Вы находитесь на странице: 1из 6

Diagnostic of Silicon Carbide Surge Arresters

using Leakage Current Measurement


A. G. Kanashiro, Member, IEEE, M. Zanotti Jr, P. F. Obase and W. R. Bacega

Abstract Nowadays, the zinc oxide surge arresters (ZnO) are


widely used in power systems, however, a large number of silicon
carbide surge arresters (SiC) are still in service in the utilities.
On the other hand, it is not possible to replace all SiC surge
arresters in a short time period, being necessary to review the
maintenance program taking into account the surge arresters
that are more degraded. In this context, a research project was
established between the University of So Paulo and the electrical
utility CTEEP, aiming the investigation of its SiC surge arresters.
This work shows that the leakage current measurement, a
diagnostic method for the ZnO surge arresters, can provide
useful information related to the condition of the SiC surge
arresters. Analysis of the amplitude and distortion of the leakage
current, also considering thermovision measurements, resulted in
better evaluation of the SiC surge arresters.
Keywords silicon carbide, leakage current, degradation,
surge-arresters, thermovision.

I. INTRODUO
M funo dos custos envolvidos e de dificuldades
operacionais no possvel realizar a substituio total dos
pra-raios de SiC a curto prazo, obrigando a
concessionria a conviver com as duas tecnologias no
sistema eltrico durante vrios anos [1]-[4]. Portanto,
torna-se imprescindvel o estabelecimento de critrios que
considerem o estado atual dos pra-raios de SiC, procurandose priorizar a retirada dos equipamentos mais crticos e
programar a substituio gradativa daqueles ainda instalados
nas subestaes de energia, antes da ocorrncia de alguma
falha.

Com o objetivo de estabelecer um melhor gerenciamento


dos pra-raios de SiC, foi firmado um convnio entre o
Instituto de Eletrotcnica e Energia da USP (IEE/USP) e a
CTEEP Companhia de Transmisso de Energia Eltrica
Paulista. Inicialmente, foi realizada uma pesquisa exaustiva no
sistema MANTEC, onde os dados dos equipamentos so
normalmente cadastrados na concessionria.
Os autores agradecem o apoio financeiro recebido da CTEEP - Companhia
de Transmisso de Energia Eltrica Paulista, dentro do Programa de P&D
ANEEL.
A. G. Kanashiro, Instituto de Eletrotcnica e Energia da USP,
arnaldo@iee.usp.br
M. Zanotti Junior, Instituto de Eletrotcnica e Energia da USP,
zanotti@iee.usp.br
P. F. Obase, Instituto de Eletrotcnica e Energia da USP,
pfobase@iee.usp.br).
W. R. Bacega, Companhia de Transmisso de Energia Eltrica Paulista,
wbacega@cteep.com.br

Atravs de ferramentas computacionais, desenvolvidas para


essa finalidade, foram realizadas vrias correlaes com os
dados do MANTEC, considerando-se a idade dos pra-raios
de SiC, fabricante, classe de tenso, etc. Com base nessas
correlaes, foram identificados os pra-raios que deveriam
ser investigados mais detalhadamente no laboratrio. Essa
investigao deveria tambm contemplar a determinao de
tcnicas de diagnstico que pudessem resultar em melhor
resposta quanto a real condio do estado dos pra-raios de
SiC.
A avaliao dos pra-raios selecionados foi realizada no
Laboratrio de Alta Tenso do IEE/USP e os seguintes
ensaios foram considerados: tenso disruptiva de impulso
atmosfrico, tenso disruptiva em freqncia industrial e
medio da corrente de fuga total. Foram tambm realizadas,
em alguns pra-raios, medies de termoviso, tenso de
radio-interferncia (RIV), resistncia de isolamento e de
perdas Watts, procurando-se obter informaes que pudessem
resultar em um melhor diagnstico dos pra-raios.
Os resultados obtidos nos ensaios de tenso disruptiva em
freqncia industrial e de tenso disruptiva de impulso
atmosfrico foram comparados com os requisitos dos
fabricantes e de normas tcnicas. A maioria dos pra-raios
atendeu os requisitos, entretanto, medies da corrente de
fuga, RIV e termoviso indicaram que algum processo de
deteriorao estava presente. Posteriormente, a inspeo visual
nos componentes internos dos pra-raios confirmou essa
hiptese.
A metodologia utilizada na pesquisa permitiu a
determinao de tcnicas que resultaram em um diagnstico
mais adequado dos pra-raios de SiC. A medio da corrente
de fuga, tcnica geralmente utilizada nos pra-raios de ZnO
[5]-[8], resultou em importantes informaes sobre o estado
do pra-raios de SiC, possibilitando a identificao de
amostras que estariam sofrendo algum processo de
envelhecimento mais acentuado, apesar de terem sido
aprovadas nos ensaios de tenso disruptiva em freqncia
industrial e de impulso atmosfrico. Os resultados obtidos na
pesquisa iro subsidiar a elaborao de um programa de
substituio dos pra-raios de SiC, priorizando-se a retirada
dos pra-raios mais degradados.
Este trabalho apresenta os resultados referentes a 18 pra-

raios de 138 kV, dentre aqueles submetidos aos ensaios [9].


importante salientar que as investigaes no laboratrio
tiveram como premissa a considerao de que o pra-raios no
poderia ser desenergizado no campo, quando da utilizao de
alguma tcnica de diagnstico.
II. METODOLOGIA
Os pra-raios disponibilizados no IEE estavam no
almoxarifado da CTEEP e foram retirados de servio em
funo da substituio dos pra-raios de SiC pelos de ZnO,
reformas na subestao ou, ainda, devido ao aquecimento
anormal detectado durante as medies rotineiras de
termoviso. Esses pra-raios apresentavam, em maior ou
menor grau, corroso nas partes metlicas.
Os pra-raios de SiC estiveram em operao por mais de 20
anos e no foi possvel obter um histrico de medies que
pudesse trazer informaes sobre o seu comportamento e a sua
degradao ao longo do tempo. Portanto, antes da realizao
dos ensaios, e at por questes de segurana no laboratrio,
algumas amostras foram submetidas s medies de
resistncia de isolamento e de perdas Watts, tendo-se por
objetivo verificar, preliminarmente, a sua integridade.
Em seguida, foram realizados em todos os pra-raios,
ensaios de tenso disruptiva de impulso atmosfrico e de
tenso disruptiva em freqncia industrial (60 Hz). Esse
procedimento foi adotado pelo fato de no existirem dados
histricos de medies no campo, e, portanto, os nicos
parmetros que poderiam ser utilizados para indicar possveis
variaes em relao s suas caractersticas originais, eram os
valores de tenso disruptiva, tanto em freqncia industrial
como de impulso atmosfrico. Inicialmente, esses parmetros
foram utilizados como referncia, sendo comparados com
aqueles apresentados em normas e catlogos do fabricante.
Nesses ensaios, foram tambm realizados registros da
corrente de descarga durante a disrupo do pra-raios. O
objetivo era identificar possveis variaes no comportamento
da corrente de descarga, em termos de amplitude e forma de
onda, que pudessem estar relacionadas com a degradao do
pra-raios. Entretanto, os resultados obtidos com esse
procedimento no se mostraram promissores.
Aps a finalizao dos ensaios de tenso disruptiva em
freqncia industrial e de impulso atmosfrico, os pra-raios
de SiC foram submetidos s medies da corrente de fuga
total, visando a obteno da amplitude e da componente de
terceira harmnica (3 H). Este procedimento foi baseado no
fato de que valores mais elevados da corrente de fuga, em
termos de amplitude e/ou da componente 3 H, poderiam estar
relacionados com a existncia de degradao mais acentuada
de um pra-raios quando comparado com outros de mesmo
fabricante. Nesse caso, a corrente de fuga total, originalmente
com predominncia capacitiva, passaria a apresentar uma
parcela resistiva mais significativa e, conseqentemente,
maior distoro harmnica. Com o objetivo de obter
informaes adicionais, foi tambm determinada a defasagem

entre a tenso aplicada e a corrente de fuga total do pra-raios.


As medies foram realizadas na tenso de 80 kV, que a
tenso de operao dos pra-raios no sistema de 138 kV da
concessionria.
Posteriormente, alguns pra-raios foram submetidos aos
ensaios de termoviso e de tenso de radio-interferncia
(RIV), com freqncia de medio 500 kHz e impedncia de
300 ohms [10].
III. ANLISES E RESULTADOS OBTIDOS
A Tabela I mostra os resultados obtidos nos ensaios de
tenso disruptiva em freqncia industrial e de tenso
disruptiva de impulso atmosfrico, referentes aos pra-raios de
138 kV. Os valores de tenso disruptiva em freqncia
industrial dos pra-raios PrC5 (fabricante C), PrD3 e PrD5
(fabricante D), no atenderam os requisitos do fabricante.
Com relao ao ensaio de tenso disruptiva de impulso, todos
os pra-raios foram aprovados.
TABELA I
TENSO DISRUPTIVA EM FREQNCIA INDUSTRIAL E DE IMPULSO
ATMOSFRICO DOS PRA-RAIOS DE 138 KV

Pra-raios

Tenso
disruptiva em
freqncia
industrial
(kV)

Tenso disruptiva de impulso


atmosfrico (kV)
Polaridade
positiva

Polaridade
negativa

PrB1

244

284

272

PrB2

246

279

272

PrB3

242

287

294

PrB4

233

234

225

PrB5

237

234

229

PrB6

241

271

269

PrB7

232

272

272

PrC1

226

382

354

PrC2

219

374

363

PrC3

224

364

359

PrC4

218

340

322

PrC5 (R)

188

349

344

PrC6

233

355

344

PrD1

274

374

367

PrD2

273

376

372

PrD3 (R)

268

376

366

PrD4

271

372

369

PrD5 (R)

268

378

369

(R) pra-raios reprovado no ensaio de tenso disruptiva em freqncia


industrial.

Durante a execuo dos ensaios de tenso disruptiva em


freqncia industrial e de impulso, foram registradas as
formas de onda da corrente de descarga dos pra-raios. Como
ilustrao, a Fig. 1 mostra o registro das formas de onda da

tenso, onde possvel observar o instante da disrupo do


pra-raios, e a respectiva corrente de descarga. Os sinais de
alta freqncia no so provenientes do pra-raios. A anlise
dos vrios registros das correntes de descarga no levou
obteno de informaes sobre o estado interno dos praraios.

Esses pra-raios apresentaram valores menores de


defasagem. As Fig. 2, 3 e 4 mostram as formas de onda da
tenso aplicada e das respectivas correntes de fuga total dos
pra-raios PrB1, PrB5 e PrB6.
TABELA II
CORRENTE DE FUGA DOS PRA-RAIOS DE 138 KV
Corrente de fuga

400

Tenso (kV)

PrB1

Valor
pico
(mA)
0,226

3 H
(%)
4,8

72

-100

PrB2

0,252

5,7

70

-200

PrB3

0,370

6,0

77

PrB4

0,234

6,4

68

PrB5

0,251

6,8

68

PrB6

0,230

8,5

63

PrB7

0,261

9,4

53

PrC1

0,363

5,6

73

PrC2

0,456

5,8

75

PrC3

0,346

6,8

79

200
100
0

-300
-400
0

25

50

75

100

Tempo (ms)
(a)
3,0
2,0

Corrente (A)

Defasagem
(graus)

Pra-raios

300

1,0

PrC4

0,332

6,9

68

0,0

PrC5 (R)

0,430

7,5

83

-1,0

PrC6

0,726

18

51

PrD1

0,364

1,9

89

PrD2

0,357

2,1

89

PrD3 (R)

0,357

2,1

82

PrD4

0,330

2,5

84

PrD5 (R)

0,331

3,8

78

-2,0
0

25

50

75

100

Tempo (ms)
(b)
Figura 1. Formas de onda obtidas no ensaio de tenso disruptiva em
freqncia industrial.
a) tenso aplicada ao pra-raios
b) corrente de descarga durante a disrupo do pra-raios

Os pra-raios do fabricante B (PrB1 a PrB7) apresentaram


valores de pico da corrente de fuga total na faixa de 0,226 mA
a 0,370 mA. Os valores percentuais de 3 H foram de 4,8 % a
9,4 % e os mais elevados foram registrados nos pra-raios
PrB6 e PrB7, o que poderia indicar a existncia de maior
degradao dos seus componentes internos.

0,4
Tenso (Vef = 80 kV)

0,2

Corrente (A)

O prximo passo foi a medio da corrente de fuga total do


pra-raios, a qual foi obtida atravs do registro da tenso sobre
um resistor conectado entre a base do pra-raios e o terra do
laboratrio. As formas de onda da tenso aplicada e da
corrente de fuga total foram registradas atravs de um
osciloscpio digital. A tenso aplicada foi igual a 80 kV. A
Tabela II mostra os valores de pico da corrente de fuga total e
os valores percentuais da componente de terceira harmnica
(3 H). Os resultados so mostrados em ordem crescente da
distoro harmnica da corrente de fuga total. mostrada
tambm a defasagem entre a tenso aplicada ao pra-raios e a
corrente de fuga total.

(R) pra-raios reprovado no ensaio de tenso disruptiva em


freqncia industrial.

0
Corrente

-0,2

-0,4
0

10

15

20

25

30

35

40

Tempo (ms)

Figura 2. Formas de onda da tenso e da corrente de fuga do pra-raios PrB1.

O t mximo refere-se maior diferena encontrada. A


temperatura mxima refere-se maior temperatura obtida no
pra-raios.

0,4

Corrente (mA)

Tenso (Vef = 80 kV)

0,2

A Tabela III apresenta os resultados da medio de


termoviso, realizada em alguns pra-raios, e a comparao
com os respectivos valores de corrente de fuga.

Corrente

-0,2

TABELA III
TERMOVISO E CORRENTE DE FUGA DOS PRA-RAIOS DE 138 KV
-0,4
0

10

15

20

25

30

35

PrB2
PrB3

0,370

6,0

77

28,3

4,3

PrB6

0,230

8,5

63

27,9

4,4

PrC3

0,346

6,8

79

19,9

2,6

PrC5 (R)

0,430

7,5

83

19,3

2,8

PrC6

0,726

18

51

32,6

17,6

PrD1

0,364

1,9

89

18,1

1,7

PrD3 (R)

0,357

2,1

82

18,2

1,9

Pra-raios
Figura 3. Formas de onda da tenso e da corrente de fuga do pra-raios PrB5.
0,4

Corrente (mA)

Tenso (Vef = 80 kV)

0,2

-0,2

Corrente

-0,4
0

10

15

20

25

30

35

40

Tempo (ms)

Termoviso (0C)

Corrente de
fuga
Valor
pico
3 H
(mA)
(%)
0,252
5,7

40

Tempo (ms)

Defasagem
(graus)

temp.
mxima

t
mximo

70

28,0

4,6

(R) pra-raios reprovado no ensaio de tenso disruptiva em freqncia


industrial.

Figura 4. Formas de onda da tenso e da corrente de fuga do pra-raios PrB6.

O pra-raios PrC5, reprovado no ensaio de tenso


disruptiva em freqncia industrial, apresentou corrente de
fuga com amplitude de 0,430 mA e componente de 3 H igual
a 7,5 %, valor ligeiramente maior em relao aos demais praraios do mesmo fabricante. Foi registrada uma defasagem de
83o. O pra-raios PrC6 apresentou corrente de fuga com
amplitude igual a 0,726 mA, distoro harmnica de 18 % e
defasagem de 51o. Esses valores destacam-se dos demais
resultados, indicando que uma degradao mais acentuada
estaria presente nesse pra-raios, apesar da sua aprovao no
ensaio de tenso disruptiva em freqncia industrial.
Os pra-raios PrD3 e PrD5 foram reprovados no ensaio de
tenso disruptiva em freqncia industrial. O PrD5 apresentou
maior distoro e menor defasagem, quando comparado com
outros pra-raios de mesmo fabricante.
O passo seguinte foi a realizao de medies de
termoviso, as quais foram realizadas somente em alguns
pra-raios. As leituras de termoviso foram registradas aps os
pra-raios estarem energizados por um perodo de 5 a 7,5
horas, dependendo do fabricante. O corpo do pra-raios foi
dividido, longitudinalmente, em 4 lados, sendo realizada uma
medio em cada lado. Uma medio corresponde imagem
trmica obtida ao longo do pra-raios, do topo at a sua base.
Em cada lado, foram determinadas as temperaturas mxima e
mnima, sendo posteriormente obtida a diferena (t) entre
essas temperaturas.

A medio de termoviso acusou aquecimento elevado


somente no pra-raios PrC6. Aps a termoviso, foram
realizadas medies de RIV, sendo constatado valores
elevados nos pra-raios PrC5 e PrC6. Os resultados so
mostrados na Tabela IV.
TABELA IV
MEDIES DE RIV NOS PRA-RAIOS DE 138 KV

Pra-raios

RIV
(V)

PrB1, PrB2, PrB4,


PrB5, PrB6,PRB7 (*)

< 25

PrC1, PrC3, PrC4

< 25

PrC2

80

PrC5, PrC6

> 4500

PrD1, PrD2, PrD4

< 25

PrD3

64

PRD5

90

(*) no foi realizado ensaio de RIV no pra-raios PrB3.

Com base nos resultados


consideraes so feitas:

obtidos,

as

seguintes

- pra-raios PrB:
todos os pra-raios PrB foram aprovados nos ensaios
de tenso disruptiva de impulso e de tenso disruptiva
em freqncia industrial, indicando um funcionamento
satisfatrio de seus centelhadores;
os pra-raios PrB6 e PrB7 apresentaram maior
distoro da corrente de fuga em comparao com os
demais pra-raios do mesmo fabricante;
os pra-raios PrB2, PrB3 e PrB6 foram submetidos s
medies
de
termoviso
e
apresentaram
comportamento trmico similar nesse ensaio;
os valores encontrados nas medies de RIV foram
baixos, resultando em um bom desempenho dos praraios;
- pra-raios PrC:
todos os pra-raios PrC foram aprovados no ensaio de
tenso disruptiva de impulso atmosfrico, entretanto, o
pra-raios PrC5 foi reprovado no ensaio de tenso
disruptiva em freqncia industrial;
a medio da corrente de fuga registrou componente de
3 H ligeiramente maior no pra-raios PrC5 e valores
elevados de amplitude e da componente de 3 H no
PrC6, sugerindo alguma anormalidade nesse pra-raios;
os pra-raios PrC3, PrC5 e PrC6 foram submetidos s
medies de termoviso, sendo observado aquecimento
excessivo no pra-raios PrC6;
os valores encontrados nas medies de RIV foram
muito elevados nos pra-raios PrC5 e PrC6, indicando
a existncia de descargas internas;
- pra-raios PrD:
todos os pra-raios PrD foram aprovados no ensaio de
tenso disruptiva de impulso atmosfrico, porm, no
ensaio de tenso disruptiva em freqncia industrial,
foi observada a reprovao dos pra-raios PrD3 e
PrD5;
a medio da corrente de fuga registrou componente de
3 H ligeiramente maior no pra-raios PrD5;
os pra-raios PrD1 e PrD3 foram submetidos s
medies de termoviso, onde foi observado
comportamento trmico similar nesses pra-raios;
os valores encontrados nas medies de RIV foram
ligeiramente maiores nos pra-raios PrD3 e PrD5 em
comparao com outros pra-raios do mesmo
fabricante.

existncia de alguma anormalidade nos pra-raios.


Este trabalho mostra que a corrente de fuga, tcnica
geralmente utilizada nos pra-raios de ZnO, pode ser tambm
aplicada aos pra-raios de SiC, trazendo informaes valiosas
sobre o seu estado atual.
Os seguintes aspectos devem ser ressaltados:
- corrente de fuga x degradao do pra-raios:
Os valores mais elevados da corrente de fuga, em termos de
amplitude e, principalmente, da distoro harmnica (3 H),
indicam algum processo de degradao dos pra-raios. Essa
afirmao pode ser exemplificada atravs dos resultados
obtidos no pra-raios PrC6, o qual apresentou aquecimento na
medio de termoviso e nveis elevados de RIV, indicando a
existncia de degradao acentuada nesse pra-raios. A
medio da corrente de fuga acusou valores elevados de
amplitude e de distoro harmnica, mostrando que a
degradao nesse pra-raios seria tambm identificada atravs
dessa tcnica;
- utilizao de somente uma tcnica para o diagnstico do
pra-raios:
A utilizao de uma tcnica de diagnstico pode no ser
suficiente para uma avaliao correta do pra-raios. O praraios PrC5 foi aprovado no ensaio de termoviso e apresentou
valor elevado de RIV, indicando a presena de descargas
internas. A componente de 3 H da corrente de fuga foi
ligeiramente maior em comparao com as medies dos
demais pra-raios do mesmo fabricante;
- classificao dos pra-raios de SiC:
A informao obtida com a corrente de fuga pode ser utilizada
para priorizar a retirada de determinados pra-raios de SiC.
No laboratrio foi verificado que todos os pra-raios PrB
foram aprovados nos ensaios de tenso disruptiva em
freqncia industrial. Os ensaios de termoviso e de RIV no
acusaram problemas, entretanto, os pra-raios PrB6 e PrB7
apresentaram maior distoro da corrente de fuga e poderiam
ser retirados como parte de um programa de substituio
gradativa dos pra-raios de SiC pelos de ZnO.
Concluindo, a implementao de procedimentos para as
medies da corrente de fuga, juntamente com a medio de
termoviso, a qual normalmente realizada pela
concessionria, resultar em informaes mais consistentes
sobre o estado atual dos pra-raios de SiC. Deve ser ressaltado
que as investigaes realizadas no laboratrio tiveram como
premissa a considerao de que os pra-raios no poderiam ser
desenergizados na subestao quando da aplicao de
qualquer tcnica de diagnstico.

AGRADECIMENTOS

IV. CONCLUSES
O procedimento normalmente utilizado para avaliao dos
pra-raios de SiC no campo tem sido a medio da
termoviso, onde atravs da imagem trmica, analisada a

Os autores agradecem aos pesquisadores Clvis Y. Kodaira,


Celso Pereira Braz e Welson Bassi, pelas importantes
sugestes feitas durante as atividades no Laboratrio de Alta
Tenso do IEE/USP.

REFERNCIAS
[1]

S. Grzybowski and G. Gao, Evaluation of 15-420 kV substation


lightning arresters after 25 years of service, in Proc. Southeastcon '99,
pp.333 336, Mar., 1999.
[2] W. McDermid, Reliability of station class surge arresters, in Proc.
IEEE International Symposium on Electrical Insulation, pp. 320-322,
Apr., 2002.
[3] M. Darveniza, R. Mercer and R. M. Watson, An assessment of the
reliability of in-service gapped silicon-carbide distribution surge
arresters, IEEE Trans. Power Delivery, vol. 11, no 4, pp. 1789-1797,
Oct. 1996.
[4] F. B. Barbosa and J. C. Carneiro, Evaluation of lightning arresters
from the CPFL technical reserve by means of laboratory tests: an
experience of success, in Proc. XIV International Symposium on High
Voltage Engineering, (B51) pp.1-8, Aug. 2005.
[5] K. Kannus and K. Lahti, Evaluation of the operational condition and
reliability of surge arresters used on medium voltage networks, IEEE
Trans. Power Delivery, vol. 20, no 2, pp. 745-750, 2005.
[6] C. Heinrich, and V. Hinrichsen, Diagnostics and monitoring of metaloxide surge arresters in high-voltage comparison of existing and
newly developed procedures, IEEE Trans. Power Delivery, vol. 16, no
1, pp. 138-143, Jan. 2001.
[7] A. Schei, Diagnostic techniques for surge arresters with main
reference to on-line measurement of a resistive leakage current of
metal-oxide arresters, in Proc. CIGRE, Session 2000, (P1-05) pp.1
10, 2000.
[8] E. T. Wanderley Neto, E. G. da Costa, R. T. de Souza, E. C. T. de
Macedo, M. J. A. Maia, "Monitoring and Diagnosis of ZnO Arresters",
IEEE Latin America Transactions, vol. 4, no. 3, pp. 170-176, May
2006.
[9] A. G. Kanashiro, M. Zanotti Junior, P. F. Obase, W. R. Bacega and E.
W. Citron, Evaluation of Gapped Silicon Carbide Surge Arresters, in
Proc. IX International Symposium on Lightning Protection, pp.257
261, Nov., 2007.
[10] CISPR-16 Specification for Radio Disturbances and Immunity
Measuring Apparatus and Methods, 1999.
Arnaldo Gakiya Kanashiro nasceu em Santos, Brasil,
em 11 de janeiro de 1957. Graduou-se em Engenharia
Eltrica pela Escola de Engenharia de So Carlos da
Universidade de So Paulo em 1979. Obteve o ttulo de
Mestre e Doutor em Engenharia Eltrica pela Escola
Politcnica da Universidade de So Paulo em 1995 e em
2001, respectivamente. Atua no Instituto de Eletrotcnica e
Energia da Universidade de So Paulo (IEE/USP) desde
1982, sendo pesquisador do Centro de Estudos em Descargas Atmosfricas e
Alta Tenso (CENDAT). Tem especial interesse na rea de alta tenso, tendo
participado de diversos projetos de pesquisa nesse tema. professor do
Programa de Ps-Graduao em Energia da Universidade de So Paulo
(PPGE/USP).
Milton Zanotti Junior nasceu em So Paulo, Brasil, em
18 de abril de 1970. Graduou-se em Licenciatura em
Fsica pelo Instituto de Fsica da Universidade de So
Paulo, em 2001. Obteve o ttulo de Mestre em Energia, em
2009, pelo Programa de Ps-Graduao em Energia da
Universidade de So Paulo (PPGE/USP). Atua
profissionalmente no Laboratrio de Alta Tenso do
Instituto de Eletrotcnica e Energia da Universidade de
So Paulo (IEE/USP) desde 1989, estando envolvido na realizao de ensaios
em diversos equipamentos eltricos de alta tenso. Tem participado de

projetos de pesquisa na rea de alta tenso. professor da Universidade Nove


de Julho.
Paulo Futoshi Obase nasceu em Santa Isabel, Brasil, em
11 de junho de 1975. Graduou-se em Engenharia Eltrica
pela Faculdade de Engenharia de Guaratinguet da
Universidade Estadual Paulista, em 2000. Obteve o ttulo
de Mestre em Engenharia Eltrica, rea Sistemas de
Potncia, em 2004, pela Escola Politcnica da
Universidade de So Paulo. Atua no Instituto de
Eletrotcnica e Energia da USP (IEE/USP), desde 2002, como pesquisador do
Centro de Estudos em Descargas Atmosfricas e Alta Tenso (CENDAT),
onde tem participado de diversos projetos de pesquisa na rea de descargas
atmosfricas e alta tenso.

Wilson Roberto Bacega nasceu em So Paulo, Brasil, em


10 de setembro de 1960. Graduou-se em Engenharia
Eltrica pela Universidade Presbiteriana Mackenzie em
1984. Possui curso de Especializao em Engenharia de
Manuteno de Subestaes, realizado na Universidade
Federal de Santa Catarina (UFSC) em 1992.
Atua na Companhia de Transmisso de Energia Eltrica
Paulista - CTEEP, desde 1986 (Eletropaulo). engenheiro da Diviso de
Gesto da Manuteno da CTEEP, onde tem participado como gerente de
projetos, de diversos projetos de pesquisa, envolvendo principalmente
equipamentos de subestaes.

Вам также может понравиться