Академический Документы
Профессиональный Документы
Культура Документы
ii
Section 5:
1.1
Introduction
The UPS inverter section converts the DC busbar voltage into a well regulated,
three-phase alternating voltage suitable for powering the critical load. As the DC
busbar voltage can vary typically between 432Vdc (when the batteries are on float
charge) and 320Vdc (the battery end of discharge voltage) the inverter must be
controllable over this entire input voltage range to ensure that the critical load
voltage remains at the UPS nominal output voltage. The inverter control method
used in the 7200 Series UPS equipment is known as pulse width modulation
(PWM), and is described in simple terms in this chapter.
Liebert manufacture two designs of PWM inverter for use in large three-phase
UPS systems. In general, modules rated below 200kVA employ three independent, but identical, inverter phases operating at 120 with respect to each other to
produce the three-phase UPS output. Modules rated at 200kVA and above employ
a total of six inverter phases, with each UPS output phase obtained from two inverter phases operating in a push-pull-like manner. These two types of inverter
configurations are described as being single-ended and double-ended respectively.
Note: As the 7200 Series UPS range are currently all less than 200kVA they all
use a single-ended inverter design; however the double-ended design is also described in this chapter for completeness of explanation.
1.2
1.2.1
TRH
O/P
TRL
Neg. Bus
DC BUS negative
5-1
When this circuit is used as a switch it has two stable states of interest:
1. When TRH is turned ON and TRL is OFF, the inverter output is effectively
connected to the positive DC busbar and is approximately equal to the positive busbar voltage.
2. Similarly, when TRH is turned OFF and TRL turned ON, the output is connected to the negative DC busbar and is equal to the negative busbar voltage.
For this circuit to operate successfully as a switch, the transistors base drive signals must always be in anti-phase i.e. one of the transistors must be OFF while
the other is ON. If both transistors are turned ON simultaneously they effectively
place a short circuit across the DC busbar and will cause the equipment to shutdown, and possibly fail, due to a DC overload condition.
Basic inverter block output waveform
As the inverter power block operates as a switch, its output voltage takes the form
of a square-wave with a peak-to-peak amplitude equal to the DC busbar voltage,
and at a frequency determined directly by the transistors drive signal switching
rate (i.e. from the control electronics).
Note that the DC busbar is derived from the phase controlled rectifier and is in
practice approximately equidistant from ground (neutral) e.g. if the bus voltage
is 450Vdc then the positive bus will be about +225Vdc with respect to neutral
(ground), and the negative bus about -225Vdc.
1.2.2
Block B
Block A
ON
ON
ON
TR1
OFF
OFF
ON
ON
A
Output Transformer
OFF
OFF
OFF
ON
ON
TR4
TR2
OFF
ON
TR3
Output Filter
OFF
OFF
Figure 5-2 illustrates two power inverter blocks connected together by a transformer: with inverter block A consisting TR1/TR2 and block B consisting TR3/
TR4. As described in paragraph 1.2.1, the drive signals to each pair of IGBTs
within an inverter block are always at 180 with respect to each other; however
the diagram in Figure 5-2 also shows that the relative polarity of the signals to the
5-2
two inverter blocks are also in anti-phase i.e. the drive signals to the high transistors of Block A (TR1) and Block B (TR3) are in anti-phase, as are the signals
to the two remaining transistors (TR2 and TR4).
At the instant in time highlighted in Figure 5-2, TR1 & TR4 are both turned ON
and TR2 &TR3 are OFF. This leads to the left-hand side of the output transformer
primary winding being connected the positive DC bus (+450V) and the right-hand
side to the negative DC bus (0V), and current flows through the primary winding
in the direction A-to-B. Although at first glance this circuit may appear to present
a short-circuit across the DC busbar, the current flowing through the transformer
is limited by the impedance presented by the primary winding which comprises
the impedance of the transformer itself, together with the reflected impedance of
the output filter and load (when connected).
When the control electronics reverse the transistor drive signals TR1 & TR4 turn
OFF and TR2 & TR3 turn ON. This reverses the polarity across the output transformer primary and, in this case, current now flows through the transformer from
B-to-A, as illustrated in Figure 5-3.
Figure 5-3: AC-DC Conversion (Step 2)
+ve Bus (450V)
ON
Block B
Block A
ON
ON
TR3
TR1
OFF
OFF
OFF
ON
ON
TR2
OFF
OFF
A
ON
ON
Output Filter
TR4
OFF
OFF
ON
OFF
Thus, by controlling the switching sequence of the two inverter blocks in relation
to each other it is possible to build-up a current flow through the transformer primary in either direction, which leads to an alternating current being induced in
the transformer secondary and the production of an (alternating) secondary voltage. In practice the (output) transformer is of a step-up design and its secondary
voltage represents the required UPS output voltage. The output amplitude is
controlled by using the pulse-width modulation techniques described below,
working in conjunction with the output filter to obtain a good sinusoidal waveshape. The output filter comprises a capacitor network tuned with the output
transformer inductance to effectively remove the high frequency switching components from the output waveform.
1.2.3
5-3
TRH
66%
TRL
Bus -ve
Bus +ve
1:1 Mark-Space
TRH
50%
TRL
Bus -ve
Bus +ve
1:2 Mark-Space
TRH
33%
TRL
Bus -ve
Basic control principles are best understood by considering the effects on the
output waveform of a single inverter power block when switching the inverter
transistors at a constant rate (modulation frequency) but at various mark-space
ratios. This is illustrated in Figure 5-4 above, which shows the inverter output
waveform when TRH:TRL are turned on at ratios of 2:1, 1:1, and 1:2 respectively.
The top diagram illustrates the case where the inverter is operating at a constant
2:1 mark-to-space ratio i.e. TRH ON period being twice that of TRL which
results in a mean output voltage (with respect to the negative DC busbar) approximately equal to 66% of the DC busbar voltage.
In the middle illustration the transistors are shown operating at a M:S of 1:1 (i.e.
equal ON and OFF periods). In this example the inverter output is a true square
wave and has a mean voltage approximately equal to 50% of the DC busbar voltage once again with respect to the negative DC busbar.
A M:S ratio of 1:2 is shown in the lower illustration to produce a mean voltage of
approximately 33%.
Notice that in the above examples the inverter switching frequency is constant in
all three cases and the mean output voltage is varied by changing the mark-tospace ratio of the drive signals only.
5-4
In the above examples the mean output voltages are obtained by filtering the
variable m:s pulse waveforms. The filter works by absorbing energy (charging)
when the pulse is present (i.e. during the mark period) and returning it back to
the circuit (discharging) when the pulse is absent (i.e. the space period). This has
the effect of averaging-out the energy provided by each pulse over the complete
pulse period (e.g. P1, P2...), as shown below in Figure 5-5 i.e. the mean value
is the integral of the pulse width (shown shaded) taken over each complete pulse
period (P1, P2 ....).
Figure 5-5: Basic filter action
2:1 m:s waveform
Positive bus
Mark
100%
Space
66%
Filter
0%
Negative bus
P1
P2
P3
A
mean voltage
A
P1
mean voltage
B
A
P1
Note that in each of the above examples the mean voltage produced is represented by the
area of the waveforms mark pulse i.e. proportional to the width of the voltage pulse.
5-5
Generating a sine-wave
From basic principles, a sine-wave can be developed by plotting the vertical component of a vector as it is rotated through a complete circle.
Figure 5-6: Instantaneous value of a rotating vector
(/2 rads)
90
180
( rads)
V1
rotation
t1
0
360
(2 rads)
270
(2/3 rads)
This is illustrated in Figure 5-6, which shows that when vector A is rotated anticlockwise for time t1, its vertical component V1 can be described in trigonometrical terms as:
V1 = A sin1 where 1 is the angle of rotation (Equation 1).
When considering an electrical voltage waveform, the length of vector A represents the peak voltage and V1 represents the instantaneous voltage at time t1.
The relationship between the angle 1 and time t1 is determined by the angular velocity of the vector, which is usually represented in mathematical equations
by the greek letter omega (), where:
= 2f rads/s (radians/second) (Equation 2).
i.e. 2 is the number of radians travelled in one complete revolution, and f is the
frequency of rotation in revolutions-per-second (Hertz). For example: at 50Hz the
angular velocity of the vector is 2 50 = 100 radians per second.
Once the angular velocity () of the vector is known, the instantaneous value of
1 at time t1 can be found by calculating the product of t. Using the previous
50Hz example; if time t1=2ms then 1 equals 2 50 2 103 = 0.2 radians
(or 36). By substituting 0.2 for 1 and solving equation 1, the instantaneous
voltage V1 can be calculated as Asin0.2 which equals 0.588A i.e. in electrical
terms, V1 = 0.588 x Vpeak.
Using the above principles, the instantaneous voltage V can be calculated at a particular time t using the general formula V=A sint where:
V = instantaneous voltage
A = peak voltage (length of the vector)
= the angular velocity in radians/s (i.e. = 2f)
t = instantaneous time (in seconds)
5-6
0/ 360
180
t8
t7
t6
t5
t4
t3
t2
t1
t0
t0
t1
t2
t3
t4
90
t5
t6
t7
t8
180
270
270
360
t1
t2
t3
t4
t5
t6
t7 t8
90
The upper diagram in Figure 5-7 shows how a sinewave shape is developed by
plotting the instantaneous voltage amplitude at regular intervals as the vector is
rotated from 0 (t0) to 180 (t8) and transferring these values to a linear scale. The
lower diagram illustrates the formation of one complete cycle, which is obtained
by continuing with the plotted points from 180 (t8) to 360 (t16) to provide the
negative half cycle.
For reasons of clarity, the sampled intervals in the above diagrams are quite large
i.e. only 16 samples are taken in the complete cycle. A much cleaner, more
accurate, waveform is produced if the sampling rate is increased: and in the practical 7200 series PWM control circuit the sine-wave is generated using 48 reference points per-cycle as opposed to the 16 points shown here.
5-7
1.2.4
As will be explained later, there are several considerations to be taken into account when deciding upon a modulating frequency, as this affects such things as
the generated output harmonics; inverter switching losses; and filter efficiency
and size. In general, Liebert-designed PWM inverters employ modulating frequencies ranging from 2.4kHz to 9.6kHz.
In the 7200 UPS equipment the modulating frequency is fixed at 2.4kHz, which
therefore means that 48 switching pulses are used to produce each 50Hz (20ms)
output cycle i.e. the output waveform is corrected every 7.5 (0.13 rad), leading
to a very accurate output waveform. The design specification is to produce a voltage sinewave with less that 5% THD for all rated input and load variations.
5-8
P2
P3
P4
t0
t1
t2
t3
P5
P6
P7
P8
t4
t5
t6
t7
P9
90
P1
P2
P3
P4
t0
t1
t2
t3
t8
180
P5
P6
P7
P8
t4
t5
t6
t7
P9
90
P1
P2
P3
P4
t0
t1
t2
t3
t8
180
P5
P6
P7
P8
t4
t5
t6
t7
P9
90
t8
180
P1
P2
P3
P4
P5
P6
P7
P8
P9
t0
t1
t2
t3
t4
t5
t6
t7
t8
90
180
5-9
1.2.5
VI dt ).
A PWM-controlled inverter provides load power each time it is turned on; therefore the power produced by the inverter during each output cycle is represented
by total area of the pulses contained in that cycle. Thus, when dealing with a
PWM waveform the integral equation above can be visualised by considering that
the area of the output sinewave is equal to the sum of the areas of the individual
pulses used to generate the sinewave (See Figure 5-9).
Figure 5-9: Output power derivation
The total amount of time the inverter IGBT devices are turned ON and delivering
load-power during each output cycle can be described in terms of the inverters
duty cycle: and, as will be shown below, this varies in accordance with the available DC busbar voltage and the prevailing load current demand.
Figure 5-10: Typical inverter output section
Bus +ve
R
(450Vdc 320Vdc)
O/P Transformer
O/P Filter
1:2 STEP-UP
R
R
S
Critical load
supply
(400VL-L)
(200VL-L)
N
Bus -ve
Figure 5-10 illustrates a typical UPS output section set to operate at the standard
400V output voltage. The output transformer has a 1:2 voltage step-up ratio,
therefore the inverter must operate at 200VL-L.
200VL-L is equivalent to 115VL-N (i.e. 200 ( 3 ) .) which is in turn equal to approximately 325Vp-p (i.e. 2 115 2 ). The inverter cannot produce a peak-topeak output voltage greater than the DC busbar voltage, therefore the output
waveform would clearly be clipped if the DC busbar falls below this 325V minimum level.
5-10
DC busbar
450Vdc
Inv output
326Vp-p
DC bus - (-225Vdc)
DC bus + (+225Vdc)
Combined area of pulses
still equals the
area under output
sine-wave
DC busbar
360Vdc
Inv output
326Vp-p
DC bus - (-225Vdc)
5-11
falls. Once again, for reasons of clarity the illustration in Figure 5-11 uses only 16
PWM pulses-per-cycle rather that the 48 pulses used in the practical 7200 series
inverter.
With regards to the duty cycle: when the inverter is off-load and the DC busbar is
operating at its float charging voltage of around 450Vdc the sum of the inverter
conduction pulses amount to approximately 75 of the possible 180 forming each
half cycle a.c. conduction period. When the DC busbar is supported from the discharging batteries the duty cycle increases to approximately 105 when the batteries approach the end-of-discharge voltage of 330Vdc.
The effects of the Load demand on the PWM Duty cycle
The PWM wave-form duty cycle is directly affected by variations in the demanded load current. For example, the previous paragraph illustrated that when operating off-load from the normal 450V busbar, the duty cycle is approximately 75.
However, if the inverter is loaded under these conditions it would require that the
individual PWM pulse-widths are increased to maintain the output waveform
whilst allowing more power through to the load. In practice, at a nominal 450V
DC busbar the 7200 inverter duty cycle increases from 75 to approximately 80
over the fully rated load range.
If the PWM duty cycle increase with falling DC busbar voltage and also with load
then the worst case conditions obviously occur when the inverter is operating near
the end-of-discharge voltage and at full load. Under these conditions the duty
cycle will increase to approximately 110.
Note: as the duty cycle from no-load to full-load increases from 75 to 80; and
the increase from float voltage to end-of-discharge voltage causes an increase of
70 to 105, it can be seen that the duty cycle is affected more by changes in DC
busbar voltage than changes in load demand.
5-12
1.2.6
Output filtering
20 msec
15 msec
10 msec
5 msec
0 msec
20 msec
Bus +ve
TRH
0V
TRL
Bus -ve
50Hz sinewave obtained by
filtering the output
PWM pattern
Figure 5-12 illustrates the production of one PWM output cycle at 50Hz and
shows that the positive half cycle is created by beginning with a 1:1 ratio and then
increasing it to a higher ratio and back to 1:1 using a controlled pattern. The negative half cycle is produced in an identical manner; but in this case the ratio begins
at 1:1 and is then reduced to a lower ratio before returning to 1:1.
The sinusoidal output waveform is obtained be employing a filter which, in
simple terms, averages out the modulated waveform on a pulse-by-pulse basis and
thereby produces an output which rises and falls in a sinusoidal manner. In practice, this is achieved by a network of filter capacitors working in conjunction with
the inductance of output transformer to bypass the inverter modulation frequency
and its associated generated harmonics.
Figure 5-13: Filter current characteristics
Filter currents
Filter charging
Filter discharging
Output waveshape
5-13
Figure 5-13 illustrates the filter action in detail. The diagram represents four
2.4kHz pulses at the beginning of the output positive half-wave and shows the effects of the charging and discharging filter currents during the presence and absence of the PWM pulses i.e. the filter capacitors charge-up whilst a pulse is
present (storing energy) and then discharge when the pulse ceases (returning
energy into the output circuit to maintain the general output voltage waveshape).
As the PWM mark:space ratio gradually increases the resulting waveshape closely resembles the required sine-wave.
Clearly, the charging and discharging filter currents are directly related to the
number of PWM pulses contained in the output cycle i.e. the modulating frequency. Where a fewer number of pulses are used per half-cycle, the overall
pulse-widths must increase to allow the filter to store a larger current during the
charge period in order to restore sufficient energy to the output circuit during the
discharge period to maintain the sinusoidal output waveshape; thus requiring
larger capacitors and inductors to handle the increased circulating power. However, although the required L-C components get smaller as the modulating is increased, the inverter switching losses also increase and the overall inverter
conversion efficiency therefore reduces. The selected modulating frequency is
therefore a compromise between these two conflicting factors. An acceptable
mean is reached when using a frequency in the range 2.4kHz to 9.6kHz, and in
the 7200 series UPS an optimal frequency of 2.4kHz is used.
5-14
1.3
POWER INVERTER
Bus +ve
R
1:2
+450Vdc
S
T
0Vdc
Bus -ve
OUTPUT
FILTER
200Vac
400Vac
225Vdc
40
tio
0V
ta
Ro
Neutral
2
V
30
225Vdc
300Vdc
Bus +450Vdc
DC Bus 0V
The inverter converts the DC primary source (nominal 450V DC busbar) to a balanced 3-phase vector system on the UPS output. The inverter output is steppedup by a factor of 1:2 by the output transformer, which also provides galvanic isolation; therefore an inverter output of 200VL-L is required to furnish the standard
400VL-L UPS output voltage
Figure 5-14 contains a block diagram of the inverter output stage and a vector diagram which shows the relationship between the DC primary source (DC bus) and
the AC secondary objective (UPS output). The output neutral point is manufactured by the output transformers star-connected secondary and is positioned exactly at the mid-point of the DC primary source at all times i.e. +225V or -225V
with respect to the nominal 0V or 450V DC input rails respectively. The neutral
is in fact floating about this mid-rail point and remains so as the busbar voltage
decreases towards 320V when powered from the discharging batteries.
As described earlier, (see "The effects of the DC Busbar voltage on the PWM Duty
cycle" on page 5-10), the mark:space ratio of the PWM drive signals are varied to
compensate for such DC busbar voltage fluctuations; however, as is evident from
Figure 5-14, a stage is reached whereby the available DC primary source is inadequate to sustain the output objective (even though the PWM duty has gone to
maximum). In the 7200 series equipment this occurs when the DC busbar falls
5-15
below 290V. When this point is reached the output transformer will saturate and
cause flat-topping of the output voltage waveforms. Note that the inverter itself is
not affected and does not mind running on low input DC sources.
In practice, the inverter is turned off before the DC voltage reaches this absolute
minimum level. In the case of a 400V operating system the end-of-battery discharge (DC undervoltage) threshold is set to approximately 330Vdc, as described
earlier in this chapter (See Figure 5-11).
Figure 5-15: Single-ended inverter output stage
Bus +ve
Three
inverter
phases
(450Vdc 320Vdc)
O/P Transformer
O/P Filter
1:2 STEP-UP
R
R
S
Critical load
supply
(400VL-L)
(200VL-L)
N
Bus -ve
T-ph Aux
T-ph Main
S-ph Aux
S-ph Main
R-ph Aux
R-ph Main
Bus +ve
Bus -ve
R
Output Transformer
R
Filter Capacitors
5-16
Figure 5-15 illustrates the single-ended inverter output design, as employed in the
lower-rated 7200 Series product range, whereby the output transformer is connected in a standard delta-star configuration. The output filter capacitors are connected to the transformer secondary line-to-line and work in conjunction with the
transformers natural impedance to remove all remnants of the modulation frequency from the output waveform and so leave a clean sinewave suitable for connecting to the load, via the inverter-side static switch (contactor).
A double-ended inverter output section, as employed in larger modules, is shown
in Figure 5-16. This design uses two power inverter blocks per output phase,
known as the main and auxiliary inverters. The transistors in each inverterpair are switched in anti-phase with respect to each other i.e. when the top transistor is turned on in the main inverter the bottom transistor is turned on in the
auxiliary inverter (and vice-versa). This enables more power to be delivered to
the load, as described below.
An alternative way of increasing the output power, for a given busbar voltage, is
to use a number of IGBTs connected in parallel in each leg of the inverter power
block; however, due to difficulties with device matching, the inverter MTBF is
adversely affected as the number of parallel devices is increased. Using the
double-ended inverter topography means that no more than two parallel-connected devices are needed for the highest power rating offered in the 7200 UPS range.
As shown below, the power increase offered by a double-ended over a singleended inverter is equal to 3 i.e. the relationship between a single-phase and
three-phase system.
Figure 5-17: Single-ended versus double-ended primary current path
Bus +ve
Bus +ve
2 x 400A
IGBTs
2 x 400A
IGBTs
160kW
2 x 400A
IGBTs
Bus -ve
200Vac
20
92kW
0V
ac
I1
I2
800A
800A
2 x 400A
IGBTs
Bus -ve
5-17
Figure 5-17 shows the comparative primary current flows in the single-ended
and double-ended inverter output transformers. In the single-ended circuit the
transformer primary windings effectively form a closed delta circuit, and the current supplied by one inverter power block is always shared between two windings. In the case of the double-ended circuit the output transformer primaries are
individually connected between the main and auxiliary power blocks of their
respective phases, effectively acting as three single-phase windings; therefore the
full current passes through each individual winding.
1.3.1
Bypass Mains
Supply
To Load
Input
Mains
Supply
Rectifier
Inverter
Isolation
Transformer
Static Switch
Battery
R
0
40
230
Perfectly balanced
3-phase bypass
source
Potential
difference
between both
neutrals
(10V - 1000V)
R
0
40
230
Perfectly
balanced 3-phase
Inverter source
5-18
The bypass supply is an alternative supply to which the load is transferred if the
inverter is switched off, or fails for any reason. A no-break changeover is required during such transfers to ensure the load sees no interruption.
The 3-phase voltage (live wires RST) manufactured by the inverter are electronically linked to the bypass 3-phase supply voltage (live wires RST) via the static
switch. The inverter neutral point is developed in the output transformer wye (zigzag) secondary, and if this point is not tied to the bypass neutral than a potential
difference may exist between the inverter and bypass power sources (it is possible
for this to extend from 10V right up to 1,000V).
To prevent this potential from appearing the output transformer neutral must be
directly tied to the bypass neutral. If this is not done the potential difference between both sources would induce a spike in the neutral during load transfers
which might damage the load equipment.
1.4
1.4.1
5-19
1.4.2
Collector
Gate
Gate
Emitter
RBE
C
CCG
Emitter
CGE
time
ton
toff
5-20
Bipolar
IGBT
1 sec
0.7 sec
12 sec
0.8 sec
The IGBT is a high-speed switching element. As the IGBT switches on and off a
large current at a high speed, the critical rate-of-rise (or fall) of collector currents
(di/dt) is considerably high and can result in the generation of high surge voltages
as illustrated in Figure 5-20.
1.4.2.1
EMITTER
+15V
VGE
N
N
N
+
+
+
- -
-15V
Ic
90%
P
10%
COLLECTOR
tdon
tr
ton
tdoff
tf
toff
Figure 5-21 illustrates the IGBT switching characteristic. The upper waveform
represents the idealised gate/emitter drive pulse (VGE); and the lower waveform
depicts the resulting collector current (Ic).
As can be seen from the lower waveform the total turn-on time (ton) is the time
taken for the collector current to rise to 90%, and is made up of two components,
tdon + tr where:
tdon is the tun-on delay time and is the time taken to attract electrons to the
region underneath the gate (i.e. holes migrate from the N-region to the Pregion) and is usually of the order of 250nsecs.
tr is the rise time and is the time required for the collector current to increase
from 10% to 90% of its final value. This is directly proportional to the gate
impedance (i.e. the gate construction and internal input capacitance) and is
usually of the order of 500 nsecs.
The total turn-off time is the time taken for the collector current to fall to 10%,
and is made up of two components, tdoff + tf where:
tdoff is the device turn-off delay time and is the time taken to remove the
electrons from the region beneath the gate. This is usually of the order of
350nsecs.
tf is the device fall time and is the time taken by the collector current to fall
to 10% of its initial value. This is the time taken to recombine the majority
carriers (holes) back to the N-region and is usually of the order of 350nsecs.
Propagation delay = ton + toff and is of the order of 1.5s.
5-21
For turn-on a positive gate voltage of 15V 10% is recommended. This value is
sufficiently high to fully saturate the IGBT and minimise the on-state losses,
while it is sufficiently low to limit short-circuit current and its resulting stress. In
no case should a gate drive outside the range of 12V-20V be used for turn-on.
An IGBT will be off when its gate voltage is zero. However, in order to ensure
that the IGBT stays in its off-state when dv/dt noise is present in the collector
emitter voltage an off bias must be used. Use of reverse bias also decreases turnoff losses. For H-series IGBTs an off bias of -15V is recommended.
1.4.2.3
Selecting the proper series gate resistor is very important as it has a significant
impact on the dynamic performance of the IGBT which is turned on and off by
charging and discharging the gate capacitance.
A smaller gate resistor will charge/discharge the gate capacitance faster, reducing
the switching times and switching losses. However, under short-circuit, or during
turn-off of the free-wheeling diode across the IGBT, the dv/dt applied to the IGBT
and its collector-to-gate capacitance can cause a current to flow in the gate circuit.
And if this current is large enough, the voltage developed across the gate resistor
can cause the IGBT to turn-on. Thus, while a smaller resistor offers enhanced ruggedness (rejection of dv/dt turn-on), they also provide less margin for gate noise
and can lead to oscillation problems in conjunction with the gate-emitter capacitance and any parasitic inductance in the gate wiring. In addition, smaller gate resistors allow faster turn-on di/dt of the IGBT and may cause an increased surge
voltage at forward recovery. Giving consideration to all the above effects, a resistor value between 1R - 10R is recommended for the series gate resistance.
1.4.3
1.4.3.1
VCE
Surge voltage V
Ed
5-22
1.4.3.2
Desaturation detector
The IGBTs saturation voltage (VCE(sat)) is the voltage drop across the IGBT collector-to-emitter when it is in the fully ON state. The saturation voltage is a function of the collector current (ICE), junction temperature (Tj) and gate-emitter
voltage (VGE) and is typically 2.5V - 4.0V at +15VGE and full ICE at Tj = 125.
VCE(sat) increases proportionally with increases in ICE and Tj and is inversely proportional to changes in VGE.
IGBT protection is incorporated by monitoring the voltage drop across the device
when it is ON and inhibiting the gate drive pulse if the monitored voltage rises the
permissible saturation voltage range. This function is provided by the individual
inverter Gate Driver Boards.
1.4.4
1.4.4.1
Vsurge 800Vdc
On
Conducted back to
DC Caps via
flywheel diode
R1
T1 (primary)
451V
450V
C1
R2
0V
0V
In the 7200 Series UPS inverter application, the IGBT is switching a PWM waveform into the output transformer primary. This primary is in fact a large inductor
and due to its magnetic properties will cause overshoot on the leading edge as
each pulse is applied. The size of the overshoot depends on both the transformer
and load inductance.
The IGBTs internal flywheel diode will be forward biased once the overshoot exceeds the DC Busbar voltage by about 1V and, once it conducts, will pass the
excess energy due to the overshoot back into the DC busbar smoothing capacitors.
Since the diode has a fixed turn-on time, the surge voltage is suppressed by the
snubber network until the diode becomes forward biased.
5-23
Device ratings
Voltage rating
From a design point of view, the maximum voltage applied to the device comprises four elements:
(Input volts(dc) x 2 ) + regen volts + surge volts + safety margin
From this it is desirable that the inverter input bus voltage should account for
about 50% - 60% of the IGBT rated voltage. The internal flywheel diode has the
same voltage rating as the IGBT.
Current rating
For safe operation the IGBT peak current must not exceed the device rating. In
general, the short-circuit rating of the inverter is set to 150%. Therefore, assuming
maximum current flows in such an overload event the desired steady-state current
should be approximately 50% - 60% of the maximum device rating.
(kVA) Overload rate
--------------------------------------------------------------------------- 2 1.2
The general formula is: I peak = Inverter
AC Volts (rms) 3
Example: Select devices for 60kVA, 380V unit with 150% overload capacity:
60, 000 1.5
Current = ------------------------------- ( 2 1.2 ) = 232 Amps
380 3
Voltage = 500 (max DC) 2 = 1000V
Note: The internal free-wheel diode is designed on the premise that a very short
current flows, so that steady state rating is regarded to be approximate half of that
of the main IGBT.
Junction temperature
5-24
1.4.4.3
Parallel devices
In larger inverter power blocks two IGBTs may be connected in parallel in each
arm of the inverter. Under such circumstances it is desirable that the current is
shared between the two parallel-operating devices to within 10% of each other
and it is necessary to match the devices such that their Vce(sat) values are within
0.3V of each other.
To this end each device is ranked according to its Vce(sat) measurement, as shown
in the table below.
Table 5-4: IGBT Rankings
Type
Vce(sat)
1.7 1.95
1.9 2.15
2.1 2.35
2.3 2.55
2.5 2.8
2.75 3.05
3.0 3.3
3.25 3.55
3.5 3.8
3.75 4.05
Note: IGBTs of different Vce(sat) values can be used in an inverter, but it is necessary to use ranked devices in any parallel arm, and preferably in the complete
power block. Across power blocks, the output transformer inductance slows
down any possible fault current. Further-more, the maximum current allowed is
derated by 15% of both IGBT ratings (e.g. 2 x 300A = 600A x 0.85 = 510Amps).
Other influences on parallel device operation are:
Inductance in the main circuit wiring
minimised by using low-inductance symmetrical wiring.
Driver wiring and differences in driver output impedance
minimised by using twisted-pair conductors of short lengths.
Equalisation of operating temperatures
temperature equalisation assisted by using equal device mounting and
torque values.
5-25
1.5
5-26
5-27
1.6
1.6.1
PWM
Waveform
20ms (50Hz)
The control mechanism compares a sinusoidal reference waveform with a triwave carrier and produces a PWM pattern which changes state each time the reference waveform crosses the carrier, as shown in Figure 5-25.
In the 7200 equipment the tri-wave carrier amplitude is fixed, and its frequency
is governed at 2.4kHz. The reference waveform mimics the UPS output voltage
and therefore has a 50/60Hz base frequency.
As the above illustration shows, when the reference waveform (VR) rises above
the tri-wave (Fc) the output PWM pattern switches high, and vice-versa. Each
PWM pulse-width is therefore directly proportional to the instantaneous mean
value of the sinewave reference and is presented to the power IGBTs. The inverter
output therefore replicates the reference sinewave, and changes in output voltage
amplitude and frequency are achieved by altering the appropriate parameter of the
basic reference voltage waveshape (VR).
Carrier ratio (P)
The ratio of the carrier waveform frequency to the reference waveform frequency
determines the number of PWM pulses present per output cycle. In the 7200 series
UPS this equates to 2400/50 = 48. Therefore the inverter output will comprise 24
pulses in each of its output positive and negative half cycles.
Note: although the carrier frequency is said to be fixed it will in fact vary slightly with the UPS base frequency as it tracks the bypass frequency as part of its synchronisation control process. This results in 48 PWM pulses per cycle at all times.
5-28
The smallest permissible pulse is a function of the IGBT propagation delay (See
section 5 paragraph 1.4.2) and determined on the Base Driver Board. The delay
is of the order of 4s.
1.6.2
The 3-phase inverter voltage is sensed at a point between the output transformer
and inverter-side static switch (contactor), and should therefore be at the nominal
UPS output voltage whenever the inverter is operating. The three independent
line-to-neutral sense signals are attenuated to 1% on the High Voltage Interface
Board and then passed to the Inverter Logic Board via the UPS Logic Board.
On the Inverter Logic Board the sense signals take the form of voltage feedback
inputs to the voltage regulation control loops.
On the UPS Logic Board, the sense voltage are converted to a digital form and
monitored by the boards microprocessor system.
5-29
filter
capacitors
DC Bus Pos
3 Phase
Power
Inverter
Inverter-side
Contactor
Critical Load
Inverter Section
Output
Tfrmr
DC Bus Neg
+ Inverter Base
Drive Bds.
High Voltage
Interface Board
1.6.2.2
Operator Control
Panel
The 3-phase inverter voltage is sensed at a point between the output transformer
and inverter-side static switch (contactor), and should therefore be at the nominal
UPS output voltage whenever the inverter is operating. The three independent
line-to-neutral sense signals are attenuated to 1% on the High Voltage Interface
Board and then passed to the Inverter Logic Board via the UPS Logic Board.
On the Inverter Logic Board the sense signals take the form of voltage feedback
inputs to the voltage regulation control loops.
On the UPS Logic Board, the sense voltage are converted to a digital form and
monitored by the boards microprocessor system.
Inverter current sense
The inverter output current is monitored by Hall effect current sensors mounted
on the inverter S and T phases. These sense signals are attenuated on the High
Voltage Interface Board (by link selectable burden resistors) and then passed to
the Inverter Logic Board via the UPS Logic Board.
5-30
The 3-phase bypass voltage is sensed at a point between the bypass isolator and
the bypass-side static switch, and should therefore be at the nominal mains voltage whenever the bypass switch is closed. The three independent line-to-neutral
sense signals are attenuated to 1% on the High Voltage Interface Board and then
passed to the UPS Logic Board.
On the UPS Logic Board, the bypass voltage sense signals are converted to a digital form and monitored by the boards microprocessor system.
1.6.2.3
Various digital signals are passed between the UPS Logic Board and all the other
boards connect to it. These can broadly be categorised as:
alarm data generated on the Inverter Logic Board and UPS Logic Board
which are passed to the Operator Control Panel via the Operator Logic
Board also to the Alarms Interface Board (for remote indication) where
fitted.
inverter stop/start control signal generated on the UPS Logic Board in
response to other system control parameters and applied to the Inverter
Logic Board as appropriate
control data entered at the Operator Control Panel which is stored by the
UPS Logic Board e.g. inverter voltage and frequency parameters.
external control options e.g. remote stop, emergency shutdown, sync
inhibit.
1.6.3
All three inverter voltage sense signals are applied to a full-wave rectifier on the
UPS Logic Board and the resulting signal is digitised and monitored by software
controlled undervoltage and overvoltage detection functions. These are once
again programmable from the Operator Control Panel and are normally set to
10%.
5-31
In the event of a voltage error occurrence the UPS Logic Board will:
send a STOP signal to the Inverter Logic Board to turn off the inverter.
transfer the load to the bypass supply through the static switch operation.
initiate the appropriate alarm indications on the Operator Control Panel.
1.6.4
As explained above, the closed-loop inverter voltage control circuit operation (on
the Inverter Logic Board) forces the inverter output to track the sinusoidal reference voltage. Therefore, the reference voltage must also determine the inverter
frequency in addition to voltage.
The reference voltage generator is a digital circuit which produces three synthesised sinusoidal 50Hz(60Hz) waveforms one per inverter phase (See paragraph
2.3.2). Its frequency is determined by a frequency reference signal produced by
the UPS Logic Boards microprocessor system which is normally synchronised
to the bypass supply and reverts to the base frequency (50/60Hz) when the
bypass supply is unavailable (See Figure 5-29) note: synchronisation is maintained during normal operation to allow a no-break load transfer to take place
between the inverter and bypass if necessary.
Although the actual reference voltage generator is situated on the Inverter Logic
Board, the previous paragraph shows that the UPS Logic Board microprocessor
provides the essential frequency control signals. The frequency control parameters are therefore entered into the UPS Logic Boards memory via the Operator
Control Panel. There include:
base frequency selection i.e. 50Hz or 60Hz.
bypass sync window (normally 2%) i.e. the frequency extremities to
which the inverter is allowed to operate whilst tracking the bypass supply.
tracking slew-rate (normally 0.10Hz/s) i.e. the maximum permissible
rate of change of inverter frequency whilst tracking the bypass supply.
Note that if the bypass frequency changes faster than the programmed
slew-rate then an out of sync error will be present during the periods of
non-synchronises operation.
External Sync Inhibit
Current protection
There are three forms of inverter current protection control:
Inverter current limit
the inverter output current sense signals are applied to a current limit circuit on the Inverter Logic Board which restrict the current on an individual
phase to approximately 150% of its nominal rating. If the phase current
reaches this level the phase voltage will be reduced to a level which sustains this limit i.e. if there is a short circuit on the critical bus then the
5-32
inverter PWM pattern will be reduced to a minimum and the inverter will
deliver 150% current at a very low voltage in an attempt to clear the short
(See paragraph 2.3.5).
IGBT overload protection
Desaturation detection circuits built into each Inverter Gate Driver Board
inform the Inverter Logic Board of an overload condition on any of the
inverter IGBT devices which will then cause its internal start/stop control
logic to shut down the inverter operation (and subsequently transfer the
load to bypass).
Output overload
When the inverter is on-load the output current is monitored by the UPS
Logic Board and a software-controlled timer function provides an inverse
load/time shutdown facility which trips the inverter off-load i.e. the
larger the overload the faster the trip action. The load profile is:
150% for 1 minute
125% for 10 minutes
110% for 1 hour
101% for 10 hours
1.6.6
1.6.7
5-33
5-34
Section 5:
2.1
Chapter overview
This chapter contains a circuit description of the Inverter Logic Board Part N
4530025-T, which is used across the whole 7200 Series UPS model range, and
should be read in conjunction with circuit diagram SE-4530025-T (5 pages).
This is a direct replacement for PCB Part N 4530024-S which may be fitted to
modules manufactured prior to February 1997. Although there are only minor
differences between the two PCBs a full description of the Inverter Logic Board
Part N 4530024-S can be found in Section 18 Chapter 3.
Signal annotations shown on the circuit diagrams are shown in italics in the following text e.g. [BLK-INV>.
2.2
2.2.1
General description
Circuit board functions
The Inverter Logic Board board is responsible for providing the drive signals for
the inverter IGBT transistors at the appropriate PWM (pulse width modulated)
pattern to produce the required inverter output voltage and frequency. In so
doing, the board monitors the following UPS parameters via the High Voltage Interface Board and UPS Logic Board:
2.2.2
Inverter overload
Inverter On/Off status
Control power supply failure
IGBT failure
Input/Output connections
The Inverter Logic Board has six connectors, described below:
5-35
I/O
1-4
I/O
5-8
I/O
9 - 12
I/O
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
[INV_F> from UPSLB micro (Inv Freq - used in ref w/form gen) 50Hz = 0 and 60Hz = 1
38
39
40
5-36
Function
2.2.3
Block Diagram
Figure 5-27 shows the Inverter Logic Board at its most basic functional block diagram level the basic function of each of the blocks shown is described below,
with a more detailed, component level description provided in the remainder of
the chapter.
Figure 5-27: Inverter Logic Board basic block diagram
Inverter I
sense (x3)
Inverter
Current
Sense
Current
Limit
Overload (x3)
Inverter Volts
F/B (x3)
(actual)
Volts
Error
Amplifier
AC Reference
voltages (x3)
Bypass Volts
F/B (x3)
Bypass Freq
Output Volts
Select
Bi-directional
Control
(UPSLB)
(UPSLB)
DC-DC Supply
Drive
Pulse
Generator
Inverter
IGBT
Drive
Pulses
AC Control
voltages (x3)
Parallel Current
share
(V Adj.)
PWM
Modulator
Frequency
Start/Stop
control line
Feed forward
PWM (x3)
Reference
Control
Voltage
Tri-wave (x1)
Generator
Start/
Stop
Logic
Power
Supply
Fault
Detection
Logic
12V
5V
This block compares the AC reference signals with voltage feedback signals derived from the inverter output, and produces error signals proportional to any
detected amplitude difference. Three individual error amplifiers are contained in
this block, one for each phase, which means that each inverter phase is individually controlled. Note that the outputs from this block are annotated AC control
signals, as it is these signals that ultimately determine the adopted PWM pattern
which in turn directly determines the inverter output three phase voltage.
5-37
AC signals proportional to the inverter output current are processed by the inverter current sense circuit and fed to the current limit block where they apply
a current limit function to the drive pulse generator circuit if the current reaches
150%. Three independent circuits are contained in this block, one per phase, so
each output phase is individually controlled.
Modulator
This circuit modulates the AC control signals with a 2.4kHz tri-wave signal, produced by the reference volts generator, and generates three PWM waveforms.
Once again three independent circuits are used, one per phase.
Drive pulse generator
The drive pulse generator converts the PWM signals into suitable IGBT base
drive signals. This block contains interlocking logic to prevent the simultaneous
triggering of both IGBTs in an inverter phase, a high frequency modulator, overload protection and general start/stop control of the output drive waveforms.
Start/stop logic and Fault detection
Numerous fault detection circuits are contained on the board. These control the
internal start/stop control lines to the reference volts generator and drive pulse
generator, and also provide status signalling to the UPS Logic Board micro for
use by the system control logic. Signals from the UPS Logic Board to this (Inverter Logic) board also effect start/stop control in accordance with the systems
control logic demands.
Power supply
The Inverter Logic Board is powered from the DC-DC Power Supply Board,
which is live whenever the power rectifier is operational or the batteries are connected to the busbar via the battery circuit breaker.
This power source provides 12V d.c. power rails which are then diode blocked
to the second supply source (from the AC-DC Power Supply board) the UPS
Logic Board hence the board will be powered only from the DC-DC Power
Supply but once the mains fails (i.e. the AC-DC Power Supply is off) the DC-DC
Power Supply will keep all the circuit boards energised.
On-board 5V regulators, fed from the 12V rails, provide stabilised 5V power
rails for those devices that require it.
5-38
2.3
2.3.1
2.3.2
[INV_A>
[INV_B>
Set
Volts
V-peak
[BLK>
Stepped
waveform
Resistor
Ladder
[INV_F>
[S_TRI>
Staircase
Pattern
Generator
Multiplexer
Filter
Multiplexer
Filter
AC Reference
Voltage
[REF_A>
[REF_B>
Disp. adj
(R247)
[O_BACK>
[O_SYNC>
Phase
Locked
Loop
C Phase
Reference
Generator
Tri wave
Generator
[REF_C>
[TRI>
Freq-reference
5-39
This circuit is responsible for producing three sinusoidal voltages, spaced at 120
with respect to each other, which are then connected to the volts error amplifier
in the form of AC reference voltages. The voltages produced by this circuit can
thus be considered as voltage demand signals, and represent the amplitude, frequency and wave-shape desired at the inverter output voltage.
Multiplexer operation
Voltage control. As the voltages at each stage of the stepped waveforms equal
the voltages present along the resistor chain, the stepped waveform peak voltage
is determined by the voltage at the top of the chain i.e. the voltage at buffer N2c
pin 8. This is controlled by the circuit block annotated set volts in Figure 5-28
and described in detail below.
As described above, the set volts circuit (See Figure 5-28) provides a controlled
voltage at the top of the resistor ladder which thereby determines the peak value
of the AC reference voltages and thus also the inverter output voltage.
It is possible to select one of three output working voltages: 380V, 400V and
415V. This is achieved by two signals from the UPS Logic Board annotated
[INV_A> and [INV_B> which are connected to the data-select inputs of D7, which is
a dual 4-channel multiplexer. The inputs to the X channel (1X to 4X) of D7
are connected to regulated DC voltages which represent the various UPS working
voltages. These are selected by the [INV_A> and [INV_B> to appear at the X
output as follows:
Table 5-2: Working voltage selection (D7)
5-40
[INV_A>
[INV_B>
Channel
Volts
X1
380V
X2
400V
X3
415V
X4
Manual Set
Note: The inputs to the set volts circuit from X4 pins 25/26 and amplifier N3a
are not used, and play no part in the stop/start function.
Staircase pattern generator
The staircase pattern generator is based on D1, which contains a complex series
of synchronous logic gates and timers and produces two sets of signals which are
connected to the multiplexer data-select inputs e.g. output A1-C1 are connected
to multiplexer D4 and outputs A2-C2 to multiplexer D3. The sequence of these
outputs, which is determined solely by D1s internal logic, produce stepped signals at the multiplexer outputs which resemble a full-wave rectified waveform.
Two frequency-related signals are applied to D1. An input to D1 pin 44, annotated [INV-F>, controls one of D1s internal dividers and sets the inverter nominal
base frequency. This signal, which is logic high for 60Hz operation and low for
50Hz, is produced on the UPS Logic Board in response to inputs from the Operator Control Panel. The input to D1 pin 43 is a 288kHz clock signal, produced by
a phase-locked-loop (PLL) circuit, which controls D1s internal operation.
Note: The PLL determines the inverter free running frequency and is normally
synchronised to the bypass supply (See Figure 5-29).
5-41
In addition to the multiplexer data-select signals described above there are several
other frequency-related outputs from D1.
The outputs from pins 31 (D2) and 36 (D1) are square-waves at the nominal base frequency which determine the zero-crossover points of the
inverter output and S phases respectively. These are connected to the filter
section described later (see page 5-44).
The output from pin 40 is a 2.4kHz square-wave which is converted to a
tri-wave by the tri-wave generator, described below, for further use by the
PWM Modulator (See paragraph 2.3.4). The frequency of this signal is
determined by the logic levels at pin 1 (S2) and pin 2 (S3), as selected by
X-15 links 1 and 2 detailed on sheet 1 of the circuit diagram.
Table 5-3:
X15(0-1) S2
X15(0-2) S3
Frequency
Usage
Open (0)
Open (0)
1.2kHz
N/A
Closed (1)
Open (0)
2.4kHz
All models
Open (0)
Closed (1)
4.8kHz
N/A
Closed (1)
Closed (1)
9.6kHz
N/A
5-42
62
15
D53
F-IN
18
F-INM
X4
X3
63
16
BACK
BACKM
15
INV-F
34
37
37
[O_BACK>
INV-F
44
50 /60 Hz
(Selected from
Operator Panel)
DATA
BUS
D1
Frequency
Divider
27
Staircase
Generator
D59 14
X34
1
Phase
Locked
Loop
2
15
64
SYNCM
Pulses proportional to
phase error between
Inverter & Bypass mains
SYNC
35
Master Freq
reference for
Inverter Osc
35
D10
13
14
12
9
VCO
Phase
Comparator
13
F Correction
2-3 = Single
1-2 = Parallel
288kHz
(nominal)
4
50/60Hz
R247
phase
align
43
CLK
MICROCONTROLLER
(PORT 2)
D17
34
D6 3
[I_SYNC>
Phase
error signal
A PLL (D6) provides the clock signal for the staircase pattern generator and
thereby has direct control over the inverter output frequency. This is a standard
type 4046 i.c. which contains two types of phase comparators (only one of which
is used) and a voltage controlled oscillator (VCO) centred at 288kHz.
One of the phase comparators inputs (D6 pin 14) is driven by a square-wave frequency reference signal, annotated [SYNC>, which is produced by the UPS Logic
Board microprocessor system. That is, this signal relates to the error between the
inverter and bypass frequency, as calculated by the microprocessor, which then
adds a percentage gain correction under its slew rate program. The signal is then
presented to the PLL phase comparator e.g. if there is an instant change to the
bypass frequency from 50Hz to 51Hz, the microprocessor detects an error of 1Hz.
This error is then divided by the slew rate e.g 0.1Hz/Sec, and the [SYNC> signal
is modified from 50Hz to 51Hz in increments of 0.1 over a 10 second period.
The other phase comparator input, to D6 pin 3) is driven by a 50/60Hz output
from the staircase pattern generator (D1 pin 26) which is described above. If the
comparators input signals are out of phase the phase comparator output (D6 pin
13) will either add or subtract voltage to C2 (depending on the phase relationship)
and apply an error correction signal to the VCOs control input (D6 pin 9) i.e.
the VCO frequency is effectively made to track the frequency reference signal.
5-43
For example if the bypass frequency rises slightly, the following actions will
take place:
1. The sync control function on the UPS Logic Board will increase the [SYNC>
signal frequency by an appropriate amount, determined by the microprocessor under the control of the slew rate programme.
2. When the PLL compares the [SYNC> signal with the base frequency signal
from the staircase pattern generator it will detect that the [SYNC> signal is of
a slightly higher frequency and the output from D6 pin 13 will exhibit logic
high pulses equal to the periods of phase difference.
3. The pulses at D6 pin 13 are filtered and applied to the VCO control input at
D6 pin 9 in the form of a dc correction voltage and will cause an increase in
the VCO output at pin 4.
Note: 2.5 volts at D6 pin 9 equates to a centre frequency of 288kHz, as set by
C1, R33 and R34. An increase in voltage at pin 9 will cause the RC charge
rate to increase, with as subsequent increase in VCO frequency. A decease in
the voltage at pin 9 will cause the VCO frequency to reduce.
4. This increases the staircase pattern generator clock rate which then
increases the inverter frequency along with the base frequency signal produced at D1 pin 27.
5. When the base frequency signal at D1 pin 27 has risen to match that of the
[SYNC> signal, the phase comparator within the PLL ceases to detect any
phase error and the correction voltage at pin 13 will stop changing. The VCO
control voltage will thus remain constant and the inverter will be maintained
at its current frequency and in sync with the bypass supply.
Filter & C-phase reference generator
The filter sections convert the full-wave rectified stepped waveforms produced
by the multiplexers into sinusoidal AC reference signals suitable for connecting
to the volts error amplifier (See Figure 5-27).
Two filter sections are used; one processes the A-phase AC reference signal and
the other for the B-phase.
Considering the A-phase circuit: the stepped waveform produced by the A-phase
multiplexer (D4) is buffered by N1a and connected to D5 pin 13. This signal is
also inverted by N1d and connected to D5 pin 12. D5 is an electronic switch controlled by the output from D1 pin 36 which was previously described as a
squarewave signal at the nominal base frequency, coinciding with the A-phase
zero crossing points. If D5 is switched by this signal then the signal at its output
pin 14 will be a stepped sine-wave comprising both halves of the signals present
at its pins 12 and 13. This stepped waveform is then filtered by N2a which produces a smooth sinusoidal AC reference voltage [REF_A> and can be monitored at
test point X8-1 as an 8V peak-to-peak sinewave.
The B-phase circuit operates in an identical manner but displaced by 120 i.e.
[REF_B> lags [REF_A> by 120.
The C-phase signal, [REF_C>, is produced by N2d which differentially sums the
other two phases with 0V. Theoretically, in a three phase system the instantaneous sum of all three voltages equals zero: therefore by subtracting the A and B
phase signals from 0V the output from N2 pin 14 is equivalent to the C-phase AC
reference signal, [REF_C> i.e. A + B + C = 0 C = -(A + B).
5-44
Tri-wave generator
[REF_X>
[VI_X>
AC Reference volts
D8
Volts
Error
Amplifier
Current
Feed/fwd
[IINV_X>
AC Control volts
[TRI>
Tri-wave
PWM waveform
to output driver
PWM
Modulator
[MOD_X>
Note: As an almost identical circuit is used for each phase the following description refers to the A phase only, with any differences between this and the B
and C phase highlighted.
The purpose of the volts error amplifier is to compare the inverter output voltage feedback signal with the AC reference voltage created by the reference volts
generator (See paragraph 2.3.2) and provide an appropriate AC control signal to
the PWM modulator i.e. if the volts error amplifier detects an error between
the inverter output voltage feedback signal and the AC reference voltage it modifies the AC control voltage to change the PWM pattern in such a way as to restore
a balanced condition; therefore effectively making the inverter voltage closely
track the AC reference voltage.
Inverter voltage feedback signal
The inverter A-phase output feedback voltage is sensed at the output side of the
output transformer (i.e. at nominal system output volts), attenuated to approximately 1% on the High Voltage Interface Board and connected to the Inverter
Logic Board at X4-18. The signal ([VINV_A>) is amplified slightly as it passes
5-45
through N5a to N5b, which acts as the error amplifier, and can be measured at
test point X9-8 as an ac voltage in the range 4.5V to 5.0V (about 14Vp-p) depending on the system working voltage. Calibration resistor R246 allows for
individual A-N line voltage adjustment.
Note: Calibration resistors are also included in the B phase and C phase feedback inverter volts feedback signal paths which enables those two phases to be
individually balanced to the A phase during board set-up. R224 adjusts the B
phase and R245 the C phase.
AC Reference voltage signal
The A-phase AC reference signal is connected to the error amplifier (N5b) via an
electronic switch comprising part of multiplexer D8. This switch is controlled by
a signal annotated [RIF> which is normally low, leaving the switch in the position shown on the circuit diagram. When [RIF> goes high the switch changes over
and replaces the AC reference voltage input into the error amplifier (N5b) with a
signal derived from the R-phase bypass voltage [VI_A> connected to X4-14 which
makes the inverter voltage track the voltage on the bypass supply line.
Bypass voltage sense signal
[VI_A>
When the inverter is first started, [RIF> goes high and energises D8 which then
connects the bypass voltage sense signal [VI_A> to the volts error amplifier reference input thereby replacing the AC reference voltage as the voltage demand
signal. The inverter voltage will thus rise to equal the bypass voltage. Once the inverter voltage has stabilised at the bypass level the output contactor will close
to put the inverter on-load. At this point [RIF> reverts to a logic low and D8 deenergises to select the AC reference voltage as the voltage demand signal. This is
done to prevent arcing across the inverter output contactor when it closes and
therefore increases its operating life and reliability.
Volts error amplifier
N5b sums the AC reference voltage and the inverter voltage feedback signal and
its output takes the form of a sinusoidal voltage representing the reference signal
superimposed with a signal representing any detected error. This is then filtered
by N5c and connected to N5d where it is processed in conjunction with an Aphase current-derived signal.
Note: A third input to N5b from N9a is used only when the module is operating
as part of a multi-module parallel system and provides a means for implementing
load sharing control. In a single module installation this circuit is not used and
the inputs to X4 pins 27-30 are left open circuit.
Current feed-forward
N5d sums the volts error amplifier output from N5c with a signal proportional to
the output current, annotated [IMN_A>. This is a feed-forward signal which calls
for an increased inverter voltage as the current increases and improves the overall
inverter voltage regulation characteristics. The output from N5d is connected to
the PWM modulator in the form of the AC control voltage, as depicted in Figure
5-27, where it directly controls the generated PWM pattern.
5-46
All three AC control signals are summed by N9d and its output is connected back
to the feed-forward amplifier in all three phases. As, in a three phase system, the
sum of all three phase voltage should equate to 0V, this provides a virtual neutral
reference point for all three amplifiers which prevents the AC control signals
drifting with respect to each other and also ensures that no harmful dc voltages
are generated in the output transformer windings.
Note: In a module fitted with a double-ended (12-pulse) inverter (optional configuration generally reserved for larger modules) the AC control voltage is
connected to the Auxiliary Inverter Logic Board via X6-9 and buffer N10a. In a
standard module connector X6 is not used.
2.3.4
PWM Modulator
The A-phase PWM pattern is generated by N11, which is configured as a differential comparator whose inverting input is driven by the variable (sinusoidal) AC
control voltage and non-inverting input by a fixed frequency (2.4kHz), fixed voltage (2V) tri-wave signal generated by the reference voltage generator.
N11 generates the PWM pattern by detecting when the fixed tri-wave voltage is
cut by the AC control voltage as illustrated below.
Figure 5-31: PWM Pattern production
N11
Tri-wave (fixed)
PWM pattern
AC control voltage
(variable)
Tri-wave (fixed)
AC control signal
(low)
3
PWM pattern
1
AC control signal
(high)
Tri-wave (fixed)
1
PWM pattern
3
The upper waveform diagram depicts the condition where the AC control voltage
is low with respect to the tri-wave (equal to about 25% of the tri-wave peak voltage) and illustrates that this results in a PWM pattern with a mark-to-space (m:s)
5-47
ratio of approximately 3:1. The lower diagrams shows the situation when the AC
control signal is increased to about 75% of the tri-wave peak voltage and illustrates the output m:s now equals 1:3. This shows that the m:s ratio of the output
waveform can be varied by varying the AC control signal; and if this signal is
varied in a sinusoidal manner then the output waveform will represent a sinusoidally modulated PWM pattern.
This pattern is processed by the drive pulse generator and applied to the inverter
IGBT transistors such that for each individual inverter phase the high IGBT is
turned on when the PWM signal is high and vice versa.
Note: if a 12-pulse inverter is fitted (option on larger modules only) the three AC
control signals and tri-wave signal [TRI> are connected to the Auxiliary Inverter
Logic Board via the four sections of N10 (buffers) and connections X6 pins 9 to
12 i.e. the Auxiliary board contains its own PWM modulator and drive pulse
generator stages.
2.3.5
The inverter current is sensed by Hall-effect CTs fitted between the inverter and
output transformer. In modules above 200 kVA a CT is fitted to each phase but
only two CTs are used in modules at or below this rating, fitted to the S and T
phases only. In the latter case the phase current is calculated from the other two
(monitored) phases.
The CTs sense signals are calibrated by jumpers on the High Voltage Interface
Board which determines the overall burden resistance (See section 7 paragraph
2.3.24) and then connected to X4 pins 21 to 23 on the Inverter Logic Board via
the UPS Logic Board.
In the lower-rated modules, where only two CTs are fitted, the A-phase current is
calculated by N15a which sums the B and C phase current sense signal (via jumpers X16-1 and X16-2) with 0V. As in a three-phase circuit the instantaneous sum
of all three currents equals zero then the output from N15a pin 1 represents the Aphase current i.e. A + B + C = 0 C = -(A + B). In installations using three
CTs, X16 jumpers 1 and 2 should be open and jumper 3 must be made. This
connects the A-phase signal directly to N15a in the same manner employed by
the other two phases.
As all three phases are identical in operation the following description refers to
the A-phase only.
N15 effectively buffers the current sense signal and the output on N15a pin 1 (test
point X10-1 shows approximately 0.2Vp-p signal when the inverter is on no-load)
is in-phase with the output phase current. From N15a this signal is inverted and
amplified by N15b whose output [IMN-A> is connected to the current feed-forward circuit in the AC control voltage line described earlier.
Current limit
The output from N15a is also rectified by N15c/N15d (zero gain) whose output
pin 14 provides a positive full-wave rectified signal representing the inverter Aphase current which is then applied to a comparator circuit comprising N18. The
comparators operating threshold is set by R248 which is connected across a 4.7V
zener regulator and adjusted to present +0.6Vdc at N18 non-inverting input
5-48
available at test point X10-4. This represents 150% of the rated inverter load current, and if the current sense signal to N18 inverting input exceeds this level then
the output from N18 pin 7 ([BLK_A>) will switch to a logic low level and apply an
inhibiting input to the drive pulse generator (described below) which prevents it
from turning on the A-phase inverter transistors. This effectively limits the inverter peak current to the set 150% threshold.
Note that the inverter is not shut down during the above event; but the current
limit action will take place during each pulse of the 2.4kHz PWM drive signal
i.e. sub-cycle operation. This effectively reduces the PWM pattern and therefore
the inverter output voltage will fall to the level necessary to restrict the current to
its 150% level. Taken to its extreme, if there is a short-circuit on the critical bus
then the inverter PWM pulses will be reduced to a minimum and the inverter will
deliver full (150%) current at very low voltage in an attempt to clear the short.
2.3.6
Those gates within D11 concerned with the drive pulse generator function comprise three independent channels controlled by the PWM modulated signals
[MOD_A>, [MOD_B>, [MOD_C>, in conjunction with [STRI>.
Taking the A-phase circuit as an example; the drive control inputs to D11 are
[MOD_A> and [STRI> and the outputs from D11 are taken from pin 36 (drive to the
A-phase inverter low IGBT [PAL>) and 37 (high IGBT [PAH>).
[PAL> switches high, turning on the low IGBT via V42, when [MOD_A> is low
and [STRI> goes low. This condition is latched until [MOD_A> is high and [STRI>
goes high, whereupon [PAL> returns low, turning off the low IGBT, and [PAH>
5-49
2.3.7
The inverter current limit circuit is shown on the diagram sheet 4 and described
in detail in paragraph 2.3.5. This circuit provides three inputs to D11 annotated
[BLK_A>, [BLK_B> and [BLK_C> which go low if an overload is detected on the associated phase. In the event of a phase current rising to the current limit level the
following occurs within D11:
1. The drive signals to the affected phase(s) are inhibited, as described above.
2. A summary current limit signal (logic low) is produced at D11 pin 21 if any
one of the three phase currents reach the current limit level. This is inverted to
a high by D10b and connected to the UPS Logic Board via X4-32 as an
inverter overload status alarm signal [OVL_INV>, where it is used for display
purposes only (code 33). From D10b pin 10 the signal is also passed back
through D11 pins 20 to 19 and illuminates H14 to provide an on-board indication that the inverter overload circuit is activate. Note that the signal to D10b
is slugged by V23/R300/R237/C141 on removal of the overload to allow the
inverter conditions time to stabilise before the overload status is reset.
3. The [BLK_A>, [BLK_B> and [BLK_C> signals are buffered within D11 and output at pins 31, 32 and 33 respectively. These are passed to the Auxiliary
Inverter Logic Board in a 12-pulse inverter installation via connector X6 pins
13, 14 and 15 (used in large module only).
Inverter Vce(sat) (from desaturation detector on driver interface boards)
A circuit on the Inverter Driver Board (See paragraph 4.3.4) detects an inverter
IGBT fault (short or open circuit) by sensing when the particular device is desaturated during its ON period. These boards thus provide six fault signals back to
the Inverter Logic Board via pins 3/4 and 13/14 of connectors X1 (A-phase) X2
(B-phase) and X3 (C-phase) respectively. The fault signal applied to these inputs
take the form of a logic low on fault, but this is inverted to a high by a section of
D9 and diode-coupled to a single input at D11 pin 8 [DIS> which is therefore high
if a desaturation condition is detected on any inverter IGBT and drives the Start/
stop logic within D11 to its stop mode (see below).
Note: the Vce(sat) signals produced by the various sections of D9 illuminate
LEDs H5 to H10 to positively identify the location of the faulty IGBT transistor.
Ribbon cable discontinuity
A system of verifying that the ribbon cables connecting the Inverter Logic Board
to the three Inverter Driver Interface Boards is implemented by the connections
to X1 to X3 pins 5/8. Pins 5 and 8 of the respective connectors are linked together
on the Inverter Driver Interface Boards and so present a short-circuit which pulls
5-50
D11 pin 9 ([COI>) low if the cables are all correctly in place. However, if one of
the cables are disconnected while the inverter is operating [COI> will rise to a
logic high and drive the Start/stop logic within D11 to its stop mode (see below).
Note: this signal is buffered within D11 and produces a logic high output at D11
pin 18 which illuminates H13 if a fault occurs.
X12 provides a means of overriding this circuit for test purpose only when it is
made 0-2 this jumper should always be OPEN during normal operation.
Inverter stack thermostat overtemperature
A facility exists in which thermostats fitted to the power inverter heatsinks can
provide an overtemperature status signal to the UPS Logic Board. The thermostats provide a normally-closed circuit between X1-5 and X3-8 and produce a
logic low signal at X4-40, which is connected to the UPS Logic Board. If any
thermostat opens (at a temperature above 90C) then this chain is broken and X440 is pulled high via R100 and V24.
Where this option is not used (standard), a jumper should be fitted to X12 position 0-1 to override the overtemperature fault signal which would otherwise
appear. Reposition this jumper to OPEN when the option is used.
2.3.8
Start/stop logic
This circuit is based on a multi-input logic gate within D11 which monitors the
fault detection logic circuits described above, together with several control
inputs from the UPS Logic Board, and either enables or disables the drive pulse
generator outputs (also within D11) in response to the input signals status.
Start/stop logic circuit outputs
Three start/stop status outputs are also produced by D11, as described below:
D11 pin 7 goes high on stop and is the source of the [BLK> signal to the
reference voltage generator circuit. When the stop/start logic is in its
stop mode this signal reduces the reference voltage generator output to
zero and thus demands zero output voltage.
D11 pin 28 goes high on stop and sends a status signal to the UPS Logic
Board via X4 pin 33 to request the micro to disable the inverter run signal.
D11 pin 34 goes high on stop and sends a status signal to the Auxiliary
Inverter Logic Board (12-pulse inverter only); thus ensuring that where
this option is used both the main and auxiliary boards are stopped and
started by a common control signal.
Start/stop logic circuit inputs
The start/stop logic within D11 is driven by the following D11 inputs:
1. Inverter Vce(sat) error (detected by desaturation detector on Inverter Driver
Interface Boards) logic high to D11 pin 8 forces the stop mode (See paragraph 2.3.7).
2. Connector discontinuity (led H13 illuminated) logic high to D11 pin 9
forces the stop mode (See paragraph 2.3.7).
3. A system start/stop control input to D11 pin 13 from the UPS Logic Board,
via X4-36, which is low on stop and high on start, provides the means of
allowing the UPS Logic Board to shut down the inverter in response to certain system events e.g. DC overvoltage, low battery, OFF selected from the
Operator Panel, emergency shutdown, etc. This input also drives led H12 via
5-51
D11 pin 17 (inverts the signal at pin 13) and illuminates the led when the signal is demanding the inverter to be turned OFF.
4. If a 12-pulse inverter is installed (option) the output from the start/stop circuit on the Auxiliary Inverter Logic Board is connected to D11 pin 14 via
X6-18 and is logic high on stop. This ensures that both main and auxiliary
Inverter Logic Boards react to a common Start/stop line (see also the output
from D11 pin 34 described above).
5. A power supply monitor circuit based on N22 applies a logic high input to
D11 pin 16, placing the stop/start circuit in its stop mode if the 12V supply
rail falls below 10Vdc. This circuit also holds off the inverter operation when
the UPS is first powered up until the 12V rail rises above this level to allow
the power supply time to stabilise before initiating the PWM drive signals.
Led H11 illuminates when this circuit is demanding a stopped condition.
6. The transfer to inverter command [INV_L> generated on the UPS Logic Board
is connected to D11 pin 12. This is clocked through D11 to enable the [RIF>
signal. This re-references the inverter voltage to the bypass voltage just
before the inverter is about to take over the load, which prevents any voltage
drop appearing across the output contactor when it is instructed to close (See
paragraph 2.3.3).
The inverter voltage is referenced to the bypass voltage level for approximately 220ms before is it switches back to its normal reverence voltage: this
more than adequately covers the output contactor closure time, which is
approximately 50ms. Note that this function is disabled by the mains fail
signal [MNS_KO> to D11 pin 11 in the event of a mains failure; thus if the load
is transferred to the inverter when there is no bypass to the UPS, then the
inverter will remain referenced to its normal reference voltage at all times.
2.3.9
Power supply
(circuit diagram sheet 5)
This board receives its control power supply from the DC-DC Power supply
Board only, via connector X5. Pins 3, 4 and 5 carry regulated +12V, 0V and -12V
power rails which form the Inverter Logic Boards main supply inputs; and pins
1 and 2 carry an isolated 36Vac supply which is used by the Inverter Driver Interface Boards and connected via connectors X1, X2 and X3, as shown.
A 5V regulator, N21, provides a regulated +5V rail from the +12 supply.
The 12V rails are diode-coupled to the 12V rails on the UPS Logic Board via
V14 and V15, as shown on sheet 5 of the diagram. Thus in the event of mains failure (i.e. the AC-DC Power Supply is inactive) the DC-DC Supply will maintain
the control power to all the electronic circuit boards.
5-52
2.4
Summary Information
Table 5-4: Inverter Logic Board configuration jumpers
Link
Position
Jumper
open
Function
Enable thermostat detector (Standard)
0-1
closed
open
0-2
closed
closed
Voltage select
override
0-3
X12
0-4
Manual inv
adj R243
0-5
0-6
0-7
0-8
X15
0-5
1200Hz
0-1
2400 Hz (Standard)
0-2
4800Hz
0-1
0-2
9600Hz
0-1
0-2
0-3
PWM modulating
frequency selection
X16
Function
R241
R242
R243
R244
R245
R246
R247
R248
5-53
Colour
Function
H1
Green
380V operation
H2
Green
400V operation
H3
Green
415V operation
H4
Amber
H5 to H10
Red
H11
Red
H12
Red
H13
Red
H14
Red
Clock-
Inverter ref. A
(8Vp-p)
X8 - 2
Inverter ref. B
(8Vp-p)
X8 - 3
Inverter ref. C
(8Vp-p)
X8 - 4
Inverter DC ref.
X8 - 5
X8 - 6
Test Point X9
X9 - 8
Inverter feedback A
X9 - 7
Inverter feedback B
X9 - 6
Inverter feedback C
X9 - 5
Bypass A
8V p-p
X9 - 4
Bypass B
8V p-p
X9 - 3
Bypass C
8V p-p
X9 - 2
X9 - 1
Not Used
X10 - 2
X10 - 3
X10 - 4
5-54
Section 18:
3.1
Chapter overview
This chapter contains a circuit description of the Inverter Logic Board 4530024S,
which was used across the whole 7200 Series UPS model range prior to February
97 when it was superceeded by 4530025T see chapter 2. This chapter should
be read in conjunction with circuit diagram SE-4530024-S (5 pages).
Signal annotations shown on the circuit diagrams are shown in italics in the following text e.g. [BLK-INV>.
3.2
3.2.1
General description
Circuit board functions
The Inverter Logic Board board is responsible for providing the drive signals for
the inverter IGBT transistors at the appropriate PWM (pulse width modulated)
pattern to produce the required inverter output voltage and frequency. In so
doing, the board monitors the following UPS parameters via the High Voltage Interface Board and UPS Logic Board:
3.2.2
Inverter overload
Inverter On/Off status
Control power supply failure
IGBT failure
Input/Output connections
The Inverter Logic Board has six connectors, described below:
18-241
I/O
1-4
I/O
5-8
I/O
9 - 12
I/O
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
[INV_F> from UPSLB micro (Inv Freq - used in ref w/form gen) 50Hz = 0 and 60Hz = 1
38
39
40
18-242
Function
3.2.3
Block Diagram
Figure 18-32 shows the Inverter Logic Board at its most basic functional block
diagram level the basic function of each of the blocks shown is described
below, with a more detailed, component level description provided in the remainder of the chapter.
Figure 18-32: Inverter Logic Board basic block diagram
Inverter I
sense (x3)
Inverter
Current
Sense
Current
Limit
Overload (x3)
Volts
Error
Amplifier
AC Reference
voltages (x3)
Bypass Volts
F/B (x3)
Bypass Freq
Output Volts
Select
Bi-directional
Control
(UPSLB)
(UPSLB)
DC-DC Supply
Drive
Pulse
Generator
Inverter
IGBT
Drive
Pulses
AC Control
voltages (x3)
Inverter Volts
F/B (x3)
(actual)
PWM
Modulator
Frequency
Start/Stop
control line
Feed forward
PWM (x3)
Reference
Control
Voltage
Tri-wave (x1)
Generator
Start/
Stop
Logic
Power
Supply
Fault
Detection
Logic
12V
5V
This block compares the AC reference signals with voltage feedback signals derived from the inverter output, and produces error signals proportional to any
detected amplitude difference. Three individual error amplifiers are contained in
this block, one for each phase, which means that each inverter phase is individually controlled. Note that the outputs from this block are annotated AC control
signals, as it is these signals that ultimately determine the adopted PWM pattern
which in turn directly determines the inverter output three phase voltage.
18-243
Current limit
AC signals proportional to the inverter output current are processed by the inverter current sense circuit and fed to the current limit block where they apply
a current limit function to the drive pulse generator circuit if the current reaches
150%. Three independent circuits are contained in this block, one per phase, so
each output phase is individually controlled.
Modulator
This circuit modulates the AC control signals with a 2.4kHz tri-wave signal, produced by the reference volts generator, and generates three PWM waveforms.
Once again three independent circuits are used, one per phase.
Drive pulse generator
The drive pulse generator converts the PWM signals into suitable IGBT base
drive signals. This block contains interlocking logic to prevent the simultaneous
triggering of both IGBTs in an inverter phase, a high frequency modulator, overload protection and general start/stop control of the output drive waveforms.
Start/stop logic and Fault detection
Numerous fault detection circuits are contained on the board. These control the
internal start/stop control lines to the reference volts generator and drive pulse
generator, and also provide status signalling to the UPS Logic Board micro for
use by the system control logic. Signals from the UPS Logic Board to this (Inverter Logic) board also effect start/stop control in accordance with the systems
control logic demands.
Power supply
The Inverter Logic Board is powered from the DC-DC Power Supply Board,
which is live whenever the power rectifier is operational or the batteries are connected to the busbar via the battery circuit breaker.
This power source provides 12V d.c. power rails which are then diode blocked
to the second supply source (from the AC-DC Power Supply board) the UPS
Logic Board hence the board will be powered only from the DC-DC Power
Supply but once the mains fails (i.e. the AC-DC Power Supply is off) the DC-DC
Power Supply will keep all the circuit boards energised.
On-board 5V regulators, fed from the 12V rails, provide stabilised 5V power
rails for those devices that require it.
18-244
3.3
3.3.1
3.3.2
[INV_A>
[INV_B>
Set
Volts
V-peak
[BLK>
Stepped
waveform
Resistor
Ladder
[INV_F>
[S_TRI>
[FRFB>
Staircase
Pattern
Generator
[ISYNC>
Freq-reference
Phase
Locked
Loop
Multiplexer
Filter
Multiplexer
Filter
C Phase
Reference
Generator
Tri wave
Generator
AC Reference
Voltage
[REF_A>
[REF_B>
[REF_C>
[TRI>
18-245
This circuit is responsible for producing three sinusoidal voltages, spaced at 120
with respect to each other, which are then connected to the volts error amplifier
in the form of AC reference voltages. The voltages produced by this circuit can
thus be considered as voltage demand signals, and represent the amplitude, frequency and wave-shape desired at the inverter output voltage.
Multiplexer operation
Voltage control. As the voltages at each stage of the stepped waveforms equal
the voltages present along the resistor chain, the stepped waveform peak voltage
is determined by the voltage at the top of the chain i.e. the voltage at buffer N2c
pin 8. This is controlled by the circuit block annotated set volts in Figure 18-33
and described in detail below.
As described above, the set volts circuit (See Figure 18-33) provides a controlled voltage at the top of the resistor ladder which thereby determines the peak
value of the AC reference voltages and thus also the inverter output voltage.
It is possible to select one of three output working voltages: 380V, 400V and
415V. This is achieved by two signals from the UPS Logic Board annotated
[INV_A> and [INV_B> which are connected to the data-select inputs of D7, which is
a dual 4-channel multiplexer. The inputs to the X channel (1X to 4X) of D7
are connected to regulated DC voltages which represent the various UPS working
voltages. These are selected by the [INV_A> and [INV_B> to appear at connected to
the X output as follows:
Table 18-9: Working voltage selection (D7)
18-246
[INV_A>
[INV_B>
Channel
Volts
X1
380V
X2
400V
X3
415V
X4
Manual Set
Note: the inputs to the set volts circuit from X4 pins 25 / 26 and amplifier N3a
are used in a multi-module parallel-operating system only and play no part in a
single module installation.
Staircase pattern generator
The staircase pattern generator is based on D1, which contains a complex series
of synchronous logic gates and timers and produces two sets of signals which are
connected to the multiplexer data-select inputs e.g. output A1-C1 are connected
to multiplexer D4 and outputs A2-C2 to multiplexer D3. The sequence of these
outputs, which is determined solely by D1s internal logic, produce stepped signals at the multiplexer outputs which resemble a full-wave rectified waveform.
Two frequency-related signals are applied to D1. An input to D1 pin 44, annotated [INV-F>, controls one of D1s internal dividers and sets the inverter nominal
base frequency. This signal, which is logic high for 60Hz operation and low for
50Hz, is produced on the UPS Logic Board in response to inputs from the Operator Control Panel. The input to D1 pin 43 is a 288kHz clock signal, produced by
a phase-locked-loop (PLL) circuit, which controls D1s internal operation.
Note: The PLL determines the inverter free running frequency and is normally
synchronised to the bypass supply (See Figure 18-34).
18-247
In addition to the multiplexer data-select signals described above there are several
other frequency-related outputs from D1.
The outputs from pins 31 (D2) and 36 (D1) are square-waves at the nominal base frequency which determine the zero-crossover points of the
inverter output and S phases respectively. These are connected to the filter
section described later (see page 18-250).
The output from pin 40 is a 2.4kHz square-wave which is converted to a
tri-wave by the tri-wave generator, described below, for further use by the
PWM Modulator (See paragraph 3.3.4). The frequency of this signal is
determined by the logic levels at pin 1 (S2) and pin 2 (S3), as selected by
X-15 links 1 and 2 detailed on sheet 1 of the circuit diagram.
Table 18-10:
X15(0-1) S2
X15(0-2) S3
Frequency
Usage
Open (0)
Open (0)
1.2kHz
N/A
Closed (1)
Open (0)
2.4kHz
All models
Open (0)
Closed (1)
4.8kHz
N/A
Closed (1)
Closed (1)
9.6kHz
N/A
18-248
62
15
D53
F-IN
18
F-INM
X4
X3
63
16
BACK
BACKM
34
R247
D17
15
INV-F
37
37
INV-F
44
50 /60 Hz
(Selected from
Operator Panel)
DATA
BUS
D1
27
26
Frequency
Divider
Staircase
Generator
64
SYNCM
Pulses proportional to
phase error between
Inverter & Bypass mains
Phase
Locked
Loop
15
SYNC
Master Freq
reference for
Inverter Osc
14
35
35
SYNC
Phase
error signal
288kHz
(nominal)
4
9
VCO
Phase
Comparator
13
F Correction
D59
50/60Hz
43
CLK
MICROCONTROLLER
(PORT 2)
34
phase
align
FRFB
D6 3
A PLL (D6) provides the clock signal for the staircase pattern generator and
thereby has direct control over the inverter output frequency. This is a standard
type 4046 i.c. which contains two phase comparators (only one of which is used)
and a voltage controlled oscillator (VCO). One of the phase comparators inputs
(D6 pin 14) is driven by a square-wave frequency reference signal, annotated
[SYNC>, which is synchronised to the bypass supply and produced on the UPS
Logic Board; the other input is driven by a 50/60Hz output from the staircase
pattern generator (D1 pin 26) which is described above. If these two signals are
out of phase the phase comparator output (D6 pin 13) will either switch high or
low (depending on the phase relationship) and apply an error correction signal to
the VCOs control input (D6 pin 9) i.e. the VCO frequency is effectively made
to track the frequency reference signal. For example if the bypass frequency
rises slightly, the following actions will take place:
1. The sync control function on the UPS Logic Board will increase the [SYNC>
signal frequency by an appropriate amount.
2. When the PLL compares the [SYNC> signal with the base frequency signal
from the staircase pattern generator it will detect that the [SYNC> signal is of
a slightly higher frequency and the output from D6 pin 13 will exhibit logic
high pulses equal to the periods of phase difference.
18-249
3. The pulses at D6 pin 13 are filtered and applied to the VCO control input at
D6 pin 9 in the form of a dc correction voltage and will cause an increase in
the VCO output at pin 4.
4. This increases the staircase pattern generator clock rate which then
increases the inverter frequency along with the base frequency signal produced at D1 pin 26.
5. When the base frequency signal at D1 pin 26 has risen to match that of the
[SYNC> signal, the phase comparator within the PLL ceases to detect any
phase error and the correction voltage at pin 13 will stop changing. The VCO
control voltage will thus remain constant and the inverter will be maintained
at its current frequency and in sync with the bypass supply.
Filter & C-phase reference generator
The filter sections convert the full-wave rectified stepped waveforms produced
by the multiplexers into sinusoidal AC reference signals suitable for connecting
to the volts error amplifier (See Figure 18-32).
Two filter sections are used; one processes the A-phase AC reference signal and
the other for the B-phase.
Considering the A-phase circuit: the stepped waveform produced by the A-phase
multiplexer (D4) is buffered by N1a and connected to D5 pin 13. This signal is
also inverted by N1d and connected to D5 pin 12. D5 is an electronic switch controlled by the output from D1 pin 36 which was previously described as a
squarewave signal at the nominal base frequency, coinciding with the A-phase
zero crossing points. If D5 is switched by this signal then the signal at its output
pin 14 will be a stepped sine-wave comprising both halves of the signals present
at its pins 12 and 13. This stepped waveform is then filtered by N2a which produces a smooth sinusoidal AC reference voltage [REF_A> and can be monitored at
test point X8-1 as an 8V peak-to-peak sinewave.
The B-phase circuit operates in an identical manner but displaced by 120 i.e.
[REF_B> lags [REF_A> by 120.
The C-phase signal, [REF_C>, is produced by N2d which differentially sums the
other two phases with 0V. Theoretically, in a three phase system the instantaneous sum of all three voltages equals zero: therefore by subtracting the and B phase
signals from 0V the output from N2 pin 14 is equivalent to the C-phase AC reference signal, [REF_C> i.e. A + B + C = 0 C = -(A + B).
Tri-wave generator
18-250
3.3.3
[VINV_X>
[REF_X>
[VI_X>
AC Reference volts
D8
Volts
Error
Amplifier
Current
Feed/fwd
[IINV_X>
AC Control volts
[TRI>
Tri-wave
PWM waveform
to output driver
PWM
Modulator
[MOD_X>
Note: As an almost identical circuit is used for each phase the following description refers to the A phase only, with any differences between this and the B
and C phase highlighted.
The purpose of the volts error amplifier is to compare the inverter output voltage feedback signal with the AC reference voltage created by the reference volts
generator (See paragraph 3.3.2) and provide an appropriate AC control signal to
the PWM modulator i.e. if the volts error amplifier detects an error between
the inverter output voltage feedback signal and the AC reference voltage it modifies the AC control voltage to change the PWM pattern in such a way as to restore
a balanced condition; therefore effectively making the inverter voltage closely
track the AC reference voltage.
Inverter voltage feedback signal
The inverter A-phase output feedback voltage is sensed at the output side of the
output transformer (i.e. at nominal system output volts), attenuated to approximately 1% on the High Voltage Interface Board and connected to the Inverter
Logic Board at X4-18. The signal ([VINV_R>) is amplified slightly as it passes
through N5a to N5b, which acts as the error amplifier, and can be measured at
test point X9-1 as an ac voltage in the range 4.5V to 5.0V (about 14Vp-p) depending on the system working voltage.
Note: Calibration resistors are included in the B phase and C phase feedback
inverter volts feedback signal paths which enables those two phases to be individually balanced to the A phase during board set-up. R224 adjusts the B phase and
R245 the C phase.
18-251
The A-phase AC reference signal is connected to the error amplifier (N5b) via an
electronic switch comprising part of multiplexer D8. This switch is controlled by
a signal annotated [RIF> which is normally low, leaving the switch in the position shown on the circuit diagram. When [RIF> goes high the switch changes over
and replaces the AC reference voltage input into the error amplifier (N5b) with a
signal derived from the R-phase bypass voltage [VI_A> connected to X4-14 which
makes the inverter voltage track the voltage on the bypass supply line.
Bypass voltage sense signal
[VI_A>
When the inverter is first started, [RIF> goes high and energises D8 which then
connects the bypass voltage sense signal [VI_A> to the volts error amplifier reference input thereby replacing the AC reference voltage as the voltage demand
signal. The inverter voltage will thus rise to equal the bypass voltage. Once the inverter voltage has stabilised at the bypass level the output contactor will close
to put the inverter on-load. At this point [RIF> reverts to a logic low and D8 deenergises to select the AC reference voltage as the voltage demand signal. This is
done to prevent arcing across the inverter output contactor when it closes and
therefore increases its operating life and reliability.
Volts error amplifier
N5b sums the AC reference voltage and the inverter voltage feedback signal and
its output takes the form of a sinusoidal voltage representing the reference signal
superimposed with a signal representing any detected error. This is then filtered
by N5c and connected to N5d where it is processed in conjunction with an Aphase current-derived signal.
Note: A third input to N5b from N9a is used only when the module is operating
as part of a multi-module parallel system and provides a means for implementing
load sharing control. In a single module installation this circuit is not used and
the inputs to X4 pins 27-30 are left open circuit.
Current feed-forward
N5d sums the volts error amplifier output from N5c with a signal proportional to
the output current, annotated [INV_A>. This is a feed-forward signal which calls
for an increased inverter voltage as the current increases and improves the overall
inverter voltage regulation characteristics. The output from N5d is connected to
the PWM modulator in the form of the AC control voltage, as depicted in Figure
18-32, where it directly controls the generated PWM pattern.
All three AC control signals are summed by N9d and its output is connected back
to the feed-forward amplifier in all three phases. As, in a three phase system, the
sum of all three phase voltage should equate to 0V, this provides a virtual neutral
reference point for all three amplifiers which prevents the AC control signals
drifting with respect to each other and also ensures that no harmful dc voltages
are generated in the output transformer windings.
Note: In a module fitted with a double-ended (12-pulse) inverter (optional configuration generally reserved for larger modules) the AC control voltage is
connected to the Auxiliary Inverter Logic Board via X6-9 and buffer N10a. In a
standard module connector X6 is not used.
18-252
3.3.4
PWM Modulator
The A-phase PWM pattern is generated by N11, which is configured as a differential comparator whose inverting input is driven by the variable (sinusoidal) AC
control voltage and non-inverting input by a fixed frequency (2.4kHz), fixed voltage (2V) tri-wave signal generated by the reference voltage generator.
N11 generates the PWM pattern by detecting when the fixed tri-wave voltage is
cut by the AC control voltage as illustrated below.
Figure 18-36: PWM Pattern production
N11
Tri-wave (fixed)
PWM pattern
AC control voltage
(variable)
Tri-wave (fixed)
AC control signal
(low)
3
PWM pattern
1
AC control signal
(high)
Tri-wave (fixed)
1
PWM pattern
3
The upper waveform diagram depicts the condition where the AC control voltage
is low with respect to the tri-wave (equal to about 25% of the tri-wave peak voltage) and illustrates that this results in a PWM pattern with a mark-to-space (m:s)
ratio of approximately 3:1. The lower diagrams shows the situation when the AC
control signal is increased to about 75% of the tri-wave peak voltage and illustrates the output m:s now equals 1:3. This shows that the m:s ratio of the output
waveform can be varied by varying the AC control signal; and if this signal is
varied in a sinusoidal manner then the output waveform will represent a sinusoidally modulated PWM pattern.
This pattern is processed by the drive pulse generator and applied to the inverter
IGBT transistors such that for each individual inverter phase the high IGBT is
turned on when the PWM signal is high and vice versa.
18-253
Note: if a 12-pulse inverter is fitted (option on larger modules only) the three AC
control signals and tri-wave signal [TRI> are connected to the Auxiliary Inverter
Logic Board via the four sections of N10 (buffers) and connections X6 pins 9 to
12 i.e. the Auxiliary board contains its own PWM modulator and drive pulse
generator stages.
3.3.5
The inverter current is sensed by Hall-effect CTs fitted between the inverter and
output transformer. In modules above 60 kVA a CT is fitted to each phase but
only two CTs are used in modules at or below this rating, fitted to the S and T
phases only. In the latter case the phase current is calculated from the other two
(monitored) phases.
The CTs sense signals are calibrated by jumpers on the High Voltage Interface
Board which determines the overall burden resistance (See section 7 paragraph
2.3.24) and then connected to X4 pins 21 to 23 on the Inverter Logic Board via
the UPS Logic Board.
In the lower-rated modules, where only two CTs are fitted, the A-phase current is
calculated by N15a which sums the B and C phase current sense signal (via jumpers X16-1 and X16-2) with 0V. As in a three-phase circuit the instantaneous sum
of all three currents equals zero then the output from N15a pin 1 represents the Aphase current i.e. A + B + C = 0 C = -(A + B). In installations using three
CTs, X16 jumpers 1 and 2 should be open and jumper 3 must be made. This
connects the A-phase signal directly to N15a in the same manner employed by
the other two phases.
As all three phases are identical in operation the following description refers to
the A-phase only.
N15 effectively buffers the current sense signal and the output on N15a pin 1 (test
point X10-1 shows approximately 0.2Vp-p signal when the inverter is on no-load)
is in-phase with the output phase current. From N15a this signal is inverted and
amplified by N15b whose output [IINV-A> is connected to the current feed-forward circuit in the AC control voltage line described earlier.
Current limit
The output from N15a is also rectified by N15c/N15d (zero gain) whose output
pin 14 provides a positive full-wave rectified signal representing the inverter Aphase current which is then applied to a comparator circuit comprising N18. The
comparators operating threshold is set by R246 which is connected across a 4.7V
zener regulator and adjusted to present +0.6Vdc at N18 non-inverting input
available at test point X10-4. This represents 150% of the rated inverter load current, and if the current sense signal to N18 inverting input exceeds this level then
the output from N18 pin 7 ([BLK_A>) will switch to a logic low level and apply an
inhibiting input to the drive pulse generator (described below) which prevents it
from turning on the A-phase inverter transistors. This effectively limits the inverter peak current to the set 150% threshold.
Note that the inverter is not shut down during the above event; but the current
limit action will take place during each pulse of the 2.4kHz PWM drive signal
i.e. sub-cycle operation. This effectively reduces the PWM pattern and therefore
the inverter output voltage will fall to the level necessary to restrict the current to
18-254
its 150% level. Taken to its extreme, if there is a short-circuit on the critical bus
then the inverter PWM pulses will be reduced to a minimum and the inverter will
deliver full (150%) current at very low voltage in an attempt to clear the short.
3.3.6
Those gates within D11 concerned with the drive pulse generator function comprise three independent channels controlled by the PWM modulated signals
[MOD_A>, [MOD_B>, [MOD_C>, in conjunction with [STRI>.
Taking the A-phase circuit as an example; the drive control inputs to D11 are
[MOD_A> and [STRI> and the outputs from D11 are taken from pin 36 (drive to the
A-phase inverter low IGBT [PAL>) and 37 (high IGBT [PAH>).
[PAL> switches high, turning on the low IGBT via V42, when [MOD_A> is low
and [STRI> goes low. This condition is latched until [MOD_A> is high and [STRI>
goes high, whereupon [PAL> returns low, turning off the low IGBT, and [PAH>
18-255
The other two inverter phases are controlled in an identical manner with their respective drive signals shown annotated [MOD_B>, [PBL>, [PBH> for the B-phase
and [MOD_C>, [PCL>, [PCH> for the C-phase.
Note: [STRI> is common to all three phases.
There are two means by which the drive pulse logic can be inhibited within D11.
The first occurs if an overload is detected, in which case the [BLK_A>, BLK_B>,
[BLK_C> signals described earlier will inhibit the particular channel being overloaded (See paragraph 3.3.5). The second is by means of a general stop/start
logic block within D11 which handles signals from the UPS Logic Board and
from the local fault detection logic and provides a controlled stop/start function
(See paragraph 3.3.8).
3.3.7
The inverter current limit circuit is shown on the diagram sheet 4 and described
in detail in paragraph 3.3.5. This circuit provides three inputs to D11 annotated
[BLK_A>, [BLK_B> and [BLK_C> which go low if an overload is detected on the associated phase. In the event of a phase current rising to the current limit level the
following occurs within D11:
1. The drive signals to the affected phase(s) are inhibited, as described above.
2. A summary current limit signal (logic low) is produced at D11 pin 21 if any
one of the three phase currents reach the current limit level. This is inverted to
a high by D10b and connected to the UPS Logic Board via X4-32 as an
inverter overload status alarm signal [OVL_INV>, where it is used for display
purposes only (code 33). From D10b pin 10 the signal is also passed back
through D11 pins 20 to 19 and illuminates H14 to provide an on-board indication that the inverter overload circuit is activate. Note that the signal to D10b
is slugged by V23/R300/R237/C141 on removal of the overload to allow the
inverter conditions time to stabilise before the overload status is reset.
3. The [BLK_A>, [BLK_B> and [BLK_C> signals are buffered within D11 and output at pins 31, 32 and 33 respectively. These are passed to the Auxiliary
Inverter Logic Board in a 12-pulse inverter installation via connector X6 pins
13, 14 and 15 (used in large module only).
Inverter Vce(sat) (from desaturation detector on driver interface boards)
A circuit on the Inverter Driver Board (See paragraph 4.3.4) detects an inverter
IGBT fault (short or open circuit) by sensing when the particular device is desaturated during its ON period. These boards thus provide six fault signals back to
the Inverter Logic Board via pins 3/4 and 13/14 of connectors X1 (A-phase) X2
18-256
(B-phase) and X3 (C-phase) respectively. The fault signal applied to these inputs
take the form of a logic low on fault, but this is inverted to a high by a section of
D9 and diode-coupled to a single input at D11 pin 8 [DIS> which is therefore high
if a desaturation condition is detected on any inverter IGBT and drives the Start/
stop logic within D11 to its stop mode (see below).
Note: the Vce(sat) signals produced by the various sections of D9 illuminate
LEDs H5 to H10 to positively identify the location of the faulty IGBT transistor.
Ribbon cable discontinuity
A system of verifying that the ribbon cables connecting the Inverter Logic Board
to the three Inverter Driver Interface Boards is implemented by the connections
to X1 to X3 pins 5/8. Pins 5 and 8 of the respective connectors are linked together
on the Inverter Driver Interface Boards and so present a short-circuit which pulls
D11 pin 9 ([COI>) low if the cables are all correctly in place. However, if one of
the cables are disconnected while the inverter is operating [COI> will rise to a
logic high and drive the Start/stop logic within D11 to its stop mode (see below).
Note: this signal is buffered within D11 and produces a logic high output at D11
pin 18 which illuminates H13 if a fault occurs.
X12 provides a means of overriding this circuit for test purpose only when it is
made 2-3 this jumper should always be position 1-2 during normal operation.
Inverter stack thermostat overtemperature
A facility exists in which thermostats fitted to the power inverter heatsinks can
provide an overtemperature status signal to the UPS Logic Board. The thermostats provide a normally-closed circuit between X1-5 and X3-8 and produce a
logic low signal at X4-40, which is connected to the UPS Logic Board. If any
thermostat opens (at a temperature above 90C) then this chain is broken and X440 is pulled high via R100 and V24.
Where this option is not used, a jumper should be fitted to X13 position 2-3 to
override the overtemperature fault signal which would otherwise appear. Reposition this jumper to 1-2 when the option is used.
3.3.8
Start/stop logic
This circuit is based on a multi-input logic gate within D11 which monitors the
fault detection logic circuits described above, together with several control
inputs from the UPS Logic Board, and either enables or disables the drive pulse
generator outputs (also within D11) in response to the input signals status.
Start/stop logic circuit outputs
Three start/stop status outputs are also produced by D11, as described below:
D11 pin 7 goes high on stop and is the source of the [BLK> signal to the
reference voltage generator circuit. When the stop/start logic is in its
stop mode this signal reduces the reference voltage generator output to
zero and thus demands zero output voltage.
D11 pin 28 goes high on stop and sends a status signal to the UPS Logic
Board via X4 pin 33 to request the micro to disable the inverter run signal.
D11 pin 34 goes high on stop and sends a status signal to the Auxiliary
Inverter Logic Board (12-pulse inverter only); thus ensuring that where
this option is used both the main and auxiliary boards are stopped and
started by a common control signal.
18-257
The start/stop logic within D11 is driven by the following D11 inputs:
1. Inverter Vce(sat) error (detected by desaturation detector on Inverter Driver
Interface Boards) logic high to D11 pin 8 forces the stop mode (See paragraph 3.3.7).
2. Connector discontinuity (led H13 illuminated) logic high to D11 pin 9
forces the stop mode (See paragraph 3.3.7).
3. A system start/stop control input to D11 pin 13 from the UPS Logic Board,
via X4-26, which is low on stop and high on start, provides the means of
allowing the UPS Logic Board to shut down the inverter in response to certain system events e.g. DC overvoltage, low battery, OFF selected from the
Operator Panel, emergency shutdown, etc. This input also drives led H12 via
D11 pin 17 (inverts the signal at pin 13) and illuminates the led when the signal is demanding the inverter to be turned OFF.
4. If a 12-pulse inverter is installed (option) the output from the start/stop circuit on the Auxiliary Inverter Logic Board is connected to D11 pin 14 via
X6-18 and is logic high on stop. This ensures that both main and auxiliary
Inverter Logic Boards react to a common Start/stop line (see also the output
from D11 pin 34 described above).
5. A power supply monitor circuit based on N22 applies a logic high input to
D11 pin 16, placing the stop/start circuit in its stop mode if the 12V supply
rail falls below 10Vdc. This circuit also holds off the inverter operation when
the UPS is first powered up until the 12V rail rises above this level to allow
the power supply time to stabilise before initiating the PWM drive signals.
Led H11 illuminates when this circuit is demanding a stopped condition.
6. The transfer to inverter command [INV_L> generated on the UPS Logic Board
is connected to D11 pin 13. This is clocked through D11 to enable the [RIF>
signal. This re-references the inverter voltage to the bypass voltage just
before the inverter is about to take over the load, which prevents any voltage
drop appearing across the output contactor when it is instructed to close (See
paragraph 3.3.3).
The inverter voltage is referenced to the bypass voltage level for approximately 220ms before is it switches back to its normal reverence voltage: this
more than adequately covers the output contactor closure time, which is
approximately 50ms. Note that this function is disabled by the mains fail
signal [MNS_KO> to D11 pin 11 in the event of a mains failure; thus if the load
is transferred to the inverter when the mains have failed then the inverter will
remain referenced to its normal reference voltage at all times.
3.3.9
Power supply
(circuit diagram sheet 5)
This board receives its control power supply from the DC-DC Power supply
Board only, via connector X5. Pins 3, 4 and 5 carry regulated +12V, 0V and -12V
power rails which form the Inverter Logic Boards main supply inputs; and pins
1 and 2 carry an isolated 36Vac supply which is used by the Inverter Driver Interface Boards and connected via connectors X1, X2 and X3, as shown.
A 5V regulator, N21, provides a regulated +5V rail from the +12 supply.
18-258
The 12V rails are diode-coupled to the 12V rails on the UPS Logic Board via
V14 and V15, as shown on sheet 4 of the diagram. Thus in the event of mains failure (i.e. the AC-DC Power Supply is inactive) the DC-DC Supply will maintain
the control power to all the electronic circuit boards.
3.4
Summary Information
Table 18-11: Inverter Logic Board configuration jumpers
Jumper
Link
Position
Function
1-2
2-3
1-2
2-3
X12
X13
5 links override control inputs from UPS Logic Board as
shown on main circuit diagram
X14
X15
0-5
1200Hz
0-1
2400 Hz
0-2
4800Hz
0-1
0-2
9600Hz
1-2
0-2
2-3
X16
Function
R241
R242
R243
R244
R245
R246
R247
Colour
H1
Green
380V operation
H2
Green
400V operation
H3
Green
415V operation
H4
Amber
Function
Clock-
18-259
LED
Colour
Function
H5 to H10
Red
H11
Red
H12
Red
H13
Red
H14
Red
Inverter ref. A
(8V p - p)
X8 - 2
Inverter ref. B
(8V p - p)
X8 - 3
Inverter ref. C
(8V p - p)
X8 - 4
Inverter DC ref.
X8 - 5
X8 - 6
Test Point X9
X9 - 1
Inverter feedback A
X9 - 2
Inverter feedback B
X9 - 3
Inverter feedback C
X9 - 4
Bypass A
8V p-p
X9 - 5
Bypass B
8V p-p
X9 - 6
Bypass C
8V p-p
X10 - 2
X10 - 3
X10 - 4
18-260
X11 - 1
X11 - 2
Block pulse A
X11 - 3
Block pulse B
X11 - 4
Block pulse C
X11 - 5
PWM A
X11 - 6
PWM B
X11 - 7
PWM C
X11 - 8
Section 5:
4.1
Chapter Overview
This chapter contains a circuit description of the Inverter Gate Driver Board used
across the whole 7200 UPS model range and should be read in conjunction with
circuit diagram SE-4519015-H.
4.2
General description
Details of the IGBT and its drive requirements are described on page 5-19.
4.2.1
Desaturation
Fault Signal
Generator
1
2
Drive
Signal
Demodulator
Control
Logic
Chip IC2
Power Supply
for High
Transistor
Power
Supply
Monitor
9
10
19
20
Desaturation
Monitor
Output
Drive
Pulses
G
E
M1
S
Power
Supply
Transformer
Thermostat
Connections
T
11
12
13
14
Power Supply
for High
Transistor
Power
Supply
Monitor
Drive
Signal
Demodulator
Control
Logic
Chip IC52
Desaturation
Fault Signal
Generator
1
2
3
Output
Drive
Pulses
G
E
Desaturation
Monitor
5-75
The Gate Driver Board is responsible for processing the modulated PWM
transistor drive signals produced by the Inverter Logic Board, making them
suitable for driving the inverter power transistors. It also provides galvanic
isolation of the drive signals and power supply, which is necessary to keep the
high voltage environment surrounding the power inverter transistors away from
the low voltage environment of the electronic control boards.
Three driver boards are used (one per power inverter phase) with each board
containing two identical, but electrically separate, circuits to drive the two
transistors contained in the inverter power block. These channels are easily
observed on the circuit diagram and described in detail below (See Figure 5-37).
4.2.2
Input/Output connections
Each of the three driver boards is connected to the Inverter Logic Board by means
of a ribbon cable to connector CN1. This cable carries the power supplies, drive
signals and fault detection signals for both high and low transistors in the particular inverter phase. The connections between the Gate Driver Board and the inverter IGBTs are made by hard-wired terminations rather than being socketed
note that in each case the connections are colour-coded:
Black = Collector
White = Gate
Red = Emitter.
Thermostats can be fitted to the inverter heatsinks as an optional facility. Where
these are used, they are hard-wired to the Inverter Gate Driver Board terminals S
and T; then connected to the control system via connector M1.
4.3
4.3.1
Power supplies
Two independent (and isolated) sets of power supplies are produced on the Gate
Driver Board one for each inverter drive channel. The supplies are obtained
from the 30Vp-p (20 kHz) output on the DC-DC Power Supply Board which is
connected to T1 primary via CN1 pins 9/10 and 19/20. T1 has two isolated
secondaries which are connected to identical power supply circuits.
T1 secondary voltage is first rectified by a diode bridge to provide a raw +15V
power rail which is then connected to a standard three-terminal +5V voltage
regulator (IC4/IC54). Notice that the supply used by the circuit driving the
inverter high transistor is annotated 0VH, 5VH and 15VH, while the low
transistor channel is annotated 0VL, 5VL and 15VL.
4.3.2
5-76
The circuit diagram shows that the gate terminal is connected to the junction of
driver transistors TR1 and TR3; and the emitter terminal is similarly connected to
the junction of TR2 and TR4. TR1 to TR4 thus form a bridge across the 15V
power rail. To turn ON the inverter transistor, drivers TR1 and TR4 must be
turned ON, and to turn the inverter transistor OFF, drivers TR2 and TR3 must be
turned ON. Regarding the control logic chip IC2, this means that IC2 pin 13 has
to be logic high and pin 12 logic low in order to turn the inverter transistor ON
with the opposite logic states being necessary to turn it OFF.
Note: links CV2/3 and CV52/53 must remain OPEN when this board is fitted to
the 7200 Series UPS range. Fitting these links increases the gate drive signal
power which is necessary when the board is used with inverters of a higher power
level.
Figure 5-38: IC2 Internal Details
1
19
3
14
3
a
b
c
d
18
5
8
7
a
b
8
13
c
d
9
a
b
10
12
c
d
11
4
17
13
12
6
16
Figure 5-38 shows IC2's internal logic functions. The internal gates have been
identified numerically as an aid to description (gate 1 to gate 13), although these
are of course inaccessible.
The Inverter Logic Board generates the required inverter PWM pattern and, in its
output stage, modulates the resultant variable mark-to-space gate drive signals
with a high frequency carrier signal (See paragraph 2.3.4). This composite drive
5-77
waveform is then connected to the Gate Driver Board at CN1 pins 1 and 2. As
such, the signal can be interpreted that the inverter transistor is to be turned ON
when the carrier signal is present and turned OFF when it is not.
The first circuit that the drive signals meets on the Gate Driver Board is a
demodulator, comprising D5-D8 and C10, which converts the drive signal back
into its basic PWM logic pattern. This signal is isolated by opto-coupler OP1 and
connected to IC2 pin 2.
4.3.3
4.3.4
De-saturation detector
The de-saturation detector circuit monitors the voltage across the inverter
transistor (Vce) during its turn ON period. This voltage is normally be very low
(i.e. less than 4V); but will increase if the load current demand becomes
excessive and makes the transistor de-saturate, or if the transistor is open circuit.
The de-saturation circuit, shown in detail in Figure 5-39, comprises a fixed
voltage divider chain (R2, R3, R4 and R6) connected to the +15VH power rail
the `hot' end of R6 is connected to IC2 pin 9, which is the de-saturation input to
the controller chip. The inverter transistor collector voltage is diode-coupled into
the divider chain via D9 and R20 i.e. D9 provides a means of clamping the
junction of R2 and R3.
Note that although the de-saturation circuit monitors the Vce of the inverter IGBT,
the monitored signal is not connected directly to the transistor's emitter terminal.
Instead, the detector uses the 0VH line which is connected to the inverter transistor emitter via TR4 when the transistor is turned ON i.e. the de-saturation detector monitors the combined Vce of the inverter high transistor and Vds of TR4.
Under `normal' circumstances (i.e. when the inverter is not being overloaded) the
monitored transistor collector voltage is sufficiently low to clamp the R2/R3 junction at a voltage seen as a logic low (<<0.8Vdc) by IC2 pin 9. The resistor values
have been chosen means that this condition is satisfied when the monitored voltage is approximately 3.7V (assuming 0.7V drop across D9 when it is turned ON).
5-78
+15VH
R2
D9
R20
R?
IGBT
RES
R3
INV
OUT
desat
IC2
TR4
R6
0VH
DC BUS NEGATIVE
A fault is registered by IC2 when its pin 9 rises to logic high (>>2.0Vdc), which
occurs if the monitored voltage rises above approximately 10.3Vdc. This is
assumed to be the point at which the inverter transistor is operating in a
potentially dangerous de-saturated condition.
Another condition that has to be taken into consideration when monitoring for
de-saturation is the transistor turn-on time. A transistor does not change from
being fully OFF to fully ON instantaneously; therefore, when the transistor is
initially turned ON there is certain to be a brief interval where its collectoremitter voltage will exceed the level detected as a de-saturated condition. For this
reason, the de-saturation monitor circuit allows the transistor 8s to attain a
saturated state after it has been instructed to turn ON (i.e. 12 s from the
application of the gate drive pulse to IC2 pin 2).
The circuit works as follows:
Within IC2, gate 4 forms the de-saturation detector gate. Gate 4d is held
permanently high due to IC8 pin 8 being pulled down to 0V by R5 (SH1 not
fitted). Gate 4b goes high as soon as a gate drive signal is applied to IC2 pin 2
(low) and gate 4a goes high 4s later when IC2 pin 3 goes high. This means that
a logic high output is produced at IC2 pin 18 if the input to gate 4c, from IC2 pin
9, goes high. The input to IC2 pin 9 comes from the de-saturation detector circuit
as previously described.
Put another way, IC2 pin 18 goes high only when the inverter is receiving a gate
drive signal and its collector-emitter voltage is greater than the saturation level.
When IC2 pin 18 goes high it sets off an 8s time delay effected by R10/C7;
however, if the de-saturation signal to IC2 pin 9 returns to a logic low within 8s,
then IC2 pin 18 will return to a logic low and reset the time delay circuit.
5-79
If the de-saturation signal remains high long enough to allow the 8s time delay
to operate fully, it will eventually apply a logic high to IC2 pin 4, with the
following effects:
1. It forces gate 11 output high which, after being inverted by gates 7 and 9,
applies a logic low to gates 8a and 10a, inhibiting the inverter transistor drive
signals at IC2 pins 12 and 13.
2. Via gate 5, IC2 pin 18 is latched into a logic high state -i.e. IC2 pin 4 is prevented from returning to a logic low due to the return-to-normal of the de-saturation fault signal at gate 4 output (which will naturally occur if the
transistor is turned OFF).
3. IC2 pin 17 is driven high, which provides a permanent charging path for C7
through R9, which reinforces the logic high fault input to IC2 pin 4.
4. IC2 pin 16 is driven high which turns OFF LS2 (normally illuminated) and
turns ON LS1, indicating that a fault has been detected. The logic high is also
opto-coupled by OP2 to CN1 pins 3 and 4 which provides a signal back to the
Inverter Logic Board to inhibit the gate drive signals to the faulty inverter
transistor (See paragraph 2.3.7).
5. The culmination of these action clearly latch the de-saturation shutdown circuit mechanism until all power is removed from the Gate Driver Board.
4.3.5
4.3.6
Other connections
There are two other groups of connections on this circuit board which are not
directly concerned with the transistor driver function.
The link between CN1 pins 6 and 7 (16 and 17) form part of the normally-closed
ribbon connector serial link which enables the Inverter Logic Board to detect
when a cable is disconnected. Thus the Inverter Logic Board will shut down the
inverter if CN1 were to be disconnected while the inverter was operational.
Finally, connector M1 pins 1 and 3, and terminals S and T, are concerned with
the thermostat connections. These are probably best understood by referring to
the inverter power schematic diagram.
5-80