Вы находитесь на странице: 1из 1

Phone : 080 41130303

Fax
: 080 - 41130306
E- - Mail: skr@hbl.in

BATTERY SIZING CALCULATION


APPLICATION
Nominal Voltage
Load
BACKUP TIME
End cell voltage
Number of cells
Operating Temp
Temp correction
Ageing Factor
Min system voltage ( No of cells x
ECV)
Max system voltage during Float ( No
of cells x 2.25 v)
Max system voltage During boost ( Vo
of cell x 2.30 v)
K Factor for 15hrs Min at 1.75 v/cell

Constant Current
48 V (Specified)
4000 Amps
15 (Specified).
1.75 V (Considered)
24 Nos
27 Deg.C ( Considered)
1
1.25 ( Considered)
42 V
54 V
55.2 v
0.95

Calculation:
Capacity required after applying K factor : Load / K.factor = AH
Capacity required after applying Ageing Factor : Capacity x AF = AH
Capacity required after applying TCF Factor : Capacity xTCF = AH
Battery capacity required for 4000 Amps Load:
4000/0.95 = 4210 X 1.25 = 5263 Ah is required.
Availability is 48V 5550 Ah Battery.
Battery capacity required for 2000 Amps Load:
2000/0.95 = 2105 X 1.25 = 2631 Ah is required.
Availability is 48V 2720 Ah Battery.

HBL Power Systems Ltd.


# 44,Central Street, Shivajinagar, Bangalore 560001
Regd Off: Road No. 10, Banjara Hills, Hyderabad 500 034
Website: www.hbl.in