DOP-B07S411K (Front View)

DOP-B07S411 / DOP-B07S411K

+0.04"+1.0

196.9 0 (7.75" -0

)
Note:

DOP-B07

+1.0 (5.63"
+0.04" )
T=1.6mm(0.063")~6mm(0.24")
-0
51.2(2.02")
0

High ColorWide Screen


User-Friendly HMI Products

215(8.46")

142.9

B07S411/B07S411K Instrunction Sheet

142.3 (5.6")

161(6.34")

(1) Preface
Thank you for purchasing DELTAs DOP-B series. This instruction sheet will be helpful in the installation,
wiring and inspection of Delta HMI. Before using the product, please read this instruction sheet to ensure
correct use. You should thoroughly understand all safety precautions before proceeding with the
installation, wiring and operation. Place this instruction sheet in a safe location for future reference. Please
observe the following precautions:
Install the product in a clean and dry location free from corrosive and inflammable gases or liquids.
Ensure that all wiring instructions and recommendations are followed.
Ensure that HMI is correctly connected to a ground. The grounding method must comply with the
electrical standard of the country (Please refer to NFPA 70: National Electrical Code, 2005 Ed.).
Do not disassemble HMI, modify or remove wiring when power is applied to HMI.
Do not touch the power supply during operation. Otherwise, it may cause electric shock.
If you have any questions during operation, please contact our local distributors or Delta sales
representatives.
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or
download the most updated version at http://www.delta.com.tw/

(5) Specifications

MODEL

User-defined Function Keys / System Keys


A

System Keys:

Backlight
Display Size

Lights in green when HMI works normally.

(2) Pin Definition of Serial Communication

: Operation LED Indicator (Blue)

COM Port

MODE1

PIN

RXD
TXD

Buzzer

Serial
COM Port

RS-232 / RS-485

COM3

RS-422 / RS-485

PIN1

User defined key x 4 +

N/A

System key x 4

1. The definition of the operation LED indicator (Blue) can be determined by the users freely.

MODE1

1
2
3
4
5
6
7
8
9

RS-232(supports hardware flow control)

COM2

Function Key

PIN

32Kbytes
Multi-Tone Frequency2K ~ 4K Hz85dB

NOTE

DOP-B07S411 / DOP-B07S411K COM2 Port

COM Port

64Mbytes

1 USB Slave Ver 2.0


1 USB Host Ver 1.1
COM1

RTS
CTS

Flash ROM 128 MB


(OS System: 30MB / Backup: 16MB / User Application: 82MB)

USB

Touch Screen / Display

154.1 x 87.6mm
Delta Real Time OS

32-bit RISC Micro-controller

Backup Memory

The alarm LED indicator blinks in red when one of the alarms is on.
D

154.08 x 85.92mm

MCU

SDRAM

: Alarm LED Indicator (Red)

GND

800 x 480 pixels


o
LED Back Light (less than 20,000 hours half-life at 25 C) (Note
1)

Operation System

NOR Flash ROM

out or the data is accessing (please refer to the Note1 below for explanation).

RS-232
1
2
3
4
5
6
7
8
9

PIN1

(Note1)

The operation LED indicator blinks in blue when either the communication is carried

DOP-B07S411 / DOP-B07S411K COM1 Port

DOP-B07S411K
7" TFT LCD (65535 colors)

Resolution

, SYS

: Power LED Indicator

DOP-B07S411
Display Type

LCD MODULE

User-defined Function Keys: F1, F2, F3, F4

MODE2
COM2

MODE3

COM2

COM3

RS-232

RS-485 RS-485 RS-485 RS-232 RS-422

COM3

COM2

D+

DOP-B07S411 / DOP-B07S411K (Rear View)

COM3

TXD+

RXD
TXD

RXD
TXD
D+

D+

GND

GND
D-

RXD+
GND
TXDE

D-

Built-in

Cooling Method

Natural air circulation

Safety Approval

CE

Waterproof Degree

IP65

Operation Voltage (Note2)

DC +24V-10% ~ +15%(please use isolated power supply)

Voltage Endurance

AC500V for 1 minute (between charging (DC24V terminal)


and FG terminals)

Power Consumption (Note 2)


D

C
D-

Perpetual Calendar (RTC)

RXD-

4.0W

Backup Battery
Backup Battery Life

Note1: Blank = No Connection.

3V lithium battery CR2032 1


It depends on the temperature used and the conditions of usage,
about 3 years or more at 25 C.

(3) Parts Names

0 C ~ 50 C

Storage Temperature

-20 C ~ +60 C

Operation Temperature

Ambient Humidity

DOP-B07S411 (Front View)


A

Power Input Terminal

COM1

COM2

USB Slave

USB Host

Battery Case / System Key

(4) Dimensions
A

Vibration Resistance

Dimensions
(W) x (H) x (D) mm
Panel Cutout
(W) x (H) mm
Weight

10% ~ 90% RH [0 ~ 40 C], 10% ~ 55% RH [41 ~ 50 C]


Pollution Degree 2
IEC 61131-2 Compliant
5Hzf9Hz = Continuous: 1.75mm / Occasional: 3.5mm
9Hzf150Hz = Continuous: 0.5g / Occasional: 1.0g
X, Y, Z directions for 10 times
215 x 161 x 50
196.9 x 142.9
Approx. 820g

Approx. 840g

NOTE
1) The half-life of backlight is defined as original luminance being reduced by 50% when the maximum driving

Touch Screen / Display

Power LED Indicator

current is supplied to HMI. The life of LED backlight shown here is an estimated value under 25 C normal
temperature and humidity conditions.
2) The value of the power consumption indicates the electrical power consumed by HMI only without connecting
to any peripheral devices. In order to ensure the normal operation, it is recommended to use a power supply
which the capacity is 1.5 ~2 times the value of the power consumption.
3) The content of this instruction sheet may be revised without prior notice. Please consult our distributors or
download the most updated version at http://www.delta.com.tw/

DOP-B07S411K (n Grnm)

DOP-B07S411 / DOP-B07S411K

+0.04"+1.0

196.9 0 (7.75" -0

)
Note:

DOP-B07

+1.0 (5.63"
+0.04" )
T=1.6mm(0.063")~6mm(0.24")
-0
51.2(2.02")
0

Yksek RenkGeni Ekran


Kullanm Kolay HMI rnleri

215(8.46")

142.9

B07S411/B07S411K Bilgi Dkman

142.3 (5.6")

161(6.34")

(1) nsz
DELTAnn DOP-B serisi operatr panellerini setiiniz iin teekkrler. Bu bilgi dkman Delta HMI
kurulum, balant, bakm ve kontrolnde kullancya yardmc olacaktr. Doru kullanm iin rn
kullanmadan nce bu dkman mutlaka okuyunuz. Kurulum, balant ve alma yapmadan nce
gvenlik uyarlarn tamamen anladnzdan emin olunuz. Bu dkman daha sonra da kullanmak iin iyi
muhafaza ediniz. Ltfen aadaki gvenlik uyarlarna dikkat ediniz:
rnn kurulumunu yanc gaz ve svlardan uzak kuru ve temiz ortamlara yapnz.
Balantlar yaparken tm balant kurallarnn salandndan emin olunuz.
HMInn toprak balantsnn doru yapldndan emin olunuz. Topraklama metodunun rnn
kurulduu lke standartlarna uygun olduuna emin olunuz (NFPA 70: National Electrical Code,
2005 Ed.).
HMI enerjili iken kablo balants yapmaynz ya da skmeyiniz.
alma srasnda enerji besleme terminallerine dokunmaynz. Aksi halde elektrik oku olabilir.
rnn kullanm ile ilgili sorularnz iin, ltfen teknik servisimizle balantya geiniz.
Herhangi bir ihbara gerek kalmakszn bu bilgi dkmannn ierii deitirilebilir. Gncellenmi versiyonu
elde etmek iin teknik servise danabilir veya internet adresinden indirebilirsiniz. http://www.delta.com.tw/

A
B

(5) zellikler

MODEL

Kullanc-tanml Fonksiyon Tular / Sistem Tular


A

LCD MODL

Kullanc-tanml Fonksiyon Tular: F1, F2, F3, F4


Sistem Tular:

Aydnlatma
Display l

HMI normal altnda yeil yanar.


: alma LED Indikator (Mavi)

(2) Seri Haberleme Pin Aklamalar


COM Port

(Not 1)

: Sa kenar: Alarm LED Indikator (Krmz)

COM1

RXD
TXD

1
2
3
4
5
6
7
8
9

PIN1

32Kbyte

1 USB Slave Ver 2.0


1 USB Host Ver 1.1

Seri
COM
Port

Touch Screen / Display

RS-232(donanm flow (ak) kontrol destekler)

COM2

RS-232/RS-485
RS-422/RS-485

NOTE
Fonksiyon Tuu

RTS
CTS

4 adet kullanc tanml tu +


4 adet sistem tuu

N/A

1. alma LED indikatr (mavi) tanmlamas kullanc tarafndan belirlenebilir.


Gerek Zaman Saati(RTC)

MODE2
COM2

MODE3

COM2

COM3

COM3

COM2

RS-232

RS-485 RS-485 RS-485 RS-232 RS-422


D+

COM3

TXD+

RXD
TXD

RXD
TXD
D+

D+

GND

GND
D-

Dahili

Soutma Metodu

DOP-B07S411 / DOP-B07S411K (Arka Grnm)

MODE1
PIN

64Mbyte

Multi-Ton Frekans2K ~ 4K Hz85dB

COM3

GND

DOP-B07S411 / DOP-B07S411K COM2 Port

COM Port

Flash ROM 128 MB


(OS Sistem: 30MB / Backup: 16MB / Kullanc Uygulama: 82MB)

USB

Herhangi bir alarm aktif olduunda Alarm LED indikator krmz flash yapar.

1
2
3
4
5
6
7
8
9

Delta Real Time OS


32-bit RISC Micro-ilemci

Buzzer

Doal hava sirkulasyonu

Gvenlik Onay

CE

Su Geirmezlik Derecesi

IP65

alma Voltaj (Not2)

DC +24V-10% ~ +15%(ltfen izoleli g kayna kullannz)

Dayanma Voltaj

1 dakika iin AC500V (DC24V besleme terminalleri ve FG terminalleri arasnda)

G Tketimi (Not 2)
E

RXD+
GND
TXD-

4.0W

Backup Pili

3V lityum pil CR2032 1


o

Backup Pil mr

Kullanm koullar ve ortam scaklna bal olarak 25 Cde yaklak 3 yl veya


zeri.
o

alma Scakl
D-

D-

RXD-

Not 1: Bo = Balant Yaplmaz.

0 C ~ 50 C
o

Saklama Scakl

-20 C ~ +60 C
o

(3) Para simleri

Rutubet Oran

DOP-B07S411 (n Grnm)

(4) ller

(Not 1)

154.1 x 87.6mm

MCU

SDRAM

RS-232
PIN1

154.08 x 85.92mm

Backup Memory

(Ltfen aadaki Not 1i inceleyiniz).

MOD 1

PIN

800 x 480 piksel


o

LED Aydnlatma (25 C yarm mrde 20,000 saatden az)

letim Sistemi

NOR Flash ROM

Haberleme saland zaman veya data iletiimi srasnda alma LEDi mavi flash yapar .

DOP-B07S411 / DOP-B07S411K COM1 Port

DOP-B07S411K
7" TFT LCD (65535 renk)

znrlk

, SYS

: Power LED Indikator

DOP-B07S411

Display Tipi

Power Giri Terminali

COM1

COM2

USB Slave

USB Host

Pil Kapa / Sistem Tuu

Titreim Direnci

10% ~ 90% RH [0 ~ 40 C], 10% ~ 55% RH [41 ~ 50 C]


Kirlenme Derecesi 2
IEC 61131-2 Uyumlu
5Hzf9Hz = Srekli: 1.75mm / Geici: 3.5mm
9Hzf150Hz = Srekli: 0.5g / Geici: 1.0g
X, Y, Z ynnde 10 defa

ller
(W) x (H) x (D) mm
Panel Kesim ls
(W) x (H) mm
Arlk

215 x 161 x 50
196.9 x 142.9
Yaklak 820g

Yaklak 840g

NOTE
A

Arka
1) k yarm-mr, HMI maksimum akmla beslendiinde orijinal aydnlatmann %50 drld anlamna gelir.
o

Yukarda gsterilen arka k LED aydnlatma mr 25 C de derecede normal scaklk ve rutubet ortamnda
tahmin edilen deerlerdir.
G
2) tketimi HMI nitesinin hi bir cihaza bal olmadan bo olarak tkettii gc gsterir. Normal almada
HMInn boken tkettii gcn 1.5 veya 2 kat g verebilen besleme kayna kullanlmas tavsiye edilir.
Herhangi bir ihbar olmadan bu dkmann ierii deitirilebilir. En son gncellenmi halini firmamzdan talep
3)
edebilir
yada aadaki link adresinden indirebilirsiniz http://www.delta.com.tw/
A

Dokunmatik Ekran / Display

Power LED Indikatr

Вам также может понравиться