PowerFlex 753 Basic Start Up for Speed Controlled


Applications

Contents
Before you begin........................................................................................................................................ 5
Tools............................................................................................................................................................ 5
About this lab............................................................................................................................................... 5
About the Demo......................................................................................................................................... 6
Lab Setup................................................................................................................................................... 7
Lab Objective............................................................................................................................................. 8
Using the Human Interface Module (H.I.M).............................................................................................. 9
Disabling DeviceLogix Program IF LOADED & RUNNING................................................................10
Preparing the PowerFlex 753 Demo To Run In Simulation Mode........................................................14
Assisted Startup using the Human Interface Module (H.I.M)...............................................................16
Resetting factory defaults.......................................................................................................................... 17
Setting the Motor Control Mode................................................................................................................. 20
Entering Motor Nameplate Data................................................................................................................ 21
Setting the Speed Feedback Device.......................................................................................................... 24
Setting the Speed Limits............................................................................................................................ 24
Direction Auto Tune and Inertia Tests........................................................................................................ 25
Configuring the Speed Reference and Ramp rates...................................................................................28
Configuring the Inputs and Outputs........................................................................................................... 30

3 of 68

Drive Programming via Software Tool (Optional).................................................................................32


About This Section..................................................................................................................................... 32
Using Drive Explorer with PF753............................................................................................................... 32
Starting Drive Explore and Connect To Drive.............................................................................................33
Reset Drive to Defaults.............................................................................................................................. 36
Displaying The Status View....................................................................................................................... 39
Displaying Parameters with the Linear List View.......................................................................................43
Displaying Parameters with the File / Group View.....................................................................................44
Using the Startup Wizard........................................................................................................................... 45
Using the Control Bar Tool......................................................................................................................... 62
Using Off-line Files..................................................................................................................................... 64

4 of 68

Before you begin

Tools
PowerFlex 753 Training Demo
Windows XP PC with DriveExplorer (full version 6.02 or greater); for optional section

About this lab


This session provides you with an opportunity to explore the PowerFlex 753 AC drive. In this session you
will learn to:
Use the Assisted Startup for simple Speed Controlled Applications
Control the Drive and simulate spinning a motor
This lab takes approximately 45 minutes to complete.

5 of 68

About the Demo


The DHQ packaged PowerFlex 753 Demo is a reduced size, packaged demo kit for demonstrating
programming of PowerFlex 753, as well as Premier Integration, and DeviceLogix. On board I/O facilitates
user input as well as feedback.
This demo unit has been designed for demonstrating the PowerFlex 753 operation and utilizes the drives
internal feedback simulation abilities to mimic an actual spinning motor. Although this is a production
drive the demo itself was not designed to run an actual motor. There are no user connections to apply an
external motor nor was the internal step up transformer or fusing sized to run anything greater then the
drive rated current w/o any loading.
The image below labels the switches, push buttons and the potentiometer required in this lab session.

Di 0 Normally Open Pushbutton


Di 1 Normally Closed Pushbutton
Di 2 Selector Switch

0- 10 V Analog Input

DRIVE POWER Circuit Breaker

6 of 68

Lab Setup
1. On the PowerFlex 753 demo case, verify position switch Di 2 is selected to the left (OFF)
2. Energize the drive demo; switch the single-pole breaker labeled POWER, located on the front of
the demo, to the on position.

7 of 68

Lab Objective
At the end of this lab, you should have successfully completed the Assisted Startup routine of the PF753
drive and
1. Programmed the Drive to start the drive/motor using the green pushbutton labeled Di 1.
2. Programmed the Drive to stop the drive/motor using the red pushbutton labeled Di 0.
3. Programmed the Drive to forward or reverse the drive/motor using the selector switch labeled Di
2.
4. Programmed the Drive to get Speed Reference from an Analog Source, the potentiometer labeled
0-10 INPUT.

8 of 68

Using the Human Interface Module (H.I.M)


The image below shows some of the essential keys which you will be using in this session. Please
familiarize yourself with these keys (buttons)

9 of 68

Disabling DeviceLogix Program IF LOADED & RUNNING


If a DeviceLogix Program is loaded and running in the PowerFlex 753 demo, the logic needs to be
disabled and the drive reset prior to conducting the lab. If the DeviceLogix program has not been properly
disabled, the drive will not operate according to the lab procedure.
Consult with your instructor before performing the following procedure:
NOTE: Disabling the DeviceLogix operation requires Advanced or Expert parameter access

1. From the Status screen which is displayed on HIM PowerUp. Use the left
arrow keys to navigate to the DeviceLogix option.

or right

2. The HIM screenshot above shows the display if the DeviceLogix is enabled LogicEnabled. If the
logic is disabled LogicDisabld then disabling of the DeviceLogix is not required, skip to the next
section.
3. Press the PAR# soft key and enter the number 53 followed by the ENTER soft key to goto
parameter 53

10 of 68

4. Use the EDIT soft key followed by the scroll down


or scroll up
arrow soft keys to change
parameter #53 to DisableLogic then the ENTER soft key to confirm.

Parameter 53 [DLX Operation] is of the parameter type that contains both operation
commands as well as status information. Setting it to disable logic is option 1, however
once the ENTER key is pressed to confirm the display is option 5 LogicDisabled.
5. Press the ESC soft key to return the display to the top level DeviceLogix screen

11 of 68

6. Use the left


or right
Control Board Slot 0)

arrow keys to navigate to the drives initial screen (Main

7. Press the Folders button


on the HIM keypad. The button is located on the bottom row of
the HIM Keypad (shown circled in the left image below).Pressing the Folders button changes the
HIM screen display to the Folders screen ( see right image below)

12 of 68

8. Use the left


or right
folder called DIAGNOSTIC.

arrow keys to scroll through the different folders, to locate the

9. Use the down arrow key


to highlight Reset Device then press the Enter key
located in the center of the HIM keypad to make this your selection.

10. A confirmation screen follows press the ENTER soft key to confirm your selection.

11. The drive will then reset, upon completion the drive maybe faulted; press the CLR soft key to
clear acknowledge and clear fault.

13 of 68

Preparing the PowerFlex 753 Demo To Run In Simulation Mode


This demo unit has been designed for demonstrating the PowerFlex 753 operation and utilizes the drives
internal feedback simulation abilities to mimic an actual spinning motor. Although this is a production
drive the demo itself was NOT designed to run an actual motor. In order to complete the lab the feedback
mode needs to changed to simulate.
1. From the Status screen which is displayed on HIM PowerUp. Press the PAR# soft key and enter
the number 301 using the numeric keypad followed by the ENTER soft key to goto parameter
301 [Access Level]

2. Verify that P301 [Access Level] is set to Expert if not press the EDIT soft key followed by the
scroll down
or scroll up
arrow soft keys to change the parameter to Expert then the
ENTER soft key to confirm.

14 of 68

3. Press the PAR# soft key and enter the number 125 followed by the ENTER soft key to goto
parameter 125 [Pri Vel Fdbk Sel]

4. Press the EDIT soft key, the default (and only choice) for Edit Spd Ref A Sel is PowerFlex 753.
Make this selection using the Enter soft key

5. For Pri Vel Fdbk Sel selection use the down arrow key
make this selection using the Enter soft key.

to select Simulator Fdbk. Then

6. Press the ESC soft key to return the display to the top level Status Screen.

15 of 68

Assisted Startup using the Human Interface Module (H.I.M)


One of the ways to perform an Assisted Startup on the PowerFlex 753 is using the Startup routine in the
H.I.M. The following steps will lead you through that:
1. Access the Status screen which is displayed on HIM PowerUp.

2. Press the Folders button


on the HIM keypad. The button is located on the bottom row of
the HIM Keypad (shown circled in the left image below).Pressing the Folders button changes the
HIM screen display to the Folders screen ( see right image below)

16 of 68

Resetting factory defaults


3. Use the left
or right
folder called MEMORY.

4. Use the down arrow key

arrow keys to scroll through the different folders, to locate the

to highlight Set Defaults if necessary and press the Enter key

located in the center of the HIM keypad to make this your selection.
5. The screen which follows after completion of the previous step is shown. Use the down arrow key
to highlight This Port only. Press the Enter key
keypad to make this your selection.

17 of 68

located in the center of the HIM

6. Use the soft key labeled ALL to reset default all parameter settings in the Drive.

7. Use the CLR soft key to acknowledge and clear the Module Defaulted fault.
8. If you receive a screen that confirms that setting factor defaults is complete press the ENTER
soft key to confirm.
9. Press the Folders button

on the HIM keypad again to access the Folders Menu.

10. Now use the left


or right
locate the folder called START UP.

arrow keys to scroll through the different folders, to

11. The first item listed in the START UP folder is Begin Start Up and this is highlighted by default.
Press the Enter key

located in the center of the HIM keypad to make this your selection.

18 of 68

12. The startup routine starts with an Introduction screen. Press the ENTER soft key to continue.
The ENTER soft key is located on the top row of the HIM keypad.

Note: You can always use the ESC soft key to return to a previous step.
13. Pressing the ENTER soft key in the previous step has led you to a new screen, which allows you
to select the type of startup you wish to perform. For this lab session, we will choose General
Startup. This is highlighted by default. Press the ENTER soft key located on the top row of the
HIM keypad to make this your selection.

19 of 68

Setting the Motor Control Mode


14. Pressing the ENTER soft key in the previous step has led you to the General Startup Main
Menu. You will go through steps listed in this menu to configure your drive. Press ENTER soft
key to enter the first section Motor Control.

15. The introduction screen provides information about the Motor Control section. Press the ENTER
soft key to continue.

20 of 68

16. Pressing the ENTER soft key in the previous step leads you to a screen which lists the available
motor control modes in the PowerFlex 753. For this lab session, we will choose the Flux Vector
mode. Use the
down arrow key to navigate and select Flux Vector. Press the ENTER
soft key to make this your selection.

17. Pressing the ENTER soft key in the previous step leads you to a screen which lists the available
Control Modes in the PowerFlex 753. For this lab session, we will choose the default selection of
Speed. Press the ENTER soft key to make this your selection

Entering Motor Nameplate Data


18. After selecting the motor control mode in the previous step, you are directed back to the General
Startup Main Menu. Motor Data should be highlighted now. Press the ENTER soft key to make
this your selection. The next few steps will require you to input the nameplate information of the
motor you are doing a Startup on.

21 of 68

19. Pressing the ENTER soft key in the previous step has led you to the Startup Motor Data Entry
screen. The first information you will provide is the Motor Nameplate (NP) Volts. The Motor in the
demo is rated for 230 V. This should be the default value for this parameter. Press the ENTER
soft key to confirm your input and move to the next screen.

20. The next information you need to provide is the Power Units. By default the value of the
parameter should be set to HP. Press the ENTER soft key to confirm your selection and move
to the next screen.

22 of 68

21. You will now be required to input the Motor Nameplate (NP) Power. Since there actually is no
motor connected use the default of 1.00 HP Press the ENTER soft key to confirm your input and
move to the next screen.

22. You will now be required to input the Motor Nameplate (NP) Amperes. Again accept the default
value here. Press the ENTER soft key to confirm your input and move to the next screen.

23. Continue through the Startup / Motor Data Entry section choosing the default values. Once all
the Motor Data Entry steps are complete you will be brought back to the General Startup Main
Menu with Feedback being highlighted.

23 of 68

Setting the Speed Feedback Device


24. Setting the Speed Feedback Device will be skipped in this lab going back to About The Demo
section there is physically no actually motor and the demo unit was selected to a simulated
feedback. Selecting this option now would force a feedback selection that is NOT valid for
simulation mode.

Setting the Speed Limits


25. In the previous step configuring your feedback device was skipped; configuring the limits is the
next step in the Startup routine. Use the
down arrow key to navigate to the Limits step. .
Press the ENTER soft key to access Limits section.

26. For this lab session, we will not be changing the limits but verify the following selections in the
Limits section. Use the number keys to input the values listed for each item and press the
ENTER soft key to move forward to the next screen. After the four values have been entered,
you will be exited out of this section.
Max Fwd Speed = 60 Hz
Max Rev Speed = -60 Hz (you can directly enter a value of 60; the negative sign is defaulted)
Min Fwd Speed = 0.00 Hz
Min Rev Speed = 0.00 Hz

24 of 68

Direction Auto Tune and Inertia Tests


27. You should now have been directed back to the General Startup Main Menu. The Tests section
is next and should be highlighted by default at this stage. Press the ENTER soft key to access
Tests section.

28. There are two tests which are part of the Startup Routine. You will perform these tests in the next
few steps. You will run the Direction test first. The Direction Test list item should be highlighted
by default. Press the ENTER soft key to make this your selection. Press the Start key
start the motor.

to

29. The next screen asks the question Is the direction of rotation forward? To demonstrate the
ability of the PowerFlex 753 to electronically swap motor leads to change motor direction, let us
choose No as the answer to this question. Use the
highlight No and press the Press the ENTER soft key.

25 of 68

down arrow key to select and

30. The next screen asks the question How would you like to fix motor polarity? . Select the default
highlighted option Automatic change by using the ENTER soft key.

31. The screen that follows asks you to stop the drive so this change in direction, initiated in the
previous step, can take place. Press the STOP

key to stop the drive.

32. Follow the direction on the next screen which asks you to START the drive. You can start the
drive and by using the START

key.

33. The next screen asks the question Is the direction of rotation forward? and requires confirmation
that the changes to direction are acceptable. Select Yes by pressing the ENTER soft key.
34. Press the Stop key

.This should successfully complete the Direction test.

35. You should now be back in the Motor Test Menu screen. Now use the ENTER soft key to select
the Auto tune Test. Read the important information on the screen and press the ENTER soft
key.

26 of 68

36. Pressing the ENTER soft key in the previous step has directed you to the Select the tuning
mode screen. For this lab session, we will perform a rotate tune on the demo motor. Select the
default highlighted option Rotate Tune by pressing the ENTER soft key.
37. As directed by the HIM screen information, press the START key
to start the Auto tune Test.
Notice the changing information on the HIM (as the different parts of the Auto tune tests are
completed).Wait till the test is completed.

38. The completion of the test is indicated by the Test Completed Successfully screen. Press the
ENTER soft key.

39. Select the Inertia Test using the ENTER soft key and use the ENTER soft key again to confirm
that the load is connected to the motor.
40. As directed by the HIM screen information, press the START key

27 of 68

to start the Inertia Test.

41. The completion of the test is indicated by the Test Completed Successfully screen. Press the
ENTER soft key. This will bring up the Edit Speed Reg BW entry screen. Select the ENTER
soft key to accept the default value of 10.00 R/S.

42. Pressing the ENTER key in the previous step has directed you back to the Motor Test Menu.
Use the ENTER soft key to select Done in the Motor Test Menu screen.

Configuring the Speed Reference and Ramp rates


43. At this time you should be in the General Startup Main Menu. The next item on the Startup
menu list Ref Ramp Stop should be highlighted by default. Press the ENTER soft key to make
this your selection.
44. The Edit Direction Mode box should be on the screen now. We will use the default parameter
value of Unipolar for this lab session. Press the ENTER soft key to confirm and save your
selection.
45. You should be on the speed reference source selection screen. Use the down arrow

or up

arrow
keys to highlight Analog Input as your Speed Reference source. Use the ENTER
soft key to make this your selection.

28 of 68

46. In the window Select Port to Use that appears following the previous step, use the down arrow
or up arrow
keys to highlight Port 00 PowerFlex 753. Press the ENTER soft key to
confirm and save your selection.

47. Use the down arrow

and up arrow

keys, to highlight Par 0260 Anlg In0 Value. The

selected choice is the last in the list and pressing the


the ENTER soft key to confirm and save your selection.

once will get you there faster. Press

48. The next few steps will configure the Analog Input you chose as Speed Reference. For this lab
session we will use the 0-10V potentiometer (labeled 0-10 Input) on the demo as our Analog Input
speed reference. Pressing the ENTER soft key in the previous step has led you to the first item
required to configure the Analog Input. You should be in Edit Anlg In0 Hi screen. Press the
ENTER soft key to accept the default value of 10.000 Volt.
49. In the Edit Anlg In0 Lo screen that follows, press the ENTER soft key to accept the default value
of 0.000 Volt.
50. In the next few screens input these values
Speed Ref A Anlg Hi = 60Hz and
Speed Ref A Anlg Lo = 0Hz. Press the ENTER soft key.

29 of 68

51. You should be in the Startup / Stop Config screen now, press the ENTER soft key to accept the
default selection of Ramp to be used as Stop Stop Mode A.
52. Pressing the ENTER key in the previous step has directed you to the screen to configure the
Bus Reg Mode A. Select the default of Adjust Freq using the ENTER soft key
53. Following the step to set bus regulation you will now set Ramp (Accel and Decel) times. In the
Edit Accel Time 1 screen, use the appropriate number key to enter a value of 3 seconds. Press
the ENTER soft key.
54. Similarly enter a value of 3 seconds for the deceleration time in the Edit Decel Time 1 screen.
Press the ENTER soft key.
55. The next screen continues the ramp speed configuration and asks the question Do you want to
perform S-curve for Accel/Decel? . We will select No as the answer for this lab session. You can
select No by highlighting it using the
down and
ENTER soft key to confirm and save your selection.

up arrow keys and then using the

Configuring the Inputs and Outputs


56. Completing the previous step successfully has led you to the General Startup Main Menu with
the item I/O highlighted. Press the ENTER soft key to enter the I/O section.
57. You should be in the Start Stop I/O screen now. The first item to configure on this list is Start
Stop & Dir. Press the ENTER soft key to enter this section. Read the Introductory screen to this
section and press the ENTER soft key to continue.
58. The next screen requires you to answer the question Will a Digital Input be used as a START
Source? Select Yes using the
down and
up arrow keys and then using ENTER
soft key to confirm and save your selection. We will use the green push button labeled Di 1 in
the demo as our Start Source in a later step.
59. The next screen will ask the question Is Reverse required from a digital input?? Select Yes
using the
down and
up arrow keys and then using ENTER soft key to confirm and
save your selection. We will use the switch labeled Di 2 in the demo as forward/reverse in a
later step.
60. Select 3 wire as your choice for the question Enter Choice for the control method.
61. In the Edit DI Start / Select Port To Use window use the up and down arrow keys to highlight
Port xx PowerFlex 753. Press the ENTER soft key to make this your selection.
(xx = Port where the I/O is located onboard or Option card)

30 of 68

62. In the Edit DI Start / Select Parm To Use window. Press the Enter soft key to select and confirm
Par 0220 Digital In Sts selection.
63. The Edit DI Start window will be displayed first; select the bit/Digital Input you want to use as
your START. We are going to use the green push button labeled Di 1 as our start input. To do
this scroll to Digital Input 1 and press the Enter soft key.
64. Follow procedures similar to the previous steps to select the red push button labeled Di 0 as
your stop switch and the selector switch labeled Di 2 as your Forward/Reverse switch in that
order.
65. You should now be back in the Start Stop I/O menu screen. This is all we will configure in this
section so use the
down arrow keys to scroll down to the last item on the list Done. After
Done is highlighted, use the ENTER soft key to make this your selection.
66. You should now be back in the General Startup Main Menu screen .you have finished with the
Startup routine steps required for this lab session. Select Done using the ENTER soft key to
exit out this screen.
67. Select Exit Startup using the ENTER soft key to exit out of the Startup routine.
68. You can now test your drive to perform the functions you configured during the startup routine
namely, Start using the green push button Di 1, Stop using the red push button Di 0, change
direction using Di 2 and provide speed reference using the 0-10V Input pot.
Again, remember that there is no physical motor connected to this demo unit however the speed
and status are being simulated on the top lines of the HIM display.

31 of 68

Drive Programming via Software Tool (Optional)


Besides the HIM the drive parameters and programming can be accessed via software tool. These tools
include DriveTools SP, Drive Explorer, or RSLogix 5000 v16 (or greater) with Drive AOP 3.01 (or greater).

About This Section


In this lab, we will introduce you to DriveExplorer software and some of the features that are common
across all the software tools. In this lab you will:

Connect to a PowerFlex drive using DriveExplorer software

Display the Status View

Display and edit parameters with the Linear List View

Display and edit parameters with the File / Group View

Use the Control Bar to control a drive

Use a Wizard

Upload configuration from drive to PC

Download configuration to drive from PC

Using Drive Explorer with PF753


1. Verify that the PowerFlex 753 drive is connected to the computer.

32 of 68

2. When using DriveExplorer, it may be necessary to shutdown RSLinx if it has the serial or USB
driver configured. If RSLinx is running, it will display an icon in the Systray on the PCs desktop.

3. Right click on the RSLinx Icon in the Systray.


4. Select Shutdown RSLinx Classic on the Pop-up menu.

Starting Drive Explore and Connect To Drive


1. Double-click the DriveExplorer icon to start the software.
2. If the Danger dialog appears, read it and click OK.
3. Maximize the DriveExplorer window, so it fills the entire screen
4. Click on the Connect Ethernet icon in the taskbar.

33 of 68

a. If the Connect Serial icon

has focus instead; DriveExplorer is configured to

communicate serially; configuration path needs to be changed to Ethernet. Go to Explore


Configure communication Select Ethernet ok.

b. The following screen will appear. Select yes to accept the communication interface
change

c.

At this point the Connect Ethernet icon will now have focus, select it by clicking on it

34 of 68

5. When the node selection window opens, highlight the node with IP address 192.168.1.20 and
click the Connect button to connect to the drive.

a. If the IP Address of the drive is not in the window then select Add Node, type in the IP
address then click OK.

b. Click Yes to the following message windows.

6. Wait for the parameters to be read and populated.

35 of 68

7. Once the parameters are read and populated, by default Port 0 PowerFlex 753 240V 4.2 A should
be highlighted, as shown in the following graphic.

Reset Drive to Defaults


8. Navigate to Actions Non Volatile Memory and click on Non Volatile Memory.

36 of 68

9. This will open a new window. Use the default selection of Host and Ports to Defaults (Preferred)
and click on the button Load Defaults

10. Observe the prompted warning then click Yes to the question Do you wish to continue? in the
next window.

37 of 68

11. A pop window confirms that loading of parameter defaults was successful. Click OK.

12. You will be returned to the Non-Volatile Memory window, Click Close

38 of 68

Displaying The Status View


13. If you have not already expanded the Drive Explorer application do so now by clicking on

the lower right corner of the window and drag it so the entire Status View area can be
seen (you can also maximize the window using the Maximize icon
if desired)

The Status View displays the drives User Text (PowerFlex 753 in the image above) as
well as important drive information, such as voltage and amp ratings, series, revision,
and operational status. The Status View is automatically displayed the first time you
connect to a drive. You can also display it at any time by clicking on the drive name in
the device tree (PowerFlex 753 in the above image).

39 of 68

14. You can display the status view for any peripheral (e.g. the DeviceLogix adapter or other

communication adapter) by selecting the peripheral in the device tree.

15. Return to the drives status view; Click on the drives User Text (in the image, it is PowerFlex
753) to edit it. Enter new text such as PowerFlex Rocks! and click Apply

16. The new User Text is now displayed.

40 of 68

17. Click on the Pencil icon

for the middle display item.

18. This is where you select, scale and assign text to Display Item 1.

19. Change Process Display Item 1 to the following values and click Apply

41 of 68

20. Close the Process Display Item 1 window.


21. Note the change you made to Process Display Item 1. Adjust the 0-10V Input potentiometer on
the drive demo to change the value on the screen.

The PowerFlex 753 has six Process Display items displayed. Other products may have
more or less and each will be display on theirs in the Status View.

42 of 68

Displaying Parameters with the Linear List View


22. Click on Parameter List in the device tree to display a linear list of the drive parameters.

23. Scroll down to view Parameter 260 [Anlg In0 Value] and then double-click on this parameter to
view it.

This is a read-only parameter that displays the value of Analog In0, which is connected to the
potentiometer (0-10V INPUT) on the demo unit. Adjust the potentiometer to see the value
change. Click Close.

43 of 68

24. Scroll down even further to Parameter 535 [Accel Time 1]. and then double-click on this
parameter to view and edit it

This is a writeable parameter that determines the acceleration rate it takes to go from 0 Hz to
P27[Motor NP Hertz] or P28[Motor NP RPM), according to the setting in P300[Speed Units]. To
edit this parameter, a new value would be entered followed by clicking either OK or Apply.
Click Cancel.

Displaying Parameters with the File / Group View


25. In the device tree, click on the Speed Control file and then the Speed Ramp Rates group to
display those parameters.

See how getting to the same parameter as what was previously scrolled to using the Linear List
function can be accessed by its grouping. If you do not know a parameters number, it maybe
easier to find it with the File / Group view.

44 of 68

Using the Startup Wizard


The Startup Wizards eliminate the need to search for setup parameters because commonly used
parameters are contained in a single wizard. Configuration becomes a guided, step-by-step process
using graphics and parameter names (not numbers!), which simplifies drive setup.

1. Click on the Wizard Browser icon

to launch the Wizard Browser and display the available

wizards.

The PowerFlex 753 Startup Wizard is similar to performing the HIM Assisted Startup.
Configuration parameters that are common to most applications are displayed in text / graphic
forms and presented in a sequential step-by-step process.
The DPI/DSI Tech Support Wizard is used to collect information for a remote support person to
help troubleshoot a problem. Drive and peripheral information such as series and revision is
collected along with changed parameters, fault & event queues, diagnostic items, etc. This
information is saved to a text file which can be emailed to RA Tech Support, the OEM that
supplied the machine, or the Corporate Engineer responsible for the remote plant, etc.
Additional wizards will be available in the future and can be added to DriveExplorer v6.02 (and
higher) at any time. New wizards will be posted on the AB Drives Web Updates page for free
download:
http://www.ab.com/support/abdrives/webupdate/index.html
Note: The same wizards also work with DriveTools SP v6.02 and higher and RSLogix
5000 v16 (or greater) with Drive AOP 3.01 (or greater).

45 of 68

26. Select the PowerFlex 753 Startup Wizard and click Select.
The wizard will first upload the parameters for each of the wizard pages.

27. The first step in the wizard is the Welcome page. It explains the wizard and gives hints and tips
for using the wizard. Click Next.

46 of 68

28. The Reset Parameters step is next. It allows you to reset the drives parameters back to factory
defaults. Verify High Voltage and Normal Duty is selected from the pull down menus. Then click
Reset Parameters.

In the confirmation window, click Yes.

Observe the on screen confirmation of the parameters being reset.

Click Next> to continue; viewing the sequential process and continuing to click Next> until you
reach the Motor Control Step of the Wizard

47 of 68

29. Perform the Motor Control Step of the PowerFlex 753 Startup Wizard. Make the selections
shown:
Motor Control Mode = Select Induction Flux Vector
Primary Speed Feedback = Slot 0 (PowerFlex 753); Parameter 138 (Simulator Fdbk)

Click Next> to the Motor Data Step of the Wizard.

48 of 68

30. The Motor Data is next. This step assists in entering the data from your motors nameplate into
the drive. No selections need to be changed on this step, keep the default selections.

Click Next> to the Stop Mode Step of the Wizard.

49 of 68

31. The Stop Mode step is next. This step assists in selecting the drives stop mode and Dynamic
Brake (DB) resistor type. No selections need to be changed on this step, keep the default
selections.

Click Next> to the Direction Test Step of the Wizard.

50 of 68

32. The Direction Test step is next. It helps you determine if the motor is rotating in the proper
direction for your application. No selections need to be changed on this screen.

Direction Tests are not needed for this example; however they can be ran if you desire. If you do
perform the autotune note the following:
Click the
button and hold it for a few seconds to run the drive. As long as you hold the jog
button, the drive will run. Once you let go of the button, the drive will stop. After the motor stops,
click the Yes radio button. Observe how clicking the Yes radio button updated the screen with a
Test Passed status as well as adding Change Direction option.
Click Next> to the AutoTune Step of the Wizard.

51 of 68

33. The AutoTune step is next. This step is where you can use automatic tuning algorithms
(AutoTune). When running these algorithms the drive energizes the motor and makes
measurements, which are used to make parameter settings.

AutoTune tests are not needed for this example; however they can be ran if you desire. If you do
perform the autotune note the test status:

leaving the AutoTune test page while test is in process will abort test; faulting the drive. Do not
leave AutoTune test page until test completes:

Click Next> to the Inertia AutoTune Step of the Wizard.


Note: Clicking <Back, Next>, or leaving step by any means will about the test.

52 of 68

34. The Inertia AutoTune is next. This step is where you can use an automatic tuning algorithm to
determine the loads inertia. When running this algorithm the drive spins the motor and makes
measurements, which are used to make parameter settings

AutoTune tests are not needed for this example; however they can be ran if you desire.
If you do perform the autotune note the test status:

leaving the AutoTune test page while test is in process will abort test; faulting the drive. Do not
leave AutoTune test page until test completes:

Click Next> to the Ramp Rates / Speed Limits Step of the Wizard.
Note: Clicking <Back, Next>, or leaving step by any means will about the test.

53 of 68

24. Perform the Ramp Rates/Speed Limits Step of the PowerFlex 755 Startup Wizard.
Enter: Max Forward / Reverse Speed 60 Hz
Min Forward / Reverse Speed 0 Hz
Enter a non-zero value for the S Curve to see what happens with the graphic.
Then reset it back to 0.

Click Next> to the Speed Reference Step of the Wizard.

54 of 68

35. The Speed Reference step is next. It helps you select where the drive gets its speed reference.
Observe the screen with the default value for speed reference selected to Port 0.

Now select the reference to be from P260 [Anlg In0], observe how the wizard shows the pertinent
parameters and for this analog input.

Click Next> to continue; viewing the sequential process, continue to click Next> until you reach
the Start / Stop step of the Wizard.

55 of 68

36. Perform the Start / Stop step of the PowerFlex 753 Startup Wizard. Make the selections shown.
DI Start = Slot 0 (PowerFlex 753); Parameter 220 (Digital In Sts); Bit 1 (Digital In 1)
DI Stop = Slot 0 (PowerFlex 753); Parameter 220 (Digital In Sts); Bit 1 (Digital In 0)
DI Forward / Reverse = Slot 0 (PowerFlex 753); Parameter 220 (Digital In Sts); Bit 1 (Digital In 2)

Click Next> to the Other Digital Inputs Step of the Wizard.

56 of 68

37. The Other Digital Inputs step is next. This step helps you configure the drives most commonly
used digital inputs. No selections need to be changed on this step, keep the default selections

Click Next> to the Digital Output Port 0 Step of the Wizard.

There are other digital inputs available to user; however the Wizard shows
the most commonly programmed inputs. All the available digital inputs can
be accessed via the HIM or software tool (parameters 150 201).

57 of 68

38. Perform the Digital Relay Out 0 step of the PowerFlex 753 Startup Wizard. This step helps you
configure the drives digital outputs. Make the selections shown
Select = Slot 0 (PowerFlex 753); Parameter 935 (Drive Status 1); Bit 16 (Running)

Click Next> to the Digital Output Port 0 Step of the Wizard.

There are no I/O options installed in this demo; however if there were an
additional digital option card installed more Digital Output and Analog
Output steps would become available to user and would be designated by
their associated port.

58 of 68

39. Perform the Digital Transistor Out 0 Step of the PowerFlex 753 Startup Wizard. This step helps
you configure the drives digital outputs. Make the selections shown
Select = Slot 0 (PowerFlex 753); Parameter 935 (Drive Status 1); Bit 7 (Faulted)

Click Next> to the Analog Output Port 0 Step of the Wizard.

59 of 68

40. The Analog Out 0 step is next. It helps you configure the drives analog outputs. No selections
need to be changed on this step, keep the default selections.

Click Next> to the Pending Changes Step of the Wizard.

60 of 68

41. The Applied and Pending Changes page will appear. The purpose of this step is to verify all of
the changes you made in the wizard, and then apply the changes to the drive. The below screen
is for reference (your changes may differ from what is shown below).

Click Finish >>. The wizard will write your changes to the drive.

The Pending Changes step can be used as a reference tool. You can print
the summary with the print button
at the bottom of the window. You can
refer to the printed summary when commissioning duplicate drives or
replacing a faulted drive.

61 of 68

Using the Control Bar Tool


42. Click on the

button in the tool bar at the top of the window

43. Read Caution advisory and click OK

62 of 68

44. Use the buttons on the left-hand side of the control bar to start, stop, jog and control the direction
of the drive

The speed reference was selected to the Analog In0 in the previous step. To allow the control bar
to have control of the speed reference; Parameter 545[Spd Ref A Sel] will need to be changed
(while the drive is not running). Stop the drive and change Parameter 545 setting to Port
PowerFlex 753, Parameter 876 - Port 6 Reference.

Start the Drive again and use the slider on the right-hand side to control the speed reference.
45. Stop the Drive and turn off the control bar by clicking the
pop up window and click Yes.

63 of 68

button again. Observe the Caution

Using Off-line Files


This feature allows you to save your drive configuration to a computer. It is useful for several reasons:

You can use the configuration if you replace the drive or install an identical one.

You can use the configuration to troubleshoot the drive if it begins to malfunction because the
settings have been changed.

Uploading and Saving the Drives Configuration to a PC


46. Select the drive in the device tree.
47. From the Actions menu, select Upload/Download All.

48. On the Upload/Download All window choose Upload.

64 of 68

49. By selecting the Upload/Download All you now are prompted to select with ports to upload.
Deselect port 1 (20-HIM-x6) and Port 6 (20-COMM-E) and then click Upload.

50. Each of the ports parameters will be uploaded. As indicated by the below screen, each port will
be displayed as its parameters are uploaded.

51. In the Save As window define the filename and location of the file. Take note of the name and
remember where you save this file, it will be needed later.
52. After choosing the name and location to save file the Uploading screen will regain focus; click
Close.

65 of 68

53. Again the Upload/Download All window will appear, click Close.

This section had described how to upload all the ports in the drive into one file. Also
available on the Actions menu is the option to select Upload and Save. Doing this will
upload and save the parameters for the selected port in the device tree.

Downloading Configuration to Drive from a PC


54. Change the value of a parameter that you can easily verify (e.g. P535 [Accel Time 1]).
55. From the Actions menu, select Upload/Download All.
56. On the Upload/Download All window choose Download.

57. Select Yes. To the resulting dialog window.

58. Select the same file you created in the section above and click the Open button.

66 of 68

59. Notice on the Select Sets To Download window that only the chosen option ports that were
selected to upload in the previous steps are available. Click Download.

60. The saved parameter file values will be downloaded. Close the Download Complete!
Acknowledgement.

61. Again the Upload/Download All window will appear, click Close.

62. Verify that the value of the parameter you changed a few steps back has returned to its original
value.

67 of 68