Академический Документы
Профессиональный Документы
Культура Документы
Metallic cable tray shall be designed, manufactured and tested in accordance with NEMA VE-1.
Fiberglass tray shall comply with NEMA FG-1.
Lengths of straight sections shall be 3.05, 3.66, 6.10, and 7.32 m (10, 12, 20 and 24 ft
respectively)
Widths shall be 152, 305, 457, 610, 762 and 914 mm (6, 12, 18, 24, 30 and 36 in respectively)
Depths shall be 76.2, 102, 127 and 152 mm (3, 4, 5, and 6 in respectively) minimum usable load
depth
Radii of bends shall be 305, 610 and 914 mm (12, 24, and 36 in respectively)
Degree of arc for elbows shall be 30, 45, 60, or 90 degrees
For ladder-type trays, the rung spacing on straight sections shall be 229 mm (9 in) on centers
Straight section covers for steel and aluminum trays shall be pre-galvanized sheet steel, and shall
be furnished in 3048 mm (10 ft) lengths
According to NEC 392.9 (B), when using ventilated tray with multiconductor control cable, the
sum of the cross sectional areas shall not exceed 50 percent of the interior cross section of the
tray
Cable tray shall be supported on straight horizontal runs at a maximum span of 6100 mm (20 ft)
and within 915 mm (3 ft) of fittings. Vertical cable tray runs shall be supported 2400 mm (8 feet)
maximum.
Cable tray splices shall be made so that connectors between horizontal straight section of cable
tray runs fall between the support point and the quarter point of the span. Splice points shall not
be made directly over support joints
Expansion joints shall be installed in each straight run of outdoor cable tray not to exceed 18.2
meters (60 feet) in length and in each straight run of indoor cable tray not to exceed 36.5 meters
(120 feet) in length.
All cable tray systems shall be connected to the plant grounding system at intervals of 150 meters
(490 feet) and at each end. Bonding jumpers, heavy duty tinned copper braid, shall be installed at
all expansion connectors. All cable tray systems shall be bonded together at intervals of 150
meters (490 feet) and at each end.
The minimum working space around cable trays shall be 1020 mm (40-inches) on at least one
side of a single tray, 1020 mm (40-inches) on both sides of two trays installed parallel to each
other. The minimum vertical separation between trays shall be 510 mm (20-inches).
Cable shall be secured in vertical runs of cable trays by the use of stainless steel clips. Horizontal
runs of cable shall be secured through the use of black nylon, sunlight resistant cable ties. Cable
ties shall be installed every 1372 mm (54 inches) on horizontal runs and every 457 mm (18
inches) on vertical runs.
The conduit shall be furnished in nominal 10 ft. (3.05 m) lengths, threaded on each end with one
Coupling attached, unless otherwise stated in this specification
All conduit and fittings shall have a minimum of 5 threads fully engaged at all connections.
Installing thread less conduit fittings on threaded conduits is prohibited.
All conduit threads shall be made with a standard conduit-cutting die and shall have 19mm(3/4")
Taper per 305mm (12") length. Running threads are not permitted.
A 15.2 m (50-ft) run with no more than three 90-degree or equivalent bends
A 30.4 m (100-ft) run with no more than two 90-degree or equivalent bends
A 45.6 m (150-ft) run with no more than one 90-degree or equivalent bend
A 60.8 m (200-ft) straight run with no bends
One wire can fill only 53% of a raceway, and two wires can fill only 31%. And if you have more
than 2 conductors in a raceway, the maximum fill is 40%.
A vertical conduit drop exceeding 6 m (20 feet) shall have a drain fitting installed at the low point.
Adequate provision shall be made for all straight horizontal conduit runs in excess of 50 meters
for thermal expansion. All expansion fittings shall include jumpers for grounding continuity.
Conduit runs shall avoid obstructions and unnecessary bends. Where possible conduit runs
shall be a minimum of 100 mm (4 inches) from fireproofed steel and insulated hot fluid lines, or
any un insulated hot object over 150 degrees C (302 degrees F).
Conduit routed on columns or vessels may be supported by ladder supports. Where it is
necessary to route the conduit between the ladder and the column or vessel, maintain a minimum
of 153 mm (6 inches) for toe space.
The smallest size to be used shall be 19 mm (3/4 inch) EMT.EMT shall not be used for power
feeder runs, rated 480 volts or above.