Manual
HLP-C100 Series
Index
Introduction
Chapter 1 Safety Precautions
1.1 Before power-up
1.2 During the power-up
1.3 During the operation
1.4 After the power-off
Chapter 2 Standards and Specifications
2.1 Label Description
2.2 Particular specifications
2.3 Technical specifications
Chapter 3 Installation and Wiring
3.1 Checks before Installation
3.2 Installation dimensions
3.2.1 Dimensions of the Inverter
3.2.2 Dimensions of the inverter
3.3 Installation and Wiring
3.3.1 Electrical Installation in General
3.3.2 Fuse Specifications
3.3.3 Installation and Direction
3.3.4 Wiring terminal
3.3.5 Wiring
Chapter 4 Operation and Display Interface
4.1 LCP Digital Operator
4.2 Quick to set parameters
4.2.1 Preset reference by LCP
4.2.2 FWD/REV Status
4.2.3 Data Read-outs
4.2.4 View alarm record
4.2.5 View state parameter
4.2.6 LED Display
Chapter 5 Quick Application Guide
5.1 Parameter initialization
5.2 Using LCP to control the drive [HAND]
5.3 Using digital in terminals to control the drive [AUTO]
5.4 Forward, Reverse and Jog
5.5 Multi-speed
Chapter 6 Parameter Overview
HLP-C100 Series Operating Manual
I
1
-1-2-3-3-4-4-5-5-8-8-8-8-9-9- 10 - 10 - 11 - 13 - 14 - 14 - 14 - 14 - 15 - 16 - 17 - 18 - 20 - 21 - 21 - 21 - 21 - 21 - 21 - 22 - 23 -
HLP-C100 Series
Chapter 7 Parameter Description
7.1 Parameter group 00: operation/display
7.2 Parameter group 01: load and motor
7.3 Parameter group 02: brakes
7.4 Parameter group 03: reference/ramps
7.5 Parameter group 04: limits/warnings
7.6 Parameter group 05: digital input/output
7.7 Parameter group 06: analog in/out
7.8 Parameter group 07: controller
7.9 Parameter group 08: comm. and options
7.10 Parameter group 14: special functions
7.11 Parameter group 15: drive information
7.12 Parameter group 16: data readouts
Chapter 8 Accessory Specification
8.1 Braking resistor
8.2 LCP Mounting Kit
8.2.1 External LCP Communication Cable
8.2.2 Mounting steps
Chapter 9 EMC
9.1 EMCCorrect Installation
9.2 RFI Switch
Chapter 10 Warnings/Alarms and Fault Handling
10.1 Fault list
10.2 Fault indication and trouble shooting
Chapter 11 Maintenance
11.1 Note
11.2 Storage and transport
Chapter 12 Communication protocol
12.1 Format specification
12.2 Coil addressing
12.3 Read coil status
12.4 Read holding registers
12.4 Force single coil
12.5 Preset single register
12.6 Force multiple coils
12.7 Preset multiple regs
12.8 Read/write array
12.9 Exception code
- 33 - 33 - 35 - 39 - 41 - 51 - 54 - 55 - 59 - 60 - 62 - 65 - 67 - 72 - 72 - 72 - 72 - 73 - 73 - 73 - 74 - 74 - 76 - 78 - 78 - 78 - 79 - 79 - 79 - 81 - 82 - 82 - 83 - 84 - 85- 85 - 87 -
HLP-C100 Series
-1-
HLP-C100 Series
high voltage.
The IC board of the inverter are susceptible to the effect and
damage of static electricity. Dont touch the main circuit board.
Installation, commissioning and maintenance must be performed
by qualified professional personnel.
It should be handled with the base to avoid the dropping of the
inverter, which may possibly cause the injuries to people and the
damages to the inverter.
Danger
Be sure to turn off the power supply before wiring.
Mount the drive in the metal and other non-combustible materials
to avoid the risk of fi re.
Dont install the drive in a space with explosive gas, otherwise,
they lead to explosion.
R, S, T terminals are power input terminals, never mixed with
U.V.W terminals. Be sure that the wiring of the main circuit is
correct. Otherwise it will cause damages of the inverter when the
power is applied to it.
The ter minal of
must be grounded separately and never
connected to N-line. Otherwise it will easily cause the protection
or errors of the inverter.
Do not dissemble or modify any internal connecting cord, wiring
or component of the inverter by yourself.
Never remodel it or exchange control boards and components by
yourself. It may expose you to an electrical shock or explosion,
etc.
Keep the inver ter from the reach of children or persons not
concerned.
-2-
HLP-C100 Series
Danger
Never connect or disconnect the motor set while the inverter is in
running. Otherwise it will cause over-current trip and even burn
up the main circuit of the inverter.
Never remove the front cover of the inverter while the inverter is
powered up to avoid any injury of electric shock.
Do not come close to the machine when the Reset Function is
used to avoid anything unexpected. The motor may automatically
recover from fault.
-3-
HLP-C100 Series
1-8
9-12
13-14
15-17
18
19
20
21
22
23
24
25
26-27
28-31
-4-
HLP-C100
0D37
21
23
43
P20
X
A
X
B
X
B
1
C
X
0
1
A
B
XX
VXXX
HLP-C100 Series
Input voltage
HLP-C1000D3721
HLP-C1000D7521
HLP-C10001D521
HLP-C1000D3723
HLP-C1000D7523
HLP-C10001D523
1200-240V50/60HZ
1200-240V50/60HZ
1200-240V50/60HZ
3200-240V50/60HZ
3200-240V50/60HZ
3200-240V50/60HZ
3380-440V50/60HZ
HLP-C1000D7543
3440-480V50/60HZ
3380-440V50/60HZ
HLP-C10001D543
3440-480V50/60HZ
3380-440V50/60HZ
HLP-C10002D243
3440-480V50/60HZ
Frequency
Max. imbalance
Output voltage
Motor output Output
f requency
Control mode
Start torque
Overload capacity
PWM switch
f requency
Main control Speed setting
f unctions
resolution
Control
command source
Frequency setting
source
Ramp control
Specification
single/three phase 220V 20%;
three phase 380V 20%;
48-62Hz;
3%;
three phase 0-100% of supply voltage;
0-400Hz
V/F
0.5Hz 150%;
150% rated output current (60s)
2K-16KHz
Digital: 0.001Hz; analogy: 0.5 of the
max. operating f requency ;
LCP , digital terminal, local bus;
LCP , analog, local bus;
Selectable 8-speed steps;
-5-
HLP-C100 Series
Item
Specification
Automatic Voltage Regulation; V/F Control, DC Brake;
Basic Functions Speed Limit; Current Limit; Reset Function; Timer; PI
Controller.
Speed Open-loop Control; Process Closed-loop Control;
Jogging ; Multi-speed Control via Digital input; Deferent
Application
speed with deferent ramp; Mechanical Braking; Catch up /
Functions
Slow down; Relative Scaling Reference; Recover user settings
by a key etc.
Missing Motor Phase Protection; Low-voltage Protection;
Over-voltage Protection; Over-current Protection; Output
Phase Loss Protection; Output Short Circuit Protection;
Protection Out put Grounding Fault Protection; Motor Ther mal
Functions Protection; CPU Fault; EEPROM Faults; Button f reeze;
Duplicate Fails; LCP Invalid; LCP Incompatible; Parameter
Read-only; Reference Out of Range; Invalid While Running;
Password Error etc.
Number
5 digital inputs.
Digital input
Scanning time
1ms;
1 analog inputs(VI),
both can receive
Number of input
voltage or current
signals.
Analog input
Max.error: 0.5% of
Input accuracy
f ull scale
Resolution
11bit;
Scanning time
1ms;
Control
Terminals
1 relay outputs (FARelay output
FB-FC) ;
Digital output
Scanning time
1ms;
Power supply
RS485 serial
communication
-6-
10VDC power
supply;
1, RS+(TX+,RX+),
Terminal number
RS-(TX-, RX-);
Ground for
COM;
RS485
+10V
HLP-C100 Series
Item
Specification
8 segments, 5
Display f requency, warnings, status and
numeric displays so on;
Light FWDREVHZAR/MIN
Indicator
display various status of the inverter;
Frequency setting, output f requency,
Display
feedback value, output current, DC link
voltage, output voltage, output power,
Data read-outs
input terminals state, output terminals
state, analogue input, 1-10 fault records
and accumulated working time etc.;
Remote
Available when the control panel for
mounting kit
external use;
Accessory
Copy parameters f rom one inverter to
Copy card
another ;
Enclosure
IP20;
Ambient
-10-40;
temperature
Humidity
5%-85% (95% without condensation) ;
Environment Vibration test
1.14g;
Max. altitude
1000m, derating use when more than
above sea level
1000 meters;
Motor cable
Shield cable: 5 meters, unshield cable: 50
length
meters;
Attention: Inverter under special environment (derating) :
Derating for ambient temperature: If the f requency converter is
operated over 40 ambient temperature, the continuous output current
should be decreased. The f requency converter has been designed
for operation at max 50 ambient temperation with one motor size
smaller than normal. Continuous operation at f ull load at 50 ambient
temperation will reduce the lifetime of the f requency converter.
Derating for low air pressure: The cooling capability of air is decreased
at low air pressure. Below 1000m altitude no de-rating is necessary but
above 1000m the ambient temperature or the maximum output current
should be decreased. Dcrease the output by 1% per 100m altitude above
1000m or reduce the max. ambient temperature by 1 degree per 200m.
-7-
HLP-C100 Series
13.3
-8-
57.1
89.2
92.6
59.5
HLP-C100 Series
Power(kW)
0.37-1.5
0.75-2.2
74
85
130
140
127
Caution
All cabling must comply with national and local regulations on
cable cross-sections and ambient temperature. Copper conductors
required, and ambient temperature(60-75) recommended.
Details of terminal tightening torques :
Power(KW)and Voltage
Torque(Nm)
levels
DC connection/ Control
120032003380Relay
Line Motor
Brake
terminals
240V
240V
480V
0.37-1.5
0.37-1.5 0.75-2.2 1.4
0.8
0.8
0.15-0.4
0.4
-9-
HLP-C100 Series
HLP-C1000D3721
10
HLP-C1000D7521
25
HLP-C10001D521
32
HLP-C1000D3723
10
HLP-C1000D7523
16
HLP-C10001D523
25
HLP-C1000D7543
10
HLP-C10001D543
10
HLP-C10002D243
16
Note: Install the unit and make sure that it is f ree f rom high moisturehigh
temperatureheavy dustmetal f ragments and high oil mist.
- 10 -
HLP-C100 Series
RST
Function
Power input:
220V class: 1- phase 200-240V50/60Hz
3- phase 200-240V50/60Hz
380V class: 3- phase 380-480V50/60Hz
Single phase connected to RT
UVW
-BR+BR
PE
Ground terminal
- 11 -
HLP-C100 Series
Relay output
(FA-FB-FC)
Description
Digital input
Digital control
(FORREV
terminals
DI1DI2DI3)
GND
+10V
Specification
Digital or
Isolated f rom internal COM;
Analog ground
10V power
supply
RS485
RS485 + and RS485- ;
communication
Ground for
Isolated f rom internal GND;
communication
Note: Only the machine with RS485 (type code number 25 is B) has RS+ RSand COM;
- 12 -
HLP-C100 Series
3.3.5 Wiring
Basic Connection Diagram of HLP-C100 series inverter:
- 13 -
HLP-C100 Series
Screen display
Status indicator
Menu key
Shift key
Hand key
Auto key
Incremental
potentiometer
LCP Display
C00.04
C03.00
C03.00
C03.10
[0]
- 14 -
Action Description
Press
C00.03
Turn
group C03
Press
Turn
C03.10
Press
HLP-C100 Series
Key-press
LCP Display
0000
000.5
000.5
020.5
END
Action Description
Press
f ractional part to 5
Press
Turn
part to 20
Press
as 20.5
Running status
STOP
STOP
FWD
REV
Indicator Display
- 15 -
HLP-C100 Series
Reference
Running status
FWD
REV
Indicator Display
Note: A flash light denotes the status coming, Light on indicates the current
state, and light off means not in this state.
Example 1: The f irst line of the table indicates the drive is stop and the
reference is greater than or equal to 0, means the dirve at some
time in the f uture will run forward.
Example 2: The fourth line of the table represents the current drive is reverse
running, and the reference setting is greater than or equal to 0, it
means the drive at some time in the f uture will run forward.
Key-press
Output
Frequency
Initial
interface
LCP Display
Action Description
Show the output
f requency (C16.13)
is 50.0Hz, display
accuracy: 0.1
Reference
(%)
Motor
Current
Motor
Voltage
- 16 -
HLP-C100 Series
Display
Items
Key-press
LCP Display
Action Description
Motor Speed
DC Voltage
Show the DC
voltage(C16.30) is 540.0V,
display accuracy: 0.1
Inverter
temperature
Feedback
Value
Analog in
VI
Show analog in VI
(C16.62) is 10.00V, display
accuracy: 0.01
Note: Press
LCP Display
C00.04
Action Description
Press
basic C00.03.
- 17 -
HLP-C100 Series
Key-press
LCP Display
C15.00
C15.00
C15.30
[0]
**
Action Description
Press
to select parameter
number.
Turn
Press
of C15.30
Press
record.
Press
[1]
Turn
LCP Display
C00.03
- 18 -
Action Description
Press
parameter C00.03.
HLP-C100 Series
Key-press
LCP Display
C16.00
Action Description
Turn
C16.00
Press
C16.01
Press
select C16.01
Turn
clockwise to finish
C16.60
Press
to select C16.60.
Press
0000
- 19 -
HLP-C100 Series
- 20 -
HLP-C100 Series
2. Parameter initialization;
3. Set parameter as following:
C03.11=10Hz
C03.15=1, C03.16=0
HLP-C100 Series Operating Manual
- 21 -
HLP-C100 Series
C03.41=0.5, C03.42=0.5, C03.80=0.5, C04.10=2
C05.11=11, C05.13=14
C06.10=0, C06.11=10, C06.14=0, C06.15=50
4. Press AUTO key on LCP;
5.5 Multi-speed
1. IO terminals connection as following:
2. Parameter initialization;
3. Set parameter as following:
C03.03=50
C05.10=8 , C05.12=15 (Bit0) , C05.13=16 (Bit1) , C05.13=17 (Bit2)
C03.10[0]=10 (Speed1=5Hz) , C03.10[1]=20 (Speed2=10Hz) ,
C03.10[2]=30 (Speed3=15Hz) , C03.10[3]=40 (Speed4=20Hz) ,
C03.10[4]=50 (Speed5=25Hz) , C03.10[5]=60 (Speed6=30Hz) ,
C03.10[6]=70 (Speed7=35Hz) , C03.10[7]=80 (Speed8=40Hz) ,
4. Press AUTO key on LCP;
- 22 -
HLP-C100 Series
Parameter
No.
Function
Description
Setting range
0: Resume; 1: Forced
Operating State stop reference=old;
C00.04
at Power-up
2: Forced stop
reference=0;
LCP Display
0-2047
C00.33
Option
HAND key on
0:Disabled; 1:Enabled;
C00.40
LCP
0:Disable All; 1:Enable
OFF key on
All; 2:Enable Reset
C00.41
LCP
Only;
AUTO key on
0:Disabled; 1:Enabled;
C00.42
LCP
Menu
0:Disabled; 1:Enabled;
C00.60
Password
0: Speed open loop;
Configuration
1: Speed closed loop;
C01.00
Mode
3: Process closed loop;
Motor Power
Dep.on motor date
*C01.20
[kW] [HP]
Motor Voltage
50~1000
*C01.22
(Um.n)
Motor
*C01.23 Frequency (f m. 20~400
n)
Motor Current
Dep.on motor date
*C01.24
(Im.n)
Motor Nominal
100~9999
*C01.25
Speed (nm.n)
Motor Cable
0~150
*C01.42
Length
U/F
C01.55
0~999
Characteristic-U
U/F
C01.56
0~400
Characteristic-F
C01.71 Start Delay
0.0~10.0
Unit
Default Page
setting No.
1
0
1
1
1
0
0
kW
Hz
rpm
50
V
Hz
s
0.0
- 23 -
HLP-C100 Series
Item
Parameter
No.
C01.72
*C01.73
C01.80
C01.82
C02.00
C02.01
C02.02
C02.04
C02.10
C02.11
C02.17
- 24 -
C03.03
C03.07
C03.10
C03.11
C03.12
Function
Description
Setting range
Unit
0: DC hold/delay
Start Function time; 2: Coast/Delay
time;
Flying start
0:Disabled; 1:Enabled;
Function at
0: Coast; 1: DC Hold;
Stop
Min Speed for
Function at
0.0~20.0
Hz
Stop [Hz]
DC Hold
0~150
%
Current
DC Brake
0~150
%
Current
DC Braking
0.0~60.0
s
Time
DC Brake Cut
0.0~400.0
Hz
In Frequency
0: Off; 1: Resistor
Brake Function
brake; 2: AC brake;
Brake Resistor
Dep.on motor date
(ohm)
Over-voltage
0: Disabled;
Control
2: Enabled;
Maximum
0.000~4999.000
Reference
0: Preset reference +
Actual
Reference source 1,2
reference
1: Preset reference
calculation
priority
Preset
-100.00~100.00
%
Reference
Jog Speed [Hz] 0.0~400.0
Hz
Catch up/slow
Down Value
0.00~100.00
Default Page
setting No.
2
0
0
0.0
50
50
10.0
0.0
0
*
0
50.000
0.00
5.0
0.00
HLP-C100 Series
Item
Parameter
No.
C03.15
C03.16
C03.18
C03.40
C03.41
C03.42
C03.50
C03.51
C03.52
C03.60
C03.61
C03.62
C03.70
C03.71
C03.72
C03.80
C03.84
C03.85
C03.86
Function
Setting range
Description
Reference
Resource 1
0: No f unction;
Reference
1: Analog input VI;
Resource 2
11: Local bus ref;
Relative Scaling 21: LCP
potentiometer;
Reference
Resource
0: Linear; 2: Sine
Ramp 1 Type
ramp;
Ramp 1 Ramp
0.10~300.00
up Time
Ramp 1 Ramp
0.10~300.00
Down Time
0: Linear; 2: Sine
Ramp 2 Type
ramp;
Ramp 2 Ramp
0.10~300.00
up Time
Ramp 2 Ramp
0.10~300.00
down Time
0: Linear; 2: Sine
Ramp 3 Type
ramp;
Ramp 3 Ramp
0.05~3600.00
up Time
Ramp 3 Ramp
0.05~3600.00
down Time
0: Linear; 2: Sine
Ramp 4 Type
ramp;
Ramp 4 Ramp
0.10~300.00
up Time
Ramp 4 Ramp
0.10~300.00
down Time
Jog Ramp Time 0.10~300.00
0: Linear; 2: Sine
Ramp 5 Type
ramp;
Ramp 5 Ramp
0.10~300.00
up Time
Ramp 5 Ramp
0.10~300.00
down Time
Unit
Default Page
setting No.
1
2
0
0
*
0
*
0
*
0
*
0
- 25 -
HLP-C100 Series
Item
Parameter
No.
C03.87
C03.88
C03.89
C03.90
C03.91
C03.92
C03.93
C03.94
C03.95
C03.96
*C04.10
Parameter Group 04: Limits/Warnings
*C04.12
*C04.14
C04.18
*C04.19
C04.52
C04.53
*C04.58
- 26 -
Function
Description
Ramp 6 Type
Setting range
Unit
0: Linear; 2: Sine
ramp;
Ramp 6 Ramp
0.10~300.00
up Time
Ramp 6 Ramp
0.10~300.00
down Time
0: Linear; 2: Sine
Ramp 7 Type
ramp;
Ramp 7 Ramp
0.10~300.00
up Time
Ramp 7 Ramp
0.10~300.00
down Time
0: Linear; 2: Sine
Ramp 8 Type
ramp;
Ramp 8 Ramp
0.10~300.00
up Time
Ramp 8 Ramp
0.10~300.00
down Time
Link preset
reference and 0: No link; 1: Link
ramp time
0: Clockwise;
Motor Speed
1: Counterclockwise;
Direction
2: Both;
Motor Speed
0.0~400.0
Low Limit [Hz]
Motor Speed
0.0~400.0
High Limit [Hz]
Current Limit 0~300
Max. Output
0.0~400.0
Frenquency
Warning Speed
0.0~400.0
Low
Warning Speed
0.1~400.0
High
Missing Motor
0: Off; 1: On;
Phase Function
Default Page
setting No.
0
*
0
*
0
*
0
2
Hz
0.0
Hz
65.0
150
Hz
65.0
Hz
0.0
Hz
65.0
HLP-C100 Series
Item
Parameter
No.
Function
Description
Bypass Speed
C04.61
From [Hz]
Bypass Speed
C04.63
To [HZ]
Terminal FOR
C05.10
Digital Input
Terminal REV
C05.11
Digital Input
Terminal DI1
C05.12
Dgital Input
Terminal DI2
C05.13
Digital Input
C05.14
Terminal DI3
Digital Input
C05.40
Relay
Function(FAFBFB-FC)
C06.10
C06.11
C06.12
Terminal VI
Low Voltage
Terminal VI
High Voltage
Terminal VI
Low Current
Setting range
Unit
Default Page
setting No.
0.0~400.0
Hz
0.0
0.0~400.0
Hz
0.0
0: No operation;
1: Reset; 2: Coast
inverse; 5: DC-brake
inverse; 6: Stop
inverse; 8: Start;
10: Reversing; 11: Start
reversing; 14: Jog;
15: Preset ref bit0;
16: Preset ref bit1;
17: Preset ref bit2;
28: Catch up; 29: Slow
down; 34: Ramp
bit0; 35: Ramp bit1;
36:Ramp bit2;
0: No operation;
5: Drive running;
9: Alarm; 10: Alarm
or Warning; 15: Out
of f requency rang;
16: Below f requency,
low; 17: Above
f requency, high;
21: Thermal warning;
24: Ready, voltage
ok; 25: Reverse;
26: Bus ok; 28: Brake,
no brake warning;
53: No alarm;
55: Running reverse;
8
10
15
16
17
0.00~9.99
0.07
0.10~10.00
10.00
0.00~19.99
mA
0.14
- 27 -
HLP-C100 Series
Item
- 28 -
Parameter
No.
Function
Description
Terminal VI
C06.13
High current
Terminal VI
C06.14 Low Ref./
Feedb.Value
Terminal VI
C06.15 High Ref./
Feedb.Value
Terminal VI
C06.16 Filter Time
Contant
Terminal VI
C06.18
Zero dead band
Terminal VI
C06.19
Mode
LCP Potmeter
C06.81
Low Ref.
LCP Potmeter
C06.82
High Ref.
Process CL
C07.20 Feedback
Resource
Process PI Anti
C07.31
Windup
Process PI
C07.33 Proportional
Gain
Process PI
C07.34
Integral time
Process PI Feed
C07.38
Forward Factor
On Reference
C07.39
Bandwidth
Process PI
C07.41
Output Low
Process PI
C07.42
Output High
Setting range
0.01~20.00
Unit
mA
Default Page
setting No.
20.00
-4999.000~4999.000
0.000
-4999.000~4999.000
50.000
0.01~10.00
0.01
0.00~20.00
V/
mA
0.00
0: Votage mode;
1: Current mode;
-4999.000~4999.000
0.000
-4999.000~4999.000
50.000
0: No Function;
1: Analog in VI;
11:Local bus;
0:Disabled; 1:Enabled;
0.0~10.00
0.01
0.10~9999.00
9999.00
0~400
0~200
-100-100
-100-100
100
HLP-C100 Series
Item
Parameter
No.
C08.01
Function
Description
Control Site
Setting range
Unit
Control Word
0: None; 1: FC RS485;
Source
Control Word
0.1~6500.0
s
C08.03
Timeout Time
0: Off; 1: Freeze
Control Word output; 2: Stop;
C08.04 Timeout
3: Jogging; 4: Max.
Function
speed; 5: Stop and
trip;
Reset Control 0: No Function; 1: Do
C08.06
Word Timeout Reset;
FC(1~126); MODBUS
C08.31 Address
RTU(1~247);
0: 2400; 1: 4800;
C08.32 Port Baud Rate 2: 9600; 3: 19200;
4: 38400;
0: Even Parity,1Stop
bit; 1: Odd Parity,
C08.33 FC Port Parity 1stop bit; 2: No Parity,
1Stop bit; 3: No
Parity,2 Stop bits;
Minimum
0.001~0.500
s
C08.35
Response Delay
Max. Response
0.010~10.000
s
C08.36
Delay
C08.94 Bus Feedback 1 -32768~32767
2~6: 2kHz~6kHz;
Switching
7: 8kHz; 8: 10 kHz;
C14.01
Frequency
9: 12kHz; 10: 16kHz;
Over
0: Off; 1: On;
*C14.03
modulation
Damping Gain
0~200
%
C14.08
Factor
C08.02
Default Page
setting No.
0
1
1.0
0
1
2
0.010
5.000
0
5
1
96
- 29 -
HLP-C100 Series
Item
Parameter
No.
C14.12
- 30 -
Function
Description
Function
at Mains
Imbalance
C14.20
Reset Mode
C14.21
Automatic
Restart Time
C14.22
Operation
Mode
C14.23
Trip Lock
Setting range
Unit
Default Page
setting No.
0: Trip; 1: Warning;
2: Disabled;
0: Manual reset;
1~10: Automatic reset
x 1~10; 11: Automatic
reset x 15;
12: Automatic reset
x 20; 13: Infinite auto
reset;
0~600
0: Normal Operation;
2: Initialisation;
3: Backup user
settings; 4: Recover
user settings;
0: Disable, Trip lock
fault reset do not
need power off
1: enable, Trip lock
fault reset need
power off
DC-Link
*C14.51 Voltage
0: Off; 1: On;
Compensation
C15.00 Operating Days 0~9999
C15.02 KWh Counter 0~65535
C15.03 Power ups
0~2147483647
Reset KWh
0: Do not reset;
C15.06
Counter
1: Reset Counter;
Fault Log: Error
0~255
C15.30
Code
Internal Fault
-32767~32767
C15.31
Reason
C15.40 FC Type
View FC type
View power size of
C15.41 Power Section
the drive
10
0
d
HLP-C100 Series
Item
Parameter
No.
Function
Description
C15.42
Voltage
C15.43
Sof tware
Version
C15.44
Ordered Type
Code
C15.46
Frequency
converter
ordering NO.
C15.47
Power Card
Ordering NO.
C15.48
C15.49
C15.50
C15.51
C15.53
C15.92
LCP ID NO.
Sof tware ID
Control Card
Sof tware ID
Power Card
Frequency
Converter
Serial Number
Power Card
Serial number
Setting range
Unit
Default Page
setting No.
- 31 -
HLP-C100 Series
Item
Parameter
Function
No.
Description
C16.00 Control Word
Reference
C16.01
[Unit]
Motor Speed
C16.05
[RPM]
C16.10 Power[KW]
C16.12 Motor Voltage
C16.13 Frequency
C16.14 Motor Current
DC Link
C16.30
Voltage
C16.34 Heat sink Temp.
Feedback #
C16.52
[Unit]
C16.60 Digital Input
Analog Input
C16.62
VI
Relay Output
C16.71
[bin]
C16.86 FC Port REF
C16.90 Alarm Word
C16.91 Alarm Word 2
C16.92 Warning Word
Warning Word
C16.93
2
Setting range
Unit
Default Page
setting No.
0~65535
-4999.000~4999.000
0~9999
Hz
0.000~1000.000
0.0~65535
0.0~400.0
0.00~655.35
kW
V
Hz
A
0~65535
0~255
-4999.000~4999.000
0~65535
0.000-20.000
V/
mA
0~65535
-32768~32767
0~0xFFFFFFFFUL
0~0xFFFFFFFFUL
0~0x7FFFFFFFUL
0~0x7FFFFFFFUL
Note: Reference signed with *in parameter No. column means this parameter
cant be modified when the motor is running. In factory setting column,
* means the default setting for this parameter is determined by the
drive type.
- 32 -
HLP-C100 Series
Function Description
Range
Operaton State at
Power-up(Hand)
Unit
Default Setting
0~2
Option: [0] Resume, local reference is stored and used af ter power up;
[1] Forced stop, ref =old, local reference is stored and used af ter power
up;
[2] Forced stop, ref =0, local reference is set to 0;
Function: This parameter is used to control whether or not the f requency
converter should automatic running the motor when powering up
af ter a power down in Hand mode.
Description of choice: When select [0], f requency converter starts in
same Hand mode roof state as when powered of f; When select[1],
f requency converter powers up in of f state meaning that motor is
stopped af ter power up; When select[2], f requency converter powers
up in off state meaning that motor is stopped af ter power up. Local
reference is set to 0. Thus motor will not start running before local
reference has been increased.
C00.3* LCP Readout
C00.33
Function Description
Range
0~2047
Unit
Default Setting
0
Description of the choice: LCP will be fixed to display the output f requency
reference and motor current. This parameter is used to show 11 basic
operating states of the inverter, each parameter corresponds to a binary
code: 1 means display the item, 0 means does not display the item.
For example, if you want to display the states of the temperature and
the terminal VI on LCP. Transform the binary code to decimal digit,
C00.33=123+124=24.
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
VI Input
Temperature
DC-voltage
Motor Speed
Motor Voltage
- 33 -
HLP-C100 Series
C00.4* LCP Keypad
C00.40
Function Description
Range
0~1
Unit
Default Setting
1
Function Description
OFF Key on LCP
Range
Unit
0~2
Default Setting
1
Function Description
AUTO Key on LCP
Range
Unit
0~1
Default Setting
1
Function Description
Menu Password
Range
Unit
Default Setting
0~1
- 34 -
HLP-C100 Series
Range
Unit
0~3
Default Setting
0
Range
KW
Function: Select the KW value that corresponds to the rated power of the
motor.
Description of choice: Factory settings depend on the inverter size, there is one
or two undersize or one oversize in comparison with factory setting.
Attention: Changing the value of this parameter af fects the setting of
C01.22-C01.25.
*C01.22 Function Description
Motor Voltage
Range
Unit
Default Setting
50~1000
Function: Select a value that equals the nameplate data on the motor.
Description of choice: Default setting depends on the inverter size.
*C01.23 Function Description
Motor Frequency
Range
Unit
Default Setting
20~400
Hz
Function: Enter the rated motor f requency f rom the nameplate data.
Description of the choice: Default setting depends on the inverter size.
Attention: Changing this parameter affects motor nominal speed set in C01.25.
- 35 -
HLP-C100 Series
*C01.24 Function Description
Motor Current
Range
Range
Unit
Default Setting
100~9999
RPM
Function: Enter the motor nominal speed value f rom the nameplate data.
Description of the choice: Factory setting depends on the unit size.
Attention: If motor f requency has been changed in C01.23, Nominal Motor
Speed will be affected.
C01.4* Motor Cable Length
*C01.42 Function Description
Motor Cable Length
Range
Unit
Default Setting
0~150
Function: Enter the motor cable length connected between the motor and the
f requency converter.
Description of the choice: Set correct cable length can suppress noises resulted
f rom the motor.
C01.5* Load Indep.Setting
C01.55
Function Description
Range
Unit
Default Setting
V/F Characteristic-V
0~999.9
0/Vn
Function: This parameter is an array parameter [0-5], used for setting voltage
[V0-V5] at each f requency point to manually form a V/F characteristic
matching motor. Frequency points are def ined in par. C01.56, V/F
characteristics - F.
Description of choice: This parameter is only f unctional when par. C01.01, Motor
Control Principle is set to V/F [0].
Attention: V0 factory setting is set to 0V, and U1-U5 factory setting is set to
Un (motor rated voltage).
C01.56
Function Description
Range
Unit
Default Setting
V/F Characteristic-F
0~400
Hz
0/Fn
- 36 -
HLP-C100 Series
Characteristic - V.
Description of choice: This parameter is only f unctional when par. C01.01 Motor
Control Principle is set to V/F [0].
Attention: F0 factory setting is set to 0Hz, and F1-F5 factory setting is set to Fn
(Motor rated f requency); for par. C01.56 the following applies F0=0 and
F1F2F3F4F5.
Function Description
Start Delay
Range
Unit
Default Setting
0.0~10.0
0.0
Function: This parameter enables a delay of the starting time. The f requency
converter begins with the start f unction selected in par. 1-72. Set the
start delay time until acceleration is to begin.
Attention: Setting start delay to 0.0 sec. disables Start Function, [C01.72], when
start command is given.
C01.72
Function Description
Start Function
Range
Unit
0~2
Default Setting
2
- 37 -
HLP-C100 Series
during start delay time; Select [2], Motor is coasted during start delay
time (inverter off ).
*C01.73 Function Description
Range
Flying Start
0~1
Unit
Default Setting
0
Function Description
Function at Stop
Range
Unit
0~1
Default Setting
0
- 38 -
HLP-C100 Series
Description of Choice: This f unction is active in the following situations: Stop
command is given and output speed is ramped down to Min. Speed for
activating Functions at Stop; Start command is removed (standby), and
output speed is ramped down to Min. Speed for activating Functions
at Stop; DC-brake command is given, and lasts out of DC-brake delay
time.
C01.82
Function Description
Min Speed for Function
at Stop [Hz]
Range
Unit
Default Setting
0.0~400.0
Hz
0.0
Function: Set the output f requency at which to activate par. C01.80 Function at
stop.
Function Description
Range
Unit
Default Setting
DC Hold Current
0~150
50
Function: This parameter either holds the motor (holding torque) or preheats
the motor. This parameter is active if DC Hold has been selected in
either C01.72 start f unction or C01.80 Function at Stop.
Description of Choice: Enter a value for holding current as a percentage of the
rated motor current set in par. C01.24 Motor Current. 100% DC holding
current corresponds to IM,N.
Attention: Avoid 100% current too long as it may overheat the motor.
C02.01
Function Description
Range
Unit
Default Setting
DC Brake Current
0~150
50
Function: This parameter is used for setting the DC brake currents that is set as
a percentage value of the rated motor current IM, N set in C01.24.
Description of Choice: Parameters related to the DC brake current are as
follows:
DC-brake command, see C05.1* choice (5) ;
DC brake cut in speed, see C02.04;
C02.02
Function Description
DC Braking Time
Range
Unit
Default Setting
0.0~60.0
10.0
Function: This parameter defines DC brake current (C02.01) time during which
HLP-C100 Series Operating Manual
- 39 -
HLP-C100 Series
DC-brake current is applied to the motor.
C02.04
Function Description
DC Brake Cut in Speed
Range
Unit
Default Setting
0.0~400.0
Hz
0.0
Function: This parameter is for setting the DC brake cut in speed at which the
DC braking current (par.02.01) is to be actived, in connection with a
stop command. When set to 0 the f unction is off.
C02.1* Brake Energy Funct.
C02.10
Function Description
Brake Function
Range
Unit
0~2
Default Setting
0
Function Description
Range
Unit
Default Setting
5~65535
Function Description
Range
Unit
Default Setting
Over-voltage Control
0~2
- 40 -
HLP-C100 Series
Function Description
Range
50.000
Function Description
Range
0~1
Range
-100.00~100.00[8]
0.00
- 41 -
HLP-C100 Series
Binary system
Terminals State
C03.11
bit2
bit1
bit0
Preset Reference
Function Description
Jog Speed
Range
Unit
Default Setting
0.0~400.0
Hz
5.0
Function: Jog f requency is a f ixed f requency that the drive supplies to the
motor af ter the jog f unction is actived. Please refer to C05.1*, select [14].
Description of Choice: The f requency converter with the highest priority
will operate at jog speed when a variety of run command activates.
Removing the jog signal makes the f requency converter run according
to the selected configuration, this parameter is set limited by C04.14.
C03.12
Function Description
Range
0.00
- 42 -
HLP-C100 Series
C03.14
Function Description
Preset Relative
Reference
Range
Unit
Default Setting
-100.00~100.00
0.00
C03.16
Function Description
Range
Reference Resource1
0~21
Function Description
Range
Reference Resource2
0~21
Unit
Default Setting
1
Unit
Default Setting
2
- 43 -
HLP-C100 Series
C03.18
Function Description
Range
0~21
Unit
Default Setting
0
Relative Scaling
Reference VI/
C03.18=1
Max Reference/
C03.03
Output
Frequency(Hz)
20%
10V
50
10+10=20
20%
8V
50
10+8=18
20%
5V
50
10+5=15
20%
3V
50
10+3=13
20%
0V
50
10+0=10
C03.19
Function Description
Range
Unit
0~2
Default Setting
0
Range
Ramp 1 Type
0~2
- 44 -
HLP-C100 Series
Option: [0] Linear: Motor ramp up to the preset f requency with constant
acceleration.
[2] S ramp: Motor ramp to the preset f requency with non-linear
acceleration.
Description of Choice: If Linear [1] is selected, the f requency may exceed the
preset setting during the acceleration; If S ramp [2] is selected, due
to smoother S curve, it will automatically adjust acceleration when
approaching to the preset f requency to avoid exceeding it.
Terminal State
bit2
0
0
0
0
1
1
1
1
bit1
0
0
1
1
0
0
1
1
bit0
0
1
0
1
0
1
0
1
Ramp Group
1
2
3
4
5
6
7
8
- 45 -
HLP-C100 Series
C03.41
Function Description
Range
Unit
Default Setting
Ramp1Ramp up Time
0.10~300.00
Function: Enter the ramp-up time f rom 0 Hz to rated Motor speed in C01.25.
Attention: Choose a rame-up time such that the output current does not exceed
the current limit in C04.18.
C03.42
Function Description
Range
Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
C03.5* Ramp2
C03.50 Function Description
Range
Ramp2 Type
0~2
Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration.
- 46 -
HLP-C100 Series
C03.51
Function Description
Range
0.10~300.00
Function: Enter the ramp-up time f rom 0Hz to rated Motor speed in C01.25.
Attention: Choose a ramp-up time such that the output current does not exceed
the current limit set in C04.18.
C03.52
Function Description
Range
Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
C03.6* Ramp3
C03.60
Function Description
Ramp3 Type
Range
Unit
Default Setting
0~2
Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration.
C03.61
Function Description
Range
Unit
Default Setting
0.10~300.00
Function: Enter the acceleration time f rom 0Hz to rated Motor speed in C01.25.
Attention: Choose a ramp-up time such that the output current does not exceed
the current limit set in C04.18.
C03.62
Function Description
Range
Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
- 47 -
HLP-C100 Series
C03.7* Ramp4
C03.70
Function Description
Ramp4 Type
Range
Unit
Default Setting
0~2
Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration.
C03.71
Function Description
Range
0.10~300.00
Function: Enter acceleration time f rom 0Hz to rated Motor speed in C01.25.
Attention: Choose a ramp-up time such that the output current does not exceed
the current limit set in C04.18.
C03.72
Function Description
Range
Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
C03.8* Other Ramps
C03.80
Function Description
Jog Ramp Time
Range
Unit
Default Setting
0.10~300.00
Function: Enter the time required motor speed f rom 0Hz up to rated motor
speed (C01.25) or f rom the rated motor speed (C01.25) down to 0Hz.
Description of Choice: Jog ramp time starts upon activation of a jog signal via
a selected digital input or serial communication port. See C05.1, choose
[14].
C03.84
Function Description
Ramp5 Type
Range
Unit
0~2
Default Setting
0
Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration.
- 48 -
HLP-C100 Series
C03.85
Function Description
Range
Unit
Default Setting
Function: Enter acceleration time f rom 0Hz to rated Motor speed in C01.25.
Attention: Choose a ramp-up time such that the output current does not exceed
the current limit set in C04.18.
C03.86
Function Description
Range
Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
selected digital input or serial communication port. See C05.1, choose [14].
C03.87
Function Description
Ramp6 Type
Range
0~2
Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration.
C03.88
Function Description
Range
Unit
Default Setting
0.10~300.00
Function: Enter acceleration time f rom 0Hz to rated Motor speed in C01.25.
Attention: Choose a ramp-up time such that the output current does not exceed
the current limit set in C04.18.
C03.89
Function Description
Range
Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
selected digital input or serial communication port. See C05.1, choose [14].
- 49 -
HLP-C100 Series
C03.90
Function Description
Ramp7 Type
Range
Unit
Default Setting
0~2
Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration.
C03.91
Function Description
Range
Unit
Default Setting
Function: Enter acceleration time f rom 0Hz to rated Motor speed in C01.25.
Attention: Choose a ramp-up time such that the output current does not exceed
the current limit set in C04.18.
C03.92
Function Description
Range
Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
selected digital input or serial communication port. See C05.1, choose [14].
C03.93
Function Description
Ramp8 Type
Range
0~2
Option: [0] Linear: Motor ramp up to the preset f requency with a constant
acceleration;
[2] S-ramp: Motor ramp to the preset f requency with non-linear
acceleration.
C03.94
Function Description
Range
0.10~300.00
Function: Enter acceleration time f rom 0Hz to rated Motor speed in C01.25.
Attention: Choose a ramp-up time such that the output current does not exceed
the current limit set in C04.18.
- 50 -
HLP-C100 Series
C03.95
Function Description
Range
Function: Enter the deceleration time f rom the rated motor speed in C01.25 to
0Hz.
Attention: Choose a ramp-down time such that no over-voltage arises in the
inverter due to regenerative operation of motor and such that the
generated current does not exceed the current limit set in C04.18.
C03.96
Function Description
Range
Range
Unit
0~2
Default Setting
2
Option: [0] Clockwise, the motor shaf t rotates in clockwise direction; this setting
prevents the motor f rom running in counter clockwise direction.
[1] Counter clockwise, motor shaf t rotates in counter clockwise
direction, this setting prevents the motor f rom running in clockwise
direction.
[2] Both Directions, with this setting, the motor can run in both
directions.
*C04.12 Function Description
Motor Speed Low Limit
Range
Unit
Default Setting
0.0~400.0
Hz
0.0
Function: Set the minimum limit for Motor Speed, the motor speed low limit
can be set to correspond to the minimum output f requency of the
motor shaf t . The motor speed low limit must not exceed the Motor
Speed High Limit in C04.14.
- 51 -
HLP-C100 Series
*C04.14 Function Description
Motor Speed High Limit
Range
Unit
Default Setting
0.0~400.0
Hz
65.0
Function: Enter the maximum limit for Motor Speed , the motor speed high
limit can be set to correspond to the maximum manufactures rated
motor speed. The motor speed high limit must exceed the Motor Speed
Low Limit in C04.19.
C04.18
Function Description
Range
Unit
Default Setting
Current Limit
0~300
150
Range
Unit
Default Setting
0.0~400.0
Hz
65
Function Description
Range
Unit
Default Setting
0.0~400.0
Hz
0.0
Function: Enter the nlow value, when the motor speed falls below this limit, the
display reads Speed Low.
Attention: This setting must be within normal motor f requency range,
otherwise, it may trigger an error warning.
C04.53
Function Description
Range
Unit
Default Setting
0.1~400.0
Hz
65.0
Function: Enter the n high value, when the motor speed exceeds this limit, the
display reads Speed High.
Attention: This setting must be within normal motor f requency range,
otherwise, it may trigger an error warning.
- 52 -
HLP-C100 Series
*C04.58 Function Description
Missing Motor Phase
Function
Range
Unit
0~1
Default Setting
1
Function Description
Range
Unit
Default Setting
0.0~400.0
Hz
0.0
Array: [3]
Function: This parameter is a dyadic Array, [0] is used to set the bypass speed
f rom of bypass speed range 1, [1] is used to set the bypass speed f rom of
bypass speed range 2,and [2] is used to set that of bypass speed range3.
Description of Choice: Some systems call for avoiding some certain output
speed due to resonance problems in system. The drive will pass quickly
when it approaching to the Bypass Speed area.
C04.63
Function Description
Bypass Speed to
Range
Unit
Default Setting
0.0~400.0
Hz
0.0
Array: [3];
Function: This parameter is a dyadic array, [0] is used to set the bypass speed to
of bypass speed range 1, [1] is used to set the bypass speed to of bypass
speed range 2,and [2] is set as that of bypass speed range3.
HLP-C100 Series Operating Manual
- 53 -
HLP-C100 Series
C05.11
C05.12
C05.13
C05.14
Function Description
Range
0~36
Function Description
Range
0~36
Function Description
Range
0~36
Function Description
Range
0~36
Function Description
Range
0~36
Unit
Default Setting
8
Unit
Default Setting
10
Unit
Default Setting
15
Unit
Default Setting
16
Unit
Default Setting
17
Option: [0] No operation, the f requency converter will not to react to signals
transmitted to the terminal;
[1] Reset, reset the f requency converter af ter a Trip/Alarm;
[2] Coast Inverse, no output, leaving the motor coasting to stop;
[5] DC-brake Inverse, see C02.01, this f unction is only active when value
in C02.02 and C02.04 are different f rom 0.
[6] Stop Inverse, the drive is stopped according to selected ramp time;
[8] Start, 1=start, 0=stop;
[10] Reversing, change direction of motor shaf t rotation, reversing
signal only changes direction of rotation, it does not activate start
f unction, C04.10 must choose [2] Both directions;
[11] Start reversing, used for start/stop and for reversing at the same
time;
[14] Jog, used for activating jog speed, see C03.11;
[15] Preset ref. bit0, Preset ref.bit0bit1bit2bit3 is used for the choice
of the preset reference, see parC03.10;
[16] Preset ref. bit1, same as[15];
[17] Preset ref. bit2, same as [15];
[28] Catch up, select catch up to increase the resulting reference value
by the percentage set in par. C03.12;
[29] Slow down, select slow down to reduce the resulting reference
- 54 -
HLP-C100 Series
value by the percentage set in par. C03.12;
[34] Ramp bit0bit0bit1bit2 used f or select acceleration or
deceleration;
[35] Ramp bit1, same as [34] ;
[36] Ramp bit2, same as [34] ;
C05.4* Relay
C05.40
Function Description
Range
Relay Function
0~55
Unit
Default Setting
5
Function Description
Terminal VI Low Voltage
Range
0.00~9.99
0.07
- 55 -
HLP-C100 Series
C06.11
Function Description
Range
10.00
Function Description
Range
mA
Function Description
Range
20.00
Range
-4999.000~4999.000
0.000
Function Description
Terminal VI High
Ref. /Feedb.
Range
-4999.000~4999.000
50.000
- 56 -
HLP-C100 Series
C06.16
Function Description
Range
0.01
Function: Enter the time constant, this is a first-order digital low pass filter time
constant for suppressing electrical noise in analog input VI. A high
time constant value improves dampening but also increases the time
delay through the f ilter. This parameter cant be adjusted while the
motor is running.
C06.18
Function Description
Range
0.00
Description of Choice: Point A as shown in the figure is the analog value that
corresponds to a setpoint that equals 0. It is calculated via analog low
high values and lowhigh references. UAB=UAC=C06.18/2
C06.19
Function Description
Terminal VI Mode
Range
Unit
0~1
Default Setting
0
- 57 -
HLP-C100 Series
C06.81 Function Description
LCP Potmeter Low
Ref.
Range
-4999.000~4999.000
0.000
Range
-4999.000~4999.000
50.000
Function Description
Process CL Feedback 1
Range
0~11
Function Description
Process PI Anti Windup
Range
Unit
0~1
Default Setting
1
Option: [0] Disable, continue regulation of a given error even when the output
f requency cant be increased/decreased.
[1] Enable, ceases regulation of a given er ror when the out put
f requency cant be increased/decreased.
Function: This f unction ensures the output f requency reaches to f requency
limit. PI-controller will be initialized to the current f requency when
the output f requency can not be changed. This can prevent the
integrator continue to integrate on an error when the PI-controller
cant adjust output f requency.
- 58 -
HLP-C100 Series
C07.33
Function Description
Process PI Proportional
Gain
Range
Unit
0.0~10.00
Default Setting
0.01
Function: The proportional Gain indicates the number of times the error
between the set point and the feedback signal is to be applied. Quick
control is obtained by a high gain, but if the gain is too high, the
process may become unstable.
Attention: This f unction is disabled when it is set to 0.
C07.34
Function Description
Range
9999.00
Function: The integral time is the time needed by the integrator to reach the
same gain as the porortional gain. Quick control is obtained at a short
integral time, however, this time may become too short, which can
make the process unstable.
C07.38
Function Description
Range
Unit
Default Setting
0~400
Function Description
Range
Unit
Default Setting
0~200
Function Description
Process PI Output Low
Range
Unit
Default Setting
-100-100
Function Description
Process PI Output High
Range
Unit
Default Setting
-100-100
100
- 59 -
HLP-C100 Series
Function Description
Control mode
Range
Unit
Default Setting
0~2
Option: [0] Digital and control word , use both digital input and control word as
control;
[1] Digital only, use digital input as control;
[2] Control word only, use control word only as control;
C08.02
Function Description
Range
0~1
Unit
Default Setting
1
Function Description
Control Word Time
Out Time
Range
Unit
Default Setting
0.1~6500.0
1.0
Function Description
Contol Word Time Out Time
Range
Unit
0~5
Default Setting
0
- 60 -
HLP-C100 Series
C08.06
Function Description
0~1
Function Description
Range
Address
0~247
Unit
Default Setting
1
Function Description
Port Baud Rate
Range
Unit
Default Setting
0~9
bit/s
Range
Unit
Default Setting
Function Description
Port Parity
0~3
C08.35
Function Description
Range
Unit
Default Setting
0.001~0.50
0.010
Function: Def ine the minmum delay time f rom receiving a request to
transmitting the respond out.
- 61 -
HLP-C100 Series
C08.36
Function Description
Range
Unit
Default Setting
0.010~10.000
5.000
Range
Unit
-32768~32767
Default Setting
0
Function Description
Range
Switching Frequency
0~10
Unit
Default Setting
5
Range
Unit
0~1
Default Setting
1
Option: [0] Off, Disable the overmodulation f unction to avoid torque ripple on
the motor shaf t;
[1] On, Connects the overmodulation f unction to obtain an output
voltage up to 15% greater than mains voltage;
Function: This feature allows more accurate speed control near and over
- 62 -
HLP-C100 Series
normal speed (50/60HZ). Another advantage with overmodulation
is the ability of staying at a constant speed even though mains fault
occurs.
C14.08
Function Description
Range
Unit
Default Setting
0~200
96
Function: Damping gain factor can help to improve the response speed of the
DC link of the f requency converter making the DC loop signal more
smooth.
C14.1* Mains On/Off
C14.12
Function Description
0~2
Function Description
Range
Reset Mode
0~13
Unit
Default Setting
0
Option: [0] Manual reset, perform reset via [reset]-button or digital inputs;
[1] - [10] Auto reset 1-10, can perform 1-10 automatic resets af ter trips;
[11] Auto reset11, can perform 15 automatic resets af ter trips;
[12] Auto reset12, can perform 20 automatic resets af ter trips;
[13] Infinite auto reset, can perform an infinite number of automatic
resets af ter tripping;
Function: Select reset f unction af ter tripping. Once auto reset is selected, the
f requency converter will be restarted af ter an alarm. If reset have
been done and the running signal is active, f requency converter will
restart automatically.
Attention: If the auto reset mode is selected, the f requency converter may
possibly restart automatically af ter the alarm disappear.
- 63 -
HLP-C100 Series
C14.21
Function Description
Range
Unit
Default Setting
0~600
10
Function: Enter time interval f rom trip to start of automatic reset f unction
af ter a warning/alarm.
Description of Choice: This parameter is active when C14.20, Auto Reset, is set
to Automatic reset [1]-[13].
C14.22
Function Description
Operation Mode
Range
Unit
Default Setting
0~4
Function Description
Trip lock
Range
Unit
Default Setting
0~1
Option: [0] Disable, Trip lock fault reset do not need power off
[1] Enable, Trip lock fault reset need power off
C14.5* DC Voltage Compensation
*C14.51 Function Description
DC-LinkVoltage
Compensation
Range
Unit
0~1
Default Setting
0
- 64 -
HLP-C100 Series
Function Description
Range
Unit
Operating Days
0~9999
Default Setting
Function: View how many days the drive has r un. The value is saved
automatically at power off and cant be reset.
C15.02
Function Description
KWh Counter(kW)
Range
Unit
0~65535
KW
Default Setting
Function: View the power consumption f rom mains in Kwh as a mean value
over one hour. Reset the counter in C15.06.
C15.03
Function Description
Power Ups
Range
Unit
0~2147483647
KW
Default Setting
Function: View the number of times the drive has been powered up. This
parameter cant be reset.
C15.06
Function Description
Reset Kwh Counter
Range
Unit
Default Setting
0~1
Function Description
Range
0~255
Unit
Default Setting
Function: View the error code, and look up its meaning in chapter 10. This
parameter group contains a fault log showing reasons for the ten latest
trips.
C15.31
Function Description
Range
Unit
Default Setting
- 65 -
HLP-C100 Series
C15.4*C15.5*Drive Identification
This parameter contains read only information about the hardware and
sof tware configuration of the f requency converter.
C15.40
Function Description
Range
Unit
Default Setting
Range
Unit
Default Setting
FC Type
Description of Choice: View FC Type.
C15.41
Function Description
Power Section
Function Description
Range
Unit
Default Setting
Voltage
Description of Choice: View the voltage level corresponding to different type
of drives.
C15.43
Function Description
Range
Unit
Default Setting
Software version
Description of Choice: View the sof tware version of the drive.
C15.44
Function Description
Range
Unit
Default Setting
Function Description
Range
Unit
Default Setting
FC ordering No.
Description of Choice: View ordering number of the FC.
C15.47
Function Description
Range
Unit
Default Setting
- 66 -
HLP-C100 Series
C15.49
Function Description
Range
Unit
Default Setting
Function Description
Range
Unit
Default Setting
Function Description
Range
Unit
Default Setting
FC Serial Number
Description of Choice: View the drives serial number.
C15.53
Function Description
Range
Unit
Default Setting
Function Description
Range
Parameter List
0~255
Unit
Default Setting
Function Description
Reference
Range
-4999.000~4999.000
Function: View the total remote reference, the total reference is sum of pulse,
analog, preset, LCP Potmeter, local bus and f reeze reference.
C16.05
Function Description
Range
0~9999
Hz
- 67 -
HLP-C100 Series
C16.1* Motor Status
C16.10
Function Description
Power(kW)
Range
0.000~1000.000
kW
Function Description
Range
Motor Voltage
0~65535
Function Description
Range
Frequency
0.0~400.0
Hz
Function Description
Motor Current
Range
Unit
0.00~655.35
Default Setting
Function Description
Range
Unit
0~65535
Function Description
Range
Unit
Inverter Temp.
0~255
DC Link Voltage
Default Setting
Default Setting
Function Description
Feedback
Range
-4999.000~4999.000
- 68 -
HLP-C100 Series
C16.6*C16.7* Inputs and Outputs
C16.60
Function Description
Digital Input
Range
Unit
Default Setting
0~65535
Function: View signal states f rom active digital inputs, which indicates in a 16bit binary code. If the drive detects digital input terminals connected,
the corresponding position is set to 1, otherwise 0. Digital input
terminal and the corresponding relationship between the binary code
are as below:
Binary Term. No. Binary Term. No. Binary Term. No. Binary Term. No.
bit0
FOR
bit4
DI3
bit8 Reserved bit12 Reserved
bit1
REV
bit5 Reserved bit9 Reserved bit13 Reserved
bit2
DI1
bit6 Reserved bit10 Reserved bit14 Reserved
bit3
DI2
bit7 Reserved bit11 Reserved bit15 Reserved
C16.62
Function Description
Analog Input VI
Range
Unit
0.00~20.00
V/mA
Default Setting
Function: View actual input voltage or current value on analog input VI.
C16.71
Function Description
Relay Output
Range
Unit
Default Setting
0~65535
Function: View the output status of the relay, the corresponding bit is set to
1when the relay output is active, otherwise it will be set to 0.
Binary
Item. No.
bit0
Relay 1
Function Description
FC Port Reference
Range
Unit
Default Setting
-32768~32767
Function Description
Alarm Word
Range
0~0xFFFFFFFFUL
Function: View the alarm word sent via the serial communication port in hex
HLP-C100 Series Operating Manual
- 69 -
HLP-C100 Series
code. Convert this parameter to a 32-bit binary code, def inition of
the bits in alarm word showed in the table below, among which that
reserved by manufacturers are undefined bits:
Binary
Alarm Word/
C16.90
Brake detect
2
3
Undefined
Undefined
Undefined
Undefined
Earth Fault
Trip
Earth Fault
Undefined
Undefined
Option part
Undefined
Undefined
Control Card
Temp
Undefined
Control Card
Temp
Undefined
Over Current
Undefined
Over Current
Undefined
Torque Limit
Undefined
Undefined
Undefined
Undefined
Undefined
Undefined
Undefined
Undefined
Damaged part
Undefined
Damaged part
Inverter
Overload
Undefined
Inverter
Overload
Undefined
10
DC Under Volt
Undefined
DC Under Volt
Undefined
11
DC Over Volt
Undefined
DC Over Volt
Undefined
Short Circuit
External
Interlock
Undefined
Undefined
12
13
Undefined
Undefined
Undefined
Undefined
14
Undefined
Undefined
15
Undefined
Undefined
No motor
Undefined
16
Undefined
Undefined
17
Internal Fault
Undefined
Undefined
Undefined
18
Brake overload
Fan Fault
Brake overload
Fan Fault
19
U phase loss
Undefined
Undefined
Undefined
20
V phase loss
Undefined
Undefined
Undefined
21
W phase loss
Undefined
Undefined
Undefined
22
Undefined
Undefined
Undefined
Undefined
- 70 -
HLP-C100 Series
Binary
Alarm Word/
C16.90
23
Control Voltage
Fault
Undefined
Undefined
24
Undefined
Undefined
Undefined
Undefined
25
Undefined
Undefined
Current Limit
Undefined
26
Brake resistor
error
Undefined
Undefined
Undefined
27
Brake transistor
fault
Undefined
Undefined
Undefined
28
Bake transistor
open circuit
Undefined
Undefined
Undefined
29
Undefined
Feedback error
30
Undefined
Undefined
Undefined
Undefined
31
Mech. Brake
low
Undefined
Undefined
Undefined
C16.91
Function Description
Alarm Word 2
Range
0~0xFFFFFFFFUF
Function: View the Alarm Word sent via serial communication port in hex
code.
C16.92
Function Description
Warning Word 1
Range
0~0x7FFFFFFFUF
Function: View the Warning Word 1 sent via serial communication port in hex
code.
C16.93
Function Description
Warning Word 2
Range
0~0x7FFFFFFFUF
Function: View Warning Word 2 sent via serial communication port in hex
code.
- 71 -
HLP-C100 Series
KW
310
0.25
145
0.065
65
0.25
310
0.25
145
0.065
65
0.25
620
0.065
310
0.25
210
0.285
Suitable
Motor(KW)
0.37
0.75
1.5
0.37
0.75
1.5
0.75
1.5
2.2
Note: An external braking unit is needed when connecting braking resistor for
the FC which power is less than 220V/380V 0.75kW(included) .
- 72 -
HLP-C100 Series
This cradle is suitable for 1.0-2.0mm
t h ick ness shee t
metal parts
Press and hold
the snap roots when
installation, using
buckle deformation
Step1: Open a hole in line with the size of the install sheet metal.
control panel in the position need to install Step2: Install the LCP according to
the LCP, hole size, as shown:
the direction of the arrow.
Recommended
to install vertical
mounting position
arrow, press with
uniform force.
Chapter 9 EMC
9.1 EMCCorrect Installation
HLP-B serials drive implement the latest international standards,
following these guidelines is advised, IEC/EN61800-3:2004 (Adjustable speed
electrical power drive systems part 3: EMC requirements and specif ic test
methods). In order to achieve the using requirements of the EMC, must meet
the following specifications:
Using shield motor cables, and connect it to the decoupling device
(optional) and the metal motor cabinet;
To reduce the noise and the leakage current, use the motor cable as short
as possible;
The entire system need to have a good earthling;
RFI Switch screw must be tightened up.
- 73 -
HLP-C100 Series
A.03
E.03
A.04
E.04*
A.07
E.07
A.08
E.08
A.09
E.09
A.10
E.10
A.13
E.13*
- 74 -
Reason analysis
Motor cable connection
problems
Missing phase on supply side
or too high voltage imbalance.
Mains Phase The allowed power imbalance
Loss
of HLP-C100 series inverter is
3% of the rated voltage.(IEC
Standard)
Intermediate circuit voltage
Over Voltage
exceeds limit.
Intermediate circuit voltage
Under Voltage drops below voltage warning
low limit.
Inverter
More than 100% overload for
Overload
too long time.
Motor ETR Over Motor temperature calculated
Temperature by ETR exceeds upper limit
Inverter peak current limit is
Over Current
exceeded.
Motor Loss
HLP-C100 Series
Warning
A.14
Earth fault
E.16*
Short Circuit
A.17
E.17
Control Word
Timeout
A.24
E.24
Fan Fault
E.25*
Brake resistor
short-circuit
E.27
Brake transisitor
short-circuit
E.28
Brake Detect
E.30*
E.31*
E.32*
E.38*
A.59
A.61
Motor phase U
missing
Motor phase V
missing
Motor phase W
missing
Internal Fault
Current Limit
E.61
A.66
A.69
E.69*
A.79
E.79
E.80
Reason analysis
Discharge f rom output phases
to ground(22KW and below)
Short circuit in motor or on
motor terminals.
Drive communication timeout,
this alarm occurs when C08.04
is set to 0 or 5.
Too much dust on the fan or
the fan is aging.
Brake resistor is short circuit,
leading the brake f unction
invalid.
Brake transistor is short circuit
leading brake f unction invalid.
Brake resistor is not connected
or working.
Motor phase U is missing,
check the phase.
Motor phase V is missing,
check the phase.
Motor phase W is
missing,check the phase.
Contact the local distributor or
Holip Company.
Current exceeds value set in
C04.18.
Feedback signal is out of range.
Feedback Error
Heat sink low
Temperature may be damaged.
temperature
Power Card Power card is over
Temp.
temperature.
Contact local distributor or
Undefined fault
Holip Company.
Parameter
Make parameter initialized.
Initialization
LCP Connection
No communication between
Er.84 with the inverter
LCP and the inverter.
failed
Button is
Refer to parameter group
Er.85
disabled
C04*
- 75 -
HLP-C100 Series
Warning
Process Method
- 76 -
HLP-C100 Series
Fault
Process Method
5. Motor cant
rotate and
screen display
is normal
without fault
message
- 77 -
HLP-C100 Series
Chapter 11 Maintenance
11.1 Note
Conf irm the main circuit power supply has been turned off, and the
display has disappeared before carry out inspection and maintenance. Make
sure the system is in dynamic state, please pay attention to the following:
Check whether the power supply voltage matches to the rated voltage
of the inverter;
Check whether the motor makes unexpected noises or abnormal
vibration when running;
Check whether there are abnormal heating;
Check whether the inverter output voltage, output current, output
f requency, and monitor display is greater than the value commonly
used.
Check whether the cooling fan installed at the lower part of the inverter
runs normally;
Check whether the ambient temperature is too high and whether there
is dust, iron filings, corrosive fluid in the inverter;
Check whether the ambient temperature of the inverter is between
-10~40, and whether the humidity is between 5%-85% (95% is
without condensation), phenomenon of water droplets is not allowed;
The inverter should be discarded as industrial waste. It is forbidden to
burn it;
- 78 -
HLP-C100 Series
Function code
8 bits
Data
N*8 bits
CRC
16 bits
1) Address: 1-247
2) Function: HLP-C100 support following f unction code
01: Read Coil Status
03: Read Holding Registers
05: Force Single Coil
06: Preset Single Register
15: Force Multiple Coils
16: Preset Multiple Regs
3) DATA: N8bits
4) CRC: CRC check
R/W
0-15
R, W
16-31
R, W
32-47
48-63
64
65-65535
Description
Frequency converter control word (see
following table)
Reserved
- 79 -
HLP-C100 Series
FC control word
Coil address
00
1
Preset reference bit0
01
02
DC brake
03
Coast stop
04
No DC brake
No coast stop
Reserved
05
Freeze f req
06
Ramp stop
No f reeze f req
Start
07
No reset
Reset
08
No jog
Jog
09
Ramp 1
Ramp 2
10
Data invalid
Data valid
11
Relay off
12
Relay on
Reserved
13
Reserved
14
Reserved
15
No reversing
Reversing
Status word
Coil address
0
1
32
Control not ready
Control ready
33
Frequency converter not ready Frequency converter ready
34
Coasting stop
Satety closed
35
No alarm
Alarm
36
Reserved
37
Reserved
38
Reserved
39
No warning
Warning
40
Not at reference
At reference
41
Hand mode
Auto mode
42
Out of f req range
In f req range
43
Stopped
Running
44
Reserved
45
No voltage warning
Voltage warning
- 80 -
HLP-C100 Series
Coil address
46
47
0
Not in current limit
No thermal warning
Register
00000-00007
00008
00009-00989
00999-01989
01999-02989
15999-16989
1
Current limit
Thermal warning
Description
Reserved
Parameter index
Parameter group 00
Parameter group 01
Parameter group 02
Parameter group 16
Description
FC address
Funtion
Coil address (ADDRH ADDRL). 0x0030 convert to decimal
number is 48. Coil address 49 is f requency converter output
f requency.
00 10
3D C9
CRC check
Receive data
Field
01
Description
FC address
01
Function
02
- 81 -
HLP-C100 Series
Field
Description
00 20
Ouput f requency. Swap high and low, the data is 0x2000, so the
output f requency is 50% of C03.03. Why does 0x2000 correspond
to 50%, please see 12.6.
B8 24
CRC check
Description
FC address
Function
Register address(ADDRH ADDRL). The register address of
C03.03 is 303*10-1=3029 (0x0BD5)
00 02
D7 D7
CRC check
Receive data
Field
Description
01
FC address
03
Function
04
00 00 EA 60
B5 7B
- 82 -
HLP-C100 Series
Transmit data
Field
01
05
00 40
FF 00
8D EE
Description
FC address
Function
0x0040 convert to decimal number is 64. The register address 64
is parameter write control
0000-Parameter changes are written to the RAM;
FF00- Parameter changes are written to the RAM and
EEPROM;
CRC check
Transmit data
Field
01
05
00 40
FF 00
8D EE
Description
FC address
Function
0x0040 convert to decimal number is 64. The register address 64
is parameter write control
0000-Parameter changes are written to the RAM;
FF00- Parameter changes are written to the RAM and
EEPROM;
CRC check
Description
FC address
Function
The register address of C01.01 is 101*10-1=1009 (0x03F1)
The parameter value is 1
CRC check
- 83 -
HLP-C100 Series
Receive data
Field
01
06
FC address
Function
Description
03 F1
00 01
19 BD
Description
FC address
Function
00 00
00 20
04
7C 04
Control word. 7C 04swap high byte and low byte, the value
is 0x047C
Note:
0x047C convertes to binary is: 0000 0100 0111 1100 are
corresponding to the coil address 0-15
9A 19
37 B3
CRC check
- 84 -
HLP-C100 Series
Receive data
Field
01
0F
00 00
00 20
54 13
Description
FC address
Function
Register address 0 is f requency converter control word.
The bit number is 32.
CRC check
Description
FC address
Function
The register address of C03.03 is 303*10-1=3029 (0x0BD5)
Register number
The byte number of data is 4
0x0000EA60 convert to decimal number is 60000. So the value
of C03.03 is 60000*0.001=60.000
CRC check
Receive data
Field
01
10
0B D5
00 02
52 14
Description
FC address
Function
The register address of C03.03 is 303*10-1=3029 (0x0BD5)
Register number
CRC check
- 85 -
HLP-C100 Series
Transmit: 01 10 0C 1B 00 01 02 00 00 69 BB (Hexadecimal)
Receive: 01 10 0C 1B 00 01 72 9E (Hexadecimal)
Transmit data 1
Field
01
06
Description
FC address
Function
00 08
00 02
89 C9
Receive data 1
Field
01
06
00 08
Description
FC address
Function
Register address (ADDRH ADDRL), the register address of
parameter index is 0x0008
00 02
89 C9
CRC check
Transmit data 2
Field
Description
01
FC address
10
Function
0C 1B
00 01
Register number
02
Byte number
00 00
69 BB
CRC check
- 86 -
HLP-C100 Series
Receive data 2
Field
01
10
0C 1B
Description
FC address
Function
The register address of C03.10 is 310*10-1=3099 (0x0C1B)
00 01
72 9E
CRC check
Function
Exception code
CRC check
8 bits
8 bits
8 bits
16 bits
Exception code
0x00
Description
Parameter number does not exist
0x01
0x02
0x03
0x04
0x05
0x06
0x07
Cannot be changed
0x0B
0x11
0x12
Other exception
0x40
0x41
Invalid length
0x42
0x43
Invalid parameter
0x82
0x83
- 87 -