Академический Документы
Профессиональный Документы
Культура Документы
Welcome
Technical Sharing Session
ABB Group
March 12, 2014 | Slide 1
Electrical Installation
Circuit Breaker Selection
ABB Group
March 12, 2014 | Slide 2
Protection of Transformers
Protection of Transformers
Switchboards with one transformer
Sn
U20
In
Isc
where
Sn = rated power of the transformer [kVA]
U20 = rated secondary voltage (no load) of the transformer [V]
ln = rated current of the transformer, LV side [A]
Protection of Transformers
The full voltage three-phase short circuit current immediately after the LV
side of the transformer can be expressed by the following relation once we
suppose infinite power at the primary:
Isc =
In x 100
Ucc %
where
Ucc %= short circuit voltage of the transformer [%]
ln = rated current, LV side, [A]
lsc = three-phase rated short circuit current, LV side, [A]
The short circuit current is normally lesser than the deduced value if
the circuit breaker is installed at a certain distance by means of a cable
or bar connection, according to the connection impedance.
Protection of Transformers
Switchboards with more than 1 transformer in Parallel
Isc2 + Isc3
I1
I2
I3
Circuit breaker A
Isc1
I5
Isc1 + Isc2 + Isc3
Circuit breaker B
I4
Protection of Transformers
As far as the calculation of the rated current of the transformer is
concerned, the rules beforehand indicated are completely valid.
The minimum breaking capacity of each circuit breaker LV side must be
greater than the highest of the following values: (the example refers to
machine 1 of the figure and it is valid for the three machines in parallel):
lsc 1 (short circuit current of transformer 1) in case of fault
immediately downstream circuit breaker 1;
Protection of Cables
The choice of the circuit breakers for switching and protection of cables
means the perfect knowledge of:
rated operating line current lB
max admissable cable current lZ
presumed short circuit current in the point of installation of the circuit
breaker Icc
Protection of Cables
The correct circuit breaker must be selected to satisfy the following
conditions:
It must have a short circuit breaking capacity (lcu or eventually lcs) greater
or equal to the short circuit current lcc
It must use a protection release so that its overload setting current ln (l1)
satisfies the relation lB < ln < lZ (Oveload protection)
The let through energy (l2t) that flows through the circuit breaker must be
lesser or equal to the maximal one allowed by the cable (KS) (Shortcircuit protection)
Protection of Cables
It
Cable KS
Circuit breaker It
Icc max
Icc
Protection of Cables
I function protection
against instantaneous
short-circuit
G function protection
against earth-fault
The example emphasizes the need for coordination between circuit breakers A and
B, such that in case of fault in C, only circuit
breaker B trips, thus leaving complete
continuity to the rest of the plant supplied
by the circuit breaker A.
Selectivity might be Total or Partial:
ImB
ImA
Total selectivity
Switchboard A
2500 kVA
(fault current 57,5 kA)
E4S40
with PR121
400V
E2N20
with PR121
Switchboard B
E2N20 MS (disconnector)
400V
T5H 630
with PR222
This co-ordination solution is used by those who need to contain the plant
costs by reducing the general performance in case of a fault.
Icc = 65 kA
Ib = 300 A
Icc 30 kA
U
Load
Rated
current
Type
[A]
Rated
uninterrupted
current
Iu [A]
Breaking
capacity
Selectivity
limit
Back-up
limit
Icu [kA]
[kA]
[kA]
36 (T)
65
1300
1600
130
300
320
36
T4S 250
50 kA !!!
T1N 160
* T1N 160 is 36 kA only mccb
70 kA
Iu
In
Icu
Ue Un
Icu or Ics Ik
Icm Ip
Distribution systems
Protection against indirect contact
and earth fault
ABB Group
March 12, 2014 | Slide 34
Agenda
Main definitions
Definitions
Indirect contact
Electric contact of persons with exposed-conductive-parts
which have become live under fault condiction (deterioration)
Direct contact
Electric contact of persons with live parts
Definitions
Earth fault
The loss of insulation between normally live conductors and exposedconductive-parts may generate a earth fault
Main causes of the loss of insulation:
mechanical breaking
rodent action
Definitions
Definitions
A contact with a live part causes the flowing of current through
the human body, the danger of this current depends on its :
duration
size
Time-current zones of the effects of alternating current on the human body
1 No reaction
2
No physiological effect
Definitions
Exposed-conductive-part
Conductive part
Can be touched
Live part
Definitions
Basic insulation
Supplementary isolation
Double isolation
Reinforced insulation
Fault current
current which flows across a given point of fault resulting from an insulation
fault
Definitions
Live part
functional isolation: in an electrical device it insulates the parts at different potentials
thus enabling operations
basic insulation is the insulation of the normally live parts
supplementary insulation is applied in addition to basic insulation in case of a failure of
the last
reinforced insulation, a unique insulation which can guarantee the equivalent protection
degree which can be provided by basic insulation plus supplementary insulation
Definitions
Reference earth
Earth electrode
Earthing resistance
resistance between the main earth collector (or node) and the Earth
Definitions
Protective conductor PE
it connects:
exposed-conductive-parts
earth electrode
PEN conductor
Residual current:
vectorial sum of the values of the electric currents in all live conductors
N
PE
L1
L3
L2
The IEC 60364-3 classifies the electrical systems with the combination of two letters
The first letter indicates the relationship of the power system to earth
I all live parts isolated from earth or one point connected to earth through an
impedance
The second letter indicates the relationship of the exposed-conductive- parts of the
installation to earth
PE
PEN
TT system
TT system
The earth fault current returns to the power supply node through the soil
TT system
Ik
Condition to be fulfilled :
Ra I Dn U 0
IDn is the rated residual operating current of the residual current circuitbreaker
the time defined in the following table for the terminal circuits with a
rated current In<32A
Thanks to a more sensitive residual current device, from a pratical point of view it
will be easier to realize an earthing system coordinated with the characteristics of
the device itself. This table shows the maximum values of earth resistance which
can be obtained with residual current devices and making reference to a common
environment (50V)
trip coil
main contact
test button
electronic circuit
(if any)
resistance
toroid
TEST
Condition to be fulfilled :
Z s Ia U0
the time defined in the following table for the terminal circuits with a
rated current In<32A
CBs
Residual
current devices
TN-S system
PE
TN-C system
PEN
TN system
the earth fault current returns to the power supply node without practically
affecting the earth electrode
TN system
It is necessary to interrupt the fault because person touching the exposedconductive-part is subjected to the voltage UT
Condition to be fulfilled :
Z S Ia U0
the time defined in the following table for the terminal circuits with a
rated current In<32
TN system: example
Un = 400 V (U0=230V)
Earth fault = 3 kA
In the TN-C systems disconnection of the neutral and use of the residual
current devices or devices with similar operating principle (function G against
earth fault) is not possible
TN-S
TN-C
IT system
may have live parts connected to earth through high value impedance
IT system
The earth fault current returns to the power supply through the earthing
arrangement of the exposed-conductive-parts and the capacities to earth of
the line conductors
Plate
Dieletric
insulator+air
Plate area
Electric field
capacitor
electric field
plate area
plate area
dielectric
cable
plate area
electric field
dielectric
insulator+air
plate area
IT system
condition to be fulfilled:
RE I d 50V
Id
IT system
IT system
IT system
according to TT system
IT system
according to TN system
U
Zs
2 Ia
U0
Z
2 Ia
'
s
Protection Solution
Protection Solution
Protection Solution
Miniature circuit-breaker
Protection Solution
Miniature circuit-breaker
Protection Solution
Miniature circuit-breaker
Protection Solution
Miniature circuit-breaker
Protection Solution
Protection Solution
Protection Solution
Protection Solution
Description
Protection Solution
Protection Solution
PR331, PR332: T7
G function setting
I4= 0.2..1 x In
t4= 0.1.0.8 x In con I2t=k o t=k
Protection Solution
G function:
Protection Solution
Protection Solution
Summary table
Protection Solution
Description
Protection Solution
G function setting
I4= 0.2..1 x In
t4= 0.1.0.8 x In con I2t=k o t=k
(depending by the releases)
Protection Solution
Protection Solution
Protection Solution
Protection Solution
Protection Solution
Protection Solution
To ensure discrimination
Example
E1N
T5N
T1B
Example
Application of RCD
Id
RCCB
MCB
Load
MCB
Load
Application of RCD
long cables
CB+RC
Id
Application of RCD
absolutely necessary
RCD:
Application of RCD
G function:
Application of RCD
Typical application:
agricultural premises
school laboratories