SR469 - Motor Settings Auto-Config Report

OVERVIEW
Device Summary

Generated at : Apr 30 2015 15:27:43

File Name

C:\Users\usuario\Desktop\Multi
lin Veronica B.469

Order Code

469

Firmware Version

5.2x

Input Parameters
Motor Name Plate Information
Full Load Amps

219 A

Locked Rotor Amps as % of FLA

570 %

Motor Nameplate Voltage

4000 V

Service Factor

1.0

HOT Safe Stall Time

15 sec

COLD Safe Stall Time

21 sec

Motor Temperature
Insulation Class

Insulation Class Temperature Rise

105 C

Motor Class

Other

Motor Class Temperature Rise

85 C

Motor Cooling Time Constants (Running)

15 min

Motor Cooling Time Constants (Stopped)

30 min

Number of Stator RTDs

Stator RTD Type

100 Ohm Platinum

Number of Bearing RTDs

Bearing RTD Type

100 Ohm Platinum

Bearing RTD Alarm Temperature

85 C

Bearing RTD Trip Temperature

90 C

Number of Ambient RTD

Ambient RTD Type

100 Ohm Platinum

Ambient RTD Alarm Temperature

40 C

Ambient RTD Trip Temperature

45 C

Version 5.23Page 1

SR469 - Motor Settings Auto-Config Report


Input Parameters(Continued)
System Information
System Frequency

60 Hz

Phase Rotation

ABC

Switching Device

Breaker

Breaker/ Starter Status

52A

You have selected the operating device as Breaker .Short Circuit Protection will be
enabled,however it is important to verify that the breaker is rated to interrupt the
maximum available fault curent Using Short circuit protection with a breaker
not rated to interrupt the fault current can result in personal injury and
equipment damage

Current Sensing
Phase CT Primary

750 A

Phase CT Primary exceeds 200% of the Full Load Amps


Ground CT(s) not configured
Current Element - Ground Fault DISABLED
Differential CT(s) not configured
Current Element - Differential DISABLED

Voltage Sensing
Voltage Transformer Connection Type
VT Ratio
VT's connected on
Voltage Sensing not configured
Voltage Element - Under Voltage DISABLED
Voltage Element - OverVoltage DISABLED
Voltage Element - Phase Reversal DISABLED
Voltage Element - Frequency DISABLED

Motor Starting
Acceleration Time at minimum voltage

6 Sec

Acceleration Time at Rated Voltage

4 Sec

Number of starts per hour

Version 5.23Page 2

SR469 - Motor Settings Auto-Config Report


Input Parameters(Continued)
Motor Starting
Time between motor start commands

30 Min

Motor Restart Time

600 Sec

Version 5.23Page 3

SR469 - Motor Settings Auto-Config Report


Calculated Settings
The following motor and system parameters will be programmed to the settings file
System Setup
Motor Full Load Amps

219 A

Motor Nameplate Voltage

4000 V

Nominal System Frequency

60 Hz

System Phase Sequence

ABC

Phase CT Primary

750 A

Ground CT Type

None

Phase Differential CT Type

None

Digital Inputs
Starter Status Switch

Start Aux a

469 Thermal Model


Curve Style

Standard

Overload Pickup Level

1.15 FLA

Unbalance k Factor

Cool Time Constant Running

15 min

Cool Time Constant Stopped

30 min

Hot/Cold Safe Stall Ratio

0.71

RTD Blasing

On/Yes

RTD Blas Minimum

40 C

RTD Blas Center Point

125 C

RTD Blas Maximum

155 C

Thermal Capacity Alarm

Latched

Thermal Capacity Alarm Relays

Alarm

Thermal Capacity Alarm Level

75 % used

Thermal Capacity Alarm Events

On/Yes

Overload Trip Relays

Trip

Standard Overload Curve Number

The above Thermal Model Protection Setpoints will be used to protect your motor.
The overload curve has been calculated based on hot and cold safe stall times provided.
The curve selection assumes a uniform motor curve supplied by motor manufacturer.
The curve recommended by the Motor Settings Auto-Config should be compared to
curve supplied by the manufacturer to ensure motor protection.

Version 5.23Page 4

SR469 - Motor Settings Auto-Config Report


Calculated Settings (Continued)
Short Circuit Trip
Short Circuit Trip

Latched

Overreach Filter

On/Yes

Short Circuit Trip Relays

Trip

Short Circuit Trip Pickup

2.8 CT

Intentional Short Circuit Trip Delay

0 ms

Short Circuit Trip Backup

Off/No

Warning : Short circuit protection should only be used if the operating device is rated to break the
maximum possible fault current. Please confirm that the breaker is rated appropriately
before putting 469 into service with Short Circuit Protection enabled.

Overload Alarm
Overload Alarm

Unlatched

Overload Alarm Relays

Alarm

Overload Alarm Events

On/Yes

Overload Alarm Delay

1 s

Mechanical Jam
Mechanical Jam Trip

Latched

Mechanical Jam Trip Relays

Trip

Mechanical Jam Pickup

3.00 xFLA

Mechanical Jam Delay

2 s

Current Unbalance
Current Unbalance Alarm

Unlatched

Current Unbalance Alarm Relay

Alarm

Current Unbalance Alarm Pickup

15 %

Current Unbalance Alarm Delay

6 s

Current Unbalance Alarm Events

On/Yes

Current Unbalance Trip

Latched

Current Unbalance Trip Relays

Trip

Current Unbalance Trip Pickup

20 %

Current Unbalance Trip Delay

2 s

Ground Fault
Ground Fault Alarm

Off

Ground Fault Alarm Events

On/Yes

Version 5.23Page 5

SR469 - Motor Settings Auto-Config Report


Calculated Settings (Continued)
Ground Fault
Ground Fault Trip

OFF

Differential
Phase Differential Trip

Off

Acceleration Timer
Accleration Timer Trip

Latched

Acceleration Timer Trip Relays

Trip

Acceleration Timer from Start

7.20 s

Start Inhibit
Start Inhibit Block

On/Yes

Jogging Block
Jogging Block

On/Yes

Maximum Starts/Hour Permissible

Time Between Starts

30 min

Restart Block
Restart Block

On/Yes

Restart Block Time

600 s

RTD Types
Stator RTD Type

100 Ohm Platinum

Bearing RTD Type

100 Ohm Platinum

Ambient RTD Type

100 Ohm Platinum

RTD Alarms
Open RTD Sensor Alarm

Latched

Open RTD Sensor Alarm Relays

Alarm

Open RTD Sensor Alarm Events

On/Yes

RTD Short/Low Temp Alarm

Latched

RTD Short/Low Temp. Alarm Relays

Alarm

RTD Short/Low Temp. Alarm Events

On/Yes

Version 5.23Page 6

SR469 - Motor Settings Auto-Config Report


Calculated Settings (Continued)
Stator RTDs
RTD #1
Application
Name
Alarm
Alarm Relays
Alarm Temperature
Alarm Events
Trip
Trip Relays
Trip Temperature

RTD #2
Stator
Stator1
Unlatched
Alarm
125 C
On/Yes
Latched
Trip
155 C

RTD #3
Application
Name
Alarm
Alarm Relays
Alarm Temperature
Alarm Events
Trip
Trip Relays
Trip Temperature

Stator
Stator2
Unlatched
Alarm
125 C
On/Yes
Latched
Trip
155 C

RTD #4
Stator
Stator3
Unlatched
Alarm
125 C
On/Yes
Latched
Trip
155 C

RTD #5
Application
Name
Alarm
Alarm Relays
Alarm Temperature
Alarm Events
Trip
Trip Relays
Trip Temperature

Application
Name
Alarm
Alarm Relays
Alarm Temperature
Alarm Events
Trip
Trip Relays
Trip Temperature

Application
Name
Alarm
Alarm Relays
Alarm Temperature
Alarm Events
Trip
Trip Relays
Trip Temperature

Stator
Stator4
Unlatched
Alarm
125 C
On/Yes
Latched
Trip
155 C

RTD #6
Stator
Stator5
Unlatched
Alarm
125 C
On/Yes
Latched
Trip
155 C

Application
Name
Alarm
Alarm Relays
Alarm Temperature
Alarm Events
Trip
Trip Relays
Trip Temperature

Stator
Stator6
Unlatched
Alarm
125 C
On/Yes
Latched
Trip
155 C

Bearing RTDs
RTD #7
Application
Name
Alarm
Alarm Relays
Alarm Temperature
Alarm Events
Trip
Trip Relays
Trip Temperature

RTD #8
Bearing
Bearing1
Unlatched
Alarm
85C
On/Yes
Latched
Trip
90C

Application
Name
Alarm
Alarm Relays
Alarm Temperature
Alarm Events
Trip
Trip Relays
Trip Temperature

Bearing
Bearing2
Unlatched
Alarm
85C
On/Yes
Latched
Trip
90C

Version 5.23Page 7

SR469 - Motor Settings Auto-Config Report


Calculated Settings (Continued)
Ambient RTD
RTD #12
Application
Name
Alarm
Alarm Relays
Alarm Temperature
Alarm Events
Trip
Trip Relays
Trip Temperature

Ambient
Ambient
Unlatched
Alarm
40C
On/Yes
Latched
Trip
45C

Version 5.23Page 8

SR469 - Motor Settings Auto-Config Report


Calculated Settings (Continued)
Under Voltage
Undervoltage Alarm

Off

Undervoltage Trip

Off

Over Voltage
Overvoltage Alarm

Off

Overvoltage Trip

Off

Phase Reversal
Voltage Phase Reversal Trip

Off

Version 5.23Page 9