Type G
Washdown Nozzle
United States Navy
General
Description

Technical
Data

TYCO Type G Nozzles are washdown


nozzles for use on United States Navy
ships. They are external deflector-type
nozzles that discharge a filled cone of
small water droplets at a relatively low
velocity. Four frame arms support the
deflector in order to help protect the
nozzle from mechanical damage.

Approvals
TYCO Type G Nozzles are manufactured
in compliance with NAVSEA Drawing
No. 803-1385828 and have been
qualified to the High Impact Shock
requirements of MIL-S-901C (Navy),
Grade A, Hull Mounted, Class I, Light
Weight Test.
Discharge Coefficient
3.0 gpm/psi1/2 (43,2 lpm/bar1/2)
Water Discharge Pattern
The design of water spray systems
using the Type G Nozzles is to be in
accordance with the applicable standards of the Naval Sea Systems
Command. The approximate water
discharge pattern at the deflector is
125 degrees. The recommended range
of flowing pressure at the nozzle inlet is
20 to 60 psi (1,4 to 4,1 bar).
Thread Connection
1/2 Inch NPT
Nozzle Marking
G-125-.328
Weight
0.3 lbs. (0,14 kg)
Physical Characteristics
The Body of the Type G Nozzle is cast
from aluminum bronze per ASTM B148
(UNS C95300), the Splitter is naval
brass per ASTM B21 (UNS C46400),
the Deflector is silicon bronze per
ASTM B96 (UNS C65500), and the
Pin is bronze per ASTM B159 (UNS
C51000).

Page 1 of 2

APRIL 2015

Installation
TYCO Type G Nozzles must be
installed in compliance with the standards of the Fire Protection Branch of
the Ship Systems Directorate, Naval
Sea Systems Command.

Maintenance
TYCO Type G Nozzles require regularly scheduled inspection and maintenance. For instructions, refer to the
Preventative Maintenance System of
the United States Navy.

TFP820

TFP820
Page 2 of 2
1.69"
(42,9 mm)
PIN

DEFLECTOR

2.43"
(59,4 mm)

SPLITTER

BODY
1/2" NPT
7/16" (11,1 mm)
NOMINAL MAKE-IN

FIGURE 1
TYPE G NOZZLE
ASSEMBLY

Limited
Warranty

Ordering
Procedure

For warranty terms and conditions, visit


www.tyco-fire.com.

Contact your local distributor for availability. When placing an order, indicate the full product name, including
description and part number (P/N).
Type G Nozzle
Specify: Bronze Type G Nozzle,
P/N 49-554-1-328

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2015 Tyco Fire Products, LP. All rights reserved.

Worldwide
www.tyco-fire.com
Contacts

Model BFV-N Butterfly Valve


Wafer Style
General
Description

Technical
Data

The TYCO Model BFV-N Wafer Style


Butterfly Valves (Ref. Figure 1) are indicating type valves designed for use in
fire protection systems where a visual
indication is required as to whether the
valve is open or closed. They are used,
for example, as system, sectional, and
pump water control valves. They are
suitable for installation between ANSI
Class 125 or 150 flanges without the
need for flange gaskets.

Model

For applications requiring supervision


of the open position of the valve, the
Gear Operators for the Model BFV-N
Butterfly Valves are provided with
two sets of factory installed internal
switches each having SPDT contacts.
The supervisory switches transfer their
electrical contacts when there is movement from the valves normal open position during the first two revolutions of
the handwheel.
NOTICE
The TYCO Model BFV-N Wafer Style
Butterfly Valves described herein must
be installed and maintained in compliance with this document, as well as with
the applicable standards of the National
Fire Protection Association, in addition
to the standards of any other authorities having jurisdiction. Failure to do so
may impair the performance of these
devices.

BFV-N

Sizes: ANSI Inches (DN)


2 (DN50), 2-1/2 (DN65), 3 (DN80),
4 (DN100), 5 (DN125), 6 (DN150),
8 (DN200), 10 (DN250), 12 (DN300)

Approvals
UL and C-UL Listed
FM Approved
California State Fire Marshall under
Listing No. 7770-1670:101

Maximum Working Pressure


250 psi (17,2) bar

Materials of Construction:
Body

Ductile iron conforming to ASTM A536

Disc

Ductile iron conforming to ASTM A395,


Nickel Plated

Seat Material

Grade EPDM E rubber conforming to


ASTM D2000

Upper Stem

Type 416 Stainless Steel conforming to


ASTM 582

Operator

Gear operator with iron housing

Friction Loss
The approximate friction loss, based
on the Hazen Williams formula and
expressed in equivalent length of pipe
with C= 120, is as follows. Unless otherwise indicated, the data is based on
friction loss information collected at a
typical flow rate of 15 feet per second.
4.4 feet of 2 inch Sch. 40 pipe for
the 2 inch valve.
6.2 feet of 2-1/2 inch Sch. 40 pipe
for the 2-1/2 inch valve.
7.6 feet of 3 inch Sch. 40 pipe for
the 3 inch valve.
9.2 feet of 4 inch Sch. 40 pipe for
the 4 inch valve.

The owner is responsible for maintaining


their fire protection system and devices
in proper operating condition. Contact the installing contractor or product
manufacturer with any questions.

9.0 feet* of 5 inch Sch. 40 pipe for


the 5 inch valve.
8.2 feet of 6 inch Sch. 40 pipe for
the 6 inch valve.
12.7 feet* of 8 inch Sch. 30 pipe for
the 8 inch valve.
20.1 feet* of 10 inch Sch. 30 pipe for
the 10 inch valve.
22.3 feet* of 12 inch Sch. 30 pipe for
the 12 inch valve.
*NFPA 13

Page 1 of 4

MARCH 2015

TFP1515

TFP1515
Page 2 of 4

Nominal Installation Dimensions


Inches (mm)

Nominal
Valve
Sizes
Inches
(DN)

2
(50)

2.53
(64,0)

1.68
(43,0)

12.62
(320,5)

2.88
(73,0)

6.48
(164,6)

6.00
(152,4)

5.80
(147,3)

2.12
(53,8)

1.38
(35,1)

5/8
(15,9)

21
(10,0)

2-1/2
(65)

2.90
(74,0)

1.81
(46,0)

13.51
(343,1)

3.25
(83,0)

6.98
(177,3)

6.00
(152,4)

5.80
(147,3)

2.12
(53,8)

2.00
(50,8)

5/8
(15,9)

24
(11,0)

3
(80)

3.17
(81,0)

1.81
(46,0)

13,88
(352,6)

3.38
(86,0)

7.22
(183,4)

6.00
(152,4)

5.80
(147,3)

2.12
(53,8)

2.55
(64,8)

5/8
(15,9)

24
(11,0)

4
(100)

4.17
(106,0)

2.06
(52,0)

15.24
(387,0)

4.00
(160,3)

7.98
(202,7)

6.00
(152,4)

5.80
(147,3)

2.12
(53,8)

2.58
(65,5)

5/8
(15,9)

27
(12,0)

5
(125)

5.17
(131,0)

2.19
(56,0)

16.49
(418,8)

4.75
(121,0)

8.48
(215,4)

6.00
(152,4)

7.80
(198,1)

2.12
(53,8)

4.64
(117,9)

3/4
(19,1)

31
(14,1)

6
(150)

6.17
(157,0)

2.19
(56,0)

17.65
(448,3)

5.25
(133,0)

9.10
(231,1)

6.00
(152,4)

7.80
(198,1)

2.12
(53,8)

5.75
(146,1)

3/4
(19,1)

34
(15,0)

8
(200)

8.17
(208,0)

2.38
(60,0)

20.11
(510,8)

6.50
(165,0)

10.35
(262,9)

10.00
(254,0)

7.90
(200,7)

2.12
(53,8)

7.77
(197,4)

3/4
(19,1)

49
(22,0)

10
(250)

10.17
(258,0)

2.68
(69,0)

23.35
(593,1)

8.00
(203,0)

12.27
(311,7)

11.80
(300,0)

9.50
(241,3)

3.03
(77,0)

9.77
(248,2)

7/8
(22,2)

78
(35,0)

12
(300)

12.17
(309,0)

3.00
(76,0)

26.10
(663,0)

9.25
(235,0)

13.77
(349,8)

11.80
(300,0)

9.50
(241,3)

3.03
(77,0)

11.75
(298,5)

7/8
(22,2)

103
(47,0)

INDICATOR
FLAG

HANDWHEEL

GEAR
OPERATOR

Weight
Lbs.
(kg)

1/2" NPT
CONDUIT
CONNECTION

BODY

C
DISC
J

K
BOLT
DIAMETER

FIGURE 1
MODEL BFV-N WAFER STYLE BUTTERFLY VALVE
NOMINAL DIMENSIONS

Installation
The TYCO Model BFV-N Wafer Style
Butterfly Valves may be installed with
flow in either direction and can be
positioned either horizontally or vertically. They are designed for installation
between the faces of ANSI Class 125
and 150 flanges. The Series BFV-N are
self-sealing between mating flanges;
therefore, they do not require the use
of additional gaskets.
The Model BFV-N may be installed with
any pressure class or schedule of pipe
or tubing no greater than schedule 40
that is listed or approved for fire protection service and installed in accordance
with the manufacturers instructions.

The wafer bodies have locating lugs to


ensure proper centering of the valve
body when flange bolts are installed.
Refer to Figure 1 for bolt diameter. Bolts
and studs must meet the minimum
strength requirements of ASTM A307
(Grade B), and the nuts must meet
the minimum strength requirements of
ASTM A563 (Grade A).
Prior to installation, close the valve.
Spread the flanges apart to allow the
valve to slip easily between the flanges.
Make sure the pipe flange faces are
clean of any foreign material such as
scale, metal shavings, or welding slag.
Insert the valve between the flanges
(without flange gaskets). Do not apply
lubricant to the seat faces as this may

Nominal
Flange Size
ANSI Inches
(DN)

Recommended
Minimum Torque
Ft.-Lbs
(Nm)

2-4
(50 - 100)

20 - 30
(27,1 - 40,7)

5-8
(125 - 200)

33 - 50
(44,7 - 67,8)

10
(250)

53 - 75
(71,8 - 101,7)

12
(300)

80 - 110
(108,4 - 149,1)

TABLE A
RECOMMENDED TORQUES

TFP1515
Page 3 of 4

SUPERVISORY
SWITCH

END OF LINE
RESISTOR

AUXILIARY
SWITCH

GND

SWITCH SHOWN
WITH VALVE
FULL OPEN

PANEL

BLUE

RED

VIOLET

SWITCH SHOWN
WITH VALVE
FULL OPEN
GREEN

ORANGE

YELLOW

YELLOW

1/2A @ 125 VDC


1/4A @ 250 VDC
15.1A/12HP @ 125, 250 VAC
5A @ 125 VAC "L"

ORANGE

CONTACT RATING:

BELL
+

POWER
-

FIGURE 2
MODEL BFV-N BUTTERFLY VALVE
INTERNAL SWITCH WIRING DIAGRAM WITH VALVE IN OPEN POSITION
damage the seat material. Be sure to
center the valve and do not damage
the liner. Relax the separation of the
flanges, install, and hand-tighten all
flange bolts. Slowly open the valve,
checking for free movement of the disc.
If valve opens freely, leave the valve in
the open position, and using a crossdraw sequence, tighten all flange bolts
until the valve is metal-to-metal with
both mating flanges. Recommended
tightening torques are listed in Table A.

Step 1. Turn the Handwheel until the


valve is fully closed.

Be certain to keep flange faces as parallel as possible during and after tightening bolts or studs. After final tightening,
again check the valve for full opening
and closing.

Step 6. Close the valve by turning the


Handwheel until the valve is fully in
the closed position. Ensure the disc
has returned to the fully closed position and the disc is centered in the seat
area. Readjust the Shut Stop Screw if
necessary.

As applicable, refer to Figure 2 for the


internal switch wiring diagram.
Conduit and electrical connections
are to be made in accordance with the
authority having jurisdiction and/or the
National Electrical Code. With reference
to Figure 2, the supervisory switch is
intended for connection to the supervisory circuit of a fire alarm control panel
in accordance with NFPA 72. The auxiliary switch is intended for the unsupervised connection to auxiliary equipment
in accordance with NFPA 70, National
Electric Code.
NOTE: For outdoor applications with
internal supervisory switches, it is recommended that wiring connections
be made at a temperature above 15F
(-9C), in order to insure sufficient flexibility of the wire lead insulation.
Stop Adjustment Procedure
The gear operators OPEN and SHUT
position have been factory set. The
following procedure should be used if
slight adjustments are needed. Refer to
Figure 3.

Step 2. Remove the two Lock Screws


(A) from the gear operator body.
Step 3. Turn the Shut Stop Screw (B)
clockwise until snug.
Step 4. Turn the Handwheel until the
valve is fully open.
Step 5. Turn the Open Stop Screw (C)
clockwise until snug.

Step 7. Replace the two Lock Screws


(A) into the gear operator body, locking
the stops into position.

Care and
Maintenance
The TYCO Model BFV-N Wafer Style
Butterfly Valves must be maintained
and serviced in accordance with this
section.
Before closing a fire protection system
control valve for maintenance or inspection work on either the valve or fire
protection system which it controls, permission to shut down the affected fire
protection systems must be obtained
from the proper authorities and all personnel who may be affected by this
decision must be notified.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in accordance with the applicable standards of the National Fire Protection

C
OPEN

B
A

SHUT

FIGURE 3
MODEL BFV-N WAFER STYLE
BUTTERFLY VALVE
OPERATOR ADJUSTMENT
Association (e.g., NFPA 25), in addition to the standards of any authority
having jurisdiction. Contact the installing contractor or product manufacturer
with any questions. Any impairment
must be immediately corrected.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified inspection service.

TFP1515
Page 4 of 4

Limited
Warranty

Ordering
Procedure

For warranty terms and conditions, visit


www.tyco-fire.com.

Wafer Style Butterfly Valves


Specify: (specify inch size) Model
BFV-N Wafer Style Butterfly Valve with
internal supervisory switches, P/N
(specify)
Valve Size
Valve Part Number
2 59-801-1-020N
2-1/2 59-801-1-025N
3 59-801-1-030N
4 59-801-1-040N
5 59-801-1-050N
6 59-801-1-060N
8 59-801-1-080N
10 59-801-1-100N
12 59-801-1-120N

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2015 Tyco Fire Products, LP. All rights reserved.

Worldwide
www.tyco-fire.com
Contacts

Series TY-B 5.6 K-factor


Horizontal and Vertical Sidewall Sprinklers
Standard Response, Standard Coverage
General
Description
The TYCO Series TY-B, 5.6 K-factor,
Horizontal and Vertical Sidewall Sprinklers described in this technical data
sheet are standard response, standard
coverage decorative 5 mm glass bulb
type spray sprinklers designed for use
in light and ordinary hazard, commercial
occupancies such as banks, hotels, and
shopping malls.
They are designed for installation along
a wall or the side of a beam and just
beneath a smooth ceiling. Sidewall
sprinklers are commonly used instead
of pendent or upright sprinklers due to
aesthetics or building construction considerations, where piping across the
ceiling is not desirable.
The recessed version of the Series TY-B
Horizontal Sidewall Sprinkler is intended for use in areas with a finished wall.
It uses a two-piece Style 10 Recessed
Escutcheon. The Recessed Escutcheon
provides 1/2 inch (12,7 mm) of recessed
adjustment or up to 3/4 inch (19,1 mm)
of total adjustment from the flush sidewall position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the fixed pipe
nipples to the sprinklers must be cut.
Corrosion-resistant coatings, where
applicable, are utilized to extend
the life of copper alloy sprinklers
beyond that which would otherwise be
obtained when exposed to corrosive
atmospheres. Although corrosion resistant coated sprinklers have passed
the standard corrosion tests of the ap-

IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 6

plicable approval agencies, the testing is not representative of all possible


corrosive atmospheres. Consequently,
it is recommended that the end user
be consulted with respect to the suitability of these coatings for any given
corrosive environment. The effects of
ambient temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
NOTICE
The Series TY-B Sprinklers described
herein must be installed and maintained
in compliance with this document, as
well as with the applicable standards of
the National Fire Protection Association,
in addition to the standards of any other authorities having jurisdiction. Failure
to do so may impair the performance of
these devices.
The owner is responsible for maintaining
their fire protection system and devices
in proper operating condition. Contact
the installing contractor or product manufacturer with any questions.

Sprinkler
Identification
Numbers
TY3351 Horizontal Sidewall
TY3451 Vertical Sidewall

Technical
Data
Approvals
UL and C-UL Listed
FM Approved
LPCB Certified
NYC Approved

Discharge Coefficient
K=5.6 gpm/psi1/2 (80,6 lpm/bar1/2)
Temperature Ratings
Refer to Table A
Finishes
Sprinkler: Refer to Table C
Recessed Escutcheon: Signal or Pure
White, Jet Black, Chrome Plated, or
Natural Brass
Physical Characteristics

Frame Bronze
Button Brass/Copper
Sealing Assembly. . Beryllium Nickel w/TEFLON
Bulb Glass
Compression Screw Bronze
HSW Deflector Bronze
VSW Deflector Copper

(Refer to Table A for complete approval


information, including corrosion-resistant status.)
Maximum Working Pressure
Refer to Table B

APRIL 2015

TFP161

TFP161
Page 2 of 6

Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to activate and water to flow.

Design
Criteria
The TYCO Series TY-B, 5.6 K-factor,
Horizontal and Vertical Sidewall Sprinklers are intended for fire protection
systems designed in accordance with
the standard installation rules recognized by the applicable Listing or Approval agency (for example, UL Listing
is based on the requirements of NFPA
13, and FM Approval is based on the
requirements of the FM Loss Prevention Data Sheets). Only the Style 10
Recessed Escutcheon, as applicable,
is to be used for recessed horizontal
installations.

General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprinkler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135F (57C) to 3/32
inch (2,4 mm) for the 360F (182C) temperature ratings.
A leak-tight 1/2 inch NPT sprinkler joint
should be obtained by applying a minimum-to-maximum torque of 7 to 14
ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque may distort the sprinkler inlet
and cause leakage or impairment of the
sprinkler.
Do not attempt to make-up for insufficient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
Horizontal Sidewall Sprinkler
Installation
The TYCO Series TY-B Recessed Horizontal Sidewall Sprinklers must be installed in accordance with the following
instructions.
Install recessed horizontal sidewall
sprinklers in the horizontal position with
the centerline of waterway perpendicular to the back wall and parallel to the

6*

1-13/16"
(46,0 mm)
CENTERLINE
OF SPRINKLER
WATERWAY

1
1/2" **
NPT

1-1/2"
(38,1 mm)
2-3/16"
(55,6 mm)

is indicated on
Deflector.

Pipe thread
connections per
ISO 7-1 can be
provided on
special request.

7/16"
(11,1 mm)
NOMINAL
MAKE-IN

* Temperature rating

**

WRENCH
FLATS

9/16"
(14,3 mm)

Installation
The TYCO Series TY-B, 5.6 K-factor,
Horizontal and Vertical Sidewall Sprinklers must be installed in accordance
with this section.

DEFLECTOR
HAT

1 - Frame
2 - Button
3 - Sealing
Assembly
4 - Bulb
5 - Compression
Screw
6 - Deflector *

STYLE 10
RECESSED
ESCUTCHEON

ESCUTCHEON
PLATE SEATING
SURFACE

2-7/8" DIA.
(73,0 mm)

FIGURE 1
SERIES TY-B HORIZONTAL SIDEWALL (TY3351) SPRINKLER
5.6 K-FACTOR STANDARD RESPONSE
ceiling. The word TOP on the Deflector is to face towards the ceiling.
Step A. After installing the Style 10
Mounting Plate over the sprinkler
threads, hand-tighten the sprinkler into
the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type 7
Recessed Sprinkler Wrench (Ref. Figure
5). Apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats
(Ref. Figure 1).
Step C. After the ceiling is installed or
the finish coat is applied, slide on the
Style 10 Closure over the Series TY-B
Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.

Vertical Sidewall Sprinkler


Installation
The Series TY-B Vertical Sidewall Sprinklers must be installed in accordance
with the following instructions.
Install vertical sidewall sprinklers in the
pendent or upright position with the arrow on the Deflector pointing away from
the wall.
Step 1. With pipe thread sealant applied
to the pipe threads, hand-tighten the
sprinkler into the sprinkler fitting.
Step 2. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 4). For
wax-coated sprinklers, use an 8 or 10
inch adjustable Crescent wrench. Apply
the W-Type 6 Sprinkler Wrench or the
Crescent wrench, as applicable, to the
wrench flats (Ref. Figure 2).

TFP161
Page 3 of 6
* Temperature

**

rating is
indicated on
Deflector.

ESCUTCHEON
PLATE SEATING
SURFACE

Pipe thread
connections
per ISO 7-1 can
be provided on
special request.

1/2" **
NPT

7/16"
(11,1 mm)
NOMINAL
MAKE-IN

1 - Frame
4 - Bulb
7 - Ejection
2 - Button
5 - Compression Spring
Screw
3 - Sealing
Assembly 6 - Deflector *
ARROW MUST
POINT AWAY
FROM AND BE
PERPENDICULAR
TO THE BACK
WALL SURFACE

FIGURE 4
W-TYPE 6
SPRINKLER WRENCH
6*
FLOW

2-3/16"
(55,6 mm)

WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)

2-3/16"
(55,6 mm)

WRENCH
RECESS

5
4
2

1-1/2"
(38,1 mm)

WRENCH
FLATS

3
1

SHOWN
PENDENT

SHOWN
UPRIGHT

CROSS
SECTION

FIGURE 2
SERIES TY-B VERTICAL SIDEWALL (TY3451) SPRINKLER
5.6 K-FACTOR, STANDARD RESPONSE

MOUNTING
SURFACE

sprinkler, loosen the wrench jaws before


removing the wrench.

FACE OF
SPRINKLER
FITTING

After installation, inspect the sprinkler


wrench flats and frame arms and retouch (repair) the wax coating whenever the coating has been damaged
and bare metal is exposed. Retouch
the wax coating on the wrench flats by
gently applying a heated 1/8 inch diameter steel rod to the damaged areas of
wax to smooth it back over areas where
bare metal is exposed.

2-7/8" DIA.
(73,0 mm)
2-1/4" DIA.
(57,2 mm)

MOUNTING
PLATE

1/8"
(3,2 mm)
1-1/4" (31,8 mm)

3/4" (19,1 mm)

3/4" (19,1 mm)

1/4" (6,4 mm)

FIGURE 3
SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON, 5.6 K-FACTOR, 1/2 INCH NPT
When installing wax-coated sprinklers
with the adjustable Crescent wrench,
exercise care to prevent damage to the
wax coating on the sprinkler wrench
flats or frame arms and, consequently, exposure of bare metal to the cor-

FIGURE 5
W-TYPE 7 RECESSED
SPRINKLER WRENCH

5/81/4"
(15,96,4 mm)

CLOSURE

SERIES
TY-B

PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA

rosive environment. Open the jaws of


the wrench sufficiently wide to pass
over the wrench flats without damaging
the wax coating. Before wrench-tightening the sprinkler, adjust the jaws of
the wrench to contact only the sprinkler
wrench flats. After wrench tightening the

NOTICE
Only retouching of the wax coating applied to the wrench flats and frame arms
is permitted, and the retouching is to be
performed only at the time of the initial
sprinkler installation.
The steel rod should be heated only to
the point at which it can begin to melt
the wax, and appropriate precautions
need to be taken when handling the
heated rod in order to prevent the installer from being burned.

TFP161
Page 4 of 6

5.6
1/2
NPT

SPRINKLER
TYPE

HORIZONTAL
SIDEWALL
(TY3351)
Figure 1

RECESSED
HORIZONTAL
SIDEWALL
(TY3351)*
Figure 3

5.6
1/2
NPT

VERTICAL
SIDEWALL
(TY3451)
PENDENT
or
UPRIGHT
Figure 2

TEMPERATURE
RATING

BULB
LIQUID
COLOR NATURAL CHROME
BRASS
PLATED

135F (57C)

Orange

155F (68C)

Red

175F (79C)

Yellow

200F (93C)

Green

286F (141C)

Blue

360F (182C)

Mauve

135F (57C)

Orange

155F (68C)

Red

175F (79C)

Yellow

200F (93C)

Green

135F (57C)

Orange

155F (68C)

Red

175F (79C)

Yellow

200F (93C)

Green

286F (141C)

Blue

360F (182C)

Mauve

SPRINKLER FINISH (10)


LEAD
WAX
WAX-OVER-LEAD
POLYESTER*** COATED
COATED
COATED

1, 2, 3, 4, 9

1, 2, 3, 9

1, 2, 4, 9

1, 2, 9

1, 2, 3, 9
1, 2, 3, 9
1**, 2**, 3**, 9**
N/A

1, 2, 3, 9

4, 5, 6, 7, 8, 9

N/A

5, 6, 7, 9
5, 6, 7, 9
5**, 6**, 7**, 9**

4, 5, 6, 8, 9

N/A

Notes:
1. UL Listed for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deflector-to-ceiling distance
2. C-UL Listed for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deflector-to-ceiling distance
3. FM Approved for use in Light Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deflector-to-ceiling distance
4. LPCB Approved (Ref. No. 094a & 007k) at a 4 to 6 inch (100 to 150 mm) deflector-to-ceiling distance
5. UL Listed for use in Light and Ordinary Hazard Occupancies
6. C-UL Listed for use in Light and Ordinary Hazard Occupancies
7. FM Approved for use in Light Hazard Occupancies
8. LPCB Approved (Ref. No. 094a & 007k)
9. Approved by the City of New York under MEA 354-01-E
10. Where Polyester Coated, Lead Coated, Wax Coated, and Wax-over-Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as corrosion-resistant sprinklers. Where Lead Coated, Wax Coated, and Wax-over-Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as corrosionresistant sprinklers.
* Installed with Style 10 (1/2 NPT) or Style 40 (3/4 NPT) 3/4 Total Adjustment Recessed Escutcheon, as applicable
** 150F (66C) maximum ceiling temperature
*** Frame and deflector only
N/A Not Applicable

TABLE A
SERIES TY-B HORIZONTAL AND VERTICAL SPRINKLERS
LABORATORY LISTINGS AND APPROVALS

TFP161
Page 5 of 6

SPRINKLER FINISH

SPRINKLER
TYPE

NATURAL
BRASS

HORIZONTAL SIDEWALL
(TY3351)

CHROME
PLATED

LEAD
COATED

POLYESTER*

WAX
COATED

WAX-OVER-LEAD
COATED

250 psi (17,2 bar) (a)


OR

5.6
1/2
NPT

RECESSED
HORIZONTAL SIDEWALL
(TY3351)

VERTICAL SIDEWALL
(TY3451)

175 psi (12,1 bar)

175 psi (12,1 bar)

Note:
a. The maximum working pressure of 250 psi (17,2 bar) only applies to UL Listing, C-UL Listing and Approval by the City of New York
* Frame and deflector only

TABLE B
SERIES TY-B HORIZONTAL AND VERTICAL SPRINKLERS
MAXIMUM WORKING PRESSURE

Care and
Maintenance

Absence of an escutcheon, which is


used to cover a clearance, may delay
the time to sprinkler operation in a fire
situation.

The TYCO Series TY-B, 5.6 K-factor,


Horizontal and Vertical Sidewall Sprinklers must be maintained and serviced
in accordance with this section.

Sprinklers which are found to be leaking


or exhibiting visible signs of corrosion
must be replaced.

Before closing a fire protection system main control valve for maintenance
work on the fire protection system that
it controls, obtain permission to shut
down the affected fire protection system from the proper authorities and notify all personnel who may be affected
by this action.
The owner must assure that the sprinklers are not used for hanging any objects and that the sprinklers are only
cleaned by means of gently dusting with
a feather duster; otherwise, non-operation in the event of a fire or inadvertent
operation may result.

Automatic sprinklers must never be


painted, plated, coated, or otherwise
altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have
not operated, should be replaced if they
cannot be completely cleaned by wiping
the sprinkler with a cloth or by brushing
it with a soft bristle brush.
Care must be exercised to avoid damage to the sprinklers before, during, and
after installation. Sprinklers damaged
by dropping, striking, wrench twist/
slippage, or the like, must be replaced.
Also, replace any sprinkler that has a

cracked bulb or that has lost liquid from


its bulb. (Refer to Installation Section.)
The owner is responsible for the inspection, testing, and maintenance of their
fire protection system and devices in
compliance with this document, as well
as with the applicable standards of the
National Fire Protection Association
(e.g., NFPA 25), in addition to the standards of any other authorities having
jurisdiction. Contact the installing contractor or product manufacturer with
any questions.
Automatic sprinklers are recommended
to be inspected, tested, and maintained
by a qualified Inspection Service in accordance with local requirements and/
or national codes.

TFP161
Page 6 of 6

P/N57XXXXXXX
TEMPERATURE
RATING

SPRINKLER
FINISH

SIN
578

HORIZONTAL SIDEWALL

TY3351

NATURAL BRASS

135

135F (57C)

575

VERTICAL SIDEWALL

TY3451

PURE WHITE (RAL9010)*


POLYESTER

155

155F (68C)

SIGNAL WHITE (RAL9003)


POLYESTER

175

175F (79C)

JET BLACK (RAL9005)**


POLYESTER

200

200F (93C)

WAX COATED
286F (141C) MAX

286

286F (141C)

LEAD COATED

360

360F (182C)

WAX-OVER-LEAD
286F (141C) MAX

000

OPEN***

CHROME PLATED

Notes:
* Eastern Hemisphere sales only
** Available only for 155F (68C) or 200F (93C) temperature
rated sprinklers
*** Available only for horizontal sidewall TY3351 for use in
Deluge Systems (OPEN indicates sprinkler assembly
without glass bulb, button, and sealing assembly)

TABLE C
SERIES TY-B HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS
PART NUMBER SELECTION

Color

Sprinkler
Temperature Rating

Part Number

Black

135F (57C)

56-065-1-135

Red

155F (68C)

56-065-1-155

Yellow

175F (79C

56-065-1-175

Blue

200F (93C)
286F (141C)

56-065-1-286

TABLE D
SERIES TY-B HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS
WAX RETOUCHING STICK PART NUMBER SELECTION

Limited
Warranty

Ordering
Procedure

For warranty terms and conditions, visit


www.tyco-fire.com.

Contact your local distributor for availability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with
NPT Thread Connections
Specify: Series TY-B (specify SIN),
(specify K-factor), (specify Horizontal or
Vertical Sidewall) Sprinklers with (specify) temperature rating, (specify) finish or
coating, P/N (Refer to Table C)
Recessed Escutcheon
Specify: Style 10 Recessed Escutcheon
with (specify) finish, P/N (specify*)
* Refer to Technical Data Sheet TFP770

Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
Wax Sticks
(for retouching wrench-damaged
wax coating)
Specify: (specify color, below) Colored
Coded Wax Stick for retouching (specify temperature rating) temperature-rated
Series TY-B Sprinklers, P/N (specify)
Note: Each wax stick is suitable for
retouching up to 25 sprinklers.
Note: The wax used for 286F (141C)
sprinklers is the same as for 200F (93C)
sprinklers, and, therefore, the 286F (141C)
sprinkler is limited to the same maximum
ceiling temperature as the 200F (93C)
sprinkler (i.e., 150F [66C]).

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2015 Tyco Fire Products, LP. All rights reserved.
TEFLON is trademark of The DuPont Corporation

Worldwide
www.tyco-fire.com
Contacts

Model EC-25 (CMDA and CMSA Applications)


25.2 (360) K-factor (360) Upright Sprinkler
Extended Coverage
General
Description
The TYCO Model EC-25 Extended
Coverage (EC) 25.2K Upright Sprinkler is a UL Listed, standard response,
extended coverage Control Mode
Density Area (CMDA) sprinkler for
storage applications. It is also FM
Approved as a quick response,
extended coverage Control Mode
Density Area (CMDA) sprinkler and
as a Control Mode Specific Application (CMSA) sprinkler, as well as
FM Approved for storage and non-storage applications.
In addition, these sprinklers may be
used in accordance with the new
Chapter 21 of the 2013 edition of
NFPA 13. As such, tables 21.2.2 and
21.3.2 of NFPA 13 may be utilized for
design options. When used in accordance with NFPA Chapter 21, smoke
vents and draft curtains are not required
as specified in the 2015 edition of the
International Building Code (IBC) and
International Fire Code (IFC) for CMSA
sprinklers with an RTI of 50 or less and a
design of 12 or fewer sprinklers.
These sprinklers offer a maximum coverage area of 196 ft. (18,2 m), which
is almost double the area offered by
standard coverage sprinklers used for
similar applications.
The Model EC-25 Upright Sprinklers
comply with the criteria for the protection of retail stores as described in the
2013 Edition of NFPA 13, Section 20.3.

Where the FM Approval is utilized, the


Model EC-25 Upright Sprinkler has
successfully undergone full-scale fire
testing at FM Global for ceiling-only
storage and non-storage applications. When used in conformance with
applicable FM Global Property Loss
Prevention Data Sheets, the Model
EC-25 Sprinkler provides low hydraulic demand, the spacing advantages of
extended coverage, and the obstruction benefits of an upright sprinkler.
For more information on applications
and benefits of the Model EC-25 Sprinkler, refer to the available white papers
at www.tyco-fire.com.
NOTICE
The Model EC-25 Upright Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applicable standards of the National Fire Protection Association (NFPA), in addition
to the standards of any other authorities
having jurisdiction (e.g., FM Global).
Failure to do so may impair the performance of these devices.
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Contact the installing contractor or sprinkler manufacturer with any
questions.

Sprinkler
Identification
Number (SIN)
TY9128

Approvals
UL and C-UL Listed: CMDA
(Standard Response)
FM Approved: CMDA and CMSA
(Quick Response)
NYC Approved under MEA 355-01-E
(Approvals only apply to the service
conditions indicated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
1 Inch NPT or ISO 7-R1
Discharge Coefficient
K=25.2 gpm/psi1/2 (362,9 lpm/bar1/2)
Temperature Ratings
165F (74C) and 212F (100C)
Maximum Coverage Area
196 ft. (18,2 m)
Finish
Natural Brass
Physical Characteristics

Frame Brass
Deflector Copper
Compression Screw Stainless Steel
Hook MONEL
Strut MONEL
Link Assembly Solder, Nickel
Button Brass
Sealing Assembly. . Beryllium Nickel w/TEFLON
Ejection Spring INCONEL
Deflector Nut Brass

IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 4

Technical
Data

Response Time Index (RTI)


Less than or equal to 50 (m-s)0.5

APRIL 2015

TFP213

TFP213
Page 2 of 4
3

TEMPERATURE
RATING

10

2-9/16" DIA.
(65,0 mm)

2
1-
2-
3-
4-
5-
6-
7-
8-
9-
10-

Frame
Deflector
Compression Screw
Hook
Strut
Link Assembly
Button
Gasketed Spring Plate
Ejection Spring
Deflector Nut

3-3/4"
(95,3 mm)

9/16"
(14,3 mm)
NOMINAL
MAKE-IN

6
9

WRENCH
FLATS

* ISO 7-R1 pipe thread can be


provided on special request.

7
1

1" NPT *

FIGURE 1
MODEL EC-25 UPRIGHT SPRINKLER, 25.2K
EXTENDED COVERAGE

Operation

The maximum coverage area per


sprinkler is 196 ft. (18,2 m).

The fusible link assembly is comprised of two link halves that are joined
together by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate, allowing the sprinkler to activate and flow water.

The maximum distance between


sprinklers is 15 feet (4,6 m) when
the coverage area does not exceed
144 ft. (13,4 m), and the maximum
distance between sprinklers is 14
feet (4,3 m) when the coverage area
does not exceed 196 ft (18,2 m).

Design
Criteria

The minimum distance between


sprinklers is 8 feet (2,44 m).

UL and C-UL Listing Criteria


NFPA 13, Chapters 12 thru 20
Density / Area Design
The TYCO Model EC-25 Extended
Coverage Upright Sprinklers (TY9128)
are UL and C-UL Listed for installation
in accordance with the extended coverage upright spray sprinkler requirements of NFPA 13 or other applicable
NFPA standards when used in conjunction with the following guidelines:
Suitable for the protection of extra
hazard and high-piled storage
occupancies where area/density
design criteria are provided
Suitable for unobstructed or
noncombustible
obstructed
construction
The Model EC-25 Sprinklers having
been specifically tested and Listed
for noncombustible obstructed
construction are suitable for use
within trusses or bar joists having
noncombustible web members
greater than 1 inch (25,4 mm) when
applying the 4 times obstruction
criteria rule defined under Obstructions to Sprinkler Discharge Pattern
Development.

The minimum flow requirement is


based on the design density applied
over the actual coverage area per
sprinkler.
For example: when sprinkler
spacing is 14
ft. x 12
ft.
-
6
in.
(4,3 m x 3,8 m) or 175 ft (16,3 m),
and the design density is 0.6 gpm/ft.
(24,4 mm/min), the sprinkler design
flow rate is 105 gpm (397 lpm) and
the required design pressure is
17.4 psi (1,2 bar).
The minimum clearance between
the deflector and the top of
storage is 36 inches (0,9 m). For
clearances of 36 inches (0,9 m)
up to 48 inches (1,21 m), the
minimum design pressure is 22 psi
(1,52 bar). For clearances of 48
inches (1,21 m) and greater, the
minimum design pressure is established by the minimum flow requirement. However, the pressure can
never be less than 7 psi (0,5 bar).
Ordinary and intermediate temperature rated Model EC-25 Sprinklers have been investigated for
use in high-piled storage occupancies at the hydraulic demand
normally associated with high
temperature sprinklers. As such,
the Model EC-25 Sprinklers are

listed storage sprinklers having a


K-factor greater than 11.2 (161,4)
and having ordinary and intermediate temperature ratings (i.e., 165F
or 74C and 214F or 101C). Consequently, the Model EC-25 Sprinklers, in accordance with NFPA 13,
may be used in conjunction with the
density curves for high temperature
sprinklers.
NFPA obstruction rules for Extended
Coverage Sprinklers must be utilized.
System Type
Wet pipe, dry pipe, and preaction
systems are acceptable.

FM Approval Criteria
FM Loss Prevention Data Sheets
2-0, 3-26, and 8-9
TYCO Model EC-25 Extended Coverage 25.2K Upright Sprinklers (TY9128)
are FM Approved to be utilized in accordance with the following guidelines.
Application
The Model EC-25 Extended Coverage Upright Sprinklers are
FM Approved ceiling-level Storage
Sprinklers for storage occupancy
hazards and other similar high heat
release type fires. When compared with
other FM Approved Storage Sprinklers,
the Model EC-25 Sprinkler provides low
hydraulic demand, the spacing advantages of extended coverage, and the
FM Global obstruction benefits of an
upright sprinkler.
Model EC-25 Sprinklers should be
used in conformance with applicable
FM Global Property Loss Prevention
Data Sheets.

TFP213
Page 3 of 4
Hydraulic Design
To determine the hydraulic design for
the Model EC-25 Sprinkler refer to the
applicable FM Global Property Loss
Prevention Data Sheet.
System Type
Wet pipe systems only
Sprinkler Spacing
The maximum coverage area per
sprinkler is 196 ft. (18,2m). The
minimum coverage area per sprinkler is
100 ft. (9,3 m). The maximum distance
between sprinklers is 14 feet (4,3 m).
The minimum distance between sprinklers is 10 feet (3,05 m).
Note: When a wall or obstruction
makes a minimum spacing of 10 feet
(3,05 m) impossible, consult FM Global
Property Loss Prevention Data Sheet
2.0 for applicable guidelines.
Sprinkler Location
Locate sprinklers with respect to
the ceiling/roof in accordance with
FM Global Property Loss Prevention
Data Sheet 2.0.
Obstructions
Follow the obstruction requirements
as detailed in FM Global Property Loss
Prevention Data Sheet 2.0.
Other Details
All other design details should be in
accordance with FM Global Property
Loss Prevention Data Sheet 2.0 as well
as any other applicable FM Global Data
Sheet.
NFPA 13, Chapter 21
Alternative System Design
(CMSA)
TYCO Model EC-25 Extended Coverage Upright Sprinklers (TY9128) have
successfully undergone large-scale
fire tests at FM Global to comply with
Chapter 21 of NFPA 13, 2013 Edition.
As such, Tables 21.2.2 and 21.3.2 of
NFPA 13 may be utilized for design
options with the Model EC-25 Upright
Sprinklers for providing ceiling-only
protection.
This allows for the protection of Palletized, Solid Piled, Bin Box, Shelf, or
Back-to-Back Shelf Storage as well
as Single, Double, and Multiple Row
Open Rack protection of up to 30 feet
(9,1 m) of Cartoned Unexpanded Group
A Plastic Commodities in a maximum
35 feet (11 m) ceiling condition with
extended spacing up to 196 ft.2 while
maintaining very reasonable flow and
pressure requirements. Pipe sizes as
well as water supply requirements
can now be kept to a minimum when
compared to other design methods for
high piled storage challenges. Refer to
Tables A and B of this data sheet for
specific flow, pressure, and number of
sprinklers to be calculated.

When used in accordance with NFPA


Chapter 21, smoke vents and draft curtains are not required as specified in the
2015 edition of the International Building
Code (IBC) and International Fire Code
(IFC) for CMSA sprinklers with an RTI of
50 or less and a design of 12 or fewer
sprinklers.
Construction Type
In accordance with NFPA 13 for
Extended Coverage Sprinklers for High
Piled Storage.
Obstruction Criteria
Follow Sections 8.8.5.1, Extended
Coverage Obstruction Guidelines for
Sprinkler Discharge Pattern Development; 8.12.5.2 and 8.12.5.3, ESFR
Obstruction Criteria, for obstructions
that prevent the pattern from reaching
the hazard below.
Exception: When using the Upright
EC-25 Sprinkler, any continuous
obstruction 4 inches (100 mm) or
less shall be permitted to be ignored
in accordance with NFPA 13, section
21.5.3.2.3.
Deflector Distance below Ceiling
Follow NFPA 13, Section 8.8.4 for
allowed deflector distances below
ceiling.
Clearance to Storage
Minimum 36 inches from deflector to
top of storage required.
Maximum Distance
between Sprinklers
14 feet (4,3 m)
Minimum Distance
between Sprinklers
10 feet (3,0 m)

WRENCH
RECESS

"FITTING SIDE"
TOWARDS SPRINKLER
FITTING

FIGURE 2
W-TYPE 1
SPRINKLER WRENCH

Installation
TYCO Model EC-25 Extended Coverage 25.2K Upright Sprinklers are to
be installed in accordance with this
section.
Damage to the fusible Link Assembly
during installation can be avoided by
handling the sprinkler using only the
frame arms and the appropriate sprinkler wrench. Do not grip or apply any
force to the fusible Link Assembly.
Damaged sprinklers must be replaced
immediately.
A leak-tight 1 inch NPT sprinkler
joint should be obtained by applying a minimum-to-maximum torque of
20 to 30 lbs.-ft. (26,8 to 40,2 Nm).
Higher levels of torque may distort the
sprinkler inlet with consequent leakage
or impairment of the sprinkler.
Note: Install the Model EC-25 Upright
Sprinkler in the upright position.
Step 1. With pipe thread sealant
applied, hand-tighten the sprinkler into
the sprinkler fitting. Do not apply any
force to the Link Assembly, and handle
the Model EC-25 Sprinkler only by the
Frame arms.
Step 3. Wrench-tighten the Model
EC-25 Sprinkler using only the W-Type
1 Sprinkler Wrench (Ref. Figure 2) and
by fully engaging (seating) the wrench
on the sprinkler wrench flats.
Step 4. After installation, inspect the
Link Assembly of each Model EC-25
Sprinkler for damage. In particular, verify that the Link Assembly and
Hook are positioned as illustrated in
Figure 1, and that the Link Assembly
has not been bent, creased, or forced
out of its normal position in any way.
Damaged sprinklers must be replaced
immediately.

TFP213
Page 4 of 4

Storage
Arrangement

Commodity
Class

Palletized,
Solid-Piled,
Bin Box,
Shelf, or
Back-to-Back
Shelf Storage

Class I thru
Class IV,
encapsulated
and unencapsulated,
and cartoned
non-expanded
plastics

Max.
Storage
Height
Feet
(m)

Max.
Ceiling/
Roof
Height
Feet
(m)

Type of
System

25
(7,6)

30
(9,1)

Wet

30
(2,1)

14 x 14
(4,3 x 4,3)

250
(950)

30
(9,1)

35
(11)

Wet

40
(2,8)

12 x 12
(3,7 x 3,7)

250
(950)

30
(9,1)

35
(11)

Wet

40
(2,8)

14 x 14
(4,3 x 4,3)

500
(1900)

1.5

Min.
Max.
Hose
Stream
Number Operating Coverage
Area
Allowance
of Design Pressure
Sprinklers
psi
Ft. x Ft.
gpm
(bar)
(m x m)
(lpm)

Water
Supply
Duration
Hours

TABLE A
NFPA 13, CHAPTER 21 ALTERNATIVE SYSTEM DESIGN
PALLETIZED, SOLID-PILED, BIN BOX, SHELF, OR BACK-TO-BACK SHELF STORAGE OF
CLASSES I - IV AND CARTONED NON-EXPANDED PLASTIC COMMODITIES

Storage
Arrangement

Commodity
Class

Sprinkler
protection
criteria for
open-frame
rack storage

Class I thru
Class IV,
encapsulated
and unencapsulated,
and cartoned nonexpanded plastics

Max.
Storage
Height
Feet
(m)

Max.
Ceiling/
Roof
Height
Feet
(m)

Type of
System

Number
of Design
Sprinklers

Min.
Operating
Pressure
psi
(bar)

25
(7,6)

30
(9,1)

Wet

30
(2,1)

14 x 14
(4,3 x 4,3)

250
(950)

30
(9,1)

35
(11)

Wet

40
(2,8)

12 x 12
(3,7 x 3,7)

250
(950)

30
(9,1)

35
(11)

Wet

40
(2,8)

14 x 14
(4,3 x 4,3)

500
(1900)

1.5

Max.
Hose
Coverage
Stream
Area
Allowance
Ft. x Ft.
gpm
(m x m)
(lpm)

Water
Supply
Duration
Hours

TABLE B
NFPA 13, CHAPTER 21 ALTERNATIVE SYSTEM DESIGN
OPEN-FRAME RACK (SINGLE, DOUBLE, AND MULTIPLE ROW) STORAGE OF
CLASSES I - IV AND CARTONED NON-EXPANDED PLASTIC COMMODITIES

Care and
Maintenance
TYCO Model EC-25 Extended Coverage 25.2K Upright Sprinklers must be
maintained and serviced in accordance
with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this decision.
Inspection, testing, and maintenance
must be performed as indicated below
and in accordance with the local
requirements and/or national codes.
Any impairment must be immediately
corrected.
The owner is responsible for the inspection, testing, and maintenance of their
fire protection system and devices in

compliance with this document, as well


as with the applicable standards of any
authorities having jurisdiction. Contact
the installing contractor or product
manufacturer with any questions.

Sprinkler Assemblies
Specify: Model EC-25 Extended Coverage 25.2K Upright Sprinklers (TY9128),
(specify temperature rating), with
Natural Brass finish, P/N (specify):

Automatic sprinkler systems are recommended to be inspected, tested,


and maintained by a qualified Inspection Service in accordance with local
requirements and/or national codes.

165F (74C) . . . . . . . . . . . . . . P/N 58-450-1-165


212F (100C) . . . . . . . . . . . . . P/N 58-450-1-214

Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.

Ordering
Procedure

Special Order
Sprinkler Assemblies with
ISO 7-R 1 Thread Connection
Specify: Model EC-25 Extended Coverage 25.2K Upright Sprinklers (TY9128)
with ISO 7-R 1 thread connection,
(specify temperature rating), with
Natural Brass finish, P/N (specify):
165F (74C) . . . . . . . . . . . . . . P/N 58-451-1-165
212F (100C) . . . . . . . . . . . . . P/N 58-451-1-214

Sprinkler Wrench
Specify W-Type 1 Sprinkler Wrench,
P/N 56-872-1-025

Contact your local distributor for availability. When placing an order, indicate
the full product description and part
number (P/N).

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2015 Tyco Fire Products, LP. All rights reserved.
TEFLON is trademark of DuPont Corporation.

Worldwide
www.tyco-fire.com
Contacts

Model ESFR-25
25.2 K-factor Pendent Sprinkler
Early Suppression, Fast Response
General
Description
TYCO Model ESFR-25 Pendent Sprinklers are Early Suppression, Fast
Response (ESFR) sprinklers having a
nominal K-factor of 25.2 (Ref. Figure 1).
They are suppression-mode sprinklers
that are especially advantageous as a
means of eliminating the use of in-rack
sprinklers when protecting high-piled
storage.
The Model ESFR-25 Sprinklers are primarily used for ceiling-only sprinkler
protection of (but not limited to) the following storage applications:
most encapsulated or non-encapsulated common materials including
cartoned, unexpanded plastics
uncartoned (exposed) expanded
plastics in accordance with NFPA 13
and FM Global standards
some storage arrangements of rubber tires, roll paper, flammable liquids, aerosols, and automotive
components
For more specific criteria, refer to
Table A as well as the applicable design
standard.
The Model ESFR-25 Pendent Sprinklers provide the system designer
with hydraulic and sprinkler placement options not presently available to
the traditional ESFR sprinklers having
nominal K-factors of 14.0 and 16.8. In
particular, the Model ESFR-25 Sprinkler has been designed to operate at
substantially lower-end head pres-

IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 4

sures, as compared to ESFR Sprinklers


having nominal K-factors of 14.0 and
16.8. This feature offers flexibility when
sizing system piping, as well as possibly reducing or eliminating the need for
a system fire pump.
Also, Model ESFR-25 Sprinklers
permit use of a maximum deflector-to-ceiling distance of 18 inches
(460 mm) versus 14 inches (356 mm).
Additionally, a storage arrangement of
40 ft. (12,2 m) with a ceiling height of
45 ft. (13,7 m) does not require in-rack
sprinklers as do other ESFR Sprinklers having nominal K-factors of
14.0 and 16.8.
The Model ESFR-25 Sprinklers are
listed by Underwriters Laboratories (UL) for specific applications
with a maximum storage height of
43 ft. (13,1 m) with a maximum ceiling
height of 48 ft. (14,6 m) without the
requirement for in-rack sprinklers.
Refer to the Specific Application Listing
(UL) for the design criteria.
Applications for the TYCO ESFR Sprinklers are expanding beyond currently
recognized installation standards. For
information on research fire tests (e.g.,
with flammable liquids and aerosols)
that may be acceptable to an authority having jurisdiction, contact Tyco Fire
Protection Products (TFPP) Technical
Services.
NOTICE
The Model ESFR-25 Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applicable standards of the National Fire Protection Association (NFPA), in addition
to the standards of any authorities
having jurisdiction (e.g., FM Global).
Failure to do so may impair the performance of these devices.

In all cases, the appropriate NFPA or


FM Global installation standard, or
other applicable standard, must be
referenced to ensure applicability and
to obtain complete installation guidelines. The general guidelines in this
data sheet are not intended to provide
complete installation criteria.

Sprinkler
Identification
Number (SIN)
TY9226
TY9226 is a re-designation for Central
SIN 9226, Gem SIN G8441, and Star
SIN S8010.

The owner is responsible for maintaining their fire protection system


and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.

APRIL 2015

TFP312

TFP312
Page 2 of 4

1
1" NPT

7
Components:
1 - Frame
2 - Deflector
3 - Compression
Screw
4 - Hook
5 - Strut
6 - Link Assembly
7 - Button
8 - Sealing
Assembly
9 - Ejection Spring

1-13/16"
(46,0 mm)

9/16"
(14,3 mm)
NOMINAL
MAKE-IN

9
6
3-13/16"
(96,8 mm)

5
4

THERMAL
SENSING
ELEMENT
WRENCH
FLATS

3
2

TEMPERATURE
RATING
2" (50,8 mm)

FIGURE 1
MODEL ESFR-25 PENDENT SPRINKLER, 25.2K
EARLY SUPPRESSION, FAST RESPONSE

Technical
Data
Approvals
UL and C-UL Listed
FM Approved
VdS Approved
NYC Approved under MEA 356-01-E
LPCB Certified (Cert. Nos. 094b
and 007l)
CE Certified (Certificate of Conformity
1725-CPD-H0010)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
1 Inch NPT or ISO 7-R 1
Discharge Coefficient
K=25.2 gpm/psi1/2 (362,9 lpm/bar1/2)
Temperature Ratings
165F (74C) and 212F (100C)
Finish
Natural Brass
Physical Characteristics
Frame Brass
Deflector Bronze
Compression Screw Stainless Steel
Hook MONEL
Strut MONEL
Link Assembly Solder, Nickel
Button Brass
Sealing Assembly. . Beryllium Nickel w/TEFLON
Ejection Spring INCONEL

Design
Criteria

The following general guidelines provided for the TYCO Model ESFR-25

Pendent Sprinklers can be used for a


quick reference.
The National Fire Protection Association (NFPA) and FM Global (FM Approvals) provide installation standards that
must be used to properly design an
automatic sprinkler system utilizing
Early Suppression, Fast Response
(ESFR) Sprinklers. The guidelines provided by NFPA and FM Global may
differ. Consequently, the appropriate standard must be used for a given
installation.
In all cases, the appropriate NFPA or
FM Global installation standard must
be referenced to ensure applicability and to obtain complete installation
guidelines.
The following general guidelines are not
intended to provide complete installation criteria.
In addition to this technical data sheet,
the following data sheets describe
other TYCO ESFR Sprinklers:
TFP315
Model ESFR-17 (TY7226)
K=16.8 Pendent Sprinkler
TFP316
Model ESFR-17 (TY7126)
K=16.8 Upright Sprinkler
TFP318
Model ESFR-1 (TY6226)
K=14.0 Pendent Sprinkler
System Type
Wet Pipe
Roof Construction
Unobstructed or obstructed con-

"FITTING SIDE"
TOWARDS SPRINKLER
FITTING

WRENCH
RECESS

FIGURE 2
W-TYPE 1
SPRINKLER WRENCH
struction (e.g., smooth ceiling, bar
joists, beam and girder, and so forth).
Where the depths of the solid structural members (e.g., beams and stem)
exceed 12 inches (302 mm), install
ESFR Sprinklers in each channel
formed by the structural members.
Ceiling Slope
Maximum 2 inch rise for 12 inch run
(16.7%)
Maximum Coverage Area
100 ft.2 (9,3 m2)
In some cases, the installation standards permit a greater coverage area.
Minimum Coverage Area
64 ft.2 (5,8 m2) per
NFPA 13 / FM Global 2-0
Maximum Spacing

TFP312
Page 3 of 4

Storage Type

NFPA

FM Global

Open Frame (i.e., no solid shelves)


Single, Double, Multiple-Row, or Portable Rack Storage of
Class I-IV and Group A or B Plastics

Refer to NFPA 13
Chapters 16 and 17

Refer to FM Global
2-0 and 8-9

Solid Pile or Palletized Storage of


Class I-IV and Group A or B Plastics

Refer to NFPA 13
Chapters 14 and 15

Refer to FM Global
2-0 and 8-9

Idle Pallet Storage

Refer to NFPA 13
Chapter 12

Refer to FM Global
2-0, 8-9, and 8-24

Rubber Tire Storage

Refer to NFPA 13
Chapter 18

Refer to FM Global
2-0 and 8-9

Roll Paper Storage


(Refer to the Standard)

Refer to NFPA 13
Chapter 19

Refer to FM Global 8-21

Flammable/Ignitable Liquid Storage


(Refer to the Standard)

Refer to NFPA 30

Refer to FM Global 7-29

Refer to NFPA 30B

Refer to FM Global 7-31

Refer to NFPA 13
Chapter 20

N/A

Aerosol Storage
(Refer to the Standard)
Automotive Components in Portable Racks
(Control mode only; refer to the Standard)
N/A Not Applicable

TABLE A
MODEL ESFR-25 PENDENT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
12 feet (3,7 m) for building heights up to
30 feet (9,1 m)
10 feet (3,1 m) for building heights
greater than 30 feet (9,1 m). In some
cases, installation standards permit a
greater spacing.

Sprinkler Position
Pendent:
Frame arms aligned with pipe
Deflectors parallel with ceiling or roof
System Type
Wet Pipe only

Minimum Spacing
8 feet (2,4 m)

Maximum Area of Coverage


100 ft.2 (9,3 m2)

Minimum Clearance to Commodity


36 inches (914 mm)

In some cases, the installation standards permit a greater coverage area.

NFPA
Deflector-to-Ceiling Distance
6 to 18 inches (152 to 457 mm)

Minimum Area of Coverage


64 ft.2 (5,8 m2) according to NFPA 13

FM Global
Centerline of Thermal Sensing
Element-to-Ceiling Distance
Refer to FM Global 2-0 for Storage
Sprinklers.

Specific
Application
Listing (UL)
TYCO Model ESFR-25 Pendent Sprinklers are listed by Underwriters Laboratories (UL) for Specific Applications
with a ceiling height greater than
45 ft. (13,7 m) up to and including 48 ft. (14,6 m), and a storage
arrangement up to and including
43 ft. (13,1 m), the following guideline are provided for the TYCO Model
ESFR-25 Pendent Sprinklers:

Maximum Slope Ceiling


2 inch rise for 12 inch run (16.7%)
Maximum Spacing
10 feet (3,1 m)
In some cases, the installation standards permit a greater spacing.
Minimum Spacing
8 feet (2,4 m)
Temperature Rating
212F (100C)
Deflector Distance from Walls
Minimum of 4 inches (102 mm) from
walls but no more than 1/2 the allowable distance permitted between
sprinklers
Deflector to Top of Storage
Minimum of 36 inches (914 mm)
Deflector-to-Ceiling Distance
6 to 14 inches (152 to 356 mm)

Maximum Ceiling Height


48 feet (14,6 m)
Maximum Storage Height
43 feet (13,1 m)
Storage Arrangement
Palletized, solid piled, open frame,
single row, or double row
Commodity
Class I-IV
Cartoned, unexpanded plastic
Sprinkler System Design
NFPA 13 for ESFR Sprinklers based
upon 45 psi (3,1 bar) design pressure,
169 gpm (640 lpm) with 12 sprinkler
remote area
Minimum Aisle Width
8 feet (2,4 m)

Operation
The fusible link assembly is comprised of two link halves that are joined
together by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate, activating the sprinkler and
flowing water.

TFP312
Page 4 of 4

Installation
TYCO Model ESFR-25 Early Suppression, Fast Response 25.2K Pendent
Sprinklers must be installed in accordance with this section.
General Instructions
Damage to the fusible Link Assembly during installation can be avoided
by handling the sprinkler by the frame
arms only (i.e., do not apply pressure
to the fusible Link Assembly), and by
using the appropriate sprinkler wrench.
Failure to do so can lead to an unstable
link assembly and premature activation
of the sprinkler. Damaged sprinklers
must be replaced.
A leak-tight 1 inch NPT sprinkler
joint should be obtained by applying a minimum-to-maximum torque of
20 to 30 lbs.-ft. (26,8 to 40,2 Nm).
Higher levels of torque can distort the
sprinkler inlet with consequent leakage
or impairment of the sprinkler.
Note: Install the Model ESFR-25
Pendent Sprinkler in the pendent position (Ref. Figure 2).
Step 1. With pipe thread sealant
applied, hand-tighten the sprinkler into
the sprinkler fitting. Do not apply pressure to the Link Assembly, and handle
the Model ESFR-25 Pendent Sprinkler
only by the Frame arms.
Step 2. Wrench-tighten the Model
ESFR-25 Pendent Sprinkler using only
the W-Type 1 Sprinkler Wrench (Ref.
Figure 2) and by fully engaging (seating)
the wrench on the sprinkler wrench
flats (Ref. Figure 1).
Step 4. After installation, inspect the
Link Assembly of each Model ESFR-25
Pendent Sprinkler for damage. In particular, verify that the Link Assembly
and Hook are positioned as illustrated
in Figure 1, and that the Link Assembly is not bent, creased, or forced out
of normal position in any way. Replace
damaged sprinklers.

Care and
Maintenance
TYCO Model ESFR-25 Early Suppression, Fast Response 25.2K Pendent
Sprinklers must be maintained and serviced in accordance with this section.

main control valve for maintenance


work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and notify all personnel who may be
affected by this action.

Sprinklers which are found to be


leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprinklers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler that has a cracked bulb or that has
lost liquid from its bulb (Ref. Installation section).

Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product name and part number
(P/N).
Sprinkler Assemblies
Specify: Model ESFR-25 Early Suppression, Fast Response 25.2K
Pendent Sprinklers (TY9226), (specify
temperature rating), with Natural Brass
finish, P/N (specify):
165F (74C) . . . . . . . . . . . . . . P/N 58-441-1-165
212F (100C) . . . . . . . . . . . . . P/N 58-441-1-214

Special Order
Sprinkler Assemblies with
ISO 7-1 Thread Connection
Specify: Model ESFR-25, Early Suppression, Fast Response 25.2K
Pendent Sprinklers (TY9226) with
ISO 7-1 thread connection, (specify
temperature rating), with Natural Brass
finish, P/N (specify):
165F (74C) . . . . . . . . . . . . . . P/N 58-442-1-165
212F (100C) . . . . . . . . . . . . . P/N 58-442-1-214

Sprinkler Wrench
Specify: W-Type 1 Sprinkler Wrench,
P/N 56-872-1-025

The owner is responsible for the


inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Association (e.g., NFPA 25), in addition to
the standards of any authorities having
jurisdiction. Contact the installing contractor or product manufacturer with
any questions.
Automatic sprinkler systems are recommended to be inspected, tested,
and maintained by a qualified Inspection Service in accordance with local
requirements and/or national codes.

Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.

Ordering

Before closing a fire protection system

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2015 Tyco Fire Products, LP. All rights reserved.
MONEL and INCONEL are trademark of Special Metals Corporation.
TEFLON is trademark of DuPont Corporation.

Worldwide
www.tyco-fire.com
Contacts

Model ESFR-17
16.8 K-factor Upright Sprinkler
Early Suppression, Fast Response
General
Description
TYCO Model ESFR-17 Upright Sprinklers are Early Suppression, Fast
Response (ESFR) sprinklers having a
nominal K-factor of 16.8 (Ref. Figure 1).
They are suppression mode sprinklers
that are especially advantageous as a
means of eliminating in-rack sprinklers
when protecting high-piled storage.
Model ESFR-17 Sprinklers are primarily
used for ceiling-only sprinkler protection of (but not limited to) the following
storage applications:
most encapsulated or non-encapsulated common materials including
cartoned, unexpanded plastics
cartoned, expanded plastics
some storage arrangements of
rubber tires and roll paper
For more specific criteria, refer to Table
A in this technical data sheet as well as
the applicable design standard.
The Model ESFR-17 Upright Sprinklers provide the system designer with
an upright option to the traditional
pendent ESFR Sprinklers. With a K-factor of 16.8, Model ESFR-17 Sprinklers
provide system designers with hydraulic and sprinkler placement options not
presently available to traditional ESFR
Sprinklers having a K-factor of 14.0. In
particular, the Model ESFR-17 Upright
Sprinklers are designed to operate at
substantially lower-end head pressures
compared to ESFR Sprinklers with 14.0
K-factors. This feature offers flexibility

IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 4

when sizing system piping and positioning the system piping with respect
to the ceiling.
Applications for the TYCO ESFR Sprinklers are expanding beyond currently
recognized installation standards. For
information on research fire tests that
may be acceptable to an authority
having jurisdiction, contact Tyco Fire
Protection Products (TFPP) Technical
Services.
NOTICE
The Model ESFR-17 Upright Sprinklers
described herein must be installed and
maintained in compliance with this document, as well as with the applicable
standards of the National Fire Protection Association (NFPA), in addition to
the standards of any authorities having
jurisdiction (e.g., FM Global). Failure to
do so may impair the performance of
these devices.
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.
In all cases, the appropriate NFPA or
FM Global installation standard must
be referenced to ensure applicability and to obtain complete installation guidelines. The general guidelines
in this data sheet are not intended to
provide complete installation criteria.

Sprinkler
Identification
Number (SIN)
TY7126

APRIL 2015

Technical
Data
Approvals
FM Approved
CE Certified (Certificate of Conformity
1725-CPD-H0012)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
3/4 Inch NPT or ISO 7-R 3/4
Discharge Coefficient
K=16.8 gpm/psi1/2 (241,9 lpm/bar1/2)
Temperature Ratings
165F (74C) and 212F (100C)
Finish
Natural Brass
Physical Characteristics

Frame Brass
Deflector Copper
Compression Screw Stainless Steel
Hook MONEL
Strut MONEL
Link Assembly Solder, Nickel
Button Brass
Sealing Assembly. . Beryllium Nickel w/TEFLON
Ejection Spring INCONEL
Deflector Nut Brass

TFP316

TFP316
Page 2 of 4
2-9/16" DIA.
(65,0 mm)
TEMPERATURE
RATING

10
Components:
1 - Frame
2 - Deflector
3 - Compression
Screw
4 - Hook
5 - Strut
6 - Link Assembly
7 - Button
8 - Sealing
Assembly
9 - Ejection Spring
10 - Deflector Nut

2
3
WRENCH
FLATS

THERMAL
SENSING
ELEMENT

3-5/8"
(92,1 mm)

5
6

1/2"
(12,7 mm)
NOMINAL
MAKE-IN

1-5/8"
(41,3 mm)

3/4" NPT

FIGURE 1
MODEL ESFR-17 UPRIGHT SPRINKLER, 16.8K
EARLY SUPPRESSION, FAST RESPONSE

Design
Criteria
The following general guidelines provided for the TYCO Model ESFR-17
Upright Sprinklers may be used for
quick reference.
The National Fire Protection Association (NFPA) and FM Global (FM Approvals) provide installation standards that
must be used to properly design an
automatic sprinkler system utilizing
Early Suppression, Fast Response
(ESFR) Sprinklers. The guidelines provided by NFPA and FM Global may
differ; consequently, the appropriate
standard must be used for a given
installation.
In all cases, the appropriate NFPA or
FM Global installation standard must
be referenced to ensure applicability and to obtain complete installation
guidelines, since the following general
guidelines are not intended to provide
complete installation criteria.
In addition to this technical data sheet,
the following data sheets describe
other TYCO ESFR Sprinklers:
TFP312
Model ESFR-25 (TY9226)
K=25.2 Pendent Sprinkler
TFP315
Model ESFR-17 (TY7226)
K=16.8 Pendent Sprinkler
TFP318
Model ESFR-1 (TY6226)
K=14.0 Pendent Sprinkler

System Type
Wet Pipe
Roof Construction
Unobstructed or obstructed construction (e.g., smooth ceiling, bar joists,
beam and girder, and so forth)
Where the depths of the solid structural members (e.g., beams and stem)
exceed 12 inches (302 mm), install
ESFR Sprinklers in each channel
formed by the structural members.
Ceiling Slope
Maximum 2 inch rise for 12 inch run
(16.7%)
Maximum Coverage Area
100 ft.2 (9,3 m2)

FM Global
Centerline of Thermal Sensing
Element-to-Ceiling Distance
Refer to FM Global 2-0 for Storage
Sprinklers.
Obstructions below Upright ESFR
Sprinklers, Including Branchlines
Per the requirements of FM, obstructions below upright ESFR Sprinklers
can be ignored as follows
open-web bar joists or trusses
having chords no more than 4
inches (102 mm) wide
bridging or wind bracing no more
than 4 inches (102 mm) wide

In some cases, the installation standards permit a greater coverage area.

individual pipes and conduit 4 inches


(102 mm) diameter or less 3 inch
[DN80] pipe size or less will not
require sprigs)

Minimum Coverage Area


64 ft.2 (5,8 m2) per
NFPA 13 / FM Global 2-0

individual groups of smaller pipe


or conduit having a total width of 4
inches or less

Maximum Spacing
12 feet (3,7 m) for building heights
up to 30 feet (9,1 m)

Operation

10 feet (3,1 m) for building heights


greater than 30 feet (9,1 m)
Minimum Spacing
8 feet (2,4 m)
Minimum Clearance to Commodity
36 inches (914 mm)
NFPA 13
Deflector-to-Ceiling Distance
3 to 12 inches (76,2 to 304 mm)

The fusible link assembly is comprised of two link halves that are joined
together by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate, activating the sprinkler and
flowing water.

TFP316
Page 3 of 4

Storage Type

NFPA

FM Global

Open Frame (i.e., no solid shelves)


Single, Double, Multiple-Row, or Portable Rack Storage of
Class I-IV and Group A or B Plastics

Refer to NFPA 13
Chapters 16 and 17

Refer to FM 2-0 and 8-9

Solid Pile or Palletized Storage of


Class I-IV and Group A or B Plastics

Refer to NFPA 13
Chapters 14 and 15

Refer to FM 2-0 and 8-9

Idle Pallet Storage

Refer to NFPA 13
Chapter 12

Refer to FM 2-0, 8-9, and 8-24

Rubber Tire Storage

Refer to NFPA 13
Chapter 18

Refer to FM 2-0 and 8-9

Refer to Chapter 13
Chapter 19

Refer to FM 8-21

Flammable/Ignitable Liquid Storage


(Refer to the standard)

N/A

Refer to FM 7-29

Aerosol Storage
(Refer to the standard)

N/A

N/A

Automotive Components in Portable Racks


(Control mode only; refer to the standard)

N/A

N/A

Roll Paper Storage


(Refer to the standard)

N/A Not Applicable

TABLE A
MODEL ESFR-17 UPRIGHT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW

Installation
TYCO Model ESFR-17 Early Suppression, Fast Response 16.8K Upright
Sprinklers must be installed in accordance with this section.
General Instructions
Avoid damage to the fusible Link
Assembly during installation by using
the Frame arms only to handle the
sprinkler (i.e., do not apply pressure
to the fusible Link Assembly) and by
using the appropriate sprinkler wrench.
Failure to do so can lead to an unstable
link assembly and premature activation
of the sprinkler. Damaged sprinklers
must be replaced.
A leak-tight 3/4 inch NPT sprinkler
joint should be obtained by applying a minimum-to-maximum torque of
10 to 20 lbs.-ft. (13,4 to 26,8 Nm).
Higher levels of torque can distort the
sprinkler inlet with consequent leakage
or impairment of the sprinkler.

Note: Install the Model ESFR-17


Upright Sprinkler in the Upright position (Ref. Figure 2).

WRENCH
RECESS

Step 1. With pipe thread sealant


applied, hand-tighten the sprinkler into
the sprinkler fitting. Do not apply pressure to the Link Assembly, and handle
the Model ESFR-17 Sprinkler only by
the Frame arms.
Step 2. Wrench-tighten the Model
ESFR-17 Upright Sprinkler using only
the W-Type 21 Sprinkler Wrench (Ref.
Figure 2) and by fully engaging (seating)
the wrench on the sprinkler wrench
flats (Ref. Figure 1).
Step 3. After installation, inspect the
Link Assembly of each Model ESFR-17
Sprinkler for damage. In particular,
verify that the Link Assembly and Hook
are positioned as illustrated in Figure
1, and that the Link Assembly is not
bent, creased, or forced out of normal
position in any way. Replace damaged
sprinklers.

"FITTING SIDE"
TOWARDS SPRINKLER
FITTING

FIGURE 2
W-TYPE 21
SPRINKLER WRENCH

TFP316
Page 4 of 4

Care and
Maintenance

Limited
Warranty

Ordering
Procedure

TYCO Model ESFR-17 Early Suppression, Fast Response 16.8K Upright


Sprinklers must be maintained and serviced in accordance with this section.

For warranty terms and conditions, visit


www.tyco-fire.com.

Contact your local distributor for availability. When placing an order, indicate
the full product name and part number
(P/N).

Before closing a fire protection system


main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and notify all personnel who may be
affected by this action.

Sprinklers which are found to be


leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprinklers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler that has a cracked bulb or that has
lost liquid from its bulb (Ref. Installation Section).

Sprinkler Assemblies
Specify: Model ESFR-17 Early Suppression, Fast Response 16.8K Upright
Sprinklers (TY7126), (specify temperature rating), with Natural Brass finish,
P/N (specify):
165F (74C) . . . . . . . . . . . . . . P/N 58-447-1-165
212F (100C) . . . . . . . . . . . . . P/N 58-447-1-214

Special Order
Sprinkler Assemblies with
ISO 7-1 Thread Connection
Specify: Model ESFR-17 Early Suppression, Fast Response 16.8K Upright
Sprinklers (TY7126) with ISO 7-1 thread
connection, (specify temperature
rating), with Natural Brass finish, P/N
(specify):
165F (74C) . . . . . . . . . . . . . . P/N 58-448-1-165
212F (100C) . . . . . . . . . . . . . P/N 58-448-1-214

Sprinkler Wrench
Specify: W-Type 21 Sprinkler Wrench,
P/N 56-001-0-686

The owner is responsible for the


inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Association (e.g., NFPA 25), in addition to
the standards of any authorities having
jurisdiction. Contact the installing contractor or product manufacturer with
any questions.
Automatic sprinkler systems are
recommended to be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2015 Tyco Fire Products, LP. All rights reserved.
INCONEL and MONEL are trademark of Special Metals Corporation.
TEFLON is trademark of the DuPont Corporation.

Worldwide
www.tyco-fire.com
Contacts

Model ESFR-17
16.8 K-factor Pendent Sprinkler
Early Suppression, Fast Response
General
Description
TYCO Model ESFR-17 Pendent Sprinklers are Early Suppression, Fast
Response (ESFR) sprinklers having a
nominal K-factor of 16.8 (Ref. Figures
1 and 2). They are suppression mode
sprinklers that are especially advantageous as a means of eliminating in-rack
sprinklers when protecting high-piled
storage.
Model ESFR-17 Pendent Sprinklers are
primarily used for ceiling-only sprinkler
protection of (but not limited to) the following storage applications:
most encapsulated or non-encapsulated common materials including
cartoned, unexpanded plastics
cartoned, expanded plastics
uncartoned, unexpanded plastics
uncartoned, expanded plastics
some storage arrangements of
rubber tires, roll paper, and aerosols
For more specific criteria, refer to Table
1 in this technical data sheet as well as
the applicable design standard.
The Model ESFR-17 Pendent Sprinklers provide the system designer
with hydraulic and sprinkler placement options not presently available
to traditional ESFR Sprinklers having
a nominal K-factor of 14.0. In particular, Model ESFR-17 Pendent Sprinklers
are designed to operate at substantially lower-end head pressures, as

IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 4

compared to ESFR Sprinklers having


a nominal K-factor of 14.0. This feature
offers flexibility when sizing system
piping, as well as possibly reducing or
eliminating the need for a system fire
pump.
Applications for the ESFR-17 Pendent
Sprinklers are expanding beyond currently recognized installation standards. For information on research fire
tests (with flammable liquids and aerosols, for example) that may be acceptable to an authority having jurisdiction,
contact Tyco Fire Protection Products
(TFPP) Technical Services.
NOTICE
The Model ESFR-17 Pendent Sprinklers
described herein must be installed and
maintained in compliance with this document, as well as with the applicable
standards of the National Fire Protection Association (NFPA), in addition to
the standards of any authorities having
jurisdiction (e.g., FM Global). Failure to
do so may impair the performance of
these devices.
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.
In all cases, the appropriate NFPA or
FM Global installation standard, or
other applicable standard, must be referenced to ensure applicability and to
obtain complete installation guidelines.
The general guidelines in this technical
data sheet are not intended to provide
complete installation criteria.

Sprinkler
Identification
Number (SIN)

Technical
Data
Approvals
UL Listed
C-UL Listed
FM Approved
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
3/4 Inch NPT or ISO 7-R 3/4
Discharge Coefficient
K=16.8 gpm/psi1/2 (241,9 lpm/bar1/2)
Temperature Ratings
165F (74C) and 212F (100C)
Finish
Natural Brass
Physical Characteristics

Frame Brass
Deflector Bronze
Compression Screw Stainless Steel
Hook MONEL
Strut MONEL
Link Assembly Solder, Nickel
Button. . . . . . . . . . . . . . . . . . . . Phosphor Bronze
Sealing Assembly. . Beryllium Nickel w/TEFLON

TY7223

APRIL 2015

TFP317

TFP317
Page 2 of 4

Components:
1 - Frame
2 - Deflector *
3 - Compression Screw
4 - Hook
5 - Strut
6 - Link Assembly
7 - Button
8 - Sealing Assembly
* Temperature rating is indicated
on Deflector.
** ISO 7-R 3/4 pipe thread can be
provided on special request.

1
3/4" **
NPT

7
1-1/2"
(38,1 mm)

8
6

1/2"
2-3/8"
(12,7 mm)
(60,3 mm)
NOMINAL
MAKE-IN

4
5
3
2*

WRENCH
FLATS

THERMAL
SENSING
ELEMENT

FIGURE 1
MODEL ESFR-17 PENDENT SPRINKLER, 16.8K, 165F (74C)
EARLY SUPPRESSION, FAST RESPONSE
Components:
1 - Frame
2 - Deflector *
3 - Compression Screw
4 - Hook
5 - Strut
6 - Link Assembly
7 - Button
8 - Sealing Assembly
* Temperature rating is indicated
on Deflector.
** ISO 7-R 3/4 pipe thread can be
provided on special request.

1
3/4" **
NPT

7
1-1/2"
(38,1 mm)

8
6

1/2"
2-3/8"
(12,7 mm)
(60,3 mm)
NOMINAL
MAKE-IN

4
5
3
2*

WRENCH
FLATS

THERMAL
SENSING
ELEMENT

FIGURE 2
MODEL ESFR-17 PENDENT SPRINKLER, 16.8K, 212F (100C)
EARLY SUPPRESSION, FAST RESPONSE

Design
Criteria
The following general guidelines provided for the TYCO Model ESFR-17
Pendent Sprinklers can be used for a
quick reference.
The National Fire Protection Association (NFPA) and FM Global (FM Approvals) provide installation standards that
must be used to properly design an
automatic sprinkler system utilizing
Early Suppression, Fast Response
(ESFR) Sprinklers. The guidelines provided by NFPA and FM Global may
differ. Consequently, the appropriate standard must be used for a given
installation.
In all cases, the appropriate NFPA or
FM Global installation standard must
be referenced to ensure applicability and to obtain complete installation guidelines. The following general
guidelines are not intended to provide
complete installation criteria.

System Type
Wet Pipe
Roof Construction
Unobstructed or obstructed construction (e.g., smooth ceiling, bar joists,
beam and girder, etc.).
Where the depths of the solid structural members (e.g., beams and stem)
exceed 12 in. (302 mm), install ESFR
Sprinklers in each channel formed by
the structural members.
Ceiling Slope
Maximum 2 inch rise for 12 inch run
(16.7%)
Maximum Coverage Area
100 ft.2 (9,3 m2)
In some cases, the installation standards permit a greater coverage area.
Minimum Coverage Area
64 ft.2 (5,8 m2) per NFPA 13
Maximum Spacing
12 feet (3,7 m) for building heights up to
30 feet (9,1 m)
10 feet (3,1 m) for building heights
greater than 30 feet (9,1 m)

Minimum Spacing
8 feet (2,4 m)
Minimum Clearance to Commodity
36 inches (914 mm)
NFPA 13
Deflector-to-Ceiling Distance
6 to 14 inches (152 to 356 mm)
FM Global 2-0
Consult FM Global and/or FM Global
guidelines for allowable deflector-toceiling distances as well as thermal
sensing element-to-ceiling criteria.

Operation
The fusible link assembly is comprised of two link halves that are joined
together by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate, activating the sprinkler and
flowing water.

TFP317
Page 3 of 4

Storage Type

NFPA

Open Frame (i.e., no solid shelves)


Single, Double, Multiple-Row, or Portable Rack
Storage of Class I-IV and Group A or B Plastics

Refer to NFPA 13
Chapters 16 & 17

Solid Pile or Palletized


Storage of Class I-IV and Group A or B Plastics

Refer to NFPA 13
Chapters 14 & 15

Idle Pallet Storage

Refer to NFPA 13
Chapter 12

Rubber Tire Storage

Refer to NFPA 13
Chapter 18

Rolled Paper Storage


(Refer to the standard)

Refer to NFPA 13
Chapter 19

Flammable Liquid Storage


(Refer to the standard)

Refer to NFPA 30

Aerosol Storage
(Refer to the standard)
Automotive Components in Portable Racks
(Control mode only; refer to the standard)

N/A

TABLE 1
MODEL ESFR-17 PENDENT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW

TYCO Model ESFR-17 Early Suppression, Fast Response 16.8K Pendent


Sprinklers must be installed in accordance with this section.
General Instructions
Avoid damage to the fusible Link
Assembly during installation by using
only the Frame arms to handle the
sprinkler (i.e., do not apply pressure
to the fusible Link Assembly), and by
using the appropriate sprinkler wrench.
Failure to do so can lead to an unstable
link assembly and premature activation
of the sprinkler. Damaged sprinklers
must be replaced.
A leak-tight 3/4 inch NPT sprinkler
joint should be obtained by applying a minimum-to-maximum torque of
10 to 20 lbs.-ft. (13,4 to 26,8 Nm).
Higher levels of torque can distort the
sprinkler inlet with consequent leakage
or impairment of the sprinkler.

WRENCH
RECESS

FIGURE 3
W-TYPE 2
SPRINKLER WRENCH

WRENCH
FLATS

Refer to NFPA 30B

N/A Not Applicable

Installation

"FITTING SIDE"
TOWARD SPRINKLER
FITTING

Note: Install the Model ESFR-17


Pendent Sprinkler in the pendent position (Ref. Figures 3 and 4).
Step 1. With pipe-thread sealant
applied, hand-tighten the sprinkler into
the sprinkler fitting. Do not apply pressure to the Link Assembly, and handle
the Model ESFR-17 Sprinkler only by
the Frame arms.
Step 2. Wrench-tighten the Model
ESFR-17 Sprinkler using only the
W-Type 2 Sprinkler Wrench or the
W-Type 30 Sprinkler Wrench (Ref.
Figures 3 and 4), and by fully engaging (seating) the wrench on the sprinkler wrench flats (Ref. Figures 1 and 2).
Step 3. After installation, inspect the
Link Assembly of each Model ESFR-17
Sprinkler for damage. In particular,
verify that the Link Assembly and Hook
are positioned as illustrated in Figures
1 and 2, and that the Link Assembly
is not bent, creased, or forced out of
normal position in any way. Replace
damaged sprinklers.

WRENCH
RECESS
SOCKET
ACCEPTS
1/2" DRIVE

HEX
ACCEPTS
1" WRENCH

FIGURE 4
W-TYPE 30
SPRINKLER WRENCH

TFP317
Page 4 of 4

Care and
Maintenance

Limited
Warranty

Ordering
Procedure

TYCO Model ESFR-17 Early Suppression, Fast Response 16.8K Pendent


Sprinklers must be maintained and serviced in accordance with this section.

For warranty terms and conditions, visit


www.tyco-fire.com.

Contact your local distributor for availability. When placing an order, indicate
the full product name and part number
(P/N).

Before closing a fire protection system


main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this action.

Sprinkler Assemblies with


3/4 NPT Thread Connection
Specify: Model ESFR-17 Early Suppression, Fast Response 16.8K
Pendent Sprinklers (TY7223) with 3/4
NPT thread connection, (specify temperature rating), with Natural Brass
finish, P/N (specify):

Sprinklers which are found to be


leaking or exhibiting visible signs of
corrosion must be replaced.

165F (74C) . . . . . . . . . . . . . . P/N 58-455-1-165


212F (100C) . . . . . . . . . . . . . P/N 58-455-1-214

Automatic sprinklers must never be


painted, plated, coated, or otherwise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprinklers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler that has a cracked bulb or that has
lost liquid from its bulb (Ref. Installation section).

Special Order
Sprinkler Assemblies with
ISO 7-R 3/4 Thread Connection
Specify: Model ESFR-17 Early Suppression, Fast Response 16.8K Pendent
Sprinklers (TY7223) with ISO 7-R 3/4
thread connection, (specify temperature rating), with Natural Brass finish,
P/N (specify):
165F (74C) . . . . . . . . . . . . . . P/N 58-456-1-165
212F (100C) . . . . . . . . . . . . . P/N 58-456-1-214

Sprinkler Wrench
Specify: W-Type 2 Sprinkler Wrench,
P/N 56-872-1-001
Specify: W-Type 30 Sprinkler Wrench,
P/N 56-001-0-688

The owner is responsible for the


inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Association (e.g., NFPA 25), in addition to
the standards of any authorities having
jurisdiction. Contact the installing contractor or product manufacturer with
any questions.
Automatic sprinkler systems are recommended to be inspected, tested,
and maintained by a qualified Inspection Service in accordance with local
requirements and/or national codes.

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2015 Tyco Fire Products, LP. All rights reserved.
MONEL is trademark of Special Metals Corporation.
TEFLON is trademark of the DuPont Corporation.

Worldwide
www.tyco-fire.com
Contacts

Model ESFR-1
14.0 K-Factor Pendent Sprinkler
Early Suppression, Fast Response
General
Description
TYCO Model ESFR-1 Pendent Sprinklers are Early Suppression, Fast
Response (ESFR) sprinklers having
a nominal K-factor of 14.0. They are
suppression-mode sprinklers that are
especially advantageous as a means of
eliminating the use of in-rack sprinklers
when protecting high-piled storage.
Model ESFR-1 Sprinklers are primarily
designed for protection of the following
storage arrangements:
most encapsulated or non-encapsulated common materials including
cartoned, unexpanded plastics
some storage arrangements of
rubber tires, roll paper, flammable
liquids
For more specific criteria, refer to
Table A as well as the applicable design
standard.
Applications for the TYCO ESFR Sprinklers are expanding beyond currently
recognized installation standards. For
information on research fire tests (with
flammable liquids and aerosols, for
example) that may be acceptable to an
authority having jurisdiction, contact
the Tyco Fire Protection Products
(TFPP) Technical Services.

NOTICE
The Model ESFR-1 Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applicable standards of the National Fire Protection Association (NFPA), in addition
to the standards of any other authorities
having jurisdiction (e.g., FM Global).
Failure to do so may impair the performance of these devices.
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.
In all cases, the appropriate NFPA,
FM Global installation standard, or
other applicable standard, must be
referenced to ensure applicability and
to obtain complete installation guidelines. The general guidelines in this
data sheet are not intended to provide
complete installation criteria.

Sprinkler
Identification
Number (SIN)
TY6226
TY6226 is a re-designation for Central
SIN C6226, Gem SIN G8440, and Star
SIN S8000.

Approvals
UL and C-UL Listed
FM Approved
VdS Approved
NYC Approved under MEA 356-01-E
LPCB Approved (Cert. Nos. 094b and
007l)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
3/4 Inch NPT
Discharge Coefficient
K=14.0 gpm/psi1/2 (201,6 lpm/bar1/2)
Temperature Ratings
165F (74C) and 212F (100C)
Finish
Natural Brass
Physical Characteristics

Frame Brass
Deflector Bronze
Compression Screw Stainless Steel
Hook MONEL
Strut MONEL
Link Assembly Solder, Nickel
Button Brass
Ejection Spring INCONEL
Sealing Assembly. . Beryllium Nickel w/TEFLON

IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 4

Technical
Data

MARCH 2015

TFP318

TFP318
Page 2 of 4

Components:
1 - Frame
2 - Deflector
3 - Compression
Screw
4 - Hook
5 - Strut
6 - Link Assembly
7 - Button
8 - Sealing
Assembly
9 - Ejection Spring

3/4" NPT

7
8

1-1/2"
(38,1 mm)

1/2"
(12,7 mm)
NOMINAL
MAKE-IN

9
6

3-9/16"
(90,5 mm)

THERMAL
SENSING
ELEMENT

5
WRENCH
FLATS

4
3
2

1-7/8"
(47,6 mm)

TEMPERATURE
RATING

FIGURE 1
MODEL ESFR-1 PENDENT SPRINKLER, 14.0K
EARLY SUPPRESSION, FAST RESPONSE

Design
Criteria
The following general guidelines provided for the TYCO ESFR-1 Sprinklers
can be used for quick reference.
NOTICE
The National Fire Protection Association (NFPA) and FM Global (FM Approvals) provide installation standards that
must be used to properly design an
automatic sprinkler system utilizing
Early Suppression, Fast Response
(ESFR) Sprinklers. The guidelines provided by NFPA and FM may differ; consequently, the appropriate standard
must be used for a given installation.
In all cases, the appropriate NFPA or
FM installation standard must be referenced to assure applicability and to
obtain complete installation guidelines,
since the following general guidelines
are not intended to provide complete
installation criteria.
In addition to this technical data sheet,
the following data sheets describe
other TYCO ESFR Sprinklers:
TFP312
Model ESFR-25 (TY9226)
K=25.2 Pendent Sprinkler
TFP315
Model ESFR-17 (TY7226)
K=16.8 Pendent Sprinkler
TFP316
Model ESFR-17 (TY7126)
K=16.8 Upright Sprinkler

System Type
Wet Pipe

Operation

Roof Construction
Unobstructed or obstructed construction (e.g., smooth ceiling, bar joists,
beam and girder, and so forth)

The fusible link assembly is comprised of two link halves that are joined
together by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate, activating the sprinkler and
flowing water.

Where the depths of solid structural members (beams and stem, for
example) exceed 12 inches (302 mm),
install ESFR Sprinklers in each channel
formed by the structural members.
Ceiling Slope
Maximum 2-inch rise for 12-inch run
(16.7%)
Maximum Coverage Area
100 ft.2 (9,3 m2)
In some cases, the installation standards permit a greater coverage area.
Minimum Coverage Area
64 ft.2 (5,8 m2) per
NFPA 13 / FM Global 2-0
Maximum Spacing
12 feet (3,7 m) for building heights up to
30 feet (9,1 m)
10 feet (3,1 m) for building heights
greater than 30 feet (9,1 m)
Minimum Spacing
8 feet (2,4 m)
Minimum Clearance to Commodity
36 inches (914 mm)
NFPA
Deflector-to-Ceiling Distance
6 to 14 inches (152 to 356 mm)
FM Global
Centerline of Thermal Sensing
Element-to-Ceiling Distance
Refer to FM Global 2-0 for Storage
Sprinklers.

TFP318
Page 3 of 4

Storage Type

NFPA

FM Global

Open Frame (i.e., no solid shelves)


Single, Double, Multiple-Row, or Portable Rack Storage of
Class I-IV and Group A or B Plastics

Refer to NFPA 13
Chapters 16 and 17

Refer to FM Global
2-0 and 8-9

Solid Pile or Palletized Storage of


Class I-IV and Group A or B Plastics

Refer to NFPA 13
Chapters 14 and 15

Refer to FM Global
2-0 and 8-9

Idle Pallet Storage

Refer to NFPA 13
Chapter 12

Refer to FM Global
2-0, 8-9, and 8-24

Rubber Tire Storage

Refer to NFPA 13
Chapter 18

Refer to FM Global
2-0 and 8-9

Roll Paper Storage


(Refer to the standard)

Refer to NFPA 13
Chapter 19

Refer to FM Global
8-21

Flammable/Ignitable Liquid Storage


(Refer to the standard)

Refer to NFPA 30

Refer to FM Global
7-29

Refer to NFPA 30B

Refer to FM Global
7-31

N/A

N/A

Aerosol Storage
(Refer to the standard)
Automotive Components in Portable Racks
(Control mode only; refer to the standard)
N/A Not Applicable

TABLE A
MODEL ESFR-1 PENDENT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW

Installation
TYCO Model ESFR-1 Early Suppression, Fast Response 14.0K Pendent
Sprinklers must be installed in accordance with this section.
NOTICE
Damage to the fusible Link Assembly during installation can be avoided
by handling the sprinkler by the frame
arms only (i.e., do not apply pressure
to the fusible Link Assembly), and by
using the appropriate sprinkler wrench.
Failure to do so can lead to an unstable
link assembly and premature activation
of the sprinkler. Damaged sprinklers
must be replaced.

A leak-tight 3/4 inch NPT sprinkler


joint should be obtained by applying a minimum-to-maximum torque of
10 to 20 lbs.-ft. (13,4 to 26,8 Nm).
Higher levels of torque can distort the
sprinkler inlet with consequent leakage
or impairment of the sprinkler.

"FITTING SIDE"
TOWARDS SPRINKLER
FITTING

Note: Install the Model ESFR-1


Pendent Sprinkler in the pendent position (Ref. Figure 2).
Step 1. With pipe thread sealant
applied, hand-tighten the sprinkler into
the sprinkler fitting. Do not apply pressure to the Link Assembly, and handle
the Model ESFR-1 Sprinkler only by the
Frame arms.
Step 2. Wrench-tighten the Model
ESFR-1 Sprinkler using only the
W-Type 2 Sprinkler Wrench (Ref.
Figure 2) and by fully engaging (seating)
the wrench on the sprinkler wrench flats
(Ref. Figure 1).
Step 3. After installation, inspect the
Link Assembly of each Model ESFR-1
Sprinkler for damage. In particular, verify that the Link Assembly and
Hook are positioned as illustrated in
Figure 1, and that the Link Assembly
is not bent, creased, or forced out of
normal position in any way. Replace
damaged sprinklers.

WRENCH
RECESS

FIGURE 2
W-TYPE 2
SPRINKLER WRENCH

TFP318
Page 4 of 4

Care and
Maintenance

Limited
Warranty

Ordering
Procedure

TYCO Model ESFR-1 Early Suppression, Fast Response 14.0K Pendent


Sprinklers must be maintained and serviced in accordance with this section.

For warranty terms and conditions, visit


www.tyco-fire.com.

Contact your local distributor for availability. When placing an order, indicate
the full product name and part number
(P/N).
Sprinkler Assemblies
Specify: Model ESFR-14 Early Suppression, Fast Response 14.0K
Pendent Sprinklers (TY6226), (specify
temperature rating), with Natural Brass
finish, P/N (specify):

Before closing a fire protection system


main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Exercise care to avoid damage before,
during, and after installation. Never
paint, plate, coat, or otherwise alter
automatic sprinklers after they leave
the factory.

165F (74C) . . . . . . . . . . . . . . P/N 58-440-1-165


212F (100C) . . . . . . . . . . . . . P/N 58-440-1-214

Sprinkler Wrench
Specify: W-Type 2 Sprinkler Wrench,
P/N 56-872-1-001

Replace sprinklers that:


were modified or over-heated
were damaged by dropping, striking,
wrench twisting, wrench slippage, or
the like
are leaking or exhibiting visible signs
of corrosion
Responsibility lies with the owner for
the inspection, testing, and maintenance of their fire protection system
and devices in compliance with this
document, as well as with the applicable standards of the National Fire Protection Association (for example, NFPA
25), in addition to the standards of any
authorities having jurisdiction. Contact
the installing contractor or product
manufacturer with any questions.
Automatic sprinkler systems are
recommended to be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2015 Tyco Fire Products, LP. All rights reserved.
MONEL and INCONEL are trademark of Special Metals Corporation.
TEFLON is trademark of DuPont Corporation.

Worldwide
Contacts

www.tyco-fire.com

Model ESFR-17
16.8 K-factor Dry Type Pendent Sprinklers
Early Suppression, Fast Response
General
Description
TYCO Model ESFR-17 Dry Type
Pendent Sprinklers are Early Suppression, Fast Response (ESFR) sprinklers
having a nominal K-factor of 16.8.
They are suppression mode sprinklers
that are especially advantageous as a
means of eliminating in-rack sprinklers
when protecting high-piled box-in-box
refrigerated storage areas.
The Model ESFR-17 Dry Type Pendent
Sprinkler is FM Approved and has
successfully undergone full-scale fire
testing at FM Global, when used in conformance with applicable FM Global
Property Loss Prevention Data Sheets.
The Model ESFR-17 Dry Type Sprinkler consists of an ESFR sprinkler permanently secured to a sprinkler drop
featuring an inlet with both grooved
and threaded connections. The drop
between the inlet and sprinkler remains
dry until the sprinkler operates, allowing for a pendent sprinkler installation on a wet pipe sprinkler system
where the dry drop and sprinkler are
located in an area subjected to freezing
temperatures.
The Model ESFR-17 Dry Type Sprinklers are primarily used for ceiling only
sprinkler protection (i.e., no need for
in-rack sprinklers) and used to protect
solid piled, palletized, and rack storage
that is subject to freezing temperatures.
The water supply is provided from a
wet pipe system located outside of the
refrigerated storage area. The Model
ESFR-17 Dry Type Sprinklers feature

IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 8

all of the same design criteria as 16.8


K-factor ESFR Pendent Sprinklers, and
substantially lowers the end head pressure requirement as compared to the
14.0 K-factor ESFR Dry Type Pendent
Sprinklers.
Combining a 16.8 K-factor with a
dry-type sprinkler design, the Model
ESFR-17 Dry Type Sprinkler provides
the system designer with features that
offer flexibility when sizing system
piping, as well as possibly reducing or
eliminating the need for a system fire
pump when protecting high-piled boxin-box refrigerated storage areas.
The ESFR-17 Dry Type Sprinkler also
includes two Insulating Seal Assemblies that help seal the clearance space
around the sprinkler casing. The seal
assemblies are intended to slow the
exchange of air between the heated
area and the protected area to help
prevent humidity and temperature differential in the area around the sprinkler. Condensation on the sprinkler and
subsequent ice buildup on or around
the sprinkler can occur that might
damage the sprinkler or prevent proper
operation in a fire situation.
To install the Insulating Seal Assemblies, follow the installation instructions in this data sheet. The Insulating
Seal Assemblies are recommended to
be installed on smooth, flat, and clean
surfaces. If it is expected that environmental conditions may result in excessive condensation, additional sealing of
the assembly is recommended.
There are specific situations, such as
corrugated surfaces where alternate
methods to seal the clearance hole are
recommended. For additional guidance, contact Tyco Fire Protection
Products (TFPP) Technical Services.
NOTICE
The Model ESFR-17 Dry Type Pendent
Sprinklers (TY7229) described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
of the National Fire Protection Association (NFPA), in addition to the standards
of any authorities having jurisdiction.
Failure to do so may impair the performance of these devices.

MARCH 2015

The owner is responsible for maintaining their fire protection system


and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.

Sprinkler
Identification
Number (SIN)
TY7229

TFP320

TFP320
Page 2 of 8
GROOVED
COUPLING
GASKET
SEALING
SURFACE

1-1/4" NPT
OR ISO 7-R 1-1/4
PIPE THREADED
CONNECTION

2" (DN50)
GROOVED
CONNECTION
THREADED
AND GROOVED
INLET
INLET
WRENCH
HEX

TABLE A
DIM. C

TABLE A
DIM. A

CASING

TABLE A
DIM. B

FRAME
WRENCH
FLATS
LINK
ASSEMBLY

CENTERLINE
OF THERMAL
SENSING
ELEMENT

HOOK

FIGURE 1
MODEL ESFR-17 DRY TYPE PENDENT SPRINKLER (TY7229)
36 Inch
(914 mm)
Sprinkler

30 Inch
(762 mm)
Sprinkler

23 Inch
(584 mm)
Sprinkler

Dimension A

37.5 in.
(952,5 mm)

31.3 in.
(795 mm)

24.3 in.
(617 mm)

Dimension B

36.2
(919,5 mm)

30.0
(762 mm)

23.0
(584 mm)

Dimension C

33.9
(861 mm)

27.7
(704 mm)

20.7
(526 mm)

TABLE A
SPRINKLER LENGTHS
Sprinkler
Type

Temperature
Rating

Laboratory Listings
and Approvals

Pendent
K=16.8 (TY7229)

165F (74C)

1, 2

212F (100C)

Notes:
1. UL Listed
2. FM Approved

TABLE B
LABORATORY LISTINGS AND APPROVALS

(Refer to Table B for specific details on


Laboratory listings and approvals.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connections
1-1/4 Inch NPT or ISO 7-R 1-1/4
Grooved Connection
2 Inch Standard Cut Grooved per
Technical Data Sheet TFP1898
Discharge Coefficient
K=16.8 gpm/psi1/2 (241,9 lpm/bar1/2)
Temperature Ratings
165F (74C) and 212F (100C)
Finish
Refer to Physical Characteristics.
Physical Characteristics

Design
Criteria

FRAME

DEFLECTOR

Approvals
UL Listed
FM Approved

Threaded and Grooved Inlet Bronze


Casing. . . . . . . . . . . . . . . . Galvanized Steel Pipe
Frame Brass
Deflector Bronze
Hook MONEL
Strut MONEL
Link Assembly Solder, Nickel

BUTTON
WITH VENT
HOLES

STRUT

Technical
Data

The following general guidelines and


Table C, provide the key design criteria
for the TYCO Model ESFR-17 Dry Type
Pendent Sprinklers (TY7229).
In all cases, the appropriate NFPA
installation standard, or other applicable standard, must be referenced
to ensure applicability and to obtain
complete installation guidelines. The
general guidelines in this technical data
sheet are not intended to provide complete installation criteria.
System Type
Wet Pipe system only
Ceiling Construction
Unobstructed or non-combustible
obstructed construction (e.g., smooth
ceiling, bar joists, beam and girder, etc.)
Ceiling Slope
Maximum 2 inch rise for 12 inch run
(16.7%)
Maximum Coverage Area
100 ft.2 (9,3 m2)
In some cases, the installation standards permit a greater coverage area.
Minimum Coverage Area
64 ft.2 (5,8 m2)

TFP320
Page 3 of 8
Storage Type

NFPA

FM Global

Open Frame (i.e., no solid shelves)


Single, Double, Multiple-Row, or Portable Rack Storage of
Class I-IV and Group A or B Plastics

Refer to NFPA 13
Chapters 16 and 17

Refer to FM Global
2-0 and 8-9

Solid Pile or Palletized Storage of Class I-IV and


Group A or B Plastics

Refer to NFPA 13
Chapters 14 and 15

Refer to FM Global
2-0 and 8-9

Refer to NFPA 13
Chapter 12

Refer to FM Global
2-0, 8-9, and 8-24

Rubber Tire Storage

Refer to NFPA 13
Chapter 18

Refer to FM Global
2-0 and 8-3

Roll Paper Storage


(Refer to the standard)

Refer to NFPA 13
Chapter 19

Refer to FM Global 8-21

Flammable/Ignitable Liquid Storage


(Refer to the standard)

Refer to NFPA 30

Refer to FM Global 7-29

Refer to 30B

Refer to FM Global 7-31

N/A

N/A

Idle Pallet Storage

Aerosol Storage
(Refer to the standard)
Automotive Components in Portable Racks
(Control mode only; refer to the standard)
N/A = Not Applicable

TABLE C
MODEL ESFR-17 DRY TYPE PENDENT SPRINKLER
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
Maximum Spacing
12 feet (3,7 m) for ceiling heights up to
30 feet (9,1 m)
10 feet (3,1 m) for ceiling heights greater
than 30 feet (9,1 m)
Minimum Spacing
8 feet (2,4 m)
Minimum Clearance to Commodity
36 inches (914 mm)
NFPA
Deflector-to-Ceiling Distance
6 to 14 inches (152 to 356 mm)
FM Global
Centerline of Thermal Sensing
Element-to-Ceiling Distance
Refer to FM Global 2-0 for Storage
Sprinklers.
Sprinkler Threaded Fittings
1-1/4 inch NPT Model ESFR-17 Dry
Type Sprinklers are to be installed in
the 1-1/4 inch NPT outlet or run of the
following fittings:
malleable or ductile iron threaded
tee fittings that meet the dimensional requirements of ANSI B16.3
(Class 150)
cast iron threaded tee fittings that
meet the dimensional requirements
of ANSI B16.4 (Class 125)

Do not install Model ESFR-17 Dry Type


Sprinkler into elbow fittings. The inlet of
the sprinkler can contact the interior of
the elbow and result in damage to the
assembly, resulting in leakage.
The Model ESFR-17 Dry Type Sprinkler
can also be installed in the 1-1/4 inch
NPT outlet of a GRINNELL Figure 730
Mechanical Tee.
Sprinkler Grooved Connection
The Model ESFR-17 Dry Type Sprinklers can be installed in typical grooved
connection scenarios illustrated in
Figure 7.
For flexible couplings, use of the 2 inch
Figure 705 GRINNELL Flexible Couplings with C Shape Pre-Lubricated
Grade A EPDM Gasket (Ref. TFP1820)
is recommended.
For rigid couplings, use of the 2 inch,
Figure 577 GRINNELL G-FIRE Grooved
Rigid Coupling with C Shape PreLubricated Grade A EPDM Gasket
(Ref. TFP1854) is recommended.
When using tees, use of the Figure
219 GRINNELL Grooved Ductile
Iron Cast Fittings (Ref. TFP1810) is
recommended.

NOTICE
Do not install Model ESFR-17 Dry Type
Sprinkler into any other type fitting connection without first consulting TFPP
Technical Services. Failure to use the
appropriate fitting may result in insufficient engagement of the inlet pipe
threads with consequent leakage.
Exposure Length
When using Model ESFR-17 Dry Type
Sprinklers to protect areas subject to
freezing temperatures, use Figures
2 and 3, and Table D to determine a
sprinklers appropriate exposed barrel
length to prevent water from freezing in
the connection pipes due to conduction. The exposed barrel length measurement must be taken from the face
of the sprinkler fitting to the exterior
surface of the structure or insulation
that is exposed to the heated area.
Do not attempt to add additional insulation around the barrel in the heated
area as a method to minimize condensation. This will reduce the calculated
exposure length.

TFP320
Page 4 of 8
1" (25,4 mm) NOMINAL

END OF
SPRINKLER
INLET
EXPOSED
BARREL
LENGTH
(REFER TO
TABLE D
AND DESIGN
CRITERIA)

FACE OF
SPRINKLER
FITTING

HEATED
AREA

EXTERIOR
SURFACE OF
CEILING

DIM. A
TABLE A

THREADED
FITTING
(REFER TO
DESIGN
CRITERIA)

INSULATING
SEAL
ASSEMBLIES

DIM. B
TABLE A

CEILING
DEPTH

6" (152 mm)


MINIMUM
14" (356 mm)
MAXIMUM

INTERIOR
SURFACE OF
CEILING
PROTECTED
AREA

CLEARANCE
HOLE
2-1/2" to 3"
(65 to 75 mm)
DIA.

FIGURE 2
THREADED FITTING INSTALLATION
1-3/8"
(35 mm)

SYSTEM
PIPE

END OF
SPRINKLER
INLET
EXPOSED
BARREL
LENGTH
(REFER TO
TABLE D
AND DESIGN
CRITERIA)

FACE OF
SPRINKLER
FITTING

HEATED
AREA
EXTERIOR
SURFACE OF
CEILING

DIM. A
TABLE A

GROOVED
FITTING AND
RIGID OR
FLEXIBLE
COUPLING
(REFER TO
DESIGN
CRITERIA)
INSULATING
SEAL
ASSEMBLIES

CEILING
DEPTH

6" (152 mm)


MINIMUM
14" (356 mm)
MAXIMUM

Exposed Barrel
Ambient
Temperature(b)(c)

SYSTEM
PIPE

INTERIOR
SURFACE OF
CEILING
PROTECTED
AREA

CLEARANCE
HOLE
2-1/2" to 3"
(65 to 75 mm)
DIA.

FIGURE 3
GROOVED CONNECTION INSTALLATION

Ambient
Temp. of
Protected
Area(a)

40F
(4C)

40F
(4C)

30F
(-1C)

20F
(-7C)

4
(101,6)

10F
(-12C)

8
(203)

1
(25,4)

0F
(-18C)

12
(305)

3
(76)

-10F
(-23C)

14
(356)

4
(101,6)

1
(25,4)

-20F
(-29C)

14
(356)

6
(152)

3
(76)

-30F
(-34C)

16
(406)

8
(203)

4
(101,6)

-40F
(-40C)

18
(457)

8
(203)

4
(101,6)

-50F
(-46C)

20
(508)

10
(254)

6
(152)

-60F
(-51C)

20
(508)

10
(254)

6
(152)

50F
(10C)

60F
(16C)

Minimum Exposed
Barrel Length
Inches
(mm)

Notes:
a. The area below the ceiling is referred to as the
protected area. Ambient temperature is the temperature at the discharge end of the sprinkler.
For protected area temperatures that range
between the listed temperatures, use the next
cooler temperature.
b. Lengths are inclusive of wind velocities up to 30
mph (48,3 km/h) and assume a minimum 40F
(4C) in heated area.
c. Minimum exposed barrel length when Insulating
Seal Assembly is installed on exterior surface of
ceiling:
Threaded Fitting Installation 5 in. (125 mm)
(Ref. Figure 2)
Grooved Fitting Installation 4-1/2 in. (114
mm) (Ref. Figure 3)

TABLE D
MINIMUM EXPOSED
BARREL LENGTH REQUIRED
PER AMBIENT TEMPERATURE
DIM. B
TABLE A

TFP320
Page 5 of 8
GROOVED
TEE

MODEL ESFR-17
SPRINKLER

WELDED
GROOVED OUTLET

GROOVED
DROP NIPPLE

GROOVED RIGID OR
FLEXIBLE COUPLING
(REFER TO DESIGN
CRITERIA)

FIGURE 4
TYPICAL GROOVED CONNECTION
OPTIONS
THREADED
SPRINKLER
FITTING

SELF
TAPPING
SCREWS

W-TYPE 26
WRENCH
"INLET
SIDE"

SYSTEM
PIPE
WRENCH
JAW

APPLY WRENCH
JAW TO INLET
WRENCH HEX

SPRINKLER
FITTING

CLEARANCE
HOLE

W-TYPE 26
WRENCH

"FRAME
ARMS"
REFERENCE
MARKS
INDICATE
RELATIVE
SPRINKLER
FRAME ARM
ORIENTATION
BELOW
CEILING

"FITTING
SIDE"
"SPRINKLER
SIDE"
WRENCH
JAW
APPLY
WRENCH
JAW TO
FRAME
WRENCH
FLATS

FRAME
ARM

WRENCH
FRAME ARM
CLEARANCE
RECESS

"FITTING SIDE"
TOWARD
SPRINKLER
FITTING
W-TYPE 26
WRENCH
"SPRINKLER
SIDE" TOWARD
SPRINKLER
DEFLECTOR

SPRINKLER
DEFLECTOR

FIGURE 5
W-TYPE 26
SPRINKLER WRENCH

CEILING

SPRINKLER
FRAME
ARMS

FIGURE 6
SPRINKLER FRAME ARMS
ORIENTATION MARK

ORIENT
HOUSING
SLOT 180
OPPOSED
TO INSERT
SLOT

HOUSING
INSERT
INSULATION
RING
CLEARANCE
HOLE

ORIENT
INSULATION
RING SPLIT
BETWEEN
HOUSING
SLOT AND
SCREW

FIGURE 7
INSULATING SEAL ASSEMBLY
INSTALLATION

TFP320
Page 6 of 8
Clearance Space
In accordance with Section 8.4.9.2
of the 2010 edition of NFPA 13, when
protecting insulated freezer structures
with dry type sprinklers, the clearance
hole around the sprinkler barrel of
the Dry Type Sprinkler and the clearance hole must be sealed. Sealing is
accomplished by use of the Insulating
Seal Assemblies (Ref. Figure 7). Failure
to use the Insulating Seal Assemblies
will increase the potential for the formation of condensation on the sprinkler and subsequent ice build-up on
or around the sprinkler can occur that
might damage the dry type sprinkler
and/or prevent proper operation in a
fire situation.
FM Global 2-0
Consult FM Global and/or FM Global
guidelines for allowable vertical distance from ceiling to centerline of
thermal sensing element.

Replace with the new sprinkler following the installation instructions in this
section.

Operation

Step 2. Wrench-tighten the Model


ESFR-17 Dry Type Sprinkler using only
the W-Type 26 Sprinkler Wrench and by
fully engaging the wrench on the inlet
wrench hex (Ref. Figure 5). For reference, the FRAME ARMS marking can
be used to align the frame arms with
the System Pipe as shown in Figure 5.

The casing between the inlet and the


sprinkler remains dry until the sprinkler
operates. The fusible link assembly is
comprised of two link halves that are
joined together by a thin layer of solder.
When the rated temperature is reached,
the solder melts and the two link halves
separate, activating the sprinkler and
allowing water to flow through the
casing and to the activated sprinkler.

Installation
TYCO Model ESFR-17 Early Suppression, Fast Response 16.8K Pendent
Sprinklers must be installed in accordance with this section.
General Instructions
Avoid damage to the fusible Link
Assembly during installation by using
only the Casing to handle the sprinkler (i.e., do not apply pressure to the
fusible Link Assembly), and by using
the appropriate sprinkler wrench.
Failure to do so can lead to an unstable
link assembly and premature activation
of the sprinkler. Damaged sprinklers
must be replaced.
Model ESFR-17 Dry Type Sprinklers
must only be installed in fittings/connections that meet the requirements
of the Design Criteria section. Refer
to the Design Criteria section for other
important requirements regarding
piping design, exposure length, and the
sealing of the clearance space around
the sprinkler casing.
If a sprinkler using a threaded connection (vs. grooved connection) requires
replacement, remove the sprinkler
using only the W-Type 26 Sprinkler
Wrench. Fully engage the wrench on
the inlet wrench hex (Ref. Figure 5).

Threaded Connection
Instructions
A leak-tight 1-1/4 inch NPT sprinkler
joint should be obtained by applying a
minimum-to-maximum torque of 45 to
65 lbs.-ft. (61 to 88 Nm). Higher levels
of torque can distort the sprinkler inlet
with consequent leakage or impairment
of the sprinkler.
Note: Install the Model ESFR-17 Dry
Type Pendent Sprinkler in the pendent
position (Ref. Figure 5) by carefully
raising the pendent sprinkler through
the clearance hole. The deflector of the
pendent sprinkler is to be parallel to the
ceiling.
Step 1. Apply a non-hardening pipe
thread sealant such as TEFLON to the
male 1-1/4 inch NPT inlet threads.

Step 3. After installation, inspect the


Link Assembly of each Model ESFR-17
Dry Type Sprinkler for damage. In particular, verify that the Link Assembly
and Hook are positioned as illustrated
in Figure 1, and that the Link Assembly is not bent, creased, or forced out
of normal position in any way. Replace
damaged sprinklers.
Step 4. Install the insulation rings of the
Insulating Seal Assemblies by slipping
the insulation rings around the sprinkler casing as shown in Figure 7. Place
the inserts over the insulation rings by
sliding the inserts around the casing.
Place the housings over the Inserts
and insulation rings ensuring that the
slot on the housings are 180 degrees to
the inserts slot. Ensure that the Insulating Seal Assemblies are snug against
the refrigerated storage ceiling. Secure
the Insulating Seal Assemblies to the
ceiling using two self-tapping screws
per assembly.
Grooved Connection
Instructions
The following instructions are based on
using the 2 inch Figure 705 Grooved
Flexible Coupling or the 2 inch Figure
577 Grooved Rigid Coupling.
Step 1. Inspect the exterior groove
and the end connection of the mating
grooved connection and sprinkler to
verify all burrs, loose debris, dirt, chips,
paint and other foreign materials such
as grease are removed. Sealing surfaces must be free from sharp edges,
projections, indentations, and/or other
defects.

Step 2. Verify that the coupling and


gasket grade are correct for the application intended. Refer to Technical
Data Sheet TFP1895 for additional
gasket information. The sealing edges
and the outer surfaces of the gasket
should be covered with a fine layer of
lubricant. To prevent deterioration of
the gasket material, a silicone lubricant
should be used to prevent freezing of
the lubricant.
Step 3. Install the Model ESFR-17 Dry
Type Pendent Sprinkler in the pendent
position (Ref. Figures 4 and 7) by carefully raising the pendent sprinkler
through the clearance hole. The deflector of the pendent sprinkler is to be parallel to the ceiling. Also, ensure that the
FRAME ARMS markings on the sprinkler casing are aligned with the System
Pipe (Ref. Figure 6).
Step 4. Install the gasket by placing it
over the sealing portion of the grooved
inlet connection so that the gasket lip
does not extend beyond the end of the
groove sealing surface. Bring end of
the grooved inlet together with end of
grooved fitting ensuring vertical and
horizontal alignment. Slide the gasket
over both sealing surfaces.
Step 5. With one bolt and nut removed,
separate the coupling housings and
place over the gasket. Verify that the
coupling housings are over the gasket
and that the coupling housing keys are
fully engaged into the grooves.
Step 6. Insert the bolt and nut into the
coupling and finger tighten both nuts.
Verify that the bolt heads are fully
recessed in the housing.
The 2 inch Figure 705 Grooved Flexible
Coupling Housing bolt pads must be
in metal-to-metal contact. For Flexible
Coupling deflection data, refer to Technical Data Sheet TFP1820.
The 2 inch Figure 577 Grooved Rigid
Coupling has an intended gap of up
to 1/16 of an inch at each pad to allow
for positive rigid gripping onto the
pipe. The patented tongue and groove
design provides protection to the back
of the gasket during installation.
Step 7. Alternate between both sides
of the coupling when tightening the
bolts. Torque bolts to 30 lbs-ft. (41
Nm).
Step 8. Install the insulation rings of the
Insulating Seal Assemblies by slipping
the insulation rings around the sprinkler casing as shown in Figure 7. Place
the inserts over the insulation rings by
sliding the inserts around the casing.
Place the housings over the Inserts
and insulation rings ensuring that the
slot on the housings is 180 degrees to
the inserts slot. Ensure that the Insulating Seal Assemblies are snug against
the refrigerated storage ceiling. Secure
the Insulating Seal Assemblies to the
ceiling using two self-tapping screws
per assembly.

TFP320
Page 7 of 8

Care and
Maintenance

Limited
Warranty

Ordering
Procedure

TYCO Model ESFR-17 Early Suppression, Fast Response 16.8K Pendent


Sprinklers must be maintained and serviced in accordance with this section.

For warranty terms and conditions, visit


www.tyco-fire.com.

Contact your local distributor for availability. When placing an order, indicate
the full product name and part number
(P/N).

Before closing a fire protection system


main control valve for maintenance
work on the fire protection system that
it controls, obtain permission to shut
down the affected fire protection from
the proper authorities and notify all
personnel who may be affected by this
action.

Sprinklers which are found to be


leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modified or overheated sprinklers must be
replaced.
A Vent Hole is provided in the Link
Assembly Button (Ref. Figure 1) to indicate if the Dry Sprinkler is remaining
dry. Evidence of leakage from the Vent
Hole indicates potential leakage past
the Inlet seal and the need to remove
the sprinkler to determine the cause of
leakage; e.g., an improper installation
or an ice plug. Close the fire protection system control valve and drain the
system before removing the sprinkler.
When replacing a sprinkler, remove and
discard the old Insulating Seal Assemblies and replace as shown in Figure 7.

Care must be exercised to avoid


damage to the sprinklers before,
during, and after installation. Sprinklers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Association (e.g., NFPA 25), in addition to
the standards of any authorities having
jurisdiction. Contact the installing contractor or product manufacturer with
any questions.
Automatic sprinkler systems are recommended to be inspected, tested,
and maintained by a qualified Inspection Service in accordance with local
requirements and/or national codes.

Sprinkler Assemblies
Specify: Model ESFR-17 Dry Type Early
Suppression, Fast Response 16.8K
Pendent Sprinklers (TY7229) with
two (2) Insulating Sealing Assemblies,
P/N (specify):
36 Inch Sprinkler
165F (74C) . . . . . . . . . . . . . . . . . . . 614411360
212F (100C) . . . . . . . . . . . . . . . . . . 614421360
30 Inch Sprinkler
165F (74C) . . . . . . . . . . . . . . . . . . . 614411300
212F (100C) . . . . . . . . . . . . . . . . . . 614421300
23 Inch Sprinkler
165F (74C) . . . . . . . . . . . . . . . . . . . 614411230
212F (100C) . . . . . . . . . . . . . . . . . . 614421230

Special Order
Sprinkler Assemblies with
ISO 7-1 Thread Connections
Specify: Model ESFR-17 Dry Type
Early Suppression, Fast Response
16.8K Pendent Sprinkler (TY7229) with
ISO 7-1 thread connection and two (2)
Insulating Sealing Assemblies, (specify
temperature rating), P/N (specify):
36 Inch Sprinkler
165F (74C) . . . . . . . . . . . . . . . . . . . I614411360
212F (100C) . . . . . . . . . . . . . . . . . . I614421360
30 Inch Sprinkler
165F (74C) . . . . . . . . . . . . . . . . . . . I614411300
212F (100C) . . . . . . . . . . . . . . . . . . I614421300
23 Inch Sprinkler
165F (74C) . . . . . . . . . . . . . . . . . . . I614411230
212F (100C) . . . . . . . . . . . . . . . . . . I614421230

Sprinkler Wrench
Specify: W-Type 26 Sprinkler Wrench,
P/N 563411001
Insulating Seal Assembly Kit
Each Insulating Seal Assembly kit consists of one (1) Insulation Ring, one (1)
Insert, one (1) Housing, and two (2)
Screws.
Specify: Insulating Sealing Assembly,
P/N 911061500

TFP320
Page 8 of 8

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700

Copyright 2015 Tyco Fire Products, LP. All rights reserved.


MONEL is trademark of Special Metals Corporation.

Worldwide
www.tyco-fire.com
Contacts

RAPID RESPONSE Series LFII Residential


4.9 K-factor Pendent Sprinkler
Wet Pipe and Dry Pipe Systems
General
Description

adjustment provided by the Recessed


Escutcheon reduces the accuracy to
which the pipe drops to the sprinklers
must be cut.

TYCO RAPID RESPONSE Series


LFII Residential 4.9K Pendent and
Recessed Pendent Sprinklers (TY2234)
are decorative, fast response, frangible bulb sprinklers designed for use
in residential occupancies such as
homes, apartments, dormitories, and
hotels. When aesthetics and optimized
flow characteristics are the major consideration, the Series LFII Residential
Sprinklers (TY2234) should be the first
choice.

The Series LFII Residential Sprinklers


have been designed with heat sensitivity and water distribution characteristics proven to help in the control
of residential fires and to improve the
chance for occupants to escape or be
evacuated.

The Series LFII Residential Sprinklers


are intended for use in the following
scenarios:
wet and dry pipe residential sprinkler systems for one- and two-family dwellings and mobile homes per
NFPA 13D
wet and dry pipe residential sprinkler
systems for residential occupancies
up to and including four stories in
height per NFPA 13R
wet and dry pipe sprinkler systems
for the residential portions of any
occupancy per NFPA 13
The recessed version of the Series
LFII Residential Sprinklers is intended
for use in areas with finished ceilings.
It employs a two-piece Style 20
Recessed Escutcheon. The Recessed
Escutcheon provides 1/4 inch
(6,4 mm) of recessed adjustment or up
to 1/2 inch (12,7 mm) of total adjustment
from the flush ceiling position. The

IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.

Page 1 of 6

Dry Pipe System Application


The Series LFII Residential Pendent
and Recessed Pendent Sprinklers
offers a laboratory approved option
for designing dry pipe residential sprinkler systems, whereas, most residential
sprinklers are laboratory approved for
wet systems only.
Through extensive testing, it has been
determined that the number of design
sprinklers (hydraulic design area) for
the Series LFII Residential Pendent and
Recessed Pendent Sprinklers (TY2234)
need not be increased over the number
of design sprinklers (hydraulic design
area) as specified for wet pipe sprinkler
systems, as is accustomed for density/
area sprinkler systems designed per
NFPA 13.
Consequently, the Series LFII Residential Sprinklers offer the features
of non-water filled pipe in addition
to not having to increase the number
of design sprinklers (hydraulic
design area) for systems designed to
NFPA 13, 13D, or 13R.
NOTICE
The Series LFII Residential Pendent
and Recessed Pendent Sprinklers
(TY2234) described herein must be
installed and maintained in compliance
with this document and the applicable
standards of the National Fire Protection Association (NFPA), in addition to
the standards of any authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.

MARCH 2015

Sprinkler
Identification
Number (SIN)
TY2234

Technical
Data
Approvals

UL Listed
(for use with wet pipe and dry pipe systems)
C-UL Listed
(for use only with wet pipe systems)
Certified to all requirements of
NSF/ANSI 61
(Refer to the Design Criteria section for details on these approvals.)

Maximum Working Pressure


175 psi (12,1 bar)

Discharge Coefficient

K=4.9 gpm/psi1/2 (70,6 lpm/bar1/2)

Temperature Rating

155F (68C) or 175F (79C)

Finishes

Natural Brass, Pure White, Signal White, or


Chrome Plated

Physical Characteristics

Frame . . . . . . . . . . . . . . . . . . . . . . . . Brass
Button. . . . . . . . . . . . . . . . . . . . . . . Copper
Sealing Assembly. . . . . . . Beryllium Nickel
w/TEFLON
Bulb (3 mm) Glass
Compression Screw Bronze
Deflector . . . . . . . . . . . . . . . . . . . . . Bronze

TFP400

TFP400
Page 2 of 6

Components:
1 - Frame
2 - Button
3 - Sealing Assembly
4 - Bulb
5 - Compression
Screw
6 - Deflector *

7/16" (11,1 mm)


NOMINAL
MAKE-IN

1/2"
NPT

rating is
indicated on
Deflector.

2-7/8" DIA.
(73,0 mm)

1
2

2-1/4"
(57,2 mm)

3
4

* Temperature

ESCUTCHEON
PLATE SEATING
SURFACE

1-5/8"
(41,3 mm)

STYLE 20
RECESSED
ESCUTCHEON

WRENCH
FLATS

6*
CROSS SECTION

PENDENT

RECESSED PENDENT

FIGURE 1
RAPID RESPONSE SERIES LFII RESIDENTIAL
4.9K PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234)

7/161/8"
(11,13,2 mm)
FACE OF
SPRINKLER
FITTING

2-7/8" DIA.
(73,0 mm)
2-1/4" DIA.
(57,2 mm)

1/2" (12,7 mm)


1/4" (6,4 mm)
MOUNTING
PLATE

WRENCH RECESS
(END "A" USED
FOR TY2234)

FIGURE 3
W-TYPE 6
SPRINKLER WRENCH
MOUNTING
SURFACE

CLOSURE

1/8"
(3,2 mm)

TY2234

WRENCH
RECESS

1-3/8" (34,9 mm)


1-1/8" (28,6 mm)

FIGURE 2
STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE
RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT SPRINKLER

Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and flow water.

Design
Criteria
The TYCO RAPID RESPONSE Series
LFII Residential 4.9K Pendent and
Recessed Pendent Sprinklers are UL
and C-UL Listed for installation in
accordance with this section.
Residential Sprinkler
Design Guide
When conditions exist that are outside
the scope of the provided criteria, refer
to the Residential Sprinkler Design
Guide TFP490 for the manufacturers recommendations that may be
acceptable to the local authority having
jurisdiction.

PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA

FIGURE 4
W-TYPE 7 RECESSED
SPRINKLER WRENCH
System Types
Per the UL Listing, wet pipe and dry
pipe systems may be utilized. Per the
C-UL Listing, only wet pipe systems
may be utilized.
Refer to Technical Data Sheet TFP485
for the use of residential sprinklers in
residential dry pipe systems.
Ceiling Types
Smooth flat horizontal, or beamed, or
sloped, in accordance with the 2013
Edition of NFPA 13D, 13R, or 13, as
applicable.

TFP400
Page 3 of 6
Hydraulic Design
(NFPA 13D and 13R)
For systems designed to NFPA 13D
or NFPA 13R, the minimum required
sprinkler flow rates are given in
Tables A and B as a function of temperature rating and the maximum
allowable coverage areas. The
sprinkler flow rate is the minimum
required discharge from each of the
total number of design sprinklers as
specified in NFPA 13D or NFPA 13R.
The number of design sprinklers
specified in NFPA 13D and 13R for wet
pipe systems is to be applied when
designing dry pipe systems.
Hydraulic Design
(NFPA 13)
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required discharge from each of the four sprinklers
is to be the greater of the following:
The flow rates given in Table A or
B as a function of temperature
rating and the maximum allowable
coverage area.
A minimum discharge of 0.1 gpm/ft2
over the design area comprised
of the four most hydraulically
demanding sprinklers for actual
coverage areas protected by the
four sprinklers.
The number of design sprinklers specified in NFPA 13 for wet pipe systems is
to be applied when designing dry pipe
systems.
Dry Pipe System Water Delivery
When using the Series LFII Residential
Sprinklers (TY2234) in dry pipe sprinkler systems, the time for water delivery must not exceed 15 seconds for the
most remote operating sprinkler.
Obstruction to
Water Distribution
Sprinklers are to be located in accordance with the obstruction rules of
NFPA 13D, 13R, and 13 as applicable
for residential sprinklers as well as with
the obstruction criteria described within
the Technical Data Sheet TFP490.
Operational Sensitivity
Sprinklers are to be installed with a
deflector-to-ceiling distance of 1-1/4 to
4 inches.
Sprinkler Spacing
The minimum spacing between sprinklers is 8 feet (2,4 m). The maximum
spacing between sprinklers cannot
exceed the length of the coverage area
(Table A or B) being hydraulically calculated (e.g., maximum 12 feet for a
12 ft. x 12 ft. coverage area, or 20 feet
for a 20 ft. x 20 ft. coverage area).

Installation
TYCO RAPID RESPONSE Series
LFII Residential 4.9K Pendent and
Recessed Pendent Sprinklers must
be installed in accordance with this
section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprinkler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm).
A leak-tight 1/2 inch NPT sprinkler joint
should be obtained by applying a minimum-to-maximum torque of 7 to 14
ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in an Escutcheon Plate by under- or over- tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.

Series LFII Residential


Pendent Sprinklers
The Series LFII Residential Pendent
Sprinklers must be installed in accordance with the following instructions:
Step 1. Install pendent sprinklers in the
pendent position with the deflector parallel to the ceiling.
Step 2. With pipe thread sealant
applied to the pipe threads, handtighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Figure 3). With reference to Figure 1, apply the W-Type 6
Sprinkler Wrench to the wrench flats.
Series LFII Residential
Recessed Pendent Sprinklers
The Series LFII Residential Recessed
Pendent Sprinklers must be installed
in accordance with the following
instructions:
Step A. Install recessed pendent sprinklers in the pendent position with the
deflector parallel to the ceiling.
Step B. After installing the Style 20
Mounting Plate over the sprinkler
threads and with pipe thread sealant
applied to the pipe threads, handtighten the sprinkler into the sprinkler
fitting.
Step C. Tighten the sprinkler into the
sprinkler fitting using only the W-Type 7
Recessed Sprinkler Wrench (Figure 4).
With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats.
Step D. After the ceiling has been
installed or the finish coat has been
applied, slide on the Style 20 Closure
over the Series LFII Residential Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.

TFP400
Page 4 of 6
WET PIPE SYSTEM
Minimum Flow and Residual Pressure (2)(3)
Maximum Ordinary Temperature Rating Intermediate Temperature Rating
Coverage
155F (68C)
175F (79C)
Area (1)
Flow
Pressure
Flow
Pressure
Ft. x Ft.
(m x m)
gpm
psi
gpm
psi
(l/min)
(bar)
(l/min)
(bar)
12 x 12
(3,7 x 3,7)

13
(49,2)

7.0
(0,48)

13
(49,2)

7.0
(0,48)

14 x 14
(4,3 x 4,3)

13
(49,2)

7.0
(0,48)

13
(49,2)

7.0
(0,48)

16 x 16
(4,9 x 4,9)

13
(49,2)

7.0
(0,48)

13
(49,2)

7.0
(0,48)

18 x 18
(5,5 x 5,5)

17
(64,3)

12.0
(0,83)

17
(64,3)

12.0
(0,83)

20 x 20
(6,1 x 6,1)

20
(75,7)

16.7
(1,15)

20
(75,7)

16.7
(1,15)

Deflector to
Ceiling

Installation
Type

Minimum
Spacing
Ft.
(m)

Smooth
Ceilings
1-1/4 to
4 inches

Recessed
using Style 20
Beamed
or
Ceilings per Escutcheon
non-recessed
NFPA 13D
per NFPA 13D,
or 13R
13R, or 13
1-1/4 to 1-3/4
inches below
bottom of
beam.

8
(2,4)

Notes:
1. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design
criteria are stated.
2. Requirement is based on minimum flow in gpm (lpm) from each sprinkler. The associated residual pressures are calculated using the nominal
K-factor. Refer to Hydraulic Design under the Design Criteria section.
3. For NFPA 13 residential applications, the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the criteria in this table must be used.

TABLE A
WET PIPE SYSTEM
SERIES LFII RESIDENTIAL 4.9K PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234)
NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA
DRY PIPE SYSTEM
Minimum Flow and Residual Pressure (2)(3)

Maximum
Coverage Ordinary Temperature Rating Intermediate Temperature Rating
Area (1)
155F (68C)
175F (79C)
Ft. x Ft.
Flow
Pressure
Flow
Pressure
(m x m)
gpm
psi
gpm
psi
(l/min)
(bar)
(l/min)
(bar)
12 x 12
(3,7 x 3,7)

13
(49,2)

7.0
(0,48)

13
(49,2)

7.0
(0,48)

14 x 14
(4,3 x 4,3)

14
(53,0)

8.2
(0,57)

14
(53,0)

8.2
(0,57)

16 x 16
(4,9 x 4,9)

15
(56,8)

9.4
(0,65)

15
(56,8)

9.4
(0,65)

18 x 18
(5,5 x 5,5)

18
(68,1)

13.5
(0,93)

18
(68,1)

13.5
(0,93)

20 x 20
(6,1 x 6,1)

21
(79,5)

18.4
(1,27)

21
(79,5)

18.4
(1,27)

Deflector to
Ceiling

Smooth
Ceilings
1-1/4 to 4
inches
Beamed
Ceilings
per NFPA 13D
or 13R
1-1/4 to 1-3/4
inches below
bottom of
beam.

Installation
Type

Minimum
Spacing
Ft.
(m)

Recessed
using Style 20
Escutcheon or
non-recessed
per NFPA 13D,
13R, or 13

8
(2,4)

Notes:
1. For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design
criteria are stated.
2. Requirement is based on minimum flow in gpm (lpm) from each sprinkler. The associated residual pressures are calculated using the nominal
K-factor. Refer to Hydraulic Design under the Design Criteria section.
3. For NFPA 13 residential applications, the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the criteria in this table must be used.

TABLE B
DRY PIPE SYSTEM
SERIES LFII RESIDENTIAL 4.9K PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234)
NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA

TFP400
Page 5 of 6

Care and
Maintenance

Limited
Warranty

Ordering
Procedure

TYCO RAPID RESPONSE Series


LFII Residential 4.9K Pendent and
Recessed Pendent Sprinklers must be
maintained and serviced in accordance
with this section:

For warranty terms and conditions, visit


www.tyco-fire.com.

Contact your local distributor for availability. When placing an order, indicate
the full product name and part number
(P/N).

Before closing a fire protection system


main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
The owner must assure that the sprinklers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, nonoperation in the event of a fire or inadvertent operation may result.

Sprinkler Assemblies
Specify: Series LFII 4.9K Residential
Pendent Sprinkler (TY2234), (specify
temperature rating), with (specify) finish,
P/N (specify):
155F (68C)
Natural Brass . . . . . . . . . . . . . P/N 51-201-1-155
Pure White (RAL 9010)* . . . . . . P/N 51-201-3-155
Signal White (RAL 9003) . . . . . P/N 51-201-4-155
Chrome Plated . . . . . . . . . . . . P/N 51-201-9-155
175F (79C)
Natural Brass . . . . . . . . . . . . . P/N 51-201-1-175
Pure White (RAL 9010)* . . . . . . P/N 51-201-3-175
Signal White (RAL 9003) . . . . . P/N 51-201-4-175
Chrome Plated . . . . . . . . . . . . P/N 51-201-9-175
* Eastern Hemisphere sales only

Recessed Escutcheon
Specify: Style 20 Recessed Escutcheon with (specify*) finish, P/N (specify*)
* Refer to Technical Data Sheet TFP770.

Sprinklers which are found to be


leaking or exhibiting visible signs of
corrosion must be replaced.

Sprinkler Wrenches
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387

Automatic sprinklers must never be


painted, plated, coated, or otherwise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.

Specify: W-Type 7 Sprinkler Wrench,


P/N 56-850-4-001

Care must be exercised to avoid


damage to the sprinklers before,
during, and after installation. Sprinklers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler that has a cracked bulb or that has
lost liquid from its bulb (Ref. Installation section).
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Association (e.g., NFPA 25), in addition to the
standards of any authorities having
jurisdiction. Contact the installing contractor or product manufacturer with
any questions.
Automatic sprinkler systems are recommended to be inspected, tested,
and maintained by a qualified Inspection Service in accordance with local
requirements and/or national codes.

TFP400
Page 6 of 6

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2015 Tyco Fire Products, LP. All rights reserved.
TEFLON is trademark of the DuPont Corporation.

Worldwide
www.tyco-fire.com
Contacts

RAVEN Studio Sprinklers


5.6K Pendent and Horizontal Sidewall
Quick Response, Standard and Extended Coverage
General
Description

and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.

TYCO RAVEN Studio Sprinklers 5.6K


Pendent and Horizontal Sidewall (HSW)
Quick Response, Standard Coverage
for Light and Ordinary Hazard applications and Extended Coverage for Light
Hazard applications only, are intended
for use in areas as designed per NFPA
13.

Sprinkler
Identification
Numbers (SINs)

The flush design is made aesthetically appealing by concealing the deflector and other operating parts behind
the link assembly. The RAVEN Studio
Sprinklers, with a heat sensitive solder
type release element, are Listed as
quick response sprinklers.
NOTICE
RAVEN Studio Sprinklers described
herein must be installed and maintained in compliance with this document and with the applicable standards
of the National Fire Protection Association (NFPA), in addition to the standards
of any authorities having jurisdiction.
Failure to do so may impair the performance of these devices.

Standard Coverage
TY1281 Pendent
TY1381 Horizontal Sidewall
Extended Coverage
TY1282 Pendent
TY1382 Horizontal Sidewall

Technical
Data
Approvals
UL and C-UL Listed
Maximum Working Pressure
175 psi (12,1 bar)
Thread Connection
Adapter: 1/2 NPT x ISO 228 G3/8
Sprinkler: ISO 228 G3/8

Tyco Fire Protection Products (TFPP)


specifically disclaims any liability for
damages or injury (including death)
arising out of or caused by manipulation, dismantling, or misuse of RAVEN
Studio Sprinklers or the use or attempted use of the RAVEN Studio Sprinklers
or any component thereof as an instrument unrelated to its intended function
as a fire protection device.

Note: Threads per ISO 228 are parallel


pipe threads.

The owner is responsible for maintaining their fire protection system

Escutcheon: White, Grey, Chrome,


Primed*, Custom Color, or
Electropolish**

IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 16

Discharge Coefficient
K=5.6 gpm/psi1/2 (80,6 lpm/bar1/2)
Temperature Rating
165F (74C)
Finishes
Sprinkler: White, Grey, or Custom
Color

(Refer to Ordering Procedure for


details.)
* Ready to paint-in-place
** Chrome-coated appearance, available for Stainless
Steel only

Physical Characteristics

Body Brass
Deflector Assembly Bronze
Sealing Assembly . . Beryllium Nickel w/TEFLON
Link Assembly Copper
Thread Adapter Brass
Escutcheon . . . . . . . . . Carbon or Stainless Steel

MARCH 2015

TFP658

TFP658
Page 2 of 16

Application
Pendent
Horizontal
Sidewall

Coverage

SIN

Standard

TY1281

Extended

TY1282

Standard

TY1381

Extended

TY1382

ISO 228 G3/8"


PARALLEL
INLET
THREADS

DUST
CAP

Dust Cap
Color

A
Inches
(mm)

Red

1-7/8
(48)

Green

2-13/16
(56)

INSTALLATION 1
LIP

BODY

NOTES:
1. USE LIP OF PAINTED SPRINKLER BODY, NOT BRASS
SHOULDER, AS INSTALLATION SURFACE,
REF. FIGURES 11 OR 12 AND INSTALLATION
PROCEDURE STEPS 8 OR G

LINK
ASSEMBLY

SPRINKLER
WRENCHING
NOTCHES

ENCLOSED
DEFLECTOR
(HORIZONTAL
SIDEWALL
SHOWN)

EXPOSED
BRASS
SHOULDER 1

FACTORY
PAINTED
AREA 1
A
SIDE VIEW

1-3/8" DIA.
(35 mm)
LINK VIEW

FIGURE 1
RAVEN STUDIO SPRINKLERS
ASSEMBLY
B

BASE
FLANGE
Dimensions
Inches
(mm)
Dim.
A
Dia.

C
PRONGS

Escutcheon
Style
J

3
(76)

4
(101)
7/16
(11)

C
Dia.

CLEARANCE
HOLE

FIGURE 2
RAVEN STUDIO SPRINKLERS
ESCUTCHEONS

2
(51)

Min.
Max.

2-1/2
(63)

3-1/2
(88)

TFP658
Page 3 of 16
1/2" NPT
TAPERED
THREADS

Fitting
Type

ISO
228 G3/8"
PARALLEL
THREADS

90 Elbow

WRENCH HEX,
1" (25 mm)
ACROSS FLATS

7/16"
(11 mm)
NOMINAL
MAKE-IN

Tee

A
Nominal
Pipe Size
Inches
DN

B
Outlet
Thread
ISO 228
Inches

1
DN25

G3/8

Dimensions
Inches
(mm)
C

1-5/8
(41)

13/16
(21)

13/16
(21)

3/4
(19)

1-3/4
(44)

1-5/8
(41)

13/16
(21)

N/A

11/16
(17)

1-13/16
(46)

NOTES:

COMMON THREAD
ADAPTER FEATURES

1. CPVC SPRINKLER ADAPTER FITTINGS WITH ISO 228


G3/8" OUTLET THREADS DESIGNED FOR USE IN
LOW-PROFILE, LIMITED-SPACE INSTALLATIONS
2. INSTALL INLET THREADS OF RAVEN STUDIO
SPRINKLER DIRECTLY INTO ISO 228 G3/8" OUTLET
THREADS OF CPVC SPRINKLER ADAPTER FITTING;
THREAD ADAPTER NOT REQUIRED

3/4"
(19 mm)

3. APPLY ONLY PERMABOND LH056 SEALANT ON


INLET THREADS OF RAVEN STUDIO SPRINKLER
WHEN INSTALLING IN CPVC SPRINKLER ADAPTER
FITTINGS, REF. FIGURE 10
4. REFER TO CPVC INSTALLATION HANDBOOK IH-1900
FOR GUIDANCE ON INSTALLING FITTINGS IN CPVC
PIPE SYSTEMS

SHORT

1"
(25 mm)

A
X

STANDARD
B

E
1-1/2"
(38 mm)

90 ELBOW
D

MEDIUM

A
X

C
B

2"
(50 mm)
C

X
A

LONG

FIGURE 3
RAVEN STUDIO SPRINKLERS
THREAD ADAPTERS

TEE

FIGURE 4
RAVEN STUDIO SPRINKLERS
CPVC SPRINKLER ADAPTER FITTINGS

TFP658
Page 4 of 16

A
Inches
(mm)

Thread
Adapter
Size

Thread
Adapter
Length
Inches
(mm)

Min.

Max.

Min.

Max.

Short

3/4
(19)

1-1/4
(32)

1-3/4
(44)

1-1/2
(38)

2
(51)

5/16
(8)

Standard

1
(25)

1-1/2
(38)

2
(51)

1-3/4
(44

2-1/4
(57)

9/16
(14)

Medium

1-1/2
(38)

2
(51)

2-1/2
(64)

2-1/4
(57)

2-3/4
(70)

1-1/16
(27)

Long

2
(50)

2-1/2
(64)

3
(64)

2-3/4
(70)

3-1/4
(83)

1-9/16
(40)

B
Nominal
Inches
(mm)

Horizontal
Sidewall

Pendent

NOTES:
1. SPRINKLER FITTING AND WATERWAY CENTERLINE
MUST BE PERPENDICULAR TO ESCUTCHEON
MOUNTING SURFACE
2. MINIMUM THREAD ENGAGEMENT APPROX.
3/16" (5 mm) = 3 FULL REVOLUTIONS AFTER INITIAL
ENGAGEMENT OF SPRINKLER INLET THREADS WITH
THREAD ADAPTER OUTLET THREADS
3. THREAD ADAPTER NOT APPLICABLE WHEN
INSTALLING SPRINKLER DIRECTLY IN ISO 228 G3/8"
OUTLET THREADS OF CPVC SPRINKLER ADAPTER
FITTING (REF. FIGURES 4 AND 6)
A

7/16"
(11 mm)
NOMINAL
MAKE-IN

FACE OF
THREAD
ADAPTER

CEILING
OR WALL
COVERING
MATERIAL

FACE OF
SPRINKLER
FITTING

CLEARANCE
HOLE

CEILING
OR WALL
ESCUTCHEON
MOUNTING
SURFACE

SPRINKLER
FITTING AND
WATERWAY
CENETRLINE 1
SPRINKLER
FITTING 3

THREAD
ADAPTER 3

3/16" (5 mm)
MINIMUM THREAD
ENGAGEMENT 2

SPRINKLER
BODY ENGAGED
BY ESCUTCHEON
PRONGS

STYLE J OR K
ESCUTCHEON

FACE OF
FRAMING
MEMBER

FIGURE 5
RAVEN STUDIO SPRINKLERS
PENDENT AND HORIZONTAL SIDEWALL INSTALLATION CRITERIA

TFP658
Page 5 of 16

Fitting
Type

Fitting
Size
Inches x ISO 228
Outlet Threads

90 Elbow

1 x G3/8

Tee

1 x 1 x G3/8

A
Inches
(mm)
Horizontal
Sidewall

Pendent
Min.

Max.

Min.

Max.

7/8
(22)

1-1/4
(32)

1-1/8
(29)

1-1/2
(38)

NOTES:
1. SPRINKLER FITTING AND WATERWAY CENTERLINE
MUST BE PERPENDICULAR TO ESCUTCHEON
MOUNTING SURFACE
2. MINIMUM THREAD ENGAGEMENT APPROX.
7/32" (6 mm) = 4 FULL REVOLUTIONS AFTER INITIAL
ENGAGEMENT OF SPRINKLER INLET THREADS WITH
ADAPTER FITTING OUTLET THREADS

CPVC
PIPE FROM
SYSTEM
FACE OF
SPRINKLER
FITTING

A
CEILING
OR WALL
COVERING
MATERIAL

CEILING
OR WALL
ESCUTCHEON
MOUNTING
SURFACE

CLEARANCE
HOLE

CPVC SPRINKLER
ADAPTER FITTING
WITH ISO 228 G3/8"
OUTLET THREADS
(REF. FIGURE 4)
7/32" (6 mm)
MINIMUM THREAD
ENGAGEMENT 2

SPRINKLER
FITTING AND
WATERWAY
CENETRLINE 1
SPRINKLER
BODY ENGAGED
BY ESCUTCHEON
PRONGS

STYLE J OR K
ESCUTCHEON

FACE OF
FRAMING
MEMBER

FIGURE 6
RAVEN STUDIO SPRINKLERS
PENDENT AND HORIZONTAL SIDEWALL
LOW-PROFILE CPVC ADAPTER FITTING INSTALLATION CRITERIA

TFP658
Page 6 of 16

CAP PRONGS
UNIQUELY SPACED TO
ENGAGE SPRINKLER
WRENCHING NOTCHES

USE CAP FOR


SPRINKLER
INSTALLATION
AND PROTECTION
WHILE PAINTING

"UP" INDICATES
TOP OF HORIZONTAL
SIDEWALL SPRINKLER
DEFLECTOR

CAP IS FOR
SINGLE-USE ONLY
DO NOT RE-USE
AFTER PAINTING

CAP FLAT
ACCOMMODATES
LEVEL IF NECESSARY
FOR HORIZONTAL
SIDEWALL SPRINKLER
INSTALLATION
RAVEN STUDIO
SPRINKLER
FINGER
GRIP

CENTER
MARKING
POINT

FIGURE 7
RAVEN STUDIO SPRINKLERS
PAINT CAP APPLICATION

WRENCH PRONGS
UNIQUELY SPACED TO
ENGAGE SPRINKLER
WRENCHING NOTCHES

USE WRENCH
FOR SPRINKLER
INSTALLATION
AND REMOVAL

"UP" INDICATES
TOP OF HORIZONTAL
SIDEWALL SPRINKLER
DEFLECTOR

WRENCH FLAT
ACCOMMODATES
LEVEL IF NECESSARY
FOR HORIZONTAL
SIDEWALL SPRINKLER
INSTALLATION
RAVEN STUDIO
SPRINKLER
SOCKET ACCEPTS
1/2" DRIVE

FIGURE 8
RAVEN STUDIO SPRINKLERS
W-TYPE 25 WRENCH APPLICATION

TFP658
Page 7 of 16
NOTES:
STEEL
PIPE FROM
SYSTEM

1. USE ONLY LOCTITE 243 SEALANT FOR SEALING SPRINKLER


INLET THREAD CONNECTION IN STEEL PIPE SYSTEM
2. DO NOT USE LOCTITE 243 SEALANT IN CPVC PIPE SYSTEMS

LOCTITE 243
SEALANT
BOTTLE

3. APPLY SEALANT AROUND FIRST 2-3 (MINIMUM) SPRINKLER INLET


THREADS
4. ASSURE SEALANT AVOIDS CONTACT WITH INTERNAL SPRINKLER
WATERWAY; FAILURE TO DO SO MAY RESULT IN EQUIPMENT
FAILURE
5. INSTALL SPRINKLER IMMEDIATELY AFTER APPLYING SEALANT
6. ALLOW MINIMUM 1 HOUR CURE TIME BEFORE SYSTEM PRESSURE
TESTING
7. REFER TO LOCTITE 243 TECHNICAL DATA SHEET FOR MORE
INFORMATION, GO TO: www.loctite.com
RAVEN STUDIO SPRINKLER
WITH PAINT CAP OR
W-TYPE 25 WRENCH

SPRINKLER
INLET
THREADS

MALLEABLE OR CAST IRON


SPRINKLER FITTING
WITH THREAD ADAPTER

FIGURE 9
RAVEN STUDIO SPRINKLERS
LOCTITE 243 SEALANT APPLICATION STEEL PIPE SYSTEM INSTALLATIONS
NOTES:
CPVC
PIPE FROM
SYSTEM

1. USE ONLY PERMABOND LH056 SEALANT FOR SEALING SPRINKLER


INLET THREAD CONNECTION IN CPVC PIPE SYSTEM
2. APPLY SEALANT AROUND FIRST 4 (MINIMUM) SPRINKLER INLET
THREADS LEAVING FIRST THREAD FREE OF SEALANT

PERMABOND LH056
SEALANT
APPLICATOR

3. ASSURE SEALANT AVOIDS CONTACT WITH INTERNAL SPRINKLER


WATERWAY; FAILURE TO DO SO MAY RESULT IN EQUIPMENT
FAILURE
4. INSTALL SPRINKLER IMMEDIATELY AFTER APPLYING SEALANT
5. ALLOW MINIMUM 2 HOUR CURE TIME BEFORE SYSTEM PRESSURE
TESTING
6. REFER TO PERMABOND LH056 TECHNICAL DATA SHEET FOR MORE
INFORMATION, GO TO: www.permabond.com

RAVEN STUDIO SPRINKLER


WITH PAINT CAP OR
W-TYPE 25 WRENCH

CPVC SPRINKLER
HEAD ADAPTER FITTING,
ISO 228 G3/8" THREAD

SPRINKLER
INLET
THREADS

FIGURE 10
RAVEN STUDIO SPRINKLERS
PERMABOND LH056 SEALANT APPLICATION CPVC PIPE SYSTEM INSTALLATIONS

TFP658
Page 8 of 16

LIP OF SPRINKLER BODY, NOT


BRASS SHOULDER, FLUSH AGAINST
SPRINKLER BODY STOP SURFACE

SPRINKLER
FITTING WITH
THREAD
ADAPTER

BASE
CLEARANCE
HOLE

CEILING OR WALL
ESCUTCHEON
MOUNTING
SURFACE

FINISHED
SURFACE
INSTALLATION
TOOL

SPRINKLER
BODY STOP
CPVC SPRINKLER
ADAPTER FITTING
WITH ISO 228 G3/8"
OUTLET THREADS

FINISHED
SURFACE
INSTALLATION
TOOL

RAVEN STUDIO SPRINKLER


WITH PAINT CAP OR
W-TYPE 25 WRENCH

FIGURE 11
RAVEN STUDIO SPRINKLERS
FINISHED SURFACE INSTALLATION TOOL APPLICATION

36" (0,9 m) BEAM


ACCOMMODATES
VARIETY OF
FRAMING SPACINGS

ROUGH-IN
INSTALLATION TOOL
LIP OF SPRINKLER BODY,
NOT BRASS SHOULDER,
FLUSH AGAINST SPRINKLER
BODY STOP SURFACE
RAVEN STUDIO SPRINKLER
WITH PAINT CAP OR
W-TYPE 25 WRENCH

WIDE BASE OF
BEAM FLUSH
AGAINST FACE
OF FRAMING
MEMBERS

CARRIAGE
SPRINKLER
FITTING WITH
THREAD
ADAPTER

CPVC SPRINKLER
ADAPTER FITTING
WITH ISO 228 G3/8"
OUTLET THREADS

ADJUST TO
ALIGN EDGE
OF GAUGE
WITH MARKING
ON IMPERIAL
OR METRIC
SCALE TO SUIT
TOTAL COVERING
MATERIAL
THICKNESS

METRIC SCALE
(0 to 40 mm)

GAUGE LOCK
HANDLE

GAUGE
ADJUST TO
SUIT FRAMING
SPACING AND
FITTING
LOCATION

LOCK

UNLOCK

IMPERIAL SCALE
(0 to 1-1/2")

FIGURE 12
RAVEN STUDIO SPRINKLERS
ROUGH-IN INSTALLATION TOOL APPLICATION

FACE OF
WALL OR
CEILING
FRAMING
MEMBER

TFP658
Page 9 of 16
NOTES:
1. INSPECT WRENCHING NOTCH POSITIONS AFTER
ESCUTCHEON INSTALLATION TO VERIFY PROPER
HORIZONTAL SIDEWALL SPRINKLER DEFLECTOR
ORIENTATION

2. FARTHEST-SPACED WRENCHING NOTCH


LOCATED AT 12 O'CLOCK POSITION INDICATES
PROPER DEFLECTOR ORIENTATION

FACE OF
FINISHED
CEILING

SPRINKLER
FITTING

RAVEN
STUDIO
HORIZONTAL
SIDEWALL
SPRINKLER

FARTHEST-SPACED
WRENCHING NOTCH

4-7/16" (133 mm)


12-7/16" (316 mm)

SPRINKLER
FITTING AND
WATERWAY
CENTERLINE
THREAD
ADAPTER

STYLE J OR K
ESCUTCHEON
ESCUTCHEON
MOUNTING
SURFACE

CLOSEST-SPACED
WRENCHING NOTCHES

FIGURE 13
RAVEN STUDIO SPRINKLERS
HORIZONTAL SIDEWALL INSTALLATION CRITERIA
NOTES:
1. REFERENCE DIMENSION D = TOTAL CEILING
OR WALL COVERING MATERIAL THICKNESS
(DRYWALL, PLYWOOD, ETC. PLUS TAPE,
PLASTER, ETC.)

D
REF.

CEILING OR WALL
ESCUTCHEON
MOUNTING
SURFACE

CLEARANCE
HOLE

PLASTER,
TAPE, ETC.

CEILING
OR WALL
COVERING
MATERIAL

FIGURE 14
RAVEN STUDIO SPRINKLERS
TOTAL CEILING AND WALL COVERING MATERIAL THICKNESS

ENCLOSED
HORIZONTAL
SIDEWALL
DEFLECTOR

TFP658
Page 10 of 16
5.6K Extended Coverage Pendent (TY1282)
Response
Rating

Coverage Area
Ft. x Ft. (m x m)

Minimum
Flow(a)
gpm (lpm)

Minimum
Pressure(b)
psi (bar)

Deflector-to-Ceiling
Distance

Sprinkler
Temperature Rating
F (C)

Minimum
Spacing
Ft. (m)

Quick

16 x 16 (4,9 x 4,9)

26 (98)

21.6 (1,49)

Flush Mounted

165 (74)

8 (2,4)

5.6K Extended Coverage Horizontal Sidewall (TY1382)


Response
Rating

Coverage Area
Ft. x Ft. (m x m)

Minimum
Flow(a)
gpm (lpm)

Minimum
Pressure(b)
psi (bar)

Deflector-to-Ceiling
Distance(c)
Inches (mm)

Sprinkler
Temperature Rating
F (C)

Lateral
Minimum
Spacing(d)
Ft. (m)

Quick

16 x 16 (4,9 x 4,9)

26 (98)

21.6 (1,49)

4 to 12 (100 to 300)

165 (74)

8 (2,4)

Notes:
a. Requirement is based on minimum flow in gpm (lpm) from each sprinkler.
b. Indicated residual pressures are based on the nominal K-factor.
c. Centerline of the sprinkler waterway is located 7/16 inch (11,1 mm) below the deflector (Ref. Figure 15).
d. Minimum spacing is for lateral distance between sprinklers located along a single wall; otherwise, adjacent sprinklers (i.e., sidewall sprinklers on an adjacent wall, on an opposite wall, or pendent sprinklers) must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized.

TABLE A
RAVEN STUDIO SPRINKLERS
UL AND C-UL LISTING EXTENDED COVERAGE AREAS for LIGHT HAZARDS AND FLOW RATE CRITERIA

Design
Criteria
Standard Coverage Criteria
RAVEN Studio 5.6K Pendent and Horizontal Sidewall Sprinklers (TY1281 and
TY1381) are intended for use in light
hazard or ordinary hazard applications as defined by NFPA 13, utilizing
the density/area method for hydraulically calculated systems, and with
fire protection systems designed in
accordance with the standard installation rules recognized by the applicable listing or approval agency
(e.g., UL Listing is based on NFPA 13
requirements).
RAVEN Studio Horizontal Sidewall
Sprinklers (TY1381) must be installed
with a deflector-to-ceiling distance of 4
to 12 inches (100 to 300 mm). To meet
this requirement, the centerline of the
sprinkler waterway must be located
4-7/16 to 12-7/16 inches (112,7 to 315,9
mm) below the ceiling (Ref. Figures 13
and 15).
Extended Coverage Criteria
RAVEN Studio 5.6K Pendent and Horizontal Sidewall Sprinklers (TY1282 and
TY1382) must be installed in accordance with the flow rate criteria provided in Table A. They must be installed
and utilized in light hazard occupancies
only under smooth, flat, horizontal ceilings as outlined in the applicable installation standard recognized by the listing
or approval agency (e.g., UL Listing is
based on NFPA 13 requirements).
RAVEN Extended Coverage, Horizontal
Sidewall Sprinklers (TY1382) must be
installed with a deflector-to-ceiling distance of 4 to 12 inches (100 to 300 mm).
To meet this requirement, the centerline of the sprinkler waterway must be
located 4-7/16 to 12-7/16 inches (112,7

to 315,9 mm) below the ceiling (Ref.


Figures 13 and 15).

Operation
Water is prevented from flowing from
the RAVEN Studio Sprinkler by means
of a sealing assembly held in place
by operating parts secured by a link
assembly. The link assembly is comprised of two link halves soldered
together with an eutectic solder that
melts when exposed to heat. When
the link reaches its rated temperature,
the link halves separate and release
the operating parts and sealing assembly, allowing the deflector assembly to
extend from the body and water to flow
from the sprinkler.

Care and
Maintenance
TYCO RAVEN Studio Sprinklers 5.6K
Pendent and Horizontal Sidewall
(HSW) Quick Response, Standard and
Extended Coverage must be maintained and serviced in accordance with
this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities and
notify all personnel who may be affected by this action.
Service inspections should be made
on a regular basis to detect possible
damage or alterations to the sprinkler and escutcheon. Inspections
should include making certain that the
escutcheon is held fast to the mounting surface. Damaged or altered sprinklers are to be replaced immediately

to avoid personal injury and to prevent


use for causing personal injury, as well
as to maintain the sprinkler system in
an operative condition.

Sprinklers which are found to be


leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprinklers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced.
Frequent visual inspections are recommended to be initially performed for
sprinklers installed in potentially corrosive atmospheres to verify the integrity
of the materials of construction as they
may be affected by the corrosive conditions present for a given installation.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the approval agency and standards
of any other authority having jurisdiction. Contact the installing contractor or product manufacturer with any
questions.
Sprinklers are recommended to be
inspected, tested, and maintained by
a qualified Inspection Service in accordance with local requirements and/or
national codes.

TFP658
Page 11 of 16

RAVEN STUDIO
SPRINKLER

ESCUTCHEON
MOUNTING
SURFACE
ESCUTCHEON

9/16"
(14 mm)

SPRINKLER
DEFLECTOR ASSEMBLY
IN OPERATED POSITION
PENDENT

FACE OF
FINISHED CEILING
11/16"
(17 mm)
4" (102 mm)
TO
12" (305 mm)
TOP OF
DEFLECTOR
7/16"
(11 mm)

CENTERLINE
OF SPRINKLER
WATERWAY

RAVEN STUDIO
SPRINKLER

SPRINKLER
DEFLECTOR ASSEMBLY
IN OPERATED POSITION
ESCUTCHEON
ESCUTCHEON
MOUNTING
SURFACE

HORIZONTAL SIDEWALL

FIGURE 15
RAVEN STUDIO SPRINKLERS
OPERATED CONDITION

TFP658
Page 12 of 16

Installation

In finished surface construction, TYCO Raven Studio 5.6 K-factor Pendent and
Horizontal Sidewall Sprinklers must be installed in accordance with this section.

Preferred Method:
Finished Surface Procedure

This procedure describes sprinkler installation in construction where ceiling or wall


covering materialdrywall, plywood, etc.has been installed in advance.

Step 1

Step 2

Step 3

C
A

Step 1. Cut clearance hole through


covering material (Ref. Figure 2, Dim.
C).
Note: Location of hole centerline determined by design location of sprinkler.

Step 2. Install sprinkler fitting with


face located at proper distance from
escutcheon mounting surface (Ref.
Figures 5 or 6, Dim. A).
Note: Sprinkler fitting centerline must
be perpendicular to escutcheon
mounting surface.
Note: Fitting outlet: 1/2 NPT proceed
to Step 3; ISO 228 G3/8 proceed to
Step 4.

Step 4

Step 4. Remove shipping cap from


sprinkler by pulling away from body
along sprinkler centerline.
NOTICE
Sprinkler with shipping cap attached to
remain in original packaging until ready
for installation. To avoid damage to link
assembly, do not pull cap away from
sprinkler at an angle.

Step 5

Step 5. Engage sprinkler wrenching notches by paint cap or wrench


prongs (Ref. Figures 1, 7 and 8). Apply
sealant to sprinkler inlet threads (steel
pipe system installations Ref. Figure 9;
CPVC pipe system installations Ref.
Figure 10).
NOTICE
Assure sealant avoids contact with
internal waterway of sprinkler. Failure to
do so may result in equipment failure.

Step 3. Apply TEFLON tape sealant to


external threads of thread adapter and
install into sprinkler fitting.
A leak-tight 1/2 inch NPT thread adapter
joint should be obtained by applying a
minimum-to-maximum torque of 7 to
14 ft.-lbs. (9,5 to 19,0 Nm).
NOTICE
Higher levels of torque will distort the
thread adapter and cause leakage or
impairment of the sprinkler.

Step 6

Step 6. Grasping paint cap or wrench,


align sprinkler inlet threads with outlet
of thread adapter or CPVC sprinkler
adapter fitting and rotate clockwise to
initially engage threads.

TFP658
Page 13 of 16

Step 7

Step 8

Step 7. Place base of finished surface


installation tool flush against escutcheon mounting surface, positioning
sprinkler body stop against sprinkler
dust cap (Ref. Figures 1 and 11). Hold
tool in place.

Step 8. Grasp paint cap or wrench and


rotate sprinkler clockwise until painted
sprinkler body lip (not brass shoulder)
is flush with tool sprinkler body stop
(Ref. Figure 11). Remove installation
tool.

Note: Tool base must be held flush


against framing members for proper
sprinkler installation.

Note: Proceed to Step 9 for horizontal


sidewall sprinkler; proceed to Step 10
for pendent sprinkler.
Note: Allow time for sealant to set
before proceeding to Step 10: 5
minutes for LOCTITE 243; 30 minutes
for PERMABOND LH056.

Step 10

Step 10. Orient escutcheon base


flange toward mounting surface, aligning escutcheon centerline with sprinkler centerline. Push escutcheon onto
sprinkler, engaging body by prongs,
until flange is flush against mounting
surface.
Note: If ceiling or wall painting is not
intended, remove paint cap to complete installation; If ceiling or wall
painting is intended, proceed to
Step 11.

Step 11

Step 11. Paint ceiling or wall to suit.


Note: Paint cap to remain attached
while painting ceiling or wall.
Note: Install primed escutcheon for
best painting results (refer to Ordering
Procedure).

Step 9

Step 9. Orientation of paint cap or


wrench UP indicator arrow must be
in the 12 oclock position (horizontal
sidewall sprinkler only). Rotate sprinkler
clockwise a maximum 1 full revolution
to attain proper orientation. Remove
wrench.
Note: Proper sprinkler orientation may
also be verified by observing position
of sprinkler wrenching notches (Ref.
Figure 13).
Note: Allow time for sealant to set
before proceeding to Step 10: 5
minutes for LOCTITE 243; 30 minutes
for PERMABOND LH056.

Step 12

Step 12. Remove and discard paint


cap to complete installation.
Note: Paint cap is single-use only when
painting. Do not re-use after painting.

TFP658
Page 14 of 16

Installation

In rough-in construction, TYCO Raven Studio 5.6 K-factor Pendent and Horizontal
Sidewall Sprinklers must be installed in accordance with this section.

Alternate Method:
Rough-in Procedure

This procedure describes sprinkler installation in construction where ceiling or wall


covering materialdrywall, plywood, etc.has not been installed in advance.

Step A

Step B

Step C

A-D

Step A. Determine Dim. D, covering


material total thickness (Ref. Figure
14). Subtract Dim. D from Dim. A (Ref.
Figures 5 or 6). Install sprinkler fitting,
locating face at proper distance from
face of framing members using calculated value.
Note: Sprinkler fitting centerline must
be perpendicular to escutcheon
mounting surface.
Note: Adjust rough-in installation tool
depth (Ref. Figure 12) to suit Dim. D.

Step B. Apply TEFLON tape sealant to


external threads of thread adapter and
install into sprinkler fitting.
A leak-tight 1/2 inch NPT thread adapter
joint should be obtained by applying a
minimum-to-maximum torque of 7 to
14 ft.-lbs. (9,5 to 19,0 Nm).
NOTICE
Higher levels of torque will distort the
thread adapter and cause leakage or
impairment of the sprinkler.

Step C. Remove shipping cap from


sprinkler by pulling away from body
along sprinkler centerline.
NOTICE
Sprinkler with shipping cap attached to
remain in original packaging until ready
for installation. To avoid damage to link
assembly, do not pull cap away from
sprinkler at an angle.

Note: Fitting outlet: 1/2 NPT proceed


to Step B; ISO 228 G3/8 proceed to
Step C.
Step D

Step D. Engage sprinkler wrenching notches by paint cap or wrench


prongs (Ref. Figures 1, 7 and 8). Apply
sealant to sprinkler inlet threads (steel
pipe system installations Ref. Figure 9;
CPVC pipe system installations Ref.
Figure 10).
NOTICE
Assure sealant avoids contact with
internal waterway of sprinkler. Failure to
do so may result in equipment failure.

Step E

Step E. Grasping paint cap or wrench,


align sprinkler threads with thread
adapter port and rotate clockwise to
initially engage threads.

Step F

Step F. Place rough-in installation tool


base flush against framing members,
positioning sprinkler body stop against
sprinkler dust cap (Ref. Figures 1 and
12). Hold tool in place.
Note: Tool base must be held flush
against framing members for proper
sprinkler installation.

TFP658
Page 15 of 16

Step G

Step H

Step J

Step G. Grasp paint cap or wrench and


rotate sprinkler clockwise until painted
sprinkler body lip (not brass shoulder)
is flush with tool sprinkler body stop
(Ref. Figure 12). Remove installation
tool.
Note: Proceed to Step H for horizontal
sidewall sprinkler; proceed to Step J for
pendent sprinkler.
Note: Allow time for sealant to set
before proceeding to Step J: 5 minutes
for LOCTITE 243; 30 minutes for PERMABOND LH056.

Step K

Step K. Orient escutcheon base


flange toward mounting surface, aligning escutcheon centerline with sprinkler centerline. Push escutcheon onto
sprinkler, engaging body by prongs,
until flange is flush against mounting
surface.
Note: If ceiling or wall painting is not
intended, remove paint cap to complete installation; If ceiling or wall
painting is intended, proceed to
Step L.

Step H. Orientation of paint cap or


wrench UP indicator arrow must be
in the 12 oclock position (horizontal
sidewall sprinkler only). Rotate sprinkler
clockwise a maximum 1 full revolution
to attain proper orientation. Remove
wrench.
Note: Proper sprinkler orientation may
also be verified by observing position
of sprinkler wrenching notches (Ref.
Figure 13).
Note: Allow time for sealant to set
before proceeding to Step J: 5 minutes
for LOCTITE 243; 30 minutes for PERMABOND LH056.

Step L

Step L. Paint ceiling or wall to suit.


Note: Paint cap to remain attached
while painting ceiling or wall.
Note: Install primed escutcheon for
best painting results (refer to Ordering
Procedure).

Step J. Hold covering material in its


installed position and press against
paint cap marking point. Cut clearance hole through covering material
(Ref. Figure 2, Dim. C) using resulting
mark as center point. Install covering
material, assuring sprinkler is centered
in clearance hole.
Note: Paint cap to remain attached for
marking center point of covering material clearance hole.
NOTICE
Install only covering material having
total thickness used in Step A.

Step M

Step M. Remove and discard paint cap


to complete installation.
Note: Paint cap is single-use only when
painting. Do not re-use after painting.

TFP658
Page 16 of 16

Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.

Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product description and Part
Number (P/N).
Note: Order all components separately.
A complete assembly consists of sprinkler, escutcheon, thread adapter and
inlet thread sealant. Order installation
tools and accessories as needed.
Sprinklers
Specify: RAVEN Studio 5.6K Sprinkler, (specifiy) SIN, (specify) coverage,
(specify) orientation, (specify) finish,
P/N (specify):
Standard Coverage
TY1281 Pendent
White . . . . . . . . . . . . . . . . . . . . . . . 50-310-4-165
Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-310-9-165
Custom Color . . . . . . . . . . . . . . . . 50-310-X-165
TY1381 Horizontal Sidewall
White . . . . . . . . . . . . . . . . . . . . . . . 50-312-4-165
Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-312-9-165
Custom Color . . . . . . . . . . . . . . . . 50-312-X-165

Extended Coverage

TY1282 Pendent
White . . . . . . . . . . . . . . . . . . . . . . . 50-311-4-165
Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-311-9-165
Custom Color . . . . . . . . . . . . . . . . . 50-311-X-165
TY1382 Horizontal Sidewall
White . . . . . . . . . . . . . . . . . . . . . . . 50-318-4-165
Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-318-9-165
Custom Color . . . . . . . . . . . . . . . . 50-313-X-165

Style J Escutcheons
(3 Inch Diameter)
Specify: RAVEN Studio Sprinkler
Escutcheon, Style J, 3 inch diameter,
(specify) material, (specify) finish, P/N
(specify):
Carbon Steel
White . . . . . . . . . . . . . . . . . . . . . . . 56-306-4-010
Grey . . . . . . . . . . . . . . . . . . . . . . . . 56-306-7-010
Chrome . . . . . . . . . . . . . . . . . . . . . 56-306-9-010
Primed White . . . . . . . . . . . . . . . . . 56-306-0-004
Primed Grey . . . . . . . . . . . . . . . . . 56-306-0-007
Custom Color . . . . . . . . . . . . . . . . 56-306-X-010
Stainless Steel
White . . . . . . . . . . . . . . . . . . . . . . . 56-307-4-010
Grey . . . . . . . . . . . . . . . . . . . . . . . . 56-307-7-010
Electropolish* . . . . . . . . . . . . . . . . 56-307-9-010
Primed White . . . . . . . . . . . . . . . . . 56-307-0-004
Primed Grey . . . . . . . . . . . . . . . . . 56-307-0-007
Custom Color . . . . . . . . . . . . . . . . 56-307-X-010
* Chrome-coated appearance

Style K Escutcheons
(4 Inch Diameter)
Specify: RAVEN Studio Sprinkler
Escutcheon, Style K, 4 inch diameter,
(specify) material, (specify) finish, P/N
(specify):
Carbon Steel
White . . . . . . . . . . . . . . . . . . . . . . . 56-308-4-010
Grey . . . . . . . . . . . . . . . . . . . . . . . . 56-308-7-010
Chrome . . . . . . . . . . . . . . . . . . . . . 56-308-9-010
Primed White . . . . . . . . . . . . . . . . . 56-308-0-004
Primed Grey . . . . . . . . . . . . . . . . . 56-308-0-007
Custom Color . . . . . . . . . . . . . . . . 56-308-X-010
Stainless Steel
White . . . . . . . . . . . . . . . . . . . . . . . 56-309-4-010
Grey . . . . . . . . . . . . . . . . . . . . . . . . 56-309-7-010
Electropolish* . . . . . . . . . . . . . . . . 56-309-9-010
Primed White . . . . . . . . . . . . . . . . . 56-309-0-004
Primed Grey . . . . . . . . . . . . . . . . . 56-309-0-007
Custom Color . . . . . . . . . . . . . . . . 56-309-X-010
* Chrome-coated appearance

Thread Adapters
Specify: RAVEN Studio Sprinkler
Thread Adapter, Brass, (specify) size,
P/N (specify):
Short 3/4 (19 mm) . . . . . . . . . . . . 91-310-0-075
Standard 1 (25 mm) . . . . . . . . . . . 91-310-0-100
Medium 1-1/2 (38 mm) 91-310-0-150
Long 2 (50 mm) . . . . . . . . . . . . . . 91-310-0-200

CPVC Sprinkler Adapter Fittings


Specify: CPVC Sprinkler Adapter
Fitting, (specify type), (specify) size,
P/N (specify):
90 Elbow
1 x ISO 228 G3/8 82198
Tee
1 x 1 x ISO 228 G3/8 82251

Sprinkler Inlet Thread Sealant


Specify: LOCTITE 243 Thread Sealant,
10 ml Bottle, P/N 91-310-1-243
Specify: PERMABOND LH056 Thread
Sealant, 350 ml Container, P/N 33045
Note: PERMABOND LH056 thread
sealant has a 12-month shelf life. Purchase of new container recommended for each RAVEN Studio Sprinkler
project.
Sprinkler Installation Tools
Specify: RAVEN Studio Installation
Tool, (specify type), P/N (specify):
Finished Surface . . . . . . . . . . . . . . 56-100-0-355
Rough-in . . . . . . . . . . . . . . . . . . . . 56-100-0-365

Paint Cap
Specify: RAVEN Studio Sprinkler Paint
Cap, P/N 56-100-0-354
Sprinkler Wrench
Specify: W-Type 25 Sprinkler Wrench,
P/N 56-314-1-001

Note: Contact Tyco Customer Service


at +1-800-558-5236 with any questions
related to custom orders.

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2015 Tyco Fire Products, LP. All rights reserved.

TEFLON is trademark of the DuPont Corporation; LOCTITE is a trademark of Henkel Corporation;


PERMABOND is a trademark of Permabond LLC

Worldwide
www.tyco-fire.com
Contacts

Series TY-FRB 5.6 K-factor


Conventional (Old Style) Sprinklers
Quick Response
General
Description
The TYCO Series TY-FRB, 5.6 K-factor, Conventional Sprinklers, Quick
Response described in this technical
data sheet are quick response, standard coverage, decorative 3 mm glass
bulb type spray sprinklers. These sprinklers are intended to be installed either
pendent or upright, and in either position, they produce a spherical water
discharge pattern with approximately
50% of the discharge directed upwards
and approximately 50% of the discharge directed downwards.
Conventional sprinklers are generally used with Ordinary and Extra High
Hazard Class Systems, as defined by
the automatic sprinkler system installation rules of the country and authority having jurisdiction. The National Fire
Protection Association (NFPA) permits
the use of Old Style Sprinklers where
special construction features require a
unique water distribution; for the protection of fur vaults; or, the replacement of similar sprinklers that had been
installed prior to 1955.
NOTICE
The Series TY-FRB Sprinklers described herein must be installed and
maintained in compliance with this document, as well as with the applicable
standards of the National Fire Protection Association, in addition to the standards of any other authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.

The owner is responsible for maintaining their fire protection system


and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.

Sprinkler
Identification
Numbers (SINs)
TY363
TY3630 (LPCB Approved only)

Technical
Data
Approvals
UL and C-UL Listed
VdS Approved
LPCB Approved (TY3630 only)
Sprinklers with Polyester Finish are UL
and C-UL Listed as Corrosion-Resistant Sprinklers.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=5.6 gpm/psi1/2 (80,6 lpm/bar1/2)
Temperature Ratings
135F (57C)
155F (68C)
175F (79C)
200F (93C)
286F (141C)

Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.

Design
Criteria
The TYCO Series TY-FRB, 5.6 K-factor, Conventional Sprinklers, Quick
Response are intended for fire protection systems designed in accordance
with the standard installation rules recognized by the applicable Listing or
Approval agency (e.g., UL Listing is
based on NFPA 13 requirements). The
Series TY-FRB Conventional Sprinklers
are only for non-recessed applications.

Finishes
Sprinkler: Refer to Table A.
Physical Characteristics

IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 4

Frame ........................................................ Bronze


Button ............................................. Brass/Copper
Sealing Assembly...........................Stainless Steel
w/TEFLON
Bulb ............................................................. Glass
Compression Screw Bronze
Deflector..................................................... Bronze

FEBRUARY 2015

TFP667

TFP667
Page 2 of 4
Components: * Temperature
rating is indicated
1 - Frame
on Deflector.
2 - Button
3 - Sealing
6*
Assembly
4 - Bulb
5
5 - Compression
Screw
4
6 - Deflector *

ESCUTCHEON PLATE
SEATING SURFACE

2"
(50,8 mm)

** Pipe thread

7/16" (11,1 mm)


NOMINAL
1/2"
NPT ** MAKE-IN

1-3/8"
(34,9 mm)

3
connections per
ISO 7-1 can be
1
provided on
special request.
CROSS SECTION
SHOWN UPRIGHT

WRENCH
FLATS
SHOWN
PENDENT

FIGURE 1
SERIES TY-FRB CONVENTIONAL SPRINKLERS (TY363 & TY3630)
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE

Installation
The TYCO Series TY-FRB, 5.6 K-factor, Conventional Sprinklers, Quick
Response must be installed in accordance with this section.
General Instructions
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss
of liquid from the bulb. With the sprinkler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135F (57C) to 3/32
inch (2,4 mm) for the 286F (141C) temperature ratings.
A leak-tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7 to
14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque may distort the sprinkler inlet
and cause leakage or impairment of the
sprinkler.
Step 1. With pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step 2. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 2).
With reference to Figure 1, the W-Type
6 Sprinkler Wrench is to be applied to
the wrench flats.

Care and
Maintenance
The TYCO Series TY-FRB, 5.6 K-factor, Conventional Sprinklers, Quick
Response must be maintained and serviced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid damage to the sprinklers before, during, and
after installation. Sprinklers damaged
by dropping, striking, wrench twist/
slippage, or the like, must be replaced.
Also, replace any sprinkler that has a
cracked bulb or that has lost liquid from
its bulb. (Refer to Installation Section.)
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Association (e.g., NFPA 25), in addition to
the standards of any other authorities

WRENCH RECESS
(USE ONLY
END "A")

FIGURE 2
W-TYPE 6
SPRINKLER WRENCH
having jurisdiction. Contact the installing contractor or product manufacturer
with any questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspection Service in accordance with local
requirements and/or national codes.

TFP667
Page 3 of 4

P/N*77XXXXXXX
SPRINKLER
FINISH

SIN

TEMPERATURE
RATINGS

373

5.6K CONVENTIONAL

TY363

NATURAL
BRASS

135

135F (57C)

373

5.6K CONVENTIONAL

TY3630**

PURE WHITE (RAL9010)***


POLYESTER

155

155F (68C)

SIGNAL WHITE (RAL9003)


POLYESTER

175

175F (79C)

CHROME
PLATED

200

200F (93C)

286

286F (141C)

Notes:
* Use suffix I for ISO 7-1 connection (e.g., 77-373-4-175-I)
** LPCB Approved Series TY-B Conventional Sprinkler assemblies only: Use suffix L for LPCB Approved assemblies (e.g., 77-373-4-175-L or 77-373-4-175-IL for LPCB
Approved and ISO 7-1 connection)
*** Eastern Hemisphere sales only

TABLE A
PART NUMBER SELECTION
SERIES TY-FRB CONVENTIONAL SPRINKLERS

Limited
Warranty

Ordering
Procedure

For warranty terms and conditions, visit


www.tyco-fire.com.

Contact your local distributor for


availability. When placing an order,
indicate the full product name and
Part Number (P/N).
Sprinkler Assemblies with
NPT Thread Connections
Specify: Series TY-FRB Conventional
Sprinkler, (specify) SIN, K=5.6, Quick
Response, (specify) temperature rating), (specify) finish, P/N (specify, refer
to Table A)
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387

TFP667
Page 4 of 4

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2015 Tyco Fire Products, LP. All rights reserved.
TEFLON is trademark of The DuPont Corporation.

Worldwide
Contacts

www.tyco-fire.com

FASTFLEX Model YN25, YB25, and YB28


Flexible Sprinkler Hose Assembly
Europe, Middle East, and Africa Only
General
Description

Technical
Data

The TYCO FASTFLEX Flexible Sprinkler


Hose is a unique sprinkler drop assembly comprised of a branchline adapter
nipple, stainless steel flexible hose
with two slip nuts, sprinkler reducer,
and lightweight ceiling bracket components. (Ref. Figure 1.)

Approvals
UL Listed
FM Approved
VdS Approved
LPCB Approved

The FASTFLEX Flexible Sprinkler Hose


can be installed in false ceilings without
cutting and threading pipes associated with installing a drop, armover,
and elbows. FASTFLEX makes it possible to test and charge the system with
water before the ceiling grid is installed.
Once the ceiling grid is in position, the
FASTFLEX hoses can be reshaped to
suit the final sprinkler location without
draining the system.
FASTFLEX Flexible Sprinkler Hose
is installed quickly without large and
expensive tools. Ideal projects are
offices, schools, libraries, hospitals,
and shopping complexes. FASTFLEX
sprinkler hoses are for use on wet pipe,
preaction, and dry pipe systems. The
FASTFLEX hose can also be used in
conjunction with ultra-low flow water
mist nozzles following the design criteria outlined in this technical data sheet.
NOTICE
The FASTFLEX flexible sprinkler hoses
described herein must be installed
and maintained in compliance with
this document and with the applicable
standards recognized by the Approval
agency, in addition to the standards of
any other authorities having jurisdiction.
Failure to do so may impair the performance of these devices.

(Specific details for laboratory


approvals are given in Table A, and
the approvals apply to the service
conditions indicated in the applicable
Design Criteria sections)
APSAD accepted per Table A
CSTB accepted for all models and
assembly lengths
Inlet Connections (Ref. Figure 1)
ISO 7-R 1
ISO 7-R 1 1/4
Outlet Connections (Ref. Figure 2)
ISO 7-Rc 3/8
1/2 inch NPT
3/4 inch NPT
Nominal Assembly Lengths
Ref. Table A
Construction (Ref. Figure 1)
The Inlet Nipple is mild steel, and the
Flexible Hose is SS AISI 304. The
connection at each end of the Flexible
Hose utilizes a brass Slip Nut, NBR/
CR o-ring, and Nylon W6 washer. The
Sprinkler Reducer is mild steel. The
Reducer Bracket, Bar Fixing Clamps,
and Support Bar are pressed steel.

The owner is responsible for maintaining their fire protection system


and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.

Page 1 of 8

APRIL 2015

TFP720

TFP720
Page 2 of 8
BRANCHLINE FITTING OUTLET

ISO 7-R 1 or
ISO 7-R 1-1/4
PIPE THREADED
END

FLEXIBLE HOSE
WITH SLIP NUTS:
25 mm ID UNBRAIDED
25 mm ID BRAIDED
25 mm ID BRAIDED - FM
28 mm ID BRAIDED
28 mm ID BRAIDED - FM

25 or 28 mm ID
HOSE THREADED
END

INLET
NIPPLE

SUPPORT
BAR

BAR
FIXING
CLAMP WITH
BUTTERFLY
BOLTS

25 or 28 mm ID
HOSE THREADED
SPRINKLER REDUCER
(STRAIGHT SHOWN)
SEE FIGURE 2
FOR DETAILS

REDUCER
BRACKET WITH
BUTTERFLY
BOLTS

SCREW

DROP-IN
CEILING PANEL

CEILING
GRID
T-BAR

TYPICAL SPRINKLER
ASSEMBLY
600 mm

BRANCHLINE
FITTING
(NOT INCLUDED)

INLET
NIPPLE

SYSTEM
BRANCHLINE

FLEXIBLE HOSE
WITH SLIP NUTS:
25 mm ID UNBRAIDED
25 mm ID BRAIDED
25 mm ID BRAIDED - FM
28 mm ID BRAIDED
28 mm ID BRAIDED - FM

ISO 7-R 1 or
ISO 7-R 1-1/4
THREADED
FITTING
OUTLET

SPRINKLER
REDUCER
(SEE FIGURE 2)
HOSE
THREADED
SLIP NUT

BAR
FIXING
CLAMP WITH
BUTTERFLY
BOLTS

SUPPORT
BAR

REDUCER
BRACKET WITH
BUTTERFLY
BOLTS

CEILING
GRID
T-BAR
DROP-IN
CEILING
PANEL
SPRINKLER INSTALLED
IN ACCORDANCE WITH
MANUFACTURER'S
INSTRUCTIONS

FIGURE 1
FASTFLEX FLEXIBLE SPRINKLER HOSE

TFP720
Page 3 of 8

INLET
NIPPLE
L1

700
1000
1200
1500
1800
2000
2500
2700
3100
3700

L2
SLIP
NUT
FLEXIBLE
HOSE

BRANCHLINE
FITTING

NOMINAL LENGTH mm
L1
L2
L2
(YN or YB)
(YN)
(YB)

MODEL
SIZE

HOSE
TERMINATION
FERRULE

580
880
1080
1380
1680
1880
2380
2580
2980
3580

390
690
890
1190
1490
1690
2190
2390
2790
3390

370
670
870
1380
1470
1670
2170
2370
2770
3370

SPRINKLER
REDUCER
HOSE ASSEMBLIES

25 or 28 mm ID
MALE HOSE
THREADED
INLET

125 mm

WRENCH
AND BRACKET
FLATS

WRENCH
AND BRACKET
FLATS

120 mm

ISO 7-Rc 3/8,


1/2" NPT,
or 3/4" NPT
FEMALE PIPE
THREADED
OUTLET

25 or 28 mm ID
MALE HOSE
THREADED
INLET

125 mm

STRAIGHT

WRENCH
AND BRACKET
FLATS

ISO 7-Rc 3/8,


1/2" NPT,
or 3/4" NPT
FEMALE PIPE
THREADED
OUTLET

140 mm

45 DEGREE

133 mm

ISO 7-Rc 3/8,


1/2" NPT,
or 3/4" NPT
FEMALE PIPE
THREADED
OUTLET
90 DEGREE

SPRINKLER REDUCERS

50 mm

25 or 28 mm ID
MALE HOSE
THREADED
INLET

90 mm
BAR FIXING CLAMPS

FIGURE 2
FASTFLEX FLEXIBLE SPRINKLER HOSE
NOMINAL DIMENSIONS

TFP720
Page 4 of 8

LPCB - Design Criteria

VdS - Design Criteria

Refer to Table A for Model, Nominal Assembly Length,


and Sprinkler Reducer combinations.

Refer to Table A for Model, Nominal Assembly Length,


and Sprinkler Reducer combinations.

Wet-pipe systems only.

Wet-pipe systems only.

Maximum service pressure of 16 bar.

Maximum service pressure of 16 bar.

Sprinklers with nominal K57, K80, or K115.

Pendent sprinklers with nominal K57, K80, or K115.

Maximum ambient temperature of 148C for YN25.

Maximum ambient temperature of 107C for YB25 and


YB28.

A pproved as a Type 2 hose of moderate flexibility


in accordance with LPS 1261. They may be used in
applications where little or no differential movement
between the two ends is expected after installation
(e.g., supply to single sprinklers in suspended ceilings).
Approved for the following locations:
Assembly Pre-Calculated Pre-Calculated
Fully
Length in
Hydraulically
Town
Mains
Pumps
Millimeters
Calculated

A pproved for use only in the following suspended


ceilings:
Odenwald Systems- S3 & S15
Richter Systems- 11.1 - 11.5
Armstrong Systems- Board and Tegular with panel
type Prima Sahara
API Systems- 15/38, 24/38, 24/60, 35/38, and 35/60
with panel type of a.m.

Up to 700

Yes

Yes

Yes

VdS Friction Loss

Up to 1200

No

Yes

Yes

Up to 3700

No

No

Yes


For compensation of pressure loss, the nominal
assembly length is to be multiplied by 12. The resulting
length will provide pressure drop in equivalent length
DN20 (26,9 x 2,3 mm) seamless metal tube per DIN
2448.

All pipe work supplying FASTFLEX in pre-calculated


systems shall be sized as distribution mains.
In suspended ceilings FASTFLEX must be installed in
accordance with this data sheet.

In suspended ceiling, sprinkler reducer must be
connected to the ceiling support system with brackets
supplied. For other applications the installer must
supply brackets to ensure sprinkler is secure.
Minimum bend radius of 55 mm.
LPCB Friction Loss for YN25.
Assembly
Length in
Millimeters

Number of
90 Bends

Equivalent Length* of
DN25 Sch. 40 Pipe at
C=120 in Meters

700

8,9

1000

13,5

1200

11,9

1500

18,7

1800

24,7

2000

20,7

2500

21,7

2700

24,2

3100

25,9

3700
3
30,3
* Add 2,3 meters when using a 45 or 90 sprinkler
reducer.

Add 2,3 m when using a 45 or 90 sprinkler reducer.


Minimum bend radius of 55 mm.
The tube assembly may not have more than one 90
bend or four 15 bends.

TFP720
Page 5 of 8

FM - Design Criteria

UL - Design Criteria

Refer to Table A for Model, Nominal Assembly Length,


and Sprinkler Reducer combinations.

Refer to Table A for Model, Nominal Assembly Length,


and Sprinkler Reducer combinations.

Wet pipe, preaction, and dry pipe systems.

Wet-pipe systems only.

Maximum service pressure of 12 bar.

The hose and fittings have limited flexibility and are


intended for direct connection to sprinklers in accordance with NFPA 13, 13D, or 13R.

Sprinklers with a maximum K80 (K5.6) for 1/2 inch


NPT or maximum K115 (K8.0) for 3/4 inch NPT.
Maximum ambient temperature of 107C for Model
YB25 and YB28.
Minimum ambient temperature of -40C for Model
YB25 and YB28 for use in dry pipe systems.
These connections are designed for use in ceilings
with grids that meet ASTM C 635 (Standard Specification for the Manufacture, Performance, and Testing
of Metal Suspension Systems for Acoustical Tile and
Lay-in Panel Ceilings) and ASTM C 636 (Standard
Practice for Installation of Metal Ceiling Suspension
Systems for Acoustical Tile and Lay-in Panels) referenced by IBC. The three structural classifications
are the following: Intermediate-Duty Systems and
Heavy-Duty Systems. These connections have been
approved for use in all Intermediate-Duty and HeavyDuty structural classifications.
Minimum bend radius of 152 mm for Model YB28 or
203 mm for Model YB25.
FM Friction Loss for YB25 and YB28:
YB25
YB28
Max
Assembly Outlet Number
Equivalent
Equivalent
Length in
of 90 Length of DN25 Length of DN25
Millimeters (NPT) Bends
Sch. 40 Pipe
Sch. 40 Pipe
C=120 in Meters C=120 in Meters
700
1/2
1
14,1
7,7
3/4
1
11,9
6,0
1000
1/2
1
16,4
12,2
3/4
1
13,8
10,4
1200
1/2
2
22,4
15,2
3/4
2
19,6
13,4
1500
1/2
3
27,4
17,6
3/4
3
26,4
16,1
1800
1/2
4
34,4
20,0
3/4
4
32,0
18,7

Maximum service pressure of 13 bar.


Sprinklers with a maximum K80 (K5.6) for 1/2 inch
NPT or maximum K115 (K8.0) for 3/4 inch NPT.
Maximum ambient temperature of 107C for Model
YB25 and YB28, or maximum ambient temperature
of 148C for Model YN25.
These connections are designed for use in ceilings
with grids that meet ASTM C 635 (Standard Specification for the Manufacture, Performance, and Testing
of Metal Suspension Systems for Acoustical Tile and
Lay-in Panel Ceilings) and ASTM C 636 (Standard
Practice for Installation of Metal Ceiling Suspension
Systems for Acoustical Tile and Lay-in Panels) referenced by IBC. The three structural classifications
are the following: Intermediate-Duty Systems and
Heavy-Duty Systems. These connections have been
approved for use in all Intermediate-Duty and HeavyDuty structural classifications.
Minimum bend radius of 76 mm.
YN25 and YB25
YB28
Assembly Outlet Maximum
Equivalent
Equivalent
Number
Length in
of 90 Length of DN25 Length of DN25
Millimeters (NPT) Bends*
Sch. 40 Pipe at Sch. 40 Pipe at
C=120 in Meters C=120 in Meters
1/2

6,7

3,0

3/4

8,5

4,9

1/2

9,8

4,9

3/4

11,6

7,0

1/2

12,5

6,1

3/4

14,6

7,6

1/2

14,9

7,0

3/4

16,5

8,5

18,3

7,9

20,4

9,8

20,4

10,1

22,6

11,6

700

1000

1200

1500

1/2
1800
3/4
* Information in this column indicates the maximum number of allowable bends and that hoses are installed with at least one bend.

TFP720
Page 6 of 8

Model

Type

Assembly
Length in
Millimeters

LPCB

VdS

FM

UL*

APSAD**

50 and 90 mm
Bar Fixing
Clamp

50 and 90 mm
Bar Fixing
Clamp

50 and 90 mm
Bar Fixing
Clamp

50 mm
Bar Fixing
Clamp

50 and 90 mm
Bar Fixing
Clamp

Sprinkler
Reducer Type

Sprinkler
Reducer Type

Sprinkler
Reducer Type

Sprinkler
Reducer Type

Sprinkler
Reducer Type

45

90

45

90

45

90

45

90

YN25-700

Un-braided

700

YN25-1000

Un-braided

1000

YN25-1200

Un-braided

1200

YN25-1500

Un-braided

1500

YN25-1800

Un-braided

1800

YN25-2000

Un-braided

2000

YN25-2500

Un-braided

2500

YN25-2700

Un-braided

2700

YN25-3100

Un-braided

3100

YN25-3700

Un-braided

3700

YB25-700

Braided

700

YB25-1000

Braided

1000

YB25-1200

Braided

1200

YB25-1500

Braided

1500

YB25-1800

Braided

1800

YB25-2000

Braided

2000

YB25-2500

Braided

2500

YB25-700

Braided-FM

700

YB25-1000

Braided-FM

1000

YB25-1200

Braided-FM

1200

YB25-1500

Braided-FM

1500

YB25-1800

Braided-FM

1800

YB28-700

Braided

700

YB28-1000

Braided

1000

YB28-1200

Braided

1200

YB28-1500

Braided

1500

YB28-1800

Braided

1800

YB28-2000

Braided

2000

YB28-2500

Braided

2500

YB28-700

Braided - FM

700

YB28-1000

Braided - FM

1000

YB28-1200

Braided - FM

1200

YB28-1500

Braided - FM

1500

YB28-1800

Braided - FM

1800

45

90

x Indicates Listed or Approved as applicable.


* UL Listing is based on the use of the ISO 7-R 1 Inlet Connection.
** Acceptance by APSAD is based on using the LPCB, VdS, FM Approved, or UL Listed Design Criteria as may be accept-

able to the authority having jurisdiction.

TABLE A
FASTFLEX SPRINKLER HOSE ASSEMBLY
MODELS, ASSEMBLY LENGTHS, AND APPROVALS

TFP720
Page 7 of 8
BRANCHLINE
FITTING
OUTLET

INLET
NIPPLE

ISO 7-R 1
OR ISO 7-R 1 1/4
THREADED END
PERMITTED

NOT PERMITTED

SLIP
NUT

FLEXIBLE
HOSE TO
SPRINKLER

MACHINE HOSE
THREADED
END

NOT PERMITTED

DO route the FASTFLEX Flexible Hose to permit entire draining


either back into the branch-line or through the sprinkler reducer.

DO use the FASTFLEX Inlet Nipple with the direction


of flow arrow properly oriented to avoid mismatched
threads.

FIGURE 3
FASTFLEX FLEXIBLE SPRINKLER HOSE
INSTALLATION GUIDANCE

Installation
The TYCO FASTFLEX Flexible Sprinkler Hose as shown in Figure 1, must
be installed in accordance with this
section.
NOTICE
Flexible Hoses are intended only to
connect sprinklers directly to system
piping (Ref. Figure 1). Flexible Hoses
cannot be joined together to form
longer hoses. Joining Flexible Hoses
together creates an assembly with
unknown performance that has not
been accounted for in system calculations or safe product performance.
Step 1. Review the Design Criteria
section that applies to the Approval
agency recognized by the authority
having jurisdiction, as well as Figure 3
that provides installation guidance.
Step 2. Determine the approximate
place where the sprinkler will be
located. The Support Bar is 700 mm
long and shall be mounted on the
600 mm width of the ceiling grid. The
sprinkler should be located as close as
possible to the center of the distance
between ceiling grid T-bars.
Step 3. Slide the Reducer Bracket
onto the Support Bar. Loosely attach
the Reducer Bracket and the two Bar
Fixing Clamps on the Support Bar and
place the Bar Fixing Clamps such that
the Support Bar crosses the location
where the sprinkler will be located.
Step 4. Attach one end of the Flexible Hose onto the sprinkler reducer.
Applying the wrench to the Slip Nut,
and not to the Flexible Hose, tighten to
a maximum torque of 35 Nm.

Step 5. Attach the Inlet Nipple on to the


branch line. Ensure that the arrow is in
the appropriate direction of flow to the
sprinkler and to use pipe thread sealant
at the connection to the branch line.
Attach one end of the Flexible Hose on
to the Inlet Nipple. Applying the wrench
to the Slip Nut, and not to the Flexible
Hose, tighten to a maximum torque of
35 Nm. Do not twist the Flexible Hose.
Step 6. Bend the Flexible Hose into
a curve(s) that locates the Sprinkler
Reducer at the other end of the Flexible
Hose in the area where the sprinkler will
be located. The tube arc should not be
twisted, and the arc should be as large
and smooth as possible.
NOTICE
For minimum bend criteria, refer to the
Design Criteria section that applies to
the Approval agency recognized by the
authority having jurisdiction.
A bend radius smaller than provided by the minimum bend criteria
may adversely effect the friction loss
specifications stated by the approval
laboratory.
For assembly lengths greater than
1800 mm the Flexible Hose shall be
supported to the structure to ensure
that the maximum unsupported length
does not exceed 1800 mm. In these
cases, it is recommended that the tube
be secured to a fixed mounting point
every 600 mm, in order to provide a
more stable installation.
For installations per LPCB, all bends
greater than 45 shall be fitted with a
MRI55 Plastic Clip Minimum Radius
Indicator (Ref. Figure 4).

Step 7. Insert the Sprinkler Reducer


into the Reducer Bracket. Locate
the Reducer Bracket and Sprinkler
Reducer where the sprinkler will be,
and loosely tighten the Butterfly Bolt
on the Reducer Bracket.
Step 8. Attach the sprinkler to the
Sprinkler Reducer. Put a wrench on
the Sprinkler Reducer to counteract the
tightening torque and prevent the Flexible Hose from twisting. Reference the
sprinkler manufacturers sprinkler data
sheet for appropriate sprinkler tightening torque, sprinkler wrench, and other
guidance.
Step 9. Verify that the Sprinkler
Reducer is seated in the Reducer
Bracket. Precisely locate the sprinkler in all three axes in accordance
with the sprinkler manufacturers data
sheet. Tighten the Butterfly Bolts on
the Bar Fixing Clamps and the Reducer
Bracket. The tightening torque for the
Bar Fixing Clamp fastener is 4,5 to
5,7 Nm, and the tightening torque for
the Reducer Bracket fastener, is a
minimum of 2,3 Nm.
Step 10. After tightening all the Butterfly Bolts, verify that the sprinkler is
properly located in accordance with
the manufactures instructions. If not,
loosen the Butterfly Bolts and readjust
as required.

TFP720
Page 8 of 8

MINIMUM
RADIUS
INDICATOR
MRI55
YN25
FLEXIBLE
HOSE

Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate
the full product name and Part Number
(P/N).
Flexible Hose Assembly
The FASTFLE X Flexible Hose
Assembly includes Flexible Hose,
ISO 7-R 1 x Hose Thread Inlet Nipple,
1/2" NPT x Hose Thread Straight Sprinkler Reducer, Reducer Bracket, Bar
Fixing Clamps, and Support Bar.
Note: Refer to Table A for Model, Type,
Length, Bar Fixing Clamp options, and
Approval details.

FIGURE 4
MINIMUM RADIUS INDICATOR
MRI55

Care and
Maintenance
The TYCO FASTFLEX Flexible Sprinkler
Hose must be maintained and serviced
in accordance with this section.
Before closing a fire protection system
control valve for inspection or maintenance work on the fire protection
system that it controls, permission to
shut down the effected fire protection
system must first be obtained from
the proper authorities and all personnel who may be affected by this action
must be notified.
After placing a fire protection system
in service, notify the proper authorities
and advise those responsible for monitoring proprietary and/or central station
alarms.
The owner is responsible for the inspection, testing, and maintenance of their
fire protection system and devices in
compliance with this document, as well
as with the applicable standards of the
authorities having jurisdiction. Contact
the installing contractor or product
manufacturer with any questions.
Automatic sprinkler systems are recommended to be inspected, tested,
and maintained by a qualified Inspection Service in accordance with local
requirements and/or national codes.

Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.

Inlet Nipple
Specify: (25 mm or 28 mm) hose thread
FASTFLEX Inlet Nipple with (ISO 7-R 1
or ISO 7-R 1 1/4) inlet thread connection, P/N (specify):
25 mm Hose Thread
ISO 7-R 1. . . . . . . . . . . . . . . . . . . HOSENIP25
ISO 7-R 1 1/4. . . . . . . . . . . . . . . HOSENIP25R
28 mm Hose Thread
ISO 7-R 1 HOSENIP28
ISO 7-R 1 1/4 HOSENIP28R

Sprinkler Reducer
Specify: (Straight, 45 Degree, or 90
Degree) for (25 mm or 28 mm hose
threads) FASTFLEX Sprinkler Reducer
with (ISO 7-Rc 3/8, 1/2 inch NPT, or 3/4
inch NPT) outlet thread connection,
P/N (specify):

Specify: Model (specify) FASTFLEX


Flexible Sprinkler Hose Assembly, Type
(specify), (specify) length, (specify) Bar
Fixing Clamp, P/N (specify):

Straight
25 mm Hose Thread
ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . . . . . PBR120
1/2 inch NPT . . . . . . . . . . . . . . . . . . . . RBR120
3/4 inch NPT . . . . . . . . . . . . . . . . . . . . SBR120

Model YN25, Un-braided, 50 mm Clamps


700 . . . . . . . . . . . . . . . . . . . . . . . . . . . . YN250700
1000 . . . . . . . . . . . . . . . . . . . . . . . . . . . YN251000
1200 . . . . . . . . . . . . . . . . . . . . . . . . . . . YN251200
1500 . . . . . . . . . . . . . . . . . . . . . . . . . . . YN251500
1800 . . . . . . . . . . . . . . . . . . . . . . . . . . . YN251800
2000 . . . . . . . . . . . . . . . . . . . . . . . . . . . YN252000
2500 . . . . . . . . . . . . . . . . . . . . . . . . . . . YN252500
2700 . . . . . . . . . . . . . . . . . . . . . . . . . . . YN252700
3100. . . . . . . . . . . . . . . . . . . . . . . . . . . . YN253100
3700 . . . . . . . . . . . . . . . . . . . . . . . . . . . YN253700

28 mm Hose Thread
ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . . . PBR28120
1/2 inch NPT . . . . . . . . . . . . . . . . . . RBR28120
3/4 inch NPT . . . . . . . . . . . . . . . . . . SBR28120

Model YN25, Un-braided, 90 mm Clamps


700 . . . . . . . . . . . . . . . . . . . . . . . . . . . YN250700C
1000 . . . . . . . . . . . . . . . . . . . . . . . . . . YN251000C
1200 . . . . . . . . . . . . . . . . . . . . . . . . . . YN251200C
1500 . . . . . . . . . . . . . . . . . . . . . . . . . . YN251500C
1800 . . . . . . . . . . . . . . . . . . . . . . . . . . YN251800C
2000 . . . . . . . . . . . . . . . . . . . . . . . . . . YN252000C
2500 . . . . . . . . . . . . . . . . . . . . . . . . . . YN252500C
2700 . . . . . . . . . . . . . . . . . . . . . . . . . . YN252700C
3100. . . . . . . . . . . . . . . . . . . . . . . . . . . YN253100C
3700 . . . . . . . . . . . . . . . . . . . . . . . . . . YN253700C
Model YB25, Braided, 50 mm Clamps
700 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . YB250700
1000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . YB251000
1200 . . . . . . . . . . . . . . . . . . . . . . . . . . . . YB251200
1500 . . . . . . . . . . . . . . . . . . . . . . . . . . . . YB251500
1800 . . . . . . . . . . . . . . . . . . . . . . . . . . . . YB251800
2000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . YB252000
2500 . . . . . . . . . . . . . . . . . . . . . . . . . . . . YB252500
Model YB25, Braided, FM Approved
50 mm Clamps
700 . . . . . . . . . . . . . . . . . . . . . . . . . . . YB250700-F
1000 . . . . . . . . . . . . . . . . . . . . . . . . . . YB251000-F
1200 . . . . . . . . . . . . . . . . . . . . . . . . . . YB251200-F
1500 . . . . . . . . . . . . . . . . . . . . . . . . . . YB251500-F
1800 . . . . . . . . . . . . . . . . . . . . . . . . . . YB251800-F
Model YB28, Braided, 50 mm Clamps
700 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . YB280700
1000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . YB281000
1200 . . . . . . . . . . . . . . . . . . . . . . . . . . . . YB281200
1500 . . . . . . . . . . . . . . . . . . . . . . . . . . . . YB281500
1800 . . . . . . . . . . . . . . . . . . . . . . . . . . . . YB281800
2000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . YB282000
2500 . . . . . . . . . . . . . . . . . . . . . . . . . . . . YB282500

45 Degree
25 mm Hose Thread
ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . . . . PBAR45
1/2 inch NPT . . . . . . . . . . . . . . . . . . . RBAR45
3/4 inch NPT . . . . . . . . . . . . . . . . . . . SBAR45
28 mm Hose Thread
ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . . PB28AR45
1/2 inch NPT . . . . . . . . . . . . . . . . . RB28AR45
3/4 inch NPT . . . . . . . . . . . . . . . . . SB28AR45
90 Degree
25 mm Hose Thread
ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . . . . PBAR90
1/2 inch NPT . . . . . . . . . . . . . . . . . . . RBAR90
3/4 inch NPT . . . . . . . . . . . . . . . . . . . SBAR90
28 mm Hose Thread
ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . . PB28AR90
1/2 inch NPT . . . . . . . . . . . . . . . . . RB28AR90
3/4 inch NPT . . . . . . . . . . . . . . . . . SB28AR90

Bar Fixing Clamps


Specify: FASTFLEX (50 mm or 90 mm)
Bar Fixing Clamps, P/N (specify):
50 mm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . RBF58T
90 mm. . . . . . . . . . . . . . . . . . . . . . . . . . . . . RBF90T

Minimum Radius Indicator


Specify: MRI55 Plastic Clip Minimum
Radius Indicator of 55 mm to be
attached to Sprinkler Hose YN25,
P/N MRI55
Note: For installations per LPCB, all
bends greater than 45 shall be fitted
with a MRI55 Plastic Clip Minimum
Radius Indicator. (Ref. Figure 4.)

Model YB28, Braided, FM Approved,


50 mm Clamps
700 . . . . . . . . . . . . . . . . . . . . . . . . . . . YB280700-F
1000 . . . . . . . . . . . . . . . . . . . . . . . . . . YB281000-F
1200 . . . . . . . . . . . . . . . . . . . . . . . . . . YB281200-F
1500 . . . . . . . . . . . . . . . . . . . . . . . . . . YB281500-F
1800 . . . . . . . . . . . . . . . . . . . . . . . . . . YB281800-F

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2015 Tyco Fire Products, LP. All rights reserved.

Worldwide
www.tyco-fire.com
Contacts

FASTFLEX
Model FB Flexible Braided Hose
General
Description

Technical
Data

The TYCO FASTFLEX Model FB Flexible Braided Hose is a unique sprinkler


drop assembly comprised of a stainless steel flexible hose a swivel inlet
nipple, a sprinkler reducer, and lightweight ceiling bracket components.
(Ref. Figure 1.)

Approvals
VdS Approved

The FASTFLEX Model FB Flexible


Braided Hose can be installed in false
ceilings without cutting and threading
pipes associated with installing a drop,
arm-over, and elbow. It provides easier
maneuverability around ducts and trays
in congested spaces and for unusual
ceiling types and curved plasterboard
ceilings. The FASTFLEX Model FB Flexible Braided Hose makes it possible to
test and charge the system with water
before the ceiling grid is installed.
Once the ceiling grid is in position, the
hoses can be reshaped to suit the final
sprinkler location without draining the
system.
The FASTFLEX Model FB Flexible
Braided Hose hoses are for use on wet
pipe sprinkler systems only.
NOTICE
The TYCO FASTFLEX Model FB Flexible Braided Hose described herein
must be installed and maintained in
compliance with this document and
with the applicable standards recognized by the Approval agency, in
addition to the standards of any other
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
The owner is responsible for maintaining their fire protection system
and devices in proper operating condition. Contact the installing contractor or product manufacturer with any
questions.

Page 1 of 6

(Approvals apply to the service


conditions indicated in the Design
Criteria sections.)
CSTB accepted for all models and
assembly lengths.
Inlet Connections (Ref. Figure 1)
ISO 7-R 1
Outlet Connections (Ref. Figure 3)
1/2 inch NPT
3/4 inch NPT
Nominal Assembly Lengths
Ref. Figure 3
Construction (Ref. Figure 1)
The Inlet Nipple is mild steel, and the
Flexible Hose is SS AISI 304. The
Sprinkler Reducer is mild steel. The
Reducer Bracket, Bar Fixing Clamps,
and Support Bar are pressed steel.

Design Criteria
The TYCO FASTFLEX Model FB Flexible Braided Hose is VdS Listed and
used with pendent sprinklers. The following paragraph provides the design
criteria unique to VdS Approval listing.
VdS Listing Design Criteria
Wet-pipe systems only
Minimum bend radius of 55 mm
Maximum service pressure of 16
bar
Pendent sprinklers with nominal
K57, K80, or K115
Maximum ambient temperature of
107C

Approved Ceiling Systems


FASTFLEX Model FB Flexible Braided
Hose assemblies are approved for
installation above suspended ceiling
systems having T-profile grid supports
manufactured only by:
AMF
Odenwald
Richter
Armstrong
Rigips
Knauf
Chicago Metallic
Durlum
Geipel
Gema Armstrong
Suckow & Fischer
USG Donn
Daldrop & Dr. Huber
Rockfon Pagos
NOTE: FASTFLEX Model FB Flexible Braided Hose assemblies are
approved for installation with RBF38T
Gypsum End Brackets in gypsum suspended ceiling systems having U-profile channel support construction.
VdS Friction Loss
For compensation of pressure loss,
the nominal assembly length is to be
multiplied by 10. The resulting length
will provide pressure drop in equivalent
length DN25 (33,7 x 3,25 mm) metal
tube per EN 10255.
Add 2,3 m when using a 90 sprinkler
reducer.

MARCH 2015

TFP730

TFP730
Page 2 of 6
INTEGRATED
KNURLED AND
MALE THREADED
SWIVEL INLET
NIPPLE
BRAIDED
JACKET
FLEXIBLE
HOSE

BRANCHLINE
FITTING
(NOT INCLUDED)
SYSTEM
BRANCHLINE

BRANCHLINE
FITTING
ISO 7-R 1
THREADED
OUTLET

INTEGRATED
HEX SPRINKLER
REDUCER
600 mm

REDUCER
BRACKET WITH
SOCKET HEAD
SCREW
END BRACKET
WITH WING
SCREW, HEX
SCREW AND
LOCK WASHER

CEILING
GRID
T-BAR
DROP-IN
CEILING
PANEL

SUPPORT
BAR

SPRINKLER INSTALLED
IN ACCORDANCE WITH
MANUFACTURER'S
INSTRUCTIONS

FIGURE 1
FASTFLEX MODEL FB FLEXIBLE BRAIDED HOSE
ASSEMBLY AND TYPICAL INSTALLATION

Installation
T-Bar Bracket Application
The TYCO FASTFLEX Model FB
Flexible Braided Hose, as shown in
Figure 1, must be installed in accordance with this section.
NOTICE
TYCO Model FB Flexible Braided Hoses
are intended only to connect sprinklers
directly to system piping (Ref. Figure
1). Model FB Flexible Braided Hoses
cannot be joined together to form
longer hoses. Joining flexible hoses
together creates an assembly with
unknown performance that has not
been accounted for in system calculations or safe product performance.

Mount the End Brackets to the Support


Bar then slide the End Brackets over
the ceiling grid T-bars. The sprinkler should be located as close to the
center of the distance between the
ceiling grid T-bars as possible.
Step 3. Hand-tighten the Wings Screws
and the Hex Screws on the End Brackets securing the Support Bar.
Step 4. Attach the Swivel Inlet Nipple
to the Branchline Fitting outlet. (Ref.
Figure 1.) Apply the wrench directly to
the Swivel Inlet Nipple and tighten to
the maximum torque of 35 Nm.

Step 1. Review the Design Criteria


section that applies to the approval
agency recognized by the authority
having jurisdiction, as well as Figure 4
that provides Installation Guidance.

Step 5. Attach the sprinkler to the


Sprinkler Reducer. Place a wrench on
the Sprinkler Reducer to counteract
the tightening torque of the sprinkler
and torque the sprinkler to the recommended torque setting. Refer to the
sprinkler manufacturers sprinkler data
sheet for appropriate sprinkler torque
setting, sprinkler wrench, and other
guidance.

Step 2. Determine approximately


where the sprinkler will be located.

Step 6. Bend the Flexible Braided Hose


and place the Sprinkler Reducer to

where the sprinkler will be located. The


hose arc should not be twisted, and the
arc should be as large and smooth as
possible. (Ref. Figures 3 and 4)
NOTICE
For minimum bend criteria, refer to the
Design Criteria section that applies to
the approval agency recognized by the
authority having jurisdiction.
A bend radius smaller than provided by the minimum bend criteria
may adversely effect the friction loss
specifications stated by the approval
laboratory.
Step 7. Slide the Reducer Bracket over
the Sprinkler Reducer end of the Flexible Braided Hose and clip over the
Support Bar. Hand-tighten the fastener
on the Reducer Bracket securing the
Reducer Bracket to the Support Bar.
Ensure that the Reducer Bracket fastener is secured to the flat surface of
the Sprinkler Reducer.
Step 8. After tightening the Reducer
Bracket fastener, verify that the sprin-

TFP730
Page 3 of 6

RBF38T
GYPSUM END
BRACKET WITH
WING SCREW

SUPPORT BAR

GYPSUM CEILING
U-PROFILE SUPPORT
CHANNEL

FIGURE 2
FASTFLEX MODEL FB FLEXIBLE BRAIDED HOSE
GYPSUM CEILING INSTALLATION DETAIL
kler is properly located in accordance
with the manufacturers instructions.
If not in the proper location, adjust its
position as necessary.
Step 9. Once the sprinkler is in the
proper location, torque all hardware as
follows:
NOTE: The End Brackets Wing Screws
must be tightened before tightening the
Reducer Bracket to the Support Bar.
End Bracket
Hex Screws . . . . . . . . . . 4,5 Nm (min)
End Bracket
Wing Screws . . . . . . . . . 4,5 to 5,7 Nm
Reducer Bracket
Fastener . . . . . . . . . . . . . 2,3 Nm (min)

Installation
Gypsum End Bracket Application
THE TYCO FASTFLEX Model FB Flexible Braided Hose gypsum ceiling
installation, using the Gypsum End
Bracket RBF38T as shown in Figure 2,
must be installed in accordance with
this section.
NOTICE
TYCO Model FB Flexible Braided Hoses
are intended only to connect sprinklers
directly to system piping (Ref. Figure
1). Model FB Flexible Braided Hoses
cannot be joined together to form
longer hoses. Joining flexible hoses
together creates an assembly with
unknown performance that has not
been accounted for in system calculations or safe product performance.
Step 1. Review the Design Criteria
section that applies to the approval
agency recognized by the authority
having jurisdiction, as well as Figure 4
that provides Installation Guidance.

Step 2. Determine approximately where


the sprinkler will be located. Set the
Support Bar on the U-profile Support
Channel, then mount the Gypsum End
Bracket to the Support Bar. Hook the
Gypsum End Bracket under the edge
of the U-profile Support Channel. The
sprinkler should be located as close
to the center of the distance between
the U-profile Support Channels as
possible.
Step 3. Hand-tighten the Wing Screw
on the Gypsum End Bracket securing
it to the Support Bar.
Step 4. Attach the Swivel Inlet Nipple
to the Branchline Fitting outlet. (Ref.
Figure 1.) Apply the wrench directly to
the Swivel Inlet Nipple and tighten to
the maximum torque of 35 Nm.
Step 5. Attach the sprinkler to the
Sprinkler Reducer. Place a wrench on
the Sprinkler Reducer to counteract
the tightening torque of the sprinkler
and torque the sprinkler to the recommended torque setting. Refer to the
sprinkler manufacturers sprinkler data
sheet for appropriate sprinkler torque
setting, sprinkler wrench, and other
guidance.
Step 6. Bend the Flexible Braided Hose
and place the Sprinkler Reducer to
where the sprinkler will be located. The
hose arc should not be twisted, and the
arc should be as large and smooth as
possible. (Ref. Figures 3 and 4)
NOTICE
For minimum bend criteria, refer to the
Design Criteria section that applies to
the approval agency recognized by the
authority having jurisdiction.

A bend radius smaller than provided by the minimum bend criteria


may adversely effect the friction loss
specifications stated by the approval
laboratory.
Step 7. Slide the Reducer Bracket over
the Sprinkler Reducer end of the Flexible Braided Hose and clip over the
Support Bar. Hand-tighten the fastener
on the Reducer Bracket securing the
Reducer Bracket to the Support Bar.
Ensure that the Reducer Bracket fastener is secured to the flat surface of
the Sprinkler Reducer.
Step 8. After tightening the Reducer
Bracket fastener, verify that the sprinkler is properly located in accordance
with the manufacturers instructions.
If not in the proper location, adjust its
position as necessary.
Step 9. Once the sprinkler is in the
proper location, torque all hardware as
follows:
NOTE: The Gypsum End Bracket Wing
Screws must be tightened before
tightening the Reducer Bracket to the
Support Bar.
Gypsum End Bracket
Wing Screws . . . . . . . . . 4,5 to 5,7 Nm
Reducer Bracket
Fastener . . . . . . . . . . . . . 2,3 Nm (min)

TFP730
Page 4 of 6

Model

Type

L
Nominal
Length

Maximum
Number of
Bends

FB25-700

Braided

700 mm

FB25-1000

Braided

1000 mm

FB25-1200

Braided

1200 mm

FB25-1500

Braided

1500 mm

FB25-2000

Braided

2000 mm

L
ISO 7-R 1
SWIVEL
INLET
NIPPLE

INNER
FLEXIBLE
HOSE

OUTER
BRAIDED
JACKET

STRAIGHT
SPRINKLER
REDUCER

1/2" NPT
or
3/4" NPT

L
ISO 7-R 1
SWIVEL
INLET
NIPPLE

INNER
FLEXIBLE
HOSE

OUTER
BRAIDED
JACKET

90
SPRINKLER
REDUCER

1/2" NPT
or
3/4" NPT

FIGURE 3
FASTFLEX MODEL FB FLEXIBLE BRAIDED HOSE ASSEMBLY
NOMINAL DIMENSIONS

Care and
Maintenance
The TYCO FASTFLEX Model FB Flexible Braided Hose must be maintained
and serviced in accordance with this
section.
Before closing a fire protection system
control valve for inspection or maintenance work on the fire protection
system that it controls, permission to
shut down the effected fire protection
system must first be obtained from
the proper authorities and all personnel who may be affected by this action
must be notified.
Inspection, testing, and maintenance
must be performed as indicated below
and in accordance with the local
requirements and/or national codes.
Any impairment must be immediately
corrected.

The owner is responsible for the inspection, testing, and maintenance of their
fire protection system and devices in
compliance with this document, as well
as with the applicable standards of the
authorities having jurisdiction. Contact
the installing contractor or product
manufacturer with any questions.
After placing a fire protection system
in service, notify the proper authorities
and advise those responsible for monitoring proprietary and/or central station
alarms.
Automatic sprinkler systems are recommended to be inspected, tested,
and maintained by a qualified Inspection Service in accordance with local
requirements and/or national codes.

180 mm

TFP730
Page 5 of 6

PERMITTED

PERMITTED

NOT PERMITTED

NOT PERMITTED

Route the Model FB Flexible Braided Hose to permit the water to drain back into the branchline or through the
sprinkler reducer.
FIGURE 4
FASTFLEX MODEL FB FLEXIBLE BRAIDED HOSE
INSTALLATION GUIDANCE

Limited
Warranty

Ordering
Procedure

For warranty terms and conditions, visit


www.tyco-fire.com.

Contact your local distributor for availability. When placing an order, indicate
the full product name and Part Number
(P/N).
Flexible Hose Assembly*
*T he FASTFLEX Model FB Flexible
Braided Hose Assemblies includes the
following items:
- Flexible Braided Hose
- Inlet Nipple, ISO 7-R 1
- Sprinkler Reducer, 1/2" or 3/4" NPT,
Straight or Angled
- Reducer Bracket
- End Brackets
- Support Bar
Specify: FASTFLEX Model FB Flexible Braided Hose Model (specify,
Ref. Figure 3), (specified) length, and
(specify size, 50 or 90 mm) Bar Fixing
Clamps, P/N (specify):
With 1/2 inch Straight Reducer:
700 . . . . . . . . . . . . . . . . . . . . . . . . . .
1000 . . . . . . . . . . . . . . . . . . . . . . . . .
1200 . . . . . . . . . . . . . . . . . . . . . . . . .
1500 . . . . . . . . . . . . . . . . . . . . . . . . .
2000 . . . . . . . . . . . . . . . . . . . . . . . . .

FBS1250700
FBS1251000
FBS1251200
FBS1251500
FBS1252000

With 1/2 inch Angled Reducer:


700 . . . . . . . . . . . . . . . . . . . . . . . . . .
1000 . . . . . . . . . . . . . . . . . . . . . . . . .
1200 . . . . . . . . . . . . . . . . . . . . . . . . .
1500 . . . . . . . . . . . . . . . . . . . . . . . . .
2000 . . . . . . . . . . . . . . . . . . . . . . . . .

FBA1250700
FBA1251000
FBA1251200
FBA1251500
FBA1252000

With 3/4 inch Straight Reducer:


700 . . . . . . . . . . . . . . . . . . . . . . . . . . FBS3250700
1000 . . . . . . . . . . . . . . . . . . . . . . . . . FBS3251000
1200 . . . . . . . . . . . . . . . . . . . . . . . . . FBS3251200
1500 . . . . . . . . . . . . . . . . . . . . . . . . . FBS3251500
2000 . . . . . . . . . . . . . . . . . . . . . . . . . FBS3252000
With 3/4 inch Angled Reducer:
700 . . . . . . . . . . . . . . . . . . . . . . . . . . FBA3250700
1000 . . . . . . . . . . . . . . . . . . . . . . . . . FBA3251000
1200 . . . . . . . . . . . . . . . . . . . . . . . . . FBA3251200
1500 . . . . . . . . . . . . . . . . . . . . . . . . . FBA3251500
2000 . . . . . . . . . . . . . . . . . . . . . . . . . FBA3252000

End Bracket
Specify: FASTFLEX End Bracket,
P/N FENDBRA
Gypsum End Bracket
Specify: Gypsum End
P/N RBF38T

Bracket,

Support Bar
Specify: FASTFLEX Support Bar,
(specify) length, P/N (specify):
700 . . . . . . . . . . . . . . . . . . . . . . . . FSUPBAR0700
1000 . . . . . . . . . . . . . . . . . . . . . . . FSUPBAR1000
1300 . . . . . . . . . . . . . . . . . . . . . . . FSUPBAR1300

Reducer Bracket
Specify: FASTFLEX Reducer Bracket,
(specify) size, P/N (specify):
1/2". . . . . . . . . . . . . . . . . . . . . . . . . FREDBRA050
3/4" . . . . . . . . . . . . . . . . . . . . . . . . . FREDBRA075

TFP730
Page 6 of 6

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


Copyright 2015 Tyco Fire Products, LP. All rights reserved.

Worldwide
www.tyco-fire.com
Contacts

Type MV-R Reverse Action and Type MV-T Tank Top


Open Nozzles
Medium Velocity
General
Description
The Tyco Type MV-R Reverse Action
and Type MV-T Tank Top Nozzles are
open (non-automatic) spray nozzles
designed for use in water spray fixed
systems for fire protection of vessels or
structures containing highly flammable
liquids, gases and solids having flashpoints of 66C (150F) and below. They
are external deflector-type nozzles that
discharge against the direction of the
orifice in a uniformly filled spray pattern
of medium velocity water droplets over
a pre-determined area.
MV-R and MV-T nozzles are effective
in covering exposed vertical, horizontal,
curved, and irregular shaped surfaces
in a cooling spray to prevent excessive
absorption of heat from an external
fire and possible structural damage or
spread of fire to the protected equipment. They also promote vapor dilution
and dispersion.
The Type MV-R Reverse Action Nozzle,
designed specifically to protect spherical vessels and bulk storage tanks,
can be installed at any angle and discharges a 118 reverse angle conical
spray pattern (refer to Graph A).
The Type MV-T Tank Top Nozzle,
designed specifically to protect tank
tops, is installed in only an upright orientation and discharges a wide-angle
hemispherical spray pattern (refer to
Graph B).
Type MV-R and MV-T nozzles having
orifice diameters smaller than 9,5 mm
(0.37 in.) are factory assembled with
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the INSTALLER
WARNING that provides cautions
with respect to handling and installation of sprinkler systems and components. Improper handling and
installation can permanently damage
a sprinkler system or its components and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

Page 1 of 6

an orifice insert and strainer. Strainers


have 3,2 mm (0.13 in.) diameter holes.
Nozzles equipped with strainers range
in size from MV10 to MV30 (refer to
Tables A and B).
It is recommended that the end user be
consulted with respect to the suitability of the materials of construction and
finish for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and
gas/chemical velocity, should be considered, at a minimum, along with the
corrosive nature to which the Type MV
Nozzles may be exposed.
NOTICE
The Tyco Type MV-R and MV-T Nozzles
described herein must be installed and
maintained in compliance with this document and with the applicable standards of the National Fire Protection
Association, in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the
performance of these devices.
The design of individual water spray
fixed systems can vary considerably,
depending on the characteristics and
nature of the hazard, the basic purpose
of the spraying system, the configuration of the hazard, and wind/draft conditions. Because of these variations,
as well as the wide range of available
nozzle spray characteristics, the design
of water spray fixed systems for fire
protection must only be performed by
experienced designers who thoroughly
understand the limitations as well as
capabilities of such systems.

Type MV-R

Type MV-T

The owner is responsible for maintaining their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.

FEBRUARY 2015

TFP809

TFP809
Page 2 of 6
47,6 mm
(1-7/8")
MV ORIFICE SIZE
AND REVERSE
ACTION CODE R
INDICATED ON
FRAME ARM

DEFLECTOR
55,6 mm
(2-3/16")

K-FACTOR AND
APPROVAL AGENCY
INDICATED ON
FRAME ARM

FRAME

65,1 mm
(2-9/16")

WRENCHING
AREA
1/2" NPT

SPLITTER

17,5 mm*
(11/16")

ORIFICE *
INSERT
STRAINER *
WITH NOMINAL
3,2 mm (1/8") DIA.
HOLES

* NOZZLES HAVING

ORIFICES SMALLER
THAN 9,5 mm (0.37")
DIAMETER INCLUDE
ORIFICE INSERT AND
STRAINER

11,1 mm (7/16")
NOMINAL MAKE-IN

FIGURE 1
TYPE MV-R REVERSE ACTION NOZZLE
ASSEMBLY AND NOMINAL DIMENSIONS
47,6 mm
(1-7/8")
MV ORIFICE
SIZE AND
TANK TOP CODE T
INDICATED ON
FRAME ARM

DEFLECTOR
55,6 mm
(2-3/16")

K-FACTOR AND
APPROVAL AGENCY
INDICATED ON
FRAME ARM

FRAME

65,1 mm
(2-9/16")

ORIFICE *
INSERT

WRENCHING
AREA
1/2" NPT

SPLITTER

17,5 mm*
(11/16")

STRAINER *
WITH NOMINAL
3,2 mm (1/8") DIA.
HOLES

* NOZZLES HAVING

ORIFICES SMALLER
THAN 9,5 mm (0.37")
DIAMETER INCLUDE
ORIFICE INSERT AND
STRAINER

11,1 mm (7/16")
NOMINAL MAKE-IN

FIGURE 2
TYPE MV-T TANK TOP
ASSEMBLY AND NOMINAL DIMENSIONS

Technical
Data
Approvals
MV-R, UL Listed and FM Approved
(refer to Table A)
MV-T, UL Listed and FM Approved
(refer to Table B)

Maximum Working Pressure


12,1 bar (175 psi)
Discharge Coefficient
MV-R, refer to Table A
MV-T, refer to Table B
Thread Connection
1/2 in. NPT

Physical Characteristics
Type MV-R and MV-T Nozzles are comprised of components constructed
from: Stainless Steel, Brass & Leaded
Gunmetal LG2, Titanium, Aluminium
Bronze, SMO254, or Zeron 100.

TFP809
Page 3 of 6

Orifice
Size

Minimum
Diameter
mm
(Inches)

MV10R

5,15 (0.20)

K-factor

Listings/Approvals per Material

LPM/bar1/2

GPM/psi1/2

17,3

1.2

MV12R

5,40 (0.21)

18,7

1.3

MV15R

6,35 (0.25)

25,9

1.8

MV18R

6,80 (0.27)

28,8

2.0

MV19R

7,15 (0.28)

31,7

2.2

MV21R

7,70 (0.30)

36,0

2.5

MV25R

8,35 (0.33)

41,8

2.9

MV26R

8,80 (0.34)

44,6

3.1

MV30R

9,00 (0.35)

49,0

3.4

MV34R

9,60 (0.38)

59,0

4.1

MV47R

11,20 (0.44)

79,2

5.5

MV57R

12,60 (0.50)

100,8

7.0

Stainless
Steel

Brass

Titanium

Aluminium
Bronze

SMO254

Zeron 100

1, 2

1, 2

1, 2

1, 2

1, 2

1, 2

NOTES:
1. UL Listed
2. FM Approved

TABLE A
TYPE MV-R REVERSE ACTION NOZZLE
ORIFICE SIZES, DISCHARGE COEFFICIENTS, MATERIALS OF CONSTRUCTION, AND
LABORATORY LISTINGS AND APPROVALS

Orifice
Size

Minimum
Diameter
mm
(Inches)

MV10T

5,15 (0.20)

K-factor

Listings/Approvals per Material

LPM/bar1/2

GPM/psi1/2

17,3

1.2
1.3

MV12T

5,40 (0.21)

18,7

MV15T

6,35 (0.25)

25,9

1.8

MV18T

6,80 (0.27)

28,8

2.0

MV19T

7,15 (0.28)

31,7

2.2

MV21T

7,70 (0.30)

36,0

2.5

MV25T

8,35 (0.33)

41,8

2.9

MV26T

8,80 (0.34)

44,6

3.1

MV30T

9,00 (0.35)

49,0

3.4

MV34T

9,60 (0.38)

59,0

4.1

MV47T

11,20 (0.44)

79,2

5.5

MV57T

12,60 (0.50)

100,8

7.0

Stainless
Steel

Brass

Titanium

Aluminium
Bronze

SMO254

Zeron 100

NOTES:
1. UL Listed

TABLE B
TYPE MV-T TANK TOP NOZZLE
ORIFICE SIZES, DISCHARGE COEFFICIENTS, MATERIALS OF CONSTRUCTION, AND
LABORATORY LISTINGS AND APPROVALS

RADIAL DISTANCE FROM


NOZZLE CENTERLINE, METERS
1,25
1,00
0,75
0,50
0,25
0

RADIAL DISTANCE FROM


NOZZLE CENTERLINE, FEET
3
1
2

0,25

0,50
2
0,75

AXIAL DISTANCE FROM


NOZZLE DEFLECTOR, FEET

AXIAL DISTANCE FROM


NOZZLE DEFLECTOR, METERS

TFP809
Page 4 of 6

1,75
0

RADIAL DISTANCE FROM


NOZZLE CENTERLINE, METERS
1,50
1,25
1,00
0,75
0,50
0,25

RADIAL DISTANCE FROM


NOZZLE CENTERLINE, FEET
3
4
2

0,25

0,50
2
0,75

AXIAL DISTANCE FROM


NOZZLE DEFLECTOR, FEET

AXIAL DISTANCE FROM


NOZZLE DEFLECTOR, METERS

GRAPH A
TYPE MV-R REVERSE ACTION NOZZLE
SPRAY PROFILE

GRAPH B
TYPE MV-T TANK TOP NOZZLE
SPRAY PROFILE

Design
Criteria
Nozzle Placement
Where direct impingement of water
spray onto all of the protected surface
is required by the authority having jurisdiction, Type MV-R and MV-R Nozzles
are to be spaced and directed so that
their spray patterns will completely
cover the protected surface with the
minimum required average density.
Both MV-R and MV-T nozzles must be
installed at a maximum effective distance of 0,75 m (2.5 ft.) from the protected surface.
Type MV-R nozzles can be oriented at
any angle on pipe sprigs (refer to Figure
3).
Type MV-T nozzles must be oriented in
the upright position on pipe sprigs (refer
to Figure 4).
Spray Patterns
Spray patterns for MV-R and MV-T
nozzles are shown in Graphs A and B
and apply to discharge pressures of 1,4
(20 psi). Though the Maximum Working
Pressure is 12,1 bar (175 psi), discharge
pressures in excess of 4,1 bar (60 psi)

will result in a decrease in coverage


area since the spray patterns tend to
draw inwards at higher pressures.
Main Pipeline Strainers
Main pipeline strainers per NFPA 15 are
required for systems utilizing nozzles
with a flow path less than 9,5 mm (0.37
in.) diameter (i.e., MV10 thru MV30, refer
to Table A), and for any system where
the water is likely to contain obstructive material.

Installation
The Tyco Type MV-R and MV-T Nozzles
must be installed in accordance with
this section.
General Instructions
A leak-tight 1/2 in. NPT sprinkler joint
should be obtained by applying a minimum-to-maximum torque of 9,5 to 19,0
Nm (7 to 14 ft.-lbs.). Higher levels of
torque can distort the nozzle Inlet with
consequent impairment of the nozzle.
Step 1. With pipe-thread sealant
applied to the pipe threads, handtighten the nozzle into the nozzle fitting.
Step 2. With reference to Figures 1 and
2, apply an appropriate size adjustable
Crescent wrench to the wrenching area
and tighten the nozzle into the nozzle
fitting.

TFP809
Page 5 of 6
Frequent visual inspections are recommended to be initially performed
for nozzles installed in potentially corrosive atmospheres to verify the integrity of the materials of construction and
finish as they may be affected by the
corrosive conditions present for a given
installation. Thereafter, annual inspections per NFPA 25 are required.

WATER
DISCHARGE
PIPE
SPRIG

Water spray fixed systems to fire protection service require regularly scheduled care and maintenance by trained
personnel.

TYPE MV-R
REVERSE ACTION
NOZZLE
(ORIENT AT
ANY ANGLE)
SUPPLY
PIPE
PROTECTED
SURFACE

FIGURE 3
TYPE MV-R REVERSE ACTION NOZZLE
TYPICAL INSTALLATION

TYPE MV-T
TANK TOP NOZZLE
(ORIENT UPRIGHT
ONLY)

WATER
DISCHARGE

In addition to inspecting nozzles for


proper spray performance during water
flow trip tests of the system, it is recommended that nozzles be periodically
inspected for broken or missing parts,
loading/obstructions, or other evidence
of impaired protection. The inspections should be scheduled weekly or
as frequently as may be necessary,
and corrective action must be taken to
ensure that the nozzles will perform as
intended in the event of a fire.
The owner is responsible for the inspection, testing, and maintenance of their
fire protection system and devices in
compliance with this document, as
well as with the applicable standards
of the National Fire Protection Association (e.g., NFPA 25), in addition to
the standards of any authorities having
jurisdiction. The installing contractor or
sprinkler manufacturer should be contacted relative to any questions.
Water spray fixed systems are recommended to be inspected, tested,
and maintained by a qualified Inspection Service in accordance with local
requirements and/or national codes.

PIPE
SPRIG

SUPPLY
PIPE

PROTECTED
SURFACE

FIGURE 4
TYPE MV-T TANK TOP NOZZLE
TYPICAL INSTALLATION

Care and
Maintenance
The Tyco Type MV-R and MV-T Nozzles
must be maintained and serviced in
accordance with this section.
Before closing a fire protection system
main control valve for maintenance work
on the fire protection system that it controls, obtain permission to shut down
the affected fire protection system from
the proper authorities and notify all per-

sonnel who may be affected by this


action.
Type MV-R and MV-T Nozzles must
never be painted, plated, coated or
altered in any way after leaving the
factory; otherwise, the spray performance may be impaired.
Exercise care to avoid damage to the
nozzles, before, during, and after installation. Replace nozzles damaged by
dropping, striking, wrench twist/slippage, or the like.

TFP809
Page 6 of 6
Material
Orifice
Size

Stainless
Steel

Brass &
Leaded
Gunmetal
LG2

Titanium

Aluminium
Bronze

SMO254

Zeron 100
28480Z

MV10R

28480

28383

28480T

28383AB

28480SMO

MV12R

28481

28384

28481T

28384AB

28481SMO

28481Z

MV15R

28482

28385

28482T

28385AB

28482SMO

28482Z

MV18R

28483

28386

28483T

28386AB

28483SMO

28483Z

MV19R

28484

28387

28484T

28387AB

28484SMO

28484Z

MV21R

28485

28388

28485T

28388AB

28485SMO

28485Z

MV25R

28486

28389

28486T

28389AB

28486SMO

28486Z

MV26R

28487

28390

28487T

28390AB

28487SMO

28487Z

MV30R

28488

28391

28488T

28391AB

28488SMO

28488Z

MV34R

28489

28392

28489T

28392AB

28489SMO

28489Z

MV47R

28490

28393

28490T

28393AB

28490SMO

28490Z

MV57R

28491

28394

28491T

28394AB

28491SMO

28491Z

TABLE C
TYPE MV-R REVERSE ACTION NOZZLE
PART NUMBERS
Material
Stainless
Steel

Brass &
Leaded
Gunmetal
LG2

Titanium

Aluminium
Bronze

SMO254

Zeron 100

MV10T

28492

28285

28492T

28285AB

28492SMO

28492Z

MV12T

28493

28281

28493T

28281AB

28493SMO

28493Z

MV15T

28494

28282

28494T

28282AB

28494SMO

28494Z

Orifice
Size

MV18T

28495

28283

28495T

28283AB

28495SMO

28495Z

MV19T

28496

28286

28496T

28286AB

28496SMO

28496Z

MV21T

28497

28287

28497T

28287AB

28497SMO

28497Z

MV25T

28498

28288

28498T

28288AB

28498SMO

28498Z

MV26T

28499

28289

28499T

28289AB

28499SMO

28499Z

MV30T

28500

28290

28500T

28290AB

28500SMO

28500Z

MV34T

28501

28291

28501T

28291AB

28501SMO

28501Z

MV47T

28502

28292

28502T

28292AB

28502SMO

28502Z

MV57T

28503

28293

28503T

28293AB

28503SMO

28503Z

TABLE D
TYPE MV-T TANK TOP NOZZLE
PART NUMBERS

Limited
Warranty

Ordering
Procedure

For warranty terms and conditions, visit


www.tyco-fire.com.

Contact your local distributor for availability. When placing an order, indicate
the full product name and part number
(P/N).

Type MV-T Tank Top Nozzles


Specify: Type MV-T Tank Top Nozzle,
Open, Medium Velocity, orifice size
(specify), material (specify), P/N (specify
from Table D).

Type MV-R Reverse Action Nozzles


Specify: Type MV-R Reverse Action
Nozzle, Open, Medium Velocity, orifice
size (specify), material (specify), P/N
(specify from Table C).