Академический Документы
Профессиональный Документы
Культура Документы
REPEATER PANEL
FEATURES
* Multi - Panel network by RS485
* Fibre Optic Link Option Available
* Local Programming
* Zonal LEDs
* Full Control Operation
* Back-Lit LCD4 x 40 Characters
* Internal Power Supply Option
* Flush Bezel Available
* Complies with BS5839 PT4 1988
and EN 54 PT2 1999
64/40RP/PS
GENERAL DESCRIPTION
Designed for connection to our Series 4000MP analogue addressable Main Fire Alarm control panel . The Repeater
Receives and Displays the information generated by the Analogue addressable panel . The information displayed
And system controls are in the same format as the Main Control Panel.
The Information is received and transmitted by a 4 core Data RS485 Link . This can be part of a Distributed system
which can also include Sub Panels And Loop Panels . The Repeater is comes fitted with the Plug in RS485/CB
communication board . A Fibre - Optic RS485 Communication Link is also available.
The panel is housed in an attractive metal enclosure with a glazed hinged lockable door . All indications and controls
Together with user instructions are provided on the inner facia . A bezel can be fitted to the back Box to enable the
control panel to be Flush Mounted . Special colours or non standard finishes are available to special order .
The 4000RP can be supplied either with or without an Internal Power supply.
A back-lit 4 x 40 Character LCD display provides Status and programmable location of each event . Zonal Fire RED
LED indications ( available up to 160 Zones as standard ) will be as the Main Control panel .
A Loss of Data link will be indicated as a Communication Fault .
Local programming is achieved by using Main Control panel Infrared controller or via the AT keyboard socket.
AVAILABLE OPTIONS
*
TECHNICAL SPECIFICATION
Mains Input( with internal power supply ) 240v AC 50/60 Hz ( other voltages to order )
Nominal panel Input voltage 24v DC
Supply rating / type( when fitted ) 1.25 amp Constant voltage with current limit & thermal shutdown
Standby current 75 mA
Alarm current 110 mA
Multi-panel network by RS485 fully redundant Loop
or Fibre - Optic Cable Link via Fibre Optic Interface Board
Construction
WIDTH
HEIGHT
DEPTH
ENCLOSURE REF
WEIGHT
Up to 64
405 mm
300 mm
125 mm
00
8.0 Kg
Up to 160
500 mm
400 mm
150 mm
01
13.0 Kg
64 / 40 00 / RP / PS ( Typical Code )
Number of Zone LEDs / 40 Enclosure Ref / RP / Power supply Option
TY PICA L
WIRING
SCHEMA TIC
0V
OUT
M AIN PAN EL
+ - + -
C LA S S 24V
24V MP X
C H A N G EA U X 1 A U X 2 ZO N E
A B A B A B A B
TX 1 RX 2
OUT
RX 1
IN
TX 2
SU B- PAN EL ( TYP.)
R EPEAT ER ( TYP.)
A B A B A B A B
A B A B A B A B
TX 1 RX 2
OUT
4 COR E
RX 1
IN
TX 1 RX2
OUT
TX 2
IN
TX 2
2 40 v AC IN PU T
L
4000 SERIES
REPEA TER PA NEL
RX 1
A B A B A B A B
TX 1 RX 2
OUT
RX 1
IN
TX 2
FR O M MA IN P A N E L, S U B -P A N E L OR R E P E A TE R
TO MA IN P A N E L, S U B -P A N E L O R R E P E A TE R
Alarmtronic Ltd
Unit 4 , Tait Road , Croydon , Surrey , CRO 2DP
Tel : 020 8665 6500 Fax : 020 8684 6511
MEMBER OF THE
BRITISH STANDARDS INSTITUTE