DATASHEET FOR
MOTOR OPERATED GATE VALVE

Hindustan Petroleum Corporation Ltd

Mott MacDonald Consultants (India) Pvt. Ltd.

Visakha Dispatch Station

Kothari House, CTS No. 185

VR-ATP Area, Naval Base Post

Off Andheri - Kurla Road

Visakhapatnam - 530 014

Andheri (East)

Andhra Pradesh

Mumbai - 400 059

P:\Andheri\IndiaProject\254624 HPCL- White Oil Terminal\05 Control &


Automation\Documents\Documents\Specs\Package -II MOV 05.11.09\13_254624-400-DS-INT-024 Gate valve DS
Rev A.xls

INSTRUMENT DATASHEET
PLUG VALVES
DOCUMENT No. 254624-400-DS-INT-024
PROJECT No.
254624
CLIENT

3 OF 5

PAGE
RFQ/RFP NO.

PROJECT

HINDUSTAN PETROLEUM CORP.LOCATION


LTD.
As per approved vendor list
VISAKH MARKETING TERMINAL VENDOR
WHITE OIL PROJECT

MODEL

BTA

GATE VALVE DATASHEET


1

Tag No.

Qty

Note 1

P&ID

Fluid State:

: Note 1

Service

Note 1

Crit Press: Pc

Line no

Units

Max

: Note 1
Normal

Min:

Shut-Off

Overall Flow Rate

kg/hr

Gas Flow Rate

kg/hr

water Flow Rate

kg/hr

Liquid Flow Rate

kg/hr

Inlet Pressure

kg/cm2 g

Outlet Pressure

kg/cm2 g

Inlet Temperature

Deg C

Density/ Spec Grav(Liq.)/Mol Wt (Vap.)

g/cc

Note 1

Viscosity(Emuls.)/Spec Heats Ratio(Vap.)

Cp

Note 1
As mentioned in Doc
254624-400-SP-INT-004
Note 1

9
10
11
12
13
14

SERVICE CONDITIONS

Compressibility factor
Vapor Pressure Pv

kPag

Required Cv

16

Travel

17

Allowable/*Predicted SPL

dBA

18

Design temperature

Deg C

Note 1

19

Design pressure

kg/cm2 g

Note 1

Note 1

20
21

LINE

15

Pipe Line Size: Note 1


40

Schedule

22

Electric actuator with integral starter, linear action for gate valve, hardwired
remote control, local & remote indication, handwheel etc.

61

Type:

62

MFR:

63

Shut-Off Differntial/Design Pressure

---

Electric Supply

415 V AC, 50 Hz 3 Phase

Power Consumption

BTA

Open / Closing time

BTA / Not more than 45 Sec.

Open/ Closing Torque

BTA

BTA

Model:

BTA
kg/cm2 g

Gate valve, Flanged end, Fire Safe.

24

Size:

Note 1

25

Max Press/Temp:

Note 1

66

26

MFR & Model:

BTA

67

Body/Bonnet Matl:

ASTM A216 GR WCB

68

Hazardous Area Protection

Zone 1 Gr. IIA / II B, T3

Liner Material/ID:

N.A.

69

Ingress Protection

IP 65 as per IEC 529

In:

Flanged

70

Control:

Hardwired for command & status

Out:

Flanged

71

ESD Command

Hardwired Command for Emergency Operation

150#, RF, 125 to 250 AARH

72

Motor Type:

Squirrel Cage Induction type

73

Fault Level Supply System :


Rating KW :

Fuse Protected

Speed (RPM) :

BTA

27
28
29
30
31
32

64
150#

ANSI Class:

End Connection:
Flg:
End Ext/Matl:

65

ACTUATOR

Type:

VALVE BODY/BONNET

23

Bidirectional

74

Type of Bonnet:

Standard

75

35

Lub & Iso Valve:

N.A

36

Packing Material:

Graphite / Graphoil

77

37

Packing Type:

Renewable-Valve open on stream

78

38

Type:

Disc 13% Cr + STELLITED

79

Starter:

Integral with Motor

39

Size:

80

Torque Switches:

2 nos. for open & close


NA

BTA

N.A

76

SS304 CF8 / AISI 410

81

Body Seat Material:

13% CR + STELLITED

82

42

Back Seat Material:

13% CR

83

43
44
45

Stem Material:
Valve Position Indicator
Inspection & Testing std

13% CR ( No Casting)
Required
BS EN 12266 Part I API 598

84
85
86

49

Required

87

Required API 607/API 6FA

88

Certification
Design Std

BS EN 10204 0.1B
API 600

89

Dimenssional Std.

ASME B16.10

91

51

End Connection Std.


Hydro Pressure:

ASME B16.5
Required

92

Shut-Off Class:

Zero leakage/ TSO

94

ANSI/FCI Leakage Class:

Class VI

95

Material Certificate:

Required

97

Electrical Certificate:

Required

98

54

TEST

53

57
58
59
60

SP.
ACCESSORIES

56

93

96

55

NOTE:

REV
A
B

99
100
101
I

Air

2 nos.
Anti Condensation Heater: NA
Local / Remote Switch: Required

Required

Local On/Off Controls: Required

Required

Handwheel for Manual Operation:


Required
Required
Open / Closing Limit Switches:
Local Poistion Indicator / Indicating LED's: Required
M12 / M25 for Control & Status - BTA

Cable Entries & Sizes:

90

50
52

Clockwise, Anti Clocwise (Facing Drive End)

Cooling Method :

STATUS / ALARM

48

Antistatic feature
Fire Safe

BTA

Direction of Rotation:

COMMAND

47

HARDWIRED SIGNALS

46

GENERAL

41

TRIM

Disk Material:

40

ANCILLARIES

Lube:

MOTOR

Flow Direction:

34

33

M25 / M40 for Power

Opening & Closing

NA

Open & Closed

2 nos. DPDT Required - One each for open & close


(two separate cable entries)

Torque switch tripped


Local / Remote Switch

2 nos.Required - one each for open & close


Required

Main power / Phase / Control power loss

Required

Actuator fault, contactor energizing fault

Required

Thermostat tripped

Required

Valve jammed

NA

Open

Required

Close

Required

For NOTES refer Page 4 of 10.

DATE
19.11.09
04.01.10

BY
HVS
HVS

CK'D
AYM
AYM

APP.
DESCRIPTION
RM Issued for Approval
RM
Issued for Tender

REV

DATE

BY

CK'D

APP.

DESCRIPTION

INSTRUMENT DATASHEET
PLUG VALVES
DOCUMENT No. 254624-400-DS-INT-024

PAGE

PROJECT No.

254624

RFQ/RFP NO.

CLIENT

LOCATION
HINDUSTAN PETROLEUM CORP.
LTD.

4 OF 5

PROJECT

As per approved vendor list


VISAKH MARKETING TERMINAL VENDOR
WHITE OIL PROJECT

MODEL

BTA

GATE VALVE DATASHEET


NOTES:
1 Refer the Gate valves tag list as on Pages 5 to 10.
2 Valves shall meet the requirements of specified in Specification Doc. No. 254624-400-SP-INT-004 Rev C
3 Vendor shall refer Piping Specification Index, Doc no.254624-400-SP-PIP-002 Rev C
4 Valve, actuator+integral starter+gear pinion+clutch & handle for manual operation shall be supplied as one assembled unit, completely
furnished and tested. Max.Actuator Torque:125% of valve torque for pressure rating of ANSI 150# & less than valve stem shear torque.
5 All items as indicated shall be provided with a permanently attached stainless steel tag plate.
6 Valve shall be firesafe in accordance with API 607, spec 6FA.
7 Inspection & test shall be performed on all valves as per API 6D/API-598.
8 BTA- Bidder to advise.Bidder to check and confirm the same. Information is mandetory & shall be given along with bid.
9 Abbreviations : MAOP : Maximum Allowable Operating Pressure; FS: Fire Safe; J: Jacketed Body; BTA :Vendor to advise;
TSO: Tight Shut Off; FB: Full bore, TAS - Terminal Automation System, ESDV - Emergency Shutdown System Valve
Neg - Negligible
10 Vendor shall select the seat material as per the maximum temperature of fluid & leakage class specified.
11 Valve shall have anti-blowout stem,anti-static design and suitable for bi-directional use.
12 Limit switch tag numbers will be HZSO & HZSC followed by the valve number. For example for HV-4521, For open position the tag number
will be HZSO-4521 & for close position the tag number will be HZSC-4521.
13 8" and above size valves shall have lifting lugs.
14 Double Compression Glands with shrouds & Plug shall be provided. Cable Gland Adapters as required shall be provided.
15 Make for Electric Actuators-a. Rotork / Rotork, India, b. Limitorque, India, c. Auma, India
16 Vendor to submit the Valve crossectional area for plug opneing nothch, valve CV & pressure drop.
17 Vendor shall submit valve torque for - starting, running, end, stem shear torque, long standing torque & maximum actuator torque.

REV
A
B

DATE
24.07.09
05.11.09

BY
HVS
HVS

CK'D
AYM
AYM

APP.
DESCRIPTION
RM Issued for Approval
RM Re Issued for Appv

REV

DATE

BY

CK'D

APP.

DESCRIPTION

DOCUMENT No.
PROJECT No.
CLIENT
PROJECT
MODEL

254624-400-DS-INT-024
254624
HINDUSTAN PETROLEUM CORP. LTD.
VISAKH MARKETING WHITE OIL TERMINAL PROJECT
VTA

RFQ/RFP NO.
LOCATION
VENDOR

VISHAKHAPATNAM
As per approved vendor list

MOTOR OPERATED / ACTUATED GATE VALVE TAG LIST - FIRE SAFE

Sr No

Area
no

400

Tag

HV

Tag Nos.

7742

Service Description

P & ID

White Oil To/From OR2 Jetty 254624-400-PID-A0-1077

Line No.

12"-WO-7709-A09A2

Line Size
Inches

12

Valve
Size
Inches

12

Valve
Class

150#

Valve
Type

Gate
Valve

Design
pressure /
Design
Temperature
Shutoff
C
Pressure
Kg/cm2 (g)

65

Inlet
Temperature
C

Stayput

Actuator

Valve

Fail
Action

Time in Seconds
Remark

Make

Model

Torque

Type

Make

BTA

BTA

BTA

Conventio
nal
Electric
Actuator

BTA

Model / Torque/
Size
kW

BTA

BTA

Open

Close

BTA

Max 45
Sec /
BTA

Conventional
Electric
Actuator