HLP-C100 Series Operating

Manual

HLP-C100 Series

Index
Introduction
Chapter 1 Safety Precautions
1.1 Before power-up
1.2 During the power-up
1.3 During the operation
1.4 After the power-off
Chapter 2 Standards and Specifications
2.1 Label Description
2.2 Particular specifications
2.3 Technical specifications
Chapter 3 Installation and Wiring
3.1 Checks before Installation
3.2 Installation dimensions
3.2.1 Dimensions of the Inverter
3.2.2 Dimensions of the inverter
3.3 Installation and Wiring
3.3.1 Electrical Installation in General
3.3.2 Fuse Specifications
3.3.3 Installation and Direction
3.3.4 Wiring terminal
3.3.5 Wiring
Chapter 4 Operation and Display Interface
4.1 LCP Digital Operator
4.2 Quick to set parameters
4.2.1 Preset reference by LCP
4.2.2 FWD/REV Status
4.2.3 Data Read-outs
4.2.4 View alarm record
4.2.5 View state parameter
4.2.6 LED Display
Chapter 5 Quick Application Guide
5.1 Parameter initialization
5.2 Using LCP to control the drive [HAND]
5.3 Using digital in terminals to control the drive [AUTO]
5.4 Forward, Reverse and Jog
5.5 Multi-speed
Chapter 6 Parameter Overview
HLP-C100 Series Operating Manual

I
1
-1-2-3-3-4-4-5-5-8-8-8-8-9-9- 10 - 10 - 11 - 13 - 14 - 14 - 14 - 14 - 15 - 16 - 17 - 18 - 20 - 21 - 21 - 21 - 21 - 21 - 21 - 22 - 23 -

HLP-C100 Series
Chapter 7 Parameter Description
7.1 Parameter group 00: operation/display
7.2 Parameter group 01: load and motor
7.3 Parameter group 02: brakes
7.4 Parameter group 03: reference/ramps
7.5 Parameter group 04: limits/warnings
7.6 Parameter group 05: digital input/output
7.7 Parameter group 06: analog in/out
7.8 Parameter group 07: controller
7.9 Parameter group 08: comm. and options
7.10 Parameter group 14: special functions
7.11 Parameter group 15: drive information
7.12 Parameter group 16: data readouts
Chapter 8 Accessory Specification
8.1 Braking resistor
8.2 LCP Mounting Kit
8.2.1 External LCP Communication Cable
8.2.2 Mounting steps
Chapter 9 EMC
9.1 EMCCorrect Installation
9.2 RFI Switch
Chapter 10 Warnings/Alarms and Fault Handling
10.1 Fault list
10.2 Fault indication and trouble shooting
Chapter 11 Maintenance
11.1 Note
11.2 Storage and transport
Chapter 12 Communication protocol
12.1 Format specification
12.2 Coil addressing
12.3 Read coil status
12.4 Read holding registers
12.4 Force single coil
12.5 Preset single register
12.6 Force multiple coils
12.7 Preset multiple regs
12.8 Read/write array
12.9 Exception code

HLP-C100 Series Operating Manual

- 33 - 33 - 35 - 39 - 41 - 51 - 54 - 55 - 59 - 60 - 62 - 65 - 67 - 72 - 72 - 72 - 72 - 73 - 73 - 73 - 74 - 74 - 76 - 78 - 78 - 78 - 79 - 79 - 79 - 81 - 82 - 82 - 83 - 84 - 85- 85 - 87 -

HLP-C100 Series

Chapter 1 Safety Precautions


Caution
Danger

Indicates misuse may damage the inverter or


mechanical system .
Misuse may result in casualty.

1.1 Before power-up


Caution
Check to be sure that the voltage of the main circuit AC power
supply matches the input voltage of the inverter.
Install the inverter in a safe location, avoiding high temperature,
direct sunlight, humid air or water.
The inverter can only be used at the places accredited by our
company. Any unauthorized working environment may have the
risks of fi re, gas explosion, electric shock and other incidents.
If more than one drive installed on the same control cabinet, make
additional cooling fan, so that the inside temperature is lower than
40 in order to prevent overheating or fi re occurs.
It will affect the service life of the inverter if a contactor is
installed on the input side to control the start and stop. Generally
it is required to control it through terminal commands. Special
attention should be paid to its use in the case of the start and stop
more frequently places.
Do not install any switch component like circuit breaker or
contactor at the output of the inverter. If any of such components
must be installed due process and other needs, it must be ensured
that the inverter has no output when the switch acts. In addition,
it is forbidden to install any capacitor for improvement of power
factor or any varistor against thunder at the output. Otherwise
it will cause malfunctions, tripping protection and damages of
components of the inverter.
Please use an independent power supply for the inverter. Do avoid
using the common power supply with an electrical welder and
other equipment with strong disturbance. Otherwise it will cause
the drive to protect or even damage the drive.
Do not make any high voltage test with any component inside the
inverter. These semi-conductor parts are subject to the damage of

HLP-C100 Series Operating Manual

-1-

HLP-C100 Series

high voltage.
The IC board of the inverter are susceptible to the effect and
damage of static electricity. Dont touch the main circuit board.
Installation, commissioning and maintenance must be performed
by qualified professional personnel.
It should be handled with the base to avoid the dropping of the
inverter, which may possibly cause the injuries to people and the
damages to the inverter.

Danger
Be sure to turn off the power supply before wiring.
Mount the drive in the metal and other non-combustible materials
to avoid the risk of fi re.
Dont install the drive in a space with explosive gas, otherwise,
they lead to explosion.
R, S, T terminals are power input terminals, never mixed with
U.V.W terminals. Be sure that the wiring of the main circuit is
correct. Otherwise it will cause damages of the inverter when the
power is applied to it.
The ter minal of
must be grounded separately and never
connected to N-line. Otherwise it will easily cause the protection
or errors of the inverter.
Do not dissemble or modify any internal connecting cord, wiring
or component of the inverter by yourself.
Never remodel it or exchange control boards and components by
yourself. It may expose you to an electrical shock or explosion,
etc.
Keep the inver ter from the reach of children or persons not
concerned.

1.2 During the power-up


Danger
Do not plug the connectors of the inverter during the power up
to avoid any surge into the main control board due to plugging,
which might cause the damage of the inverter.

-2-

HLP-C100 Series Operating Manual

HLP-C100 Series

1.3 During the operation


Caution
Do not measure the signals on circuit boards while the inverter is
running to avoid danger.
The drive has been optimized before sold. Please make proper
adjustments according to the desired functions.
Do consider the vibration, noise and the speed limit of the motor
bearings and the mechanical devices.

Danger
Never connect or disconnect the motor set while the inverter is in
running. Otherwise it will cause over-current trip and even burn
up the main circuit of the inverter.
Never remove the front cover of the inverter while the inverter is
powered up to avoid any injury of electric shock.
Do not come close to the machine when the Reset Function is
used to avoid anything unexpected. The motor may automatically
recover from fault.

1.4 After the power-off


Caution
Even in the case of the main power, the other voltage inputs and
the share load (linkage of DC intermediate circuit) all have been
disconnected from the mains; the internal of the drive may still
have residual energy. Before touching any potentially live parts
of the inverter, please wait at least 4 minutes. Otherwise, it may
expose you to a risk of electrical shock.
The user must strictly follow the instruction to operate and make
wire connection. Otherwise HOLIP will not responsible for the
damages due to wrong operation. The user will responsible for the
damages themselves.

HLP-C100 Series Operating Manual

-3-

HLP-C100 Series

Chapter 2 Standards and Specifications


2.1 Label Description

Significance of the type code:

1-8
9-12
13-14

15-17
18
19
20
21
22
23
24
25
26-27
28-31

-4-

HLP-C100
0D37
21
23
43
P20
X
A
X
B
X
B
1
C
X
0
1
A
B
XX
VXXX

Indicate Product Series


Indicate 0.37KW
Indicate 1-Phase AC 220V
Indicate 3-Phase AC 220V
Indicate 3-Phase AC 380V
IP rating is 20
Without AC choke
With AC choke
Without Brake unit
With Brake unit
Without DC choke
With DC choke
Control panel with LED display and potentiometer
With coating on PCB
Reserved
Domestic sale
Overseas sale
Without RS485
With RS485
Reserved
Indicate sof tware version number, such as
V235 means the version number is 2.35 .

HLP-C100 Series Operating Manual

HLP-C100 Series

2.2 Particular Specifications


Model

Input voltage

HLP-C1000D3721
HLP-C1000D7521
HLP-C10001D521
HLP-C1000D3723
HLP-C1000D7523
HLP-C10001D523

1200-240V50/60HZ
1200-240V50/60HZ
1200-240V50/60HZ
3200-240V50/60HZ
3200-240V50/60HZ
3200-240V50/60HZ
3380-440V50/60HZ
HLP-C1000D7543
3440-480V50/60HZ
3380-440V50/60HZ
HLP-C10001D543
3440-480V50/60HZ
3380-440V50/60HZ
HLP-C10002D243
3440-480V50/60HZ

Input Output Rated Suitable Net


current/ current/ power/ motor/ weight/
KG
KW
KW
A
A
6.1
2.2
0.37
0.37
0.84
11.6
4.2
0.75
0.75
0.84
18.7
6.8
1.5
1.5
0.84
3.5
2.2
0.37
0.37
0.84
6.7
4.2
0.75
0.75
0.84
10.9
6.8
1.5
1.5
0.84
3.5
2.2
0.75
0.75
0.84
3.0
2.1
5.9
3.7
1.5
1.5
0.84
5.1
3.4
8.5
5.3
2.2
2.2
0.84
7.3
4.8

2.3 Technical Specifications


Item
Supply voltage
Power supply

Frequency
Max. imbalance
Output voltage
Motor output Output
f requency
Control mode
Start torque
Overload capacity
PWM switch
f requency
Main control Speed setting
f unctions
resolution
Control
command source
Frequency setting
source
Ramp control

Specification
single/three phase 220V 20%;
three phase 380V 20%;
48-62Hz;
3%;
three phase 0-100% of supply voltage;
0-400Hz
V/F
0.5Hz 150%;
150% rated output current (60s)
2K-16KHz
Digital: 0.001Hz; analogy: 0.5 of the
max. operating f requency ;
LCP , digital terminal, local bus;
LCP , analog, local bus;
Selectable 8-speed steps;

HLP-C100 Series Operating Manual

-5-

HLP-C100 Series
Item
Specification
Automatic Voltage Regulation; V/F Control, DC Brake;
Basic Functions Speed Limit; Current Limit; Reset Function; Timer; PI
Controller.
Speed Open-loop Control; Process Closed-loop Control;
Jogging ; Multi-speed Control via Digital input; Deferent
Application
speed with deferent ramp; Mechanical Braking; Catch up /
Functions
Slow down; Relative Scaling Reference; Recover user settings
by a key etc.
Missing Motor Phase Protection; Low-voltage Protection;
Over-voltage Protection; Over-current Protection; Output
Phase Loss Protection; Output Short Circuit Protection;
Protection Out put Grounding Fault Protection; Motor Ther mal
Functions Protection; CPU Fault; EEPROM Faults; Button f reeze;
Duplicate Fails; LCP Invalid; LCP Incompatible; Parameter
Read-only; Reference Out of Range; Invalid While Running;
Password Error etc.
Number
5 digital inputs.
Digital input
Scanning time
1ms;
1 analog inputs(VI),
both can receive
Number of input
voltage or current
signals.
Analog input
Max.error: 0.5% of
Input accuracy
f ull scale
Resolution
11bit;
Scanning time
1ms;
Control
Terminals
1 relay outputs (FARelay output
FB-FC) ;
Digital output
Scanning time
1ms;
Power supply

RS485 serial
communication

-6-

10VDC power
supply;
1, RS+(TX+,RX+),
Terminal number
RS-(TX-, RX-);
Ground for
COM;
RS485
+10V

HLP-C100 Series Operating Manual

HLP-C100 Series
Item
Specification
8 segments, 5
Display f requency, warnings, status and
numeric displays so on;
Light FWDREVHZAR/MIN
Indicator
display various status of the inverter;
Frequency setting, output f requency,
Display
feedback value, output current, DC link
voltage, output voltage, output power,
Data read-outs
input terminals state, output terminals
state, analogue input, 1-10 fault records
and accumulated working time etc.;
Remote
Available when the control panel for
mounting kit
external use;
Accessory
Copy parameters f rom one inverter to
Copy card
another ;
Enclosure
IP20;
Ambient
-10-40;
temperature
Humidity
5%-85% (95% without condensation) ;
Environment Vibration test
1.14g;
Max. altitude
1000m, derating use when more than
above sea level
1000 meters;
Motor cable
Shield cable: 5 meters, unshield cable: 50
length
meters;
Attention: Inverter under special environment (derating) :
Derating for ambient temperature: If the f requency converter is
operated over 40 ambient temperature, the continuous output current
should be decreased. The f requency converter has been designed
for operation at max 50 ambient temperation with one motor size
smaller than normal. Continuous operation at f ull load at 50 ambient
temperation will reduce the lifetime of the f requency converter.
Derating for low air pressure: The cooling capability of air is decreased
at low air pressure. Below 1000m altitude no de-rating is necessary but
above 1000m the ambient temperature or the maximum output current
should be decreased. Dcrease the output by 1% per 100m altitude above
1000m or reduce the max. ambient temperature by 1 degree per 200m.

HLP-C100 Series Operating Manual

-7-

HLP-C100 Series

Chapter 3 Installation and wiring


3.1 Checks before Installation
The inver ter has been st rictly and well packed bef ore sold. In
consideration of various factors during the transportation special attention
should be paid to the following points before installation. If there is anything
abnormal please notif y the dealer or the relevant people of our company.
Check if the inverter has got any damage or deformation during the
transportation and handling;
Check if there is one piece of HLP-C100 series inverter and one copy of
the quick guide available when unpacking it;
Check the information on the label to see if the specifications meet your
order (Operating voltage and KW value);
Check if there is a certificate of qualification and a warranty card.

3.2 Installation Dimensions


3.2.1 Dimensions of LCP
Dimensions of the LCP are shown below(unit:mm):
21.7
12.8

13.3

-8-

57.1

89.2

92.6

59.5

HLP-C100 Series Operating Manual

HLP-C100 Series

3.2.2 Dimensions of the inverter

Power(kW)

1200-240V 3200-240V 3380-480V mm mm mm mm mm mm


0.37-1.5

0.37-1.5

0.75-2.2

74

85

130

140

127

3.3 Installation and Wiring


3.3.1 Electrical Installation in General

Caution
All cabling must comply with national and local regulations on
cable cross-sections and ambient temperature. Copper conductors
required, and ambient temperature(60-75) recommended.
Details of terminal tightening torques :
Power(KW)and Voltage
Torque(Nm)
levels
DC connection/ Control
120032003380Relay
Line Motor
Brake
terminals
240V
240V
480V
0.37-1.5
0.37-1.5 0.75-2.2 1.4
0.8
0.8
0.15-0.4
0.4

HLP-C100 Series Operating Manual

-9-

HLP-C100 Series

3.3.2 Fuse Specifications


Model

Fuse size (Rated current/A)

HLP-C1000D3721

10

HLP-C1000D7521

25

HLP-C10001D521

32

HLP-C1000D3723

10

HLP-C1000D7523

16

HLP-C10001D523

25

HLP-C1000D7543

10

HLP-C10001D543

10

HLP-C10002D243

16

3.3.3 Installation and Direction

Note: Install the unit and make sure that it is f ree f rom high moisturehigh
temperatureheavy dustmetal f ragments and high oil mist.

- 10 -

HLP-C100 Series Operating Manual

HLP-C100 Series

3.3.4 Wiring terminal


3.3.4.1 Main Circuit Terminals

Description of main circuit terminals:


Symbol

RST

Function
Power input:
220V class: 1- phase 200-240V50/60Hz
3- phase 200-240V50/60Hz
380V class: 3- phase 380-480V50/60Hz
Single phase connected to RT

UVW

Power output, connect to the motor

-BR+BR

Connect the brake resistor, make sure to set C02.10


C02.11 etc.

PE

Ground terminal

HLP-C100 Series Operating Manual

- 11 -

HLP-C100 Series

3.3.4.2 I/O Control Terminals

Description of I/O control terminals:


Symbol

Relay output
(FA-FB-FC)

Description

Digital input
Digital control
(FORREV
terminals
DI1DI2DI3)
GND

+10V

Specification

1Resistive load: 250VAC 3A/30VDC 3A;


2Inductive load: 250VAC 0.2A/24VDC 0.1A
Relay output (cos=0.4) ;
3FA FB normally closed, FB FC normally
open;
1Logic:
>DC19V
logic 0;
<DC14V
logic 1;
2Voltage: DC 0-24V;

Digital or
Isolated f rom internal COM;
Analog ground
10V power
supply

Max.load 25 mA, with over load and short


circuit protection f unctions;

Set by the related parameter, analog input


channel can be configurated to 0-20mA or
0-10V :
Voltage input:
1Input impedance: about 10 K;
Analog input Analog setting/ 2Maximum withstand voltage is 20V,
duration of 2 seconds, the maximum reverse
(VI)
Feedback
voltage is -15V, duration of 2seconds.
Current input:
1Input impedence500;
2Maximum withstand current is 29 mA
duration of 2 seconds.
RS+, RSCOM

RS485
RS485 + and RS485- ;
communication
Ground for
Isolated f rom internal GND;
communication

Note: Only the machine with RS485 (type code number 25 is B) has RS+ RSand COM;

- 12 -

HLP-C100 Series Operating Manual

HLP-C100 Series

3.3.5 Wiring
Basic Connection Diagram of HLP-C100 series inverter:

Precautions for the main circuit wiring:


While wiring the sizes and specifications of wires should be selected and
the wiring should be executed according to the electrical engineering
regulations to ensure the safety.
It is better to use shielded wire or wire conduit for power cord and
ground the shielded layer or two ends of wire conduit.
Be sure to install a circuit Breaker between the power supply and the
input terminals (R.S.T). (If using RCD, please choose B type)
Phase-shif ting capacitors, LC, RC noise f ilters etc, can never be
connected to the output terminals of the inverter.
Please lower the inverter switching f requency when there is a longer
distance between the inverter and the motor.
Drive earth leakage current is greater more than 3.5 mA. According
to the requirments of IEC 61800-5-1 , must use the following ways to
enhance the protection of ground: minimum 10mm2 cross sectional area
of copper, or additional PE line, its cross sectional area and the main
power cable should be the same, must be separate grounded.
Make sure reliable ground of the inverter in accordance with IEC 618005-1.
Please refer to 9.2 for the use of RFI SWITCH.
HLP-C100 Series Operating Manual

- 13 -

HLP-C100 Series

Chapter 4 Operation and Display Interface


4.1 LCP Digital Operator

Screen display
Status indicator
Menu key

Shift key

Hand key

Auto key

Incremental
potentiometer

Off Reset key

4.2 Quick to set parameters


4.2.1 Preset reference by LCP
Example: Set a reference to10.25 That is C03.10 [0] =20.5:
Key-press

LCP Display
C00.04

C03.00

C03.00

C03.10

[0]

- 14 -

Action Description
Press

key to display the first basic

C00.03
Turn

clockwise to select parameter

group C03

Press

key to shif t to f ractional part

Turn

clockwise to select parameter

C03.10

Press

to show the first option of C03.10

HLP-C100 Series Operating Manual

HLP-C100 Series
Key-press

LCP Display
0000

000.5

000.5

020.5

END

Action Description
Press

to show the value of the first

option of parameter C03.10


Turn

clockwise to change the

f ractional part to 5

Press

key to shif t to integral part

Turn

clockwise to change the integral

part to 20
Press

to accept the change and save it

as 20.5

4.2.2 FWD/REV Status


Confirm the direction of the motor according to the set value, as shown in
the following table:
Reference

Running status

STOP

STOP

FWD

REV

Indicator Display

HLP-C100 Series Operating Manual

- 15 -

HLP-C100 Series
Reference

Running status

FWD

REV

Indicator Display

Note: A flash light denotes the status coming, Light on indicates the current
state, and light off means not in this state.
Example 1: The f irst line of the table indicates the drive is stop and the
reference is greater than or equal to 0, means the dirve at some
time in the f uture will run forward.
Example 2: The fourth line of the table represents the current drive is reverse
running, and the reference setting is greater than or equal to 0, it
means the drive at some time in the f uture will run forward.

4.2.3 Data Read-outs


Display
Items

Key-press

Output
Frequency

Initial
interface

LCP Display

Action Description
Show the output
f requency (C16.13)
is 50.0Hz, display
accuracy: 0.1

Reference
(%)

Show the preset


reference (C16.01) is 50%,
display accuracy: 0.001

Motor
Current

Show the motor current


(C16.14) is 9.00A, display
accuracy: 0.01

Motor
Voltage

Show the motor voltage


(C16.12) is 380.0V, display
accuracy: 0.1

- 16 -

HLP-C100 Series Operating Manual

HLP-C100 Series
Display
Items

Key-press

LCP Display

Action Description

Motor Speed

Show the motor speed


(C16.05) is 1440rpm,
display accuracy:1

DC Voltage

Show the DC
voltage(C16.30) is 540.0V,
display accuracy: 0.1

Inverter
temperature

Show the inverter


temperature (parC16.34)
is 45, display
accuracy:1

Feedback
Value

Show the feedback


value(C16.52) is 28.000,
display accuracy: 0.001

Analog in
VI

Show analog in VI
(C16.62) is 10.00V, display
accuracy: 0.01

Note: Press

key to change the display items on control panel, however,

C00.33 must be activated (see C00.33).

4.2.4 View alarm record


If the drive trips, fault code will be showed to illustrate the reason, all the
trip record will be saved.
Key-press

LCP Display

C00.04

Action Description
Press

key to display the first

basic C00.03.

HLP-C100 Series Operating Manual

- 17 -

HLP-C100 Series
Key-press

LCP Display

C15.00

C15.00

C15.30

[0]

**

Action Description

group No. C15.

Press

to select parameter

number.

Turn

clockwise to select C15.30

Press

to show the first option

of C15.30

Press

to show the first fault

record.

Press
[1]

clockwise to select par.

Turn

to show the second fault

record, it can display up to ten


recent fault records in turn.

4.2.5 View state parameter


View the status of input terminal, reference, feedback value, output
f requency, output current, output voltage, and the power etc.
Key-press

LCP Display

C00.03

- 18 -

Action Description
Press

to display the first basic

parameter C00.03.

HLP-C100 Series Operating Manual

HLP-C100 Series
Key-press

LCP Display

C16.00

Action Description
Turn

clockwise to select Par.

group No. C16

C16.00

Press

to select parameter No.

C16.01

Press

select C16.01

Turn

clockwise to finish

browse value of C16.01.

C16.60

Press

to select C16.60.

Press

to view the value in

0000

C16.60, 0100 indicates status of


FORDI1DI2 is 0, and status of
REV is 1.

HLP-C100 Series Operating Manual

- 19 -

HLP-C100 Series

4.2.6 LED Display

- 20 -

HLP-C100 Series Operating Manual

HLP-C100 Series

Chapter 5 Quick Application Guide


5.1 Parameter initialization
1. Set C14.22 = 2
2. Cut off the main power and Re-power on, LCP displays E.80
3. Press OFF key on LCP.

5.2 Using LCP to control the drive [HAND]


1. Parameter initialization;
2. Press HAND key on LCP;
3. Turn the incremental potentiometer to adjust the f requency;
4. PressOFFkey on LCP to stop the f requency converter;

5.3 Using digital in terminals to control the drive [AUTO]


1. Parameter initialization;
2. Press AUTO key on LCP (Digital control and communication control
are only active in auto mode);
3. Frequency source: Preset C03.10 or select f requency source by C03.15
C03.16;
4. Connect digital input terminal FOR and GND to operate the f requency
convert;
5. Disconnect the digital input terminal FOR and GND to stop the
f requency converter.

5.4 Forward, Reverse and Jog


1. IO terminals connection as following:

2. Parameter initialization;
3. Set parameter as following:
C03.11=10Hz
C03.15=1, C03.16=0
HLP-C100 Series Operating Manual

- 21 -

HLP-C100 Series
C03.41=0.5, C03.42=0.5, C03.80=0.5, C04.10=2
C05.11=11, C05.13=14
C06.10=0, C06.11=10, C06.14=0, C06.15=50
4. Press AUTO key on LCP;

5.5 Multi-speed
1. IO terminals connection as following:

2. Parameter initialization;
3. Set parameter as following:
C03.03=50
C05.10=8 , C05.12=15 (Bit0) , C05.13=16 (Bit1) , C05.13=17 (Bit2)
C03.10[0]=10 (Speed1=5Hz) , C03.10[1]=20 (Speed2=10Hz) ,
C03.10[2]=30 (Speed3=15Hz) , C03.10[3]=40 (Speed4=20Hz) ,
C03.10[4]=50 (Speed5=25Hz) , C03.10[5]=60 (Speed6=30Hz) ,
C03.10[6]=70 (Speed7=35Hz) , C03.10[7]=80 (Speed8=40Hz) ,
4. Press AUTO key on LCP;

- 22 -

HLP-C100 Series Operating Manual

HLP-C100 Series

Chapter 6 Parameter Overview


Item

Parameter
No.

Function
Description

Setting range

Parameter Group 00: Operation/Display


Parameter Group01: Load/motor

0: Resume; 1: Forced
Operating State stop reference=old;
C00.04
at Power-up
2: Forced stop
reference=0;
LCP Display
0-2047
C00.33
Option
HAND key on
0:Disabled; 1:Enabled;
C00.40
LCP
0:Disable All; 1:Enable
OFF key on
All; 2:Enable Reset
C00.41
LCP
Only;
AUTO key on
0:Disabled; 1:Enabled;
C00.42
LCP
Menu
0:Disabled; 1:Enabled;
C00.60
Password
0: Speed open loop;
Configuration
1: Speed closed loop;
C01.00
Mode
3: Process closed loop;
Motor Power
Dep.on motor date
*C01.20
[kW] [HP]
Motor Voltage
50~1000
*C01.22
(Um.n)
Motor
*C01.23 Frequency (f m. 20~400
n)
Motor Current
Dep.on motor date
*C01.24
(Im.n)
Motor Nominal
100~9999
*C01.25
Speed (nm.n)
Motor Cable
0~150
*C01.42
Length
U/F
C01.55
0~999
Characteristic-U
U/F
C01.56
0~400
Characteristic-F
C01.71 Start Delay
0.0~10.0

Unit

Default Page
setting No.
1

0
1
1
1
0
0
kW

Hz

rpm

50

V
Hz
s

HLP-C100 Series Operating Manual

0.0

- 23 -

HLP-C100 Series

Item

Parameter
No.
C01.72
*C01.73
C01.80
C01.82
C02.00

Parameter Group 02: Brake Function

C02.01
C02.02
C02.04
C02.10
C02.11
C02.17

Parameter Group 03: Reference/Ramps

- 24 -

C03.03

C03.07

C03.10
C03.11
C03.12

Function
Description

Setting range

Unit

0: DC hold/delay
Start Function time; 2: Coast/Delay
time;
Flying start
0:Disabled; 1:Enabled;
Function at
0: Coast; 1: DC Hold;
Stop
Min Speed for
Function at
0.0~20.0
Hz
Stop [Hz]
DC Hold
0~150
%
Current
DC Brake
0~150
%
Current
DC Braking
0.0~60.0
s
Time
DC Brake Cut
0.0~400.0
Hz
In Frequency
0: Off; 1: Resistor
Brake Function
brake; 2: AC brake;
Brake Resistor
Dep.on motor date

(ohm)
Over-voltage
0: Disabled;
Control
2: Enabled;
Maximum
0.000~4999.000
Reference
0: Preset reference +
Actual
Reference source 1,2
reference
1: Preset reference
calculation
priority
Preset
-100.00~100.00
%
Reference
Jog Speed [Hz] 0.0~400.0
Hz
Catch up/slow
Down Value

0.00~100.00

HLP-C100 Series Operating Manual

Default Page
setting No.
2
0
0
0.0
50
50
10.0
0.0
0
*
0
50.000

0.00
5.0
0.00

HLP-C100 Series

Item

Parameter
No.
C03.15
C03.16
C03.18
C03.40
C03.41
C03.42
C03.50
C03.51

Parameter Group 03: Reference/Ramps

C03.52
C03.60
C03.61
C03.62
C03.70
C03.71
C03.72
C03.80
C03.84
C03.85
C03.86

Function
Setting range
Description
Reference
Resource 1
0: No f unction;
Reference
1: Analog input VI;
Resource 2
11: Local bus ref;
Relative Scaling 21: LCP
potentiometer;
Reference
Resource
0: Linear; 2: Sine
Ramp 1 Type
ramp;
Ramp 1 Ramp
0.10~300.00
up Time
Ramp 1 Ramp
0.10~300.00
Down Time
0: Linear; 2: Sine
Ramp 2 Type
ramp;
Ramp 2 Ramp
0.10~300.00
up Time
Ramp 2 Ramp
0.10~300.00
down Time
0: Linear; 2: Sine
Ramp 3 Type
ramp;
Ramp 3 Ramp
0.05~3600.00
up Time
Ramp 3 Ramp
0.05~3600.00
down Time
0: Linear; 2: Sine
Ramp 4 Type
ramp;
Ramp 4 Ramp
0.10~300.00
up Time
Ramp 4 Ramp
0.10~300.00
down Time
Jog Ramp Time 0.10~300.00
0: Linear; 2: Sine
Ramp 5 Type
ramp;
Ramp 5 Ramp
0.10~300.00
up Time
Ramp 5 Ramp
0.10~300.00
down Time

Unit

Default Page
setting No.
1
2
0
0

*
0

*
0

*
0

*
0

HLP-C100 Series Operating Manual

- 25 -

HLP-C100 Series

Item

Parameter
No.
C03.87
C03.88
C03.89
C03.90

Parameter Group 03: Reference/Ramps

C03.91
C03.92
C03.93
C03.94
C03.95
C03.96

*C04.10
Parameter Group 04: Limits/Warnings

*C04.12
*C04.14
C04.18
*C04.19
C04.52
C04.53
*C04.58

- 26 -

Function
Description
Ramp 6 Type

Setting range

Unit

0: Linear; 2: Sine
ramp;

Ramp 6 Ramp
0.10~300.00
up Time
Ramp 6 Ramp
0.10~300.00
down Time
0: Linear; 2: Sine
Ramp 7 Type
ramp;
Ramp 7 Ramp
0.10~300.00
up Time
Ramp 7 Ramp
0.10~300.00
down Time
0: Linear; 2: Sine
Ramp 8 Type
ramp;
Ramp 8 Ramp
0.10~300.00
up Time
Ramp 8 Ramp
0.10~300.00
down Time
Link preset
reference and 0: No link; 1: Link
ramp time
0: Clockwise;
Motor Speed
1: Counterclockwise;
Direction
2: Both;
Motor Speed
0.0~400.0
Low Limit [Hz]
Motor Speed
0.0~400.0
High Limit [Hz]
Current Limit 0~300
Max. Output
0.0~400.0
Frenquency
Warning Speed
0.0~400.0
Low
Warning Speed
0.1~400.0
High
Missing Motor
0: Off; 1: On;
Phase Function

Default Page
setting No.
0

*
0

*
0

*
0

2
Hz

0.0

Hz

65.0

150

Hz

65.0

Hz

0.0

Hz

65.0

HLP-C100 Series Operating Manual

HLP-C100 Series

Item

Parameter
No.

Function
Description
Bypass Speed
C04.61
From [Hz]
Bypass Speed
C04.63
To [HZ]
Terminal FOR
C05.10
Digital Input
Terminal REV
C05.11
Digital Input
Terminal DI1
C05.12
Dgital Input
Terminal DI2
C05.13
Digital Input

Parameter Group 05: Digital In/Out

C05.14

Terminal DI3
Digital Input

C05.40

Relay
Function(FAFBFB-FC)

C06.10
C06.11
C06.12

Terminal VI
Low Voltage
Terminal VI
High Voltage
Terminal VI
Low Current

Setting range

Unit

Default Page
setting No.

0.0~400.0

Hz

0.0

0.0~400.0

Hz

0.0

0: No operation;
1: Reset; 2: Coast
inverse; 5: DC-brake
inverse; 6: Stop
inverse; 8: Start;
10: Reversing; 11: Start
reversing; 14: Jog;
15: Preset ref bit0;
16: Preset ref bit1;
17: Preset ref bit2;
28: Catch up; 29: Slow
down; 34: Ramp
bit0; 35: Ramp bit1;
36:Ramp bit2;
0: No operation;
5: Drive running;
9: Alarm; 10: Alarm
or Warning; 15: Out
of f requency rang;
16: Below f requency,
low; 17: Above
f requency, high;
21: Thermal warning;
24: Ready, voltage
ok; 25: Reverse;
26: Bus ok; 28: Brake,
no brake warning;
53: No alarm;
55: Running reverse;

8
10
15
16

17

0.00~9.99

0.07

0.10~10.00

10.00

0.00~19.99

mA

0.14

HLP-C100 Series Operating Manual

- 27 -

HLP-C100 Series

Item

Parameter Group 06: Analog In/Out


Parameter Group07: PID Control

- 28 -

Parameter
No.

Function
Description
Terminal VI
C06.13
High current
Terminal VI
C06.14 Low Ref./
Feedb.Value
Terminal VI
C06.15 High Ref./
Feedb.Value
Terminal VI
C06.16 Filter Time
Contant
Terminal VI
C06.18
Zero dead band
Terminal VI
C06.19
Mode
LCP Potmeter
C06.81
Low Ref.
LCP Potmeter
C06.82
High Ref.
Process CL
C07.20 Feedback
Resource
Process PI Anti
C07.31
Windup
Process PI
C07.33 Proportional
Gain
Process PI
C07.34
Integral time
Process PI Feed
C07.38
Forward Factor
On Reference
C07.39
Bandwidth
Process PI
C07.41
Output Low
Process PI
C07.42
Output High

Setting range
0.01~20.00

Unit
mA

Default Page
setting No.
20.00

-4999.000~4999.000

0.000

-4999.000~4999.000

50.000

0.01~10.00

0.01

0.00~20.00

V/
mA

0.00

0: Votage mode;
1: Current mode;

-4999.000~4999.000

0.000

-4999.000~4999.000

50.000

0: No Function;
1: Analog in VI;
11:Local bus;

0:Disabled; 1:Enabled;

0.0~10.00

0.01

0.10~9999.00

9999.00

0~400

0~200

-100-100

-100-100

100

HLP-C100 Series Operating Manual

HLP-C100 Series

Item

Parameter
No.
C08.01

Function
Description
Control Site

Setting range

Unit

0: Digital and ctrl.


word; 1: Digital only;
2: Control Word
only;

Control Word
0: None; 1: FC RS485;
Source
Control Word
0.1~6500.0
s
C08.03
Timeout Time
0: Off; 1: Freeze
Control Word output; 2: Stop;
C08.04 Timeout
3: Jogging; 4: Max.
Function
speed; 5: Stop and
trip;
Reset Control 0: No Function; 1: Do
C08.06
Word Timeout Reset;
FC(1~126); MODBUS
C08.31 Address
RTU(1~247);
0: 2400; 1: 4800;
C08.32 Port Baud Rate 2: 9600; 3: 19200;
4: 38400;
0: Even Parity,1Stop
bit; 1: Odd Parity,
C08.33 FC Port Parity 1stop bit; 2: No Parity,
1Stop bit; 3: No
Parity,2 Stop bits;
Minimum
0.001~0.500
s
C08.35
Response Delay
Max. Response
0.010~10.000
s
C08.36
Delay
C08.94 Bus Feedback 1 -32768~32767
2~6: 2kHz~6kHz;
Switching
7: 8kHz; 8: 10 kHz;
C14.01
Frequency
9: 12kHz; 10: 16kHz;
Over
0: Off; 1: On;
*C14.03
modulation
Damping Gain
0~200
%
C14.08
Factor
C08.02

Parameter Group 08: FC Port Settings

HLP-C100 Series Operating Manual

Default Page
setting No.
0

1
1.0

0
1
2

0.010
5.000
0
5
1
96

- 29 -

HLP-C100 Series

Item

Parameter
No.
C14.12

Parameter Group 14: Special Functions


Parameter Group 15: Drive Information

- 30 -

Function
Description
Function
at Mains
Imbalance

C14.20

Reset Mode

C14.21

Automatic
Restart Time

C14.22

Operation
Mode

C14.23

Trip Lock

Setting range

Unit

Default Page
setting No.

0: Trip; 1: Warning;
2: Disabled;

0: Manual reset;
1~10: Automatic reset
x 1~10; 11: Automatic
reset x 15;
12: Automatic reset
x 20; 13: Infinite auto
reset;

0~600

0: Normal Operation;
2: Initialisation;
3: Backup user
settings; 4: Recover
user settings;
0: Disable, Trip lock
fault reset do not
need power off
1: enable, Trip lock
fault reset need
power off

DC-Link
*C14.51 Voltage
0: Off; 1: On;
Compensation
C15.00 Operating Days 0~9999
C15.02 KWh Counter 0~65535
C15.03 Power ups
0~2147483647
Reset KWh
0: Do not reset;
C15.06
Counter
1: Reset Counter;
Fault Log: Error
0~255
C15.30
Code
Internal Fault
-32767~32767
C15.31
Reason
C15.40 FC Type
View FC type
View power size of
C15.41 Power Section
the drive

10

0
d

HLP-C100 Series Operating Manual

HLP-C100 Series

Item

Parameter
No.

Function
Description

Parameter Group 15: Drive Information

C15.42

Voltage

C15.43

Sof tware
Version

C15.44

Ordered Type
Code

C15.46

Frequency
converter
ordering NO.

C15.47

Power Card
Ordering NO.

C15.48
C15.49
C15.50
C15.51
C15.53
C15.92

LCP ID NO.
Sof tware ID
Control Card
Sof tware ID
Power Card
Frequency
Converter
Serial Number
Power Card
Serial number

Setting range

Unit

Default Page
setting No.

View Mains Voltage


of the drive
View the sof tware
version
View the ordered
type code of the
drive
View f requency
converter ordering
NO.
View power card
ordering No. of the
drive
View LCP ID NO.
View sof tware ID
control card
View sof tware ID
Power card
View f requency
converter No.

View power card


serial number
View parameter list
Parameter List
of the drive

HLP-C100 Series Operating Manual

- 31 -

HLP-C100 Series

Item

Parameter Group 16: Data Readouts

Parameter
Function
No.
Description
C16.00 Control Word
Reference
C16.01
[Unit]
Motor Speed
C16.05
[RPM]
C16.10 Power[KW]
C16.12 Motor Voltage
C16.13 Frequency
C16.14 Motor Current
DC Link
C16.30
Voltage
C16.34 Heat sink Temp.
Feedback #
C16.52
[Unit]
C16.60 Digital Input
Analog Input
C16.62
VI
Relay Output
C16.71
[bin]
C16.86 FC Port REF
C16.90 Alarm Word
C16.91 Alarm Word 2
C16.92 Warning Word
Warning Word
C16.93
2

Setting range

Unit

Default Page
setting No.

0~65535
-4999.000~4999.000
0~9999

Hz

0.000~1000.000
0.0~65535
0.0~400.0
0.00~655.35

kW
V
Hz
A

0~65535

0~255

-4999.000~4999.000
0~65535
0.000-20.000

V/
mA

0~65535
-32768~32767
0~0xFFFFFFFFUL
0~0xFFFFFFFFUL
0~0x7FFFFFFFUL
0~0x7FFFFFFFUL

Note: Reference signed with *in parameter No. column means this parameter
cant be modified when the motor is running. In factory setting column,
* means the default setting for this parameter is determined by the
drive type.

- 32 -

HLP-C100 Series Operating Manual

HLP-C100 Series

Chapter 7 Parameter Description


7.1 Parameter Group 00: Operation/Display
C00.0* Basic Settings
C00.04

Function Description

Range

Operaton State at
Power-up(Hand)

Unit

Default Setting

0~2

Option: [0] Resume, local reference is stored and used af ter power up;
[1] Forced stop, ref =old, local reference is stored and used af ter power
up;
[2] Forced stop, ref =0, local reference is set to 0;
Function: This parameter is used to control whether or not the f requency
converter should automatic running the motor when powering up
af ter a power down in Hand mode.
Description of choice: When select [0], f requency converter starts in
same Hand mode roof state as when powered of f; When select[1],
f requency converter powers up in of f state meaning that motor is
stopped af ter power up; When select[2], f requency converter powers
up in off state meaning that motor is stopped af ter power up. Local
reference is set to 0. Thus motor will not start running before local
reference has been increased.
C00.3* LCP Readout
C00.33

Function Description

Range

LCP Display Option

0~2047

Unit

Default Setting
0

Description of the choice: LCP will be fixed to display the output f requency
reference and motor current. This parameter is used to show 11 basic
operating states of the inverter, each parameter corresponds to a binary
code: 1 means display the item, 0 means does not display the item.
For example, if you want to display the states of the temperature and
the terminal VI on LCP. Transform the binary code to decimal digit,
C00.33=123+124=24.
Reserved

Reserved

Reserved

Reserved

Reserved

Reserved

VI Input

Temperature

DC-voltage

Motor Speed

Motor Voltage

HLP-C100 Series Operating Manual

- 33 -

HLP-C100 Series
C00.4* LCP Keypad
C00.40

Function Description

Range

HAND Key on LCP

0~1

Unit

Default Setting
1

Option: [0] Disabled: Hand key has no f unction;


[1] Enabled: Hand key is f unctional;
Description of the choice: The f requency converter can operate in the
following three mode: HANDOFF and AUTO. When running in
Hand mode, the f requency converter is locally operated and does not
allow any remote control. By activating hand a start signal is given.
C00.41

Function Description
OFF Key on LCP

Range

Unit

0~2

Default Setting
1

Option: [0] Disabled, OFF key has no f unction;


[1] Enabled, OFF key stop signal and reset of any fault;
[2] Enabled reset only, reset only (fault), stop (off ) f unction is disabled;
Description of the choice: When OFF key is chosen, the f requency converter
stops with a normal stop ramp; it can only be started by pressing either
hand or auto key on the LCP.
C00.42

Function Description
AUTO Key on LCP

Range

Unit

0~1

Default Setting
1

Option: [0] Disabled, Auto-on key has no f unction;


[1] Enabled, Auto-on key is f unctional;
Description of the choice: In auto-mode, the f requency can be remote
controlled (bus/digital).
C00.6* Protection
C00.60

Function Description
Menu Password

Range

Unit

Default Setting

0~1

Option: [0] Disabled;


[1] Enabled, none of parameter can be changed except this;
Function: This feature used to prevent non-commissioning person to change
the parameter settings.
Attention: Main Menu Password f unction is only valid to LCP, not active to
local bus.

- 34 -

HLP-C100 Series Operating Manual

HLP-C100 Series

7.2 Parameter Group 01: Load and Motor


C01.0* General Settings
*C01.00 Function Description
Configuration Mode

Range

Unit

0~3

Default Setting
0

Option: [0] Speed open loop, for general applications;


[3] Process closed loop, feedback signal is a process unit, such as:
pressuretemperature etc. When process closed loop is selected, the
motor can only run clockwise. For detailed parameter settings, please
refer to C07.3*.
Attention: If configuration mode is changed, C03.03 will be restored to factory
setting.
C01.2* Motor Date
Attention: Data of Parameter group C01.2* can not be changed when motor is
running.
*C01.20 Function Description
Motor Power

Range

Unit Default Setting

Dep. Motor date

KW

Function: Select the KW value that corresponds to the rated power of the
motor.
Description of choice: Factory settings depend on the inverter size, there is one
or two undersize or one oversize in comparison with factory setting.
Attention: Changing the value of this parameter af fects the setting of
C01.22-C01.25.
*C01.22 Function Description
Motor Voltage

Range

Unit

Default Setting

50~1000

Function: Select a value that equals the nameplate data on the motor.
Description of choice: Default setting depends on the inverter size.
*C01.23 Function Description
Motor Frequency

Range

Unit

Default Setting

20~400

Hz

Function: Enter the rated motor f requency f rom the nameplate data.
Description of the choice: Default setting depends on the inverter size.
Attention: Changing this parameter affects motor nominal speed set in C01.25.

HLP-C100 Series Operating Manual

- 35 -

HLP-C100 Series
*C01.24 Function Description
Motor Current

Range

Unit Default Setting

Dep. motor data

Function: Enter motor current value f rom nameplate data.


Description of the choice: Factory settings depend on the unit size.
*C01.25 Function Description
Motor Norminal Speed

Range

Unit

Default Setting

100~9999

RPM

Function: Enter the motor nominal speed value f rom the nameplate data.
Description of the choice: Factory setting depends on the unit size.
Attention: If motor f requency has been changed in C01.23, Nominal Motor
Speed will be affected.
C01.4* Motor Cable Length
*C01.42 Function Description
Motor Cable Length

Range

Unit

Default Setting

0~150

Function: Enter the motor cable length connected between the motor and the
f requency converter.
Description of the choice: Set correct cable length can suppress noises resulted
f rom the motor.
C01.5* Load Indep.Setting
C01.55

Function Description

Range

Unit

Default Setting

V/F Characteristic-V

0~999.9

0/Vn

Function: This parameter is an array parameter [0-5], used for setting voltage
[V0-V5] at each f requency point to manually form a V/F characteristic
matching motor. Frequency points are def ined in par. C01.56, V/F
characteristics - F.
Description of choice: This parameter is only f unctional when par. C01.01, Motor
Control Principle is set to V/F [0].
Attention: V0 factory setting is set to 0V, and U1-U5 factory setting is set to
Un (motor rated voltage).
C01.56

Function Description

Range

Unit

Default Setting

V/F Characteristic-F

0~400

Hz

0/Fn

Function: This parameter is an array parameter [0-5], used f or setting


f requency points [F0-F5] to manually form a V/F characteristic
matching motor. Voltage at each point is def ined in par. C01.55, V/F

- 36 -

HLP-C100 Series Operating Manual

HLP-C100 Series
Characteristic - V.
Description of choice: This parameter is only f unctional when par. C01.01 Motor
Control Principle is set to V/F [0].
Attention: F0 factory setting is set to 0Hz, and F1-F5 factory setting is set to Fn
(Motor rated f requency); for par. C01.56 the following applies F0=0 and
F1F2F3F4F5.

Fig. 6.1 V/F characteristic diagram


Simplif y V/F characteristic by merging 2 or more points (voltages and
f requencies), which respectively are set equal.
The slope (ratio of V/F) af ter point (F5, V5) must be equal to the slope
between point (F5, V5) and the previous point.
C01.7* Start Adjustments
C01.71

Function Description
Start Delay

Range

Unit

Default Setting

0.0~10.0

0.0

Function: This parameter enables a delay of the starting time. The f requency
converter begins with the start f unction selected in par. 1-72. Set the
start delay time until acceleration is to begin.
Attention: Setting start delay to 0.0 sec. disables Start Function, [C01.72], when
start command is given.
C01.72

Function Description
Start Function

Range

Unit

0~2

Default Setting
2

Option: [0] DC Hold;


[2] Coast;
Function: Select [0], Motor is energized with DC holding current (par. C02.00)
HLP-C100 Series Operating Manual

- 37 -

HLP-C100 Series
during start delay time; Select [2], Motor is coasted during start delay
time (inverter off ).
*C01.73 Function Description

Range

Flying Start

0~1

Unit

Default Setting
0

Option: [0] Disabled;


[1] Enabled;
Description of Choice: This f unction applies for the inertia load to restart due
to mains drop-out; If Clockwise[0] is selected(C04.10), and no rotating
motor is found, It is possible to use DC-brake command to ramp down
the motor speed to 0 rpm, and then start the motor in the normal way;
If Both directions [2](C04.10) is selected, and no rotating motor is found,
the drive will assume the motor is stationary or in low-speed rotation,
and then start the motor in the normal way. When Flying start is
enabled, C01.71 (Start delay) and C01.72 (Start f unction) is invalid.
Warning: This f unction is not suitable for hoisting applications.
C01.8* Stop Adjustments
C01.80

Function Description
Function at Stop

Range

Unit

0~1

Default Setting
0

Option: [0] Coast, the inverter is off;


[1] DC Hold, the motor is energized with a DC current. See par. C02.00
DC Hold Current for more information.
Function: Here it is possible to select the stop f unction according to different
applications.

- 38 -

HLP-C100 Series Operating Manual

HLP-C100 Series
Description of Choice: This f unction is active in the following situations: Stop
command is given and output speed is ramped down to Min. Speed for
activating Functions at Stop; Start command is removed (standby), and
output speed is ramped down to Min. Speed for activating Functions
at Stop; DC-brake command is given, and lasts out of DC-brake delay
time.
C01.82

Function Description
Min Speed for Function
at Stop [Hz]

Range

Unit

Default Setting

0.0~400.0

Hz

0.0

Function: Set the output f requency at which to activate par. C01.80 Function at
stop.

7.3 Parameter Group 02: Brakes


C02.0* DC -Brake
C02.00

Function Description

Range

Unit

Default Setting

DC Hold Current

0~150

50

Function: This parameter either holds the motor (holding torque) or preheats
the motor. This parameter is active if DC Hold has been selected in
either C01.72 start f unction or C01.80 Function at Stop.
Description of Choice: Enter a value for holding current as a percentage of the
rated motor current set in par. C01.24 Motor Current. 100% DC holding
current corresponds to IM,N.
Attention: Avoid 100% current too long as it may overheat the motor.
C02.01

Function Description

Range

Unit

Default Setting

DC Brake Current

0~150

50

Function: This parameter is used for setting the DC brake currents that is set as
a percentage value of the rated motor current IM, N set in C01.24.
Description of Choice: Parameters related to the DC brake current are as
follows:
DC-brake command, see C05.1* choice (5) ;
DC brake cut in speed, see C02.04;
C02.02

Function Description
DC Braking Time

Range

Unit

Default Setting

0.0~60.0

10.0

Function: This parameter defines DC brake current (C02.01) time during which
HLP-C100 Series Operating Manual

- 39 -

HLP-C100 Series
DC-brake current is applied to the motor.
C02.04

Function Description
DC Brake Cut in Speed

Range

Unit

Default Setting

0.0~400.0

Hz

0.0

Function: This parameter is for setting the DC brake cut in speed at which the
DC braking current (par.02.01) is to be actived, in connection with a
stop command. When set to 0 the f unction is off.
C02.1* Brake Energy Funct.
C02.10

Function Description
Brake Function

Range

Unit

0~2

Default Setting
0

Option: [0] off;


[1] Resistor brake, use the resistor brake to consume surplus energy
resulting f rom motor braking, and prevent the f requency converter to
trip due to over-voltage in the intermediate circuit;
Attention: Resistor brake is only f unctional when the f requency converter
build-in braking unit or external braking unit must be installed.
C02.11

Function Description

Range

Unit

Default Setting

Brake Resistor (ohm)

5~65535

Function Description

Range

Unit

Default Setting

Over-voltage Control

0~2

Function: Set brake resistor value.


C02.17

Option: [0] Disabled, The OVC is not active/required;


[2] Enabled, OVC is running;
Function: OVC is used to consume surplus energy by increasing the output
f requency. Select whether to enable OVC, which reduces the risk of
drive trip due to over voltage on the DC link caused by generative
power f rom load.
Attention: The OVC is not active/required if resistor brake has been chosen in
C02.10 (Brake Function).

- 40 -

HLP-C100 Series Operating Manual

HLP-C100 Series

7.4 Parameter Group 03: Reference/Ramps


C03.0* Reference Limits
C03.03

Function Description

Range

Unit Default Setting

Maximum Reference 0.000~4999.000

50.000

Function: Enter value for Maximum Reference.


Description of Choice: The sum of all internal and external references is
clamped (limited) to the maximum reference value.
C03.07

Function Description

Range

Actual reference calculation

Unit Default Setting

0~1

Option: [0] Preset reference + Reference source 1,2


[1] Preset reference priority
Description of Choice:
[0], Actual reference = Preset reference + Reference source 1,2
[1], When using preset reference 1-N, actual reference = preset reference [1-N],
else actual reference = preset reference [0] + reference source 1,2
C03.1** References
C03.10 Function Description
Preset Reference

Range
-100.00~100.00[8]

Unit Default Setting


%

0.00

Function: This parameter is an array-8 to be used for presetting dif ferent


references.
Description of Choice: 100%= value set in C03.03; It contains 8 preset references
which are selectable via digital terminals or local bus. See C05.1*.
Selection of preset reference indicates with a three-digital binary
code. If the f requency converter detects the corresponding terminals
connected, then the bit is 1, otherwise, the bit is 0. Digital input
terminalbinary code and the corresponding relationship between preset values as follows:

HLP-C100 Series Operating Manual

- 41 -

HLP-C100 Series
Binary system

Terminals State

C03.11

bit2

bit1

bit0

Preset Reference

Function Description
Jog Speed

Range

Unit

Default Setting

0.0~400.0

Hz

5.0

Function: Jog f requency is a f ixed f requency that the drive supplies to the
motor af ter the jog f unction is actived. Please refer to C05.1*, select [14].
Description of Choice: The f requency converter with the highest priority
will operate at jog speed when a variety of run command activates.
Removing the jog signal makes the f requency converter run according
to the selected configuration, this parameter is set limited by C04.14.
C03.12

Function Description

Range

Catch up/Slow down Value 0.00~100.00

Unit Default Setting


%

0.00

Function: This parameter enables the entry of a percentage value (relative)


which will to be either added to or deducted f rom the actual reference.
Description of Choice: The Catch up/Slow down f unction is activated by a
digital input terminal (See C05.1*, choose [28]/ [29] ). If this f unction
is active, the catch up/slow down value will be added to the actual
reference constituting new setting at which the f requency converter is
going to run, calculated as follows:
Total reference= reference reference (Catch up/Slowdown value) If
this f unction is inactive, the reference returns to its original value (the
actual reference).
For example: Set C05.12=28, C05.13=29, C03.12=30, assuming the actual reference
value is 20 Hz, when only DI1 is on, the output f requency is 26 Hz,
when only DI2 is connected, the output f requency is14Hz, when both
DI1 and DI2 are on, the output f requency is 20Hz.

- 42 -

HLP-C100 Series Operating Manual

HLP-C100 Series
C03.14

Function Description
Preset Relative
Reference

Range

Unit

Default Setting

-100.00~100.00

0.00

Function: Define an adjustable Preset Relative Reference which is to be added


to the total reference as a percentage value of the actual reference .
Total Reference=Actual Reference+Actual Reference * Preset Relative
Reference + Actual reference * Relative Scaling Reference
Example:
Preset
Relative
Preset
Max
Output
Min
Relative
Scaling
Reference/ Reference/ Frequency
Reference/
Reference/ Reference
C03.10
C03.03
(Hz)
C03.02
C03.14
VI/C03.18=1
0
0%
10V
20%
50
10+0+10=20
0
10%
8V
20%
50
10+1+8=19
0
20%
5V
20%
50
10+2+5=17
0
30%
3V
20%
50
10+3+3=16
0
40%
0V
20%
50
10+4+0=14
C03.15

C03.16

Function Description

Range

Reference Resource1

0~21

Function Description

Range

Reference Resource2

0~21

Unit

Default Setting
1

Unit

Default Setting
2

Option: [0] No f unction, no reference resource is defined;


[1] Analog in VI, use signals f rom Analog input VI as reference
resource, see C06.1*;
[11] Local bus reference, use signals f rom Local bus reference as
reference resource, see C08.9;
[21] LCP potentiometer, use signals f rom LCP potentiometer as
reference resource, see C06.8*;
Function: C03.15C03.16 define up to three different reference signals, the sum
of which defines is the actual reference.

HLP-C100 Series Operating Manual

- 43 -

HLP-C100 Series
C03.18

Function Description

Range

Relative Scaling Ref.

0~21

Unit

Default Setting
0

Option: [0] No f unction: No relative scaling ref. resource is defined;


[1] Analog input VI, select analog input VI as relative scaling ref.
source, see C06.1*;
[11] Local bus reference, select local bus reference as relative scaling ref.
source, see par. C08.9*;
[21] LCP potentiometer, select LCP potentiometer as relative scaling ref.
source, see par. C06.8*;
Function: The Relative Scaling Ref. Resource can be set via Analog input
terminalsLocal bus reference and LCP potentiometer.
Total Reference=Actual Reference + Actual reference * Relative Scaling
Reference.
Example:
Preset Reference/
C03.10

Relative Scaling
Reference VI/
C03.18=1

Max Reference/
C03.03

Output
Frequency(Hz)

20%

10V

50

10+10=20

20%

8V

50

10+8=18

20%

5V

50

10+5=15

20%

3V

50

10+3=13

20%

0V

50

10+0=10

C03.19

Function Description

Range

Save Speed Up/Down Value

Unit

0~2

Default Setting
0

Option: [0] No Function;


[1] Stop Save;
[2] Power Down Save;
Function: This parameter is used for setting whether to save the data changed
in the Up/Down f unction if the f requency stops or af ter it power
down.
C03.4* Ramp1
C03.40 Function Description

Range

Ramp 1 Type

0~2

- 44 -

Unit Default Setting

HLP-C100 Series Operating Manual

HLP-C100 Series
Option: [0] Linear: Motor ramp up to the preset f requency with constant
acceleration.
[2] S ramp: Motor ramp to the preset f requency with non-linear
acceleration.
Description of Choice: If Linear [1] is selected, the f requency may exceed the
preset setting during the acceleration; If S ramp [2] is selected, due
to smoother S curve, it will automatically adjust acceleration when
approaching to the preset f requency to avoid exceeding it.

Ramp type and Ramp time


Attention: It is possible to switch acceleration and deceleration via digital
input terminals, see parameterC05.1* choice. The state of the digital
input terminal is shown in binary code; If the drive detects the
corresponding digital input terminals connected, then the bit is1, on
the contrary is0. The corresponding relationship between state of the
digital input terminalsbinary code and the selected ramp type are as
follows:
Binary system

Terminal State

bit2
0
0
0
0
1
1
1
1

bit1
0
0
1
1
0
0
1
1

bit0
0
1
0
1
0
1
0
1

HLP-C100 Series Operating Manual

Ramp Group
1
2
3
4
5
6
7
8

- 45 -

HLP-C100 Series
C03.41

Function Description

Range

Unit

Default Setting

Ramp1Ramp up Time

0.10~300.00

Function: Enter the ramp-up time f rom 0 Hz to rated Motor speed in C01.25.
Attention: Choose a rame-up time such that the output current does not exceed
the current limit in C04.18.

C03.42

Function Description

Range

Ramp1 Ramp Down Time 0.10~300.00

Unit Default Setting


S

Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
C03.5* Ramp2
C03.50 Function Description

Range

Ramp2 Type

0~2

Unit Default Setting


0

Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration.

- 46 -

HLP-C100 Series Operating Manual

HLP-C100 Series
C03.51

Function Description

Range

Ramp2 Ramp up Time

0.10~300.00

Unit Default Setting


s

Function: Enter the ramp-up time f rom 0Hz to rated Motor speed in C01.25.
Attention: Choose a ramp-up time such that the output current does not exceed
the current limit set in C04.18.
C03.52

Function Description

Range

Unit Default Setting

Ramp2 Ramp down Time 0.10~300.00

Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
C03.6* Ramp3
C03.60

Function Description
Ramp3 Type

Range

Unit

Default Setting

0~2

Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration.
C03.61

Function Description

Range

Unit

Default Setting

Ramp3 Ramp up Time

0.10~300.00

Function: Enter the acceleration time f rom 0Hz to rated Motor speed in C01.25.
Attention: Choose a ramp-up time such that the output current does not exceed
the current limit set in C04.18.
C03.62

Function Description

Range

Ramp3 Ramp Down Time 0.10~300.00

Unit Default Setting


S

Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.

HLP-C100 Series Operating Manual

- 47 -

HLP-C100 Series
C03.7* Ramp4
C03.70

Function Description
Ramp4 Type

Range

Unit

Default Setting

0~2

Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration.
C03.71

Function Description

Range

Ramp4 Ramp up Time

0.10~300.00

Unit Default Setting


S

Function: Enter acceleration time f rom 0Hz to rated Motor speed in C01.25.
Attention: Choose a ramp-up time such that the output current does not exceed
the current limit set in C04.18.
C03.72

Function Description

Range

Unit Default Setting

Ramp4 Ramp Down Time 0.10~300.00

Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
C03.8* Other Ramps
C03.80

Function Description
Jog Ramp Time

Range

Unit

Default Setting

0.10~300.00

Function: Enter the time required motor speed f rom 0Hz up to rated motor
speed (C01.25) or f rom the rated motor speed (C01.25) down to 0Hz.
Description of Choice: Jog ramp time starts upon activation of a jog signal via
a selected digital input or serial communication port. See C05.1, choose
[14].
C03.84

Function Description
Ramp5 Type

Range

Unit

0~2

Default Setting
0

Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration.

- 48 -

HLP-C100 Series Operating Manual

HLP-C100 Series
C03.85

Function Description

Range

Unit

Default Setting

Ramp5 Ramp up Time 0.10~300.00

Function: Enter acceleration time f rom 0Hz to rated Motor speed in C01.25.
Attention: Choose a ramp-up time such that the output current does not exceed
the current limit set in C04.18.
C03.86

Function Description

Range

Unit Default Setting

Ramp5 Ramp Down Time 0.10~300.00

Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
selected digital input or serial communication port. See C05.1, choose [14].
C03.87

Function Description
Ramp6 Type

Range

Unit Default Setting

0~2

Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration.
C03.88

Function Description

Range

Unit

Default Setting

Ramp6 Ramp up Time

0.10~300.00

Function: Enter acceleration time f rom 0Hz to rated Motor speed in C01.25.
Attention: Choose a ramp-up time such that the output current does not exceed
the current limit set in C04.18.
C03.89

Function Description

Range

Ramp6 Ramp Down Time 0.10~300.00

Unit Default Setting


S

Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
selected digital input or serial communication port. See C05.1, choose [14].

HLP-C100 Series Operating Manual

- 49 -

HLP-C100 Series
C03.90

Function Description
Ramp7 Type

Range

Unit

Default Setting

0~2

Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration.
C03.91

Function Description

Range

Unit

Default Setting

Ramp7 Ramp up Time 0.10~300.00

Function: Enter acceleration time f rom 0Hz to rated Motor speed in C01.25.
Attention: Choose a ramp-up time such that the output current does not exceed
the current limit set in C04.18.
C03.92

Function Description

Range

Ramp7 Ramp Down Time 0.10~300.00

Unit Default Setting


S

Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
selected digital input or serial communication port. See C05.1, choose [14].
C03.93

Function Description
Ramp8 Type

Range

Unit Default Setting

0~2

Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration.
C03.94

Function Description

Range

Ramp8 Ramp up Time

0.10~300.00

Unit Default Setting


S

Function: Enter acceleration time f rom 0Hz to rated Motor speed in C01.25.
Attention: Choose a ramp-up time such that the output current does not exceed
the current limit set in C04.18.

- 50 -

HLP-C100 Series Operating Manual

HLP-C100 Series
C03.95

Function Description

Range

Unit Default Setting

Ramp8 Ramp Down Time 0.10~300.00

Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
C03.96

Function Description

Range

Unit Default Setting

Link preset reference and 0.10~300.00

Option: [0] No link;


[1] Link.
Function: If choose [1] link preset reference and ramp time, preset reference
0-7 are corresponding to ramp time 1-8. For example, choose preset
reference 2 by using terminals control, the ramp time is 3.

7.5 Parameter Group 04: Limits/warnings


C04.1* Motor Limits
*C04.10 Function Description
Motor Speed Direction

Range

Unit

0~2

Default Setting
2

Option: [0] Clockwise, the motor shaf t rotates in clockwise direction; this setting
prevents the motor f rom running in counter clockwise direction.
[1] Counter clockwise, motor shaf t rotates in counter clockwise
direction, this setting prevents the motor f rom running in clockwise
direction.
[2] Both Directions, with this setting, the motor can run in both
directions.
*C04.12 Function Description
Motor Speed Low Limit

Range

Unit

Default Setting

0.0~400.0

Hz

0.0

Function: Set the minimum limit for Motor Speed, the motor speed low limit
can be set to correspond to the minimum output f requency of the
motor shaf t . The motor speed low limit must not exceed the Motor
Speed High Limit in C04.14.

HLP-C100 Series Operating Manual

- 51 -

HLP-C100 Series
*C04.14 Function Description
Motor Speed High Limit

Range

Unit

Default Setting

0.0~400.0

Hz

65.0

Function: Enter the maximum limit for Motor Speed , the motor speed high
limit can be set to correspond to the maximum manufactures rated
motor speed. The motor speed high limit must exceed the Motor Speed
Low Limit in C04.19.
C04.18

Function Description

Range

Unit

Default Setting

Current Limit

0~300

150

Function: Set the output current high limit.


Attention: If a setting in C01.20 to C01.25 is changed, this parameter is not
automatically reset to default setting.
*C04.19 Function Description
Max Output Frequency

Range

Unit

Default Setting

0.0~400.0

Hz

65

Function: Enter value of the maximum output f requency.


C04.5* Adj. Warnings
C04.52

Function Description

Range

Unit

Default Setting

Warning Speed Low

0.0~400.0

Hz

0.0

Function: Enter the nlow value, when the motor speed falls below this limit, the
display reads Speed Low.
Attention: This setting must be within normal motor f requency range,
otherwise, it may trigger an error warning.
C04.53

Function Description

Range

Unit

Default Setting

Warning Speed High

0.1~400.0

Hz

65.0

Function: Enter the n high value, when the motor speed exceeds this limit, the
display reads Speed High.
Attention: This setting must be within normal motor f requency range,
otherwise, it may trigger an error warning.

- 52 -

HLP-C100 Series Operating Manual

HLP-C100 Series
*C04.58 Function Description
Missing Motor Phase
Function

Range

Unit

0~1

Default Setting
1

Option: [0] Off, f unctoin is disabled;


[1] On, f unction is enabled;
Attention: Missing motor phase causes motor torque to decrease. This f unction
may be disabled for special purpose (e.g. small motor running pure U/
f mode). However, choosing [0] Of f, f unction disabled, may lead to
overheating, Holip strongly recommends to make an active setting to
avoid motor damage.
C04.6* Speed Bypass
C04.61

Function Description

Range

Unit

Default Setting

Bypass Speed From

0.0~400.0

Hz

0.0

Array: [3]
Function: This parameter is a dyadic Array, [0] is used to set the bypass speed
f rom of bypass speed range 1, [1] is used to set the bypass speed f rom of
bypass speed range 2,and [2] is used to set that of bypass speed range3.
Description of Choice: Some systems call for avoiding some certain output
speed due to resonance problems in system. The drive will pass quickly
when it approaching to the Bypass Speed area.

C04.63

Function Description
Bypass Speed to

Range

Unit

Default Setting

0.0~400.0

Hz

0.0

Array: [3];
Function: This parameter is a dyadic array, [0] is used to set the bypass speed to
of bypass speed range 1, [1] is used to set the bypass speed to of bypass
speed range 2,and [2] is set as that of bypass speed range3.
HLP-C100 Series Operating Manual

- 53 -

HLP-C100 Series

7.6 Parameter Group 05: Digital Input/Output


C05.1* Digital Input
C05.10

C05.11

C05.12

C05.13

C05.14

Function Description

Range

Terminal FOR Digital Input

0~36

Function Description

Range

Terminal REV Digital Input

0~36

Function Description

Range

Terminal DI1Digital Input

0~36

Function Description

Range

Terminal DI2Digital Input

0~36

Function Description

Range

Terminal DI3Digital Input

0~36

Unit

Default Setting
8

Unit

Default Setting
10

Unit

Default Setting
15

Unit

Default Setting
16

Unit

Default Setting
17

Option: [0] No operation, the f requency converter will not to react to signals
transmitted to the terminal;
[1] Reset, reset the f requency converter af ter a Trip/Alarm;
[2] Coast Inverse, no output, leaving the motor coasting to stop;
[5] DC-brake Inverse, see C02.01, this f unction is only active when value
in C02.02 and C02.04 are different f rom 0.
[6] Stop Inverse, the drive is stopped according to selected ramp time;
[8] Start, 1=start, 0=stop;
[10] Reversing, change direction of motor shaf t rotation, reversing
signal only changes direction of rotation, it does not activate start
f unction, C04.10 must choose [2] Both directions;
[11] Start reversing, used for start/stop and for reversing at the same
time;
[14] Jog, used for activating jog speed, see C03.11;
[15] Preset ref. bit0, Preset ref.bit0bit1bit2bit3 is used for the choice
of the preset reference, see parC03.10;
[16] Preset ref. bit1, same as[15];
[17] Preset ref. bit2, same as [15];
[28] Catch up, select catch up to increase the resulting reference value
by the percentage set in par. C03.12;
[29] Slow down, select slow down to reduce the resulting reference

- 54 -

HLP-C100 Series Operating Manual

HLP-C100 Series
value by the percentage set in par. C03.12;
[34] Ramp bit0bit0bit1bit2 used f or select acceleration or
deceleration;
[35] Ramp bit1, same as [34] ;
[36] Ramp bit2, same as [34] ;
C05.4* Relay
C05.40

Function Description

Range

Relay Function

0~55

Unit

Default Setting
5

Option: [0]No operation;


[5]Drive running, Motor is running;
[9]Alarm. Frequency converter alarms;
[10]Alarm or warning. An alarm or warning occurs;
[15]Beyond f requency range. Output f requency beyond range set in
C04.52 and C04.53;
[16]Below f requency, low. Output f requency is lower than value set in
C04.52;
[17]Above f requency,high. Output f requency is higher than value set in
C04.53;
[21] Thermal warning. A thermal warning occurs;
[24]Ready-Voltage OK. Frequency converter is ready for operation,
main voltage is within specified voltage range;
[25] Reverse. Motor runs in counter clockwise;
[26] Bus OK. Local bus communication is normal;
[28] Brake-No warning. Brake is active, and no warnings are present;
[53]No alarm. Frequency converter is running normally, no alarm;
[55]Running reverse. Drive runs in counter clockwise;

7.7 Parameter Group 06: Analog In/Out


C06.1* Analoge Input 1
C06.10

Function Description
Terminal VI Low Voltage

Range
0.00~9.99

Unit Default Setting


V

0.07

Function: Enter VI Low Voltage corresponding to Min. reference/feedback set


in C06.14.

HLP-C100 Series Operating Manual

- 55 -

HLP-C100 Series
C06.11

Function Description

Range

Terminal VI High voltage 0.10~10.00

Unit Default Setting


V

10.00

Function: Enter VI High Voltage corresponding to Max. reference/feedback set


in C06.15.
C06.12

Function Description

Range

Terminal VI Low Current 0.00~19.99

Unit Default Setting


mA

mA

Function: Enter VI Low Current corresponding to Min. reference/feedback set


in C06.14.
C06.13

Function Description

Range

Terminal VI High Current 0.01~20.00

Unit Default Setting


mA

20.00

Function: Enter VI High Current corresponding to Max. reference/feedback


set in C06.15.
C06.14 Function Description
Terminal VI Low
Ref. /Feedb.

Range

Unit Default Setting

-4999.000~4999.000

0.000

Function: Enter VI Low Ref./Feedb. Corresponding to Min. voltage or min.


current set in C06.10 or C06.12.
C06.15

Function Description
Terminal VI High
Ref. /Feedb.

Range

Unit Default Setting

-4999.000~4999.000

50.000

Function: Enter VI High Ref./Feedb. Corresponding to max voltage or max


current set in C06.11 or C06.13.

- 56 -

HLP-C100 Series Operating Manual

HLP-C100 Series
C06.16

Function Description

Range

Unit Default Setting

Terminal Filter Time Constant 0.01~10.00

0.01

Function: Enter the time constant, this is a first-order digital low pass filter time
constant for suppressing electrical noise in analog input VI. A high
time constant value improves dampening but also increases the time
delay through the f ilter. This parameter cant be adjusted while the
motor is running.
C06.18

Function Description

Range

Unit Default Setting

Terminal VI Zero Dead Band 0.00~20.00 V/mA

0.00

Function: Set the dead-band of VI at 0 speed. When analog input VI ref.


low and ref. high have opposite signs, there must be a set point that
corresponding to an analogue value equals 0. In order to prevent the
set point jitter at zero point due to analog interference, this parameter
should be set properly.

Description of Choice: Point A as shown in the figure is the analog value that
corresponds to a setpoint that equals 0. It is calculated via analog low
high values and lowhigh references. UAB=UAC=C06.18/2
C06.19

Function Description
Terminal VI Mode

Range

Unit

0~1

Default Setting
0

Option: [0] Voltage mode;


[1] Current mode;
Function: Select the input to be present on analog input VI.
C06.8* LCP Potmeter
The LCP potmeter can be select either as reference resource or relative
reference resource.
HLP-C100 Series Operating Manual

- 57 -

HLP-C100 Series
C06.81 Function Description
LCP Potmeter Low
Ref.

Range

Unit Default Setting

-4999.000~4999.000

0.000

Function: This reference value corresponding to potentiometer turned f ully


counterwise .
C06.82 Function Description
LCP Potmeter High
Ref.

Range

Unit Default Setting

-4999.000~4999.000

50.000

Function: This reference value corresponding to potentiometer turned f ully


clockwise.

7.8 Parameter Group 07: Controller


C07.2* Process Ctrl. Feedb
C07.20

Function Description
Process CL Feedback 1

Range

Unit Default Setting

0~11

Option: [0] No Function;


[1] Analog in VI(0-10 V0-20 mA4-20 mA);
[11] Local Bus (0 ~ 200%);
Function: Select resource of feedback signal.
C07.3* Process PI Ctrl.
This parameter is active in closed loop process control mode.
C07.31

Function Description
Process PI Anti Windup

Range

Unit

0~1

Default Setting
1

Option: [0] Disable, continue regulation of a given error even when the output
f requency cant be increased/decreased.
[1] Enable, ceases regulation of a given er ror when the out put
f requency cant be increased/decreased.
Function: This f unction ensures the output f requency reaches to f requency
limit. PI-controller will be initialized to the current f requency when
the output f requency can not be changed. This can prevent the
integrator continue to integrate on an error when the PI-controller
cant adjust output f requency.

- 58 -

HLP-C100 Series Operating Manual

HLP-C100 Series
C07.33

Function Description
Process PI Proportional
Gain

Range

Unit

0.0~10.00

Default Setting
0.01

Function: The proportional Gain indicates the number of times the error
between the set point and the feedback signal is to be applied. Quick
control is obtained by a high gain, but if the gain is too high, the
process may become unstable.
Attention: This f unction is disabled when it is set to 0.
C07.34

Function Description

Range

Unit Default Setting

Process PI Integral Time 0.10~9999.00

9999.00

Function: The integral time is the time needed by the integrator to reach the
same gain as the porortional gain. Quick control is obtained at a short
integral time, however, this time may become too short, which can
make the process unstable.
C07.38

Function Description

Range

Unit

Default Setting

Process PI Feed Forward


Factor

0~400

Function: Feed Forward Factor acts an antidampening role to the PI action,


setting this parameter to optimize the PI controller.
C07.39

Function Description

Range

Unit

Default Setting

On reference Band Width

0~200

Description of Choice: The PI control error occurs according to the deviation


between the setpoint and the feedback , when the deviation is less
than set value in this parameter, On reference Band Width f unction is
active.
C07.41

Function Description
Process PI Output Low

Range

Unit

Default Setting

-100-100

Function: Process PI controller output low limit, 100% corresponds to C04.19.


C07.42

Function Description
Process PI Output High

Range

Unit

Default Setting

-100-100

100

Function: Process PI controller output High limit, 100% corresponds to C04.19.


HLP-C100 Series Operating Manual

- 59 -

HLP-C100 Series

7.9 Parameter Group 08: Comm. and Options


C08.0* Comm. General Settings
C08.01

Function Description
Control mode

Range

Unit

Default Setting

0~2

Option: [0] Digital and control word , use both digital input and control word as
control;
[1] Digital only, use digital input as control;
[2] Control word only, use control word only as control;
C08.02

Function Description

Range

Control Word Source

0~1

Unit

Default Setting
1

Option: [0] None, control word is inactive;


[1] FC RS485 , select local bus as control word source.
C08.03

Function Description
Control Word Time
Out Time

Range

Unit

Default Setting

0.1~6500.0

1.0

Function: This f unction is disabled, when the reference is set to 0. If the


reference is not set to 0, the control word timeout time is not exceeded,
and the serial communication is still innormal, action set in C08.04
will be carried out.
C08.04

Function Description
Contol Word Time Out Time

Range

Unit

0~5

Default Setting
0

Option: [0] Off, No f unction;


[1] Freeze output, Freeze output until communication resumes.
[2] Stop, Stop with auto restart when communication resumes;
[3] Jogging, Run motor at jog f requency until communication resumes;
[4] Max. speed, Run motor at max.f requency until communication
resumes;
[5] Stop and trip, Stop motor and restart f requency in order to restart
via either LCP or Digital input .
Function: Select action to be taken in case of timeout.

- 60 -

HLP-C100 Series Operating Manual

HLP-C100 Series
C08.06

Function Description

Range Unit Default Setting

Reset Control Word Time Out

0~1

Option: [0] No f unction Control word timeout is not reset;


[1] Do reset Control word timeout is reset;
Function: Resetting control word timeout will remove any timeout f unction;
C08.3* FC Port Setting
C08.31

Function Description

Range

Address

0~247

Unit

Default Setting
1

Function: Select the address for the bus.


C08.32

Function Description
Port Baud Rate

Range

Unit

Default Setting

0~9

bit/s

Range

Unit

Default Setting

Option: [0] 2400;


[1] 4800;
[2] 9600;
[3] 19200;
[4] 38400;
Function: Select baud rate for Port.
C08.33

Function Description
Port Parity

0~3

Option: [0] Even parity (1 stop bit);


[1] Odd parity (1 stop bit) ;
[2] No parity (1 stop bit) ;
[3] No parity (2 stop bit) ;

C08.35

Function Description

Range

Unit

Default Setting

Min. Response Delay

0.001~0.50

0.010

Function: Def ine the minmum delay time f rom receiving a request to
transmitting the respond out.

HLP-C100 Series Operating Manual

- 61 -

HLP-C100 Series
C08.36

Function Description

Range

Unit

Default Setting

Max. Response Delay

0.010~10.000

5.000

Function: Specif y maximum permissible delay time between transmitting a


request and receiving a respond. Exceeding this time delay will cause
word timeout.
C08.9* Bus Jog/Feedback
C08.94 Function Description
Bus Feedback 1

Range

Unit

-32768~32767

Default Setting
0

Function: Enter the value to be used as bus-feedback. Hex-value 4000H


corresponds to 100% feedback/range is +/-200%.

7.10 Parameter Group 14: Special Functions


C14.01

Function Description

Range

Switching Frequency

0~10

Unit

Default Setting
5

Option: [2] - [6] 2-6kHz;


[7] 8kHz;
[8] 10kHz;
[9] 12kHz;
[10] 16kHz;
Description of choice: Switching f requency of the f requency converter has a
significant influence to the inverter and the motor. Select appropriate
switch f requency can help to adjust acoustic noise f rom the motor
power consumption and the inverter ef f iciency. When switching
f requency increases, the consumption and the noise of the motor are
reduced, but the drives temperature will increase, and motor leakage
and the interference to the external device will increase; the contrary
the opposite.
*C14.03 Function Description
Over modulation

Range

Unit

0~1

Default Setting
1

Option: [0] Off, Disable the overmodulation f unction to avoid torque ripple on
the motor shaf t;
[1] On, Connects the overmodulation f unction to obtain an output
voltage up to 15% greater than mains voltage;
Function: This feature allows more accurate speed control near and over

- 62 -

HLP-C100 Series Operating Manual

HLP-C100 Series
normal speed (50/60HZ). Another advantage with overmodulation
is the ability of staying at a constant speed even though mains fault
occurs.
C14.08

Function Description

Range

Unit

Default Setting

Damping Gain Factor

0~200

96

Function: Damping gain factor can help to improve the response speed of the
DC link of the f requency converter making the DC loop signal more
smooth.
C14.1* Mains On/Off
C14.12

Function Description

Range Unit Default Setting

Function at Mains Imbanlance

0~2

Option: [0] Trip, f requency converter trips;


[1] Warning, f requency converter issues a warning (but continues to
run);
[2] Disabled, no action is taken;
Function: Select actions when a severe mains imbalance is detected.
C14.2* Trip Reset
C14.20

Function Description

Range

Reset Mode

0~13

Unit

Default Setting
0

Option: [0] Manual reset, perform reset via [reset]-button or digital inputs;
[1] - [10] Auto reset 1-10, can perform 1-10 automatic resets af ter trips;
[11] Auto reset11, can perform 15 automatic resets af ter trips;
[12] Auto reset12, can perform 20 automatic resets af ter trips;
[13] Infinite auto reset, can perform an infinite number of automatic
resets af ter tripping;
Function: Select reset f unction af ter tripping. Once auto reset is selected, the
f requency converter will be restarted af ter an alarm. If reset have
been done and the running signal is active, f requency converter will
restart automatically.
Attention: If the auto reset mode is selected, the f requency converter may
possibly restart automatically af ter the alarm disappear.

HLP-C100 Series Operating Manual

- 63 -

HLP-C100 Series
C14.21

Function Description

Range

Unit

Default Setting

Automatic Restart Time

0~600

10

Function: Enter time interval f rom trip to start of automatic reset f unction
af ter a warning/alarm.
Description of Choice: This parameter is active when C14.20, Auto Reset, is set
to Automatic reset [1]-[13].
C14.22

Function Description
Operation Mode

Range

Unit

Default Setting

0~4

Option: [0] Normal operation;


[2] Initialization, initialise all the parameters except information about
the inverter itself and the recorded parameters.
[3] Backup user settings;
[4] Recover user settings;
Function: Af ter modif ying the inverter parameters based on the f unctional
requirements, OEM manuf acturers can set C14.22 = 3 to backup
settings. If the end user modif y parameters and can not be selfrecovery, it can be recovered by setting C14.22 = 4 or pressing "OFF"
key on LCP 5 seconds.
C14.23

Function Description
Trip lock

Range

Unit

Default Setting

0~1

Option: [0] Disable, Trip lock fault reset do not need power off
[1] Enable, Trip lock fault reset need power off
C14.5* DC Voltage Compensation
*C14.51 Function Description
DC-LinkVoltage
Compensation

Range

Unit

0~1

Default Setting
0

Option: [0] Disable;


[1] Enable;
Function: This f unction ensures the output voltage is independent of any
voltage fluctuations in the DC link . Low torque ripple. In some cases,
this dynamic compensation may cause resonance problems in DC link
circuit and then this f unction should be disabled.

- 64 -

HLP-C100 Series Operating Manual

HLP-C100 Series

7.11 Parameter Group 15: Drive Information


C15.0* Operating Data
C15.00

Function Description

Range

Unit

Operating Days

0~9999

Default Setting

Function: View how many days the drive has r un. The value is saved
automatically at power off and cant be reset.
C15.02

Function Description
KWh Counter(kW)

Range

Unit

0~65535

KW

Default Setting

Function: View the power consumption f rom mains in Kwh as a mean value
over one hour. Reset the counter in C15.06.
C15.03

Function Description
Power Ups

Range

Unit

0~2147483647

KW

Default Setting

Function: View the number of times the drive has been powered up. This
parameter cant be reset.
C15.06

Function Description
Reset Kwh Counter

Range

Unit

Default Setting

0~1

Option: [0] Do not reset;


[1] Reset counter, Counter is reset;
Attention: This parameter cant be set via local bus.
C15.3* Fault Log
C15.30

Function Description

Range

Fault Log:Error Code

0~255

Unit

Default Setting

Function: View the error code, and look up its meaning in chapter 10. This
parameter group contains a fault log showing reasons for the ten latest
trips.
C15.31

Function Description

Range

Unit

Default Setting

Internal Fault Reason -32767~32767


Function: This parameter contains internal f ault reasons, mostly used in
combination with alarm 38.
HLP-C100 Series Operating Manual

- 65 -

HLP-C100 Series
C15.4*C15.5*Drive Identification
This parameter contains read only information about the hardware and
sof tware configuration of the f requency converter.
C15.40

Function Description

Range

Unit

Default Setting

Range

Unit

Default Setting

FC Type
Description of Choice: View FC Type.
C15.41

Function Description
Power Section

Description of Choice: View the power size of the f requency converter.


C15.42

Function Description

Range

Unit

Default Setting

Voltage
Description of Choice: View the voltage level corresponding to different type
of drives.
C15.43

Function Description

Range

Unit

Default Setting

Software version
Description of Choice: View the sof tware version of the drive.
C15.44

Function Description

Range

Unit

Default Setting

Ordered Type Code


Description of Choice: View the ordered type code of the drive.
C15.46

Function Description

Range

Unit

Default Setting

FC ordering No.
Description of Choice: View ordering number of the FC.
C15.47

Function Description

Range

Unit

Default Setting

Power Card Ordering No.


Description of Choice: View ordering number of the power card.

- 66 -

HLP-C100 Series Operating Manual

HLP-C100 Series
C15.49

Function Description

Range

Unit

Default Setting

Software ID Control Card


Description of Choice: View the control card ID number.
C15.50

Function Description

Range

Unit

Default Setting

Software ID Power Card


Description of Choice: View the power card ID number.
C15.51

Function Description

Range

Unit

Default Setting

FC Serial Number
Description of Choice: View the drives serial number.
C15.53

Function Description

Range

Unit

Default Setting

Power Card Serial Number


Description of Choice: View power card serial number.
C15.5* Defined parameters
C15.92

Function Description

Range

Parameter List

0~255

Unit

Default Setting

Function: View drive parameters that has been defined.

7.12 Parameter Group 16: Data Readouts


This parameter group is read-only.
C16.0* General Status
C16.01

Function Description
Reference

Range

Unit Default Setting

-4999.000~4999.000

Function: View the total remote reference, the total reference is sum of pulse,
analog, preset, LCP Potmeter, local bus and f reeze reference.
C16.05

Function Description

Range

Unit Default Setting

Motor Speed [RPM]

0~9999

Hz

Function: View motor speed.


HLP-C100 Series Operating Manual

- 67 -

HLP-C100 Series
C16.1* Motor Status
C16.10

Function Description
Power(kW)

Range

Unit Default Setting

0.000~1000.000

kW

Function: View output power in KW.


C16.12

Function Description

Range

Motor Voltage

Unit Default Setting

0~65535

Function: View motor phase voltage.


C16.13

Function Description

Range

Frequency

Unit Default Setting

0.0~400.0

Hz

Function: View output f requency.


C16.14

Function Description
Motor Current

Range

Unit

0.00~655.35

Default Setting

Function: View motor phase current.


C16.3* Drive Status
C16.30

Function Description

Range

Unit

0~65535

Function Description

Range

Unit

Inverter Temp.

0~255

DC Link Voltage

Default Setting

Function: View DC-link voltage.


C16.34

Default Setting

Function: View the temperature of drives heatsink.


C16.5* Ref./Feedb.
C16.52

Function Description
Feedback

Range

Unit Default Setting

-4999.000~4999.000

Function: View analog or pulse feedback in HZ.

- 68 -

HLP-C100 Series Operating Manual

HLP-C100 Series
C16.6*C16.7* Inputs and Outputs
C16.60

Function Description
Digital Input

Range

Unit

Default Setting

0~65535

Function: View signal states f rom active digital inputs, which indicates in a 16bit binary code. If the drive detects digital input terminals connected,
the corresponding position is set to 1, otherwise 0. Digital input
terminal and the corresponding relationship between the binary code
are as below:
Binary Term. No. Binary Term. No. Binary Term. No. Binary Term. No.
bit0
FOR
bit4
DI3
bit8 Reserved bit12 Reserved
bit1
REV
bit5 Reserved bit9 Reserved bit13 Reserved
bit2
DI1
bit6 Reserved bit10 Reserved bit14 Reserved
bit3
DI2
bit7 Reserved bit11 Reserved bit15 Reserved
C16.62

Function Description
Analog Input VI

Range

Unit

0.00~20.00

V/mA

Default Setting

Function: View actual input voltage or current value on analog input VI.
C16.71

Function Description
Relay Output

Range

Unit

Default Setting

0~65535

Function: View the output status of the relay, the corresponding bit is set to
1when the relay output is active, otherwise it will be set to 0.
Binary
Item. No.

bit0
Relay 1

C16.8* Field bus/FC Port


C16.86

Function Description
FC Port Reference

Range

Unit

Default Setting

-32768~32767

Function: View the last received reference f rom the FC port.


C16.9* Diagnosis Readouts
C16.90

Function Description
Alarm Word

Range

Unit Default Setting

0~0xFFFFFFFFUL

Function: View the alarm word sent via the serial communication port in hex
HLP-C100 Series Operating Manual

- 69 -

HLP-C100 Series
code. Convert this parameter to a 32-bit binary code, def inition of
the bits in alarm word showed in the table below, among which that
reserved by manufacturers are undefined bits:
Binary

Alarm Word/
C16.90

Brake detect

Power Card over


Temp.

2
3

Alarm Word 2 / Warning Word/ Warning Word


C16.91
C16.92
2/C16.93
Undefined

Undefined

Undefined

Undefined

Power Card over


Temp.

Undefined

Earth Fault

Trip

Earth Fault

Undefined

Undefined

Option part

Undefined

Undefined

Control Card
Temp

Undefined

Control Card
Temp

Undefined

Over Current

Undefined

Over Current

Undefined

Torque Limit

Undefined

Undefined

Undefined

Undefined

Undefined

Undefined

Undefined

Undefined

Damaged part

Undefined

Damaged part

Inverter
Overload

Undefined

Inverter
Overload

Undefined

10

DC Under Volt

Undefined

DC Under Volt

Undefined

11

DC Over Volt

Undefined

DC Over Volt

Undefined

Short Circuit

External
Interlock

Undefined

Undefined

12
13

Undefined

Undefined

Undefined

Undefined

14

Mains ph. loss

Undefined

Mains ph. loss

Undefined

15

Undefined

Undefined

No motor

Undefined

16

Live zero error

Undefined

Live zero error

Undefined

17

Internal Fault

Undefined

Undefined

Undefined

18

Brake overload

Fan Fault

Brake overload

Fan Fault

19

U phase loss

Undefined

Undefined

Undefined

20

V phase loss

Undefined

Undefined

Undefined

21

W phase loss

Undefined

Undefined

Undefined

22

Undefined

Undefined

Undefined

Undefined

- 70 -

HLP-C100 Series Operating Manual

HLP-C100 Series

Binary

Alarm Word/
C16.90

23

Control Voltage
Fault

Alarm Word 2 / Warning Word/ Warning Word


C16.91
C16.92
2/C16.93
Undefined

Undefined

Undefined

24

Undefined

Undefined

Undefined

Undefined

25

Undefined

Undefined

Current Limit

Undefined

26

Brake resistor
error

Undefined

Undefined

Undefined

27

Brake transistor
fault

Undefined

Undefined

Undefined

28

Bake transistor
open circuit

Undefined

Undefined

Undefined

29

Drive initialize Feedback error

Undefined

Feedback error

30

Undefined

Undefined

Undefined

Undefined

31

Mech. Brake
low

Undefined

Undefined

Undefined

C16.91

Function Description
Alarm Word 2

Range

Unit Default Setting

0~0xFFFFFFFFUF

Function: View the Alarm Word sent via serial communication port in hex
code.
C16.92

Function Description
Warning Word 1

Range

Unit Default Setting

0~0x7FFFFFFFUF

Function: View the Warning Word 1 sent via serial communication port in hex
code.
C16.93

Function Description
Warning Word 2

Range

Unit Default Setting

0~0x7FFFFFFFUF

Function: View Warning Word 2 sent via serial communication port in hex
code.

HLP-C100 Series Operating Manual

- 71 -

HLP-C100 Series

Chapter 8 Accessory Specification


8.1 Braking Resistor
When the motor acts as a generator, the braking resistor consumes surplus
energy resulting f rom motor braking to achieve fast stop. And to prevent the
intermediate circuit voltage is too high to trip eventually.
Note: The braking resistor will be very hot, and will have a risk of fire, if the
transistor in the braking unit is damaged and shorted. The installation
length of the braking resistor should be not less than 5 meters.
Brake resistor (option):
Model
HLP-C1000D3721
HLP- C1000D7521
HLP- C10001D521
HLP- C1000D3723
HLP- C1000D7523
HLP- C10001D523
HLP- C1000D7543
HLP- C10001D543
HLP- C10002D243

Braking Resistor Specification

KW
310
0.25
145
0.065
65
0.25
310
0.25
145
0.065
65
0.25
620
0.065
310
0.25
210
0.285

Suitable
Motor(KW)
0.37
0.75
1.5
0.37
0.75
1.5
0.75
1.5
2.2

Note: An external braking unit is needed when connecting braking resistor for
the FC which power is less than 220V/380V 0.75kW(included) .

8.2 LCP Mounting Kit


8.2.1 External LCP Communication Cable
External LCP Communication Cable is network cable. Length should
not exceed 15m. More than five types of shielded cable is recommended for use
in the presence of electromagnetic interference environment.

8.2.2 Mounting steps


An external LCP mounting kit is provided; users need to open a hole (size
as shown below). The installation steps are as follows:

- 72 -

HLP-C100 Series Operating Manual

HLP-C100 Series
This cradle is suitable for 1.0-2.0mm
t h ick ness shee t
metal parts
Press and hold
the snap roots when
installation, using
buckle deformation
Step1: Open a hole in line with the size of the install sheet metal.
control panel in the position need to install Step2: Install the LCP according to
the LCP, hole size, as shown:
the direction of the arrow.
Recommended
to install vertical
mounting position
arrow, press with
uniform force.

Step 3: The LCP is installed in the cradle,


according to the direction of the arrow.

Step 4: Install the external LCP communication


cable, insert into RJ45 terminal f rom thebottom
of hole.

Chapter 9 EMC
9.1 EMCCorrect Installation
HLP-B serials drive implement the latest international standards,
following these guidelines is advised, IEC/EN61800-3:2004 (Adjustable speed
electrical power drive systems part 3: EMC requirements and specif ic test
methods). In order to achieve the using requirements of the EMC, must meet
the following specifications:
Using shield motor cables, and connect it to the decoupling device
(optional) and the metal motor cabinet;
To reduce the noise and the leakage current, use the motor cable as short
as possible;
The entire system need to have a good earthling;
RFI Switch screw must be tightened up.

9.2 RFI Switch


Use the RFI switch screw to remove the internal EMC f ilter, if the
f requency converter is supplied f rom IT or TN Grid. If a drive with EMC
filter is connected to the IT grid, then the system may be grounded through the
EMC filter capacitors, this may cause damage to the inverter. If a drive with
EMC filter is connected to the TN grid, the drive may be burned. Remove the
RFI switch can help to reduce the leakage currents.
HLP-C100 Series Operating Manual

- 73 -

HLP-C100 Series

Chapter 10 Warnings/Alarms and Fault Handling


10.1 Fault List
The HLP-C100 drive has three different fault types: Warning, alarm and error.
When a fault happens, the drive shows a specific code to indicate it.
When a warning happens, it means that the drive is close to its design
limits for some reason, but the drive still works. If the drive fault disappear,
the warning will also disappear.
An alarm means that the drive has exceeded its design limits for some
reason. When this happens, the drive will trip. Af ter an alarm the driver must
be reset in order to re-run. When some alarms happen, the drive will lock itself.
These alarms are called trip-lock alarm. The Trip-lock alarm offers additional
protection, the default setting is that the main power should be cut off before
resetting the alarm. But by setting parameters C14.23 = 0, the trip-lock alarm
can be reset without cutting the main power off. But there is a risk of accident
when choosing this f unction. Before using this f unction, it is important to be
familiar with the drive and the whole system in order to be safe when dealing
with the drive.
Error means that the drive is in a certain state where it is unable to carry
out an operation.
Warning

Alarm Error Fault Description

A.03

E.03

A.04

E.04*

A.07

E.07

A.08

E.08

A.09

E.09

A.10

E.10

A.13

E.13*

- 74 -

Reason analysis
Motor cable connection
problems
Missing phase on supply side
or too high voltage imbalance.
Mains Phase The allowed power imbalance
Loss
of HLP-C100 series inverter is
3% of the rated voltage.(IEC
Standard)
Intermediate circuit voltage
Over Voltage
exceeds limit.
Intermediate circuit voltage
Under Voltage drops below voltage warning
low limit.
Inverter
More than 100% overload for
Overload
too long time.
Motor ETR Over Motor temperature calculated
Temperature by ETR exceeds upper limit
Inverter peak current limit is
Over Current
exceeded.
Motor Loss

HLP-C100 Series Operating Manual

HLP-C100 Series
Warning
A.14

Alarm Error Fault Description


E.14*

Earth fault

E.16*

Short Circuit

A.17

E.17

Control Word
Timeout

A.24

E.24

Fan Fault

E.25*

Brake resistor
short-circuit

E.27

Brake transisitor
short-circuit

E.28

Brake Detect

E.30*
E.31*
E.32*
E.38*
A.59
A.61

Motor phase U
missing
Motor phase V
missing
Motor phase W
missing
Internal Fault
Current Limit

E.61

A.66
A.69

E.69*

A.79

E.79
E.80

Reason analysis
Discharge f rom output phases
to ground(22KW and below)
Short circuit in motor or on
motor terminals.
Drive communication timeout,
this alarm occurs when C08.04
is set to 0 or 5.
Too much dust on the fan or
the fan is aging.
Brake resistor is short circuit,
leading the brake f unction
invalid.
Brake transistor is short circuit
leading brake f unction invalid.
Brake resistor is not connected
or working.
Motor phase U is missing,
check the phase.
Motor phase V is missing,
check the phase.
Motor phase W is
missing,check the phase.
Contact the local distributor or
Holip Company.
Current exceeds value set in
C04.18.
Feedback signal is out of range.

Feedback Error
Heat sink low
Temperature may be damaged.
temperature
Power Card Power card is over
Temp.
temperature.
Contact local distributor or
Undefined fault
Holip Company.
Parameter
Make parameter initialized.
Initialization
LCP Connection
No communication between
Er.84 with the inverter
LCP and the inverter.
failed
Button is
Refer to parameter group
Er.85
disabled
C04*

HLP-C100 Series Operating Manual

- 75 -

HLP-C100 Series
Warning

Alarm Error Fault Description


Reason analysis
Parameter read- Try to write read-only
Er.89
only
parameter.
LCP and RS485 connection
Parameter
Er.90
try to updata parameter at the
Database Busy
same time.
Parameter value
Invalid parameter value to
Er.91 is invalid in this
write.
mode
Parameter Value
Value try to be set exceeds the
Er.92 Beyond Max./
limit allowed.
Min. Limit
Parameter has f rozen or cant
Err
Unchangeable
be changed during running.

Note: Trip-lock alarm is with *.

10.2 Fault Indication and Trouble Shooting


The inverter of HLP-C100 serials is relatively perfective with protection
f unctions of overload, inter-phase short circuit, earth short circuit, and overcurrent etc. When a protection f unction occurs, please check reasons of the
faults according to the information listed in the table below. The inverter can
be restart af ter the disposal. If the fault cant be disposaled, please contect the
distributor or Holip company.
Fault

Process Method

Motor runs unsteadily but no warnings issued, may be


1. Motor runs motor parameter settings are not correct, please adjust
unsteadily motor parameter settings, if no effect, please contact Holip
Company.
Confirm whether the screen display is normal;
If screen display is properly, verif y if warning or alarm
information displays;
If any warning or alarm occurred, please refer to
2. Motor cant
corresponding troubleshooting section;
rotate
If no warning or alarm occurred, please refer to item 5 below;
If there is no screen display, please make sure if the supply
voltage is correct;
If the supply voltage is correct, please refer to item 4 below.
3. Motor brake
f unction cant Please refer to braking f unction section;
be performed.

- 76 -

HLP-C100 Series Operating Manual

HLP-C100 Series
Fault

Process Method

Confirm whether the input f use meltdown;


Verif y whether control card is overload;
4. No fault
Suppose control card is overload, and 24V is shorted, please
message or
remove the connection of control terminal;
screen display
Make sure if any fault message is displayed, and if no, please
contact Holip Company;

5. Motor cant
rotate and
screen display
is normal
without fault
message

Press [Enter] on LCP;


Make sure whether the screen is active i.e. the screen display
cant be switched or parameter cant be edited;
Suppose screen is f reeze, please make sure screened cable
used and connected correctly;
If operation of the display screen is normal, please make
sure connection between motor and the f requency converter
is correct and then operate the drive in hand mode. Please
contact Holip Company if motor cant rotate.

HLP-C100 Series Operating Manual

- 77 -

HLP-C100 Series

Chapter 11 Maintenance
11.1 Note
Conf irm the main circuit power supply has been turned off, and the
display has disappeared before carry out inspection and maintenance. Make
sure the system is in dynamic state, please pay attention to the following:
Check whether the power supply voltage matches to the rated voltage
of the inverter;
Check whether the motor makes unexpected noises or abnormal
vibration when running;
Check whether there are abnormal heating;
Check whether the inverter output voltage, output current, output
f requency, and monitor display is greater than the value commonly
used.
Check whether the cooling fan installed at the lower part of the inverter
runs normally;
Check whether the ambient temperature is too high and whether there
is dust, iron filings, corrosive fluid in the inverter;
Check whether the ambient temperature of the inverter is between
-10~40, and whether the humidity is between 5%-85% (95% is
without condensation), phenomenon of water droplets is not allowed;
The inverter should be discarded as industrial waste. It is forbidden to
burn it;

11.2 Storage and Transport


The inverter must be kept in its original package box before installation.
Pay attention to the followings when keeping it in storage if the inverter is not
used for the time being:
It must be stored in a dry place without rubbish or dust;
The suitable temperature for storage is between -25-65;
The relative humidity required is 5%-95% without condensation;
There is no corrosive gas or liquid in the storage ambience;
It is better to lay the inverter on a rack and keep it in a proper package;
The ambient temperature for transport is between -25-70;
The relative humidity of transport ambience must be less than 95%
(Ambient temperature is 40) .
Attention: It is better not to store the inverter for long time. Long time storage
of the inverter will lead to the deterioration of electrolytic capacity.
If it needs to be stored for a long time make sure to power it up one
time within a year and the power-up time should be at least above five
hours. When powering up, supply voltage must be increased slowly
with a voltage regulator to the rated voltage value.

- 78 -

HLP-C100 Series Operating Manual

HLP-C100 Series

Chapter 12 Communication protocol


HLP-C100 series inverter follows the standard Modbus RTU protocol.

12.1 Format specification


Address
8 bits

Function code
8 bits

Data
N*8 bits

CRC
16 bits

1) Address: 1-247
2) Function: HLP-C100 support following f unction code
01: Read Coil Status
03: Read Holding Registers
05: Force Single Coil
06: Preset Single Register
15: Force Multiple Coils
16: Preset Multiple Regs
3) DATA: N8bits
4) CRC: CRC check

12.2 Coil addressing


Coil address

R/W

0-15

R, W

16-31

R, W

Frequency converter speed or setpoint

32-47

Frequency converter status word(see


following table)

48-63

Frequency converter output f requency

Parameter write control


0000-Parameter changes are written to the
RAM;
FF00- Parameter changes are written to the
RAM and EEPROM;

64

65-65535

Description
Frequency converter control word (see
following table)

Reserved

HLP-C100 Series Operating Manual

- 79 -

HLP-C100 Series
FC control word
Coil address

00

1
Preset reference bit0

01

Preset reference bit1

02

DC brake

03

Coast stop

04

No DC brake
No coast stop
Reserved

05

Freeze f req

06

Ramp stop

No f reeze f req
Start

07

No reset

Reset

08

No jog

Jog

09

Ramp 1

Ramp 2

10

Data invalid

Data valid

11

Relay off

12

Relay on
Reserved

13

Reserved

14

Reserved

15

No reversing

Reversing

Status word
Coil address
0
1
32
Control not ready
Control ready
33
Frequency converter not ready Frequency converter ready
34
Coasting stop
Satety closed
35
No alarm
Alarm
36
Reserved
37
Reserved
38
Reserved
39
No warning
Warning
40
Not at reference
At reference
41
Hand mode
Auto mode
42
Out of f req range
In f req range
43
Stopped
Running
44
Reserved
45
No voltage warning
Voltage warning

- 80 -

HLP-C100 Series Operating Manual

HLP-C100 Series
Coil address
46
47

0
Not in current limit
No thermal warning

Register
00000-00007
00008
00009-00989
00999-01989
01999-02989

15999-16989

1
Current limit
Thermal warning
Description
Reserved
Parameter index
Parameter group 00
Parameter group 01
Parameter group 02

Parameter group 16

The relationship between register address and parameter number is:


register address = parameter number 10-1

12.3 Read Coil Status


Example: Detect inverter output f requency
Transmit: 01 01 00 30 00 10 3D C9 (Hexadecimal)
Receive: 01 01 02 00 20 B8 24 (Hexadecimal)
Transmit data
Field
01
01
00 30

Description
FC address
Funtion
Coil address (ADDRH ADDRL). 0x0030 convert to decimal
number is 48. Coil address 49 is f requency converter output
f requency.

00 10

Data bits number is 16. 0x 0010 convert to decimal number is 16

3D C9

CRC check

Receive data
Field
01

Description
FC address

01

Function

02

The read byte number is 2

HLP-C100 Series Operating Manual

- 81 -

HLP-C100 Series
Field

Description

00 20

Ouput f requency. Swap high and low, the data is 0x2000, so the
output f requency is 50% of C03.03. Why does 0x2000 correspond
to 50%, please see 12.6.

B8 24

CRC check

12.4 Read Holding Registers


Example: Read the value of C03.03
Transmit: 01 03 0B D5 00 02 D7 D7 (Hexadecimal)
Receive: 01 03 04 00 00 EA 60 B5 7B (Hexadecimal)
Transmit data
Field
01
03
0B D5

Description
FC address
Function
Register address(ADDRH ADDRL). The register address of
C03.03 is 303*10-1=3029 (0x0BD5)

00 02

The number of read registers is 2

D7 D7

CRC check

Receive data
Field

Description

01

FC address

03

Function

04

The byte number of received data

00 00 EA 60
B5 7B

0x0000EA60 convert to decimal number is 60000. So the value


of C03.03 is 60000*0.001=60.000
CRC check

12.4 Force Single Coil


Example: write parameter to RAM and EEPROM
Transmit: 01 05 00 40 FF 00 8D EE (Hexadecimal)
Receive: 01 05 00 40 FF 00 8D EE (Hexadecimal)

- 82 -

HLP-C100 Series Operating Manual

HLP-C100 Series
Transmit data
Field
01
05
00 40
FF 00
8D EE

Description
FC address
Function
0x0040 convert to decimal number is 64. The register address 64
is parameter write control
0000-Parameter changes are written to the RAM;
FF00- Parameter changes are written to the RAM and
EEPROM;
CRC check

Transmit data
Field
01
05
00 40
FF 00
8D EE

Description
FC address
Function
0x0040 convert to decimal number is 64. The register address 64
is parameter write control
0000-Parameter changes are written to the RAM;
FF00- Parameter changes are written to the RAM and
EEPROM;
CRC check

12.5 Preset Single Register


Example: set C01.01 = 1
Transmit: 01 06 03 F1 00 01 19 BD (Hexadecimal)
Receive: 01 06 03 F1 00 01 19 BD (Hexadecimal)
Transmit data
Field
01
06
03 F1
00 01
19 BD

Description
FC address
Function
The register address of C01.01 is 101*10-1=1009 (0x03F1)
The parameter value is 1
CRC check

HLP-C100 Series Operating Manual

- 83 -

HLP-C100 Series
Receive data
Field
01
06

FC address
Function

Description

03 F1

The register address of C01.01 is 101*10-1=1009 (0x03F1)

00 01
19 BD

The parameter value is 1


CRC check

12.6 Force Multiple Coils


Example: the f requency is 40% of C03.03.
Transmit: 01 0F 00 00 00 20 04 7C 04 9A 19 37 B3 (Hexadecimal)
Receive: 01 0F 00 00 00 20 54 13 (Hexadecimal)
Transmit data
Field
01
0F

Description
FC address
Function

00 00

Register address 0 is f requency converter control word.

00 20

The bit number is 32.

04

The byte number is 4

7C 04

Control word. 7C 04swap high byte and low byte, the value
is 0x047C
Note:
0x047C convertes to binary is: 0000 0100 0111 1100 are
corresponding to the coil address 0-15

9A 19

Frequency reference.9A 19 swap high byte and low byte, the


value is 0x199A. Frequency is 40% of C03.03(see the following
f requency conversion specification).

37 B3

CRC check

Frequency conversion specification:


If you want to set the f requency as 20Hz, 20Hz is 40% of the maximum
f requency (it determined by the C03.03 parameters, the def ault is 50Hz).
Calculation method: 20/50 * 16384 = 6553.6 converted to hexadecimal 0x199A.
So if you want to set the f requency as feq, you can calculate: feq / C03.03
16384 then converts into hexadecimal. 16384 converts into hexadecimal is
0x4000. The reason to be multiplied 16384 is for a higher accuracy.

- 84 -

HLP-C100 Series Operating Manual

HLP-C100 Series
Receive data
Field
01
0F
00 00
00 20
54 13

Description
FC address
Function
Register address 0 is f requency converter control word.
The bit number is 32.
CRC check

12.7 Preset Multiple Regs


Example: Set C03.03 = 60.000
Transmit: 01 10 0B D5 00 02 04 00 00 EA 60 02 B4 (Hexadecimal)
Receive: 01 10 0B D5 00 02 52 14 (Hexadecimal)
Transmit data
Field
01
10
0B D5
00 02
04
00 00 EA 60
02 B4

Description
FC address
Function
The register address of C03.03 is 303*10-1=3029 (0x0BD5)
Register number
The byte number of data is 4
0x0000EA60 convert to decimal number is 60000. So the value
of C03.03 is 60000*0.001=60.000
CRC check

Receive data
Field
01
10
0B D5
00 02
52 14

Description
FC address
Function
The register address of C03.03 is 303*10-1=3029 (0x0BD5)
Register number
CRC check

12.8 Read/Write array


Example: write parameter 310[2] (index=2)
Transmit: 01 06 00 08 00 02 89 C9 (Hexadecimal)
Receive: 01 06 00 08 00 02 89 C9 (Hexadecimal)
HLP-C100 Series Operating Manual

- 85 -

HLP-C100 Series
Transmit: 01 10 0C 1B 00 01 02 00 00 69 BB (Hexadecimal)
Receive: 01 10 0C 1B 00 01 72 9E (Hexadecimal)
Transmit data 1
Field
01
06

Description
FC address
Function

00 08

Register address (ADDRH ADDRL), the register address of


parameter index is 0x0008

00 02
89 C9

The index is 2(0x0002)


CRC check

Receive data 1
Field
01
06
00 08

Description
FC address
Function
Register address (ADDRH ADDRL), the register address of
parameter index is 0x0008

00 02

The index is 2(0x0002)

89 C9

CRC check

Transmit data 2
Field

Description

01

FC address

10

Function

0C 1B

The register address of C03.10 is 310*10-1=3099 (0x0C1B)

00 01

Register number

02

Byte number

00 00

The value of 310[2] is 0

69 BB

CRC check

- 86 -

HLP-C100 Series Operating Manual

HLP-C100 Series
Receive data 2
Field
01
10
0C 1B

Description
FC address
Function
The register address of C03.10 is 310*10-1=3099 (0x0C1B)

00 01

The number of register

72 9E

CRC check

12.9 Exception code


When a communication exception is happened, the inverter returns data
format as following:
Address

Function

Exception code

CRC check

8 bits

8 bits

8 bits

16 bits

Exception code
0x00

Description
Parameter number does not exist

0x01

Defined parameters can not be written

0x02

The value exceeds the upper limit of the parameter

0x03

Index does not exist

0x04

The parameter is not array type

0x05

Data type exception

0x06

Only use for reset

0x07

Cannot be changed

0x0B

Not allowed to write

0x11

Data cannot be changed in the current mode(some


parameter cannot be changed when the inverter is running)

0x12

Other exception

0x40

Invalid data address

0x41

Invalid length

0x42

Invalid length and value

0x43

Invalid parameter

0x82

The parameters has no bus connection

0x83

Factory settings, cannot be changed.

HLP-C100 Series Operating Manual