80/82
95
38
2.1
A7E44202026
14
12.5
36
14.9 31/33
95
38
2.1
A7E44202027
11
12.5
36
14.9 31/33
95
38
2.1
A7E44202027
11
16
36
17.9 40/42
95
38
2.1
A7E44202027
12
16
36
17.9 40/42
95
38
2.1
A7E44202027
12
25
36
28
63/65
95
38
2.1
A7E44202027
13
25
36
28
63/65
95
38
2.1
A7E44202027
13
25
36
28
63/65
95
38
1.5
A7E44202029
13
25
36
28
63/65
95
38
1.5
A7E44202029
13
31.5
36
35.4 80/82
95
38
2.1
A7E44202027
14
31.5
36
35.4 80/82
95
38
2.1
A7E44202027
14
31.5
36
35.4 80/82
95
38
1.5
A7E44202029
14
31.5
36
35.4 80/82
95
38
1.5
A7E44202029
14
40
36
44.9 100/104 95
38
1.7
A7E44202070
15
40
36
44.9 100/104 95
38
1.0
A7E44202071
15
Up
Ud
kA
kA
kV
kV
mV
mm mm mm mm
kg
3AE1 264-1...
3AE1 265-1...
3AE1 271-1...
3AE1 272-1...
3AE1 274-1...
3AE1 275-1...
3AE1 281-1...
3AE1 282-1...
3AE1 284-1...
3AE1 285-1...
mm mm
ISC
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
Ima
17.5 kV
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
68
Technical Data
Ima
Up
Ud
kA
kV
kV
mV
mm mm mm mm
40
36
44.9 100/104 95
38
1.0
A7E44202071
15
40
36
44.9 100/104 95
38
1.0
A7E44202071
15
31.5
36
44.9 80/82
95
38
2.1
80/
14
31.5
36
44.9 80/82
95
38
2.1
80/
14
31.5
36
44.9 80/82
95
38
2.1
90/
14
31.5
36
44.9 80/82
95
38
14
40
36
44.9 100/104 95
38
1.7
120/
15
40
36
44.9 100/104 95
38
1.0
160/
15
40
36
44.9 100/104 95
38
1.0
160/
15
3AE1 625-1...
mm mm
tk
ISC
kA
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
17.5 kV
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
kg
20 000
2 000
1 000
80
10 000
5 000
5 000
2 000
1 000
5 000
2 000
1 000
500
500
500
350
200
200
200
100
100
100
60
50
HG11-2541b_en eps
20 000
10 000
10 000
180
HG11-2890_en eps
20 000
80
11
50
50
30
20
10
0.5
12 13
1
15
16 20 kA 40 50
25
Breaking current (r.m.s. value)
10
20
10
0.5
12a 13a
16 20 kA 50
25
Breaking current (r.m.s. value)
10
20
10
0.5
11a
14
20 31.5 50
5 kA 10
12.5
Breaking current (r.m.s. value)
of the breaking current (r.m.s. value). All SION vacuum circuit-breakers full
average experience data. The number of operating cycles that can actually
the endurance classes E2, M2 and C2 according to IEC 62271-100. The curve
69
Technical Data
12.5
36
14.9 31/33
125
50
2.6
A7E44202050
16
12.5
36
14.9 31/33
125
50
2.6
A7E44202050
16
16
36
17.9 40/42
125
50
2.6
A7E44202050
17
16
36
17.9 40/42
125
50
2.6
A7E44202050
17
16
36
17.9 40/42
125
50
2.0
A7E44202051
17
20
36
22.4 50/52
125
50
2.6
A7E44202050
18
20
36
22.4 50/52
125
50
2.6
A7E44202050
18
20
36
22.4 50/52
125
50
2.0
A7E44202051
18
20
36
22.4 50/52
125
50
2.0
A7E44202051
18
25
36
28
63/65
125
50
2.6
A7E44202050
19
25
36
28
63/65
125
50
2.6
A7E44202050
19
25
36
28
63/65
125
50
2.0
A7E44202051
19
25
36
28
63/65
125
50
2.0
A7E44202051
19
16
36
17.9 40/42
125
50
2.6
A7E44202052
17
16
36
17.9 40/42
125
50
2.6
A7E44202052
17
16
36
17.9 40/42
125
50
2.0
A7E44202053
17
20
36
22.4 50/52
125
50
2.6
A7E44202052
18
20
36
22.4 50/52
125
50
2.6
A7E44202052
18
20
36
22.4 50/52
125
50
2.0
A7E44202053
18
20
36
22.4 50/52
125
50
2.0
A7E44202053
18
Up
Ud
kA
kV
kV
mV
mm mm mm mm
3AE1 321-1...
3AE1 322-1...
3AE1 323-1...
3AE1 324-1...
3AE1 352-1...
3AE1 353-1...
mm mm
ISC
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
kA
Ima
24 kV
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
kg
70
Technical Data
Ima
Up
Ud
kA
kA
kV
kV
mV
mm mm mm mm
25
36
28
63/65
125
50
2.6
A7E44202052
19
25
36
28
63/65
125
50
2.6
A7E44202052
19
25
36
28
63/65
125
50
2.0
A7E44202053
19
25
36
28
63/65
125
50
2.0
A7E44202053
19
25
36
28
63/65
125
50
2.6
120/
19
25
36
28
63/65
125
50
2.0
150/
19
25
36
44.9 63/65
125
50
2.0
150/
19
A
3AE1 354-1...
mm mm
ISC
kA
tk
DC component in % of the
rated short-circuit breaking current
Ir
O 0.3 s CO 15 s CO
O 0.3 s CO 3 min CO
O 3 min CO 3 min CO
Pole-center distance
Order No.
50 / 60 Hz
24 kV
Weight 1)
(xed-mounted circuit-breaker / withdrawable
module)
kg
20 000
10 000
10 000
5 000
2 000
1 000
150
HG11-2542b_en eps
20 000
5 000
2 000
1 000
500
500
200
200
100
90
100
50
50
30
20
20
16
10
0.5
17 19
18
10 12.5 20 kA
50
10
0.5
10
16 25 kA 50
of the breaking current (r.m.s. value). All SION vacuum circuit-breakers full
average experience data. The number of operating cycles that can actually
the endurance classes E2, M2 and C2 according to IEC 62271-100. The curve
71
Technical Data
Dimensions drawings for voltage levels 7.2 kV to 17.5 kV for 3AE5
c
q
d
e
HG11-2834 eps
o
g
f
Voltage level
7.2 kV
3
12 kV
17.5 kV
Pole-center
distance a
mm
Width across
ats b
mm
c
mm
d
mm
e
mm
f
mm
g
mm
l
mm
m
mm
n
mm
o
mm
p
mm
q
mm
150
205
445
540
217.5
380
540
105
288
169
150
275
445
540
217.5
380
540
105
288
169
150
310
445
540
237.5
380
540
105
288
169
160
205
465
540
217.5
380
540
105
288
169
160
275
465
540
217.5
380
540
105
288
169
160
310
465
540
237.5
380
540
105
288
169
210
205
565
540
217.5
380
540
105
288
169
210
275
565
540
217.5
380
540
105
288
169
210
310
565
540
237.5
380
540
105
288
169
150
205
445
540
217.5
380
540
105
288
169
150
275
445
540
217.5
380
540
105
288
169
150
310
445
540
237.5
380
540
105
288
169
160
205
465
540
217.5
380
540
105
288
169
160
275
465
540
217.5
380
540
105
288
169
160
310
465
540
237.5
380
540
105
288
169
210
205
565
540
217.5
380
540
105
288
169
210
275
565
540
217.5
380
540
105
288
169
210
310
565
540
237.5
380
540
105
288
169
150
205
445
540
217.5
380
329
540
371
540
105
288
169
150
275
445
540
217.5
380
329
540
371
540
105
288
169
150
310
445
540
237.5
380
329
540
371
540
105
288
169
160
205
465
540
217.5
380
329
540
371
540
105
288
169
160
275
465
540
217.5
380
329
540
371
540
105
288
169
160
310
465
540
237.5
380
329
540
371
540
105
288
169
210
205
565
540
217.5
380
329
540
371
540
105
288
169
210
275
565
540
217.5
380
329
540
371
540
105
288
169
210
310
565
540
237.5
380
329
540
371
540
105
288
169
72
i
mm
Technical Data
Dimensions drawings for voltage levels 7.2 kV to 24 kV for 3AE1
HG11-2813a eps
d
e
g
f
Voltage level
7.2 kV
12 kV
17.5 kV
24 kV
Pole-center
distance a
mm
Width across
ats b
mm
c
mm
d
mm
e
mm
f
mm
g
mm
i
mm
l
mm
m
mm
n
mm
o
mm
p
mm
q
mm
150
205
445
540 5)
217.5
380
300 6)
523 7)
371
540
105
30
279
165
150
275
445
540 5)
217.5
380
300 6)
523 7)
371
540
105
30
279
165
150
310
445
540 5)
237.5
380
300 6)
523 7)
371
540
105
30
279
165
160
205
465
540 5)
217.5
380
300 6)
523 7)
371
540
105
30
279
165
160
275
465
540 5)
217.5
380
300 6)
523 7)
371
540
105
30
279
165
160
310
465
540 5)
237.5
380
300 6)
523 7)
371
540
105
30
279
165
210
205
565
540 5)
217.5
380
300 6)
523 7)
371
540
105
30
279
165
210
275
565
540 5)
217.5
380
300 6)
523 7)
371
540
105
30
279
165
210
310
565
540 5)
237.5
380 1)
300 2) 6)
540
105
30 8)
279
165
523 3) 7) 371 4)
150
205
445
540 5)
217.5
380
300 6)
523 7)
371
540
105
30
279
165
150
275
445
540 5)
217.5
380
300 6)
523 7)
371
540
105
30
279
165
150
310
445
540
5)
237.5
380
300
523
7)
371
540
105
30
279
165
160
205
465
540 5)
217.5
380
300 6)
523 7)
371
540
105
30
279
165
160
275
465
540 5)
217.5
380
300 6)
523 7)
371
540
105
30
279
165
160
310
465
540 5)
237.5
380
300 6)
523 7)
371
540
105
30
279
165
210
205
565
540 5)
217.5
380
300 6)
523 7)
371
540
105
30
279
165
210
275
565
540 5)
217.5
380
300 6)
523 7)
371
540
105
30
279
165
210
310
565
540 5)
237.5
380 1)
540
105
30 8)
279
165
150
205
445
562
217.5
380
310
517.5
371
540
105
30
279
165
150
275
445
562
217.5
380
310
517.5
371
540
105
30
279
165
150
310
445
562
237.5
380
310
517.5
371
540
105
30
279
165
160
205
465
562
217.5
380
310
517.5
371
540
105
30
279
165
160
275
465
562
217.5
380
310
517.5
371
540
105
30
279
165
160
310
465
562
237.5
380
310
517.5
371
540
105
30
279
165
210
205
565
562
217.5
380
310
517.5
371
540
105
30
279
165
210
275
565
562
217.5
380
310
517.5
371
540
105
30
279
165
210
310
565
562
237.5
380 1)
310 2)
540
105
30 8)
279
165
210
310
570
739
283
469
360
739
421
540
105
58
279
165
275
310
700
739
283
469
360
739
421
540
105
58
279
165
6)
517.5 3) 371 4)
Note: Dimension drawings for 8B retrot (13th position = 7) are available on request.
Note: Small deviations of the dimensions are permissible
1)
2)
3)
4)
5)
6)
7)
8)
73
Technical Data
Dimensions drawings for voltage levels 7.2 kV to 17.5 kV for 3AE5
c
q
HG11-2835 eps
o
g
f
Voltage level
7.2 kV
3
12 kV
17.5 kV
Pole-center
distance a
mm
Width across
ats b
mm
c
mm
e
mm
f
mm
g
mm
i
mm
k
mm
l
mm
m
mm
n
mm
o
mm
p
mm
q
mm
150
205
445
540
217.5
380
371
540
105
288
169
150
275
445
540
217.5
380
371
540
105
288
169
150
310
445
540
237.5
380
371
540
105
288
169
160
205
465
540
217.5
380
371
540
105
288
169
160
275
465
540
217.5
380
371
540
105
288
169
160
310
465
540
237.5
380
371
540
105
288
169
210
205
565
540
217.5
380
371
540
105
288
169
210
275
565
540
217.5
380
371
540
105
288
169
210
310
565
540
237.5
380
371
540
105
288
169
150
205
445
540
217.5
380
371
540
105
288
169
150
275
445
540
217.5
380
371
540
105
288
169
150
310
445
540
237.5
380
371
540
105
288
169
160
205
465
540
217.5
380
371
540
105
288
169
160
275
465
540
217.5
380
371
540
105
288
169
160
310
465
540
237.5
380
371
540
105
288
169
210
205
565
540
217.5
380
371
540
105
288
169
210
275
565
540
217.5
380
371
540
105
288
169
210
310
565
540
237.5
380
371
540
105
288
169
150
205
445
540
217.5
380
329
540
274
371
540
105
288
169
150
275
445
540
217.5
380
329
540
274
371
540
105
288
169
150
310
445
540
237.5
380
329
540
274
371
540
105
288
169
160
205
465
540
217.5
380
329
540
274
371
540
105
288
169
160
275
465
540
217.5
380
329
540
274
371
540
105
288
169
160
310
465
540
237.5
380
329
540
274
371
540
105
288
169
210
205
565
540
217.5
380
329
540
274
371
540
105
288
169
210
275
565
540
217.5
380
329
540
274
371
540
105
288
169
210
310
565
540
237.5
380
329
540
274
371
540
105
288
169
74
d
mm
Technical Data
Dimensions drawings for voltage levels 7.2 kV to 24 kV for 3AE1
c
q
d
e
HG11-2812a eps
Voltage level
7.2 kV
12 kV
17.5 kV
24 kV
g
f
Pole-center
distance a
mm
Width across
ats b
mm
c
mm
d
mm
e
mm
f
mm
g
mm
i
mm
k
mm
l
mm
m
mm
n
mm
o
mm
p
mm
q
mm
150
205
300 6)
523 7)
274
371
540
105
30
279
165
150
275
300 6)
523 7)
274
371
540
105
30
279
165
150
310
300 6)
523 7)
274
371
540
105
30
279
165
160
205
300 6)
523 7)
274
371
540
105
30
279
165
160
275
300 6)
523 7)
274
371
540
105
30
279
165
160
310
300 6)
523 7)
274
371
540
105
30
279
165
210
205
300 6)
523 7)
274
371
540
105
30
279
165
210
275
300 6)
523 7)
274
371
540
105
30
279
165
210
310
523 3) 7)
274
371 4)
540
105
30 8)
279
165
150
205
300 6)
523 7)
274
371
540
105
30
279
165
150
275
300 6)
523 7)
274
371
540
105
30
279
165
150
310
445 540
300
523
7)
274
371
540
105
30
279
165
160
205
300 6)
523 7)
274
371
540
105
30
279
165
160
275
300 6)
523 7)
274
371
540
105
30
279
165
160
310
300 6)
523 7)
274
371
540
105
30
279
165
210
205
300 6)
523 7)
274
371
540
105
30
279
165
210
275
300 6)
523 7)
274
371
540
105
30
279
165
210
310
274
371 4) 540
105
30 8)
279
165
150
205
445
310
517.5
274
371
540
105
30
279
165
150
275
445
310
517.5
274
371
540
105
30
279
165
150
310
445
310
517.5
274
371
540
105
30
279
165
160
205
465
310
517.5
274
371
540
105
30
279
165
160
275
465
310
517.5
274
371
540
105
30
279
165
160
310
465
310
517.5
274
371
540
105
30
279
165
210
205
565
310
517.5
274
371
540
105
30
279
165
210
275
565
310
517.5
274
371
540
105
30
279
165
210
310
565
310 2)
517.5 3)
274
371 4) 540
105
30 8)
279
165
210
310
570
739
283
469
360
739
324
421
540
105
58
279
165
275
310
700
739
283
469
360
739
324
421
540
105
58
279
165
5)
237.5 380
6)
75
Technical Data
Dimensions drawings for voltage levels 7.2 kV to 17.5 kV for 3AE5
k
l
HG11-2836 eps
Voltage level
Pole-center
distance a
mm
Width across
ats b
mm
c
mm
d
mm
e
mm
f
mm
g
mm
h
mm
i
mm
k
mm
l
mm
m
mm
n
mm
q
mm
150
275
594
147
850
266.5
710
263
224
476
371
540
105
169
150
310
594
147
905
286.5
710
263
224
476
371
540
105
169
210
275
794
187
850
266.5
710
263
224
476
371
540
105
169
210
310
794
187
905
286.5
710
263
224
476
371
540
105
169
150
275
594
147
850
266.5
710
263
224
476
371
540
105
169
150
310
594
147
905
286.5
710
263
224
476
371
540
105
169
210
275
794
187
850
266.5
710
263
224
476
371
540
105
169
210
310
794
187
905
286.5
710
263
224
476
371
540
105
169
150
205
594
147
850
266.5
710
263
224
476
371
540
105
169
150
275
594
147
905
286.5
710
263
224
476
371
540
105
169
210
205
794
187
850
266.5
710
263
224
476
371
540
105
169
210
275
794
187
905
286.5
710
263
224
476
371
540
105
169
7.2 kV
12 kV
17.5 kV
HG11-2590a eps
Withdrawable part
7.2 kV
12 kV
17.5 kV
24 kV
76
Voltage level
Pole-center distance
mm
a
mm
b
mm
c
mm
d
mm
e
mm
f
mm
Weight
150
529
424
500
470
107
42
approx. 15 kg
160
529
424
500
470
107
42
approx. 15 kg
210
679
424
650
620
107
42
approx. 20 kg
150
529
424
500
470
107
42
approx. 15 kg
160
529
424
500
470
107
42
approx. 15 kg
210
679
424
650
620
107
42
approx. 20 kg
150
529
424
500
470
107
42
approx. 15 kg
160
529
424
500
470
107
42
approx. 15 kg
210
679
424
650
620
107
42
approx. 20 kg
210
679
424
650
620
107
42
approx. 20 kg
275
879
424
850
820
107
42
approx. 25 kg
Technical Data
Dimensions drawings for voltage levels 7.2 kV to 24 kV for 3AE1
k
l
HG11-2782b eps
Voltage level
Pole-center
distance a
mm
Width across
ats b
mm
c
mm
d
mm
e
mm
150
275
594
147
150
310
594
147
210
275
794
210
310
150
150
7.2 kV
12 kV
17.5 kV
24 kV
f
mm
g
mm
h
mm
h
mm
i
mm
i
mm
k
mm
l
mm
m
mm
n
mm
q
mm
850
266.5 710
263
224
476
371
540
105
165
905
266.5 710
263
224
476
371
540
105
165
187
850
286.5 710
263
224
476
371
540
105
165
794
187
905
323
224
105
165
275
594
147
850
266.5 710
263
224
476
371
540
105
165
310
594
147
905
266.5 710
263
224
476
371
540
105
165
210
275
794
187
850
286.5 710
263
224
476
371
540
105
165
210
310
794
187
905
323
224
105
165
150
275
594
147
850
266.5 710
263
224
476
371
540
105
165
150
310
594
147
905
266.5 710
263
224
476
371
540
105
165
210
275
794
187
850
286.5 710
263
476
371
210
310
794
187
905
210
310
794
810
275
310
994
810
224
540
105
165
323
224
105
165
323
323
274
323
537
421
540
105
165
323
323
274
323
537
421
540
105
165
h/i = up to Ir = 1250 A
h/i = up to Ir = 2000 A, 2500 A and 3150 A
Note: Small deviations of the dimensions are permissible
1) At Isc = 40 kA --> 760 mm
2) At Isc = 40 kA --> 526 mm
3) At Isc = 40 kA --> 420 mm
HG11-2590a eps
Withdrawable part
Voltage level
7.2 kV
12 kV
17.5 kV
a
a
mm
b
mm
c
mm
d
mm
e
mm
f
mm
Weight
150
529
424
500
470
107
42
approx. 15 kg
160
529
424
500
470
107
42
approx. 15 kg
210
679
424
650
620
107
42
approx. 20 kg
150
529
424
500
470
107
42
approx. 15 kg
160
529
424
500
470
107
42
approx. 15 kg
210
679
424
650
620
107
42
approx. 20 kg
150
529
424
500
470
107
42
approx. 15 kg
160
529
424
500
470
107
42
approx. 15 kg
210
679
424
650
620
107
42
approx. 20 kg
210
679
424
650
620
107
42
approx. 20 kg
275
879
424
850
820
107
42
approx. 25 kg
24 kV
Pole-center distance
mm
77
Technical Data
Dimensions drawings for voltage levels 7.2 kV to 17.5 kV for 3AE5
c
l
HG11-2837 eps
h
r
t
u
Voltage level
7.2 kV
12 kV
17.5 kV
Voltage level
7.2 kV
12 kV
17.5 kV
78
Pole-center
distance a
mm
Width across
ats b
mm
c
mm
d
mm
e
mm
150
275
594
147
150
310
594
147
210
275
794
210
310
150
g
mm
h
mm
i
mm
k
mm
l
mm
m
mm
n
mm
850
266.5 710
263
224
476
371
540
105
905
286.5 710
263
224
476
371
540
105
187
850
266.5 710
263
224
476
371
540
105
794
187
905
286.5 710
263
224
476
371
540
105
275
594
147
850
266.5 710
263
224
476
371
540
105
150
310
594
147
905
286.5 710
263
224
476
371
540
105
210
275
794
187
850
266.5 710
263
224
476
371
540
105
210
310
794
187
905
286.5 710
263
224
476
371
540
105
150
275
594
147
850
266.5 710
263
224
476
371
540
105
150
310
594
147
905
286.5 710
263
224
476
371
540
105
210
275
794
187
850
266.5 710
263
224
476
371
540
105
210
310
794
187
905
286.5 710
263
224
476
371
540
105
o
mm
p
mm
q
mm
r
mm
s
mm
359
287
169
803
64
363
287
169
803
64
359
287
169
803
359
287
169
359
287
363
359
v
mm
w
mm
1142 1233
575
25
1142 1233
575
25
65
1143 1234
803
65
1142 1234
169
803
64
1142 1233
575
25
287
169
803
64
1142 1233
575
25
287
169
803
65
1143 1234
359
287
169
803
65
1143 1234
359
287
169
803
64
1142 1233
575
25
363
287
169
803
64
1142 1233
575
25
359
287
169
803
65
1143 1234
359
287
169
803
65
1143 1234
t
mm
u
mm
f
mm
Technical Data
Dimensions drawings for voltage levels 7.2 kV to 17.5 kV for 3AE1
Voltage level
7.2 kV
12 kV
17.5 kV
24 kV
Voltage level
7.2 kV
12 kV
17.5 kV
24 kV
Pole-center
distance a
mm
Width across
ats b
mm
c
mm
d
mm
e
mm
150
275
594
147
150
310
594
147
210
275
794
210
310
150
150
f
mm
g
mm
h
mm
h
mm
i
mm
i
mm
k
mm
l
mm
m
mm
n
mm
850
266.5 710
263
224
476
371
540
105
905
286.5 710
263
224
476
371
540
105
187
850
266.5 710
263
224
476
371
540
105
794
187
905
323
224
105
275
594
147
850
266.5 710
263
224
476
371
540
105
310
594
147
905
286.5 710
263
224
476
371
540
105
210
275
794
187
850
266.5 710
263
476
371
540
105
210
310
794
187
905
105
150
275
594
147
850
266.5 710
150
310
594
147
905
286.5 710
210
275
794
187
850
266.5 710
210
310
794
187
905
210
310
794
810
275
310
994
810
224
323
224
263
224
476
371
540
105
263
224
476
371
540
105
263
224
476
371
540
105
323
224
105
323
323
274
323
537
421
540
105
323
323
274
323
537
421
540
105
v
mm
w
mm
h / i = up to Ir = 1250 A
h / i = up to Ir = 2000 A, 2500 A and 3150 A
1142 1233
575
25
1142 1233
575
25
65
1143 1234
803
65
1142 1234
803
64
1142 1233
575
25
165
803
64
1142 1233
575
25
165
803
65
1143 1234
287
165
803
65
1143 1234
359
287
165
803
64
1142 1233
575
25
359
287
165
803
64
1142 1233
575
25
359
287
165
803
65
1143 1234
359
287
165
803
65
1143 1234
359
287
165
902
64
1243 1433
575
10
359
287
165
902
65
1243 1433
o
mm
p
mm
q
mm
r
mm
s
mm
359
287
165
803
64
359
287
165
803
64
359
287
165
803
359
287
165
359
287
165
359
287
359
287
359
t
mm
u
mm
79
Technical Data
Equipment of circuit-breaker
Closing time
Opening time
< 60 ms
< 60 ms
2nd release
< 45 ms
Arcing time
< 15 ms
Break time
< 75 ms
2nd release
< 60 ms
Dead time
300 ms
< 75 ms
2nd release
< 60 ms
Closing solenoid
45 ms
40 ms
2nd release
20 ms
> 10 ms
2nd release
> 6 ms
< 15
2 ms
Operating voltage
Power consumption
of the motor
max. V
min. V
W / VA
24 DC
26
20
140 + 50
48 DC
53
41
110
60 DC
66
51
130
110 DC
121
93
100
0.5
220 DC
242
187
110
0,315
110 AC
121
93
170
0.315
230 AC
244
187
200
0.25
1) The current inrush in the drive motor can be neglected due to its very short presence.
Power consumption
Tripping ranges
Operation at
Tripping voltage
Tripping voltage or
tripping current
at AC 50 / 60 Hz
DC
approx. W
AC 50 / 60 Hz
approx. VA
at DC
300 370
300 370
85 to 110 % U
85 to 110 % U
300
300
70 to 110 % U
85 to 110 % U
70
50
70 to 110 % U
85 to 110 % U
20
20
35 to
0%U
35 to
0%U
10 2)
90 to 110 % Ia
2) Consumption at pickup current (90 % of the rated normal current) and open armature.
80
Equipment of circuit-breaker
Closing time
< 60 ms
Opening time
< 60 ms
2nd release
< 45 ms
Arcing time
< 15 ms
Break time
< 75 ms
2nd release
< 60 ms
Dead time
300 ms
< 75 ms
2nd release
< 60 ms
Closing solenoid
45 ms
40 ms
2nd release
20 ms
> 15 ms
2nd release
> 10 ms
< 15
2 ms
Operating voltage
Power consumption
of the motor
max. V
min. V
W / VA
24 DC 2)
26
20
520 590
48 DC
53
41
470 600
60 DC
66
51
520 610
110 DC
121
93
650 740
220 DC
242
187
610 900
1.6
110 AC
121
93
670 740 VA
230 AC
244
187
620 960 VA
1.6
1) The current inrush in the drive motor can be neglected due to its very short presence.
2) Does not apply to a rated short-circuit breaking current of 40 kA.
Power consumption
Tripping ranges
Operation at
Tripping voltage
Tripping voltage or
tripping current
at DC
at AC 50 / 60 Hz
DC
approx. W
AC 50 / 60 Hz
approx. VA
140 210
140 210
85 to 110 % U
85 to 110 % U
140
140
70 to 110 % U
85 to 110 % U
70
50
70 to 110 % U
85 to 110 % U
20
20
35 to
0%U
35 to
0%U
10 2)
90 to 110 % Ia
2) Consumption at pickup current (90 % of the rated normal current) and open armature.
81
Technical Data
Circuit diagrams for 3AE1
Electrical closing
lock-out
Undervoltage
release
Low energy
c.t.-operated release
1st c.t.-operated
release 5A
1st c.t.-operated
release
DC
-Q0 -X0
-Q0 -X0
C2
C3
-Q0 -X0
A3
-Q0 -S1 23
D3
-Q0 -X0
A4
-Q0 -X0
-Q0 -X0
A4
A4
3)
C5
-Q0 -S1 33
24
-Q0 -X0
D5
A5
-Q0 -S1 43
1 L 2 N
34
44
-V4.1
4 3 +
1) 2)
1) 2)
A1
1) 2)
A1
-Q0 -Y1
A2
1) 2)
A1
-Q0 -Y2
A2
1) 2)
A1
-Q0 -Y4
A2
1) 2)
A1
-Q0 -Y4.1
-Q0 -Y6
A2
A2
D1
U
E1
-Q0 -Y7
D2
-Q0 -F1
E2
1
2
-Q0 -X0 D2
-Q0 -X0 B3
S_A7E_449_38020_001
-Q0 -X0 B4
S_A7E_449_38021_001
-Q0 -X0 B4
S_A7E_449_38024_004
Order code A49
S_A7E_449_38024_001
-Q0 -X0 B4
S_A7E_449_38023_001
Q1
Withdrawable part
-Q0 -X01 2
14
14
14
14
14
-Q0 -X02 2
14
14
14
HG11-2847 eps
-Q0 -X01
14
S_A7E_449_38085_001
-Q0 -X01
-Q0 -X0
A14
A15
A16
B14
B15
B16
C1
C4
-Q0 -X02
C15
C16
D1
D13
D14
D15
C13
C14
S_A7E_449_38085_002
82
HG11-2848 eps
-Q0 -X0
-Q0 -X0 B5
S_A7E_449_38026_001
-Q0 -X0 B1
HG11-2843 eps
-Q0 -R1
S_A7E_449_38030_001
Order code A49
Technical Data
Circuit diagrams for 3AE1
21
23
31
33
41
43
51
53
61
63
14
22
24
32
34
42
44
52
54
62
64
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
(-Y9)
S_A7E_449_38066_001
-Q0 -S1
(-Y1)
A8
(-Y2)
C8
Closed
Closed
Closed
Closed
Open
Closed
Open
Closed
Open
C8
A12
C12
A13
(-Y7)
11 13 21 23 31 33 41 43 51 53 61 63 71 73
81
12 14 22 24 32 34 42 44 52 54 62 64 72 74
82
1)
2)
2)
3)
-Q0 -X0
3)
D7
3)
B8
2)
2)
B12
2)
D12
2)
B13
2)
HG11-2846 eps
13
12
HG11-2849 eps
11
Closed
-Q0 -X0
C7
-Q8 -S1
Open
Open
Closed
Open
Closed
Open
Closed
Open
Closed
Open
Closed
Open
Closed
Open
Open
S_A7E_449_38063_001
Auxiliary switch 12NO/12NC
Motor charging
Closing and
anti-pumping with
mechanical interlocking
and closing lock-out
Additional equipment
-Q0 -X0
-Q0 -X0
A2
A1
2)
-Q0 -S21
21
-Q0 -S1 11
-Q0 -S3 21
12
22
-Q0 -K1 21
13
22
14
22
-Q0 -K1 31
A1
32
1) 2)
1)
-Q0 -M1
M
1=
A1
U
-Q0 -Y9
U -Q0 -K1
A2
D2
-Q0 -S5
13
14
22
-Q0 -S12 13
21
14
HG11-2841 eps
2)
S_A7E_449_38001_001
-Q0 -X0
B2
HG11-2842 eps
-Q0 -S22
S_A7E_449_38011_504
83
Technical Data
Circuit diagrams for 3AE1
-Q0 -S4 13
21
14
22
-Q0 -X0 B6
D6
A7
-Q0 -S6
A7
21
-Q0 -R01 1
22
-Q0 -X0 B7
-Q0 -X0 B7
HG11-2845 eps
C6
HG11-2844 eps
A6
S_A7E_449_33042_001
-Q0 -X0
-Q0 -X0
-Q0 -X0
Heating
Circuit breaker
tipping signal
Signal:
Spring charged
S_A7E_449_38043_001 S_A7E_449_38050_001
Order code A30
Contactor (anti-pumping)
Motor operating mechanism
Circuit-breaker wiring
Wiring of withdrawable part
Resistance
Auxiliary switch
Position switch
(anti-pumping)
S4
Position switch
(for closing spring charged)
S5 Electrical closing lock-out
S6 Circuit-breaker tripping signal
S12 Mechanical interlocking
S21 Position switches
S22 (to de-energise the motor operating mechanism after charging)
X0
X1
Y1
Y2
Y4
Plug connector,
24-pole or 64-pole
Terminal strip, 27-pole
1st shunt release
2nd shunt release
Current-transformer
operated release (rated
normal current 0.5 A or 1 A)
The circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring.
84
Y6
Y7
Y9
Current-transformer
operated release
(tripping pulse W 0.1 Ws)
Undervoltage release
Closing solenoid
Abbreviations:
NC = Normally closed
NO = Normally open
Technical Data
Circuit diagrams for 3AE5
-Q0 -X1.1
-Q0 -X1.5.1
-Q0 -X0
C3
-Q0 -X1.5.2
4
-Q0 -X1.1
-Q0 -X1.1
-Q0 -X0
Undervoltage
release
-Q0 -X1.1
D3
1st c.t.-operated
release 5A
1st c.t.-operated
release
-X1.1
-Q0 -X1.1
7
-Q0 -S1 33
-Q0 -S1 43
34
44
1)
A1
-Q0 -Y7
A2
1)
1)
A1
24
-Q0 -Y2
A2
-Q0 -X1.1 3
S_A7E_449_41020_001 S_A7E_449_41020_010
Part of basic wiring
S_A7E_449_41099_010
-Q0 -Y4
A2
-Q0 -X1.5.1 3
-Q0 -X1.5.2 4
A1
A1
-Q0 -Y1
-Q0 -X1.1 6
S_A7E_449_41020_002
-Q0 -X1.1 6
S_A7E_449_41021_001
A1
-Q0 -Y6
A2
S_A7E_449_41024_001
A2
-Q0 -X1.1 6
S_A7E_449_41023_001
-Q0 -X1.1 6
HG11-2855 eps
-Q0 -S3 23
S_A7E_449_41026_001
3
Position switch for withdrawable part
-Q0 -X02
3
Q1
Withdrawable
part
-Q0 -X01 2
14
14
14
14
14
-Q0 -X02 2
14
14
14
HG11-2858 eps
-Q0 -X01
14
S_A7E_449_41085_001
-Q0 -X01
-Q0 -X0
A14
A15
A16
B14
B15
B16
C1
C4
-Q0 -X02
C15
C16
D1
D13
D14
D15
C13
C14
HG11-2859 eps
-Q0 -X0
S_A7E_449_41085_002
85
Technical Data
Circuit diagrams for 3AE5
-Q0 -X0
13
21
23
31
33
41
43
51
53
61
63
12
14
22
24
32
34
42
44
52
54
62
64
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
C8
C8
A12
C12
A13
1)
-Q0 -S1
(-Y1)
(-Y2)
(-Y7)
11 13 21 23 31 33 41 43 51 53 61 63 71 73
81
12 14 22 24 32 34 42 44 52 54 62 64 72 74
82
1)
2)
2)
1)
3)
4)
2)
2)
2)
2)
2)
S_A7E_449_41066_401
-Q0 -X0
D7
B8
B12
D12
B13
HG11-2857 eps
11
HG11-2860 eps
(-Y9)
-Q8 -S1
A8
Closed
Open
Closed
Open
Closed
Open
Closed
Open
Closed
Open
Closed
Open
C7
S_A7E_449_41063_001
-Q0 -X1.2
-Q0 -X1.2
-Q0 -X1.2
4
48 V - 60 V
220 V - 240 V
-Q0 -X1.2
Motor charging
24 V - 32 V
100 V - 127 V
Closing and
anti-pumping device
Closing and
anti-pumping device
48 V - 60 V
220 V - 240 V
Closing and
anti-pumping device
Closing and
anti-pumping device
24 V - 32 V
100 V - 127 V
-Q0 -X1.2
-Q0 -X1.5.2
7
Closing and
anti-pumping device
Closing and
anti-pumping device
Closing and
anti-pumping device
Additional equipment
-Q0 -X1.2
4
-Q0 -X1.5.1
8
1)
A1
-Q0 -Y9
A1
A2
1)
-Q0 -M1
-Q0 -S3 21
22
-Q0 -S3 11
-Q0 -S12 14
12
13
M
1=
D2
-Q0 -S3 13
-Q0 -X1.2 5
-Q0 -X1.5.2 7
-Q0 -X1.5.2 7
-Q0 -X1.5.2 9
-Q0 -X1.5.2 9
86
S_A7E_449_41012_010
Part of basic wiring
S_A7E_449_41099_010
-Q0 -X1.5.1 2
HG11-2851 eps
-Q0 -X1.2 6
HG11-2852 eps
14
S_A7E_449_41001_010
Part of basic wiring
S_A7E_449_41099_010
Technical Data
Circuit diagrams for 3AE5
-Q0 -X1.1
-Q0 -X1.5.2
1
Circuit breaker
tipping signal
-Q0 -S4 13
21
22
14
22
-Q0 -X1.5.2 1
-Q0 -X1.1 2
-Q0 -X1.5.2 5
-Q0 -X1.2 1
-Q0 -X0
2
3
4
5
6
7
8
9
10
-Q0 -X1.4 1
2
3 (100 - 127 V)
4 (220 - 240 V)
5
6
7
8
9
10
-R01 1
21
-Q0 -X1.5.2 6
S_A7E_449_41043_001
-Q0 -X1.2 9
-Q0 -X1.5.1 6
S_A7E_449_41050_001
Order code A30
S_A7E_449_41043_010
Part of basic wiring
S_A7E_449_41099_010
S_A7E_449_41042_001
-Q0 -X1.1 1
2
3
4
5
6
7
8
9
10
22
-Q0 -X1.2
-Q0 -X1.5.1
2
-Q0 -S6
S_A7E_449_41001_001
-Q0 -X1.2
21
HG11-2850 eps
-Q0 -S21
-Q0 -X1.2
-Q0 -X1.2
1
0
HG11-2856 eps
-Q0 -X1.1
Signal:
Spring charged
Motor charging
A1
D16
D2
C2
C6
B6
D6
A7
B7
2
3 (100 - 127 V)
4 (220 - 240 V)B2
A2
5
6
7
8
(-R01)
9
(-R01 )
10
(-M1)
(-M1)
(-Y1)
(-Y1)
(-S4)
(-S4)
(-S4)
(-S6)
(-S6)
(-Y9)
(-Y9)
HG11-2853 eps
-Q0 -K1
-Q0 -X1.1 1
1
2
3
4
5
6
7
8
9
10
2
3
4
5
6
7
8
9
10
-Q0 -X1.2 1
-Q0 -X0
-X1.3
A1
D16
D2
C2
C6
B6
D6
-Q0 -X1.4 1
2
3 (24 - 32 V)
4 (48 - 60 V)
5
6
7
8
9
10
2
3 (24 - 32 V)
4 (48 - 60 V)
5
6
7
8
9
10
A7
B7
B2
A2
(-M1)
(-M1)
(-Y1)
(-Y1)
(-S4)
(-S4)
(-S4)
(-S6)
(-S6)
(-Y9)
(-Y9)
(-R01)
(-R01 )
HG11-2854 eps
S_A7E_449_41012_051
S_A7E_449_41012_053
Contactor (anti-pumping)
Motor operating mechanism
Circuit-breaker wiring
Wiring of withdrawable part
Resistance
Auxiliary switch
Position switch
(anti-pumping)
S4
Position switch
(for closing spring charged)
S5 Electrical closing lock-out
S6 Circuit-breaker tripping signal
S12 Mechanical interlocking
S21 Position switches
S22 (to de-energise the motor operating mechanism after charging)
X0
X1
Y1
Y2
Y4
Plug connector,
24-pole or 64-pole
Terminal strip, 27-pole
1st shunt release
2nd shunt release
Current-transformer
operated release (rated
normal current 0.5 A or 1 A)
Y6
Y7
Y9
Current-transformer
operated release
(tripping pulse W 0.1 Ws)
Undervoltage release
Closing solenoid
Abbreviations:
NC = Normally closed
NO = Normally open
The circuit diagrams shown here are examples from the manifold possibilities of circuit-breaker wiring.
87
R-HG11-181.tif
88
Annex
Contents
Contents
Page
Annex
89
Inquiry form
Conguration instructions
91
Foldout page
R-HG11-180.eps
Conguration aid
90
89
Annex
Inquiry form
Please copy, ll in and return to your
Siemens partner.
Inquiry concerning
Technical data
Other values
SION vacuum
circuit-breaker
from 7.2 to 24 kV
Please
Submit an offer
Call us
Visit us
Rated voltage
Rated lightning impulse
withstand voltage
7.2 kV
24 kV
12 kV
60 kV
125 kV
75 kV
Rated short-duration
20 kV
power-frequency withstand voltage 42 kV
17.5 kV
_ _ _ kV
95 kV
_ _ _ kV
28 kV
50 kV
38 kV
55 kV
_ _ _ kV
_ _ _ kA
Rated short-circuit
breaking current
12.5 kA
25 kA
16 kA
31.5 kA
20 kA
40 kA
800 A
2500 A
1250 A
3150 A
2000 A
Pole-center distance
150 mm
160 mm
210 mm
205 mm
275 mm
310 mm
___ A
275 mm
Your address
Secondary equipment
Company
Drive motor
_ _ _ V DC
_ _ _ V AC, _ _ _ H z
Closing solenoid
_ _ _ V DC
_ _ _ V AC, _ _ _ H z
1st
shunt release
_ _ _ V DC
_ _ _ V AC, _ _ _ H z
shunt release
_ _ _ V DC
_ _ _ V AC, _ _ _ H z
Dept.
Fixed
mounting
Name
Street
Postal code / city
nd
Country
Current-transformer operated release
Phone
Undervoltage release
_ _ _ V DC
_ _ _ V AC, _ _ _ H z
Auxiliary switch
6 NO + 6 NC
12 NO + 12 NC
Low-voltage connection
20- or 27-pole
terminal strip
24-pole
plug
64-pole
plug
French
Spanish
Fax
E-mail
Mechanical interlocking
Circuit-breaker tripping signal
Siemens AG
German
English
Dept.
Name
Street
Postal code / city
Country
Fax
90
_ _ _ Please ll in
Possible options:
Ur: 7.2 kV to 24 kV
Up: 60 kV to 125 kV
ISC: 16 kA to 40 kA
Pole-center distance
150 mm to 275 mm
205 mm to 310 mm
Possible options:
Release combination
(position 9)
Closing solenoid
(position 10)
Installation accessories
(position 13)
Drive motor
(position 14)
6 NO + 6 NC, 12 NO + 12 NC
With or without
DC or AC 50 Hz; 60 Hz
3rd step: Do you have any further requirements concerning the equipment? (Please refer to page 39)
Do you have any further requirements, please contact your responsible sales partner.
91
10 11 12
13 14 15 16
3 A
3 A
3 A
3 A
3 A
3 A
3 A
See page 38
See page 37
See page 36
See page 34
See page 34
See page 33
page 32
See page 33
to
3 A
See page 18
See page 39
3 A
Siemens AG
Infrastructure & Cities Sector
Low and Medium Voltage Division
Nonnendammallee 104
13629 Berlin, Germany
www.siemens.com