Академический Документы
Профессиональный Документы
Культура Документы
nx frequency converters
multi motor 2
(multipurpose)
2 vacon
INDEX
1.
2.
Introduction ..................................................................................................................................... 3
Programming principle of the Multi Motor 2 application .............................................................. 4
2.1
Defining an input/output for a certain function on keypad................................................... 4
2.2
Defining a terminal for a certain function with NCDrive programming tool....................... 5
2.3
Defining unused inputs/outputs ............................................................................................ 6
2.4
Control I/O.............................................................................................................................. 7
3. Multi Motor 2 Application Parameter lists .................................................................................. 8
3.1
Monitoring values (Control keypad: menu M1)..................................................................... 8
3.2
Basic parameters (Control keypad: Menu M2 G2.1) ........................................................ 9
3.3
Input signals......................................................................................................................... 10
3.4
Output signals ...................................................................................................................... 15
3.5
Drive control parameters (Control keypad: Menu M2 G2.4).......................................... 20
3.6
Prohibit frequency parameters (Control keypad: Menu M2 G2.5)................................. 20
3.7
Motor control parameters (Control keypad: Menu M2 G2.6)......................................... 21
3.8
Protections (Control keypad: Menu M2 G2.7)................................................................. 23
3.9
Autorestart parameters (Control keypad: Menu M2 G2.8) ............................................ 25
3.10
Fieldbus parameters (Control Keypad: Menu M2 G2.9).................................................. 25
3.11
Torque control parameters (Control Keypad: Menu M2 G2.10) ..................................... 26
3.12
Motor 2 parameter............................................................................................................... 27
3.13
Keypad control (Control keypad: Menu M3)........................................................................ 27
3.14
System menu (Control keypad: Menu M6) .......................................................................... 28
3.15
Expander boards (Control keypad: Menu M7) .................................................................... 28
4. Description of parameters............................................................................................................ 29
4.1
Basic parameters ................................................................................................................ 29
4.2
Input signals......................................................................................................................... 32
4.3
Drive control ........................................................................................................................ 58
4.4
Prohibit frequencies ............................................................................................................ 62
4.5
Motor control ....................................................................................................................... 63
4.6
Protections........................................................................................................................... 70
4.7
Auto restart parameters...................................................................................................... 78
4.8
Fieldbus control ................................................................................................................... 81
4.9
Torque control ..................................................................................................................... 82
4.10
Motor 2 parameters............................................................................................................. 83
4.11
Keypad control parameters................................................................................................. 84
5. Control signal logic in Multi Motor 2 Application......................................................................... 85
vacon 3
INTRODUCTION
The digital inputs and all the outputs are freely programmable and the application
supports all I/O-boards
4 vacon
2.
The programming principle of the input and output signals in the Multipurpose Control Application
as well as in the Pump and Fan Control Application (and partly in the other applications) is
different compared to the conventional method used in other Vacon NX applications.
In the conventional programming method, Function to Terminal Programming Method (FTT), you
have a fixed input or output that you define a certain function for. The applications mentioned above,
however, use the Terminal to Function Programming method (TTF) in which the programming
process is carried out the other way round: Functions appear as parameters which the operator
defines a certain input/output for. See Warning on page 5.
2.1
Connecting a certain input or output with a certain function (parameter) is done by giving the
parameter an appropriate value. The value is formed of the Board slot on the Vacon NX control
board (see Vacon NX User's Manual, Chapter 6.2) and the respective signal number, see below.
READY
I/O term
AI Ref Faul/Warn
DigOUT:B.1
Function name
Slot
Terminal type
Terminal number
Example: You want to connect the digital output function Reference fault/warning (parameter
2.3.3.7) to the digital output DO1 on the basic board NXOPTA1 (see Vacon NX User's Manual, Chapter
6.2).
First find the parameter 2.3.3.7 on the keypad. Press the Menu button right once to enter the edit
mode. On the value line, you will see the terminal type on the left (DigIN, DigOUT, An.IN, An.OUT)
and on the right, the present input/output the function is connected to (B.3, A.2 etc.), or if not
connected, a value (0.#).
When the value is blinking hold down the Browser button up or down to find the desired board slot
and signal number. The program will scroll the board slots starting from 0 and proceeding from A
to E and the numbers referring to the I/O selection from 1 to 10.
Once you have set the desired value, press the Enter button once to confirm the change.
READY
I/Oterm
AI Ref Faul/Warn
DigOUT:0.0
READY
READY
I/Oterm
I/Oterm
AI Ref Faul/Warn
DigOUT:0.0
AI Ref Faul/Warn
DigOUT:A.1
enter
2.2
vacon 5
If you use the NCDrive Programming Tool for parametrizing you will have to establish the
connection between the function and input/output in the same way as with the control panel. Just
pick the address code from the drop-down menu in the Value column (see the Figure below).
!
WARNING
Note: The inputs, unlike the outputs, cannot be changed in RUN state.
6 vacon
2.3
All unused inputs and outputs must be given the board slot value 0 and the value 1 also for the
terminal number. The value 0.0 is also the default value for most of the functions. However, if you
want to use the values of a digital input signal for e.g. testing purposes only, you can set the board
slot value to 0 and the terminal number to any number between 210 to place the input to a TRUE
state. In other words, the value 1 corresponds to 'open contact' and values 2 to 10 to closed contact.
In case of analogue inputs, giving the value 1 for the terminal number corresponds to 0%, value 2
corresponds to 20% and any value between 3 and 10 corresponds to 100%.
2.4
vacon 7
Control I/O
Reference
potentiometer
NXOPTA1
mA
READY
RUN
220
VAC
Terminal
1
+10Vref
2
AI1+
Signal
Reference output
Analogue input, voltage range
010V DC
Description
Voltage for potentiometer, etc.
Voltage input frequency reference
3
4
5
AI1AI2+
AI2-
I/O Ground
Analogue input, current range
020mA
6
7
8
+24V
GND
DIN1
DIN2
10
DIN3
11
CMA
12
13
14
+24V
GND
DIN4
15
DIN5
16
DIN6
17
18
19
20
CMB
AOA1+
AOA1DOA1
NXOPTA2
21
22
23
RO1
RO1
RO1
Relay output 1
RUN
Programmable
24
25
26
RO2
RO2
RO2
Relay output 2
FAULT
Programmable
J u m p er b lo ck X 3:
CMA a n d CMB g r ou n d in g
CMB connected to GND
CMA connected to GND
CMB isolated from GND
CMA isolated from GND
CMB and CMA
internally connected together,
isolated from GND
= Factory default
8 vacon
3.
On the next pages you will find the lists of parameters within the respective parameter groups. The
parameter descriptions are given on pages 29 to 84.
Column explanations:
Code
Parameter
Min
Max
Unit
Default
Cust
ID
3.1
=
=
=
=
=
=
=
=
=
Location indication on the keypad; Shows the operator the present param. number
Name of parameter
Minimum value of parameter
Maximum value of parameter
Unit of parameter value; Given if available
Value preset by factory
Customers own setting
ID number of the parameter (used with PC tools)
On parameter code: Parameter value can only be changed after the FC has been
stopped.
= Apply the Terminal to Function method (TTF) to these parameters (see Chapter 2)
The monitoring values are the actual values of parameters and signals as well as statuses and
measurements. Monitoring values cannot be edited.
See Vacon NX User's Manual, Chapter 7 for more information.
Code
V1.1
Parameter
Output frequency
V1.2
Frequency reference
V1.3
V1.4
V1.5
V1.6
V1.7
V1.8
V1.9
Motor speed
Motor current
Motor torque
Motor power
Motor voltage
DC link voltage
Unit temperature
V1.10
Motor temperature
V1.11
V1.12
V1.13
V1.14
V1.15
V1.16
V1.17
V1.18
Analogue input 1
Analogue input 2
DIN1, DIN2, DIN3
DIN4, DIN5, DIN6
Analogue Iout
Analogue input 3
Analogue input 4
Torque reference
M1.19
Unit
Hz
ID
1
Hz
25
rpm
A
%
%
V
V
C
2
3
4
5
6
7
8
V/mA
V/mA
13
14
15
16
26
27
28
18
mA
V/mA
V/mA
%
Description
Output frequency to motor
Frequency reference to
motor control
Motor speed in rpm
In % of Motor nominal torque
Motor shaft power
3.2
vacon 9
Code
P2.1.1
Parameter
Min frequency
Min
0,00
Max
Par. 2.1.2
Unit
Hz
Default
0,00
Cust
ID
101
P2.1.2
Max frequency
Par. 2.1.1
320,00
Hz
50,00
102
P2.1.3
P2.1.4
P2.1.5
Acceleration time 1
Deceleration time 1
Current limit
0,1
0,1
Varies
3000,0
3000,0
Varies
s
s
A
103
104
107
P2.1.6
Nominal voltage of
the motor
180
690
1,0
1,0
Varies
NX2: 230V
NX5: 400V
NX6: 690V
P2.1.7
Nominal frequency
of the motor
30,00
320,00
Hz
50,00
111
P2.1.8
Nominal speed of
the motor
300
20 000
rpm
1440
112
P2.1.9
Nominal current of
the motor
Varies
Varies
Varies
113
P2.1.10
Motor cos
0,30
1,00
0,85
120
P2.1.11
I/O Reference
14
117
P2.1.12
Keypad control
reference
121
122
0,00
Par. 2.1.2
Hz
5,00
124
0,00
0,00
0,00
0,00
0,00
0,00
0,00
Par. 2.1.2
Par. 2.1.2
Par. 2.1.2
Par. 2.1.2
Par. 2.1.2
Par. 2.1.2
Par. 2.1.2
Hz
Hz
Hz
Hz
Hz
Hz
Hz
10,00
15,00
20,00
25,00
30,00
40,00
50,00
105
106
126
127
128
129
130
P2.1.13
P2.1.14
P2.1.15
P2.1.16
P2.1.17
P2.1.18
P2.1.19
P2.1.20
P2.1.21
Fieldbus control
reference
Jogging speed
reference
Preset speed 1
Preset speed 2
Preset speed 3
Preset speed 4
Preset speed 5
Preset speed 6
Preset speed 7
Note
NOTE: If fmax > than the
motor synchronous speed,
check suitability for motor
and drive system
See Table 6- 27
110
Check the rating plate of
the motor
The default applies for a 4pole motor and a nominal
size frequency converter.
Check the rating plate of
the motor. See Table 6- 27
Check the rating plate of
the motor
0=AI1
1=AI2
2=AI1+AI2
3=AI1-AI2
4=AI2-AI1
5=AI1xAI2
6=AI1 Joystick
7=AI2 Joystick
8=Keypad
9=Fieldbus
10=Motor potentiometer
11=AI1, AI2 minimum
12=AI1, AI2 maximum
13=Max frequency
14=AI1/AI2 selection
0=AI1
1=AI2
2=AI1+AI2
3=AI1-AI2
4=AI2-AI1
5=AI1xAI2
6=AI1 Joystick
7=AI2 Joystick
8=Keypad
9=Fieldbus
See par. 2.1.12
Multi-step speed 1
Multi-step speed 2
Multi-step speed 3
Multi-step speed 4
Multi-step speed 5
Multi-step speed 6
Multi-step speed 7
10 vacon
3.3
Input signals
3.3.1
Code
Min
Max
Unit
Default
Cust
ID
P2.2.1.1
Start/Stop logic
selection
P2.2.1.2
Motor potentiometer
ramp time
P2.2.1.3
Motor potentiometer
frequency reference
memory reset
367
P2.2.1.4
Adjust input
493
P2.2.1.5
P2.2.1.6
Adjust minimum
Adjust maximum
0,0
0,0
100,0
100,0
0,0
0,0
494
495
300
Note
Start signal 1
(Default: DIN1)
0
1
2
3
4
5
6
P2.2.1.7
I/O Reference 2
0,1
2000,0
14
Hz/s
%
%
10,0
Start forw.
Start/Stop
Start/Stop
Start pulse
Start
Fwd pulse
Start pulse
Start pulse
Start
signal 2
(Default:
DIN2)
Start rev.
Reverse
Run enable
Stop pulse
Mot.pot.UP
Rev pulse
Rev pulse
Enabl pulse
331
154
0
0=No reset
1=Reset if stopped or powered
down
2=Reset if powered down
0=Not used
1=AI1
2=AI2
3=AI3
4=AI4
5=Fieldbus (FBProcessDataIN3)
0=AI1
1=AI2
2=AI1+AI2
3=AI1-AI2
4=AI2-AI1
5=AI1xAI2
6=AI1 Joystick
7=AI2 Joystick
8=Keypad
9=Fieldbus
10=Motor potentiometer
11=AI1, AI2 minimum
12=AI1, AI2 maximum
13=Max frequency
14=AI1/AI2 selection
3.3.2
vacon 11
Code
P2.2.2.1
P2.2.2.2
Parameter
AI1 signal selection
AI1 filter time
Min
Max
Unit
0
0,00
10,00
P2.2.2.3
-100,00
100,00
-100,00
P2.2.2.9
P2.2.2.10
AI1 custom
minimum setting
AI1 custom
maximum setting
AI1 reference
scaling, minimum
value
AI1 reference
scaling, maximum
value
AI1 joystick
hysteresis
AI1 sleep limit
AI1 sleep delay
P2.2.2.11
P2.2.2.4
P2.2.2.5
P2.2.2.6
P2.2.2.7
P2.2.2.8
Default
A.1
0,10
Cust
ID
377
324
320
0,00
321
100,00
100,00
322
0,00
320,00
Hz
0,00
303
0,00
320,00
Hz
0,00
304
0,00
20,00
0,00
384
0,00
0,00
100,00
320,00
%
s
0,00
0,00
385
386
0,00
165
-100,0
100,0
Note
0=No filtering
0=0100%*
1=20100%*
2= -10V+10V*
3= Custom range
12 vacon
3.3.3
Code
P2.2.3.1
P2.2.3.2
Parameter
AI2 signal selection
AI2 filter time
Min
Max
Unit
0
0,00
10,00
P2.2.3.3
-100,00
100,00
-100,00
P2.2.3.4
P2.2.3.5
P2.2.3.6
P2.2.3.7
AI2 custom
minimum setting
AI2 custom
maximum setting
AI2 reference
scaling, minimum
value
AI2 reference
scaling, maximum
value
Default
A.2
0,10
Cust
ID
388
329
325
0,00
326
100,00
100,00
327
0,00
320,00
Hz
0,00
393
0,00
320,00
Hz
0,00
394
P2.2.3.8
AI2 joystick
hysteresis
0,00
20,00
0,00
395
P2.2.3.9
0,00
100,00
0,00
396
P2.2.3.10
0,00
320,00
0,00
397
P2.2.3.11
-100,0
0,00
166
100,0
Note
0=No filtering
0=0100%*
1=20100%*
2= -10V+10V*
3= Custom range
3.3.4
Code
P2.2.4.1
P2.2.4.2
Parameter
AI3 signal selection
AI3 filter time
Min
Max
Unit
0
0,00
10,00
P2.2.4.3
-100,00
100,00
-100,00
100,00
P2.2.4.4
P2.2.4.5
P2.2.4.6
AI3 custom
minimum setting
AI3 custom
maximum setting
AI3 signal inversion
Default
0.1
0,10
Cust
ID
141
142
143
0,00
144
100,00
145
151
Note
0=No filtering
0=0100%
1=20100%
2= -10V+10V
3= Custom range
0=Not inverted
1=Inverted
3.3.5
vacon 13
Code
P2.2.5.1
P2.2.5.2
Parameter
AI4 signal selection
AI4 filter time
Min
Max
Unit
0
0,00
10,00
P2.2.5.3
-100,00
100,00
-100,00
100,00
P2.2.5.4
P2.2.5.5
P2.2.5.6
AI4 custom
minimum setting
AI4 custom
maximum setting
AI4 signal inversion
Default
0.1
0,10
Cust
ID
152
153
154
0,00
155
100,00
156
162
Note
0=No filtering
0=0100%
1=20100%
2= -10V+10V
3= Custom range
0=Not inverted
1=Inverted
3.3.6
Code
Parameter
Min
Max
P2.2.6.1
Scaling of current
limit
399
400
401
402
485
P2.2.6.2
P2.2.6.3
P2.2.6.4
P2.2.6.5
Unit
Default
Cust
ID
Note
0=Not used
1=AI1
2=AI2
3=AI3
4=AI4
5=Fieldbus
(FBProcessDataIN2)
14 vacon
3.3.7
Cust
Code
Parameter
Min
Default
P2.2.7.1
P2.2.7.2
P2.2.7.3
Start signal 1
Start signal 2
Run enable
0
0
0
A.1
A.2
0.2
403
404
407
P2.2.7.4
Reverse
0.1
412
P2.2.7.5
P2.2.7.6
P2.2.7.7
0
0
0
0.1
0.1
0.1
419
420
421
0.1
417
0.1
418
P2.2.7.10
P2.2.7.11
P2.2.7.12
Preset speed 1
Preset speed 2
Preset speed 3
Motor potentiometer
reference DOWN
Motor potentiometer
reference UP
Fault reset
External fault (close)
External fault (open)
0
0
0
A.3
A.5
0.2
414
405
406
P2.2.7.13
A.6
408
P2.2.7.14
P2.2.7.15
Acc/Dec prohibit
DC braking
0
0
0.1
0.1
415
416
P2.2.7.16
Jogging speed
A.4
413
P2.2.7.17
AI1/AI2 selection
0.1
422
P2.2.7.18
0.1
409
P2.2.7.19
0.1
410
P2.2.7.20
0.1
411
P2.2.7.21
0.1
496
P2.2.7.22
0.1
164
P2.2.7.23
0.1
1509
0.1
1514
P2.2.7.8
P2.2.7.9
P2.2.7.24
ID
Note
3.4
vacon 15
Output signals
3.4.1
Code
P2.3.1.1
P2.3.1.2
P2.3.1.3
P2.3.1.4
Digital output 1
function
Digital output 1 on
delay
Digital output 1 off
delay
Min
Max
Unit
Default
Cust
0.1
26
0,00
320,00
0,00
320,00
ID
Note
486
312
0=Not used
1=Ready
2=Run
3=Fault
4=Fault inverted
5=FC overheat warning
6=Ext. fault or warning
7=Ref. fault or warning
8=Warning
9=Reverse
10=Jogging spd selected
11=At speed
12=Mot. regulator active
13=Freq. limit 1 superv.
14=Freq. limit 2 superv.
15=Torque limit superv.
16=Ref. limit supervision
17=External brake control
18=I/O control place act.
19=FC temp. limit superv.
20=Reference inverted
21=Ext. brake control
inverted
22=Therm. fault or warn.
23=On/Off control
24=FB data to DO/RO
25=FB data to DO/RO
26=FB data to DO/RO
0,00
487
0.00
488
3.4.2
Code
P2.3.2.1
P2.3.2.2
P2.3.2.3
P2.3.2.4
Min
Max
Unit
Default
Cust
ID
Note
0.1
489
490
26
0,00
320,00
0,00
491
0,00
320,00
0,00
492
16 vacon
3.4.3
Min
0
0
0
0
0
0
0
Default
A.1
B.1
B.2
0.1
0.1
0.1
0.1
0.1
439
0
0
0
0
0
0
0.1
0.1
0.1
0.1
0.1
0.1
440
441
442
443
444
445
0.1
446
0.1
447
0.1
448
0.1
449
0.1
450
0.1
451
0.1
452
0.1
463
0.1
454
P2.3.3.24
P2.3.3.25
P2.3.3.26
P2.3.3.27
P2.3.3.28
P2.3.3.29
Parameter
Ready
Run
Fault
Inverted fault
Warning
External fault
Reference fault/warning
Over temperature
warning
Reverse
Unrequested direction
At speed
Jogging speed
External control place
External brake control
External brake control,
inverted
Output frequency limit 1
supervision
Output frequency limit 2
supervision
Reference limit
supervision
Temperature limit
supervision
Torque limit supervision
Motor thermal
protection
Analogue input
supervision limit
Motor regulator
activation
Fieldbus data to DO/RO
Fieldbus data to DO/RO
Fieldbus data to DO/RO
Fieldbus data to DO/RO
Fieldbus data to DO/RO
Under Load Fault Active
0
0
0
0
0
0
0.1
0.1
0.1
0.1
0.1
0.1
455
456
457
169
170
1515
P2.3.3.30
0.1
1530
P2.3.3.31
0.1
1532
P2.3.3.8
P2.3.3.9
P2.3.3.10
P2.3.3.11
P2.3.3.12
P2.3.3.13
P2.3.3.14
P2.3.3.15
P2.3.3.16
P2.3.3.17
P2.3.3.18
P2.3.3.19
P2.3.3.20
P2.3.3.21
P2.3.3.22
P2.3.3.23
Cust
ID
432
433
434
435
436
437
438
Note
!
WARNING
3.4.4
vacon 17
Code
Parameter
Min
Max
P2.3.4.1
Output frequency
limit 1 supervision
P2.3.4.2
Output frequency
limit 1;
Supervised value
0,00
Par. 2.1.2
P2.3.4.3
Output frequency
limit 2 supervision
P2.3.4.4
Output frequency
limit 2;
Supervised value
0,00
Par. 2.1.2
P2.3.4.5
Torque limit
supervision
P2.3.4.6
Torque limit
supervision value
-1000,0
1000,0
P2.3.4.7
Reference limit
supervision
0,00
Par. 2.1.2
0,0
P2.3.4.8
P2.3.4.9
P2.3.4.10
Reference limit
supervision value
External
brake-off delay
External
brake-on delay
315
0,00
316
346
0,00
347
350
Hz
0,00
351
100,0
0,5
352
0,0
100,0
1,5
353
354
355
P2.3.4.12
FC temperature
supervised value
10
100
P2.3.4.15
349
ID
100,0
P2.3.4.14
Hz
Cust
348
FC temperature
supervision
On/Off control
signal
Hz
Default
P2.3.4.11
P2.3.4.13
Unit
Par.
2.3.4.15
Par.
100,00
2.3.4.14
356
10,00
357
90,00
358
Note
0=No limit
1=Low limit supervision
2=High limit supervision
3=Brake-on control
0=No limit
1=Low limit supervision
2=High limit supervision
3=Brake-off control
4=Brake on/off-control
0=Not used
1=Low limit supervision
2=High limit supervision
3=Brake-off control
0=Not used
1=Low limit
2=High limit
0=Not used
1=Low limit
2=High limit
0=Not used
1=AI1
2=AI2
3=AI3
4=AI4
18 vacon
3.4.5
Code
P2.3.5.1
P2.3.5.2
P2.3.5.3
P2.3.5.4
P2.3.5.5
P2.3.5.6
P2.3.5.7
Analogue output 1
function
Analogue output 1
filter time
Analogue output 1
inversion
Analogue output 1
minimum
Analogue output 1
scale
Analogue output 1
offset
Min
Max
Unit
Default
Cust
A.1
ID
Note
464
307
0=Not used
1=Output freq. (0fmax)
2=Freq. reference (0fmax)
3=Motor speed (0Motor
nominal speed)
4=Motor current (0InMotor)
5=Motor torque (0TnMotor)
6=Motor power (0PnMotor)
7=Motor voltage (0-UnMotor)
8=DC-link volt (01000V)
9=AI1
10=AI2
11=Output freq. (fmin - fmax)
12=Motor torque
(2+2xTNmot)
13=Motor power
(2+2xTNmot)
1,00
308
0=No filtering
309
310
10
1000
100
311
-100,00
100,00
0,00
375
13
0,00
10,00
0=Not inverted
1=Inverted
0=0 mA
1=4 mA
3.4.6
Code
P2.3.6.1
P2.3.6.2
P2.3.6.3
P2.3.6.4
P2.3.6.5
P2.3.6.6
P2.3.6.7
Min
Max
Unit
Default
Cust
ID
0.1
471
472
1,00
473
0=No filtering
13
0,00
10,00
474
475
10
1000
100
476
-100,00
100,00
0,00
477
Note
0=Not inverted
1=Inverted
0=0 mA
1=4 mA
3.4.7
Code
P2.3.7.1
P2.3.7.2
P2.3.7.3
P2.3.7.4
P2.3.7.5
P2.3.7.6
P2.3.7.7
vacon 19
Min
Max
Unit
Default
Cust
ID
0.1
478
479
1,00
480
0=No filtering
13
0,00
10,00
481
482
10
1000
100
483
-100,00
100,00
0,00
484
Note
0=Not inverted
1=Inverted
0=0 mA
1=4 mA
20 vacon
3.5
Code
Parameter
Min
Max
Unit
Default
Cust
ID
P2.4.1
Ramp 1 shape
0,0
10,0
0,0
500
P2.4.2
Ramp 2 shape
0,0
10,0
0,0
501
P2.4.3
P2.4.4
Acceleration time 2
Deceleration time 2
0,1
0,1
3000,0
3000,0
s
s
10,0
10,0
502
503
Note
0=Linear
>0=S-curve ramp time
0=Linear
>0=S-curve ramp time
0=Disabled
1=Used when running
2=External brake chopper
3=Used when
stopped/running
4=Used when running (no
testing)
0=Ramp
1=Flying start
0=Coasting
1=Ramp
2=Ramp+Run enable coast
3=Coast+Run enable ramp
P2.4.5
Brake chopper
504
P2.4.6
Start function
505
P2.4.7
Stop function
506
P2.4.8
DC braking current
DC braking time
at stop
Frequency to start
DC braking during
ramp stop
DC braking time
at start
0,15 x In
1,5 x In
Varies
507
0,00
600,00
0,00
508
0,10
10,00
Hz
1,50
515
0,00
600,00
0,00
516
P2.4.12
Flux brake
520
0=Off
1=On
P2.4.13
0,0
Varies
0,0
519
P2.4.9
P2.4.10
P2.4.11
3.6
Code
P2.5.1
P2.5.2
P2.5.3
P2.5.4
P2.5.5
P2.5.6
P2.5.7
Parameter
Prohibit frequency
range 1 low limit
Prohibit frequency
range 1 high limit
Prohibit frequency
range 2 low limit
Prohibit frequency
range 2 high limit
Prohibit frequency
range 3 low limit
Prohibit frequency
range 3 high limit
Prohibit freq. acc./
dec. ramp scaling
Min
0,00
0,00
0,00
0,00
0,00
0,00
0,1
Max
Par.
2.5.2
Par.
2.1.2
Par.
2.5.4
Par.
2.1.2
Par.
2.5.6
Par.
2.1.2
Unit
Default
Cust
ID
Note
Hz
0,00
509
0=Not used
Hz
0,00
510
0=Not used
Hz
0,00
511
0=Not used
Hz
0,00
512
0=Not used
Hz
0,00
513
0=Not used
Hz
0,00
514
0=Not used
10,0
Times
1,0
518
3.7
vacon 21
Code
Parameter
Min
Max
P2.6.1
Motor control
mode
2/6
600
P2.6.2
U/f optimisation
109
P2.6.3
108
32000
1520
0,00
par.
P2.6.4
Hz
50,00
604
0,00
100,00
100,00
605
n% x Unmot
Parameter max. value =
par. 2.6.5
0,00
40,00
0,00
606
n% x Unmot
1,0
Varies
kHz
Varies
601
607
608
2/6
521
32767
3000
637
300
638
0,00
620
631
0,00
612
30
613
ms
30,0
614
0,00
626
100
619
0,00
627
0,0
628
ms
100
615
ms
100
616
P2.6.4
P2.6.6
P2.6.7
P2.6.8
P2.6.9
P2.6.10
Measured Rs
voltage drop
U/f curve midpoint
frequency
U/f curve midpoint
voltage
Output voltage at
zero frequency
Switching
frequency
Over voltage
controller
32767
P2.6.15
Under voltage
controller
Motor control
mode 2
Speed controller
P gain (open loop)
Speed controller
I gain (open loop)
Load Drooping
0,00
100,00
P2.6.16
Identification
P2.6.11
P2.6.12
P2.6.13
P2.6.14
Unit
Default
Cust
ID
Note
NXS:
0=Frequency control
1=Speed control
2=Torque control
Additionally for NXP:
3=Closed loop speed ctrl
4=Closed loop torque ctrl
0=Not used
1=Automatic torque boost
0=Linear
1=Squared
2=Programmable
3=Linear with flux optim.
0=No Action
1=ID Without Run
2=ID With Run
22 vacon
P2.6.17.11
P2.6.17.12
P2.6.17.13
P2.6.17.15
P2.6.17.17
P2.6.17.19
Start-up torque
Start-up torque
FWD
Start-up torque
REV
Encoder filter time
Current control
P gain
Ir Add Zero Point
Voltage
621
300,0
300,0
0,0
633
300,0
300,0
0,0
634
1000
ms
618
0,00
100,00
40,00
617
30000
664
P2.6.17.20
Ir Add Motor
30000
100
667
P2.6.17.21
Ir Add Generator
30000
665
0,00
10,00
2,00
1525
-32000
32000
25000
1522
P2.6.17.22
Hz
0=Not used
1=Torque memory
2=Torque reference
3=Start-up torque fwd/rev
3.8
vacon 23
Code
Parameter
Min
Max
P2.7.1
Response to 4mA
reference fault
P2.7.2
0,00
Par. 2.1.2
P2.7.3
Response to external
fault
P2.7.4
730
727
702
703
704
100,0
100,0
0,0
705
0,0
150,0
40,0
706
200
min
45
707
100
100
708
InMotor x 2
120,00
Par. 2.1.2
P2.7.23
P2.7.24
Response to fieldbus
fault
Response to slot fault
No. of PT100 inputs
728
0,1
1,00
1,0
P2.7.22
0,00
P2.7.21
700
P2.7.14
P2.7.15
P2.7.16
Response to
thermistor fault
701
ID
P2.7.18
Cus
t
Stall protection
Hz
Default
P2.7.13
P2.7.17
Unit
10,0
150,0
5,0
2,00
A
s
Hz
709
InMotor x1,3
15,00
25,0
710
711
712
713
50,0
714
150,0
10,0
715
600,00
20,00
716
Note
0=No response
1=Warning
2=Warning+prev.freq.
3=Wrng+PresetFreq 2.7.2
4=Fault,stop acc. to 2.4.7
5=Fault,stop by coasting
0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
732
0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
733
See P2.7.21
0
0
3
3
2
0
734
739
See P2.7.21
24 vacon
P2.7.25
P2.7.26
P2.7.27
P2.7.28
P2.7.28
Response to PT100
fault
30,0
30,0
200,0
200,0
65000
740
C
C
120,0
130,0
741
742
1600
0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
0=Disabled
1=Enabled
3.9
vacon 25
Code
P2.8.1
P2.8.2
Parameter
Wait time
Trial time
Min
0,10
0,00
Max
10,00
60,00
P2.8.3
Start function
719
10
720
10
721
722
10
723
10
726
10
725
10
738
Unit
s
s
Default
0,50
0,10
Cust
ID
717
718
Note
0=Ramp
1=Flying start
2=According to par. 2.4.6
Parameter
Fieldbus min scale
Fieldbus max scale
Fieldbus data out 1
selection
Fieldbus data out 2
selection
Fieldbus data out 3
selection
Fieldbus data out 4
selection
Fieldbus data out 5
selection
Fieldbus data out 6
selection
Fieldbus data out 7
selection
Fieldbus data out 8
selection
Min
0,00
0,00
Max
320,00
320,00
Unit
Hz
Hz
Default
0,00
0,00
10000
852
10000
853
10000
854
10000
855
10000
856
10000
857
10000
858
10000
37
859
Cust
ID
850
851
Note
26 vacon
P2.10.4
P2.10.5
P2.10.6
P2.10.7
P2.10.8
P2.10.9
P2.10.10
Parameter
Torque limit
Torque limit control
P-gain
Torque limit control
I-gain
Torque reference
selection
Torque reference
max.
Torque reference
min.
Torque speed limit
Minimum frequency
for open loop
torque control
Torque controller
P gain
Torque controller
I gain
Min
0,0
Max
400,0
0,0
32000
3000
610
0,0
32000
200
611
300,0
300,0
300,0
300,0
0,00
par.2.1.1
0
0
Unit
%
Default
400,0
Cust
ID
609
641
100
642
0,0
643
644
3,00
636
32000
150
639
32000
10
640
Hz
Note
0=Not used
1=AI1
2=AI2
3=AI3
4=AI4
5=AI1 joystick
6=AI2 joystick
7=Torque reference from
keypad, R3.5
8=Fieldbus
0=Max. frequency
1=Selected freq.
reference
2=Preset speed 7
vacon 27
Parameter
Current limit
Min
Varies
Max
Varies
Unit
A
Default
Varies
NX2: 230V
NX5: 400V
NX6: 690V
Cust
ID
1500
P2.11.2
Nominal voltage of
the motor
180
690
P2.11.3
Nominal frequency
of the motor
30,00
320,00
Hz
50,00
1503
P2.11.4
Nominal speed of
the motor
300
20 000
rpm
1440
1504
P2.11.5
Nominal current of
the motor
Varies
Varies
Varies
1506
P2.11.6
Motor cos
0,30
1,00
0,85
1507
Note
See Table 6- 27
1502
Check the rating plate of
the motor
The default applies for a
4-pole motor and a
nominal size frequency
converter.
Check the rating plate of
the motor. See Table 627
Check the rating plate of
the motor
0=Frequency control
1=Speed control
2=Torque control
3=Closed loop speed ctrl
4=Closed loop torque ctrl
0=Not used
1=Automatic torque boost
P2.11.7
2/6
1524
P2.11.8
U/f optimisation
1523
P2.11.9
0,00
par.
P2.6.4
Hz
50,00
1511
P2.11.10
0,00
100,00
100,00
1512
n% x Unmot
Parameter max. value =
par. 2.6.5
0,00
40,00
0,00
1513
n% x Unmot
30000
1521
P2.11.11
P2.11.12
Output voltage at
zero frequency
Measure Rs voltage
drop
Parameter
Min
Max
P3.1
Control place
R3.2
Keypad reference
Par.
2.1.1
Par. 2.1.2
P3.3
P3.4
Stop button
R3.5
Torque reference
0,0
100,0
Unit
Default
Cust
ID
125
123
Note
0=I/O terminal
1=Keypad
2=Fieldbus
Hz
114
%
0,0
0 = Forward
1 = Reverse
0=Limited function of Stop
button
1=Stop button always
enabled
28 vacon
4.
DESCRIPTION OF PARAMETERS
4.1
Basic parameters
vacon 29
2.1.5
Current limit
This parameter determines the maximum motor current from the frequency converter.
The parameter value range differs from size to size. See the table below for the range
and the default values of parameters 2.1.5 and 2.1.9 for your converter.
Type
NX 0003 5
NX 0004 5
NX 0005 5
NX 0007 5
NX 0009 5
NX 0012 5
NX 0016 5
NX 0022 5
NX 0031 5
NX 0038 5
NX 0045 5
NX 0061 5
NX 0072 5
NX 0087 5
NX 0105 5
NX 0140 5
NX 0168 5
NX 0205 5
NX 0261 5
NX 0300 5
Par. 2.1.5/2.1.9
(min)
0,70
1,00
1,30
1,70
2,2
3,1
4,0
5,4
7,0
9,0
12,0
16,0
22,0
31,0
38,0
45,0
61,0
72,0
87,0
105,0
Par. 2.1.5/2.1.9
(max)
4,40
6,20
8,00
10,80
14,0
18,0
24,0
32,0
44,0
62,0
76,0
90,0
122,0
144,0
174,0
210,0
280,0
336,0
360,0
450,0
Par. 2.1.5
(default)
3,10
4,00
5,40
7,00
9,0
12,0
16,0
22,0
31,0
38,0
45,0
61,0
72,0
87,0
105,0
140,0
168,0
205,0
261,0
300,0
Par. 2.1.9
(default)
2,20
3,10
4,00
5,40
7,0
9,0
12,0
16,0
22,0
31,0
38,0
45,0
61,0
72,0
87,0
105,0
140,0
168,0
205,0
240,0
2.1.6
2.1.7
30 vacon
2.1.8
2.1.9
2.1.10
2.1.11
2.1.12
vacon 31
2.1.13
2.1.14
2.1.15 2.1.21
Preset speeds 1 7
These parameters define the Multi-step speed selected with the digital inputs
The parameter values are automatically limited between minimum and maximum
frequency (par. 2.1.1, 2.1.2)
32 vacon
4.2
Input signals
Basic Settings
Analogue Input 1 Signals
Analogue Input 2 Signals
Analogue Input 3 Signals
Analogue Input 4 Signals
Free analogue input, signal selection
Digital Input Signals
All parameters in group Digital Input Signals and one parameter in the Analogue Input Signal
groups each (P2.2.2.1, P2.2.3.1, P2.2.4.1 and P2.2.5.1) are programmable according to the Terminal
to Function Programming method (TTF) explained in more detail in Chapter 2.
All other parameters are programmed in the conventional (FTT) manner.
Note! When changing the function of an input, it is advisable to remove the previous selections of
that input. It is however possible to connect several functions to one and same input, if necessary.
4.2.1
Basic settings
FWD
Output
frequency
Stop function
(par 2.4.7)
= coasting
REV
DIN1
DIN2
NX12K09
vacon 33
FWD
Output
frequency
Stop function
(par 2.4.7
= coasting)
REV
DIN1
DIN2
NX12K10
34 vacon
FWD
Output
frequency
Stop function
(par 2.4.7)
= coasting
REV
DIN1
Start
DIN2
Stop
NX012K11
2.2.1.2
2.2.1.3
2.2.1.4
vacon 35
Adjust input
With this parameter you can
select the signal, according to
which the frequency reference
to the motor is fine adjusted
f/Hz
Adjusted
Adjust
maximum
P2.2.1.6 = 10%
44Hz
Adjust 0 %
40Hz
0
1
2
3
4
5
Not used
Analogue input 1
Analogue input 2
Analogue input 3
Analogue input 4
Signal from fieldbus
(FBProcessDataIN)
36Hz
Adjust
minimum
P2.2.1.5 = 10%
Analogue input
NX12K108
2.2.1.5
2.2.1.6
Adjust minimum
Adjust maximum
These parameters define the minimum and maximum of adjusted signals. See Figure 65.
2.2.1.7
36 vacon
4.2.2
2.2.2.1
2.2.3.1
2.2.2.2
2.2.3.2
%
Unfiltered signal
100%
Filtered signal
63%
t [s]
NX12K77
2.2.2.3
2.2.3.3
2.2.2.4
2.2.2.5
2.2.3.4
2.2.3.5
2.2.2.6
2.2.2.7
2.2.3.6
2.2.3.7
vacon 37
Output
frequency
par. 2.2.2.6
2.2.3.6
2.2.4.6
2.2.5.6
Analogue
input [V]
10
Analogue
input [V]
10
NX12K76
38 vacon
2.2.2.8
2.2.3.8
Reference
scaling max
P2.2.2.7 = 70Hz
REVERSE
FORWARD
50%
50%
B
From reverse to forward
Analogue
input (V/mA)
(0-10V/20mA)
Par. 2.2.2.4
= 20 %
Joystick hysteresis,
Par. 2.2.2.5
= 90 %
P2.2.2.8 = 20 %
NX12k92
limit) = 0
2.2.2.9
2.2.3.9
vacon 39
Frequency reference
Hz
Reference
scaling max
P2.2.2.7 = 70Hz
REVERSE
FORWARD
50%
50%
B
From reverse to forward
Analogue
input (V/mA)
(0-10V/20mA)
Par. 2.2.2.4
= 20 %
Sleep limit
P2.2.2.9 = 7%
Par. 2.2.2.5
= 90 %
Joystick hysteresis,
NX12k99
P2.2.2.8 = 20 %
Reference
scaling max
P2.2.2.7 = 70Hz
REVERSE
FORWARD
50%
50%
Analogue
input (V/mA)
(0-10V/20mA)
Par. 2.2.2.4
= 20 %
Joystick hysteresis,
Par. 2.2.2.5
= 90 %
P2.2.2.8 = 20 %
NX12k95
40 vacon
4.2.3
2.2.4.1
2.2.5.1
2.2.4.2
2.2.5.2
2.2.4.3
2.2.5.3
2.2.4.4
2.2.4.5
2.2.5.4
2.2.5.5
2.2.4.6
2.2.5.6
4.2.4
2.2.6.1
vacon 41
= Not used
= AI1
= AI2
= AI3
= AI4
= Fieldbus (FBProcessDataIN2)
This signal will adjust the maximum motor current between 0 and max. limit set with
parameter 2.1.5.
2.2.6.2
100%
Par. 2.4.8
Free analogue
input
0,15 x IL
0
Signal range
NX12K58
10
2
1
Signal range
NX12K59
42 vacon
2.2.6.4
Torque
limit
100%
Par. 2.3.4.6
Free
analogue
input
0
Signal
range
NX12K60
2.2.6.5
Torque limit
See par. 2.2.6.1 for the selections.
4.2.5
vacon 43
Digital inputs
All parameters of this group shall be programmed using the Terminal to Function Programming
method (TTF). In other words, all functions (parameters) that you wish to use shall be connected to a
certain input on a certain option board. For more information, see Chapter 2, PROGRAMMING
PRINCIPLE OF THE MULTI MOTOR 2 APPLICATION.
2.2.7.1
Start signal 1
Signal selection 1 for the start/stop logic.
Default programming A.1
2.2.7.2
Start signal 2
Signal selection 2 for the start/stop logic.
Default programming A.2
2.2.7.3
Run enable
Contact open:
Start of motor disabled
Contact closed: Start of motor enabled
2.2.7.4
Reverse
Contact open:
Direction forward
Contact closed: Direction reverse
2.2.7.5
2.2.7.6
2.2.7.7
Preset speed 1
Preset speed 2
Preset speed 3
Parameter values are automatically limited between the minimum and maximum
frequencies (par. 2.1.1, 2.1.2).
2.2.7.8
2.2.7.9
Motor potentiometer UP
Contact closed:
opened.
2.2.7.10
2.2.7.13
2.2.7.12
Fault reset
Contact closed:
2.2.7.11
44 vacon
2.2.7.14
Acceleration/Deceleration prohibited
Contact closed:
2.2.7.15
DC-braking
Contact closed:
2.2.7.16
Jogging speed
Contact closed: Jogging speed selected for frequency reference
See parameter 2.1.14.
Default programming: A.4.
2.2.7.17
AI1/AI2 selection
With this parameter you can select either AI1 or AI2 signal for frequency reference.
2.2.7.18
2.2.7.19
2.2.7.20
NOTE: When the control place is forced to change the values of Start/Stop, Direction and
Reference valid in the respective control place are used.
The value of parameter 3.1 (Keypad Control Place) does not change.
When the input opens the control place is selected according to keypad control
parameter 3.1.
2.2.7.21
2.2.7.22
2.2.7.23
vacon 45
2.2.7.24
46 vacon
4.2.6
Output signals
All parameters in group Digital Output Signals and one parameter in the Delayed Digital Output
Signal groups and Analogue Output Signal groups each (parameters 2.3.1.1, 2.3.2.1, 2.3.5.1, 2.3.6.1
and 2.3.7.1) are programmable according to the Terminal to Function Programming method (TTF)
explained in more detail in Chapter 2, PROGRAMMING PRINCIPLE OF THE MULTI MOTOR 2
APPLICATION.
All other parameters are programmed in the conventional (FTT) manner
4.2.7
2.3.1.1
2.3.2.1
2.3.1.2
2.3.2.2
Signal content
0 = Not used
Out of operation
Digital output DO1/DO2 sinks the current when:
1 = Ready
2 = Run
3 = Fault
4 = Fault inverted
5 = Frequency converter overheat
warning
6 = External fault or warning
8 = Warning
9 = Reversed
10 = Jogging speed
11 = At speed
13
= Output frequency
supervision
limit
14
= Output frequency
supervision
limit
vacon 47
Setting value
Signal content
Active reference goes beyond the set supervision low
limit/high limit (par. 2.3.4.7 and 2.3.4.8)
External brake ON/OFF control with programmable
delay (par. 2.3.4.9 and 2.3.4.10)
External control mode (Menu M3; par. 3.1)
Frequency converter heat sink temperature goes
beyond the set supervision limits (par. 2.3.4.11 and
2.3.4.12)
Motor rotation direction is different from the
requested one.
External brake ON/OFF control (par. 2.3.4.9 and
2.3.4.10); Output active when brake control is OFF
The thermistor input of option board indicates over
temperature. Fault or warning depending on
parameter 2.7.21.
Selects the analogue input to be monitored. See
par.2.3.4.13, 2.3.4.14, 2.3.4.15 and 2.3.3.22.
Fieldbus data (FBFixedControlWord) to DO/RO
2.3.1.3
2.3.2.3
2.3.1.4
2.3.2.4
Signal programmed to
digital output
ON-delay
OFF-delay
NX12k102
48 vacon
4.2.8
All parameters of this group shall be programmed using the Terminal to Function Programming
method (TTF). In other words, all functions (parameters) that you wish to use shall be connected to a
certain output on a certain option board. For more information, see Chapter 2, PROGRAMMING
PRINCIPLE OF THE MULTI MOTOR 2 APPLICATION.
2.3.3.1
Ready
The frequency converter is ready to operate.
2.3.3.2
Run
The frequency converter operates (the motor is running).
2.3.3.3
Fault
A fault trip has occurred.
Default programming: A.1.
2.3.3.4
Inverted fault
No fault trip has occurred.
2.3.3.5
Warning
General warning signal.
2.3.3.6
2.3.3.7
2.3.3.8
2.3.3.9
Reverse
The Reverse command has been selected.
2.3.3.10
Unrequested direction
Motor rotation direction is different from the requested one.
2.3.3.11
At speed
The output frequency has reached the set reference.
2.3.3.12
vacon 49
Jogging speed
Jogging speed selected.
2.3.3.13
2.3.3.14
2.3.3.15
2.3.3.16
2.3.3.17
2.3.3.18
2.3.3.19
2.3.3.20
2.3.3.21
2.3.3.22
2.3.3.23
2.3.3.24
2.3.3.25
2.3.3.26
2.3.3.27
50 vacon
2.3.3.28
2.3.3.29
2.3.3.30
2.3.3.31
4.2.9
vacon 51
Limit settings
The Limit Settings parameter group consists of parameters used to set limits for digital output
signals in group G2.3.3.
Parameters 2.3.4.1 to 2.3.4.6 and 2.3.4.9/2.3.4.10:
External brake control with additional limits
The external brake used for additional braking can be controlled through parameters 2.3.4.1 to
2.3.4.6 and 2.3.4.9/2.3.4.10. Selecting On/Off Control for the brake, defining the frequency or torque
limit(s) the brake should react to and defining the Brake-On/-Off delays will allow an effective brake
control. See Figure 6- 15.
Torque limit
Par. 2.3.4.6
Frequency limit
Par. 2.3.4.4
START
STOP
Brake off
Brake on
Brake-off
delay;
P2.3.4.9
Brake-on delay;
P2.3.4.10
NX12k115.fh8
In Figure 6- 15 above, the brake control is set to react to both the torque supervision limit (par.
2.3.4.6) and frequency supervision limit (2.3.4.4). Additionally, the same frequency limit is used for
both brake-off and brake-on control by giving parameter 2.3.4.3 the value 4. Use of two different
frequency limits is also possible. Then parameters 2.3.4.1 and 2.3.4.3 must be given the value 3.
Brake-off: In order for the brake to release, three conditions must be fulfilled: 1) the drive must be
in Run state, 2) the torque must be over the set limit (if used) and 3) the output frequency must be
over the set limit (if used).
Brake-on: Stop command activates the brake delay count and the brake is closed when the output
frequency falls below the set limit (2.3.4.1 or 2.3.4.3). As a precaution, the brake closes when the
brake-on delay expires, at the latest.
Note: A fault or Stop state will close the brake immediately without a delay.
See Figure 6- 16.
52 vacon
It is strongly advisable that the brake-on delay be set longer than the ramp time in order to
avoid damaging of the brake.
No brake-off control
Par 2.3.4.3
0-2
3
4
TRUE
Output frequency P2.3.4.4
Par 2.3.4.5
No brake-off control
0-2
Brake-off ctrl,
torque limit
TRUE
Motor torque P2.3.4.6
0-2
3-4
AND
OFFDELAY
COUNT
0-2
3
Brake off
Brake on
Run state
NOT
ONDELAY
COUNT
No Run request
Reversing
No run request
OR
No brake-on control
0-2
No brake-on control
0-3
Par 2.3.4.1
AND
OR
OR
Par 2.3.4.3
4
4
Par. 2.3.4.2
0-3
Par. 2.3.4.4
Output frequency
Fault
NX12k114.fh8
2.3.4.1
2.3.4.3
No supervision
Low limit supervision
High limit supervision
Brake-on control (See Figure 6- 15 and Figure 6- 16)
No supervision
Low limit supervision
High limit supervision
Brake-off control
Brake on/off control (See Figure 6- 15 and Figure 6- 16)
If the output frequency goes under/over the set limit (par. 2.3.4.2 or 2.3.4.4) this function
generates a warning message through the digital output or the relay outputs depending
on to which output the supervision signals (par. 2.3.3.16 and 2.3.3.17) are connected.
Tel. +358 (0)201 2121 Fax +358 (0)201 212 205
2.3.4.2
2.3.4.4
vacon 53
f[Hz]
Par 2.3.4.1 = 2
Par 2.3.4.2
t
Example: 21 RO1
22 RO1
23 RO1
21 RO1
22 RO1
23 RO1
21 RO1
22 RO1
23 RO1
NX12K19
54 vacon
2.3.4.5
2.3.4.6
2.3.4.7
2.3.4.8
2.3.4.9
2.3.4.10
2.3.4.11
2.3.4.12
2.3.4.13
vacon 55
2.3.4.14
2.3.4.15
P2.3.4.15
P2.3.4.14
Time
RO1
1
0
NX12k116
56 vacon
4.2.10
2.3.5.1
Analogue output 1
Analogue output 1 signal selection
Connect the AO1 signal to the analogue output of your choice with this parameter. For
more information, see Chapter 2, PROGRAMMING PRINCIPLE OF THE MULTI
MOTOR 2 APPLICATION.
2.3.5.2
2.3.5.3
Unfiltered signal
100%
2.3.5.4
Filtered signal
63%
t [s]
Par. 2.3.5.3
NX12K16
0 Not inverted
1 Inverted
Analogue
output
current
20 mA
2.3.5.5
12 mA
Param. 2.3.5.6
= 50%
10 mA
Param.
2.3.5.6= 100%
4 mA
Param. 2.3.5.6
= 200%
0 mA
0
0.5
1.0
NX12K17
2.3.5.6
vacon 57
Analogue
output
current
Param. 2.3.5.6
= 200%
Param. 2.3.5.6
= 100%
20 mA
Signal
Output frequency
Motor speed
Motor current
Motor torque
Motor power
Motor voltage
DC-link voltage
2.3.5.7
12 mA
Par. 2.3.5.5 = 1
4 mA
1.0
Analogue output 2
Analogue output 3
See 4.2.10 for parameter descriptions and functions.
0.5
NX12K18
4.2.12
Par. 2.3.5.5 = 0
0 mA
4.2.11
Param. 2.3.5.6
= 50%
10 mA
58 vacon
4.3
2.4.1
2.4.2
Drive control
[Hz]
2.1.3, 2.1.4
(2.4.3, 2.4.4)
2.4.1 (2.4.2)
2.4.1 (2.4.2)
[t]
NX12K20
2.4.3
2.4.4
Acceleration time 2
Deceleration time 2
These parameters give you the possibility to set two different acceleration/deceleration
time sets for one application. Connect the Acceleration time selection signal (parameter
2.2.7.13) to one of the digital inputs and choose the active Acceleration/Deceleration
time by setting the contact open (Acc/Dec time 1) or close (Acc/Dec time 2).
2.4.5
Brake chopper
0 =
1 =
2 =
3 =
4=
When the frequency converter is decelerating the motor, the inertia of the motor and the
load are fed into an external brake resistor. This enables the frequency converter to
decelerate the load with a torque equal to that of acceleration (provided that the correct
brake resistor has been selected). See separate Brake resistor installation manual.
2.4.6
vacon 59
Start function
Ramp:
0
The frequency converter starts from 0 Hz and accelerates to the set reference
frequency within the set acceleration time. (Load inertia or starting friction
may cause prolonged acceleration times).
Flying start:
1
The frequency converter is able to start into a running motor by applying a
small torque to motor and searching for the frequency corresponding to the
speed the motor is running at. The searching starts from the maximum
frequency towards the actual frequency until the correct value is detected.
Thereafter, the output frequency will be increased/decreased to the set
reference value according to the set acceleration/deceleration parameters.
Use this mode if the motor is coasting when the start command is given. With
the flying start, it is possible to ride through short mains voltage interruptions.
2.4.7
Stop function
Coasting:
0
The motor coasts to a halt without control from the frequency converter after
the Stop command.
Ramp:
1
After the Stop command, the speed of the motor is decelerated according to
the set deceleration parameters.
If the regenerated energy is high it may be necessary to use an external
braking resistor for faster deceleration.
2.4.8
DC-braking current
Defines the current injected into the motor during DC-braking.
60 vacon
2.4.9
fout
fn
fn
Output frequency
Motor speed
Output frequency
0,1 x fn
DC-braking ON
Motor speed
DC-braking ON
t = 1 x par. 2.4.9
RUN
RUN
STOP
STOP
NX12K21
vacon 61
fout
Motor speed
Output frequency
DC-braking
par. 2.4.10
t
t = Par. 2.4.9
RUN
STOP
NX12K23
2.4.10
2.4.11
t
Par 2.4.11
RUN
STOP
NX12K80
2.4.12
Flux brake
The flux braking can be set ON or OFF.
0 = Flux braking OFF
1 = Flux braking ON
2.4.13
62 vacon
4.4
2.5.1
2.5.2
2.5.3
2.5.4
2.5.5
2.5.6
Prohibit frequencies
Output
frequency [Hz]
2.5.1
2.5.3
2.5.5
2.5.2
2.5.4
2.5.6
Reference [Hz]
NX12K33
2.5.7
Par. 2.5.2
(2.5.4; 2.5.6)
Par. 2.5.1
(2.5.3; 2.5.5)
Time [s]
NX12k81
4.5
2.6.1
vacon 63
Motor control
Frequency control:
Speed control:
Torque control
Torque crtl (closed loop) The I/O terminal and keypad references are torque
references and the frequency converter controls the motor
torque.
2.6.2
U/f optimisation
Automatic
torque boost
EXAMPLE:
What changes are required to start with load from 0 Hz?
o First set the motor nominal values (Parameter group 2.1).
o
Motor Control Mode = 0 (Frequency control) and 1 (Speed control)
Option 1: Activate the Automatic torque boost (par. 2.6.2).
64 vacon
NOTE!
2.6.3
The voltage of the motor changes linearly with the frequency in the constant
flux area from 0 Hz to the field weakening point where the nominal voltage is
supplied to the motor. Linear U/f ratio should be used in constant torque
applications. See Figure 6- 28.
This default setting should be used if there is no special need for another
setting.
Squared: The voltage of the motor changes following a squared curve form
1
with the frequency in the area from 0 Hz to the field weakening point where
the nominal voltage is also supplied to the motor. The motor runs under
magnetised below the field weakening point and produces less torque and
electromechanical noise. Squared U/f ratio can be used in applications
where torque demand of the load is proportional to the square of the speed,
e.g. in centrifugal fans and pumps.
U[V]
Un
Nominal
par.2.6.5 Default:
voltage of the motor
Field weakening
point
Linear
Squared
Default: Nominal
frequency of the
motor
f[Hz]
NX12K07
vacon 65
U[V]
Un
Par 2.6.5
Default: Nominal
voltage of the motor
Par. 2.6.7
(Def. 10%)
Default: Nominal
frequency of the motor
f[Hz]
Par. 2.6.8
(Def. 1.3%)
Par. 2.6.6
(Def. 5 Hz)
Par. 2.6.4
NX12K08
2.6.4
The frequency converter starts to search for the minimum motor current and
in order to save energy, lower the disturbance level and the noise. Can be
used in applications with constant motor load, such as fans, pumps etc.
2.6.5
2.6.6
2.6.7
2.6.8
66 vacon
2.6.9
Switching frequency
Motor noise can be minimised using a high switching frequency. Increasing the
switching frequency reduces the capacity of the frequency converter unit.
The range of this parameter depends on the size of the frequency converter:
Type
00030061 NX5
00720300 NX5
Min. [kHz]
1.0
1.0
Max. [kHz]
16,0
10.0
Default
10.0
3.6
2.6.10
2.6.11
2.6.12
2.6.13
2.6.14
2.6.15
Load drooping
The drooping function enables speed drop as a function of load. This parameter sets that
amount corresponding to the nominal torque of the motor.
2.6.15
vacon 67
Identification
Identification Run is a part of tuning the motor and the drive specific parameters. It is a
tool for commissioning and service of the drive with the aim to find as good parameter
values as possible for most drives. The automatic motor identification calculates or
measures the motor parameters that are needed for optimum motor and speed control.
0 = No action
No identification requested.
1 = Identification without motor run
The drive is run without speed to identify the motor parameters. The motor is supplied
with current and voltage but with zero frequency.
2 = Identification with motor run
The drive is run with speed to identify the motor parameters.
Note: It is recommended to do this identification test with no load on the motor for best
results.
3 = Encoder ID run
The basic motor name plate data has to be set correctly before performing the identification run:
ID110
ID111
ID112
ID113
ID120
When in closed loop and with an encoder installed, also the parameter for pulses /
revolutions (in Menu M7) has to be set.
The automatic identification is activated by setting this parameter to the appropriate
value followed by a start command in the requested direction. The start command to the
drive has to be given within 20 s. If no start command is given within 20 s the identification run is cancelled and the parameter will be reset to its default setting.
The identification run can be stopped any time with normal stop command and the parameter is reset to its default setting. In case identification run detects fault or other problems, the identification run is completed if possible. After the identification is finished,
the application checks the status of the identification and generates fault/ warning if any.
During Identification Run, the brake control is disabled (see chapter 4.5).
68 vacon
EXAMPLE:
Motor Control Mode = 3 (Closed loop speed control)
This is the usual operation mode when fast response times, high accuracy or controlled
run at zero frequencies are needed. Encoder board should be connected to slot C of the
control unit. Set the encoder P/R-parameter (P7.3.1.1). Run in open loop and check the
encoder speed and direction (V7.3.2.2). Change the direction parameter (P7.3.1.2) or switch
the phases of motor cables if necessary. Do not run if encoder speed is wrong. Program
the no-load current to parameter P2.6.15.1 and set parameter P2.6.15.6 (Slip Adjust) to get
the voltage slightly above the linear U/f-curve with the motor frequency at about 66% of
the nominal motor frequency. The Motor Nominal Speed parameter (P2.1.8) is critical. The
Current Limit parameter (2.1.5) controls the available torque linearly in relative to motor
nominal current.
2.6.17.1
Magnetizing current
Set here the motor magnetizing current (no-load current).
2.6.17.2
2.6.17.3
2.6.17.5
Acceleration compensation
Sets the inertia compensation to improve speed response during acceleration and
deceleration. The time is defined as acceleration time to nominal speed with nominal
torque. This parameter is active also in advanced open loop mode.
2.6.17.6
Slip adjust
The motor name plate speed is used to calculate the nominal slip. This value is used to
adjust the voltage of motor when loaded. The name plate speed is sometimes a little
inaccurate and this parameter can therefore be used to trim the slip. Reducing the slip
adjust value increases the motor voltage when the motor is loaded.
2.6.17.7
2.6.17.8
2.6.17.9
2.6.17.10
2.6.17.11
vacon 69
Start-up torque
Choose here the start-up torque.
Torque Memory is used in crane applications. Start-up Torque FWD/REV can be used in
other applications to help the speed controller.
0 = Not Used
1 = TorqMemory
2 = Torque Ref
3 = Torq.Fwd/Rev
2.6.17.12
2.6.17.13
2.6.17.15
2.6.17.17
70 vacon
4.6
2.7.1
Protections
2.7.2
2.7.3
= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting
A warning or a fault action and message is generated from the external fault signal
(parameters 2.2.7.11 and 2.2.7.12) in the digital input selected. The information can also
be programmed into the digital output or the relay outputs (par. 2.3.3.6).
2.7.4
= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting
The input phase supervision ensures that the input phases of the frequency converter
have an approximately equal current.
2.7.5
2.7.6
vacon 71
= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting
Output phase supervision of the motor ensures that the motor phases have an
approximately equal current.
2.7.7
= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting
Earth fault protection ensures that the sum of the motor phase currents is zero. The
over current protection is always working and protects the frequency converter from
earth faults with high currents.
Parameters 2.7.82.7.12, Motor thermal protection:
General
The motor thermal protection is to protect the motor from overheating. The Vacon drive is capable
of supplying higher than nominal current to the motor. If the load requires this high current there is
a risk that the motor will be thermally overloaded. This is the case especially at low frequencies. At
low frequencies the cooling effect of the motor is reduced as well as its capacity. If the motor is
equipped with an external fan the load reduction at low speeds is small.
The motor thermal protection is based on a calculated model and it uses the output current of the
drive to determine the load on the motor.
The motor thermal protection can be adjusted with parameters. The thermal current IT specifies the
load current above which the motor is overloaded. This current limit is a function of the output
frequency.
CAUTION!
The calculated model does not protect the motor if the airflow to the
motor is reduced by blocked air intake grill.
72 vacon
2.7.8
= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting
If tripping is selected the drive will stop and activate the fault stage.
Deactivating the protection, i.e. setting parameter to 0, will reset the thermal stage of
the motor to 0%.
2.7.9
2.7.10
Pcooling
Overload area
100%
IT
Par.
2.7.10=40%
fn
NX12k62
2.7.11
vacon 73
Motor temperature
Trip area
105%
Motor
current
Fault/warning
par. 2.7.8
I/IT
*)
Time constant T
Motor temperature
= (I/IT)2 x (1-e-t/T)
Time
NX12k82
2.7.12
74 vacon
2.7.13
Stall protection
0
1
2
3
= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting
Setting the parameter to 0 will deactivate the protection and reset the stall time counter.
2.7.14
Stall area
Par. 2.7.14
Par. 2.7.16
NX12k63
2.7.15
vacon 75
Stall time
This time can be set between 1.0 and
120.0s.
This is the maximum time allowed for a
stall stage. The stall time is counted by
an
internal
up/down
counter.
If the stall time counter value goes
above this limit the protection will
cause a trip (see parameter 2.7.13).
Par. 2.7.15
Trip/warning
par. 2.7.13
Time
Stall
No stall
NX12k64
2.7.16
2.7.17
= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting
If tripping is set active the drive will stop and activate the fault stage.
Deactivating the protection by setting the parameter to 0 will reset the under load time
counter.
76 vacon
2.7.18
Par. 2.7.19
Underload area
f
5 Hz
Fieldweakening
point par. 2.6.4
NX12k65
2.7.19
2.7.20
Par. 2.7.20
Trip/warning
par. 2.7.17
Time
Underload
No underl.
NX12k66
2.7.21
vacon 77
= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting
Setting the parameter to 0 will deactivate the protection and reset the stall time counter.
2.7.22
2.7.23
2.7.24
2.7.25
2.7.26
= No response
= Warning
= Fault, stop mode after fault according to ID506
= Fault, stop mode after fault always by coasting
2.7.27
2.7.27
78 vacon
4.7
2.8.1
2.8.2
Wait time
Par. 2.8.1
Wait time
Par. 2.8.1
Fault trigger
Restart 2
Trial time
Par. 2.8.2
Fault active
RESET/
Fault reset
NX12k67
Parameters 2.8.4 to 2.8.9 determine the maximum number of automatic restarts during
the trial time set by this parameter. The time count starts from the first auto restart. If
the number of faults occurring during the trial time exceeds the values of parameters
2.8.4 to 2.8.9, the fault state becomes active. Otherwise the fault is cleared after the trial
time has elapsed and the next fault starts the trial time count again.
If a single fault remains during the trial time, a fault state is true.
2.8.3
2.8.4
vacon 79
2.8.5
2.8.6
2.8.7
2.8.8
80 vacon
2.8.9
2.8.10
4.8
vacon 81
Fieldbus control
The Fieldbus control parameters are used when the frequency or the speed reference comes from
the fieldbus (Modbus, Profibus, DeviceNet etc.). With the Fieldbus Data Out Selection 18 you can
monitor values from the fieldbus.
2.9.1
2.9.2
2.9.3 to
2.9.10
15
16
17
25
26
27
28
31
32
37
45
82 vacon
4.9
Torque control
Torque control can be activated by setting parameter 2.6.1 (2.6.12) to torque control.
2.10.1
Torque limit
With this parameter you can set the torque limit control between 0.0 400.0 %.
2.10.2
2.10.3
2.10.4
2.10.5
2.10.6
Not used
Analogue input 1
Analogue input 2
Analogue input 3
Analogue input 4
Analogue input 1 (joystick)
Analogue input 2 (joystick)
From keypad, parameter R3.5
Fieldbus
2.10.7
2.10.8
2.10.9
2.10.10
vacon 83
2.11.1
Current limit
This parameter determines the maximum motor current from the frequency converter.
2.11.2
2.11.3
2.11.4
2.11.5
2.11.6
2.11.7
2.11.8
2.11.9
2.11.10
84 vacon
3.1
Control place
The active control place can be changed with this parameter. For more information, see
Vacon NX User's Manual, Chapter 7.3.3.1.
Pushing the Start button for 3 seconds selects the control keypad as the active control
place and copies the Run status information (Run/Stop, direction and reference).
3.2
Keypad reference
The frequency reference can be adjusted from the keypad with this parameter.
The output frequency can be copied as the keypad reference by pushing the Stop button
for 3 seconds when you are on any of the pages of menu M3. For more information, see
Vacon NX User's Manual, Chapter 7.3.3.2.
3.3
Keypad direction
0
Forward: The rotation of the motor is forward, when the keypad is the active
control place.
Reverse: The rotation of the motor is reversed, when the keypad is the active
control place.
3.4
3.5
Torque reference
Define here the torque reference within 0.0100.0%.
5.
vacon 85
DIN#
DIN#
DIN#
DIN#
Preset Speed 1
Preset Speed 2
Preset Speed 3
AIA#
AIA#
DIN# Up
Down
Internal frequency
reference
Motor
Potentiometer
DIN#
Reset button
Start/Stop buttons
Start forward
(programmable)
Start reverse (programmable)
Programmable
Start/Stop and
reverse logic
Start/Stop
Internal Start/Stop
Reverse
Internal reverse
DIN#
>1
(programmable)
NX12k103.fh8
production:
Vaasa
Vacon Plc
Runsorintie 7
65380 Vaasa
firstname.lastname@vacon.com
telephone: +358 (0)201 2121
fax: +358 (0)201 212 205
Suzhou, China
Vacon Suzhou Drives Co. Ltd.
Building 13CD
428 Xinglong Street
Suchun Industrial Square
Suzhou 215126
telephone: +86 512 6283 6630
fax: +86 512 6283 6618
Vacon Traction Oy
Vehnmyllynkatu 18
33580 Tampere
telephone: +358 (0)201 2121
fax: +358 (0)201 212 710
Vacon Plc
yritie 12
01510 Vantaa
telephone: +358 (0)201 212 600
fax: +358 (0)201 212 699
Tampere
Vacon Plc
Vehnmyllynkatu 18
33580 Tampere
telephone: +358 (0)201 2121
fax: +358 (0)201 212 750
australia
Vacon Pacific
17, Corporate Ave.
Rowville, Victoria 3178
telephone: +61 (03) 92139300
fax: +61 (03) 92139310
austria
Vacon AT Antriebssysteme GmbH
Aumhlweg 21
2544 Leobersdorf
telephone: +43 2256 651 66
fax: +43 2256 651 66 66
belgium
Vacon Benelux NV/SA
Interleuvenlaan 62
3001 Heverlee (Leuven)
telephone: +32 (0)16 394 825
fax: +32 (0)16 394 827
china
Vacon Suzhou Drives Co. Ltd.
Beijing Office
A205, Grand Pacific Garden Mansion
8A Guanhua Road
Beijing 100026
telephone: +86 10 6581 3734
fax: +86 10 6581 3754
france
Vacon France
ZAC du Fresne
1 Rue Jacquard BP72
91280 Saint Pierre du Perray CDIS
telephone: +33 (0)1 69 89 60 30
fax: +33 (0)1 69 89 60 40
Vacon distributor:
germany
Vacon GmbH
Gladbecker Strasse 425
45329 Essen
telephone: +49 (0)201 806 700
fax: +49 (0)201 806 7099
spain
Vacon Drives Ibrica S.A.
Miquel Servet, 2. P.I. Bufalvent
08243 Manresa
telephone: +34 93 877 45 06
fax: +34 93 877 00 09
india
Vacon India
Flat no T1, 3rd floor
VNS Ashok Apartment
Plot no. 9A, New Beach Road
Thiruvanmiyur
Chennai-600041
Tel. +91 44 245 150 18
sweden
Vacon AB
Torget 1
172 67 Sundbyberg
telephone: +46 (0)8 293 055
fax: +46 (0)8 290 755
italy
Vacon S.p.A.
Via F.lli Guerra, 35
42100 Reggio Emilia
telephone: +39 0522 276811
fax: +39 0522 276890
the netherlands
Vacon Benelux BV
Weide 40
4206 CJ Gorinchem
telephone: +31 (0)183 642 970
fax: +31 (0)183 642 971
norway
Vacon AS
Langgata 2
3080 Holmestrand
telephone: +47 330 96120
fax: +47 330 96130
russia
ZAO Vacon Drives
Bolshaja Jakimanka 31,
109180 Moscow
telephone: +7 (095) 974 14 47
fax: +7 (095) 974 15 54
ZAO Vacon Drives
2ya Sovetskaya 7, office 210A
191036 St. Petersburg
telephone: +7 (812) 332 1114
fax: +7 (812) 279 9053
thailand
Vacon South East Asia
335/32 5th-6th floor
Srinakarin Road, Prawet
Bangkok 10250
Tel. +66 (0)85 100 7090
united arab emirates
Vacon Middle East and Africa
Block A, Office 4A 226
P.O.Box 54763
Dubai Airport Free Zone
Dubai
Tel. +971 (0)4 204 5200
Fax: +971 (0)4 204 5203
united kingdom
Vacon Drives (UK) Ltd.
18, Maizefield
Hinckley Fields Industrial Estate
Hinckley
LE10 1YF Leicestershire
telephone: +44 (0)1455 611 515
fax: +44 (0)1455 611 517