Академический Документы
Профессиональный Документы
Культура Документы
Abstract
The purpose of this appendix is to present design concepts and a procedure that can
be used in designing anchor bolts or evaluating an existing anchor bolt arrangement.
Contents
Chevron Corporation
Page
B1.0
Introduction
B-2
B1.1
Failure Modes
B1.2
Nomenclature
B2.0
Design Concepts
B2.1
Bolt Capacities
B2.2
High-strength Bolts
B2.3
B2.4
B2.5
B2.6
Factor of Safety
B2.7
Allowable Loads
B2.8
B3.0
Special Design For Anchor Bolt Load Transfer to Reinforcing Steel B-19
B3.1
B3.2
B3.3
B3.4
B4.0
Design Procedure
B4.1
B4.2
B5.0
Design Examples
B5.1
Design Example 1
B5.2
Design Example 2
B6.0
References
B-6
B-28
B-31
B-39
B-1
June 1997
Appendix B
B1.0
Introduction
In the past, embedment lengths and bolt capacities for anchor bolts in tension were
based on the bond strength developed between the bolt shank and the concrete foundation. The bond strength was based on requirements for plain reinforcing bars and
reinforced concrete members established to avoid any slippage of the steel. This
steel-to-concrete bond strength was small and resulted in large embedment lengths.
Anchor bolt pull-out tests have indicated that embedment lengths, based on this
concept, are overly conservative.
Placing a standard bolt head at the anchor bolt end, without a plate or washer, and
relying on the compression on the bolt head, is reliable and practicable. Therefore,
headed bolt or stud is the preferred bolt for anchorage.
Properly detailed reinforcing steel in close proximity to the bolt can increase the
reliability, reduce the bolt spacing and edge distance requirements and thus, result
in a more economical foundation design. Design of foundations in petrochemical
facilities often involves anchorage for tall vessels and structures which are
subjected to high wind and seismic forces, resulting in large diameter anchor bolts.
The required embedment length, spacing, and edge distance of these anchor bolts
can sometimes become excessive, and often control the size of the foundation.
Two design concepts are presented in this appendix i.e., Cast-in-place Anchor Bolt
in Plain Concrete and Cast-In-Place Anchor Bolt in Reinforced Concrete. Sections
B2.3 through B2.7 provide guidance for design of anchor bolt in plain concrete
which is based on the requirements of Section 1925 of Vol. II of the 1994 edition of
the Uniform Building Code (UBC) [6]. The guidance also includes the design of
anchor bolts in concrete with minimum reinforcement parallel or perpendicular to
the bolt. However, it does not take full advantage of the reinforcing bar to reduce
bolt spacing and edge distance. The standard drawing for anchor bolts, GDQ68922 is developed using the concepts presented in these sections.
Section B3.0 provides guidance for the design of Cast-In-Place Anchor Bolt in
Reinforced Concrete, which is developed based on the guidelines contained in a
new ASCE publication entitled Design of Anchor Bolts in Petrochemical Facilities [13]. This design concept take full advantages of the reinforcing bar in the
concrete to reduce the required edge distance and bolt spacing without any reduction in capacity or ductility of the bolt. This type of anchorage design methodology
is highly suitable for structures or equipment founded on small pier or pedestal
foundations where the embedment, spacing, and edge distance limitations of standard drawing GD-Q68922 can not be met.
B1.1
Failure Modes
Without Reinforcing
Anchoring embedded bolts in concrete is designed to prevent tension, shear, wedge
splitting, and lateral bursting failure of the concrete. The desired failure mode is
bolt yielding because it is more reliable and ductile. The five concrete failure modes
are described briefly below:
June 1997
B-2
Chevron Corporation
Appendix B
Tension: The concrete above the anchor head pulls out in the shape of a cone
which radiates towards the surface from the anchor bolt head. The cone angle
increases with increasing embedment depth and has conservatively been taken
to be 45 (Figure B-1).
Shear: The failure mode of concrete for an anchor bolt in shear near an edge is
one half of a 45 cone. The cone extends laterally from the centerline of the
bolt at the concrete surface towards the edge in the direction of the shear
(Figure B-2).
Wedge Splitting: The concrete cracks or splits in the direction of the nearest
obstruction. This mode of failure happens most frequently when bolts are
placed too close together or near an edge, and the cracking forces are not
resisted by adequate reinforcement (Figure B-4).
Concrete Crushing: For an anchor bolt in shear, the concrete next to the anchor
bolt near the surface crushes and allows the anchor bolt to displace and break.
This failure mode occurs when edge distances are large.
With Reinforcing
Where the main reinforcement is parallel to and in close proximity to the bolt, the
bolt tension is transferred to the reinforcing bars. For this to occur, the bolts and
reinforcing steel must be confined by hoops, spirals, or sufficient concrete edge
distance to contain the high-compressive stresses which form in the region of the
bolt head. When these stresses are confined, tests have shown the failure mode to
be a splitting in the concrete similar to the failure mode for deformed reinforcing
bars in tension. Where minimal reinforcement exists perpendicular to the bolt, tests
show that the shear cone is interrupted and ultimate shear values may be higher.
The cause of failure is diagonal tension; however, the solution is beyond analysis
and results are given based on empirical data. Solutions to both cases are shown in
this text.
Fig. B-1
Chevron Corporation
B-3
June 1997
Appendix B
Fig. B-2
Fig. B-3
POTENTIAL
FAILURE
PLANE
Fig. B-4
June 1997
B-4
Chevron Corporation
B1.2
Appendix B
Nomenclature
AB
AR
ABT
Chevron Corporation
ALB
ASFC
AS
ASR
AT
BACT
BCR
EACT
ECR
FY
Yield tensile stress of bolt material (33000 psi for A-307 material) or
reinforcing steel (psi)
FUR
Ultimate tensile stress of bolt material (60,000 psi for A-307 material),
psi
LACT
LCR
L.F.
PA
PB
Allowable bolt capacity in tension based upon the steel properties of the
bolt (lbs)
B-5
June 1997
Appendix B
B2.0
PBY
PBU
PCR
Tensile capacity of the concrete cone reduced for spacing and edge interferences (lbs)
PC
TU
VA
VB
Allowable bolt capacity in shear based upon the steel properties of the
bolt (lbs)
VC
VCR
Shear capacity of the concrete shear cone reduced for bolt spacing (lbs)
db
fc
ft
ld
Development length required for the anchor bolt reinforcing steel (in)
Strength-reduction factor
Design Concepts
Anchor bolts embedded in concrete foundations should be placed and sized so that
the tension capacities of an anchorage system are governed by the steel properties
of the anchor bolts rather than the concrete properties of the foundation. This
results in a ductile connection that prevents sudden failure since the anchor bolts
will yield and gradually deform plastically before the concrete approaches its
tensile capacity and fails suddenly. A ductile connection is particularly important
for connections which are designed to resist earthquake loads or other dynamic
loads.
Since the steel shear failure of an anchor bolt has little ductility, ensuring a ductile
shear connection is meaningless. However, it is preferable to have the shear
capacity of the concrete be greater than the shear capacity of the bolt.
June 1997
B-6
Chevron Corporation
B2.1
Appendix B
Bolt Capacities
To design a ductile anchorage system, the anchor bolt steel and concrete capacities
must be calculated and compared. The allowable capacities for anchor bolt shear
and tension should be determined according to the allowable stresses specified in
AISC Specification for Structural Steel Buildings (1989 Edition). The allowable
capacities for tension and shear based on the steel properties of the bolt are listed in
Figure B-5.
Fig. B-5
Nominal
Bolt
Diameter d
(in.)
Tensile
Stress Area
ABT (in2)
Bolt Gross
Area AB
(in2)
Bolt Root
Area AR
(in2)
Bolt Head
Dia. h
(in)
Allowable
Tensile
Capacity of
Bolt PB (lbs)
Allowable
Shear
Capacity of
Bolt VB (lbs)
1/2
.142
.196
0.129
0.750
2,800
1,290
5/8
.226
.307
0.207
0.938
4,500
2,070
3/4
.334
.442
0.309
1.125
6,700
3,090
7/8
.462
.601
0.429
1.313
9,200
4,290
.606
.785
0.563
1.500
12,100
5,630
1-1/8
.763
.994
0.709
1.688
15,300
7,090
1-1/4
.969
1.227
0.908
1.875
19,400
9,080
1-1/2
1.41
1.767
1.32
2.250
28,200
13,200
1-3/4
1.90
2.405
1.78
2.625
38,000
17,800
2.50
3.142
2.34
3.000
50,000
23,400
2-1/2
4.00
4.909
3.78
3.750
80,000
37,800
5.97
7.069
5.70
4.500
119,400
57,000
Notes:
B2.2
High-strength Bolts
Only standard A-307 or A-36 type bolts with American standard hexagon heads are
considered in this appendix. High- strength bolts (A-325 and A-490) are not recommended because the higher yield strength requires greater embedment, edge
distance, and more reinforcing. High-strength anchor bolts also do not have as
much ductility as A-307 bolts.
If high-strength bolts are required, they should be designed according to the principles presented in this appendix.
Chevron Corporation
B-7
June 1997
Appendix B
B2.3
where:
fc = specified compressive strength of concrete (psi).
AS = the sloping area (in square inches) of an assumed failure surface.
The surface to be that of a cone or truncated pyramid radiating at
a 45 slope from the bearing edge of the anchor or anchor group
to the surface. For shallow concrete sections with anchor groups,
the failure surface shall be assumed to follow the extension of the
slope through to the far side rather than truncate as in AT.
AT = the flat bottom area (in square inches) of the truncated pyramid
of an assumed tension failure surface.
= concrete strength reduction factor. It is 0.85 when reinforcing
steel is placed parallel to the bolt and 0.65 when parallel reinforcing steel is not present.
For all bolt arrangements, (except the special case listed below), the failure surface
should be based upon full failure cones and reduced for interferences as needed.
The sloping area of the failure surface for full failure cones can be calculated by
using equations B-2 and B-3 listed below:
A S = ( L + h )L 2 (for tension failure cones)
(Eq. B-2)
June 1997
B-8
Chevron Corporation
Appendix B
For the special case of four or more anchors simultaneously in tension and in a rectangular pattern which are spaced closer together than twice their embedded length,
the failure surface is a single pyramid truncated at the anchor-bolt heads rather than
separate cones.
(Eq. B-4)
For restrictive edge distances, the concrete pullout strength should be reduced by
the ratio of the edge distance over the embedment length, EACT/LACT.
For bolt groups with overlapping tension failure cones, the tensile capacity of the
concrete cone reduced for edge and spacing interferences (PCR) becomes:
E ACT
P CR = f c [ 2.8 ( A S A LB ) ] -------------L
ACT
(Eq. B-5)
The reduction for edge distance is more severe than bolt spacing because tests [12]
show that the effective tensile capacity of concrete drops from 4 f c to 2 f c for
Chevron Corporation
B-9
June 1997
Appendix B
small edge distances. The value of EACT/LACT can never be greater than one. Also,
logically, as the edge distance goes to zero, the concrete cone strength should also
go to zero, not half its original value.
If a bolt has multiple restricting edge distances the concrete cone strength shall be
reduced accordingly. A bolt group strength shall be the weakest bolt times the
number of bolts.
Bolt Layout Example
Fig. B-6
Concrete
edge
Ve r tica l
In te rs e c tio n
p la n e d u e to
a d ja ce n t b o lt
In e ffe ctive
slo p in g a re a s
Ve rtic a l
In te rs e ctio n
p la n e s d u e to
co n c re te e d g e s
C o n c re te
edge
r = L + 0 .5 h
Critical Dimensions
The minimum embedment length, edge distance, and bolt spacing are found in
Figure B-7 for values of fc = 3000 psi. These dimensions should be met at all times
and are based on test results and theory.
Critical Dimensions (fc = 3000 PSI) (1 of 2)
Fig. B-7
June 1997
Bolt
Diameter (in)
LCR (in)
ECR
(min. reinf.) (in)
ECR
(no reinf.) (in)
BCR
(in)
1/2
4.0
4.0
4.0
6.0
5/8
5.0
4.0
4.0
6.0
3/4
6.0
4.0
4.0
6.0
7/8
7.0
4.0
5.0
6.0
B-10
Chevron Corporation
Appendix B
Fig. B-7
1.
Bolt
Diameter (in)
LCR (in)
ECR
(min. reinf.) (in)
ECR
(no reinf.) (in)
BCR
(in)
7.0
6.0
5.0
6.0
1-1/8
8.0
6.0
6.0
6.0
1-1/4
9.0
6.0
7.0
6.0
1-1/2
11.0
6.0
8.0
6.0
1-3/4
13.0
6.0
9.0
6.0
14.0
6.0
11.0
6.0
2-1/2
18.0
8.0
13.0
8.0
21.0
8.0
16.0
8.0
2.
b.
d < 1 inch
ECR = 6 inches
ECR = 8 inches
d 2 inches
PA 1 / 2 h
+ --Without steel reinforcement = E CR = ----------------
2
12 f c
(Eq. B-6)
d 2 inches
Chevron Corporation
B-11
June 1997
Appendix B
of very high compressive stresses, a critical stress area, in the region at the bolt
head. If this region is not confined by sufficient cover and reinforcement, spalling
or a lateral blowout occurs, resulting in a reduction in bolt capacity. This blowout is
similar to lateral bursting. The minimum edge distances needed to satisfy lateral
bursting can be found in Figure B-7.
When reinforcing steel is placed parallel to the bolt, 0.85 can be used for . When
calculating PCR, however, the additional resistance provided by the reinforcing steel
was conservatively not included. The required area of reinforcing steel needed for
the anchor bolt load to be transferred into the concrete is found by Equation B-7
listed below:
1.3P ( L.F. )
A SR = -------------------------0.9F Y
(Eq. B-7)
FY is the grade of reinforcing steel in this equation. A conservative method of satisfying Equation B-7 when using A-307 or A-36 bolts and grade 60 reinforcing steel
is to provide an area of reinforcing steel equal to the tensile stress area of the bolt.
This will slightly oversatisfy Equation B-7.
The reinforcing steel should be placed within a circle having a radius equal to five
bolt diameters, using the bolt as the center of the circle. As a minimum, the bolt
should have two reinforcing bars within six inches of the bolt and all reinforcement
should be distributed evenly. The reinforcing steel should have a minimum clear
distance between the bolt head and reinforcing bars of 1 inch or the bolt diameter.
Reinforcement should be developed on both sides where it intersects with the
surface of the predicted tension failure cone.
Figure B-8 and Standard Drawing GD-Q68922 are developed using this approach.
For major equipment, the aforementioned approach may be considered to be too
conservative and an alternative design method may be used. This method allows the
concrete to crack and transfers the load across the crack by the reinforcing steel. To
transfer the load and develop sufficient ductility, the length of the reinforcing steel
on either side of the crack should equal or exceed the recommended development
length of ACI 318. A minimum edge distance and sufficient stirrups shall be
provided to prevent lateral bursting and splitting of concrete caused by the high
stress level at the bolt head. Consult with the CRTC Civil/Structural Technical
Service Team or a Structural Engineer for this type of application.
June 1997
B-12
Chevron Corporation
B2.4
Appendix B
V C = 800A BT f c
(Eq. B-8)
V C = 4A SFC f c
(Eq. B-9)
where:
ASFC = E2
--2
E = distance from the anchor axis to the free edge.
= concrete strength reduction factor. It is always 0.65 except it may
be 0.85 in Equation B-9 if hairpin reinforcing bars are used. See
Reinforcement Parallel to the Shear Loads.
The shear capacities will change with varying bolt areas and concrete edge
distances.
Reinforced Concrete
With minimum reinforcement, tests show a different behavior for shear than for
tension or shear in unreinforced concrete. The shear cone of reinforced concrete is
interrupted, and the stress distributed over a wider area than the shear cone of unreinforced concrete. A value for VC shown by tests [3] is:
V C = 60 f c E
(Eq. B-10)
where:
fc =
Chevron Corporation
B-13
June 1997
Appendix B
When the edge distance is greater than nine inches, adding perpendicular reinforcing has little effect; however, perpendicular reinforcing is recommended for
shear loads whenever the edge distance is less than 10 diameters.
2 2
(Eq. B-11)
When more than one interference exists for a particular bolt, the concrete capacity
must be reduced further. This reduction should be based upon engineering judgment.
June 1997
B-14
Chevron Corporation
B2.5
Appendix B
(Eq. B-13)
B2.6
Factor of Safety
The factors of safety must satisfy the previously stated design concepts. Factors of
safety can be broken down into three groups:
Tension Loads
Ductile Design
For an anchor bolt to have a ductile performance, the bolt must yield before it is
pulled out of the concrete. In design, this can be met by satisfying the following
equation:
P CR
--------------- 1.2
P BY
(Eq. B-14)
The bolt yield capacity, PBY, should be determined for A-307 bolts by using the
tensile stress area, ABT, and a yield tensile strength, FY, of 33,000 psi.
The recommended safety factor for a ductile performing bolt is 2.7 and is expressed
by the following equation:
P CR
--------------- 2.7
PA
(Eq. B-15)
The value of 2.7 is a calculated value based upon factors found in the UBC [6].
Restrictions may exist with certain installations that limit the placement of the
anchor bolts. Bolts spaced close together or placed close to the concrete edge interfere with the full development of the failure cones in the concrete. This limitation
decreases the tension capacity of the concrete cone, and can be calculated using the
principles found in Section B2.3. The loss in capacity can be compensated for by
increasing the embedment length of the bolt, increasing edge distance, or increasing
spacing.
Chevron Corporation
B-15
June 1997
Appendix B
Non-Ductile Design
Where ductile anchorage systems are not practical, an alternative is an anchorage
system governed by concrete properties. Although it is not preferred, this anchorage
system may be used for resisting both static and dynamic loads. Care should be
taken to avoid using these bolts for resisting earthquake tension loads on large
pieces of equipment because the bolts may not have a ductile performance. This
alternate system bases the placement of the anchor bolts in the foundation on the
actual applied loads rather than on the anchor bolt capacities. A factor of safety of
four shall be used with this design as described by the following equations:
P CR
--------------- 4
P
(Eq. B-16)
The factor of safety is higher than for a ductile failure because a concrete failure is
sudden, with no warning.
Shear Loads
As stated in Section B2.0, steel shear failure has little ductility. Therefore, the
required safety factor against concrete breakage can be lower for shear than for
tension. The following is recommended:
V CR
---------------- 1.9
VA
(Eq. B-17)
B2.7
Allowable Loads
Tension
For a ductile connection, the allowable load of an anchor bolt is the lesser of that
based on the steel properties of the bolt, PB, or that based on the tension failure
cone capacity, PCR, of the concrete with a factor of safety of 2.7
PA = PB
or,
whichever is less
P CR
P A = -------------2.7
June 1997
B-16
Chevron Corporation
Appendix B
Shear
The allowable shear load for a bolt is the lesser of that based on the steel properties
of the bolt, VB, or that based on the concrete properties, VCR, with a safety factor
of 1.9.
VA = VB
or
V CR
V A = --------------1.9
whichever is less
B2.8
Fig. B-8
BOLT
DIAMETER
(IN)
TENSILE
STRESS
AREA
(IN2)
EMBEDMENT
LENGTH (IN)
EDGE
DISTANCE
(IN)
MINIMUM
SPACING
(IN)
TENSION
CAPACITY
WITH PARALLEL
REINFORCEMENT
CASE A
(LBS)
ABT
PA
VA
1/2
0.142
2,800
1,300
2,800
5/8
0.226
4,500
2,000
3,700
3/4
0.334
10
6,700
3,000
5,200
7/8
0.462
11
12
9,200
4,200
7,500
0.606
12
16
12,100
5,500
9,700
1-1/8
0.763
14
18
15,300
6,900
12,800
1-1/4
0.969
15
20
19,400
8,900
16,200
Chevron Corporation
B-17
SHEAR
CAPACITY
WITH MINIMUM
REINFORCEMENT
CASE B
(LBS)
TENSION
CAPACITY WITHOUT
PARALLEL
REINFORCEMENT
CASE B
( LBS)
June 1997
Appendix B
Fig. B-8
BOLT
DIAMETER
(IN)
TENSILE
STRESS
AREA
(IN2)
EMBEDMENT
LENGTH (IN)
EDGE
DISTANCE
(IN)
MINIMUM
SPACING
(IN)
TENSION
CAPACITY
WITH PARALLEL
REINFORCEMENT
CASE A
(LBS)
ABT
PA
VA
1-1/2
1.41
18
24
28,200
10,200
21,900
1-3/4
1.90
21
11
28
38,000
14,400
31,300
2.50
24
12
32
50,000
17,100
39,000
2-1/2
4.00
30
15
43
80,000
26,700
64,700
5.97
36
18
51
119,400
38,400
92,300
SHEAR
CAPACITY
WITH MINIMUM
REINFORCEMENT
CASE B
(LBS)
TENSION
CAPACITY WITHOUT
PARALLEL
REINFORCEMENT
CASE B
( LBS)
The embedment length, edge distance, and bolt spacing listed on Standard Drawing
GD-Q68922 are as follows:
L
= 12d
= 6d
The bolt embedment length of 12d was used because with the edge distance and
bolt spacing shown on the standard drawing, PCR increases very little with embedment depths greater than 12d. The edge distance of 6d is from the UBC and will
also meet the blowout requirements listed in Figure B-7. The bolt spacing was set
to satisfy Equation B-15 for bolts with parallel reinforcement and assuming the bolt
geometry shown in Figure B-9.
The tension capacities with parallel reinforcing were determined according to the
AISC Specification for Structural Steel Buildings (1989 Edition), using the tensile
stress area instead of the nominal area. The allowable corner bolt and tension
without parallel reinforcing values are based upon a ductile failure and the safety
factor of Equation B-15; and the embedment, spacing, and edge distances shown on
the standard drawing. The allowable shear loads are the lesser of VB shown in
Figure B-5 or that found by Equation B-17 using the geometries listed on the standard drawing.
Two graphs are shown on the standard drawing. An interaction graph is given for
simultaneous shear and tension loads. This graph applies in all cases with the given
spacing, geometries, and allowable forces shown on the standard drawing. The
other graph given is a scaling graph which adjusts for concrete with other than
3000 psi specified compressive strength. This scaling graph can be used by simply
multiplying the table value by the factor corresponding to the specified design
concrete compressive strength. This table applies to tension without parallel reinforcing and corner bolt values only.
June 1997
B-18
Chevron Corporation
Fig. B-9
Appendix B
Since the allowable loads for the tension with parallel reinforcing and most of the
shear values are based upon the steel strength of the bolt, these values can not be
increased beyond those shown on the standard drawing. They can, however, be
decreased for concrete strengths below 3000 psi.
Since the tension without parallel reinforcing and the corner bolt values are limited
by the concrete strength, these values can be increased when edges greater than
those listed on the standard drawing are used. For the corner bolt values, the new
allowable load is found by multiplying the value listed on the standard drawing by
(EACT / E)2. The value of E in this case is shown on Standard Drawing GDQ68922. For the tension without parallel reinforcing values, the new allowable load
is found by multiplying the listed value by (EACT /E). The new allowable loads can
never exceed the tension with parallel reinforcing values. At some edge distance
then, the tension capacity with parallel reinforcement values can be used without
including the parallel reinforcement. A simple way for omitting the parallel reinforcement when using these values is to increase the edge distance listed on the
standard drawing by 1/3.
B3.0
Chevron Corporation
B-19
June 1997
Appendix B
Figure B-7 can be used without any capacity reduction if all detailing requirements
presented in this section are fully adhered.
The method for load transfer is as follows:
- Tension force:
- Shear force:
- Lateral bursting force: Provide side cover which is sufficient to prevent side
bursting, i.e.,ECR (w/o reinforcement) in Figure B-7.
Alternatively, provide ties at bolt head and provide
minimum side cover ECR (w/ min. reinforcement) in
Figure B-7.
The procedure to determine the required size of anchor bolts in reinforced concrete
is basically the same as that for anchor bolt in plain concrete described in
Section B2.1 and B2.5 which is based on the bolts allowable load shown in
Figure B-5 and satisfying the shear-tension interaction ratio per Equation B-13.
B3.1
June 1997
B-20
Chevron Corporation
Appendix B
where:
ASR = the area of vertical pier reinforcement per bolt, in2.
TU = factored tensile load per bolt, kips (ACI 318-95, Chapter 9)
Fy = minimum specified yield strength of reinforcement steel, ksi
= 0.90, strength reduction factor (ACI 318-95, Chapter 9)
.
Chevron Corporation
B-21
June 1997
Appendix B
Fig. B-10 Reinforcement for Resisting Bolt Tension in Square and Rectangular Pedestals
June 1997
B-22
Chevron Corporation
Appendix B
Chevron Corporation
B-23
June 1997
Appendix B
For ductile performance, the bolt must yield prior to yielding the reinforcing bar.
To achieve this condition, the factored load TU in Equation B-18 should be set
equal to or larger than the nominal tension capacity of the bolt i.e.,
TU = 0.75 FUB ABT. When using A307 or A36 bolts and grade 60 reinforcing steel,
(FUB = 60 ksi and Fy = 60 ksi.) Equation B-18 becomes:
ASR = 0.883 ABT
(Eq. B-19)
where:
ABT = tensile stress area of bolt.
A conservative method of satisfying Equation B-18 when using A307 or A36 bolts
and grade 60 steel is to provide an area of reinforcing steel equal to the tensile
stress areas of the bolt.
The area of vertical pier reinforcement calculated using Equation B-18 is not to be
considered as additive to the reinforcement required strictly for resisting the
moment and tension in sections of the pier. The anchor bolt tension load should
have already been included in the loads used in determining the required vertical
reinforcement in the pier. Therefore, calculated area of steel required for resisting
the external loads applied to the pier should be compared with the area of steel
required for resisting the tension force in the anchor bolts. The area of vertical pier
steel provided should equal or exceed the area of steel required for resisting the
anchor bolt tension.
B3.2
where:
ASV = area of reinforcement (one leg of tie) required, in2.
VU = factored shear force resisted by the bolt, kips (ACI 318-95,
Chapter 9)
June 1997
B-24
Chevron Corporation
Appendix B
B3.3
where:
ASB = area of reinforcement (one leg of tie) required, in2.
= 0.25, lateral force coefficient (ACI 349)
TU = factored tensile load per bolt, kips
Fy = minimum specified yield strength of reinforcement steel, ksi
n = number of legs of the 2 sets of ties at the bolts head. In
Figure B-12, the failure plane only intersects the top tie, thus n =
1 for section A and n = 2 for section B. In Figure B-11, n = 4 for
2 sets hairpin.
= 0.85, strength reduction factor (ACI 318-95, Chapter 9)
Chevron Corporation
B-25
June 1997
Appendix B
Fig. B-12 Reinforcement for Resisting Bolt Shear in Square and Rectangular Pedestals
June 1997
B-26
Chevron Corporation
Appendix B
For ductile performance, TU should be set equal to or larger than the ultimate
capacity of the bolt i.e., TU = FUB. ABT. When using A307 or A36 bolts and grade
60 reinforcing steel, i.e., FUB = 60 ksi and Fy = 60 ksi., Equation B-21 becomes:
ASB = 0.29 ABT
(Eq. B-22)
B3.4
ld = 27 db
L = 27 db + 8 inches
ld = 33 db
L = 33 db + 8 inches
ld = 55 db
L = 55 db + 8 inches
Figure B-13 shows the bolts embedment length required for various reinforcing bar
combinations. The critical edge distance and bolt spacing from Figure B-7 are also
included in the table.
Shorter development lengths than are shown above can be used if the reinforcing
bar is terminated in a standard hook. The required development length for reinforcement terminating in a standard hook should also be determined in accordance
with ACI 318-95. When the reinforcing bar inside the failure cone (i.e., above the
bolt head) is terminated in a standard hook, it should be bent toward the anchor bolt.
Chevron Corporation
B-27
June 1997
Appendix B
Fig. B-13 Critical Dimension and Size of Reinforcing Steel (fc = 3000 psi and Fy = 60,000 psi)
BOLT
TENSILE
DIAMETER STRESS
(IN)
AREA
d
1/2
5/8
3/4
7/8
1
11/8
11/4
11/2
13/4
2
21/2
3
B4.0
MINIMUM
EDGE
DISTANCE
(with no .reinf)
Ecr
MINIMUM
C. TO C.
SPACING
ABT
MINIMUM
EDGE
DISTANCE
(with min. reinf.)
Ecr
Bcr
db
db
db
(IN2)
0.142
0.226
0.334
0.462
0.606
(IN)
4
4
4
4
6
6
6
6
6
6
8
8
(1 bar)
#4
#4
#5
#6
#7
#8
#8
#10
#11
-
(IN)
22
22
25
28
37
41
41
50
84
-
(IN)
19
19
22
22
25
25
28
37
41
50
-
(4 bars)
0.969
1.41
1.9
2.5
4
5.97
(IN)
6
6
6
6
6
6
6
6
6
6
8
8
(2 bars)
0.763
(IN)
4
4
4
5
5
6
7
8
9
11
13
16
(IN)
19
19
22
22
22
25
28
37
46
50
2 - #3
2-#3
2 - #4
2 - #4
2 - #5
2 - #5
2 - #6
2 - #7
2 - #8
2 - #10
-
4 - #3
4 - #3
4 - #4
4 - #4
4 - #4
4 - #5
4 - #6
4 - #7
4 - #9
4 - #10
Design Procedure
The design concepts presented in the previous sections are outlined below to assist
in placing standard A-307 anchor bolts in concrete foundations. This general procedure addresses alternatives and special conditions for different embedment lengths,
bolt spacings, and edge distances. In general, Standard Drawing GD-Q68922 will
cover most cases. Determining design loads is not covered; however, these loads
can be computed from other design practices and computer programs depending on
the type of structure or equipment that is being investigated.
B4.1
June 1997
B-28
Chevron Corporation
B4.2
Appendix B
Follow the basic design steps listed in Sub-section 241 of this manual to get a
preliminary solution.
Step 2.
Check the geometric limitations given (edge distance, etc.) against the values found
in Figure B-7. If the values cannot be met, one of the following alternatives may be
used:
1.
2.
3.
Step 3.
For cases where the dimensions listed on Standard Drawing GD-Q68922 cannot be
met, due to interference from adjacent bolts and/or edge distance, the tension and
shear strength of the concrete should be checked using the following procedure:
1.
Lay out bolt arrangement, and define the tensile failure planes. Find the
tensile failure cone capacity reduced for bolt interference and edge
distance (PCR) described in Section B2.3, assuming no parallel reinforcing steel is present ( = 0.65).
b.
Chevron Corporation
1.
2.
3.
4.
5.
B-29
June 1997
Appendix B
6.
If PCR > 2.7 PA, the full allowable anchor bolt load, PB, listed in
Figure B-5 can be used.
If PCR < 2.7 PA, the following options exist:
1.
2.
3.
4.
5.
6.
2.
Since the steel strength of the anchor bolt controls for most of the bolts listed on the
standard drawing, the allowable shear load of a bolt not meeting the required placement dimensions may be the same. To find the allowable load, use the following
procedure:
a.
b.
Find the allowable shear load, VA, on the bolt by taking the lesser of
V CR
---------------- or VB listed in Figure B-5. If more shear resistance is
1.9
needed, use one of the following options:
1.
2.
3.
4.
5.
6.
Design connection so that the threads of the bolt are out of the shear
plane.
Options 2 through 5 will increase the allowable bolt shear loads when the
concrete properties control. When option 6 is used, the gross area instead of
the root area can be used in calculating the allowable bolt shear capacity, VB.
This will increase the allowable bolt shear load, VA, when the steel strength of
the bolt governs.
June 1997
B-30
Chevron Corporation
Appendix B
Step 4.
Adding Reinforcement
Adding reinforcement parallel to the applied loads can increase the reliability and
ductility of the anchor bolt system. Therefore, a of 0.85 instead of 0.65 can be
used. The reinforcing steel must be able to resist the required loads and be fully
developed on both sides of the failure cone as described in section B2.3. The
following procedure is recommended:
1.
(Tension)
For tension, the above can be met by providing an area of reinforcing steel (60
ksi) parallel to the bolt and equal to or greater than the bolt area. The minimum
number of reinforcing bars is two, and the bars should be spaced equally
around the bolt within a radius as described in Section B2.3.
As mentioned earlier, 180 hairpin reinforcing bars can increase the shear resistance of a bolt when edge distances are small. Hairpin steel should be placed as
described in Section B2.4.
Reinforcement perpendicular to the bolt should be included according to
Section B2.3.
2.
B5.0
a.
b.
c.
d.
Design Examples
B5.1
Design Example 1
Determine the anchor bolt diameter and placement dimensions required to anchor a
vertical pressure vessel to a reinforced concrete foundation. Assume the anchor bolt
circle diameter and number of anchor bolts are fixed due to the vessel design.
The anchor bolt layout and foundation are shown in Figure B-14.
Given:
Chevron Corporation
B-31
June 1997
Appendix B
2.
3.
Check shear:
VA
5,500 lbs
OK
Check tension:
P
June 1997
B-32
OK
Chevron Corporation
Appendix B
Check interaction:
V
3 ,200
------------------ = ------------- = 0.44
1.33V A
7 ,300
16 ,000
P
----------------- = ---------------- = 0.99
16 ,100
1.33P A
P 5 / 3 V 5 / 3
----------------+ -----------------= 1.24 > 1.0
1.33P
1.33V
A
Therefore: No Good
Note 1.33 VA and 1.33 PA were substituted for VA and PA in the interaction
equation because the loads are seismic.
4.
15,300 lbs
1.33 PA =
VA
6,900 lbs
1.33 VA =
Check interaction:
V
P
16 ,000
3 ,200
----------------- = ---------------- = 0.78 ------------------ = ------------- = 0.35
1.33V A
1.33P A
20 ,400
9 ,200
P 5 / 3 V 5 / 3
----------------+ -----------------= 0.84 < 1.0
1.33P
1.33V
A
A
Therefore: Bolt size is O.K.
5.
Check spacing:
BACT
= 13.7 inches
= 18 inches
BCR
= 6.0 inches
Chevron Corporation
B-33
June 1997
Appendix B
Because the bolt spacing cannot be changed and the edge distance is less than
the edge distance shown on the standard drawing, the capacity of the tensile
failure cone PCR will not meet our required safety factors and needs to be
increased. Therefore, increase the edge distance E to that recommended on the
standard drawing and check the concrete cone strength.
E ACT = 7
L ACT = 14
E ACT
P CR = f c [ 2.8 ( A S A LB ) ] -------------L
ACT
June 1997
B-34
Chevron Corporation
Appendix B
P CR
35 ,400
-------------- = ---------------- = 2.31 < 2.7
PA
15 ,300
Therefore, since the maximum allowable bolt load is desired, increase the concrete
design strength, PCR, by adding parallel reinforcing steel, is then 0.85.
P CR = 46 ,250 lbs
P A
46 ,250
----------- = ---------------- = 3.02 > 2.7
P BY
15 ,300
OK
Alternatively, the edge distance could be increased to 11 inches and parallel reinforcing would not be required.
Shear failure cone capacity
Since EACT is 9 inches, calculate the shear cone capacity assuming unreinforced
concrete. From Equation B-11:
A LB
V CR = 4 A SFC --------------- f c
2 2
A LB = 24 in 2
2 ( 24 )
V CR = 0.65 ( 4 ) 127 -------------- 3 ,000
2 2
V CR = 15 ,670 lbs
OK
Therefore, the full allowable shear load may be used. Note that since
VCR/VB > 1.9, the full allowable shear load based on the steel properties could be
used, i.e., VA = VB = 7,090 lbs.
7.
Chevron Corporation
B-35
June 1997
Appendix B
inches (#4 bar assumed). The minimum radius satisfies the required clear
distance between the bolt head and the reinforcing steel.
Use four #4 bars in a five-inch radius circle.
Perpendicular: (from paragraph B2.3)
Use hoop ties which require #4 bars in a closed hoop with a maximum spacing
of six inches.
8.
2
h
8 5 --- = 3.8 below the bolt head, assuming a hook
2
Since 21.1 inches > LACT = 14 inches, hook the top end of the reinforcing
bar.
h
OK
8 + 5 --- = 12.1 < 14
2
Also, increase the foundation thickness by one inch to accommodate the reinforcing bar.
Summary:
Use 1-1/8 inch diameter bolts with an embedment of 14 inches, given spacing
of 13.7 inches and an edge distance of nine inches. Use four #4 bars spaced
evenly around each bolt and hooked on both ends, and #4 closed hoop ties at
two inches from the top of the pedestal and six inches below the top mat. The
total foundation thickness is 21 inches.
B5.2
Design Example 2
Determine the anchor bolt diameter and placement dimensions required to anchor a
structural column to a reinforced concrete foundation. Assume that the anchor bolt
spacing and number of anchor bolts are fixed due to the column design.
The anchor bolt layout and foundation are shown in Figure B-15
Given:
Loads: (Simultaneous)
June 1997
B-36
Chevron Corporation
Appendix B
Solution:
1.
2.
OK
Check shear:
From the standard drawing VA = 3,000 lbs.
VA = 3,000 lbs > V = 1,400 lbs
3.
Chevron Corporation
OK
Check interaction:
B-37
June 1997
Appendix B
5 ,000
P
------- = ------------- = 0.75
6 ,700
PA
1 ,400
V
-------- = ------------- = 0.47
3 ,000
VA
P 5 / 3 V 5 / 3
-----+ -------= ( 0.75 ) 5 / 3 + ( 0.47 ) 5 / 3 = 0.90 < 1.0
P
V
A
4.
OK
Check spacing:
BACT =
BCR
The required spacing is less than given for the standard drawing. It is, however,
more than critical (see Design Step 2, Section B4.2); therefore, the standard
drawing limitations cannot be met. Step 3 (Options Where Interference Exists)
will be required.
5.
6.
EACT
>
OK
Find embedment:
L
Since the depth of the foundation is 18 inches and minimum cover is three
inches, this embedment is O.K.
7.
Evaluate the bolts for interference. Since only the two bolts 8 inches apart are
in tension, only their interference is considered below:
Tension failure cone capacity
EACT
P CR = f c [ 2.8 ( A S A LB ) ] ------------LACT
A S = 2 ( LACT + h )LACT
0.5B ACT
A LB = ( L ACT + 0.5h ) 2 COS 1 ------------------------------- 0.5B ACT [ ( L ACT + 0.5h ) 2 ( 0.5BACT ) 2 ] 1 / 2
L ACT + 0.5h
where:
LACT = 9 inches
EACT = 18 inches > LACT ( Use EACT = 9 inches for Equation B-5
above)
BACT = 8 inches
h = 1.125 inches
June 1997
B-38
Chevron Corporation
Appendix B
Adding reinforcement
Parallel:
Since 0.65 was used for when calculating PCR, reinforcement parallel to
the bolt is not required.
Perpendicular:
Since EACT is greater than L, and EACT > 10d, additional horizontal reinforcement is not required for the anchor bolts.
Summary:
Use 3/4-inch diameter anchor bolts with an embedment of 9 inches and the
column bolt spacing of 8 inches. No additional reinforcement is required for
the given edge distance.
B6.0
References
Chevron Corporation
1.
2.
B-39
June 1997
Appendix B
3.
4.
J. E. Breen, Center for Highway Research, The University of Texas, Development Length for Anchor Bolts, Technical Report, April 1964.
5.
6.
7.
8.
Concrete International, Guide to the Design of Anchor Bolts and Other Steel
Embedments, Vol. 3 No. 7, July 1981.
9.
The University of Texas, Tensile Capacity of Short Anchor Bolts and Welded
Studs, by R. E. Klingner and J. A. Mendonca, June 1981.
10. R. E. Klingner and J. A. Mendonca Shear Capacity of Short Anchor Bolts and
Welded Studs: A Literature Review, ACI Journal, September - October 1982.
(pp. 339 - 349)
11. R. E. Klingner, J. A. Mendonca, J. B. Malik Effect of Reinforcing Details on
the Shear Resistance of Anchor Bolts Under Reversed Cyclic Loading, ACI
Journal, January-February 1982 (pp. 3-12)
12. A. F. Shaikh and W. Yi In-Place Strength of Welded Headed Studs, PCI
Journal, March - April 1985. (pp. 56-81)
13. ASCE Publication, Design of Anchor Bolts in Petrochemical Facilities, 1996.
June 1997
B-40
Chevron Corporation