Minimum cooler flow Flow (maximum cooler temperature rise) for standard units is shown in the Unit Operating Ranges table. Maximum change in temperature is
20 F (11.1 C). When flow rate required is lower (or rise is
higher), follow recommendations below:
Multiple smaller chillers can be applied in series, each
providing a portion of the design temperature rise.
Some chilled fluid can be recirculated through the cooler
to raise flow rate. However, mixed temperature entering
cooler must be maintained at a minimum of at least 5 F
(2.8 C) above the leaving chilled fluid temperature.
Special reduced pass or multiple pass heads cooler can
be used. Contact your Carrier representative for further
information.
NOTE: Recirculation flow is shown below.
RECIRCULATION FLOW
Fouling factor The factor used to calculate tabulated ratings was 0.00010 ft2 hr F/Btu (.000018 m2 C/W). As
fouling factor is increased, unit capacity decreases and compressor power increases. To determine selections at other fouling factors, use the chiller program in the electronic catalog.