Monitoring Device
TPM
Contents
Subject
Page
Description
Description of Function
Diagram of Function
Specification Text
Description
The TPM Pressure Monitoring Device has been designed to
monitor pressure-controlled rooms and comprises a basic
unit with the FCCU-T Operator Terminal. As a supplementary option a matching pressure transducer can be supplied
if there is not one, i.e. to provide an independent monitoring
function.
The Monitoring includes:
indication of power supply failure
an visual alarm that cannot be deleted
an acoustic alarm
alarm via potential-free contact
The TPM uses the actual value output (analogue signal)
of the room pressure differential transducer, that is either
existing or is available as a supplementary option.
It provides a visual and acoustic alarm if the required
pressure is not reached. The acoustic alarm can be suppressed via a button on the operator terminal or stops
automatically after a period of time that can be set. The
alarm can be passed on via a potential-free contact.
Basic Unit
2
3
1
2
3
4
5
Pressure OK
Alarm (falling below required pressure)
Simultaneous acoustic alarm,
alarm passed on via relay
Required pressure exceeded
150
7.5
23
19
10
Description of Function
The TPM monitoring device is used to visualise and
monitor the room pressure. For this purpose the
pressure-linear analogue output signal of a pressure transducer is connected. This transducer usually simultaneously
acts as an actual value sensor for room control. In especially sensitive areas the use of an additional separate pressure
transmitter (recording of independent measured values)
is recommended. All standard diaphragm pressure transducers (possibly with a digital display) can be used because
the TPM can be programmed accordingly.
Room
p
Reference
room
Yellow LED
Green LED
Tolerance
Red LED +
acoustic alarm
Green
LED
Tolerance
Yellow LED
Key
N
L
: Neutral
: Supply voltage (230 VAC, depending on
device configuration, see sample order,
page 6, 24 VAC optional)
PE
: Technical earthing
GND
: Signal Ground
RC1
: Switching input changeover
RC2
: Not assigned
RC3
: Not assigned
1
: Input reference signal
2
: Not assigned
NO, C, NC: Alarm output to building central control,
(BMS)
volt-free, changeover contact
Power
supply
Switching inputs
Operator
terminal connection
Operator terminal
COM1
or
COM2
Specification Text
TPM
Pressure monitoring device to control room pressure, visual
and acoustic indication if required pressure is not reached
and visual indication if pressure is exceeded. Evaluation of
the actual output signal of an existing or optionally available
an additional pressure transducer to independently record
the room pressure.
The following values are monitored:
Pressure below the set/required pressure, visual alarm
red LED and acoustic alarm with adjustable acoustic
alarm time that can be suppressed on the operator
terminal, as well as passing on via potential-free contact.
Exceeding the set/required pressure, yellow LED
Set pressure OK, green LED
Special function:
Pressure reversal via switching input.
Supply voltage 230 VAC
Degree of protection IP21
Design changes reserved All rights reserved Gebrder Trox GmbH (01/2004) Leaflet No. E016NQ0
Sample Order
Type TPM, 230 VAC, M546EY2
Terminal cable, Art. No. M546EW5
Disclaimer
Purchase of goods and services is subject to Gebrder Trox GmbH standard terms and
conditions.
also show products and systems that were customised to specific customers requirements
and are only available in this form as customer-specific solutions. Some products and
systems provided in this brochure may show special equipment that is only available at an
additional charge.
Warranties only apply to explicit contracts between customers and the Company. The
details provided in this brochure are for general information purposes only. They are
not intended to guarantee any particular product properties or suitability for particular
purposes of use. They are only intended as general information. Illustrated products and
systems are only intended to show possible product alternatives. The illustrations may