Вы находитесь на странице: 1из 107

Lionel Ng, LPBS - Low Voltage Products

Welcome
Technical Sharing Session
ABB Group
March 12, 2014 | Slide 1

Lionel Ng, LPBS - Low Voltage Products, 2014

Electrical Installation
Circuit Breaker Selection
ABB Group
March 12, 2014 | Slide 2

Protection of Transformers

As to be able to protect LV/MV transformers LV side, we must mainly


take into account:
Rated current of the protected transformer, LV side, from which
the rated current of the circuit breaker and the setting depend on
(In);
The maximum estimated short circuit current in the installation
point which defines the minimal breaking power of the protection
circuit breaker (Isc).

Protection of Transformers
Switchboards with one transformer

Sn

U20

In
Isc

The rated current of the transformers LV side is defined by the


following expression
Sn x 103
In =
3 x U20

where
Sn = rated power of the transformer [kVA]
U20 = rated secondary voltage (no load) of the transformer [V]
ln = rated current of the transformer, LV side [A]

Protection of Transformers
The full voltage three-phase short circuit current immediately after the LV
side of the transformer can be expressed by the following relation once we
suppose infinite power at the primary:
Isc =

In x 100
Ucc %

where
Ucc %= short circuit voltage of the transformer [%]
ln = rated current, LV side, [A]
lsc = three-phase rated short circuit current, LV side, [A]

The short circuit current is normally lesser than the deduced value if
the circuit breaker is installed at a certain distance by means of a cable
or bar connection, according to the connection impedance.

Protection of Transformers
Switchboards with more than 1 transformer in Parallel

Isc2 + Isc3

I1

I2

I3

Circuit breaker A

Isc1

I5
Isc1 + Isc2 + Isc3

Circuit breaker B

I4

Protection of Transformers
As far as the calculation of the rated current of the transformer is
concerned, the rules beforehand indicated are completely valid.
The minimum breaking capacity of each circuit breaker LV side must be
greater than the highest of the following values: (the example refers to
machine 1 of the figure and it is valid for the three machines in parallel):
lsc 1 (short circuit current of transformer 1) in case of fault
immediately downstream circuit breaker 1;

lsc2 + lsc3 (short circuit currents of transformer 2 and 3) in case of


fault immediately upstream circuit breaker 1;
Circuit breakers l4 and l5 on the load side must have a short circuit
capacity greater than lsc1 + lsc2 + lsc3; naturally every transformer
contribution in the short circuit current calculation is to be lessened by the
connection line transformer - circuit breaker (to be defined case by case).

Protection of Cables

The choice of the circuit breakers for switching and protection of cables
means the perfect knowledge of:
rated operating line current lB
max admissable cable current lZ
presumed short circuit current in the point of installation of the circuit
breaker Icc

Protection of Cables
The correct circuit breaker must be selected to satisfy the following
conditions:
It must have a short circuit breaking capacity (lcu or eventually lcs) greater
or equal to the short circuit current lcc

It must use a protection release so that its overload setting current ln (l1)
satisfies the relation lB < ln < lZ (Oveload protection)
The let through energy (l2t) that flows through the circuit breaker must be
lesser or equal to the maximal one allowed by the cable (KS) (Shortcircuit protection)

Protection of Cables

It
Cable KS

Circuit breaker It

Icc max

Icc

Protection of Cables

As far as the verification required by IEC 60364, according to which


the overload protection must have an intervention current (lf) that
assures the operation for a value lesser than 1.45 lz (lf < 1.45 lz), we
must state that it is always verified for ABB Circuit breakers, since
according to IEC 60947-2 the required value is less than 1.3 ln.

Circuit Breaker Curves


LV protection devices
L function protection against
overload

Circuit Breaker Curves


LV protection devices

S function protection against


delayed short-circuit

Circuit Breaker Curves


LV protection devices

I function protection
against instantaneous
short-circuit

Circuit Breaker Curves


LV protection devices

G function protection
against earth-fault

Protection of Primary & Secondary Distribution


Selective Protection

The example emphasizes the need for coordination between circuit breakers A and
B, such that in case of fault in C, only circuit
breaker B trips, thus leaving complete
continuity to the rest of the plant supplied
by the circuit breaker A.
Selectivity might be Total or Partial:

Total selectivity: only the circuit breaker B


trips for every current value lesser or equal to
the max short circuit current foreseen in C;
Partial selectivity: the circuit breaker B opens
only according to fault current lower than a
certain value; values that are equal or greater
than this will give the intervention of both
circuit breakers A and B.

Protection of Primary & Secondary Distribution


Selective Protection
Amperometric (Current) selectivity is obtained
by
setting
on
different
values
the
instantaneous tripping currents of the circuit
breakers chain (greater values for upstream
circuit breakers)
B

ImB

ImA

ImA is the selectivity limit

Protection of Primary & Secondary Distribution


Selective Protection
Chronometric (Time) selectivity is obtained by
introducing intentionally always greater delays in
the intervention tripping timings of the upstream
circuit breakers in the chain.

Total selectivity

Protection of Primary & Secondary Distribution

Switchboard A

2500 kVA
(fault current 57,5 kA)

E4S40
with PR121

400V

E2N20
with PR121

Switchboard B

E2N20 MS (disconnector)
400V

T5H 630
with PR222

Protection of Primary & Secondary Distribution

Protection of Primary & Secondary Distribution

Protection of Primary & Secondary Distribution


Back-up Protection

In the figure, the circuit breaker B, downstream in respect


with A, might have a short circuit breaking capacity lesser
than the presumed short circuit current in case of fault in
C if the circuit breaker A satisfies at all the two following
conditions:

It has a short circuit rating greater or equal to the


presumed short circuit current in its installation point and
obviously greater than the short circuit current in C
In case of fault in C with short circuit values greater
than the short circuit breaking capacity of circuit breaker
B, the circuit breaker A must limit the let through energy
by limiting it to a correct value than can be stood by
circuit breaker B and by the protected lines

Protection of Primary & Secondary Distribution


Back-up Protection
The back-up protection is used in electric plants where operation continuity
is not a main need. This means that the up stream breaker will always trip
with or without the help from the down stream protection device. This
means the whole system including the sound parts of the installation will
be without power.

This co-ordination solution is used by those who need to contain the plant
costs by reducing the general performance in case of a fault.

Protection of Primary & Secondary Distribution


Back-up Protection
Ib = 1300 A
A

Icc = 65 kA
Ib = 300 A

Icc 30 kA
U

Load

Electrical characteristics of the employed circuit breakers


Reference

Rated
current

Type

[A]

Rated
uninterrupted
current
Iu [A]

Breaking
capacity

Selectivity
limit

Back-up
limit

Icu [kA]

[kA]

[kA]

36 (T)

65

1300

SACE Emax E2L16

1600

130

300

SACE Tmax T4N 320

320

36

Protection of Primary & Secondary Distribution


Back-up Protection

T4S 250

50 kA !!!

T1N 160
* T1N 160 is 36 kA only mccb

Protection of Primary & Secondary Distribution


Selectivity

T6H 800 (70kA)

70 kA

T4H 250 (70kA)

Selection of Protective Devices


Main electrical parameters
Rated operational voltage Ue: the value of voltage which
determines the application and to which all the other
parameters are referred to.
Rated uninterrupted current Iu: the value of current which the
device is able to carry for an indefinite time. It defines the size
of the CB

Rated current In: the value of current which characterizes the


protection release installed. Is often related to the rated
current of the load protected

T5N400 PR221DS-LS/I In 320

Iu

In

Selection of Protective Devices


Main electrical parameters
Rated ultimate short-circuit breaking capacity Icu: it is the
r.m.s. value of the symmetrical component of the short-circuit
current which the circuit-breaker is able to break (test cycle Ot-CO)
Rated service short-circuit breaking capacity Ics: it is the r.m.s.
value of the symmetrical component of the shortcircuit current
which the circuit-breaker is able to break (O-t-CO-t-CO)

T5N400 PR221DS-LS/I In 320

Icu

Selection of Protective Devices


Main electrical parameters
Rated short-circuit making capacity Icm: it is the maximum
prospective peak current which the circuit-breaker must be
able to make
Icm=n x Icu

T5N400 PR221DS-LS/I In 320

Icu 36kA Icm 75.6 kA @415V

Selection of Protective Devices


Main electrical parameters
Rated short-time withstand current Icw: it is the r.m.s. value of
the alternate current component which the circuit-breaker is
able to withstand without damages for a determined time,
preferred values being 1s and 3 s
Defined for category B only

Selection of Protective Devices


Main electrical parameters

Selection of Protective Devices


Main electrical parameters
Generalities about the main electrical parameters
Dont forget

Ue Un
Icu or Ics Ik
Icm Ip

Ue, Icu, Ics, Icm?

Lionel Ng, Low Voltage Products, 2014

Distribution systems
Protection against indirect contact
and earth fault
ABB Group
March 12, 2014 | Slide 34

Agenda

Main definitions

Distribution systems and protection


against indirect contact and earth fault

ABB solutions for protection

against earth fault

Discrimination of the protections


against earth fault

Definitions

Indirect contact
Electric contact of persons with exposed-conductive-parts
which have become live under fault condiction (deterioration)

Direct contact
Electric contact of persons with live parts

Definitions

Earth fault
The loss of insulation between normally live conductors and exposedconductive-parts may generate a earth fault
Main causes of the loss of insulation:

time decay of dieletric properties

mechanical breaking

particularly aggressive environments

overvoltages of atmospheric origin or due to switching

rodent action

Definitions

Main effects of the earth fault current


energizing of exposed-conductiveparts

localized electric arcs and consequent


overheatings

disturbances to telecommunication systems

erosion phenomena of earth electrodes

Definitions
A contact with a live part causes the flowing of current through
the human body, the danger of this current depends on its :
duration
size
Time-current zones of the effects of alternating current on the human body
1 No reaction
2

No physiological effect

Reversible pathological effects

Fibrillation risk greater than


50%

Definitions

Exposed-conductive-part

Conductive part

Can be touched

Is not normally live

Can become live when basic insulation fails

Live part

Conductor or conductive part intended to be enegized in normal operation

Including a neutral conductor

By convetion not a PEN.

Definitions

Basic insulation

Isolation of live part

Base protection against direct and indirect contact

Supplementary isolation

independent insulation applied in addition to basic insulation

Insures the protection when the basic insulation fails

Double isolation

Reinforced insulation

comprises both basic insulation and supplementary insulation

provides a degree of protection against electric shock equivalent to double


insulation (unique insulation)

Fault current

current which flows across a given point of fault resulting from an insulation
fault

Definitions

Live part
functional isolation: in an electrical device it insulates the parts at different potentials
thus enabling operations
basic insulation is the insulation of the normally live parts
supplementary insulation is applied in addition to basic insulation in case of a failure of
the last
reinforced insulation, a unique insulation which can guarantee the equivalent protection
degree which can be provided by basic insulation plus supplementary insulation

Double insulation: comprises both basic insulation and supplementary


insulation

Definitions

Reference earth

Earth electrode

part of the Earth considered as conductive, the electric potential of which is


conventionally taken as zero
conductive part, which may be embedded in a specific conductive medium,
e.g. concrete or coke, in electric contact with the Earth

Earthing resistance

resistance between the main earth collector (or node) and the Earth

Definitions

Protective conductor PE

conductor provided for purposes of safety (protection against electric shock)

it connects:
exposed-conductive-parts

main earth collector (or node)

earth electrode

earthed point of the source or artificial neutral

PEN conductor

combines the functions of both a PE conductor and a neutral conductors

Residual current:

vectorial sum of the values of the electric currents in all live conductors

Id = IL1+ IL2+ IL3+ IN

N
PE
L1
L3
L2

Classification of electrical distribution systems


Protection
Protection

against indirect contact


throught automatic disconnection :

CBs with thermomagnetic or electronic releases;

CBs with electronic releases with G function against earth fault

CBs with residual current devices integrated

Residual current circuit breaker

Residual current releases

protection without automatic disconnection:

Protection by double or reinforced insulation;

Protection by earth-free local equipotential bonding;

Protection by electrical separation for the supply of only one item


of current-using equipment

Protection by electrical separation for the supply of more than one


item of current-using equipment

Classification of electrical distribution systems

The IEC 60364-3 classifies the electrical systems with the combination of two letters

The first letter indicates the relationship of the power system to earth

T direct connection to earth of one point

I all live parts isolated from earth or one point connected to earth through an
impedance

The second letter indicates the relationship of the exposed-conductive- parts of the
installation to earth

T direct connection to earth

N direct electrical connection of the exposed-conductive-parts to the earthed point of


the power system

Classification of electrical distribution systems

Subsequent letters, if any, indicates the arrangement of neutral and protective


conductors

S neutral and protective functions provided by separate conductors

PE

C neutral and protective functions combined in a single conductor (PEN


conductor)

PEN

Classification of electrical distribution systems

TT system

the neutral and the exposed-conductive-parts are connected to


earth electrodes electrically independent

Classification of electrical distribution systems

TT system

The earth fault current returns to the power supply node through the soil

Classification of electrical distribution systems

TT system

The exposed-conductive-part assumes the potential UT = Ik RA

The person touching the exposed-conductive-part is subjected to the voltage UT

Ik

Classification of electrical distribution systems

Condition to be fulfilled :

Ra I Dn U 0

Ra is the total resistance of the earth electrode and of the protective


conductor of the exposed-conductive-parts

IDn is the rated residual operating current of the residual current circuitbreaker

the time defined in the following table for the terminal circuits with a
rated current In<32A

within 1 sec for distribution circuits or terminal circuits with a rated


current In>32A

Classification of electrical distribution systems

Thanks to a more sensitive residual current device, from a pratical point of view it
will be easier to realize an earthing system coordinated with the characteristics of
the device itself. This table shows the maximum values of earth resistance which
can be obtained with residual current devices and making reference to a common
environment (50V)

How an RCD works

trip coil

main contact

test button

electronic circuit
(if any)
resistance

toroid

How an RCD works

How the RCD works

TEST

Classification of electrical distribution systems

Condition to be fulfilled :

Z s Ia U0

Zs is the total impedance of the loop;

Ia is the disconnection current in these time:

the time defined in the following table for the terminal circuits with a
rated current In<32A

within 1 sec for distribution circuits or terminal circuits with a rated


current In>32A

Classification of electrical distribution systems

Conclusion about TT system

Domestic installations and similar, small industries with LV power supply

Typical value of earth fault currents 10 ~ 100A

The standards allow the use of:


CBs

with inverse time tripping characteristics

CBs

with instantaneus tripping characteristics

Residual

current devices

If automatic disconnection cannot be obtained in compliance with the


disconnection times of the table or within the conventional time, it shall be
necessary to provide supplementary equipotential bonding connnected to
earth, however the use of supplementary protective bonding does not exclude
the need to disconnect the supply for other reasons, for example protection
against fire, thermal stresses in equipment

Classification of electrical distribution systems

TN-S system

the neutral and the exposed-conductive-parts are connected to the same


earthing arrangement

the exposed-conductive-parts are connected to the earth electrode by


means of the PE

PE

Classification of electrical distribution systems

TN-C system

the neutral and the exposed-conductive-parts are connected to the same


earthing arrangement

the exposed-conductive-parts are connected to the earth electrode by


means of the PEN

PEN

Classification of electrical distribution systems

TN system

the earth fault current returns to the power supply node without practically
affecting the earth electrode

the current is limited by the impedance of the fault loop

Classification of electrical distribution systems

TN system

It is necessary to interrupt the fault because person touching the exposedconductive-part is subjected to the voltage UT

Classification of electrical distribution systems

Condition to be fulfilled :

Z S Ia U0

Zs is the impedance of the fault loop

U0 is the nominal voltage to earth

Ia is the diconnection time in ampere of the protective devices within:

the time defined in the following table for the terminal circuits with a
rated current In<32

within 5 sec for distribution circuits or terminal circuits with a rated


current In>32A

Classification of electrical distribution systems

TN system: example

Un = 400 V (U0=230V)

This system supplies a terminal circuit with In>32A

Earth fault = 3 kA

Classification of electrical distribution systems

Conclusion about TN system:

Industries and big installations with MV power supply

Fault current values similar to those of the single-phase fault

The standard allow the use of:

Automaic devices against overcurrents

RCD or CBs with G function

In the TN-C systems disconnection of the neutral and use of the residual
current devices or devices with similar operating principle (function G against
earth fault) is not possible

if automatic disconnection cannot be obtained in compliance with the


disconnection times of the table or within the conventional time, it shall be
necessary to provide supplementary equipotential bonding connected to
earth, however the use of supplementary protective bonding do not exclude
the need to disconnect the supply for other reasons, for the example
protection against fire, thermal stresses in equipment

Classification of electrical distribution systems

Why in TN-C system it is not possible to use RCD or


function G against earth fault?

TN-S

TN-C

Classification of electrical distribution systems

IT system

has no active parts directly earthed

may have live parts connected to earth through high value impedance

the exposed-conductive-parts are connected to an independent earth


electrode

Classification of electrical distribution systems

IT system

The earth fault current returns to the power supply through the earthing
arrangement of the exposed-conductive-parts and the capacities to earth of
the line conductors

the fault current value depends on the size of the installation

Plate

Dieletric
insulator+air

Plate area

Electric field

Classification of electrical distribution systems

capacities to earth of the line conductors

capacitor

electric field
plate area

plate area
dielectric

cable

plate area
electric field

dielectric
insulator+air
plate area

Classification of electrical distribution systems

IT system

the automatic disconnection of the circuit is not necessary

condition to be fulfilled:

RE I d 50V

RE is the sum of the resistance, in ohms, of the earth electrode and


protective conductor for exposed-conductive-parts;

Id

is the fault current, in amperes, of the first fault of negligible


impedance between a line conductor and an exposed-conductive-part;
such value takes account of the leakage currents and of the total earthing
impedance of the electrical installation

an insulation monitoring device shall be provided to indicate the presence of


fault.

Classification of electrical distribution systems

IT system

the occurrence of a first earth fault modifies the distribution system

two situations may occur in the event of a fault to earth

Classification of electrical distribution systems

IT system

the occurrence of a first earth fault modifies the distribution system

two situations may occur in the event of a fault to earth

Classification of electrical distribution systems

IT system

in the event of a second fault, the supply shall be disconnected

according to TT system

Classification of electrical distribution systems

IT system

in the event of a second fault, the supply shall be disconnected

according to TN system

Classification of electrical distribution systems


Neutral distribuited:

U
Zs
2 Ia

Neutral not distribuited:

U0
Z
2 Ia
'
s

U0= is the nominal voltage between line conductor and


neutral conductor
U = is the nominal voltage between line conductor
Zs = is the impedance of the fault loop comprising the line
conductor and the protective conductor of the circuit
Zs= is the impedance of the fault loop comprising the neutral
conductor and the protective conductor of the circuit
Ia = is the current causing the operation of protective device
within the time required for TN system

Classification of electrical distribution systems

Conclusion about IT system:

chemical and petrochemical industries, i.e. plants for


which service continuity is fundamental

fault currents A ~ 2A dependent on the size of the


installation

system suitable for the cases in which service continuity


must be assured

The presence of a first fault does not cause high current


and/or currents dangerous for the people

Protection Solution

A reliable and safe protection is realized by combining:

The protection functions against overcurrent with those against


earth faults

An effective earthing arrangement

This choice allows to obtain:

Protection against indrect contact

A timely protection against earth falts of small value where


prevention from fire risks is absolutely necessary

Protection Solution

For an adequate protection against earth faults


ABB has designed the following product
categories:

Miniature circuit breaker

Residual current operated circuit-breakers with integral


overcurrent protection DS201 & DS202;

Residual current operated circuit-breakers with integral


overcurrent protection DS200;

Residual current operated circuit-breakers with integral


overcurrent protection DS800

Residual current blocks DDA200

Residual current blocks DDA 60, DDA 70, DDA 90 (S290)

Residual current blocks DDA 800

Residual current circuit breaker F200

Protection Solution

Miniature circuit-breaker

Residual current operated circuit-breakers with integral


overcurrent protection DS201

Protection Solution

Miniature circuit-breaker

Residual current operated circuit-breakers with integral


overcurrent protection DS202

Protection Solution

Miniature circuit-breaker

Residual current operated circuit-breakers with


integral overcurrent protection DS200

Protection Solution

Miniature circuit-breaker

Residual block DDA200

Protection Solution

Miniature circuit breaker

Residual block DDA 60, DDA 70, DDA 90

Protection Solution

Miniature circuit breaker

Residual block DDA 800

Protection Solution

Miniature circuit breaker

Residual current circuit breaker F200

Protection Solution

For an adequate protection against earth faults


ABB SACE has designed the following product
categories:

Moulded case circuit breaker

RC221 residual current devices

RC222 residual caurrent devices

RC223 residual current devices

Electronic release LSIG: PR222, PR223

Electronic release LSIG: PR331, PR332

Electronic release LSIRc: PR332

Description

Protection Solution

Moulded case circuit breaker

Residual current devices RC221, RC222, RC223

Protection Solution

Moulded case circuit breaker

Electronic releases LSIG:

PR222: T2, T4, T5, T6

PR223: T4, T5, T6

PR331, PR332: T7

G function setting
I4= 0.2..1 x In
t4= 0.1.0.8 x In con I2t=k o t=k

(depending by the type of


release)

Protection Solution

G function:

currently used in MV/LV transformer substations to protect


both transformers as well as distribution lines

guarantees selectivity with regard to the residual current


releases located on the load side

can be used for protection against indirect contact, when


allowed by the installation conditions

improve protection against earth faults with regard to the


normal phase protections

Protection Solution

Moulded case circuit breaker

Electronic release PR332 LSIRc for T7

Protection Solution

Moulded case circuit breaker

Summary table

Protection Solution

For an adequate protection against earth faults


ABB has designed the following product
categories:

Air circuit breakers

Electronic releases LSIG: PR331, PR332, PR333

Electronic release LSIG: PR121, PR122, PR123

Electronic release LSIRc: PR332

Electronic release LSIRc: PR122

Description

Protection Solution

For an adequate protection against earth faults


ABB has designed the following product
categories:

Air circuit breakers

Electronic releases LSIG: PR331, PR332, PR333

Electronic releases LSIG: PR121, PR122, PR123

G function setting
I4= 0.2..1 x In
t4= 0.1.0.8 x In con I2t=k o t=k
(depending by the releases)

Protection Solution

For an adequate protection against earth faults


ABB has designed the following product
categories:

Air circuit breaker

Electronic releases LSIRc: PR332

Electronic releases LSIRc: PR122

Protection Solution

For an adequate protection against earth faults


ABB has designed the following product
categories

Residual current relay with external trasformer

SACE RCQ switchboard electronic residual current relay

Residual current relay for DIN rail: RD2 & RD3

Protection Solution

For an adequate protection against earth faults


ABB has designed the following product
categories

Residual current relay with external trasformer

SACE RCQ switchboard electronic residual current relay

Protection Solution

For an adequate protection against earth faults


ABB has designed the following product
categories

Residual current relay for DIN rail: RD2

Protection Solution

For an adequate protection against earth faults


ABB has designed the following product
categories

Residual current relay for DIN rail: RD3

Protection Solution

For an adequate protection against earth faults


ABB has designed the following product
categories

Front panel residual current relay: ELR

Discrimination of the protections against earth fault

Two types of residual current discrimination

horizontal residual current discrimination

vertical residual current discrimination

Discrimination of the protections against earth fault

To ensure discrimination

for residual current CBs type S located on the supply side


(in compliance with Standards IEC 61008-1 and IEC 61009)

downstream non-selective residual current CBs having


In three times lower

for residual current electronic releases (RC 221/222/223,


RCQ and RD2)

tripping times and currents of the device on the supply


side are immediately higher than those of the device
on the load side

Discrimination of the protections against earth fault

Example

E1N

1250 PR121/P-LSIG In=1250A 4p

T5N

400 PR222DS/P-LSI In =400A con


RC222

T1B

160 TMD In=160A con RC221

Discrimination of the protections against earth fault

Example

Application of RCD

Domestic Installation (TT)

Id

RCCB

MCB
Load

MCB
Load

Application of RCD

Industrial installation (TN-S)

long cables
CB+RC

Id

Application of RCD

Protection function G or residual current protection?

the choice can be done taking in consideration:

the distribution system

the value of the fault current

particularly suitable for protection of people

absolutely necessary

RCD:

in TT systems (small fault current to earth)

earthing of the exposed-conductive-parts is deficient

normal protections are not sufficient to provide


protection that falls within the limits set by the Standards

dangerous environmental conditions (e.g. excessive


humidity)

Application of RCD

G function:

currently used in MV/LV transformer substations to protect


both transformers as well as distribution lines

guarantees selectivity with regard to the residual current


releases located on the load side

can be used for protection against indirect contact, when


allowed by the installation conditions

improve protection against earth faults with regard to the


normal phase protections

Application of RCD

Typical application:

all types of construction sites (building, naval, etc.)

mobile equipment or plants

hospital environments and operating rooms

excavations and mines

campground electric installations

pools, saunas, canteens and, generally, environments with


high humidity levels

aquarium and fountain lighting

agricultural premises

school laboratories

Вам также может понравиться