Вы находитесь на странице: 1из 4

http://www.svri.

nl/en/selecting-a-currenttransformer-ct/

Selecting a Current Transformer (CT)


14 AUGUST 2014

If the current ratio, burden and class are selected, the current transformer (CT) has
been specified basically. Of course additional requirements like type, frequency,
isolation level, maximal short circuit current and environmental conditions should
also be specified.

Current ratio Ip/Is


The current ratio is the ratio between the primary and secondary current.
For the primary current Ip you can select the first value that follows the highest
continuous current from the range:
1 1.25 1.5 2 2.5 3 4 5 6 7.5 A
Decades also belong to the range, like for example:
1000 - 1250 - 1500 - 2000 - 2500 - 3000 - 4000 - 5000 - 6000 - 7500 A
The secondary current Is is mostly 1A or 5A.
1A is my favorite, because the cable losses verliezen (VA) are 25x less compared
with 5A.
1A current transformer could be smaller at a required knee-point voltage.
5A was required when relays took their power supply from the sensing current.
5A is still commonly used in the US, unfortunately.

Accuracy
The accuracy of a current transformer depends among others of :
burden
class/saturation
load

frequency
temperature

Accuracy based on burden and class (IEC)


For the burden you can select the first value that follows the actual load (including
cable losses) from the range:
2.5 5 10 15 - 30 VA
For the class you can select:

Application

Class

Very accurate metering

0.1 - 0.2

Tariff (kWh) metering

0.5 0.5S 0.2 0.2S

Instrument meters and control

Protection (P)

5P20 5P10 10P10

Sometimes the factor of


security (FS) is also
specified to protect metering
devices against high short
circuit currents. If FS = 5,

the composite error at 5 x Ip 10%. Standard values are:


FS 5 FS 10

Accuracy based on knee-point voltage and Rct


For class X (BS), and class PX and PR (IEC) current transformer for
protection relays the accuray is not based on burden and class, but on:
minimum knee-point voltage, with corresponding maximum magnetising current
secondary winding resistance Rct (75C)
- load
Note: IEC and ANSI/IEEE define knee-point voltage different

Accuracy based on ANSI/IEEE standards


For current transformers for metering you should select a burden in ohms and
an accuracy percentage. A B0.5 is a 0.5 ohm load, For example.
Burden: B0.1 B0.2 B0.5 B0.9 B1.8
Accuracy percentage: 0.3 0.6 0.9 1.2 2.4
For current transformers for protection there is a C-range, that is given in the
tabel with the IEC equivalent.

ANSI/IEEE

IEC (5 A CTs)

C100

25VA, 5P20

C200

50VA, 5P20

C400

100VA, 5P20

C800

200VA, 5P20

Notes:
- C400 and C800 can be very large CTs
Divide burden (VA) by 5 for 1 A CTs

Examples and tips

If the maximum continuous current is 1124 A (50 Hz), then the current
transformer specification for protection could be: 1250/1 A, 10 VA, 5P20

For kWh metering could be: 1250/1 A, 5 VA, cl. 0.2S

Or with a factor of security: 1250/1 A, 5 VA, cl. 0.2S FS 5

The accuracy class is only applicable if the total load including cable losses is
approximately equal to the current transformer burden.

If the burden of a current transformer for metering is much higher than the
load, instruments and devices could be damaged if short circuit occurs
somewhere.

A current transformer could comply with requirements of several


combinations, e.g. 30 VA, 5P10 and 15 VA, 5P20.

For metering the ANSI/IEEE specification of the current transformer could


be 500/5A, 0.3 B0.5 (, 60 Hz). In that case, the burden will be 0.5 x 5 = 12.5
VA.

For protection the ANSI/IEEE specification of the current transformer could


be 500/5A C100 (, 60 Hz). The secondary current through a standaard 1 ohm
load can be 20 5 A = 100 A , with an inaccuracy less than 10%. The
voltage over the load will be 100 V.

See also

Wikipedia - Current transformer

RS Isolsec - Selecting a Current Transformer

References

IEC 61869-1 Instrument transformers Part 1: General requirements

IEC 61869-2 Instrument transformers Part 2: Additional requirements for


current transformers

IEC 60044-1 and IEC 185 are withdrawn current transformer standards

IEEE Std C57.13-2008 IEEE Standard Requirements for Instrument


Transformers

Вам также может понравиться