Академический Документы
Профессиональный Документы
Культура Документы
The manufacturers literature for a given relay make and model must be consulted w
hen planning the CT connections.
Percentage-differential characteristics are available as fixed-percentage or
variable percentage. The difference is that a fixed-percentage relay exhibits a
constant percentage restraint, and for a variable-percentage relay the percenta
ge restraint increases as the restraint current increases.
For an electromechanical relay, the percentage characteristic must be specified
for each relay; for solid-state electronic or microprocessor-based relays these
characteristics are adjustable. For transformers relays with an additional harmo
nic restraint are available. Harmonic restraint restrains the relay when certain
harmonics, normally the 2nd and 5th, are present.
These harmonics are characteristic of transformer inrush and without harmonic re
straint the transformer inrush may cause the relay to operate.
An important concept in the application of differential relays is that the relay
typically trips fault interrupting devices on both sides of the transformer. Th
is is due to the fact that motors and generators on the secondary side of the pr
otected device will contribute to the fault current produced due to an internal
fault in the device.
An example one-line diagram representation of the transformer differential prote
ction from 1 is given in figure 2 below:
Transformer differential relay application from figure 1 in one-line diagram for
mat
Figure 2 Transformer differential relay application from figure 1 in one-line di
agram format
Note that the secondary protective device is shown as a low voltage power circui
t breaker. It is important that the protective devices on both sides of the tran
sformer be capable of fault-interrupting duty and suitable for relay tripping.
In figure 2 a lockout relay is used to trip both the primary and secondary overc
urrent devices. The lockout relay is designated 86T since it is used for transfo
rmer tripping, and the differential relay is denoted 87T since it is protecting
the transformer. The wye and delta CT connections are also noted.
An important concept in protective relaying is the zone of protection. A zone of
protection is the area that a given protective relay and/or overcurrent device(
s) are to protect.
While the zone of protection concept applies to any type of protection (note the
term zone selective interlockingas described earlier in this section), it is es
pecially important in the application of differential relays because the zone of
protection is strictly defined by the CT locations.
In figure 2 the zone of protection for the 87T relay is shown by the dashed-line
box around the transformer. For faults within the zone of protection, the curre
nts in the CTs will not sum to zero at the relay operating windings and the relay
s will operate.
Outside the zone of protection the operating winding currents should sum to zero
(or be low enough that the percentage restraint is not exceeded), and therefore
the relays will not operate.
Go back to Index
High-impedance differential relays