Вы находитесь на странице: 1из 2

AMOT

CONTROLS

Model 8632A
Hawk-I
Hardware

Hawk-I model 8632A is a unique controller combining the power of a PLC with the ease of use of an embedded controller.
Applications include engines, motors, pump monitoring, compressor control, well control, generator set control, small scale
automation and process monitoring and control.

A basic Hawk-I provides functions for Alarm and Shutdown and is expandable for complete control applications. Model
8632A is based on an expandable platform in a single fixed enclosure, featuring a 32 character backlit display and a tactile
keypad. Base Hawk-Is have discrete inputs (32), relay outputs (4), speed input (1) and communication ports (2). The unit
can be expanded to include any or all of the following: thermocouples (16), 4-20mA loop inputs (8), 4-20mA loop (PID)
outputs (3), relay drivers (4 or 24) and MODBUS RTU protocol communications.

Software
Hawk-ls operational sequence is controlled by data downloaded from HawkWin, a Windows based configuration
program. HawkWin simplifies programming by using separate windows for Sequence and Analog Functions. Common
functions, such as override classes, first out annunciation and alarm & shutdown setpoints have been integrated into the
software for ease of programming. The Hawk-I automatically logs the last 64 events with a date and time stamp.
The Sequence Diagram (Ladder
based) allows users to create control
logic for their specific application.
HawkWin provides single menu
configurations of items such as inputs, outputs, timers, and display
messages. All object names are user
definable while programming or
troubleshooting. Plain text messages
can be fully configured by the user;
Alarm and Shutdown annunciation is
automatic.
AMOT Controls Corporation
401 First Street
Richmond, CA 94801-2906
Tel: (510) 307-8300
Fax: (510) 234-9950
www.amotusa.com

2000 AMOT Controls Corp.

HawkWin uses an Analog Diagram


to represent the operational flow of
analog inputs, data and outputs. By
placing objects and connecting them,
the user draws the process functionality for the associated control. Examples of available embedded functions are: PID control, Split Range
Control, Multiplex, Setpoint Constants, Setpoint Variable, and most
standard math functions.
AMOT Controls Ltd.
Western Way
Bury St. Edmunds IP33 3SZ
Suffolk England
Tel: (01284) 762222
Fax: (01284) 760256
www.amot.com

AMOT-Controls Corporation
230 Orchard Road
# 09-230 Faber House
Singapore 238854
Tel: (65) 235-8187|
Fax: (65) 235-8869

Form 1391-B0001

Hazardous Approvals:
ETL:
Class 1, Division 2
Groups A, B, C, & D
ETL FM 3810
FM 3611

CETL

DEMKO
EEX

CAN/CSA C22.2 No. 142


CAN/CSA C22.2 No. 2B

Power Requirements: Table A


Voltage:
24 Vdc (18-36 Vdc)
Current:
500 mA max.(24V)
Ripple:
<1V pk-pk
Environment:
Temperature:
Vibration:
Sealing:
EMC:

Speed Input (Non-Incendive):


Type:
Magnetic Pickup
Number:
1
Signal:
Zero Crossing >2V pk-pk
Analog Inputs (Optional): Table C
Type:
4-20mA, 2-wire Transmitter, (Non Incendive)
Number:
8 or 16
Accuracy:
Better than 1% of FSD
Loop Power:
24 Vdc provided by the Hawk-I
Thermocouple Inputs (Optional): Table C
Type:
J and/or K, (Non Incendive)
Number:
8,16 or 32
Accuracy:
Better than 1% of FSD

0 to 150 F (-18 to 65 C)
0-10g @ 100 Hz
NEMA4 from Front Panel
IEC 801-2(ESD), 801-3(RF Immunity)

Relay Outputs: Table B


Type:
DC Solid State Relay
Number:
4
Rating:
3-36 V at 1.75 A (Continuous)
Isolation:
4 kV

Display: Table E
Type:
Backlit LCD
Characters:
16 Chars X 2 Lines
Char Size:
8.05 X 5.5mm

Digital Outputs (Optional): Table B


Type:
Solid State Relay, Common Ground
Number:
8 or 24
Rating:
36 V at 100 mA
Isolation:
1.5 kV (min)

Digital Inputs (Non-Incendive):


Type:
Volt-Free Contacts
Number:
32
Open Circuit:
> 15 k ohms

Analog Outputs (Optional): Table D


Type:
4-20 mA (2-wire)
Number:
1, 2 or 3
Accuracy:
Better than 0.75% of FSD

Model Code

8632A1

Relays

Extended Board

Code

Relay Options

1
3
4

4 DC Relays
4 DC Relays + 8 Aux. Outputs
24 Aux. Outputs
Code
0
1
2
3
4
5
6
7

Extended Input Options


Extended Board not Fitted
16TC Inputs
8 (4-20mA) Inputs
16TC Inputs + 8 (4-20mA) Inputs
8TC Inputs
16 (4-20mA) Inputs
8TC + 16 (4-20mA) Inputs
32TC Inputs

= Basic Unit

2000 AMOT Controls Corp.

Analog Output

Code
0
1
2
3

LCD Options

PID Options
PID Board not Fitted
Qty. 1 - PID for Grounded Load
Qty. 2 - PID for Grounded Load
Qty. 3 - PID for Grounded Load

Note: Option 1, 2, 3 are not available


with the 32 TC board (C7)

Code
1
2
FORM 1391 - B001

LCD Options
with Backlight
wide temp. range

Вам также может понравиться