Power Circuit Breakers

Contents

Tmax Technical Data ....................................................................

4-2

Distribution & Generator Protection Tmax......................................

4-10

Isomax Technical Data ..................................................................

4-16

Distribution & Generator Protection Isomax....................................

4-20

Tmax Accessories..........................................................................

4-30

Isomax Accessories ......................................................................

4-34

Motor Protection Tmax..................................................................

4-48

Motor Protection Isomax................................................................

4-51

Current Limiting MCCBs ..............................................................

4-58

Emax Technical Data ....................................................................

4-60

Emax Air Ciruit Breakers................................................................

4-66

Emax Accessories..........................................................................

4-83

Return to main index

ABB LIMITED

4/1

Tmax Electrical Specifications

Description

T1
Iu

[A]

B
160

C
160

N
160

Poles

No.

3/4

3/4

3/4

3/4

Rated service voltage


(AC) 50-60Hz
(DC)

Ue
[V]
[V]

690
500

690
500

690
500

Uimp

[kV]

Ui

[V]

800

800

800

[V]

3000

3000

3000

[kA]
[kA]
[kA]
[kA]
[kA]
[kA]
[kA]
[kA]

25
16
10
8
3
16
20
16

40
25
15
10
4
25
30
25

50
36
22
15
6
36
40
36

[kA]
[kA]
[kA]
[kA]
[kA]

100%
100%
100%
100%
100%

75%
75%
75%
75%
75%

75%
50% (19kA)
50%
50%
50%

[kA]
[kA]
[kA]
[kA]
[kA]

52.5
32
17
13.6
4.3

84
52.5
30
17
5.9

105
75.6
46.2
30
9.2

[ms]

IEC 60947-2

IEC 60947-2

IEC 60947-2

Performance level

Rated impulse withstand voltage


Rated insulation voltage
Voltage test at industrial frequency for 1 min.
Rated ultimate short circuit breaking capacity
(AC) 50-60Hz 220/230 V
(AC) 50-60Hz 380/415 V
(AC) 50-60Hz 440 V
(AC) 50-60Hz 500 V
(AC) 50-60Hz 690 V
(DC) 250 V 2 poles in series
(DC) 250 V 3 poles in series
(DC) 500 V 3 poles in series

Icu

Rated short circuit service breaking capacity


(AC) 50-60Hz 220/230 V
(AC) 50-60Hz 380/415 V
(AC) 50-60Hz 440 V
(AC) 50-60Hz 500 V
(AC) 50-60Hz 690 V

Ics

Rated short circuit making capacity


(AC) 50-60Hz 220/230 V
(AC) 50-60Hz 380/415 V
(AC) 50-60Hz 440 V
(AC) 50-60Hz 500 V
(AC) 50-60Hz 690 V

Icm

Breaking time
Utilisation category
Isolation behavior
Reference Standards
Releases

Thermomagnetic
TMF (fixed)

TMD (adj.)
-

MA

PR221 DS-LS

magnetic only
microprocessor based
PR221 DS-I

Versions
Terminals F - P

FC Cu-EF-FC CuAI 95mm

Fixing on DIN rail


Mechanical life

Basic dimensions, fixed version


4 poles

Weight

DIN EN 50022

[No. Operations]

[No. Hourly Operations]


Electrical life at 415 V
[No. Hourly Operations]

fixed version
plug-in version

240
[No. Operations]
120
3 poles
L [mm]
H [mm]
P [mm]
3/4 Poles
3/4 Poles

1) MF up to R 12.5 A
2) In the plug-in version, the maximum setting is derated by 10% at 40C
3) F-FC Cu-FC CuAI-EF-ES-R-FC Cu AI 240mm2

ABB LIMITED

F
2

L [mm]
102
130
70
[kg]
[kg]

25000
240
8000
120

25000
240
8000
120

25000

76
102
130
70

76
102
130
70

76

0.9 / 1.2
-

0.9 / 1.2
-

0.9 / 1.2
-

8000

Return to main index

4/2

T2

T3

N
160

S
160

H
160

L
160

N
160

S
160

3/4

3/4

3/4

3/4

3/4

3/4

690
500

690
500

690
500

690
500

690
500

690
500

800

800

800

800

800

800

3000

3000

3000

3000

3000

3000

65
36
30
25
6
36
40
36

85
50
45
30
7
50
55
50

100
70
55
36
8
70
85
70

120
85
75
50
10
85
100
85

50
36
25
20
5
36
40
36

85
50
40
30
8
50
55
50

100%
100%
100%
100%
100%

100%
100%
100%
100%
100%

100%
100%
100%
100%
100%

100%
75%(70kA)
75%
75%
75%

75%
75%
75%
75%
75%

50%
50% (27kA)
50%
50%
50%

143
75.6
63
52.5
9.2

187
105
94.5
63
11.9

220
154
121
75.6
13.6

264
187
165
105
17

105
75.6
52.5
40
7.7

187
105
84
63
13.6

IEC 60947-2

IEC 60947-2

IEC 60947-2

IEC 60947-2

IEC 60947-2

IEC 60947-2

F-P2)

F-P2)

3)

3)

1)

F-P2)

1)

1)

F-P2)

F-P2)

1)

F-P2)

F-FC Cu-FC CuAI-EF-ES-R-FC CuAI 185mm 2


DIN EN 50022

DIN EN 50022

25000
240
8000
120

25000
240
8000
120

25000
240
8000
120

25000
240
8000
120

25000
120
8000
120

25000
120
8000
120

90
120
130
70

90
120
130
70

90
120
130
70

90
120
130
70

105
140
150
70

105
140
150
70

1.1 / 1.5
1.5 / 1.9

1.1 / 1.5
1.5 / 1.9

1.1 / 1.5
1.5 / 1.9

1.1 / 1.5
1.5 / 1.9

2.1 / 3
2.7 / 3.7

2.1 / 3
2.7 / 3.7

Return to main index

ABB LIMITED

4/3

Isomax Electrical Specifications

Description
Performance level

H
160-250

L
160-250

N
160-250

3/4

3/4

3/4

3/4

[V]
[V]

690
750

690
750

690
750

690
-

Uimp

[kV]

Ui

[V]

800

800

800

800

[V]

3000

3000

3000

3000

[kA]
[kA]
[kA]
[kA]
[kA]
[kA]
[kA]
[kA]

65
35
30
25
14
35
35
20

100
65
50
40
18
65
50
35

170
85
65
50
50
85
65
50

65
35
30
25
18
-

100%

75%

75%

100%

Iu

Poles

No.

Rated service voltage


(AC) 50-60Hz
(DC)

Ue

Rated impulse withstand voltage


Rated insulation voltage
Voltage test at industrial frequency for 1 min.
Rated ultimate short circuit breaking capacity
(AC) 50-60Hz 220/230 V
(AC) 50-60Hz 380/415 V
(AC) 50-60Hz 440 V
(AC) 50-60Hz 500 V
(AC) 50-60Hz 690 V
(DC) 250 V 2 poles in series
(DC) 250 V 3 poles in series
(DC) 750 V 3 poles in series

Icu

Rated short circuit service breaking capacity

Ics

Rated short circuit making capacity


Opening Time

S4

S3
N
160-250

[A]

[%Icu]

(415 V)

[kA]

74

143

187

74

(415 V at Icu)

[ms]

[kA]

Rated short time withstand current for 1 s, Icw


Utilisation category (EN 60947-2)
Isolation behavior
IEC 60947-2, EN 60947-2
Releases

Thermomagnetic

T adjustable, M fixed 3 Ith


T adjustable, M fixed 5 Ith

T adjustable, M fixed 10 Ith

T adjustable, M adjustable
magnetic only
microprocessor based

PR211/P (I-LI)

PR212/P (LSI-LSIG

M fixed

Versions

F-P-W

Terminals

Fixed

Fixing on DIN rail

DIN EN 50023

[No. Operations]
[No. Hourly Operations]

Electrical life at 415 V

F-P-W

F-EF-ES-FC
FC CuAI-RC-R
EF-FC-R
EF-FC-R

Plug-in
Withdrawable

Mechanical life

25000
120

[No. Operations]

25000
120

25000
120

20000
120

10000 (160A) -8000 (250A)

[No. Hourly Operations]

120

120

120

120

Basic dimensions, fixed

3/4 poles
D [mm]
H [mm]

L [mm]
103.5
170

105/140
103.5
170

105/140
103.5
170

105/140
103.5
254

105/140
103.5
254

Weight

3/4 Poles
3/4 Poles
3/4 Poles

[kg]
[kg]
[kg]

2.6/3.5
3.1/4.1
3.5/4.5

2.6/3.5
3.1/4.1
3.5/4.5

2.6/3.5
3.1/4.1
3.5/4.5

4/5.3
4.5/5.9
4.9/6.3

fixed version
plug-in version
withdrawable

Return to main index

ABB LIMITED

4/4

S6

S5

S4

S7

H
160-250

L
160-250

N
400-630

H
400-630

L
400-630

N
630-800

S
630-800

H
630-800

L
630-800

S
1250-1600

H
1250-1600

L
1250-1600

3/4

3/4

3/4

3/4

3/4

3/4

3/4

3/4

3/4

3/4

3/4

3/4

690
-

690
-

690
750

690
750

690
750

690
750

690
750

690
750

690
750

690
-

690
-

690
-

800

800

800

800

800

800

800

800

800

800

800

800

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

3000

100
65
50
40
22
-

200
100
80
65
30
-

65
35
30
25
20
35
35
20

100
65
50
40
25
65
50
35

200
100
80
65
30
100
65
50

65
35
30
25
20
35
20
16

85
50
45
35
22
50
35
20

100
65
50
40
25
65
50
35

200
100
80
65
30
100
65
50

85
50
40
35
20
-

100
65
55
45
25
-

200
100
80
70
35
-

100%

75%

100%

100%

75%

100%

100%

100%

75%

100%

75%

50%

143

220

74

143

220

74

105

143

220

105

143

220

10

22

22

22

5 (400A)

B (400A) - A (630A)

7.6 (630A) - 10 (800A)

F-P(400)-W

F-EF-ES-FC
FC CuAI-RC-R
EF-FC-R
EF-FC-R

F-EF(400A)-ES-FC
FC CuAI(400A)-RC-(400A)-R
EF-FC-R
EF(400A)-ES-FC(400A)

DIN EN 50023

20000
120

F-P-W

15 (1250A) - 20 (1600A)

F-W

F-W

F-EF-ES-FC-CuAI
RC-R
EF-HR-VR

F-EF-ES-FC CuAI(1250A)
HR-VR
EF-HR-VR

DIN EN 50023

20000
120

20000
120

10000(160A) - 8000(250A)

20000
120

20000
120

20000
120

7000 (400A) - 5000 (800A)

20000
120

20000
120

20000
120

10000
120

7000 (630A) - 5000 (800A)

10000
120

10000
120

7000 (1250A) - 5000 (1600A)

120

120

60

60

60

60

60

60

60

20

20

20

105/140
103.5
254

105/140
103.5
254

140/184
103.5
254

140/184
103.5
254

140/184
103.5
268

210/280
103.5
268

210/280
103.5
268

210/280
103.5
268

210/280
138.5
406

210/280
138.5
406

210/280
138.5
406

210/280

4/5.3
4.5/5.9
4.9/6.3

4/5.3
4.5/5.9
4.9/6.3

5/7
6.1/8.4
6.4/8.7

5/7
6.1/8.4
6.4/8.7

5/7
6.1/8.4
6.4/8.7

9.5/12
12.1/15.1

9.5/12
12.1/15.1

9.5/12
12.1/15.1

9.5/12
12.1/15.1

17/22
21.8/29.2

17/22
21.8/29.2

17/22
21.8/29.2

Return to main index

ABB LIMITED

4/5

Tmax Construction Characteristics


Modularity of the series

1
2

14

13

Return to main index

ABB LIMITED

4/6

Starting from the fixed version circuit-breaker, all the other versions used for various requirements are obtained by means of
mounting conversion kits.

12
The following are available:

Kit for converting a fixed circuit-breaker into the moving


part of a plug-in

Circuit-breaker fixed parts for plug-in circuit-breakers

Conversion kit for the connection terminals

Various accessories are also available:

8
6

Shunt opening releases

Undervoltage releases

Auxiliary contacts

Position contacts

Advanced contacts on rotary handle

Front and rear connection terminals

10

Bracket for rear fixing on DIN EN 50022 rail

11

Front interlocking plate

12

Solenoid operating mechanism

13

Rotary handle operating mechanism - direct on circuit-

breaker and transmitted on compartment door

14

Three-pole and four-pole residual current releases

Return to main index

ABB LIMITED

4/7

Tmax Electronic Releases

Protection functions
of the PR221DS-LS release
Protection Function

Trip threshold

Against overload with inverse


long delay trip and trip characteristic according to a definite
time curve (I 2t = constant)

CANNOT BE
EXCLUDED

i1 = 0.40
0.56
0.72
0.88

0.44
0.60
0.76
0.92

0.48
0.64
0.80
0.96

- 0.52 - 0.68
- 0.84
- 1 x In

at 6 x I1
t1 = 3s

at 6 x I1
t1 = 6s

(Tolerence

10% up to 2 x In;
20% over 2 xIn)

Release between 1.05...1.30 x I1


(IEC 60947-2)

Against a short-circuit with


inverse short delay and trip
characteristic with definite time
(I2t = constant)

i1 =

1 - 1.5 - 2 - 2.5 - 3 - 3.5 - 4.5


- 5.5 - 6.5 - 7 - 7.5 - 8 - 8.5 9 - 10 x In

Against short-circuit with instantaneous adjustable trip (can be


selected as an alternative to
protection function S)

at 8 x In
t2 = 0.1s

at 8 x In
t2 = 0.25s

(Tolerence 20%)
Tolerence

CAN BE
EXCLUDED

Trip Curves
A
B

I3 =

10% up to 2 x In
20% over 2 x In

1 - 1.5 - 2 - 2.5 - 3 - 3.5 - 4.5


- 5.5 - 6.5 - 7 - 7.5 - 8 - 8.5 9 - 10 x In

Tolerence

20%

CAN BE
EXCLUDED

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/8

Tmax Thermomagnetic Releases

Thermomagnetic releases
The Tmax T1, T2 and T3 circuit-breakers can be fitted with thermomagnetic releases and are
used to protect alternating and direct current networks with an application range from 1A to
250A. They allow protection against overloads with a thermal device (with adjustable threshold)
made using the bimetal technique, and protection against short-circuit with a magnetic device
(with fixed threshold).
The four-pole circuit-breakers are always supplied with the neutral protected by the release
and protection of the neutral at 100% of the phase setting for settings up to 100A. For higher
settings, the version with protection of the neutral at 50% of the phase setting is available.

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/9

Distribution and Generator Protection MCCBs


Tmax T2N (160A)

Protection types available


Type

Ratings @ 415V
T2N

Icu

Ics

36kA

100%

Settings
L

PR221DS/LS

0.4 -1x In

1-10x In

Thermomagnetic

Ith

Im

Standard Distribution

70 - 100%

10x Ith

Electronic

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx
Icu (415V)

Model

T2N160R1.6
T2N160R2

Thermomagnetic
1SDA0

1.6A

PR221DS/LS
R1

3 Pole

4 Pole

3 Pole

4 Pole

50940

50962

2A

50941

50963

T2N160R2.5

2.5A

50942

50964

T2N160R3.2

3.2A

50943

50965

T2N160R4

4A

50944

50966

T2N160R5

5A

50945

50967

6.3A

50946

50968

8A

50947

50969

10A

50948

50970

51123

51128

12.5A

50949

50971

T2N160R6.3
T2N160R8
T2N160R10
T2N160R12.5
36kA

Current (A)
Ith

T2N160R16

16A

50950

50972

T2N160R20

20A

50951

50973

T2N160R25

25A

50952

50974

51124

51129

T2N160R32

32A

50953

50975

T2N160R40

40A

50954

50976

T2N160R50

50A

50955

50977

T2N160R63

63A

50956

50978

51125

51130

T2N160R80

80A

50957

50979

T2N160R100

100A

50958

50980

51126

51131

T2N160R125

125A

50959

51115

T2N160R160

160A

50960

51116

51127

51613

Plug-in Circuit breakers


To convert fixed pattern device to plug-in pattern:1). Select correct Fixed Pattern Device from part numbers above
2). Select Conversion Kit from part numbers below
3). Add Fixed portion (Base) from part numbers below

Plug-in
1SDA0

Conversion Kit

R1

3 Pole

4 Pole

51411

51412

51329

51330

Fixed portion (Base)


Front Copper Cable Terminals**

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/11

Distribution and Generator Protection MCCBs


Tmax T2S (160A)

Protection types available


Type

Ratings @ 415V
T2S

Icu

Ics

50kA

100%

Settings
L

PR221DS/LS

0.4 -1x In

1-10x In

Thermomagnetic

Ith

Im

Standard Distribution

70 - 100%

10x Ith*

Electronic

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx
Icu (415V)

Model

50kA

T2S160R1.6

Current (A)
Ith

Thermomagnetic
1SDA0

PR221DS/LS
R1

3 Pole

4 Pole

3 Pole

1.6A

50984

51006

2A

50985

51007

T2S160R2.5

2.5A

50986

51008

T2S160R3.2

3.2A

50987

51009

4A

50988

51010

T2S160R2

T2S160R4
T2S160R5
T2S160R6.3
T2S160R8
T2S160R10

4 Pole

5A

50989

51011

6.3A

50990

51012

8A

50991

51013

10A

50992

51014

51133

51138

12.5A

50993

51015

T2S160R16

16A

50994

51016

T2S160R20

20A

50995

51017

51139

T2S160R12.5

T2S160R25

25A

50996

51018

51134

T2S160R32

32A

50997

51019

T2S160R40

40A

50998

51020

T2S160R50

50A

50999

51021

T2S160R63

63A

51000

51022

51135

51140

T2S160R80

80A

51001

51023

T2S160R100

100A

51002

51024

51136

51141

T2S160R125

125A

51003

51117

T2S160R160

160A

51004

51118

51137

51614

Plug-in Circuit breakers


To convert fixed pattern device to plug-in pattern:1). Select correct Fixed Pattern Device from part numbers above
2). Select Conversion Kit from part numbers below
3). Add Fixed portion (Base) from part numbers below
Plug-in
1SDA0
Conversion Kit

R1

3 Pole

4 Pole

51411

51412

51329

51330

Fixed portion (Base)


Front Copper Cable Terminals**

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/12

Distribution and Generator Protection MCCBs


Tmax T2H (160A)

Protection types available


Type

Ratings @ 415V
Icu

Ics

70kA

100%

T2H

Settings
L

PR221DS/LS

0.4 -1x In

1-10x In

Thermomagnetic

Ith

Im

Standard Distribution

70 - 100%

10x Ith

Electronic

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx
Icu (415V)

Model

T2H160R1.6
T2H160R2

Thermomagnetic
1SDA0

1.6A

PR221DS/LS
R1

3 Pole

4 Pole

3 Pole

4 Pole

51028

51050

2A

51029

51051

T2H160R2.5

2.5A

51030

51052

T2H160R3.2

3.2A

51031

51053

T2H160R4

4A

51032

51054

T2H160R5

5A

51033

51055

6.3A

51034

51056

8A

51035

51057

10A

51036

51058

51143

51148

12.5A

51037

51059

T2H160R6.3
T2H160R8
T2H160R10
70kA

Current (A)
Ith

T2H160R12.5
T2H160R16

16A

51038

51060

T2H160R20

20A

51039

51061

T2H160R25

25A

51040

51062

51144

51149

T2H160R32

32A

51041

51063

T2H160R40

40A

51042

51064

T2H160R50

50A

51043

51065

T2H160R63

63A

51044

51066

51145

51150

T2H160R80

80A

51045

51067

T2H160R100

100A

51046

51068

51146

51151

T2H160R125

125A

51047

51119

T2H160R160

160A

51048

51120

51147

51615

Plug-in Circuit breakers


To convert fixed pattern device to plug-in pattern:1). Select correct Fixed Pattern Device from part numbers above
2). Select Conversion Kit from part numbers below
3). Add Fixed portion (Base) from part numbers below
Plug-in
1SDA0
Conversion Kit

R1

3 Pole

4 Pole

51411

51412

51329

51330

Fixed portion (Base)


Front Copper Cable Terminals**

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/13

Distribution and Generator Protection MCCBs


Tmax T1... (160A)

Ratings @ 415V (230V for 1 pole)

Protection types available


Type

Icu

Ics

Icw

T1B (1Pole)

25kA

75%

Standard Distribution (1 pole)

T1B (3 & 4 Pole)

16kA

100%

Standard Distribution (3&4 pole)70-100%

T1C

25kA

75%

T1N

36kA

50%

T1D

(1sec)

Settings
Ith

Im

100%

10x Ith*
10x Ith*

* Subject to a Minimum value of 500A

2kA

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front cable terminals for copper cables - for other terminals see
accessories section pagexx

Icu (415V)

Model

Current (A)
Ith

Thermomagnetic
1SDA0
R1
1 Pole

3 Pole

4 Pole

T1B160R16

16A

52616

50870

50881

T1B160R20

20A

52617

50871

50882

T1B160R25

25A

52618

50872

50883

T1B160R32

32A

52619

50873

50884

T1B160R40

40A

52620

50874

50885

16kA (25A for

T1B160R50

50A

52621

50875

50886

1 pole)

T1B160R63

63A

52622

50876

50887

T1B160R80

80A

52623

50877

50888

T1B160R100

100A

52624

50878

50889

25kA

36kA

T1B160R125

125A

52625

50879

50890

T1B160R160

160A

52626

50880

50936

T1C160R25

25A

50894

50905

T1C160R32

32A

50895

50906

T1C160R40

40A

50896

50907

T1C160R50

50A

50897

50908

T1C160R63

63A

50898

50909

T1C160R80

80A

50899

50910

T1C160R100

100A

50900

50911

T1C160R125

125A

50901

50912

T1C160R160

160A

50902

50937

T1N160R32

32A

50917

50928

T1N160R40

40A

50918

50929

T1N160R50

50A

50919

50930

T1N160R63

63A

50920

50931

T1N160R80

80A

50921

50932

T1N160R100

100A

50922

50933

T1N160R125

125A

50923

50934

T1N160R160

160A

50924

50938

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/10

Distribution and Generator Protection MCCBs


Tmax T2 (160A)

Protection types available


Type

Ratings @ 415V
T2L

Icu

Ics

85kA

75%

Settings
L

PR221DS/LS

0.4 -1x In

1-10x In

Thermomagnetic

Ith

Im

Standard Distribution

70 - 100%

10x Ith

Electronic

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx
Icu (415V)

Model

T2L160R1.6
T2L160R2

Thermomagetic
1SDA0

PR221DS/LS
R1

3 Pole

3 Pole

4 Pole

4 Pole

1.6A

51072

51094

2A

51073

51095

T2L160R2.5

2.5A

51074

51096

T2L160R3.2

3.2A

51075

51097

T2L160R4

4A

51076

51098

T2L160R5

5A

51077

51099

T2L160R6.3

85kA

Current (A)
Ith

6.3A

51078

51100

T2L160R8

8A

51079

51101

T2L160R10

10A

51080

51102

51153

51158

12.5A

51081

51103

T2L160R16

T2L160R12.5

16A

51082

51104

T2L160R20

20A

51083

51105

T2L160R25

25A

51084

51106

51154

51159
-

T2L160R32

32A

51085

51107

T2L160R40

40A

51086

51108

T2L160R50

50A

51087

51109

T2L160R63

63A

51088

51110

51155

51160

T2L160R80

80A

51089

51111

51161

T2L160R100

100A

51090

51112

51156

T2L160R125

125A

51091

51121

T2L160R160

160A

51092

51122

51157

51162

Plug-in Circuit breakers


To convert fixed pattern device to plug-in pattern:1). Select correct Fixed Pattern Device from part numbers above
2). Select Conversion Kit from part numbers below
3). Add Fixed portion (Base) from part numbers below

Plug-in
1SDA0
Conversion Kit

R1

3 Pole

4 Pole

51411

51412

51329

51330

Fixed portion (Base)


Front Copper Cable Terminals**

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/14

Distribution and Generator Protection MCCBs


Tmax T3 (250A)

Ratings @ 415V
Icu

Ics

36kA

75%

Icw

(1sec)
T3N
T3S

50kA

50%

T3D

Protection types available


Type
Thermomagnetic

Settings
Ith

Im

Standard Distribution

70-100%

10x Ith*

3.6kA

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx

Icu (415V)

36kA

50kA

Model

Current (A)
I th

Thermomagnetic
1SDA0
R1
3 Pole

4 Pole

T3N250R63

63A

51241

51252

T3N250R80

80A

51242

51253

T3N250R100

100A

51243

51254

T3N250R125

125A

51244

51303
51304

T3N250R160

160A

51245

T3N250R200

200A

51246

51305

T3N250R250

250A

51247

51306

T3S250R63

63A

51263

51274

T3S250R80

80A

51264

51275

T3S250R100

100A

51265

51276

T3S250R125

125A

51266

51307

T3S250R160

160A

51267

51308

T3S250R200

200A

51268

51309

T3S250R250

250A

51269

51310

Fixed Pattern Switch Disconnector


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front cable terminals for copper cables - for other terminals see
accessories section pagexx

lcw (1 sec)
3.6kA

Model
T3D250

Current (A)

1SDA0

R1

Iu

3 Pole

4 Pole

250A

51327

51328

Plug-in Circuit breakers


To convert fixed pattern device to plug-in pattern:1). Select correct Fixed Pattern Device from part numbers above
2). Select Conversion Kit from part numbers below
3). Add Fixed portion (Base) from part numbers below

Conversion Kit

Plug-in
1SDA0

R1

3 Pole

4 Pole

51411

51412

51329

51330

Fixed portion (Base)


Front Copper Cable Terminals**

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/15

Isomax Construction Characteristics


Modularity of the series

Shunt trip

Rotary handle

Locking device

10

Aux contact

Motor operator

11

Rear stud terminal

Thermal Magnetic Release

12

Cable clamp aluminium

27
5

Standard escutcheon

13

Cable clamp copper

Data plate

14

Extended bar terminals

DINescutcheon

15

Conversion kit from fixed to moving

UVR

16

Position carriage switch

22

8
9
7
5
1

10

22

27

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/16

18

17

19

14
13
23
12
24

11

25

16
15

20

26

21
22

Long terminal shrouds

17

Fixed portion terminal shrouds

23

Plug-in tulip contacts

18

Rear cable connections

24

Shunt trip + UVR female socket

19

Rear bolt connections

25

Aux connections plug-in / drawout

20

Door closing racking device

26

Female sockets for fixed breaker

21

Carriage locking device

27

Short terminal shrouds

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/17

Isomax Electronic Releases

PR211/P

PR212/P

In
S4

S5

320
400

S6

630
800

S7

100
160
250

In
S4

100
160
250

I1 (0.4 ... 1xIn)


t1 = 3 ... 18s

S5

320
400

S6

630
800

S7

1000
1250
1600

I3 (1.5 ... 12 x In)

1000
1250
1600

L
I1 (0.4 ... 1xIn)
t1 = 3 ... 18s
S
I2 (1 ... 10 OFF x In)
t2 = 0.05 ... 0.5s
I
I3 (1.5 ... 12 OFF x In)
G
I4 (0.2 ... 1 OFF x In)
t4 = 0.01 ... 0.8s

Against overload with inverse long time delay and trip characteristic
according to a time dependent curve (I2t = constant)

CANNOT BE
EXCLUDED

Against short-circuit with inverse short time delay and trip


characteristic with dependent time (I 2t = constant) independent

CAN BE
EXCLUDED

Against short-circuit with adjustable instantaneous trip

CAN BE
EXCLUDED

Against earth fault with short inverse time delay and trip characteristic according to a dependent time curve (I2t = constant)

CAN BE
EXCLUDED

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/18

Isomax Thermomagnetic Releases

The thermomagnetic releases which equip the SACES3 circuit-breakers have the thermal element with
threshold adjustable from 0.7 1 x In. The regulated current value which is obtained by using the appropriate selector must be intended as the rated value at 40C. The magnetic element has fixed trip threshold,
with trip values which may vary according to the phase setting.
The thermomagnetic releases which equip SACE S5 and S6 circuit-breakers have the thermal element with
threshold adjustable from 0.7 1 x In. The regulated current value which is obtained by using the approproate selector must be intended as the rated value at 40C. The magnetic element can be adjusted from
5 10 x In. The table gives the maximum magnetic trip values (10 x In) for protection of the phases (L1 L2 - L3) and of the neutral.

S3

S5/6

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/19

Distribution and Generator Protection MCCBs


Isomax S3 (250A)

Ratings @ 415V
S3N

Icu

Ics

35kA

100%

S3H

65kA

75%

S3L

85kA

75%

S3D

Icw (1sec)

6.5kA

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx

Icu (415V)

35kA

65kA

Model

Current (A)
Ith

Standard

Low Threshold
1SDA0
R1

Generator

3 Pole

4 Pole

3 Pole

4 Pole

3 Pole

4 Pole

S3N160R32

32A

13346

13371

13359

13383

S3N160R50

50A

13348

13373

13361

13385

S3N160R80

80A

13350

13375

13363

13387

S3N160R100

100A

13352

13377

13365

13389

48539

48549

S3N160R125

125A

13354

13379

13367

13391

48540

48550

S3N160R160

160A

13356

13381

13369

13393

48541

48551

S3N250R200

200A

13491

13499

13495

13503

48545

48555

S3N250R250

250A

13493

13501

13497

13505

48546

48556

S3H160R32

32A

13395

13419

13407

13431

S3H160R50

50A

13397

13421

13409

13433

S3H160R80

80A

13399

13423

13411

13435

S3H160R100

100A

13401

13425

13413

13437

48542

48552

S3H160R125

125A

13403

13427

13415

13439

48543

48553

S3H160R160

160A

13405

13429

13417

13441

48544

48554

S3H250R200

200A

13507

13515

13511

13519

48547

48557

S3H250R250

250A

13509

13517

13513

13521

48548

48558

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/20

Distribution and Generator Protection MCCBs


Isomax S3 (250A)

Protection types available


Type
Standard Distribution

Settings
Ith

Im

70-100% 10xIth

Low Threshold Thermomagnetic 70-100% 5xIth


Generator Thermomagnetic

70-100% 3xIth

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx

Icu (415V)

Model

Current (A)
Ith

Standard
1SDA0
3 Pole

85kA

4 Pole

Low Threshold
R1
3 Pole

4 Pole

S3L160R32

32A

13443

13467

13455

S3L160R50

50A

13445

13469

13457

13479
13481

S3L160R80

80A

13447

13471

13459

13483

S3L160R100

100A

13449

13473

13461

13485

S3L160R125

125A

13451

13475

13463

13487

S3L160R160

160A

13453

13477

13465

13489

S3L250R200

200A

13523

13531

13527

13535

S3L250R250

250A

13525

13533

13529

13537

Current (A)

1SDA0

R1

Fixed Pattern Switch Disconnector


lcw (1 sec)

6.5kA

Model

Iu

3 Pole

4 Pole

S3D100

100A

20906

20907

S3D100

160A

20908

20909

S3D250

250A

20910

20911

Plug-in / Withdrawable Circuit breakers / Disconnectors


To convert fixed pattern device to plug-in or withdrawable pattern:1). Select correct Fixed Pattern Device from part numbers above
2). Select Conversion Kit from part numbers below
3). Add Fixed portion (Base) from part numbers below
Plug-in
1SDA0

Withdrawable
R1

1SDA0

R1

3 Pole

4 Pole

3 Pole

4 Pole

13608

13609

13610

13611

Front Copper Cable Terminals

13543

13550

13559

13568

Extended Front bar Terminals

13539

13548

13555

13564

Threaded Rear Terminals

13547

13554

13563

13572

Conversion Kit
Fixed portion (Base)

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/21

Distribution and Generator Protection MCCBs


Isomax S4 (250A)

Ratings @ 415V
Icu

Ics

S4N

35kA

100%

S4H

65kA

100%

S4L

100kA

75%

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx

Icu (415V)

Model

Current (A)

Protection

In
LI
35kA

S4N160R100

100A

LSI
LSIG
LI

35kA

S4N160R160

160A

S4N250R250

250A

100A

160A

S4H250R250

250A

15550

15838

15553

15841

15558

15846

15551

15839

15554

15842

15559

15847

17319

17385

17320

17386
17389

LSI

LSI

17323

16144

16426

16146

16428

16152

16434

16145

16427

LSI

16147

16429

LSIG

16153

16435

LI
65kA

4 Pole

LSIG
S4H160R100

4 Pole

LI
65kA

3 Pole

R1

3 Pole

LSIG
S4H160R100

1SDA0

LSIG

LI
65kA

PR212
R1

LSI
LI

35kA

PR211
1SDA0

17451

17517

LSI

17452

17518

LSIG

17455

17521

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/22

Distribution and Generator Protection MCCBs


Isomax S4 (250A)

Protection types available


Electronic (ac only)
Type

Settings
L

G
-

PR211/LI

0.4-1x In

1.5-12x In

PR212/LSI

0.4-1x In

1-10x In

1.5-12x In

PR212/LSIG 0.4-1x In

1-10xIn

1.5-12x In

0.2-1x In

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx

Icu (415V)

Model

Current (A)

Protection

In
LI
100kA

S4L160R100

100A

LSI
LSIG

100kA

S4L160R160

S4L250R250

160A

250A

PR212

1SDA0
3 Pole

R1
4 Pole

1SDA0
3 Pole

R1
4 Pole

16732

17014

16734

17016

16740

17022

16733

17015

LSI

16735

17017

LSIG

16741

17023

LI
100kA

PR211

LI

17583

17649

LSI

17584

17650

LSIG

17587

17653

Plug-in / Withdrawable Circuit breakers / Disconnectors


To convert fixed pattern device to plug-in or withdrawable pattern:1). Select correct Fixed Pattern Device from part numbers above
2). Select Conversion Kit from part numbers below
3). Add Fixed portion (Base) from part numbers below

Plug-in
1SDA0
Conversion Kit

Withdrawable
R1

1SDA0

R1

3 Pole

4 Pole

3 Pole

4 Pole

13608

13609

13610

13611

Fixed portion (Base)


Front Copper Cable Terminals

13616

13625

13634

13643

Extended Front bar Terminals

13612

13621

13630

13639

Threaded Rear Terminals

13620

13629

13638

13647

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/23

Distribution and Generator Protection MCCBs


Isomax S5 (630A)

Ratings @ 415V
Icu

Ics

Icw

S5N

35kA

100%

5kA

S5H

65kA

100%

5kA

S5L

100kA 75%

(1sec)*

5kA

*400A only
Fixed Pattern Circuit Breaker
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx

Icu (415V)

35kA

35kA

35kA

35kA

65kA

65kA

65kA

65kA

Model

S5N400R320

S5N400R400

S5N630R500

S5N630R630

S5H400R320

S5H400R400

S5H630R500

S5H630R630

Current (A)
Ith

320A

400A

500A

630A

320A

400A

500A

630A

Protection Thermomagnetic

PR211
1SDA0
R1

PR212

3 Pole

4 Pole

3 Pole

4 Pole

3 Pole

T/Mag

38438

38440

4 Pole
-

LI

17716

17848

LSI

17718

17850

LSIG

17724

17856

T/Mag

38439

38441

LI

17717

17849

LSI

17719

17851

LSIG

17725

17857

T/Mag

38678

38683

LI

LSI

LSIG

T/Mag

LI

38675

38680

LSI

38676

38681

LSIG

38677

38682

T/Mag

38522

38524

LI

17992

18124

LSI

17994

18126

LSIG

18000

18132

T/Mag

38523

38525

LI

17993

18125

LSI

17995

18127

LSIG

18001

18133

T/Mag

38708

38713

LI

LSI

LSIG

T/Mag

LI

38705

38710

LSI

38706

38711

LSIG

38707

38712

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/24

Distribution and Generator Protection MCCBs


Isomax S5 (630A)

Protection types available


Electronic
L
S
Type

Settings

PR211/LI

0.4-1x In

1.5-12x In

PR212/LSI

0.4-1x In

1-10x In

1.5-12x In

PR212/LSIG 0.4-1x In

1-10x In

1.5-12x In 0.2-1x In

Thermomagnetic
Standard Distribution

Ith

Im

70-100%

5-10x Ith

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx

Icu (415V)

100kA

100kA

100kA

100kA

Model

S5L400R320

S5L400R400

S5L630R500

S5L630R630

Current (A)
I th

Protection Thermomagnetic

320A

400A

500A

630A

PR211
1SDA0
R1

PR212

3 Pole

4 Pole

3 Pole

4 Pole

3 Pole

4 Pole

T/Mag

38606

38608

LI

18256

18388

LSI

18258

18390

LSIG

18264

18396

T/Mag

38607

38609

LI

18257

18389

LSI

18259

18391

LSIG

18265

18397

T/Mag

38740

38745

LI

LSI

LSIG

T/Mag

LI

38737

38742

LSI

38738

38743

LSIG

38739

38744

Plug-in / Withdrawable Circuit breakers / Disconnectors


To convert fixed pattern device to plug-in or withdrawable pattern:1). Select correct Fixed Pattern Device from part numbers above
2). Select Conversion Kit from part numbers below
3). Add Fixed portion (Base) from part numbers below

400A
plug-in

400A
withdrawable
1SDA0

Conversion Kit

630A
withdrawable

R1

3 Pole

4 Pole

3 Pole

4 Pole

3 Pole

4 Pole

13716

13717

13718

13719

38778

38779

Fixed portion (Base)


Front Copper Cable Terminals (400A)

13724

13733

13742

13751

Extended Front bar Terminals

13720

13729

13738

13747

Spreaded Ext Front bar Terminals

38761

38762

Threaded Rear Terminals

13728

13737

13746

13755

38763

38970

Vertical Flat bar Terminals

38971

38972

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/25

Distribution and Generator Protection MCCBs


Isomax S6 (800A)

Ratings @ 415V
Icu

Ics

Icw (1sec)

S6D

15kA

S6N

35kA 100% 7.6kA (630A) 10kA (800A)

S6S

50kA 100% 7.6kA (630A) 10kA (800A)

S6H

65kA 100% 7.6kA (630A) 10kA (800A)

S6L100kA

75%

7.6kA (630A) 10kA (800A)

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx

Icu (415V)

35kA

Model

S6N630R630

Current (A)
Ith

630A

Thermomagnetic

S6N800R800

800A

3 Pole

4 Pole

3 Pole

4 Pole

3 Pole

38788

S6S630R630

630A

S6S800R800

800A

18519

18573

LSI

18520

18574

LSIG

18577

S6H630R630

630A

S6H800R800

800A

18523

18951

19005

LSI

18952

19006

LSIG

19009

18955

38800

18681

LI

18627

LSI

18628

18682

LSIG

18631

18685

38884

LI

19059

19113

LSI

19060

19114

LSIG

19117

19063

38824

18735

18789

LSI

18736

18790

LSIG

18739

18793

38908

LI

T/Mag 38907
65kA

38872

LI

T/Mag 38823
65kA

T/Mag 38883
50kA

4 Pole

LI

T/Mag 38799
50kA

PR212
R1

T/Mag 38787

T/Mag 38871
35kA

PR211
1SDA0

LI

19167

19221

LSI

19168

19222

LSIG

19171

19225

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/26

Distribution and Generator Protection MCCBs


Isomax S6 (800A)

Protection types available


Electronic
L

Type

Settings

PR211/LI

0.4-1x In

1.5-12x In

PR212/LSI

0.4-1x In

1-10x In

1.5-12x In

PR212/LSIG

0.4-1x In

1-10x In

1.5-12x In

0.2-1x In

Ith

Im

70-100%

5-10x Ith

Thermomagnetic
Standard Distribution

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx
Icu (415V)

Model

Current (A)
Ith

Thermomagnetic

S6L630R630 630A

4 Pole

3 Pole

4 Pole

3 Pole

38847

38848

LI

18843

18897

LSI

18844

18898

18847

18901

38931

38932

LSIG
T/Mag
100kA

S6L800R800 800A

PR212
R1

3 Pole
T/Mag
100kA

PR211
1SDA0

4 Pole
-

LI

19275

19329

LSI

19276

19330

LSIG

19279

19333

Fixed Pattern Switch Disconnector


lcw (1 sec)

Model

Current (A)
Iu

1SDA0
3 Pole

15kA

R1
4 Pole

S6D400

400A

20545

20581

S6D630

630A

20674

20699

S6D800

800A

20724

20749

Withdrawable Circuit breakers


To convert fixed pattern device to withdrawable pattern:1). Select correct Fixed Pattern Device from part numbers above
2). Select Conversion Kit from part numbers below
3). Add Suitable Fixed portion (Base) from part numbers below
Special Notes:
a).Withdrawable devices must be fitted with a front plate accessory such as:
Motor operator
Padlock Device
Rotary Handle
c). Remember to use accessories suitable for withdrawable pattern devices
1SDA0

R1

Withdrawable

3 Pole

4 Pole

Conversion Kit

13962

13963

Fixed portion (Base)


Extended Front bar Terminals

13964

13973

Horizontal Flat bar Terminals

13968

13977

Vertical Flat bar Terminals

13972

13981

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/27

Distribution and Generator Protection MCCBs


Isomax S7 (1250A)

Ratings @ 415V
Icu

Ics

S7S

50kA

100% 15kA (1250A) 20kA (1600A)

Icw (1sec)

S7H

65kA

75%

S7L

100ka

50%

15kA (1250A) 20kA (1600A)

S7D

25kA

15kA (1250A) 20kA (1600A)

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx

Icu (415V)

Model

Current (A)
In

Protection

PR211
1SDA0
3 Pole
4 Pole

LI

19384

19492

50kA

S7S1250R1000

1000A

LSI

19386

19494
19500

LSIG

19392

19385

19493

LSI

19387

19495

LSIG

19393

19501

20031

20073

20032

20074
20077

LI
50kA

S7S1250R1250

1250A

LI
50kA

S7S1600R1600

1600A

LSI
LSIG
LI

65kA

S7H1250R1000

1000A

LSI
LSIG

S7H1250R1250

1250A

S7H1600R1600

1600A

20035

19708

19602

19710
19716

19608

19709

LSI

19603

19711

LSIG

19609

19717

LI
65kA

19600

19601

LI
65kA

PR212
R1
3 Pole 4 Pole

20115

20157

LSI

20116

20158

LSIG

20119

20161

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/28

Distribution and Generator Protection MCCBs


Isomax S7 (1250A)

Protection types available


Electronic
L

Type

Settings

PR211/LI

0.4-1x In

PR212/LSI

0.4-1x In

1-10xIn

1.5-12x In
1.5-12x In

PR212/LSIG

0.4-1x In

1-10x In

1.5-12x In

0.2-1x In

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx

Icu (415V)

Model

Current (A)
In

Protection

PR211
1SDA0
3 Pole
4 Pole

LI

19816

19924

100kA

S7L1250R1000

1000A

LSI

19818

19926
19932

LSIG
LI
100kA

S7L1250R1250

1250A

LSI
LSIG
LI

100kA

S7L1600R1600

1600A

PR212
R1
3 Pole 4 Pole

19824

19817

19925

19819

19927

19825

19933

20199

20241

LSI

20200

20242

LSIG

20203

20245

Fixed Pattern Switch Disconnector


lcw (1 sec)

Model

Current (A)
Iu

1SDA0
3 Pole

25kA

R1
4 Pole

S7D1000

1000A

20774

20799

S7D1250

1250A

20824

20849

S7D1600

1600A

20874

20890

Withdrawable Circuit breakers


To convert fixed pattern device to withdrawable pattern:1). Select correct Fixed Pattern Device from part numbers above
2). Select Conversion Kit from part numbers below
3). Add Suitable Fixed portion (Base) from part numbers below
Special Notes:
a).Withdrawable devices must be fitted with a front plate accessory such as:
Motor operator
Padlock Device
Rotary Handle
c). Remember to use accessories suitable for withdrawable pattern devices
1SDA0

R1

Withdrawable

3 Pole

4 Pole

Conversion Kit

23299

14087

Extended Front bar Terminals

48951

14097

Horizontal Flat bar Terminals

14092

14101

Vertical Flat bar Terminals

14096

14105

Fixed portion (Base)

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/29

Accessories Tmax T1, T2 and T3

1). Electrical Accessories


a). Shunt Opening Releases ( cabled version)
AC Voltage

1SDA0

R1

DC Voltage

1SDA0

12V DC

53001

2430 AC

51339

2430V DC

51339

4860V AC

51340

4860V DC

51340

110127V AC

51341

110125V DC

51341

220240V AC

51342

220250V DC

51342

380440V AC

51343

480500V AC

51344

R1

b). Undervoltage Release (UVR) (cabled Version)


AC Voltage

1SDA0

2430V AC

R1

51351

DC Voltage

1SDA0

2430V DC

R1

51351

48V AC

51352

48V DC

51352

60V AC

52335

60V DC

52335

110127V AC

51353

110127V DC

51353

220240V AC

51354

220250V DC

51354

380440V AC

51355

480500V AC

51356

c). Time lag device for UVR (UVD)


AC Voltage

1SDA0

24V AC

R1

DC Voltage

51357

1SDA0

24V DC

48V AC

51358

48V DC

51358

60V AC

51359

60V DC

51359

110125V AC

51360

110125V DC

51360

220250V AC

51361

220250V DC

51361

a)

b)

R1

51357

c)

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/30

Accessories Tmax T1, T2 and T3

1). Electrical Accessories cont....


d). Solenoid operator (inc padlock device)
Voltage

1SDA0
R1
Front Fitting

1SDA0
R1
Side by Side

4860V DC

51376

51379

110250V AC

51377

51380

e). Auxiliary Contacts (cabled version)


ON/OFF
(c/o)

Tripped
Position (c/o)

Release
Tripped (c/o)

Breaker Protection
Type

1SDA0

R1

Thermomagnetic

51370

Electronic

53704

Thermomagnetic

51371

f). Residual - current releases


RC221 and RC222 addon blocks
Breakers must be fitted with Front cable terminals for copper cables on lower terminals
( Terminal kit supplied with RCD addon kit for T2 and T3)
1SDA0
Breaker Type

R1

1SDA0

RC221

R1

RC222

3 Pole

4 Pole

3 Pole

4 Pole

T1

51398

51401

51400

51402

T2

51403

51405

51404

51406

T3

51407

51409

51408

51410

d)

e)

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/31

Accessories Tmax T1, T2 and T3

2). Mechanical Accessories


a). Direct Mounted Rotary Handles (RHD)
For Fixed/Plug-in devices - Grey/White

1SDA051381R1

For Fixed/Plug-in devices - Red/Yellow

1SDA051382R1

b). Door Mounted Rotary Handles (complete with transmission rod Lmax = 300mm) (RHE)
Adjustable depth
Padlockable
Complete with Door Interlock ( defeatable)
For Fixed/Plug-in devices - Grey/White

1SDA051383R1

For Fixed/Plug-in devices - Red/Yellow

1SDA051384R1

500mm transmission rod

1SDA051386R1

Optional Keylock

1SDA051389R1

IP54 Gasket

1SDA051392R1

c). Padlock Lever lock (PLL)


Padlock in OPEN Position

1SDA051393R1

Padlock in OPEN/CLOSED

1SDA051394R1

d). Mechanical Interlock across Two/ Three circuit breakers (MIF)


Between 2 circuit breakers

1SDA051396R1

Between 3 Circuit Breakers

1SDA052165R1

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/32

Accessories Tmax T1, T2 and T3

2). Mechanical Accessories Cont....


e). Terminals for fixed pattern MCCBs and Plug-in Bases
1SDA0
Terminal Type

T1
6 pieces 8 pieces

Extended Front (EF)


Spreaded Extended (ES)
Rear Terminals (R)

R1

T2

T3

6 pieces

8 pieces

6 pieces

8 pieces

51440

51441

51464

51465

51488

51489

51468

51469

51492

51493

51472

51473

51496

51497

Std

Std

51452

51453

51480

51481

1x95mm 2 External

51444

51445

1x95mm 2 Internal

51456

51457

1x185mm2 External

51460

51461

1x185mm2 Internal

51484

51485

140240mm2

51942

51943

Copper Front Cable terminals (FC Cu):


Cu/Al Front Cable terminals (FC CuAl):

External

f). Terminal covers

1SDA0
MCCB
T1
T2
T3

No of poles
3 poles

R1

High

Low

51415

51421

4 poles

51416

51422

3 poles

51417

51423

4 poles

51418

51424

3 poles

51419

51425

4 poles

51420

51426

g). Separating Partitions (PB)


Height

Qty

100mm

1SDA0

51427

R1
51428

100mm

200mm

51429

200mm

51430

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/33

Accessories Isomax S3, S4 and S5

1). Electrical Accessories


a). Shunt Trip
AC Voltage

1SDA0

R1

DC Voltage

1SDA0

12V DC
24V AC

13781

24V DC

13781

48V AC

13782

48V DC

13782

60V AC

23405

6072V DC

23405

110120V AC

13783

110125V DC

13783

220240V AC

13785

220250V DC

13785

380400V AC

13786

480V AC

37512

Wiring Connector:

Fixed pattern devices

13865

Wiring Connector:

Plug-in/Withdrawable devices

13866

b). Undervoltage Release (UVR)


AC Voltage
1SDA0
24V AC

R1

DC Voltage

13842

1SDA0

24V DC

48V AC

13843

48V DC

13835

23346

60V DC

13836

110127V AC

13844

110125V DC

13838

220250V AC

13846

220250V DC

13839

13847

480V AC

37513

Wiring Connector:

Fixed pattern devices

13865

Wiring Connector:

Plug-in/Withdrawable devices

13866

c). UVR + Time Lag Device

1SDA0

UVR + Delay: S3/S5

Input voltage 110220V AC only

13840

UVR + Delay: S6/S7

Input voltage 110220V AC only

14186

Wiring Connector:

Fixed pattern devices

13865

Wiring Connector:

Plug-in/Withdrawable devices

13866

a)

b)

R1

13833

60V AC

380440V AC

R1

23403

R1

c)

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/34

Accessories Isomax S3, S4 and S5

d). Direct acting Motor operator (inc padlock device)


AC Voltage
1SDA0
R1
DC Voltage

1SDA0

110127V AC

13875

24V DC

220240V AC

13876

4860V DC

13874

380V AC

13877

110125V DC

13875

440V AC

14545

220...250V DC

13876

R1

13873

e). Auxiliary Contacts


ON/OFF (c/o)

Tripped position (c/o)

Analogue (>24V)

Digital (<24V)

25545

Analogue (>24V)

13856

Digital (<24V)

25544

Signal type

1SDA0

R1

13575

Wiring connector when fitting motor & auxiliary contacts:


Fixed pattern devices

13857

Plug-in/Withdrawable devices

13858

Wiring connector when fitting auxiliary contacts only:


Fixed pattern devices

13863

Plug-in/Withdrawable devices

13864

e)

d)

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/35

Accessories Isomax S3, S4 and S5

1). Electrical Accessories cont....


f). Protection Release Trip Signal
X3/X4 Connector
Pattern
Protection Type
Fixed pattern

Plug-in/Withdrawable

1SDA0

PR211/LI

13702

PR212/LSI

13704

PR212/LSIG

13704

PR211/LI

13703

PR212/LSI

13705

PR212/LSIG

13705

g). External Neutral Current Transformer


MCCB
Current Rating

1SDA0

100A
S4

S5

Connector for Neutral CT


Pattern

Plug-in/Withdrawable

R1

37114

160A

37115

250A

37117

320A

37118

400A

37119

630A

37120

Protection Type

1SDA0

PR211/LI
Fixed pattern

R1

R1

13702

PR212/LSI

13704

PR212/LSIG

13704

PR211/LI

13703

PR212/LSI

13705

PR212/LSIG

13705

h). Residual-current release RC211 and RC212


Type

Vertical Mount
1SDA0

Side/side Mount
R1

RC211-S3

20289

20288

RC212-S3

20291

20290

RC211 and RC212 add on blocks for S3 breaker


Fitting by our workshop is recommended
4 pole circuit breaker/switch disconnector required

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/36

Accessories Isomax S3, S4 and S5

2). Mechanical Accessories


a). Direct Mounted Rotary Handles
1SDA0
For Fixed/Plug-in devices - Grey/White

R1

13867

For Fixed/Plug-in devices - Red/Yellow

13870

For Withdrawable devices - Grey/White

13868

b). Door Mounted Rotary Handles ( complete with transmission rod Lmax = 300mm)
Adjustable depth, Padlockable, complete with Door Interlock ( defeatable)

1SDA0

R1

For Fixed/Plug-in devices - Grey/White

13869

For Fixed/Plug-in devices - Red/Yellow

13871

For Withdrawable devices - Grey/White

50714

500mm transmission rod

25427

Optional Keylock

13881

IP54 Gasket

13891

c). Front Flange


Padlockable

1SDA0

R1

Fixed/ Plug-in devices

13889

Withdrawable devices

13890

Optional Keylock

13881

d). Mechanical Interlock across two circuit breakers


MCCB

Horizontal

Vertical
1SDA0

R1

S3

23330

23331

S4

13690

13691

S5

43453

43454

S3X

50524

S4X

50525

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/37

Accessories Isomax S3, S4 and S5

2). Mechanical Accessories Cont....


e). Terminal for Fixed Pattern MCCBs
Terminal kits consist of 6 or 8 pieces
kits of 3 or 4 pieces are available - consult technical catalogue for order references
Terminal Type

Extended Front (EF)

Max
Current
250A
400A

Copper Front Cable terminals (FC Cu)

R1
S5

6 pcs

8 pcs

6 pcs

8 pcs

6 pcs

8 pcs

13596

13597

13596

13597

13706

13707

46515

46516

46515

46516

47549

47550

250A

13606

13607

13606

13607

400A

13714

13715

630A

38968

38775

Spreaded Extended (ES)

Threaded rear stud (R)

1SDA0
S4

S3

250A

13598

13599

13598

13599

400A

13708

13709

630A

38767

38768

Cu/Al Front Cable terminals (FC CuAl) :


1x95mm

1x150mm
2x120mm
1x240mm

160A

13602

13603

13602

13602

250A

20293

20294

20293

20294

400A

23295

23296

400A

13710

13711

250A

13604

13605

13604

13605

400A

13712

13713

Cu/Al Rear cable terminals (RC CuAl)


1x120mm
1x240mm

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/38

Accessories Isomax S3, S4 and S5

2). Mechanical Accessories Cont....


f). Terminals for Plug-in and Withdrawable Bases
Terminal kits consist of 6 or 8 pieces
Terminal Type

Max Current

1SDA0
S4

S3

Extended Front (EF)

Threaded rear stud (R)

Cu/Al Front Cable terminals (FC CuAl) :

Vertical Flat Bar terminals (VR)

R1
S5

6 pcs

8 pcs

6 pcs

8 pcs

6 pcs

8 pcs

250A

13650

13651

13650

13651

400A

13759 13760

630A

38780 38781

250A

13654

13655

13654

13655

400A

13763 13764

630A

38969 38782

250A

13652

13653

13652

13653

400A

13760 13762

630A

38763 38784

g). Terminal Covers


Types available
High:

For fixed pattern devices

Low:

For Fixed pattern devices and for Moving parts of Plug-in and Withdrawable devices

FP High:

For Plug-in and Withdrawable Bases


1SDA0

MCCB
S3
S4
S5

No of poles

R1

High

Low

FP High

3 poles

13695

13693

13697

4 poles

13696

13694

13698

3 poles

13695

13693

13697

4 poles

13696

13694

13698

3 poles

13897

13895

13899

4 poles

13898

13896

13900

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/39

Accessories Isomax S6 and S7

1). Electrical Accessories


a). Shunt Trip
AC Voltage

1SDA0

24V AC

R1

14136

DC Voltage

1SDA0

12V DC

23404

24V DC

14136
14137

48V AC

14137

48V DC

60V AC

23406

6072V DC

23406

110120V AC

14138

110125V DC

14138

220240V AC

14140

220250V DC

14140

380400V AC

14141

480V AC

37512

R1

Shunt trip Wiring Connector


Fixed pattern devices
Plug-in/Withdrawable

S6

13865

S7

14209

S6

13866

S7

14210

b). Undervoltage Release (UVR)


AC Voltage

1SDA0

R1

DC Voltage

1SDA0

24V AC

14188

24V DC

48V AC

14189

48V DC

14181

60V AC

23347

60V DC

14182

R1

14179

110127V AC

14190

110125V DC

14184

220250V AC

14192

220250V DC

14185

380440V AC

14193

480V AC

37515

UVR Wiring Connector


Fixed pattern devices
Plug-in/Withdrawable

S6

13865

S7

14209

S6

13866

S7

14210

a)

b)

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/40

Distribution and Generator Protection MCCBs


Accessories Isomax S6 and S7

1). Electrical Accessories cont...


c). UVR + Time Lag Device
1SDA0
UVR + Delay:

Input voltage 110220V AC only

R1

14186

Wiring Connector:
Fixed pattern devices
Plug-in/Withdrawable

S6

13865

S7

14209

S6

13866

S7

14210

d). Stored Energy Motor operator


AC Voltage

1SDA0
S6

110127V AC

14031

R1

DC Voltage

1SDA0

S7

S6

R1
S7

24V DC

14029

14214

48V DC

14030

14215

60V DC

23348

23350

14216

110125V DC

14031

14216

220250V DC

14032

14217

220250V AC

14032

14217

380V AC

14033

14218

Motor Op Wiring Connector


S6

Fixed pattern devices


Plug-in/Withdrawable

13857

S7

14203

S6

13858

S7

14204

S6/S7

13885

Optional Keylock
Lock against manual and electrical operation

d)
c)

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/41

Distribution and Generator Protection MCCBs


Accessories Isomax S6 and S7

1). Electrical Accessories cont....


e). Auxiliary Contacts
On/Off
(c/o)

Tripped pos On/Off


(c/o)
(1no & 1nc)

Tripped position
(no)

Analogue (>24V)

Digital (<24V)

25775

Analogue (>24V)

23366

Digital (<24V)

25774

Analogue (>24V)

48956

Signal type
1SDA0

Digital (<24V)

R1
23332

Wiring connector when fitting motor & and auxiliary contacts:


Fixed pattern devices
Plug-in/Withdrawable

S6

13857

S7

14203

S6

13858

S7

14204

Wiring connector when fitting auxiliary contacts only:


Fixed pattern devices
Plug-in/Withdrawable

S6

13863

S7

14207

S6

13864

S7

14208

f). Protection Release Trip Signal


X3/X4 Connector
Pattern
Fixed pattern

Plug-in/Withdrawable

Protection Type
PR211/LI

13702

PR212/LSI

13704

PR212/LSIG

13704

PR211/LI

13703

PR212/LSI

13705

PR212/LSIG

13705

e)

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/42

Distribution and Generator Protection MCCBs


Accessories Isomax S6 and S7

1). Electrical Accessories Cont....


g). External Neutral Current Transformer
MCCB
S6

S7

Current Rating

1SDA0

R1

630A

25777

800A

25778

1000A

25779

1250A

25780

1600A

25781

X3/X4 Connector
Pattern

Protection Type
PR211/LI

13702

Fixed pattern

PR212/LSI

13704

Plug-in/Withdrawable

1SDA0

R1

PR212/LSIG

13704

PR211/LI

13703

PR212/LSI

13705

PR212/LSIG

13705

2). Mechanical Accessories


a). Direct Mounted Rotary Handles
1SDA0
TypeColour

S6

For Fixed/Plug-in devices


For Withdrawable devices - Grey/White

R1
S7

Grey/White

14026

14211

Red/Yellow

14027

14212

Grey/White

46568

46570

b). Door Mounted Rotary Handles ( complete with transmission rod Lmax = 500mm)
Adjustable depth padlockable, complete with door interlock ( defeatable)
Type
Colour
For Fixed/Plug-in devices
For Withdrawable devices - Grey/White

1SDA0
S6

R1
S7

Grey/White

14028

14213

Red/Yellow

46569

46572

Grey/White

50715

50716

Optional Keylock

13881

IP54 Gasket

13891

c). Front Flange


1SDA0
S6

Padlockable

R1
S7

Fixed/ Plug-in devices

14035

14227

Withdrawable devices

14036

14228

Optional Keylock

13881

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/43

Accessories Isomax S6 and S7

2). Mechanical Accessories Cont....


d). Mechanical Interlock across two circuit breakers
MCCB

Horizontal Vertical
1SDA0
R1

S6

14024

14025

S7

14205

14206

e). Terminals for fixed pattern MCCBs


Terminal kits consist of 6 or 8 pieces
kits of 3 or 4 pieces are available - consult technical catalogue for order references
Terminal Type

Max Current
1SDA0
R1
S6

S7

6 pcs

8 pcs

6 pcs

630A

13920

13921

800A

13954

13955

1600A

14079

14080

Spreaded Extended (ES)

1600A

50690

50691

Threaded rear stud (R)

800A

13960

13961

2x240mm2

630A

13922

13923

3x185mm2

800A

13956

13957

4x240mm 2

1250A

14081

14082

2x150mm2

630A

13924

13925

3x240mm

800A

13958

13959

1600A

14083

14084

Extended Front (EF)

8 pcs

Cu/Al Front Cable terminals (FC CuAl)

Cu/Al Rear cable terminals (RC CuAl)


2

Horizontal/Vertical Flat Bar terms (HR/VR)

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/44

SACE Isomax S circuit-breakers for


motor protection (protection against short-circuit)

Three-phase asynchronous motor starting, switching and protection are essential operations for its correct use. The traditional system
used for this purpose has three different devices: a circuit-breaker for protection against short-circuit, a thermal relay for protection
against overload and lack of or unbalanced phase, and a counter for the motor operations. Everything must necessarily take into account
the problems which arise on start-up.
In particular, these different factors must be taken into account when selecting these devices, such as:
- the motor power
- the starting diagram
- the type of motor: with cage rotor or with wound rotor
- the fault current at the point of motor installation in the network
ABB SACEproposes a wide range of circuit-breakers, which by implementing the protection against short-circuit exclusively, are suitable
for use inside protected starters of traditional type.
The new SACE T2 with fixed magnetic protection is an extremely compact circuit-breaker, which stands out for its exceptional performances in terms of breaking capacity and limitation of the specific let-through energy.
It can be used in a vast range of start-ups, from 0.37kW to 37kW and from 400V-50kA up to 690V-50kA. SACE S3 N/H/L 160/250 circuit
breakers and the S3X 125/200 current-limiting circuit-breaker are fitted with a magnetic only release adjustable from 4 to 12 time the rated
service current. They cover coordinations from 37 to 132kW and allow optimal motor protection thanks to their great flexibility due to the
wide setting range of the magnetic threshold.
Finally, SACES4 160/250, S5 400/630, S6 630/800, and S7 1250/1600, with different capacity levels, like the current-limiting S4X and
S6X, can be fitted with the PR211/P (I) electronic microprocessor-based release. Above all, they are used for protection of high power
motors and, thanks to adjustment of the protection against short-circuit from 1.5 to 12 times, allow the optimumtrip value to be selected
for any motor type.

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/46

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/47

Motor Protection MCCBs


Tmax T2N (160A)

Ratings @ 415V
Icu

Ics

T2N

36kA

100%

T2S

50kA

100%

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx

Icu (415V)

Model

Current (A)
In

36kA

1SDA0

R1

MF

MA

3 Pole

3 Pole

3 Pole

PR221DS/I
4 Pole

T2N160R1

1A

53110

T2N160R1.6

1.6A

53111

T2N160R2

2A

53112

T2N160R2.5

2.5A

53113

T2N160R3.2

3.2A

53114

T2N160R4

4A

53115

T2N160R5

5A

53116

T2N160R6.5

6.5A

53117

T2N160R8.5

8.5A

53118

T2N160R10

10A

51163

51169

T2N160R11

11A

53119

T2N160R12.5

12.5A

53120

T2N160R20

20A

51207

T2N160R25

25A

51164

51170

T2N160R32

32A

51208

T2N160R52

52A

51209

T2N160R63

63A

51165

51171

T2N160R80

80A

51210

T2N160R100

100A

51211

51166

51172

T2N160R160

160A

51168

51617

for accessories see page x/xx

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/48

Motor Protection MCCBs


Tmax T2S (160A)

Protection types available


Type

Settings

Electronic

PR221DS/I

1 - 10x In

Magnetic Only

Im

Fixed Magnetic (MF)

13x In

Adjustable Magnetic (MA)

612x In

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx

Icu (415V)

Model

Current (A)
In

50kA

1SDA0

R1

MF

MA

3 Pole

3 Pole

3 Pole

PR221DS/I
4 Pole
-

T2S160R1

1A

53121

T2S160R1.6

1.6A

53122

T2S160R2

2A

53123

T2S160R2.5

2.5A

53124

T2S160R3.2

3.2A

53125

T2S160R4

4A

53126

T2S160R5

5A

53127

T2S160R6.5

6.5A

53128

T2S160R8.5

8.5A

53129

T2S160R10

10A

T2S160R11

11A

T2S160R12.5

12.5A

51174

51179

53130

53131

--

T2S160R20

20A

51216

T2S160R25

25A

51175

51180

T2S160R32

32A

51217

T2S160R52

52A

51218

T2S160R63

63A

51176

51181

T2S160R80

80A

51219

T2S160R100

100A

51220

51177

51182

T2S160R160

160A

51178

51618

for accessories see page x/xx

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/49

Motor Protection MCCBs


Tmax T3 (250A)

Ratings @ 415V
Icu

Ics

Protection types available


Type

T3N

36kA

75%

Magnetic Only

T3S

50kA

50%

Adjustable Magnetic (MA)

Settings
612x In

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals see
accessories section pagexx

Icu (415V)

36kA

50kA

Model

Current (A)
I th

1SDA0
R1
MA 3 Pole

T3N250R100

100A

51315

T3N250R125

125A

51316

T3N250R160

160A

51317

T3N250R200

200A

51318

T3S250R100

100A

51320

T3S250R125

125A

51321

T3S250R160

160A

51322

T3S250R200

200A

51323

Plug-in Circuit breakers


To convert fixed pattern device to plug-in pattern:1). Select correct Fixed Pattern Device from part numbers above
2). Select Conversion Kit from part numbers below
3). Add Fixed portion (Base) from part numbers below

1SDA0

R1

Plug-in

3 Pole

4 Pole

Conversion Kit

51413

51414

51331

51332

Fixed portion (Base)


Front Copper Cable Terminals**
**for other terminals see accessories section pagexx

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/50

Accessories Isomax S6 and S7

2). Mechanical Accessories Cont....


f). Terminals for Plug-in and Withdrawable Bases
Terminal kits consist of 6 or 8 pieces
Terminal Type

Max Current

1SDA0

R1

S6

Extended Front (EF)


Horizontal Flat Bar (HR)
Vertical Flat Bar terminals (VR)

S7

6 pieces

8 pieces

6 pieces

800A

13984

13985

8 pieces
-

1600A

14108

14109

800A

13986

13987

1600A

14110

14111

800A

13988

13989

1600A

14112

14113

g). Terminal Covers


Types available
High:
Low:
FP High:

For fixed pattern devices


For Fixed pattern devices and for Moving parts of Plug-in and
Withdrawable devices
For Plug-in and Withdrawable Bases

MCCB

No of poles

1SDA0

S6
S7

R1

High

Low

FP High

3 poles

14040

14038

4 poles

14041

14039

3 poles

23324

4 poles

23325

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/45

Motor Protection MCCBs


Isomax S3N, H, L (250A)

Ratings @ 415V
Icu

Ics

S3N

35kA

100%

All breakers are Magnetic Only with adjustable

S3H

65kA

75%

settings AVAILABLE IN 3 POLE ONLY

S3L

85kA

75%

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals &
accessories section pagexx

Icu (415V)

35kA

65kA

85kA

Model

Current (A)

1SDA0

Im

3 Pole

S3N160RM3

1236A

47782

S3N160RM5

2060A

47783

S3N160RM10

40120A

47784

S3N160RM25

100300A

47785

S3N160RM50

200600A

47786

S3N160RM100

4001200A

47787

S3N160RM125

5001500A

47788

S3N160RM160

6401600A

47789

S3N250RM160

6401920A

48651

S3N250RM200

8002400A

48654

S3H160RM50

200600A

45185

S3H160RM100

4001200A

45186

S3H160RM125

5001500A

45187

S3H160RM160

6401600A

45188

S3H250RM160

6401920A

48657

S3H250RM200

8002400A

48658

S3L160RM50

200600A

50544

S3L160RM100

4001200A

50545
50546

S3L160RM125

5001500A

S3L160RM160

6401600A

50547

S3L250RM160

6401920A

50548

S3L250RM200

8002400A

50549

R1

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/51

Motor Protection MCCBs


Isomax S3X (250A)

Ratings @ 415V
S3X

Icu

Ics

200kA

100%

All breakers are Magnetic Only with adjustable


settings AVAILABLE IN 3 POLE ONLY

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals &
accessories section pagexx

Icu (415V)

Model

Current (A)

1SDA0

Im

200kA

R1

3 Pole

S3X125RM25

100300A

45387

S3X125RM50

200600A

45388

S3X125RM100

4001200A

45389

S3X125RM125

5001500A

45390

S3X200RM125

5001500A

46135

S3X200RM160

6401920A

48659

S3X200RM200

8002400A

48660

Plug-in and Withdrawable Circuit breakers


To convert fixed pattern device to plug-in or withdrawable pattern:1). Select correct Fixed Pattern Device from part numbers above
2). Select Conversion Kit from part numbers below
3). Add Suitable Fixed portion (Base) from part numbers below
Special Notes:
a).Withdrawable devices must be fitted with a front plate accessory such as:
Motor operator
Padlock Device
Rotary Handle
b). Remember to use accessories suitable for Plug-in or withdrawable pattern devices

Plug-in

Withdrawable
1SDA0

R1

3 Pole

4 Pole

3 Pole

4 Pole

46519

46520

46521

46522

Front Copper Cable Terminals

13543

13550

13559

13568

Extended Front bar Terminals

13539

13548

13555

13564

Threaded Rear Terminals

13547

13554

13563

13572

Conversion Kit
Fixed

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/52

Motor Protection MCCBs


Isomax S4N, H, L, X (250A)

Ratings @ 415V
Icu

Ics

Protection types available


Electronic (ac only)
Type

S4N

35kA

100%

S4H

65kA

100%

Settings

S4L

100kA

75%

PR212/I

S4X

200kA

100%

PR212/LR

1.5 - 12x In

0.4 - 1x In

3 - 10x In

6 - 12x In

ON/OFF

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals &
accessories section pagexx
Icu (415V)

Model

Current (A)
Ith

1SDA0
3 Pole

35kA

65kA

100kA

200kA

R1
PR212/LRIU

PR211/I
4 Pole

3 Pole Only

S4N160R100

100A

15548

15836

50139

S4N160R160

160A

15549

15837

50140

S4N250R200

200A

50141

S4N250R250

250A

17318

17384

S4H160R100

100A

16142

16424

45049

S4H160R160

160A

16143

16425

45050

S4H250R200

200A

48662

S4H250R250

250A

17450

17516

S4L160R100

100A

16730

17012

50550

S4L160R160

160A

16731

17013

50551

S4L250R200

200A

50552

S4L250R250

250A

17582

17648

S4X250R100

100A

46590

S4X250R160

160A

46591

S4X250R200

200A

48661

Plug-in and Withdrawable Circuit breakers


To convert fixed pattern device to plug-in or withdrawable pattern:1). Select correct Fixed Pattern Device from part numbers above
2). Select Conversion Kit from part numbers below
3). Add Suitable Fixed portion (Base) from part numbers below
Special Notes:
a).Withdrawable devices must be fitted with a front plate accessory such as:
Motor operator, Padlock Device, Rotary Handle
b). Remember to use accessories suitable for Plug-in or withdrawable pattern devices

Plug-in
S4N/H/L
Conversion Kit

Withdrawable
S4X

S4N/H/L

S4X

3 Pole

4 Pole

3Pole

3 Pole

4 Pole

3Pole

13608

13609

46511

13610

13611

46521

Fixed portion (Base)


Front Copper Cable Terminals

13543

13550

13634

13643

Extended Front bar Terminals

13612

13621

13630

13639

Threaded Rear Terminals

13547

13554

13638

13647

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/53

Motor Protection MCCBs


Isomax S5 (630A)

Protection types available


Electronic (ac only)

Ratings @ 415V
Icu

Ics

Icw (1sec)

S5N

35kA

100%

5kA

S5H

65kA

100%

5kA

PR211/I

S5L

100kA

75%

5kA

PR212/LRIU 0.4-1x In

Type

Settings
L

0.4-1x In

1.5-12x In
3-10x In

6-12x In ON/OFF

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals &
accessories section pagexx

Icu (415V)

35kA

65kA

100kA

Model

Current (A)
Ith

1SDA0
PR211/I

R1
PR212/LRIU

3 Pole

4 Pole

3 Pole Only

S5N400R320

320A

17714

17846

50142

S5N400R400

400A

17715

17847

S5N630R630

630A

38674

38679

S5H400R320

320A

17990

18122

45051

S5H400R400

400A

17991

18123

S5H630R630

630A

38704

38709

50553

S5L400R320

320A

18254

18386

S5L400R400

400A

18255

18387

S5L630R630

630A

38736

38741

Plug-in and Withdrawable Circuit breakers


To convert fixed pattern device to plug-in or withdrawable pattern:1). Select correct Fixed Pattern Device from part numbers above
2). Select Conversion Kit from part numbers below
3). Add Suitable Fixed portion (Base) from part numbers below
Special Notes:
a). Withdrawable devices must be fitted with a front plate accessory such as:
Motor operator, padlock device, rotary handle
b). Remember to use accessories suitable for Plug-in or withdrawable pattern devices

400A
1SDA0
Plug-in
Conversion Kit

R1
Withdrawable

630A
1SDA0
R1
Withdrawable

3 Pole

4 Pole

3 Pole

4 Pole

3 Pole

4 Pole

13716

13717

13718

13719

38778

38779

Fixed portion (Base)


Front Copper Cable Terminals (400A)

13724

13733

13742

13751

Extended Front bar Terminals

13720

13729

13738

13747

Spreaded Ext Front bar Terminals

38761

38762

Threaded Rear Terminals

13728

13737

13746

13755

38763

38970

Vertical Flat bar Terminals

38971

38972

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/54

Motor Protection MCCBs


Isomax S6 (800A)

Ratings @ 415V
Icu

Ics

Protection types available


Electronic (ac only)

S6N

35kA

100%

Type

S6S

50kA

100%

S6H

65kA

100%

PR211/I

S6L

100kA

75%

PR212/LRIU

S6X

200kA

100%

Settings
L

1.5-12x In
0.4-1x In

3-10x In

6-12x In

ON/OFF

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals &
accessories section pagexx
Icu (415V)

35kA

50kA

65kA

100kA

200kA

Model

Current (A)
Ith

S6N630R630

630A

S6N800R630

630A

S6N800R800

800A

1SDA0
PR211/I

R1
PR212/LRIU

3 Pole

4 Pole

3 Pole Only

18518

18572

50143

18950

19004

S6S630R630

630A

18626

18680

S6S800R800

250A

19058

19112

S6H630R630

630A

18734

18788

S6H800R630

630A

45052

S6H800R800

800A

19166

19220

S6L630R630

630A

38736

38741

S6L800R630

630A

50554

S6L800R800

800A

19274

19328

47780

S6X400R320

320A

47595

47601

S6X400R400

400A

46534

46538

S6X630R400

400A

47781

S6X630R630

630A

46560

46564

48663

Withdrawable Circuit breakers


To convert fixed pattern device to withdrawable pattern:1). Select correct Fixed Pattern Device from part numbers above
2). Select Conversion Kit from part numbers below
3). Add Suitable Fixed portion (Base) from part numbers below
Special Notes:
a).Withdrawable devices must be fitted with a front plate accessory such as:
Motor operator, Padlock Device, Rotary Handle
c). Remember to use accessories suitable for withdrawable pattern devices
1SDA0

R1

S6N/S/H/L
Conversion Kit

S6X

3 Pole

4 Pole

3 Pole

13962

13963

47619

Fixed portion (Base)


Extended Front bar Terminals

13964

13973

13964

Horizontal Flat bar Terminals

13968

13977

13968

Vertical Flat bar Terminals

14096

14105

14096

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/55

Motor Protection MCCBs


Isomax S7 (1250A)

Protection types available


Electronic (ac only)

Ratings @ 415V
Icu

Ics

S7S

50kA

100%

S7H

65kA

100%

PR211/I

S7L

100kA

75%

PR212/LRIU

Type

Settings
L

1.5-12x In
0.4-1x In

3-10x In

6-12x In

ON/OFF

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals &
accessories section pagexx
Icu (415V)

50kA

65kA

100kA

Model

Current (A)
Ith

1SDA0
PR211/I

R1
PR212/LRIU

3 Pole

4 Pole

3 Pole Only

S7S1250R1000

1000A

19382

19490

50144

S7S1250R1250

1250A

19383

19491

S7H1250R1000

1000A

19598

19706

45053

S7H1250R1250

1250A

19599

19707

S7L1250R1000

1000A

19814

19922

S7L1250R1250

1250A

19815

19923

Withdrawable Circuit breakers


To convert fixed pattern device to withdrawable pattern:1). Select correct Fixed Pattern Device from part numbers above
2). Select Conversion Kit from part numbers below
3). Add Suitable Fixed portion (Base) from part numbers below
Special Notes:
a).Withdrawable devices must be fitted with a front plate accessory such as:
Motor operator, Padlock Device, Rotary Handle
c). Remember to use accessories suitable for withdrawable pattern devices

Withdrawable
1SDA0
Conversion Kit

R1

3 Pole

4 Pole

23299

14087

Fixed portion (Base)


Extended Front bar Terminals

48951

14097

Horizontal Flat bar Terminals

14092

14105

Vertical Flat bar Terminals

14096

14101

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/56

Current Limiting MCCBs


Tmax T2, Isomax S3X, S4X, S6X

Applications
These current-limiting circuit-breakers are suitable for installation in all types of civil, industrial and service sector installations, as well as for electrical installations on board ships, in mines or on oil rigs, as well as, generally speaking, in any installations where high power generators and transformers make it possible for very high short-circuit currents of up to 200kA at
380/415 V~, 180 kA at 440 V~ and 75 kA at 690 V~ to occur.
The circuit-breakers can be positioned downstream of the power supply either to provide general protection (installations,
multi-user systems and electrical lines) or for protecting electrical equipment (motors, generators, transformers and capacitors).
They can also be fitted in systems where back-up protection is required that allows the use of circuit-breakers downstream
which have a lower breaking capacity than the prospective short-circuit current in the point of installation.
The breaking capacities of the SACE current-limiting circuit-breakers are higher than the best values achieved by other units
of this type.

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/57

Current Limiting MCCBs


Tmax T2 (160A)

Icu

Ics

Protection types available


Type
Electronic

85kA

75%

PR221DS/LS

Ratings @ 415V
T2L

Settings
L

0.4 - 1x I n

1 - 10x I n

Thermomagnetic

Ith

Im

70-100%

10x Ith*

Low Threshold Thermomagnetic 70-100%

10x Ith

Standard Distribution

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals &
accessories section pagexx
Icu (415V)

Model

Standard

Low Threshold
1SDA0
R1

PR221DS/LS

3 Pole

4 Pole

3 Pole

4 Pole

3 Pole

4 Pole

1.6A

51072

51094

2A

51073

51095

T2L160R2.5

2.5A

51074

51096

T2L160R3.2

3.2A

51075

51097

T2L160R4

4A

51076

51098

T2L160R5

5A

51077

51099

T2L160R1.6
T2L160R2

T2L160R6.3

6.3A

51078

51100

T2L160R8

8A

51079

51101

T2L160R10

10A

51080

51102

51153

51158

T2L160R12.5
85kA

Current (A)
Ith

T2L160R16

12.5A

51081

51103

16A

51082

51104

T2L160R20

20A

51083

51105

T2L160R25

25A

51084

51106

51154

51159

T2L160R32

32A

51085

51107

T2L160R40

40A

51086

51108

T2L160R50

50A

51087

51109

T2L160R63

63A

51088

51110

51155

51160

T2L160R80

80A

51089

51111

T2L160R100

100A

51090

51112

51156

51161

T2L160R125

125A

51091

51121

T2L160R160

160A

51092

51122

51157

51162

Plug-in Circuit breakers


To convert fixed pattern device to plug-in pattern:1). Select correct Fixed Pattern Device from part numbers above
2). Select Conversion Kit from part numbers below
3). Add Fixed portion (Base) from part numbers below
Plug-in
1SDA0
Conversion Kit

R1

3 Pole

4 Pole

51411

51412

51329

51330

Fixed portion (Base)


Front Copper Cable Terminals**

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/58

Current Limiting MCCBs


Isomax S3X, S4X, S6X

Protection types available


Ratings @ 415V
Icu

Ics

Type
Electronic

S3X

200kA

100%

PR211/LI

0.4-1x In

S4X

200kA

100%

PR212/LSI

0.4-1x In

1-10x In

1.5 - 12x In

100%

PR212/LSIG 0.4-1x In

1-10x In

1.5-12x In

S6X

200kA

Settings
L

Thermomagnetic
Standard Distribution

1.5-12x In

Ith

Im

70-100%

5-10x Ith

0.2-1x In

Fixed Pattern Circuit Breaker


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Supplied as standard with front bar terminals for busbar - for other terminals &
accessories section pagexx

Icu (415V) Model

S3X

S4X

S4X

S4X

S6X

S6X

S6X

Thermomagnetic

Current (A)
In/Ith

Protection
3 Pole

S3X125R32

32A

T/Mag

45197

S3X125R50

50A

T/Mag

S3X125R80

80A

PR211

PR212

1SDA0

R1

4 Pole

3 Pole

4 Pole

3 Pole

4 Pole

45207

45199

45209

T/Mag

45201

45211

S3X125R100 100A

T/Mag

45203

45213

S3X125R125 125A

T/Mag

45205

45215

S3X200R125 125A

T/Mag

46039

46045

S3X200R160 160A

T/Mag

46041

46047

S3X200R200 200A

T/Mag

46043

46049

S4X250R100 100A

S4X250R160 160A

S4X250R250 250A

S6X400R320 320A

S6X400R400 400A

S6X630R630 630A

LI

46584

46594

LSI

46586

46596

LSIG

46588

46598

LI

46585

46595

LSI

46587

46597

LSIG

46589

46599

LI

46525

46529

LSI

46526

46530

LSIG

46527

46531

LI

47596

47602

LSI

47597

47603

LSIG

47598

47604

LI

46535

46539

LSI

46536

46540

LSIG

46537

46541

LI

46561

46565

LSI

46562

46566

LSIG

46563

46567

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/59

Emax Air Circuit Breaker Electrical Specifications

Description
Voltages

Rated Service Voltage


Rated Insulation Voltage
Rated Impulse Voltage

Ue [V]
Ui [V]
Uimp [kV]

690(ac) 250(dc)
1000
12

Temperature Service
Storage

C
C

-5...+70
-40...+70

Performance Level
Rated uninterrupted current @ 40VC

Iu

[A]
[A]
[A]
[A]
[A]

Capacity of neutral on 4 pole breakers

% Iu

Rated ultimate short circuit breaking capacity


220/230/380/400/415 Vac
440 Vac
500/660/690 Vac
250Vdc

Icu

Rated duty short circuit breaking capacity


220/230/380/400/415 Vac
440 Vac
500/660/690 Vac
250 Vdc

Ics

Rated short time withstand current


1 sec
3 secs

Icw

Rated short circuit making capacity


220/230/380/400/415 Vac
440 Vac
500/600/690 Vac

Icm

E1

E2

800
1250
-

1600
2000
-

1250
1600
2000
-

1250
1600
-

100%

[kA]
[kA]
[kA]
[kA]

50
50
36
36

42
42
42
40

65
65
55
55

130
110
85
-

[kA]
[kA]
[kA]
[kA]

50
50
36
36

42
42
42
42

65
65
55
55

130
110
65
-

[kA]
[kA]

50
36

42
42

55
42

10
-

[kA]
[kA]
[kA]

105
105
75.6

88.2
88.2
88.2

143
143
121

286
242
187

[mS]
[mS]
[mS]

80
70
30

80
70
30

80
70
30

80
70
12

[mm]
[mm]

296/386
324/414

[kg]
[kg]

45/54
70/82

Utilisation category (according to BS EN 60947-2)


Microprocessor-based releases for a.c. applications operating time
Closing time (max)
Break time for I < Icw (max)
Break time for I > Icw (max)

100%

Dimensions
Fixed (H=418mm D=302mm W=3/4 pole)
Drawout (H=461mm D=396.5mm W=3/4 pole)

296/386
324/414

Weight
Fixed 3/4 pole
Drawout 3/4 pole

Rated uninterrupted current @ 40C


Iu
Mechanical Life (with routine maintenance)
Frequency
Electrical Life
Frequency

[A]
[ops x 1000]
[No. ops per Hr]
[ops x 1000]
[No. ops per Hr]

800/1250
25
60
10
30

50/61
78/93

50/61
78/93

52/63
8095

1250

1600

25(B-N) 10 (L)

25 (B-N) 20(L)

2000
25
60
10
30

60

60

15(B-N) 4(L)

12(B-N) 3(L)

30

30

Return to main index

ABB LIMITED

4/60

E3

E4 E4

E3

E6
E6

H/b

S/f

H/f

2500
3200
-

1250
1600
2000
2500
3200

1250
1600
2000
2500
3200

1250
1600
2000
2500
3200

2000
2500
-

4000
-

3200
4000
-

3200
4000
-

5000
6300
-

5000
6300
-

50%

100%

50%

50%

100%

100%

65
65
65
65

75
75
75
75

80
80
75
75

100
100
85
75

130
110
85
-

75
75
75
75

80
80
75
75

100
100
85
100

100
100
100
100

100
100
100
100

65
65
65
65

75
75
75
75

80
80
75
75

85
85
85
75

130
110
65
-

75
75
75
75

80
80
75
75

100
100
85
100

100
100
100
100

100
100
100
100

65
65

75
65

80
-

75
65

15
-

75
75

80
-

100
75

100
85

100
-

143
143
143

165
165
165

176
176
165

220
220
187

286
242
187

165
165
165

176
176
165

220
220
187

220
220
220

220
220
220

80
70
30

80
70
30

80
70
30

80
70
30

80
70
12

80
70
30

80
70
30

80
70
30

80
70
30

80
70
30

556/656
594/684

757*
778*

556/656
594/684

782/908
810/936

1045*
1062*

404/530
432/558

66/80
104/125

66/80
104/125

1250
20
60
12
20

1600
20
60
10
20

66/80
104/125

66/80
104/125

72/83
110/127

97/117
147/165

132*
211*

97/117
147/165

140/160
210/240

193*
295*

2000

2500

20 (N-S-H) 15(L)

20 (N-S-H) 15(L)

3200
20
60
6
20

3200
15
60
7
10

4000
12
60
5
10

3200
12
60
5
10

4000
12
60
4
10

60

60

9 (N-S-H) 2(L)

8(N-S-H) 1.8(L)

20

20

Return to main index

ABB LIMITED

4/61

Emax Air Circuit Breakers


Microprocessor-based overcurrent releases

General specificications of the microprocessor-based releases include:


operation without the need for an external power supply
microprocessor technology (8-bit for SACE PR111 and 16-bit for SACE PR112 and PR113)
high precision
sensitivity to the true r.m.s. value of the current
interchangeability among all types of releases
setting for neutral normally 50% of setting phases, with possibility of setting it to 100% (on request
only for circuit -breakers E1, E2, E3 standard and 4/f, E6/f full size versions).

For the release PR113, it is also possible to select neutral protection at 150% and 200% of the rated
current of the phases, if compatible with the setting of the current transformers.
The main performance features of the releases are listed in the tables below.

SACE PR111
Protection

PR111/P

PR111/P

L S I G

L S I

PR111/P

L I

SACE PR112
Protection

PR112/P

PR112/P

L S I G

L S I

PR112/PD
Modbus
Protection &
Communication L S I G

SACE PR113

PR112/PD PR112/PD
Modbus
LON

L S I

L S I G

PR112/PD
LON

L S I

PR113/P
Protection

Protection &
Communication

L S I G

OT

UV

OV

RV

RP

OT

UV

OV

RV

RP

PR113/PD
Modbus

L S I G

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/62

Emax Air Circuit Breakers


Microprocessor-based overcurrent releases

Protection Functions

PR111

Inverse long time-delay trip overload protection


Adjustable-slope curve (IEC 60255-3)

Selective short-circuit protection with inverse or definite


short time-delay trip

Instantaneous short-circuit protection with adjustable


trip current threshold

source ground return (external sensor)


Directional short-circuit protection with adjustable delay

Protection against phase umbalance

OT

Protection against over temperature

RV

PR113

residual (internal sensor)

Earth fault protection

OV UV

PR112

Undervoltage and overvoltage protection


Residual voltage protection / neutral displacement protection

RP

Reverse power protection

Thermal memory for L and S functions

Measurements
Currents (phases, neutral, earth fault)
Voltage (phase-phase, phase-neutral, residual)
Power (active, reactive, apparent)
Power factor
Frequency and peak factor
Energy (active, reactive, apparent, counter)
Harmonics calculation (displays waveform and module of the harmonics)
Maintenance events and data
Events stored in chronological order
Counting number of operations and contact wear
Communication with centralized supervision and control system
Remote setting of parameters for protection functions, unit configuration and communication
Transmission of measurements, states and alarms from circuit-breaker to system
Transmission of maintenance events and data from circuit-breaker to system
Self-test
Alarm and tripping for release overtemperature
Alarm for microprocessor fault
User interface
Parameters set using DIP switches
Parameters set using keys and liquid crystal display
Alarm signals for L, S, I and G functions
Alarm signalling one of the following protections: undervoltage, overvoltage, residual voltage, reverse power
Imbalance phase and overtemperature signal
Complete management of pre-alarms and alarms for all protection and self monitoring functions
Password for use with READ or EDIT mode
Load control
Connection-disconnection of loads in relation to the current flowing through the circuit breaker
Zone selectivity
May be activated for protection functions S or G
May be activated for protection funcions S, G or D
Number of programmable contacts
Start-up function S, D, I and G

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/63

Emax Air Circuit Breakers


Automatic circuit-breakers with full-size neutral conductor

The Emax range of automatic circuit-breakers with full size neutral conductor is used in special applications where the presence of triple-N harmonics on individual phases may lead to a very high current
on the neutral conductor.
Typical applications include installations with loads having high harmonics distortions (computers and
electronic devices in general), lighting systems with a large number of fluorescent lamps, systems with
inverters and rectifiers, UPS, systems for adjusting the speed of electric motors.
This range includes standard circuit-breakers with full-size neutral conductor in sizes E1, E2, E3.
Models E4 and E6 are available in the full size version up to rated currents of 6300A. Models E4/f
and E6/f are available in fixed and withdrawable four-pole versions. These models may be fitted with
all accessories available of the Emax range; the exception, on the E6/f model, are the mechanical
interlocks made using flexible wires and 15 external auxiliary contacts, which are therefore incompatible.
All the models may be fitted with all available version of electronic protection relays, in the standard
version.

Rated uninterrupted current (at 40C) Iu

[A]

E4S/f

E6H/f

4000

5000

[A]

6300

Number of poles

[V~]

690

690

220/230/380/400/415 V ~

[kA]

80

100

440 V ~

[kA]

80

100

500/660/690 V ~

[kA]

75

100

Rated service voltage Ue


Rated ultimate short-circuit breaking capacity Icu

Rated service short-circuit breaking capacity Ics


220/230/380/400/415 V ~

[kA]

80

100

440 V ~

[kA]

80

100

500/660/690 V ~

[kA]

75

100

Rated short-time withstand current Icw


(1s)

[kA]

80

100

(3s)

[kA]

75

85

[kA]

176

220

Rated short-circuit making capacity (peak value) Icm


Application category (in accordance with IEC 60947-2)
Isolation behavior (in accordance with IEC 60947-2)

Overall dimensions
Fixed: H= 418mm - D= 302mm L

[mm]

746

1034

Withdrawable: H=461 - D= 396.5mm L

[mm]

774

1062

Weights (circuit-breaker complete with releases and CT, not including accessories)
Fixed

[kg]

120

165

Withdrawable (including fixed part)

[kg]

170

250

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/64

Emax Air Circuit Breakers


Switch-disconnectors

The switch-disconnectors are derived from the corresponding automatic circuit-breakers, of which
they maintain the overall dimensions and the possibility of mounting accessories.
This version differs from the automatic circuit-breakers only in the absence of overcurrent releases.
The circuit-breaker is available in both fixed and withdrawable versions, three-pole and four-pole. The
switch-disconnectors, identified by the label /MS, may be used according to the category of use AC23A (switching motor loads or other highly inductive loads) in accordance with the standard IEC
60947-3. The electrical specifications of the switch-disconnectors are listed below.

Rated uninterrupted current (at 40C) Iu

E1B/MS

E1N/MS

E2B/MS

E2N/MS

E3N/MS

E3S/MS

[A]

800

800

1600

1250

2500

1250

E4S/MS E4S/fMS
4000

4000

E4H/MS E6H/MS
3200

5000

E6H/fMS
5000

[A]

1250

1250

2000

1600

3200

1600

4000

6300

6300

[A]

2000

2000

[A]

2500

[A]

3200

690

690

690

690

690

690

690

690

690

690

690

Rated service voltage Ue

[V ~]
[V ~]

250

250

250

250

250

250

250

250

250

250

250

Rated insulation voltage Ui

[V ~]

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

Rated impulse withstand voltage Uimp


Rated short-time withstand current Icw

[kV]

12

12

12

12

12

12

12

12

12

12

12

(1s)

[kA]

36

50

42

55

65

75

75

80

100

100

100

(3s)

[kA]

36

36

42

42

65

65

75

75

75

85

85

Rated short-circuit making capacity (peak value) ICM


220/230/380/400/415/440 V ~

[kA]

75.6

105

88.2

121

143

165

165

176

220

220

220

500/660/690 V ~

[kA]

75.6

75.6

88.2

121

143

165

165

165

187

220

220

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/65

Emax Air Circuit Breakers


Emax E1 - Fixed Rear Horizontal Terminals

Ratings @ 415V
E1N

Icu

Ics

Icw (1sec)

50kA

50kA

50kA

With Rear Horizontal Terminals


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
For version with FULLY RATED NEUTRAL, add /FRN to order reference
eg 1SDA0 39676R1/FRN

Icu
Model
(415V)

Current (A) Protection


I th

42kA

E1N 08

E1N 12

800A

1250A

PR111
1SDA0

PR112
R1

3 Pole

4 Pole

3 Pole

4 Pole

3 Pole

4 Pole

53803

53804

LSI

53754

53761

53757

53763

LSIG

53755

53762

53758

53764

LI
42kA

Non Automatic

LI

53805

53806

LSI

53767

53773

53769

53775

LSIG

53768

53774

53770

53776

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/66

Emax Air Circuit Breakers


Emax E1 - Drawout

Ratings @ 415V
E1N

Icu

Ics

Icw (1sec)

50kA

50kA

50kA

Moving Portions
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
For version with FULLY RATED NEUTRAL, add /FRN to order reference
eg 1SDA0 39676R1/FRN

Icu
Model
(415V)

Current (A) Protection


Ith
LI

42kA

E1N 08

800A

LSI
LSIG
LI

42kA

E1N 12

1250A

LSI

Non Automatic

PR111
1SDA0
3 Pole

PR112
R1

3 Pole

4 Pole

4 Pole

3 Pole

4 Pole

53807

53808

53780

53786

53782

53788
53789

53781

53787

53783

53809

53810

53792

53798

53794

53800

53793

53799

53795

53801

LSIG

Refer to sales office for breakers fitted with PR113 release


Fixed Portions
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Front, Flat and mixed terminal versions available on request, refer to technical catalogue

Terminal type

1SDA0
3 pole

R1
4pole

Rear Horizontal

37821

37826

Rear Vertical

37872

37877

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/67

Emax Air Circuit Breakers


Emax E2 - Fixed Rear Horizontal Terminals

Ratings @ 415V
Icu

Ics

Icw (1sec)

E2N

65kA

65kA

55kA

E2L

130kA

130kA 10kA

With Rear Horizontal Terminals


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
For version with FULLY RATED NEUTRAL, add /FRN to order reference
eg 1SDA0 39676R1/FRN

Icu
Model
(415V)

Current (A) Protection


Ith
MS

65kA

65kA

E2N 12

E2N12

800A

1250A

1600A

3 Pole

4 Pole

3 Pole

4 Pole

3 Pole

4 Pole

n/a

n/a

39676

39791

39684

39799

39680

39795

39688

39803

MS

37531

37559

LSI

39677

39792

39685

39800

39681

39796

39689

39803

37532

37560

39906

39994

39912

40000
40003

LSI
LSIG

65kA

E2N 20

130kA E2L 12

2000A

1250A

39909

39997

39915

MS

37533

37561

LSI

40082

40170

40088

40176

LSIG

40085

40173

40091

40091

MS

n/a

n/a

LSI

43394

40341

43402

40349
40353

LSIG
130kA E2L 16

1600A

PR112
R1

LSIG

LSIG
E2N 16

PR111
1SDA0

LSI

MS
65kA

Non-Automatic

43398

40345

43406

MS

n/a

n/a

LSI

40455

40543

40461

40549

LSIG

40458

40546

40464

40552

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/68

Emax Air Circuit Breakers


Emax E2 - Drawout

Ratings @ 415V
Icu

Ics

Icw (1sec)

E2N

65kA

65kA

55kA

E2L

130kA

130kA 10kA

Refer to sales office for breakers fitted with PR113 release


Fixed Portions
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Front, Flat and mixed terminal versions available on request, refer to technical catalogue

Terminal type

1SDA0
3 pole

R1
4pole

Rear Horizontal

37822

37827

Rear Vertical

37873

37886

Moving Portions
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
For version with FULLY RATED NEUTRAL, add /FRN to order reference
eg 1SDA0 39676R1/FRN
Icu
Model
(415V)

65kA

E2N 12

Current (A) Protection


Ith

800A

E2N 12

1250A

65kA

E2N 16

E2N 20

130kA E2L 12

1600A

2000A

1250A

MS

n/a

n/a

LSI

39762

39878

39770

39886

1600A

4 Pole

3 Pole

4 Pole

39890

39766

39882

39774

MS

37648

37652

LSI

39763

39879

39771

39887
39891

39767

39883

39775

MS

37647

37651

LSI

39972

40060

39978

40066

LSIG

39975

40064

39981

40069

MS

37649

37650

LSI

40148

40214

40154

40220

LSIG

40151

40217

40157

40223

MS

n/a

n/a

LSI

40296

40428

40304

40436
40440

LSIG
130kA E2L 16

3 Pole

PR112
R1

4 Pole

LSIG
65kA

PR111
1SDA0

3 Pole

LSIG
65kA

Non-Automatic

40300

40432

40308

MS

n/a

n/a

LSI

40521

40609

40527

40615

LSIG

40524

40612

40530

40618

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/69

Emax Air Circuit Breakers


Emax E3N, S - Fixed Rear Horizontal Terminals

Ratings @ 415V
Icu

Ics

E3N

65kA

65kA

Icw (1sec)
65kA

E3S

75kA

75kA

75kA

With Rear Horizontal Terminals


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
For version with FULLY RATED NEUTRAL, add /FRN to order reference
eg 1SDA0 39676R1/FRN

Icu
Model
(415V)

65kA

65kA

75kA

75kA

75kA

75kA

75kA

E3N 25

Current (A)
Ith

2500A

E3N 32 3200A

E3S 12

E3S 16

E3S 20

E3S 25

E3S 32

1250A

1600A

2000A

2500A

3200A

Protection

Non-Automatic

PR111
1SDA0
R1

3 Pole 4 Pole

PR112

3 Pole

4 Pole

3 Pole

MS

4 Pole
-

LSI

40651

40711

40655

40715

LSIG

41653

41713

40657

40717

MS

LSI

40786

43375

40790

43379

LSIG

40788

43377

40792

43381

MS

LSI

40891

40951

40895

40955
40957

LSIG

40893

40953

40897

MS

LSI

41011

41071

41015

41075

LSIG

41013

41073

41017

41077

MS

LSI

41131

41191

41135

41195
41197

LSIG

41133

41193

41137

MS

LSI

41251

41311

41255

41315
41317

LSIG

41253

41313

41257

MS

LSI

41371

41431

41375

41435

LSIG

41373

41933

41377

41437

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/70

Emax Air Circuit Breakers


Emax E3H/b, H, L - Fixed Rear Horizontal Terminals

Ratings @ 415V
Icu

Ics

Icw (1sec)

80kA

80kA

80kA

E3H

100kA

85kA

75kA

E3L

130kA

130kA 15kA

E3H/b

With Rear Horizontal Terminals


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
For version with FULLY RATED NEUTRAL, add /FRN to order reference
eg 1SDA0 39676R1/FRN
Icu
(415V)

Model

Current (A) Protection


Ith
MS

80kA

E3H/b 12

1250A

E3H/b 16

1600A

E3H/b 20

2000A

E3H/b 25

2500A

100kA

100kA

100kA

100kA

100kA

130kA

130kA

E3H/b 32

E3H 12

E3H 16

E3H 20

E3H 25

E3H 32

E3L 20

E3L 25

3200A

1250A

1600A

2000A

2500A

3200A

2000A

2500A

4 Pole

3 Pole

4 Pole

TBC
TBC

TBC

TBC

TBC

TBC

TBC

TBC

LSI

TBC

TBC

TBC

TBC

LSIG

TBC

TBC

TBC

TBC

TBC

TBC

TBC

TBC

LSI

TBC

TBC

TBC

TBC

LSIG

TBC

TBC

TBC

TBC

TBC

TBC

LSI

TBC

TBC

TBC

TBC

LSIG

TBC

TBC

TBC

TBC

MS
80kA

3 Pole

TBC

TBC

MS
80kA

3 Pole 4 Pole

PR112

LSIG

MS
80kA

PR111
1SDA0
R1

LSI
MS

80kA

Non-Automatic

TBC

TBC

LSI

TBC

TBC

TBC

TBC

LSIG

TBC

TBC

TBC

TBC

MS

LSI

41491

41551

41495

41555

LSIG

41493

41553

41497

41557

MS

LSI

41611

41671

41615

41675

LSIG

41613

41673

41617

41677

MS

LSI

41731

41791

41735

41795

LSIG

41733

41793

41737

41797

MS

LSI

41851

41911

41855

41915

LSIG

41853

41913

41857

41917

MS

LSI

41971

42031

41975

42035

LSIG

41973

42033

41977

42037

MS

LSI

42091

42151

42095

42155

42093

42153

42097

42157

LSIG

MS

LSI

42211

42271

42215

42275

LSI

42213

42273

42217

42277

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/71

Emax Air Circuit Breakers


Emax E3N, S - Drawout

Ratings @ 415V
Icu

Ics

Icw (1sec)

E3N

65kA

65kA

65kA

E3S

75kA

75kA

75kA

Refer to sales office for breakers fitted with PR113 release


Fixed Portions
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Front, Flat and mixed terminal versions available on request, refer to technical catalogue
Terminal type

1SDA0
3 pole

R1
4pole

Rear Horizontal

37822

37827

Rear Vertical

37873

37886

Moving Portions
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
For version with FULLY RATED NEUTRAL, add /FRN to order reference eg 1SDA0 39676R1/FRN
Icu
Model
(415V)

Current (A)
Ith

Protection

MS
65kA

65kA

75kA

75kA

E3N 25

E3N 32

E3S 12

E3S 16

2500A

3200A

1250A

1600A

E3S 20

2000A

75kA

E3S 25

E3S 32

2500A

3200A

3 Pole 4 Pole

3 Pole

4 Pole

3 Pole

4 Pole

37656

37653

PR112

40696

40756

40700

40760

LSIG

40698

40758

40702

40762

MS

37655

37654

LSI

40831

40876

40835

40880

LSIG

40833

40878

40837

40882

MS

37657

37664

LSI

40936

40996

40940

41000

LSIG

40938

40998

40942

41002

MS

37660

37665

LSI

41056

41116

41060

41120
41122

41058

41118

41062

MS

37658

37666

LSI

41176

41236

41180

41240
41242

LSIG
75kA

PR111
1SDA0
R1

LSI

LSIG
75kA

Non-Automatic

41178

41238

41182

MS

37661

37662

LSI

41296

41356

41300

41360

LSIG

41298

41358

41302

41362

MS

37659

37663

LSI

41416

41476

41420

41480

LSIG

41418

41478

41422

41482

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/72

Emax Air Circuit Breakers


Emax E3H/b, H, L Drawout

Ratings @ 415V
Icu

Ics

Icw (1sec)

E3H/b

80kA

80kA

80kA

E3H

100kA

85kA

75kA

E3L

130kA

130kA

15kA

Refer to sales office for breakers


fitted with PR113 release
Fixed Portions - Refer to page ????

Moving Portions
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
For version with FULLY RATED NEUTRAL, add /FRN to order reference
eg 1SDA0 39676R1/FRN
Icu
(415V)

Model

Current (A) Protection


Ith
MS

80kA

E3H/b 12

1250A

E3H/b 16

1600A

PR111
1SDA0
R1

3 Pole 4 Pole

3 Pole

TBC

2000A

TBC

TBC

TBC

TBC

TBC

TBC

TBC

TBC

TBC

TBC

TBC

TBC

TBC

TBC

TBC

TBC

TBC

LSI

E3H/b 25

2500A

100kA

100kA

100kA

100kA

100kA

130kA

130kA

E3H/b 32

E3H 12

E3H 16

E3H 20

E3H 25

E3H 32

E3L 20

E3L 25

3200A

1250A

1600A

2000A

2500A

3200A

2000A

2500A

TBC
TBC

TBC

TBC

TBC

LSIG

TBC

TBC

TBC

TBC

TBC

TBC

LSI

TBC

TBC

TBC

TBC

LSIG

TBC

TBC

TBC

TBC

LSI

TBC

TBC

TBC

TBC

LSIG

TBC

TBC

TBC

TBC

MS
80kA

TBC

LSI
MS

80kA

4 Pole

TBC

LSIG
E3H/b 20

3 Pole

TBC

LSIG

MS
80kA

4 Pole

PR112

LSI
MS

80kA

Non-Automatic

TBC

TBC

MS

LSI

41536

41596

41540

41600

LSIG

41568

41598

41542

41602

MS

LSI

41656

41716

41660

41720

LSIG

41658

41718

41662

41722

MS

LSI

41776

41836

41780

41840

LSIG

41778

41838

41782

41842

MS

LSI

41896

41956

41900

41960
41962

LSIG

41898

41958

41902

MS

LSI

42016

42076

42020

42080

LSIG

42018

42078

42022

42082

MS

LSI

42136

42196

42140

42200

LSIG

42138

42198

42142

42202

MS

LSI

42256

42316

42260

42320

LSI

42258

42318

42262

42322

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/73

Emax Air Circuit Breakers


Emax E4S, S/f, H - Fixed - Rear Horizontal Terminals

Ratings @ 415V
Icu

Ics

Icw (1sec)

E4S

75kA

75kA

75kA

E4S/f

80kA

80kA

80kA

E4H

100kA

100kA 100kA

* Available in 4 pole ( fully rated neutral) version only


* Available with 50% rated neutral only

Refer to sales office for breakers fitted with PR113 release


With Rear Horizontal Terminals
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
For E4S 3 pole version for use with fully rated external neutral CT, add /FRN to order
reference eg 1SDA039791R1/FRN. For E4S 4 pole fully rated neutral version use E4S/f
part numbers
Icu
(415V)

75kA

80kA

100kA

Model

E4S

E4S/f

E4H 32

Current (A) Protection


Ith

4000A

4000A

3200A

E4H 40

4000A

PR111
1SDA0
R1

PR112

3 Pole

4 Pole

3 Pole

4 Pole

3 Pole

MS

37546

37574

LSI

42332

42392

42336

42396

LSIG

42334

42394

42338

42398

4 Pole

MS

n/a

48737

n/a

n/a

LSI

n/a

n/a

48675

n/a

48677

LSIG

n/a

n/a

48676

n/a

48678

MS

37547

37575

LSI

42452

43419

42456

42423
42425

LSIG
100kA

Non-Automatic

42454

43421

42458

MS

37548

37576

LSI

42557

42617

42561

42621

LSIG

42559

42619

42563

42623

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/74

Emax Air Circuit Breakers


Emax E4S, S/f, H Drawout

Ratings @ 415V
Icu

Ics

Icw (1sec)

75kA

75kA

75kA

E4S/f

80kA

80kA

80kA

E4H

100kA

100kA 100kA

E4S

* Note: Available in 4 pole ( fully rated neutral) version only


* Note: Available with 50% rated neutral only

Refer to sales office for breakers fitted with PR113 release


Fixed Portions
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Front, Flat and mixed terminal versions available on request, refer to technical catalogue
For E4S 4 pole fully rated neutral version use E4S/f part numbers

Terminal type

1SDA0
E4S & E4H

Rear Horizontal

E4S/f
E4S & E4H

Rear Vertical

E4S/f

R1

3 pole

4pole

37824

37829

n/a

48702

37875

37879

n/a

48707

Moving Portions
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
For E4S 3 pole version for use with fully rated external neutral CT, add /FRN to order
reference eg 1SDA039791R1/FRN. For E4S 4 pole fully rated neutral version use E4S/f
part numbers
Icu
(415V)

Model

Current (A) Protection


Ith
MS

75kA

80kA

100kA

E4S

E4S/f

4000A

4000A

E4H 32 3200A

E4H 40 4000A

PR111
1SDA0
R1

PR112

3 Pole

4 Pole

3 Pole

4 Pole

3 Pole

4 Pole

37677

37678

LSI

42377

42437

42381

42441

LSIG

42379

42439

42383

42443

MS

n/a

48740

n/a

n/a

LSI

n/a

n/a

48696

n/a

48698

LSIG

n/a

n/a

48697

n/a

48699

MS

37682

37679

LSI

42497

42542

42501

42546
42548

LSIG
100kA

Non-Automatic

42499

42544

42503

MS

37681

37680

LSI

42602

42662

42606

42666

LSIG

42604

42664

42608

42668

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/75

Emax Air Circuit Breakers


Emax E6H, H/f, V - Fixed Rear Horizontal Terminals

Ratings @ 415V
Icu

Ics

E6H

100kA

100kA 100kA

Icw (1sec)

E6H/f

100kA

100kA 100kA
* Note:isAvailable
* Note: This breaker
availableinin44pole
pole( (fully
fullyrated
ratedneutral)
neutral)version
versiononly
only

E6V

150kA

125kA

100kA
* Note:isAvailable
* Note: This breaker
availablewith
with50%
50%rated
ratedneutral
neutralonly
only

With Rear Horizontal Terminals


Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
For E6H 3 pole version for use with fully rated external neutral CT, add /FRN to order
reference eg 1SDA039791R1/FRN. For E6H 4 pole fully rated neutral version use E6H/f
part numbers

Icu
(415V)

100kA

Model

E6H 50

Current (A)
Ith

5000A

Protection

E6H 63

6300A

100kA

150kA

150kA

150kA

150kA

E6H/f 50 5000A

E6H/f 63 6300A

E6V 32

E6V 40

E6V 50

E6V 63

3200A

4000A

5000A

6300A

3 Pole 4 Pole

PR112

3 Pole

4 Pole

3 Pole

37549

37577

LSI

42677

42737

42681

42741

4 Pole

42743

42679

42739

42683

MS

37550

37578

LSI

42797

42857

42801

42861
42863

LSIG
100kA

PR111
1SDA0
R1

MS
LSIG
100kA

Non-Automatic

42799

42859

42803

MS

n/a

50810

n/a

n/a

LSI

n/a

n/a

50768

n/a

50770

LSIG

n/a

n/a

50769

n/a

50771

MS

n/a

50813

n/a

n/a

LSI

n/a

n/a

50789

n/a

50791

LSIG

n/a

n/a

50790

n/a

50792

MS

LSI

42923

42955

42925

42957

LSIG

42924

42956

42926

42958

MS

LSI

42996

43056

43000

43060
43062

LSIG

42998

43058

43002

MS

LSI

43101

43161

43105

43165
43167

LSIG

43103

43163

43107

MS

LSI

43221

43281

43225

43285

LSIG

43223

43283

43227

43287

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/76

Emax Air Circuit Breakers


Emax E6H, H/f, V Drawout

Ratings @ 415V
Icu

Ics

E6H

100kA

100kA 100kA

Icw (1sec)

E6H/f

100kA

100kA 100kA

* Note: Available in 4 pole ( fully rated neutral) version only

E6V

150kA

125kA

* Note: Available with 50% rated neutral only

100kA

Refer to sales office for breakers fitted with PR113 release


Fixed Portions
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1
Front, Flat and mixed terminal versions available on request, refer to technical catalogue
For E6H 4 pole fully rated neutral version use E6H/f part numbers
1SDA0
Terminal type
Rear Horizontal
Rear Vertical

E6H & E6V


E6H/f
E6H & E6V
E6H/f

R1

3 pole

4pole

37825

37830

n/a

50816

37876

37880

n/a

50821

Moving Portions
Ordering example: place five digit code below into order reference eg 1SDA0 39676 R1. For
E6H 3 pole version for use with fully rated external neutral CT, add /FRN to order reference
eg:1SDA039791R1/FRN. For E6H 4 pole fully rated neutral version use E6H/f part numbers
Icu
(415V)

Model

Current (A)
Ith

Protection

Non-Automatic

PR111
1SDA0
R1

3 Pole

4 Pole

3 Pole

4 Pole

3 Pole

4 Pole

37683

37686

LSI

42722

42782

42726

42786

LSIG

42742

42784

42728

42788

MS
100kA

100kA

100kA

100kA

150kA

150kA

150kA

150kA

E6H 50

E6H 63

5000A

6300A

E6H/f 50 5000A

E6H/f 63 6300A

E6V 32

E6V 40

E6V 50

E6V 63

3200A

4000A

5000A

6300A

PR112

MS

37684

37685

LSI

42842

42902

42846

42906

LSIG

42844

42904

42848

42908

MS

n/a

50812

n/a

n/a

LSI

n/a

n/a

50782

n/a

50784

LSIG

n/a

n/a

50783

n/a

50785

MS

n/a

50815

n/a

n/a

LSI

n/a

n/a

50804

n/a

50806

LSIG

n/a

n/a

50805

n/a

50807

MS

LSI

42939

42971

42941

42973
42974

LSIG

42940

42972

42942

MS

LSI

43026

43086

43030

43090

LSIG

43028

43088

43032

43092

MS

LSI

43146

43206

43150

43210
43212

LSIG

43148

43208

43152

MS

LSI

43266

43311

43270

43315

LSIG

43268

43313

43272

43317

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/77

Emax Air Circuit Breakers


Emax fixed part accessories

Electrical Accessories
1). Shunt opening/closing release
E 1/6

1SDA0

24 V

38286

30 V

38287

48 V

38288

60 V

38289

110...120 V

38290

120...127 V

38291

220...240 V

38292

240...250 V

38293

380...400 V

38294

440 V

38295

R1

the shunt opening release and closng release share the same construction and are therefore interchangable. Their function is determined by
the position in which they are mounted on the circuit-breaker.

2a). Undervoltage release


E1/6

1SDA0

24 V

38306

30 V

38307

48 V

38308

60 V

38309

110...120 V

38310

120...127 V

38311

220...240 V

38312

240...250 V

38313

380...400 V

38314

440...480 V

38315

R1

2b). Electronic time-delay device for undervoltage release


E1/6

1SDA0

24...30 V

38316

48 V

38317

60 V

38318

110...115 V

38319

220...250 V

38320

R1

3). Geared motor for automatic charging of closing springs


E1/6

1SDA0

24...30 V

38321

48...60 V

38322

100...130 V

38323

220...250 V

38324

R1

supplied as standard with limit contact and microswitch for signalling the closing springs are charged

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/78

Emax Air Circuit Breakers


Emax fixed part accessories

Electrical Accessories cont...


4). Signal for overload current releases tripped
E 1/6

1SDA0

Mechanical
Electrical
1)

R1

38337

1)

38338

Requires mechanical signal as well.

5a). Electrical signalling of circuit-breaker open/closed


E1/6

1SDA0

4 auxilliary contacts

2)

10 auxilliary contacts

38327

3) 4)

15 additional auxilliary contacts

43475

5)

15 additional auxilliary contacts (special version for withdrawable)

48827

5)

2)

Order for MS-CS-MT-MTP version only. Already included for automatic circuit-breaker.

3)

Not available with PR112 release.

4)

Order for MS-CS-MT-MTP version. Order as a loose kit only for automatic circuit-breaker
Outside circuit-breaker. Order as alternative to various types of interlock and to accessory 8e.
For mounting on fixed circuit-breaker requires accessory 10.4 as well (interlock plate for fixed circuit-breaker)

5)

R1

38326

5b). Electrical signalling of connected/isolated/isolated for test position


1SDA0
E1/E6 - 5 auxilliary contacts

38361

E1/E2 - 10 auxilliary contacts 3 poles

38360

E1/E2 - 10 auxilliary contacts 4 poles

43467

E3 - 10 auxilliary contacts 3 poles

43468

E3 - 10 auxilliary contacts 4 poles

43469

E4/E6 - 10 auxilliary contacts 3/4 poles

43470

R1

5c). Contact for signalling closing springs charged


E1/6

1SDA0

R1

38325

Order as alternative to geared motor

5d). Contact for signalling undervoltage release energised


E1/6

1SDA0

1 normally open contact

38340

1 normally closed contact

38341

R1

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/79

Emax Air Circuit Breakers


Emax fixed part accessories

Electrical Accessories cont...


6a). Current transformer for neutral conductor outside circuit-breaker
E2

1SDA0

R250

R1

38269

R400

38270

R800

38271

R1250

38272

R1600

38273

R2000

38274

E3

1SDA0

R250

48952

R400

48953

R800

38277

R1250

38278

R1600

38279

R2000

38280

R2500

38281

R3200

38282

E4

1SDA0

R2000

48957

R3200

38275

R4000

38276

E6

1SDA0

R3200

48958

R4000

38283

R5000

38284

R6300

38285

R1

R1

R1

6b). Homopolar toroid for the main power supply earthing conductor
1SDA0
In 100A

R1

48067

In 250A

48068

In 400A

48069

In 800A

48070

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/80

Emax Air Circuit Breakers


Emax fixed part accessories

Mechanical Accessories
7). Mechanical operation counter
E 1/6

1SDA0

R1

38345
1)

Requires mechanical signal as well.

8a). Lock in open position


E1/6 - key lock

1SDA0

for 1 circuit-breaker (different keys)

R1

38350

for sets of circuit-breakers (same keys No. 3004222)

38346

for sets of circuit-breakers (same keys No. 0025431)

38347

for sets of circuit-breakers (same keys No. 0233424)

38348

for sets of circuit-breakers (same keys No. 0335452)

38349

padlock (as alternative to mechanical accessory 3a)

38351

castell lock (not supplied please order from Castell International Ref: PDS01388(s))

NONSTD161

8b). Circuit-breaker lock in connected/isolated/isolated for test position


E1/6 - key lock + padlock

1SDA0

for 1 circuit-breaker (different keys)

R1

38356

for sets of circuit-breakers (same keys No. 3004222)

38352

for sets of circuit-breakers (same keys No. 0025431)

38353

for sets of circuit-breakers (same keys No. 0233424)

38354

for sets of circuit-breakers (same keys No. 0335452)

38355

8c). Accessory for lock in isolated/isolated for test position


E1/6

1SDA0

R1

38357

Order in addition to mechanical accessory 2b

8d). Accessory for padlock device for shutters


E1/6

1SDA0

R1

38363

8e). Mechanical lock for compartment door


E1/6
-

1SDA0

R1

45039

1) 2) 3)

1) Order as an alternative to the various types of interlocks and electrical accessory 5a (15 auxilliary contacts)
2) the use of accessory 10.2 is necessary for installation
3) for fixed circuit-breaker, plate 10.4

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/81

Emax Air Circuit Breakers


Emax fixed part accessories

Mechanical Accessories
9a). Protection cover opening and closing pushbuttons
E 1/6

1SDA0

R1

38343

9b). IP54 protective cover for door


E1/6 - key lock

1SDA0

R1

38344

10a). Interlock cable set

(order one per interlock set)

E1/6
Description

Horizontal
1SDA0
R1

Vertical
1SDA0
R1

A type cable set

38329

38333

B type cable set

38330

38334

C type cable set

38331

38335

D type cable set

38332

38336

10b). Interlock mechanism

(order one per breaker)

Type

1SDA0

E1

38366

E2

38366

E3

38367

E4 - 3 poles

38368

E5 - 4 poles / E6 - 3 poles

43466

E6 - 4 poles

38369

10c). Interlock mechanism

(order one per breaker)

Type

1SDA0

R1

E2 - E6 fixed or moving part

R1

38364

E2 - E6 fixed or moving part

38364

E2 - E6 fixed or moving part

38365

E2 - E6 fixed or moving part

38364

10d). Interlock plate for fixed breaker (order one per breaker)
E1/6

1SDA0

R1

38363

Mechanical Interlock Ordering Example:


C type horizontal interlock for 3 off E2N drawout pattern breakers
1 off
C type cable set (10a)
1SDA038331R1
2 off
Interlock mechanism (10c)
1SDA038366R1
3 off
Interlock mechanism (10b)
1SDA038365R1
3 off E2Nfixed pattern breakers
3 off
Interlock mechanism (10d)

1SDA038358R1

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/82

Emax Air Circuit Breakers


Conversion kit for fixed circuit-breaker or fixed parts

Conversion Kits
Kit for converting fixed circuit-breaker
with horizontal rear terminals to vertical rear terminals
Type

1SDA0

R1

3 terminals for 3 poles

4 terminals for 4 poles

E1

38052

38057

E2

38053

38058
38059

E3

38054

E4

38055

38060

E6

38056

38061

Each kit fits both upper and lower application.To convert a complete circuit-breaker, order 2 kits.

Kit for converting fixed circuit-breaker


with horizontal rear terminals to front terminals
Type

1SDA0

R1

3 terminals for 3 poles

4 terminals for 4 poles

E1

38062

38067

E2

38063

38068
38069

E3

38064

E4

38065

38070

E6

38066

38071

Each kit fits both upper and lower application.To convert a complete circuit-breaker, order 2 kits.

Kit for converting fixed parts


with horizontal rear terminals to front terminals
Type

1SDA0
3 terminals for 3 poles

R1
4 terminals for 4 poles

E1

38062

38067

E2

45031

45035

E3

45032

45036

E4

45033

45037

E6

45034

45038

Each kit fits both upper and lower application.To convert a complete circuit-breaker, order 2 kits.

Return to main index


www.abb.com/lowvoltage

ABB LIMITED

email marketing.info@gb.abb.com

Telephone 02476 368549

Facsimile 02476 368401

4/83