On-load tap-changer OILTAP V


Technical Data TD 82/03

Table of Contents

Table of Contents
1

General ..................................................................................................................................................................................................................

1.1
1.2

4
6

Technical Data ................................................................................................................................................................................................... 13


2.1
2.2
2.3
2.4
2.5

Summary of the technical data .......................................................................................................................................................


Survey .......................................................................................................................................................................................................

Rated through-current (Iu), rated step voltage (Ui) and step capacity (PStN) ................................................................
On-load tap-changer V III 250 Y/D and V III 400 Y/D ..............................................................................................................
Restriction of the rated step voltage Ui ........................................................................................................................................
Contact life .............................................................................................................................................................................................
Rated withstand voltages of the internal insulation ................................................................................................................

13
13
14
14
15

Appendix dimension and installation drawings .............................................................................................................................. 17

NOTE
These technical data are intended for the calculator and designer of the transformer. These type-specific data are only
valid in connection with the information contained in the general section (TD 61) since this section contains important
information on such subjects as potential connection, leakage inductance, current division, and so on.
Dimensional drawings and connection diagrams are subject to change without prior notice.
Drawings submitted during bidding and ordering are always binding.
Since the on-load tap-changer is delivered to the specifications of the transformer manufacturer, the transformer
manufacturer is responsible for selecting the correct properties of the on-load tap-changer so that the requirements
of the transformer are met.

TD 82/03 EN

1 General

General

1.1

Summary of the technical data

On-load tap-changer

V III 200 Y

Number of poles and


application

3
neutral point

V III 200 D

V III 350 Y

V III 350 D

V I 350

3
neutral point

at any point on

at any point on

the winding
Max. rated through-current Ium
(in A)

the winding

200

350

Rated short-time withstand


current (in kA)

Rated short-circuit duration


(in s)

10

12,5

Rated peak withstand current


(in kA)
Max. rated step
voltage Uim
(in V)

10 contacts
12 contacts
14 contacts

1500
1200 to 1400
1000

1500
1200 to 1400
1000

Step capacity
(PStN)
(in kVA)

10 contacts
12 contacts
14 contacts

300
280
200

525
420
350

Rated frequency (in Hz)

50 to 60

Operating positions

without change-over selector: max. of 14


with change-over selector: max. of 27

Rated insulation level


Highest voltage for
equipment Um (in kV)1

40 76 123

40 76 123/76

40 76 123

40 76 123/76

40

76

Highest operating voltage


Ub (phase - phase) on
diverter switch (in kV)

40 76 123

30 55

40 76 123

30 55

30

55

Rated lightning impulse


withstand voltage
(in kV, 1,2 I 50)
AC withstand voltage
(in kV, 50 Hz, 1 min.)

Um 40

79

Um 76

Oil suction pipe


Temperature range

350

550

550

70

140

230

230

see table 4
Pressure-proof up to 0.3 bar, continuous difference pressure (test pressure 0.6 bar),
head and cover of the on-load tap-changer are vacuum-proof.
Installed as standard (for details, see BA 18)
The on-load tap-changer OILTAP V can be operated in the rated load range with
oil temperatures of -25 C to +105 C.

Table 1a
4

Um 123/76

200

Rated withstand voltages of


internal insulation
Oil compartment

Um 123

79

TD 82/03 EN

1 General

On-load tap-changer

V III 200 Y

V III 200 D

V III 350 Y

V III 350 D

V I 350

Weight without oil (ca. in kg)

130

140

140

150

120

Displacement
volume
(ca. in dm3)

without changeover selcctor

125

165

140

185

85

with changeover selcctor

155

200

170

220

115

Oil filling
quantity VS
and minimum
volume V1 of
the diverter
switch oil
compartment
(in dm3)

VS

VS

VS

VS

VS

without changeover selector

100

14

145

19

110

15

165

21

68

10

with
over selector

125

16

20

135

18

180

22

85

12

165

Table 1b
Notes for table 1a:
1)

In accordance with VDE 0111, part 1: R.m.s. value of the phase-phase voltage for which a piece of equipment is rated for its
insulation.

Notes for table 1b:


1)
Applies to oil temperature = 30 C ... +100 C

TD 82/03 EN

1 General

1.2

Survey

Fig. 1 Survey of the designs (no. of poles, change-over selector, and installation lengths)

TD 82/03 EN

8996820E

1 General

Survey of the basic connection diagrams (fig. 2a, 2b, 2c) with designation of the tap selector terminal contacts in accordance
with MR standards. This contact designation corresponds to the specifications in the on-load tap-changer dimension
drawings.
Fig. 2a

excerpt from 8906164E_1

TD 82/03 EN

1 General

Fig. 2b

excerpt from 8906164E_2

TD 82/03 EN

1 General

Fig. 2c

excerpt from 8906164E_3

TD 82/03 EN

1 General

Fig. 3

10

Example: On-load tap-changer V III 200 / 350 Y, basic connection diagram 10 10 0

TD 82/03 EN

1 General

Fig. 4

Example: On-load tap-changer V III 200 / 350 Y, basic connection diagram 10 19 1 W

TD 82/03 EN

11

1 General

Fig. 5

12

Example: On-load tap-changer V III 200 / 350 Y, basic connection diagram 10 19 1 G

TD 82/03 EN

2 Technical Data

Technical Data

2.1

Rated through-current (Iu), rated step voltage (Ui) and step capacity ((PStN)

On-load tap-changer

V III 200 Y/D

V III 350 Y/D, V I 350

Contacts

10

12

14

10

Iu (A)

200

200

200

350

300

350

350

Ui (V)

1500

1400

1000

1500

1400

1200

1000

PStN (kVA)

300

280

200

525

420

420

350

Table 2

12

14

Rated through-currents (Iu), related rated step voltages (Ui) and step capacities (PStN), at
highest and lowest rated step voltage of the step capacity curve (see fig. 6)

8997600E

Fig. 6

2.2

Step capacities (Iu, Ui)

On-load tap-changer V III 250 Y/D and V III 400 Y/D

On-load tap-changers V III 250 Y/D and V III 400 Y/D are available as special designs with a maximum rated
through-current of Ium = 250 A or 400 A.
Dimensional drawings on request.

TD 82/03 EN

13

2 Technical Data

2.3

Restriction of the rated step voltage Ui


Due to insulation, the rated step voltage is also limited by
the dielectric strength of the tap-changer, i.e. by limitation
of the total operating voltage across the contact circle.
The total voltage must not exceed the limit values.:
10 contacts: Total Ui = 13 500 V,
12 contacts: Total Ui = 13 200 V,
14 contacts: Total Ui = 13 000 V.
The rated step voltages Ui of these on-load tap-changers
depend on the basic connection diagrams as shown in
figures 2a, 2b and 2c and are valid under the condition
that the rated step voltage is constant within the entire
setting range.

Basic connection diagram

2.4

Contact life

The mean expected contact life of the arcing tap-changer


contacts can be estimated based on the relative load (= Iu/
Ium) as shown in fig. 7. Since actual contact life in individual cases depends on many influencing factors while in
service, only estimations can be given (not applicable to
constant current service).
The inspection regulations must be observed.

Rated step voltage Ui (in V)


1 500

Ui = 13 500 V

10 10 0
10 09 1 W
10 19 1 W
10 09 1 G
10 19 3 W
10 19 1 G
10 19 3 G

1 500

12 12 0
12 11 1 W
12 23 1 W
12 23 3 W
12 23 1 G
12 11 1 G
12 23 3 G

1 200
1 400
1 200
1 320
1 200
1 400
1 320

Ui = 13 200 V

14 14 0
14 13 1 W
14 13 1 G
14 27 1 W
14 27 3 W
14 27 1 G
14 27 3 G

1 000

Ui = 13 000 V

Fig. 7
Expected mean contact life under average load
n
Number of operations
Iu
Rated through-current
Ium Max. rated through-current

1 000

Table 3
Max. rated step voltage

14

TD 82/03 EN

2 Technical Data

2.5

Rated withstand voltages of the internal insulation

Fig. 8 shows the specific voltage stresses present on the tap winding. When selecting the on-load tap-changer, a check must
be made to determine whether the stress at the most unfavorable position on the on-load tap-changer does not exceed the
related rated withstand voltages as shown in table 4.
Insulation distances

10 contacts
a, a1 12 contacts

14 contacts

Um = 40 kV
Um = 76 kV
Um = 123 kV/76
b

Um = 123 kV

Um = 40 kV
Um = 76 kV
Um = 123/76 kV
c2

Um = 123 kV

Um = 40 kV
f

Um = 76 kV
Um = 123/76 kV
Um = 123 kV

Table 4

Voltage shape and


period

V III 200 D
V III 350 D

V III 350 Y
V III 200 Y

V I 350

200
50
180
50
170
50

200
50
180
50
170
50

b1

200
50
180
50
170
50
b2

b3

230
70
350
140
550
150

230
70
490
165
580
165

300
90
520
180
620
180

kV 1.2|50 s
kV 50 Hz 1min
kV 1.2|50 s
kV 50 Hz 1min
kV 1.2|50 s
kV 50 Hz 1min
kV 1.2|50 s
kV 50 Hz 1min
kV 1.2|50 s
kV 50 Hz 1min
kV 1.2|50 s
kV 50 Hz 1min
kV 1.2|50 s

200
70
200
70

200

kV 50 Hz 1min
kV 1.2|50 s
kV 50 Hz 1min
kV 1.2|50 s
kV 50 Hz 1min
kV 1.2|50 s
kV 50 Hz 1min
kV 1.2|50 s
kV 50 Hz 1min
kV 1.2|50 s
kV 50 Hz 1min
kV 1.2|50 s
kV 50 Hz 1min
kV 1.2|50 s
kV 50 Hz 1min
kV 1.2|50 s
kV 50 Hz 1min

70
c21
350
140
490
165
580
165

c22
350
140
520
180
620
180

350
140
350
140

350
140
f1

f2

f1

f2

f1

f2

200
70
350
140
550
230

300
90
490
165
580
230

200
70
350
140

300
90
490
165

200
70
350
140

300
90
490
165

550
230

550
230

Rated withstand voltages (in kV) of the insulation distances (rated lightning impulse withstand voltage,
AC withstand voltage) on the on-load tap-changer

TD 82/03 EN

15

2 Technical Data

a1 = Between tap selector contacts of the winding of one tap position


(connected or not connected)

Without
change-over
selector

a = Between beginning and end of a tapped winding and, with coarse


tap winding, between beginning and end of a coarse tap winding.
Note for coarse tapping arrangement in (-) - position of the changeover selector:
When stressed with impulse voltage, the permissible withstand
voltage a must be adhered to between the end of a coarse tap
winding connected with the K tap selector contact and the tap
selector contact at the end of the tapped winding of the same phase.

With
reversing
switch
(+) - position

b = Between the tap selector contacts of different phases and between


change-over selector contacts of different phases, which are connected with the beginning/end of a tapped winding or with a tap
selector contact.
With tap-changers for delta connection, the permissible voltages
between the contacts depend on the positions of the change-over
selector and the tap selector. This is why the various withstand
voltages b1, b2 or b3 must be adhered to for any insulation distance:
b1 = Between selected contacts of different phases
b2 = From the selected contact of one phase to the unselected
contacts of other phases
b3 = Between unselected contacts of different phases

With
reversing
switch
() - position

= To ground
The following applies to designs without change-over selector.
f1 = Between selected tap selector contacts and ground
f2 = Between unselected tap selector contacts and ground
The following applies to designs with change-over selector.
f1 = Between selected change-over selector contacts and ground
f2 = Between unselected change-over contacts and ground

With coarse
tap selector
(+) - position

In addition, with coarse tapping arrangement in (+) - position of the


change-over selector:
c2 = Between (-) - change-over selector contacts of different phases and
of one (-) -change-over selector and one (+) - change-over contact of
another phase
Different permissible values apply to tap-changers for delta connections.
c21 = Between one (-) - change-over selector contact and one
(+) - change-over selector contact of another phase
c22 = Between one (-) - change-over selector contact of
different phases

With coarse
tap selector
() - position

8997570E

Fig. 8

16

Specific voltage stress of the tap winding

TD 82/03 EN

3 Appendix

Appendix

Dimension drawings, Um = 40 kV and 123 kV


On-load tap-changer OILTAP V III 200 Y
Without change-over selector .......................................................................................................................................................................... 893949
With change-over selector ................................................................................................................................................................................. 893950
On-load tap-changer OILTAP V III 200 D
Without change-over selector .......................................................................................................................................................................... 893952
With change-over selector ................................................................................................................................................................................. 893951
On-load tap-changer OILTAP V III 350 Y
Without change-over selector .......................................................................................................................................................................... 898212
With change-over selector ................................................................................................................................................................................. 898213
On-load tap-changer OILTAP V III 350 D
Without change-over selector .......................................................................................................................................................................... 893955
With change-over selector ................................................................................................................................................................................. 893956
On-load tap-changer OILTAP V I 350
Without change-over selector .......................................................................................................................................................................... 893957
With change-over selector ................................................................................................................................................................................. 893958
Installation drawings
On-load tap-changer OILTAP V 200 ..............................................................................................................................................................
On-load tap-changer OILTAP V 350 ..............................................................................................................................................................
On-load tap-changer OILTAP V 200, tie-in resistors attached on the side ......................................................................................
On-load tap-changer OILTAP V 350, tie-in resistors attached on the side ......................................................................................
On-load tap-changer OILTAP V III 200 Y / V III 350 Y, tie-in resistors attached on the cylinder for 2, 3 or
4 tie-in resistors/phase ........................................................................................................................................................................................

893945
893821
898289
898216
898530

Additional drawings
On-load tap-changer head ................................................................................................................................................................................
Special design for installation in bell-type tanks .......................................................................................................................................
On-load tap-changer head with mounting flange for pressure relief valve ....................................................................................
Swivelling range of the gear unit, drive shaft left ....................................................................................................................................
Swivelling range of the gear unit, drive shaft right ..................................................................................................................................
Horizontal drive shaft (standard and special design) ................................................................................................................................
Directory of additional drawings for on-load tap-changer OILTAP V in acc. w. note in
the dimension drawings ......................................................................................................................................................................................

TD 82/03 EN

893779
893864
895167
894679
894680
893772
898018

17

8939498E

18

On-load tap-changer OILTAP V


V III 200 Y - 40 to 123 - 0, dimension drawing

TD 82/03 EN

8939508E

On-load tap-changer OILTAP V


V III 200 Y - 40 to 123 - W/G, dimension drawing

TD 82/03 EN

19

8939528E

20

On-load tap-changer OILTAP V


V III 200 D - 40 to 123/76 - 0, dimension drawing

TD 82/03 EN

8939518E

On-load tap-changer OILTAP V


V III 200 D - 40 to 123/76 - W/G, dimension drawing

TD 82/03 EN

21

8982122E

22

On-load tap-changer OILTAP V


V III 350 Y - 40 to 123 - 0, dimension drawing

TD 82/03 EN

8982132E

On-load tap-changer OILTAP V


V III 350 Y - 40 to 123 - W/G, dimension drawing

TD 82/03 EN

23

8939559E

24

On-load tap-changer OILTAP V


V III 350 D - 40 to 123/76 - 0, dimension drawing

TD 82/03 EN

8939569E

On-load tap-changer OILTAP V


V III 350 D - 40 to 123/76 - W/G, dimension drawing

TD 82/03 EN

25

8939579E

26

On-load tap-changer OILTAP V


V I 350 - 40 to 76 - 0, dimension drawing

TD 82/03 EN

8939589E

On-load tap-changer OILTAP V


V I 350 - 40 to 76 - W/G, dimension drawing

TD 82/03 EN

27

8939456E

28

On-load tap-changer OILTAP V


Installation drawing

TD 82/03 EN

8938218E

On-load tap-changer OILTAP V 350


Installation drawing

TD 82/03 EN

29

8982891E

30

On-load tap-changer OILTAP V III 200 Y/D


Tie-in resistors, attached on the side

TD 82/03 EN

8982162E

On-load tap-changer OILTAP V III 350 Y/D


Tie-in resistors, attached on the side

TD 82/03 EN

31

8985302E

32

On-load tap-changer OILTAP V III 200 Y / V III 350 Y


Tie-in resistors, attached on the cylinder for 2, 3 or
4 tie-in resistors/phase

TD 82/03 EN

8937799E

On-load tap-changer OILTAP V


On-load tap-changer head

TD 82/03 EN

33

8938644E

On-load tap-changer OILTAP V


Special design for bell-type tank installation

Lifting device

O-ring 44.2 - 5.7

Lifting traverse (illustrated in turned position)

Transformer
cover

Washer 8

Gasket

Supporting flange

Lifting traverse

Centering bolt
Further dimensions of tap changer
head see dwg. 893 779
Lifting traverse see dwg. 893 805

34

TD 82/03 EN

8951673E

On-load tap-changer OILTAP V


Mounting flange for pressure relief valve

TD 82/03 EN

35

8946793E

36

On-load tap-changer OILTAP V


Design with flange for pressure relief valve
Swivelling range of the gear unit, drive shaft left

TD 82/03 EN

8946804E

On-load tap-changer OILTAP V


Design with flange for pressure relief valve
Swivelling range of the gear unit, drive shaft right

TD 82/03 EN

37

8937723E

38

On-load tap-changer OILTAP V


Horizontal drive shaft (standard and special design)

TD 82/03 EN

8980183E

On-load tap-changer OILTAP V


Directory of the additional drawings in acc. w. note in
dimension drawings

Installation drawing for


on-load tap-changer OILTAP V 200...........................................

893945

Installation drawing for


on-load tap-changer OILTAP V 350...........................................

893821

On-load tap-changer head ...........................................................

893779

On-load tap-changer head,


bell-type tank.....................................................................................

893864

Horizontal drive shaft ......................................................................

893772

TD 82/03 EN

39

www.reinhausen.com

Maschinenfabrik Reinhausen GmbH


Falkensteinstrasse 8
93059 Regensburg, Germany

Phone +49 941 40 90-0


Fax
+49 941 40 90-111
E-Mail sales@reinhausen.com

Please note: The data in our publications may differ from the data of the devices delivered.
We reserve the right to make changes without notice.
TD 82/03 EN F0017802 Printed in Germany