Вы находитесь на странице: 1из 20

Products

Solutions

Got Steam?
New Techniques for Measuring Steam Quality in Utilities

Slide 1

08/27/2014

Adam Battinieri

Services

Got Steam? New Techniques for Measuring Steam Quality in Utilities

How does steam safety impact you?

Slide 2

08/27/2014

Adam Battinieri

Got Steam? New Techniques for Measuring Steam Quality in Utilities

What we dont measure- we cant control


What is Wet Steam?
80% steam quality

Do you know the quality of your Steam?


100% steam quality

Slide 3

08/27/2014

Adam Battinieri

Got Steam? New Techniques for Measuring Steam Quality in Utilities

How do you measure steam quality?


3 Components:
Pressure
Temperature
Amount of liquid (condensate)

Slide 4

08/27/2014

Adam Battinieri

Got Steam? New Techniques for Measuring Steam Quality in Utilities

Where am I on the steam curve?

Slide 5

08/27/2014

Adam Battinieri

Got Steam? New Techniques for Measuring Steam Quality in Utilities

What is Dryness Fraction


Mass Fraction vs. Volume Fraction Quality is the % mass that is vapor

Quality = 1 Saturated Vapor


Quality = 0 Saturated Liquid

Slide 6

08/27/2014

Adam Battinieri

Got Steam? New Techniques for Measuring Steam Quality in Utilities

Application Example Why dryness fraction is a mass term


Low Pressure Steam: Steam Quality 90%
In volume terms: 99.9% of the volume is Vapor

Low Pressure Steam: Steam Quality 10%


In volume terms: 98.9% of the Volume is Vapor

Conclusion: 90% steam quality to 10% steam quality has a volume


difference of 1% resulting in a 340% difference in Energy

Slide 7

08/27/2014

Adam Battinieri

Got Steam? New Techniques for Measuring Steam Quality in Utilities

Dangers of Wet Steam


Water Hammer

Erode control valves

Premature failure of steam system

Slide 8

08/27/2014

Adam Battinieri

Got Steam? New Techniques for Measuring Steam Quality in Utilities

Impact: Supplying values you need

Direct Mass and Energy


NEW direct 4-20mA input allows temperature and pressure
correction with an output format a customer desires

Slide 9

08/27/2014

Adam Battinieri

Got Steam? New Techniques for Measuring Steam Quality in Utilities

Impact: Poor steam quality - expanded

Dryness fraction

Slide 10

08/27/2014

Adam Battinieri

Got Steam? New Techniques for Measuring Steam Quality in Utilities

Value: Steam quality energy correction

Slide 11

08/27/2014

Adam Battinieri

Got Steam? New Techniques for Measuring Steam Quality in Utilities

Prowirl 200 is optimized for steam measurement


IAPWS - table
The International Association for the
Properties of Water and Steam

Mass and energy


compensation for
wet/saturated and
superheated steam
Compensation with
temperature and
pressure (fixed or
dynamic)

Slide 12

08/27/2014

Got Steam? New Techniques for Measuring Steam Quality in Utilities

Causes of Wet Steam

Slide 13

08/27/2014

Adam Battinieri

Got Steam? New Techniques for Measuring Steam Quality in Utilities

Application example: How improving steam quality


impacts the bottom line
Improving your steam quality from 0.8 to 0.95 on a 13000 lb/hr Boiler
80% steam quality

How Much Money does improving my Steam quality from 0.8 to 0.95
save?

95k/year
Slide 14

08/27/2014

Adam Battinieri

95% steam quality

Got Steam? New Techniques for Measuring Steam Quality in Utilities

Application Example: Measuring in Mass vs. Energy


How much are you being
over charged if the steam
you are receiving is 0.9
dryness fraction?

Utility bill will be 8%


higher than it should be

Slide 15

08/27/2014

Adam Battinieri

Got Steam? New Techniques for Measuring Steam Quality in Utilities

What have we learned?

Boilerhouse, Marstons Brewery, UK

Your meter is wrong!!


Slide 16

08/27/2014

Adam Battinieri

Got Steam? New Techniques for Measuring Steam Quality in Utilities

Brewery Flow Measurement

FT

FT
8022

Air

8023
FT
8017

FT
03
FT
02

Fuel

Blow down

FT
01

Slide 17

08/27/2014

Adam Battinieri

FT
8016

FT8016
FT 02
Saturated
FT(Middle)
01Steam
Fuel
Oil
FT8023
No2bara
insulation
Air
FT8022
PCombustion
=
/ 29psi
FT8017
Saturated
FT 03Steam
T
343F
PSaturated
1bara
15psi
Saturated
Steam
T==173C
25C /Steam
77F
P = 8.5
bara
/ 123psi
Feed
Water
Q
=
1.55t/h
T
=
20C
/
68F
T
=
155C
311F
Q
=
0.785t/h
TT == 155C
/
311F
173C
/ 343F
DN 80
40
DN
QQ
==
13.650t/h
Q
=
2.4t/h
DN
8
2.4t/h
Q_m
=
4.6t/h
VLDN
=
2.6m/s
=
300
250
DN
80m
4.3m/s
Feed water V =
DN
80
DN=100
tank
Q_loss
182kW
= 61.8m/s
=V913.31kg/m
Q_m_cond.
= 0.32t/h
= 121.8cP

Got Steam? New Techniques for Measuring Steam Quality in Utilities

Your flowmeter is wrong!


Comparison of boiler outlet and sub-meters:
FT8023 (Boiler outlet): 4.6t/h
Sum of FT8017, FT8022 and FT8016: 2.4t/h + 2.4t/h + 1.55t/h
= 6.35 t/h

Deviation of 38%
Reason: Prowirl 73

Slide 18

08/27/2014

Adam Battinieri

Got Steam? New Techniques for Measuring Steam Quality in Utilities

What is your boiler operation & efficiency plan?

Slide 19

08/27/2014

Adam Battinieri

Classification:
Public

Slide 20

Thank you very much


for your attention

Вам также может понравиться