ELECTRICAL WORK SECTION IV ELECTRICAL INSTALLATION for HVAC Design, manufacture,
supply, installation, testing and commissioning of the following cubicle type, dead front, sheet
steel, wall mounted control panels, including anchoring into the wall, wiring terminating into
MCCB and copper earthing, in each panel shall be provided by the HVAC contractor. All outgoing
shall be provided with Stop /Manual /Auto selector switch to facilitate operation through BAS. All
starters shall be provided with potential free Contact for Connections to Building Automation
System. The panel shall include the following components & accessories. MCCB/MCB as per the
ratings given below, suitable for motor duty and able to withstand fault level of 20 KA. Incoming/
out Going feeder as per Given Rating Cable ally & Terminal block for Power distribution as
required. Contactor, over load relay with built in single phasing protection. Phase indicating
lights and indicating light for `ON status. 144 mm x 144 mm voltmeter and digital ammeter.
Time delay relay for delayed automatic restart of motor. Wiring for microswitch for stopping the
fan when fire damper closes (in case of Fan only). For on/off/remote and local operation, 3 pole
single throw switch shall be provided in each panel to facilitate override of the automatic
operation. All starters shall be provided with suitable potential free contract for connections to
the Building Automation System. Aluminium Bus bar Internal power and control wiring in copper
1.Main Incomer 150 HP 2. 1 no out going feeder for stores fresh air fan 2 x 7.5 HP Rating (15 HP)
(complete starter) 2. 2 no out going feed for stores Exhaust air fan 2 nosx 5.0 HP Rating(10 HP) (
complete starter) 3. 1 no out going feed for pump room,locker, store counter area Exhaust air
with 2 x 3 HP Rating (6.0 HP) ( complete starter) 4.1 no out going feed for pump room, locker,
store counter area fresh air with 3HP Rating (complete starter) 5. 4no out going feed for Parking
area Ex air fan with 3.0 HP Rating ( complete starter) 6. 2 no out going feed for toilet block Fresh
Air 1.0 HP Rating ( complete starter) 7. 2 no out going feed for toilet block Ex Air 1.0 HP Rating
(complete starter) 8. 2 no out going feed for painting workshop Fresh Air 3.0 HP Rating( 6.0 HP)
( complete starter) 9. 1 no out going feed for painting workshop Fresh Air 7.5 HP Rating
( complete starter) 10. 2 no out going feeder for VRF unit penal 25 HP ( only out going feeder for
VRF unit control penal) (Note: Power Supply for Auditorium cassette unit & split of Depot
manager will be from other penal and same will supplied by Electrical contactor) (Note: Main
Incomer Power with double Earthing for HVAC penal by Electrical contractor) (Note: In other
area Power/control cabling with double Earthing from HVAC penal to respective unit by HVAC
contractor)

Nos.

Power & Control Cabling, 4 core x25 sq.mm Aluminium Power Cable

Rmt

3 core x 4 sq.mm Copper cable

Rmt

3 core x 2.5 sq.mm Copper cable

Rmt

3 core x 1.5 sq.mm Copper cable

Rmt

G.I Double Earthing Wiring for Equipement

Rmt