OUTDOOR SOLID CORE POST INSULATORS

Outdoor Solid Core Post Insulators


About us

ANKARA SERAMK A.
Ankara Seramik A.S established in 1996 is one of the largest porcelain insulator companies in Turkey.
Ankara Seramik is the most progressive porcelain insulator manufacturing company in Turkey
because of new and innovative production flow systems and manufacturing concepts integrated
with Ankara Seramik A.S ISO 9001:2000 Quality programs. Our quality policy is to design
and manufacture quality products at competitive prices with decreased lead times
to exceed the needs and expectations of our customers.Today,
Ankara Seramik with a built up area of 20.500 m2 (10.250 m2 closed plant
facilities) has a wide range of insulators produced at low, medium and
high voltage levels.We are able to carry out the routine tests in line with the
international and national standards.At the time, Ankara Seramik believes in retaining
a strong domestic market while serving global (international) markets.

Outdoor Solid Core Post Insulators


Index

Iso 9001 IEC


Index
>> Page

2 - 10 > Design

>> Page

10 - 12 > Product

>> Page

13

> Advantages

>> Page

14

> Type Bil 60 - 95 kV

>> Page

15

> Type Bil 125 - 170 kV

>> Page

16

> Type Bil 200 - 325 kV

>> Page

17 - 18 > Type Bil 450 - 650 kV

>> Page

19 - 20 > Type Bil 750 - 950 kV

>> Page

21 - 22 > Type Bil 1050 - 1300 kV

>> Page

23 - 24 > Type Bil 1425 - 1675 kV

>> Page

25 - 26 > Type Bil 1800 - 2100 kV

>> Page

27 - 28 > Type Bil 2250- 2550 kV

Outdoor Solid Core Post Insulators


Design

Introduction
According to IEC60273, an IEC post insulator is
defined by the following designation:
Post insulators are designed to comply with the
demands of the level of electrical insulation and
mechanical strength, while also taking into account
the environmental situation where the insulators
are intended for service.To specify the correct
standard outdoor porcelain solid core post
insulator, the following characteristics
have to be defined :

IEC post insulator Type C10-1050-II

> Lightning impulse withstand voltage, dry


> Switching impulse withstand voltage, wet
(when a switching impulse level is required)
> Power frequency withstand voltage, wet
> Mechanical failing load
> Minimum nominal creepage distance
> Fixing arrangement of top and bottom metal
fitting
> Color of glaze

means outdoor post insulator with


external metal fittings

10

means a minimum bending failing


load of 10 kN

1050

means a lightning impulse withstand


voltage, dry of 1050 kV

II

means creepage distance class II


(in reference to IEC60273)

According to IEC60273, an IEC operating rod


can be defined by the following designation:

IEC operating rod Type T3-1050-II

Standarts
Ankara Sramik A.S. Insulators manufactures
outdoor porcelain solid core post insulators
with external metal fittings and outdoor operating
rods with external metal fittings (for High Voltage
Switchgears) according to standard IEC60273.
Components according to other standards or
special customer requirements can be supplied
upon request.

means outdoor operating rod with


external metal fittings

means a minimum failing load torsion


3 kNm

1050 means a lightning impulse withstand


voltage, dry of 1050 kV
II

means creepage distance class


II (in reference to IEC60273)

These designations do not always fully specify the insulator type;


sometimes there are alternative constructions regarding the fixing arrangement
and creepage distance included in the standards

Outdoor Solid Core Post Insulators


Electrical Design

The insulation performance of a post insulator column is a function of the height,


creepage distance, arcing distance of the insulating part(s) as well as the number of
insulator units for a defined height and follows the standards IEC60071 and IEC60273.

Nominal system
voltage Un

Max . system
voltage Um

One minute withstand


voltage wet 50 cs

kV (r.m.s.)

kV (r.m.s.)

kV (r.m.s.)

Lightning impulse withstand voltage 1,2/50 s


kV (peak value)

3,6

10

20 - 40

7.2

20

40 - 60

10

12

28

60 - 75 - 95

15

17.5

38

75 - 95

20

24

50

95 - 125 - 145

30

36

70

145 - 170

45

52

95

250

66

72 .5

140

325

110
132

123
145

185 - 230
185 - 230 -325

150

170

220

245

Nominal system
voltage Un
kV (r.m.s.)

Max. system
voltage Um

230 - 275 - 325

450 - 550
450 - 550 -650
550 - 650 -750

275 - 325 - 360 -395 -460

650 -750 - 850 - 950 - 1050

Switching impulse with stand voltage 250/2500

Lightning impulse withstand voltage 1,2/50 s

kV (peak value)

kV (peak value)

kV (r.m.s.)

275

300

750
850

330

362

850
950

380

420

850
950
1050

480

525 (550)

850
950
1050

700

765 (800)

1300
1425
1550

850
950
1050
950
1050
1175
1050
1175
1300
1425
1175
1300
1425
1550
1675
1800
1950
2100

Outdoor Solid Core Post Insulators


Design

RIV
The RIV performance of single post insulator styles will be
tested in accordance with the standard IEC60437 upon
request. If corona rings are necessary to reach a certain
RIV level for a single insulator column, the appropriate ones
will be offered with the insulator column.

Mechanical Design
In-service stresses on post insulators are mainly due to
bending loads (e.g., weight, wind force, seismic conditions,
short circuit loads). A few applications require
compression strength (e.g., capacitors banks) or
torsion strength (e.g., rotating disconnectors) or
tensile strength (e.g., underhung post insulator).

The high strength


C130 porcelain body
allows for a reduction in
the number of
components on insulators
comprised of multiple
units. The advantages
provided by the reduction
of additional fittings
include increased
arcing distance/creep
and less assembly time.
All insulators up to and
including the C20-1050
are available in a
one-unit design.

Outdoor Solid Core Post Insulators


Pollution Levels and Creepage Distances
Note : Creepage distances and max. nominal diameters of sheds
can be designed according to pollution levels and customer requirement.

Level

Pollution

Light

Specific Creepage Distance


16 mm/kV

> Areas without industry and with low housing density


equipped with heating plants.

> Areas with low density of industry or houses but subjected


to frequent winds and/or rainfall.

> Agricultural areas.


> Mountainous areas.
Level

Pollution

Medium

Specific Creepage Distance


20 mm/kV

In standard IEC60273, creepage distances are


standardized for post insulators in class I and II,which is
not in accordance with the general recommendations of
the guide IEC60815 Guide for the selection of insulators
in respect to environmental conditions. In IEC60815 the
basic pollutionlevels are defined qualitatively with
examples of typical environmental situations. The
corresponding minimum nominal creepage distance is
given in mm/kV.

Regular sheds
Dm = (De + Dc) / 2

> Industrial areas not producing particulate polluting smoke


and/or with average housing density equipped with heating
plants.
> Areas with high density of houses and/or industry but
subjected to frequent winds and/or rainfall.
> Areas exposed to wind from the sea but not too close to the
coast (at least several kilometers distant).

Level

Pollution

Heavy

Specific Creepage Distance


25 mm/kV

> Areas with high density of industries and suburbs of large


cities with high density of heating plants producing pollution.

> Areas close to the sea in any case exposed to relatively

Alternating sheds

strong winds from the sea.

Dm= (De1 + De2 + (2*Dc) )/4


Level

Pollution

Specific Creepage Distance

Very Heavy

31 mm/kV

> Areas generally of moderate extent, subjected to conductive


dusts and to industrial smoke producing particularly thick
conductive deposits.
> Areas generally of moderate extent, very close to the coast
and exposed to sea-spray or to very strong and polluting
winds from the sea.
> Desert areas, characterized by no rain for long periods,
exposed to strong winds carrying sand and salt, and
subjected to regular condensation.

The creepage distance shouldbe increased


in relation to the average diameter, Dm .
Dm< 300 mm
D m 300-500 mm
Dm> 500 mm

kd =1.0
kd =1.1
kd =1.2

De
Dc
De1
De

Shed diameter
Core diameter
Greater shed diameter
Smaller shed diameter

Outdoor Solid Core Post Insulators


Design

d1

d2

Outdoor Solid Core Post Insulators


Pollution Levels and Creepage Distances

Alternating Shed

Plain Shed

Standart (Traditonal) Shed

Outdoor Solid Core Post Insulators


Design

K-Value Increased Pollution Performance Equalized Field Distribution


K-value design is a method to improve traditional creepage distance.
In its full extent, K-value design is a method to reduce weight,
volume and space while improving properties in-service by increasing
pollution performance and equalizing the electrical field.
K-value is the unit for insulator shape and IEC 60507 defines the formula as form factor:

l is the creepage distance


p(l) is the circumference of the insulator as a function of l.

Form factor used as a design method is referred to as K-value and can be used for different types of improvements.
Creepage distance considers a leakage current as traveling along the insulator, in a strict line, identifying only distance.
K-value considers a leakage current as traveling along the insulator,over its complete surface. It calculates reduced diameter and/or
increased creepage distance for higher resistance against the leakage currents. K-value identifies an insulators total shape, i.e., geometric
(ohmic) resistance against leakage currents.
The shape of the insulator must be calculated for optimum design of pollution performance.
The traditional calculation of creepage distance is sometimes sufficient, but to achieve best performance in relation to
material and space used, K-value design is necessary.

ANKARA SERAMK A.. Insulators offers complete computer design


of K-value, integrated with electrical, mechanical,
dimension and material calculations.

Outdoor Solid Core Post Insulators


Design

Insulating Material
The insulator body of the unit is made from high
quality aluminium oxide porcelain, C130 or C120,
which conforms to standard IEC60672. Glazing
provides a dirt repellent surface. Glazing is normally
brown in colour, though Blue grey can also be
provided upon request. Semi-conductive surface
glazing can be provided
for special polluted environments.

Fittings
Fittings are made in malleable cast iron
according to standard En1562 or spheroidal graphite
cast iron according to standard En1563.
All fittings are hot
dip galvanized according to standard EN ISO 1461
with a zinc weight of min. 600 g/m2 (min. 85 m)
as average value.
The following table shows the standard dimensions for
fittings according to IEC60273.

Pitch circle diameter


p.c.d. d1
mm

76
127
178
200
225
254
275
300
325
356
375

Depth of the tabbed


blind holes h2
mm

12
18 (22)

Number Of Holes n
-

Bolt holes tapped d2


-

Bolt holes plain d2


mm

Nominal maximum
diameter of
mounting face d3
mm

4
4
4
4
4
8

M12
M16
-

18
18
18
18

115
165
225
245
270
300

8
8
8
8
8

18
18
18
18
18

320
345
370
400
420

Fittings with other dimensions (e.g., for operation rod columns)


can be supplied on request. Threads are generally tapped after
hot dip galvanizing; for shipment and storage, the threads
will be protected by a protective layer and/or special plastic
plugs.
NOTE: Multiple unit insulator columns will be delivered with hardware
(bolts, nuts and spring washers) for the interconnection of the insulator
units.

10

Outdoor Solid Core Post Insulators


Advantages

Cementing
The fittings are assembled to the porcelain body with a special cement
mortar as standard. The cement 's basic material is calcium aluminate
which has a stronger strength.The properties of this cement are setting
in a short time , useful at cold weather conditions and strong strength.

11

Outdoor Solid Core Post Insulators


Production

12

Outdoor Solid Core Post Insulators


Advantages
Advantages
of porcelain solid core post insulators with external fittings

> puncture proof


The theoretical puncture path through
the porcelain body is almost equal to
the dry arcing distance.
Since porcelain has several times the
dielectric breakdown strength of air,
flashover, if any, always occurs in the air
outside the porcelain body.

> insulator body made of


aluminium oxide porcelain
> high mechanical strength
> free of internal stresses
> no measurable aging
> resistant to salt pollution
> high resistance to temperature variations
> high resistance to vandalism

Ankara Seramik A..

Production and
Product Tables
Insulators production facilities
for IEC station post insulators manufacture
in full accordance to IEC60273. Operating

> electrically and mechanically


stressed zones are separated

rod columns for disconnectors are manufactured corresponding to the relevant

> low sur face leakage current resulting


in reduced transmission losses

post insulators.

> the creepage distance is made from


sheds and core par ts which have
> good self-cleaning properties with respect

ratings from BIL 60 kV to 2550 kV.

>

Insulation requirements are available in


This catalogue includes standard IEC
solid core station post insulators with

to the climatic conditions

external metal fittings. Insulator creepage

better insulation performance under

distances are in accordance with IEC60273

pollution conditions

and IEC608 1 5. Special requirements,


such as other creepage distances, special

> routine test load


= 70 % of the minimum failing load

shed forms, other top bending moments


or pitch circle diameters, can also be
offered upon request

> can be checked ultrasonically


for mechanical soundness
> lowest maintenance costs
> minimum total life cycle costs
by high reliability
> packaging in crates offers
the maximum protection
during shipping and storage

13

Outdoor Solid Core Post Insulators


TYPE BIL 60-95 kV
Porcelain

C130 (or C120) according to IEC60672-3 Brown glazed

Tolerance

according to IEC60168

Fittings

malleable cast iron according to EN1562 or spheroidal graphite cast


iron according to EN1563, hot dip galvanized according to ENISO1461

Cementing

Calcium aluminate cement


TYPE
PRODUCT NO

IEC POST INSULATOR DESIGNATION

C4-60

C6-60

C8-60

C10-60

381103

382103

383103

384103

190 1
175
76/4x M12
76/4x M12

1901
175
76/4x M12
76/4x M12

4
0.38
0.76
0.6

6
0.57
1.14
0.6

8
0.76
1.52
0.8

10
0.95
1.9
1

60
20

60
20

60
20

60
20

C8-75

C10-75

Dimensions

BIL 60 kV

Height H [mm]
Max. nom. diameter of insulating part d1 [mm]
Top fitting p.c.d. d2 [mm] / hole pattern
Bottom fitting p.c.d. d3 [mm] / hole pattern

1901
185
76/4x M12
76/4x M12

d2

190 1
185
76/4x M12
76/4x M12

Mechanical Values
Minimum failing load - Bending [kN]
Minimum failing load - Bending moment underhung [kNm]
Minimum failing load - Bending moment upright [kNm]
Minimum failing load - Torsion [kNm]
Electrical Values
Lightning impulse withstand voltage, dry [kV peak value]
Power frequency withstand voltage, wet [kV r.m.s.]

TYPE
PRODUCT NO

IEC POST INSULATOR DESIGNATION

C4-75

Dimensions
Dimensions
Height H [mm]
Height
H [mm]
Max. nom.
diameter of insulating part d1 [mm]
Top fitting p.c.d. d2 [mm] / hole pattern
Bottom fitting p.c.d. d3 [mm] / hole pattern

BIL 75 kV

C6-75

381101

382101

383101

384101

215 1
180
76/4x M12
76/4x M12

215 1
180
76/4x M12
76/4x M12

215 1
190
76/4x M12
76/4x M12

215 1
190
76/4x M12
76/4x M12

Mechanical Values
Mechanical Values
Minimum failing load - Bending [kN]
Minimum failing load - Bending moment underhung [kNm]
Minimum failing load - Bending moment upright [kNm]
Minimum failing load - Torsion [kNm]

4
0.43
0.86
0.6

6
0.65
1.29
0.6

8
0.86
1.72
0.8

10
1.08
2.15
1

Electrical Values
Electrical Values
Lightning impulse withstand voltage, dry [kV peak value]
Power frequency withstand voltage, wet [kV r.m.s.]

75
28

75
28

75
28

75
28

IEC POST INSULATOR DESIGNATION

TYPE
PRODUCT NO

C4-95

C6-95

C8-95

C10-95

C12.5-95

381201

382201

383201

384201

385201

255 1
190
76/4x M12
76/4x M12

255 1
210
76/4x M12
76/4x M12

255 1
210
76/4x M12
76/4x M12

d1

Dimensions

BIL 95 kV

Height H [mm]
Max. nom. diameter of insulating part d1 [mm]
Top fitting p.c.d. d2 [mm] / hole pattern
Bottom fitting p.c.d. d3 [mm] / hole pattern

255 1
190
76/4x M12
76/4x M12

255 1
190
76/4x M12
76/4x M12

Mechanical Values
Minimum failing load - Bending [kN]
Minimum failing load - Bending moment underhung [kNm]
Minimum failing load - Bending moment upright [kNm]
Minimum failing load - Torsion [kNm]

4
0.51
1.02
0.8

6
0.77
1.53
0.8

8
1.02
2.04
1.2

10
1.28
2.55
1.2

12.5
1.6
3.19
1.8

95
38

95
38

95
38

95
38

95
38

Electrical Values
Lightning impulse withstand voltage, dry [kV peak value]
Power frequency withstand voltage, wet [kV r.m.s.]

14

d3

Outdoor Solid Core Post Insulators


TYPE BIL 125-170 kV
Porcelain

C 1 30 (or C 1 20) according to IEC60672-3


Brown glazed

Tolerance

according to IEC601 68

Fittings

malleable cast iron according to EN1562 or spheroidal graphite cast iron


according to EN1563, hot dip galvized according to ENISO 1461

Cementing

Calcium aluminate cement

IEC POST INSULATOR DESIGNATION

TYPE
PRODUCT NO

C4-125

C6-125

C8-125

C10-125

C12.5-125

381301

382301

383301

384301

385301

305 1
230
76/4x M12
76/4x M12

305 1
230
76/4x M12
76/4x M12

BIL 125 kV

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]
Top fitting p.c.d. d2 [mm] / hole pattern
Bottom fitting p.c.d. d3 [mm] / hole pattern

305 1
195
76/4x M12
76/4x M12

305 1
195
76/4x M12
76/4x M12

4
0.61
1.22
0.8

6
0.92
1.83
0.8

305 1
195
76/4x M12
76/4x M12

Mechanical Values
Minimum failing load - Bending [kN]
Minimum failing load - Bending moment underhung [kNm]
Minimum failing load - Bending moment upright [kNm]
Minimum failing load - Torsion [kNm]

8
1.22
2.44
1.2

10
1.53
3.05
1.2

12.5
1.91
3.82
2

Electrical Values
Lightning impulse withstand voltage, dry [kV peak value]
Power frequency withstand voltage, wet [kV r.m.s.]
IEC POST INSULATOR DESIGNATION

TYPE
PRODUCT NO

125
50

125
50

125
50

125
50

125
50

C4-150

C6-150

C8-150

C10-150

C12.5-150

381501

382501

383501

384501

385501

BIL 150 kV

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]
Top fitting p.c.d. d2 [mm] / hole pattern
Bottom fitting p.c.d. d3 [mm] / hole pattern

355 1
195
76/4x M12
76/4x M12

355 1
195
76/4x M12
76/4x M12

355 1
195
76/4x M12
76/4x M12

355 1
235
76/4x M12
76/4x M12

355 1
235
76/4x M12
76/4x M12

Mechanical Values
Minimum failing load - Bending [kN]
Minimum failing load - Bending moment underhung [kNm]
Minimum failing load - Bending moment upright [kNm]
Minimum failing load - Torsion [kNm]

4
0.71
1.42

6
1.07
2.13
1.2

8
1.42
2.84
1.5

10
1.78
3.55
1.8

12.5
2.22
4.44
2.5

150
50

150
50

150
50

150
50

C4-170

C6-170

C8-170

C10-170

C12.5-170

381401

382401

383401

384401

385401

445 1
205
76/4x M12
76/4x M12

445 1
205
76/4x M12
76/4x M12

6
1.34
2.67
1.5

8
1.78
3.56
2

10
2.23
4.45
2.5

170
70

70
70

170
70

Electrical Values
Lightning impulse withstand voltage, dry [kV peak value]
Power frequency withstand voltage, wet [kV r.m.s.]
IEC POST INSULATOR DESIGNATION

TYPE
PRODUCT NO

150
50

BIL 170 kV

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]
Top fitting p.c.d. d2 [mm] / hole pattern
Bottom fitting p.c.d. d3 [mm] / hole pattern

445 1
205
76/4x M12
76/4x M12

445 1
245
76/4x M12
76/4x M12

445 1
245
127/4x M16
127/4x M16

Mechanical Values
Minimum failing load - Bending [kN]
Minimum failing load - Bending moment underhung [kNm]
Minimum failing load - Bending moment upright [kNm]
Minimum failing load - Torsion [kNm]

4
0.89
1.78
1.2

12.5
2.79
5.57
3

Electrical Values
Lightning impulse withstand voltage, dry [kV peak value]
Power frequency withstand voltage, wet [kV r.m.s.]

170
70

15

170
70

Outdoor Solid Core Post Insulators


TYPE BIL 200-325 kV
Porcelain

C 1 30 (or C 1 20) according to IEC60672-3


Brown glazed

Tolerance

according to IEC601 68
malleable cast iron according to EN1562 or
spheroidal graphite cast iron according to EN
1563, hot dip galvanized according to ENISO1461

Fittings

Calcium aluminate cement

Cementing
IEC POST INSULATOR DESIGNATION

TYPE
PRODUCT NO

C4-200
711001

C6-200
712001

475 1
210
76/4x M12
76/4x M12

475 1
210
76/4x M12
76/4x M12

475 1
210
76/4x M12
76/4x M12

4
0.95
1.9
1.2

6
1.43
2.85
1.8

8
1.9
3.8
2

10
2.38
4.75
2.5

200
70

200
70

200
70

C6-250
712002

C8-250
713002

C10-250
714002

C12.5-250
715002

560 1
215
76/4x M12
127/4x M16
76/4x M12
127/4x M16

560 1
215

560 1
255

560 1
255

127/4x M16

127/4x M16

127/4x M16

127/4x M16

127/4x M16

127/4x M16

6
1.68
3.36
2

8
2.24
4.48
2.5

250
95

250
95

C8-200
713001

C10-200
714001

C12.5-200
715001

BIL 200 kV

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]
Top fitting p.c.d. d2 [mm] / hole pattern
Bottom fitting p.c.d. d3 [mm] / hole pattern

475 1
245
76/4x M12
76/4x M12

475 1
245
127/4x M16
127/4x M16

Mechanical Values
Minimum failing load - Bending [kN]
Minimum failing load - Bending moment underhung [kNm]
Minimum failing load - Bending moment upright [kNm]
Minimum failing load - Torsion [kNm]

12.5
2.97
5.94
3

Electrical Values
Lightning impulse withstand voltage, dry [kV peak value]
Power frequency withstand voltage, wet [kV r.m.s.]

IEC POST INSULATOR DESIGNATION

200
70

TYPE
PRODUCT NO

200
70

C4-250
711002

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]

560 1
215
76/4x M12
127/4x M16
76/4x M12
127/4x M16

BIL 250 kV

Top fitting p.c.d. d2 [mm] / hole pattern


Bottom fitting p.c.d. d3 [mm] / hole pattern
Mechanical Values
Minimum failing load - Bending [kN]
Minimum failing load - Bending moment underhung [kNm]
Minimum failing load - Bending moment upright [kNm]
Minimum failing load - Torsion [kNm]

4
1.12
2.24
1.8

10
2.8
5.6
3

12.5
3.5
7
4

Electrical Values
Lightning impulse withstand voltage, dry [kV peak value]
Power frequency withstand voltage, wet [kV r.m.s.]

IEC POST INSULATOR


DESIGNATION

TYPE
PRODUCT NO

250
95

250
95

250
95

C4-325

C6-325

C8-325

C10-325

C12.5-325

C16-325

C20-325

711003

712003

713003

714003

715003

716014

717012

770 1
225
127 /4x M16
127 /4x M16

770 1
225
127 /4x M16
127 /4x M16

770 1
260
127 /4x M16
127 /4x M16

770 1
270
127 /4x M16
127 /4x M16

770 1
270
127 /4x M16
127 /4x M16

4
1.54
3.08
2

6
2.31
4.62
2.5

8
3.08
6.16
3

10
3.85
7.7
4

325
140

325
140

BIL 325 kV

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]
Top fitting p.c.d. d2 [mm] / hole pattern
Bottom fitting p.c.d. d3 [mm] / hole pattern

770 1
300
127 /4x M16
225/4x18

770 1
300
127 /4x M16
254/8x18

Mechanical Values
Min. failing load - Bending [kN]
Min. failing load - Bending moment underhung [kNm]
Min. failing load - Bending moment upright [kNm]
Min. failing load - Torsion [kNm]

12.5
4.82
9.63
4

16
6.16
12.32
5

20
7.7
15.4
6

Electrical Values
Lightn. impulse withst. voltage, dry [kV peak value]
Power frequency withst. voltage, wet [kV r.m.s.]

325
140

16

325
140

325
140

325
140

325
140

Outdoor Solid Core Post Insulators


TYPE BIL 450-650 kV

IEC POST INSULATOR


DESIGNATION

TYPE
PRODUCT NO

C4-450

C6-450

C8-450

C10-450

C12.5-450

C16-450

711004

712004

713004

714004

715004

716001

C20-450
717001

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]
Top fitting p.c.d. d2 [mm] / hole pattern

BIL 450 kV

Bottom fitting p.c.d. d3 [mm] / hole pattern

1020 1
235
127 /4x M16
127 /4x M16
178/4x18

1020 1
260
127 /4x M16
127 /4x M16
178/4x18

1020 1
260
127 /4x M16
127 /4x M16
200/4x18

1020 1
290
127 /4x M16
127 /4x M16
225/4x18

1020 1
300
127 /4x M16

1020 1
300
127 /4x M16

1020 1
300
127 /4x M16

225/4x18

254/8x18

12.5
6.38
12.75
6

16
8.16
16.32
6

20
10.2
20.4
6

450
185

450
185

254/8x18

Mechanical Values
Min. failing load - Bending [kN]
Min. failing load - Bending moment underhung [kNm]
Min. failing load - Bending moment upright [kNm]
Min. failing load - Torsion [kNm]

4
2.04
4.08
2.5

6
3.06
6.12
3.5

8
4.08
8.16
4

10
5.1
10.2
4

450
185

450
185

450
185

Electrical Values
Lightn. impulse withst. voltage, dry [kV peak value]
Power frequency withst. voltage, wet [kV r.m.s.]
IEC POST INSULATOR
IEC POST INSULATOR
DESIGNATION

TYPE
PRODUCT NO

450
185

450
185

C4-550

C6-550

C8-550

C10-550

C12.5-550

C16-550

C20-550

711005

712005

713004

714004

715005

716001

717002

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]
Top fitting p.c.d. d2 [mm] / hole pattern

BIL 550 kV

Bottom fitting p.c.d. d3 [mm] / hole pattern

1220 1
300
127 /4x M16
127 /4x M16
178/4x18

1220 1
300
127 /4x M16
127 /4x M16
200/4x18

1220 1
300
127 /4x M16
127 /4x M16
200/4x18

1220 1
350
127 /4x M16
127 /4x M16
225/4x18

1220 1
350
127 /4x M16

10
6.1
12.2
4

12.5
7.63
15.25
6

254/8x18

1220 1
350
127 /4x M16

1220 1
350
127 /4x M16

254/8x18

275/8x18

Mechanical Values
Min. failing load - Bending [kN]
Min. failing load - Bending moment underhung [kNm]
Min. failing load - Bending moment upright [kNm]
Min. failing load - Torsion [kNm]

4
2.44
4.88
3

6
3.66
7.32
4

8
4.88
9.76
4

16
9.76
19.52
6

20
12.2
24.4
6

Electrical Values
Lightn. impulse withst. voltage, dry [kV peak value]
Power frequency withst. voltage, wet [kV r.m.s.]
IEC
IEC POST
POST INSULATOR
INSULATOR
DESIGNATION

TYPE
PRODUCT NO

550

550

550

550

550

550

550

230

230

230

230

230

230

230

C8-650

C10-650

C12.5-650

C16-650

713006

714006

715006

716003

717003

1500 2.5
400
127 /4x M16
225/4x18

1500 2.5
400
127 /4x M16
225/4x18

1500 2.5
400

1500 2.5
420

254/8x18

254/8x18

C4-650

C6-650

711006

712006

Height H [mm]
Heightnom.
H [mm]
Max.
diameter of insulating part d1 [mm]

1500 2.5
350

1500 2.5
350

Top fitting p.c.d. d2 [mm] / hole pattern

127 /4x M16

127 /4x M16

Bottom fitting p.c.d. d3 [mm] / hole pattern

127 /4x M16


200/4x18

127 /4x M16


200/4x18

C20-650

BIL 650 kV

Dimensions
1500 2.5
350
127 /4x M16
225/4x18
127 /4x M16
225/4x18

225/4x18

225/4x18

275/8x18

300/8x18

Mechanical Values
Min. failing load - Bending [kN]
Min. failing load - Bending moment underhung [kNm]
Min. failing load - Bending moment upright [kNm]
Min. failing load - Torsion [kNm]

4
3
6
3

6
4.5
9
3

8
6
12
4

10
7.5
15
4

12.5
9.33
18.75
6

16
12
24
6

20
15
30
6

650
275

650
275

650
275

650
275

650
275

650
275

650
275

Electrical Values
Lightn. impulse withst. voltage, dry [kV peak value]
Power frequency withst. voltage, wet [kV r.m.s.]

17

Outdoor Solid Core Post Insulators


TYPE BIL 450-650 kV
d2

Porcelain

C 1 30 (or C 1 20)
according to IEC60672-3,
Brown glazed

Tolerance

according to IEC601 68

Fittings

malleable cast iron


according to EN1562
or spheroidal graphite cast
iron according to EN1563,
hot dip galvanized
according to ENISO1461

Cementing

Calcium aluminate cement

18

Outdoor Solid Core Post Insulators


TYPE BIL 750-950 kV

IEC POST INSULATOR


DESIGNATION

TYPE
PRODUCT NO

C4-750

C6-750

C8-750

C10-750

C12.5-750

C16-750

C20-750

711007

712007

713007

714007

715007

716004

717004

1700 2.5
350

1700 2.5
350
127 /4x M16
225/4x18

1700 2.5
350
127 /4x M16
225/4x18

1700 2.5
400
127 /4x M16
225/4x18

1700 2.5
400
225 /4x 18
254/8x18

1700 2.5
420
225 /4x18
254/8x18

127 /4x M16


225/4x18

127 /4x M16


225/4x18

254/8x18

275/8x18

300/8x18

16
5.44
27.2
6

20
6.8
34
6

Dimensions

BIL 750 kV

Height H [mm]
Max. nom. diameter of insulating part d1
Top fitting p.c.d. d2 [mm] / hole pattern

127 /4x M16

Bottom fitting p.c.d. d3 [mm] / hole pattern

127 /4x M16


200/4x18

1700 2.5
400
127 /4x M16
225/4x18
254/8x18

Mechanical Values
4
1.36
6.8
3

Min. failing load - Bending [kN]


Min. failing load - Bending moment underhung [kNm]
Min. failing load - Bending moment upright [kNm]
Min. failing load - Torsion [kNm]

6
2.04
10.2
3

8
2.72
13.6
4

10
3.4
17
4

12.5
4.25
21.25
6

750
325

750
325

750
325
C12.5-850

Electrical Values
Lightn. impulse withst. voltage, dry [kV peak value]
Power frequency withst. voltage, wet [kV r.m.s.]

750
325

TYPE
PRODUCT NO

C6-850

750
325
C16-850
C16-850

750
325
C20-850
C20-850

C8-850

C10-850

711008

712008

713008

714008

Height H [mm]
Max. nom. diameter of insulating part d1 [mm]

1900 3.5
400

1900 3.5
400

1900 3.5
400

1900 3.5
400

1900 3.5
400

1900 3.5
400

1900 3.5
420

Top fitting p.c.d. d2 [mm] / hole pattern

127/4x M16

127/4x M16
225/4x18

127/4x M16
225/4x18

127/4x M16
225/4x18

225/4x18
254/8x18

225/4x18
254/8x18

200/4x18

225/4x18

254/8x18

254/8x18

127/4x M16
254/8x18
225/4x18
254/8x18

275/8x18

300/8x18

8
3.04
15.2
4

10
3.8
19
4

IEC POST INSULATOR


DESIGNATION

C4-850

750
325

715008

716005

717005

Dimensions

BIL 850 kV

Bottom fitting p.c.d. d3 [mm] / hole pattern


Mechanical Values
Min. failing load - Bending [kN]
Min. failing load - Bending moment underhung [kNm]
Min. failing load - Bending moment upright [kNm]
Min. failing load - Torsion [kNm]

4
1.52
7.6
3

6
2.28
11.4
3

12.5
4.75
23.75
6

16
6.08
30.4
6

20
7.6
38
6

Electrical Values
Lightn. impulse withst. voltage, dry [kV peak value]
Power frequency withst. voltage, wet [kV r.m.s.]
IEC POST INSULATOR
IEC POST INSULATOR
DESIGNATION
DESIGNATION

TYPE
PRODUCT NO

850

850

850

850

850

850

360

360

360

360

360

360

C4-950

C6-950

711009

712009

C10-950

C12.5-950

713009

714009

715009

2100 3.5
450

2100 3.5
450

C8-950

850
360

C16-950

C20-950

716006

717006

2100 3.5
450

2100 3.5
450

225/4x18

225/4x18
254/8x18

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]
Top fitting p.c.d. d2 [mm] / hole pattern

BIL 950 kV

Bottom fitting p.c.d. d3 [mm] / hole pattern

2100 3.5
450

2100 3.5
450

2100 3.5
450

127/4x M16

127/4x M16
225/4x18

127/4x M16
225/4x18

127/4x M16
225/4x18

200/4x18

225/4x18

254/8x18

254/8x18

127/4x M16
225/4x18
254/8x18
275/8x18

8
3.36
16.8
4

10
4.2
21
4

12.5
5.25
26.25
6

16
6.72
33.6
6

254/8x18
300/8x18

325/8x18

Mechanical Values
Min. failing load - Bending [kN]
Min. failing load - Bending moment underhung [kNm]
Min. failing load - Bending moment upright [kNm]
Min. failing load - Torsion [kNm]

4
1.68
8.4
3

6
2.52
12.6
3

20
8.4
42
6

Electrical Values
Lightn. impulse withst. voltage, dry [kV peak value]
Switching impulse withstand voltage, wet [kV peak value]
Power frequency withst. voltage, wet [kV r.m.s.]

950
750

950
750

950
750

950
750

950
750

950
750

950
750

395

395

395

395

395

395

395

19

Outdoor Solid Core Post Insulators


TYPE BIL 750-950 kV

Porcelain

C 1 30 (or C 1 20)
according to IEC60672-3,
Brown glazed

Tolerance

according to IEC601 68

Fittings

malleable cast iron


according to EN1562
or spheroidal graphite cast
iron according to EN1563,
hot dip galvanized
according to ENISO1461

Cementing

Calcium aluminate cement

20

Outdoor Solid Core Post Insulators


TYPE BIL 1050-1300 kV

IEC POST INSULATOR


DESIGNATION

TYPE
PRODUCT NO

C4-1050

C6-1050

C8-1050

C10-1050

C12.5-1050

C16-1050

C20-1050

711010

712010

713010

714010

715010

716007

717007

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]
Top fitting p.c.d. d2 [mm] / hole pattern

BIL 1050 kV

Bottom fitting p.c.d. d3 [mm] / hole pattern

2300 3.5
450

2300 3.5
450

2300 3.5
450

2300 3.5
450

127 /4x M16

127 /4x M16


225/4x18

127 /4x M16


225/4x18

127 /4x M16


225/4x18

200/4x18

225/4x18

254/8x18

275/8x18

2300 3.5
450
127 /4x M16
225/4x18
254/8x18
275/8x18

2300 3.5
450

2300 3.5
450

225/4x18
254/8x18

225/4x18
254/8x18

300/8x18

325/8x18

Mechanical Values
Min. failing load - Bending [kN]
Min. failing load - Bending moment underhung [kNm]
Min. failing load - Bending moment upright [kNm]
Min. failing load - Torsion [kNm]

4
1.84
9.2
3

6
2.76
13.8
3

8
3.68
18.4
4

10
4.6
23
4

12.5
5.75
28.75
6

16
7.36
36.8
6

20
9.2
46
6

1050
750
460

1050
750
460

1050
750
460

1050
750
460

1050
750
460

1050
750
460

1050
750
460

C4-1175

C6-1175

C8-1175

C10-1175

C12.5-1175

C16-1175

C20-1175

711011

712011

713011

715011

716008

717008

Electrical Values
Lightn. impulse withst. voltage, dry [kV peak value]
Switching impulse withstand voltage, wet [kV peak value]
Power frequency withst. voltage, wet [kV r.m.s.]
IEC POST INSULATOR
DESIGNATION

TYPE
PRODUCT NO

714011

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]

2650 4.5
450

2650 4.5
450

2650 4.5
450

2650 4.5
450

Top fitting p.c.d. d2 [mm] / hole pattern

127/4x M16
225/4x18

127 /4x M16


225/4x18

127 /4x M16


225/4x18

127 /4x M16


225/4x18

254/8x18

254/8x18

BIL 1175 kV

Bottom fitting p.c.d. d3 [mm] / hole pattern

225/4x18

2650 4.5
450

2650 4.5
450

225/4x18
254/8x18

225/4x18
254/8x18

275/8x18

2650 4.5
450
127 /4x M16
225/4x18
254/8x18
300/8x18

325/8x18

356/8x18

8
4.24
21.2
4

10
5.3
26.5
4

12.5
6.63
33.13
6

16
8.48
42.4
6

20
10.6
53
6

1175
850

1175
850

1175
850

1175
850

1175
850

Mechanical Values
4
2.12
10.6
3

Min. failing load - Bending [kN]


Min. failing load - Bending moment underhung [kNm]
Min. failing load - Bending moment upright [kNm]
Min. failing load - Torsion [kNm]

6
3.18
15.9
3

Electrical Values
Lightn. impulse withst. voltage, dry [kV peak value]
Switching impulse withstand voltage, wet [kV peak value]

1175
850

1175
850

C4-1300

C6-1300

C8-1300

C10-1300

C12.5-1300

C16-1300

C20-1300

711012

712012

713012

714012

715012

716009

717009

Height H [mm]
Max. nom. diameter of insulating part d1 [mm]

2900 4.5
450

2900 4.5
450

2900 4.5
450

2900 4.5
450

2900 4.5
450

2900 4.5
450

Top fitting p.c.d. d2 [mm] / hole pattern

127/4x M16
225/4x18

127 /4x M16


225/4x18

127 /4x M16


225/4x18

127 /4x M16


225/4x18

225/4x18
254/8x18

225/4x18
254/8x18

254/8x18

275/8x18

275/8x18

325/8x18

356/8x18

IEC POST INSULATOR


DESIGNATION

TYPE
PRODUCT NO

Dimensions

BIL 1300 kV

Bottom fitting p.c.d. d3 [mm] / hole pattern

225/4x18

2900 4.5
450
127 /4x M16
225/4x18
254/8x18
300/8x18

Mechanical Values
Min. failing load - Bending [kN]
Min. failing load - Bending moment underhung [kNm]
Min. failing load - Bending moment upright [kNm]
Min. failing load - Torsion [kNm]

4
2.32
11.6
3

6
3.48
17.4
3

8
4.64
23.2
4

10
5.8
29
4

12.5
7.25
36.25
6

16
9.28
46.4
6

20
11.6
58
6

1300
950

1300
950

1300
950

1300
950

1300
950

Electrical Values
Lightn. impulse withst. voltage, dry [kV peak value]
Switching impulse withstand voltage, wet [kV peak value]

1300
950

1300
950

21

Outdoor Solid Core Post Insulators


TYPE BIL 1050-1300 kV

Porcelain

C 1 30 (or C 1 20)
according to IEC60672-3,
Brown glazed

Tolerance

according to IEC601 68

Fittings

malleable cast iron


according to EN1562
or spheroidal graphite cast
iron according to EN1563,
hot dip galvanized
according to ENISO1461

Cementing

Calcium aluminate cement

22

Outdoor Solid Core Post Insulators


TYPE BIL 1425-1675 kV

TYPE
PRODUCT NO

C4-1425

C6-1425

C8-1425

C10-1425

711013

712013

713013

714013

Height H [mm]
Max. nom. diameter of insulating part d1 [mm]

3150 4.5
450

3150 4.5
450

3150 4.5
450

3150 4.5
450

Top fitting p.c.d. d2 [mm] / hole pattern

127/4x M16
225/4x18

127 /4x M16


225/4x18

127 /4x M16


225/4x18

127 /4x M16


225/4x18

225/4x18

254/8x18

275/8x18

300/8x18

4
2.52
12.6
3

6
3.78
18.9
3

8
5.04
25.2
4

IEC POST INSULATOR


DESIGNATION

C12.5-1425
715013

C16-1425
716010

C20-1425
717010

Dimensions

BIL 1425 kV

Bottom fitting p.c.d. d3 [mm] / hole pattern

3150 4.5
450
127 /4x M16
225/4x18
254/8x18
325/8x18

3150 4.5
450

3150 4.5
450

225/4x18
254/8x18

225/4x18
254/8x18

356/8x18

356/8x18

Mechanical Values
Min. failing load - Bending [kN]
Min. failing load - Bending moment underhung [kNm]
Min. failing load - Bending moment upright [kNm]
Min. failing load - Torsion [kNm]

10
6.3
31.5
4

12.5
7.88
39.38
6

16
10.08
50.4
6

20
12.6
63
6

Electrical Values
Lightn. impulse withst. voltage, dry [kV peak value]
Switching impulse withstand voltage, wet [kV peak value]

1425
950

1425
950

1425
950

C4-1550

C6-1550

C8-1550

711014

712014

713014

Height H [mm]
Max. nom. diameter of insulating part d1 [mm]

3350 4.5
450

3350 4.5
450

3350 4.5
450

3350 4.5
450

Top fitting p.c.d. d2 [mm] / hole pattern

127/4x M16
225/4x18

127 /4x M16


225/4x18

127 /4x M16


225/4x18

127 /4x M16


225/4x18

225/4x18

254/8x18

275/8x18

300/8x18

4
2.68
13.4
3

6
4.02
20.1
3

8
5.36
26.8
4

IEC POST INSULATOR


DESIGNATION

TYPE
PRODUCT NO

1425
950

1425
950

1425
950

C10-1550

C12.5-1550

C16-1550

714014

715014

716011

1425
950
C20-1550
717011

Dimensions

BIL 1550 kV

Bottom fitting p.c.d. d3 [mm] / hole pattern

3350 4.5
450
127 /4x M16
225/4x18
254/8x18
325/8x18

3350 4.5
450

3350 4.5
450

225/4x18
254/8x18

225/4x18
254/8x18

356/8x18

356/8x18

Mechanical Values
Min. failing load - Bending [kN]
Min. failing load - Bending moment underhung [kNm]
Min. failing load - Bending moment upright [kNm]
Min. failing load - Torsion [kNm]

10
6.7
33.5
4

12.5
8.38
41.88
6

16
10.72
53.6
6

20
13.4
67
6

Electrical Values
Lightn. impulse withst. voltage, dry [kV peak value]
Switching impulse withstand voltage, wet [kV peak value]
IEC POST INSULATOR
DESIGNATION

TYPE
PRODUCT NO

1550
1050

1550
1050

1550
1050

1550
1050

1550
1050

1550
1050

1550
1050

C4-1675

C6-1675

C8-1675

C10-1675

C12.5-1675

C16-1675

711015

712015

713015

714015

715015

716012

3650 5.5
450
127 /4x M16
225/4x18
254/8x18

3650 5.5
450
127 /4x M16
225/4x18
275/8x18

3650 5.5
450
127 /4x M16
225/4x18
300/8x18

3650 5.5
450
127 /4x M16
225/4x18
300/8x18

3650 5.5
450
225/4x18
254/8x18
325/8x18

3650 5.5
450
225/4x18
254/8x18
356/8x18

4
2.92
14.6
3

6
4.38
21.9
3

8
5.84
29.2
4

10
7.3
36.5
4

1675
1050

1675
1050

1675
1050

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]
Top fitting p.c.d. d2 [mm] / hole pattern

BIL 1675 kV

Bottom fitting p.c.d. d3 [mm] / hole pattern


Mechanical Values
Min. failing load - Bending [kN]
Min. failing load - Bending moment underhung [kNm]
Min. failing load - Bending moment upright [kNm]
Min. failing load - Torsion [kNm]

12.5
9.13
45.63
6

16
11.68
58.4
6

Electrical Values
Lightn. impulse withst. voltage, dry [kV peak value]
Switching impulse withstand voltage, wet [kV peak value]

23

1675
1050

1675
1050

1675
1050

Outdoor Solid Core Post Insulators


TYPE BIL 1425-1675 kV

Porcelain

C 1 30 (or C 1 20)
according to IEC60672-3,
Brown glazed

Tolerance

according to IEC60 1 68

Fittings

malleable cast iron


according to EN1562
or spheroidal graphite cast
iron according to EN1563,
hot dip galvanized
according to ENISO1461

Cementing

Calcium aluminate cement

24

Outdoor Solid Core Post Insulators


TYPE BIL 1800-2100 kV

TYPE
PRODUCT NO

IEC POST INSULATOR DESIGNATION

C4-1800

C6-1800

C8-1800

C10-1800

C12.5-1800

C16-1800

711016

712016

713016

714016

715016

716013

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]

4000 5.5
450
225/4x18
254/8x18
254/8x18

Top fitting p.c.d. d2 [mm] / hole pattern

BIL 1800 kV

Bottom fitting p.c.d. d3 [mm] / hole pattern

4000 5.5
450
225/4x18
254/8x18
275/8x18

4000 5.5
4 50
225/4x18
254/8x18
300/8x18

4000 5.5
450
225/4x18
254/8x18
325/8x18

4000 5.5
450
225/4x18
254/8x18
356/8x18

4000 5.5
450
225/4x18
254/8x18
356/8x18

Mechanical Values
Min. failing load - Bending [kN]
Min. failing load - Bending moment underhung [kNm]
Min. failing load - Bending moment upright [kNm]
Min. failing load - Torsion [kNm]

4
3.2
16
3

6
4.8
24
3

8
6.4
32
4

10
8
40
4

12.5
10
50
6

1800
1175

1800
1175

1800
1175

1800
1175

1800
1175

16
12.8
64
6

Electrical Values
Lightn. impulse withst. voltage, dry [kV peak value]
Switching impulse withstand voltage, wet [kV peak value]
IEC
POSTINSULATOR
INSULATORDESIGNATION
DESIGNATION
IEC POST

TYPE
PRODUCT NO

1800
1175

C4-1950

C6-1950

C8-1950

C10-1950

C12.5-1950

711017

712017

713017

714017

715017

4400 5.5
450
225/4x18
254/8x18
325/8x18

4400 5.5
450
225/4x18
254/8x18
356/8x18

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]

4400 5.5
450
225/4x18
254/8x18
254/8x18

Top fitting p.c.d. d2 [mm] / hole pattern

BIL 1950 kV

Bottom fitting p.c.d. d3 [mm] / hole pattern

4400 5.5
450
225/4x18
254/8x18
275/8x18

4400 5.5
450
225/4x18
254/8x18
300/8x18

Mechanical Values
Minimum failing load - Bending [kN]
Minimum failing load - Bending moment underhung [kNm]
Minimum failing load - Bending moment upright [kNm]
Minimum failing load - Torsion [kNm]

4
3.52
17.6
3

6
5.28
26.4
3

8
7.04
35.2
4

10
8.8
44
4

12.5
11
55
6

1950
1300

1950
1300

1950
1300

C10-2100

C12.5-2100

Electrical Values
Lightning impulse withstand voltage, dry [kV peak value]
Switching impulse withstand voltage, wet [kV peak value]
IEC POST INSULATOR DESIGNATION

TYPE
PRODUCT NO

1950
1300

1950
1300

C4-2100

C6-2100

C8-2100

711018

712018

713018

714018

715018

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]
Top fitting p.c.d. d2 [mm] / hole pattern

BIL 2100 kV

Bottom fitting p.c.d. d3 [mm] / hole pattern

4700 5.5
450
225/4x18
254/8x18
254/8x18

4700 5.5
450
225/4x18
254/8x18
275/8x18

4700 5.5
450
225/4x18
254/8x18
300/8x18

4700 5.5
450
225/4x18
254/8x18
325/8x18

4700 5.5
450
225/4x18
254/8x18
356/8x18

8
7.52
37.6
4

10
9.4
47
4

12.5
11.75
58.75
6

2100
1300

2100
1300

Mechanical Values
Minimum failing load - Bending [kN]
Minimum failing load - Bending moment underhung [kNm]
Minimum failing load - Bending moment upright [kNm]
Minimum failing load - Torsion [kNm]

4
3.76
18.8
3

6
5.64
28.2
3

Electrical Values
Lightning impulse withstand voltage, dry [kV peak value]
Switching impulse withstand voltage, wet [kV peak value]

2100
1300

25

2100
1300

2100
1300

Outdoor Solid Core Post Insulators


TYPE BIL 1800-2100 kV

Porcelain

C 1 30 (or C 1 20)
according to IEC60672-3,
Brown glazed

Tolerance

according to IEC601 68

Fittings

malleable cast iron


according to EN1562
or spheroidal graphite cast
iron according to EN1563,
hot dip galvanized
according to ENISO1461

Cementing

Calcium aluminate cement

26

Outdoor Solid Core Post Insulators


TYPE BIL 2250-2550 kV

IEC POST INSULATOR DESIGNATION


IEC POST INSULATOR DESIGNATION

TYPE
PRODUCT NO

C4-2250

C6-2250

C8-2250

C10-2250

C12.5-2250

711019

712019

713019

714019

715019

5000 6.5
450
225/4x18
254/8x18
300/8x18

5000 6.5
450
225/4x18
254/8x18
325/8x18

5000 6.5
450
225/4x18
254/8x18
356/8x18

5000 6.5
450
225/4x18
254/8x18
356/8x18

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]

5000 6.5
450
225/4x18
254/8x18
254/8x18

Top fitting p.c.d. d2 [mm] / hole pattern

BIL 2250 kV

Bottom fitting p.c.d. d3 [mm] / hole pattern


Mechanical Values
Minimum failing load - Bending [kN]
Minimum failing load - Bending moment underhung [kNm]
Minimum failing load - Bending moment upright [kNm]
Minimum failing load - Torsion [kNm]

4
4
20
3

6
6
30
3

8
8
40
4

10
10
50
4

12.5
12.5
62.5
6

Electrical Values
Lightning impulse withstand voltage, dry [kV peak value]
Switching impulse withstand voltage, wet [kV peak value]
C12.5-2400

IEC POST INSULATOR DESIGNATION

TYPE
PRODUCT NO

2250
1425

2250
1425

2250
1425

2250
1425

2250
1425

C4-2400

C6-2400

C8-2400

C10-2400

C12.5-2400

711020

712020

713020

714020

715019

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]

5300 6.5
450
225/4x18
254/8x18
254/8x18

Top fitting p.c.d. d2 [mm] / hole pattern

BIL 2400 kV

Bottom fitting p.c.d. d3 [mm] / hole pattern

5300 6.5
450
225/4x18
254/8x18
300/8x18

5300 6.5
450
225/4x18
254/8x18
325/8x18

5300 6.5
450
225/4x18
254/8x18
356/8x18

5300 6.5
450
225/4x18
254/8x18
356/8x18

Mechanical Values
Minimum failing load - Bending [kN]
Minimum failing load - Bending moment underhung [kNm]
Minimum failing load - Bending moment upright [kNm]
Minimum failing load - Torsion [kNm]

4
4.24
21.2
3

6
6.36
31.8
3

8
8.48
42.4
4

10
10.6
53
4

12.5
13.25
66.25
6

2400
1425

2400
1425

2400
1425

2400
1425

2400
1425

C4-2550

C6-2550

C8-2550

C10-2550

712021

713021

714021

Electrical Values
Lightning impulse withstand voltage, dry [kV peak value]
Switching impulse withstand voltage, wet [kV peak value]
IEC POST INSULATOR DESIGNATION

TYPE
PRODUCT NO

711021

Dimensions
Height H [mm]
Max. nom. diameter of insulating part d1 [mm]

5700 6.5
450
225/4x18
254/8x18
275/8x18

Top fitting p.c.d. d2 [mm] / hole pattern

BIL 2550 kV

Bottom fitting p.c.d. d3 [mm] / hole pattern

5700 6.5
450
225/4x18
254/8x18
300/8x18

5700 6.5
450
225/4x18
254/8x18
325/8x18

5700 6.5
450
225/4x18
254/8x18
356/8x18

8
9.12
45.6
4

10
11.4
57
4

Mechanical Values
Minimum failing load - Bending [kN]
Minimum failing load - Bending moment underhung [kNm]
Minimum failing load - Bending moment upright [kNm]
Minimum failing load - Torsion [kNm]

4
4.56
22.8
3

6
6.84
34.2
3

2550
1550

2550
1550

Electrical Values
Lightning impulse withstand voltage, dry [kV peak value]
Switching impulse withstand voltage, wet [kV peak value]

27

2550
1550

2550
1550

Outdoor Solid Core Post Insulators


TYPE BIL 1800-2100 kV

Porcelain

C 1 30 (or C 1 20)
according to IEC60672-3,
Brown glazed

Tolerance

according to IEC601 68

Fittings

malleable cast iron


according to EN1562
or spheroidal graphite cast
iron according to EN1563,
hot dip galvanized
according to ENISO1461

Cementing

Calcium aluminate cement

28