Академический Документы
Профессиональный Документы
Культура Документы
DISCONNECT SWITCHES
David Childress, Marketing Manager-Power Switching Division
Southern States, LLC
30 Georgia Avenue
Hampton, GA 30228
phone: 770-946-4562, ext. 139
fax: 770-946-8106
e-mail: d.childress@southernstatesLLC.com
website: www.southernstatesLLC.com
AbstractGroup operated air disconnect switches are used in all types of substationsdistribution,
subtransmission, transmission, and extra high voltage (EHV). The correct selection of the type of group
operated disconnect switch for a given application is key to the proper and desired performance of the
installation, as disconnect switches are the substation component that isolates other pieces of substation
equipment (such as circuit breakers, power transformers, etc.) when they need periodic, preventative, or
emergency maintenance. This paper covers all of the types of group operated disconnect switches
commonly used in the United States and Canada today, the various criteria which affect the selection of a
specific type for a given installation, and the standards which govern these products.
I. DEFINITION, FUNCTIONS, AND OBSERVATIONS
Substation class group operated air disconnect switches can be defined quite simply as mechanical
devices which conduct electrical current and provide an open point in a circuit for isolation of one of the
following devices: circuit breaker, circuit switcher, power transformer, capacitor bank, reactor, or other.
The three most important functions that disconnect switches must perform are: (1) to open and close
reliably when called upon to do so, (2) to carry current continuously without overheating, and (3) to
remain in the closed position under fault current conditions. The first important function listed above is
taken for granted by some purchasers who deem that all disconnect switch types and their corresponding
manufacturers are equal, thus reducing switches to a commodity item. In truth and point of logical fact,
disconnect switches are the least commodity item of any substation, as they isolate the equipment which
can be taken out of service when the equipment being isolated has a problem. The disconnect switch
itself, if it has a problem, is very difficult to isolate from the system. This point has, in recent years, been
erroneously overlooked by some key decision makers; making the selection of the correct disconnect
switch for a given application a choice which should not be made before the decision maker is well
informed about all of their options.
II. STANDARDS WHICH GOVERN DISCONNECT SWITCHES
Disconnect switches are governed by four key organizationsNEMA (National Electrical
Manufacturers Association), ANSI (American National Standards Institute), IEEE (Institute of Electrical
and Electronics Engineers), and IEC (International Electrotechnical Commission). Today each governs
some specific aspects of disconnect switch design. NEMA governs wind loading design requirements
and up until around 1971 also governed temperature rise and short circuit withstand requirements.
Around 1971 ANSI/IEEE took over as the governing standard for temperature rise and short circuit
withstand requirements. ANSI/IEEE also governs terminal pad loading requirements, altitude derating
factors, seismic performance criteria, and switch overload capabilities. IEC governs all pertinent switch
design criteria for switches manufactured outside the United States and Canada.
switcher) can clear the system fault. Vertical break switches encompass a ratings range of 15.5 kV
through 800 kV; 600 Amps through 6500 Amps.
Figure 1
A Horizontal Upright Mounted Vertical Break
Switch
Figure 2
A Vertically Mounted Vertical Break Switch
Figure 3
Reverse Loop Contact Design
IV.B. DOUBLE END BREAK SWITCHES
Double end break switches (See Figures 4 and 5.) can be installed on minimal phase spacing, the
same phase spacing that vertical break switches can be installed on; as the double end break switchs
disconnect blades, when in the open position, are disconnected from both the source and the load. In
the open position the blade is not complete de-energized, but instead is at a floating potential of about
30% of system voltage. An advantage that double end break switches enjoy over vertical break
switches is that they can be installed in locations which have minimal overhead clearance as the
blades swing open to the side rather than lifting upward. An additional advantage that double end
break switches enjoy over vertical break switches is that they do not require their blades to be
counterbalanced as the blades are not lifted. (Vertical break switches typically require their blades to
be counterbalanced at 69 kV and above.) Double end break switches are excellent for applications in
environments which can experience large amounts of ice formation and are also excellent for
installations which have large amounts of fault current due to their reverse loop contact design. In
fact, double end break switches are even better performers in icy environments than vertical break
switches are as the orientation of the jaw assembly of a double end break switch (a C configuration
rather than the vertical break switchs U configuration) reduces the amount of ice accumulation
occurring in the jaw assembly area. Ice is inherently weak in shear but very strong in compression,
making it much easier for any type of group operated disconnect switch to open under accumulated
ice than to close into accumulated ice. Perhaps the second most overlooked performance
characteristic of the double end break switch (behind only the fact that it can be installed on vertical
break switch phase spacing) is that its design of two breaks per phase in series provides much greater
line charging or magnetizing current interrupting capability with standard arcing horns or with quick
break whip type arcing horns than does any single break type switch (Vertical break switches, center
break switches, center break Vee switches, and single side break switches are all single break per
phase type switches.). Double end break switches encompass a ratings range of 38 kV through 1100
kV; 1200 Amps through 4000 Amps.
Figure 4
A Horizontally Upright Mounted Double End
Break Switch In The Closed Position
Figure 5
A Horizontally Upright Mounted Double End
Break Switch In The Open Position
Figure 6
Figure 7
A Pair of Horizontally Upright Mounted Double End
A Horizontally Upright Mounted Double End
Break Vee Switches In The Closed Position Feeding
Break Vee Switch In The Open Position
A Circuit Breaker
IV.D. CENTER BREAK SWITCHES
Center break switches (See Figure 8.) can be installed with the same minimal overhead clearances
that double end break and double end break Vee switches can but need greater phase spacing than
vertical break, double end break, and double end break Vee switches as when center break switches
are in the open position one of the two disconnect blades per phase is still energized. An economic
advantage of center break switches is that they only require a total of six insulators per three phase
switch versus the nine required for vertical break switches, double end break switches, and double
end break Vee switches. Like the double end break and double end break Vee switches the
center break switch does not require a counterbalance for the blades as they swing out to the side
rather than having to be lifted. A seldom realized characteristic of the center break switch is that it is
the best available switch design for vertical mounting as its blades self-counterbalance each other on
opening and on closing via the synchronizing pipe linkage which connects the two rotating insulator
stacks on each phase. When a vertically mounted center break switch is opening the bottommost
blades weight tends to push open the uppermost blade, and when closing the uppermost blades
weight tends to pull closed the bottommost blade. Center break switches encompass a ratings range
of 15.5 kV through 362 kV; 600 Amps through 6000 Amps.
Figure 8
A Horizontal Upright Mounted Center Break Switch
Figure 9
A Horizontal Upright Mounted Center Break
Vee Switch In The Open Position
Figure 10
A Horizontally Upright Mounted Center Break
Vee Switch In The Closed Position
Figure 11
A Horizontally Upright Mounted Single Side Break Switch
Providing An Isolation Point On The Secondary Side Of A
Small Power Transformer At A Wind Farm Substation
Figure 12
A Vertically Mounted Single Side
Break Switch
effort required to operate the switch justifies a manual gear operator but the switch may need to be closed
under iced conditions where speed on closing is essential to dislodge the accumulated ice. The required
speed on closing necessary to break accumulated ice is generally not achievable via a manual gear
operator but can be achieved using the manual swing handle operator while the manual gear operator is
decoupled from the vertical operating pipe. This combination manual operator (See Figure 13.) is
typically called a manual gear operator with auxiliary ice breaking swing handle and decoupler.
Auxiliary Ice
Breaking Swing
Handle Would
Be Inserted Into
This Sleeve
Figure 13
Manual Gear Operator With Auxiliary Ice Breaking Swing Handle And Decoupler
(Swing Handle Not Current Installed Since Gear Operator Is Currently Coupled)
Manual gear operators should generally not be installed on single side break switches as these switches
are required to slam-seat the blade into the jaw contact to achieve full blade/contact engagement. Manual
gear operators, as previously mentioned, do not generate enough speed to slam-seat the blade into the jaw
contact.
For group operated switches requiring motor operators, the higher the kV rating of the switch the
slower the motor operator needs to operate. For example, a 4 second operating time motor operator is
well suited for use on a 115 kV switch but is far too fast for operation of a 345 kV switch. Higher kV
rated switches require slower operating time motor operators to maintain full control of the switch blades
during the entire operational travel.
The installation of a group operated switch should allow for 180 degrees of operating travel of the
outboard bearing as the switch goes from full open to full closed and vice versa with an additional 5
degrees of overtoggle at the end of the opening and at the end of the closing operations (for 190 degrees
of total travel). The 180 degrees of operational travel provides for a much better mechanical advantage
on the switch than does any set up which has less than 180 degrees of operational travel, resulting in less
effort being required to operate the switch.
Quick break whip type arcing horns should not be installed on 230 kV switches due to the strong
possibility of the whips generating corona (either visible and/or audible). [Quick break whip type arcing
horns do not generally exhibit any corona problems at 161 kV and below.]
Group operated switches which are required to interrupt charging current or magnetizing current using
arcing horns (either standard arcing horns or quick break whip type arcing horns) should not be installed
in the underhung mounting position as any arc drawn as a result of interrupting charging current or
magnetizing current in air will travel upward as the air becomes superheated. This upward arc travel
could track across the switchs insulators since the insulators are above the live parts on an underhung
mounted switch.
All group operated switches equipped with group operated ground switches should have the switch
vertical pipe and the ground switch vertical pipe interlocked in some fashion; using either a mechanical
cam-action interlock, a pair of key interlocks, or some other type of interlocking scheme; to prevent the
possibility of closing the switch when the ground switch is closed and to prevent the possibility of closing
the ground switch when the switch is closed. If the switch and its integral ground switch are both
manually operated then the interlocking scheme need only be able to prevent manual closing of one when
the other is closed; but if either the switch, the ground switch, or both are motor operated then the
interlocking becomes more complex. If the switch is motor operated and the ground switch is manually
operated then the switch must be blocked via interlocking from being closed either manually or
electrically if the ground switch is closed. If the switch is motor operated and the ground switch is motor
operated then each must be blocked via interlocking from being closed either manually or electrically if
the other is closed.
In some instances where switches are required to be installed in contaminated environments (salt spray,
cement dust, etc.) there is a tendency on the part of the purchaser to want to use a higher kV rated
insulator on the switch (for example, a 54 inch tall 138 kV rated insulator on a 115 kV rated switch
designed for a 45 inch tall insulator) to increase the insulators creepage distance to compensate for the
degradation of the line-to-ground insulation as a result of the contaminated environment. If this is done
then the inherent coordination of having a greater open gap distance on the switch than its phase-toground distance could be defeated completely and, at a minimum, will be marginalized. The potential
consequences of this are dire, as if the open gap dimension of the switch is less than the phase-to-ground
distance then a flashover, if one occurred, would take the shortest distance, jumping the open gap of the
switch rather than going phase-to-ground. An open gap flashover with personnel working on the piece of
substation equipment that the switch is supposed to be isolating could result in personnel injury or death.
To avoid this it is necessary to re-establish the inherent coordination of the open gap distance and the
phase-to-ground distance. This is accomplished via the use of spill gaps (also known as rod gaps, arc
gaps, and spark gaps). Spill gaps are bolted on either below the bottom of the insulator, above the top of
the insulator, or both below the bottom of the insulator and above the top of the insulator; and they make
the insulator look electrically the same height that it would otherwise look electrically if it were furnished
with the correct height insulator for that kV rating. A better solution to handle contaminated
environments that does not produce this hazard to personnel and which does not require spill gaps to be
used is to choose resistance glazed insulators. These insulators have a semi-conductive coating baked
into them during the firing process of making the insulators. This semi-conductive coating creates a small
leaking current across the insulator, heating the insulator and preventing moisture from accumulating on
it. If moisture were to accumulate on the insulator the airborne contaminants would be even more likely
to deposit onto the insulator, creating a greater potential for flashovers.
VI. SUMMARY
The chart below summarizes information previously outlined in text form regarding the various features
and characteristics of the group operated disconnect switches covered in this paper.
Table 2
Summary of Features & Characteristics of Group Operated Disconnect Switches
Vertical Break
Double End
Break
Double End
Break Vee
Installable on
minimal phase
spacing
Installable with
minimal
overhead
clearance
Excellent
choice for icy
environments
Excellent
choice for sites
having high
fault currents
Number of
breaks per
phase
Number of
insulators
Does not
require a
counterbalance
Excellent at
minimizing
structure cost
and land space
consumed
Center Break
Center Break
Vee
Single Side
Break
VII. CONCLUSION
The selection of the proper group operated disconnect switch is key to the success of any substations
long term reliable performance. Many different types are available to meet the varied needs of each
specific installation. Considerable care should be taken when choosing a group operated disconnect
switch to meet a given installations needs. If the decision maker is uncertain about which offering best
meets their required criteria for a specific installation then it is highly recommended that the switch
manufacturer be consulted for guidance as both the purchaser and the seller have a strongly vested interest
in assuring that the chosen product completely meets the requirements and expectations of the
installation; providing the desired long, trouble-free operational life needed from all disconnect switches.
VIII. BIOGRAPHY
David Childress received his Bachelor of Science degree in Engineering from Mississippi State
University in 1991. He joined Siemens Energy & Automation in 1991 as an application engineer
responsible for circuit switchers and disconnect switches and later joined Southern States in 1997 holding
positions of regional manager, international sales manager, and product manager. He is presently the
marketing manager of Southern States Power Switching Division responsible for all Southern States SF6
products including circuit switchers, load and line switchers, and capacitor switchers. He is a member of
IEEE; a multi-published technical paper author; an author of over 100 catalog flyers, catalog bulletins,
and other technical/product related documents; and has recently co-authored a chapter for Electric Power
Substations Engineering Book-Second Edition entitled High Voltage Switching Equipment.