OVERVIEW
Device Summary
File Name
C:\Users\usuario\Desktop\Multi
lin Veronica B.469
Order Code
469
Firmware Version
5.2x
Input Parameters
Motor Name Plate Information
Full Load Amps
219 A
570 %
4000 V
Service Factor
1.0
15 sec
21 sec
Motor Temperature
Insulation Class
105 C
Motor Class
Other
85 C
15 min
30 min
85 C
90 C
40 C
45 C
Version 5.23Page 1
60 Hz
Phase Rotation
ABC
Switching Device
Breaker
52A
You have selected the operating device as Breaker .Short Circuit Protection will be
enabled,however it is important to verify that the breaker is rated to interrupt the
maximum available fault curent Using Short circuit protection with a breaker
not rated to interrupt the fault current can result in personal injury and
equipment damage
Current Sensing
Phase CT Primary
750 A
Voltage Sensing
Voltage Transformer Connection Type
VT Ratio
VT's connected on
Voltage Sensing not configured
Voltage Element - Under Voltage DISABLED
Voltage Element - OverVoltage DISABLED
Voltage Element - Phase Reversal DISABLED
Voltage Element - Frequency DISABLED
Motor Starting
Acceleration Time at minimum voltage
6 Sec
4 Sec
Version 5.23Page 2
30 Min
600 Sec
Version 5.23Page 3
219 A
4000 V
60 Hz
ABC
Phase CT Primary
750 A
Ground CT Type
None
None
Digital Inputs
Starter Status Switch
Start Aux a
Standard
1.15 FLA
Unbalance k Factor
15 min
30 min
0.71
RTD Blasing
On/Yes
40 C
125 C
155 C
Latched
Alarm
75 % used
On/Yes
Trip
The above Thermal Model Protection Setpoints will be used to protect your motor.
The overload curve has been calculated based on hot and cold safe stall times provided.
The curve selection assumes a uniform motor curve supplied by motor manufacturer.
The curve recommended by the Motor Settings Auto-Config should be compared to
curve supplied by the manufacturer to ensure motor protection.
Version 5.23Page 4
Latched
Overreach Filter
On/Yes
Trip
2.8 CT
0 ms
Off/No
Warning : Short circuit protection should only be used if the operating device is rated to break the
maximum possible fault current. Please confirm that the breaker is rated appropriately
before putting 469 into service with Short Circuit Protection enabled.
Overload Alarm
Overload Alarm
Unlatched
Alarm
On/Yes
1 s
Mechanical Jam
Mechanical Jam Trip
Latched
Trip
3.00 xFLA
2 s
Current Unbalance
Current Unbalance Alarm
Unlatched
Alarm
15 %
6 s
On/Yes
Latched
Trip
20 %
2 s
Ground Fault
Ground Fault Alarm
Off
On/Yes
Version 5.23Page 5
OFF
Differential
Phase Differential Trip
Off
Acceleration Timer
Accleration Timer Trip
Latched
Trip
7.20 s
Start Inhibit
Start Inhibit Block
On/Yes
Jogging Block
Jogging Block
On/Yes
30 min
Restart Block
Restart Block
On/Yes
600 s
RTD Types
Stator RTD Type
RTD Alarms
Open RTD Sensor Alarm
Latched
Alarm
On/Yes
Latched
Alarm
On/Yes
Version 5.23Page 6
RTD #2
Stator
Stator1
Unlatched
Alarm
125 C
On/Yes
Latched
Trip
155 C
RTD #3
Application
Name
Alarm
Alarm Relays
Alarm Temperature
Alarm Events
Trip
Trip Relays
Trip Temperature
Stator
Stator2
Unlatched
Alarm
125 C
On/Yes
Latched
Trip
155 C
RTD #4
Stator
Stator3
Unlatched
Alarm
125 C
On/Yes
Latched
Trip
155 C
RTD #5
Application
Name
Alarm
Alarm Relays
Alarm Temperature
Alarm Events
Trip
Trip Relays
Trip Temperature
Application
Name
Alarm
Alarm Relays
Alarm Temperature
Alarm Events
Trip
Trip Relays
Trip Temperature
Application
Name
Alarm
Alarm Relays
Alarm Temperature
Alarm Events
Trip
Trip Relays
Trip Temperature
Stator
Stator4
Unlatched
Alarm
125 C
On/Yes
Latched
Trip
155 C
RTD #6
Stator
Stator5
Unlatched
Alarm
125 C
On/Yes
Latched
Trip
155 C
Application
Name
Alarm
Alarm Relays
Alarm Temperature
Alarm Events
Trip
Trip Relays
Trip Temperature
Stator
Stator6
Unlatched
Alarm
125 C
On/Yes
Latched
Trip
155 C
Bearing RTDs
RTD #7
Application
Name
Alarm
Alarm Relays
Alarm Temperature
Alarm Events
Trip
Trip Relays
Trip Temperature
RTD #8
Bearing
Bearing1
Unlatched
Alarm
85C
On/Yes
Latched
Trip
90C
Application
Name
Alarm
Alarm Relays
Alarm Temperature
Alarm Events
Trip
Trip Relays
Trip Temperature
Bearing
Bearing2
Unlatched
Alarm
85C
On/Yes
Latched
Trip
90C
Version 5.23Page 7
Ambient
Ambient
Unlatched
Alarm
40C
On/Yes
Latched
Trip
45C
Version 5.23Page 8
Off
Undervoltage Trip
Off
Over Voltage
Overvoltage Alarm
Off
Overvoltage Trip
Off
Phase Reversal
Voltage Phase Reversal Trip
Off
Version 5.23Page 9