Вы находитесь на странице: 1из 8

Type SDV7

distribution circuit breaker


Top performance - proven reliability

Answers for energy.

Type SDV7
distribution
circuit breaker
The SDV7 family is the latest generation
of the successful SDV product line.
Ratings have been expanded, and the
highly reliable type 3AH operators are
retained. With over 7,000 type SDV units
and 350,000 type 3AH operators in
service, you can rely on Siemens products
to meet your distribution system
demands.
The design of the type SDV7 features
significant reduction in enclosure size;
and, consequently, in the overall
footprint.
The type SDV7 product line encompasses
the voltage groups: 15.5 kV and 27.6 kV.
Each group is specifically designed to
optimize space and material for the
voltage class while retaining common
features across the entire product line.

Table of contents

Ratings available:
15.5 kV
20 kA or 25 kA
1,200 A or 2,000 A
110 kV BIL
27.6 kV
20 kA or 25 kA
1,200 A or 2,000 A
150 kV BIL

Introduction

2-3

Type 3AH3 vacuum circuit


breaker and stored-energy
operating mechanism

4-5

Vacuum interrupters

Technical ratings and


control voltages

Dimensions

Standard features

Options

Type 3AH3 operating mechanism

Terminal connectors for bushings

Trip and close coil

Terminal connectors for ground

Visual circuit breaker status window

Current transformers (up to 2/bushing)

Operations counter
Mechanical position indicator

Capacitor trip unit for alternating


current (ac) tripping supply

External manual trip handle

Second trip coil

Generous relay and metering space

Undervoltage trip device

Hinged panel for relays or devices

Additional auxiliary switch contacts

Necessary terminal blocks and wiring


Fused knife-switch control voltage
disconnects
Porcelain dry-type roof bushings
Bolted cabinet construction
Permanent lifting eyes (2)
Adjustable galvanized legs (4)
Corrosion resistant powder paint finish
(ANSI-61 light gray)

Siemens protective relays


Other protective relays
Circuit breaker control switch with
indicating lights
Local/remote or toggle switches
Additional heaters for -40 C
application
1/2 voltage heaters

Stainless steel external ground pads (2)

Adjustable thermostat

Stainless steel external hardware

Seismic capability (IEEE 693 high level)

Cabinet heaters to prevent


condensation

Interior convenience outlet (GFCI)

Filtered ventilation
ANSI rain-tested design
(per ANSI C37.20.2-1999)
Reduced footprint from previous
models.

Interior light with switch


Molded case circuit breakers in lieu of
fused knife switches
Wire markers.

Standards

Seismic

The type SDV7 meets the following


standards:

When specified, the type SDV7


distribution vacuum circuit breaker
can be provided with the capability of
maintaining structural integrity during
and following a seismic disturbance,
as appropriate for the specified UBC
zones 1-4, IBC-2006 or IEEE 693 levels.

IEEE C37.04-1999 rating structure


for ac high-voltage circuit
breakers
IEEE C37.09-1999 test procedure
for ac high-voltage circuit
breakers
IEEE C37-06-2009 preferred
ratings ac high-voltage circuit
breakers
NEMA SG-4-2009 ac high-voltage
circuit breakers.

Maintenance interval
If applied under ANSI usual service
conditions, maintenance is only needed
at intervals of five years/10,000
operations on any circuit breaker in an
outdoor application.

Type 3AH3 operator


compartment

Type 3AH3
vacuum
circuit breaker
Circuit breaker

11

9
4
6

15

10

14
12
2

3
8

13

16

17

Operator
The type 3AH3 circuit breaker operator is
a durable and reliable stored-energy
mechanism. This operator is designed to
perform up to 10,000 operations before
overhaul, and the basic operator in the
3A family has a mean time before failure
(MTBF) of over 12,000 years (as of 2006).
Type 3AH3 stored-energy operating
mechanism

Operator elements, controls and indicators


1. Spring charging gearbox
2. Closing spring
3. Opening spring
4. Main rotating shaft
5. Contact pressure spring
6. Opening operation
shock absorber
7. Spring charging motor

Siemens has been manufacturing


medium-voltage vacuum circuit breakers
for over 30 years and has over 350,000
vacuum circuit breakers in service
throughout the world. Siemens designs
and develops circuit breaker operators
and interrupters at its circuit breaker
Center of Competence in Berlin,
Germany. Design (type) short-circuit tests
are performed at independent power test
laboratories. Design configuration of the
operating mechanism is controlled from
Berlin to ensure that circuit breakers
assembled at any of the regional
manufacturing centers will meet the
performance requirements of the design.

8. Manual spring charging


access port
9. OPEN-CLOSE indicator
10. CHARGED-DISCHARGED
indicator
11. Mechanical operation
counter
12. Spring release (close)
coil

13. Manual close


pushbutton
14. Trip coil
15. Manual open (trip)
pushbutton
16. Auxiliary switch
17. Anti-pump relay

The type SDV7 outdoor distribution


circuit breaker utilizes the type 3AH3
stored-energy operating mechanism. The
type 3AH3 is the latest member of the
type 3A operator family, of which over
350,000 units are in service worldwide in
vacuum circuit breakers. Over 60,000
type 3AH3 operators are in service.
The type 3AH3 operator builds on the
vast experience with the type 3A family
of operating mechanisms. Improvements
in the operator have been incorporated
to enhance service life and simplify
maintenance. Newer lubricants and
alternative bearing materials have been
selected to reduce the chance for
interaction between the lubricants and
the metals to ensure long service life.
Mounting provisions for devices, such as
the opening latch, closing latch and
similar items, are designed for oneperson removal and installation.

Reusable spring clips are used for pivot


pins, avoiding the need for special
removal tools or a supply of special
purpose retainers during maintenance.
The type SDV7 circuit breaker now is
provided with a 3-cycle rated interrupting
time as standard for control voltage
ratings of 48 Vdc and higher and for units
equipped for capacitor tripping.
Optionally, slower trip coils for 5-cycle
interrupting time can be provided.
The type 3AH3 operator is a true storedenergy operating mechanism. Closing
springs are charged electrically
immediately following a closing
operation, and the opening spring is
charged by the rotation of the circuit
breaker main shaft during the closing
operation.
The spring charging mechanism is a geardrive design. Compared to a ratchet-andpawl mechanism, the type 3AH3 operator
is quieter and exhibits longer mechanical
life. The estimated total mechanical
endurance of the operator is 60,000
operations with overhaul and vacuum
interrupter replacement at 10,000
operations.

Horizontally installed Siemens vacuum interrupters

Siemens vacuum interrupter cutaway


1

3
2
4

The recommended maintenance interval


for the operating mechanism is five years
or 10,000 operations, whichever occurs
first, when used in the ANSI/IEEE usual
service conditions.
The entire type SDV7 family, from
15.5 kV through 27.6 kV, uses the same
basic type 3AH3 operating mechanism.
The operators differ only in elements
related to the design voltage or
interrupting rating of the circuit breaker.
The components that differ according to
rating include: the main rotating shaft,
contact pressure springs, closing spring,
opening spring and pushrods, as well as
the high voltage elements, such as the
interrupter, standoff insulators and
similar items.

1. Stationary terminal connection


2. Internal arc shield
3. Insulator
4. Stationary contact
5. Moving contact
6. Metal bellows
7. Guide bushing
8. Moving contact connection

6
7

Vacuum interrupters
At the heart of the medium-voltage
circuit breaker are the vacuum
interrupters. Siemens vacuum
interrupters use chrome-copper contact
material, which keeps the chopping
current to 5 amperes or less and thereby
keeps overvoltages to a minimum.

Over 350,000 type 3A


operators are in
service on vacuum
circuit breakers
worldwide.

For 15.5 kV and 27.6 kV circuit breakers


up to 25 kA, radial magnetic field
contacts are used to force high current
(>10 kA) arcs to rotate rapidly around the
contact surfaces to reduce contact
erosion.
The Siemens vacuum interrupter is
designed to interrupt up to 100 full-rated
faults (depending on rating) before
replacement is necessary. A contact-wear
indicator is provided to directly determine
the wear of the contacts within the
vacuum interrupter.
5

Technical ratings
Circuit
breaker
type

Rated
maximum
voltage

Rated withstand
voltages

Rated
shortcircuit and
short-time
current

Rated
interrupting
time1

Rated
continuous
current

Lightning
impulse
(BIL)

Power
frequency

kV, rms

kV3

kV

kA, rms

ms/cycles

15.5-20

15.5

110/142

50

20

15.5-25

15.5

110/142

50

25

27.6-20

27.6

150/194

60

27.6-25

27.6

150/194

60

Rated transient
recovery voltage2

Rated
permissible
tripping
delay time
Y

Rated
closing
and
latching
current

uc TRV
peak
value

t3 time to
voltage uc

A, rms

kV

sec

kA,
peak

50/3

1,200, 2,000

29.2

32

52

50/3

1,200, 2,000

29.2

32

65

20

50/3

1,200, 2,000

52.1

45

52

25

50/3

1,200, 2,000

52.1

45

65

Type SDV7 circuit breaker control data


Nominal

Range
Close

Close coil

Trip coil4

Trip

Spring charging motor


Amperes run
(avg.)

Charging
seconds

48 Vdc

36-56

28-56

11.4

30/11.4

10

125 Vdc

90-140

70-140

2.1

7.4/4.8

10

250 Vdc

180-280

140-280

2.1

9.6/4.2

10

120 Vac

104-127

104-127

2.0

---

10

240 Vac

208-254

208-254

2.0

---

10

Footnotes:
1
Standard 50 ms (3-cycle) with 48 Vdc, 125 Vdc or 250 Vdc trip voltage or capacitor trip with 83 ms (5-cycle) interrupting time optional. For 24 Vdc trip, interrupting
time is 83 ms (5-cycle).
2
TRV values are in accord with IEEE C37.06-2009. TRV peak value uc is roughly equal to historic E2 value in ANSI C37.06-2000.
Value t3, time to voltage uc, is approximately 1/1.138 times the T2 value in ANSI C37.06-2000.
3
First value is full-wave impulse withstand circuit breaker open or closed. Second value is chopped-wave impulse withstand, applicable only
with circuit breaker closed.
4
First value is for standard 50 ms/3-cycle interrupting time. Second value is for optional 83 ms/5-cycle interrupting time (see note 1).

Type SDV7 angled view

Type SDV7 with control compartment door open

Dimensions1
Rating

G
Minimum

G
Maximum

15.5 kV

10.7
(272)

13.0
(330)

47.2
(1,199)

44.5
(1,130)

12.4
(315)

19.8
(503)

92.0
(2,337)

113.0
(2,870)

38.8
(986)

31.4
(798)

42.8
(1,087)

27.6 kV

12.3
(312)

16.0
(406)

56.5
(1,435)

49.8
(1,265)

14.4
(366)

21.0
(533)

96.0
(2,438)

117.0
(2,972)

44.2
(1,123)

39.4
(1,001)

52.0
(1,321)

Footnote:
1
Dimensions in inches (mm).

D
A

Operator
compartment

High-voltage
compartment

Control
compartment

Published by and copyright 2010:


Siemens AG
Energy Sector
Freyeslebenstrasse 1
91058 Erlangen, Germany
Siemens Energy, Inc.
7000 Siemens Road
Wendell, NC 27591
For more information, please contact:
+1 (800) 347-6659
www.usa.siemens.com/energy
Order No. E50001-F710-A374-X-76US
Printed in USA
All rights reserved.
Trademarks mentioned in this document
are the property of Siemens AG, its affiliates,
or their respective owners.
Subject to change without prior notice.
The information in this document contains
general descriptions of the technical options
available, which may not apply in all cases.
The required technical options should therefore
be specified in the contract.

www.usa.siemens.com/energy