Вы находитесь на странице: 1из 20

PRESSURE REGULATORS

Type Cronos

TM

Process Management

Cronos Regulators
Pressure Regulators
This series of Top-Entry appliances was designed to meet a wide range of applications, offering easy maintenance
combined with compact size.
To achieve this, we introduced a new modularity concept which, combined with our experience and TARTARINI technologies developed in axial flow regulators, has enabled us to build a wide range of versions to the same design philosophy.
These are, in brief, the features of the project:
MODULARITY
Modularity is ensured by a central cross-shaped body, which is the systems key component, enabling either
horizontal or 90 gas flow.
The other components are assembled to it (flange, regulator head, monitor head, shut-off, and silencers).
COUNTERBALANCED SHUTTER
Use of a special counter-balanced shutter of very simple design, makes CRONOS highly reliable, easy to maintain, in the more complex configurations too (Shut-off, Monitor, Regulator, Silencer).
Versatile design can clearly be seen in the CCBS
right-angled model, which Tartarini uses to make
highly compact reduction units.

CCBS

Cronos Regulators
Configurations

C Regulator

CB Regulator + Shut-off

CC Regulator + Monitor

CCB Regulator + Monitor + Shut-off


ID-ABREVIATIONS
Horizontal flow

Configurations

90 flow

Silenced

Standard

SR

Standard

SRS

SR

SRS

Regulator

C-SR

C-SRS

Regulator + Shut-off

CB

CB-SR

CB-SRS

CBS

CBS-SR

CBS-SRS

Regulator + Monitor

CC

CC-SR

CC-SRS

CCS

CCS-SR

CCS-SRS

Regulator + Monitor + Shut-off

CCB

CCB-SR

CCB-SRS

CCBS

CCBS-SR

CCBS-SRS

N.B.:

Silenced

SRS silenced solutions have a widened output flange.


Also available: version with widened output, but without a built-in silencer.

Examples of Descriptions:

DN 25 ANSI 150 horizontal flow regulator with SRS silencer:


DN 25 ANSI 150 horizontal flow regulator with widened output:

C/025x100 ANSI 150 SRS


C/025x100 ANSI 150

Cronos Regulators
Operation
Regulated pressure
chamber (Pd)

MONITOR
Monitor spring

Diaphragm unit

Moving
chamber (Pm)

Monitor shutter

Monitor seal pad

SHUT-OFF
Regulator and
monitor seat

Shut-off spring
Shut-off shutter

Regulator seal pad


Shut-off reset shaft
Regulator shutter
Shut-off seal pad
Moving
chamber (Pm)

Shut-off seat

Diaphragm
unit

Regulated pressure
chamber (Pd)
Regulator spring

REGULATOR

Cronos Regulators
Operation
HOW THE REGULATOR WORKS
The Diaphragm Unit (permanently connected to the shutter) divides the regulator control head into two chambers.
One of the chambers is connected to regulated pressure (Pd), and the other to moving pressure (Pm) produced by the pilot
according to pressure downstream.
Due to lack of pressure, the regulator spring acts on the diaphragm unit and closes the shutter.
The shutter moves to its open position when the force produced by moving pressure acting on the diaphragm unit becomes greater
than the force produced by downstream regulated pressure (Pd) added to the load of the regulator spring. The shutter stays idle
when the two forces are equal under these conditions, downstream pressure is equal to the systems set value.
Any change in requested flow-rate produces a variation in downstream regulated pressure and the regulator controlled by the pilot
opens or closes to deliver the requested flow-rate while keeping downstream pressure uniform.
Monitor Pilot
Monitor

A
Pilot

To body rear side


connection

Regulator
Pilot

Inlet pressure
Regulator moving pressure
Monitor moving pressure
Stabilized pressure
Outlet pressure

A Downstream or to a safe area

Regulator

HOW THE MONITOR WORKS


The Monitor or emergency regulator is used as a safety device in gas pressure reduction systems. The purpose of this device is to
protect the system against possible overpressure, while keeping the reduction line in service.
The monitor controls downstream pressure at the same point as the main regulator and is set a little higher than the latter.
Under normal duty, the monitor is fully open as it detects a pressure value lower than its set value. If, due to any regulator fault,
downstream pressure increases, when it exceeds the tolerated level, the monitor comes into operation and adjusts pressure to its
own set value.

HOW THE SHUT-OFF DEVICE WORKS


The shut-off device has a shutter and its own seat, and is provided with functions independent of the regulator/monitor. The shutter
can be opened by hand only, by rotating the shut-off reset shaft anti-clockwise. To keep the shutter open, actuator-pilot series
OS/80X or series OS/80X-PN is used both are designed to operate on maximum and minimum pressure, on maximum only, on
minimum only.
When the systems downstream pressure is at normal operating value, the actuator-pilot remains set and prevents the shut-off reset
shaft from turning by keeping the shut-off shutter open.
When downstream pressure varies beyond its set limits, the actuator-pilot releases the reset shaft and the shutter is closed by the
thrust of the spring.

Cronos Regulators
Features
Applications
CRONOS series regulators are used in reduction, distribution and conveying stations of suitably filtered natural gas.
They can also be used for air, propane, butane, LPG, city gas, nitrogen, carbon dioxide and hydrogen.

Technical Features
Flange rating PN 16 - ANSI 150
Allowable pressure
Inlet pressure range
Set range
Min.operating differential pres.

PS
: up to 20 bar
bpu : 0.2 to 20 bar
Wd
: 0.01 to 16 bar
pmin : 0.2 bar

Flange rating PN 25/40 - ANSI 300/600


Allowable pressure
Inlet pressure range
Set range
Min.operating differential pres.

PS
: up to 100 bar
bpu : 1 to 100 bar
Wd : 0.5 to 80 bar
pmin : 0.5 bar

Functional Features
Accuracy class
Lock-up pressure class
Class of lock-up pressure zone

AC
SG
SZ

: up to 1%
: up to + 5%
: up to 5%

AG
ta

: up to 1%
: 1 s

Shut-off device
Accuracy class
Response time
Flanged connections
Same Inlet and outlet
: DN 25 - 50 - 80
Different Inlet and outlet : DN 25 x 100 - 50 x 150 - 80 x 250
Temperature
Standard version
Working: -10 C +60 C
Low temperature version
Working: -20 C +60 C

Materials
Body
Flanges and covers
Regulator shutter
Shut-off shutter
Seat
Diaphragms
Pads

:
:
:
:
:
:
:

Steel
Steel
Steel
Steel
Stainless steel
Fabric NBR+PVC/Nitrile rubber
NBR Nitrile rubber

Cronos Regulators
Calculation Procedures
Symbols

Q =
P1 =
P2 =
Cg =
C1 =
d =

Natural gas flow rate in Stm3/h


Absolute inlet pressure in bar
Absolute outlet pressure in bar
Flow rate coefficient
Body shape factor
Relative density of the gas

Flow Coefficients
DN
25

Horizontal Flow

Standard Model

Model with SR

Model with SRS

Model with Widended Outlet

CB

CC

CCB

CB

CC

CCB

CB

CC

CCB

CB

CC

CCB

Cg

550

510

510

500

540

500

500

490

500

460

460

450

580

550

550

540

C1

30

30.5

30.5

31

30

30.5

30.5

31

33

33.5

33.5

34

31

31

30

Cg 2250 2080 2080 2050 2200 2030 2030 2000 1900 1780 1780 1750

50

C1

29

30

30

30.5

29

30

30

31

32

33

33

33.5

Cg 5100 4800 4800 4700 5000 4700 4700 4600 4200 4000 4000 3900

80

C1

29

30

30

31

29

30

30

31

32

33

33

34

2300
29

30

5200
29

31

2100 2100
30

30.5

4850 4850
30

30

2050
4800
31

90 flow
DN
25
50
80

Standard Model

Model with SR

Model with SRS

Model with Widended Outlet

CBS

CCS

CCBS

CBS

CCS

CCBS

CBS

CCS

CCBS

CBS

CCS

CCBS

Cg

450

450

440

440

440

430

400

400

390

475

475

470

C1

30

30

31

30

30

31

33

33

34

30

30

31

Cg

1850

1850

1800

1800

1800

1750

1650

1650

1600

1900

1900

1850

C1

30

30

31

30

30

31

32

32

33

30

30

31

Cg

4300

4300

4200

4200

4200

4100

3500

3500

3400

4400

4400

4300

C1

30

30

31

30

30

31

33

33

34

30

30

31

Flow Rate Q

Sub-critical state with P2>

P1
2

Q = 0.525 Cg P1 sin 3417


C1

Deg

P1-P2
P1

P1
Critical state with P2
2
Q = 0.525 Cg P1

Gas

For other gases with different densities, the flow


rate calculated with the above formulas must be
multiplied by the correction factor:
F=

0.6
d

Air

Relative Density
d

Factor
F

0.78

City gas

0.44

1.17

Butane

2.01

0.55

Propane

1.53

0.63

Nitrogen

0.97

0.79

Carbon dioxide

1.52

0.63

Hydrogen

0.07

2.93

Cronos Regulators
DN Size
Calculate the required Cg with the following formula:
P1
2

Sub-critical state with P2>


Q

Cg =

3417

0.525 P1 sin

C1

P1 - P2 Deg
P1

P2 P1
2

Critical state with


Cg =

Q
0.525 P1

N.B. The above formulas apply to natural gas flow rate only. If the flow rate value (Q) refers to other gasses,
divide it by the correction factor F (see table).
Select the diameter of the regulator with Cg higher than calculated value (see table).
After finding the DN of the regulator, check that gas speed on the seat does not exceed 120 m/sec,
using the following formula:
V = 345.92

V
345.92
Q
DN
Pu

=
=
=
=
=

Q
DN2

1 - 0.002 Pu
1 + Pu

Velocity (m/s)
Numerical constant
Flow rate under standard conditions (Stm3/h)
Regulator nominal diameter (mm)
Inlet pressure in relative value (bar)

Detail of reducing unit with CB-SRS. Right to left gas flow

Cronos Regulators
Pilots
The following pilots are used with CRONOS series regulator with built-in shut-off device:
OS/80X series:

Spring loaded pneumatic device

OS/80X-PN series: Pneumatic device controlled by PRX series pilots

OS/80X

The OS/80X series pilot is supplied in different models according to set ranges required.

Technical Features
Model

Servomotor Body
Resistance (bar)

OS/80X-BP

OS/80X-BPA-D

20

OS/80X-MPA-D
OS/80X-APA-D
OS/84X

OS/80X-PN

Underpressure Set Range


Wdu (bar)

Min.

Max.

Min.

Max.

0.03

0.01

0.60

0.50

0.25

10

0.30

41

16

18

80

70

100

OS/88X

Materials

Overpressure Set Range


Wdo (bar)

OS/80X
Servomotor body:

Diaphragm:
O-ring:

OS/80X-BP, OS/80X-BPA-D
OS/80X-MPA-D, OS/80X-APA-D
Fabric NBR+PVC/Nitrile rubber
NBR Rubber

OS/84X, OS/88X
Servomotor body:
Lip seal:
O-ring:

Brass
Teflon (PTFE)
NBR Rubber

Aluminim
Steel

The OS/80X-PN series pilot is supplied in two models:


OS/80X-PN: Pressure range 0.5 to 40 bar
Appliance made of an OS/80X-APA-D set at about 0.4 bar and a
variable number of PRX/182 pilots for overpressure and PRX/181
for underpressure, as many as necessary to control different points
of the installation.

OS/80X-BP

OS/84X-PN: Pressure range 30 to 80 bar


Appliance made of an OS/84X set at about 20 bar and a variable number of PRX-AP/182 pilots for
overpressure and PRX-AP/181 for underpressure, as many as necessary to control different points of
the installation.

Technical Features
Model

Materials

Servomotor Body
Resistance (bar)

Overpressure Set Range


Wdo (bar)

Underpressure Set Range


Wdu (bar)

Min.

Max.

Min.

Max.

OS/80X-PN

100

0.5

40

0.5

40

OS/84X-PN

100

30

80

30

80

PRX/181/182, PRX-AP/181/182
Body
Steel
Diaphragm
Fabric-finished NBR
O-ring
NBR Rubber

Cronos Regulators
Pilots
PS/ Series

Cronos series regulators are equipped with the PS/ or PRX/ series pilots.
Application

Allowable
Pressure
PS (bar)

Regulator or Monitor
PS/79-1

0.01 - 0.5

25

PS/79-2

Body and
Covers
Material

Set Range
Wd (bar)

Aluminium

0.5 - 3

1/4 NPT female threaded connections

Application
Regulator or
Monitor

Allowable
Pressure
PS (bar)

Operating Monitor
Regulator

Monitor

PS/79

PSO/79

REO/79

PS/80

PSO/80

REO/80

100

Set Range
Wd (bar)
0.5 - 40
1.5 - 40

Body and
Covers
Material
Steel

1/4 NPT female threaded connections

All PS/ series pilots are supplied with a filter (5 filtering degree) and built-in pressure
stabilizer, with the exception of pilots PSO/79 and PSO/80.

PRX/ Series

Application
Regulator or
Monitor

Allowable
Pressure
PS (bar)

Operating Monitor
Regulator

Monitor

PRX/120

PRX/120

PRX/125

PRX-AP/120

PRX-AP/120

PRX-AP/125

Set Range
Wd (bar)

100

1 - 40
30 - 80

Body and
Covers
Material
Steel

1/4 NPT female threaded connections

The SA/2 pressure pre-reducer must be used with PRX/ series pilots.

SA/2

The pressure pre-reducer is equipped with a 5 filtering degree filter and is suitable
for heating.
Model
SA/2

Allowable Pressure
PS (bar)

Supplied Pressure

Body and Covers


Material

100

3 bar + Downstream pressure

Steel

1/4 NPT female threaded connections

FU

When the pressure difference between upstream and downstream is below 10 bar,
SA/2 can be used with the following FU filter.
Model
FU

Allowable Pressure
PS (bar)

Filtering Degree

Body and Covers


Material

100

Steel

1/4 NPT female threaded connections

Booster Valves

Model
V/31-1
PRX/131
PRX-AP/131

Allowable Pressure
PS (bar)

Set Range Wd (bar)

Body and Covers


Material

19

0.025 - 0.55

Aluminium

100

1/4 NPT female threaded connections

10

0.5 - 40
30 - 80

Steel

Cronos Regulators
Operating Monitor and Booster Valve
OPERATING MONITOR
The operating monitor has two functions: under normal duty, it reduces pressure in the intermediate section between
the two regulators, but, if the main regulator fails, it comes into operation as an emergency regulator.

REO/79
PS/79

PSO/79

Operating
Monitor

Regulator

To the connection on the body rear side

BOOSTER VALVE
The booster valve is fitted on the monitor-regulator system which branches off from the monitor drive pressure circuit,
so that the monitor operates more quickly.
PS/79
Monitor
PRX/131
A
A

To the connection on
the body rear side

PS/79

A
Regulator

Inlet pressure
Intermediate pressure

Regulator moving pressure


Monitor moving pressure

Stabilized pressure
Outlet pressure

11

A Downstream or to a safe area

Cronos Regulators
Silencers
SR

Beyond this speed could be necessary to act on


the noise generated by the expansion cone usually installed downstream of the regulator.

30

Noise reduction db (A)

This silencer is fitted near the regulator shutter


and is highly efficient up to a theoretical speed of
80 m/s calculated at the outlet flange.

Built-in multi-path or split-flow silencer

35

25
20

V 80 m/s

15

V=120 m/s

10

V 200 m/s

70

75

80

85

90

95

100

105

110

120

115

Noise of non silenced regulator db(a)

SRS

Mixed split-flow, multi-stage silencer

40

Multi-stage
section

Multi-path
section

35

Noise reduction db (A)

The SRS silencer consists of an SR silencer plus a


widened outlet flange in which a second silencer
is fitted.

30

The second silencer has an initial multi-path section and a second multi-stage section.
This silencer is highly efficient under all operating conditions, is not limited by the theoretical
speed on the regulator outlet flange.

25
20

15
10
5
70

75

80

85

90

95

100

105

110

115

Noise of non silenced regulator db(a)

STP

Dissipative silencer
40

Habitually used down-stream of SRS silencers but


can also be combined with the SR silencer.

The STP silencer consists of one or more porous


channels clad with soundproofing material.
Sound penetrates inside the soundproofing layer
and is transformed into heat by friction.
The silencer is fitted in the pipe and is secured
with two flanges.

35

Noise reduction db (A)

Overall reduction in noise level is the sum of the


reduction produced by SR or SRS plus the STP
induced reduction.

Soundproofing
material
Porous
channel

30

25

STP 20
20
15

STP 10
10

70

75

80

85

90

95

100

Noise of silenced regulator db(a)

Two types of silencers are supplied:


STP10 10 dB(A) attenuation, with length of approximately 1m
STP10 20 dB(A) attenuation, with length of approximately 2m

12

105

110

120

Cronos Regulators
Accessories
PROPORTIONAL TRAVEL TRANSMITTER
In order to communicate the valve position, a potentiometer-type straightaway
position transmitter is used connected to the regulator travel indicator. Thanks to
this transducer, it is possible to know accurately the valve position and thus have
correct information on the regulator operating condition.
It is supplied in two models:
PA1/25 suitable for Cronos DN 25-50
PA1/50 suitable for Cronos DN 80
This transducer features a single element as foreseen by EN 50020 standards and can
thus be used in hazardous areas.
Single element transducers, if fitted in intrinsic safety circuits, should be protected
through suitable safety barriers anyway.
Model

PA1/25

PA1/50

Useful electrical travel

mm

26

51

Resistance

Resolution

mm

infinite

Suggested current

<1

Max. current

mA

Max. voltage

Working temperature

10
25

60

-30 C +100 C

PROXIMITY SWITCH
In order to send the shut-off or the regulator/monitor opening/closing signal, a proximity switch suitable for installation in hazardous area is used.
The use of this switch foresees the application of an intrinsic safety separation barrier
which should be installed in safe area.
The distance between the proximity switch and the barrier should be calculated
according to the type of gas and installation electrical specifications.
The proximity switch should be positioned at about 0.5 mm from the stem (S). The adjustment is made by means of
adjusting nuts.
On request it is possible to supply the pilot in the version with two proximity switches in order to indicate extreme
positions of valve opening/closing.

OS/80X

0.5 mm
Proximity
0.5 mm

Adjusting nuts
Proximity

Pilot installation

Regulator/Monitor installation

13

Cronos Regulators
Accessories
ELECTROVALVE FOR REMOTE
CONTROLLED CLOSURE

C
Electrovalve

The OS/80X and the OS/80X-PN equipped with


a shut-off device for minimum pressure, can be
equipped with a 3-way valve with explosionproof construction to permit remote-controlled
closure.

IT/3V THREE-WAY VALVE FOR SETTING


CONTROL (Pu max 50 bar)

Regulator + Shut-off

It allows the OS/80X operation and setting control, without having to change the regulator
setting.

Q
B

The valve is installed on the OS/80X control line


and it must be connected to a suitable pressure
source that is capable of reaching the settings of
the OS/80X.
The IT/3V three-way valve is of the spring-return
type and it is equipped with a safety lock plate (B)
on the control knob (Q).

To pressure
source
To pilot

Downstream
When the plate (B) is pivoted, pressure on the
knob (Q) makes it possible to put the sensitive
member into communication with a pressure
source, thus making it possible to perform operation and setting tests.

Upon completion of the procedures, releasing the knob will reset normal running conditions.
The safety lock plate on the knob prevents accidental maneuvers.

MIC/25 Underground Module

14

Cronos Regulators
Installation
The central cross-shaped body is designed so that the actuator-pilot can be installed both at front and rear.
This facility combined with body rotation enables all types of orientation.
For orientations different from those shown below, please contact our Technical Department.

Left to right flow

Right to left flow

OFF

OFF

ON

ON

RIARMO

OS/80X

RIARMO

OS/80X
ERGENZA
EM

ERGENZA
EM
RESET

Vertical Flow

ME

R ES ET

RG EN

Upward flow

ME

Horizontal Flow

RG EN

Downward flow
OFF

OFF

ON

L.C.B.

ON

OS/80X

OS/80X
ERGENZA
EM

ERGENZA
EM
R ES ET
ME

RG E N

ME

RG E NC

.B.C.L

R ES ET

RIARMO

RIARMO

Left downward flow

Right downward flow

OFF

OFF

ON

ON

RIARMO

OS/80X

RIARMO

OS/80X
ERGENZA
EM

ERGENZA
EM
R ES ET

M E L.C.B.C
RG E N

Right upward flow

ME

RG EN

RESET

ERGENZA
EM

ME

C
L.C.B.
R
G EN

ERGENZA
EM

OS/80X

RIARMO

ON

OS/80X
ON

OFF

OFF

Regulator

15

RIARMO

Monitor

ME

RG E N

Left upward flow

R ES ET

R ES ET

90 Flow

Cronos Regulators
Examples of Connections
PS/79-1
PS/79-2
Series

PS/79-1-2

TA RT ARINI

DN

OS/80X

PS/79-1-2

PS/79 Series

4 x DN

PS/79
R
TA RT ARINI

DN

OS/80X

PS/79
4 x DN

PS/80 Series
PS/80
R
TA RT ARINI

DN

OS/80X

PS/80

4 x DN

PRX Series
PRX/120
PRX/120-AP
R

TA RT ARIN I

SA/2

DN

OS/80X

4 x DN

PRX/120
PRX/120-AP

Inlet pressure

Moving pressure

Outlet pressure

16

A Downstream or to a safe area

R To the heating system

Cronos Regulators
Horizontal Flow Dimensions (mm)
Standard and SR

Widened outlet and SRS

I1

C
B

L.C.B.

L.C.B.

C
I

CB

165

I1
OFF

OFF

ON

270

ON

OS/80X

OS/80X

CB

C
I

I1

CC

CC

L.C.B.

L.C.B.

C
I

CCB

I1

CCB

165

OFF

ON

OF F

ON

NZ
A

270

OS/80X

OS/80X

Overall Dimensions (mm)


PN 16
ANSI 150

DN

Face-to-Face (mm)

PN 25/40
ANSI 300/600

PN 16
ANSI 150

PN 25/40
ANSI 300

ANSI 600

I1

I1

I1

25

215

180

285

260

170

220

180

225

260

170

184

350

197

353.5

210

360

50

245

195

335

285

175

260

195

287

285

175

254

465

267

471.5

286

482

80

330

260

400

325

185

350

260

400

325

185

298

570

317

590

337

600

Threaded 1/4 NPT female impulse connections

17

Cronos Regulators
90 Flow Dimensions (mm)
Standard and SR
I

CBS

Widened outlet and SRS


165

165

CBS

OF F
OFF
ON

I2

I1

OS/80X

270

270

ON

OS/80X

C
C

CCS
A

CCS

L.C.B.

I2

I1

L.C.B.

C
C

165

CCBS

165

OFF

ON

270

ON

OS/80X

I2

I1

OS/80X

OF F

270

CCBS

C
C

Overall Dimensions (mm)


PN 16
ANSI 150

DN
A

Face-to-Face (mm)

PN 25/40
ANSI 300/600
D

PN 16
ANSI 150
E

I1

I2

I1

I2

98.5

215 180 285 260 170 220 180 225 260 170

295

385

105

295

385

50

245 195 335 285 175 260 195 287 285 175 127 347 473 133.5 370

484

143

370

484

80

330 260 400 325 185 350 260 400 325 185 149 450 622 158.5 485 648.5 168.5 485

18

280 386

ANSI 600

25

Threaded 1/4 NPT female impulse connections

92

I1

PN 25/40
ANSI 300

648.5

Cronos Regulators
Weights
Horizontal Flow
Standard and SR (kg)
DN

Widened Outlet and SRS (kg)

PN 25/40
ANSI 300/600

PN 16 ANSI 150

PN 16 ANSI 150

PN 25/40 ANSI 300/600

CB

CC

CCB

CB

CC

CCB

CB

CC

CCB

CB

CC

CCB

25

36

38

56

58

37

39

61

63

49

51

69

71

56

58

78

80

50

62

66

96

100

74

78

118

122

87

91

121

125

109

113

153

157

80

128

142

191

197

171

185

271

277

190

204

253

259

273

279

373

379

90 Flow
Standard and SR (kg)
DN

PN 16 ANSI 150

Widened Outlet and SRS (kg)

PN 25/40
ANSI 300/600

PN 16 ANSI 150

PN 25/40 ANSI 300/600

CBS

CCS

CCBS

CBS

CCS

CCBS

CBS

CCS

CCBS

CBS

CCS

CCBS

25

40

56

58

43

63

65

53

69

71

60

80

82

50

72

102

106

92

132

136

97

127

131

127

167

171

80

159

208

214

225

319

325

221

270

286

327

421

427

CCB

19

Industrial Regulators

Natural Gas Technologies

LP-Gas Equipment

TESCOM

Emerson Process Management


Regulator Technologies, Inc.

Emerson Process Management


Regulator Technologies, Inc.

Emerson Process Management


Regulator Technologies, Inc.

Emerson Process Management


Tescom Corporation

USA - Headquarters
McKinney, Texas 75070 USA
Tel: +1 800 558 5853
Outside US: +1 972 548 3574

USA - Headquarters
McKinney, Texas 75070 USA
Tel: +1 800 558 5853
Outside US: +1 972 548 3574

USA - Headquarters
McKinney, Texas 75070 USA
Tel: +1 800 558 5853
Outside US: +1 972 548 3574

USA - Headquarters
Elk River, Minnesota 55330-2445 USA
Tel: +1 763 241 3238

+1 800 447 1250

Europe
Bologna 40013, Italy
Tel: +39 051 419 0611

Europe
Bologna 40013, Italy
Tel: +39 051 419 0611
Chartres 28008, France
Tel: +33 2 37 33 47 00

Asia-Pacific
Shanghai 201206, China
Tel: +86 21 2892 9000
Middle East and Africa
Dubai, United Arab Emirates
Tel: +011 971 4811 8100

Asia-Pacific
Singapore 128461, Singapore
Tel: +65 6770 8337

Europe
Selmsdorf 23923, Germany
Tel: +49 38823 31 287
Asia-Pacific
Shanghai 201206, China
Tel: +86 21 2892 9499

Middle East and Africa


Dubai, United Arab Emirates
Tel: +011 971 4811 8100

For further information visit www.emersonprocess.com/regulators


Our Global Product Brands:

TM

The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher, Tartarini, Francel, Emerson Process Management and the Emerson
Process Management design are marks of the Emerson Process Management group of companies.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express
or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Process Management does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson Process
Management product remains solely with the purchaser.
O.M.T. Officina Meccanica Tartarini S.R.L., Via P. Fabbri 1, I-40013 Castel Maggiore (Bologna), Italy
R.E.A 184221 BO Cod. Fisc. 00623720372 Part. IVA 00519501209 N IVA CEE IT 00519501209, Cap. Soc. 1.548 000 Euro i.v. R.I. 00623720372 - M BO 020330
Francel SAS, 3 Avenue Victor Hugo, CS 80125, Chartres 28008, France
SIRET 552 068 637 00057 APE 2651B, N TVA : FR84552068637, RCS Chartres B 552 068 637, SAS capital 534 400 Euro
0001EN_CRONOS_BUL - 02/2008 - Rev. 03 - Emerson Process Management Regulator Technologies, Inc., 2014; All Rights Reserved

Вам также может понравиться