Вы находитесь на странице: 1из 54

TECHNICAL MANUAL

TBX
CONDENSING
LOW NOx BOILER

INDEX

TOC

GENERAL DETAILS

These condensing heating boilers allow full exploitation of heat resulted from combustion, subjecting the
fumes to a considerable temperature reduction or dehumidifying boost.
The heat generator does not impose return temperature limits.
The performance will increase reducing the return temperature, therefore, the floor standing heat exchange
surface systems with low return temperatures will have an improved efficiency;
The efficiency will remain high even with traditional heating systems operating at high temperatures (e.g. t
80/60 C).
The boiler bodies whose axes are inclined in relation to the vertical axis, consist of:
- Entirely submerged passing flame combustion chamber;
- Corrugated smoke ducts whose particular shape increases the heat exchange surface, develops smoke
turbulence and allows condensate formation and drainage through the rear collection chamber;
- Water containment casing connected to the low and medium temperature return, delivery and the control
and safety accessory connections;
- The smoke chamber able to collect condensate through the combustion chamber nozzle from the
chimney and condensate drainage tube.
All surfaces that come into contact with the combustion products are made from STAINLESS steel and,
therefore, are also resistant to acid condensate attacks.
High efficiency due to complete exploitation of the fuel's thermal energy and to considerable
insulation consisting ofself extinguishing, fire resistant reticulated polyethylene foam, label these
boilers as "4 star high-efficiency" according to Efficiency Directive 92/42/EEC.
Every boiler body is equipped with an air/gas pre-mix burner.
Permanent lowering of combustion products in the full combustion chamber limit nitrogen oxide (NOx)
formation.

SUPPLIED EQUIPMENT

These heating units consist in one to three components to connect with supplied kits.
TBX CONSISTING OF A SINGLE THERMAL UNIT:
TBX 35 code 81024035 Effective output kW 35*
TBX 50 code 81024050 Effective output kW 50*
TBX 70 code 81024070 Effective output kW 70*
TBX CONSISTING OF TWO THERMAL UNITS
TBX 100 code 81024100 Effective output kW 50+50*
TBX 120 code 81024120 Effective output kW 60+60*
TBX 140 code 81024140 Effective output kW 70+70*
TBX CONSISTING OF THREE THERMAL UNITS
TBX 150 code 81024150 Effective output kW 50+50+50*
TBX 170 code 81024170 Effective output kW 57+57+56*
TBX 190 code 81024190 Effective output kW 63+63+64*
TBX 210 code 81024210 Effective output kW 70+70+70*

* with 50C delivery and 30C return


In order to optimize the operation of the modular heat generator (two or three thermal units connected in
cascade) all the burners must have the fan speed adjustment potentiometers set at the same values (see

the POWER ADJUSTMENT chapter).

The overall power of the boiler is given by the sum of individual heating units, so in order to reach
intermediate values set the trimmers properly.

ASSEMBLED STANDARD COMPONENTS


INAIL Safeties
Inserted in the control panel:
Thermometer
Full scale adjustment thermometer 100 C
Safety thermometer 110C
Manometer
Mounted on the boiler:
Safety valve with drainage funnel
Maximum pressure regulator
Minimum pressure regulator
Fuel interruption valve
Control panel witheterm electric components
Boiler probe
Fume thermostat
STANDARD ACCESSORIES AND DOCUMENTS
INAIL valve with manometer connection (installed by the customer on the external manifold)
External probe
Cascade collector probe (for 2 or 3 boiler unit version)
Thermal unit's identification plate mounted on the front cover panel.
Manual of the termal unit *
* In order to configure the electronic board, who's parameters depend on the loaded firmware, see the manual
related to theETERM01 boiler management board. The firmware can be downloaded from the website
www.icicaldaie.com :
SelectDownload NEREIX ETERM Manuali IT_Manual ETERM01.pdf ,
Free registration is required to download the manual.
The standard accessories and documents are placed on top of the boiler and contained in the
cardboard package.
ASSEMBLY STANDARD COMPONENTS
TBX CONSISTING OF A SINGLE THERMAL UNIT:
Fumes exhaust kit
TBX CONSISTING OF TWO THERMAL UNITS
Fumes exhaust kit code TBX V140.50
Manifold kit code TBX V140.30
Accessories kit code 90082020
TBX CONSISTING OF THREE THERMAL UNITS
Fumes exhaust kit code TBX V210.50
Manifold kit code TBX V210.30
Accessories kit code 90082030

GENERAL WARNING

Each boiler is provided with a manufacturers plate that can be found in the envelope with the boiler
documents. The plate lists:
Serial number or identification code
Rated thermal output in kcal/h and in kW
Furnace thermal output in kcal/h and in kW
Types of fuels that can be used (natural gas or lpg)
Max operating pressure.
A manufacturers certificate is also provided which certifies the hydraulic test.
The installation must be carried out in accordance with in force regulations by professional qualified staff ,
meaning staff specially trained in the field of heating system components used in domestic environments for
hot water production, staff trained mainly by a Service Centre authorised by ICI CALDAIE.
Incorrect installation may cause damage to persons, animals or objects for which the manufacturer cannot be
held responsible.
At the first start up, all regulation and control devices positioned on the control panel should be checked for
efficiency. The guarantee shall be valid only upon compliance with the instruction given in this manual.
Our boilers have been built and tested in observance of EEC requirements and, as a consequence, CEmarked. EEC directives are as follows:

Directive on
Directive on
Directive on
Directive on

Gas 2009/142/CE
Output 92/42/EEC
Electromagnetic Compatibility 2004/108/CE
Low Voltage 2006/95/CE

This boiler has been designed to heat water to a temperature less than the
boiling temperature of water at atmospheric pressure (100C) and must be
connected to a heating plant and/or a domestic hot water plant within the
limits of its performance and output.

THE BOILER MAY ONLY BE INSTALLED IN A ROOM


WHICH COMPLIES WITH THE APPROPRIATE
VENTILATION REQUIREMENTS. READ THE
INSTALLATION AND USER INSTRUCTION BEFORE
INSTALLING AND LIGHTING THE BOILER.

Systems must be cleaned in accordance with British Standard Code of Practice BS


7593:1992, Code of practice for treatment of water in central heating systems

TECHNICAL SPECIFICATIONS

DIMENSIONS

TBX CONSISTING OF A SINGLE THERMAL UNIT:

TBX CONSISTING OF TWO THERMAL UNITS:

TBX CONSISTING OF THREE THERMAL UNITS:

1
2
3
4
5
6
7

POS.
- FUMES EXHAUST
- COND. DRAIN. PIPE
- GAS
- DELIVERY
- RETURN MEDIUM TEMP.
- RETURN LOW TEMP.
- CONDENSATE DRAINAGE

1 ELEM.
80
3/4"
1-1/4"
1"
1-1/4"
28

2 ELEM.
160
25
1-1/2"
DN65
DN50
DN65
40

3 ELEM.
160
25
1-1/2"
DN65
DN50
DN65
40

INAIL ACCESSORIES

POS.
NAME
1
INTERMEDIATE TBX V70.00 BODY
2
COND. DRAINAGE RUBBER TUBE L=1500 "STELT"
DISCHARGE VALVE M 1/2" - WITH HOSE
3
CONNECTION
5
PRESSURE SWITCH M 1/4 (0.2 - 6 BAR)
6
ADAPTER MF 1/2" X 1/4"
7
SAFETY PRESSURE SWITCH R.M. (1-5 BAR) F1/4"
8
T-JOINT 1/2"
9
SAFETY VALVE 3,5 BAR - F 1/2"
10
NIPPLE =4 L=33
11
FUNNEL DRAIN 3/4"
12
HOSE CONNECTION 3/4" X TUBE 20
13
NIPPLE 1/2"
14
CHECK VALVE X TERMOID. 1/2" - 1/4"
15
HOSE CLAMP 15-25-9
16
REDUCING NIPPLE 1/2" X 1/4" GALVANIZED IRON
17
RUBBER TUBE 20X28 (V.SCAR.WALL)

CODE
71028070
14000195

Q.TY'
1
1

18022810

L4553490
7050051
16031008
7040013
13091569
40000320
13052045
14000414
60000255
20000070
10050102
7025152
14000446

1
1
1
2
1
1
1
1
1
1
1
1
1

10

INSTALLATION WARNINGS

Before connecting the boiler, the following operations must be completed:


- Thoroughly clean all the system pipes in order to remove any foreign matter that could affect correct
operation of the boiler;
- Check that the flue has an adequate draught, that there is no narrowing of passages and that it is free from
debris; also check that other appliances do not release into the flue (unless designed to serve several utilities).
See the regulations in force.

THERMAL PLANT
BOILER ROOM
As a rule, regulations in force should be always observed. Premises in which boilers will be installed should be
sufficiently ventilated and guarantee access for ordinary and extraordinary maintenance operations.

EXTERNAL INSTALLATION
It is possible to utilise a special base (optional) for external installation to further weatherproof the thermal plant.

CHIMNEY
The pressurised boiler, is so-called, because it uses a burner provided with fan. The fan introduces into the
combustion chamber, the exact amount of air necessary in relation to the fuel and maintains an pressurisation in
the furnace equivalent to all the internal resistances of the flue gas path as far as the boiler exhaust. At this point
the fan pressure should have dropped to zero to prevent the flue connection pipe and the lower area of the flue
itself from being under pressure and combustion gas leaks occurring in the boiler room.
The connection pipe from the boiler to the flue must slope incline in the direction of the flue gas flow with
recommended gradient of no less than 10%. Its path must be as short and straight as possible with the bends and
fittings rationally designed in accordance with air duct criteria.
WARNING
The flue gas temperature of this boiler (between 35 and 120C) is very low compare to the traditional noncondensing boilers, therefore, there is a very high humidity density. For this reason the boiler chimney
must be water resistant, acid condense resistant and insulated to warrant sufficient draught.

HYDRAULIC CONNECTIONS
Ensure that the hydraulic pressure measured after the reduction valve on the supply pipe does not exceed the
operating pressure specified on the rating plate of the component (boiler, heater etc.).
As the water contained in the heating system increases in pressure during operation, ensure that its maximum
value does not exceed the maximum hydraulic pressure specified on the component rating plate (5 bar).
Ensure that the safety valve outlets of the boiler and hot water tank, if any, have been connected to drain in
order to prevent the valves from flooding the room if they open.
Ensure that the pipes of the water and heating system are not used as an earth connection for the electrical
system as this can seriously and very rapidly damage the pipes, boiler, heater and radiators.
Once the heating system has been filled, you are advised to close the supply cock and keep it closed so that any
leaks from the system will be identified by a drop in hydraulic pressure indicated on the system pressure gauge.
In case the single unit boiler's condensate neutralisation (optional) is not being
used, check if a siphon is connected to the condensate drainage tube, inside the
boiler, in order to facilitate fume output.
NOTE: IF ONLY ONE RETURN IS REQUIRED, ALWAYS USE THE LOW TEMPERATURE ONE

ELECTRICAL CONNECTIONS
Electrical systems of thermal plants designed only for heating purposes must comply with numerous legal
regulations which apply to in general as well as specifically to each application or fuel type.
Please refer to this manual's wiring diagram when connecting the control panel.
PRE-MIX BURNER
The boiler is supplied with a pre-mix burner already mounted on the boiler, suitably calibrated for a 20mbar
gas pressure.
Check combustion parameters before assembly (CO e CO 2).
Please refer to the BURNER chapter for burner information.
BOILER BODY INSULATION
The boiler's body and upper door side's insulation consists of a layer of insulating, reticulated, fire resistant, self
extinguishing, polyethylene foam.

11

SET-UP

CASING DISMANTLING

12

CONTROL PANEL TURNOVER AND FASTENING

13

TBX accessories kit for three thermal units code 90082030 (image)
TBX accessories kit for two thermal units code 90082020

A
B
C

Expansion tank connection


Screws and nuts for lever block
Opened valve

14

POS.

NAME

T-JOINT 3/4"

GALVANIZED ADAPTER 3/4"X3/8" MF

ADAPTER MF 1" X 3/4"

STRAIGHT CONICAL BRASS NOZZLE 1"1/2" MF

STRAIGHT NOZZLE MF 1''

CAST IRON F/331 STRAIGHT NOZZLE 1"1/4 FF

GALVANIZED IRON PLUG 3/4" M

GALVANIZED IRON PLUG 1"1/2" F

CODE

Q.TY'
90082020

90082030

07040004(3-4)

07050013 (MF 3-4 X 3-8)

07050014 (MF 1 X 3-4)

7060104

07060251 (MF 1)

07060260 (FF 1-1.4)

7070204

07070355 (1-1.2 F)

HOSE GAS MF L=130-220 mm YELLOW

7080201

10

HOSE AVC32 1''1/4 L=245 ATT. MF

7080217

11

HOSE AVC32 1''1/4 L=480 ATT. MM

7080218

12

HOSE AVC25 1'' L=550 ATT. MM

7080219

13

GASKET 3/4 - 38 X 29 X SP.2

9060046

14

CAP NUT 5M

10031040

15

ADJUSTABLE SUPPORT 30 M10

10050020

16

TUBE FASTENING COLLAR X TUBE 1"1/2"

10050303

17

THREADED SOCKET M10X19 FTT/C HOLE12 ACC.

10050518

18

BEAD 8X20 C/GALVAN. TIP UNI5923

10050716

19

POLISHED ZN WASHER 8X14 C60

10060010

20

FLAT GALVANIZED WASHER 5X10 UNI6592

10060042

21

CROSS GALVANIZED SCREWS M5X16 TC DIN7985

10071516

22

ELECTRIC ACTUATOR 220V - FOR BALL VALVE

13020090

23

3 WAY PORTAMAN ACC VALVE MF 3/8 MOD.690300

13032040

24

GAS BALL VALVE M/F 3/4"

13080036

25

BALL VALVE 1"1/4 MF

13080057

26

MOTORISED BALL VALVE MM 1"1/4"

13080062

27

3 WAY "T-JOINT" VALVE 1"

13080071

28

HOSE CONNECTION 3/4" X TUBE 20

14000414

29

PROBE SHEATH H1/2 X 3 TUBES L=90 D=8

14002030

30

WASHER 1 44X34X3 ECOL.005 RACC.11/2

18050050

31

WASHER 11/4 56X42X3 ECOL.005

18050120

32

WASHER 23,5X15,5XSP.2 - CON.3/4"

50000820

33

BLACK PAINTED MANIFOLD ENSEMBLE TBX V210

TBX V210.30

34

YELLOW PAINTED GAS MANIFOLD TBX V210 RAL 1004

TBX V210.33

35

MANIFOLD SHELL i75 L= 1000

TBX V210.35

36

MANIFOLD SHELL i 60 L= 1000

TBX V210.37

15

PHASE 1
Position the gas and hydraulic manifolds.
Mount the manifolds on the wall and fasten using supplied screws and slots (1)

PHASE 2
Insulate the manifolds.

PHASE 3
Mount drainage ensemble onto the delivery manifold using the 3/4'' T-joint:
- Valve for the INAIL sample manometer
- 3/4'' connection for the expansion tank

16

PHASE 4
Connect the manifolds to the boiler's connections using the supplied valves.

PHASE 5

A
B
C
D

GAS TUBE: 11/2 mount the ingoing brass nozzle and the F 11/2 plug on its extremity
Select RH or LH for the condensate drainage tube output and remove the base tray's precut slot plugs.
Insert the boiler's condensate drainage tube
Insert the safety valve drainage hose

17

PHASE 6
Connect the fume exhaust to each individual thermal unit.

Insert the fume thermostat's bulb into the fume exhaust tube's nozzle

Mount the supplied fume collector for two or three TBX units.

18

ELECTRICAL WIRING
TERMINALS

TERMINAL
NAME

FUNCTION

HIGH VOLTAGE

X1

X2

X3

X4

L
T
N
1
2
3
T
4
5
6
7
8
9
10
11
12
13
14
15
16

BR
(BROWN)
BU
(BLUE)
X VM
GN
(GREEN)
WH
(WHITE)
PN
(RED)
LOW VOLTAGE / SIGNAL
17
18
19
20
21
X5
22
23
24
25
26
27
28
29
30
X6
31
32
33

CONTROL PANEL MAIN POWER SUPPLY


EXTERNAL SAFETIES
BURNER POWER SUPPLY
BURNER CONSENT
STAGE 1 SIGNAL
STAGE 2 SIGNAL (UNUSED)
BLOCK SIGNAL
3 POINT COMMAND (CONFIGURABLE FOR
MIXING VALVE)

L
T
N
IN
OUT
L
T
N
T1
T2
B4
B5
S3
T6
T7
T8

UNUSED
VOLTAGE FREE CONTACT OUT R2

IN
OUT
L

MOTORIZED VALVE POWER SUPPLY


N
MOTORIZED VALVE COMMAND

L1
FC

MOTORISED VALVE LIMIT SWITCH


FC

PT1 Boiler Probe (PT1000)


PT2
PT3
NTC
IN 0-10 V
OUT 0-10 V
(BURNER MODULATION)
RS485 (RS1)
RS485 (RS2)

19

1
2
1
2
1
2
1
2
+
+
A
B
A
B
C

20

21

22

23

24

25

CONTROL PANEL

COMANDO BRUCIATORE
MANUALE
SPENTO
AUTOMATICO

DISPLAY

TERMOSTATO
REGOLAZIONE

INTERRUTTOR
E GENERALE
COMANDO
USCITE
R1 R2
MANUALE
SPENTO
AUTOMATICO

TERMOMETRO

USB

SAFETY THERMOSTAT WITH MANUAL RESET

TERMOSTATO
SICUREZZA
ACQUA
TERMOSTATO
SICUREZZA
FUMI

26

TASTIERA

MANOMETRO

STANDARD EQUIPMENT AND CODES OF THE MAIN CONTROL PANEL SPARE PARTS
- Manual of the electronic board for ETERM01 boiler management ....................................................
Spare part
cod. 93120332
- Electronic board .. Spare part cod. 17120273
- LCD Display . Spare part cod.
17120274
- Main switch
Spare part cod.
-Burner mode switch (Manual / Off / Automatic)..
Spare part cod.
- Operation switch of the 2 programmable outputs (Manual / Off / Automatic) ..
Spare part cod.
- PT1000 boiler probe ..
Spare part cod. 16111247
- CE / ISPESL full scale regulating thermostat 100C
Spare part cod. 16090029
- CE / ISPESL 110 C safety thermostat ...
Spare part cod. 16090032
- Fumes safety thermostat 110 C
Spare part code
- CE / ISPESL thermostat . Spare part cod. 16080209
- Pressure gauge .
Spare part cod.
- External probe . Spare part cod.
17120012

(Optional) Accessories for the control panel


System management panel for input / output implementation .

Cod. QETERM02

Temperature probe PT1000 .


PT1000 immersion probe for water heaters, mixed zone, solar panels, etc..

Cod. 16111247

NTC Temperature probe .


Immersion probe for water heaters, mixed zone, etc..

Cod. 18022218

Fumes temperature probe PT1000. Cod. CB1093


Duct temperature probe PT1000.
Air duct probe

Cod. CB1091

Duct temperature probe NTC . CB1092


Air duct probe
Modem KIT with antenna and 1,5 meter cable .
Installed inside the boiler's panel

Cod. CB876

Modem antenna with 10 meter cable ....

Cod. CB913

PC modem ....
For remote computer - system modem communication

Cod. CB916

27

CONTROL PANEL QUICK CONFIGURATION

The firmware loaded on the electronic board can be upgraded and the operations can be implemented.
For additional information please consult the manual regarding the ETERM01 boiler management board
downloadable from www.icicaldaie.com :
related to the ETERM01 boiler management board downloadable from www.icicaldaie.com :
SelectDownload NEREIX ETERM Manuali IT_Manual ETERM01.pdf ,
Free registration is required to download the manual.

Firmware update and configuration from the PC are implemented using the etermPCmanager
software available at www.eterm.it and www.icicaldaie.com

DISPLAY
STATO USCITA BRUCIATORE

TEMPERATURA DI CALDAIA

MODULAZIONE IN SALITA

GIORNO DELLA SETTIMANA


ORE : MINUTI : SECONDI

CONSENSO SICUREZZE ESTERNE

SET POINT CALDAIA

MODULAZIONE IN DICESA
OFF / MANUALE /
AUTOMATICO / FORZATURA

VISUALIZZAZIONE FUNZIONE DEI TASTI INFERIORI


WIRING CHECK PROCEDURE
For the R1 and R2 outputs:
Set the mechanical switches to:
- Manual and check if the devices connected to R1 and R2 are powered on
( R1 may be connected to the cascade valve)
- 0 and check if the devices connected to R1 and R2 are powered-off
For burner control, when setting the switch to the manual mode:
- Check if the regulating thermostat causes burner start-up.
Probes
The probes that must be connected depend on the configuration that will be implemented. The boiler probe is
always necessary and it can be viewed in the upper right side (boiler temperature)
Burner notifications:
Make sure that when the burner's auxiliary power supply are enabled, this symbol is displayed

Make sure that in case of burner block, this symbol is displayed

Make sure that when the burner is lit (flame presence) this symbol is displayed
In case of failure (for example a disconnected or short-circuited probe), the "alarm" icon will flash in the "menu"
section
Select the "Instantaneous alarms" menu to check current alarm type.

28

ELECTRONIC BOARD CONFIGURATION


The meaning of the keys is variable. Please refer to the corresponding icon displayed on the screen.
Standard parameters are loaded in the electronic board's firmware and can be used as a starting point for the
configuration of your system. The TBX's following preloaded configurations may be used:
- TBX:
automatically sets the appropriate parameters of a single unit TBX boiler
- TBX Master:
automatically sets the appropriate parameters of a cascade master TBX unit
- TBX Slave 1 or 2: automatically sets the appropriate parameters of a slave TBX boiler
Always conduct a quick setup before starting a configuration (even from PC).
This operation allows the cancellation of previous configurations conducted by mistake or by third parties.
After a quick setup all parameters are still editable.
Enter the

menu and scroll using the arrow keys to the Quick setupmenu

Access the menus by pressing


Press and hold the

and select the desired predefined setup.

key until the electronic board will reset.

MAINE PARAMETERS THAT MUST BE CHECKED


Some parameters can be locked to prevent configuration tampering.
For this purpose, there are two levels (user and technical). The controller's default setting is
"technical" and thus allows a complete freedom of configuration.
Please refer to the manual of eterm boiler's electronic board (Code 93120301).
"General configuration" menu
Contains parameters related to:
- Language
- Address configuration (if necessary)
- The external probe (yes / no / system: if the board is slave to a master with an external probe)
- Boiler mode (single / master / slave)
- Cascade parameters (if the device is cascade master)
- Display contrast
"Burner parameters" menu
- Burner type: the TBX's quick setup configures the controller to control the burner with 0-10 volt impulses
- Time between maximum and minimum power: TBX's quick setup implements the correct value
- Fumes probe: input enabled (off = no fumes probe) and possible burner shut-down threshold.
"Operation mode" menu
This menu configures the mode of setpoint determination in automatic mode.
The menu expands displaying required parameters when various functions are enabled:
- Fixed Point 1 or 2: requires the use of inputs with digital function (open / closed)
After this feature is enabled, the system will request the temperature to be associated with the closing of the
relay and possible schedule.
An input may not be used as digital and analogue at the same time (temperature probe or 010 Volt input). The configuration via PC eliminates the posibility of configuration
inconsistencies
- Programmed operation: fixed temperatures (comfort / reduced / off) depending on a schedule. You must
choose the associated program and the temperatures (in off mode the boiler will operate according to an
antifreeze temperature).
- Boiler climatic curve: Select the climatic curve (OFF = feature disabled) and then select possible digital
conditions and / or schedule to associate with the request.
- 0/-10 volt operation Select the function, the temperature corresponding to 10 volts and possible digital
conditions and / or schedule to associate with the request (0 volts always corresponds to 0C).
- Time intervals and temperature: Allows configuration of
- Boiler minimum and maximum temperatures
- Antifreeze temperature
- Manual function and climatic curve setpoint thresholds
- Pump circulation
- Various probe offset (correction of the displayed reading)

29

"Domestic water" menu


Configure if a water heater is present
"Output configuration" menu
Associate the R1 and R2 outputs with:
- Boiler pump (or valve)
- Cascade pump
- Condensate pump
- Water heater pump
- Solar circuit pump
(by implementing this function the PT2 is associated with the solar panel and PT3 to the solar accumulation tank
probe).
- An alarm (the relay closes the board triggers an alarm: probe, burner, bus communication)
(by configuring the board from a PC, additional alarm conditions may be configured such as relay closing /
opening, temperature limits, etc.)
- System pump
- Direct temperature
- Mixed temperature
- Fixed point 1/2
- 1-2-3 schedule
"Domestic water" menu
Configure if a mix circuit is present
Forcing
Allows digital and analogue output forcing in order to verify board and/or the connected user functionality.
Boiler status
Allows you to view all operational and relay data.
Date / time /period
Caution:
- The parameters can not be modified if the device is set as slave.
- Climatic operation is enabled only during winter time.
Time programs
3 weekly schedules are available that can be associated wit various functions:
- Operation mode
- Water heater
- Mixing valve
Instant alarms
Displays current alarms (currently active)
Alarm history
Displays the last 50 alarms (can be reset from PC or keyboard see the eterm boiler electronic board's manual,
Code 93120301).

30

10 CASCADE BOILER CONFIGURATION


In a cascade the master's setpoint (manual or automatic) represents the delivery manifold's setpoint.
Check if the manifold's probe is connected to the master's PT2 input and if the bus connections have been carried
out.
Use the specific quick setup :
- TBX Master
- TBX Slave 1 o 2
Once the quick setup has been completed for all slave devices, from the master unit access the Address
configuration menu and press the key
If the configurations are correct and if the bus is correctly connected , the master unit's screen will display a list of
cascaded device registration numbers.
The PC configuration is conducted by typing the board's registration number in the address list.
However, it is recommended that you run the quick setup even before a PC configuration.
The board's serial number is printed on the transformer and is displayed on screen during the control panel's start
up.
After the address configuration, the master displays
e the slave
.
If the slave device's addresses are not configured or if the bus connection is interrupted, the screen will display

.
The devices' cascade symbols are displayed intermittently.
When displayed and cascade setpoints are switched on (determined by the master unit).
When displayed and boiler setpoints are switched off.
Each single boiler is then configured as described in the previous paragraph paying particular attention to burner
parameters and output configuration.
"Operation types" will settable only by the master unit (which determines the manifold's set point).
Check these fundamental parameters form the master's configuration ("General Setup" menu):
- Cascade time reversal:
OFF = no priority reversal
0
= priority reversal at any interruption / request reset
xx hours= priority inversion after xx houres and after any interruption / request reset
- Manifold's initial dosage: initial setpoint temperature difference between boilers and manifold

31

11 MODEM (optional)
ALL THE ASSEMBLY AND WIRING OPERATIONS MUST BE PERFORMED WITHOUT VOLTAGE

GENERAL CHARACTERISTICS OF THE MODEM


The modem is directly powered by the board by means of the flat.
Cut off power supply when connecting the modem and when inserting the SIM card.
The SIM card must be enabled for data traffic (no voice!!).
The SIM must be pushed to limit switch: a click will anounce a successful insertion.
Before inserting the SIM, disable the PIN by using a cellphone.
Main characteristics:
Module MODEM GSM - GPRS Quad-Band
LED that signals GSM network sign-in status
Buzzer for acoustic signals (disabled)
TTL interface
Compatible with the NEREIX motherboard
RADIO CHARACTERISTICS
Quad-band EGSM 850/900/1800/1900 MHz
Emission power:
class 4 (2W) @ 850/900 MHz
class 1 (1W) @ 1800/1900 MHz
Sensitivity:
107 dBm (typ.) @ 850/900 MHz
106 dBm (typ.) @ 1800/1900 MHz
GPRS CHARACTERISTICS
GPRS class 10
Mobile station class B
Encoding patterns: from 1 to 4
PBCCH support
The green status LED stands for:
FAST FLASHING = Searching for a network
SLOW FLASHING = Registered in a network
CONTINUOUSLY ON
= Data connection in progress

In order to mount the antenna with optional extension, remove the serial antenna by pulling the connector directly
from the module's connector and insert the new one.
Insert the antenna in the appropriate socket (in case the extended antenna is used, use a cable socket for the
extended antenna's output from the control panel).

32

MODEM ASSEMBLY
Remove the two small middle nuts that fasten the board in the lower part (adjacent to the keys).
Assemble the 2 hexagonal turrets (A).
Position the modem board after having removed the antenna.
Fasten the board with the nuts (B) removed previously.
Connect the flat onto the board and modem.

CAVETTO ANTENNA

FLAT

The antenna supplied can be fastened inside the panel (with its double-sided tape) or brought to the outside,
compatibly with the length of the wire included in the supply.
If necessary, in order to pick up the signal outside of the room, use the optional antenna with a 10 meter extension
(code CB913)

33

12 eterm PANEL UTILISATION


If the controller is not configured or is faulty the burner can be controlled by the mechanical thermostat by setting
the burner's mechanical switch to MAN
Similarly the devices connected to R1 and R2 can be activated.
Once the electronic control unit has been activated, all the electronic switches must be set to AUTO.
The electronic board has three operating modes that can be selected with by pressing and holding the left side
key(from the main page):
Standby = only the anti-freeze function is enabled.
Manual = the boiler's setpoint (or manifold if the boiler is cascade master) and can be set manually using
the "+" and "-" buttons.
Automatic = the boiler's or manifold's setpoint (if the electronic board is cascade master) is determined
automatically, depending on the implemented configurations (operation type - domestic water - mixing valve).
If the cascade slave is in:
Standby = only the anti-freeze function is enabled.
Manual = the boiler's setpoint can be set manually by using the "+" and "-" keys and the boiler is relieved
from cascade master.
Automatic = the boiler's setpoint depends exclusively on the master's commands
Cascade slaves will normally be set to Automatic mode.
A special menu has been provisioned for the user and it only contains the parameters useful for the current
configuration.
In automatic mode, from the main screen, an operator can easily access the schedules by pressing
During the operation, the following icons may appear:

if a hot domestic water production request has been activated.

if a mix circuit request has been activated


If multiple requests are activated the symbols alternate.

34

13 BURNER
Warranty and liability
The manufacturer gives warranties regarding the burner in respect to in force regulations.
Warranty and liability rights are declared void, in the event of damage to persons and/or things, where the damage
itself refer to one or more of the following causes:
- improper burner commissioning, use and maintenance;
- improper, erroneous, and unreasonable burner use;
- unauthorised personnel intervention;
- unauthorized equipment modifications;
- use of the burner with faulty safety devices, applied in the an improper way and/or non-functioning;
- installation of additional components that are not tested together with the burner;
- burner supply unsuitable fuels;
- fuel system feeding defects;
- use of the burner after the occurrence of an error and/or a fault;
- repairs and/or revisions improperly executed;
- combustion chamber modification through the introduction of inlays that prevent normal flame development
constructively set;
- insufficient and inappropriate supervision and care of burner components subjected to wear.
- non-genuine part use (spare parts, kits, accessories and optional components);
- causes of force majeure
The manufacturer also declines any responsibility for failure to comply with the instructions stated in this manual.
Personnel training
The user is the person, institution, organization or company, which has bought the machine and that means to use
it for its intended purpose.
The machine and personnel training is the customer's responsibility.
The customer:
- is required to entrusts the machine only to qualified and trained personnel;
- is required to take all necessary measures to prevent access to unauthorized personnel to the machine.
- is required to adequately inform their personnel to apply and comply with safety requirements. To this end, the
customer must strive to ensure that all employees are knowledgeable regarding the use and security instructions;
- must inform the manufacturer in case accident prevention system defects or malfunctions are discovered, as
well as any allegedly dangerous situation.
- The staff should always use the means of individual protection required by the legislation and follow the
instructions presented in this manual.
- The staff must comply with all instructions regarding danger and caution signs displayed on the machine.
- The staff must follow all the signs of danger and caution reported on the machine.
- The staff has the obligation to report to their superior every problem or dangerous situation that might occur.
- Installing other brand components or implement possible modifications can change the characteristics of the
machine and therefore compromise operational security. The Manufacturer declines any and all responsibility for
any damage that may arise due to the use of parts that are not original.

35

BURNER DESCRIPTION

POS.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

NAME
REDUCED NIPPLE 3/4"X1/2"
LOCK NUT 3/4"
GAS BURNER AIR DUCT - TBX V70
BURNER FAN G 70 MXH PREMIX-UNIT
FUEL INTERRUPTION VALVE
BURNER TUBE G 70 MXH PREMIX-UNIT
NIPPLE =4 L=33
YELLOW HOSE MF 3/4X 3/4 GAS L=7500
SCREWS 8X25 TE CL8.8-ZN GALVANIZED ALL THREADED
FLAT GALVANIZED WASHER 8X15 UNI6592
FLAT GALVANIZED WASHER 5X10 UNI6592
SCREWS TBEI CL-10.9-ZN GALVANIZED
NUT 5M HIGH CL8-ZN GALVANIZED
BURNER GASKET
GASKET 23,5X15,5XSP.2 CONNECTION 3/4"
CERAMIC MATTRESS L= 610 INSULFRAX-S BLANKET
DOOR
GALVANIZED FLAME VISOR (AQ-3001)
GASKET 30X22X1,5 OMNIA BLU DOOR VISOR
GAS PRESSURE INLET EN 150
FLAME CONTROL VISOR GLASS D=30X5 MM

36

CODE
7025309
18030310
TBX V70.37
17010190P1
13052048
17010190P2
40000320
07080203 (MF 3-4)
10070835
10060009
10060042
10070519
10031051
R3020294
18050020
92070600
TBX V70.05
7080801
9060040
18052114
16010201

Q.TY'
1
1
1
1
1
1
1
1
4
4
4
4
4
2
1
1
1
1
2
1
1

FUEL SUPPLY
The burners are matched with pneumatic proportional monolithic gas valves, that allow delivered gas amount
modulation, thus modulating developed power.
A pressure signal detected in the air circuit is led to the pneumatic gas valve, which delivers a quantity of gas
proportional to the flow of air processed by the fan.
In order to optimize the dimensions, the gas ramp is assembled directly on the body of the burner.
GAS RAMP GROUP
The valve-manifold connection allows the compensation of suction accidental blocking by reducing the amount of
delivered gas.

AIR/GAS MIXER
The mixing of gas and combustion air is performed inside the ventilation circuit (mixer), starting with the suction
inlet entrance.
The fuel is inserted through the gas ramp into the air intake and with the help of a mixer starts an optimum mixing.
GAS VALVE

37

IONISATION CURRENT
The minimum equipment operating current is 5A.
The burner produces a significantly higher current, so that normally it does not require any control.
If, however, we want to measure the ionization current, the connector (CN1) inserted into the red wire must be
opened and then a microammeter must be inserted.

Optimal calibration values

Safety Notes for the first commissioning


The first commissioning of the burner should be carried out by authorised personnel and
authorized by ICI CALDAIE SpA, as shown in this manual and in accordance with in force rules
and regulations.
Verify regulating, control and safety device correct operation .
ADJUSTMENTS PRIOR TO IGNITION
The adjustments that need to be executed are:
- Open the manual valves located upstream of the gas ramp.
- Vent the air from the gas pipe by suing the P1 plug screw.
- Check the equipment's potentiometer settings.
BURNER START
Close the thermostat and electrically power the burner.
The burner starts in pre-ventilation mode at maximum value. After 30 seconds, it reaches START speed and the
ignition occurs.
If, on the other hand, the fan starts but at the end of the safety time the flame does not appear, the equipment
allows the repetition of the start-up program for maximum 2 attempts.
At the third attempt, if not the lighting does not occur, the burner will be blocked.
Unlock and wait for a new start attempt.
If the lighting still does not occur, it may be possible that the gas does not arrive at the combustion head within a
safety time of 5s.
Slightly rotate clockwise (no more than 360 ) the V1 screw placed on the gas valve mixer.
Once lighting has occurred, move on to the full adjustment of the burner.

38

POWER ADJUSTMENT
The modulation is based on variable speed technology.
The combustion air flow is adjusted through the variation in the number of engine revolutions,
The proportional gas ramp delivers the correct amount of fuel depending on the pressure sensed in the ventilation
circuit,
So, the engine speed rotation variation adjusts the delivered power.
The engine speed can be adjusted by acting on the burner's three potentiometers
Adjustments may be necessary based on the installation.
The thermal capacity of the burner should not exceed the capacity of the boiler.
MIN Determines the speed of the fan when the modulation is minimal
MAX Determines the speed of the fan when the modulation is at its peak
START Determines the speed of the fan during the starting phase
"MIN" adjustment is replaced instantly at the end of the pre-ventilation outlined by the opening of the valve and
the presence of the vent.
Maximum modulation enabling with "MAX" occurs approximately 10 sec from the valve opening.
Boiler
rated
effective
output*
kW
35
40
50
60
70

MIN timer
calibratio
n

MAX
timer
calibratio
n

START
timer
calibration

2
2
2
2
2

3.5
4
5
6
7

5
4.5
4
3.5
3
* with 50C delivery temperature and 30C return
temperature

In order to optimize the operation of the modular heat generator (two or three thermal units connected in cascade)
all the burners must have the fan speed adjustment potentiometers set at the same values.
The overall power of the boiler is given by the sum of individual heating units, so in order to reach intermediate
values set the trimmers properly.
GAS VALVE ADJUSTMENT
The adjustment of the gas flow rate is obtained by using the two screws V1 and V2.
In order to vary the maximum flow rate of gas operate screw V1.
- In order to increase the flow rate: turn the screw counter-clockwise (not more than 360 with respect to the
default calibration).
- In order to decrease the flow rate: turn the screw clockwise (not more than 360 with respect to the default
calibration).
In order to vary the minimum gas flow rate operate the gas valve's V2 screw.
Remove protection screw and operate the inner screw using Torx key.
- In order to increase the flow rate: turn the screw clockwise (not more than 360 with respect to the default
calibration).
- In order to decrease the flow rate: turn the screw counter-clockwise (not more than 360 with respect to the
default calibration).

39

40

BURNER ADJUSTMENT
In order to obtain an optimum burner adjustment, the analysis of gas exhausted from the boiler's combustion must
be conducted. When installing the burner onto the boiler, adjustments and tests must be carried out in compliance
with the boiler instruction manual, including the control of CO and CO2 concentration in flue gases and their
temperature.
Sequentially check:
- Maximum power
- Minimum power
- Ignition power
Themaximum power should match the one required by the used boiler. In order to increase or decrease its value
operate the equipment's MAX potentiometer.
Measure the meter's gas flow to find exactly the amount of power burned.
Using an fume analyser, measure the value of CO2 or O2 in order to optimize the calibration of the burner.
The correct values are: CO2 8.5 9% or O2 55.5%.
To correct these values operate the gas valve (no more than 360 from default calibration) as follows:
- To increase the gas flow rate and CO2: rotate screw V1 counter-clockwise.
- To decrease the gas flow rate and CO2: rotate screw V1 clockwise.
Theminimum power should match the one required by the used boiler. In order to increase or decrease its value
operate the equipment's MIN potentiometer.
Measure the meter's gas flow to find exactly the amount of power burned.
Using an fume analyser, measure the value of CO2 or O2 in order to optimize the calibration of the burner.
The correct values are: CO2 8 8.2% or O2 5.5 6%.
To correct these values operate the gas valve (no more than 360 from default calibration) as follows:
To increase the gas flow rate and CO2: rotate screw V2 clockwise.
To decrease the gas flow rate and CO2: rotate screw V2 counter-clockwise.
The ignition power can be varied by operating the equipment's START trimmer.
Combustion head
The combustion head consists of a high thermal resistant cylinder. Its surface is interspersed with several holes
and shrouded with a metallic mesh.
The air-gas mixture is pushed inside the cylinder and escapes through the outer holes toward the exterior of the
head.
The combustion starts when the air-gas mixture is ignited by the electrode's spark.
The metallic mesh is the fundamental element of the combustion head as it greatly improves the performance of
the burner.
The flame developed on the head's surface is perfectly attached and adheres to the mesh during maximum
operation.
This allows high modulation ratios up to 6:1, thus avoiding the danger of backfiring to minimum modulation.
The flame is characterized by an extremely compact shape that avoids any risk of contact between the flame and
boiler components and consequently the risk of poor combustion phenomenon.
The structure of the flame allows the development of compact combustion chambers, designed to take advantage
of this feature.
Emissions
The burners' emission values are much lower than the limits imposed by the most stringent regulations. Flame
distribution and its expansion on a large surface, allows thermal NOx containment, mainly responsible for
emissions.

41

NORMAL OPERATION

42

BLOCK DUE TO MISFIRE

BLOCK DUE TO FLAME PRESENCE OR FLAME SIMULATION DURING PRE-VENTILATION

BLOCK TYPES AND INTERVENTION TIMES IN CASE OF BURNER FAILURE

RECYCLING FUNCTION IN CASE OF FLAME DISAPPEARANCE DURING OPERATION


The equipment allows the recycling, namely the complete repeat of the ignition program
If the flame is not present after the safety time of the last restart has passed, the burner will block.
RE-IGNITION FUNCTION DUE TO MISFIRE
The equipment allows start-up repeat for maximum 3 attempts, if at the end of the safety time there is no flame.
A further lack of flame after the fourth ignition attempt determines the block of the burner at the end of the safety
time.

43

CHECK OF THE NUMBER OF ENGINE REVOLUTIONS


Verification of engine operation if it exceeds the minimum number of rotations per minute (900 rpm).
If the engine does not exceed the minimum number of revolutions, check the block after 20 seconds.
EQUIPMENT UNLOCKING (INTEGRATED PUSH-BUTTON)
To unlock of equipment proceed as following:
Press the release button for 1 or 2 seconds.
EQUIPMENT UNLOCKING (FROM REMOTE CONNECTION)
Use input RS from the X1 terminal strip to remotely unlock the equipment.
MAINTENANCE SAFETY NOTES
Periodic maintenance is essential for the proper operation, safety, efficiency and the lifespan of the burner.
This allows a power consumption and pollutant emissions decrease and also allows to maintain a reliable product
over time.
Before performing any maintenance, cleaning, or control operation:
MAINTENANCE PROGRAM
DANGER
Maintenance and burner calibration interventions should be carried out by trained and authorized personnel by ICI
CALDAIE SpA, as shown in this manual and in accordance with in force rules and regulations.
DANGER
remove the burner's power supply using the system's main switch;
DANGER
close the fuel interruption valve
Maintenance frequency
The combustion system should be checked at least once a year by an ICI BOILERS SpA representative or other
specialist.
Flexible tubes
Make sure that the fuel lines, air intake and combustion products evacuation do not have blockages or bottlenecks.
Electrical wiring
Check the correct execution of burner and gas ramp electrical connections.
Gas leaks
Check that there are no gas leaks in the following areas:
- the meter-burner pipe
- the valve-mixer coupling
- the burner sealing flange.
Combustion head
View the combustion head and check that the fabric is intact, free of holes or wide and deep corrosion.
Also check that there are no deformations due to high temperature.
Gas ramp
Check the valve calibration and operation proportionality using exhaust gas analysis.
Check the valve/manifold compensation tube.

44

Electrode group
In case of electrode verification and/or replacement, check that the electrodes and the probe do not show
pronounced deformations and surface oxidation. Check that the distances indicated in the figure are still met,
possibly reset them.

If necessary, eliminate the oxide from the probe's surface using an abrasive paper.
Do not rotate the electrode. Place it as shown in the figure; if the electrode is placed near the
ionization probe, the equipment's amplifier could be damaged.
Combustion
Leave the burner running at full speed for about ten minutes, correctly calibrating all the elements listed in this
manual.
Then perform a combustion analysis and check:
CO2 percentage (%);
CO content (ppm);
NOx content (ppm);
Ionisation current (A);
Chimney fume temperature.
Adjust the burner if the combustion values recorded at the beginning of the operation do not meet in force
regulations or, in any case, do not correspond to a good combustion.
Write the new combustion values in a suitable form, they will be useful for the subsequent checks.
FAULTS / REMEDIES
This is a listing of some causes and possible remedies to a series of faults that may occur and lead to burner
failure or non-regular operation. A fault, in most cases, leads to lighting of the equipment's command and control
release button.
After this signal is enabled, the burner will work again only after the release push-button is pressed; after this has
been done, if there is a regular ignition, you can allocate the arrest to a transient and non dangerous anomaly. If
the block persists, you will have to search for the cause of fault and implement the remedies shown in the
following tables.
Operation faults

45

Ignition difficulties

Safety warnings
In order to ensure a combustion with a minimum rate of pollutant emissions, the size and the type of the heat
generator's combustion chamber must match clearly defined values.
Therefore, you should consult the Assistance Technical Service before choosing this type of burner for this generator
generator. Qualified staff has the technical professional requirements specified by the law no. 46 of 5 March 1990
The commercial organization has an extensive network of agencies and technical services, who's staff regularly
attends courses of instruction and update at the corporate Training Centre.
This burner must be used only for its intended purpose.
Any contractual and non-contractual liability of the manufacturer for any damage caused to people, animals or things,
errors of installation, adjustment, maintenance and improper use are excluded.

46

Basic safety rules


- This equipment may not be used by children or unauthorised personnel.
- Plunging with rags, cards or other things of the intake or dissipation gratings and the ventilation opening of the area
where the equipment is installed it is strictly forbidden.
- Any attempt of equipment repair by unauthorized personnel is strictly forbidden.
- Pulling or twisting of electrical cables is dangerous.
- Any cleaning operation before disconnecting the equipment's power supply is strictly forbidden.
- Do not carry out cleaning operations of the burner or its parts using flammable substances (e.g. , gasoline, alcohol,
etc. ). Cleaning of the casing must be carried out using only soapy water.
- Do not place objects on the burner.
- Do not cap or reduce vent dimensions of the establishment where the generators is installed.
- Do not leave containers and flammable substances in the establishment where the equipment is installed.
Notes regarding electrical wiring safety
- Default electrical wiring must not be altered
- Any checks must be performed in the absence of electrical power.
- The manufacturer declines any responsibility for changes or connections other than those represented in the wiring
diagrams.
- Do not switch the power supply line's neutral conductor with the phase conductor The possible reversal would induce
a stop due to misfire.
- The equipment's electrical safety is reached only when the machine is correctly connected to an effective grounding
system, executed as required by the in force regulations. This fundamental security requirement must be verified. In
case of doubt, an authorised staff should carry out an accurate control of the electric system .
- The electrical system must be adequate for the maximum power absorbed by equipment, displayed by the
identification in plate and in the manual, in particular making sure that the cable section is suitable for the power
absorbed by the unit.

Electrical schematics legend


A1
ESYS S4965V2208-HSI electrical equipment
FCS Rotor speed control
G
Signal converter 0-10 V / 4-20 mA
MV
Fan motor
RS
Remote release button
SB
Unlock signal
SO
Ionisation probe
TA
Ignition transformer
TB
Burner earth connection
TL
Limit thermostat/pressure switch
TS
Safety thermostat/pressure switch
T6A Mono phase power supply fuse
Y
Valve group
Y1
Valve 1
Y2
Valve 2
X1
10-pin connector
X2
6-pin connector
X3
18-pin connector
XMB Terminal strip
XP7
7-pin socket
XS7
7-pin plug

47

48

49

14 START UP WARNINGS
PRELIMINARY CHECKS
Before starting the boiler, check that:
- The rating plate specifications and power supply network (electricity, water, gas) specifications correspond;
- The burner power range is compatible with the power of the boiler;
- The boiler room also contains the instructions for the burner;
- The flue gas exhaust pipe is operating correctly;
- The air inlet supply is well dimensioned and free from any obstacle;
- The boiler door, the smoke box and the burner plate are closed in order to provide a complete flue gas seal;
- The system is full of water and that any air pockets have therefore been eliminated;
- The anti-freeze protections are operative;
- The water circulation pumps are operating correctly.
- The expansion vessel and the safety valve(s) have been connected correctly (with no interception) and are
properly operating.
- Check the electrical parts and thermostat operation.

WATER TREATMENT
If the boiler is to be installed in an existing system where there could be frequent losses from the system
or if the hardness of the water is greater than 10 F, it will be necessary to use a filter and a softener for
system water and control the pH above 8-9.
The most common phenomena that occur in heating systems are:
Scaling
Scale obstructs heat transfer between the combustion gases and the water, causing an abnormal increase in
the temperature of the metal and therefore reducing the life of the boiler.
Scale is found mostly at the points where the wall temperature is highest and the best remedy, at construction
level, is to eliminate areas that overheat.
Scale creates an insulating layer, which reduces the thermal transfer of the boiler, affecting system efficiency.
This means that the heat produced by burning the fuel is not fully transferred and is lost to the flue.
Scale diagram
Key
%
% fuel not used
mm mm scale
-

Corrosion on the water side


Corrosion of the metal surfaces of the
boiler on the water-side is due to the
passage of dissolved iron through its
ions (Fe+). In this process the presence
of
dissolved gases and in particular of
oxygen and carbon dioxide is very
important. Corrosion often occurs with
softened or de-mineralised water, which has a more aggressive effect on iron (acid water with Ph <7): in these
cases, although the system is protected from scaling, it is not protected against corrosion and the water must
be treated with corrosion inhibitors.

FILLING THE SYSTEM


The water must enter the system as slowly as possible and in a quantity proportional to the air bleeding capacity of
the components involved. In the case of a system with closed expansion vessel, water must be let in until the
pressure gauge indicator reaches the static pressure value, pre-set by the vessel. Heat the water to maximum
temperature. During this operation, the air contained in the water is released through the automatic air separators
or through manual bleed valves. The water released from the system with elimination of the air is made up by the
automatic or manual-filling valve.

50

15 OPERATION
This operation and all regulation, verification, periodic checks and maintenance op-erations
must be performed by professionally-qualified personnel.

OPERATION CHECKS
The heating system must be used suitably, ensuring on the one hand, optimum combustion with reduced emission
to the atmosphere of carbon monoxide, hydrocarbons and soot, and on the other avoiding all damage to persons
and property.
The pressurisation must remain within the limit values shown in the technical data table.
In the event of poor smoke sealing in the upper part of the boiler (upper door), check the closing tie-rods.
Do not open the door while the burner is in operation. In all cases wait a few minutes after
stopping the burner for the insulation to cool.

TEMPORARY BOILER STOP


To stop the boiler temporarily, set the main switch on the control panel to OFF. The electrical parts will now be
free of power.

PROLONGED BOILER STOP


Close the gas valve that is fitted upstream of the boiler
During long stoppages in winter, and in order to avoid frost damage, freeing the heating system
is recommended. The adding of antifreeze liquids in proportion to the installation site is
recommended regardless.

PERIODICAL CHECKS
-

Check periodically that there is no air in the heating system


Periodically check the boiler pressure.

MAINTENANCE AND CLEANING


All maintenance and cleaning can only be carried out only after closing the fuel supply and switching off the
electrical supply.
As economic operation depends on the cleanliness of the heat exchanger surfaces and on burner adjustment, it is
recommended to:
- Have the burner settings checked by professionally qualified personnel;
- Analyse the system water and allow for adequate water treatment to avoid the formation of calcareous
incrustations that initially reduce boiler efficiency, and then lead to damage;
- Check that the cladding and the flue gas sealing gaskets are in good order and if not, replace;
- Periodically check the efficiency of the regulation and safety instruments on the system.

51

ICI CALDAIE SpA


Via G. Pascoli, 38
37059 Campagnola di Zevio VR
Telefono 045 8738511
Fax 045 8731148
Info@icicaldaie.com
www.icicaldaie.com
Partita Iva 00227490232
Rag. Soc. n. 6677
C.C.I.A.A. VR n. 69600
Appartenente al Gruppo Finluc
Iscritto R.I. VR 02245640236

DECLARATION OF CONFORMITY WITH


THE EUROPEAN COMMUNITY REGULATIONS
I undersigned Emanuela Lucchini, Managing Director of ICI CALDAIE S.p.A.,
headquarted in via G. Pascoli 38 37059 Campagnola di Zevio (VR) Italy
DECLARE THAT STEEL BOILERS

TBX
comply with the CE certificate and in accordance with the boards regulations:
-

Gas Directive 2009/142/CE


Low Voltage Directive 2006/95/CE
Efficiency Directive 92/42/CEE
EMC Directive 2004/108/CE
S. Maria di Zevio, li 17/01/2013

52

Member of Finluc Group, Bus. Registry VR No. 02245640236

Via G. Pascoli, 38 - Zevio - sect. Campagnola - VERONA - ITALY


Tel +39-045/8738511 - Fax +39-045/8731148
info@icicaldaie.com - www.icicaldaie.com
The data reported are only approximate and are not binding. Our company reserves the right to introduce alterations at any time, as it deems fit and
proper for the development of the product.

93120351-EN Ed. 1-09/13

1 - St. 10- 09/13

Вам также может понравиться