Contents
General presentation
Application
Description
Sulphur hexafluoride gas (SF6) properties
Advantages
Tests
Safety
Reliability/Service continuity
Quality assurance
Standards
Environment
Rating
Principle of interruption and pole sectional view
Operating mechanism
Sepam
Metering and protection unit
Selection table
Current and voltage transformers
General presentation
Wiring diagram
Accessories and ratings of auxiliaries
Overall dimensions
Outdoor circuit breaker GI-E type A
Outdoor circuit breaker GI-E type B
Packing
Installation and commissioning
Order form
Outdoor GI-E
Current transformers
Sepam Series 20
AMTED300042EN.indd
pages
2
2
2
2
3
4
5
6
6
6
7
8
9
10
12
12
13
14
14
16
18
20
20
21
22
23
24
24
25
26
GI-E Range
General presentation
Application
The SF6 outdoor circuit breakers GI-E range are particularly suitable for the
following applications:
b protection of distribution system up to 40.5 kV
b protection of transformers
b switching of capacitor banks
b protection of distribution network characterized by severe conditions of
Transient Recovery Voltage, largely exceeding the IEC requirements.
Description
b SF6 gas (Sulphur Exafluoride Gas) is utilized in the oudoor circuit breakers GI-E
range, for the switching and for the insulation purpose.
b The interrupting system using SF6 gas as medium of interruption is the puffer
type; it is the same system utilized in all the extra high voltage circuit breakers
benefiting of the large experience accumulated by our group, in this field, since
years 60s.
b The breaking chambers of the three poles SF6 gas circuit breakers, GI-E
range, are mounted inside porcelain insulators. They have long creepage
distance which gets the circuit breaker suitable for installation in areas with high
degree of environmental pollution too.
b Every pole is filled with SF6 gas at the rated pressure of 400 kPa gauge,
referred to 20 C.
The monitoring of the pressure of SF6 gas is achieved by using pressure
switches mounted in the lower part of the poles. The pressure switches are
complete with contacts and in case of low pressure, they are suitable to initiate:
v An alarm circuit (first pressure switch contact).
v The electrical block circuit of both closing and opening operations or the block
of any further electrical operations after the automatic opening of the circuit
breaker (second pressure switch contact).
b The three poles are mounted on a base frame hot dip galvanised and operated
by a common three pole spring motorcharged operating mechanism which is
housed in a box having very high degree of protection.
b Option for integrated measuring protection facilities and/or
instrument transformers.
DE60329
b Sulphur hezafluoride gas has been used in the medium voltage and high voltage
electrical switchgears for more than 30 years for its excellent properties and
even more for its remarkable characteristics as a medium of interruption of an
electric
b arc.This gas combines the following main properties:
v high and rapid heat evacuation capacity by convection of the heat originated by
v the switching of the arc;
v high radial thermal conductivity near zero current which allows the cooling of
the arc;
v high electron captation capacity as the very high electronegativity of the
fluorine atoms, at the passage through zero current, captures the free electrons
which are responsible for the electrical conduction.
b Several millions of different types of units using the SF6 gas as a medium of
insulation and interruption are estimated to be currently in service troughout
the world.They are operating with full end-users satisfaction.
v Techniques of interruption using SF6 gas usually do not originate any
switching overvoltages and restrikes of the electric arc, assuring the blow out at
the first zero current.
b SF6 is an insulating gas offering at low pressure too, very high dielectric strength.
At atmospheric pressure its dielectric strength is 2.5 times higher than air.
b SF6 is an inert gas, non toxic, very stable and flame proof.
b The possible presence of humidity in SF6 gas and the minimum quantity of
decomposition products originated by the arc are absorbed by molecular sieves.
v The general properties of new SF6 are described in IEC 60376 section 2,
while
safety aspects, basic information and guidelines for working with SF6 are covered
by IEC 61634.
For additional information about SF6 gas characteristics, end-users can refer to
the above mentioned standards.
AMTED300042EN.indd
Advantages
AMTED300042EN.indd
GI-E Range
General presentation
Tests
b The SF6 gas circuit breakers GI-E range have been fully type tested in accordance
with IEC Standards.
b The type tests have been carried out at laboratories which enjoy high international
reputation as follows:
v CESI (ITALY)
v KEMA (HOLLAND)
v SVEPPI (ITALY)
v LUIGI MAGRINI TEST LABORATORY (ITALY)
Type test evidence and reports are available on customer request.
b All the SF6 gas circuit breakers GI-E range are tested in our workshop before
delivering in accordance with the Routine test list and procedure, as stated in the
IEC Standards. The routine tests carried out on GI-E range circuit breakers are as
follows:
v Power frequency withstand voltage test on the main circuit.
v Dielectric test on auxiliary and control circuit.
v Measurement of the resistance of the main circuit.
v Mechanical operations test, which includes:
a) measurement of resistance of the operation coils and of the heating resistors;
b) measurement of closing and opening times. Check of simultaneous operation
of the three phases;
c) recording of closing and opening speed;
d) check of antipumping device operation;
e) check of all the electrical and mechanical locks and of the signalling devices;
f) check of the auxiliary contacts.
v SF6 gas tightness test.
v SF6 gas humidity test.
v Conformity checks.
The routine test reports are filled in and issued by our quality control department
and they can be available on customer request.
AMTED300042EN.indd
Safety
b The design of the SF6 gas circuit breakers GI-E range has been made in order to
guarantee and to ensure the maximum safety to the installation and
operational personnel.
b SF6 gas monitoring device
The pre-arrangement in every pole of a SF6 gas pressure monitoring system,
by means of pressure switches is able to give remote electrical alarm signals.
b The SF6 gas
The utilization of SF6 gas (very stable and fireproof) as a medium of
interruption makes impossible any fire hazard.
b The electrical clearance
Appropriate clearance distances between phases and between the line terminals
to ground have been provided allowing to assure insulation levels higher than what
foreseen in the Standard IEC.
b Degree of protection
The spring motorcharged operating mechanism is housed in a box having degree
of protection IP 55, with door closed and degree of protection IP 20, with door
open. The design of the operating mechanism box has been performed in order to
safely allow the accessibility to the devices of operation and to the auxiliary
switches.
b Interlocks
The pre-arrangement of a simple and reliable selector switch provided with
mechanical lock prevents any dangerous operations from the remote control
room when the personnel are performing on the circuit breakers local operations.
b Instructions
Complete and exhaustive instruction manual book relevant to the storage,
unpacking, installation, commissioning and ordinary maintenance of the
circuit breaker, is available inside every operating mechanism box.
AMTED300042EN.indd
GI-E Range
General presentation
Reliability/Service continuity
v The design of the SF6 gas circuit breaker GI-E range has been developped in
order to assure high reliability during the whole expected service life.
v The reliability of the equipment is not only derived from the experience of the
service, as it is planned at the time of design of all components by means of
severe mechanical endurance tests and by the application of severe quality
control procedures.
v The circuit breakers GI-E range assure long continuity of service because of the
following features:
v long proven experience with the technique of interruption of the electric arc by
the system of self-compression and selfregulation of the SF6 gas pressure,
v high guarantee of gas tight enclosures assured by the reliability of the design of
v the sealing system and by severe tests performed in our work-shop before
delivering to sites, simple maintenance usually confined to quick periodical
checks,
v easy and fast replacement of the main components, steady remote control of
the condition of the insulating medium,
v suitability for installation in any environment with temperatures ranging from
-25C up to +40C. For higher performances, please consult our technical
department.
Quality assurance
v High technology product like the GI-E range calls for the application of a quality
assurance program which goes beyond the usual acceptance test.
v The design of the SF6 gas circuit breaker GI-E range has been strictly made in
accordance with the high quality level ISO 9001 which concernes all the process
of design, manufacturing up to the after sale service management.
v Quality assurance organisation in force since 1975 and control procedures
applied to all the activities, from work shop to office work, guarantees the high
degree of quality conformity.
v The certificate of compliance with the standard EN 29001 (ISO 9001) achieved
by the quality assurance system in force in our company is the evidence of our
steady commitment towards the quality. Schneider Electric has been qualified by
CSQ, the official independent certification body in the electric field in Italy.
Standards
b The SF6 gas circuit breakers GI-E range for outdoor installation comply with the
following standards:
- International standards IEC 60056 (1987) and IEC 62271-100 (2001) High
voltage alternating current circuit breakers.
AMTED300042EN.indd
Environment
GI-E Range
PE60244
PE60245
AMTED300042EN.indd
kV
24-36-40,5
24-36-40,5
kV
kV
80 (3)
80 (3)
200
200 (2)
(2)
Type A
Rated normal current (1)
630A
1250A
1600A
2000A
3150A
kA
kA
kA
A
A
ms
ms
ms
ms
16
16
40
20
20
50
630
31,5 - 50 (***)
33/50
15
48/65
60/83
25
25
63
b
b
400
10
500-1600 (shunt reactor switching)
3-6-12 (no load transformer switching)
Type B
b
b
16
16
40
20
20
50
25
25
63
31,5
31,5
80
1250
31,5 - 50 (***)
30/43
15
45/58
57/80
b
b
400
10
500-1600 (shunt reactor switching)
3-6-12 (no load transformer switching)
GI-E Range
E28670
E28673
fig.2
E28671
E28672
fig.1
fig.3
DE60330
fig.4
PE41156
b The SF6 gas circuit breaker GI-E range is equipped with a well proven stored
energy type operating mechanism, series GMh, suitable for three-pole reclosing.
This type of operating mechanism has been used for many years in the indoor
circuit breakers too and it is proven by a long service experience. The spring
motorcharged operating mechanism has been designed in order to assure a long
mechanical life.
b The operating mechanism is stored energy type.
v The closing springs are charged by a motoreducer that can be operated either
by d.c.or by a.c.operating voltages;
v after every closing operation the motoreducer automatically recharges the closing
spring.(Charging time is less than 15 seconds) The opening springs get charged
with the energy stored by the closing spring during the circuit breaker closing
operation;
v in case of emergency the springs can be manually charged by means of hand
charging lever. This device is removable type, located on the front of the
operating mechanism;
v the stored energy is capable to carry out the O-C-O cycle without recharging.
b Opening and closing operations have a speed independent from the operator one.
b The opening and closing operations of the circuit breaker can be performed
either electrically by means of electrical push buttons, operating opening and
closing coils, or manually, by means of mechanical push buttons.
v The mechanical and electrical push buttons are provided on the front of
the operating mechanism.
b The electrical closing and opening operations can be performed either locally
or remotely.
v The operating mechanism is equipped with a 3 positions selector switch, (local/
zero/remote positions with withdrawble key in zero and remote positions and with
N1 aux.contact available in order to remotely signalize the local and zero
positions).
The spring motorcharged operating mechanism complete of all its operating
and control devices is housed in an hot dip galvanised box.
PE60235
b All the exposed ferrous parts of the operating mechanism box (and of the
supporting structure too) are hot dip galvanised (600 g/m2) in accordance with
Standard UNI 5744 which substantially corresponds to Standard BS 729, ASTM
123- 153 and DIN 50976.
v The operating mechanism box has been designed in order to prevent the entry
of water and the deterioration of the mechanism due to the condensation that
could be originated by the humidity.
v In accordance with standard IEC 529, the operating mechanism box has a
degree of protection IP 55;
v the operating mechanism box is complete with two heaters, one of which
is permanently on, while the other one is controlled by a thermostat.
b The accessibility to the operating and control devices of the spring
motorcharged operating mechanism and the watertightness of the operating
mechanism box is provided by means of a door, hinged on the left side and by a
proper gasket.
b A facility for the locking of the door by padlock device mounted on the door,
is provided.
b The mechanical position indicators as well as the operation counter, which are
mounted inside the operating mechanism box, are visible from the outside
through inspection windows located on the front door of the box.
b The indication of the circuit breaker position (open-closed) is achieved by
means of a mechanical position indicator. The indication is stressed as follows:
v open position: with a black letter O engraved on a green background
v closed position: with a white letter I engraved on a red background.
b A gland plate for the cable entry is provided in the bottom of the
operating mechanism box.
v The gland plate must be purposely drilled on site.
v The available surface is 200x400 mm.
v The cable glands are usually provided by the contractors.
AMTED300042EN.indd
11
GI-E Range
Sepam
PE41157
Optional Sepam Series 20 unit can be installed inside the operating mechanism
box, visible from the outside through inspection windows located on the front door
of the box.
Metering functions:
Currents
b RMS measurement of the circuits 3 phase currents.
b Residual current measurement.
Average currents and peak demand currents Measurement of the
average current on each of the 3 phases. Measurement of the
greatest average current on each of the 3 phases.
The peak demand currents give the current consumed at the time of peak loads.
The average current is calculated over a period that may be parameterized from 5
to 60 mn. The clear key is used to reset the peak demand currents to zero when
they are on the display.
Tripping currents
Storage of the greatest average value of the 3 phase currents and earth current
at the time Sepam gave the last tripping order, to provide the fault breaking
current (fault analysis).
These values are stored until the next trip order is given.
Diagnosis measurements:
Cumulative breaking current
The displayed value may be used to evaluate the state of the circuit breaker poles.
Operating time, charging time
Measures the device operating time. These data may be used to evaluate the
state of the pole and operating mechanism.
Number of operations
Cumulative number of breaker opening operations.
Running hours counter / operating time
Cumulative time during which the protected equipment is on load (I > 0.1 Ib).
The cumulative value is displayed in hours (0 to 65535 h) and saved every 4 hours.
Phase overcurrent (ANSI 50/51)
Three-phase protection against overloads and phase-to-phase short-circuits.
The protection comprises four units:
b IDMT or definite time,
b instantaneous or time-delayed.
Sepam Series 20 offers a number of tripping curves:
b definite time (DT),
b IDMT.
The IDMT curves also include a reset time which is used for:
b detection of restriking faults,
b coordination with electromechanical relays.
Earth fault (ANSI 50/51N or 50/51G)
Connection and equipment earth fault protection.
Earth faults may be detected by three phase currents (3I sum).
The protection comprises four units:
b IDMT or definite time,
b instantaneous or time-delayed.
The characteristic curves are the same as those for the phase current
overcurrent protection.
Each set point has a reset time setting (by an adjustable timer hold with definite
time characteristic) that allows restriking faults to be detected.
Each set point has a 2nd harmonic restraint in order to ensure stability
during transformer energizing.
Negative sequence / unbalance (ANSI 46)
Protection against phase unbalance.
Sensitive protection against 2-phase faults on long feeders.
Protection of equipment against temperature build-up caused by an
unbalanced supply or wrong phase rotation or the loss of a phase and
protection against low levels of phase-to-phase overcurrent.
IDMT or definite time characteristics.
Recloser (ANSI 79)
Automation device used to reclose the circuit breaker after tripping triggered by
a transient fault on a line (the function includes 4 parameterizable reclosing
cycles).
12
AMTED300042EN.indd
GI-E Range
Sepam
Selection table
Sepam Series 20
functions
protections
phase overcurrent (1)
earth fault (or neutral) (1)
unbalance / negative sequence
thermal oveload
rate of change of frequency
recloser (4cycles)
thermostat / Buchholz
temperature monitoring (2)
metering
phase current I1, I2, I3 RMS
residual current Io
average current I1, I2, I3
peak demand phase current IM1, IM2,
IM3 temperature measurement (2)
network diagnosis
tripping current I1, I2, I3, Io
unbalance ratio / negative sequence current li
running hours counter / operating time
thermal capacity used
remaining operating time before overload tripping
waiting time after overload tripping)
disturbance recording
switchgear diagnosis
cumulative breaking current (2)
trip circuit supervision
number of operations
operating times
self-diagnosis
watchdog
output realy test (3)
control and monitoring
circuit breaker / contractor control (4)
logic discrimination
4 addressable logic outputs
additional modules
MET 148 module - 8 temperature sensor
inputs MSA 141 module - 1 low level analog
output108 module - (4I/4S) or MES 114 module - (10I/4O)
MES
ACE 949-2 module - (2-wire) or ACE 959 (4-wire) RS485
interface
Detailed brochure of Sepam unit is available on request.
type of Sepam
ANSI code
50/51
50N/51N
46
49 RMS
81R
79
S20
4
4
1
T20
4
4
1
2
v
v
v
38/49T
b
b
b
b
b
b
b
b
v
b
b
b
b
b
b
b
b
b
b
v
v
v
b
v
v
v
b
v
b
v
v
v
b
v
v
b
v
v
v
v
v
v
v
standard
according to parameter setting and MES 108 or MES
114 input/output module options.
(1)4 relays with the exclusive possibility of logic
discrimination or switching from one 2-relay group of settings
to another 2- relay group.
(2)with MET 148 sensor option, 2 set points per sensor.
(3)with advanced UMI option only.
(4)for shunt trip unit or undervoltage release coil according
to parameter setting.
AMTED300042EN.indd
13
GI-E Range
DE60331
14
Product quality over time is guarantee not only by thirty years experience in the
field of resin insulated instrument transformer manufacturing but also by:
b the use of silica-loaded epoxy resin resulting in
v high dielectric strength including at high temperatures (18kV/mm at 180C
for 20.000 hours),
v insulation class B according to IEC 44-1 provisions.
b extremely good ageing behaviour both to heat mass ageing according to
IEC216 (over 20 years at 120C) and to surface ageing obtained in salty mist.
b In case of fire, no toxic substances are released in accordance with standards
CEI 20-37, CEI 20-22 and ASTM D3286.
b Extremely effective behaviour in tropical climates.
b High strength even at the highest working temperatures (Martens point
exceeding 105C).
b Accurate production process resulting in:
v no blisters or blowholes in the resin thanks to vacuum casting;
v low constant partial discharge figure also thanks to the high quality of the
other insulating materials used (SF6 injection in voltage transformer windings);
v high strength and very good electric conductivity in primary and
secondary terminals even at the temperatures reached during a short
circuit, thanks to mechanical seaming;
process parameters remaining unchanged over time thanks to computer
control used to manage and monitor the whole production line.
AMTED300042EN.indd
PE60237
PE60238
PE60239
Characteristics:
Standard reference: IEC 60044-2
Standard primary voltage Up: 30 - 33 - 35 kV
Rated insulation level: 36 kV
Rated secondary voltage Us: 100: 3 100 : 3 110: 3 110 : 3 V
Frequency: 50 or 60 Hz
Rated voltage factor: 1,9 for 8 hours
Thermal burden: 450 VA
DE60332
GI-E Range
DE6033
Optional
Wiring diagram
CIRCUITS
(1) closing
(2) opening and SF6 gas monitoring
(3) closing springs charging motor
(4) a.c. auxiliaries: heaters, current socket, lightning
(5) undervoltage opening release
(6) available aux. contacts
(7) ammetrical connection for Sepam
(8) auxiliary connection for Sepam
(9) Sepams aux. contacts
(10) Sepams available aux. contacts
LEGEND:
EC anticondensation resistor
EL lightning lamp
ET heating resistor
F1 Sepam
KN antipumping relay
KP pressure switches aux. relay (locking)
M spring charging gear motor
QC MCCB for the protection of the closing circuit
QE MCCB for the protection of the heating and anticondensation
resistors QL lightning lamp switch
QM MCCB for the protection of the spring charging motor
circuit QO MCCB for the protection of the opening circuit
RUM varistor (resistor voltage dependent)
RYU resistor for the YU circuit
SC closing push botton
SM1-2 end limit switches of the springs charging gear motor
SO opening push botton
SOO consent contact to close the circuit
breaker SPA1-2-3 pressure switches alarm
contacts SPB1-2-3pressure switches locking
contacts SQ1-2 circuit breaker aux. contacts
SS selector switch D-0-L (remote - zero - local)
ST thermostat
XC terminal block to sectionalize the closing circuit
XE terminal block to sectionalize the anticondensation and heating resistors
circuits XE1 bivalent socket
XE2 bivalent socket
XM terminal block to sectionalize the spring charging gear motor
circuit XO terminal block to sectionalize the opening circuit
XU terminal block to sectionalize the under voltage release
circuit YC closing release
YU under voltage release
Y01 opening release
Y02 additional opening release GI-E Range
GI-E Range
b Closing springs gear motor (M) complete with end limit switches (SM1-SM2)
b Electric contacts indicating that closing springs are charged (SM1)
b Closing release (YC)
b Opening release (Y01)
b Antipumping relay (KN)
b Pressure switch with 2 contacts (SPA-SPB) (one pressure switch for each pole)
b Aux.pressure switches relay (KP)
b Local/zero/remote selector switch (SS)
b Terminal block to sectionalize the closing spring gear motor circuit (XM)
b Terminal block to sectionalize the anticondensation and heating resistors
circuit (XE)
b Terminal block to sectionalize the opening circuit (XO)
b Terminal block to sectionalize the closing circuit (XC)
b Mechanical position indicator of circuit breaker position (open-closed)
b Mechanical indicator of springs condition (charged-released)
b Mechanical operated operation counter
b 11NA+9NC free aux.contacts
b Mechanical close-opening push buttons
b Electrical close-opening push botton (SO-SC)
b Anticondensation resistor (EC)
b Heating resistor and thermostat (ET+ST)
b Operating mechanism box with degree of protection IP 55
b Operating mechanism box hot dip galvanised (600g/m2 average coating value)
b Hot dip galvanized supporting structure
b Poles lifting facilities
b Grounding facilities (holes)
b Fixing anchor bolts
b Spring charging lever
b Packing: wooden structure covered with plywood panels
b Nota: the porcelain insulators of the poles are brown coloured, RAL 8016.
Optional accessories
b Additional opening release (Y02)
b Under voltage release (YU)
b MCCB complete of aux.contact for protection of the circuit of the spring
charging gear motor (QM)
b MCCB complete of aux.contact for protection of the circuit of the
anticondensation and heating resistors (QE)
b MCCB complete of aux.contact for protection of the opening circuit (QO)
b MCCB complete of aux.contact for protection of the closing circuit (QC)
b Mechanical interlock Ronis type;with key removed, the circuit breaker
is mechanically locked in open position
b Key padlock device mounted on the door of the operating mechanism box
b Portable lightning lamp (EL)
b 2 poles + earth bivalent outlet socket 10-16A/250V a.c.(XE1+XE2)
b Hot dip galvanized supporting structure suitable to fit outdoor current transformers
b Earthing clamp
b Cables clamp
b Flexible connection between C.B. and C.Ts.
b SF6 gas filling device
b SF6 gas (bottles by 5 kg or 20 kg each)
b RAL 7035 grey colour porcelain insulators
b Digital control and protection unit Sepam (see pages 10-11)
GI-E Range
Overall dimensions
GI-E Range
DE60334
Rated current
24 GI-E 16
24 GI-E 20
24 GI-E 25
630A
1250A
1600A
2000A
3150A
Dim.type A
Dim.type A
Dim.type A
Dim.type A
Dim.type A
Dim.type A
Dim.type
Dim.type
Dim.type
Dim.type
Dim.type
A
A
A
B
B
24 GI-E 31
Dim.type B
Dim.type B
36 GI-E 16
36 GI-E 20
Dim.type A
Dim.type A
Dim.type A
Dim.type A
Dim.type A
Dim.type A
Overall dimensions
GI-E Range
DE60335
Rated current
36 GI-E 25
630A
1250A
1600A
2000A
3150A
Dim.type
Dim.type
Dim.type
Dim.type
Dim.type
A
A
A
B
B
36 GI-E 31
Dim.type B
Dim.type B
40 GI-E 16
40 GI-E 20
40 GI-E 25
40 GI-E 31
Dim.type A
Dim.type A
Dim.type A
Dim.type A
Dim.type A
Dim.type A
Dim.type
Dim.type
Dim.type
Dim.type
Dim.type
Dim.type B
Dim.type B
A
A
A
B
B
PE60240
GI-E Range
Packing
b The packing has been designed in order to guarantee the correct protection of
the equipment during transportation and during the short time of storage before
assembly and commissioning in the substation take place.
v In addition, on specific customer request, the operating mechanism box can be
protected by means of a thermic-weld barrier bag, complete of sufficient quantity of
dehydrated salt suitable to keep the internal humidity below 35% referred to 20C,
for a maximum period of 12 months.
PE60241
b Every crate includes the three sets of poles, the operating mechanism box
and the loose elements of the supporting structure.
The gross weight of the case including the equipment is as follows:
v roughly 900 kg for circuit breaker with dimensions type A
v roughly 950 kg for circuit breaker with dimensions type B
v If are requested, the SF6 gas bottles for the first filling and the refilling devices
are delivered in separate cases.
PE60242
GI-E Range
Points to note
During the installation procedure, warning shall have to be taken in order
to assembly the operating mechanism and the three pole set having the
same serial number.
b In case of transportation by sea/truck, the GI-E circuit breakers poles are
shipped at rated SF6 pressure; therefore it is not necessary to carry out any gas
filling at site. It means that the SF6 bottles are not needed, as the GI-E poles will
be supplied at the rated SF6 pressure.
b In case of air-transportation, in accordance with the safety transport regulation in
force, the GI-E circuit breakers poles have to be shipped at a reduced pressure (50
kPa relative pressure). It means that, when the installation of the equipment has
been completed, the poles have to be re-filled with SF6 gas up to the rated
pressure. As the SF6 gas bottles for the first filling, as well as the refilling device
are supplied if requested.
b After the circuit breaker has been installed and all the connections to the
auxiliaries and to the line have been completed, the end user may personally
conduct the commissioning test, in order to check that no damages have
occurred during transportation and storage.
b The series of test shall be carried out in accordance with manufacturers
instructions, as for what concerns the kind of test to be performed, as well as for
what concerns the limits of the acceptable values. In this regard the IEC 62271-100
(2001) recommendations will govern too.
GI-E Range
Order form
Outdoor GI-E
Calculation zone
Quantity
Rated voltage Ur
(kV)
(kA)
Rated current Ir
Rated frequency
50 Hz
60 Hz
Rated operating sequence
O-0,3s-CO-3min-CO
Protection of the auxiliary circuits
by terminal block
Electrical motor - M
24 Vdc
110 Vdc
48 Vdc
125 Vdc
60 Vdc
220 Vdc
Closing shunt release - YC
24 Vdc
110 Vdc
48 Vdc
125 Vdc
60 Vdc
220 Vdc
1st opening shunt release - Y01
24 Vdc
110 Vdc
48 Vdc
125 Vdc
60 Vdc
220 Vdc
Heating resistors - ET+EC
110 V (50-60 Hz)
(A)
O-0,3s-CO-15s-CO
by MCCB
110 Vac (50 Hz)
127 Vac (50 Hz)
220 Vac (50 Hz)
English
Spanich
Leaflets language
French
Italian
Options
2nd opening shunt release - Y02
24 Vdc
110 Vdc
48 Vdc
125 Vdc
60 Vdc
220 Vdc
Undervoltage release - YU
24 Vdc
110 Vdc
48 Vdc
125 Vdc
60 Vdc
220 Vdc
Accessories
First filing device
SF6 gas for first filing (each CB needs 2 kg)
5 kg cylinder
20 kg cylinder
40 kg cylinder
quantity
quantity
quantity
quantity
Order form
GI-E Range
Current transformers
Current transformers
Type
Quantity
Cubicle type
Quantity
Standard
IEC
Frequency
ANSI
AS
50Hz
12
Number of secondaries
Rating plate language
60Hz
17.5
24
36
French
English
Spanish
Primary
Rated short time current
Rated primary current
1st rated (A)
(kA)
(kA)
Secondary
1st primary
protection
2nd primary
measure
protection
measure
3nd primary
protection
measure
(A)
(A)
(VA)
(VA)
Rated output
(VA)
Accuracy class
Sepam Series 20
Sepam Series 20
Type of sepam
Type
Integrated
advanced UMI
Substation
S20
Quantity
Transformer
T20
Quantity
working language
English / French
English / Spanish
English / Italian
English / Swedish
English / Polish
24Vdc
48 to 250Vdc or 100 to 240Vda
Quantity
SFT 2841
Quantity