Metrik

AnalogueIndicatingMeters

Manual
Metrik
Analogue Indicating Meters
Publication Reference:

mtrka/EN/M/C2011.ALSTOM,theALSTOMlogoandanyalternativeversionthereofaretrademarksandservicemarksofALSTOM.Theothernames
mentioned,registeredornot,arethepropertyoftheirrespectivecompanies.Thetechnicalandotherdatacontainedinthisdocumentisprovidedfor
information only.NeitherALSTOM, its officers or employeesacceptresponsibilityfor, orshould be takenasmakinganyrepresentation or warranty
(whetherexpressorimplied),astotheaccuracyorcompletenessofsuchdataortheachievementofanyprojectedperformancecriteriawheretheseare
indicated.ALSTOMreservestherighttoreviseorchangethisdataatanytimewithoutfurthernotice.

mtrka/EN/M/C

GRID

Service Manual

MTRKA/EN M/C

METRIK

Page 1/56

HANDLING OF ELECTRONIC EQUIPMENT


A persons normal movements can easily generate electrostatic potentials of several
thousand volts. Discharge of these voltages into semiconductor devices when handling
circuits can cause serious damage, which often may not be immediately apparent but the
reliability of the circuit will have been reduced.
The electronic circuits of Alstom Grid products are immune to the relevant levels of
electrostatic discharge when housed in their cases. Do not expose them to the risk of
damage by withdrawing modules unnecessarily.
Each module incorporates the highest practicable protection for its semiconductor devices.
However, if it becomes necessary to withdraw a module, the following precautions should be
taken to preserve the high reliability and long life for which the equipment has been designed
and manufactured.
1.

Before removing a module, ensure that you are a same electrostatic potential as the
equipment by touching the case.

2.

Handle the module by its front-plate, frame, or edges of the printed circuit board.
Avoid touching the electronic components, printed circuit track or connectors.

3.

Do not pass the module to any person without first ensuring that you are both at the
same electrostatic potential. Shaking hands achieves equipotential.

4.

Place the module on an anti-static surface, or on a conducting surface that is at the


same potential as you.

5.

Store or transport the module in a conductive bag.

More information on safe working procedures for all electronic equipment can be found in
BS5783 and IEC 60147-0F.
If you are making measurements on the internal electronic circuitry of equipment in service, it
is preferable that you are earthed to the case with a conductive wrist strap.
Wrist straps should have a resistance to ground between 500k 10M ohms. If a wrist strap
is not available you should maintain regular contact with the case to prevent the build up of
static. Instrumentation which may be used for making measurements should be earthed to
the case whenever possible.
Alstom Grid strongly recommends that detailed investigations on the electronic circuitry, or
modification work, should be carried out in a Special Handling Area such as described in
BS5783 or IEC 60147-0F.

MTRKA/EN M/C

Service Manual

Page 2/56

METRIK

BLANK PAGE

Service Manual

MTRKA/EN M/C

METRIK

1.

Page 3/56

SAFETY SECTION
This Safety Section should be read before commencing any work on the equipment.

1.1

Health and Safety


The information in the Safety Section of the product documentation is intended to ensure
that products are properly installed and handled in order to maintain them in a safe condition.
It is assumed that everyone who will be associated with the equipment will be familiar with
the contents of the Safety Section.

1.2

Explanation of symbols and labels


The meaning of symbols and labels may be used on the equipment or in the product
documentation, is given below.

Caution: refer to product documentation

Caution: risk of electric shock

Protective/safety *earth terminal

Functional *earth terminal


NOTE: This symbol may also be used for a
protective/safety earth terminal if that
terminal is part of a terminal block or
sub-assembly e.g. power supply.

*NOTE:

THE TERM EARTH USED THROUGHOUT THE PRODUCT


DOCUMENTATION IS THE DIRECT EQUIVALENT OF THE NORTH
AMERICAN TERM GROUND.

MTRKA/EN M/C
Page 4/56

2.

Service Manual
METRIK

INSTALLING, COMMISSIONING AND SERVICING

Equipment connections
Personnel undertaking installation, commissioning or servicing work on this equipment
should be aware of the correct working procedures to ensure safety. The product
documentation should be consulted before installing, commissioning or servicing the
equipment.
Terminals exposed during installation, commissioning and maintenance may present a
hazardous voltage unless the equipment is electrically isolated.
If there is unlocked access to the rear of the equipment, care should be taken by all
personnel to avoid electrical shock or energy hazards.
Voltage and current connections should be made using insulated crimp terminations to
ensure that terminal block insulation requirements are maintained for safety. To ensure that
wires are correctly terminated the correct crimp terminal and tool for the wire size should be
used.
Before energising the equipment it must be earthed using the protective earth terminal, or
the appropriate termination of the supply plug in the case of plug connected equipment.
Omitting or disconnecting the equipment earth may cause a safety hazard.
The recommended minimum earth wire size is 2.5mm2, unless otherwise stated in the
technical data section of the product documentation.
Before energising the equipment, the following should be checked:

Voltage rating and polarity;

CT circuit rating and integrity of connections;

Protective fuse rating;

Integrity of earth connection (where applicable)

Service Manual
METRIK

3.

MTRKA/EN M/C
Page 5/56

EQUIPMENT OPERATING CONDITIONS


The equipment should be operated within the specified electrical and environmental limits.

3.1

Current transformer circuits

Do not open the secondary circuit of a live CT since the high level voltage produced may be
lethal to personnel and could damage insulation.
3.2

External resistors

Where external resistors are fitted to relays, these may present a risk of electric shock or
burns, if touched.
3.3

Battery Replacement

Where internal batteries are fitted they should be replaced with the recommended type and
be installed with the correct polarity, to avoid possible damage to the equipment.
3.4

Insulation and dielectric strength testing

Insulation testing may leave capacitors charged up to a hazardous voltage. At the end of
each part of the test, the voltage should be gradually reduced to zero, to discharge
capacitors, before the test leads are disconnected.
3.5

Insertion of modules and pcb cards

These must not be inserted into or withdrawn from equipment whist it is energised since this
may result in damage.
3.6

Fibre optic communication

Where fibre optic communication devices are fitted, these should not be viewed directly.
Optical power meters should be used to determine the operation or signal level of the device.

MTRKA/EN M/C
Page 6/56

4.

Service Manual
METRIK

OLDER PRODUCTS
Electrical adjustments

Equipments that require direct physical adjustments to their operating mechanism to change
current or voltage settings should have the electrical power removed before making the
change, to avoid any risk of electrical shock.
Mechanical adjustments

The electrical power to the relay contacts should be removed before checking any
mechanical settings, to avoid any risk of electric shock.
Draw out case relays

Removal of the cover on equipment incorporating electromechanical operating elements,


may expose hazardous live parts such as relay contacts.
Insertion and withdrawal of extender cards

When using an extender card, this should not be inserted or withdrawn from the equipment
whilst it is energised. This is to avoid possible shock or damage hazards. Hazardous live
voltages may be accessible on the extender card.
Insertion and withdrawal of heavy current test plugs

When using a heavy current test plug, CT shorting links must be in place before insertion or
removal, to avoid potentially lethal voltages.

Service Manual

MTRKA/EN M/C

METRIK

5.

Page 7/56

DECOMMISSIONING AND DISPOSAL

Decommissioning:

The auxiliary supply circuit in the relay may include capacitors across
the supply or to earth. To avoid electric shock or energy hazards,
after completely isolating the supplies to the relay (both poles of any
dc supply), the capacitors should be safely discharged via the external
terminals prior to decommissioning.

Disposal:

It is recommended that incineration and disposal to water courses is


avoided. The product should be disposed of in a safe manner. Any
products containing batteries should have them removed before
disposal, taking precautions to avoid short circuits.
Particular
regulations within the country of operation, may apply to the disposal
of lithium batteries.

MTRKA/EN M/C

Service Manual

Page 8/56

METRIK

6.

TECHNICAL SPECIFICATIONS

6.1

Protective fuse rating


The recommended maximum rating of the external protective fuse for this equipment is 16A,
Red Spot type or equivalent, unless otherwise stated in the technical data section of the
product documentation.
Insulation class:

IEC 61010-1 : 2002 Class II


EN 61010-1 : 2002 Class II

Insulation Category
(Over voltage):

IEC 61010-1 : 2002


Category III
EN 61010-1 : 2002
Category III

Environment:

IEC 61010-1 : 2002


Pollution degree 2
EN 61010-1 : 2002
Pollution degree 2

Product Safety:

Compliance is demonstrated by
reference to generic safety
standards.

73/23/EEC & 2006/95/EC

Compliance with the European


Commission Low Voltage
Directive.

EN 61010-1 : 2002

Compliance is demonstrated by
reference to generic safety
standards.

Service Manual
METRIK

MTRKA/EN M/C
Page 9/56

CONTENT
1.

SAFETY SECTION

1.1

Health and Safety

1.2

Explanation of symbols and labels

2.

INSTALLING, COMMISSIONING AND SERVICING

3.

EQUIPMENT OPERATING CONDITIONS

3.1

Current transformer circuits

3.2

External resistors

3.3

Battery Replacement

3.4

Insulation and dielectric strength testing

3.5

Insertion of modules and pcb cards

3.6

Fibre optic communication

4.

OLDER PRODUCTS

5.

DECOMMISSIONING AND DISPOSAL

6.

TECHNICAL SPECIFICATIONS

6.1

Protective fuse rating

7.

INTRODUCTION

13

8.

TECHNICAL INFORMATION

15

8.1

METRIK A (AMMETERS)

15

8.1.1

Moving Iron

15

8.1.2

Moving Coil

16

8.1.3

Rectified Moving Coil

16

8.2

METRIK C (METER RELAYS)

16

8.3

METRIK D (DIFFERENTIAL METER)

17

8.3.1

Differential instruments

17

8.3.2

Dual value instruments

18

8.4

METRIK F (FREQUENCY METERS)

19

8.4.1

Pointer instruments

19

8.4.2

Reed instruments

20

8.5

METRIK M (MAXIMUM DEMAND AMMETERS)

21

8.5.1

Maximum demand ammeters

21

8.6

METRIK P (POWER FACTOR METERS)

22

8.7

METRIK PSI (PHASE SEQUENCE INDICATORS)

23

8.8

METRIK R (VARMETERS)

24

8.9

METRIK S (SYNCHRONISING METER)

25

MTRKA/EN M/C
Page 10/56

Service Manual
METRIK

8.9.1

Electronic meters

25

8.9.2

Electro-mechanical meters

26

8.10

METRIK T (TIME ELAPSE/HOURS RUN)

26

8.11

METRIK V (VOLTMETERS)

27

8.11.1

Moving Iron

28

8.11.2

Moving Coil

28

8.11.3

Rectified Moving Coil

28

8.12

METRIK W (WATTMETERS)

28

9.

INSTRUMENT NOMENCLATURE

30

9.1

METRIK A ammeters

30

9.2

METRIK C meter relays

30

9.3

METRIK D Differential Instruments

31

9.4

METRIK F frequency meters

31

9.5

METRIK M maximum demand meter

32

9.6

METRIK P Phase Angle meters

32

9.7

METRIK PSI Phase Sequence Indication

33

9.8

METRIK R Varmeters

33

9.9

METRIK S Synchronising Instruments

34

9.10

METRIK T time elapse/hours run

34

9.11

METRIK V Voltmeters

35

9.12

METRIK W Wattmeters

36

10.

WIRING DIAGRAMS

37

10.1

ST/SM SYNCHRONISING METERS

37

10.2

SL SYNCHRONISING METERS

38

10.3

P, R AND W POWER METERS

39

11.

INSTRUMENTATION ACCESSORY

40

11.1

TA SERIES MOULDED CASE CURRENT TRANSFORMERS

40

11.1.1

Introduction

40

11.1.2

CT selection tables

41

11.1.3

Technical details

42

11.2

TC SERIES NARROW WIDTH CURRENT TRANSFORMERS

43

11.2.1

Introduction

43

11.2.2

CT selection tables

43

11.3

TYPE 17* CURRENT TRANSFORMERS

45

Service Manual
METRIK

MTRKA/EN M/C
Page 11/56

11.3.1

Introduction to type 173

45

11.3.2

Features

45

11.3.3

Technical specification

45

11.3.4

Range

45

11.3.5

Outline dimensions

45

11.3.6

Introduction to type 174

46

11.3.7

Features

46

11.3.8

Technical specification

46

11.3.9

Range

46

11.3.10 Outline dimensions

46

11.4

RT SPLIT CORE CURRENT TRANSFORMERS

47

11.4.1

Introduction to type RT

47

11.4.2

Features

47

11.4.3

Technical specification

47

11.4.4

Range and dimensions

47

11.4.5

Outline drawing

48

11.5

RT RING CORE CURRENT TRANSFORMERS

48

11.5.1

Introduction to type RT

48

11.5.2

Features

48

11.5.3

Technical specification

48

11.5.4

Measurement

49

11.5.5

Protection

49

11.5.6

Dimensions

50

11.6

DC SHUNTS

51

11.6.1

Introduction

51

11.6.2

Accuracy

51

11.6.3

Range

51

11.6.4

Outline drawings

51

11.6.5

Dimensions

52

11.7

PHASE SELECTOR SWITCH

53

11.7.1

Introduction

53

11.7.2

Types

53

11.7.3

Accessories

53

11.7.4

Features

53

11.7.5

Technical details

53

11.7.6

Standards

53

11.7.7

Ordering information

54

11.7.8

Outline and dimensions

54

11.7.9

Switch drawings

55

MTRKA/EN M/C

Service Manual

Page 12/56

METRIK

BLANK PAGE

Service Manual

MTRKA/EN M/C

METRIK

7.

Page 13/56

INTRODUCTION
The METRIK range of analogue indicating instruments cover a number of measurement,
monitoring and metering functions for comprehensive power system information. The use of
analogue technology achieves high accuracy over a wide dynamic measuring range for
instantaneous and integrated power system parameters. METRIK provides a host of
measurement, monitoring and metering facilities as detailed below:

METRIK A (Ammeters)

AC moving iron measurement

DC moving coil measurement

AC rectified moving coil measurement

Short (90) and long scale (240) display of readings

METRIK C (Indicating meter with an output contact)

AC moving iron measurement

DC moving coil measurement

Voltage and current measurement

Alarm contact

Short (90) scale display of readings

METRIK D (Differential meters)

DV differential voltmeters

DF Differential frequency meters

Short (90) scale display of readings

METRIK F (Frequency meters)

Single and double pointer indication

Single and double reed indication

Differential indication

Short (90) and long scale (240) display of readings

METRIK M (Maximum Demand meters)

8, 15, 20 or 30 minute integration time

With a saturable CT

With or without instantaneous current indication

Short (90) scale display of readings

METRIK P (Phase Angle meters)

Single or three phase connection

3 wire or 4 wire, balanced or unbalanced loads

Short (90) and long scale (240) display of readings

METRIK PSI (Phase Sequence Indication)

Single phase connection

MTRKA/EN M/C

Service Manual

Page 14/56

METRIK
METRIK R (Varmeters)

Single or three phase connection

3 wire or 4 wire, balanced or unbalanced loads

Class 1.0 or 1.5 accuracy

Short (90) and long scale (240) display of readings

METRIK S (Synchronising Instruments)

Single or three phase connection

Rotary (360) scale display of readings

METRIK T (Hours run/time elapse Meters)

AC or DC voltage input

Rotary digit indication

METRIK V (Voltmmeters)

AC moving iron measurement

DC moving coil measurement

AC rectified moving coil measurement

Short (90) and long scale (240) display of readings

METRIK W (Wattmeters)

Single or three phase connection

3 wire or 4 wire, balanced or unbalanced loads

Class 1.0 or 1.5 accuracy

Short (90) and long scale (240) display of readings

User friendly features.

High accuracy, typically 1.5 for for current, voltage and power measurements.
Class 0.5 for frequency meaurements.

True RMS measurement (moving iron).

Mean measurement (moving coil).

Customer defined scaling details.

Service Manual

MTRKA/EN M/C

METRIK

Page 15/56

8.

TECHNICAL INFORMATION

8.1

METRIK A (AMMETERS)
METRIK A ammeters can be supplied with either moving iron, moving coil or rectified moving
coil movements.
DESIGN
Accuracy

Class 1.5

Burden

0.3 1.2VA

Material

PC (uninflammable to UL94 V-0)

Enclosure protection

Case IP52, terminals IP00 to EN60529 :1989

Operating position

Vertical

Test Voltage

2kv rms to EN61010-1 :1990

Environmental conditions

EN60051-1 :1995/01
EN60051-2 :1984
EN60051-9 :1988

Temperature: nominal range

-25 +55 C

Temperature: reference range

+18 +28 C

Temperature: storage range

-40 +70 C

Humidity

Up to 80% (without condensing)

DIMENSIONS

8.1.1

Case size

48mm

72mm

96mm

144mm

Bezel height (mm)

48mm

72mm

96mm

144mm

Panel cut out (mm)

45mm+
0.6mm

68mm+
0.8mm

92mm+
0.8mm

138mm+
1.0mm

Bezel depth (mm)

5mm

5.5mm

5.5mm

8mm

Scale length

41mm

62mm

92mm

135mm

Weight

0.14kg

0.18kg

0.2kg

0.4kg

Moving Iron
Meters with a moving iron are intended for measurement of AC currents with frequencies
from 15 Hz to 100 Hz. They measure rms values independently on the signal form of current.
The accuracy class is 1.5. As the beginning of the scale is non-linear, reading from 15% of
rating onwards is possible. Ammeters with ratings for double, triple or even six-times the
value of rated current are available on request. The overload range is extremely non-linear.
MEASURING RANGE
mA

100, 150, 250, 400 or 600 mA

1, 1.5, 2.5, 4, 6, 10, 15, 25, 40 or 60A

MTRKA/EN M/C

Service Manual

Page 16/56
8.1.2

METRIK

Moving Coil
Meters with a moving coil are intended for measurement of direct currents. A measuring
system with a core magnet is not sensitive to external electromagnetic fields and is resistant
to mechanical impacts and vibrations. The scale is entirely linear and interchangeable. The
accuracy class is 1.5.
MEASURING RANGE

8.1.3

40, 60, 100, 150, 250, 400 or 600 A

mA

1, 1.5, 2.5, 4, 5, 6, 10, 15, 20, 25, 40, 50, 60, 100, 150, 250, 400, 600mA or
4 20mA

Rectified Moving Coil


Meters with a moving coil and a rectifier are intended for measurement of AC currents in the
frequency range from 40 Hz to 5000 Hz where low meter consumption is required. The
meters measure the mean value of rectified current. The scale is expressed in rms values at
the sine form of the measured quantity. Distortion or deviation from the sine form of more
than 1% entails additional errors. The scale is interchangeable. The accuracy class is 1.5.
MEASURING RANGE

8.2

100, 150, 250, 400, 500 or 600 A

mA

1, 1.5, 2.5, 4, 5, 6, 10,mA

METRIK C (METER RELAYS)


METRIK C meter relays combine indication and control of ac or dc voltages and currents.
They can be used with a variety of transducers or sensors and have a wide range of
applications in the electrical amd process industries.
Indication is by means of accurate and robust moving iron and moving coil movements. Each
instrument has two independently adjustable alarm or control points which can be set
anywhere on the scale by back of panel potentiometers.
Two relay outputs are provided with adjustable time delay on pickup or drop off. The relays
are available in combinations of alarm indication:

High and Low

Low and Low

High and High

This alarm configuration has to be specified at the time of order. In addition LED indicators
display when either of the alarms trip.
DIMENSIONS
Case size

96mm

Bezel height (mm)

96mm

Panel cut out (mm)

91mm

Bezel depth (mm)

5.7mm

Scale length

90mm

Weight

0.48g

Service Manual

MTRKA/EN M/C

METRIK

Page 17/56
MEASURING RANGE

8.3

Voltage

mV

10, 15, 20, 25, 40 or 50mV


60, 100, 150, 250, 300, 400, 500 or 600mV

Voltage

1, 1.5, 2.5, 4 , 5, 6 , 10, 15, 20, 25 or 40V


50, 60, 100, 150, 250 or 300V
400, 500 or 600V

Current

15, 20, 30, 40 or 50A


60, 100, 150, 250, 300, 400, 500 or 600A

Current

mA

1, 1.5, 2.5, 4 , 5, 6 , 10, 15, 20, 25, 40 or 60mA


100, 150, 200, 300, 400, 500 or 600mA

Current

1, 1.5, 2.5, 4 , 5A

METRIK D (DIFFERENTIAL METER)


METRIK D differential meters can be supplied as either showing the difference between two
measured signals or showing two measured values on the same meter.
DIMENSIONS
Case size

96mm

144mm

Bezel height (mm)

96mm

144mm

Panel cut out (mm)

92mm+ 0.8mm

138mm+1.0mm

Bezel depth (mm)

5.5mm

8mm

Scale length

92mm

135mm

Weight

0.2kg

0.4kg

Instrument Options : the following options are available on this instrument:


Glass: Clear, low glare or polycarbonate
Construction : Tropic sealing
8.3.1

Differential instruments
METRIK D differential instruments are intended to show the diffential measurement of either
voltage or frequency. The voltmeters use rectified moving coil movements whlist the
frequency meters have a microprocessor measurement method.
DESIGN : VOLTAGE
Accuracy

Class 1.5

Burden

0.3 1.2VA

Material

PC (uninflammable to UL94 V-0)

Enclosure protection

Case IP52, terminals IP00 to EN60529 :1989

Operating position

Vertical

Test Voltage

2kv rms to EN61010-1 :1990

Environmental conditions

EN60051-1 :1995/01
EN60051-2 :1984
EN60051-9 :1988

Temperature: nominal range

-25 +55 C

Temperature: reference range

+18 +28 C

Temperature: storage range

-40 +70 C

Humidity

Up to 80% (without condensing)

MTRKA/EN M/C

Service Manual

Page 18/56

METRIK

DESIGN : FREQUENCY
Accuracy

Class 0.5

Voltage circuit

57.7/110, 230, 400 or 500V ac

Voltage range (power supply)

20%

Voltage Burden

1.0VA (57.7V) to 2VA (500V)

Voltage overload

1.2 x continuously, 2 x for 5s

Material

PC (uninflammable to UL94 V-0)

Enclosure protection

Case IP52, terminals IP00 to EN60529 :1997

Operating position

Vertical

Test Voltage

EN61010-1 :2002, CAT III 300v

Environmental conditions

EN60051-1 :1995/01
EN60051-2 :1984
EN60051-9 :1988

Temperature: nominal range

-25 +55 C

Temperature: reference range

+18 +28 C

Temperature: storage range

-40 +70 C

Humidity

Up to 80% (without condensing)

MEASURING RANGE
Frequency
8.3.2

45 .. 55Hz, 48 .. 52Hz, 45 .. 65Hz, 55 .. 65Hz or 58 .. 62Hz

Dual value instruments


METRIK D dual value instruments are intended to show two voltage measurements on the
same meter. They use a moving iron measurement method.
DESIGN : VOLTMETERS
Accuracy

Class 1.5

Burden

0.3 1.2VA

Material

PC (uninflammable to UL94 V-0)

Enclosure protection

Case IP52, terminals IP00 to EN60529 :1989

Operating position

Vertical

Test Voltage

2kv rms to EN61010-1 :1990

Environmental conditions

EN60051-1 :1995/01
EN60051-2 :1984
EN60051-9 :1988

Temperature: nominal range

-25 +55 C

Temperature: reference range

+18 +28 C

Temperature: storage range

-40 +70 C

Humidity

Up to 80% (without condensing)

Service Manual

MTRKA/EN M/C

METRIK
8.4

Page 19/56
METRIK F (FREQUENCY METERS)
METRIK F frequency meters can be supplied with either pointer or reed indication.

8.4.1

Pointer instruments
METRIK F Pointer frequency meters are intended for measurement of frequencies in the
range from 45 Hz to 65 Hz. The accuracy class is 0.5. It is designed for measurement of
mains voltage frequency within five different measuring ranges (45-55 Hz, 48-52 Hz, 45-65
Hz, etc). The Meter consists of: power supply unit, measuring unit with microprocessor and
instrument with moving coil.
DESIGN
Accuracy

Class 0.5

Voltage circuit

57.7/110, 230, 400 or 500V ac

Voltage range (power supply)

20%

Voltage Burden

1.0VA (57.7V) to 2VA (500V)

Voltage overload

1.2 x continuously, 2 x for 5s

Material

PC (uninflammable to UL94 V-0)

Enclosure protection

Case IP52, terminals IP00 to EN60529 :1997

Operating position

Vertical

Test Voltage

EN61010-1 :2002, CAT III 300v

Environmental conditions

EN60051-1 :1995/01
EN60051-2 :1984
EN60051-9 :1988

Temperature: nominal range

-25 +55 C

Temperature: reference range

+18 +28 C

Temperature: storage range

-40 +70 C

Humidity

Up to 80% (without condensing)

DIMENSIONS
Case size

72mm

96mm

Bezel height (mm)

72mm

96mm

Panel cut out (mm)

68mm+0.8mm

92mm+0.8mm

Bezel depth (mm)

5.5mm

5.5mm

Scale length

62mm

92mm

Weight

0.18kg

0.2kg

MEASURING RANGE
Frequency

45 .. 55Hz, 48 .. 52Hz, 45 .. 65Hz, 55 .. 65Hz or 58 .. 62Hz

Instrument Options: the following options are available on this instrument:


Glass: Clear, low glare or polycarbonate
Construction : Tropic sealing

MTRKA/EN M/C

Service Manual

Page 20/56
8.4.2

METRIK

Reed instruments
METRIK F Reed frequency meters are intended for measurement of frequencies in the
range from 45 Hz to 65 Hz. Two-system reed frequency meters are intended for
measurement of two frequencies in the system for synchronisation. Their class is 0.5. They
are in three different sizes: 144x144 mm, 96x96 mm or (72x72mm single reed only).
DESIGN
Accuracy

Class 0.5

Voltage circuit

110, 230, 400 or 500V ac

Voltage range (power supply)

20%

Voltage Burden

1.0VA (57.7V) to 2VA (500V)

Voltage overload

1.2 x continuously, 2 x for 5s

Material

PC (uninflammable to UL94 V-0)

Enclosure protection

Case IP52, terminals IP00 to EN60529 :1989

Operating position

Vertical

Test Voltage

2kv to EN61010-1 :1990

Environmental conditions

EN60051-1 :1995/01
EN60051-2 :1984
EN60051-9 :1988

Temperature: nominal range

-25 +55 C

Temperature: reference range

+18 +28 C

Temperature: storage range

-40 +70 C

Humidity

Up to 80% (without condensing)

DIMENSIONS
Case size

72mm

96mm

144mm

Bezel height (mm)

72mm

96mm

144mm

Panel cut out (mm)

68mm+0.8mm

92mm+0.8mm

138mm+1.0mm

Bezel depth (mm)

5.5mm

5.5mm

8mm

Scale length

62mm

92mm

135mm

Weight

0.18kg

0.2kg

0.4kg

MEASURING RANGE
Frequency

47 .. 53Hz, 57 .. 63Hz, 45 .. 55Hz or 55 .. 65Hz

Instrument Options: the following options are available on this instrument:


Glass: Clear, low glare or polycarbonate
Construction : Tropic sealing

Service Manual

MTRKA/EN M/C

METRIK

Page 21/56

8.5

METRIK M (MAXIMUM DEMAND AMMETERS)

8.5.1

Maximum demand ammeters


METRIK M Maximum demand ammeters can be supplied with either with or without an
instantaneous current indicator. These bimetal maximum current meters with a bimetal
measuring system are intended for testing the thermal load of transformers, cables, electrical
machines, etc. They indicate average rms current value in a setting period of 8, 15, 20 or 30
minutes. The accuracy class is 3 and the meters are provided with an interchangeable scale.
METRIK M are supplied with a protecting saturable current transformer (available in 96mm
or 144mm case sizes).
DESIGN
Accuracy

Class 3.0 integrated measurement

Accuracy

Class 1.5 instananeous measurement

Current circuit

1A or 5A

Current Burden

1.8VA (1A) or 2.8VA (5A)

Material

PC (uninflammable to UL94 V-0)

Enclosure protection

Case IP52, terminals IP00 to EN60529 :1989

Operating position

Vertical

Test Voltage

2kv rms to EN61010-1 :1990

Environmental conditions

EN60051-1 :1995/01
EN60051-2 :1984
EN60051-9 :1988

Temperature: nominal range

-25 +55 C

Temperature: reference range

+18 +28 C

Temperature: storage range

-40 +70 C

Humidity

Up to 80% (without condensing)

DIMENSIONS
Case size

96mm

144mm

Bezel height (mm)

96mm

144mm

Panel cut out (mm)

92mm+0.8mm

138mm+1.0mm

Bezel depth (mm)

5.5mm

8mm

Scale length

92mm

135mm

Weight

0.2kg

0.4kg

MEASURING RANGE
Rating is calculated as 20% higer than the transformer ratio
Transformer ratio

Rating

Transformer ratio

Rating

10A

12 A

40A

48A

15A

18 A

50A

60A

20A

24A

60A

72A

25A

30A

75A

90A

30A

36A

80A

96A

MTRKA/EN M/C

Service Manual

Page 22/56
8.6

METRIK

METRIK P (POWER FACTOR METERS)


METRIK P Power factor meters are intended for measurement of power factors in single or
three phase networks, with balanced or unbalanced loads. The accuracy class is 2.5. Power
factor meters are available in two different sizes: 144x144 mm and 96x96 mm.
DESIGN
Accuracy

Class 2.5

Voltage circuit

57.7/100, 63.5/110 or 230/400V ac


3u or 3b max voltage 150/250V
4u, 4b or 1b max voltage 230/400V

Voltage Burden

<1.5VA per phase

Voltage overload

1.2 x continuously, 2 x for 5s

Current circuit

1A or 5A

Current Burden

<0.1VA per phase

Current overload

3 x continuously, 25 x for 3s, 50x for 1s

Frequency range

45 to 65Hz

Material

PC (uninflammable to UL94 V-0)

Enclosure protection

Case IP52, terminals IP00 to EN60529 :1989

Operating position

Vertical

Test Voltage

3.7kv rms to EN61010-1 :1990

Environmental conditions

EN60051-1 :1995/01
EN60051-2 :1984
EN60051-9 :1988

Temperature: nominal range

-25 +55 C

Temperature: reference range

+18 +28 C

Temperature: storage range

-40 +70 C

Humidity

Up to 80% (without condensing)

DIMENSIONS
Case size

96mm

144mm

Bezel height (mm)

96mm

144mm

Panel cut out (mm)

92mm+0.8mm

138mm+1.0mm

Bezel depth (mm)

5.5mm

8mm

Scale length

92mm

135mm

Weight

0.3kg

0.3kg

Active

Reactive

Single phase system 1b

U I Cos

U I Sin

Single phase system 4b

3 x U I Cos

3 x U I Sin

Three phase, 3 wire system

3 x U I Cos

3 x U I Sin

Three phase, 4 wire system

3 x U I Cos

3 x U I Sin

MEASURING RANGE
Power is calculated as follows :

Instrument Options: the following options are available on this instrument:


Scales: Spares scales and red line scale markings
Glass: Clear, low glare or polycarbonate
Construction: Tropic sealing

Service Manual

MTRKA/EN M/C

METRIK
8.7

Page 23/56
METRIK PSI (PHASE SEQUENCE INDICATORS)
METRIK PSI Phase Sequence Indicators are intended for to show that the phase rotation of
the connected three phase supply is correct. Illumination of the red neonindicator shows
incorrect phase rotation and green neon shows correct rotation.
DESIGN
Voltage circuit

Specified within 100 to 500V ac

Frequency range

50 or 60Hz

Material

PC (uninflammable to UL94 V-0)

Enclosure protection

Case IP52, terminals IP00 to EN60529 :1989

Operating position

Vertical

Test Voltage

3.7kv rms to EN61010-1 :1990

Environmental conditions

EN60051-1 :1995/01
EN60051-2 :1984
EN60051-9 :1988

Temperature: nominal range

-25 +55 C

Temperature: reference range

+18 +28 C

Temperature: storage range

-40 +70 C

Humidity

Up to 80% (without condensing)

DIMENSIONS
Case size

72mm

96mm

Bezel height (mm)

72mm

96mm

Panel cut out (mm)

68mm+0.8mm

92mm+0.8mm

Bezel depth (mm)

5.5mm

5.5mm

Scale length

62mm

92mm

Weight

0.18kg

0.3kg

MTRKA/EN M/C

Service Manual

Page 24/56
8.8

METRIK

METRIK R (VARMETERS)
METRIK R Power meters are electronic meters intended for measuring reactive power in
single or three phase networks, with balanced or unbalanced loads. The accuracy class is
1.5, but on request we are also able to produce class 1 meters. The scale value depends on
primary values of current and voltage. The power meters are in two different sizes: 144x144
mm or 96x96 mm.
DESIGN
Accuracy

Class 1.5 or Class 1.0

Voltage circuit

57.7/100, 63.5/110 or 230/400V ac


3u or 3b max voltage 150/250V
4u, 4b or 1b max voltage 230/400V

Voltage Burden

<1.5VA per phase

Voltage overload

1.2 x continuously, 2 x for 5s

Current circuit

1A or 5A

Current Burden

<0.1VA per phase

Current overload

3 x continuously, 25 x for 3s, 50x for 1s

Frequency range

45 to 65Hz

Material

PC (uninflammable to UL94 V-0)

Enclosure protection

Case IP52, terminals IP00 to EN60529 :1989

Operating position

Vertical

Test Voltage

3.7kv rms to EN61010-1 :1990

Environmental conditions

EN60051-1 :1995/01
EN60051-2 :1984
EN60051-9 :1988

Temperature: nominal range

-25 +55 C

Temperature: reference range

+18 +28 C

Temperature: storage range

-40 +70 C

Humidity

Up to 80% (without condensing)

DIMENSIONS
Case size

96mm

144mm

Bezel height (mm)

96mm

144mm

Panel cut out (mm)

92mm+0.8mm

138mm+1.0mm

Bezel depth (mm)

5.5mm

8mm

Scale length

92mm

135mm

Weight

0.3kg

0.3kg

Active

Reactive

Single phase system 1b

U I Cos

U I Sin

Single phase system 4b

3 x U I Cos

3 x U I Sin

Three phase, 3 wire system

3 x U I Cos

3 x U I Sin

Three phase, 4 wire system

3 x U I Cos

3 x U I Sin

MEASURING RANGE
Power is calculated as follows :

Service Manual

MTRKA/EN M/C

METRIK

Page 25/56
Instrument Options : the following options are available on this instrument:
Scales : Spares scales and red line scale markings
Glass : Clear, low glare or polycarbonate
Construction : Tropical sealing

8.9

METRIK S (SYNCHRONISING METER)


METRIK S synchronising meters are used to indicate when two voltage circuits can be
connected. This is done by checking that the voltage magnitude, phase rotation and
frequency are within preset limits.

8.9.1

Electronic meters
The SL96 synchroscope comprises of a circle of 18 red LEDs that light alternatively to
indicate phase differences. The speed and direction in which the LEDs light indicates the
whether the incoming machine is fast or slow. If the frequency is difference exceeds 3Hz
three LEDs above the FAST or SLOW inscriptions light alternately. In addition, the SL96 has
a LCD display for synchronisation information. Optional check- synchronising output relay
contacts close when synchronisation is reached.
DESIGN
Voltage circuit

57.7/100, 63.5/110, 120, 380, 415 or 440V ac

Voltage range

80 120%

Voltage Burden

<4VA

Voltage overload

1.2 x continuously, 2 x for 3s

Frequency range

40 to 70Hz

Material

PC (uninflammable to UL94 V-0)

Enclosure protection

Case IP52, terminals IP00 to EN60529 :1989

Operating position

Vertical

Environmental conditions

EN60051-1 :1995/01
EN60051-2 :1984
EN60051-9 :1988

Temperature: nominal range

-20 +55 C

Temperature: reference range

0 +50 C

Temperature: storage range

-40 +70 C

Humidity

Up to 95% (without condensing)


NOTE:

Further SL96 information is contained in the SL96 manual.

MTRKA/EN M/C

Service Manual

Page 26/56
8.9.2

METRIK

Electro-mechanical meters
These electromechanical synchroscopes have a analogue indication. They are available for
single (SM96 or SM14) and three phase (ST96 or ST14) circuits. The speed and direction of
the pointer indicates the whether the incoming machine is fast or slow. The pointer will rotate
in the correct direction when the difference in supply and running frequency has been
reduced to 1.5Hz or below.
DESIGN
Voltage circuit

Single : 57.7/100, 63.5/110, 220, 380, 440 or 500V ac


Three : 63.5/110, 220, 380, 440 or 500V ac

Voltage Burden

<4.5VA

Frequency range

50Hz : 47 to 51Hz, 60Hz : 57.5 to 61Hz

Operating position

Vertical

DIMENSIONS
Case size

96mm

144mm

Bezel height (mm)

96mm

144mm

Panel cut out (mm)

92mm+0.8mm

137mm+1.0mm

Bezel depth (mm)

5.7mm

7.3mm

Scale length

90mm

147mm

Weight

1.7kg

2.25kg

Instrument Options : the following options are available on this instrument:


Glass : Clear, low glare or plastic (ST and SM only)
Construction : Tropical sealing
8.10

METRIK T (TIME ELAPSE/HOURS RUN)


METRIK T time elapse meters count the number of hours that the circuit that they are
connected to has energised. They use a 7 digit cyclometer type indicator to diplay the
cumulative time in hours. They are available in either 48mm, 72mm or 96mm sizes.
DESIGN
Display

5 integers, 2 decimal (AC voltage)


6 integers, 1 decimal (DC voltage)

99,999.99
999,999.9

Burden

2VA

Enclosure protection

Case IP40,
48mm terminals IP20 to EN60529 :1989
72 & 96mm terminals IP00 to EN60529 :1989

Operating position

Vertical

Temperature: nominal range

-25 +80 C (AC voltage)


-20 +70 C (DC voltage)

MEASURING RANGE
AC Voltage

24, 48, 60, 110, 120, 230, 240 or 400V (610%)

Frequency

50 or 60Hz

DC Voltage

6/30, 10/80 or 110V (10%)

Instrument Options : the following options are available on this instrument:

Service Manual

MTRKA/EN M/C

METRIK

Page 27/56
Glass : Clear or low glare (not 48mm)
DIMENSIONS

8.11

Case size

48mm

72mm

96mm

Bezel height (mm)

48mm

72mm

96mm

Panel cut out (mm)

45mm+0.6mm

68mm+0.8mm

92mm+0.8mm

Bezel depth (mm)

5mm

5.5mm

5.5mm

Weight

0.14kg

0.18kg

0.2kg

METRIK V (VOLTMETERS)
METRIK V voltmeters can be supplied with moving iron, moving coil or rectified moving coil
movements
DESIGN
Accuracy

Class 1.5

Burden

0.3 1.2VA

Material

PC (uninflammable to UL94 V-0)

Enclosure protection

Case IP52, terminals IP00 to EN60529 :1989

Operating position

Vertical

Test Voltage

2 kv rms to EN61010-1 :1990

Environmental conditions

EN60051-1 :1995/01
EN60051-2 :1984
EN60051-9 :1988

Temperature: nominal range

-25 +55 C

Temperature: reference range

+18 +28 C

Temperature: storage range

-40 +70 C

Humidity

Up to 80% (without condensing)

DIMENSIONS
Case size

48mm

72mm

96mm

144mm

Bezel height (mm)

48mm

72mm

96mm

144mm

Panel cut out (mm) 45mm + 0.6mm 68mm + 0.8mm 92mm + 0.8mm 138mm + 1.0mm
Bezel depth (mm)

5mm

5.5mm

5.5mm

8mm

Scale length

41mm

62mm

92mm

135mm

Weight

0.14kg

0.18kg

0.2kg

0.4kg

MTRKA/EN M/C

Service Manual

Page 28/56
8.11.1

METRIK

Moving Iron
Meters with a moving iron are intended for measurement of AC voltages with frequencies
from 15 Hz to 100 Hz. They measure rms values independently on the signal form of
voltage. The accuracy class is 1.5. As the beginning of the scale is non-linear, reading from
15% of rating onwards is possible. The overload range is extremely non-linear.
MEASURING RANGE
V

8.11.2

6, 10, 15, 25, 40, 60, 100, 150, 250, 400 or 600V

Moving Coil
Meters with a moving coil are intended for measurement of direct voltages. A measuring
system with a core magnet is not sensitive to external electromagnetic fields and is resistant
to mechanical impacts and vibrations. The scale is entirely linear and interchangeable. The
accuracy class is 1.5.
MEASURING RANGE

8.11.3

mV

100, 150, 250, 400 or 600mV

1, 1.5, 2.5, 4, 6, 10, 15, 25, 40, 60, 100, 150, 250, 400, 500 or 600V

Sensitivity

1 k / per volt

Rectified Moving Coil


Meters with a moving coil and a rectifier are intended for measurement of AC voltages in the
frequency range from 40 Hz to 5000 Hz where low meter consumption is required. The
meters measure the mean value of rectified voltage. The scale is expressed in rms values at
the sine form of the measured quantity. Distortion or deviation from the sine form of more
than 1% entails additional errors. The scale is interchangeable. The accuracy class is 1.5.
MEASURING RANGE
V

8.12

2.5, 6, 10, 15, 25, 40, 60, 100, 150, 250, 400, 500 or 600V

METRIK W (WATTMETERS)
METRIK W Wattmeters are electronic meters intended for measuring active power in single
or three phase networks, with balanced or unbalanced loads. The accuracy class is 1.5, but
on request we are also able to produce class 1 meters. The scale value depends on primary
values of current and voltage. The power meters are in two different sizes: 144x144 mm or
96x96 mm.
DESIGN
Accuracy

Class 1.5 or Class 1.0

Voltage circuit

57.7/100, 63.5/110 or 230/400V ac


3u or 3b max voltage 150/250V
4u, 4b or 1b max voltage 230/400V

Voltage Burden

<1.5VA per phase

Voltage overload

1.2 x continuously, 2 x for 5s

Current circuit

1A or 5A

Current Burden

<0.1VA per phase

Current overload

3 x continuously, 25 x for 3s, 50x for 1s

Frequency range

45 to 65Hz

Material

PC (uninflammable to UL94 V-0)

Enclosure protection

Case IP52, terminals IP00 to EN60529 :1989

Operating position

Vertical

Test Voltage

3.7kv rms to EN61010-1 :1990

Environmental conditions

EN60051-1 :1995/01

Service Manual

MTRKA/EN M/C

METRIK

Page 29/56
EN60051-2 :1984
EN60051-9 :1988
Temperature: nominal range

-25 +55 C

Temperature: reference range

+18 +28 C

Temperature: storage range

-40 +70 C

Humidity

Up to 80% (without condensing)

DIMENSIONS
Case size

96mm

144mm

Bezel height (mm)

96mm

144mm

Panel cut out (mm)

92mm + 0.8mm

138mm + 1.0mm

Bezel depth (mm)

5.5mm

8mm

Scale length

92mm

135mm

Weight

0.3kg

0.3kg

Active

Reactive

Single phase system 1b

U I Cos

U I Sin

Single phase system 4b

3 x U I Cos

3 x U I Sin

Three phase, 3 wire system

3 x U I Cos

3 x U I Sin

Three phase, 4 wire system

3 x U I Cos

3 x U I Sin

MEASURING RANGE
Power is calculated as follows :

Instrument Options: the following options are available on this instrument:


Scales : Spares scales and red line scale markings
Glass : Clear, low glare or polycarbonate
Construction : Tropic sealing

MTRKA/EN M/C

Service Manual

Page 30/56

9.

METRIK

INSTRUMENT NOMENCLATURE
The METRIK analogue instrumentation range uses the following model number system to
identify the mechanical construction of the meter. In addition information of the design of the
dial will also be required.

9.1

METRIK A ammeters
The model number is 13 digits long. The first 5 digits identify the application whilst the
remainder identify the technical specification of the instrument.

9.2

Identifier

Scale

Case

Accuracy

Type

A48DC

90

48mm

1.5%

DC Moving Coil

A72DC

90

72mm

1.5%

DC Moving Coil

A96DC

90

96mm

1.5%

DC Moving Coil

A14DC

90

144mm

1.5%

DC Moving Coil

A48DI

90

48mm

1.5%

AC Moving Iron

A72DI

90

72mm

1.5%

AC Moving Iron

A96DI

90

96mm

1.5%

AC Moving Iron

A14DI

90

144mm

1.5%

AC Moving Iron

A48DR

90

48mm

1.5%

AC Rectified Moving Coil

A72DR

90

72mm

1.5%

AC Rectified Moving Coil

A96DR

90

96mm

1.5%

AC Rectified Moving Coil

A14DR

90

144mm

1.5%

AC Rectified Moving Coil

A48IC

240

48mm

1.5%

DC Moving Coil

A72IC

240

72mm

1.5%

DC Moving Coil

A96IC

240

96mm

1.5%

DC Moving Coil

A14IC

240

144mm

1.5%

DC Moving Coil

A48IR

240

48mm

1.5%

AC Rectified Moving Coil

A72IR

240

72mm

1.5%

AC Rectified Moving Coil

A96IR

240

96mm

1.5%

AC Rectified Moving Coil

A14IR

240

144mm

1.5%

AC Rectified Moving Coil

METRIK C meter relays


The model number is 14 digits long, The first 6 digits identify the application whilst the
remaining 8 identify the technical specification of the instrument.
Identifier

Movement

Case

Type

CA96ZC

Moving Coil

96mm

Ammeter

CA96ZI

Moving Iron

96mm

Ammeter

CA96ZR

Rectified Moving Coil

96mm

Ammeter

CV96ZC

Moving Coil

96mm

Voltmeter

CV96ZI

Moving Iron

96mm

Voltmeter

CV96ZR

Rectified Moving Coil

96mm

Voltmeter

Service Manual

MTRKA/EN M/C

METRIK
9.3

Page 31/56
METRIK D Differential Instruments
The model number is 13 digits long, The first 5 digits identify the application whilst the
remaining 8 identify the technical specification of the instrument.

9.4

Identifier

Case

Type

2V96D

96mm

Double Voltmeter

2V14D

144mm

Double Voltmeter

DF96D

96mm

Differential Frequency

DF14D

144mm

Differential Frequency

DV96D

96mm

Differential Voltmeter

DV14D

144mm

Differential Voltmeter

METRIK F frequency meters


The model number is 12 or 13 digits long depending on the model selected. The first 3 or 4
digits identify the application whilst the remaining 9 identify the technical specification of the
instrument.
Identifier

Scale

Case

Accuracy

Type

DF14D

90

144mm

0.5%

Differential Pointer

DF96D

90

96mm

0.5%

Differential Pointer

F72D

90

72mm

0.5%

Single pointer

F72L

240

72mm

0.5%

Single pointer

F96D

90

96mm

0.5%

Single pointer

F96L

240

96mm

0.5%

Single pointer

2R14D

144mm

0.5%

Single reed

2R72D

72mm

0.5%

Single reed

2R96D

96mm

0.5%

Single reed

2F14D

90

144mm

0.5%

Double pointer

2F14L

240

144mm

0.5%

Double pointer

2F96D

90

96mm

0.5%

Double pointer

2F96L

240

96mm

0.5%

Double pointer

2R14D

144mm

0.5%

Double reed

2R96D

96mm

0.5%

Double reed

MTRKA/EN M/C

Service Manual

Page 32/56
9.5

METRIK

METRIK M maximum demand meter


The model number is 14 digits long. The first 6 digits identify the application whilst the
remainder identify the technical specification of the instrument.

9.6

Identifier

Scale

Case

Time

Type

M96DDA

90

96mm

8 min

With instantaneous ammeter

M96DDB

90

96mm

15 min

With instantaneous ammeter

M96DDC

90

96mm

20 min

With instantaneous ammeter

M96DDD

90

96mm

30 min

With instantaneous ammeter

M96DSA

90

96mm

8 min

Without instantaneous ammeter

M96DSB

90

96mm

15 min

Without instantaneous ammeter

M96DSC

90

96mm

20 min

Without instantaneous ammeter

M96DSD

90

96mm

30 min

Without instantaneous ammeter

METRIK P Phase Angle meters


The model number is 16 digits long. The first 6 digits identify the application whilst the
remainder identify the technical specification of the instrument.
Identifier

Scale

Case

Accuracy

Phase

Wires

Load

P14DB1

90

144mm

2.5%

Single

balanced

P14DB3

90

144mm

2.5%

three

three

balanced

P14DB4

90

144mm

2.5%

three

four

balanced

P14DU3

90

144mm

2.5%

three

three

unbalanced

P14DU4

90

144mm

2.5%

three

four

unbalanced

P14IB1

240

144mm

2.5%

Single

balanced

P14IB3

240

144mm

2.5%

three

three

balanced

P14IB4

240

144mm

2.5%

three

four

balanced

P14IU3

240

144mm

2.5%

three

three

unbalanced

P14IU4

240

144mm

2.5%

three

four

unbalanced

P96DB1

90

96mm

2.5%

Single

balanced

P96DB3

90

96mm

2.5%

three

three

balanced

P96DB4

90

96mm

2.5%

three

four

balanced

P96DU3

90

96mm

2.5%

three

three

unbalanced

P96DU4

90

96mm

2.5%

three

four

unbalanced

P96IB1

240

96mm

2.5%

Single

balanced

P96IB3

240

96mm

2.5%

three

three

balanced

P96IB4

240

96mm

2.5%

three

four

balanced

P96IU3

240

96mm

2.5%

three

three

unbalanced

P96IU4

240

96mm

2.5%

three

four

unbalanced

Service Manual

MTRKA/EN M/C

METRIK
9.7

Page 33/56
METRIK PSI Phase Sequence Indication
The model number is 10 digits long. The first 5 digits identify the application whilst the
remainder identify the technical specification of the instrument.

9.8

Identifier

Case

Digits 6 to 8

Digit 9

Digit 10

PSI72

72mm

Ac voltage

Operating frequency

Design issue

PSI96

96mm

Ac voltage

Operating frequency

Design issue

METRIK R Varmeters
The model number is 16 digits long. The first 6 digits identify the application whilst the
remainder identify the technical specification of the instrument.
Identifier

Scale

Case

Accuracy

Phase

Wires

Load

R14DB1

90

144mm

1.5%

Single

balanced

R14DB3

90

144mm

1.5%

three

three

balanced

R14DB4

90

144mm

1.5%

three

four

balanced

R14DU3

90

144mm

1.5%

three

three

unbalanced

R14DU4

90

144mm

1.5%

three

four

unbalanced

R14IB1

240

144mm

1.5%

Single

balanced

R14IB3

240

144mm

1.5%

three

three

balanced

R14IB4

240

144mm

1.5%

three

four

balanced

R14IU3

240

144mm

1.5%

three

three

unbalanced

R14IU4

240

144mm

1.5%

three

four

unbalanced

R96DB1

90

96mm

1.5%

Single

balanced

R96DB3

90

96mm

1.5%

three

three

balanced

R96DB4

90

96mm

1.5%

three

four

balanced

R96DU3

90

96mm

1.5%

three

three

unbalanced

R96DU4

90

96mm

1.5%

three

four

unbalanced

R96IB1

240

96mm

1.5%

Single

balanced

R96IB3

240

96mm

1.5%

three

three

balanced

R96IB4

240

96mm

1.5%

three

four

balanced

R96IU3

240

96mm

1.5%

three

three

unbalanced

R96IU4

240

96mm

1.5%

three

four

unbalanced

R14EB1

90

144mm

1.0%

Single

balanced

R14EB3

90

144mm

1.0%

three

three

balanced

R14EB4

90

144mm

1.0%

three

four

balanced

R14EU3

90

144mm

1.0%

three

three

unbalanced

R14EU4

90

144mm

1.0%

three

four

unbalanced

R14KB1

240

144mm

1.0%

Single

balanced

R14KB3

240

144mm

1.0%

three

three

balanced

R14KB4

240

144mm

1.0%

three

four

balanced

R14KU3

240

144mm

1.0%

three

three

unbalanced

R14KU4

240

144mm

1.0%

three

four

unbalanced

MTRKA/EN M/C

Service Manual

Page 34/56

9.9

METRIK

Identifier

Scale

Case

Accuracy

Phase

Wires

Load

R96EB1

90

96mm

1.0%

Single

balanced

R96EB3

90

96mm

1.0%

three

three

balanced

R96EB4

90

96mm

1.0%

three

four

balanced

R96EU3

90

96mm

1.0%

three

three

unbalanced

R96EU4

90

96mm

1.0%

three

four

unbalanced

R96KB1

240

96mm

1.0%

Single

balanced

R96KB3

240

96mm

1.0%

three

three

balanced

R96KB4

240

96mm

1.0%

three

four

balanced

R96KU3

240

96mm

1.0%

three

three

unbalanced

R96KU4

240

96mm

1.0%

three

four

unbalanced

METRIK S Synchronising Instruments


The model number is 11 (mechanical movement) or 14 (electronic movement) digits long.
The first 4 digits identify the application whilst the remainder identify the technical
specification of the instrument.

9.10

Identifier

Case

Connection

Type

SL96

96mm

Single phase

Electronic display

SM14

144mm

Single phase

Mechanical pointer display

SM96

96mm

Single phase

Mechanical pointer display

ST14

144mm

Three phase

Mechanical pointer display

ST96

96mm

Three phase

Mechanical pointer display

METRIK T time elapse/hours run


The model number is 12 digits long. The first 4 digits identify the application whilst the
remainder identify the technical specification of the instrument.
Identifier

Case

Type

T48D

48mm

AC or DC hours run

T72D

72mm

AC or DC hours run

T96D

96mm

AC or DC hours run

Service Manual

MTRKA/EN M/C

METRIK
9.11

Page 35/56
METRIK V Voltmeters
The model number is 13 digits long. The first 5 digits identify the application whilst the
remainder identify the technical specification of the instrument.
Identifier

Scale

Case

Accuracy

Type

V48DC

90

48mm

1.5%

DC Moving Coil

V72DC

90

72mm

1.5%

DC Moving Coil

V96DC

90

96mm

1.5%

DC Moving Coil

V14DC

90

144mm

1.5%

DC Moving Coil

V48DI

90

48mm

1.5%

AC Moving Iron

V72DI

90

72mm

1.5%

AC Moving Iron

V96DI

90

96mm

1.5%

AC Moving Iron

V14DI

90

144mm

1.5%

AC Moving Iron

V48DR

90

48mm

1.5%

AC Rectified Moving Coil

V72DR

90

72mm

1.5%

AC Rectified Moving Coil

V96DR

90

96mm

1.5%

AC Rectified Moving Coil

V14DR

90

144mm

1.5%

AC Rectified Moving Coil

V48IC

240

48mm

1.5%

DC Moving Coil

V72IC

240

72mm

1.5%

DC Moving Coil

V96IC

240

96mm

1.5%

DC Moving Coil

V14IC

240

144mm

1.5%

DC Moving Coil

V48IR

240

48mm

1.5%

AC Rectified Moving Coil

V72IR

240

72mm

1.5%

AC Rectified Moving Coil

V96IR

240

96mm

1.5%

AC Rectified Moving Coil

V14IR

240

144mm

1.5%

AC Rectified Moving Coil

MTRKA/EN M/C

Service Manual

Page 36/56
9.12

METRIK

METRIK W Wattmeters
The model number is 16 digits long. The first 6 digits identify the application whilst the
remainder identify the technical specification of the instrument.
Identifier

Scale

Case

Accuracy

Phase

Wires

Load

W14DB1

90

144mm

1.5%

Single

balanced

W14DB3

90

144mm

1.5%

three

three

balanced

W14DB4

90

144mm

1.5%

three

four

balanced

W14DU3

90

144mm

1.5%

three

three

unbalanced

W14DU4

90

144mm

1.5%

three

four

unbalanced

W14IB1

240

144mm

1.5%

Single

balanced

W14IB3

240

144mm

1.5%

three

three

balanced

W14IB4

240

144mm

1.5%

three

four

balanced

W14IU3

240

144mm

1.5%

three

three

unbalanced

W14IU4

240

144mm

1.5%

three

four

unbalanced

W96DB1

90

96mm

1.5%

Single

balanced

W96DB3

90

96mm

1.5%

three

three

balanced

W96DB4

90

96mm

1.5%

three

four

balanced

W96DU3

90

96mm

1.5%

three

three

unbalanced

W96DU4

90

96mm

1.5%

three

four

unbalanced

W96IB1

240

96mm

1.5%

Single

balanced

W96IB3

240

96mm

1.5%

three

three

balanced

W96IB4

240

96mm

1.5%

three

four

balanced

W96IU3

240

96mm

1.5%

three

three

unbalanced

W96IU4

240

96mm

1.5%

three

four

unbalanced

W14EB1

90

144mm

1.0%

Single

balanced

W14EB3

90

144mm

1.0%

three

three

balanced

W14EB4

90

144mm

1.0%

three

four

balanced

W14EU3

90

144mm

1.0%

three

three

unbalanced

W14EU4

90

144mm

1.0%

three

four

unbalanced

W14KB1

240

144mm

1.0%

Single

balanced

W14KB3

240

144mm

1.0%

three

three

balanced

W14KB4

240

144mm

1.0%

three

four

balanced

W14KU3

240

144mm

1.0%

three

three

unbalanced

W14KU4

240

144mm

1.0%

three

four

unbalanced

W96EB1

90

96mm

1.0%

Single

balanced

W96EB3

90

96mm

1.0%

three

three

balanced

W96EB4

90

96mm

1.0%

three

four

balanced

W96EU3

90

96mm

1.0%

three

three

unbalanced

W96EU4

90

96mm

1.0%

three

four

unbalanced

W96KB1

240

96mm

1.0%

Single

balanced

W96KB3

240

96mm

1.0%

three

three

balanced

W96KB4

240

96mm

1.0%

three

four

balanced

W96KU3

240

96mm

1.0%

three

three

unbalanced

W96KU4

240

96mm

1.0%

three

four

unbalanced

Service Manual

MTRKA/EN M/C

METRIK

Page 37/56

10.

WIRING DIAGRAMS

10.1

ST/SM SYNCHRONISING METERS

2 5 8

21

51

R(L1)
S(L2)
T(L3)

u v

u v

u v

u v

incoming

u v
u v

R(L1)
S(L2)
T(L3)

running
M0104ENa

ST THREE PHASE CONNECTION

MTRKA/EN M/C

Service Manual

Page 38/56

METRIK

B E H

E H

E H

21

51

ACC1

R(L1)
S(L2)
100V
125V

100/3, 110/3
200V, 380V
440V, 500V

u v

u v

u v

u v

u v
u v

R(L1)
S(L2)

incoming

running
M0105ENa

SM SINGLE PHASE CONNECTION


10.2

SL SYNCHRONISING METERS

SYNC.
6

BUS BAR
4
L

GEN

3
N

2
L

1
N

K1
L
GEN.

N
US

M0102ENa

SL96 PHASE TO NEUTRAL CONNECTION

SYNC.
6

BUS BAR
4
L2

GEN

3
L1

2
L2

1
L1

K1
L3
L2
L1
US

GEN.

M0101ENa

P SL96 PHASE TO PHASE CONNECTION

Service Manual

MTRKA/EN M/C

METRIK
10.3

Page 39/56
P, R AND W POWER METERS

>>>

1b

CT1
CT2

15
16
17
18

Bat.

19
20
21

L1

Power Factor
Watts & vars

CT3
11
2
5
8

M161
M2x1

13
14
U

1b
*
*
*
*

b-balanced load

3b
*
*
*
*

3u
*
*
*
*

4b
*
*
*
*

4u
*
*
*
*

u-unbalanced load

3b

3b

CT3

19
20
21

L1

CT1

CT2
Bat.

11
2
5
8

4u

CT1
15
16
17
18

11
2
5
8

CT3
CT2
Bat.

19
20
21

13
14

L1
L2

>>>

Bat.

>>>

>>>

>>>
CT3
CT2

13
14

4b
CT1

11
2
5
8

L2
L3
N

Bat.

19
20
21

13
14

L1

19
20
21

CT3
CT2

15
16
17
18

L2
L3
N

15
16
17
18

>>>

>>>

>>>
CT1
15
16
17
18

11
2
5
8

L1
L2

L3
N

L3
N

Note: Connection teminals 19, 20, 21 are not on Power Factor types.

CONNECTION DIAGRAMS FOR PANEL METERS

13
14
V

L
K

M0106ENa

MTRKA/EN M/C

Service Manual

Page 40/56

METRIK

11.

INSTRUMENTATION ACCESSORY

11.1

TA SERIES MOULDED CASE CURRENT TRANSFORMERS

11.1.1

Introduction
The TA Series is a range of moulded case current transformers manufactured to IEC 60185,
the International Electrotechnical Commission Standard which specifies the rating and
performance requirements for CTs to be used with electrical measuring instruments and
protective devices. The TA Series includes CTs only for use with electrical measuring
instruments.
Product Features

11.1.1.1

User benefits

Class 3, 1 or 0.5 with 5A and 1A


secondaries as standard

One range of CTs allows a wide variety


of CT applications to be achieved from
one supplier

Compact design having apertures


designed for standard busbars up to
4000A

Conforms
with
industry
standard
dimensions for copperwork, eliminates
mounting problems and reduces the
requirement for special CTs to
accommodate the primary circuit

Choice of bar or foot mounting

Adaptable and easily mounted

Terminal cover and all fixings supplied


with each CT as standard

Full package approach


ordering process

simplifies

Application
In addition to the class accuracy, primary and secondary ratings, when selecting a CT the
aperture size and VA rating must also be determined.

11.1.1.2

Aperature size
The TA series is designed with aperture dimensions that suit the size of busbar for given
primary currents. Table 1 shows the copper busbar current ratings for different sizes of
busbar according to DIN 43761.
Busbar

Current (Amps)

Dimensions
(mm)

Number of bars
1

20 x 5

320

560

725

20 x 10

500

925

1320

25 x 3

280

470

525

25 x 5

385

660

840

30 x 3

335

545

590

30 x 5

445

760

940

30 x 10

675

1200

1670

40 x 10

850

1470

2000

2580

50 x 5

695

1140

1330

2010

50 x 10

1020

1720

2320

2950

60 x 5

825

1330

1510

2310

60 x 10

1180

1960

2610

3290

80 x 5

1070

1680

1830

2830

80 x 10

1500

2410

3170

3930

100 x 5

1300

2010

2150

3300

100 x 10

1810

2850

3720

4530

TABLE 1 : COPPER BUSBAR CURRENT RATINGS

Service Manual

MTRKA/EN M/C

METRIK
11.1.1.3

Page 41/56
VA RATING
The VA rating of a CT must be greater than, or equal to, the total VA burden of all the
devices being fed and the connecting cable. In order to select a CT with an appropriate VA
rating, refer to Tables 2 and 3 which show typical device and cable burdens respectively.
Moving Iron Instruments

0.4 . . . 1.5

Rectified Moving Coil Instruments

0.5

Power Instrument

1.0 . . . 2.5

Maximum Demand Indicators

2.5 . . . 5.0

Digital Indicators

0.5 . . . 1.0

kWh Meters

1.0 . . . 5.0

Recorders

2.0 . . . 5.0

Istat 300 Transducers

0.2 . . . 1.5

Numeric Relays

1.0 . . . 2.5
TABLE 2 : TYPICAL DEVICE BURDEN IN VA
Burden (VA/mm) of single conductor

Copper cross section


(mm2)

For 5A secondary CT

For 5A secondary CT

0.75

0.047

0.034

1.5

0.57

0.023

0.43

0.017

2.5

0.34

0.014

0.22

0.0085

0.14

0.0057

10

0.085

0.0034

TABLE 3 : CABLE BURDEN IN VA


11.1.2

CT selection tables
All CTs supplied with full fixing kit and terminal cover as standard. All CTs are available with
either 1A or 5A secondary. Wound primary CTs for lower primary currents are also available
on request.
VA

Type TA210: Primary current, secondary 1A or 5A:


Wound Primary
5A

10A

15A

20A

25A

Class 0.5

15

Class 1

20

Class 3

30
75A

100A

125A

150A

Class 0.5

15

Class 1

20

Class 3

30

200A

30A

40A

250A

300A

50A

60A

MTRKA/EN M/C

Service Manual

Page 42/56

METRIK

Type TA400: Primary current, secondary 1A or 5A:

VA

Size 100mm x 20mm


750A

10

Class 1

15

Class 3

20

1200A

1500A

2000A

Type TA500: Primary current, secondary 1A or 5A:


size 100mm x 30mm
1500A

2000A

1000A

Class 0.5

10

Class 1

15

Class 3

20

2500A

3000A 4000A

Type TA600: Primary current, secondary 1A or 5A:

VA

size 125mm x 60mm


1000A

11.1.3.1

1000A

Class 0.5

VA

11.1.3

800A

1500A 2000A 2500A

3000A

4000A

5000A

Class 0.5

15

20

30

35

40

Class 1

20

30

40

50

60

Class 3

30

40

60

70

80

Technical details
Manufactured to IEC60185

Current transformers

Maximum system voltage

660V

Secondary

1A or 5A

Voltage Isolation

3kv rms for 60 seconds

Overload

1.2In continuously

Thermal current (Ith)

60 x primary current for 1 second

Dynamic current (Idyn)

2.5 x (Ith)

Rated current factor

5 x primary

Case

High Impact polycarbonate

Linearity
The error limits are maintained between the following load values:

For CT with VA > 2.5 between 25 and 100% In

For CT with VA 2.5 between 50 and 100% In

Service Manual

MTRKA/EN M/C

METRIK
11.1.3.2

Page 43/56
Accuracy
Accuracy at other load values is indicated in Table 4 below:
Class

% accuracy at

Phase angle in minutes at

0.1In

0.2In

1In

1.2In

0.1In

0.2In

1In

1.2In

0.5

0.75

0.5

0.5

60

45

30

20

1.0

1.5

120

90

60

60

TABLE 4 : ACCURACY AT LOAD VALUES


11.1.3.3

Order details
We require the following information:
1.

Model type: to suit busbar size

2.

CT ratio

3.

Class/VA: to suit the loading conditions

eg. TA250: 800/5A: Class 0.5, 10VA


11.2

TC SERIES NARROW WIDTH CURRENT TRANSFORMERS

11.2.1

Introduction
The TC Series is a range of moulded case current transformers manufactured to IEC 60185,
the International Electrotechnical Commission Standard which specifies the rating and
performance requirements for CTs to be used with electrical measuring instruments and
protective devices. The TC Series has a narrower profile than the TA range and is only for
use with electrical measuring instruments.

11.2.1.1

Application
In addition to the class accuracy, primary and secondary ratings, when selecting a CT the
aperture size and VA rating must also be determined.

11.2.1.2

Aperature size
The TC series is designed with aperture dimensions that suit the size of busbar for given
primary currents. Table 1 above shows the copper busbar current ratings for different sizes
of busbar according to DIN 43761.

11.2.1.3

VA rating
The VA rating of a CT must be greater than, or equal to, the total VA burden of all the
devices being fed and the connecting cable. In order to select a CT with an appropriate VA
rating, refer to Tables 2 and 3 that show typical device and cable burdens respectively.

11.2.2

CT selection tables
All CTs supplied with full fixing kit and terminal cover as standard. All CTs are available with
either 1A or 5A secondary. Wound primary CTs for lower primary currents are also available
on request.
VA

Type TC050: Primary current, secondary 1A or 5A:


size 25mm x 5mm
40A

50A

60A

75A

100A

125A

150A

200A

250A

Class 0.5

1.5

1.75

2.5

3.75

Class 1

1.25

2.5

3.5

3.5

7.5

Class 3

1.5

3.5

3.5

3.75

7.5

MTRKA/EN M/C

Service Manual

Page 44/56

METRIK
Type TC052: Primary current, secondary 1A or 5A:

VA

size 30mm x 10mm


125A

150A

200A

250A

300A

400A

500A

600A

2.5

3.5

3.5

3.5

Class 1

1.5

3.75

3.75

7.5

Class 3

2.5

3.5

7.5

10

10

Class 0.5

Type TC060: Primary current, secondary 1A or 5A:

VA

size 40mm x 10mm


150A

200A

250A

300A

400A

500A

600A

700A

800A

3.5

7.5

7.5

10

10

Class 1

3.5

7.5

7.5

7.5

10

10

15

15

Class 3

7.5

10

10

10

15

15

20

20

Class 0.5

Type TC062: Primary current, secondary 1A or 5A:

VA

size 30mm x 10mm


100A

125A

150A

200A

250A

300A

400A

500A

600A

Class 0.5

1.75

3.75

7.5

7.5

10

10

15

15

Class 1

3.75

7.5

7.5

10

10

10

10

15

20

Class 3

7.5

10

10

10

15

15

15

20

20

Type TC080: Primary current, secondary 1A or 5A:

VA

size 60mm x 12mm


400A

500A

600A

750A

800A

1000A

1200A

1500A

1600A

7.5

10

15

15

15

15

15

15

Class 1

7.5

10

15

20

20

20

20

20

20

Class 3

15

20

25

25

30

30

30

30

30

Class 0.5

Type TC120: Primary current, secondary 1A or 5A:

VA

11.2.2.1

size 100mm x 50mm


1500A

1600A

2000A

2500A

3000A

4000A

Class 0.5

15

15

15

20

30

35

Class 1

20

20

20

30

40

50

Class 3

30

30

30

40

60

60

Order details
We require the following information:
1.

Model type: to suit busbar size

2.

CT ratio

3.

Class/VA: to suit the loading conditions

eg. TC120: 1500/5A: Class 0.5, 15VA

Service Manual

MTRKA/EN M/C

METRIK

Page 45/56

11.3

TYPE 17x CURRENT TRANSFORMERS

11.3.1

Introduction to type 173


A range of moulded case current transformers suitable for primary currents from 1A to 800A
using cable (24mm circular)or bar (30 mm x 10mm) primaries. They have secondary values
of 1A or 5A.

11.3.2

11.3.3

11.3.4

Features

Transparent terminal covers

Base or busbar mounting

Screw or push on terminals

Technical specification

Conforms to: IEC44-1, IEC185 and BS7626

Rated system voltage: 0.72/3kV

Ambient temperature range: -30 to +80 degrees C

Self extinquishing to UL94V0

Enclosure to IP54

Range
CLASS 3

Primary A

CLASS 1

2.5VA

5VA

1, 2.5

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

5, 7.5

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

10, 15

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

20, 30

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

40

Yes

60

Yes

80

Yes

Yes

100

Yes

Yes

Yes

Yes

150

Yes

Yes

Yes

Yes

Yes

Yes

200

Yes

Yes

Yes

Yes

Yes

Yes

Yes

300

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

400, 500

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

600, 800

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

11.3.5

10VA 15VA 2.5VA

Outline dimensions

5VA

CLASS 0.5

10VA 15VA 2.5VA

5VA

10VA 15VA

MTRKA/EN M/C

Service Manual

Page 46/56
11.3.6

METRIK

Introduction to type 174


A range of moulded case current transformers suitable for primary currents from 200A to
1200A using cable (35mm circular)or bar (40 mm x 10mm) primaries. They have secondary
values of 1A or 5A.

11.3.7

11.3.8

11.3.9

Features

Transparent terminal covers

Base or busbar mounting

Screw or push on terminals

Technical specification

Conforms to: IEC44-1, IEC185 and BS7626

Rated system voltage: 0.72/3kV

Ambient temperature range: -30 to +80 degrees C

Self extinquishing to UL94V0

Enclosure to IP54

Range
CLASS 3

Primary A

2.5VA 5VA

10VA 15VA 2.5VA 5VA

200

Yes

Yes

300

Yes

Yes

Yes

400, 500

Yes

Yes

Yes

600, 800

Yes

Yes

1000,1200

Yes

Yes

11.3.10 Outline dimensions

CLASS 1

CLASS 0.5

10VA 15VA 2.5VA 5VA

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

10VA 15VA

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Service Manual

MTRKA/EN M/C

METRIK

Page 47/56

11.4

RT SPLIT CORE CURRENT TRANSFORMERS

11.4.1

Introduction to type RT
A range of ring type split core current transformers supplied with a 1 metre length flying lead.
They are suitable for primary currents from 100A to 3000A with a standard 5A secondary

11.4.2

11.4.3

11.4.4

Features

Flying leads

Split core allows installation without disconnecting cables

Technical specification

Conforms to: IEC185, BS7626, BSEN600044-1 and IEC 60044-1

Rated system voltage: 0.72/3kV

Ambient temperature range: -30 to +80 degrees C

Frequency range 50 60Hz

Insulation level 3kV for 1 minute

Continuous current 1.2 x rated current

Range and dimensions


Rating

Dimension

Primary
current A

Burden VA

100A

1.5VA

32mm

88mm

12mm

35mm

150A

5VA

32mm

88mm

12mm

35mm

200A

5VA

32mm

88mm

12mm

35mm

300A

5VA

32mm

88mm

12mm

35mm

400A

5VA

45mm

95mm

12mm

30mm

500A

5VA

45mm

95mm

12mm

30mm

600A

5VA

45mm

95mm

12mm

30mm

800A

5VA

65mm

115mm

12mm

25mm

1000A

5VA

65mm

115mm

12mm

25mm

1200A

5VA

85mm

145mm

12mm

30mm

1250A

5VA

85mm

145mm

12mm

30mm

1500A

5VA

85mm

145mm

12mm

30mm

1600A

5VA

85mm

145mm

12mm

30mm

2000A

5VA

105mm

165mm

12mm

30mm

2500A

5VA

105mm

165mm

12mm

30mm

3000A

5VA

105mm

165mm

12mm

30mm

MTRKA/EN M/C
Page 48/56

Service Manual
METRIK

11.4.5

Outline drawing

11.5

RT RING CORE CURRENT TRANSFORMERS

11.5.1

Introduction to type RT
A range of ring type Current transformers suitable for primary currents from 1A to 5000A
with 1A or 5A secondaries. They are supplied with either resin coating or tape wrapped.

11.5.2

11.5.3

Features

Primary current 1A to 5000A

Base or bus bar mounting

Choice of sizes

Technical specification

Conforms to: IEC185, BS7626, and IEC 60044-1

Rated system voltage: 0.72/3kV

Ambient temperature range: -30 to +80 degrees C

Frequency range 50 60Hz

Insulation level 3kV for 1 minute

Continuous current 1.2 x rated current

Short term terminal current Ith 60 x rated current

Service Manual

MTRKA/EN M/C

METRIK
11.5.4

Page 49/56
Measurement
CLASS 3

Primary A

2.5VA 5VA

CLASS 1

10VA 15VA 2.5VA 5VA

CLASS 0.5

10VA 15VA 2.5VA 5VA

10VA 15VA

40

Yes

Yes

50

Yes

Yes

Yes

60

Yes

Yes

Yes

Yes

80

Yes

Yes

Yes

Yes

Yes

100

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

150

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

200

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

300

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

400

Yes

Yes

Yes

500

Yes

Yes

Yes

600

Yes

Yes

Yes

Yes

Yes

Yes

800

Yes

Yes

Yes

1000

Yes

Yes

Yes

1200-1600

Yes

Yes

Yes

2000

Yes

Yes

Yes

3000

Yes

Yes

Yes

4500-5000

Yes

Yes

Yes

11.5.5

Protection
CLASS 5P10
10VA

15VA

CLASS 10P10

Primary A

5VA

20VA

5VA

100

Yes

Yes

120

Yes

Yes

150

Yes

Yes

200

Yes

Yes

300

Yes

400

10VA

15VA

20VA

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

500

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

600

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

800

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

1000

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

1200

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

1600

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

2000-2500

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

3000-5000

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

MTRKA/EN M/C
Page 50/56
11.5.6

Dimensions
Measurement Current Transformers

PROTECTION current transformers

Service Manual
METRIK

Service Manual

MTRKA/EN M/C

METRIK

Page 51/56

11.6

DC SHUNTS

11.6.1

Introduction
Shunts are used to enable measurements of dc currents in ranges from 1A to 15,000A
(depending on the model) and also allow instruments to be located at a safe working
distance. All shunts rated at under 25A are mounted on self extinquishing plastic base or on
a 35mm rail to DIN EN500022 standard.
The shunts comply with EN60051 for measuring dc ammeters and dc power meters to
accuracy class 1, 1.5 or 2.5.

11.6.2

Accuracy
Class 0.2 and 0.5 available to DIN 43703

11.6.3

Range

Current Rating

50mV

60mV

75mV

100mV

150mV

300mV

1, 1.5, 2.5, 4, 6, 10, 15 or 25A

Case 1

Case 1

Case 1

Case 1

Case 1

Case 1

40, 60, 100 or 150A

Case 1

Case 1

Case 1

Case 1

Case 1

Case 1

250, 400, 600 or 1000A

Case 2

Case 2

Case 2

Case 2

Case 2

Case 2

1500A

Case 2

Case 2

Case 2

Case 2

Case 3

Case 3

2000A

Case 2

Case 2

Case 3

Case 3

Case 3

Case 3

2500A

Case 2

Case 2

Case 3

Case 3

Case 3

Case 3

4000A

Case 3

Case 3

Case 3

Case 3

Case 3

Case 3

6000A

Case 3

Case 3

Case 3

Case 3

Case 3

N/a

10000A

Case 3

Case 3

Case 3

Case 3

Case 3

N/a

15000A

Case 3

Case 3

Case 3

Case 3

Case 3

N/a

11.6.4

Outline drawings
Case 1

MTRKA/EN M/C

Service Manual

Page 52/56

METRIK

Case 2

Case 3

11.6.5

Dimensions
Dimensions
A1

A2

B1

B2

B3

C1

C2

Minimum

90

28

20

73

Maximum

385

33

25

365

Minimum

138

28

30

15

48

10

10

98

30

Maximum

450

33

120

30

60

10

10

240

60

Minimum

158

28

90

15

31

15

10

115

60

Maximum

460

33

120

35

30

30

20

410

170

Case 1

Case 2

Case 3

Service Manual

MTRKA/EN M/C

METRIK

Page 53/56

11.7

PHASE SELECTOR SWITCH

11.7.1

Introduction
Series 12 phase selector switches are designed for use in conjunction with indicating
voltmeters, ammeters and their associated current transformers for monitoring voltage or
current in three phase circuits.

11.7.2

11.7.3

11.7.4

Types
Type

Description

12-8151

Measures currents in 3 phase supply lines

12-8351

Measures voltages in 3 phase circuits without neutral

12-8357

Measures voltages in 3 phase circuits with neutral

Accessories

72mm2 DIN legend plates designed to suit

Extended duty lables engraved as required

Features

16A rated

Double break contacts

Semi rapid notch mechanism

Positive switch location

48mm2 bezel to match Standard DIN and Metrik instruments

Legend plates and duty labels

Optional:

11.7.5

Recessed terminals for safety

Switch block sealing to IP40

Technical details
Parameter

Value

Rated operating voltage

600V

Rated operating current

16A

Rated thermal current

20A

Rated short duration (1 sec) current

300A

Mechanical life

1.25 x 108 operations, maximum 150 per hour

Normal operating temperature

-20 to +70 degrees C

Degree of protection

IP40 to IEC60144

Terminals (recessed)

M3.5 screws and U clamp

Terminals (capacity)

Up to 4mm2 solid connectors


Up to 2.5mm2 flexible cable

11.7.6

Standards
Standards: VDE 0660, IEC 60408
Approvals: CSA, UL, Bureau Veritas

MTRKA/EN M/C
Page 54/56
11.7.7

Ordering information
Specify switch type required and any accessories needed.

11.7.8

Outline and dimensions

Service Manual
METRIK

Service Manual
METRIK
11.7.9

MTRKA/EN M/C
Page 55/56

Switch drawings

MTRKA/EN M/C

Service Manual

Page 56/56

METRIK

BLANK PAGE

PXXX
Product Description

Alstom Grid
- ALSTOM 2011. ALSTOM, the ALSTOM
logo and any alternative version thereof are
trademarks and service marks of ALSTOM.
The other names mentioned, registered or
not, are the property of their respective
companies. The technical and other data
contained in this document is provided for
information only. Neither ALSTOM, its officers
or employees accept responsibility for, or
should be taken as making any representation
or warranty (whether express or implied), as
to the accuracy or completeness of such data
or the achievement of any projected
performance criteria where these are
indicated. ALSTOM reserves the right to
revise or change this data at any time without
further notice.