Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Temperature Rise
Sandwich construction and high conductivity
copper busbar temp.rise less than 55oC at
full load
Schneider Busway
Busbar Insulation
2 layers 0.2mm Mylar insulation
(IEC requires 1 layer)
Excellent dielectric properties
0.1mm Mylar can withstand 7000V
Class B insulation (130oC)
Schneider Busway
Schneider Busway
EZ Joint Pak
Schneider Patten Design
Single bolt connection
Double head
Visible tighten torque
Belleville washer
Tighten torque = 105N-m (70
lb-ft)
Schneider Busway
EZ Joint Pak
Electroplated surface reduce
contact resistance
Each joint pak allows 3 mm
adjustment for thermal
expansion
Reduce installation time and
equipment
Improve reliability
Schneider Busway
Product Range
Feeder, Riser , Plug-in
Common Rating 200A-600A & 800A-5000A
Rated Voltage = 600V
IP rating:
Feeder : IP40, IP41, IP54, IP65, IP66
Plug-in / Riser : IP40, IP54
Schneider Busway
Common Fitting
Elbows
Standard 90o
Schneider Busway
Common Fitting
Elbows
Other shape available upon request e.g.
Double elbows, Offset, Elbow + flanged end
Schneider Busway
Common Fitting
Flanged End
For connection to Switchboard
For connection cable to busduct
Schneider Busway
Common Fitting
Expansion Joint
Allow 38mm expansion
Apply where busduct pass through structural
expansion joint
Schneider Busway
Vertical Hangers
Fixed hangers
Spring Hangers
Apply in new building
Eliminate the effect of
settlement
Schneider Busway
Plug-in Units
Fusible PIU (30A-1600A)
MCCB PIU (16-1600A)
Schneider Busway
Plug-in Units
High level of safety
Complete insulated conductor
Interlocks
Contact earth terminal first
Schneider Busway
System Design
Cable Vs busduct
Choice of breaking capacity, IP rating
Earthing system arrangement
Voltage drop consideration
Provision for expansion
Harmonic issue
Schneider Busway
Cable Vs Busduct
Busduct system have advantage in high ampere
range, say 600A or up
Comparison between cable & busduct
Cable
Busduct
Space requirement
High
Low
Heat Dissipation
Poor
Good
Temperature rise
Poor
Good
Voltage Drop
High
Fair
Electromagnetic Interference
High
Low
Labour Cost
Higher
Lower
Schneider Busway
Schneider Busway
Choice of IP Rating
Minimize water hazard
Horizontal Vs Vertical
Corridor Vs meter room
Schneider Busway
Schneider Busway
Schneider Busway
Provision of Expansion
Thermal expansion
Busbar thermal expansion absorbed by joint
pack
No need to install any expansion joint
Structural expansion
Busduct cannot absorb expansion
Shear force can damage busduct
Expansion fitting should be installed
Schneider Busway
Harmonic Issues
Generated by Non-linear load, e.g. UPS,
Inverters, High frequency lamps
Can overheat neutral conductor
Alter the operation of Tx, Capacity bank
Affect the normal operation of switchgear
nuisance tripping
200% neutral busduct cannot solve the
problem
Apply power control equipment, like harmonic
filter OR Upgrade the whole busduct
Schneider Busway
Installation Procedure
Video of Installation (about 8 minutes)
Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Missing Link
Schneider Busway
Schneider Busway
Contractor-Supplier Interaction
Project Start
Technical support
and routing deisgn
AutoCad Drawing
Installation support
Project
Management
Support
BRASS and
manufacturing
instruction
Fabrication
Schneider Busway
Schneider Busway
Schneider Busway
Maintenance Issues
Vertical spring hanger adjustment
Bowing Symptom
Thermal checking/ scanning
Schneider Busway
Schneider Busway
Schneider Busway
Bowing Symptom
Schneider Busway
Bowing Symptom
Common causes
Misalignment
Improper installation, e.g. loosen bolts
Improper vertical support
Uneven pressure or expansion force the
busduct to bend at weak points
Bowing can make permanent deforming of
busduct
Schneider Busway
Schneider Busway
Trouble shooting
Common causes of burnt busduct
Water/dust ingress during installation stage
Water ingress after energize (for IP40
mainly)
Improper installation, e.g. misalignment,
lossen bolts
Some real examples
Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Schneider Busway
Trouble Shooting
Recommend spare parts
1 pair of flanged ends for each busduct
rating used
A number of plug-in units
24-hours services hotline provided by
Schneider Busway
7298 9771(for HK Market)
Schneider Busway
End of Presentation!
Thank you!