Академический Документы
Профессиональный Документы
Культура Документы
nx frequency converters
apfiff08
Advanced
Application manual
1.
Introduction ....................................................................................................................... 3
1.1
1.2
1.3
1.4
2.
3.
3.1
3.2
3.3
4.
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12
4.13
4.14
5.
5.1
5.2
6.
6.1
6.2
6.3
6.4
6.5
6.6
6.7
7.
General........................................................................................................................................ 3
Basic IO Support ......................................................................................................................... 3
Fast response ............................................................................................................................. 3
Basic Features ............................................................................................................................ 4
External brake control with additional limits (IDs 315, 316, 346 to 349, 352, 353)...............119
Closed loop parameters (IDs 612 to 621) ...............................................................................121
Parameters of motor thermal protection (IDs 704 to 708):...................................................121
Parameters of Stall protection (IDs 709 to 712): ...................................................................122
Parameters of Underload protection (IDs 713 to 716):..........................................................122
Fieldbus control parameters (IDs 850 to 859) .......................................................................122
Master/Follower function........................................................................................................124
Fault codes .................................................................................................................... 127
apfiff08 Advanced
vacon 3
Advanced Application
Software APFIFF08
1.
INTRODUCTION
1.1
General
While application version is less than 100, earlier version parameter files may not work same way in
new version. See updated parameter description from NCDrive when making commissioning.
1.2
Basic IO Support
Fast response
This application digital inputs and analogue inputs are handled in 1 ms time level.
- A type option boards.
- By using hardware bypassing filtering function to OPT-A1 option board
o See ID1084 Control Options
Support for Fast Profibus profile
- When fast mode is activated its not possible to use B-type boards.
- Only bypass mode can be used when fast Profibus mode is activated.
- Service data is not supported by fast profibus
4 vacon
1.4
apfiff08 Advanced
Basic Features
Additional functions:
The parameters of the Advance Application are explained in Chapter 5 of this manual. The
explanations are arranged according to the individual ID number of the parameter.
apfiff08 Advanced
2.
vacon 5
CONTROL I/O
Reference potentiometer, OPT-A1
Terminal
110 k
mA
Signal
Reference voltage output
Analogue input 1.
Range 0-10V, Ri = 200
Range 0-20 mA Ri = 250
I/O Ground
Analogue input 2.
Range 0-10V, Ri = 200
Range 0-20 mA Ri = 250
Control voltage output
Description
Voltage for potentiometer, etc.
Analogue input 1 frequency reference.
Input range selected by jumpers.
Default range: Voltage 0 10 V
Ground for reference and controls
Analogue input 2 frequency reference
Input range selected by jumpers.
Default range: Current 0 20 mA
Voltage for switches, etc. max 0.1 A
CMA
I/O ground
Start forward
Programmable G2.2.7
Start reverse
Programmable G2.2.7
Fault reset
Programmable G2.2.7
Common for DIN 1DIN 3
12
13
14
+24V
GND
DIN4
15
DIN5
Programmable G2.2.7
16
DIN6
Programmable G2.2.7
17
18
19
CMB
AOA1+
AOA1-
20
DOA1
Digital output
1
2
+10Vref
AI1+
3
4
5
AI1AI2+
AI2-
+24V
7
8
GND
DIN1
DIN2
10
DIN3
11
OPT-A2
220
VAC
21
22
23
RO1
RO1
RO1
Relay output 1
Programmable G2.3.3
24
25
26
RO2
RO2
RO2
Relay output 2
Programmable G2.3.3
Switching capacity
24 VCD / 8 A
250 VAC / 8 A
125 VDC / 0.4 A
Programmable
No function defined at default
Note: See Users Manual, chapter Control Connections, for hardware specification and configuration.
Note: See jumper selections below.
More information in Vacon NX User's
Manual, Chapter 6.2.2.2.
Jumper block X 3 :
CM A a nd CM B grounding
CMB connected to GN D
CMA connected to GN D
CMB isolated from GN D
CMA isolated from GN D
CMB and CMA
internally connected together,
isolated from GN D
= Factory default
6 vacon
2.1
apfiff08 Advanced
DIN#
DIN#
DIN#
DIN#
Preset Speed 1
Preset Speed 2
Preset Speed 3
AI#
AIA#
AIA#
AI#
DIN#
Internal frequency
reference
Motor
Potentiometer
DIN#
Reset button
Start/Stop buttons
Start forward
(programmable)
Start reverse (programmable)
Programmable
Start/Stop and
reverse logic
Start/Stop
Internal Start/Stop
Reverse
Internal reverse
DIN#
>1
(programmable)
NX12k103.fh8
apfiff08 Advanced
3.
vacon 7
The programming principle of the input and output signals in the Multipurpose Control Application
NXP as well as in the Pump and Fan Control Application (and partly in the other applications) is
different compared to the conventional method used in other Vacon NX applications.
In the conventional programming method, Function to Terminal Programming Method (FTT), you
have a fixed input or output that you define a certain function for. The applications mentioned above,
however, use the Terminal to Function Programming method (TTF) in which the programming process is carried out the other way round: Functions appear as parameters which the operator defines
a certain input/output for. See Warning on page 8.
3.1
Connecting a certain input or output with a certain function (parameter) is done by giving the
parameter an appropriate value. The value is formed of the Board slot on the Vacon NX control
board (see Vacon NX User's Manual, Chapter 6.2) and the respective signal number, see below.
READY
I/O term
AI Ref Faul/Warn
DigOUT:B.1
Function name
Slot
Terminal type
Terminal number
Example: You want to connect the digital output function Reference fault/warning (parameter
2.3.3.7) to the digital output DO1 on the basic board OPT-A1 (see Vacon NX User's Manual, Chapter
6.2).
First find the parameter 2.3.3.7 on the keypad. Press the Menu button right once to enter the edit
mode. On the value line, you will see the terminal type on the left (DigIN, DigOUT, An.IN, An.OUT)
and on the right, the present input/output the function is connected to (B.3, A.2 etc.), or if not
connected, a value (0.#).
When the value is blinking, hold down the Browser button up or down to find the desired board slot
and signal number. The program will scroll the board slots starting from 0 and proceeding from A
to E and the I/O selection from 1 to 10.
Once you have set the desired value, press the Enter button once to confirm the change.
READY
I/O term
AI Ref Faul/Warn
DigOUT:0.0
READY
I/Oterm
AI Ref Faul/Warn
DigOUT:0.0
READY
I/Oterm
AI Ref Faul/Warn
DigOUT:B.1
enter
8 vacon
3.2
apfiff08 Advanced
If you use the NCDrive Programming Tool for parametrizing you will have to establish the connection between the function and input/output in the same way as with the control panel. Just pick the
address code from the drop-down menu in the Value column (see the Figure below).
Figure 3-1. Screenshot of NCDrive programming tool; Entering the address code
!
WARNING
Note: The inputs, unlike the outputs, cannot be changed in RUN state.
apfiff08 Advanced
3.3
vacon 9
All unused inputs and outputs must be given the board slot value 0 and the value 1 also for the terminal number. The value 0.1 is also the default value for most of the functions. However, if you want
to use the values of a digital input signal for e.g. testing purposes only, you can set the board slot
value to 0 and the terminal number to any number between 210 to place the input to a TRUE state.
In other words, the value 1 corresponds to 'open contact' and values 2 to 10 to 'closed contact'.
In case of analogue inputs, giving the value 1 for the terminal number corresponds to 0% signal
level, value 2 corresponds to 20%, value 3 to 30% and so on. Giving value 10 for the terminal number
corresponds to 100% signal level.
10 vacon
4.
apfiff08 Advanced
On the next pages you will find the lists of parameters within the respective parameter groups. The
parameter descriptions are given on pages 43 to 118.
Column explanations:
Code
Parameter
Min
Max
Unit
Default
Cust
ID
_____
_____
_____
4.1
=
=
=
=
=
=
=
=
=
Location indication on the keypad; Shows the operator the present param. number
Name of parameter
Minimum value of parameter
Maximum value of parameter
Unit of parameter value; Given if available
Value preset by factory
Customers own setting
ID number of the parameter
On parameter code: Parameter value can only be changed after the FC has been
stopped.
= Apply the Terminal to Function method (TTF) to these parameters (see chapter 3)
= Monitoring value is possible to control from fieldbus with ID number
The monitoring values are the actual values of parameters and signals as well as statuses and
measurements. See the product's User's Manual for more information.
Code
V1.1
Parameter
Output frequency
Unit
Hz
ID
1
V1.2
Frequency reference
Hz
25
V1.3
V1.4
V1.5
V1.6
V1.7
V1.8
V1.9
V1.10
V1.11
V1.12
V1.13
V1.14
V1.15
V1.16
V1.17
V1.18
V1.19
V1.20
Motor speed
Motor current
Motor torque
Motor power
Motor voltage
DC link voltage
Unit temperature
Motor temperature
Analogue input 1
Analogue input 2
Analogue input 3
Analogue input 4
Analogue output 1
Analogue output 2
Analogue output 3
DIN1, DIN2, DIN3
DIN4, DIN5, DIN6
Torque reference
rpm
A
%
%
V
V
C
2
3
4
5
6
7
8
9
13
14
27
28
26
50
51
15
16
18
V1.21
PT-100 temperature
42
G1.22
Multimonitoring items
%
%
%
%
%
%
%
%
Description
Output frequency to motor
Frequency reference to motor
control
Motor speed in rpm
Calculated shaft torque
Motor shaft power
Heatsink temperature
Calculated motor temperature
AI1, unfiltered
AI2, unfiltered
AI3, unfiltered
AI4, unfiltered
AO1
AO2
AO3
Digital input statuses
Digital input statuses
Highest temperature of used
PT100 inputs
Displays three selectable
monitoring values
apfiff08 Advanced
4.1.1
vacon 11
Parameter
Monitor 2
Current
Torque
DC Voltage
Status Word
Encoder 1 Frequency
Shaft Rounds
Shaft Angle
Measured temperature 1
Measured temperature 2
Measured temperature 3
Encoder 2 Frequency
Absolute encoder position
Absolute encod. rotations
Identification run status
Pole pair number
Final Frequency
Reference in Closed loop
Step Response
Unit
ID
A
%
V
1113
1125
44
43
1124
1170
1169
50
51
52
53
54
55
49
58
Hz
r
Deg
C
C
C
Hz
Hz
1131
Hz
1132
Description
Unfiltered motor current
Unfiltered motor torque
Unfiltered DC link voltage
See ID 1090
See ID 1090
4.1.2
Code
G1.24
V1.24.1
V1.24.2
V1.24.3
V1.24.4
Parameter
FieldBus
FB torque reference
FB limit scaling
FB adjust reference
FB analogue output
V1.24.5
V1.24.6
Motor Current to FB
V1.24.7
V1.24.8
V1.24.9
V1.24.10
V1.24.11
V1.24.12
V1.24.13
DIN StatusWord 1
DIN StatusWord 2
MC Status Word
Profibus Status Word
Fault Word 1
Fault Word 2
FB Control Word
Unit
ID
%
%
%
%
1140
46
47
48
Description
Default control of FB PD 1
Default control of FB PD 2
Default control of FB PD 3
Default control of FB PD 4
37
A
45
56
57
67
68
1172
1173
1160
12 vacon
4.1.3
apfiff08 Advanced
TRUE
b0
b1
b2
b3
b4
b5
b6
b7
Direction Forward
EM Stop not active
Run Disabled
No Warning
Direction Reverse
EM Stop Active
Run Enable
Warning
b8
b9
b10
b11
No DC brake
DC Brake is active
No Run Request
No Limit Controls Active
External Brake Control OFF
Run Request
Limit control Active
External Brake Control ON
b12
b13
b14
b15
4.1.4
TRUE
b0
b1
b2
b3
Ready
Running
Counterclockwise
Fault
b4
b5
b6
b7
No Warning
Warning
At reference speed
At Zero Speed
Flux Ready
b8
b9
b10
b11
b12
b13
b14
b15
Encoder Direction
No DC brake
apfiff08 Advanced
4.1.5
vacon 13
Comment
b0
b1
b2
b3
b4
b5
b6
b7
Earth Fault
Motor Under Load
Drive over temperature
Over Temperature
F3
F17
F14
F16, F56, F29
b8
Input Phase
b9
b10
Device Changed
b11
Keypad or PCControl
F10
F42
(Not implemented)
F37, F38, F39, F40, F44, F45
(Not implemented)
F52
b12
b13
b14
b15
FielBus
SystemBus
Slot
4 mA
F53
F59
F54
F50
4.1.6
Comment
b0
b1
b2
b3
Output phase
Charge Switch
Encoder
Inverter
b4
b5
b6
b7
EEPROM
External
Brake Chopper
b8
b9
b10
b11
Watch Dog
IGBT
Brake
Fan Cooling
b12
b13
b14
b15
Application
Control fault
Main Switch Open
14 vacon
4.1.7
b0
b1
b2
4.1.8
apfiff08 Advanced
DIN1/DIN2/DIN3 status
DIN3
DIN2
DIN1
DIN4/DIN5/DIN6 status
DIN6
DIN5
DIN4
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
b15
DIN StatusWord 1
DIN: A.1
DIN: A.2
DIN: A.3
DIN: A.4
DIN: A.5
DIN: A.6
DIN: B.1
DIN: B.2
DIN: B.3
DIN: B.4
DIN: B.5
DIN: B.6
DIN: C.1
DIN: C.2
DIN: C.3
DIN: C.4
DIN StatusWord 2
DIN: C.5
DIN: C.6
DIN: D.1
DIN: D.2
DIN: D.3
DIN: D.4
DIN: D.5
DIN: D.6
DIN: E.1
DIN: E.2
DIN: E.3
DIN: E.4
DIN: E.5
DIN: E.6
apfiff08 Advanced
4.1.9
vacon 15
*.trn, *.par and Print Service info to file (*.txt) with situation description.
16 vacon
4.2
apfiff08 Advanced
Code
P2.1.1
Parameter
Min frequency
Min
0,00
Max
P2.1.2
Unit
Hz
Default
0,00
Cust
ID
101
Note
NOTE: If fmax > than the
motor synchronous speed,
check suitability for motor
and drive system
0 Hz to Max frequency
Max frequency to 0 Hz
Limit will lower frequency
Check the rating plate of
the motor. Note also used
connegtion Delta/Star
Check the rating plate of
the motor
The default applies for a 4pole motor and a nominal
size frequency converter.
Check the rating plate of
the motor.
Check the rating plate of
the motor
0=No action
1=Identification w/o run
2=Identification with run
3=Encoder ID Run
4=Ident All
0=AI1
1=AI2
2=AI1+AI2
3=AI1-AI2
4=AI2-AI1
5=AI1xAI2
6=AI1 Joystick
7=AI2 Joystick
8=Keypad
9=Fieldbus
10=Motor potentiometer
11=AI1, AI2 minimum
12=AI1, AI2 maximum
13=Max frequency
14=AI1/AI2 selection
15=Encoder 1
16=Encoder 2
0=AI1
1=AI2
2=AI1+AI2
3=AI1-AI2
4=AI2-AI1
5=AI1xAI2
6=AI1 Joystick
7=AI2 Joystick
8=Keypad
9=Fieldbus
P2.1.2
Max frequency
P2.1.1
320,00
Hz
50,00
102
P2.1.3
P2.1.4
P2.1.5
Acceleration time 1
Deceleration time 1
Current limit
0,10
0,10
0,1 x IH
327,00
327,00
2 x IH
s
s
A
103
104
107
P2.1.6
Nominal voltage of
the motor
180
690
3,00
3,00
IL
NX2: 230V
NX5: 400V
NX6: 690V
P2.1.7
Nominal frequency
of the motor
8,00
320,00
Hz
50,00
111
P2.1.8
Nominal speed of
the motor
24
20 000
rpm
1440
112
P2.1.9
Nominal current of
the motor
0,1 x IH
2 x IH
IH
113
P2.1.10
Motor cos
0,30
1,00
0,85
120
P2.1.11
Identification
631
P2.1.12
I/O Reference 1
16
117
P2.1.13
Keypad control
reference
121
122
See P2.1.12
0,00
320,00
Hz
5,00
124
See ID413
0,00
0,00
320,00
320,00
Hz
Hz
10,00
15,00
105
106
P2.1.14
P2.1.15
P2.1.16
P2.1.17
Fieldbus control
reference
Jogging speed
reference
Preset speed 1
Preset speed 2
110
apfiff08 Advanced
P2.1.18
P2.1.19
P2.1.20
P2.1.21
P2.1.22
Preset speed 3
Preset speed 4
Preset speed 5
Preset speed 6
Preset speed 7
vacon 17
0,00
0,00
0,00
0,00
0,00
320,00
320,00
320,00
320,00
320,00
Hz
Hz
Hz
Hz
Hz
20,00
25,00
30,00
40,00
50,00
126
127
128
129
130
4.3
Input signals
4.3.1
Code
Min
Max
P2.2.1.1
Start/Stop logic
selection
P2.2.1.2
Motor potentiometer
ramp time
0,10
200,00
P2.2.1.3
Motor potentiometer
frequency reference
memory reset
P2.2.1.4
Adjust input
P2.2.1.5
P2.2.1.6
P2.2.1.7
Adjust minimum
Adjust maximum
I/O Reference 2
Unit
Default
Hz/s
Cust
ID
300
1,00
331
367
493
0,0
0,0
0
100,0
100,0
16
0,0
0,0
1
494
495
131
%
%
Note
0
1
2
3
4
5
6
Start
signal 1
Start
signal 2
Start fwd
Start/Stop
Start/Stop
Start pulse
Start
Start fwd*
Start*/Stop
Start*/Stop
Start rvs
Reverse
Run enable
Stop pulse
Mot.Pot UP
Start rvs*
Reverse
Run Enable
7
Ramp speed for motor
potentiometer reference
0=No reset
1=Reset if stopped or
powered down
2=Reset if powered down
0=Not used
1=AI1
2=AI2
3=AI3
4=AI4
5=FB Adjust Reference
Ajust limit to decrease ref.
Adjust limit to increase ref.
See ID117 & ID422
18 vacon
4.3.2
apfiff08 Advanced
Code
P2.2.2.1
P2.2.2.2
Parameter
AI1 signal selection
AI1 filter time
Min
0.1
0,000
Max
E.10
32,000
P2.2.2.3
-160,00
160,00
-160,00
Unit
s
Default
A.1
0,000
Cust
ID
377
324
320
0,00
321
160,00
100,00
322
0,00
320,00
Hz
0,00
303
0,00
320,00
Hz
0,00
304
0,00
20,00
0,00
384
0,00
100,00
0,00
385
P2.2.2.9
AI1 custom
minimum setting
AI1 custom
maximum setting
AI1 reference
scaling, minimum
value
AI1 reference
scaling, maximum
value
AI1 joystick
hysteresis
AI1 sleep limit
P2.2.2.10
0,00
320,00
0,00
386
P2.2.2.11
-100,00
100,00
0,00
165
P2.2.2.4
P2.2.2.5
P2.2.2.6
P2.2.2.7
P2.2.2.8
4.3.3
Code
P2.2.3.1
P2.2.3.2
Parameter
AI2 signal selection
AI2 filter time
Min
0.1
0,000
Max
E.10
32,000
P2.2.3.3
-160,00
160,00
-160,00
Unit
s
Default
A.2
0,000
Cust
ID
388
329
325
20,00
326
160,00
100,00
327
0,00
320,00
Hz
0,00
393
0,00
320,00
Hz
0,00
394
0,00
20,00
0,00
395
0,00
100,00
0,00
396
P2.2.3.9
AI2 custom
minimum setting
AI2 custom
maximum setting
AI2 reference
scaling, minimum
value
AI2 reference
scaling, maximum
value
AI2 joystick
hysteresis
AI2 sleep limit
P2.2.3.10
0,00
320,00
0,00
397
P2.2.3.11
-100,00
100,00
0,00
166
P2.2.3.4
P2.2.3.5
P2.2.3.6
P2.2.3.7
P2.2.3.8
Note
Slot . Board input No.
0=No filtering
0=0100%*
1=20100%* (4 mA Fault)
2= -10V+10V*
3= Custom range*
Custom Range:
Minimum input
Custom Range:
Minimum input
Selects the frequency that
corresponds to the min.
reference signal
Selects the frequency that
corresponds to the max.
reference signal
Dead Zone for joystick
input
Drive goes to stop if input
is below this limit for set
time.
Press enter for 1s to set
offset. Reset to set 0,00
Note
Slot . Board input No.
0=No filtering
0=0100%*
1=20100%* (4 mA Fault)
2= -10V+10V*
3= Custom range*
Custom Range:
Minimum input
Custom Range:
Minimum input
Selects the frequency that
corresponds to the min.
reference signal
Selects the frequency that
corresponds to the max.
reference signal
Dead Zone for joystick
input
Drive goes to stop if input
is below this limit for this
time.
Press enter for 1s to set
offset. Reset to set 0,00
apfiff08 Advanced
4.3.4
vacon 19
Code
Parameter
Min
Max
P2.2.4.1
0.1
E.10
P2.2.4.2
0,000
32,000
-160,00
P2.2.4.3
P2.2.4.4
P2.2.4.5
Unit
Default
Cust
ID
0.1
141
0,000
142
160,00
20,00
144
-160,00
160,00
100,00
145
151
P2.2.4.6
32000
1037
P2.2.4.7
32000
1038
10000
1509
P2.2.4.8
AI3 Controlled ID
Note
Slot . Board input No.
If 0.1 ID61 can be
controlled from FB
0=No filtering
Custom range always
active. See ID326
Custom range always
active. See ID327
0=Not inverted
1=Inverted
Selects the value that
corresponds to the min.
reference signal
Selects the value that
corresponds to the max.
reference signal
Select parameter that you
want to control by ID
number.
4.3.5
Code
Parameter
Min
Max
P2.2.5.1
0.1
E.10
0,000
32,000
-160,00
P2.2.5.2
Unit
Default
Cust
ID
0.1
152
0,000
153
160,00
20,00
155
-160,00
160,00
100,00
156
P2.2.5.5
162
P2.2.5.6
-32000
-32000
1039
P2.2.5.7
-32000
32000
1040
P2.2.5.8
AI4 Controlled ID
10000
1510
Note
Slot . Board input No.
If 0.1 ID61 can be
controlled from FB
0=No filtering
Custom range always
active. See ID326
e.g. 18 mA = 90 %
0=Not inverted
1=Inverted
Selects the value that
corresponds to the min.
reference signal
Selects the value that
corresponds to the max.
reference signal
Select parameter that
you want to control by
ID number.
20 vacon
4.3.6
apfiff08 Advanced
Code
Parameter
Min
Max
P2.2.6.1
Scaling of current
limit
399
P2.2.6.2
Scaling of DC-braking
current
400
P2.2.6.3
Reducing of acc./dec.
times
401
402
485
1087
179
1088
P2.2.6.4
P2.2.6.5
P2.2.6.6
P2.2.6.7
P2.2.6.8
Scaling of torque
supervision limit
Scaling Motoring
torque limit
Scaling of generator
torque limit
Scaling Motoring power
limit
Scaling of generator
power limit
Unit
Default
Cust
ID
Note
Scaling from 0 to ID107
0=Not used
1=AI1
2=AI2
3=AI3
4=AI4
5=FB Limit Scaling ID46
As parameter P2.2.6.1
Scaling from 0 to ID507
As parameter P2.2.6.1
Scales active ramp from
100 % to 10 %.
As parameter P2.2.6.1
Scaling from 0 to ID348
As parameter P2.2.6.1
Scaling from 0 to ID1287
As parameter P2.2.6.1
Scaling from 0 to ID1288
As parameter P2.2.6.1
Scaling from 0 to ID1289
As parameter P2.2.6.1
Scaling from 0 to ID1290
apfiff08 Advanced
4.3.7
vacon 21
Code
Parameter
Min
Default
P2.2.7.1
P2.2.7.2
P2.2.7.3
Start signal 1
Start signal 2
Run enable
0.1
0.1
0.1
A.1
A.2
0.2
403
404
407
P2.2.7.4
Reverse
0.1
0.1
412
P2.2.7.5
P2.2.7.6
P2.2.7.7
0.1
0.1
0.1
0.1
0.1
0.1
419
420
421
0.1
0.1
417
0.1
0.1
418
P2.2.7.10
P2.2.7.11
P2.2.7.12
Preset speed 1
Preset speed 2
Preset speed 3
Motor potentiometer
reference DOWN
Motor potentiometer
reference UP
Fault reset
External fault (close)
External fault (open)
0.1
0.1
0.1
A.3
0.1
0.2
414
405
406
P2.2.7.13
0.1
0.1
408
P2.2.7.14
P2.2.7.15
Acc/Dec prohibit
DC braking
0.1
0.1
0.1
0.1
415
416
P2.2.7.16
Jogging speed
0.1
0.1
413
P2.2.7.17
AI1/AI2 selection
0.1
0.1
422
P2.2.7.18
0.1
0.1
409
P2.2.7.19
0.1
0.1
410
P2.2.7.20
0.1
0.1
411
P2.2.7.21
0.1
0.1
496
P2.2.7.22
0.1
0.1
164
P2.2.7.23
0.1
0.2
750
0.1
0.2
1210
P2.2.7.25
P2.2.7.26
Cooling Monitor
External brake
acknowledge
Prevention of startup
Enable inching
0.1
0.1
0.2
0.1
1420
532
P2.2.7.27
Inching reference 1
0.1
0.1
530
P2.2.7.28
Inching reference 2
0.1
0.1
531
P2.2.7.29
0.1
0.1
1090
P2.2.7.30
P2.2.7.31
Emergency stop
Master Follower mode 2
Input switch
acknowledgement
0.1
0.1
0.2
0.1
1213
1092
0.1
0.2
1209
P2.2.7.8
P2.2.7.9
P2.2.7.24
P2.2.7.32
ID
Note
Forward, See ID300
Reverse. See ID300
Motor start enabled (cc)
Direction forward (oc)
Direction reverse (cc)
See preset speeds in Basic
Parameters (G2.1)
22 vacon
4.3.8
apfiff08 Advanced
Code
Parameter
Min
Max
P2.2.8.1
ID Control DIN
0.1
E.10
P2.2.8.2
Controlled ID
10000
P2.2.8.3
P2.2.8.4
False value
True value
-32000
-32000
32000
32000
Unit
ID
Default
Cust
ID
0.1
1570
1571
0
0
1572
1573
Note
Slot . Board input No.
If 0.1 ID61 can be
controlled from FB
Select ID that is
controlled by digital input
Value when DI is low
Value when DI is high
apfiff08 Advanced
4.4
vacon 23
Output signals
4.4.1
Code
P2.3.1.1
P2.3.1.2
P2.3.1.3
P2.3.1.4
Digital Output 1
function
Digital output 1 on
delay
Digital output 1 off
delay
Min
Max
Unit
Default
Cust
ID
Note
Possibility to invert with
P2.4.23 INV commands
0=Not used
1=Ready
2=Run
3=Fault
4=Fault inverted
5=FC overheat warning
6=Ext. fault or warning
7=Ref. fault or warning
8=Warning
9=Reverse
10=Jogging spd selected
11=At speed
12=Mot. regulator active
13=Freq. limit 1 superv.
14=Freq. limit 2 superv.
15=Torque limit superv.
16=Ref. limit supervision
17=External brake control
18=I/O control place act.
19=FC temp. limit superv.
20=Reference inverted
21=Ext. brake control
inverted
22=Therm. fault or warn.
23=Analogue supervision
24=Fieldbus input data 1
25=Fieldbus input data 2
26=Fieldbus input data 3
0.1
E.10
0.1
486
26
312
0,00
320,00
0,00
487
0,00
320,00
0.00
488
ID
Note
Possibility to invert with
P2.4.23 INV commands
4.4.2
Code
P2.3.2.1
P2.3.2.2
P2.3.2.3
P2.3.2.4
Min
Max
Unit
Default
Cust
0.1
E.10
0.1
489
26
490
See P2.3.1.2
0,00
320,00
0,00
491
0,00
320,00
0,00
492
24 vacon
4.4.3
apfiff08 Advanced
Min
0.1
0.1
0.1
0.1
0.1
0.1
0.1
Default
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
439
P2.3.3.9
Parameter
Ready
Run
Fault
Inverted fault
Warning
External fault
Reference fault/warning
Overtemperature
warning
Reverse
0.1
0.1
440
P2.3.3.10
Unrequested direction
0.1
0.1
441
P2.3.3.11
At speed
0.1
0.1
442
P2.3.3.12
Jogging speed
0.1
0.1
443
P2.3.3.13
P2.3.3.14
0.1
0.1
0.1
0.1
444
445
0.1
0.1
446
0.1
0.1
447
See ID315
0.1
0.1
448
See ID346
0.1
0.1
449
See ID350
0.1
0.1
450
P2.3.3.20
0.1
0.1
451
P2.3.3.21
0.1
0.1
452
0.1
0.1
463
0.1
0.1
454
0.1
0.1
456
P2.3.3.8
P2.3.3.15
P2.3.3.16
P2.3.3.17
P2.3.3.18
P2.3.3.19
Cust
ID
432
433
434
435
436
437
438
P2.3.3.24
Analogue input
supervision limit
Motor regulator
activation
Fieldbus digital input 1
P2.3.3.25
FB Dig 1 Parameter
ID0
891
P2.3.3.26
0.1
0.1
456
P2.3.3.27
FB Dig 2 Parameter
ID0
ID0
892
P2.3.3.28
0.1
0.1
457
P2.3.3.29
FB Dig 3 Parameter
ID0
ID0
893
P2.3.3.30
0.1
0.1
169
P2.3.3.31
FB Dig 4 Parameter
ID0
ID0
894
P2.3.3.32
0.1
0.1
170
P2.3.3.33
FB Dig 5 Parameter
ID0
ID0
895
P2.3.3.34
DC Ready Pulse
0.1
0.1
1218
P2.3.3.22
P2.3.3.23
Note
Ready to Run
Running
Drive in fault state
Drive not in fault state
Warning active
External fault active
4 mA fault active
Drive over temperature
active
Output frequency < 0 Hz
Reference <> Output
freqyency
Reference = Output
frequency
Jgging or preset speed
command active
IO control active
Drive temperature
supervision. See ID354
See ID348
Thermistor fault or
warning
See ID356
One of limit controller is
active
FB CW B11
Select parameter to
control
FB CW B12
Select parameter to
control
FB CW B13
Select parameter to
control
FB CW B14
Select parameter to
control
FB CW B15
Select parameter to
control
For external DC charger
apfiff08 Advanced
!
WARNING
vacon 25
26 vacon
4.4.4
apfiff08 Advanced
Code
Parameter
Min
Max
P2.3.4.1
Output frequency
limit 1 supervision
P2.3.4.2
Output frequency
limit 1;
Supervised value
0,00
320,00
P2.3.4.3
Output frequency
limit 2 supervision
P2.3.4.4
Output frequency
limit 2;
Supervised value
0,00
320,00
P2.3.4.5
Torque limit
supervision
P2.3.4.6
Torque limit
supervision value
-300,0
300,0
P2.3.4.7
Reference limit
supervision
0,0
100,0
0,00
P2.3.4.8
P2.3.4.9
P2.3.4.10
Reference limit
supervision value
External
brake-off delay
External
brake-on delay
315
0,00
316
346
0,00
347
350
0,0
351
100,00
0,10
352
0,00
100,00
2,90
353
354
40
355
P2.3.4.12
FC temperature
supervised value
10
100
P2.3.4.16
349
P2.3.4.15
ID
100,0
Analogue
supervision signal
Analogue supervision low limit
Analogue supervision high limit
Brake On/Off
Current Limit
Hz
Cust
348
FC temperature
supervision
P2.3.4.14
Hz
Default
P2.3.4.11
P2.3.4.13
Unit
Note
0=No limit
1=Low limit supervision
2=High limit supervision
3=Brake-on control
0=No limit
1=Low limit supervision
2=High limit supervision
3=Brake-off control
4=Brake on/off-control
0=Not used
1=Low limit supervision
2=High limit supervision
3=Brake-off control
For brake control absolute
values are used
0=Not used
1=Low limit
2=High limit
356
0=Not used
1=AI1
2=AI2
3=AI3
4=AI4
10,00
357
100,00
90,00
358
2 x IH
0,00
1085
100,00
0
0,00
apfiff08 Advanced
4.4.5
Code
P2.3.5.1
P2.3.5.2
P2.3.5.3
P2.3.5.4
P2.3.5.5
P2.3.5.6
P2.3.5.7
vacon 27
Analogue output 1
function
Analogue output 1
filter time
Analogue output 1
inversion
Analogue output 1
minimum
Analogue output 1
scale
Analogue output 1
offset
Min
Max
Unit
0.1
E.10
A.1
464
15
307
0,00
100,00
0,20
308
309
310
10
1000
100
311
-100,00
100,00
0,00
375
Default
Cust
ID
Note
TTF programming
See chapter 3.1 and 3.2
0=Not used (4 mA / 2 V)
1=Output freq. (0fmax)
2=Freq. reference (0fmax)
3=Motor speed (0Motor
nominal speed)
4=Motor current (0InMotor)
5=Motor torque (0TnMotor)
6=Motor power (0PnMotor)
7=Motor voltage (0-UnMotor)
8=DC-link volt (01000V)
9=AI1
10=AI2
11=Output freq. (fmin - fmax)
12=-2xTorque+2xTorque
13=-2xPower+2xPower
14=PT100
temperature
15=FB Analog Output
0=No filtering
0=Not inverted
1=Inverted
0=0 mA (0 %)
1=4 mA (20 %)
4.4.6
Code
P2.3.6.1
P2.3.6.2
P2.3.6.3
P2.3.6.4
P2.3.6.5
P2.3.6.6
P2.3.6.7
Min
Max
Unit
0.1
E.10
0.1
471
15
472
See P2.3.5.2
0,00
100,00
0,20
473
0=No filtering
474
475
10
1000
100
476
-100,00
100,00
0,00
477
Default
Cust
ID
Note
TTF programming
See chapter 3.1 and 3.2
0=Not inverted
1=Inverted
0=0 mA (0 %)
1=4 mA (20 %)
28 vacon
4.4.7
Code
P2.3.7.1
P2.3.7.2
P2.3.7.3
P2.3.7.4
P2.3.7.5
P2.3.7.6
P2.3.7.7
apfiff08 Advanced
Min
Max
Unit
0.1
E.10
0.1
478
14
479
See P2.3.5.2
0,00
100,00
0,20
480
0=No filtering
481
482
10
1000
100
483
-100,00
100,00
0,00
484
Default
Cust
ID
Note
TTF programming
See chapter 3.1 and 3.2
0=Not inverted
1=Inverted
0=0 mA (0 %)
1=4 mA (20 %)
4.4.8
Code
Parameter
Min
Max
P2.3.8.1
Brake Logic
P2.3.8.2
BrakeMechDelay
0,00
320,00
P2.3.8.3
0,00
P2.3.8.4
P2.3.8.5
Unit
Default
Cust
ID
1534
0,00
1544
320,00
Hz
1,50
1535
0,00
320,00
Hz
0,00
1555
Brake ON FreqLim +
0,00
320,00
Hz
1,00
1539
P2.3.8.6
Brake ON FreqLim -
0,00
320,00
Hz
1,50
1540
P2.3.8.7
0,00
320,00
0,00
1085
Note
0= MultiPurpose
1= Smooth
Time that is required to
open the brake
Opening limit and
maximum reference
limit when brake is
closed.
Opening limit and
maximum reference
limit when brake is
closed.
Close frequency from
positive direction
Close frequency from
negative direction
Brake is closed
immediately id current
goes below this value.
apfiff08 Advanced
4.5
vacon 29
Code
Parameter
Min
Max
Unit
Default
Cust
ID
P2.4.1
Ramp 1 shape
100
500
P2.4.2
Ramp 2 shape
100
501
P2.4.3
P2.4.4
Acceleration time 2
Deceleration time 2
0,10
0,10
327,00
327,00
s
s
10,00
10,00
502
503
Note
0=Linear
>0=S-curve ramp time
0=Linear
>0=S-curve ramp time
0=Disabled
1=Used when running
2=External brake chopper
3=Used when stopped/running
4=Used when running (no
testing)
0=Ramp
1=Flying start
2=Conditional flying start
0=Coasting
1=Ramp
2=Ramp+Run enable coast
3=Coast+Run enable ramp
P2.4.5
Brake chopper
504
P2.4.6
Start function
505
P2.4.7
Stop function
506
P2.4.8
DC braking current
DC braking time
at stop
Frequency to start
DC braking during
ramp stop
DC braking time
at start
IL
0,7 x IH
507
0,00
600,00
0,00
508
0,10
10,00
Hz
1,50
515
0,00
600,00
0,00
516
520
0=Off
1=On
P2.4.9
P2.4.10
P2.4.11
P2.4.12
Flux brake
P2.4.13
P2.4.14
0
0
IL
65535
A
s
0
Varies
519
1424
IL
0,1 x IH
1080
-320,00
-320,00
0,10
320,00
320,00
320,00
Hz
Hz
s
2,00
-2,00
1,00
1239
1240
1257
1262
1205
Varies
1267
1276
65536
1084
1091
0,50
0
0
0
1283
1560
1561
1563
P2.4.15
P2.4.16
P2.4.17
P2.4.18
P2.4.19
Overvolt. controller
reference selector
P2.4.22
Brake chopper
operation level
Emergency stop
mode
Control options
P2.4.23
Inversion control
65526
P2.4.24
P2.4.25
P2.4.26
P2.4.27
0,00
0
0
0
320,00
65535
65535
65535
P2.4.20
P2.4.21
Hz
0=Coasting
1=Ramp
b0=Delayed DO1
b1=Delayed DO2
30 vacon
4.6
apfiff08 Advanced
Code
P2.5.1
P2.5.2
P2.5.7
Parameter
Prohibit frequency
range 1 low limit
Prohibit frequency
range 1 high limit
Prohibit acc./dec.
ramp
Min
Max
Unit
Default
Cust
ID
Note
-1,00
320,00
Hz
0,00
509
0=Not used
0,00
320,00
Hz
0,00
510
0=Not used
0,1
10,0
1,0
518
4.7
Code
Parameter
Min
Max
P2.6.1
Motor control
mode
Unit
Default
Cust
ID
600
Note
0=Frequency control
1=Speed control
2=Torque control
3=Closed loop speed ctrl
4=Closed loop torque ctrl
apfiff08 Advanced
4.7.1
vacon 31
Code
Parameter
Min
Max
P2.6.2.1
U/f optimisation
109
P2.6.2.2
108
P2.6.2.3
P2.6.2.4
P2.6.2.5
P2.6.2.6
P2.6.2.7
P2.6.2.8
Unit
Default
Cust
ID
Field weakening
point
Voltage at field
weakening point
U/f curve midpoint
frequency
8,00
320,00
Hz
50,00
602
10,00
200,00
100,00
603
0,00
P2.6.4
Hz
50,00
604
0,00
100,00
100,00
605
n% x Unmot
Parameter max. value =
P2.6.2.4
0,00
40,00
0,00
606
n% x Unmot
1,0
Varies
kHz
Varies
601
Output voltage at
zero frequency
Switching
frequency
P2.6.2.9
Overvoltage
controller
607
P2.6.2.10
Undervoltage
controller
608
521
32767
3000
637
32767
300
638
P2.6.2.11
P2.6.2.12
P2.6.2.13
P2.6.2.14
P2.6.2.15
P2.6.2.16
P2.6.2.17
P2.6.2.18
P2.6.2.19
P2.6.2.20
P2.6.2.21
P2.6.2.22
P2.6.2.23
Note
0=Not used
1=Automatic torque boost
0=Linear
1=Squared
2=Programmable
3=Linear with flux optim.
Motor control
0
mode 2
Speed controller
0
P gain (open loop)
Speed controller
0
I gain (open loop)
Negative frequency
-320,00
limit
Positive frequency
-320,00
limit
Generator torque
0,0
limit
Motoring torque
0,0
limit
Load drooping
0,00
Load Drooping
0
Time
TorqueStabGain
0
TorqueStabDamp
0
TorqueStabGain
0
FWP
Over modulation
50
limit
n% x Unmot
320,00
Hz
-320,00
1286
320,00
Hz
320,00
1285
300,0
300,0
1288
300,0
300,0
1287
100,00
0,00
620
32000
ms
656
1000
1000
100
900
1412
1413
1000
50
1414
105
1515
120
32 vacon
4.7.2
Code
P2.6.3.1
P2.6.3.2
P2.6.3.3
P2.6.3.5
P2.6.3.6
P2.6.3.7
P2.6.3.8
P2.6.3.9
P2.6.4310
P2.6.3.11
P2.6.3.12
P2.6.3.13
P2.6.3.15
P2.6.3.17
P2.6.3.19
P2.6.3.20
P2.6.3.21
P2.6.3.22
P2.6.3.23
P2.6.3.24
P2.6.3.25
P2.6.3.26
P2.6.3.27
P2.6.3.28
P2.6.3.29
P2.6.3.30
P2.6.3.31
P2.6.3.32
P2.6.3.33
P2.6.3.34
P2.6.3.35
apfiff08 Advanced
Min
Max
Unit
Default
0,00
2 x IH
Varies
612
1000
30
613
-3200,0
32000
ms
100
614
0,00
300,00
0,00
626
500
100
619
IL
0,00
627
0,000
60,000
0,000
628
32000
ms
100
615
32000
ms
100
616
300,0
300,0
300,0
Cust
ID
621
0,0
633
300,0
0,0
634
0,1
100,0
ms
0,1
618
0,00
100,00
40,00
617
0,0
300,0
300,0
1290
0,0
300,0
300,0
1289
0,0
300,0
300,0
645
0,0
300,0
300,0
646
-1
0,0
0,00
0,00
0
0
32000
150,0
320,00
320,00
1000
1000
s
%
Hz
Hz
%
%
0
100,0
0,00
0,00
100
100
1402
1401
1301
1300
1299
1298
400,0
0,0
1296
1000
100
1295
0
0,0
1000
500,0
ms
%
0
100,0
1297
1250
1000
ms
1311
200
100
655
60,000
Varies
672
Note
0=Not used
1=Torque memory
2=Torque reference
3=Start-up torque fwd/rev
-1=Always
apfiff08 Advanced
4.7.3
vacon 33
Code
Parameter
Min
Max
Unit
Default
Cust
ID
P2.6.4.1
Motor type
650
P2.6.4.2
Flux Current Kp
32000
5000
651
P2.6.4.3
Flux Current Ti
1000
25
652
P2.6.4.4
65565
649
P2.6.4.5
EnableRsIdentifi
654
P2.6.4.6
Modulator Nomal
1516
P2.6.4.7.
Modulator PMSM
with incremental
1517
Note
0=Induction Motor
1=PMS Motor
0=No
1=Yes
0=ASIC
1=Software 1
2=Software 2
3=Software 3
0=ASIC
1=Software 1
2=Software 2
3=Software 3
4.7.4
Code
P2.6.5.1
P2.6.5.2
Min
Max
Unit
Default
Cust
ID
0,0
360,0
0,0
1518
1000
100
1519
Note
34 vacon
4.7.5
apfiff08 Advanced
Code
P2.6.6.1
P2.6.6.2
P2.6.6.3
P2.6.6.4
P2.6.6.5
P2.6.6.6
P2.6.6.7
P2.6.6.8
P2.6.6.9
P2.6.10
P2.6.6.11
P2.6.6.12
P2.6.6.13
P2.6.6.14
P2.6.6.15
Parameter
Flux 10 %
Flux 20 %
Flux 30 %
Flux 40 %
Flux 50 %
Flux 60 %
Flux 70 %
Flux 80 %
Flux 90 %
Flux 100 %
Flux 110 %
Flux 120 %
Flux 130 %
Flux 140 %
Flux 150 %
Min
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Max
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
P2.6.6.16
Rs voltage drop
30000
Varies
662
30000
Varies
664
30000
Varies
665
30000
Varies
667
0,00
0
-32000
-32000
-32000
-50,0
-100,0
320,00
3000
32000
32000
32000
50,0
100,0
Varies
0,0
0,0
0
0
0
0,0
0,0
674
673
668
669
670
1252
1253
P2.6.6.17
P2.6.6.18
P2.6.6.19
P2.6.6.20
P2.6.6.21
P2.6.6.22
P2.6.6.23
P2.6.6.24
P2.6.6.25
P2.6.6.26
Unit
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
Default
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
Cust
ID
1355
1356
1357
1358
1359
1360
1361
1362
1363
1364
1365
1366
1367
1368
1369
Note
4.7.6
Code
Parameter
Min
Max
P2.6.7.1
Speed Scale
Unit
Default
1
Cust
ID
523
Note
0=0,0 Hz
1=0,00 Hz
2=0,000 Hz
apfiff08 Advanced
4.8
vacon 35
Code
Parameter
Min
Max
P2.7.1
Response to 4mA
reference fault
P2.7.2
0,00
P2.1.2
P2.7.3
Response to external
fault
Input phase
0
supervision
Response to
P2.7.5
0
undervoltage fault
Output phase
P2.7.6
0
supervision
P2.7.7 Earth fault protection
0
Thermal protection
P2.7.8
0
of the motor
Motor ambient
P2.7.9
100,0
temperature factor
Motor cooling factor
P2.7.10
0,0
at zero speed
Motor thermal time
P2.7.11
1
constant
P2.7.12
Motor duty cycle
0
P2.7.4
727
702
703
704
100,0
0,0
705
150,0
40,0
706
200
min
45
707
100
100
708
2 x IH
120,00
P2.1.2
P2.7.23
728
0,1 x IH
1,00
1,0
Response to
fieldbus fault
Response to slot
fault
0,00
730
Stall current
Stall time limit
Stall frequency limit
P2.7.22
700
P2.7.14
P2.7.15
P2.7.16
P2.7.21
Response to
thermistor fault
ID
701
Cust
Stall protection
P2.7.18
Hz
Default
P2.7.13
Unit
10,0
150,0
5,0
2,00
A
s
Hz
709
IL
15,00
25,0
710
711
712
713
50,0
714
150,0
10,0
715
600,00
20,00
716
Note
0=No response
1=Warning
2=Warning+Previous freq.
3=Wrng+Preset freq 2.7.2
4=Fault,stop acc. to 2.4.7
5=Fault,stop by coasting
0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
732
0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
733
See P2.7.21
734
See P2.7.21
739
36 vacon
apfiff08 Advanced
Code
Parameter
Min
Max
P2.7.25
Response to PT100
fault
30,0
30,0
200,0
200,0
P2.7.29
0,00
320,00
P2.7.30
P2.7.33
0,00
320,00
0,00
7,00
100
0,00
10,00
0,00
30,00
0,0
100,0
P2.7.34
P2.7.35
P2.7.39
Speed error
maximum
difference
Speed error fault
delay
Unit
C
C
Default
Cust
ID
740
120,0
130,0
741
742
1316
0,20
1317
1082
3,00
1352
2,00
751
752
753
0,50
754
1353
0,00
1354
50,0
1333
1086
Note
0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
0=No response
1=Warning
2=Fault,stop by coasting
0=No response
1=Warning
2=Fault,stop by coasting
apfiff08 Advanced
4.9
vacon 37
Code
P2.8.1
P2.8.2
Parameter
Wait time
Trial time
Min
0,10
0,00
Max
10,00
60,00
P2.8.3
Start function
719
10
720
10
721
722
10
723
10
726
10
725
10
738
P2.8.4
P2.8.5
P2.8.6
P2.8.7
P2.8.8
P2.8.9
P2.8.10
Unit
s
s
Default
0,50
30,00
Cust
ID
717
718
Note
0=Ramp
1=Flying start
2=According to P2.4.6
38 vacon
apfiff08 Advanced
Parameter
Fieldbus min scale
Fieldbus max scale
Min
0,00
0,00
Max
320,00
320,00
P2.9.3
Fieldbus process
data out 1 selection
10000
852
P2.9.4
Fieldbus process
data out 2 selection
10000
853
P2.9.5
Fieldbus process
data out 3 selection
10000
45
854
P2.9.6
Fieldbus process
data out 4 selection
10000
855
P2.9.7
Fieldbus process
data out 5 selection
10000
856
P2.9.8
Fieldbus process
data out 6 selection
10000
857
P2.9.9
Fieldbus process
data out 7 selection
10000
858
P2.9.10
Fieldbus process
data out 8 selection
10000
37
859
P2.9.11
Fieldbus process
data in 1 selection
10000
1140
876
P2.9.12
Fieldbus process
data in 2 selection
10000
46
877
P2.9.13
Fieldbus process
data in 3 selection
10000
47
878
P2.9.14
Fieldbus process
data in 4 selection
10000
48
879
10000
880
10000
881
10000
882
10000
883
896
P2.9.15
P2.9.16
P2.9.17
P2.9.18
P2.9.19
Fieldbus process
data in 5 selection
Fieldbus process
data in 6 selection
Fieldbus process
data in 7 selection
Fieldbus process
data in 8 selection
FB Profile
Unit
Hz
Hz
Default
0,00
0,00
Cust
ID
850
851
Note
3=Reserved
P2.9.20
FB General Status
Word ID
10000
68
897
P2.9.21
Control Slot
Selectopr
1440
apfiff08 Advanced
P2.9.22
P2.9.23
FB Custom Min
Scale
FB Custom Max
Scale
vacon 39
-320,00
320,00
898
-320,00
320,00
&
10000
899
40 vacon
4.10.1.1
Code
P2.10.1
P2.10.2
P2.10.3
P2.10.4
P2.10.5
P2.10.6
P2.10.7
P2.10.8
P2.10.9
P2.10.10
P2.10.11
P2.10.12
P2.10.13
P2.10.14
P2.10.15
P2.10.16
apfiff08 Advanced
Torque reference
selection
Torque reference
max.
Torque reference
min.
Minimum frequency
for open loop
torque control
Torque speed limit
for Open Loop
Torque controller
P gain
Torque controller
I gain
Torque reference
filtering time
Window negative
Window positive
Window negative off
Window positive off
Speed control output
limit
Min
Max
0,0
32000
3000
610
0,0
32000
200
611
300,0
300,0
300,0
Unit
Default
Cust
ID
641
100
642
300,0
0,0
643
0,00
50,00
Hz
3,00
636
644
32000
150
639
32000
10
640
1278
32000
ms
1244
0,00
0,00
0,00
0,00
50,00
50,00
P2.10.11
P2.10.12
Hz
Hz
Hz
Hz
2,00
2,00
0,00
0,00
1305
1304
1307
1306
0,0
300,0
300,0
1382
Note
Used only in Open Loop
control mode
0=Not used
1=AI1
2=AI2
3=AI3
4=AI4
5=AI1 joystick (-10 10 V)
6=AI2 joystick (-10 10 V)
7=Torque reference from
keypad, R3.5
8=FB Torque Reference
0=Max. frequency
1=Selected frequency ref.
2=Preset speed 7
apfiff08 Advanced
vacon 41
Parameter
Min
Max
Unit
Default
Cust
ID
P2.11.1
Master Follower
mode
1324
P2.11.2
Follower stop
function
1089
P2.11.3
Follower speed
reference select
18
17
1081
P2.11.4
Follower torque
reference select
10
10
1083
P2.11.5
Speed share
-300,00
300,00
100,00
1241
P2.11.6
Load share
0,0
500,0
100,0
1248
P2.11.7
Master Follower
mode 2
1093
Note
0=Single Drive
1=Master Drive
2=Follower Drive
0=Coasting
1=Ramping
2=As Master
0=AI1
1=AI2
2=AI1+AI2
3=AI1-AI2
4=AI2-AI1
5=AI1xAI2
6=AI1 Joystick
7=AI2 Joystick
8=Keypad
9=Fieldbus
10=Motor potentiometer
11=AI1, AI2 minimum
12=AI1, AI2 maximum
13=Max frequency
14=AI1/AI2 selection
15=Encoder 1
16=Encoder 2
17=Master Reference
18=Master Ramp Out
0=Not used
1=AI1
2=AI2
3=AI3
4=AI4
5=AI1 joystick
6=AI2 joystick
7=Torque reference from
keypad, R3.5
8=FB Torque Reference
9=Master Torque
Active also in Single
mode
Active also in Single
mode
Activated by ID1092
0=Single Drive
1=Master Drive
2=Follower Drive
42 vacon
apfiff08 Advanced
Parameter
Min
Max
P3.1
Control place
R3.2
Keypad reference
Direction (on
keypad)
P2.1.1
P2.1.2
P3.4
Stop button
R3.5
Torque reference
0,0
100,0
P3.3
Unit
Default
Cust
ID
125
123
Note
0=PC Control
1=I/O terminal
2=Keypad
3=Fieldbus
Hz
114
%
0=Forward
1=Reverse
0=Limited function of Stop
button
1=Stop button always
enabled
0,0
apfiff08 Advanced
5.
vacon 43
DESCRIPTION OF PARAMETERS
On the following pages you will find the parameter descriptions arranged according to the individual
ID number of the parameter. A shaded parameter ID number (e.g. 418 Motor potentiometer UP)
indicates that the TTF programming method shall be applied to this parameter (see chapter 3).
Some parameter names are followed by a number code indicating the "All in One" applications in
which the parameter is included. If no code is shown the parameter is available in all applications.
See below. The parameter numbers under which the parameter appears in different applications
are also given.
Note: These is parameter ID numbers that are not used in this application or there are selections
that are not available in this application, refer to parameter list table for right functions and
selections. See also Vacon Marine application APFIFF09.
101
102
Minimum frequency
Maximum frequency
(2.1.1)
(2.1.2)
103
104
Acceleration time 1
Deceleration time 1
(2.1.3)
(2.1.4)
These parameters defines time required for the output frequency to increase from the
zero frequency to maximum frequency (ID102) and reverse.
105
106
Preset speed 1
Preset speed 2
(2.1.15)
(2.1.16)
These parameters defines reference when Preset Speed digital inputs are activated.
See also Digital inputs Preset Speed 1 (ID419) and 2 (ID420).
Basic reference
Preset speed 1
ID419
0
Preset speed 2
ID420
0
ID105
ID106
1
0
0
1
Speed
107
Current limit
(2.1.5)
This parameter determines the maximum motor current from the frequency converter.
The parameter value range differs from size to size. When Current limit is changed stall
current limit (ID710) is internally calculated to 90% of current limit if value is greater.
When current limit is active drive output frequency is lowered.
44 vacon
108
apfiff08 Advanced
Squared:
1
234567
(2.6.3)
The voltage of the motor changes linearly from zero point voltage (ID606)
with the frequency in the constant flux area from 0 Hz to the field weakening
point (ID602) where the voltage at FWP (ID602) is supplied to the motor.
The voltage of the motor changes from zero point voltage (ID606) following
the squared curve form zero frequency to the field weakening point (ID602).
The motor runs under magnetised below the field weakening point (ID602)
and produces less torque. Squared U/f ratio can be used in applications
where torque demand is proportional to the square of the speed, e.g. in
centrifugal fans and pumps.
U[V]
Un
Nominal
ID603 Default:
voltage of the motor
Field weakening
point
Linear
Squared
Default: Nominal
frequency of the
motor
f[Hz]
NX12K07
U[V]
Un
ID603
Default: Nominal
voltage of the motor
ID605
(Def. 10%)
Default: Nominal
frequency of the motor
f[Hz]
ID606
(Def. 1.3%)
ID604
(Def. 5 Hz)
ID602
NX12K08
apfiff08 Advanced
vacon 45
109
U/f optimisation
Automatic
torque boost
(2.6.3.1)
EXAMPLE:
NOTE!
110
In high torque low speed applications it is likely that the motor will
overheat. If the motor has to run long times under these conditions,
special attention must be paid to cooling of the motor. Use external
cooling for the motor if the temperature tends to rise too high.
111
(2.1.7)
Find this value fn on the rating plate of the motor. This parameter sets the field
weakening point (ID602) to the same value.
46 vacon
112
apfiff08 Advanced
(2.1.8)
Find this value nn on the rating plate of the motor. Note also nominal freqyency.
113
117
(2.1.11)
Defines which frequency reference source is selected when control place is I/O terminal
ID125.
Applic.
Sel.
0
AI1+AI2
AI1AI2
AI2AI1
AI1*AI2
AI2 joystick
Fieldbus reference
Potentiometer reference; controlled with ID418 (TRUE=increase) and
ID417 (TRUE=decrease)
AI1 or AI2, whichever is lower
10
11
12
14
15
16
13
120
PC Control
Acceleration prohibited input
Inching frequency references
Jogging speed
Preset speeds
4 mA fault frequency
Selected control place frequency reference
(2.1.10)
Find this value cos phi on the rating plate of the motor.
Tel. +358 (0)201 2121 Fax +358 (0)201 212 205
apfiff08 Advanced
121
vacon 47
(2.1.12)
Defines which frequency reference source is selected when control place is keypad
ID125.
Applic.
Sel.
Analogue Input 1
(AI1)
Analogue Input 2
(AI2)
AI1+AI2
AI1AI2
AI2AI1
5
6
7
8
9
AI1*AI2
AI1 joystick
AI2 joystick
Keypad reference (R3.2)
Fieldbus reference*
122
(2.1.13)
Defines which frequency reference source is selected when control place is Fieldbus
ID125. For selections in different applications, see keypad reference selection ID121.
124
(2.1.14)
Defines the jogging speed reference when activated by digital input. See parameter
Jogging Speed (ID413).
126
127
128
129
130
Preset speed 3
Preset speed 4
Preset speed 5
Preset speed 6
Preset speed 7
(2.1.17)
(2.1.18)
(2.1.19)
(2.1.20)
(2.1.21)
Parameter values define the Preset speeds references activated by digital inputs.
See Preset Speeds digital inputs ID419, ID420 and ID421.
Speed
Basic speed
P2.1.15 (1)
P2.1.16 (2)
P2.1.17 (3)
P2.1.18 (4)
P2.1.19 (5)
P2.1.20 (6)
P2.1.21 (7)
Preset speed 1
ID419
0
1
0
1
0
1
0
1
Preset speed 2
ID420
0
0
1
1
0
0
1
1
Preset speed 3
ID421
0
0
0
0
1
1
1
1
48 vacon
131
apfiff08 Advanced
141
(2.2.4.1)
Connect the AI3 signal to the analogue input of your choice with this parameter. For
more information, see Chapter 3 Terminal To Function (TTF) programming principle.
When this input is set to 0.1 you can control AI3 from fieldbus.
142
(2.2.4.2)
When this parameter is given a value greater than 0 the function that filters out disturbances from the incoming analogue signal is activated. Long filtering time makes the
regulation response slower. See parameter AI1 Signal filter time (ID324).
144
145
(2.2.4.3)
(2.2.4.4)
Set the custom minimum and maximum input levels for the AI3 signal within 160160%.
151
(2.2.4.5)
0 = No inversion
1 = Signal inverted
152
(2.2.5.1)
Connect the AI4 signal to the analogue input of your choice with this parameter. For
more information, see Chapter 3 Terminal To Function (TTF) programming principle.
In NXP when this input is set to 0.1 you can control AI3 from fieldbus.
153
(2.2.5.2)
When this parameter is given a value greater than 0,0 the function that filters out
disturbances from the incoming analogue signal is activated. See Figure 8 20.
155
156
(2.2.5.3)
(2.2.5.4)
Set the custom minimum and maximum input levels for the AI4 signal within 160160%. E.g. min 40 %, max 80 % = 816 mA
162
(2.2.5.5)
0 = No inversion
1 = Signal inverted
apfiff08 Advanced
164
vacon 49
(2.2.7.22)
165
(2.2.2.11)
Define the frequency zero point as follows: With this parameter on display, place the
potentiometer at the assumed zero point and press Enter on the keypad.
Note: This will not, however, change the reference scaling.
Press Reset button to change the parameter value back to 0,00%.
166
(2.2.3.11)
169
170
(2.3.3.27)
(2.3.3.28)
The data from the fieldbus (FBFixedControlWord) can be led to the digital outputs of the
frequency converter. See details from used fieldbus board manual.
179
(2.2.6.7)
The motoring power limit is equal to parameter Motoring Power Limit (ID1289) if value
'0' is selected. If any of the inputs is selected the motoring power limit is scaled between
zero and parameter Motoring Power Limit (ID1289). This parameter is available for
Closed Loop control mode only. Input level zero causes power limit zero.
0
1
2
3
4
5
= Not Used
= AI1
= AI2
= AI3
= AI4
= FieldBus Scaling ID46 (Monitoring Value)
50 vacon
300
apfiff08 Advanced
(2.2.1.1)
Output
frequency
Stop function
(ID506)
= coasting
REV
DIN1
DIN2
NX12K09
c
d
e
Output
frequency
Stop function
(ID506)
= coasting
REV
DIN1
DIN2
NX12K10
apfiff08 Advanced
vacon 51
Output
frequency
Stop function
(ID506)
= coasting
REV
DIN1
Start
DIN2
Stop
NX012K11
The selections including the text 'Rising edge required to start' shall be used to exclude the possibility of an unintentional start when, for example, power is connected, reconnected after a power failure, after a fault reset, after the drive is stopped by Run
Enable (Run Enable = False) or when the control place is changed. The Start/Stop
contact must be opened before the motor can be started.
4 DIN1: closed contact = start forward
DIN2: closed contact = Increases motor potentiometer reference; this parameter is
5 DIN1: closed contact = start forward (Rising edge required to start)
DIN2: closed contact = start reverse (Rising edge required to start)
6 DIN1: closed contact = start (Rising edge required to start)
open contact = stop
DIN2: closed contact = reverse
open contact = forward
7 DIN1: closed contact = start (Rising edge required to start)
open contact = stop
DIN2: closed contact = start enabled
open contact = start disabled and drive stopped if running
Reverse (ID412) can be used on those start logics that do not have reversion in Start
Signal 2 (ID404)
52 vacon
303
304
apfiff08 Advanced
(2.2.2.6)
(2.2.2.7)
Additional reference scaling. If both ID303 and ID304 are zero scaling is set off. The
minimum and maximum frequencies are used for scaling.
Output
frequency
Output
frequency
ID303
Analogue
input [V]
10
Analogue
input [V]
10
NX12K13
307
This parameter selects the desired function for the analogue output signal.
Function
Selection
0
1
2
3
4
5
6
7
8
9
10
11
Not used
Output freq. (0fmax)
Freq. reference (0fmax)
Motor speed
(0Motor nominal speed)
Output current (0-InMotor)
Motor torque (0TnMotor)
Motor power (0PnMotor)
Motor voltage (0-UnMotor)
DC-link volt (01000V)
AI1
AI2
Output freq. (fmin - fmax)
14
Motor torque
(-TnMotor TnMotor)
Motor power
(-PnMotor PnMotor)
PT100 temperature
15
FB analogue output
ID48 Monitoring signal
12
13
Comment
apfiff08 Advanced
308
vacon 53
(2.3.5.3)
%
Unfiltered signal
100%
Filtered signal
63%
t [s]
ID308
NX12K16
309
(2.3.5.4)
Analog
output
current
20 mA
12 mA
ID311=
50%
10 mA
ID311 =
100%
4 mA
ID311 =
200%
0 mA
0
0.5
1.0
NX12K17
OutputSignal =
310
(2.3.5.5)
Defines the signal minimum to either 0 mA or 4 mA (living zero). Note the difference in
analogue output scaling in parameter ID311 (Figure 5-9).
0 Set minimum value to 0 mA (0 %)
1 Set minimum value to 4 mA (20 %)
54 vacon
311
apfiff08 Advanced
(2.3.5.6)
Analogue
output
current
ID311 =
200%
ID311 =
100%
20 mA
12 mA
ID311 =
50%
10 mA
ID310 = 1
4 mA
ID310 = 0
0 mA
0.5
1.0
NX12K18
312
313
314
(2.3.7, 2.3.1.2)
(2.3.8, 2.3.1.3)
(2.3.9)
Setting value
Signal content
0 = Not used
1 = Ready
Out of operation
Digital output DO1 sinks the current and
programmable relay (RO1, RO2) is activated when:
The frequency converter is ready to operate
2 = Run
3 = Fault
4 = Fault inverted
8 = Warning
9 = Reversed
10 = Jogging speed
11 = At speed
12 = Motor regulator activated
13 = Output frequency limit supervision
apfiff08 Advanced
vacon 55
Table 5-6. Output signals via DO1 and output relays RO1 and RO2.
315
(2.3.4.1)
No supervision
Low limit supervision
High limit supervision
Brake-on control (See chapter 6.1 on page 119)
If the output frequency goes under/over the set limit (ID316) this function generates a
message via digital output depending on to which output the supervision signal 1 (ID447)
is connected. Brake control uses different output functions. See ID445 & ID446.
56 vacon
316
apfiff08 Advanced
(2.3.4.2)
Selects the frequency value supervised by parameter ID315. See Figure 5-10.
f[Hz]
ID315 = 2
ID316
t
Example: 21 RO1
22 RO1
23 RO1
21 RO1
22 RO1
23 RO1
21 RO1
22 RO1
23 RO1
NX12K19
320
(2.2.2.3)
APFIFF08
0100%
20100%
10+10V (0100%)
Customised
321
322
(2.2.2.4)
(2.2.2.5)
These parameters set the analogue input 1 signal for any input signal span within -160
160%. E.g. if signal input scaling is set to 40 % to 80 % reference is changing between
Minimum Frequency (ID101) and Maximum Frequency (ID102) with mA signal 8 mA to 16
mA
apfiff08 Advanced
324
vacon 57
(2.2.2.2)
Unfiltered signal
100%
Filtered signal
63%
t [s]
ID324
NX12K74
325
(2.2.3.3)
APFIFF08
0100%
20100%
10+10V (0100%)
Customised
326
327
(2.2.3.4)
(2.2.3.5)
Output
frequency
ID304
ID325 = Custom
ID325 = 0
AI2 = 0100%
ID325 = 1
AI2 = 20-100%
ID303
ID326
4 mA
ID327
AI2
(term. 3,4)
20 mA
NX12K75
58 vacon
329
apfiff08 Advanced
(2.2.3.2)
When this parameter is given a value greater than 0 the function filters out disturbances
from the incoming analogue signal.
See AI1 signal filtering time (ID324).
331
(2.2.1.2)
Defines the speed of change of the motor potentiometer reference value. Hz/s. Motor
Control ramp times are still active.
346
(2.3.4.3)
No supervision
Low limit supervision
High limit supervision
Brake-on control (Application 6 only, see chapter 6.1 on page 119)
Brake-on/off control (Application 6 only, see chapter 6.1 on page 119)
If the output frequency goes under/over the set limit (ID347) this function generates a
message via digital output depending on to which output the supervision signal 2 (ID448)
is connected. Brake control uses different output functions. See ID445 & ID446.
347
(2.3.4.4)
Selects the frequency value supervised by parameter ID346. See Figure 5-10.
348
(2.3.4.5)
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
3 = Brake-off control (See chapter 6.1 on page 119)
If the calculated torque value falls below or exceeds the set limit (ID349) this function
generates a message via the digital output depending on to which output the torque limit
supervision signal (ID451) is connected.
349
(2.3.4.6)
350
(2.3.4.7)
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
If the reference value falls below or exceeds the set reference limit (ID351), this function
generates a message via the digital output depending on to which output the reference
limit supervision signal (ID449) is connected
apfiff08 Advanced
351
vacon 59
(2.3.4.8)
The frequency value to be supervised with the parameter ID350. % value between
minimum and maximum frequency.
352
353
(2.3.4.9)
(2.3.4.10)
The function of the external brake can be timed to the start and stop control signals with
these parameters. See Figure 5-13 and chapter 6.1 on page 119.
The brake control signal can be programmed via the digital outputs. See parameters
External brake control (ID445), inverted (ID446) and Delayed outputs (G2.3.1 and G2.3.2)
a)
b)
tOFF = ID352
tON = ID353
tOFF = ID352
External
External
BRAKE: OFF
ON
BRAKE: OFF
DO1/RO1/
RO2
ON
DO1/RO1/
RO2
DIN1: START
STOP
PULSE
STOP
DIN2: STOP
PULSE
NX12K45
60 vacon
354
apfiff08 Advanced
(2.3.4.11)
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
If the temperature of the frequency converter unit falls below or exceeds the
temperature limit value (ID355), this function generates a message via the digital output
depending on to which output the temperature limit supervision signal (ID450) is
connected.
355
(2.3.4.12)
356
(2.3.4.13)
With this parameter you can select the analogue input to be monitored.
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
357
358
(2.3.4.14)
(2.3.4.15)
These parameters set the low and high limits of the signal selected with par. ID356. See
Figure 5-14.
Analogue input (selected with par. ID356)
ID358
ID357
Time
RO1
1
0
NX12k116
apfiff08 Advanced
366
vacon 61
(2.2.1.8)
0 Keep reference
1 Copy reference
2 Copy actual
This function copies reference frequency or actual frequency from other IO reference
place when IO Reference is changed to Motor potentiometer reference with ID422.
367
(2.2.1.3)
0 No reset
1 Memory reset at stop and powerdown
2 Memory reset at powerdown
375
(2.3.5.7)
377
(2.2.2.1)
Connect the AI1 signal to the analogue input of your choice with this parameter. For
more information about the TTF programming method, see chapter 3.
62 vacon
384
apfiff08 Advanced
(2.2.2.8)
Reference
scaling max
ID304 = 70Hz
REVERSE
FORWARD
50%
50%
B
From reverse to forward
Analogue
input (V/mA)
(0-10V/20mA)
Par. ID321
= 20 %
Joystick hysteresis,
Par. ID322
= 90 %
ID384 = 20 %
NX12k92
Figure 5-15. An example of joystick hysteresis. In this example, the value of par. ID385 (Sleep
limit) = 0
apfiff08 Advanced
385
vacon 63
(2.2.2.9)
The frequency converter is stopped automatically if the AI signal level falls below the
Sleep limit defined with this parameter. See Figure 5-16.
Frequency reference
Hz
Reference
scaling max
ID304 = 70Hz
REVERSE
FORWARD
50%
50%
B
From reverse to forward
STOP
STOP START
From forward to reverse
Analogue
input (V/mA)
(0-10V/20mA)
Par. ID321
= 20 %
Sleep limit
ID385 = 7%
Par. ID322
= 90 %
Joystick hysteresis,
NX12k99
ID384 = 20 %
Frequency reference
Hz
Reference
scaling max
ID304 = 70Hz
REVERSE
FORWARD
50%
50%
B
From reverse to forward
Analogue
input (V/mA)
(0-10V/20mA)
ID321
= 20 %
Joystick hysteresis,
ID322
= 90 %
ID384 = 20 %
NX12k95
64 vacon
386
apfiff08 Advanced
(2.2.2.10)
This parameter defines the time the analogue input signal has to stay under the sleep
limit determined with parameter ID385 in order to stop the frequency converter.
388
(2.2.3.1)
Connect the AI2 signal to the analogue input of your choice with this parameter. For
more information about the TTF programming method, see chapter 3.
393
394
(2.2.3.6)
(2.2.3.7)
Additional reference scaling. If both ID393 and ID394 are zero scaling is set off. The
minimum and maximum frequencies are used for scaling.
See figure from parameter reference scaling (ID303).
395
(2.2.3.8)
396
(2.2.3.9)
The frequency converter is stopped if the AI signal level falls below the Sleep limit
defined with this parameter. See also Sleep Delay (ID397).
See Figure 5-16 from AI1 sleep limit (ID3859.
397
(2.2.3.10)
This parameter defines the time the analogue input signal has to stay under the sleep
limit determined with parameter AI2 sleep limit (ID396) in order to stop the frequency
converter.
399
(2.2.6.1)
= Not used
= AI1
= AI2
= AI3
= AI4
= FB Limit Scaling ID46 Monitoring value
This signal will adjust the maximum motor current between 0 and Parameter Motor
Current Limit (ID107).
apfiff08 Advanced
400
vacon 65
(2.2.6.2)
DC-braking
current
100%
Par. ID507
0,15 x IL
0
Signal range
NX12K58
401
(2.2.6.3)
Factor R
10
Free
analogue
input
2
1
Signal range
NX12K59
66 vacon
402
apfiff08 Advanced
(2.2.6.4)
See ID399.
The set torque supervision limit
can be reduced with the free
analogue input signal between 0
and the set supervision limit,
ID349. See Figure 5-20.
Torque
limit
100%
Par. ID349
Free
analogue
input
0
Signal
range
NX12K60
403
Start signal 1
(2.2.7.1)
404
Start signal 2
(2.2.7.2)
405
406
407
Run enable
(2.2.7.11)
(2.2.7.12)
Contact open:
Start of motor disabled
Contact closed: Start of motor enabled
Stop is made accordingly stop function ID596. Follower Drive will make always coasting
stop.
408
(2.2.7.13)
Set Acceleration/Deceleration times with parameters ID103 and ID104 and alternative
ramp times with ID502 and ID503.
Tel. +358 (0)201 2121 Fax +358 (0)201 212 205
apfiff08 Advanced
409
vacon 67
(2.2.7.18)
410
(2.2.7.19)
411
(2.2.7.20)
412
Reverse
(2.2.7.4)
Contact open:
Direction forward
Contact closed: Direction reverse
This reverse command is active when Start signal 2 is used for other purpose.
413
Jogging speed
(2.2.7.16)
414
Fault reset
Contact closed:
415
Acceleration/Deceleration prohibited
Contact closed:
416
(2.2.7.10)
(2.2.7.14)
DC-braking
(2.2.7.15)
Contact closed: In STOP mode, the DC braking operates until the contact is opened.
See ID 1080 DC Brake current in stop state.
417
(2.2.7.8)
68 vacon
418
Motor potentiometer UP
Contact closed:
opened.
419
420
421
apfiff08 Advanced
(2.2.7.9,)
Preset speed 1
Preset speed 2
Preset speed 3
(2.2.7.5)
(2.2.7.6)
(2.2.7.7)
422
AI1/AI2 selection
(2.2.7.17)
With this parameter you can select either AI1 or AI2 signal for frequency reference if I/O
reference selection is 14. If different than 14 see I/O Reference 2 (ID1505).
432
Ready
(2.3.3.1)
433
Run
(2.3.3.2)
434
Fault
(2.3.3.3)
435
Inverted fault
(2.3.3.4)
436
Warning
(2.3.3.5)
437
(2.3.3.6)
438
(2.3.3.7)
Fault or warning depending on parameter Response to the 4mA reference fault (ID700).
439
(2.3.3.8)
440
Reverse
(2.3.3.9)
441
Unrequested direction
(2.3.3.10)
apfiff08 Advanced
442
At speed
vacon 69
(2.3.3.11)
443
Jogging speed
(2.3.3.12)
444
(2.3.3.13)
445
(2.3.3.14)
446
(2.3.3.15)
447
(2.3.3.16)
The output frequency goes outside the set supervision low limit/high limit (see
parameters Output frequency 1 supervision function (ID315) and Output frequency
supervision value (ID316).
448
(2.3.3.17)
The output frequency goes outside the set supervision low limit/high limit (see
parameters Output frequency 2 supervision function (ID346) and Output frequency 2
supervision value (ID347)
70 vacon
449
apfiff08 Advanced
(2.3.3.18)
Active reference goes beyond the set supervision low limit/high limit (see parameters
Reference limit supervision function (ID350) and Reference limit supervision value
(ID351).
450
(2.3.3.19)
Frequency converter heatsink temperature goes beyond the set supervision limits (see
parameters FC temperature function (ID354) and FC Temperature limit (ID355).
451
(2.3.3.20)
The motor torque goes beyond the set supervision limits (see parameters Torque limit
function (ID348) and Supervision Torque limit (ID349).
452
(2.3.3.21)
Motor thermistor initiates a overtemperature signal which can be led to a digital output.
NOTE: This parameter will not work unless you have Vacon OPT-A3 or OPT-B2
(thermistor relay board) connected.
454
(2.3.3.23)
455
456
457
(2.3.3.24)
(2.3.3.25)
(2.3.3.26)
The data from the fieldbus (FBFixedControlWord) can be led to frequency converter
digital outputs. See details from used fieldbus board manual.
463
(2.3.3.22)
The selected analogue input signal goes beyond the set supervision limits (see
parameters Supervised AI (ID372), AI supervision function (ID373) and AI Supervision
value (ID374).
464
( 2.3.5.1)
Connect the AO1 signal to the analogue output of your choice with this parameter. For
more information about the TTF programming method, see chapter 3.
471
(2.3.6.1)
Connect the AO2 signal to the analogue output of your choice with this parameter. For
more information about the TTF programming method, see chapter 3.
apfiff08 Advanced
472
473
474
475
476
vacon 71
(2.3.6.2)
(2.3.6.3)
(2.3.6.4)
(2.3.6.5)
(2.3.6.6)
For more information on these five parameters, see the corresponding parameters for
the analogue output 1 on pages 52 to 54.
477
(2.3.6.7)
478
(2.3.7.1)
Connect the AO1 signal to the analogue output of your choice with this parameter. For
more information about the TTF programming method, see chapter 3.
479
(2.3.7.2)
This parameter selects the desired function for the analogue output signal.
Function
Selection
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
480
Not used
Output freq. (0fmax)
Freq. reference (0fmax)
Motor speed (0Motor
nominal speed)
Output current (0-InMotor)
Motor torque (0TnMotor)
Motor power (0PnMotor)
Motor voltage (0-UnMotor)
DC-link volt (01000V)
AI1
AI2
Output freq. (fmin - fmax)
Motor torque
Motor power
PT100 temperature
FB analogue output
ID48 Monitoring signal
(2.3.7.3)
481
(2.3.7.4)
72 vacon
482
apfiff08 Advanced
(2.3.7.5)
483
(2.3.7.6)
Scaling factor for analogue output. Value of 200 % will double the output .
See figure from Analogue output scale (ID311).
484
(2.3.7.7)
apfiff08 Advanced
485
vacon 73
(2.2.6.5)
= Not used
= AI1
= AI2
= AI3
= AI4
= FB Limit Scaling ID46 Monitoring value
This signal will adjust the motoring torque limit between 0 and Parameter Motoring
Torque Limit (UD1287).
486
(2.3.1.1)
Connect the delayed digital output signal to the digital output of your choice with this
parameter. For more information about the TTF programming method, see chapter 3.
Digital output function can be inverted by Inversion command word (ID1091).
487
488
(2.3.1.3)
(2.3.1.4)
With these parameters you can set on- and off-delays to digital outputs.
Signal programmed to
digital output
ON-delay
OFF-delay
NX12k102
489
(2.3.2.1)
Connect the delayed DO2 signal to the digital output of your choice with this parameter.
See ID486.
490
(2.3.2.2)
491
(2.3.2.3)
492
(2.3.2.4)
With these parameters you can set on- and off-delays to digital outputs.
See ID487 and ID488.
74 vacon
493
apfiff08 Advanced
Adjust input
With this parameter you can
select the signal, according
to which the frequency
reference to the motor is
fine adjusted.
0
1
2
3
4
5
Not used
Analogue input 1
Analogue input 2
Analogue input 3
Analogue input 4
FB Adjust Reference ID47
Monitoring Signal
(2.2.1.4)
Adjust
maximum
ID495 = 10%
f/Hz
Adjusted
44Hz
Adjust 0 %
40Hz
36Hz
Adjust
minimum
ID494 = 10%
Analogue input
NX12K108
494
495
Adjust minimum
Adjust maximum
(2.2.1.5)
(2.2.1.6)
These parameters define the minimum and maximum of adjusted signals. See Figure
5-22. Adjust is made to main reference.
496
(2.2.7.21)
With this parameter you can select between Parameter Set 1 and Set 2. The input for
this function can be selected from any slot. The procedure of selecting between the sets
is explained in Vacon NX Users Manual, Chapter 7.3.6.3.
Digital input = FALSE:
- Set 1 is loaded as the active set
Digital input = TRUE:
- The active set is saved to set 1
Note: The parameter values are stored only when selecting from System menu P6.3.1
Parameter sets Store Set 1 or Store Set 2 or from NCDrive: Drive > Parameter Sets.
apfiff08 Advanced
500
501
vacon 75
(2.4.1)
(2.4.2)
The start and end of acceleration and deceleration ramps can be smoothed with these
parameters. Setting value 0 gives a linear ramp shape which causes acceleration and
deceleration to act immediately to the changes in the reference signal. Setting value
0.110 seconds for this parameter produces an S-shaped acceleration/deceleration.
The acceleration time is determined with parameters ID103/ID104 (ID502/ID503).
[Hz]
ID103, ID104
(ID502, ID503)
ID500 (ID501)
ID500 (ID501)
[t]
NX12K20
Used to reduce mechanical erosion and current spikes when reference is changed.
502
503
Acceleration time 2
Deceleration time 2
(2.4.3)
(2.4.4)
These values correspond to the time required for the output frequency to accelerate
from the zero frequency to the set maximum frequency (ID102). These parameters give
the possibility to set two different acceleration/deceleration time sets for one
application. The active set can be selected with the programmable signal DIN3 (par.
ID301).
504
Brake chopper
0
1
2
3
4
=
=
=
=
=
(2.4.5)
When the frequency converter is decelerating the motor, the inertia of the motor and the
load are fed into an external brake resistor. This enables the frequency converter to
decelerate the load with a torque equal to that of acceleration (provided that the correct
brake resistor has been selected). See separate Brake resistor installation manual.
Brake chopper test mode generates pulse to resistor every second, if pulse feedback is
wrong (resistor or chopper is missing) fault F12 is generated.
76 vacon
505
apfiff08 Advanced
Start function
Ramp:
0
(2.4.6)
The frequency converter starts from 0 Hz and accelerates to the set reference
frequency within the set acceleration time. (Load inertia or starting friction
may cause prolonged acceleration times).
Flying start:
1
The frequency converter is able to start into a running motor by applying a
small current pulses to motor and searching for the frequency corresponding
to the speed the motor is running at. Searching starts from the maximum
frequency towards the actual frequency until the correct value is detected.
Use this mode if the motor is coasting when the start command is given. With
the flying start it is possible to start motor form actual speed without forcing
the speed to zero before ramping to reference.
Conditional flying start:
2
With this mode it is possible to disconnect and connect the motor from the
frequency converter even when the Start command is active. On re-connecting
the motor, the drive will operate as described in selection 1.
506
Stop function
(2.4.7)
Coasting:
0
The motor coasts to a halt without any control from the frequency converter,
after the Stop command.
Ramp:
1
After the Stop command, the speed of the motor is decelerated according to
the set deceleration parameters to zero speed.
If the regenerated energy is high it may be necessary to use an external
braking resistor to stop within deceleration time.
507
DC-braking current
(2.4.8)
Defines the current injected into the motor during DC-braking. On start this parameter
is used together with DC Brake time on start (ID516) to decrease time when motor is
able to produce maximum torque. See ID516.
Tel. +358 (0)201 2121 Fax +358 (0)201 212 205
apfiff08 Advanced
508
vacon 77
(2.4.9)
Determines if braking is ON or OFF and the braking time of the DC-brake when the
motor is stopping. The function of the DC-brake depends on the stop function,
parameter ID506.
0
>0
fout
fn
fn
Output frequency
Motor speed
Output frequency
Motor speed
0,1 x fn
DC-braking ON
DC-braking ON
t = 1 x Par. ID508
RUN
RUN
STOP
STOP
NX12K21
Motor speed
Output frequency
DC-braking
par. ID515
t
t = Par. ID508
RUN
STOP
NX12K23
78 vacon
509
510
511
512
513
514
apfiff08 Advanced
(2.5.1)
(2.5.2)
(2.5.3)
(2.5.4)
(2.5.5)
(2.5.6)
Output
frequency [Hz]
ID509
ID511
ID513
ID510
ID512
ID514
Reference [Hz]
NX12K33
515
(2.4.10)
The output frequency at which the DC-braking is applied. See Figure 5-26.
516
(2.4.11)
DC-brake is activated when the start command is given. This parameter defines the time
how long DC current is given to motor before acceleration starts. DC brake curren at
start is used in order to premagnetize motor before running. This will improve torque
performance at start. Needed time is depending on motor size, value varies between 100
ms to 3 second. Bigger motor needs more time. Default setting 0,00 s will means 0,20
second. See ID507
Note: When flying start is used, DC Brake on start is disabled
apfiff08 Advanced
518
vacon 79
(2.5.3, 2.5.7)
Defines the acceleration/deceleration time when the output frequency is between the
selected prohibit frequency range limits (parameter group G2.5). The ramping speed
(selected acceleration/ deceleration time 1 or 2) is multiplied with this factor. E.g. value
0.1 makes the acceleration time 10 times shorter than outside the prohibit frequency
range limits.
fout [Hz]
Par. ID510
(ID512; ID514)
Par. ID509
(ID511; ID513)
Time [s]
NX12k81
519
(2.4.13)
Defines the flux braking current value. The value setting range depends on the used unit
size.
520
Flux brake
(2.4.12)
Instead of DC braking, flux braking is a useful way to raise the braking capacity in cases
where additional brake resistors are not needed.
When braking is needed, the frequency is reduced and the flux in the motor is increased,
which in turn increases the motor's capability to brake. Unlike DC braking, the motor
speed remains controlled during braking.
The flux braking can be set ON or OFF.
0 = Flux braking OFF
1 = Flux braking ON
Note: Flux braking converts the energy into heat at the motor, and should be used
intermittently to avoid motor damage.
521
(2.6.3.11)
With this parameter you can set another motor control mode. Which mode is used is
determined with parameter ID164.
For the selections, see parameter ID600.
Note: Control mode can not be changed between open loop and closed loop while drive
is in run state.
80 vacon
522
apfiff08 Advanced
523
Speed Scale
(2.6.7.1)
This parameter defines speed area where frequency converter can operate.
0 : 0,000 - 32,000 Hz for low speed motors
1 : 0,00 - 320,00 Hz standard
2 : 0,0 - 3200,0 Hz for high speed motors.
530
531
Inching reference 1
Inching reference 2
(2.2.7.27)
(2.2.7.28)
These inputs activate the inching reference if inching is enabled. The inputs also start
the drive if activated and if there is no Run Request command from anywhere else.
532
Enable inching
(2.2.7.26)
If you are using the inching function the input value must be TRUE set by a digital signal
or by setting the value of the parameter to 0.2.
apfiff08 Advanced
600
601
vacon 81
(2.6.1)
Frequency control:
Speed control:
Torque control
Torque crtl (closed loop) Speed reference is used as maximum speed limit depending
of Torque Speed limit CL (ID1278) and motor produces
torque within speed limit to achieve torque reference. In
Closed Loop control mode speed feedback signal is used to
make optimum torque accuracy.
Switching frequency
(2.6.3.8)
Motor noise can be minimised using a high switching frequency. Increasing the
switching frequency incerases losses of the frequency converter unit. Lower frequencies
are used when motor cable is long and motor is small.
The range of this parameter depends on the size of the frequency converter:
Type
00030061 NX_5
00030061 NX_2
00720520 NX_5
00410062 NX_6
01440208 NX_6
Min. [kHz]
Max. [kHz]
Default [kHz]
1.0
16,0
10.0
1.0
10.0
3.6
1.0
6.0
1.5
"Note !
The actual switching frequency might be reduced down to 1,5kHz by thermal
management functions. This has to be considered when using sine wave filters or
other output filters with a low resonance frequency." See Control Option and Over
modulation limit.
602
(2.6.3.3)
The field weakening point is the output frequency at which the output voltage reaches
the field weakening point voltage (ID603).
82 vacon
603
apfiff08 Advanced
(2.6.3.4)
Above the frequency at the field weakening point, the output voltage remains at the set
maximum value. Below the frequency at the field weakening point, the output voltage
depends on the setting of the U/f curve parameters. See parameters U/f Optimization
(ID109), U/f ratio (ID108), Mid pont frequency (ID604) and Mid point voltage (ID605).
When the parameters nominal voltage (ID110) and nominal frequency (ID111) are set,
the parameters field weakening point (ID602) and field weakening voltage (ID603) are
automatically given the corresponding values. If you need different values for the field
weakening point and the maximum output voltage, change these parameters after
setting the parameters nominal voltage (ID110) and nominal frequency (ID111).
604
(2.6.3.5)
If the programmable U/f curve has been selected with parameter U/f ratio (ID108) this
parameter defines the middle point frequency of the curve. See also Mid point voltage
(ID605) Figure 5-2.
605
(2.6.3.6)
If the programmable U/f curve has been selected with the parameter U/f ratio (ID108)
this parameter defines the middle point voltage of the curve. See Figure 5-2
606
(2.6.3.7)
This parameter defines the zero frequency voltage of the U/f curve. Default value is unit
size dependent
NOTE: If the value of parameter U/f Ratio Select (ID108) is changed this parameter is set
to zero.
607
Overvoltage controller
(2.6.3.9)
apfiff08 Advanced
608
Undervoltage controller
vacon 83
(2.6.3.10)
610
(2.10.1)
This parameter defines the gain of the torque limit controller. It is used in Open Loop
control mode only.
611
(2.10.2)
This parameter determines the I-gain of the torque limit controller. It is used in Open
Loop control mode only.
612
(2.6.4.1)
Set here the motor magnetizing current (no-load current). See chapter 6.2. In NXP drive
U/f parameters are identified accordingly magnetization current, if given before
identification.
613
(2.6.4.2)
Sets the gain for the speed controller in % per Hz. See chapter 6.2.
614
(2.6.4.3)
Sets the integral time constant for the speed controller. Increasing the I-time increases
stability but lengthens the speed response time. See chapter 6.2.
615
(2.6.4.9)
After giving the start command the drive will remain at zero speed for the time defined
by this parameter. The ramp will be released to follow the set frequency/speed
reference after this time has elapsed from the instant where the command is given. See
chapter 6.2.
616
(2.6.4.10)
The drive will remain at zero speed with controllers active for the time defined by this
parameter after reaching the zero speed when a stop command is given. This parameter
has no effect if the selected stop function (ID506) is Coasting. See chapter 6.2. Zero
speed time starts when ramp time is expected to reach zero speed not from actual
speed
617
(2.6.4.17)
Sets the gain for the current controller. This controller is active only in closed loop
control mode. The controller generates the voltage vector reference to the modulator.
See chapter 6.2.
24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com
84 vacon
618
apfiff08 Advanced
(2.6.4.15)
619
(2.6.4.6)
The motor name plate speed is used to calculate the nominal slip. This value is used to
adjust the voltage of motor when loaded. The name plate speed is sometimes a little
inaccurate and this parameter can therefore be used to trim the slip. Reducing the slip
adjust value increases the motor voltage when the motor is loaded. See chapter 6.2.
620
Load drooping
(2.6.3.18)
The drooping function enables speed drop as a function of load. This parameter sets that
amount corresponding to the nominal torque of the motor.
E.g. If load drooping is set to 10 % with motor that have nominal frequency of 50 Hz and
motor is loaded with nominal load (100 % of torque) output frequency is allowed to
decrease 5 Hz from the frequency reference. Used for e.g. when load is needed to
balanced with motors that have mechanically connected.
621
(2.6.4.11)
626
(2.6.4.5)
Sets the inertia compensation to improve speed response during acceleration and
deceleration. The time is defined as acceleration time to nominal speed with nominal
torque. Used when inertia of system is known to achieve best speed accuracy when
reference is changed
(2 f nom )
2 f nom
AccelCompensationTC = J
=J
,
Pnom
Tnom
2
apfiff08 Advanced
627
vacon 85
(2.6.4.7)
Defines current that is applied to motor when start command is given in closed loop
control. On start this parameter is used together with Magnetizing time at start (ID628)
to decrease time when motor is able to produce maximum torque.
628
(2.6.4.8)
Defines time how long magnetization curren (ID627) in start is applied to motor.
Magnetizing curren at start is used in order to premagnetize motor before running. This
will improve torque performance at start. Needed time is depending on motor size, value
varies between 100 ms to 3 second. Bigger motor needs more time. Set this time so that
RotorFlux is more than 90 % before speed is released (Start Zero Speed Time ID615)
or mechanical brake is released.
86 vacon
631
apfiff08 Advanced
Identification
(2.6.2)
Identification Run is a part of tuning the motor and the drive specific parameters. It is a
tool for commissioning and service of the drive with the aim to find as good parameter
values as possible for most drives. The automatic motor identification calculates or
measures the motor parameters that are needed for optimum motor and speed control.
0 = No action
No identification requested.
1 = Identification without motor run
The drive is run without speed to identify the motor parameters. The motor is supplied
with current and voltage but with zero frequency. U/f ratio is identified.
2 = Identification with motor run
The drive is run with speed to identify the motor parameters. U/f ratio and magnetization
current is identified.
Note: It is required to do the this identification run with no load on the motor shaft for
accurate results.
3 = Encoder identification run
For PMS motor drive will make angle identification run when absolute encoder is in use.
4 = PMSM Identification run
All identification runs are made
5 = Identification failed
This value is stored if identification has faild
The basic motor name plate data has to be set correctly before performing the identification run:
ID110
ID111
ID112
ID113
ID120
When in closed loop and with an encoder installed, also the parameter for pulses /
revolutions (in Menu M7) has to be set.
The automatic identification is activated by setting this parameter to the appropriate
value followed by a start command in the requested direction. The start command to the
drive has to be given within 20 s. If no start command is given within 20 s the identification run is cancelled and the parameter will be reset to its default setting. The identification run can be stopped any time with normal stop command and the parameter is
reset to its default setting. In case identification run detects fault or other problems, the
identification run is completed if possible. After the identification is finished, the application checks the status of the identification and generates fault/ warning if any.
During Identification Run, the brake control is disabled (see chapter 6.1).
Note: After identification is made drive requires rising edge of start command.
Tel. +358 (0)201 2121 Fax +358 (0)201 212 205
apfiff08 Advanced
633
vacon 87
(2.6.4.12)
Sets the start-up torque for forward direction if selected with pararameter Startup
Torque (ID621).
634
(2.6.4.13)
Sets the start-up torque for reverse direction if selected with pararameter Startup
Torque (ID621).
636
(2.10.7)
Defines the frequency limit below which the frequency converter operates in frequency
control mode.
Because of the nominal slip of the motor, the internal torque calculation is inaccurate at
low speeds where is it recommended to use the frequency control mode.
637
(2.6.3.12)
Defines the P gain for the speed controlled in Open Loop control mode.
638
(2.6.3.13)
Defines the I gain for the speed controlled in Open Loop control mode.
639
(2.10.8)
Defines the Integration gain of the torque controller. When motor control mode is open
loop torque control.
640
(2.10.9)
Defines the Integration gain of the torque controller on open loop control mode.
641
(2.10.3)
642
643
(2.10.4)
(2.10.5)
Scale the custom minimum and maximum levels for analogue inputs within
-300,0300,0%.
88 vacon
644
apfiff08 Advanced
(2.10.7)
With this parameter the maximum frequency for the torque control can be selected.
0 Maximum frequency, par. ID102
1 Selected frequency reference
2 Preset speed 7, par. ID130
NXP drives have more selections for this parameter in Closed Loop control.
See page 108.
645
646
(2.6.4.21)
(2.6.4.22)
649
(2.6.4.3)
Identified shaft position. Updated when making encoder identification run with absolute
encoder.
650
Motor Type
(2.1.23)
651
Flux Current Kp
(2.6.5.1)
Defines the gain for the flux current controller when a PMS motor is used.
652
Flux Current Ti
(2.6.5.2)
Defines the integration time for the flux current controller when a PMS motor is used.
654
655
(2.6.4.5)
This parameter can be used to control how the drive modulates the output
voltage. Reducing this value limits the maximum output voltage. If a sinusoidal filter
is used set this parameter to 96%.
656
apfiff08 Advanced
658
vacon 89
662
(2.6.5.18)
The measured voltage drop at stator resistance between two phases with the nominal
current of the motor. This parameter is identified durin ID run. Adjust this value to gain
optimum torque calculation for open loop low frequencies.
664
(2.6.5.20)
Defines how much voltage is applied to motor in zero speed when torque boost is used.
665
(2.6.5.21)
Defines scaling factor for generator side IR-compensation when torque boost is used
667
(2.6.5.22)
Defines scaling factor for motoring side IR-compensation when torque boost is used
668
669
670
IU Offset
IV Offset
IW Offset
(2.6.5.23)
(2.6.5.24)
(2.6.5.25)
672
(2.6.3.35)
The delay time within which the drive can not be restarted if flying start is used or in
closed loop control mode. The time can be set up to 60.000 seconds.
673
674
90 vacon
700
apfiff08 Advanced
(2.7.1)
0 = No response
1 = Warning
2 = Warning, the frequency from 10 seconds back is set as reference
3 = Warning, the Preset Frequency (Par. ID728) is set as reference
4 = Fault, stop mode after fault according to ID506
5 = Fault, stop mode after fault always by coasting
A warning or a fault action and message is generated if the 420 mA reference signal
is used and the signal falls below 3.0 mA for 5 seconds or below 0.5 mA for 0.5 seconds.
The information can also be programmed into digital output DO1 or relay outputs RO1
and RO2.
701
(2.7.3)
= No response
= Warning
= Fault, stop mode after fault according to ID506
= Fault, stop mode after fault always by coasting
A warning or a fault action and message is generated from the external fault signal
in the programmable digital inputs DIN3 or with ID405 and ID406. The information can
also be programmed into digital output DO1 and into relay outputs RO1 and RO2.
702
(2.7.6)
= No response
= Warning
= Fault, stop mode after fault according to ID506
= Fault, stop mode after fault always by coasting
Output phase supervision of the motor ensures that the motor phases have an
approximately equal current.
703
(2.7.7)
= No response
= Warning
= Fault, stop mode after fault according to ID506
= Fault, stop mode after fault always by coasting
Earth fault protection ensures that the sum of the motor phase currents is zero. The
overcurrent protection is always working and protects the frequency converter from
earth faults with high currents.
apfiff08 Advanced
704
vacon 91
(2.7.8)
= No response
= Warning
= Fault, stop mode after fault according to ID506
= Fault, stop mode after fault always by coasting
If tripping is selected the drive will stop and activate the fault stage.
Deactivating the protection, i.e. setting parameter to 0, will reset the thermal stage of
the motor to 0%. See chapter 6.3.
705
(2.7.9)
706
(2.7.10)
Defines cooling factor in zero speed related to point where motors in running nominal
speed without external cooling. See Figure 5-28.
The default value is set assuming that there is no external fan cooling the motor. If an
external fan is used this parameter can be set to 90% (or even higher).
Note: The value is set as a percentage of the motor name plate data, par. ID113
(Nominal current of motor), not the drive's nominal output current. The motor's nominal
current is the current that the motor can withstand in direct on-line use without being
overheated.
If you change the parameter Nominal
current of motor, this parameter is
automatically restored to the default
value.
Setting this parameter does not affect
the maximum output current of the
drive which is determined by parameter
Current Limit (ID107) alone.
See chapter 6.3.
cooling
Overload area
100%
IT
Par.
ID706=40%
fn
NX12k62
92 vacon
707
apfiff08 Advanced
(2.7.11)
708
(2.7.12)
Motor temperature
Trip area
105%
Motor
current
Fault/warning
par. ID704
I/IT
*)
Time constant T
Motor temperature
= (I/IT)2 x (1-e-t/T)
Time
NX12k82
709
Stall protection
0
1
2
3
(2.7.13)
= No response
= Warning
= Fault, stop mode after fault according to ID506
= Fault, stop mode after fault always by coasting
Setting the parameter to 0 will deactivate the protection and reset the stall time counter.
See chapter 6.4.
apfiff08 Advanced
710
vacon 93
(2.7.14)
Stall area
Par. ID710
Par. ID712
NX12k63
711
Stall time
(2.7.15)
Stall time counter
Trip area
Par. ID711
Trip/warning
par. ID709
Time
Stall
No stall
NX12k64
712
(2.7.16)
713
Underload protection
0
1
2
3
(2.7.17)
= No response
= Warning
= Fault, stop mode after fault according to ID506
= Fault, stop mode after fault always by coasting
If tripping is set active the drive will stop and activate the fault stage.
Deactivating the protection by setting the parameter to 0 will reset the underload time
counter to zero. See chapter 6.5.
94 vacon
714
apfiff08 Advanced
(2.7.18)
Torque
Par. ID714
Par. ID715
Underload area
f
5 Hz
Fieldweakening
point par. ID602
NX12k65
715
(2.7.19)
apfiff08 Advanced
716
vacon 95
Underload time
(2.7.20)
Par. ID716
Trip/warning
par. ID713
Time
Underload
No underl.
NX12k66
96 vacon
717
apfiff08 Advanced
(2.8.1)
Defines the time before the frequency converter tries to automatically restart the motor
after the fault trig has been appeared inside trial time.
718
(2.8.2)
If the fault trig appears more than defines by parameters ID720 to ID725 inside trial time
permanent fault is generated.
Wait time
Par.ID717
Wait time
Par.ID717
Wait time
Par.ID717
Fault trigger
Restart 2
Trial time
Par. ID718
Fault active
RESET/
Fault reset
NX12k67
Parameters ID720 to ID725 determine the maximum number of automatic restarts during the trial time set by parameter ID718. The time count starts from the first autorestart. If the number of faults occurring during the trial time exceeds the values of
parameters ID720 to ID725 the fault state becomes active. Otherwise the fault is cleared
after the trial time has elapsed and the next fault start the trial time count again.
If a single fault remains during the trial time, a fault state is true.
719
(2.8.3)
The Start function for Automatic restart is selected with this parameter. The parameter
defines the start mode:
0 = Start with ramp
1 = Flying start
2 = Start according to ID505
apfiff08 Advanced
720
vacon 97
(2.8.4)
This parameter determines how many automatic restarts can be made during the trial
time set by parameter ID718 after and undervoltage trip.
0
>0
721
= No automatic restart
= Number of automatic restarts after undervoltage fault. The fault is
reset and the drive is started automatically after the DC-link voltage
has returned to the normal level.
(2.8.5)
This parameter determines how many automatic restarts can be made during the trial
time set by parameter ID718 after an overvoltage trip.
0
>0
722
(2.8.6)
723
(2.8.7)
This parameter determines how many automatics restarts can be made during the trial
time set by ID718.
0
>0
725
(2.8.9)
This parameter determines how many automatics restarts can be made during the trial
time set by ID718.
0
>0
726
(2.8.8)
This parameter determines how many automatics restarts can be made during the trial
time set by ID718.
0
>0
98 vacon
727
apfiff08 Advanced
(2.7.5)
728
(2.7.2)
If the value of parameter ID700 is set to 3 and the 4mA fault occurs then the frequency
reference to the motor is the value of this parameter.
730
(2.7.4)
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to ID506
3 = Fault, stop mode after fault always by coasting
The input phase supervision ensures that the input phases of the frequency converter
have an approximately equal current.
731
Automatic restart
(2.20)
732
Overcurrent (F1)
Overvoltage (F2)
Undervoltage (F9)
Frequency converter overtemperature (F14)
Motor overtemperature (F16)
Reference fault (F50)
(2.7.21)
= No response
= Warning
= Fault, stop mode after fault according to ID506
= Fault, stop mode after fault always by coasting
733
(2.7.22)
Set here the response mode for the fieldbus fault if active control place is fieldbus. For
more information, see the respective Fieldbus Board Manual.
See parameter ID732.
Tel. +358 (0)201 2121 Fax +358 (0)201 212 205
apfiff08 Advanced
734
vacon 99
(2.7.23)
Set here the response mode for a board slot fault due to missing or broken board.
See parameter ID732.
738
(2.8.10)
This parameter determines how many automatic restarts can be made during the trial
time set by parameter ID718.
0
>0
739
(2.7.24)
If you have a PT100 input board installed in your frequency converter you can choose
here the number of PT100 inputs in use. See also the Vacon I/O boards manual.
0 = Not used (ID Write)
1 = PT100 input 1
2 = PT100 input 1 & 2
3 = PT100 input 1 & 2 & 3
4 = PT100 input 2 & 3
5 = PT100 input 3
Note: If the selected value is greater than the actual number of used PT100 inputs, the
display will read 200C. If the input is short-circuited the displayed value is 30C.
740
741
(2.7.25)
= No response
= Warning
= Fault, stop mode after fault according to ID506
= Fault, stop mode after fault always by coasting
(2.7.26)
Set here the limit at which the PT100 warning (W56) will be activated.
742
(2.7.27)
Set here the limit at which the PT100 fault (F56) will be activated.
743
745
746
100 vacon
750
Cooling monitor
apfiff08 Advanced
(2.2.7.25)
When using a liquid-cooled drive, connect this input to the Cooling OK signal from Vacon
flow control application or any input that shows state of used cooling unit. Fault is
generated if input is low when drive is in run state, while drive is in stop state only
warning is generated. See product user manual of liquid-cooled drive.
751
752
(2.7.33)
Defines fault function when speed reference and encoder speed over set limits.
0 = No response
1 = Warning
2 = Fault, stop mode after fault always by coasting
753
(2.7.34)
Defines limit when fault situation is noted. Difference between speed reference and
encoder speed.
754
(2.7.35)
755
756
apfiff08 Advanced
850
851
vacon 101
(2.9.1)
(2.9.2)
852 to
859
(2.9.3 to 2.9.10)
Using these parameters, you can monitor any monitoring or parameter value from the
fieldbus. Enter the ID number of the item you wish to monitor for the value of these
parameters. See chapter 6.6.
See monitoring signals for full detail of ID numbers
Some typical values:
1
Output frequency
2
Motor speed
3
Motor current
4
Motor torque
5
Motor power
6
Motor voltage
7
DC link voltage
8
Unit temperature
9
Motor temperature
13
AI1
14
AI2
15
16
17
25
26
27
28
31
32
37
45
Table 5-10.
876 to
883
102 vacon
apfiff08 Advanced
896
Fieldbus profile
With this parameter its possible to select what FB profile is used in application.
1 = ProfiDrive
2 = ByPass See table 5-11
3 = Reserved
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
897
Description
Value = 0
Value = 1
OFF
ON, Reset after Fault or b1 and b2
Emergency stop by coast ON, On normal operation: Keep TRUE
Emergency stop by ramp ON, On normal operation: Keep TRUE
STOP REQUEST
RUN REQUST
Force ramp to Zero
Enable Ramp,
Freeze Ramp
Enable Ramp,
Force Ref to Zero
Enable Ramp,
No Action
FAULT RESET (0 -> 1)
No Action
No Action
No Action
No Action
Disable Profibus control
Enable Profibus control
Fieldbus DIN1=OFF
Fieldbus DIN1=ON (Watchdog pulse)
Fieldbus DIN2=OFF
Fieldbus DIN2=ON
Fieldbus DIN3=OFF
Fieldbus DIN3=ON
Fieldbus DIN4=OFF
Fieldbus DIN4=ON
No Action
No Action
Table 5-11.Profibus Control Word in ByPass Mode
apfiff08 Advanced
898
899
vacon 103
With these parameter its possible to define what inputs levels corresponds minimum
and maximum frequency references.
104 vacon
1080
apfiff08 Advanced
(2.4.15)
Defines the current injected to the motor in stop state when parameter ID416 is active.
1081
(2.11.3)
2
3
AI1AI2
AI2AI1
0
1
AI1*AI2
AI1 joystick
AI2 joystick
Fieldbus reference
11
12
10
14
15
13
17
18
16
1082
Function
Analogue input 1 (AI1). See ID377
Terminals 2-3
Anlogue input 2 (AI2). See ID388
Terminals 4-5
AI1+AI2
Comment
(2.7.30)
1083
= No response
= Warning
= Fault, stop mode after fault according to ID506
= Fault, stop mode after fault always by coasting
(2.11.4)
apfiff08 Advanced
1084
Control options
vacon 105
(2.4.22)
These parameter functions are dependent of the Vacon Advanced application version.
b0 = Reserved
b1 = Update Ramp Generator when MotorControlMode changes from TC (4) to SC (3)
b2 = RampUp; use acceleration ramp with TC
b3 = RampDown; use deceleration ramp with TC
b4 = FollowActual; follow actual speed value within WindowPos/NegWidth with TC
b5 = TC ForceRampStop; Under stop request the speed limit forces the motor to stop
b6 = Reserved
b7 = Disables switching frequency decrease
b8 = Reserved
b9 = Reserved
b10=Reserved
b11= Force LoadDrooping to Zero when reference is below Zero freq. Limit
b12= Disable Slot A filtering, DI and AI will work in 1 ms time level.
B13 +8192 = Reserved
B14 +16384 = Reserved
B15 +32768 = Reserved
1085
(2.3.4.16)
If motor current falls below this value the brake is closed immediately.
1086
(2.7.32)
When this parameter is activated it is possible to adjust the parameters that are
normally locked during RUN state. May be used by Vacon personnel only.
1087
(2.2.6.6)
= Parameter
= AI1
= AI2
= AI3
= AI4
= FB Limit Scaling
This signal will adjust the maximum motor generating torque between 0 and maximum
limit set with parameter Generator Torque Limit (ID1288). Analogue input level zero
means zero generator torque limit.
106 vacon
1088
apfiff08 Advanced
(2.2.6.8)
Parameter
AI1
AI2
AI3
AI4
FiledBus Scaling
This signal will adjust the maximum motor generating power between 0 and maximum
limit set with parameter Generator Power Limit (ID1290). Analogue input level zero
means zero generator power limit.
1089
(2.11.2)
Defines how the follower drive stops. When reference is not Master Ramp.
0 Coasting, follower remains in control even if master has stopped at fault.
1 Ramping, follower remains in control even if master has stopped at fault.
2 As master; follower behaves as master.
1090
(2.2.7.29)
Resets the monitoring values Shaft Angle (ID1169) and Shaft Rounds (ID1170) to zero.
1091
Inversion control
(2.4.23)
With this control word it is possible to invert some input and output signals.
b0 Delayed digital outputs 1 signals are inverted
b1 Delayed digital outputs 2 signals are inverted
1092
(2.2.7.31)
Select the digital input to activate the second Master Follower mode selected by
parameter ID1093.
1093
(2.11.7)
Select Master Follower mode 2 that is used when the DI activated. When Follower is
selected the Run Request command is monitored from Master and all other references
are selectable by parameters.
0
1
2
3
4
Single Drive
Master
Follower
Current Master
Current Follower
apfiff08 Advanced
1209
vacon 107
(2.2.7.32)
Select the digital input to acknowledge the status of the input switch. The input switch
is normally a switch fuse unit or main contactor with which the power is fed to the
drive. If the input switch acknowledgement is missing, drive trips at Input switch open
fault (F64).
1210
(2.2.7.23)
Connegt this input signal to auxiliary contact of mechanical brake. If contact is not
closed within given time (ID1317) when brake is open the drive will generate a brake
fault F58.
1213
Emergency stop
(2.2.7.30)
Indicates to the drive that machine has been stop by external emergency stop circuit..
When the digital input is low the drive stops as per the parameter definition of ID1276
Emergency stop mode and indicates warning code A63.
1216
1218
Charge DC link
(2.3.3.29)
Charge DC. Used to charge the inverter drive through OEVA type of input switch. When
the DC link voltage is above the charging level a 2-second pulse train is generated to
close the input switch. The pulse train is OFF when the input switch acknowledgement
goes high.
1239
1240
Inching reference 1
Inching reference 2
(2.4.16)
(2.4.17)
1241
Speed share
(2.11.5)
Defines the percentage for final speed reference from received speed reference.
1244
(2.10.10)
1248
Load Share
(2.11.6)
Defines the percentage for final torque reference from received torque reference.
1250
Flux reference
(2.6.3.32)
108 vacon
1252
apfiff08 Advanced
Speed step
(2.6.5.26)
NCDrive parameter to help adjusting the speed controller. See NCDrive Tools: Step
Response. With this tool you can give step to speed reference after ramp control.
1253
Torque step
(2.6.5.27)
NCDrive parameter to help adjusting the torque controller. See NCDrive Tools: Step
Response. With this tool you can give step to torque reference.
1257
Inching ramp
This parameter defines acceleration and deceleration times when inching is active
1262
(2.4.19)
1267
(2.4.20)
400*1.35*1.18 = 638V
500*1.35*1.18 = 808V
690*1.35*1.18 = 1100V
Please note that when brake chopper is used the overvoltage controller can be switched
off or the overvoltage reference level can be set above the brake chopper level.
1276
(2.4.21)
1278
apfiff08 Advanced
1283
vacon 109
1285
(2.6.3.15)
Maximum frequency limit for the drive. Speed is limted here recardles of limit functions.
1286
(2.6.3.14)
Minimum frequency limit for the drive. Speed is limted here recardles of limit functions.
1287
(2.6.3.17)
1288
(2.6.3.16)
1289
(2.6.4.20)
Defines the maximum motoring side power limit. Only for Closed Loop control.
1290
(2.6.4.19)
Defines the maximum generating side power limit. Only for Closed Loop control.
1316
(2.7.28)
1317
(2.7.29)
The delay before the brake fault is activated F58. Used when there is mechanical delay in
the brake. See External Brake acknowledge (ID1210).
1324
Master/Follower selection
(2.11.1)
Select Master/Follower mode. When the value Follower is selected the Run Request
command is monitored from Master. All other references are selectable by parameters.
0 = Single Drive
1 = Master
2 = Follower
1333
110 vacon
1352
apfiff08 Advanced
(2.7.31)
1353
(2.7.36)
Defines function when econder signal is missing in closed loop control mode.
0 = No response
1 = Warning
2 = Fault, stop mode after fault always by coasting
1354
FB Watchdog Delay
This defines delay when fault is generated when watchdog pulse is missing. Zero will
disable monitoring.
1355 to
1369
Flux 10150%
Motor voltage corresponding to 10%.150%c of flux as a percentage of Nominal
Flux voltage. Measured during identification.
apfiff08 Advanced
1401
vacon 111
(2.6.4.24)
The amount of flux as a percentage of the motor nominal flux maintained in the motor
after the drive is stopped. The flux is maintained for the time set by parameter ID1402.
This parameter can be used in closed loop motor control mode only.
1402
(2.6.4.23)
The flux defined by parameter ID1401 is maintained in the motor for the set time after
the drive is stopped. This function is used to shorten the time before full motor torque is
available.
0 No flux after the motor is stopped.
>0 The flux off delay in seconds.
<0 The flux is maintained in the motor after stop untill the next run request is given to
the drive.
Note: For mechanical brake control logic Flux Off Delay is same as Run State. It is
recommended to activate Frequency supervision ON limit for brake control ID315.
1412
1413
1414
1420
Prevention of startup
(2.2.7.24)
This parameter is enabled when the Prevention of start circuit is used to inhibit the
gate pulses.
1424
Restart delay
(2.4.14)
The delay time within which the drive can not be restarted after the coast stop and flying
start is not in use. Closed Loop control mode and flying start uses different delay see
ID672 The time can be set up to 60.000 seconds.
1440
= All slots
= Slot D
= Slot E
= Slot D, Fast profibus support.
= Slot E, Fast profibus support.
112 vacon
5.1
apfiff08 Advanced
Gain -%
SpeedControl_Kp_FW
100 %
SpeedControl_Kp_f0
f
W
SpeedControl_f0
SpeedControl_f1
FieldWeakeningPoint
1295
(2.6.4.30)
The relative gain as a percentage of ID613 of the speed controller when the torque reference or the speed control output is less than the value of par. ID1296. This parameter is
normally used to stabilise the speed controller for a drive system with gear backlash.
1296
(2.6.4.29)
The level of torque reference or speed controller output which the speed controller gain
is changed to ID1295 through a filter set by ID1297. This is in percentage of motor nominal torque.
1297
(2.6.4.31)
Filtering time for torque. When the speed controller gain is changed between ID613 and
ID1295 depending on ID1296.
1298
(2.6.4.28)
The relative gain of the speed controller in the field weakening area as a percentage of
par. ID613.
1299
(2.6.4.27)
The relative gain of the speed controller as a percentage of par. ID613 when the speed is
below the level defined by ID1300.
apfiff08 Advanced
1300
vacon 113
(2.6.4.26)
The speed level in Hz below which the speed controller gain is equal to par. ID1299.
1301
(2.6.4.25)
The speed level in Hz above which the speed controller gain is equal to par. ID613. From
the speed defined by par. ID1300 to speed defined by par. ID1301, the speed controller
gain changes linearly from par. ID1299 to ID613 and vice versa.
1304
Window positive
(2.10.12)
Defines size of window to positive direction from the final speed reference.
1305
Window negative
(2.10.11)
Defines size of window to negative direction from the final speed reference.
1306
(2.10.14)
Defines speed controller positive off limit when the speed controller brings speed back
to window.
1307
(2.10.13)
Defines speed controller negative off limit when the speed controller brings speed back
to window.
1509
AI3 Controlled ID
1510
AI4 Controlled ID
With this parameter its possible to control any parameter by analogue input 3 and/or 4.
Controlled value range is from -32000 to 32000.
Example:
You want to control motor field weakening point voltage by analogue input from 70,00 %
to 130,00 %.
Set ID 1037 AI3 Scale min to 7000
Set ID 1038 AI3 Scale max to 13000
Set ID 1509 AI3 Controlled ID to 603
Now analogue input 3 signal 0 V to 10 V (0 mA to 20 mA) will control field weakening
point voltage between 70,00 % - 130,00 %. When setting value, decimals are handled as
integer.
1311
(2.6.3.33)
Filter time constant for speed reference and actual speed error. May be used to remove
small disturbance from encoder signal.
1382
(2.10.15)
The maximum torque limit for the speed controller output as a percentage of the motor
nominal torque.
24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com
114 vacon
1505
I/O Reference 2
apfiff08 Advanced
(2.2.1.7)
If ID117 I/O reference 1 value is different than 14 (AI1/AI2 selection). Digital input ID422
AI1/AI2 selection will change reference between ID117 I/O Reference 1 and ID1505 I/O
Reference 2. If ID117 I/O reference 1 value is 14 reference signal is changed between AI1
and AI2.
1506
1507
1509
AI3 Controlled ID
1510
AI4 Controlled ID
With this parameter its possible to control any parameter by analogue input 3 and/or 4.
Controlled value range is from -32000 to 32000.
Example:
You want to control motor field weakening point voltage by analogue input from 70,00 %
to 130,00 %.
Set ID 1037 AI3 Scale min to 7000
Set ID 1038 AI3 Scale max to 13000
Set ID 1509 AI3 Controlled ID to 603
Now analogue input 3 signal 0 V to 10 V (0 mA to 20 mA) will control field weakening
point voltage between 70,00 % - 130,00 %. When setting value, decimals are handled as
integer.
1511
1512
1515
1516
Modulator Normal
Parameter for changing modulator type when induction motor is used.
Tel. +358 (0)201 2121 Fax +358 (0)201 212 205
apfiff08 Advanced
1517
vacon 115
Modulator PM Inc
Parameter for changing modulator type when PMS motor is used with incremental
encoder.
1518
1519
1520
(2.3.8.2)
This parameter selects the desired function for the analogue output signal.
Function
Selection
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1521
Not used
Output freq. (0fmax)
Freq. reference (0fmax)
Motor speed (0Motor
nominal speed)
Output current (0-InMotor)
Motor torque (0TnMotor)
Motor power (0PnMotor)
Motor voltage (0-UnMotor)
DC-link volt (01000V)
AI1
AI2
Output freq. (fmin - fmax)
Motor torque
Motor power
PT100 temperature
FB analogue output
ProcessData4 (NXS)
(2.3.8.3)
1522
(2.3.8.4)
1523
(2.3.8.5)
1525
(2.3.8.6)
Scaling factor for analogue output. Value of 200 % will double the output . See ID311.
116 vacon
1524
apfiff08 Advanced
(2.3.8.7)
Add 100.0 to 100.0% to the analogue output signal. E.g. 50 % adds 10 mA or 5 V to basic
signal. See ID375.
1527
(2.3.8.1)
Connect the AO4 signal to the analogue output of your choice with this parameter. For
more information about the TTF programming method, see chapter 3.
1528
1534
Brak Logic
Use this parameter to select brake control logic
0 = Multi-Purpose brake control logic
Parameters in Group G2.3.4 are used for brake control
1 = Smooth brake control logic
Parameters in Group G2.3.8 are used for brake control
See ID numbers from 1535 to 1555.
1535
1539
1540
1544
1555
apfiff08 Advanced
1557
vacon 117
1560
1561
1562
1563
AdvancedOptions 1
AdvancedOptions 2
AdvancedOptions 3
AdvancedOptions 4
Contact factory before changing.
1570
1571
DIN Controlled ID
Select parameter ID that is controlled by ID1570.
1572
1573
1574
118 vacon
5.2
apfiff08 Advanced
Unlike the parameters listed above, these parameters are located in the M3 menu of the control
keypad. The reference parameters do not have an ID number.
114
(3.4, 3.6)
If you wish to make the Stop button a "hotspot" which always stops the drive regardless
of the selected control place, give this parameter the value 1.
See also parameter ID125.
125
Control Place
(3.1)
The active control place can be changed with this parameter. For more information, see
the product's User's Manual.
Pushing the Start button for 3 seconds selects the control keypad as the active control
place and copies the Run status information (Run/Stop, direction and reference).
0 = PC Control, Activeted by NCDrive
1 = I/O terminal
2 = Keypad
3 = Fieldbus
123
Keypad Direction
(3.3)
Forward: The rotation of the motor is forward, when the keypad is the active
control place.
Reverse: The rotation of the motor is reversed, when the keypad is the active
control place.
R3.2
Keypad Reference
(3.2)
The frequency reference can be adjusted from the keypad with this parameter.
The output frequency can be copied as the keypad reference by pushing the Stop button
for 3 seconds when you are on any of the pages of menu M3. For more information, see
the product's User's Manual.
R3.5
Torque reference
(3.5)
Appendices
6.
vacon 119
APPENDICES
In this chapter you will find additional information on special parameter groups. Such groups are:
6.1
External brake control with additional limits (IDs 315, 316, 346 to 349, 352, 353)
6.1.1
The external brake used for additional braking can be controlled through parameters ID315, ID316,
ID346 to ID349 and ID352/ID353. Selecting On/Off Control for the brake, defining the frequency or
torque limit(s) the brake should react to and defining the Brake-On/-Off delays will allow an effective
brake control. See Figure 6-1.
Note: During Identification Run (see par. ID631), brake control is disabled.
Torque limit
ID349
Frequency limit
ID347
START
STOP
Brake off
Brake on
Brake-off
delay;
ID352
Brake-on delay;
ID353
NX12k115.fh8
In Figure 6-1 above, the brake control is set to react to both the torque supervision limit (par. ID349)
and frequency supervision limit (ID347). Additionally, the same frequency limit is used for both
brake-off and brake-on control by giving parameter ID346 the value 4. Use of two different frequency
limits is also possible. Then parameters ID315 and ID346 must be given the value 3.
24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com
120 vacon
Appendices
Brake-off: In order for the brake to release, three conditions must be fulfilled: 1) the drive must be
in Run state, 2) the torque must be over the set limit (if used) and 3) the output frequency must be
over the set limit (if used).
Brake-on: Stop command activates the brake delay count and the brake is closed when the output
frequency falls below the set limit (ID315 or ID346). As a precaution, the brake closes when the
brake-on delay expires, at the latest.
Note: A fault or Stop state will close the brake immediately without a delay.
See Figure 6-2.
It is strongly advisable that the brake-on delay be set longer than the ramp time in order to
avoid damaging of the brake.
No brake-off control
ID346
0-2
3
4
TRUE
Output frequency ID347
ID348
0-2
3-4
No brake-off control
0-2
Brake-off ctrl,
torque limit
TRUE
Motor torque ID349
AND
OFFDELAY
COUNT
0-2
3
Brake off
Brake on
Run state
NOT
ONDELAY
COUNT
No Run request
Reversing
No run request
OR
No brake-on control
0-2
No brake-on control
0-3
ID315
AND
OR
OR
ID346
4
4
ID316
0-3
ID347
Output frequency
Fault
NX12k114.fh8
Note: Operation of brake control is different when using master follower function or smooth brake
function. When using Master Follower function follower drive will open the brake when Master will
even if Follower conditions to open the brake have not been met.
6.1.2
When selection Smooth brake logic parameters in the group G2.3.8 are used fro brake control.
Main difference for Multi-Purpose logic is that speed is limited to certain level when brake is closed.
Appendices
6.2
vacon 121
Select the Closed loop control mode by setting value 3 or 4 for parameter ID600.
Closed loop control mode (see page 81) is used when enhanced performance near zero speed and
better static speed accuracy with higher speeds are needed. Closed loop control mode is based on
"rotor flux oriented current vector control". With this controlling principle, the phase currents are
divided into a torque producing current portion and a magnetizing current portion. Thus, the squirrel
cage induction machine can be controlled in a fashion of a separately excited DC motor.
Note: These parameters can be used with Vacon NXP drive only.
EXAMPLE:
Motor Control Mode = 3 (Closed loop speed control)
This is the usual operation mode when fast response times, high accuracy or controlled
run at zero frequencies are needed. Encoder board should be connected to slot C of the
control unit. Set the encoder P/R-parameter (P7.3.1.1). Run in open loop and check the
encoder speed and direction (V7.3.2.2). Switch the encoder wiring or the phases of motor
cables if necessary. Do not run if encoder speed is wrong. Program the no-load current to
parameter ID612 or make ID run without load on motor shaft and set parameter ID619 (Slip
Adjust) to get the voltage slightly above the linear U/f-curve with the motor frequency at
about 66% of the nominal motor frequency. The Motor Nominal Speed parameter (ID112) is
critical. The Current Limit parameter (ID107) controls the available torque linearly in
relative to motor nominal current.
6.3
General
The motor thermal protection is to protect the motor from overheating. The Vacon drive is capable of
supplying higher than nominal current to the motor. If the load requires this high current there is a
risk that the motor will be thermally overloaded. This is the case especially at low frequencies. At
low frequencies the cooling effect of the motor is reduced as well as its capacity. If the motor is
equipped with an external fan the load reduction at low speeds is small.
The motor thermal protection is based on a calculated model and it uses the output current of the
drive to determine the load on the motor.
The motor thermal protection can be adjusted with parameters. The thermal current IT specifies the
load current above which the motor is overloaded. This current limit is a function of the output
frequency.
The thermal stage of the motor can be monitored on the control keypad display V1.10 ID9. See the
product's User's Manual.
CAUTION!
The calculated model does not protect the motor if the airflow to the
motor is reduced by blocked air intake grill.
122 vacon
6.4
Appendices
General
The motor stall protection protects the motor from short time overload situations such as one
caused by a stalled shaft. The reaction time of the stall protection can be set shorter than that of
motor thermal protection. The stall state is defined with two parameters, ID710 (Stall current) and
ID712 (Stall frequency limit). If the current is higher than the set limit and output frequency is lower
than the set limit, the stall state is true. There is actually no real indication of the shaft rotation. Stall
protection is a type of overcurrent protection.
6.5
General
The purpose of the motor underload protection is to ensure that there is load on the motor when the
drive is running. If the motor loses its load there might be a problem in the process, e.g. a broken
belt or a dry pump.
Motor underload protection can be adjusted by setting the underload curve with parameters ID714
(Field weakening area load) and ID715 (Zero frequency load), see below. The underload curve is a
squared curve set between the zero frequency and the field weakening point. The protection is not
active below 5Hz (the underload time counter is stopped).
The torque values for setting the underload curve are set in percentage which refers to the nominal
torque of the motor. The motor's name plate data, parameter motor nominal current and the drive's
nominal current IH are used to find the scaling ratio for the internal torque value. If other than
nominal motor is used with the drive, the accuracy of the torque calculation decreases.
6.6
The Fieldbus control parameters are used when the frequency or the speed reference comes from
the fieldbus (Modbus, Profibus, DeviceNet etc.). With the Fieldbus Data Out Selection 18 you can
monitor values from the fieldbus.
Value
Output Frequency
Motor Speed
Motor Current
Motor Torque
Motor Power
Motor Voltage
DC link voltage
Active Fault Code
Unit
Hz
rpm
A
%
%
V
V
-
Scale
0,01 Hz
1 rpm
0,1 A
0,1 %
0,1 %
0,1 V
1V
-
The Advance application has a selector parameter for every Process Data. The monitoring values
and drive parameters can be selected using the ID number Default selections are as in the table
above.
Appendices
vacon 123
Data
Reference
ControlWord
Process Data IN1
Process Data IN2
Process Data IN3
PD3 PD8
Value
Speed Reference
Start/Stop Command
Fault reset Command
Torque Reference
Free Analogue INPUT
Adjust Input
Not Used
Unit
%
-
Scale
0.01%
-
%
%
%
-
0.1%
0.01%
0.01%
-
124 vacon
6.7
Appendices
Master/Follower function
The Master/Follower function is designed for applications in which the system is run by several NXP
drives and the motor shafts are coupled to each other via gearing, chain, belt etc. The NXP drives are
in closed loop control mode. Limited support for Open Loop is provided.
The external control Start/Stop signals are connected to the Master drive only. Speed and torque
references can be selected freely in follower drive. The Master controls the Follower(s) via a
SystemBus. The Master station is typically speed-controlled and the other drives follow its torque or
speed reference.
Torque control of the Follower should be used when the motor shafts of the Master and Follower
drives are coupled solidly to each other by gearing, a chain etc., so that no speed difference between
the drives is possible.
Speed control of the Follower should be used when the motor shafts of the Master and the
Follower drives are coupled flexibly to each other, so that a slight speed difference between the
drives is possible. When both the Master and the Followers are speed-controlled, drooping is
typically also used. Window control is recommended if speed is required to near each other..
6.7.1
The master drive is located on the left side and all others are followers (Figure 6-3 and 4). The
master/follower physical link can be built with OPT-D1 or OPT-D2 option boards.
OPT-D1 is used when there is need to change master driven on fly or follower drives need to send
data to other follower drives (Function is not supported by standard applications).
6.7.2
In this connection example, the leftmost device is the Master and the others are followers. Connect
the output 1 of Device 1 to the input 2 of Device 2 and the input of Device 1 to the output 2 of Device 2.
Note that in the end devices one terminal pair remains unused.
...
TX RX TX RX
1
1
2
2
TX RX TX RX
1
1
2
2
TX RX TX RX
1
1
2
2
TX RX TX RX
1
1
2
2
Figure 6-3. System bus physical connections with the OPT-D1 board
Appendices
6.7.3
vacon 125
In this connection example, the leftmost device is the Master and the others are followers. The OPTD2 board in the Master has the default jumper selections, i.e. X6:1-2, X5:1-2. For the followers, the
jumper positions have to be changed: X6:1-2, X5:2-3. In this board have also CAN communication
possibility what is useful when commissioning Master Follower functions or line systems.
...
R X
1
T X
1
R X
1
T X
2
R X
1
T X
2
R X
1
T X
2
Figure 6-4. System bus physical connections with the OPT-D2 board
6.7.4
SBCRCErrorCounter
Indicates the number of CRC-errors in the communication.
SBOk
Indicator: SystemBus working properly.
0=
1=
SBInUse
Parameter for activating SystemBus communication.
0 = Not in used
1 = Communication activated
SBId
Drive number in SystemBus line. Use 1 for Master or the same ID as in CAN line.
Follower drives use 2 or same ID as in CAN line.
SBNextId
Next Drive number in SystemBus line.
SBSpeed
Parameter for the selection of SystemBus speed. All drives need to have same speed.
24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com
126 vacon
Appendices
Fault codes
7.
vacon 127
FAULT CODES
The fault codes, their causes and correcting actions are presented in the table below. The shadowed
faults are A faults only. The items written in white on black background present faults for which you
can program different responses in the application. See parameter group Protections.
Note: When contacting distributor or factory because of a fault condition, always write down all texts
and codes on the keypad display.
Fault
code
1
Overcurrent
Overvoltage
Earth fault
Charging
switch
Emergency
stop
Saturation trip
Fault
Possible cause
Frequency converter has detected too
high a current (>4*IH) in the motor
cable:
sudden heavy load increase
short circuit in motor cables
unsuitable motor
Subcode in T.14:
S1 = Hardware trip
S2 = reserved
S3 = Current controller supervision
The DC-link voltage has exceeded the
drive limit. See User manual.
- Too short a deceleration time
- high overvoltage spikes in supply
Subcode in T.14:
S1 = Hardware trip
S2 = Overvoltage control supervision
Current measurement has detected that
the sum of motor phase current is not
zero.
insulation failure in cables or motor
The charging switch is open, when the
START command has been given.
faulty operation
component failure
Stop signal has been given from the
option board.
Various causes:
defective component
brake resistor short-circuit or
overload
Correcting measures
- Check loading.
- Check motor.
- Check cables.
- Make Identification run
128 vacon
Fault
code
8
System fault
Undervoltage
10
11
12
13
14
15
16
Fault
Input line
supervision
Output phase
supervision
Brake chopper
supervision
Fault codes
Possible cause
Correcting measures
- component failure
- faulty operation
Note exceptional fault data record
Subcode in T.14:
S1 = Reserved
S2 = Reserved
S3 = Reserved
S4 = Reserved
S5 = Reserved
S6 = Reserved
S7 = Charging switch
S8 = No power to driver card
S9 = Power unit communication (TX)
S10 = Power unit communication (Trip)
S11 = Power unit comm. (Measurement)
DC-link voltage is under the drive fault
voltage limit. See user manual.
most probable cause: too low a
supply voltage
frequency converter internal fault
One of input fuse is broken.
External charge switch have not
been closed.
Subcode in T.14:
S1 = DC-link too low during run
S2 = No data from power unit
S3 = Undervoltage control supervision
Input line phase is missing.
Subcode in T.14:
S1 = Phase supervision diode supply
S2 = Phase supervision active front end
Current measurement has detected that
there is no current in one motor phase.
no brake resistor installed
brake resistor is broken
brake chopper failure
Motor stalled
Motor overtemperature
Fault codes
Fault
code
17
18
Fault
Motor
underload
Unbalance
(Warning only)
22
EEPROM
checksum fault
24
Counter fault
25
Microprocessor
watchdog fault
26
Start-up
prevented
29
Thermistor
fault
31
IGBT
temperature
(hardware)
Fan cooling
32
34
35
37
38
39
40
41
CAN bus
communication
Application
Device changed
(same type)
Device added
(same type)
Device removed
Device
unknown
IGBT temperature
vacon 129
Possible cause
Correcting measures
Check load.
- Check loading.
- Check motor size.
- Make Identification run
130 vacon
Fault
code
43
Encoder fault
Possible cause
Correcting measures
44
Device changed
(different type)
45
Device added
(different type)
49
Div by zero in
application
50
Analogue input
Iin < 4mA (sel.
signal range 4
to 20 mA)
External fault
53
Keypad
communication
fault
Fieldbus fault
54
Slot fault
56
PT100 board
temp. fault
57
Identification
(Warning only)
58
Brake
59
60
Follower
Communication
Cooling
61
Speed Error
62
Run Disable
51
52
Fault
Fault codes
Reset
Set the option board parameters again if
option bard changed. Set converter
parameters again if power unit changed.
Reset
Set the option board parameters again.
Contact your distributor if fault accrues
while frequency converter is in run state.
If you are application programmer check
the application program.
Check the current loop circuitry.
Fault codes
Fault
code
63
64
Fault
Emergency
stop (Warning
only)
Input switch
open
vacon 131
Possible cause
Correcting measures
Vaasa
Vacon Oyj (Headquarters and Production)
Runsorintie 7, 65380 Vaasa
firstname.lastname@vacon.com
tel. +358 (0) 201 2121
fax: +358 (0) 201 212 205
Helsinki
Vacon Oyj
yritie 12, 01510 Vantaa
tel. +358 (0)201 212 600
fax: +358 (0)201 212 699
Tampere
Vacon Oyj
Alasniitynkatu 30, 33700 Tampere
tel. +358 (0)201 2121
fax: +358 (0)201 212 750
Rotatek Finland Oy
Laserkatu 6, 53850 Lappeenranta
tel. +358 (0)5 6243 870
fax: +358 (0)5 6243 871
Vacon Traction Oy
Alasniitynkatu 30, 33700 Tampere
tel. +358 (0)201 2121
fax: +358 (0)201 212 710
Italy
Vacon S.p.A.
Via F.lli Guerra, 35
42100 Reggio Emilia
info@vacon.it
tel. +39 0522 276811
fax: +39 0522 276890
Belgium
Vacon Benelux NV/SA
Interleuvenlaan 62
3001 Heverlee (Leuven)
info@vacon.be
tel. +32 (0)16 394 825
fax: +32 (0)16 394 827
The Netherlands
Vacon Benelux BV
Weide 40, 4206 CJ Gorinchem
vacon.benelux@vacon.com
tel. +31 (0)183 642 970
fax: +31 (0) 183 642 971
France
Vacon France s.a.s.
Batiment le Sextant
462 rue Benjamin Delessert
Zl de Moissy Cramayel
BP 83
77 554 Moissy Cramayel
www.vacon-france.fr
tel. +33 (0)1 64 13 54 11
fax: +33 (0)1 64 13 54 21
Germany
Vacon GmbH
Gladbecker Str. 425
45329 Essen
tel. +49 (0)201/80670-0
fax: +49 (0)201/80670-93
Great Britain
Vacon Drives (UK) Ltd.
18 Maizefield
Hinckley Fields Industrial Estate
Hinckley
LE10 1YF Leicestershire
vacon.uk@vacon.com
tel. +44 (0)1455 611 515
fax: +44 (0)1455 611 517
Vacon distributor:
Norway
Vacon AS
Langgata 2
3080 Holmestrand
vacon@vacon.no
tel. +47 330 96120
fax: +47 330 96130
PR China
Vacon Plc
Beijing Representative Office
A205, Grand Pacific Garden Mansion
8A Guanhua Road
Beijing 100026
www.vacon.com.cn
vacon.china@vacon.com
tel. +86 10 6581 3734
fax: +86 10 6581 3754
Russia
ZAO Vacon Drives
Bolshaja Jakimanka 31
stroenie 18
109180 Moscow
www.ru.vacon.com
tel. +7 (095) 974 1541
fax: +7 (095) 974 1554
ZAO Vacon Drives
2ya Sovetskaya 7, office 210A
191036 St. Petersburg
www.ru.vacon.com
tel. +7 (812) 332 1114
fax: +7 (812) 279 9053
Singapore
Vacon Plc
Singapore Representative Office
102F Pasir Panjang Road
#02-06 Citilink Warehouse Complex
Singapore 118530
vacon.singapore@vacon.com
tel. +65 6278 8533
fax: +65 6278 1066
Spain
Vacon Drives Ibrica S.A.
Miquel Servet, 2. P.l. Bufalvent
08240 Manresa
www.vacon.es
info@vacon.es
tel. +34 93 877 45 06
fax: +34 93 877 00 09
Sweden
Vacon AB
Torget 1
172 67 Sundbyberg
tel. +46 (0)8 293 055
fax: +46 (0)8 290 755