Buchholz relay
Transformer outages have a considerable
economic impact on the operation of a
power supply network. Therefore it is the
aim to ensure an accurate assessment of the
transformer condition.
Partial discharges, leakage currents, hot
spots and arcing are phenomena that
contribute to degradation of oil insulating
performances by generating dangerous gas
flow inside the transformer tank.
BR
Internal gas accumulation and oil flow are monitored and kept under
control by the Buchholz relay.
Thanks to COMEMs proven expertise, we have developed a
reliable Buchholz relay that promptly provide information about
internal malfunctioning giving the possibility to eventually stop
the system prior its destruction.
The Buchholz relay is sited in the pipework between the
transformer and its conservator and it is filled with oil during
normal transformer operation.
When gas is generated in the transformer it rises towards the
conservator and collects in the upper chamber of the relay.
The oil level drops and the top float triggers alarm switch.
Gas shall not freely pass from the relay body and escape into the
pipework before the alarm contact has operated.
Another important functionality of the Buchholz relay is
to operate if oil flow from the transformer tank to the oil
conservator. In case the oil flow speed exceed the pre-set value,
the the flow vent operates and switch the trip contact.
Advantages
Proven on the field reliability
No false alarms
Robust reed switch design
Electrical wiring provided with change-over contacts
Additional accessories: Gas sampling device.
Buchholz relay
(1)
(8)
(9)
Construction
Special features
Installation guidelines
The following table gives guidelines values:
Transformer
Power
MVA
Pipe Nominal
diameter
Volume
of oil
Tons
Up to 5MVA
25
Up to 3,5
From 5 up to 20 MVA
50
From 3,6 up to 14
Over 20 MVA*
80
Over 14,1*
Over 20 MVA*
100
Over 14,1*
Tests
Topic
Type tests
Routine tests
Test description
Standard
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
50216-1
50216-2
50216-1
50216-2
50216-2
50216-2
50216-2
50216-2
50216-1
50216-1
50216-2
50216-2
and EN 50216-2_A1
and
and
and
and
and
EN
EN
EN
EN
EN
50216-2_A1
50216-2_A1
50216-2_A1
50216-2_A1
50216-2_A1
and EN 50216-2_A1
and EN 50216-2_A1
Buchholz relay
Overall dimensions according to EN 50216-2 and EN 50216-2_A1
G1" 1/2 A
BG25
Weight 2.1 Kg
BR25
Weight 2.9 Kg
Buchholz relay
Overall dimensions according to EN 50216-2 and EN 50216-2_A1
BR50
Weight 4.9 Kg
BR80
Weight 5.8 Kg
Buchholz relay
Overall dimensions according to EN 50216-2 and EN 50216-2_A1
BS25
Weight 2.2 Kg
10
BS50
Weight 4.1 Kg
11
Buchholz relay
Overall dimensions according to EN 50216-2 and EN 50216-2_A1
BS80
Weight 4.3 Kg
12
NF25
Weight 3.0 Kg
13
Buchholz relay
Overall dimensions according to EN 50216-2 and EN 50216-2_A1
NF50
Weight 4.8 Kg
14
NF80
Weight 5.5 Kg
15
Buchholz relay
Overall dimensions according to EN 50216-2 and EN 50216-2_A1
C01
Weight 2.2 Kg
16
C1
Weight 2.3 Kg
17
Buchholz relay
Overall dimensions according to EN 50216-2 and EN 50216-2_A1
C4
Weight 5.9 Kg
18
Main features
General data
Material
All the external part are resistant to transformer oils, salt fog and UV rays
Ambient temperature
-40 to 80C
Oil temperature
-40 to 115 C
Degree of protection
Voltage
Current
Breaking capacity
250 W
L/R<40 ms
400 VA
cos>0.5
100-200 cm3
NF50-NF80
100-200 cm3
BR50-BR80-C4
150-250 cm3
BS25
170-230 cm3
BS50-BS80
250-300 cm3
19
Buchholz relay
Wiring diagrams
Diagram type A
- ALARM CONTACT (terminals 3-4)
NO contact
1
Alarm circuit
Trip circuit
Diagram type L
- ALARM CONTACT (terminals 3-4- C2) change over contact
NO contact: terminals 4-C2; NC contact: terminal 3-4
1
C1
C2
Alarm circuit
Trip circuit
Diagram type P
- ALARM CONTACT (terminals C2-3)
NO contact
- ALARM CONTACT (terminals C1-4)
NO contact
C1
C1
Alarm circuit
Trip circuit
20
Diagram type G
- ALARM CONTACT (terminals 3-4)
NO contact
- TRIP CONTACT (terminals C2-2)
NO contact
C2
C1
Alarm circuit
Trip circuit
Diagram type I
- ALARM CONTACT (terminals 5-6)
NO contact
- ALARM CONTACT (terminals 7-8)
NO contact
Trip circuit
Diagram type V
- ALARM CONTACT (terminals 5-6)
NC contact
- ALARM CONTACT (terminals 7-8)
NC contact
Trip circuit
21
Buchholz relay
Gas sampling device
Insulating materials within transformers and electrical equipment
break down to liberate gases. The distribution of these gases
can be related to the type of electrical fault, and the rate of gas
generation can indicate the severity of the fault. The identity
of the gases being generated by a particular unit can be very
useful information in any preventative maintenance program.
22
Construction
Requirement sheet
Number of pieces
BG25
Size and model
Sealing
BR25
BR50
BR80
BR80
8 holes
BS25
BS50
BS80
NF25
NF50
NF80
C01
C1
C4
NBR -40
VITON
Tube 6 mm
Tube 8 mm
Tube 10 mm
23
Gas relay
Distribution transformers have the same
working principle of Power transformers
therefore they are influenced by the same
fault principles. However, their specific
design requires a different approach when
talking about safety devices: COMEM Gas
relay is the right solution for detecting the
internal gas generated by various phenomena
like dielectric failure, slight overload and
degradation of insulating oil.
R1
Gas accumulation is monitored and kept under control by the gas relay.
Ensure air bag functionality within the oil conservator.
Additionally, all kind of transformers may be equipped with
oil conservator air bag (air cushion embedded into the oil
conservator) and it is fundamental to ensure its correct
functioning: thanks to COMEM Gas relay flexibility, it can be used
for promptly detecting unexpected deflation or punching
by stopping the transformer.
24
Working principle
For Distribution transformers, the gas relay is mounted on
the transformer tank.
When gas is generated in the transformer it rises towards the
conservator and collects in the upper chamber of the relay.
The oil level drops and the top float triggers alarm switch.
Gas shall not freely pass from the relay body and escape into
the pipework before the alarm contact has operated.
Alternatively, it is mounted on top of oil conservators and
once there is a sudden air flow from air bag it trips the
transformer.
25
Gas relay
Overall dimensions
R1
Weight 1.9 Kg
26
RF1
Weight 2.2 Kg
27
Gas relay
Main features
General data
Material
All the external part are resistant to transformer oils, salt fog and UV rays
Ambient temperature
-40 to 80C
Oil temperature
-40 to 115 C
Degree of protection
Voltage
Current
Breaking capacity
250 W
L/R<40 ms
400 VA
cos>0.5
Operating pressure - 1 bar, tested to 2,5 bar for 2 minutes at 100 deg C.
75 cm3
Wiring diagrams
Diagram type A
- ALARM CONTACT (terminals 3-4)
NO contact
Diagram type L
- ALARM CONTACT (terminals 3-4- C2) change over contact
NO contact: terminals 4-C2; NC contact: terminal 3-4
C1
28
C2
Alarm circuit
Alarm circuit
Trip circuit
Trip circuit
Requirement sheet
Number of pieces
Sealing
R1
RF1
NBR-40C
VITON
29
Flow relay
The flow Relay is used as a protective device
sensitive to the effects of dielectric failure
inside the energized (on load) tap-changer.
The flow relay detects a failing transformer.
If an arc forms, gas accumulation is rapid,
and oil flows rapidly into the conservator.
This flow of oil operates a switch attached
to a vane located in the path of the moving
oil. This switch normally will operate a circuit
breaker to isolate the apparatus before the
fault causes additional damage.
OR-25 relay
Promptly detect leakages from Energized Tap Changers oil compartment to
the oil conservator.
The relay for OLTC application is positioned in the pipe work
between the on-load tap-changer head and the oil conservator.
This relay responds only if oil flow occurs from the on-load tapchanger head to the oil conservator. If this happens, the flow
vane switches the reed . The circuit breakers are tripped and the
transformer is de-energized.
30
Advantages
- Complete protection for both the energized tap-changer and
the transformer
- Detection of any eventual malfunctioning or failure in the
diverter switch or sector oil compartment
- Transformer trip
31
Flow relay
Overall dimensions
or25
Weight 2.9 Kg
32
Main features
General data
Material
All the external part are resistant to transformer oils, salt fog and UV rays
Ambient temperature
-40 to 80C
Oil temperature
-40 to 115 C
Degree of protection
Voltage
Current
Breaking capacity
24 V DC to 220 V DC
250 W
L/R<40 ms
230 V AC
400 VA
cos>0.5
Tests
Type test:
Relevant
Standard
Routine test
Relevant
Standard
Vibration test
EN
EN
EN
EN
60137-3-4
60068-3-3
50216-2 and EN 50216-2_A1
50216-2 and EN 50216-2_A1
33
Flow relay
Wiring diagrams
Diagram type AO
- TRIP CONTACT (terminals 1-2)
NO contact
00
01
DIAGRAM TYPE AO
DIAGRAM TYPE LO
Diagram type LO
- TRIP CONTACT (terminals 1-2-3) change over contact
DIAGRAM TYPE AO
NO contact: terminals 2-3; NC contact: terminal 1-2
1
00
Diagram type GO
- TRIP CONTACT (terminals 1-2)
DIAGRAM TYPE AO
NO contact
1
01
Trip circuit
02
Codice: 5COR468900
5COR468
01
5COR468
02
5COR468
Trip circuit
03
5COR468
03
Codice: 5COR468901
DIAGRAM TYPE GO
1(14)
2(13)
3(24)
4(23)
Codice: 5COR468900
Trip circuit
Codice: 5COR468901
TIPO
Type
CODICE
p/n
00
5COR468900
011
5COR468901
02
5COR468902
Trip circuit5COR468903
03
Codice: 5COR468902
04
5COR468904
05
5COR468905
4(23)
CODIC
p/n
Codice: 5COR468902
04
Trip circuit
3(24)
00
5COR468
DIAGRAM TYPE VO
05
5COR468
1
06
34
2(13)
TIPO
Type
Trip circuit
Codice: 5COR46890
DIAGRAM TYPE GO
1(14)
02
DIAGRAM TYPE LO
Trip circuit
Codice: 5COR468900
DIAGRAM TYPE LO
01
Trip circuit
00
5COR468
Trip circuit
Codice: 5COR46890
Diagram type VO
- TRIP CONTACT (terminals 1-2)
DIAGRAM TYPE LO
DIAGRAM TYPE AO
NC contact
- 1TRIP2 CONTACT (terminals 3-4)1 2 3
NC contact
03
04
DIAGRAM TYPE GO
DIAGRAM TYPE VO
DIAGRAM TYPE RO
1(14)
01
02
1(14)
3(24)
2(13)
3(24)
03
CODICE
p/n
00
5COR468900
01
5COR468901
02
5COR468902
Trip circuit
02
03
2(13)
3(24)
4(23)
1(12)
1(12)
2(11) 3(14)
Trip circuit
4(13)
00
5COR468900
01
5COR468901
02
5COR468902
Trip circuit
03
5COR468903
Codice: 5COR468902
04
5COR468904
05
5COR468905
Codice: 5COR46
DIAGRAM TYPE CO
4(13)
05
06 ADESIV
PVC BIANCO
Codice: 5COR468904
Materiale
Material
Codice: 5COR46
--
Rives. / Tratt.
Protec. / Treat.
DIAGRAM TYPE CO
Dimensioni in mm
Dimensions in mm
Scala:
Scale:
Data:
Date:
Dimens
NO
11/09/2012
Riferimenti:
References:
Descrizion
Trip circuit
Codice: 5COR468903
Trip circuit
SCH
NUO
Codice: 5COR468904
Materiale
Material
Rives. / Tratt.
Protec. / Treat.
Codice: 5COR4
Codice: 5COR468905
CODICE
p/n
4(13)
Codice: 5COR468903
2(11) 3(14)
05
DIAGRAM TYPE RO
Trip circuit
04
2(11) 3(14)
Trip circuit
Codice: 5COR468903
06 change
5COR468906
- TRIP CONTACT (terminals 3-4-C2)
over contact
NO contact: terminals 4-C2; NC contact: terminal 3-C2
TIPO
Type
1(12)
Codice: 5COR468902
04
04
5COR468904
Diagram type CO
- TRIP CONTACT (terminals
1-2-C1)
change
over contactDIAGRAM TYPE RO
DIAGRAM TYPE VO
DIAGRAM TYPE GO
5COR468905
NO contact: terminals 2-C1; 05
NC contact:
terminal 1-C1
1(14)
Trip circuit
Trip circuit5COR468903
03
Codice: 5COR468901
Codice: 5COR468902
DIAGRAM TYPE VO
4(23)
TIPO
Type
Trip circuit
Codice: 5COR468901
4(23)
Trip circuit
Codice: 5COR468900
Diagram type RO
- TRIP CONTACT (terminals 1-2)
DIAGRAM TYPE GO
DIAGRAM TYPE LO
NC contact
2
2(13)
Trip circuit
02
01
00
Tolleranze Generali
General Tolerances
Dimensioni
Dimensions
<=3
>3
<=6
0.05
>6
<=30
0.1
>30
>120
>400 >1
<=120 <=400 <=1000 <=
35
0.15
0.2
0.3
Wiring
03 diagrams
04
06
05
Diagram type TO
- TRIP
CONTACT
1-2-C1) TYPE
changeRO
over contactDIAGRAM TYPE CO
DIAGRAM
DIAGRAM
TYPE
VO (terminals
NO contact: terminals 2-C1; NC contact: terminal 1-C1
1
1(12)
2(11) 3(14)
4(13)
UGOLIN G.
A
18/09/13
DIAGRAM TYPE TO
Flow relay
Trip circuit
Trip circuit
Trip circuit
Codice: 5COR468904
Trip circuit
Codice: 5COR468906
Codice: 5COR468905
Rives. / Tratt.
Protec. / Treat.
-Tolleranze Generali
General Tolerances
Materiale
Material
Dimensioni in mm
Dimensions in mm
Scala:
Scale:
Data:
Date:
Dimensioni
Dimensions
0.05
0.1
0.2
NO
11/09/2012
>3
<=6
<=3
0.3
>6
<=30
>30
>120
>400 >1000 >2000
<=120 <=400 <=1000 <=2000 <=4000
0.1
0.15
0.2
0.3
0.5
0.2
0.3
0.5
0.8
1.2
0.5
0.8
1.2
36
Modifiche
Alterations
kg
Peso Grezzo
Gross. Wt.
Peso Netto
Net. Wt.
Propriet della COMEM. Senza autorizzazione scritta dalla stessa il presente disegno non potr essere utilizzato per la costruzione
dell'oggetto rappresentato n venire comunicato a terzi o riprodotto. La societ proprietaria tutela i propri diritti a norma di legge.
All property rights of COMEM. This drawing must not be reproduced in any medium nor utilized for the manufacture of the article
herein rapresented or disclosed to other parties without our licence. Any infringement will be legally persecuted.
Riferimenti:
References:
Sost.:
Replaced:
Descrizione Description
Valori
Angolari
30'
Angular
Values
SCHEMI ELETTRICI
NUOVO RELE' OLTC
6
E-4689
Disegn.:
Operat.:
Ramponi E.
5COR468900
7
Codice: 5COR468903
F
Contr.:
Chkd.:
EMESSO
01
Dis. Drwg.
R-4689-01
8
Requirement sheet
Number of pieces
Sealing
OR25
AO
LO
GO
VO
RO
CO
LO
NBR
37
38
39