7A.7 Application.
7A.7.1 At all integral flashing, apply 40-mil film thickness of elastomeric coating to the surface to be
flashed extending 150mm unto the floor slab and up the vertical wall.
7A.7.2 Apply a minimum of 40 dry mils of elastomeric coating at or projections, such as service pipes, to
a height equal to desired wearing surface height.
7A.7.3 Membrane waterproofing coating.
7A.7.3.1 Apply elastomeric coating, approx. 2 mils thick as first coat at 15 sqm/4L container.
7A.7.3.2 Apply elastomeric coating for six coats as top coating, approx. 7 mils thick per coat (at
10sqm/4L container) after other coat has completely dried. Total thickness of membrane
waterproofing shall be approx. 40 mils. Mortar setting beds for tile works to cover the membrane
waterproofing shall be done by others. Provide an average of 38mm thickness and this shall slope to
drain.
7A.8 Material application shall be made by roller, brush, or squeegee.
7A.9 Field quality control.
7A.9.1 Flood testing (optional)
7A.9.1.1 Waterproofed area shall be given a 24-hour flood test upon complete installation of the
waterproofing system. Allow system to cure 48 hours prior to flood test.
7A.9.1.2 Plug drains and place barriers to contain the water.
7A.9.1.3 Repair any leak.
7A.10 Cleaning. All debris from work completion shall be removed.
7A.11 Performance of waterproofing. Waterproofing works shall be done in a skillful manner,
completely watertight. The contractor shall submit a guarantee certificate against leaks for five
years.
7A.12 Submittal requirements. Prior to procurement and delivery, the contractor shall submit brochure
and sample of elastomeric waterproofing materials used for approval. Work will not be done until
approval of materials is received.