Академический Документы
Профессиональный Документы
Культура Документы
DISTRIBUTION
Neil McDonagh
ESB International, Ireland
ABSTRACT
In urban areas, high voltage underground cables are commonly used for the transmission and distribution of electricity.
Many such high voltage cables have metallic sheaths or screens surrounding the conductors, and/or armour and metallic
pipes surrounding the cables. During earth faults applied to directly earthed systems, these metallic paths are expected to
carry a substantial proportion of the total fault current, which would otherwise flow through the general mass of earth, while
returning to system neutrals. These alternative return paths must be considered when determining the extent of the grid
potential rise at an electrical plant due to earth faults. This paper examines fault current distribution following a single phase
to earth fault at a high voltage urban substation. Sub A 110kV substation is fed by two 110kV connections to Sub B and Sub
C substations. Both feeders are pipe type cables. A network model incorporating the substation earth grid and cable sheaths
is built using proprietary software and the results presented. Current injection tests are carried out to verify modelled results.
Finally the implications of alternative return paths provided by cables are discussed and conclusions are drawn.
Keywords:
Earthing, Grounding, cable sheaths, Substation, Fault current distribution, Cable sheaths, current injection
test, computer modelling.
INTRODUCTION
(Equation 1)
Fault
CALCULATIONS
Cable
core
Steel pipe
(R
I
A + lzm1,2 + RB) - - - - - - - - - - - - |
2
|
|
Ig = -If - I1 - I2 - .............-In
(Equation 4)
= Earth grid resistance at Sub A
RA
= Earth grid resistance at Sub B
RB
l
= length of feeder
Zc1 = series impedance along return path 1
Zm1,2 = Mutual impedance between path 1 and 2
Zmp,1 = mutual impedance between faulted phase and
return path 1
= Current flowing along return path 1
I1
1
2
3
4
5
6
7
Fig. 6
410.134 @ - 104.93o
114.48 @ 160.147 o
o
114.48 @160.147
o
570.16 @ 143.87
147.87 @ - 144.84 o
66.63 @ 167.27 o
o
66.63 @ 167.27
(b)
300.13@ - 129.093o
98.734@168.035 o
o
98.734@168.035
491.7@151.735
127.51@ - 136.974 o
57.461@175.127 o
o
57.461@175.127
400
GPR (volts) per kA of
injected current
(a)
350
300
250
20 ohm
10 ohm
200
5 ohm
150
2 ohm
100
1 ohm
50
0
2
5
10
Cable lengths (km)
20
MEASURED RESULTS
A current injection test was carried out at an urban
substation in the spring of 2005. The circuit used for the
current injection was similar to the description of the
network provided in the introduction. The faulted phase
was on the feeder to Sub C. The lengths of the feeders to
Sub B and Sub C were 4.7km and 7.2km respectively.
The EGR at Sub A was modelled as 40 , while the
EGRs at Subs B and C were assumed to be 1 . The
results shown are averages of measurements taken for a
number of different injected currents. The magnitudes
displayed are percentages of the fault current.
It must be noted that a number of issues were noted
during measurement. At times there were current surges
of up to 10A being measured on the pipe of feeder C
when no current was being injected. Injected currents
varied between 10A and 137A; therefore a 10A surge
could have a serious effect on measurements. When the
current on this pipe was measured, erratic variations were
noted. It must also be noted that medium voltage
connections were not considered and it is expected that a
proportion of current may have taken this path. It was not
possible to measure the currents on the armour. In reality
the cable sheaths, armours and pipe are bonded at every
joint.
Table 3 Measured Results
Sub B
Sub C
Injected current
R phase
R sheath
S sheath
T sheath
Pipe
mag
0
2.42
2.58
2.48
8
angle
0
180
180
180
180
mag
100
26.69
11.29
11.23
*85.5
angle
0
-141.4
-162.8
-164
-170
Sub B
mag
angle
0
0
0.139 -30.1
0.131 -33.8
0.131 -33.8
0.081 -23.0
0.077 -28.5
0.077 -28.5
2.81
53.7
Sub C
mag
angle
100
0
30
-129
9.81
168
9.81
168
12.7
-137
5.71
175
5.71
175
50
150
mag
0
0.21
0.175
0.175
0.125
0.102
0.102
3.46
angle
0
180
120
120
134
127
127
-146
mag
100
40.9
11.36
11.36
14.72
6.613
6.614
58.63
Ig
Measured
Equation 3
CDEGS
**56.7
3.13
2.79
GPR (V)
***
11.16
12.55
angle
0
-104.9
159.9
159.9
-144.8
167
167
142.7
AUTHORS ADDRESS
The author may be contacted at
Power Systems Studies
ESB International
Stephen Court
18-21 St Stephens Green
Dublin 2.
neil.mcdonagh@esbi.ie