Академический Документы
Профессиональный Документы
Культура Документы
Commissioning Guide
Contents
Contents
3 Network Commissioning .........................................................................................................3-1
3.1 Engineering Information ...............................................................................................................................3-3
3.1.1 Networking Diagram............................................................................................................................3-3
3.1.2 Wavelength Allocation Diagram ..........................................................................................................3-4
3.1.3 Optical Amplifier Configuration Diagram ...........................................................................................3-5
3.1.4 Orderwire Configuration Diagram.......................................................................................................3-5
3.1.5 NE Board Configuration ......................................................................................................................3-5
3.1.6 Fiber Connection Diagram................................................................................................................. 3-11
3.2 Requirements of Optical Power Commissioning ........................................................................................3-22
3.2.1 EDFA Optical Amplifier Units...........................................................................................................3-22
3.2.2 Raman Amplifier Units ......................................................................................................................3-23
3.2.3 OTU ...................................................................................................................................................3-24
3.2.4 OSC....................................................................................................................................................3-25
3.2.5 Other Boards ......................................................................................................................................3-25
3.3 Optical Power Commissioning Procedures .................................................................................................3-26
3.3.1 Commissioning at Station A (OTM) ..................................................................................................3-27
3.3.2 Commissioning at Station B (OLA)...................................................................................................3-29
3.3.3 Commissioning at Station C (OADM/ROADM)...............................................................................3-31
3.3.4 Commissioning at Station D (OLA)...................................................................................................3-40
3.3.5 Commissioning at Station E (OTM) ..................................................................................................3-40
3.4 Uploading NE Data .....................................................................................................................................3-41
3.5 Creating ONEs and Fiber Connection.........................................................................................................3-41
3.6 Testing the Wavelength Protection ..............................................................................................................3-41
3.7 Testing ALC ................................................................................................................................................3-44
3.8 Testing IPA ..................................................................................................................................................3-44
3.9 Testing APE.................................................................................................................................................3-45
3.10 Testing the Orderwire................................................................................................................................3-46
3.10.1 Testing the Addressing Call..............................................................................................................3-46
3.10.2 Testing the Conference Call .............................................................................................................3-46
3.11 Testing the Bit Errors.................................................................................................................................3-47
3.11.1 Testing the 10-Minute Bit Errors of Each Optical Channel .............................................................3-48
3.11.2 Testing the 24-Hour Network-Wide Bit Errors ................................................................................3-48
Issue 03 (2007-09-30)
Contents
ii
Issue 03 (2007-09-30)
Figures
Figures
Figure 3-1 Networking diagram of Project G.....................................................................................................3-3
Figure 3-2 Wavelength allocation diagram of Project G ....................................................................................3-4
Figure 3-3 Optical amplifier configuration diagram of Project G ......................................................................3-5
Figure 3-4 Orderwire configuration diagram of project G .................................................................................3-5
Figure 3-5 Board configuration of ONE A and ONE E (OTM) .........................................................................3-6
Figure 3-6 Board configuration of ONE B and ONE D (OLA) .........................................................................3-7
Figure 3-7 Board configuration of ONE C (OADM) .........................................................................................3-8
Figure 3-8 Board configuration of ONE C (ROADMDWC+DWC)..............................................................3-9
Figure 3-9 Board configuration of ONE C (ROADMWSD9+WSM9) ........................................................3-10
Figure 3-10 Board configuration of ONE C (ROADMWSD9+RMU9) ...................................................... 3-11
Figure 3-11 Fiber connection at station A (OTM, direction 1) .........................................................................3-12
Figure 3-12 Fiber connection at station B (OLA, direction 1) .........................................................................3-12
Figure 3-13 Fiber connection at station C (OADM, direction 1) .....................................................................3-13
Figure 3-14 Fiber connection at station C (ROADMDWC+DWC, direction 1) ..........................................3-14
Figure 3-15 Fiber connection at station C (ROADMWSD9+WSM9, direction 1) ......................................3-15
Figure 3-16 Fiber connection at station C (ROADMWSD9+RMU9, direction 1).......................................3-15
Figure 3-17 Fiber connection at station D (OLA, direction 1) .........................................................................3-16
Figure 3-18 Fiber connection at station E (OTM, direction 1) .........................................................................3-16
Figure 3-19 Fiber connection at station E (OTM, direction 2) .........................................................................3-17
Figure 3-20 Fiber connection at station D (OLA, direction 2) .........................................................................3-17
Figure 3-21 Fiber connection at station C (OADM, direction 2) .....................................................................3-18
Figure 3-22 Fiber connection at station C (ROADMDWC+DWC, direction 2) ..........................................3-19
Figure 3-23 Fiber connection at station C (ROADMWSD9+WSM9, direction 2) ......................................3-20
Figure 3-24 Fiber connection at station C (ROADMWSD9+RMU9, direction 2).......................................3-20
Figure 3-25 Fiber connection at station B (OLA, direction 2) .........................................................................3-21
Figure 3-26 Fiber connection at station A (OTM, direction 2) .........................................................................3-21
Issue 03 (2007-09-30)
iii
Figures
iv
Issue 03 (2007-09-30)
Tables
Tables
Table 3-1 Service requirement matrix in Project G ............................................................................................3-3
Issue 03 (2007-09-30)
3 Network Commissioning
Network Commissioning
Connect all the NEs in a network in line with the engineering design scheme.
Test the functions of the network, such as the orderwire and protection switching.
Test quality of the long-term communication in the network through alarms and
performance events.
Describes
Issue 03 (2007-09-30)
3-1
3 Network Commissioning
3-2
Section
Describes
Issue 03 (2007-09-30)
3 Network Commissioning
Networking diagram
80 km (49.72 mi.)
22 dB
B
OTM
78 km (48.68 mi.)
21.45 dB
OLA
82 km (50.96 mi.)
22.55 dB
D
76 km (47.23 mi.)
20.9 dB
OLA
OADM
OTM
Service Requirement
Table 3-1 lists the service requirements in Project G.
Table 3-1 Service requirement matrix in Project G
Station
4 x STM-64
4 x STM-64
1 x STM-16
4 x STM-64
4 x STM-64
4 x STM-64
4 x STM-64
1 x STM-16
a: The inter-board wavelength protection is required for 1 x STM-16 service between stations A and E.
Issue 03 (2007-09-30)
3-3
3 Network Commissioning
192.10THz
LWF
192.20THz
LWF
192.30THz
LWF
192.40THz
LWF
192.50THz
LWF
192.60THz
STM-64
STM-64
STM-64
STM-64
STM-64
STM-64
STM-64
LWF
192.10THz
STM-64
LWF
192.20THz
STM-64
LWF
192.30THz
STM-64
LWF
192.40THz
LWF
192.50THz
LWF
192.60THz
LWF
192.70THz
LWF
192.80THz
STM-64
LWF
192.70THz
STM-64
LWF
192.80THz
LWC1 192.90THz
LWC1 193.00THz
3-4
STM-16 (Woking)
STM-16 (Protection)
LWC1 192.90THz
LWC1 193.00THz
Issue 03 (2007-09-30)
3 Network Commissioning
From
V40
OBU
-C03
DCM-D
DCM-D
OAU
-C03
OAU
-C03
OAU
-C03
OAU
-C03
DCM-D
DCM-D
To
D40
80 km (49.72 mi.)
22 dB
OBU
-C03
OBU
-C03
O
A
D
M
DCM-D
DCM-D
OAU
-C03
OAU
-C03
OAU
-C03
OAU
-C03
DCM-D
DCM-D
78 km (48.68 mi.)
21.45 dB
82 km (50.96 mi.)
22.55 dB
To
D40
OBU
-C03 From
V40
76 km (47.23 mi.)
20.9 dB
For indices of the boards with different specifications in Figure 3-3, refer to the OptiX BWS 1600G
Backbone DWDM Optical Transmission System Product Description.
OTM
OLA
OADM
OLA
Phone number
101
Phone number
102
Phone number
103
Phone number
104
OTM
Phone number
105
The client-side optical modules on the LWFs on OTM and OADM stations are S-64.2b modules and
the WDM-side optical modules are PIN NRZ 100GHz modules.
The client-side optical modules on the LWC1 are I-16 modules and the WDM-side optical modules
are PIN NRZ 100GHz modules.
Issue 03 (2007-09-30)
3-5
3 Network Commissioning
L S
W W C
C C S
3-6
L L L L S L L L
W W W W C W W W W
F F F F C F F F
S S
C C
1 C
Issue 03 (2007-09-30)
3 Network Commissioning
Issue 03 (2007-09-30)
O
A
F S S
I C C
F
I
O
A
U 2 C
3-7
3 Network Commissioning
L L
W W
F F
M M L L F F S M M L L L L
R R W W I
I C R R W W W W
2 2 F F U U C 2 2 F F F F
3-8
S S
C C
2 C
Issue 03 (2007-09-30)
3 Network Commissioning
Issue 03 (2007-09-30)
L L L L S L L L L
W W WW C W W W W
F F F F C F F F F
F F S
I C
U U C
S S
A
U
B
U
C C
2 C
C
A
B
U
A
U
3-9
3 Network Commissioning
L L L L
S L L L L
W W W W
C WW W W
F F F F
C F F F F
F F S
I C
U U C
S S
C C
2 C
3-10
Issue 03 (2007-09-30)
3 Network Commissioning
L L L L
S L L L L
W W W W
C W W W W
F F F F
C F F F F
M R
F F S M R
R M
I C R M
2 U
9
D
9
U U C 2 U
9
D
9
O
A
O
B
S S
C C
M
C
O
B
O
A
2 C
Direction 1: A
Direction 2: E
If the D40 connects to an OTU whose WDM side is a 2.5Gbit/s APD receiver, add a 10 dB fixed
optical attenuator to the IN interface of this OTU.
The fixed optical attenuator configured at the RX interface of the LWF is of 7 dB.
The fibers between the FIU and ODF subrack, the fibers between the LWF and client equipment and
the fibers between cabinets are all external fibers that should be routed on site.
For the rules to configure optical attenuators, refer to Appendix A "Optical Attenuator Configuration
Rules".
Issue 03 (2007-09-30)
3-11
3 Network Commissioning
East
RX
LWF
OUT M40
RX
LWF
OUT M39
LWF
OUT M38
LWF
OUT M37
LWF
OUT M36
LWF
OUT M35
LWF
OUT M34
LWF
OUT M33
LWC1
OUT M32
LWC1
OUT M31
(M-03)
(M-04)
RX
(M-05)
RX
(M-06)
RX
(M-08)
ODF
RX
(M-09)
RX
OUT
V40
IN
OBU
OUT
RC
FIU
(D-09)
(D-01)
(M-02)
OUT
ODF
(M-10)
RX
SC1
(M-11)
TI1
TO11 RX
SCS
(U-03) TO12 RX
TM
RM
(D-06)
(U-01)
(U-02)
From
client
equipment
To
station B
Fixed attenuator
Variable attenuator
(X-nn): Subrack-slot. U indicates upper subrack. M indicates middle subrack. D indicates lower subrack.
East
DCM
TDC
IN
ODF
FIU
TC
OAU
IN
RDC
OUT
RC
TM
RM1
SC2
FIU
OUT
(D-09)
(D-01)
(D-05)
TM2
ODF
RM
(D-06)
From
station A
To
station C
Variable attenuator
(X-nn): Subrack-slot. U indicates upper subrack. M indicates middle subrack.
D indicates lower subrack.
3-12
Issue 03 (2007-09-30)
3 Network Commissioning
Figure 3-13, Figure 3-14, Figure 3-15 and Figure 3-16 show the fiber connection at station C
(direction 1).
Figure 3-13 Fiber connection at station C (OADM, direction 1)
To client equipment
TX
TX
L
W
F
West
L
W
F
TX
TX
L
W
F
L
W
F
RX RX
L
W
F
L
W
F
RX
L
W
F
L
W
F
East
IN
IN
IN
OUT
D02
D01
D02
A01
OUTOUT
A02 A01
OUT
A02
DCM
TDC
IN
ODF
FIU
TC
(M-05)
IN
OAU
(D-01)
RDC
OUT
IN
MR2 MO
IN
(M-01)
MR2 MO
(M-02)
MI
MR2 OUT
West
RM1
TM
MI
(M-08)
OUT RC
FIU OUT
(M-06)
(D-10)
ODF
East
SC2
TM2
RM
(D-06)
From
station B
To
station D
Fixed attenuator
Variable attenuator
(X-nn): Subrack-slot. U indicates upper subrack. M indicates middle subrack. D indicates lower subrack.
Issue 03 (2007-09-30)
3-13
3 Network Commissioning
To client equipment
TX
TX
L
W
F
West
(U-03) (U-04)
IN
D40
IN
D39
D01
TX
TX
L
W
F
L
W
F
(U-05) (U-06)
IN
RX
L
W
F
L
W
F
IN
RX RX
OUT
M40 M39
M38
M01
TDC
IN
ODF
FIU
TC
(M-05)
IN
OAU
(D-01)
IN
OUT
M37
OUT
ADD
MO
DWC
MI
DWC
(U-01)
(M-08)
West
OUT IN
OBU
OUT RC
FIU
OUT
(M-06)
(D-10)
ODF
East
RM1
TM
OUT
(M-11)
IN
DROP
RDC
East
M40M40
D40
(M-04)
DCM
L
W
F
D38 D37
D02
RX
L
W
F
L
W
F
SC2
TM2
RM
(D-06)
From
station B
To
station D
Fixed attenuator
Variable attenuator
(X-nn): Subrack-slot. U indicates upper subrack. M indicates middle subrack. D indicates lower subrack.
In Figure 3-15, the M40 and WSM9 all locate in the lower subrack of the cabinets on the right.
3-14
Issue 03 (2007-09-30)
3 Network Commissioning
TX
L
W
F
West
IN
ODF
FIU
TC
IN
(M-05)
OUT
M40
D39
OAU
East
(U-10) (U-11)
OUT
M39
M40
OUT
DM2
DM3
AM1
EXPO
WSD9
(D-01)
L
W
F
(D-13)
IN
DM1
IN
RX
L
W
F
OUT OUT
(M-13)
RDC
L
W
F
(U-08) (U-09)
IN
D40
DCM
IN
IN
RX RX
L
W
F
L
W
F
(U-03) (U-04)
IN
D40
RX
TX
L
W
F
(U-01) (U-02)
TDC
TX
L
W
F
AM2
EXPI
WSM9
(M-11)
OBU
FIU OUT
OUT RC
(M-06)
(D-10)
(D-11)
West
ODF
East
RM1
TM
AM3
OUT IN
TM2
SC2
RM
(D-06)
From
station B
To
station D
Fixed attenuator
Variable attenuator
(X-nn): Subrack-slot. U indicates upper subrack. M indicates middle subrack. D indicates lower subrack.
TX
L
W
F
West
L
W
F
(U-01) (U-02)
IN
D01
IN
ODF
FIU
TC
(M-05)
IN
OAU
(D-01)
L
W
F
TX
L
W
F
(U-03) (U-04)
IN
IN
RX
L
W
F
A01
D02
East
OUT
A02
MR2
(M-08)
IN
DM1
IN
L
W
F
OUT
OUT
(M-01)
RDC
RX
L
W
F
DM2
WSD9
DM3
AM1 AM2
EXPO EXPI
(M-04)
RM1
OUT
AM3 TOA
RMU9
(M-09)
West
TM
RX RX
L
W
F
MR2
DCM
TDC
IN
TX
ROA
OUT IN
OBU
OUT RC
FIU
(M-06)
(D-10)
OUT
ODF
East
SC2
TM2
RM
(D-06)
From
station B
To
station D
Fixed attenuator
Variable attenuator
(X-nn): Subrack-slot. U indicates upper subrack. M indicates middle subrack. D indicates lower subrack.
Issue 03 (2007-09-30)
3-15
3 Network Commissioning
East
DCM
IN
ODF
FIU
TC
IN
TDC
RDC
OAU
OUT
RC
TM
RM1
FIU
OUT
ODF
(D-09)
(D-01)
(D-05)
TM2
SC2
RM
(D-06)
From
station C
To
station E
Variable attenuator
(X-nn): Subrack-slot. U indicates upper subrack. M indicates middle subrack.
D indicates lower subrack.
East
D40
IN
LWF
TX
LWF
TX
LWF
TX
LWF
TX
LWF
TX
LWF
TX
(M-03)
D39
IN
D38
IN
(M-05)
DCM
D37
TDC
ODF
FIU
TC
IN
(D-09)
OAU
(D-12)
IN
RDC
(M-06)
D36
IN
(M-04)
OUT
IN
IN
(M-08)
D40
(M-13) D35
IN
D34
IN
ODF
(M-09)
LWF
TX
(M-10)
TM
RM
D33
IN
SC1
(D-06)
LWF
(M-11)
D32
IN
LWC1
(U-01)
D31
IN
LWC1
TX
TI1
TX TO11
SCS
TX TO12 (U-03)
(U-02)
From
station D
To
client
equipment
Fixed attenuator
Variable attenuator
(X-nn): Subrack-slot. U indicates upper subrack. M indicates middle subrack. D indicates lower subrack.
3-16
Issue 03 (2007-09-30)
3 Network Commissioning
East
M40 OUT
LWF
RX
LWF
RX
LWF
RX
LWF
RX
LWF
RX
LWF
RX
(M-03)
M39 OUT
M38 OUT
(M-04)
(M-05)
M37 OUT
(M-06)
M36 OUT
OUT
ODF
FIU
RC
OUT
OBU
(D-09)
IN
OUT
(D-01)
(M-08)
V40
(M-02) M35 OUT
M34 OUT
ODF
(M-09)
LWF
RX
(M-10)
M33 OUT
RM
TM
SC1
LWF
RX
(M-11)
(D-06)
M32 OUT
LWC1
(U-01)
M31 OUT
LWC1
TI1
RX TO11
SCS
RX TO12 (U-03)
(U-02)
From
client
equipment
To
station D
Fixed attenuator
Variable attenuator
(X-nn): Subrack-slot. U indicates upper subrack. M indicates middle subrack. D indicates lower subrack.
East
DCM
RDC
OUT
ODF
FIU
RC
OUT
(D-05)
TDC
OAU
IN
TC
(D-12)
RM
TM1
SC2
RM2
FIU
IN
(D-09)
ODF
TM
(D-06)
To
station C
From
station E
Variable attenuator
(X-nn): Subrack-slot. U indicates upper subrack. M indicates middle subrack.
D indicates lower subrack.
Issue 03 (2007-09-30)
3-17
3 Network Commissioning
Figure 3-21, Figure 3-22, Figure 3-23 and Figure 3-24 show the fiber connection at station C
(direction 2).
Figure 3-21 Fiber connection at station C (OADM, direction 2)
From client equipment
RX
West
L
W
F
(M-03) (M-04)
OUT
A02
RX
RX RX
L
W
F
To client equipment
L
W
F
TX
L
W
F
L
W
F
(U-01) (U-02)
A01 A02
A01
TX
TX
L
W
F
L
W
F
East
OUT
OUT OUT
TX
L
W
F
IN
IN
IN
IN
D02
D01
D02
D01
DCM
OUT
ODF
FIU
RC OUT
(M-06)
OBU
(D-03)
IN OUT
MR2 MI
OUT MR2 MI
(M-01)
(M-02)
MO
MR2 IN
(M-08)
West
RM
MO
MR2
IN
RDC
OUT
(M-09)
TDC
OAU
IN
TC
IN
FIU
(M-05)
(D-12)
ODF
East
TM1
SC2
RM2
TM
(D-06)
From
station D
To
station B
Fixed attenuator
Variable attenuator
(X-nn): Subrack-slot. U indicates upper subrack. M indicates middle subrack. D indicates lower subrack.
3-18
Issue 03 (2007-09-30)
3 Network Commissioning
RX RX
L
W
F
West
TX
RX
L
W
F
L
W
F
To client equipment
L
W
F
(U-08) (U-09)
OUT
M39
OUT
M38
M01
TX
L
W
F
L
W
F
OUT
M37
IN
IN
D40
M40M40
D39
D01
(M-02)
FIU
RC
OUT
(M-05)
OBU
(D-03)
IN
OUT
East
(U-10) (U-11)
IN
IN
D40
IN
DCM
RDC
TDC
DROP
DWC
MI
MO
(U-01)
TM1
DWC
(M-08)
West
RM
TX
L
W
F
(M-13)
ADD
OUT
L
W
F
D38 D37
D02
OUT
ODF
TX
IN OUT
OAU
IN TC
FIU
(M-06)
(D-12)
IN
ODF
East
SC2
RM2
TM
(D-06)
To
station B
Fixed attenuator
From
station D
Variable attenuator
(X-nn): Subrack-slot. U indicates upper subrack. M indicates middle subrack. D indicates lower subrack.
In Figure 3-23, the D40 and WSD9 all locate in the lower subrack of the cabinets on the right.
Issue 03 (2007-09-30)
3-19
3 Network Commissioning
RX RX
L
W
F
West
L
W
F
RX
L
W
F
(U-01) (U-02)
(U-03) (U-04)
OUT OUT
OUT
M40
TX
TX
L
W
F
L
W
F
IN
AM1
FIU
RC
OUT
(M-05)
OBU
IN
OUT
(D-03)
IN
D39
DCM
(D-02)
IN
DM1
OUT
OUT
IN
D40
M40
(M-02)
ODF
L
W
F
(U-10) (U-11)
IN
D40
TX
L
W
F
(U-08) (U-09)
OUT
M39
TX
L
W
F
AM2
AM3
EXPI
WSM9
EXPO
DM2
IN OUT
OAU
IN TC
FIU
IN
ODF
(M-06)
(D-12)
(D-04)
West
TDC
DM3
WSD9
(M-04)
East
TM1
RM
RDC
RM2
SC2
TM
(D-06)
To
station B
From
station D
Fixed attenuator
Variable attenuator
(X-nn): Subrack-slot. U indicates upper subrack. M indicates middle subrack. D indicates lower subrack.
L
W
F
West
RX RX
RX
L
W
F
L
W
F
L
W
F
OUT OUT
OUT
A02
A01
MR2
OUT
ODF
FIU
RC
(M-05)
OUT
OBU
(D-03)
IN OUT
TX
TX
L
W
F
L
W
F
IN
D01
L
W
F
IN
East
IN
D02
DCM
(M-08)
IN
DM1
ROA
EXPI EXPO
(M-02)
TM1
TX
(U-10) (U-11)
IN
DM2
DM3
WSD9
(M-11)
West
RM
L
W
F
(U-08) (U-09)
OUT
AM3 TOA
RMU9
TX
MR2
(M-01)
AM1 AM2
To client equipment
RDC
IN OUT
TDC
OAU
IN TC
(D-12)
FIU
(M-06)
IN
ODF
East
SC2
RM2
TM
(D-06)
To
station B
From
station D
Fixed attenuator
Variable attenuator
(X-nn): Subrack-slot. U indicates upper subrack. M indicates middle subrack. D indicates lower subrack.
3-20
Issue 03 (2007-09-30)
3 Network Commissioning
East
DCM
RDC
OUT
ODF
RC
FIU
OUT
(D-05)
TDC
OAU
IN
TC
(D-12)
RM
TM1
SC2
RM2
FIU
IN
ODF
(D-09)
TM
(D-06)
To
station A
From
station C
Variable attenuator
(X-nn): Subrack-slot. U indicates upper subrack. M indicates middle subrack.
D indicates lower subrack.
East
TX
LWF
IN
D40
TX
LWF
IN
D39
LWF
IN
D38
LWF
IN
D37
TX
LWF
IN
D36
TX
LWF
IN
D35 (M-13)
LWF
IN
D34
LWF
IN
D33
LWC1
IN
D32
LWC1
IN
D31
(M-03)
(M-04)
TX
(M-05)
TX
DCM
(M-06)
RDC
(M-08)
ODF
D40
(M-09)
TX
IN
OUT
TDC
OAU
IN
TC
FIU
(D-09)
(D-12)
IN
ODF
(M-10)
TX
SC1
(M-11)
TI1
TO11 TX
SCS
(U-03) TO12 TX
RM
TM
(D-06)
(U-01)
(U-02)
To
client
equipment
From
station B
Fixed attenuator
Variable attenuator
(X-nn): Subrack-slot. U indicates upper subrack. M indicates middle subrack. D indicates lower subrack.
Issue 03 (2007-09-30)
3-21
3 Network Commissioning
Tools/Instruments
None
None
Prerequisites
Required/As
needed
Required
Set-up diagram
None
The optical power commissioning serves to optimize the network performance parameter,
ensure that there is a margin for the system optical power without affecting the expansion, and
adjust the signal-to-noise ratio to the best value to ensure the long-term stable operation of the
system.
The basic requirements of optical power commissioning are as follows:
z
The optical power under commissioning should be between the permitted maximum and
minimum values.
Allowance is required to ensure that the power fluctuation within a range brings no
impact on the services.
Optical power commissioning should meet the requirement of system expansion from
the customer.
The requirements of the input optical power commissioning to each optical amplifier unit are the same.
Adjust the average per-channel input power of the optical amplifier unit and make it
close to the standard per-channel input power.
Standard per-channel input power = Maximum input optical power 10lgN, where N is
the maximum number of wavelengths
Adjust the average per-channel output power of the optical amplifier unit and make it
close to the standard per-channel output power.
Standard per-channel output power = Maximum output optical power 10lgN, where N
is the maximum number of wavelengths
3-22
If the average per-channel input power before the input end of the optical amplifier is
added with a variable attenuator is higher than the standard per-channel input power,
Issue 03 (2007-09-30)
3 Network Commissioning
adjust the variable attenuator before the amplifier to make the average per-channel input
power reach the standard value.
z
If the average per-channel input power before the input end of the optical amplifier is
added with a variable attenuator is lower than the standard per-channel input power,
remove the variable attenuator.
To the E2OAU, set the variable optical attenuator (VOA) inside the board to adjust the
output optical power of single wavelength to the standard value.
To the E3OBU and E3OPU, the gain is fixed. After the input optical power is adjusted,
the output optical power is obtained.
To the E3OAU and E4OAU, set the gain on the T2000-LCT to make the output of the
OAU reach the standard optical power.
Gain to be set = Standard per-channel output power Average per-channel input power
After the adjustment, the optical power of each channel on the optical amplifier unit
must be within the range of standard optical power 2 dB.
Raman amplifier emits strong light. Do not insert or remove the fiber connector when the
laser is working, to avoid damage to human body.
The basic requirements of Raman amplifier unit are as follows:
z
Test the optical power on the SYS interface of the Raman unit when the laser is enabled
and when it is disabled. Determine the on-off gain of the Raman unit.
On-off gain = Optical power on the SYS interface when the laser is enabled Optical
power on the SYS interface when the Raman laser is disabled
When the Raman amplifier is used in backward or forward pumping, the output optical
power is rather great. The greater the optical power is, the higher the requirements of the
fiber jumper become. Great optical power may bring damages to equipment and injuries
to human body. Thus, the power of the Raman pumping light should be as low as
possible on the premise that the on-off gain is not less than 10 dB. The maximum optical
power should be not more than 27 dBm.
Raman amplifier is used in the case of extremely low input optical power. When the SYS
interface of the Raman amplifier is connected to the OAU, the input optical power of the
OAU is still lower than the standard input optical power of single wavelength. Therefore,
the VOA is not needed.
Issue 03 (2007-09-30)
3-23
3 Network Commissioning
z
The requirement on the fiber line from the Raman unit lies on the single-point additional
loss in the line cable. The following are the requirements of the single-point additional
loss:
0 km10 km (0 mi.6 mi.): The single-point additional loss is less than 0.1 dB (G.652)
or 0.2 dB (G.655).
10 km20 km (6 mi.12 mi.): The single-point additional loss is less than 0.2 dB
(G.652) or 0.4 dB (G.655) and the single-point return loss is less than 40 dB.
The output optical power reaches 27 dBm when the Raman amplifier is used in
backward or forward pumping. Be careful of this. The fiber connector should be the
special APC fiber connector. If the PC fiber connector is used, great reflection burns the
fiber connector.
As for the Raman unit used for backward pumping, the strong pump light enters the fiber
through the input end (LINE) instead of the output end (SYS). Do not add any attenuator
or fiber jumper before the input end.
The bending radius of the fiber jumper should meet the requirement. The bending should
not be too great; otherwise, the fiber jumper is burnt.
The laser is by default to be turned off after the Raman amplifier is powered on. You can
turn on the laser by issuing a command.
Before the laser of the Raman amplifier is turned on, connect the fiber jumper of the
input end and that of the ODF cabinet. Keep the fiber clean when removing or inserting
the fiber. If there is dirt on the surface of the connector, the connector can be easily
damaged.
The Raman amplifier has a very strict requirement on the loss of the near-end line fiber.
Such a fiber should have no connector within the distance of 0 km20 km (12 mi.)
except that used to connect to the ODF. The fibers should be connected to each other by
melting.
3.2.3 OTU
For the parameters of each type of the OTU in the OptiX BWS 1600G, refer to the OptiX BWS
1600G Backbone DWDM Optical Transmission System Product Description.
The basic requirements of the optical power commissioning on the OTU are as follows:
z
Adjust the input optical power of the OTU to a value between the receiver sensitivity and
the overload point, at least 5 dBm less than the overload point and 3 dBm greater than
the receiver sensitivity.
The input optical power of the OTU is adjusted by adding or replacing the fixed
attenuator.
Usually, internal fixed attenuators of the DWDM are equipped before delivery. Only needed to make an
examination during the commissioning on site is required.
3-24
Since the output optical power of the receive-end amplifier is required to be set to that of
a single standard WDM wavelength, the fixed attenuator used on the WDM side of the
receive-end OTU should be fixed according to this.
The optical module used as the receiver on the client side is configured on the premise
that the client equipment adopts the same optical module and is installed in the same
equipment room. If the actual situation is not so, add, replace or remove the fixed
attenuator based on the actual optical power.
Issue 03 (2007-09-30)
3 Network Commissioning
The transmitting optical power on the client side and WDM side of the OTU requires no
commissioning.
Make sure the input optical power of the OTU (including the WDM side and line side) is
lower than the receiver overload to avoid damage to the optical module during commissioning.
Note the overload of the APD receiver laser is only 9 dBm.
3.2.4 OSC
For the parameters of each type of the OSC board in the OptiX BWS 1600G, refer to the
OptiX BWS 1600G Backbone DWDM Optical Transmission System Product Description.
The basic requirements of the optical power commissioning on the OSC are as follows:
z
The optical power of the OSC should be within the range from 45 dBm to 15 dBm.
A 15 dB fixed attenuator is required for the interconnection between the OSCs in the
station.
Issue 03 (2007-09-30)
3-25
3 Network Commissioning
Tools/Instruments
Flange
Fiber jumper
None
Prerequisites
Required/As
needed
Required
Set-up diagram
Before the OptiX BWS 1600G is connected to the line fiber in each station, you must:
z
Test the span loss to ensure the value is in accordance with the requirement of the
engineering design.
Test the transmission distance of the line signals to ensure the value is in accordance with
the requirement of the engineering design.
Check the type of the line fiber to ensure the value is in accordance with the requirement
of the engineering design.
If any one of the above conditions is not met, the system commissioning will be affected.
Thus, when the above conditions are not met, give feedback to the construction party who is
in charge to solve the problem.
As mentioned in section 3.1.6 "Fiber Connection Diagram", there are two directions: direction
1 and direction 2. Because the commissioning in the two directions are performed in a similar
way, only the commissioning in direction 1 is given. This section describes the optical power
commissioning on each station along the following link direction.
A
3-26
Issue 03 (2007-09-30)
3 Network Commissioning
After adjusting the optical power between the D40 and the OAU in the network commissioning, remove
the 15 dB attenuator that is added according to the requirements in section 2.2.5 "Adding Attenuators".
Make the client sides of all OTUs access the actual services. (recommended)
Access the signals from the splitter and perform the commissioning after the
maximum number of services is configured. Access the signal from the splitter
according to Figure 3-27. Go to Step 5.
LWF
OUT M40
RX
LWF
OUT M39
RX
LWF
OUT M38
LWF
OUT M37
LWF
OUT M36
LWF
LWF
OUT M34
LWF
OUT M33
LWC1
OUT M32
LWC1
OUT M31
(M-03)
(M-04)
(M-05)
RX
SDH/SONET
analyzer
(M-06)
RX
Splitter
(M-08)
RX
(M-09)
RX
V40
OUT
IN
OBU
(D-01)
(M-10)
RX
(M-11)
SDH/SONET
analyzer
TI1
TO11 RX
SCS
(U-03) TO12 RX
(U-01)
(U-02)
Fixed attenuator
Variable attenuator
(X-nn): Subrack-slot. U indicates upper subrack. M indicates middle subrack. D indicates lower subrack.
Step 3 Obtain the information on the optical module of the OTU by observing the bar code on the
front panel or the board manufacturing information. For this project, the client-side optical
module of the LWF is S-64.2b module and that on the LWC1 is I-16 module.
Step 4 Ask the equipment engineer of the customer to provide the transmitting optical power and the
optical module type of the equipment. Compare the optical power with the receiving optical
power on the client side of the OTU to determine if the fixed attenuator should be adjusted.
Record the receiving optical power on the client side of the OTU.
In Project G, we can learn from the OTU optical power commissioning requirements that the
input optical power of the client-side RX should be within the range from 6 dBm to 11
dBm (LWF) or from 8 dBm to 15 dBm (LWC1). If the measured input optical power of the
RX on the LWF and LWC1 without being added with an attenuator is 0 dBm and 5 dBm,
add a 7 dB fixed attenuator to the LWC1 and LWF. After the attenuator is added, the measured
optical power is 7 dBm and 12 dBm, which meets the requirements.
Issue 03 (2007-09-30)
3-27
3 Network Commissioning
Step 5 Check whether the WDM-side OUT interfaces on all OTUs emit lights or not. If not,
z
Check whether the accessed SDH/SONET services are normal or not. If not, clear the
fault first.
Check whether the OTU having no services emits light and whether the laser on the
OTU is enabled or not. If not, refer to section 2.11.2 to force the OTU to emit light and
to enable the laser.
Step 6 Test the output optical power of the OUT interface on the OTU. The value should be within
the range from 0 dBm to 5 dBm and is 2 dBm normally.
Step 7 Test the receiving optical power of the Mn interface of the V40 and record the value.
If the difference between the optical power and the optical power of the OUT interface on the OTU is
greater than 1 dB, check the fiber routing and clean the fiber.
Because the V40 is used in Project G, the principle of "observing the receive end and adjusting the
transmit end" should be adopted during commissioning. Adjust the VOA of each channel on the V40 to
ensure that the maximum difference of signal-to-noise ratio between channels is lower than 2 dB.
Step 8 Connect the optical spectrum analyzer to the OUT interface of the V40 by fiber jumper. Scan
the output multiplexed signal, record the optical power of each channel and of the multiplexed
signal, and determine the insertion loss of each channel on the V40. Check if the insertion loss
after each channel passes the V40 meets the requirement.
For insertion loss parameters, refer to the OptiX BWS 1600G Backbone DWDM Optical Transmission
System Product Description. If the output optical power does not meet the requirement, check if the Mn
interface is connected to a wrong interface.
Step 9 Connect the fiber jumper which is to be inserted into the IN interface of the OBU to the
optical spectrum analyzer. Scan the multiplexed signal. Adjust the mechanical variable
attenuator before the OBU to make the average per-channel input power of the OBU be close
to the standard per-channel input power (19 dBm).
Standard per-channel input power = Maximum input optical power 10lgN, where N is the
maximum number of wavelengths
Attenuation of the variable attenuator = Input optical power of the IN interface on the OBU
Output optical power of the OUT interface on the V40
Step 10 Test the output optical power of the OUT interface on the OBU. The standard per-channel
input power of the E3OBUC03 is +4 dBm. Adjust the optical power of each channel and
make it reach +4 dBm.
Step 11 Calculate the gain of each channel. The gain flatness should be less than 2 dB.
Gain of each channel = Per-channel output power Per-channel input power
Record the input/output optical power and gain of each channel and the input/output optical power of the
multiplexed signal on the OBU.
Step 12 Use a power meter to test the optical power of the RC interface on the FIU and record the
value.
If the difference between the optical power and the optical power of the OUT interface on the OBU is
greater than 1 dB, check the fiber routing and clean the fiber.
3-28
Issue 03 (2007-09-30)
3 Network Commissioning
Step 13 Test the optical power of the OUT interface on the FIU and determine the RC-OUT insertion
loss.
RC-OUT insertion loss on the FIU = Input optical power of the RC on the FIU Optical
power of the OUT on the FIU
Test the optical power of the OUT interface on the FIU when RM is disconnected. For the insertion loss
requirement, refer to the OptiX BWS 1600G Backbone DWDM Optical Transmission System Product
Description.
Step 14 Test the optical power of the TM interface on the SC1 and the RM interface on the FIU, and
calculate the RM-OUT insertion loss.
RM-OUT insertion loss on the FIU = Optical power of the RM on the FIU Optical power of
the OUT on the FIU (disconnect RC interface)
Test the optical power of the OUT interface on the FIU when RC is disconnected. For the insertion loss
requirement, refer to the OptiX BWS 1600G Backbone DWDM Optical Transmission System Product
Description.
During the commissioning, ensure that the fiber jumper for test and the optical interface and
fiber jumper that have ever been removed are clean. Make sure that there is no impact on the
system.
For details on how to clean fiber connectors, refer to Appendix A "Inspecting and Cleaning
the Fiber-Optic Connection" in the OptiX BWS 1600G Backbone DWDM Optical
Transmission System Troubleshooting.
----End
Step 3 Test the output optical power of the TM on the west FIU. Calculate the IN-TM insertion loss.
IN-TM insertion loss of the west FIU = Optical power of the IN interface at 1510 nm on the
FIU Optical power of the TM interface at 1510 nm on the FIU
Step 4 Test the input optical power of the RM1 and the output optical power of the TM2 on the SC2.
Issue 03 (2007-09-30)
3-29
3 Network Commissioning
Step 5 Test the optical power of the RM and the OUT interface on the east FIU (L-09). Calculate the
RM-OUT insertion loss.
RM-OUT insertion loss of the east FIU = Optical power of the RM interface at 1510 nm on
the FIU Optical power of the OUT interface at 1510 nm on the FIU
Record the optical power of the supervisory signal, the IN-TM insertion loss of the west FIU, and the
RM-OUT insertion loss of the east FIU. For the parameters of optical power and insertion loss, refer to
the OptiX BWS 1600G Backbone DWDM Optical Transmission System Product Description.
Step 6 Test the output optical power of the TC on the west FIU and calculate the IN-TC insertion
loss.
IN-TC insertion loss on the FIU = Optical power of a certain channel in IN interface on the
FIU Optical power of a certain channel in TC interface on the FIU
The received signals contain supervisory signals and main channel signals, and there is impact
from the noise. To avoid having incorrect test result, perform the test on a certain channel.
Step 7 Test the input optical power of the west OAU (L-01). Adjust the variable attenuator before the
OAU to make the input optical power on IN interface reach 19 dBm. Record the optical
power of each channel in IN interface on the OAU.
Step 8 Connect the optical spectrum analyzer to the OUT interface of the OAU by fiber jumper. Scan
the multiplexed signal. Adjust the OAU gain on the T2000-LCT and make the per-channel
output power of the OAU reach the standard value.
The standard value of the OAU per-channel output power is +4 dBm. Normally, a value close
to +4 dBm is required to be the optical power of each channel.
Gain to be set = Standard per-channel output power Average per-channel input power
Step 9 Calculate the gain of each channel on the OAU. The gain flatness should be less than 2 dB.
Gain of each channel = Per-channel output power Per-channel input power
Record the input/output optical power and gain of each channel and the input/output optical power of the
multiplexed signal on the OAU.
Step 10 Test the input and output optical power of the DCM and calculate the DCM insertion loss.
DCM insertion loss = DCM input optical power DCM output optical power
Step 11 Use an optical power meter to test the optical power of the RC interface on the FIU and
record the value.
If the difference between the optical power and the optical power of the OUT interface on the OAU is
greater than 1 dB, check the fiber routing and clean the fiber.
Step 12 Test the optical power of the OUT interface on the east FIU and calculate the RC-OUT
insertion loss.
3-30
Issue 03 (2007-09-30)
3 Network Commissioning
RC-OUT insertion loss on the FIU = Input optical power of the RC on the FIU Optical
power of the OUT on the FIU
Test the optical power of the OUT interface on the FIU when RM is disconnected. For the insertion loss
requirement, refer to the OptiX BWS 1600G Backbone DWDM Optical Transmission System Product
Description.
----End
Step 1 Check if the fiber connection between boards is correct based on the fiber connection diagram
and if the fiber on each board is well inserted. If not, correct the error immediately.
Step 2 Test the optical power of the west FIU and the SC2 by referring to section 3.3.2
"Commissioning at Station B (OLA)".
Step 3 Perform the commissioning on the west OAU by referring to section 3.3.2
at Station B (OLA)".
"Commissioning
Step 4 Test the receiving optical power of the IN interfaces of all west LWFs respectively and record
all the values.
Step 5 Connect the optical power meter to the IN interface of the LWF with the largest optical
power.
Step 6 After the commissioning of the west receiving optical amplifier is complete, adjust the
variable attenuator between the west OAU and the MR2. Make the input optical power of the
IN interface on the west LWF that has the highest receiving optical power reach 8 dBm, to
ensure that the input optical power of the IN interfaces on all the west LWFs is within the
range from 6 dBm to 10 dBm.
Step 7 Test the optical power of the IN interface on the first west MR2 and calculate the insertion
loss of the attenuator.
Insertion loss of the attenuator = Output optical power of the receiving optical amplifier OAU
Input optical power of the IN interface on the MR2
For the parameters of optical power and insertion loss, refer to the OptiX BWS 1600G Backbone DWDM
Optical Transmission System Product Description.
Step 8 Test the output optical power of the D01/D02/MO interface on the first west MR2 and
calculate the wavelength dropping insertion loss and the passthrough insertion loss.
Wavelength dropping insertion loss = Per-channel input power of dropping wavelengths on
the IN interface on the MR2 Output optical power of the D01/D02 interface on the MR2
Passthrough insertion loss = Per-channel input power of passthrough wavelengths on the IN
interface on the MR2 Per-channel output power of passthrough wavelengths on the MO
interface on the MR2
Issue 03 (2007-09-30)
3-31
3 Network Commissioning
Step 9 Repeat Steps 4 to 8 to complete the commissioning on the second west MR2.
Step 10 Use a spectrum analyzer to test the input optical power of the east OBU. Adjust the variable
attenuator between the west MR2 and the east MR2, to make the average input optical power
of the passthrough wavelengths in the input optical power of the east transmitting optical
amplifier OBU reach the standard value.
Step 11 Test the client-side transmitting optical power of the west LWF. There are the following two
situations:
z
If the client equipment is also newly installed, connect the LWF to the client equipment
for test.
If the client equipment is not connected, use a fiber to connect on the ODF the client-side
TX interface on the west LWF through a fixed optical attenuator to the client-side RX
interface on the east LWF of station C.
The client side of the LWF is connected to the client equipment normally after the commissioning. The
interconnection of the LWFs is for the testing of 24-hour bit errors in serial after an SDH/SONET
analyzer connects to station A after the commissioning.
Step 12 Test the optical power of the adding wavelengths on the east LWFs.
Step 13 Use a spectrum analyzer to test the input optical power of the east OBU. Adjust the variable
attenuator of each OTU and make the input optical power of the wavelength on the east OBU
reach the standard value.
Step 14 Test the optical power of the MI/A01/A02 and OUT interfaces on the east MR2 and calculate
the wavelength adding insertion loss and the passthrough insertion loss.
Wavelength adding insertion loss = Optical power of the A01/A02 interface on the MR2
Per-channel power of adding wavelengths on the OUT interface on the MR2
Passthrough insertion loss = Per-channel power of passthrough wavelengths on the MRI
interface on the MR2 Per-channel power of passthrough wavelengths on the OUT interface
on the MR2
For the parameters of optical power and insertion loss, refer to the OptiX BWS 1600G Backbone DWDM
Optical Transmission System Product Description.
Step 15 Perform the commissioning on the east OBU by referring to section 3.3.1
at Station A (OTM)".
"Commissioning
Step 16 Perform the commissioning on the east FIU by referring to section 3.3.2
Station B (OLA)".
"Commissioning at
----End
3-32
Issue 03 (2007-09-30)
3 Network Commissioning
"Commissioning
Set wavelengths that pass through from west to east to passthrough state.
Step 5 Measure the single-wavelength input optical power at the IN interface and the
single-wavelength output optical power at the MO and DROP interfaces of the west DWC.
Calculate the insertion loss of wavelengths dropped from IN to DROP and the insertion loss
of wavelengths that pass through IN to MO of the DWC.
Wavelength drop insertion loss = Single-drop-wavelength input optical power at the IN
interface of the DWC Single-drop-wavelength output optical power at the DROP interface of
the DWC
Wavelength passthrough insertion loss = Single-passthrough-wavelength input optical power
at the IN interface of the DWC Single-passthrough-wavelength output optical power at the
MO interface of the DWC.
For the parameters of optical power and insertion loss, refer to the OptiX BWS 1600G Backbone DWDM
Optical Transmission System Product Description.
Step 6 Use a spectrum analyzer to measure the single-wavelength input optical power at the IN
interface and the single-wavelength output optical power at the Dn interface of the west D40.
Calculate the insertion loss of the D40.
Per-channel insertion loss of the D40 = Single-wavelength input optical power at the IN
interface of the D40 Single-wavelength output optical power at the Dn interface of the D40
Step 7 Measure the input optical power at the IN interface of all the west LWFs. The measured input
optical power at the IN interface of all the west LWFs should be about 8 dBm that is within
the stipulated optical power range of 6 dBm to 10 dBm.
As for the OTU whose WDM side is a 2.5 Gbit/s APD receiver, add a 10 dB fixed optical attenuator to
the IN interface to obtain about 18 dBm optical power that is within the stipulated optical power range
of 16 dBm to 22 dBm.
Step 8 Test the client-side transmitting optical power of the west LWF. There are the following two
situations:
Issue 03 (2007-09-30)
3-33
3 Network Commissioning
z
If the client equipment is also newly installed, connect the LWF to the client equipment
for test.
If the client equipment is not connected, use a fiber to connect on the ODF the client-side
TX interface on the west LWF through a fixed optical attenuator to the client-side RX
interface on the east LWF of station C.
The client side of the LWF is connected to the client equipment normally after the commissioning. The
interconnection of the LWFs is for the testing of 24-hour bit errors in serial after an SDH/SONET
analyzer connects to station A after the commissioning.
Step 9 Use a spectrum analyzer to measure the input optical power of the east OBU. Set on the
T2000 the VOA that corresponds to each wavelength passing through the west DWC to adjust
the input optical power of each passthrough wavelength of the OBU to 19 dBm.
The single-wavelength input optical power of the OBU permits a tolerance of 1 dB; however, the
average of optical power of all the wavelengths input to the OBU should be 19 dBm.
Step 10 Measure the optical power at the Rx interface of the east LWF. Add, replace or remove a
fixed optical attenuator to obtain 6 dBm through 11 dBm input power at the Rx interface of
the LWF board.
Optical interfaces of the LWF used in this network scenario are of S-64.2b type. For client-side
specifications of other types of OTUs, refer to the OptiX BWS 1600G Backbone DWDM Optical
Transmission System Product Description.
Step 11 Measure the output optical power at the OUT interface of the east LWF. This value should be
from 0 dBm to 5 dBm, usually about 2 dBm.
Step 12 Use a spectrum analyzer to measure the single-wavelength received optical power at the Mn
interface and the single-wavelength output optical power at the OUT interface of the east M40.
Calculate the insertion loss of the M40.
For the parameters of optical power and insertion loss, refer to the OptiX BWS 1600G Backbone DWDM
Optical Transmission System Product Description.
Step 13 Use a spectrum analyzer to measure the input optical power at the IN interface of the east
OBU. Tune the VOA between the M40 and DWC to adjust the input optical power of each
add wavelength of the OBU to 19 dBm.
The single-wavelength input optical power of the OBU permits a tolerance of 1 dB; however, the
average of optical power of all the wavelengths input to the OBU should be 19 dBm.
Step 14 Measure the single-wavelength input optical power at the MI and ADD interfaces and the
single-wavelength output optical power at the OUT interface of the east DWC. Calculate the
insertion loss of wavelengths added from ADD to OUT and the insertion loss of wavelengths
that pass through MI to OUT of the DWC.
Wavelength add insertion loss = Single-add-wavelength input optical power at the ADD
interface of the DWC Single-add-wavelength output optical power at the OUT interface of
the DWC
Wavelength passthrough insertion loss = Single-passthrough-wavelength input optical power
at the MI interface of the DWC Single-passthrough-wavelength output optical power at the
OUT interface of the DWC
3-34
Issue 03 (2007-09-30)
3 Network Commissioning
For the parameters of optical power and insertion loss, refer to the OptiX BWS 1600G Backbone DWDM
Optical Transmission System Product Description.
Step 15 Perform the commissioning on the east OBU by referring to section 3.3.1
at Station A (OTM)".
"Commissioning
Step 16 Perform the commissioning on the east FIU by referring to section 3.3.2
Station B (OLA)".
"Commissioning at
----End
"Commissioning
Step 4 On the T2000, create three optical cross-connections: from the west FIU to the WSD9, from
the west FIU to the east FIU, and from the WSM9 to the east FIU.
For the method of creating optical cross-connections, refer to the OptiX BWS 1600G Backbone DWDM
Optical Transmission System Configuration Guide.
Step 5 Measure the single-wavelength input optical power at the IN interface and the
single-wavelength output optical power at the DMn and EXPO interfaces of the west WSD9.
Calculate the insertion loss of wavelengths dropped from IN to DMn and the insertion loss of
wavelengths that pass through IN to EXPO of the DWC.
Wavelength drop insertion loss = Single-drop-wavelength input optical power at the IN
interface of the WSD9 Single-drop-wavelength output optical power at the DMn interface
of the WSD9
Wavelength passthrough insertion loss = Single-passthrough-wavelength input optical power
at the IN interface of the WSD9 Single-passthrough-wavelength output optical power at the
EXPO interface of the WSD9
For the parameters of optical power and insertion loss, refer to the OptiX BWS 1600G Backbone DWDM
Optical Transmission System Product Description.
Step 6 Use a spectrum analyzer to measure the single-wavelength input optical power at the IN
interface and the single-wavelength output optical power at the Dn interface of the west D40.
Calculate the insertion loss of the D40.
Per-channel insertion loss of the D40 = Single-wavelength input optical power at the IN
interface of the D40 Single-wavelength output optical power at the Dn interface of the D40
Issue 03 (2007-09-30)
3-35
3 Network Commissioning
Step 7 Set on the T2000 the VOAs that correspond to the west wavelength drop channels
respectively of the west WSD9 to obtain 8 dBm input optical power at the IN interface of
each west LWF.
As for the OTU whose WDM side is a 2.5 Gbit/s APD receiver, add a 10 dB fixed optical attenuator to
the IN interface to obtain about 18 dBm optical power that is within the stipulated optical power range
of 16 dBm to 22 dBm.
Step 8 Test the client-side transmitting optical power of the west LWF. There are the following two
situations:
z
If the client equipment is also newly installed, connect the LWF to the client equipment
for test.
If the client equipment is not connected, use a fiber to connect on the ODF the client-side
TX interface on the west LWF through a fixed optical attenuator to the client-side RX
interface on the east LWF of station C.
The client side of the LWF is connected to the client equipment normally after the commissioning. The
interconnection of the LWFs is for the testing of 24-hour bit errors in serial after an SDH/SONET
analyzer connects to station A after the commissioning.
Step 9 Set on the T2000 the VOA that corresponds to each wavelength passing through the west
WSD9 to adjust the attenuation to 0.
Step 10 Use a spectrum analyzer to measure the input optical power of the east OBU. Set on the
T2000 the VOA that corresponds to each wavelength passing through the east WSM9 to
adjust the input optical power of each passthrough wavelength of the OBU to 19 dBm.
The single-wavelength input optical power of the OBU permits a tolerance of 1 dB; however, the
average of optical power of all the wavelengths input to the OBU should be 19 dBm.
Step 11 Measure the optical power at the Rx interface of the east LWF. Add, replace or remove a
fixed optical attenuator to obtain 6 dBm through 11 dBm input power at the Rx interface of
the LWF board.
Optical interfaces of the LWF used in this network scenario are of S-64.2b type. For client-side
specifications of other types of OTUs, refer to the OptiX BWS 1600G Backbone DWDM Optical
Transmission System Product Description.
Step 12 Measure the output optical power at the OUT interface of the east LWF. This value should be
from 0 dBm to 5 dBm, usually about 2 dBm.
Step 13 Use a spectrum analyzer to measure the single-wavelength received optical power at the Mn
interface and the single-wavelength output optical power at the OUT interface of the east M40.
Calculate the insertion loss of the M40.
For the parameters of optical power and insertion loss, refer to the OptiX BWS 1600G Backbone DWDM
Optical Transmission System Product Description.
Step 14 Use a spectrum analyzer to measure the input optical power at the IN interface of the east
OBU. Set on the T2000 the VOA that corresponds to each wavelength of the WSM9 to adjust
the input optical power of each add wavelength of the OBU to 19 dBm.
3-36
Issue 03 (2007-09-30)
3 Network Commissioning
The single-wavelength input optical power of the OBU permits a tolerance of 1 dB; however, the
average of optical power of all the wavelengths input to the OBU should be 19 dBm.
Step 15 Measure the single-wavelength input optical power at the EXPI and AMn interfaces and the
single-wavelength output optical power at the OUT interface of the east WSM9. Calculate the
insertion loss of wavelengths added from AMn to OUT and the insertion loss of wavelengths
that pass through EXPI to OUT of the WSM9.
Wavelength add insertion loss = Single-add-wavelength input optical power at the AMn
interface of the WSM9 Single-add-wavelength output optical power at the OUT interface of
the WSM9
Wavelength passthrough insertion loss = Single-passthrough-wavelength input optical power
at the EXPI interface of the WSM9 Single-passthrough-wavelength output optical power at
the OUT interface of the WSM9
For the parameters of optical power and insertion loss, refer to the OptiX BWS 1600G Backbone DWDM
Optical Transmission System Product Description. The insertion loss measured in the preceding step
includes the VOA attenuation, which differs from that measured when the VOA attenuation is set to 0.
Step 16 Perform the commissioning on the east OBU by referring to section 3.3.1
at Station A (OTM)".
"Commissioning
Step 17 Perform the commissioning on the east FIU by referring to section 3.3.2
Station B (OLA)".
"Commissioning at
----End
"Commissioning
Step 4 On the T2000, create an optical cross-connection from the west FIU to the WSD9.
In the ROADM station comprising the WSD9 and the RMU9 boards, the wavelengths added by the
RMU9 board do not need to be configured. In this case, just correctly establish physical fiber
connections.
For the method of creating optical cross-connections, refer to the OptiX BWS 1600G Backbone DWDM
Optical Transmission System Configuration Guide.
Step 5 Measure the single-wavelength input optical power at the IN interface and the
single-wavelength output optical power at the EXPO and DMn interfaces of the west WSD9.
Calculate the insertion loss of wavelengths dropped from IN to DMn and the insertion loss of
wavelengths that pass through IN to EXPO of the west WSD9.
Issue 03 (2007-09-30)
3-37
3 Network Commissioning
For the parameters of optical power and insertion loss, refer to the OptiX BWS 1600G Backbone DWDM
Optical Transmission System Product Description.
Step 6 Use a spectrum analyzer to measure the single-wavelength input optical power at the IN
interface and the single-wavelength output optical power at the Dn interface of the west MR2.
Calculate the insertion loss of the MR2.
Step 7 Set on the T2000 the VOAs that correspond to the west wavelength drop channels
respectively of the west WSD9 to obtain 8 dBm input optical power at the IN interface of
each west LWF.
As for the OTU whose WDM side is a 2.5 Gbit/s APD receiver, add a 10 dB fixed optical attenuator to
the IN interface to obtain about 18 dBm optical power that is within the stipulated optical power range
of 16 dBm to 22 dBm.
Step 8 Test the client-side transmitting optical power of the west LWF. There are the following two
situations:
z
If the client equipment is also newly installed, connect the LWF to the client equipment
for test.
If the client equipment is not connected, use a fiber to connect on the ODF the client-side
TX interface on the west LWF through a fixed optical attenuator to the client-side RX
interface on the east LWF of station C.
The client side of the LWF is connected to the client equipment normally after the commissioning. The
interconnection of the LWFs is for the testing of 24-hour bit errors in serial after an SDH/SONET
analyzer connects to station A after the commissioning.
Step 9 Use a spectrum analyzer to measure the input optical power of the east OBU. Set on the
T2000 the VOA that corresponds to each wavelength passing through the west WSD9 to
adjust the input optical power of each passthrough wavelength of the OBU to 19 dBm.
The single-wavelength input optical power of the OBU permits a tolerance of 1 dB; however, the
average of optical power of all the wavelengths input to the OBU should be 19 dBm.
Step 10 Measure the optical power at the Rx interface of the east LWF. Add, replace or remove a
fixed optical attenuator to obtain 6 dBm through 11 dBm input power at the Rx interface of
the LWF board.
Optical interfaces of the LWF used in this network scenario are of S-64.2b type. For client-side
specifications of other types of OTUs, refer to the OptiX BWS 1600G Backbone DWDM Optical
Transmission System Product Description.
Step 11 Measure the output optical power at the OUT interface of the east LWF. This value should be
from 0 dBm to 5 dBm, usually about 2 dBm.
3-38
Issue 03 (2007-09-30)
3 Network Commissioning
Step 12 Use a spectrum analyzer to measure the input optical power at the IN interface of the east
OBU.
z
As for wavelengths directly added through the RMU9, set on the T2000 the VOA that
corresponds to each optical interface of the RMU9 to adjust the input optical power of
each add wavelength of the OBU to 19 dBm.
The single-wavelength input optical power of the OBU permits a tolerance of 1 dB; however, the
average of optical power of all the wavelengths input to the OBU should be 19 dBm.
As for wavelengths added through the RMU9 after the wavelengths are multiplexed by
the MR2, perform the following substeps:
1.
Set the attenuation of the corresponding RMU9-imbedded VOA connected to the MR2
to 3 dB.
2.
Set the VOA attenuation between the MR2 and LWF to the minimum.
3.
Find out the smallest one among the input optical power values of wavelengths added
through the MR2 to the IN interface of the OBU. Adjust the optical power of each of the
other wavelengths to this smallest value to flatten the optical power.
4.
Set the attenuation of the corresponding RMU9-imbedded VOA connected to the MR2
to obtain 19 dBm per-channel optical power of wavelengths added through the MR2.
Step 13 Use a spectrum analyzer to measure the single-wavelength received optical power at the An
interface and the single-wavelength output optical power at the OUT interface of the east
MR2. Calculate the insertion loss of the MR2.
For the parameters of optical power and insertion loss, refer to the OptiX BWS 1600G Backbone DWDM
Optical Transmission System Product Description.
Step 14 Measure the single-wavelength input optical power at the EXPI and AMn interfaces and the
single-wavelength output optical power at the OUT interface of the east RMU9. Calculate the
insertion loss of wavelengths added from AMn to OUT and the insertion loss of wavelengths
that pass through EXPI to OUT of the RMU9.
Wavelength add insertion loss = Single-drop-wavelength input optical power at the AMn
interface of the RMU9 Single-add-wavelength output optical power at the OUT interface of
the RMU9
Wavelength passthrough insertion loss = Single-passthrough-wavelength input optical power
at the EXPI interface of the RMU9 Single-passthrough-wavelength output optical power at
the OUT interface of the RMU9
For the parameters of optical power and insertion loss, refer to the OptiX BWS 1600G Backbone DWDM
Optical Transmission System Product Description.
Step 15 Perform the commissioning on the east OBU by referring to section 3.3.1
at Station A (OTM)".
"Commissioning
Step 16 Perform the commissioning on the east FIU by referring to section 3.3.2
Station B (OLA)".
"Commissioning at
----End
Issue 03 (2007-09-30)
3-39
3 Network Commissioning
"Commissioning
"Commissioning at
Step 4 Connect the fiber jumper which is to be inserted into the IN interface of the D40 to optical
spectrum analyzer. Scan the multiplexed signal and record the optical power of each channel.
Step 5 Test the optical power of each channel on the Dn interface on the D40 and calculate the
insertion loss of each channel on the D40.
Insertion loss of each channel = Optical power of each channel on the IN interface on the D40
Optical power of each channel on the Dn interface on the D40
For the parameters of optical power and insertion loss, refer to the OptiX BWS 1600G Backbone DWDM
Optical Transmission System Product Description.
Step 6 Test the optical power of the WDM-side input interface (IN) on the OTU.
In Project G, we can learn from the OTU optical power commissioning requirements that the
input optical power of the WDM-side IN should be within the range from 6 dBm to 10
dBm (LWF) or from 5 dBm to 15 dBm (LWC1). If the measured input optical power does
not meet the requirements, add, replace or remove the fixed attenuator based on the measured
value to ensure that the receiving optical power of the OTU is within the required range.
Step 7 Test the client-side transmitting optical power of the west OTU. There are the following two
situations:
z
If the client equipment is also newly added to the network, it can be the client equipment
that tests the services for 24 hours after the OptiX BWS 1600G connects to the client
equipment.
If the OptiX BWS 1600G connects to no client equipment, the client-side TX interface
and the RX interface on the OTU at station E must be connected on the ODF after they
pass the fixed attenuator.
The client side of the OTU is connected to the client equipment normally after the commissioning. The
interconnection of the OTUs is for the testing of 24-hour bit errors in serial after an SDH/SONET
analyzer connects to station A after the commissioning.
----End
3-40
Issue 03 (2007-09-30)
3 Network Commissioning
After commissioning, check if there are channels that are wrongly connected in the following
ways, to ensure that there is no mismatch in the channels between the commissioned stations:
z
On the T2000-LCT, shut down the lasers of all OTUs at station A in the direction to
station C one by one. Check if the OTU with the corresponding channel at station C and
E reports the R_LOS alarm. When any alarm is raised, reopen the laser of the
corresponding OTU at station A in the direction to station C. if the alarm disappears, it
indicates that the corresponding fibers are correctly connected. If not, the corresponding
fibers are wrongly connected. Check the fiber connections again.
On the T2000-LCT, shut down the lasers of all OTUs at station E in the direction to
station C one by one. Check if the OTU with the corresponding channel at station C and
A reports the R_LOS alarm. When any alarm is raised, reopen the laser of the
corresponding OTU at station E in the direction to station C. if the alarm disappears, it
indicates that the corresponding fibers are correctly connected. If not, the corresponding
fibers are wrongly connected. Check the fiber connections again.
Tools/Instruments
T2000
Fiber jumper
Prerequisites
Required/As needed
As needed
Set-up diagram
The OptiX BWS 1600G supports the following wavelength protection modes:
Issue 03 (2007-09-30)
3-41
3 Network Commissioning
z
For details on each type of the protection mode, refer to the OptiX BWS 1600G Backbone
DWDM Optical Transmission System Product Description.
For details on how to configure each type of the protection mode, refer to the OptiX BWS
1600G Backbone DWDM Optical Transmission System Configuration Guide.
This section describes how to test the protection switching of the inter-board wavelength
protection between ONE A and ONE E in Project G.
Perform the following steps to test the inter-board wavelength protection between ONE A and
ONE E.
Step 1 Access the SDH analyzer on the client side of station A, and loop back the client side of
station E by fiber jumpers, as shown in Figure 3-28.
Step 2 Test the optical channel and make sure that there is no bit error.
Figure 3-28 Testing the inter-board wavelength protection switching
RX
TI1
TX
RO1
SDH
analyzer
S
C
S
LWC 1
LWC 1
LWC 1
LWC 1
Station A
Station
S
C
S
RO1
TI1
Step 3 Login in to the T2000. Double-click the optical NE icon in the Main Topology, and the status
figure of the optical NE is displayed.
Step 4 Right-click a subrack NE icon and select NE Explorer to display the NE Explorer dialogue
box.
Step 5 Select the subrack NE in the left-hand pane and choose Configuration > Wavelength
Protection Group from the Function Tree.
Step 6 Click Query, and all the wavelength protection groups are displayed in the protection group
list on the right side. The switching status of the protection groups and channel status should
be normal.
3-42
Issue 03 (2007-09-30)
3 Network Commissioning
TI1
TX
RO1
SDH
analyzer
S
C
S
LWC 1
LWC 1
LWC 1
LWC 1
Station A
Station
S
C
S
RO1
TI1
Step 7 The switch test of the inter-board wavelength protection can be performed in two ways:
z
Remove the fibers of the working channel (or shut down the laser of the transmit optical
interface of the OTU) to perform the switching, as shown in Figure 3-29.
Right-click the desired protection group on the T2000, and select Forced to Protection
to perform the switching.
Step 8 The switching status of the protection groups and channel status queried by the T2000 should
be consistent with the actual situation.
Step 9 Query the alarms on the T2000. The PS alarm must be reported.
Step 10 Use an SDH/SONET analyzer to test the service and the switching time. The services should
be available.
Step 11 If all the previous items meet the requirements, two methods can be used to restore the
switching status to normal:
z
Reconnect the fiber (or open the laser of transmit interface of the OTU).
Right-click the desired protection group in the Protection Group, and select Clear.
The switching status should be restored to normal within the time set in WTR Times(s) field.
Step 12 Refer to Steps 7 to 11, and test the Manual to Protection.
----End
If the inter-board wavelength protection switching occurs, the SCC board of the switched NE reports
the OPS_PS_INDI alarm.
Refer to the above test procedures for the test of other protection modes.
For the SDH services, read the switching time directly in the SDH analyzer.
For the data services, such as GE, ESCON and FICON, read the packet loss ratio in the test instrument
and then figure out the switching time.
Switching time= (NtNr)/Np
Nt: Number of transmitted packets
Nr: number of received packets
Np: number of packets transmitted per second
Issue 03 (2007-09-30)
3-43
3 Network Commissioning
From
V40
To
D40
OBU
-C03
DCM-D
DCM-D
OAU
-C03
OAU
-C03
OAU
-C03
OAU
-C03
DCM-D
DCM-D
80 km (49.72 mi.)
22 dB
OBU
-C03
O
A
D
M
OBU
-C03
DCM-D
DCM-D
OAU
-C03
OAU
-C03
OAU
-C03
DCM-D
78 km (48.68 mi.)
21.45 dB
OAU
-C03
To
D40
OBU
-C03 From
V40
DCM-D
82 km (50.96 mi.)
22.55 dB
76 km (47.23 mi.)
20.9 dB
For indices of the boards with different specifications in Figure 3-30, refer to the OptiX BWS 1600G
Backbone DWDM Optical Transmission System Product Description.
Perform the following steps to verify the IPA function and restart the equipment in a manual
restart way.
Step 1 Break the fiber connection from A to B.
Step 2 Check the IPA status and verify if the IPA starts on the T2000.
3-44
Issue 03 (2007-09-30)
3 Network Commissioning
For details on how to check the IPA status, refer to the OptiX BWS 1600G Backbone DWDM Optical
Transmission System Configuration Guide.
Step 3 Use an optical power meter to test the optical power of the OUT interfaces on the OAU and
OBU at station A, and verify that the lasers on the OAU and OBU are shut down.
Step 4 Recover the fiber connection between A and B.
Step 5 Log in to the T2000. Double-click the optical NE icon in the Main Topology, and the status
figure of the optical NE is displayed.
Step 6 Right-click the subrack NE and select NE Explorer. The NE Explorer dialog box is
displayed.
Step 7 Select the subrack NE from the Navigation Tree and choose Configuration > IPA
Management from the Function Tree.
Step 8 Click Manual Reboot. A dialog box is displayed, indicating a successful operation.
Step 9 Click Close.
Step 10 Use an optical power meter to test the output optical power of the OUT interfaces on the OAU
and OBU at station A, and verify that the lasers are enabled.
----End
Issue 03 (2007-09-30)
3-45
3 Network Commissioning
Tools/Instruments
T2000
Prerequisites
Required/As needed
As needed
Set-up diagram
None
3-46
Issue 03 (2007-09-30)
3 Network Commissioning
The conference call comprises network-wide conference call and subnet conference call.
The network-wide conference call covers all the stations in the network and the number can be set on the
T2000, for example, 999.
The subnet conference call involves only the optical ports with the same subnet number that can be set
on the T2000.
The subnet conference number is formed by replacing the one or two significant digits of the conference
number by the subnet number.
For example, if the subnet number is 1 and the network-wide conference number is 999, the subnet
conference call number is 199.
Tools/Instruments
Fiber jumper
Optical attenuator
Flange
None
Prerequisites
Required/As needed
Required
Set-up diagram
The bit error test must cover all the service channels in the network. There must be no bit
error in consecutive 24 hours. To ensure that the 24-hour network-wide bit error test is
completed successfully, perform a 10-minute bit error test to each channel in advance.
This section takes Project G as an example to illustrate the test of network-wide bit errors.
Since the inter-board wavelength protection is provided by Project G, make sure that you shut down the
protection mode on the T2000 before commissioning.
Before the test, make sure that the input and the output optical power of each board is in the
optimal range. Make sure that there is no abnormal alarm and performance event.
Issue 03 (2007-09-30)
3-47
3 Network Commissioning
Rx
SDH/SONET
analyzer
Tx
LWC1
RX
LWC1
Tx
Rx
Station A
Station E
3-48
Issue 03 (2007-09-30)
3 Network Commissioning
Rx
SDH/SONET
analyzer
Station A
Station E
LWF
LWF
LWF
LWF
LWF
LWF
LWF
IN
LWF
Tx
L
W
F
L
W
F
L
W
F
L
W
F
Station C
Pay attention to the direction of the signal flow on each ONE during the commissioning.
There are four types of LC connector-shape fixed optical attenuators: 15 dB, 10 dB, 5 dB and 2 dB.
According to the requirement of the optical power, use the fixed optical attenuators of a proper type
when you perform the network commissioning.
Issue 03 (2007-09-30)
3-49
3 Network Commissioning
Tools/Instruments
T2000
Prerequisites
Required/As needed
Required
Set-up diagram
None
Use the T2000 to set performance and alarm monitoring. For details, refer to OptiX iManager
T2000 Operator Guide for WDM or the T2000 online help.
Observe the performance event as long as possible, at least one hour. A 24-hour performance
test is recommended. There should be no abnormal performance event during the test.
Query the NE alarms and clear the fault accordingly.
3-50
Issue 03 (2007-09-30)
3 Network Commissioning
Tools/Instruments
T2000
Prerequisites
Required/As needed
Required
Set-up diagram
None
After the configuration data is delivered, it is required to backup the NE database. The NE
database can ensure that the SCC board restores to normal operation automatically upon data
loss or power failure.
Perform the following steps to back up the NE database.
Step 1 Log in to the T2000.
Step 2 In the Main Topology, select Configuration > Configuration Data Management.
Step 3 Select the NE with database to be backed up in the left-hand pane. Click the
double-right-arrow button.
Step 4 Select the NE to be backed up from the list on the right-hand pane.
Step 5 Right-click the NE and select Backup to Database from the drop-down menu.
Step 6 Click OK in the prompt box.
----End
Issue 03 (2007-09-30)
3-51