Вы находитесь на странице: 1из 344

R407C

SERIES
Variable Refrigerant Flow System

Multi Air Conditioning System for Buildings

Model : AO90M

HEAT RECOVERY TYPE

DESIGN & TECHNICAL DATA

CONTENTS
1.GENERAL INFORMATION
1-1 FEATURES OF SYSTEM ......................................................................................

1 - 01

1-2 MODEL LINE UP ....................................................................................................

1 - 07

2.CONTROL SYSTEM
2-1 CONTROL SYSTEM .............................................................................................. 2 - 01
2-1-1 LINE UP OF CONTROLLERS ............................................................................

2 - 01

2-1-2 CONTROL SYSTEM DESIGN .............................................................................

2 - 03

2-1-3 SYSTEM CONFIGURATION EXAMPLES ..........................................................

2 - 04

2-1-4 FEATURES OF CONTROL SYSTEM ..................................................................

2 - 07

2-2 CONTROLLER UNIT.............................................................................................. 2 - 08


2-2-1 WIRED REMOTE CONTROLLER .......................................................................

2 - 09

2-2-2 SIMPLE REMOTE CONTROLLER(with MASTER control button) ...................

2 - 12

2-2-3 SIMPLE REMOTE CONTROLLER(without MASTER control button) ..............

2 - 15

2-2-4 WIRELESS REMOTE CONTROLLER ................................................................

2 - 18

2-2-5 IR RECEIVER UNIT .............................................................................................

2 - 21

2-2-6 COMBINATION OF INDIVIDUAL REMOTE CONTROLLER ...............................

2 - 23

2-2-7 GROUP CONTROL METHOD .............................................................................

2 - 24

2-2-8 GROUP REMOTE CONTROLLER .....................................................................

2 - 26

2-2-9 CENTRAL REMOTE CONTROLLER ..................................................................

2 - 29

2-2-10 PC (Personal Computer) CONTROLLER..........................................................

2 - 33

2-2-11 COMPARISON TABLE OF CONTROLLER ......................................................

2 - 36

2-3 ADAPTOR / CONVERTOR UNIT .........................................................................

2 - 37

2-3-1 NETWORK CONVERTOR(UTR-YRDA) ..............................................................

2 - 38

2-3-2 NETWORK CONVERTOR(UTR-YLLA) ..............................................................

2 - 42

2-3-3 BACnet gateway .................................................................................................

2 - 45

2-3-4 SIGNAL AMPLIFIER............................................................................................

2 - 47

2-3-5 TRANSMISSION ADAPTOR ...............................................................................

2 - 49

2-3-6 EXETERNAL SWITCH CONTROLLER...............................................................

2 - 51

2-4 SERVICE & MONITORING ................................................................................... 2 - 54


2-4-1 SERVICE TOOL...................................................................................................
2-4-2 WEB MONITORING TOOL..................................................................................

2 - 54
2 - 58

CONTENTS
3.OUTDOOR UNITS
3-1 MODEL LINE UP .................................................................................................... 3 - 01
3-2 FEATURE ................................................................................................................ 3 - 02
3-3 SPECIFICATIONS .................................................................................................. 3 - 04
3-4 DIMENSIONS .......................................................................................................... 3 - 05
3-5 INSTALLATION SPACE ....................................................................................... 3 - 06
3-6 REFRIGERANT CIRCUIT ..................................................................................... 3 - 11
3-7 WIRING DIAGRAM ................................................................................................ 3 - 12
3-8 CAPACITY TABLE ................................................................................................. 3 - 13
3-9 SELECTION PROCEDURE .................................................................................. 3 - 16
3-10 REFRIGERANT PIPING LENGTH COMPENSATION CURVE ................... 3 - 18
3-11 OPERATION RANGE .......................................................................................... 3 - 19
3-12 SOUND LEVEL ..................................................................................................... 3 - 20
3-13 ELECTRIC CHARACTERISTICS ...................................................................... 3 - 22
3-14 SAFETY DEVICES SETTING ............................................................................ 3 - 22

4.INDOOR UNITS
4-1 MODEL LINE UP .................................................................................................... 4 - 01
4-2 FEATURE ................................................................................................................ 4 - 02
4-2-1 UNIVERSAL FLOOR / CEILING TYPE ...............................................................

4 - 02

4-2-2 LARGE CEILING TYPE ......................................................................................

4 - 03

4-2-3 COMPACT DUCT TYPE .....................................................................................

4 - 04

4-2-4 DUCT TYPE .........................................................................................................

4 - 05

4-2-5 HIGH STATIC PRESSURE DUCT TYPE ............................................................

4 - 06

4-2-6 COMPACT CASSETTE TYPE .............................................................................

4 - 07

4-2-7 CASSETTE TYPE ...............................................................................................

4 - 09

4-2-8 WALL MOUNTED TYPE .....................................................................................

4 - 13

......................................................................................

4 - 14

4-2-9 CEILING WALL TYPE

4-3 SPECIFICATIONS .................................................................................................. 4 - 15


4-3-1 UNIVERSAL FLOOR / CEILING TYPE ...............................................................

4 - 15

4-3-2 LARGE CEILING TYPE .......................................................................................

4 - 16

4-3-3 COMPACT DUCT TYPE ......................................................................................

4 - 17

4-3-4 DUCT TYPE .........................................................................................................

4 - 18

4-3-5 HIGH STATIC PRESSURE DUCT TYPE .............................................................

4 - 19

4-3-6 COMPACT CASSETTE TYPE .............................................................................

4 - 20

4-3-7 CASSETTE TYPE ................................................................................................

4 - 21

4-3-8 WALL MOUNTED TYPE ......................................................................................

4 - 23

......................................................................................

4 - 24

4-3-9 CEILING WALL TYPE

CONTENTS
4.INDOOR UNITS
4-4 ELECTRIC CHARCTERISTICS ........................................................................... 4 - 26
4-5 DIMENSIONS .......................................................................................................... 4 - 28
4-5-1 UNIVERSAL FLOOR / CEILING TYPE ...............................................................

4 - 28

4-5-2 LARGE CEILING TYPE ......................................................................................

4 - 29

4-5-3 COMPACT DUCT TYPE .....................................................................................

4 - 30

4-5-4 DUCT TYPE .........................................................................................................

4 - 34

4-5-5 HIGH STATIC PRESSURE DUCT TYPE ............................................................

4 - 36

4-5-6 COMPACT CASSETTE TYPE ............................................................................

4 - 37

4-5-7 CASSETTE TYPE ...............................................................................................

4 - 38

4-5-8 WALL MOUNTED TYPE ......................................................................................

4 - 40

......................................................................................

4 - 41

4-5-9 CEILING WALL TYPE

4-6.WIRING DIAGRAMS ............................................................................................. 4 - 42


4-6-1 UNIVERSAL FLOOR / CEILING TYPE ..............................................................

4 - 42

4-6-2 LARGE CEILING TYPE ......................................................................................

4 - 43

4-6-3 COMPACT DUCT TYPE ......................................................................................

4 - 44

4-6-4 DUCT TYPE ......................................................................................................... 4 - 45


4-6-5 HIGH STATIC PRESSURE DUCT TYPE ............................................................

4 - 47

4-6-6 COMPACT CASSETTE TYPE ............................................................................

4 - 48

4-6-7 CASSETTE TYPE ...............................................................................................

4 - 49

4-6-8 WALL MOUNTED TYPE ......................................................................................

4 - 51

......................................................................................

4 - 52

4-6-9 CEILING WALL TYPE

4-7 PIPING DIAGRAM ................................................................................................. 4 - 53


4-8 CAPACITY TABLE COOLING ............................................................................ 4 - 54
4-8-1 UNIVERSAL FLOOR / CEILING TYPE .............................................................. 4 - 54
4-8-2 LARGE CEILING TYPE ....................................................................................... 4 - 55
4-8-3 COMPACT DUCT TYPE ...................................................................................... 4 - 56
4-8-4 DUCT TYPE ......................................................................................................... 4 - 58
4-8-5 HIGH STATIC PRESSURE DUCT TYPE ............................................................. 4 - 59
4-8-6 COMPACT CASSETTE TYPE ............................................................................ 4 - 60
4-8-7 CASSETTE TYPE ............................................................................................... 4 - 62
4-8-8 WALL MOUNTED TYPE ......................................................................................

4 - 64

......................................................................................

4 - 65

4-8-9 CEILING WALL TYPE

CONTENTS
4.INDOOR UNITS
4-9 CAPACITY TABLE HEATING ............................................................................. 4 - 67
4-9-1 UNIVERSAL FLOOR / CEILING TYPE ..............................................................

4 - 67

4-9-2 LARGE CEILING TYPE .....................................................................................

4 - 68

4-9-3 COMPACT DUCT TYPE ....................................................................................

4 - 69

4-9-4 DUCT TYPE ......................................................................................................... 4 - 70


4-9-5 HIGH STATIC PRESSURE DUCT TYPE ............................................................

4 - 71

4-9-6 COMPACT CASSETTE TYPE .............................................................................

4 - 72

4-9-7 CASSETTE TYPE ................................................................................................

4 - 73

4-9-8 WALL MOUNTED TYPE......................................................................................

4 - 75

4-9-9 CEILING WALL TYPE ......................................................................................

4 - 76

4-10 AIR VELOCITY DISTRIBUTION ........................................................................

4 - 78

4-10-1 UNIVERSAL FLOOR / CEILING TYPE .............................................................

4 - 78

4-10-2 LARGE CEILING TYPE .....................................................................................

4 - 84

4-10-3 COMPACT CASSETTE TYPE ..........................................................................

4 - 88

4-10-4 CASSETTE TYPE .............................................................................................

4 - 91

4-10-5 WALL MOUNTED TYPE ...................................................................................

4 - 97

4-10-6 CEILING WALL TYPE .......................................................................................

4 - 100

4-11 FAN PERFORMANCE AND AIR FLOW ..........................................................

4 - 107

4-11-1 FAN CURVE (COMPACT DUCT TYPE) ...........................................................

4 - 107

4-11-2 FAN CURVE (DUCT TYPE) ...............................................................................

4 - 109

4-11-3 CAPACITY BY AIR FLOW (DUCT TYPE).........................................................

4 - 110

4-11-4 OUTLET AIR TEMPERATURE (DUCT TYPE) ..................................................

4 - 111

4-11-5 FAN CURVE (HIGH STATIC PRESSURE DUCT TYPE) ..................................

4 - 112

4-12 FRESH AIR ............................................................................................................

4 - 113

4-13 NOISE LEVEL CURVE ......................................................................................

4 - 117

4-13-1 UNIVERSAL FLOOR / CEILING TYPE .............................................................

4 - 117

4-13-2 LARGE CEILING TYPE ....................................................................................

4 - 118

4-13-3 COMPACT DUCT TYPE ...................................................................................

4 - 119

4-13-4 DUCT TYPE .......................................................................................................

4 - 121

4-13-5 HIGH STATIC PRESSURE DUCT TYPE ..........................................................

4 - 122

4-13-6 COMPACT CASSETTE TYPE ..........................................................................

4 - 123

4-13-7 CASSETTE TYPE .............................................................................................

4 - 125

4-13-8 WALL MOUNTED TYPE ...................................................................................

4 - 127

4-13-9 CEILING WALL TYPE .....................................................................................

4 - 128

4-14 SAFETY DEVICE .................................................................................................

4 - 131

CONTENTS
5.INSTALLTION
5-1 PIPING DESIGN ................................................................................................................ 5 - 01
5-1-1 PIPING METHOD .............................................................................................. 5 - 01
5-1-2 LIMITATIONS ................................................................................................................. 5 - 03
5-1-3 PIPE SIZE ....................................................................................................................... 5 - 04
5-1-4 SELECTION OF PIPE HEAT INSULATING MATERIAL.......................................... 5 - 05
5-1-5 ADDITIONAL CHARGE CALCULATION ................................................................... 5 - 06
5-1-6 EXAMPLE OF PIPING DESIGN .................................................................................. 5 - 07

5-2 WIRING DESIGN .............................................................................................................. 5 - 13


5-2-1 WIRING SPECIFICATION ............................................................................................ 5 - 13
5-2-2 POWER SUPPLY CABLE WIRING ....................................................................................... 5 - 14
5-2-3 TRANSMISSION LINE ................................................................................................. 5 - 15
5-2-4 WIRING SEPARATION ................................................................................................ 5 - 19
5-2-5 WIRING EXAMPLE ............................................................................................... 5 - 21

5-3 SYSTEM SETTING ........................................................................................................... 5 - 22


5-3-1 SYSTEM TYPE SETTING .................................................................................... 5 - 22
5-3-2 ADDRESS SETTING .................................................................................................... 5 - 23

5-4 FUNCTION SETTING ....................................................................................................... 5 - 29


5-4-1 OUTDOOR UNIT ........................................................................................................... 5 - 29
5-4-2 SWITCH FUNCTION (OUTDOOR UNIT) .................................................................. 5 - 30
5-4-3 INDOOR UNIT ................................................................................................................ 5 - 33
5-4-4 SWITCH FUNCTION (INDOOR UNIT) ...................................................................... 5 - 34
5-4-5 WIRED,SIMPLE REMOTE CONTROLLER ................................................................ 5 - 38
5-4-6 DIP - SW FUNCTION (WIRED,SIMPLE REMOTE CONTROLLER) ...................... 5 - 39
5-4-7 GROUP REMOTE CONTROLLER ............................................................................... 5 - 41
5-4-8 SWITCH FUNCTION(GROUP REMOTE CONTROLLER) ...................................... 5 - 41
5-4-9 CENTRAL REMOTE CONTROLLER ......................................................................... 5 - 42
5-4-10 DIP SW FUNCTION (CENTRAL REMOTE CONTROLLER) ................................ 5 - 43

5-5 EXTERNAL INPUT & OUTPUT ............................................................................ 5 - 45


5-5-1 INDOOR UNIT ..................................................................................................... 5 - 45
5-5-2 OUTDOOR UNIT ................................................................................................. 5 - 47
5-5-3 CENTRAL REMOTE CONTROLLER / PC CONTROLLER ................................ 5 - 48

CONTENTS
5.INSTALLTION
5-6 INSTALLATION WORK .................................................................................................. 5 - 50
5-6-1 INSTALLATION THE OUTDOOR UNIT .................................................................. 5 - 50
5-6-2 INSTALLATION SPACE ....................................................................................... 5 - 52
5-6-3 PIPING CONNECTION .................................................................................................. 5 - 56
5-6-4 ELECTRICAL WIRING ................................................................................................. 5 - 68
5-6-5 DRAIN PROCESSING ................................................................................................. 5 - 71
5-6-6 SYSTEM & FUNCTION SETTING ............................................................................... 5 - 78
5-6-7 TEST RUN ...................................................................................................................... 5 - 78

5-7 COMPATIBILITY ............................................................................................................... 5 - 79


5-8 STANDARD ACCESSORIES ....................................................................................... 5 - 81
5-8-1 OUTDOOR UNIT ...................................................................................................... 5 - 81
5-8-2 INDOOR UNIT ...................................................................................................... 5 - 82

5-9 REFRIGERANT LEAKAGE CAUTION ...................................................................... 5 - 87


5-9-1 INTRODUCTION .............................................................................................. 5 - 87
5-9-2 CHECKING CONCENTRATION LIMIT ....................................................................... 5 - 87

6.TROUBLE SHOOTING
6-1 TROUBLE SHOOTING ..........................................................................................

6 - 01

6-1-1 OUTDOOR UNIT ................................................................................................

6 - 01

6-1-2 INDOOR UNIT .....................................................................................................

6 - 03

6-1-3 WIRED,SIMPLE REMOTE CONTROLLER ........................................................

6 - 04

6-1-4 GROUP REMOTE CONTROLLER ......................................................................

6 - 05

6-1-5 CENTRAL REMOTE CONTROLLER / PC CONTROLLER ................................

6 - 07

6-1-6 CASE SUCH AS THESE ARE NORMAL ...........................................................

6 - 08

7.OPTIONAL PARTS
7-1 RB(REFRIGERANT BRANCH) UNIT .................................................................

7 - 01

7-2 SEPARATION TUBE .............................................................................................

7 - 03

7-3 HEADER ..................................................................................................................

7 - 05

7-4 CONTROLLER .......................................................................................................

7 - 07

7-5 ADAPTOR / CONVERTOR ..................................................................................

7 - 08

7-6 OTHERS ..................................................................................................................

7 - 09

R407C

TM

SERIES

1 . GENERAL INFORMATION

GENERAL
INFORMATION

Combining multiple constant speed compressors, Fujitsu General VRF system creates High COP.
This enables to provide the superior energy saving and the top class quiet operation.
Fujitsu General VRF system offers the individual air conditioning system, that allows a design
to provide a higher installation freedom.

FEATURE
(1) Long piping for high rise building

Vertical lift between indoor unit and indoor units


: 15m maximum.
Actual pipe length

: 100m maximum.

Equivalent pipe length

: 120m maximum.

Total pipe length

: 200m maximum.

Height difference : 15m max.

When outdoor unit is located above indoor unit.


When outdoor unit is located below the indoor unit
the height difference is 40m maximum.

Height difference : 50m max.

Vertical lift between outdoor unit and indoor units


: 50m maximum.

Actual pipe length : 100m max.

GENERAL
INFORMATION

1-1 FEATURES OF SYSTEM

.Equivalent pipe length: 120m maximum.


.Total pipe length: 200m maximum.

- (01 - 01) -

GENERAL
INFORMATION

Operating system
Cooling and heating can be performed simultaneously within the same refrigerant circuit.
Energy savings are made by transferring heat between the indoor units when in heat
recovery operation.

Cooling COP
Heating COP

3.0
3.15
(28kW)

The configuration of 3 constant speed


compressors with differing capacities
and power accumulation technology
ensure smooth step changes and
highly efficient operation.

Required capacity

Smooth operation delivering high efficiencies

Comp.1

High
Power accumulation
technology

Comp.2

Flow rate between each step is controlled


by power accumulation technology.

low

High
Operating capacity

Comp.3

Power Accumulation Technology

Diagram

Flow rate to the indoor unit(s) is controlled through


the use of 3 differently rated compressors operating
in a sequential step arrangement.While power
accumulation technology controls the circulating load
of the refrigerant flow between those steps.

Comp.1

Flow of
refrigerant

Comp.2

Power accumulation
technology

Comp.3

(3) Super quiet


Low operation sound level
A jarring noise was considerably reduced by adopting new Bellmouse and fan.
Noise can be reduced by 5dB (A) compared with normal operation by reducing the operating
speed of fan as the outdoor temperature lowers. (DIP-SWITCH setting nesessary)
Furthermore, the noise can be reduced in the low capacity range.

Normal operation mode :


Silent operation mode :

55dB(A)
50dB(A)

(380V)
(380V)

Nomal Operation Mode


Silent Operation Mode

60

Noise Level (dB)

GENERAL
INFORMATION

(2) High energy efficiency system

55
50
45
40

Capacity (HP)

- (01 - 02) -

10

GENERAL
INFORMATION

GENERAL
INFORMATION

(4) Flexibility of layout


Maximum 16 indoor units could be connected (2.15kW )
One outdoor unit can control individually up to 16 indoor units of different type and capacity.

outdoor unit

maximum number of
connectable indoor unit

AO 90

16

capacity ratio of outdoor unit


50 to 130%

Various connectable indoor unit


Various combinations of indoor unit type and capacity 11 types 41 models
ranging from 2.15kW to 17.0kW.
Type
Capacity
(kW)

Model code

17.0

60

14.1

54

12.7

45

10.5
8.8

36
30

7.05

25

6.8

24

5.7

20

5.3

18

4.05

14

3.6

12

2.8

2.15

Cassette Cassette Cassette


(compact)

Duct

(compact)

Duct

(compact)

Duct

Duct

Universal

(High Static Floor/Ceiling


Pressure)

Ceiling

Wall
mounted
(compact)

Wall
Ceiling wall
mounted

Indoor unit

Outdoor unit

Indoor unit

- (01 - 03) -

GENERAL
INFORMATION

height

1,30

-52% wide

depth

width

-31% wide

(5.2kW + 11.2kW x2)

-61% wide

(14.0kW x2)

(7.0kW x4)

Dimensions

height 1,380mm
width 1,300mm
depth
650mm

Easy Installation
Four-direction pipe allows a
variety of installation,
configurations.
Easy installation and pipe
direction setting.

Outdoor unit goes into elevator.

650

1,050

1,500

GENERAL
INFORMATION

Space saving

4
Back

1,300

1
Front

(Unit :mm)

800

2
Bottom

3
Right

Flexible piping
Selectable variation by using separation tube and header.
Outdoor
unit

Separation tube

Header

RB unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

- (01 - 04) -

Indoor
unit

Indoor
unit

Indoor
unit

GENERAL
INFORMATION

GENERAL
INFORMATION

(5) Flexibility of control system


Flexible Design System
A flexible system can be designed as outdoor units, indoor units and controllers
can be connected anywhere within the transmission line wiring connection.
Outdoor unit

Transmission line
(non-polar 2 core)

Indoor unit

Remote controller line

Maximum connectable number per


onetransmission line
Refrigerant system

Central
remote
controller

PC Controller

Indoor units
Outdoor units

100
400
100

Easy wiring
Non-polar 2-core transmission
line prevents erroneous wiring.
Transmission Line

Various control system


By combining each remote controllers of central control and individual control,
it provides wide variety of controls that fit to each customer's used.
Wired / Simple / Wireless remote controllers can be simultaneously used with the same indoor
unit, as the remote controller signal receiver is built into the indoor unit body.

Wired or Simple
Remote Controller

Wired or Wireless
Remote Controller

2 remote controllers
(joint use)

- (01 - 05) -

Central control and individual control

GENERAL
INFORMATION

GENERAL
INFORMATION

(6) High reliability


Recovery operation
Outdoor unit
Even if one or two compressors should fail, the remaining
compressor(s) perform the recovery operation automatically
while generating an alarm and, thus, the system continues
to operate without any interruption.

Comp.1

Comp.2

Indoor unit
Each indoor unit on the transmission line acts as an
independent transmission processor, therefore, even if one
unit fails, the remaining system is not affected.

Comp.3

Oil recovery operation


Oil recovery operation is performed automatically after
fixed operation time to return the oil that has accumulated
inside the refrigerant circuit and indoor unit.

(7) Wide operating range


Outdoor unit operates over an outdoor temperature range
of 52 C to 5 C for cooling and 21 C to 15 C for heating.

50

52 CDB

40

21 CDB

30
20
10
0
-10

5 CDB
Cooling

15 CDB
Heating

(8) Environmentally Friendly


Harmonic-less
Our VRF system don't use inverter to control the refrigerant flow rate, thus hardly does harmonic
current emit. Because the system has no harmful effects on office automation equipment, factory
automation equipment and power distribution facilities, it can be used anywhere, such as in hospital
where the harmonic current emissions are restricted.

No Harmful effects

Office
automation
Power distribution
facilities.
Factory automation

Alternative refrigerant
To protect the earth's environment, alternative refrigerant R407C is used.

(9) Comfortable Operation


Heat Recovery operation
Heat Recovery operation is a cooling/heating free operation system, cooling and heating can be
performed simultaneously in the same refrigerant system according to user needs.
At the moment, The Heat Recovery operation is an extremely superior type that provides a still
greater energy saving effect by moving heat between indoor units that are performing the cooling
and heating operations. This is by having the compressors act like a pump.

- (01 - 06) -

GENERAL
INFORMATION

GENERAL
INFORMATION

1-2. MODEL LINE UP


OUTDOOR UNIT
TYPE

CAPACITY

MODEL

28.0 kW(10HP)

AO 90MPBMF

Maximum Connectable
Indoor unit

TM

Heat recovery type

16

Refrigerant : R407C

Heat recovery type


AO90M

CONTROLLER
TYPE
Wired Remote Controller
Simple Remote Controller

Maximum Connectable
Indoor unit

MODEL
UTB-YUB,UTB-GUB,UTB-TUB
UTB-YPB,UTB-GPB,UTB-TPB

4
4

UTB-YRA,UTB-GRA,UTB-TRA

Wireless Remote Controller UTB-YVB,UTB-GVB

---

Group Remote Controller

UTB-YDB,UTB-GDB

32

Central Remote Controller

UTB-YCA,UTB-GCA

400

PC Controller

UTR-YOTB

400

Individual Control
Wired
Remote Controller

Simple Remote Controller


(With MASTER (Without MASTER
control button)
control button)

Central Control

Wireless
Remote Controller

Group
Remote Controller

SU MO TU WE TH FR SA

7
3 6 9 12 15 18 21

- (01 - 07) -

Central
Remote Controller

PC Controller

GENERAL
INFORMATION

GENERAL
INFORMATION

INDOOR UNIT
11 types, 41 models ranging from 2.15kW to 17.0kW
Type
Capacity
(kW)

Model code

17.0

60

14.1

54

12.7

45

10.5
8.8

36
30

7.05

25

6.8

24

5.7

20

5.3

18

4.05

14

3.6

12

2.8

2.15

Cassette Cassette Cassette


(compact)

Universal Floor / Ceiling


TYPE
AB12
AB14
AB18
AB24

Compact Duct TYPE

Duct

(compact)

Duct

(compact)

Duct

Duct

Universal

(High Static Floor/Ceiling


Pressure)

Ceiling

Wall
mounted
(compact)

Wall
Ceiling wall
mounted

Large Ceiling TYPE

Compact Duct TYPE

AB30
AB36
AB45
AB54

AR 7
AR 9

Duct TYPE

(Low Static Pressure)

Duct TYPE

(Hight Static Pressure)

AR12
AR14
AR18

AR25
AR30
AR36
AR45

AR36H
AR45H
AR60H

Compact Cassette TYPE

Cassette TYPE

Cassette TYPE

AU 7
AU 9
AU12
AU14
AU18

AU20
AU25
AU30

AU36
AU45
AU54

Wall mounted TYPE


AS18
AS24
AS30

Ceiling Wall TYPE

AW7
AW9
AW12
AW14
AW18
AW24
AW30

- (01 - 08) -

Type
Heat recovery

Model

Connectable indoor unit

UTF-Y54A1A

UTF-Y90A4A

SEPARATION TUBE
Type
Heat recovery

Model

Total model code of connectable indoor unit

UTR-BP54MA

Less than 60

UTR-BP90MA

More than 61

HEADER
Type
Heat recovery

Model

Connectable indoor units

UTR-HD906R

UTR-HD908R

ADAPTOR / CONVERTOR
Type

Model

Network
convertor

UTR-YRDA

Features
The equipment for controlling operation of split type/big multi type
air conditioners from transmission line of VRF system.
Control up to 4 group remote controller(8 remote controller groups)
is possible with one group remote controller.

UTR-YLLA

The equipment for connecting our original LONWORKS R to the system


built by LONWORKS R ,to manage mutually between medium and
small-sized BMS and VRF system.

UTR-YLBA

The central control of maximum 1600 indoor units can be realized


by connecting the VRF system to the BACnet R , a global standard
of the open network.

Signal
Amplifier

UTR-YRPC

When the total length of Transmission Line exceeds 500m, or the


number of units exceeds 64 units, Signal Amplifier will be necessary
to use.
The equipment for extend the transmission line up to Max 2000m.

Transmission
adaptor

UTR-YTMA

The equipment for enabling control by other equipment with RS-232C


cable.

External switch
controller

UTR-YESA

The function which enables various kinds of operations by the


point-of-contact input.

Network
convertor
BACnet R
gateway

*LONWORKS is a resistered mark of Echelon Corporation.


R

*BACnet is a registered trademark of the American Society of Heating Refrigeration and


Air Conditioning Engineers (ASHRAE).
R

- (01 - 09) -

GENERAL
INFORMATION

GENERAL
INFORMATION

RB (REFRIGERANT BRANCH) UNIT

Models

Model

Note

Flange (square)

UTD-SF045T For duct type 205 x 1,063, L=40(mm)

Flange (round)

UTD-RF204 For duct type 195 (205),L=85(mm)

Flexible Duct

UTD-RD202 For high static pressure duct type 200,L=2m

Outlet Chamber

UTD-BC200 195(200),L=85 Base size : H x W x D (mm) 297 x 1,066 x 400

Long-life Filter

UTD-LF270

For duct type

Long-life Filter

UTD-LF400

For high static pressure duct type

IR receiver unit

UTB-YWA

Remote Sensor Unit

UTD-RS100

Drain Pump

UTR-DPB241 For ceiling type (AB30 - AB54)

Model

Models
Grille Kit

UTG-UDYD-W

UTG-UDGD-W

- (01 - 10) -

GENERAL
INFORMATION

GENERAL
INFORMATION

OTHERS

R407C

TM

SERIES

2 . CONTROL SYSTEM

2-1. CONTROL SYSTEM


2-1-1. LINE UP OF CONTROLLERS
Installation Work Saving

Control System Configuration Expansion

Simplified wiring and reduced installation cost by


the use of non-polar 2-core transmission line.

Optimum system configuration by various controller combinations, allowing for various applications
and future expansion.

Easy Operation

Free System Configuration

Advanced control functions can be set up with the


easy-to-use setting operation.

Up to 400 indoor units are connectable in one


system. System is adaptable to various applications, from small to large buildings.

Flexible Control System


to Meet a Variety of Needs.

- (02 - 01) -

CONTROL
SYSTEM

CONTROL
SYSTEM

Features of control system

Air Conditioning Individual Control

Air Conditioning Central Control


PC Controller and Central Remote Controller specially designed for centralized control.

A range of Remote Controllers suitable for a wide range of


individual control situations, using various built-in timers

PC Controller

Wired Remote Controller

SU MO TU WE TH FR SA

CONTROL
SYSTEM

CONTROL
SYSTEM

3 6 9 12 15 18 21

UTB-YUB / UTB-GUB / UTB-TUB

The room temperature can be controlled by being detected


the temperature accurately with built-in thermo sensor.
Build-in thermo sensor doesn't work in S series system.

UTR-YOTB [Software]

High performance and optimum control system for various


building applications
A high degree of building air conditioning management is
possible including electricity cost calculation and
numerous data management functions as well as standard
equipment monitoring and control.

Wireless Remote Controller

UTB-YVB / UTB-GVB
(Symbol type)

Central Remote Controller

Simple and sophisticated operations with a choice of


4 daily timers
UTB-YCA / UTB-GCA

Simple Remote Controller


(With MASTER control button)

Functionality in a compact housing with built-in weekly timer


It allows operation and monitoring to be achieved from the
central control room, at each floor, by each tenant, or in the
plant room.

UTB-YPB / UTB-GPB / UTB-TPB

Compact remote controller concentrates on the basic


functions such as On/Off, Fan Control, Temperature
Setting and Operation Mode.

Group Remote Controller

Simple Remote Controller


(Without MASTER control button)

UTB-YDB / UTB-GDB

Group control of indoor units with simple operation

UTB-YRA / UTB-GRA / UTB-TRA

Group remote convertor (UTR-YRDA) is required to


connect group remote controllers to an VRF system.

Compact remote controller concentrates on the basic


functions such as On/Off, Fan Control and Temperature
Setting.

(To be released soon)

Web Monitoring Tool

Building Management System (BMS)

Trouble-shooting is performed by monitoring each air conditioning


unit remotely during periodical system checks.
Internet
Explorer
6.0 or later

The VRF system can be controlled by Building Management


System through LONWORKS or BACnet Gateway.

UTR-YMSA (Software)

UTR-YLBA

Network convertor
UTR-YLLA

System Status
&
Error Information
Remote Side

BACnet gateway

VRF System Side

BACnet

Lighting facilities

LONWORKS

Monitoring & Control


for VRF system

Automatic fire
alarm interface

BMS
console

Security system

Ventilation system

Error notification can be automatically transmitted to up to several


locations by using internet*.
Requires either a dedicated internet connection* or public telephone
line.

Hydraulic systems

*Unchanging global IP address is required.

Parking lot facilities

- (02 - 02) -

2-1-2. CONTROL SYSTEM DESIGN

Advanced Integrated Control System with BMS


Control

Air Conditioning
Central Control

Building Management

Air Conditioning
Individual Control

Connectable to
*1
various sized BMS/BAS

Wired Remote Controller


Network Convertor

System
Outdoor unit

SU MO TU WE TH FR SA

7
3 6 9 12 15 18 21

UTR-YLLA
UTB-YLB
/ UTB-TLB
UTB-YUB/ UTB-GLB
/ UTB-GUB
/ UTB-TUB

BACnetgateway

Wireless Remote Controller


*2

Indoor unit

USB
Adaptor
(Field
supplied)

UTR-YLBA [Software]

PC Controller

UTB-YVB / UTB-GVB
(Symbol type)

Transmission
Adaptor

General-purpose
building control
computer

Simple Remote Controller

(UTR-YTMA)

UTR-YOTB [Software]

Central Remote Controller

Transmission line
(LONWORKS Network)
(UNVT)

Transmission
Adaptor

USB Cable

UTB-YPB / UTB-GPB / UTB-TPB

Simple Remote Controller

(UTR-YTMA)

Transmission line
Interlink Cable

UTB-YCA / UTB-GCA

Group Remote Controller

Remote controller line

UTB-YRA / UTB-GRA / UTB-TRA

Remote controller line


(Single System)

Network
Convertor

Shielded Twist Pair Cable


Remote Controller Line

UTR-YRDA

External Switch Controller


UTB-YDB / UTB-GDB

UTR-YRPC

LONWORKS Network
(SNVT)
UTR-YESA

BACnet / IP

Card-key

Internet or Public
Telephone Line
Additional Cable

Signal
Amplifier

(Field supplied)

Web Monitoring Tool


VRF System Side
(User Side)

Remote Side

(Internet Explorer)

UTR-YMSA (Software)

Transmission
Adaptor
UTR-YTMA

Transmission
Adaptor
UTR-YTMA

Service Tool

Network
Convertor
UTR-YRDA

or
or
USB*3
USB *3
Adaptor
Adaptor
(Field supplied)(Field supplied)
UTR-YSTC [Software]

*1. BMS/BAS: Building Management System / Building Automation System.


Building Management System is supplied by the other vendors.
*2. An XLON USB adaptor is provided. (XLON is a registered trademark of DH electronics company Gmbh.)
*3. U10 USB Network Interface - TP/FT-10 (Echelon corporation)

- (02 - 03) -

Split type /
Big multi type
air conditioner

CONTROL
SYSTEM

CONTROL
SYSTEM

Management / Monitoring

2-1-3 SYSTEM CONFIGURATION EXAMPLES


INDIVIDUAL CONTROL

Up to 4 indoor units can be connected to a single


wired remote controller.
Wired, simple, and wireless remote controllers can be
used simultaneously.
Two remote controller can be connected with a single
indoor unit.

Single control
for private room

Multiple control
for meeting room etc.

CONTROL
SYSTEM

CONTROL
SYSTEM

Wired Remote Controller

Wired Remote Controller


Outdoor units

Up to 4 indoor units

Wireless Remote Controller

Single control
for private room

Up to 4 indoor units can be connected to a single


wireless remote controller.
Wired, simple, and wireless remote controllers can be
used simultaneously.

Multiple control
for meeting room etc.

Wireless Remote Controller


Outdoor units

Up to 4 indoor units

Simple Remote Controller


Up to 4 indoor units can be connected to a single simple remote controller.
Enables easy control of basic functions by the hotel or
office guest.
Two remote controller can be connected with a single
indoor unit.

Single control for guest room

Simple Remote Controller


Outdoor units

Up to 4 indoor units

Simple Remote Controller


Up to 4 indoor units can be connected to a single simple remote controller.
Enables easy control of basic functions by the hotel or
office guest.
Card-key switch can be connected to indoor unit by
external switch controller.
Two remote controller can be connected with a single
indoor unit.

Single control for hotel room with Card-key switch

Ext. SW
Outdoor units controller

Simple Remote Controller (For hotel use)

Card-key

Combination with single or multi type

Single System Connectability


Single system or Big multi system can be connected
to the VRF system and controlled simultaneously
from Central remote controller or PC controller.

Central Remote
Controller

Network Convertor
(UTR-YRDA)
Outdoor units
Wired Remote Controller

- (02 - 04) -

Single type or Big multi


type air conditioner

CENTRAL CONTROL

Up to 8 remote controller groups (32 indoor units) can be connected to a single group remote controller.
Up to 64 groups remote controller (Up to 16 groups remote convertor) can be connected in a single VRF system.
Up to 4 groups remote controller can be connected in a single network convertor (UTR-YRDA).
One network convertor (UTR-YRDA) covers 2 refrigerant circuits.
Office & Hotel building (Small class)
Group Remote Control 1 for office floor

network
convertor

Wireless
Remote
Controller
office room

Outdoor units

1
2
Group Remote
Controller

Wired Remote Controller

Meeting room

Group Remote Control 2 for hotel floor

Wired Remote
Controller
Guest room

Simple Remote Controller

Lobby
Up to 8 remote controller groups (32 indoor units)

Central Remote Controller


Up to 400 indoor units / 64 groups can be connected to a single central remote controller.
Up to 16 central remote controllers can be connected to a single system.
Simple system configuration available using built-in weekly / daily timer.
Commercial building (Small class)

Office floor

Wired Remote
Controller

Wired Remote
Controller

Central Remote
Controller

Tenant floor

Wired Remote
Controller

Up to 100 outdoor units

Office floor

Wireless
Remote
Controller

Wired Remote
Controller

Up to 400 indoor units

- (02 - 05) -

Central Remote
Controller

Lobby
floor

CONTROL
SYSTEM

CONTROL
SYSTEM

Group Remote Controller

PC Controller
Administrator's room

Commercial building (Medium class)


PC Controller

Transmission
Adaptor

Office floor

Office floor

Tenant floor

Tenant floor

Up to 100
outdoor units
Up to 400 indoor units

Combination of Central Remote Controller and PC Controller


The central remote controller and PC controller can be used simultaneously.
Commercial building (Large class)
Floor & total control

Administrator's room

PC Controller

Transmission
Adaptor

Hall floor

Central Remote
Controller

Conference
floor

Tenant floor

Central Remote
Controller

Tenant floor

Up to 100
outdoor units

Lobby floor
Up to 16 central
remote controllers

Up to 400 indoor units

- (02 - 06) -

CONTROL
SYSTEM

CONTROL
SYSTEM

UP to 400 indoor units / 400 groups can be connected to a single PC controller.


Incorporates a function that automatically calculates electrical costs.

1.

Wiring work can be reduced since all equipment making up the system is wired with
only one transmission line (non-polar 2-conductor).

2.

Since each equipment on the transmission line is independently processed, a


system failure at one indoor unit does not affect other equipment.

3.

Total wiring length (total length of transmission line) can be extended up to 2000m
(with signal amplifier unit).

4.

Maximum 400 indoor units can be connected.

5.

Maintenance work efficiency is improved, because PC control system can be connected


to anywhere on the transmission line.

6.

Indoor units can be controlled by Wired, Simple, Wireless, Group, Central remote controller
and PC controller.

7.

When a failure occurs, the error code is displayed and details can be confirmed at
the Wired remote controller,Simple remote controller, Group remote controller,
Central remote controller, or PC controller.

8.

By adopting an interface for FUJITSU GENERAL's single split type models (excluding some
models) or multi air conditioner for Building models, the central control will be available from
the Group remote controller or Central remote controller or PC controller.

9.

Simple remote controller that allows an easy operation is available for the installation
such as a hotel guest room.

10. These components can be freely combined to get the maximum control depending on
the usage of the building

- (02 - 07) -

CONTROL
SYSTEM

CONTROL
SYSTEM

2-1-4 FEATURES OF CONTROL SYSTEM

2-2. CONTROLLER UNIT


The following types of controllers are available with the FUJITSU GENERAL LIMITED VRF System :

Wired remote controller


Simple remote controller

CONTROL
SYSTEM

CONTROL
SYSTEM

(With MASTER control button)


(Without MASTER control button)
Wireless remote controller
IR receiver unit
Group remote controller
Central remote controller
PC controller

Individual Control
Wired
Remote Controller

Simple
Remote Controller
(With MASTER
control button)

Wireless
Remote Controller

IR Receiver
Unit

(Without MASTER
control button)

SU MO TU WE TH FR SA

7
3 6 9 12 15 18 21

Central Control
Group
Remote Controller

Central
Remote Controller

- (02 - 08) -

PC Controller

2-2-1. WIRED REMOTE CONTROLLER


Model : UTB -

UB ( Market region Y or G or T,
Build-in thermo sensor does't work in S Series System. )

CONTROL
SYSTEM

CONTROL
SYSTEM

Various timer setup (ON / OFF / WEEKLY) are possible.


Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)

FEATURES

When setting up a timer, operation mode and a temperature


setup can be changed.

SU MO TU WE TH FR SA

7
3 6 9 12 15 18 21

When a failure occurs,the error code is displayed. (Maximum of 16)


Error indication.(A maximum of 16 error histories are memorizable.)
Up to 4 indoor units can be simultaneously controlled.
Energy saving operation is possible.
Easy installation with a slim shape with no bulge in the back.

High performance and compact size


Three functions are combined in

Wired
remote
controller

Weekly
timer

Setback
timer

Built-in timers
Weekly timer

Setback timer
Possible to set temperature for two time spans and
for each day of the week.

Possible to set ON/OFF time to operate twice each day


of the week.
Easy-to-understand time bar display

SU MO TU WE TH FR SA

SU MO TU WE TH FR SA

Screen
after setup

3 6 9 12 15 18 21

SU MO TU WE TH FR SA

3 6 9 12 15 18 21

3 6 9 12 15 18 21

Setup screen example


(Set from Sunday to Saturday: 12:00 to 15:00, 28 C.)
28C

Setup screen example


(Set to Wednesday: 8:00 to 20:00.)

24C
0

12

15

18

21 Time

12

18

21

Time

15

18

21

Time

At "Weekly timer" + "Set back timer" setup


24

28

24C

24
0

Easy-to-understand operation

Timer
area

28C
12

15

Simple installation

Operation
area

Components are compatible with standard


switch boxes. Flat back construction allows
equipment to be installed wherever it is
needed.

European
switch box

[ Variable timer control ]


The operation/display sections are zoned according to time and operation, enabling variable programming to match application.
- (02 - 09) -

JIS box

FUNCTIONS
1

START/STOP button
Pressed to start and stop operation.

Display

Set Temperature button


Selects the setting temperature.(18-30 C[COOL], 10-30 C[HEAT])

3
2
7
8
9
10

DAY
CLOCK ADJUST

DAY OFF

SET BACK

DELETE

ENERGY
SAVE

THERMO
SENSOR

SET

11
12

Master control button


Selects the operating mode (AUTO, HEAT, FAN, COOL, DRY).

15

3 6 9 12 15 18 21

1
3
4
6
5

13
14

Fan control button


Selects the fan speed (AUTO, LOW, MED, HIGH).

Energy save button


Turns the energy efficient mode on and off.

Thermo sensor button


Selects whether the room temperature is detected at the indoor unit
(remote sensor) or the remote controller.
This function cannot be used with the S series.

Timer mode (CLOCK ADJUST) button


Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER)
Set the current time.

Display panel

Day (DAY OFF) button


Temporarily cancels of one day timer.

16

19 20 18

17

Set back button


Pressed select the set back timer.

SU MO TU WE TH FR SA

10

Set time button


Pressed to select the set back timer.

11

3 6 9 12 15 18 21

Delete button
The schedule of a weekly timer is deleted.

24 25 22 23

21

12

Set button
Sets the date, hour, minute and on-off time.

13

Horizontal air flow direction and swing button


Push for two seconds to change the swing mode.

14

Vertical air flow direction and swing button


Push for two seconds to change the swing mode

15

Operation lamp
Lights during operation and when the timer is on.

SPECIFICATION
Model name
Size [H x W x D (mm)]
Weight (g)

UTB -

16

Timer and clock display

17

Operation mode display

18

Fan speed display

19

Operation lock display

20

Temperature display

21

22

Defrost display
Indicates during the oil recovery and defrosting operation.
Vertical swing display

23

Horizontal swing display

24

Energy save display

25

Thermo sensor display

UB

120 x 120 x 17
160

- (02 - 10) -

CONTROL
SYSTEM

CONTROL
SYSTEM

SU MO TU WE TH FR SA

SYSTEM DIAGRAM
1 remote controller

2 remote controllers
Indoor unit

Master
Remote controller

Slave

Remote controllers

PACKING LIST
Name

Quantity

Wired remote controller

Application

1)

Remote controller cable

For connecting the remote controller


(Exclude some models)

10m
2

Tapping screw (M4 x 16mm)

Binder

Cord clamper

For installing the remote controller


For remote controller and remote
controller cable binding
For installing the remote controller
cable to the indoor unit
For installing the remote controller
cable to the indoor unit

Tapping screw (M4 x 14mm)

1) If necessary , use shielded cable (Field supply) in accordance with the standard of the country.

DIMENSION
30

23

Hole

120

3 6 9 12 15 18 21

4.5

CLOCK ADJUST

DAY OFF

ENERGY
SAVE

SET BACK

THERMO
SENSOR

SET

4.5

DELETE

12.5

DAY

Front view

HoleX2

Side view

HoleX3

Rear view

ELECTRICAL WIRING
1 remote controller

2 remote controllers

Indoor unit

REMOTE
CONTROLLER

1 2 3

Indoor unit

CONNECTION CABLE

1(L)

2(N)

REMOTE
CONTROLLER

G
G

1 2 3
G

1 2 3

1(L)

1 2 3
G

2(N)

1 2 3
G

Master
Remote controller

CONNECTION CABLE

Slave

Remote controllers
- (02 - 11) -

1 (RED) : 12V
2 (WHITE) : Signal
3 (BLACK) : COM

83.5

63.5

SU MO TU WE TH FR SA

4.5

45.3

17

33.5

15.3

[ Unit : mm ]

120

120

CONTROL
SYSTEM

A , B , C : Remote controller cable. Refer to 5-2-1


for detail specification.
A < 500m ; B+C < 500m

CONTROL
SYSTEM

Indoor unit

2-2-2.SIMPLE REMOTE CONTROLLER


Model : UTB -

(With MASTER control button)

PB ( Market region Y or G or T )

CONTROL
SYSTEM

Easy operation.
Built-in Back ground Light function.
Easy installation with a slim shape with no bulge in the back.
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 4 indoor units can be simultaneously controlled.
Can be installed onto SW-BOX. (applies to European and
other country's standard)

Easy operation
Concentrates on the basic operations such as On/Off, Fan Control, Operation Mode Switching,
and Temperature Setting.
A large Start/Stop button is provided in the centre of the remote controller unit for easy operation.
Background light enables easy operation in a darkened room.
Diagnostics are carried out during the stop mode following an error display.

Back ground light


Backlight enables easy operation in a darkened room.
The backlight is lit during the button operations, and also 10 seconds more
in operation mode and 5 seconds more in stop mode.

Simple installation work


Can be mounted on the European mounting Box (installation dimension: 60mm) or
the JIS Built-in Box (installation dimension: 83.5mm).

60mm

83.5mm

European
switch box

JIS box

- (02 - 12) -

CONTROL
SYSTEM

FEATURES

FUNCTION
1

START/STOP button
Pressed to start and stop operation

Display background light


Lights during operation.
Lights during operation.

2
4

Fan control button


Selects the fan speed (AUTO

1
4

Operation lamp

, HIGH

,MED

,LOW

).

Set temperature button


Selects the setting temperature.(18-30 C[COOL], 16-30 C[HEAT])

Master control button

Selects the operating mode(AUTO

,COOL

,DRY

,FAN

,HEAT ).

Standby display
Indicates during the oil recovery and defrosting operation.

Power source display


Indicates the main power ON.

Central control display


Indicates when function is locked from central remote controller
or PC controller.

Display panel

10
7

11

13

Fan speed display


Set temperature
Indicates Error history number. *2)
Indicates Indoor unit address. *3)

12
10

11

13

Operation mode display


(Upper) Indicates the error code *1) *2) / the refrigerant
system address. *3)
(Lower) Indicates the remote controller address. *1) *2) *
*1) during self Diagnosis mode.
*2) during Error code history display mode.
*3) during address display mode.

12

SPECIFICATION
Model name

UTB -

PB

120 x 75 x 14

Size [H x W x D (mm)]
Weight ( g )

90

SYSTEM DIAGRAM
1 remote controller

2 remote controllers

Indoor unit

Indoor unit

Master
Remote controller

A , B , C : Remote controller cable. Refer to 5-2-1


for detail specification.
A < 500m ; B+C < 500m

Slave

Remote controllers

PACKING LIST
Name

Quantity

Simple remote controller

1)

Remote controller cable

Application

10m

Tapping screw(M4x16mm)

Binder

For connecting the remote controller


(Exclude some models)
For installing the remote controller
For remote controller and remote
controller cable binding

1) If necessary , use shielded cable (Field supply) in accordance with the standard of the country.

- (02 - 13) -

CONTROL
SYSTEM

CONTROL
SYSTEM

DIMENSION
[ Unit : mm ]
75
49
39

14

11

CONTROL
SYSTEM

CONTROL
SYSTEM

18

hole x 2

60

120

23.5

47.5

4.5

83.5

12.5

hole x 2

Front View

Rear View

ELECTRICAL WIRING
1 remote controller

2 remote controllers

CONTROL
SYSTEM

Indoor unit

REMOTE
CONTROLLER

1 2 3

Indoor unit

CONNECTION CABLE

1(L)

2(N)

REMOTE
CONTROLLER

G
G

1 2 3
G

1 2 3

1(L)

1 2 3
G

2(N)

1 2 3
G

Master
Remote controller

CONNECTION CABLE

Slave

Remote controllers

- (02 - 14) -

1 (RED) : 12V
2 (WHITE) : Signal
3 (BLACK) : COM

2-2-3.SIMPLE REMOTE CONTROLLER


Model : UTB -

(Without MASTER control button)

RA ( Market region Y or G or T )

CONTROL
SYSTEM

FEATURES

Easy operation.
Built-in Back Light function.
Easy installation with a slim shape with no bulge in the back.
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 4 indoor units can be simultaneously controlled.
Can be installed onto SW-BOX. (applies to European and
other country's standard)
Concentrates on the basic operations such as On/Off, Fan Control,
and Temperature Setting.

Easy operation
Concentrates on the basic operations such as On/Off, Fan Control and Temperature Setting.
A large Start/Stop button is provided in the centre of the remote controller unit for easy operation.
Background light enables easy operation in a darkened room.
Diagnostics are carried out during the stop mode following an error display.

Back ground light


Backlight enables easy operation in a darkened room.
The backlight is lit during the button operations, and also 10 seconds more
in operation mode and 5 seconds more in stop mode.

Simple installation work


Can be mounted on the European mounting Box (installation dimension: 60mm) or
the JIS Built-in Box (installation dimension: 83.5mm).

60mm

83.5mm

European
switch box

JIS box

- (02 - 15) -

CONTROL
SYSTEM

A part of the function is limited. It is recommended to use it together


with other type controller.

FUNCTIONS
1

START/STOP button

Display background light

Pressed to start and stop operation


Lights during operation.

Operation lamp

CONTROL
SYSTEM

Lights during operation.


2

Selects the fan speed (AUTO

1
5

Fan control button

, HIGH

,MED

,LOW

).

Set temperature button

CONTROL
SYSTEM

Selects the setting temperature.(18-30 C[COOL], 16-30 C[HEAT])

5
6

Standby display
Indicates during the oil recovery and defrosting operation.

Power source display


Indicates the main power ON.

Central control display


Indicates when function is locked from central remote controller
or PC controller.

9
10

Display panel

Fan speed display


Set temperature
Indicates Error history number. *2)
Indicates Indoor unit address. *3)

12

11
12

Operation mode display


(Upper) Indicates the error code *1) *2) / the refrigerant
system address. *3)(Lower) Indicates the remote controller addre

10

*1) during self Diagnosis mode.


*2) during Error code history display mode.
*3) during address display mode.

11

SPECIFICATION
Model name
Size [H x W x D (mm)]

120 x 75 x 14

Weight ( g )

90

UTB -

RA

SYSTEM DIAGRAM
1 remote controller

2 remote controllers

Indoor unit

Indoor unit

Master
Remote controller

A , B , C : Remote controller cable. Refer to 5-2-1


for detail specification.
A < 500m ; B+C < 500m

Slave

Remote controllers

PACKING LIST
Name

Quantity

Simple remote controller

1)

Remote controller cable

Application

10m

Tapping screw(M4x16mm)

Binder

For connecting the remote controller


(Exclude some models)
For installing the remote controller
For remote controller and remote
controller cable binding

1) If necessary , use shielded cable (Field supply) in accordance with the standard of the country.

- (02 - 16) -

DIMENSION
[ Unit : mm ]

75
49
39

14

11

CONTROL
SYSTEM

CONTROL
SYSTEM

18

hole x 2

60

120

23.5

47.5

4.5

83.5

12.5

Front View

hole x 2

Rear View

ELECTRICAL WIRING
1 remote controller

2 remote controllers

Indoor unit

REMOTE
CONTROLLER

1 2 3

Indoor unit

CONNECTION CABLE

1(L)

2(N)

REMOTE
CONTROLLER

G
G

1 2 3
G

1 2 3

1(L)

1 2 3
G

2(N)

1 2 3
G

Master
Remote controller

CONNECTION CABLE

Slave

Remote controllers

- (02 - 17) -

1 (RED) : 12V
2 (WHITE) : Signal
3 (BLACK) : COM

2-2-4. WIRELESS REMOTE CONTROLLER


Model : UTB -

VB ( Market region Y or G )

Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible.
Four kinds of timers. Easy operation.
Up to 4 indoor units connected to the remote controller group can be
simultaneously controlled.
Can be used jointly with Wired remote controllers .
Easy to change transmission code (4 patterns) by button operation.

Built-in timers
Select from four different timer programs (On/Off/Program/Sleep).

Program timer
The program timer operates the ON and OFF timer once within a 24 hour period.

Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to
the time setting to prevent excessive cooling and heating while sleeping.
Cooling operation/dry operation

Heating operation

When the sleep timer is set, the set temperature


automatically rises 1C every hour. The set
temperature can rise up to a maximum of 2C.

When the sleep timer is set, the set temperature


automatically drops 1C every 30 minutes. The
set temperature can drop to a maximum of 4C.
1C

Timer setting

60min.

2C

3C

4C

30min.
60min.
2C

1C

90min.
Timer setting

Simple operation
After code change
Mixed-up

Code selector switch eliminates unit


being wrongly switched.
(Up to 4 codes can be set.)

1. Press the MASTER CONTROL


button for more than five seconds
to start the code change.

Wide and precise


transmitting range.

2. Press the (+) or (-) button to


select the desired code.
A
B
C
D
3. Press the MASTER CONTROL
button again to end the code
change.

Note : Timer setting from a wireless remote controller becomes invaild, if the indoor unit is connected with
a wired or a simple remote controller.

- (02 - 18) -

CONTROL
SYSTEM

CONTROL
SYSTEM

FEATURES

FUNCTIONS
5
4

START/STOP button
Pressed to start and stop operation

Display

Set temp./Set time buttons/Set remote controller


custom code buttons

4
11

10

, HEAT

Sleep timer button


Pressed to select sleep timer.

1
8

Master control button/Code change


Selects the operating mode (AUTO , COOL , DRY ,FAN
Start/end R.C. custom code change. (Max. 4 types)

CONTROL
SYSTEM

CONTROL
SYSTEM

Sets the indoor temp.(From 18-30 C [Cool] , 16-30 C [Heat] )


Sets the current time and on-off time
Sets R.C. custom code

Signal transmitter

Timer button
Pressed to select the timer mode. (OFF TIMER, ON TIMER,
PROGRAM TIMER, TIMER RESET)

Fan control button


Selects the fan speed (AUTO

TEST
RUN

12

Battery compartment lid

Air flow direction button

, HIGH

,MED

Used to set the desired air flow direction & swing function.
10

Time adjust button


Sets the current time.

11

ACL button
Used when replacing batteries or change the code.

12

Test run button


Used when testing the air conditioner after installation.

Display panel
13

Transmit indicator

14

Clock display

15

Master control display

16

Timer mode display

17

Fan speed display

18

Set temperature display

19

Timer set indicator

20

Temperature set indicator

13

14

16

17

18
15

,LOW

19
20

- (02 - 19) -

).

).

SPECIFICATION
UTB -

Model name
Size [H x W x D (mm)]

158 x 56 x 20
70
CONTROL
SYSTEM

Weight (g)

SYSTEM DIAGRAM

Signal receiver
window

Control signal might not be recognized in following cases:


(i) A curtain or a wall, etc. exists between transmitter and receiver.
(ii) There is an instant-start type (inverter type, etc.) fluorescent lamp in the room.

Signal transmitter

Air conditioner might not work correctly when strong light hits the signal receiver
window. Shut off the direct sunlight and also make illuminator far away from the
receiver window.

PACKING LIST
Name

Quantity

Remote controller

Remote controller holder

Tapping screw

Battery

DIMENSION

[ Unit : mm ]

Controller

Holder

158.0

CONTROL
SYSTEM

VB

20.0

Front view

Side view

Bottom view

- (02 - 20) -

Side view

56.0

Front view

2-2-5. IR RECEIVER UNIT


Model : UTB - YWA
[Unit : mm]

CONTROL
SYSTEM

CONTROL
SYSTEM

FEATURES

Duct type indoor unit can be controlled with wireless remote controller
if the IR receiver unit is used.

DIMENSION
8.5

11.5

18.5

13.6

7.2

7.2

FUNCTIONS

OPERATION LAMP
TIMER LAMP
MANUAL AUTO
SIGNAL RECEIVER

- (02 - 21) -

118.4

17

72.4

83
.5

145

60

57.6

22.9

90

13.6

57.4

ATTACHMENT RANGE
5m

CONTROL
SYSTEM

CONTROL
SYSTEM

5m

SIGNAL ANGLE

120
120

5m

5m

WIRING
Control box cover
Indoor unit

60mm x 120mm hole

Connection cable B (L = 5m, Shielded)


(optional parts)

Connection cable A (L = 5m)


(Connected to CN13 of PCB)

OPTIONAL PARTS

STANDARD ACCESSORIES
Name

Please use the parts number shown below to order


the cable from your sales representative.
Select shielded type conncetion cable in accordance
with the standard of the country.

Quantity

Holder (PCB)

PCB assy

Bracket (Holder)

Holder cover

Screw

Connection cable A (5m)

Parts name
Connection cable B

- (02 - 22) -

Type

Parts No.

Shielded

9707370010

2-2-6.COMBINATION OF INDIVIDUAL REMOTE CONTROLLER

CONTROL
SYSTEM

CONTROL
SYSTEM

Wired, wireless and simple remote controllers can be used jointly in


the following combinations.

(Up to 4 indoor units)

Wired or Simple
Remote Controller

Wireless Remote
Controller

Wireless Remote
Controller
Wired or Simple
Remote Controller

Combination of "

Wired Remote
Controller

"+"

"

Wireless Remote
Controller

Timer function cannot be used by wireless remote controller by setting,


combination,

- (02 - 23) -

2-2-7. GROUP CONTROL METHOD

Remote controller group.


Group.

CONTROL
SYSTEM

CONTROL
SYSTEM

"Group" is defined as one indoor unit (remote controller group) or


a combination of two or more indoor units (remote controller groups).
Group formation consists of two or more groups.

REMOTE CONTROLLER GROUP


Example of minimum indoor unit combination for "Remote controller group"

without
remote
controller

wired
remote
controller

2 remote
controllers

wired
wireless
remote controller remote controller
group
group

Up to 4 indoor units can be connected.

remote controller
remote controller
group
group
+
+
2 remote controllers 2 remote controllers
(joint use)

NOTICE
Setting that extends into the refrigerant system is impossible.
for example)
Pipe
Refrigerant
system 1
Pipe
Refrigerant
system 2

- (02 - 24) -

GROUP
This function is used when operating a multiple number of remote controller group at one time from the
central remote controller or PC controller.

CONTROL
SYSTEM

CONTROL
SYSTEM

Example of "Group"

Refrigerant
system1

Refrigerant
system2
"Group" is possible
with only one indoor unit

Overlapped "Group"
is possible

C
Operation of either A group or B group is possible.
Simulataneous operation of A group and B group is possible.
(Last setting has priority)
As shown in drawing "C","Group" spanning
the refrigerant system is possible.
It is very convenient that PC controller can assign the
title on each group.

- (02 - 25) -

2-2-8.GROUP REMOTE CONTROLLER


Model : UTB -

DB ( Market region Y or G or T )

FEATURES

CONTROL
SYSTEM

The optional group remote convertor (Model name: UTR-YRDA) allows up to


4 Group Remote Controllers to be incorporated within the control layout.
This flexibility is ideal for a number of different building sizes, types and
applications.
On/off, operation mode, set temperature, timer control and air flow can be
controlled/monitored centrally or individually.
Easy installation with a slim shape with no bulge in the back.
One-touch ON/OFF operation of each indoor unit is possible. All the indoor
units can also be easily operated by pressing an ALL ON, ALL OFF, or
ALL TIMER ON/OFF button.

High performance and compact size


ON/OFF, operating mode, set temperature and air flow can be controlled / monitored centrally or individually.
Central
control

ON/OFF
control

Weekly
timer

Built-in weekly timers


The WEEKLY TIMER is provided as a
standard function.
1. The timer can be set up for up to 4 times/day.
(On/Off, operating mode, set temperature)
2. Allows separate settings for each day of the week.

Example : Office

ON
OFF

Weekly schedule
Day
off

Day
off

Sun Mon Tue Wed Thu

Fri

Sat

Operation :
Mon,Wed,Fri : 8:00~12:00 and 13:00~18:00
Tue,Thu : 8:00~12:00
Sat,Sun : Off

System 1

Group
remote
convertor

ON/OFF control

Power

temp.

8:00

18:00 time

12:0013:00

Mode/Temperature control

28 C
25 C

Heating
8:00

Cooling

12:0013:00

System 2

4F
Group
remote
controller

Kitchen

Dining
Room

Living
Room

Bath
Room

Private
Room 1

Private
Room 2

Bed
Room 1

Bed
Room 2

Kitchen
Private
Room 1

Dining
Room

Living
Room

Bath
Room

Kitchen

Private
Room 2

Bed
Room 1

Bed
Room 2

Private
Room 1

3F
Kitchen

Dining
Room

Living
Room

Bath
Room

Private
Room 1

Private
Room 2

Bed
Room 1

Bed
Room 2

Dining
Room

Living
Room

Bath
Room

Private
Room 2

Bed
Room 1

Bed
Room 2

Tenant A

Tenant B

2F
Kitchen

Dining
Room

Living
Room

Bath
Room

Private
Room 1

Private
Room 2

Bed
Room 1

Bed
Room 2

Kitchen
Private
Room 1

GF

BF

Dining
Room

Living
Room

Bath
Room

Kitchen

Private
Room 2

Bed
Room 1

Bed
Room 2

Private
Room 1

C
Kitchen

Dining
Room

Living
Room

Bath
Room

Private
Room 1

Private
Room 2

Bed
Room 1

Bed
Room 2

Dining
Room

Living
Room

Bath
Room

Private
Room 2

Bed
Room 1

Bed
Room 2

Tenant C

Tenant D

Control Room

Possible to control the building air conditioning by floor.


Remote controller line can extend up to 100m in length.

Possible to control the air conditioning system


between several floors and by tenant if required.

- (02 - 26) -

18:00 time

CONTROL
SYSTEM

Control and monitoring of up to 8 units (remote controller group Max32


indoor unit) is possible with one group remote controller.
Up to 64 group remote controllers can be connected in one VRF system.

FUNCTIONS
Indoor units operation
display, control

TIMER and Clock


Display and setting

Operation Lock Display

Day Display

Operation Lamp

Timer and
Clock Display

Timer Mode Display

Fan Speed Display


Temperature Display
Operation Mode Display
All ON

All Timer Mode

All OFF

Timer Mode
(DELETE) Button

Start/Stop Button
Select Button

DAY Button

Set Time Button

Fan Control Button

PROGRAM
(CLOCK ADJUST) Button

Master Control Button

ENTER Button

Set Temperature Button

SPECIFICATION
Group remote controller (UTB - DB)
Size [H x W x D (mm) ]
Weight

120 x 120 x 17
160

(g)

PACKING LIST

Group remote controller (UTB - DB)


Name

Quantity

Group remote controller

Label

Tapping screw(M4x16mm)

Binder

Application
Use this for writing the names of the indoor
units that have been registered.

For installing the remote controller


For remote controller and remote
controller cable binding

- (02 - 27) -

CONTROL
SYSTEM

CONTROL
SYSTEM

Transmitting
Setting Display

DIMENSION
[ Unit : mm ]

33.5
CONTROL
SYSTEM

23

4.5

Hole

63.5

4.5

12.5

120

4.5

83.5

17

45.3

CONTROL
SYSTEM

120

15.3

30

HoleX3

Name plate
(84 x 21)

HoleX2

Rear View

Front View

ELECTRICAL WIRING
Transmission
Line
Transmission
Line
SWITCH

Group
Remote
Controller

1.12V
2.Signal
3.COM
1

2 3

FUSE (3A)

1 50 Hz
220-240V

G
E

Power Supply

TRANSMISSION

1 2 3

1 2 3

Remote Controller Line


RC

UNIT

NETWORK CONVERTOR

Group remote controller cable


(Field supply) cross-section 0.33 mm2
Polar 3 - core,Shield.

- (02 - 28) -

2-2-9.CENTRAL REMOTE CONTROLLER

CONTROL
SYSTEM

CA ( Market region Y or G )

CONTROL
SYSTEM

Model : UTB -

FEATURES
One remote controller can control up to 400 indoor units/64 groups.
Up to 16 central remote controllers can be connected in one VRF system.
Central remote controller can control the system by all/group/individual.
The selectable functions (all functions, timer mode,operating mode,temperature
setting, filter reset, and On / Off) of the standard controller can be locked by
central remote controller.
Weekly timer is equipped as standard function. (2 times On / Off per day for one week).
Setting contents of central remote controller are all memorized, so that each indoor unit
can be operated under the memorized conditions even if the operating conditions are
changed later on.
Error code is displayed when an error occurs.
The history of failures can also be displayed, which is convenient for maintenance.
Examples of errors:
1. Microcomputer communication error
2. Heat exchanger thermistor error
3. Outdoor unit thermistor error
4. Discharge temperature error
5. Compressor error
6. Model information error
7. Indoor unit fan error
8. Room temperature thermistor error

9. Power supply frequency abnormal


10. Reverse phase blocker error
11. Pressure error
12. Pressure sensor error

- (02 - 29) -

FUNCTIONS
Display
33

1
2

31

SUN MON TUE WED THU FRI SAT

MONITOR MEMORY SETTING ERROR TEST

30

CLOCK AM
ADDRESS PM

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19

20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39

29

NON STOP AM
OFF ON PM
TIMER AM

40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59

60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79

28

WEEKLY

CENTRAL CONTROL

FILTER
ZONE

ALL

ON
OFF
OFF

PM
NEXT DAY

27

x100

ON OFF

80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99

ALL/GROUP

ON

SELECT

ALL

TEMP
F
C

AUTO

ENERGY
SAVE
ON OFF

OPERATION LOUVER

AUTO
COOL
DRY
FAN
HEAT

3
4

FIXED
ANTI
FREEZE
ON OFF

ON OFF

DEFROST

OFF

X100

MASTER
CONTROL

26
25

CLOCK
ADJUST
TIMER
MODE

DAY

24

TIMER
COPY

DAY OFF

TIME

TIMER
DELETE

MEMORY
OPERATION

CENTRAL
CONTROL

TIMER
SET

MEMORY
SETTING

GROUP
SETTING

BACK

ZONE

ENERGY
SAVE

DELETE

FILTER
RESET

ON OFF

TEMP.

FAN
CONTROL

7
8

ANTI
FREEZE

SET

CHECK

CONTROL
SYSTEM

CONTROL
SYSTEM

32

TEST

23 22 21 20 19 18 17 16 15 14 13 12 11 10

1
2
3
4
5
6
7
8
16
17
18
19
20
21
22
23
24
25
26
27
28

All ON/OFF button


All ON/OFF LED
Back button
Zone button
Energy save button
Fan control button
Master control button
Anti freeze button

Horizontal Air flow direction and swing button


Vertical air flow direction and swing button
11 Temp button
Indoor temperature setting.
9

10

12

ON/OFF button
Filter reset button
14 Delete button
15 Test button

Starts energy save operation.

Set button
Set LED
Check button
Group setting button
Memory setting button
Timer set button
Time button
Day off button
Timer copy button
Timer mode button
Clock adjust button
Day button
Timer delete button

ON/OFF setting.

13

Deletion of setting.

Transmits of all changed setting details.


Blinks when transmission is necessary.
Confirmation of address display and error code.
Setting of group of a remote controller group connected to the central remote controller.
Memorizes the entire setting contents.
Sets date, hour, minute and on-off time.
On-off time setting.
Temporary cancellation of one day timer.
Copies the timer condition (the day before).
Changes the timer mode (NON STOP, OFF, ON1, ON2, WEEKLY).

29

Memory operation button


Central button
31 All/Group button
32 Select 100 button
33 Select button
30

Operates the memorized condition.


Inhibits some operations of the individual remote controller.
Changes the control unit (ALL GROUP R.C.GROUP).
Remote controller group indication by hundreds.
Changes remote controller group or group number.

Display panel
37

36

34

35

SUN MON TUE WED THU FRI SAT

MONITOR MEMORY SETTING ERROR TEST

CENTRAL CONTROL

ALL

52

CLOCK AM
ADDRESS PM

NON STOP AM
OFF ON PM
TIMER AM
1

WEEKLY

51
34
35
36
37
38
39

ON
OFF
OFF

PM
NEXT DAY

FILTER
ZONE

ON OFF

TEMP
F
C

AUTO

43
AUTO
COOL
DRY
FAN
HEAT

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19

20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39

40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59

60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79

ANTI
OPERATION LOUVER FREEZE

x100

80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99

DEFROST

50

Day of week display


Status display
Transmit indicator display
Central control display
Filter reset display
Zone display

38 39 40 41 42

49

Temperature display
Energy save display
42 Fan control display
43 Master control display
44 Fixed cooling or heating
operation display

ENERGY
SAVE
ON OFF

40

45
46
47
48
49
50

Anti freeze display


Defrost display
Air flow direction display
ON/OFF display
Group control display
ON/OFF time display

- (02 - 30) -

ON OFF

ON OFF

48

41

FIXED

47
51
52

44
45

46

Timer mode display


Clock and address
display

DIMENSIONS
Control panel

22

Front View

Rear View

Transmission adaptor

107

100

FIXING HOLE PITCH

100

243

272
288

WIRING SPECIFICATION
Use

Size
Maximum
Minimum

Power supply cable (mm 2 )


Transmission cable (mm 2 )
Fuse capacity (A)

Wire type

Remarks

1.25
0.5

H07RN-F or equivalent

1 2 wire 50Hz 220-240V *

0.33

shielded Level 4
22AWG (0.65mm)

Non-polar,One twisted pair,


Solid core diameter 0.65mm

*The ground wire is not included in this cord.Always ground the unit.

SPECIFICATIONS
Transmission adaptor

Control panel

50-60Hz 220-240V

POWER SUPPLY

4.8 W

POWER CONSUMPTION
SIZE (H x W x D mm)

143 x 296 x 22

107 x 288 x 100

550

1300

WEIGHT (g)

PACKING LIST
Parts Name

Piece

Parts Name

Piece

Controll Panel

Tapping Screw ( M4 x 6mm)

Transmisshon Adaptor

Wood Screw ( M4 x 20mm)

Connection Cord

Bushing ( 16mm)

Binder (Push Mount)

Bushing ( 20mm)

Binder (Small)

Cover

Tapping Screw ( M4 x10mm)

Tooth Washer

- (02 - 31) -

CONTROL
SYSTEM

Control section

90

CONTROL
SYSTEM

143

296

INSTALLATION

107

143

Transmission Line

10

Transmission
adaptor

Control
panel
296

22

There are 2 ways of set up.


One body set up

Separated set up
Setting Example
Transmission
adaptor

Control panel
and transmission
adaptor together

Setting Example

Behind ceiling

Control panel and


transmission adaptor
separately

Possible to extend
up to 5m.(Max)
(optional service parts)

Control panel

Wall
Make a hole in Wall
277
272
248-253

90

112-120

Square hole in wall

OPTIONAL SERVICE PARTS


5-meters extension cord (service parts) is required
when installing the control panel transmission adaptor separately
Please use the part number shown below to order
the extension cord from your sales representative

Control panel
Position of pilot holes for tapping screw (2 locations)

Name and shape

5-meter extension cord

For mounting the control panel.


Mounting position of wood screws (4 locations)
For mounting the transmission adaptor

- (02 - 32) -

Q'ty

Parts NO

9704270016

CONTROL
SYSTEM

288

Connection cable

CONTROL
SYSTEM

Power Supply
220-240V
(Use a 3A or more fuse)

2-2-10. PC (Personal Computer) CONTROLLER


MODEL : UTR-YOTB
FEATURE
Detailed settings can be programmed for each whole building/group/remote
controller group or individual indoor units.
The PC and central remote controller can be used together to permit system
control from two or more locations, if required.

CONTROL
SYSTEM

CONTROL
SYSTEM

(1) Central building monitoring and control

(2) Central control


Any of 6 standard controller function sets can be locked to permit access from the
PC only: all functions, timer mode, operating mode, temperature setting, filter reset,
on/off. Or the system can be set to allow control from the PC Controller only.
Operation Control

(3) Auto mode (Priority-mode changer)


Auto mode function automatically switches between cooling and heating
modes based on the temperatures set and the room temperature detected
by the master indoor unit.
Other operating indoor units can be operated in the same operating mode.

(4) User-friendly operation

Runs under Windows 2000 and Windows XP Professional / Home so is as easy to use as a standard PC.
Operational status can be color-coded for instant recognition: On/green, Off/red, test/orange, error/flashing.
,
Operational status can be displayed according to user s preference.

Rotating 3-D Display

Floor Layout Display

List Table Display

When monitoring and controlling


the operations by whole building.

When monitoring and controlling


the operations by each floor or group.

When monitoring and controlling


each unit in detail.

(5) Calculating electrical costs


Total electrical costs, billed for multiple indoor connected to the charge meter for air conditioning, is apportioned according to the
accumulated refrigerant time and indoor unit capacity.
Allows accounting for special rates (e.g., for night or weekend use).
Calculations can be printed as final bills.

Electric bill

Bill

Block(Tenant) A

M
Meter

ELECTRICITY
COMPANY

Input data
Apportioned
charges

Block(Tenant) B
PC controller

Block(Tenant) C

BUILDING

- (02 - 33) -

(6) Schedule control


Annual schedules can be set for each remote controller group.
Start/stop, operating status, remote controller prohibition, and temperature
settings can be recorded up to 72 times per day at 10 minute intervals for up
to 6 configurations for each remote controller group.
Allows programming of special settings for holidays, including public holidays,
for a complete year.
Standard 6 functions are available by schedule control.

Schedule Control

(7) Error display


Audible alarms are accompanied by explanatory text. Up to 100 alarms can be recorded for each piece of equipment, this is
particularly useful during maintenance.

Error Warning

(8) Operating record


The operating status of indoor units and accumulated operating time of outdoor units can be logged and a daily or monthly report
produced.

Operation Record

(9) Pattern setting


Recognizes patterns of use, including ON/OFF, operating mode, and set temperature.
An arbitrarily pattern operation can be done with just one button clicking.

COMPOSITION
PC(Personal Computer)

Transmission Line

Inter link cable

Power supply
50Hz 220-240V

CD-ROM

Software protection
key(for USB)

- (02 - 34) -

CONTROL
SYSTEM

CONTROL
SYSTEM

Settings can be made for periods straddling midnight.

STANDARD PARTS

CD-ROM

CONTROL
SYSTEM

CONTROL
SYSTEM

TRANSMISSION ADAPTOR

Software protection key


Personal Computer and Inter link cable must be procured at the site.

PERSONAL COMPUTER SPECIFICATION


The following equipment is required for using PC controller AT compatible machine that
runs on Microsoft R Windows.R

PC (Personal Computer) CONTROLLER [ UTR - YOTB ]


CPU
Hard Drive

TM

Intel Pentium / Celeron ,AMD Athlon /Duron

TM

1GHz or higher

4GB or more of free space is required

Memory

256MB or more

Display

1024 X 768 dots or more, High color ( 16bit ) or more


Requires that the internal graphics accelerator be compatible
with Microsoft DirectX 7.0 or later

Intrerface

Requires Serial port and USB port

Microsoft R Windows R 2000 ( English language version )


Service Pack 3 or later
Operarating System
Microsoft R Windows R XP ( English language version )
Service Pack 1 or later
R

Required Software Adobe Acrobat

reader 4.0 or later

Inter Link cable


(Serial D-sub 9 pin)

Name and shapes

Q'ty

Parts No.

Inter Link cable

KRS-L09-4K

GND

GND

2
3

2
3

D-sub 9 pin
female

D-sub 9 pin
female

- (02 - 35) -

2-2-11.COMPARISON TABLE OF CONTROLLER

Max. controllable indoor units

Wired
remote
controller

Wireless
remote
controller

1
4

1
4

2
14
5

Simple
remote
controller

Simple
remote
controller

With master
control button

Without master
control button

1
4

1
4

Group
remote
controller

Central
remote
controller

PC
controller

8
32

400
400
64

400
400
400

2
14

2
14

72
504

10

10

10

Max. controllable groups


On / Off

Airconditioning control function

Operation mode setting


Fan speed setting
Room temp. setting
Test operation
Up/down air direction flap setting
Right/left air direction flap setting

Save operation
Auto restart

Address display
Group setting
Failure

Display

Defrosting
Current time
Day of week
R.C. prohibition
Cooling/Heating priority
On/Off timer
Weekly timer

Timer

Sleep timer
Program timer
On/Off per day
On/Off per week
Day off
Minuit unit of timer setting
Status monitoring system
Electricity charge calculation
Error history

1 Auto restart can be set by DIP switch on PCB inside of indoor unit.

- (02 - 36) -

CONTROL
SYSTEM

Max. controllable remote controller groups

Control

CONTROL
SYSTEM

Table 1 List of Controller Functions

2-3.ADAPTOR / CONVERTOR UNIT


The following types of convertors and adaptors are available with the FUJITSU
GENERAL LIMITED VRF system.

Split type systems can be controlled from a central remote controller or PC controller
by connecting it to the VRF's network convertor.
Control up to 4 group remote controller(8 remote controller groups) is possible with
one group remote controller.

Network convertor (UTR-YLLA)


For connection between our LONWORKS R system and a LONWORKS R open network
for the management of a small to medium-sized BMS and VRF system.

BACnet gateway (UTR-YLBA)


The central control of maximum 1600 indoor units can be realized by connecting the
VRF system to the BACnet, a global standard of the open network

Signal amplifier (UTR-YRPC)


If the total length of Transmission Line exceeds 500m, or the number of units exceeds
64 units, Signal Amplifier will be necessary to use.

Transmission adaptor (UTR-YTMA)


For the air condition of the medium and large size building, the control software can
control and monitor the air conditioners together with the ones in the other buildings.

External switch controller (UTR-YESA)


The function which enables various kinds of operations by the point-of-contact input.

- (02 - 37) -

CONTROL
SYSTEM

CONTROL
SYSTEM

Network convertor (UTR-YRDA)

2-3-1.NETWORK CONVERTOR
Model : UTR - YRDA

SPLIT SYSTEM CONVERTOR

CONTROL
SYSTEM

With this Network convertor, single split type, big multi type and J series
air conditioners can be controlled by Central remote / PC controller in VRF
system or by wired remote controller connected to the Network convertor.
ON/OFF, operation mode, temperature setting, fan speed, etc.
can be done with these controller.
Up to 4 single units can be connected to and controlled with one
Network convertor.
2 wired remote controllers are possible for one Network convertor.
Up to 100 units of Network convertor can be connected in one VRF
transmission system. (One Network convertor is regarded as one
refrigerant system. The total refrigerant systems in one VRF
transmission system must be within 100.)

APPLICABLE MODEL
1 There is inadaptable model in old type.Contact the authorized

J series
Big Multi
type

sales company for confirmation of these models.

Simultanuous model

Individual model
Single Split Wired RC model 1
type
Wireless RC model
Window type

2 Indoor units which can be controlled from a network convertor are

denoted by 'L' , 'U' or 'F' as the controller method (remote controller),


except the following models.
AR 7RLB , AR 9RLB , AR 12RLB , AR 14RLB , AR 18RLB ,
AR 18RLBH , AR 9ALA , AR 9ALB , AR 18ALBH , AR 7ELA ,
AR 9ELA , AR 12ELA , AR 14ELA , AR 18ELA.

SYSTEM OUTLINE

Single Split
System

Group of Single Split System

Big Multi system

VRF system

VRF
Outdoor unit

Outdoor unit for


big multi

Outdoor unit for


single system

Wired remote 3
Transmission line
controller
(non-polar 2-conductor)

FUNCTION
ON / OFF
MASTER CONTROL
FAN CONTROL

Indoor unit

Remote
controller line

Central remote
controller

3 When connecting an indoor unit that has an 'L' control method, connect the remote
controller for VRF (UTB - L , UTB - U , UTB - R
and UTB - P )
to control from a wired remote controller. Do not connect the wired remote controller
included with the indoor unit.

Network
convertor

TEMPERATURE CONTROL
TIMER SETTING
CENTRAL CONTROL (Lock the remote controller functions)
- (02 - 38) -

CONTROL
SYSTEM

FEATURES

DIMENSIONS
63

91

11 GROMMET

17 GROMMET

CONTROL
SYSTEM

95 (Hole pitch)

211

95 (Hole pitch)

CONTROL
SYSTEM

2 - 5
For M4x20L screws

241.6
272 (Hole pitch)
288

4 - 5
For M4x20L
screws

67

SPECIFICATION
POWER SUPPLY
POWER CONSUMPTION

50-60Hz

220-240V
8.5W

SIZE (H X W X D) (mm)

67 X 288 X 211

WEIGHT (g)

1500

ELECTRICAL WIRING
Transmission Line to VRF System

Transmission Line to VRF System

Wired Remote Controller

SU MO TU WE TH FR SA

150 Hz
220-240V

FUSE (3A)

3 6 9 12 15 18 21

SWITCH

Indoor Unit

1 2 3

TRANSMISSION

Power Supply

1 2 3

Remote Controller Line


RC

UNIT

NETWORK CONVERTOR

*Do not bind the power cable and remote controller cable
to avoid an erroneous operation.
**Use shield cable for transmission line and remote controller
line. The shield metal should be grounded.

RC line
to RC
RC line to
indoor unit

Power
supply

***Use ground wire to ground the Network convertor.

Transmission
line

WIRING SPECIFICATION
Use
Power supply cable (mm 2 )

Size
Maximum
Minimum

Wire type
1.25
0.5

Remarks

H07RN-F or equivalent

1 2 wire 50Hz 220-240V *


2 wire + Ground

Transmission cable (mm 2 )

0.33

shielded Level 4
22AWG (0.65mm)

Non-polar,One twisted pair,


Solid core diameter 0.65mm

Remote controller cable (mm2 )

0.33

shield cable
22AWG (0.65mm)

Polar 3-core

Fuse capacity (A)

*Always ground the unit.


- (02 - 39) -

GROUP REMOTE CONVERTOR


DIMENSIONS
63

CONTROL
SYSTEM

17 GROMMET

CONTROL
SYSTEM

91

11 GROMMET

95 (Hole pitch)

211

95 (Hole pitch)

2 - 5
For M4x20L screws

241.6
272 (Hole pitch)
288

4 - 5
For M4x20L
screws

67

SPECIFICATION
POWER SUPPLY
POWER CONSUMPTION (W)

50-60Hz

220-240V
6.5

SIZE (H X W X D) (mm)

67 X 288 X 211

WEIGHT (g)

1500

ELECTRICAL WIRING (example 1)


Transmission Line
to VRF System

150 Hz
220-240V

FUSE (3A)

Maximum length Maximum length


25m
25m

SWITCH

Group Remote Controller


(The maximum connection is four sets.)

Transmission Line
to VRF System

Power Supply

1 2 3

TRANSMISSION

1 2 3

Remote Controller Line


RC

UNIT

GROUP REMOTE CONVERTOR

*Do not bind the power cable and remote controller cable
to avoid an erroneous operation.
**Use shield cable for transmission line and remote controller
line. The shield metal should be grounded.

RC line
to RC
RC line to
indoor unit

***Use ground wire to ground the Group remote convertor.


Transmission
line

Power
supply

- (02 - 40) -

ELECTRICAL WIRING (example 2)

Maximum
length 25m

150 Hz
220-240V

Group Remote Controller


(The maximum connection is four sets.)

Transmission Line
to VRF System

Maximum Maximum Maximum


length 25m length 25m length 25m

FUSE (3A)
SWITCH

1 2 3

TRANSMISSION

Power Supply

1 2 3

Remote Controller Line


RC

UNIT

GROUP REMOTE CONVERTOR

*Do not bind the power cable and remote controller cable
to avoid an erroneous operation.
**Use shield cable for transmission line and remote controller
line. The shield metal should be grounded.
***Use ground wire to ground the Group remote convertor.
RC line to RC

Power supply

Transmission line

WIRING SPECIFICATION
Use
Power supply cable (mm 2 )

Size
Maximum
Minimum

Transmission cable (mm 2 )

0.33

Remote controller cable (mm2 )

0.33

Fuse capacity (A)

Wire type
1.25
0.5

Remarks

H07RN-F or equiv

1 2 wire 50Hz 220-240V *

shielded Level 4
22AWG (0.65mm)
shield cable
22AWG (0.65mm)

Non-polar,One twisted pair,


Solid core diameter 0.65mm

*The ground wire is not included in this cord.Always ground the unit.

- (02 - 41) -

Polar 3-core

CONTROL
SYSTEM

CONTROL
SYSTEM

Transmission Line
to VRF System

2-3-2.NETWORK CONVERTOR
Model : UTR - YLLA

FEATURES
The convertor for connecting VRF system Network to the system built by LONWORKS R network,

Up to 128 Indoor units can be connected to 1 unit of


Network Convertor.
By using UTR-YLLA , VRF system can be centrally controlled or
monitored from BMS which has LONWORKS R interface.

Network
convertor
(UTR-YLLA)

SYSTEM OUTLINE

Router

(field suply)

Maximum 128 units

VRF Network

General-purpose building
control computer
(LONWORKS device)
R

LONWORKS
Network

VRF system

Network
convertor
(UTR-YLLA)
Lighting
facilities

Maximum 128 units

Router

Security
system

Router

Automatic fire
alarm interface

Router

Ventilation
system

Router

VRF Network

Router

VRF system
VRF
Outdoor unit

Indoor unit

VRF Network

FUNCTION (Example)
Control
(LONWORKS R Network VRF Network)
Operation (ON / OFF)
Operation Mode Setting
Temperature Setting
Fan Speed Setting
R.C.prohibition
(Lock the remote controller functions)

Monitor infomation
(LONWORKS R Network VRF Network)
Operation Condition (ON / OFF)
Operation Mode
Set Temperature
Fan Speed
Error Display
Central Control Display
(Lock the remote controller functions)

- (02 - 42) -

CONTROL
SYSTEM

CONTROL
SYSTEM

to manage mutually between BMS and VRF system.

DIMENSIONS
63

91

17 GROMMET

CONTROL
SYSTEM
211

95 (Hole pitch)

2 - 5
For M4x20L screws

95 (Hole pitch)

CONTROL
SYSTEM

11 GROMMET

4 - 5
For M4x20L
screws

241.6
272 (Hole pitch)
288

67

SPECIFICATION
Main specification
POWER SUPPLY
POWER CONSUMPTION (W)
SIZE (H X W X D) (mm)

50-60Hz

220-240V

4.5W
67 X 288 X 211

WEIGHT (g)

1500

Transmission specification
BMS SIDE

Transmission speed
Transceiver
Transmission way form
Termined resistor

78kbps
FTT-10A
Free topology
None
(It attaches at the terminal of a network.)

- (02 - 43) -

ELECTRICAL WIRING
FUSE (3A)
Transmission Line to
R
LONWORKS Network

SWITCH

1
2
E
TRANSMISSION

POWER

Transmission Line to
VRF System Network

LON

1
2
E
TRANSMISSION

VRF

TRANSMISSION

UNIT

NETWORK CONVERTOR

UNIT

Transmission Line

CONTROL
SYSTEM

CONTROL
SYSTEM

150 Hz
220-240V

*Do not bind the power cable and remote controller cable
to avoid an erroneous operation.
**Use shield cable for transmission line. The shield metal
should be grounded.
Power supply

***Use ground wire to ground the Network convertor.

Transmission line to
LONWORKS Network
R

Transmission line
to VRF System Network

WIRING SPECIFICATION
Use

Size
Maximum
Minimum

Power supply cable (mm )


2

Transmission cable (mm 2 )

Wire type
1.25
0.5

0.33

Fuse capacity (A)

Remarks

H07RN-F or equivalent

1 2 wire 50Hz 220-240V *

shielded Level 4
22AWG (0.65mm)

Non-polar,One twisted pair,


Solid core diameter 0.65mm

*The ground wire is not included in this cord.Always ground the unit.

PACKING LIST
The following installation parts are supplied. Use them as required.
Name/Illustration
Network
convertor

Qty.

Application

Name/Illustration

Qty.

CD-ROM
1

Binder (Push Mount)


3
Wood screw ( 4 x20)
4

Application
For initial setting.

1
For mounting the power
supply cord, and transmission cord.

Connector cable

For initial setting.


1

For mounting the network


convertor.

- (02 - 44) -

2-3-3.BACnet gateway
Model : UTR - YLBA

FEATURES

ANSI / ASHRAE Standards 135-2001 BACnet Application Specific Controller (B-ASC)


BACnet / IP over Ethernet

CONTROL
SYSTEM

CONTROL
SYSTEM

The central control of maximum 1600 indoor units can be realized by connecting the VRF system
to the BACnet , a global standard of the open network.

BACnet gateway run on Micrsoft Windows 2000 / XP.


It can be connected up to 4 systems (400 indoor units for 1 system) for 1 gateway.
It can be corresponded to the large-scale buildings and hotels etc.

SYSTEM OUTLINE
BACnet Operator
Workstation

Outdoor
unit

Indoor unit

VRF system 1

USB Adaptor
(Field supplied)

Indoor unit

VRF system 2

BACnet

Outdoor
unit

USB Adaptor

Lighting
facilities

BACnet Gateway

Security
system

(UTR-YLBA)

Automatic fire
alarm interface

(Max. 4 systems)

USB Adaptor

Ventilation
system

CD-ROM
Software
(Software) protection Key

= BACnet corresponding interface of


each company

USB Adaptor

VRF Network

USB

Ethernet

FUNCTION (Example)
Control (BMS Network VRF Network)
Operation (ON / OFF)
Operation Mode Setting
Temperature Setting
Fan Speed Setting
R.C. prohibition Setting
(Lock the remote controller functions)

Monitor infomation (BMS Network VRF Network)


Operation Condition (ON / OFF)
Operation Mode
Set Temperature
Fan Speed
Error Display
Central Control Display
(Lock the remote controller functions)

- (02 - 45) -

STANDARD PARTS

Software Protection key


Personal Computer and Serial cable must be procured at the site.

PERSONAL COMPUTER SPECIFICATION


BACnet Gateway (UTR-YLBA)
CPU

AT compatible machine that runs on Microsoft Windows


Pentium 400MHz or higher

Memory

256MB or more

Display

1024 X 768 dots or more

Intrerface

LAN (10BASE-T / 100BASE-TX)


USB 1.1
*The power supply of 100mA / 5VDC is necessary for one USB adaptor.

Microsoft Windows 2000 ( English language version )


Service Pack 3 or later
Operarating System
Microsoft Windows XP ( English language version )
Service Pack 1 or later
Personal Computer (Field supplied)
Required Hardware USB Adaptor (DH electronics XLON USB USB4-WM-FTT) (Field supplied)
* 1 adaptor is necessary for 1 VRF system.
Required Software Adobe Acrobat

reader 4.0 or later

- (02 - 46) -

CONTROL
SYSTEM

CONTROL
SYSTEM

CD-ROM

2-3-4.SIGNAL AMPLIFIER
Model : UTR - YRPC

FEATURES
By using this unit, it can connect the following number
of each units,
(1) Transmission Line
(2) Connectable Units

: Max. 2000m
: Max. Indoor Unit : 400 units
Outdoor Unit : 100 units
Central Remote Controller : 16 units
Signal Amplifier : 8 units

* Standard can connect up to 500m of Transmission Line


and 64 units of connecting units.

SYSTEM OUTLINE
Up to 64 units

Network Segment

500m

Signal Amplifier
9
1

Up to 64 units
3

Network Segment

500m

Signal Amplifier
Up to 64 units

9
1

Network Segment

Each network segment must be within


Total wiring length of transmission line : 500m
A number of units : 64
The number of total control unit [Central remote controller, PC controller,
Network convertor (UTR-YLLA) and BACnet gateway] : Max 2
The number of terminal resistor : 1
Note:
1) 22AWG Level 4 cable with shielded(National Electrical Manufacturers Association (NEMA) )
**differs from the Category 4 specification proposed by the Electronic Industries Association/
Telecommunication Industry Association (EIA/TIA)**
2) Unit means indoor unit, outdoor unit, signal amplifier, central remote controller, PC controller and so on.

- (02 - 47) -

CONTROL
SYSTEM

CONTROL
SYSTEM

If the total length of Transmission Line exceeds 500m, or the number of units exceeds 64
units, Signal Amplifier will be necessary to use.

DIMENSIONS
63

91

11 GROMMET

17 GROMMET

CONTROL
SYSTEM

95 (Hole pitch)

211

95 (Hole pitch)

CONTROL
SYSTEM

2 - 5
For M4x20L screws

241.6
272 (Hole pitch)
288

4 - 5
For M4x20L
screws

67

SPECIFICATION
Main specification
POWER SUPPLY
POWER CONSUMPTION

50-60Hz

220-240V

4.5W

SIZE (H X W X D) (mm)

67 X 288 X 211

WEIGHT (g)

1500

ELECTRICAL WIRING
150 Hz
220-240V

FUSE (3A)
SWITCH

1
2
E
TRANSMISSION

UNIT

Network
Segment A

POWER

Network
Segment B

1
2
E
TRANSMISSION

TRANSMISSION

SIGNAL AMPLIFIER

Transmission Line

TERMINAL
RESISTOR*

UNIT

* Make sure to install 1peace of Terminal Resistor to each 1 Network segment.


It is provided to each Outdoor unit, but please remove it if there is a multiple number
of Outdoor units in the one Network segment.

- (02 - 48) -

2-3-5.TRANSMISSION ADAPTOR
Model : UTR - YTMA

FEATURES
CONTROL
SYSTEM

CONTROL
SYSTEM

For the air condition of the medium and large size building, the control software can control
and monitor the air conditioners together with the ones in the other buildings.

Up to 400 Indoor units / 100 Outdoor units can be connected to


1 Network Convertor.

SYSTEM EXAMPLE
Web
monitoring tool

Transmission adaptor

VRF system

RS-232C

VRF
Outdoor unit

- (02 - 49) -

Indoor unit

Transmission line
(non-polar 2-conductor)

CONTROL
SYSTEM

CONTROL
SYSTEM

DIMENSIONS

90

106.6

243

100

277

SPECIFICATION
POWER SUPPLY
POWER CONSUMPTION

50-60Hz

220-240V
2.9W
3A

FUSE CAPACITY
SIZE (H x W x D) (mm)

100 x 288 x 110

WEIGHT (g)

1300

ELECTRICAL WIRING

1 2 E
Power
Terminal
Connector
CN4

12
E
Trans
mission
Terminal

Fuse
(3A)

Switch

150Hz
220-240V

POWER SUPPLY CORD

TRANSMISSION
ADAPTOR

- (02 - 50) -

2-3-6.EXTERNAL SWITCH CONTROLLER (UTR-YESA)


FEATURES
CONTROL
SYSTEM

ON/OFF, Temperature, Fan speed and Operating mode can be switched by a


combination with Card-key switch equipped in facilities such as hotel room.
Card-key or other sensor switches are available as a field supplied parts.

SYSTEM DIAGRAM
A

shorter than 50m


External 1)
input cable

SW

shorter than 25m


External switch
Remote
2)
controller
controller cable

Indoor Unit

B + C < 500m
Remote
3)
controller cable

Remote controller

1) External input cable : Field supply. Refer to 5-2-1 for detail specification.
2) Remote controller cable : Field supply. Refer to 5-2-1 for detail specification.
3) Remote controller cable : Refer to 5-2-1 for detail specification.

PACKING LIST
Name

Quantity

Application

External switch controller

Tapping screw(M4x16mm)

For installing the external switch controller

Binder

For external switch controller and


cable binding

DIMENSION
30
7x5

75

60

83.5

19.5 19.5
19.5
19.5
21

120

21

18

Left view

Front view

Rear view

- (02 - 51) -

(Unit: mm)

CONTROL
SYSTEM

Air conditioner switching can be controlled byconnecting other sensor switches.

ELECTRICAL WIRING

CONTROL
SYSTEM

CONTROL
SYSTEM

Connection to external contacts


Voltage
External contact 1
SW1
SW2

External contact 2

COM

Terminal

H level input (VIH) : 8 to 24 (V).


L level input (VIL) : <
= 4 (V).
Input current (IIH) : <
= 2.5 (mA) (VIH = 24V).
Since this device has a non-isolated input, isolation
shall be performed at the controller side.

External switch controller

No voltage

CONTROL
SYSTEM

SW1
SW2

External contact 1
External contact 2

Open circuit voltage : 12 (V) +


- 2 (V).
Short circuit current : <
2
(mA).
=
Short circuit detection resistance (RON) :
Open circuit detection resistance (ROFF) :

<
= 1 (kilo-ohm).
>
= 50 (kilo-ohm).

COM
Terminal

External switch controller

Example
Application
When
controlling the
individual
operation
states with two
external
contact

Setting
MODE0
P1: Arbitrary
operation state
Contact OFF ON
P2: Arbitrary
operation state
Contact OFF ON
Others setting are
arbitrary.

Wiring

Operation example
P1 : ON, COOL, 26C P2 : OFF

Indoor
unit
External
SW controller
External
contact 1
External
contact 2

- (02 - 52) -

SW1 ON
OFF

P1

SW2 ON
OFF
Operation state
OFF

P2
ON
COOL
26 C

Example

When
controlling
operation by
ON or OFF of
an external
contact switch

Setting
MODE1
P1 : Arbitrary operation
state
P2 : Arbitrary operation
state
Others setting are
arbitrary.

When operating in
the state set when
an external
contact switch
was set to ON and
returning to the
original operation
state when the
switch was set to
OFF

MODE1 or 0
P1 : SETBACK
P2 : Arbitrary
operation state
Others setting are
arbitrary.

When operated
in the state
when an
external
contact switch
was set to OFF
and returned to
original
operation state

MODE1 or 0
P1 : Arbitrary
operation state
P2 : SETBACK
Others setting are
arbitrary.

When a
temperature
sensor switch
is connected
and cooling
and heating
switching is
performed.

MODE2
P1 : ON, COOL or
HEAT
P2 : ON, COOL or
HEAT
Operation conditions
:Unit operationg only
Others setting are
arbitrary.

Wiring

Operation example
P1 : OFF P2 : ON, COOL, 26C

Indoor
unit

SW1 ON

External
SW controller

Operation state
External
contact 1

P2

OFF

P1

ON
COOL
26 C

OFF

MODE1, P1 : SETBACK P2 : ON, COOL, 26C


Indoor
unit

SW1 ON

External
SW controller

P2

OFF

P1

Operation state ON
External
contact 1

OFF

COOL
23C

COOL
26 C

COOL
23 C

MODE1, P1 : ON, COOL, 26C


P2 : When SETBACK

Indoor
unit

SW1

ON

P1
OFF

External
SW controller

P2

Operation state ON
External
contact 1

Indoor
unit

OFF

COOL
23C

COOL
26 C

COOL
23 C

P1 : ON, COOL, 26C


P2 : ON,HEAT, 21C
SW1
ON

P2
OFF

P1

Operation state ON
OFF

Thermal sensor SW

COOL
23C

HEAT
21C

COOL
26C

An external switch controller is


connected to all the indoor units
of the same refrigerant system
and cooling and heating are
switched by one temperature
sensor.

When
preventing
chattering noise
within 1 minute
of the external
contact switch.

CONTROL
SYSTEM

CONTROL
SYSTEM

Application

MODE1
Delay-time setting
:Delay
P1 : Arbitrary
operation state
P2 : Arbitrary
operation state
Others setting are
arbitrary.

Indoor
unit
External
SW controller

P1 : OFF P2 : ON, COOL, 26 C


SW1
ON

P2
1min

P1
1min

Operation state ON
External
contact 1

- (02 - 53) -

OFF

COOL
26 C

2-4.SERVICE & MONITORING


2-4-1.SERVICE TOOL
Extensive monitoring and analysis functions for installation and maintenance.
Operation status and error history can be grasped promptly and adequately.

FEATURE
Adopting to USB type network interface to convert VRF network, it realizes highly portability and
simple connection.

Storage of data on system operating status on a PC allows access even from off site.
Up to 400 units can be controlled and monitored for large scale building or hotels.
Operational status can be checked and analyzed to detect even the small abnormalities.
The operation status and various sensor information of each unit can be monitored
real time and can be understood in detail as history information.
By realizing operation control to each unit from PC, the operation status in various
condition and system requirements can be grasped.
The Y axis of old fixed data graph screens can be specified within an arbitrary range at
a setup modification screen.
This allows verification of even minute changes of each value.

Preserving the operation status record at arbitrarily term evenwhile current data sampling
continuously.

WIRING CONNECTION
Transmission
adaptor

Refrigerant piping

Indoor unit

or
USB
adaptor
(Field supplied)

Transmission line
Indoor unit

COMMISSIONING TOOL
Test run commands can be executed with this tool.
During test running, the outdoor unit/indoor unit sensor data can be saved (commissioning log data).
After the end of test running, this data can be exported in CSV file format.

- (02 - 54) -

CONTROL
SYSTEM

CONTROL
SYSTEM

Model : UTR-YSTC

MAIN FUNCTION
1 System List Screen

CONTROL
SYSTEM

CONTROL
SYSTEM

Displays the overall operating status from a list of the status of each unit.

2 Detail Screen
Displays the schematic, sensor values, and electrical components operating status of the selected unit.
Normal operation checks and cause specification when an error occurs are performed.
The schematic of 1 outdoor unit and 3 indoor units and three items graph can be simultaneously displayed.

3 Status List Screen


Detail data(sensor values and electrical components operating status) for all the units in the specified
refrigerant system will be displayed at a certain point of time(displayed items is as same as the Detail screen).

- (02 - 55) -

4 Operation History Screen


The indoor units or outdoor unit operation history can be recorded.

CONTROL
SYSTEM

CONTROL
SYSTEM

The displayed operation history can be printed out and saved to a CSV file.

5 Error History Screen


Displays the error information for each unit. The error information can sequentially display
up to 50 items beginning from the newest error for each unit.

6 Download Screen
Any unit data currently displayed can be saved.
The saved data may be displayed as offline data.

COMPOSITION
PC(Personal Computer)

Serial cable
RS-232c

Transmission Line (LONWORKS R wire)


Power supply
50Hz 220-240V

Hardware protection key(for USB)


CD-ROM

PC(Personal Computer)
Hardware protection key (for USB)
Transmission Line (LONWORKS R wire)
USB Network Interface
(Field supplied)
- (02 - 56) -

CONTROL
SYSTEM

CONTROL
SYSTEM

PACKING LIST

PERSONAL COMPUTER SPECIFICATION


The following equipment is required for using PC controller AT compatible machine that
Runs on Microsoft Windows.

Operating System
Personal
Computer

CPU
HDD
Memory
Interface

AT compatible machine that runs Microsoft Windows


Microsoft Windows 2000 Professional (English version / Service pack3 or later)
Microsoft Windows XP Professional (English version / Service pack1 or later)
TM
Intel Pentium / Celeron, AMD AthlonTM / Duron 1GHz or higher
2.1 GB or more
256 MB or more
Serial port (for UTR-YTMA)
USB port(for U10 USB Network Interface, Software protection key)

Software

Internet Explorer 6.0 or later / Adobe Acrobat Reader 4.0 or later

Hardware

Interlink cable D-sub 9Pin [Field supplied] / Transmission Adaptor (UTR-YTMA)


Or U10 USB Network Interface (Echelon Corporation)

USB NETWORK INTERFACE SPECIFICATION


Ordering Information
Echelon Model Number

Product
U10 USB Network Interface TP/FT-10 Channel

75010

Specifications
Network Connector

U20 Interface:2.1 barrel connector with


positive tip. Wal l plug coupling circuit/power
supply included. May be connected directly to
10.8-18VDC power line, or to customer
-suppulied coupling circuit/power supply.

Operating input current(USB)


USB Compatibility

LED Indicators
Temperature
Operating
Non-operating

50mA maximum @ 5VDC


Certified USB 2.0 compatible. Compatible with
USB 1.1 and Hi-Speed USB systems,
peripherals and cables.
Service(amber),Transmit(green),Receive(green)
0 to +70 C
-20 to +85 C

Humidity
Operating(Non-condensing)

25 to 90% RH @ +50 C

Non-operating(Non-condensing) 95% RH @ +70 C


Dimension

1.8mm high113.2mm long22.4mm wide

Note : Make sure that USB equipment(USB hub, etc.) which this USB adaptor connected should not overloaded
(Total power supplied from PC should not exceed the maximum limits).
For more information please contact sales representive.
- (02 - 57) -

2-4-2.WEB MONITORING TOOL


Model : UTR-YMSA
FEATURES
Trouble-shooting is performed by monitoring each air conditioning unit remotely during periodical system checks.

Web Monitoring System

VRF system side

Remote side

Outdoor
unit

Monitoring center

VRF system

Internet
(Provider)

Internet
explorer
6.0 or later

or
Public
Telephone
Line

UTR-YMSA

Indoor unit

Sales Company

Installer

Features

Error notification can be automatically transmitted to several


locations using the internet*.
Requires either a dedicated internet connection* or public
telephone line.
Determination of an error occurrence can be made through error
warnings and equipment status
information obtained from a remote
location.
The monitoring data in a remote side can be optionally
downloaded. And, this data can be displayed in off-line
mode of the service tool.
*Unchanging global IP address is required.

System Status
&
Error Information

VRF System Side

Remote Side

COMPOSITION
System components
Remote Side

VRF System Side

(Monitoring Center)

(User Side)

Personal
Computer
(Field Supplied)

Software
(UTR-YMSA)
Internet
or
Public
Telephone
Line

Software
Protection
Key
Interlink cable
(Field Supplied)

Internet
Explorer
6.0 or later

Personal
Computer
(Field Supplied)

Transmission
Adaptor
(UTR-YTMA)
or
USB adaptor
(Field Supplied)

VRF System

- (02 - 58) -

CONTROL
SYSTEM

CONTROL
SYSTEM

Product features

Support 4 VRF system

CONTROL
SYSTEM

CONTROL
SYSTEM

PC Transmission adaptors (max. four adaptors per PC) permit control and monitoring of up to 1,600 units.
Suitable for large-scale buildings or hotels.

VRF System1
Indoor unit :

VRF System2
Indoor unit :

VRF System3
Indoor unit :

VRF System4
Indoor unit :

Max.400

Max.400

Max.400

Max.400

PACKING LIST

PERSONAL COMPUTER SPECIFICATION


The following equipment is required for using PC controller AT compatible machine that Runs on Microsoft Windows.

Personal
Computer

Operating
System
CPU
HDD
Memory
Interface

AT compatible machine that runs Microsoft Windows


Microsoft Windows 2000 Professional
(English version / Service pack3 or later)
Microsoft Windows XP Professional
(English version / Service pack1 or later)
TM
TM
Intel Pentium / Celeron, AMD Athlon / Duron 1GHz or higher
2.1 GB or more
512 MB or more
Serial port (for UTR-YTMA Max.4 *1)
USB port (for U10 USB Network Interface Max.4 *1, Software protection key)
Or U10 USB Network Interface Echelon Corporation)

Software

Internet Explorer 6.0 or later / Adobe Acrobat Reader 4.0 or later *2

Hardware

Interlink cable D-sub 9Pin [Field supplied]


Transmission Adaptor (UTR-YTMA)

USB NETWORK INTERFACE


Please refer specification in 2-4-1 SERVICE TOOL.

- (02 - 59) -

COMPARISON TABLE
Web Monitoring Tool
Item

Interchangeability of equipment

Indication of equipment list

Operation control

Indication of unit circuit diagram

Commissioning tool

Monitoring of equipment information

Monitoring of operating condition

Monitoring of sensor data

Indication of trend graph

10

Storage and CSV output of operating


history (sensor data)

11

Printing of trend graph

12

Monitoring and screen display of abnormalities

13

E-mail automatic transmission of abnormalities

14

Setting for user level


*It

UTR-YSTC

UTR-YMSA

VRF System Side

Remote Side

CONTROL
SYSTEM

CONTROL
SYSTEM

No.

Service Tool

is available only during a connection to the Internet.

- (02 - 60) -

R407C

TM

SERIES

3 . OUTDOOR UNITS

3-1. MODEL LINE UP


LINE UP
TYPE

CAPACITY

MODEL NAME

Maximum Connectable
Indoor unit

28.0 kW(10HP)

AO 90MPBMF

16

OUTDOOR
UNITS

Heat recovery type

OUTDOOR
UNITS

TM

REFRIGERANT R407C
MODEL DESIGNATION
1

TYPE

MARKET REGION

AO : OUTDOOR UNIT

BLANK : 380-415V 50Hz


G

: 380-415V 50Hz

: 380-415V 50Hz

10

MODEL CODE
(kW)
90 : (28.0)

FUNCTION TYPE
HEAT RECOVERY
(R407C)

COMPRESSOR

MODEL CHANGE
CODE

SPECIAL METHOD
FUNCTION

P : SCROLL

A: (2000.12 ~
2005.6)

MF : MULTI F TYPE

T : (2000.12 ~ 2003.3)

B: (2005.7 ~ )

M : (2003.4 ~ )

CAPACITY RANGE
MODEL

CAPACITY

Total capacity of
Indoor unit

AO 90

28.0kW

14.0

36.4kW

- (03 - 01) -

Ratio of
outdoor unit capacity
50

130%

3-2 FEATURE
NEW COMPACT

COMPACT CONSTRUCTION
Layout of evaporator and fan
allows us to reduce the height.

Heat
exchanger

Width

Low machinery
room

Depth

Side

Dimensions

Width
Depth

1,380mm
1,300mm
650mm

OUTDOOR UNIT GOES INTO ELEVATOR


1,050mm

(Unit : mm)

650mm

Height

1,500mm

OUTDOOR
UNITS

OUTDOOR
UNITS

Height

Lowered motor
layout

SPACE SAVING

1,300mm

Space saving by setting side by side


without space in between.

(Unit : mm)

800mm

Setting size

5.72

(Unit : m2 )

Only a small area is needed for outdoor unit (total capacity


30HP, height of surrounding wall 1.2m)

HIGH COP
Cooling and heating can be performed simultaneously in the same
refrigerant circuit. Moreover,high energy saving is possible by heat
transfer between indoor units during heat recovery operation.

Power Accumulation Technology

Cooling COP
Heating COP

3.0
3.15

Diagram

Flow rate to the indoor unit(s) is controlled through


the use of 3 differently rated compressors operating
in a sequential step arrangement.While power
accumulation technology controls the circulating load
of the refrigerant flow between those steps.

Comp.1

Flow of
refrigerant

Comp.2

Comp.3

WIDE OPERATION RANG


Cooling operation -5 C to 52 C
Heating operation -15 C to 21 C
- (03 - 02) -

Power accumulation
technology

LOW NOISE LEVEL


Large 590mm diameter fan
provides top class low noise
level.

55dB(A)

Low outdoor unit (10HP)


noise level
(Silent operation mode 50dB(A) )

OUTDOOR
UNITS

outdoor units

Power requirement

Normal mode

Silent mode

380V

55

50

415V

57

51

AO 90

EASY MAINTENANCE
Easy to replace compressors

Indication of operating status


on PCB.
Indicating the operating status
and details of failures on PCB
in outdoor unit, allows better
service and quick and easy
maintenance.

EASY INSTALLATION
Four-direction piping allows
a variety of installation,
configurations
Easy installation and
pipe direction setting

Outdoor unit can be lifted by a crane set


up on the roof of the building
Four-direction pipe
4
Back
1
Front

2
Bottom

3
Right

OTHERS
Power requirement
Pipe limitation

The pump down can be performed


from Outdoor unit by the switch on
the PCB in outdoor unit.

3-phase 4-wire

Maximum Length

100m

Height Difference

50m

- (03 - 03) -

Protective boards

OUTDOOR
UNITS

(unit : dB(A))

3-3. SPECIFICATIONS
AO90MPBMF
Model

Total Capacity

OUTDOOR
UNITS

Total Input Watts


Total Ampacity

Cooling

3W4,50Hz

380 - 415
28.0

kW

Heating
Cooling

31.5
9.40

kW

Heating
Cooling

10.0
16.2

Heating

Starting Current
E.E.R.

, Hz

17.0

A
Cooling

75
2.98

W/W

Heating

3.15

Type

Plate Fin Coil

Heat Exchanger Rows x Stages

2 X 30 + 2 X 30

Fin Pitch
Air Circulation

High

1.5
9800

m /h
3

Fan Type x Qty

Propeller x 2

Fan Motor Output

Compressor

150 x 2

Model

ZR22K3E-TFD
ZR49KCE-TFD
ZR72KCE-TFD

Type

Hermetically sealed
scroll type

Motor Output

kW

1.5/3.4/5.0
Internal Protector(OCR)
High Pressure Relief Valve

Protection
Dimensions
(H x W x D)
Weights

Net
Gross
Net

Refrigerant OIL

1,535 x 1,400 x 770


313

kg

Gross

Noise Level (Sound Pressure)


Refrigerant

1,380 x 1,300 x 650

mm

350

dB (A)

57

Type

R407C

Charge

kg

13.0

Type

EMIKARATE RL 32CF

Charge

cc

1120/1690/1690 + 2000

Liquid
Size
Pipe

Discharge Gas

12.70
mm

19.05

Suction Gas
Max Length
Max Height

Operation (Outdoor)

Cooling
Heating

28.58
100

50
-5 to 52

-15 to 21

- (03 - 04) -

OUTDOOR
UNITS

Power Requirement

AO90MPBMF

3-4 DIMENSIONS

(Unit : mm)

1000mm

OUTDOOR
UNITS

678mm

2
3
4
5
6

1380mm

Knock out hole for piping


Knock out hole for wiring
Bush for wiring
Knock out hole for drain piping
Liquid pipe valve (flare)
Discharge pipe valve (flange)
Suction pipe valve (flange)

35mm

3
53mm
302mm
200mm
39
100mm
mm

13mm 80mm

250mm

400mm

41
mm

177mm

1300mm

75mm

200mm
100mm

156mm
239mm

50mm

400mm

650mm

- (03 - 05) -

80mm

650mm

OUTDOOR
UNITS

850mm

3-5 INSTALLATION SPACE

There are no height restriction for


the side wall.
The height (H) of front and rear wall
should be less than 1,200mm.
If the height of wall exceed 1,200mm
by h mm,add h mm to the service
space width for L1 and L2.

OUTDOOR
UNITS

10mm or more

Top air outlet

500mm
or more
10mm or more

H (1200mm)

300mm or more

H (1200mm)

FRONT
SIDE

L2
h

L1

Front side
intake port

Back side
intake port

FOR CONTINUOUS
10mm or more

500mm or more
300mm
or more
10mm or more

If outdoor unit is not installed to specifications,


capacity may drop because of a short-circuit.
As a result, a high pressure error may occur.

Since specified values are minimum


permissible measurements, install unit
after duly considering the measurements
required for installation location,piping work
and maintenance.

FRONT SIDE
10mm or more

10mm or more

- (03 - 06) -

OUTDOOR
UNITS

>
H<
= 1,200 :L1= 500, L2 >
= 300
H >1,200 :L1 > 500+h, L2 > 300+h

FOR INDIVIDUALLY

FOR CENTRALIZED
10mm
or more
700mm
or more

300mm
or more

Front

Front

OUTDOOR
UNITS

10mm
or more

10mm
or more

10mm
or more
300mm
or more

700mm
or more

300mm
or more

Front

Front

10mm
or more

10mm
or more

If outdoor unit is installed beyound allowable values, capacity will drop because of
short-circuit. As a result, there is a danger of high pressure.
Since specified values are minimum permissible measurements, install unit after duly
considering the measurements required for installtion location and piping work.

- (03 - 07) -

OUTDOOR
UNITS

500mm
or more

REQUIRED SPACE FOR DISCHARGE OUTLET

OUTDOOR
UNITS

OUTDOOR
UNITS

1 Minimum space : 700mm


Install a hood when the space is less than 1000mm.
2 When a hood is installed, the static
pressure has to be less than 3mmAq.

CONSIDERATION FOR SEASONAL WIND AND SNOW


Install inlet and outlet ducts in order to maintain stable operation in cold
or snowy regions
Seasonal wind

500

870

Air intake hood


(Field - supplied)

Air discharge hood


(Field - supplied)

50m

590

500

R6

Air intake side

Air intake hood


(Field - supplied)

Air intake side

Snow

Snow
Make the foundation
as high as possible

- (03 - 08) -

OUTDOOR
UNITS

OUTDOOR
UNITS

RECOMMENDED SHAPES OF EACH DUCT

Fig.1 Overall view


1300mm

250mm

870mm
100mm

500mm

Fig.2 Outdoor unit rear side duct


1300mm

250mm

590mm

Fig.3 Outdoor unit front side duct

- (03 - 09) -

100mm

500mm

OUTDOOR
UNITS

R650

140

OUTDOOR
UNITS

1300

650

Fig.4 Outdoor unit upper part duct

CAUTION
1. Don't put weight of the duct on outdoor unit. (20kg or less).
2.When the leakage of air from the connecting gaps (between the duct and outdoor unit or gallery) is large and
the air temperature around outdoor unit increases more than 2 deg, Seal the joining gaps with putty.
3.When the duct is installed, remove two fan covers first.

- (03 - 10) -

HP

OIL
SEPARATOR

OUTDOOR UNIT

- (03 - 11) -

4WV4

4WV3

4WV2

THD3

THD2

THD1

COMP.3

COMP.2

COMP.1

SV3

THHI3

THHI2

THHI1

SV4 SV5

THO

H.E.3

H.E.2

H.E.1

ACCUMU
LATOR

THHO3

THHO2

T HO1

SV6

SV8

SV7

HP

EEV2

EEV1

SV1

EEV3

MP

RECEIVER
TANK

SV2

3W.V

BV2

BV1

SVB1

SVs

SVB2

SVs

:3-way valve

:Ball valve

:Capillary tube

:Expansion valve

SVB2

OUTDOOR
UNITS

SVD

R.B UNIT

EEV

:Dryer

:Pressure switch
HP:High pressure

:Pressure sensor
HP:High pressure
MP:Middle pressure

THIA

THOA

THHM

INDOOR UNIT C

:Thermistor
TH D:Discharge thermistor
THHi :H.E. inlet thermistor
TH HM :H.E. middle thermistor
TH HO :H.E. outlet thermistor
TH OA :Outlet air thermistor
THo:Outdoor temp thermistor
THIA:Indoor Room temp thermistor

:Heat exchanger

:Strainer

SVB1

:4-way valve

SVB2

SVs

:Power accumulation unit

SVB1

SVD

R.B UNIT

EEV

:Check valve

:Solenoid valve

SVD

R.B UNIT

THIA

THOA
EEV

THOA
THIA

THHM

INDOOR UNIT B

THHM

INDOOR UNIT A

OUTDOOR
UNITS

3-6 REFRIGERANT CIRCUIT


HEAT RECOVERY TYPE
MODEL : AO90MPBMF

3-7 WIRING DIAGRAM


HEAT RECOVERY TYPE

OUTDOOR
UNITS

OUTDOOR
UNITS

MODEL : AO90M

- (03 - 12) -

COOLING CAPACITY

3-8 CAPACITY TABLE


COOLING CAPACITY
MODEL : AO90M

( kW )

OUTDOOR
UNITS

36. 4
( 130% )

33. 6
( 120% )

30. 8
( 110% )

28. 0
( 100% )

25. 2
( 90% )

Outdoor
Temperature

Indoor Temperature
20 CDB/15 CWB 23 CDB/16 CWB 26 CDB/18 CWB 27 CDB/19 CWB 28 CDB/20 CWB 30 CDB/22 CWB 32 CDB/23 CWB
68 FDB/59 FWB 73 FDB/61 FWB 79 FDB/64 FWB 81 FDB/66 FWB 82 FDB/68 FWB 86 FDB/72 FWB 90 FDB/73 FWB
( CDB) ( FDB)
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
10
50
35. 8
7. 3
36. 6
7. 4
38. 1
7. 6
38. 9
7. 7
39. 7
7. 8
41. 3
8. 0
42. 1
8. 1
15
59
34. 7
8. 2
35. 5
8. 3
37. 0
8. 5
37. 7
8. 6
38. 5
8. 7
40. 1
8. 9
40. 9
9. 0
20
68
34. 0
8. 8
34. 7
8. 9
36. 3
9. 1
37. 0
9. 2
37. 8
9. 2
39. 4
9. 4
40. 2
9. 5
23
73
33. 3
9. 4
34. 0
9. 4
35. 5
9. 6
36. 3
9. 7
37. 1
9. 8
38. 6
10. 0
39. 4
10. 0
25
77
32. 8
9. 7
33. 6
9. 8
35. 1
10. 0
35. 8
10. 0
36. 6
10. 1
38. 1
10. 2
38. 9
10. 3
27
81
32. 4
10. 0
33. 1
10. 1
34. 6
10. 3
35. 3
10. 4
36. 0
10. 4
37. 6
10. 6
38. 3
10. 7
30
86
32. 1
10. 2
32. 8
10. 3
34. 3
10. 4
35. 1
10. 5
35. 8
10. 6
37. 4
10. 8
38. 1
10. 8
33
91
31. 4
10. 8
32. 1
10. 9
33. 6
11. 0
34. 3
11. 1
35. 0
11. 2
36. 5
11. 3
37. 3
11. 4
35
95
30. 9
11. 2
31. 6
11. 2
33. 0
11. 4
33. 8
11. 5
34. 5
11. 5
36. 0
11. 7
36. 7
11. 8
37
99
30. 4
11. 5
31. 1
11. 6
32. 5
11. 8
33. 2
11. 8
34. 0
11. 9
35. 4
12. 1
36. 2
12. 1
40
104
29. 6
12. 1
30. 3
12. 2
31. 7
12. 3
32. 4
12. 4
33. 1
12. 5
34. 6
12. 6
35. 3
12. 7
45
113
28. 3
13. 0
29. 0
13. 1
30. 3
13. 3
31. 0
13. 3
31. 7
13. 4
33. 1
13. 5
33. 8
13. 6
52
125
26. 4
14. 3
27. 1
14. 3
28. 4
14. 4
29. 0
14. 5
29. 7
14. 6
31. 0
14. 7
31. 6
14. 8
10
50
35. 6
7. 1
36. 4
7. 2
37. 9
7. 3
38. 7
7. 4
39. 4
7. 5
41. 0
7. 7
41. 8
7. 8
15
59
34. 5
8. 0
35. 3
8. 1
36. 8
8. 2
37. 5
8. 3
38. 3
8. 4
39. 8
8. 6
40. 6
8. 7
20
68
33. 8
8. 5
34. 6
8. 6
36. 1
8. 8
36. 8
8. 9
37. 6
9. 0
39. 1
9. 1
39. 9
9. 2
23
73
33. 1
9. 1
33. 9
9. 2
35. 3
9. 3
36. 1
9. 4
36. 8
9. 5
38. 4
9. 7
39. 1
9. 8
25
77
32. 7
9. 4
33. 4
9. 5
34. 9
9. 7
35. 6
9. 8
36. 3
9. 9
37. 9
10. 0
38. 6
10. 1
27
81
32. 2
9. 8
32. 9
9. 9
34. 4
10. 1
35. 1
10. 1
35. 8
10. 2
37. 3
10. 4
38. 1
10. 5
30
86
31. 9
10. 0
32. 7
10. 1
34. 1
10. 2
34. 9
10. 3
35. 6
10. 4
37. 1
10. 5
37. 9
10. 6
33
91
31. 2
10. 6
31. 9
10. 6
33. 4
10. 8
34. 1
10. 8
34. 9
10. 9
36. 3
11. 1
37. 1
11. 1
35
95
30. 7
10. 9
31. 5
11. 0
32. 9
11. 1
33. 6
11. 2
34. 3
11. 3
35. 8
11. 4
36. 5
11. 5
37
99
30. 3
11. 3
31. 0
11. 4
32. 4
11. 5
33. 1
11. 6
33. 8
11. 6
35. 2
11. 8
36. 0
11. 8
40
104
29. 5
11. 8
30. 2
11. 9
31. 6
12. 0
32. 3
12. 1
33. 0
12. 2
34. 4
12. 3
35. 1
12. 4
45
113
28. 2
12. 7
28. 9
12. 8
30. 2
12. 9
30. 9
13. 0
31. 6
13. 1
33. 0
13. 2
33. 7
13. 3
52
125
26. 4
14. 0
27. 0
14. 1
28. 3
14. 2
29. 0
14. 2
29. 6
14. 3
30. 9
14. 4
31. 5
14. 5
10
50
32. 6
6. 8
33. 3
6. 9
34. 7
7. 1
35. 4
7. 1
36. 1
7. 2
37. 5
7. 4
38. 3
7. 5
15
59
31. 7
7. 7
32. 3
7. 8
33. 7
7. 9
34. 4
8. 0
35. 1
8. 1
36. 5
8. 3
37. 2
8. 4
20
68
31. 0
8. 2
31. 7
8. 3
33. 0
8. 5
33. 7
8. 6
34. 4
8. 6
35. 8
8. 8
36. 5
8. 9
23
73
30. 4
8. 8
31. 1
8. 9
32. 4
9. 0
33. 1
9. 1
33. 8
9. 2
35. 2
9. 3
35. 8
9. 4
25
77
30. 0
9. 1
30. 6
9. 2
32. 0
9. 4
32. 6
9. 5
33. 3
9. 5
34. 7
9. 7
35. 4
9. 8
27
81
29. 6
9. 5
30. 2
9. 6
31. 5
9. 7
32. 2
9. 8
32. 9
9. 9
34. 2
10. 0
34. 9
10. 1
30
86
29. 3
9. 7
30. 0
9. 8
31. 3
9. 9
32. 0
10. 0
32. 7
10. 1
34. 0
10. 2
34. 7
10. 3
33
91
28. 7
10. 2
29. 3
10. 3
30. 6
10. 5
31. 3
10. 5
32. 0
10. 6
33. 3
10. 7
34. 0
10. 8
35
95
28. 2
10. 6
28. 9
10. 7
30. 2
10. 8
30. 8
10. 9
31. 5
10. 9
32. 8
11. 1
33. 5
11. 2
37
99
27. 8
11. 0
28. 4
11. 0
29. 7
11. 2
30. 4
11. 2
31. 0
11. 3
32. 3
11. 4
33. 0
11. 5
40
104
27. 1
11. 5
27. 7
11. 6
29. 0
11. 7
29. 7
11. 8
30. 3
11. 8
31. 6
12. 0
32. 2
12. 0
45
113
26. 0
12. 4
26. 6
12. 5
27. 8
12. 6
28. 4
12. 7
29. 1
12. 7
30. 3
12. 8
30. 9
12. 9
52
125
24. 3
13. 6
24. 8
13. 7
26. 1
13. 8
26. 7
13. 9
27. 3
13. 9
28. 4
14. 1
29. 0
14. 1
10
50
29. 7
5. 7
30. 3
5. 7
31. 6
5. 9
32. 3
6. 0
32. 9
6. 0
34. 3
6. 2
34. 9
6. 3
15
59
28. 8
6. 5
29. 4
6. 5
30. 7
6. 7
31. 3
6. 8
32. 0
6. 8
33. 3
7. 0
34. 0
7. 0
20
68
28. 2
7. 0
28. 8
7. 1
30. 1
7. 2
30. 7
7. 3
31. 3
7. 3
32. 7
7. 5
33. 3
7. 5
23
73
27. 6
7. 5
28. 2
7. 6
29. 5
7. 7
30. 1
7. 8
30. 7
7. 8
32. 0
8. 0
32. 7
8. 0
25
77
27. 2
7. 8
27. 8
7. 9
29. 1
8. 0
29. 7
8. 1
30. 3
8. 1
31. 6
8. 3
32. 3
8. 3
27
81
26. 8
8. 1
27. 5
8. 2
28. 7
8. 3
29. 3
8. 4
29. 9
8. 5
31. 2
8. 6
31. 8
8. 7
30
86
26. 6
8. 4
27. 2
8. 4
28. 4
8. 5
29. 1
8. 6
29. 7
8. 7
31. 0
8. 8
31. 6
8. 8
33
91
26. 0
8. 9
26. 6
8. 9
27. 8
9. 0
28. 4
9. 1
29. 0
9. 1
30. 3
9. 2
30. 9
9. 3
35
95
25. 6
9. 2
26. 2
9. 2
27. 4
9. 3
28. 0
9. 4
28. 6
9. 5
29. 9
9. 6
30. 5
9. 6
37
99
25. 2
9. 5
25. 8
9. 6
27. 0
9. 7
27. 6
9. 7
28. 2
9. 8
29. 4
9. 9
30. 0
9. 9
40
104
24. 6
10. 0
25. 2
10. 0
26. 3
10. 2
26. 9
10. 2
27. 5
10. 3
28. 7
10. 4
29. 3
10. 4
45
113
23. 5
10. 8
24. 1
10. 9
25. 2
11. 0
25. 8
11. 0
26. 4
11. 1
27. 5
11. 1
28. 1
11. 2
52
125
22. 0
11. 9
22. 5
12. 0
23. 6
12. 1
24. 2
12. 1
24. 7
12. 2
25. 8
12. 2
26. 4
12. 3
10
50
26. 6
5. 5
27. 3
5. 5
28. 4
5. 7
29. 0
5. 7
29. 6
5. 8
30. 8
5. 9
31. 3
6. 0
15
59
25. 9
6. 2
26. 5
6. 3
27. 6
6. 4
28. 2
6. 5
28. 7
6. 5
29. 9
6. 7
30. 5
6. 7
20
68
25. 3
6. 8
26. 0
6. 8
27. 0
6. 9
27. 6
7. 0
28. 2
7. 0
29. 3
7. 2
29. 9
7. 2
23
73
24. 9
7. 2
25. 4
7. 3
26. 5
7. 4
27. 1
7. 4
27. 6
7. 6
28. 8
7. 7
29. 4
7. 8
25
77
24. 5
7. 6
25. 1
7. 7
26. 2
7. 8
26. 7
7. 8
27. 3
7. 9
28. 4
8. 0
29. 0
8. 1
27
81
24. 2
7. 9
24. 7
8. 0
25. 8
8. 1
26. 4
8. 1
26. 9
8. 2
28. 0
8. 3
28. 6
8. 4
30
86
23. 9
8. 1
24. 5
8. 2
25. 6
8. 3
26. 1
8. 3
26. 7
8. 4
27. 8
8. 5
28. 4
8. 5
33
91
23. 4
8. 6
24. 0
8. 6
25. 0
8. 7
25. 6
8. 8
26. 1
8. 8
27. 3
8. 9
27. 8
9. 0
35
95
23. 1
8. 9
23. 6
8. 9
24. 7
9. 0
25. 2
9. 1
25. 8
9. 1
26. 9
9. 2
27. 4
9. 3
37
99
22. 7
9. 2
23. 2
9. 3
24. 3
9. 3
24. 8
9. 4
25. 4
9. 4
26. 5
9. 5
27. 0
9. 7
40
104
22. 2
9. 8
22. 7
9. 8
23. 7
9. 9
24. 3
9. 9
24. 8
10. 0
25. 9
10. 1
26. 4
10. 1
45
113
21. 2
10. 5
21. 7
10. 6
22. 8
10. 7
23. 3
10. 7
23. 8
10. 7
24. 8
10. 8
25. 4
10. 9
52
125
19. 9
11. 6
20. 3
11. 6
21. 4
11. 7
21. 8
11. 7
22. 3
11. 9
23. 3
12. 0
23. 8
12. 0
TC : Total Capacity kW
PI : Power Input kW ( Comp. + Outdoor fan motor )

- (03 - 13) -

OUTDOOR
UNITS

Total Capacity
Of Indoor Unit

COOLING CAPACITY
Total Capacity
Of Indoor Unit

Outdoor
Temperature

( kW )

( CDB) ( FDB)
10
50
15
59
20
68
23
73
25
77
27
81
30
86
33
91
35
95
37
99
40
104
45
113
52
125
10
50
15
59
20
68
23
73
25
77
27
81
30
86
33
91
35
95
37
99
40
104
45
113
52
125
10
50
15
59
20
68
23
73
25
77
27
81
30
86
33
91
35
95
37
99
40
104
45
113
52
125
10
50
15
59
20
68
23
73
25
77
27
81
30
86
33
91
35
95
37
99
40
104
45
113
52
125

OUTDOOR
UNITS

22. 4
( 80% )

19. 6
( 70% )

16. 8
( 60% )

14. 0
( 50% )

Indoor Temperature
20 CDB/15 CWB 23 CDB/16 CWB 26 CDB/18 CWB 27 CDB/19 CWB 28 CDB/20 CWB 30 CDB/22 CWB 32 CDB/23 CWB
68 FDB/59 FWB 73 FDB/61 FWB 79 FDB/64 FWB 81 FDB/66 FWB 82 FDB/68 FWB 86 FDB/72 FWB 90 FDB/73 FWB
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
23. 8
4. 6
24. 4
4. 6
25. 4
4. 7
25. 9
4. 8
26. 5
4. 8
27. 5
4. 9
28. 1
5. 0
23. 1
5. 2
23. 6
5. 2
24. 7
5. 4
25. 2
5. 4
25. 7
5. 5
26. 8
5. 6
27. 3
5. 6
22. 6
5. 6
23. 1
5. 7
24. 1
5. 8
24. 7
5. 8
25. 2
5. 9
26. 2
6. 0
26. 8
6. 0
22. 2
6. 0
22. 7
6. 1
23. 7
6. 2
24. 2
6. 2
24. 7
6. 3
25. 7
6. 4
26. 3
6. 4
21. 9
6. 3
22. 4
6. 3
23. 4
6. 4
23. 9
6. 5
24. 4
6. 5
25. 4
6. 6
25. 9
6. 7
21. 6
6. 5
22. 1
6. 6
23. 0
6. 7
23. 5
6. 7
24. 0
6. 8
25. 1
6. 9
25. 6
6. 9
21. 3
6. 7
21. 8
6. 8
22. 8
6. 9
23. 3
6. 9
23. 8
6. 9
24. 9
7. 0
25. 4
7. 1
20. 9
7. 1
21. 4
7. 2
22. 3
7. 3
22. 8
7. 3
23. 3
7. 3
24. 3
7. 4
24. 8
7. 5
20. 5
7. 4
21. 0
7. 4
22. 0
7. 5
22. 4
7. 6
23. 0
7. 6
24. 0
7. 7
24. 5
7. 7
20. 2
7. 6
20. 7
7. 7
21. 7
7. 8
22. 1
7. 8
22. 6
7. 9
23. 6
7. 9
24. 1
8. 0
19. 7
8. 0
20. 2
8. 1
21. 1
8. 2
21. 6
8. 2
22. 1
8. 2
23. 1
8. 3
23. 6
8. 4
18. 9
8. 7
19. 3
8. 7
20. 3
8. 8
20. 7
8. 8
21. 2
8. 9
22. 1
9. 0
22. 6
9. 0
17. 7
9. 6
18. 1
9. 6
19. 0
9. 7
19. 4
9. 7
19. 9
9. 8
20. 8
9. 8
21. 2
9. 9
20. 6
4. 6
21. 0
4. 6
22. 0
4. 6
22. 5
4. 6
22. 9
4. 7
23. 8
4. 8
24. 3
4. 8
20. 1
5. 0
20. 5
5. 1
21. 4
5. 2
21. 8
5. 2
22. 3
5. 3
23. 2
5. 4
23. 6
5. 4
19. 7
5. 4
20. 1
5. 5
20. 9
5. 6
21. 4
5. 6
21. 8
5. 7
22. 7
5. 7
23. 2
5. 9
19. 3
5. 9
19. 7
5. 9
20. 6
6. 0
21. 0
6. 1
21. 4
6. 1
22. 3
6. 2
22. 8
6. 2
19. 0
6. 1
19. 4
6. 2
20. 3
6. 3
20. 7
6. 3
21. 2
6. 3
22. 0
6. 4
22. 5
6. 5
18. 8
6. 4
19. 2
6. 4
20. 0
6. 5
20. 4
6. 5
20. 9
6. 6
21. 7
6. 7
22. 2
6. 7
18. 6
6. 6
19. 0
6. 6
19. 8
6. 7
20. 3
6. 7
20. 7
6. 7
21. 6
6. 8
22. 0
6. 9
18. 2
6. 9
18. 6
6. 9
19. 4
7. 0
19. 8
7. 2
20. 3
7. 2
21. 1
7. 3
21. 6
7. 3
17. 9
7. 2
18. 3
7. 3
19. 1
7. 4
19. 6
7. 4
20. 0
7. 4
20. 8
7. 5
21. 3
7. 5
17. 6
7. 5
18. 0
7. 5
18. 8
7. 6
19. 3
7. 6
19. 7
7. 7
20. 5
7. 7
21. 0
7. 8
17. 2
7. 8
17. 6
7. 9
18. 4
8. 0
18. 8
8. 0
19. 2
8. 0
20. 1
8. 1
20. 5
8. 1
16. 5
8. 5
16. 9
8. 6
17. 7
8. 6
18. 1
8. 7
18. 5
8. 7
19. 3
8. 8
19. 7
8. 8
15. 5
9. 3
15. 8
9. 4
16. 6
9. 4
16. 9
9. 5
17. 4
9. 5
18. 1
9. 6
18. 5
9. 6
17. 7
3. 6
18. 1
3. 6
18. 9
3. 6
19. 4
3. 6
19. 8
3. 7
20. 7
3. 7
21. 2
3. 7
17. 6
3. 7
18. 0
3. 7
18. 8
3. 8
19. 2
3. 8
19. 6
3. 8
20. 4
3. 9
20. 8
3. 9
17. 2
4. 1
17. 3
4. 4
18. 0
4. 4
18. 4
4. 5
19. 2
4. 2
19. 6
4. 6
20. 0
4. 6
16. 6
4. 6
16. 9
4. 6
17. 7
4. 7
18. 1
4. 8
18. 5
4. 8
19. 2
4. 9
19. 6
4. 9
16. 3
4. 8
16. 7
4. 8
17. 5
4. 9
17. 8
4. 9
18. 2
5. 0
19. 0
5. 1
19. 4
5. 1
16. 1
5. 0
16. 5
5. 0
17. 2
5. 1
17. 6
5. 1
18. 0
5. 2
18. 7
5. 2
19. 1
5. 3
15. 9
5. 1
16. 3
5. 2
17. 0
5. 2
17. 4
5. 3
17. 8
5. 3
18. 6
5. 4
19. 0
5. 4
15. 6
5. 4
15. 9
5. 5
16. 7
5. 5
17. 1
5. 6
17. 4
5. 6
18. 2
5. 7
18. 6
5. 7
15. 3
5. 6
15. 7
5. 7
16. 4
5. 7
16. 8
5. 8
17. 2
5. 8
17. 9
5. 8
18. 3
5. 9
15. 1
5. 8
15. 5
5. 9
16. 2
5. 9
16. 5
5. 9
16. 9
6. 0
17. 7
6. 0
18. 0
6. 2
15. 0
5. 9
15. 4
5. 9
16. 1
6. 0
16. 5
6. 0
16. 8
6. 0
17. 6
6. 2
18. 0
6. 2
14. 4
6. 5
14. 7
6. 5
15. 4
6. 6
15. 8
6. 6
16. 1
6. 6
16. 9
6. 7
17. 2
6. 7
13. 5
7. 2
13. 8
7. 2
14. 5
7. 2
14. 9
7. 3
15. 1
7. 3
15. 8
7. 3
16. 2
7. 3
14. 6
3. 1
15. 0
3. 6
15. 6
3. 6
16. 0
3. 6
16. 3
3. 6
17. 1
3. 6
17. 4
3. 6
14. 6
3. 1
15. 0
3. 6
15. 6
3. 6
15. 9
3. 6
16. 3
3. 7
16. 9
3. 7
17. 2
3. 8
14. 3
3. 4
14. 6
3. 9
15. 3
4. 0
15. 6
4. 0
15. 9
4. 0
16. 6
4. 1
16. 9
4. 1
13. 8
3. 9
14. 1
4. 5
14. 7
4. 6
15. 0
4. 6
15. 3
4. 6
16. 0
4. 7
16. 3
4. 7
13. 6
4. 1
13. 9
4. 7
14. 5
4. 8
14. 8
4. 8
15. 2
4. 8
15. 8
4. 9
16. 1
4. 9
13. 4
4. 3
13. 7
4. 9
14. 3
5. 0
14. 7
5. 0
15. 0
5. 0
15. 6
5. 1
15. 9
5. 1
13. 3
4. 4
13. 6
5. 0
14. 2
5. 1
14. 5
5. 1
14. 8
5. 2
15. 4
5. 2
15. 8
5. 2
13. 0
4. 7
13. 3
5. 3
13. 9
5. 4
14. 2
5. 4
14. 5
5. 5
15. 1
5. 5
15. 4
5. 5
12. 8
4. 9
13. 1
5. 5
13. 7
5. 6
14. 0
5. 6
14. 3
5. 7
14. 9
5. 7
15. 2
5. 7
12. 6
5. 0
12. 9
5. 7
13. 5
5. 8
13. 8
5. 8
14. 1
5. 9
14. 7
5. 9
15. 0
5. 9
12. 0
5. 6
12. 3
6. 4
12. 8
6. 4
13. 1
6. 5
13. 4
6. 5
14. 0
6. 6
14. 3
6. 6
11. 5
6. 0
11. 8
6. 8
12. 3
6. 9
12. 6
6. 9
12. 9
7. 0
13. 4
7. 0
13. 7
7. 1
10. 8
6. 6
11. 1
7. 5
11. 5
7. 6
11. 8
7. 6
12. 1
7. 6
12. 6
7. 7
12. 8
7. 7

TC : Total Capacity kW
PI : Power Input kW ( Comp. + Outdoor fan motor )

- (03 - 14) -

OUTDOOR
UNITS

MODEL : AO90M

HEATING CAPACITY

HEATING CAPACITY
Total Capacity
Of Indoor Unit
( kW )

OUTDOOR
UNITS

36. 4
( 130% )

33. 6
( 120% )

30. 8
( 110% )

28. 0
( 100% )

25. 2
( 90% )

22. 4
( 80% )

19. 6
( 70% )

16. 8
( 60% )

14. 0
( 50% )

Outdoor
Temperature
( CDB) ( FDB)
-15
5
-10
14
-5
23
0
32
5
41
7
45
10
50
15
59
-15
5
-10
14
-5
23
0
32
5
41
7
45
10
50
15
59
-15
5
-10
14
-5
23
0
32
5
41
7
45
10
50
15
59
-15
5
-10
14
-5
23
0
32
5
41
7
45
10
50
15
59
-15
5
-10
14
-5
23
0
32
5
41
7
45
10
50
15
59
-15
5
14
-10
-5
23
0
32
5
41
7
45
10
50
15
59
-15
5
-10
14
-5
23
0
32
5
41
7
45
10
50
15
59
-15
5
-10
14
-5
23
0
32
5
41
7
45
10
50
15
59
-15
5
-10
14
-5
23
0
32
5
41
7
45
10
50
15
59

RH

RH85%

RH85%

RH85%

RH85%

RH85%

RH85%

RH85%

RH85%

RH85%

15 CDB
59 FDB
TC
PI
22. 7
8. 1
25. 8
8. 7
29. 5
9. 3
33. 6
10. 1
38. 2
10. 9
40. 8
11. 3
42. 8
11. 8
47. 8
12. 6
22. 3
7. 8
25. 4
8. 4
29. 0
9. 1
33. 0
9. 9
37. 5
10. 7
39. 4
11. 1
41. 9
11. 5
46. 7
12. 4
21. 9
8. 1
24. 9
8. 8
28. 4
9. 5
32. 3
10. 3
34. 5
10. 8
36. 2
11. 0
38. 4
11. 6
42. 8
12. 5
21. 2
8. 4
24. 0
9. 0
27. 2
9. 8
30. 9
10. 6
31. 3
9. 0
32. 9
9. 3
34. 9
9. 7
36. 0
10. 4
20. 6
8. 7
23. 4
9. 4
26. 5
10. 3
28. 5
11. 1
30. 4
8. 6
31. 9
8. 9
33. 9
9. 4
34. 8
10. 5
19. 6
9. 1
22. 1
9. 8
22. 4
8. 4
25. 3
9. 1
25. 8
7. 3
26. 3
7. 6
28. 0
7. 9
31. 2
8. 4
17. 2
8. 9
19. 4
9. 7
19. 7
8. 3
22. 2
8. 9
22. 7
7. 3
23. 0
7. 4
24. 5
7. 7
27. 2
8. 4
15. 7
7. 9
17. 7
8. 6
18. 8
6. 9
19. 2
7. 5
19. 5
5. 6
19. 7
5. 8
21. 0
6. 0
23. 4
6. 4
11. 4
5. 7
12. 9
6. 2
13. 4
4. 7
13. 9
5. 0
15. 7
5. 5
16. 4
5. 6
17. 5
5. 8
19. 4
6. 3

18 CDB
64 FDB
TC
PI
21. 9
8. 6
25. 0
9. 2
28. 6
10. 0
32. 7
10. 7
37. 3
11. 6
39. 8
11. 9
41. 8
12. 3
46. 7
13. 1
21. 6
8. 4
24. 6
9. 0
28. 2
9. 7
32. 1
10. 4
36. 6
11. 2
38. 5
11. 6
40. 9
12. 0
45. 6
12. 9
21. 2
8. 6
24. 2
9. 3
27. 6
10. 0
31. 5
10. 6
33. 7
11. 2
35. 3
11. 4
37. 5
12. 3
40. 0
10. 5
20. 4
8. 9
23. 2
9. 5
26. 5
10. 3
30. 1
11. 1
30. 5
9. 4
32. 0
9. 7
34. 1
10. 1
35. 3
10. 8
19. 9
9. 2
22. 7
9. 9
25. 8
10. 7
27. 7
11. 6
28. 6
9. 0
30. 5
9. 3
32. 6
10. 6
33. 4
8. 5
18. 9
9. 5
21. 5
10. 3
21. 8
8. 8
24. 7
9. 5
25. 2
7. 7
25. 6
7. 9
27. 3
8. 2
30. 4
8. 7
16. 6
9. 3
18. 8
10. 0
19. 1
8. 6
21. 7
9. 3
7. 5
22. 1
7. 7
22. 5
8. 1
23. 9
26. 6
8. 6
15. 2
8. 3
17. 2
9. 0
18. 2
7. 3
18. 6
7. 8
18. 9
5. 9
19. 2
6. 0
20. 5
6. 3
22. 8
6. 7
11. 0
6. 0
12. 5
6. 5
13. 0
4. 9
13. 5
5. 3
15. 3
5. 6
16. 1
5. 8
17. 0
6. 1
18. 9
6. 5

Indoor Temperature
20 CDB
23 CDB
68 FDB
73 FDB
TC
PI
TC
PI
21. 4
9. 0
20. 6
9. 5
24. 5
9. 6
23. 7
10. 2
28. 1
10. 3
27. 3
10. 8
32. 1
11. 0
31. 2
11. 6
36. 7
11. 9
35. 7
12. 4
39. 4
12. 2
38. 8
12. 7
41. 1
12. 6
40. 0
13. 1
45. 9
13. 5
40. 1
11. 1
21. 0
8. 7
20. 3
9. 2
24. 1
9. 3
23. 3
9. 9
27. 6
10. 0
26. 8
10. 5
31. 6
10. 7
30. 7
11. 3
36. 0
11. 6
35. 0
12. 1
37. 8
11. 9
36. 8
12. 4
40. 2
12. 3
39. 2
12. 8
40. 3
10. 4
39. 2
10. 8
20. 7
9. 0
19. 9
9. 5
23. 7
9. 6
22. 9
10. 1
27. 1
10. 3
26. 3
10. 9
30. 9
11. 1
30. 1
11. 6
33. 1
11. 4
32. 7
11. 9
34. 7
11. 6
34. 2
12. 5
36. 9
12. 5
36. 4
10. 5
39. 3
10. 8
38. 3
11. 2
19. 9
9. 2
19. 2
9. 7
22. 8
9. 9
22. 0
10. 4
26. 0
10. 6
25. 2
11. 1
29. 5
11. 4
28. 7
11. 9
30. 0
9. 7
29. 2
10. 1
31. 5
10. 0
30. 7
10. 4
33. 5
10. 4
32. 7
10. 8
34. 7
8. 3
33. 8
8. 6
19. 4
9. 6
18. 7
10. 1
22. 2
10. 3
21. 5
10. 8
25. 3
11. 1
24. 6
11. 6
26. 8
11. 9
26. 2
12. 4
27. 5
9. 3
26. 9
10. 5
28. 4
9. 7
27. 8
10. 8
31. 8
10. 8
30. 6
8. 5
32. 5
8. 7
31. 7
9. 0
18. 5
9. 9
17. 8
10. 3
21. 0
10. 6
20. 3
11. 1
21. 3
9. 1
20. 7
9. 5
24. 2
9. 7
23. 6
10. 1
24. 7
7. 9
24. 1
8. 2
25. 2
8. 1
24. 5
8. 4
26. 8
8. 4
26. 1
8. 7
29. 9
8. 9
29. 2
9. 2
16. 2
9. 7
15. 7
10. 0
18. 4
10. 4
17. 8
10. 8
18. 7
8. 8
18. 2
9. 2
21. 3
9. 6
20. 7
10. 0
7. 7
21. 1
8. 0
21. 7
7. 9
21. 6
8. 3
22. 1
8. 3
22. 9
8. 6
23. 5
26. 1
8. 7
25. 5
9. 0
14. 8
8. 6
14. 3
9. 0
16. 8
9. 2
16. 3
9. 6
17. 9
7. 5
17. 3
7. 8
18. 3
8. 1
17. 7
8. 4
18. 6
6. 0
18. 1
6. 3
18. 9
6. 2
18. 4
6. 4
20. 1
6. 4
19. 6
6. 7
22. 4
6. 8
21. 9
7. 1
10. 7
6. 2
10. 4
6. 5
12. 2
6. 7
11. 9
7. 0
12. 7
5. 0
12. 4
5. 3
13. 3
5. 4
12. 9
5. 6
15. 0
5. 8
14. 7
6. 0
15. 8
6. 0
15. 4
6. 2
16. 8
6. 2
16. 3
6. 4
18. 6
6. 5
18. 2
6. 7

TC : Total Capacity kW
PI : Power Input kW ( Comp. + Outdoor fan motor )
- (03 - 15) -

25 CDB
77 FDB
TC
PI
20. 1
10. 0
23. 2
10. 6
26. 7
11. 2
30. 7
12. 0
35. 1
12. 7
37. 7
13. 0
39. 3
13. 6
39. 4
11. 3
19. 8
9. 6
22. 8
10. 2
26. 3
10. 9
30. 1
11. 6
34. 4
12. 4
36. 2
12. 7
38. 5
13. 1
38. 6
11. 1
19. 4
9. 8
22. 4
10. 5
25. 8
11. 2
29. 5
12. 0
32. 4
12. 4
33. 8
10. 2
35. 3
10. 7
37. 6
11. 4
18. 7
10. 1
21. 5
10. 7
24. 7
11. 5
28. 2
12. 2
28. 6
10. 4
30. 1
10. 7
32. 1
11. 0
33. 5
8. 8
18. 3
10. 4
21. 0
11. 1
24. 1
11. 9
25. 6
12. 7
26. 3
10. 8
27. 2
8. 4
30. 0
8. 7
31. 1
9. 2
17. 4
10. 7
19. 9
11. 4
20. 3
9. 7
23. 1
10. 4
23. 6
8. 4
24. 1
8. 6
25. 7
8. 9
28. 7
9. 5
15. 2
10. 3
17. 4
11. 1
17. 8
9. 5
20. 3
10. 1
20. 7
8. 2
21. 1
8. 5
22. 5
8. 7
25. 1
9. 2
13. 9
9. 2
15. 9
9. 9
17. 0
8. 0
17. 4
8. 6
17. 8
6. 4
18. 1
6. 6
19. 3
6. 8
21. 5
7. 2
10. 1
6. 7
11. 6
7. 2
12. 1
5. 4
12. 6
5. 7
14. 4
6. 2
15. 1
6. 4
16. 1
6. 5
18. 2
6. 7

27 CDB
81 FDB
TC
PI
19. 6
10. 3
22. 7
10. 9
26. 2
11. 6
30. 1
12. 3
34. 4
13. 1
36. 2
13. 5
38. 6
13. 9
38. 7
11. 7
19. 3
9. 9
22. 3
10. 6
25. 7
11. 2
29. 5
11. 9
33. 7
12. 7
35. 5
13. 0
37. 8
13. 5
37. 9
11. 3
18. 9
10. 2
21. 9
10. 8
25. 2
11. 5
28. 9
12. 3
29. 4
10. 4
30. 9
10. 7
33. 0
11. 0
36. 9
11. 7
18. 2
10. 4
21. 0
11. 1
24. 2
11. 8
27. 7
12. 6
28. 1
10. 7
29. 6
11. 0
31. 5
11. 3
32. 4
9. 0
17. 8
10. 7
20. 5
11. 4
23. 6
12. 2
24. 9
10. 4
25. 7
8. 4
26. 6
8. 6
28. 8
8. 9
29. 9
9. 4
16. 9
11. 0
19. 4
11. 7
19. 9
10. 0
22. 7
10. 7
23. 2
8. 6
23. 7
8. 9
25. 2
9. 1
28. 1
9. 7
14. 8
10. 6
17. 0
11. 4
17. 5
9. 8
19. 9
10. 4
20. 4
8. 5
20. 7
8. 6
22. 1
8. 9
25. 1
9. 2
13. 5
9. 5
15. 5
10. 1
16. 6
8. 3
17. 0
8. 8
17. 4
6. 6
17. 8
6. 8
18. 9
7. 0
21. 1
7. 4
9. 8
6. 9
11. 3
7. 3
11. 9
5. 6
12. 4
5. 9
14. 1
6. 3
14. 8
6. 5
15. 7
6. 6
18. 2
6. 7

OUTDOOR
UNITS

MODEL : AO90M

3-9 SELECTION PROCEDURE


CHARACTERISTICS OF CAPACITY ( COOLING CAPACITY )
Example) In case of AU12 x 6 units and AR14 x 3units.
Design Condition : Indoor 28 C DB, 20 C WB. Outdoor 40 C DB.

Select the indoor unit


1 Select the indoor unit

MODEL
Rated CAPACITY
TC

AU12 AR14
3.60 4.00
3.81 4.24

... 1 -a
... 1 -b

OUTDOOR
UNITS

OUTDOOR
UNITS

Refer to 4-8.CAPACITY TABLE(COOLING) of INDOOR UNIT


Enter the given designed indoor and outdoor air temperature.
Please find the indoor unit capacity TC.

based on table1 4.

Select the unit by using TC 1 -b to make nearest to and larger than the load of each room.
Table.1 Capacity of indoor unit (AB)
Cooling capacity(kw)
Heating capacity(kw)

AB12
3.5
4.1

AB14
4.05
5.0

AB18
5.3
5.6

AB24
6.6
7.7

AB30
8.8
9.1

AB36
10.5
10.7

AB45
12.7
13.7

AB54
14.1
15.8

AR12
3.5
4.10

AR14
4.0
4.8

AR18
5.3
5.6

AR25
7.05
7.85

AR30
8.8
9.1

AR36
10.5
10.7

AU14
4.0
4.5

AU18
5.0
5.45

AU20
5.7
5.8

AU25
7.05
7.85

AU30
8.8
9.1

AW14
4.3
4.9

AW20
5.4
5.6

AW24
6.9
7.8

AW30
8.0
8.8

Table.2 Capacity of indoor unit (AR)


Cooling capacity(kw)
Heating capacity(kw)

AR7
2.15
2.45

AR9
2.8
3.10

Cooling capacity(kw)
Heating capacity(kw)

AR45 AR36H AR45H AR60H


12.7
10.5
12.7
17.0
10.7
13.7
13.7
17.6

Table.3 Capacity of indoor unit (AU)


Cooling capacity(kw)
Heating capacity(kw)

AU7
2.15
2.45

AU9
2.8
3.1

AU12
3.6
4.1

Table.4 Capacity of indoor unit (AS)


Cooling capacity(kw)
Heating capacity(kw)

AS18
5.4
5.6

AS24
6.9
7.8

AS30
8.0
8.8

Table.5 Capacity of indoor unit (AW)


Cooling capacity(kw)
Heating capacity(kw)

AW7
2.15
2.45

AW9
2.80
3.10

AW12
3.60
4.10

AU36
10.5
10.7

AU45
12.7
13.7

AU54
14.1
15.8

Calculate the capacity of the system


2 Calculate cooling capacity of the system based on table1 5.

Total capacity of indoor unit (COOLING) = {3.6(kW)x6(units)}+{4.0(kW)x3(units)} = 33.6(kW)... 2


3 Calculate the cooling capacity of OUTDOOR UNIT
Refer to CAPACITY TABLE of OUTDOOR UNIT
Please find the outdoor unit capacity TC.
Outdoor unit capacity = 33.0 (kW) ... 3

OUTDOOR
UNITS

OUTDOOR
UNITS

Enter the total capacity of indoor unit ( 2 ) and given designed indoor and outdoor air temperature.

Calculate the actual capacity for individual indoor unit


Calculate according to the following formulas.

4 Calculate the individual indoor unit actual capacity of system.


Actual capacity

= Cooling Capacity 3 x (Indoor unit capacity

-a / Total capacity

) x Ratio

Capacity of AU12 = 33.0 x (3.60 / 33.6) = 3.54(kW)


Capacity of AR14 = 33.0 x (4.00 / 33.6) = 3.93(kW)
Ratio : Ratio of capacity based on Piping Length / 100
(Reference the capacity ratio of REFRIGERANT PIPING LENGTH COMPENSATION CURVE)
If the actual capacity is less than load of room,select the unit again as exceed to load.
Note : Select the optimum size units and make sure not to select oversized units.

3-10 REFRIGERANT PIPING LENGTH COMPENSATION CURVE


CAPACITY RATIO OF COOLING OPERATION
100

70
OUTDOOR
UNITS

Capacity ratio (%)

80

60
50
7.5 10

20

30

40

50
60
Pipe length (m)

70

80

90

100

CAPACITY RATIO OF HEATING OPERATION


100
90

Capacity ratio (%)

OUTDOOR
UNITS

90

80
70
60
50
7.5 10

20

30

40

50
60
Pipe length (m)

70

80

90

100

These datas are under the rated standard condition.

- (03 - 18) -

3-11 OPERATION RANGE


AO90
Cooling

20
18
10

-10 -5

0
10
20
30
Outdoor temperature( CDB)

40

Heating
40
30 C or less

30

20

10
0
-20 -15 -10
0
10
20 21
Outdoor temperature( CDB)

30

- (03 - 19) -

50 52

60

OUTDOOR
UNITS

Indoor temperature( CDB)

32

30

0
-20

Indoor temperature( CDB)

OUTDOOR
UNITS

40

3-12 SOUND LEVEL


OVERALL

OUTDOOR
UNITS

AO 90

VOLTAGE

SOUND LEVEL

380V

55 dB (A)

415V

57 dB (A)

OUTDOOR
UNITS

MODEL

SOUND LEVEL CHECK POINT

1m

1m

MIC
1.5m

Front
Rear

- (03 - 20) -

OCTAVE-BAND LEVEL
MODEL : AO90
80

70

60

NC-60

NC-55
50

OUTDOOR
UNITS

Octave band sound pressure level,dB:(0dB=0.0002bar)

OUTDOOR
UNITS

NC-65

NC-50

NC-45
40

NC-40

NC-35
30

NC-30

NC-25
20
NC-20

NC-15
10

0
63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency, Hz

- (03 - 21) -

3-13 ELECTRIC CHARACTERISTICS


MODEL NAME

AO90MPBMF

W
FREQUENCY
VOLTAGE

min / MAX

RATED LOAD CURRENT

RLC

MAX. LOAD CURRENT

MLC

MAX. LOAD INPUT

MLI

MAX. FUSE AMP.

FS

STARTING CURRENT

SC

50

Hz

RATED

4W

380 - 415

min.342 / MAX.456
16.2

30
14.8

kW

40

75

COMP

Rated Load Amp.

RLA

3.9/7.5/10

RESSOR

MOTOR OUTPUT

MO

kW

1.52/3.35/4.93

RLC is based on follwing standard condition.


Indoor : 27 C DB/19 C WB
Outdoor : 35 C DB
MLC is based on the value of using maximum operation range.
To select electrical equipment and wire size, caluculate follwing method.
To select electrical circuit breaker, refer to the value of FS.
EX)
FS RLC S *
S : Safety Factor 2.25

Caution

Safety Factor is depend on the wiring regulation of each regions.

3-14 SAFETY DEVICES SETTING


MODEL NAME

AO90MPBMF

250V 6.3A

PCB FUSE

COMPRESSOR

INTERNAL
PROTECTOR

RELIEF VALVE

COMP.1

130 C ON
61 C OFF

21A
in 3-10sec

COMP.2

135 C ON
61 C OFF

40A
in 3-10sec

COMP.3

120 C ON
61 C OFF

60A
in 3-10sec

Pd-Ps 2.99MPa

HIGH PRESSURE PROTECTION


FAN MOTOR
THERMAL PROTECTOR
REMARKS

3.3MPa OFF

130 C 5 C OFF
83 C ON
REVERSE PHASE BLOCK

- (03 - 22) -

OUTDOOR
UNITS

OUTDOOR
UNITS

POWER
SUPPLY

R407C

TM

SERIES

4 . INDOOR UNIT

4-1. MODEL LINE UP


LINE UP
11 types, 41models ranging from 2.15kW to 17.0kW.
Type

Cassette Cassette Cassette


(compact)

(kW)

Model code

17.0

60

14.1

54

12.7

45

10.5
8.8

36
30

7.05

25

6.8

24

5.7

20

5.3

18

4.05

14

3.6

12

2.8

2.15

Duct

(compact)

Duct

(compact)

Universal

Duct

Duct

(High Static Floor/Ceiling


Pressure)

Ceiling

Wall
mounted
(compact)

Wall
Ceiling wall
mounted

INDOOR

INDOOR
UNIT

Capacity

MODEL CHANGE CODE : C, D


APPLICABLE OUTDOOR UNIT
Model

Type

Refrierant type

COOLING ONLY

R22

AO90APCMF , AO72APCMF
AO90RPCMF , AO72RPCMF

HEAT PUMP
COOLING ONLY
HEAT PUMP

R407C

MODEL CHANGE CODE

AO90EPCMF , AO72EPCMF

MODEL CHANGE CODE : C

AO90TPCMF , AO72TPCMF

HEAT RECOVERY

AO90MPBMF

MODEL CHANGE CODE : B

MODEL DESIGNATION
1

TYPE
AB : LARGE CEILING
OR UNIVERSAL
(FLOOR/CEILING)
AR : DUCT
AU : CASSETTE
AS : WALL MOUNTED
AW : CEILING WALL

MARKET REGION
BLANK : 380-415V 50Hz
G
: 380-415V 50Hz
Y
: 380-415V 50Hz

10

MODEL CODE

7
9
12
14
18
20
24
25
30
36
45
54
60

FUNCTION
TYPE

CONTROL METHOD
(REMOTE CONTROL)

T: Standard
F : FREE
H: High static
pressure

MODEL CHANGE
CODE
A: 2000 - 2002
B:
C: 2003 D: 2005 (AS7-14)

- (04 - 01) -

MULTI F TYPE

4-2 FEATURE
4-2-1 UNIVERSAL FLOOR / CEILING TYPE
MODELS : AB12, AB14, AB18, AB24

FEATURES
Compact design
Symmetrical thin and compact design
Flat and round form

INDOOR
UNIT

INDOOR
UNIT

Flexible installation

CEILING

FLOOR

Combination of up/down and right/left air


direction swing allows three-dimensional air
direction control.
Since up/down air direction flaps operate
automatically, according to the operating
mode of the unit, it is possible to set the air
direction based on the operating mode.

RIGHT and LEFT

UP and DOWN

swing
swing

Double auto swing

Swing
Steps

5 steps selectable

4 steps selectable

Super vane
The double-flap "Super Vane" with newly
developed special configuration boosts
the air flow, sending cool air quickly to
every corner of the room.

Others
Auto Restart
Detachable and Washable Open Panel

New model

Old model

Non-operation mode

Auto Shut Flaps

- (04 - 02) -

Operation mode

4-2-2 LARGE CEILING TYPE


MODELS : AB30, AB36, AB45, AB54

FEATURES
Installation
WALL MOUNTED

(for high-ceilinged room)

OUTDOOR

INDOOR

Wide air flow

INDOOR
UNIT

CONCEALED

INDOOR
UNIT

OPEN SPACE

Fresh-air intake

Slender shape
A slender shape with curves harmonizes
perfectly with the room interior.

Wide air flow

Drain lift-up mechanism

Slender

Long-life filter

High efficiency long-life filter that extends the cleaning


cycle up to 2 times that of the current model is standard.

Optional drain lift-up mechanism


allows more flexible installation.

Filter

Double auto swing


VERTICAL

HORIZONTAL

SW

IN

SWING

Others

Option parts

Auto Restart

Drain water rizer kit

Detachable and Washable Open Panel

- (04 - 03) -

UTR-DPB241

4-2-3. COMPACT DUCT TYPE


MODELS : AR7, AR9, AR12, AR14, AR18

FEATURES
Ultra-thin duct air conditioner for easy installation

INDOOR
UNIT

INDOOR
UNIT

Compact design
Low noise level
Low noise level is realized for each capacity.

MODEL CODE
Static pressure

Pa

(Normal/Max.)

12

14

18

0 / 39.6

Volume of air-flow m 3 / h
340/290 420/360 460/380 640/480 750/640
(High/Low)
Noise level
(Low speed)

dB(A)

26

31

Easy to install (universal type)


Ceiling concealed

26

30

33

Installation example

Floor concealed

Filter (Accessory)

Others
Auto restart

Filter

Air intake from rear or bottom side

Option parts

- (04 - 04) -

Remote sensor kit

UTD-RS100

IR receiver unit

UTB-YWA

4-2-4. DUCT TYPE


MODELS : AR25, AR30, AR36, AR45
Installed behind the ceiling (or with a double
ceiling for existing rooms) this design offers
space savings and low noise.
One indoor unit can condition the air of
multiple rooms. With a beautiful finish, the
outlet grille does not stick out into the room.

FEATURES
Ultra thin models for very low ceilings

Flexible installation
Suspended installation
INDOOR
UNIT

INDOOR
UNIT

27cm

Hanger bolts

Piping can be laid in almost any


direction.

Direct installation

Anchor bolts

DRAIN
PORT
CONTROL
BOX

Fresh air can be taken in from


two directions.

Sample installation / Installation style

Rear
Bottom

Sample installation

Air intake
opening

Duct

Air outflow
opening

Installation styles
Embedded in Ceiling

Hanging from Ceiling

Embedded in Ceiling

Hanging from Ceiling

Others
Auto Restart

Option parts
Flange ( square )

UTD-SF045T

Flange ( round )

UTD-RF204

Flexible duct

UTD-RD202

Long life filter

UTD-LF270

Remote sensor kit UTD-RS100


IR receiver unit

UTB-YWA
- (04 - 05) -

4-2-5. HIGH STATIC PRESSURE DUCT TYPE


MODELS : AR36H, AR45H, AR60H

Installed behind the ceiling this design


offers s pace savings and low noise.
One indoor unit can condition the air of
multiple rooms.
With a beautiful finish, the outlet does
not stick out into the room.

FEATURES
Easy maintenance
Fan motor maintenance can be performed
from the top and the bottom.

Recommended external static pressure : 196 Pa


(Max. 300Pa)

Top access

AIR FLOW
Bottom access

Easy maintenance

Installation example

Control Box Cover


(Electrical parts access)

Maintenance Panel
(Thermistor access)

Maintenance Panel
(Fan motor access)

Optional parts

Others

Flange ( square )

UTD-SF045T

Flange ( round )

UTD-RF204

Outlet chamber

UTD-BC200

Flexible duct

UTD-RD202

Long life filter

UTD-LF400

Remote sensor kit

UTD-RS100

IR receiver unit

UTB-YWA

Auto Restart

- (04 - 06) -

INDOOR
UNIT

INDOOR
UNIT

High static pressure

4-2-6. COMPACT CASSETTE TYPE


MODELS : AU7, AU9, AU12, AU14, AU18

Applicable grille unit:


UTG-UD

D-W

FEATURES
Flat & simple design

This compact air conditioner can be fit


to ceiling tiles (600 x 600mm)

INDOOR
UNIT

INDOOR
UNIT

Compact Design

570mm

FLAP
245mm
20mm

Plastic flap with no velvet coating


Fit to ceiling tiles (600mm x 600mm)

Adjustable grill
Adjustment to ceiling design
Current model

New model

Plastic Flap with no Velvet Coating

Auto Air Frow Direction and Auto Swing

4-way air flow system


You can select 2-way, 3-way or 4-way air flow to
suit your needs.

4-step swing

4-step swing

- (04 - 07) -

Easy maintenance
By putting the Electrical Component box inside the unit, we realized easy maintenance.

Simple maintenance

Detachable, washable
air intake grille

Wide opening for easy


maintenance.

ELECTRICAL COMPONENT BOX (built-in)

Ceiling

INDOOR
UNIT

Airflow range
Airflow at floor level is increased by chainging the air velocity.
(m)
3

UNIT:m/s

6
4

2
1

23 C

21 C

0
7

0.55
0.5

6 (m)

Low noise
Large air volume and low noise achieved by large diameter variable pitch Turbo
Fan( 298mm) and 7 evaporator.
New fan (7 blades)
298

INDOOR
UNIT

By putting the P.C. board


inside the unit, we realized
easy maintenance.

(Unit : mm)

298mm, 7 blades,variable pitch Fan

By reducing the noise level of arround 100Hz, we realized to reduce the harsh grating noise
in actual hearing.

Light weight & easy installation

Drain water pipe lifted


to 400mm

Body : 18kg

Auto Restart
Auto Shut Flaps

Panel : 2.2kg

Bolt
New Model

Others

Old Model

- (04 - 08) -

4-2-7 CASSETTE TYPE (Slim body)


MODELS : AU20, AU25, AU30

Setting space
Model

AU20, AU25, AU30

Height

200 or 235

Width

830

Depth

830

Width
940

200 mm

Standard setting

Slender setting

Improved noise level and air distribution


Noise level is lowered dramatically.

Improved turbo fan shape (aerodynamic design)


Expanded air distribution
Low internal resistance
Molded fan motor

Improvement of fan blade


Old fan (13 blades)

(Unit : mm)

129.5

(Unit : mm)

Wide air flow


Larger air flap distributes the outlet air flow a longer distance in the horizontal direction.
New model

Old model

- (04 - 09 ) -

450

350.5

420

320

New fan (7 blades)

INDOOR
UNIT

Depth

Small and compact body


allows space saving installation.
New mechanism allows the
cassette body to move 35mm
downward and contributes to
keeping the ceiling surface clean.

235 mm

INDOOR
UNIT

Flexible installation

940

Height

FEATURES

4-2-7 CASSETTE TYPE


MODELS : AU36, AU45, AU54

Height

FEATURES

Model

AU36, AU45, AU54

Height

250 or 285

Width
Depth

830
830

Width

250 mm

285 mm

940

Standard setting

Slender setting

Improved noise level and air distribution


Comparison of noise level (dB)
Noise level is lowered dramatically.

Improved turbo fan shape (aerodynamic design)


Expanded air distribution
Low internal resistance
Molded fan motor

Improvement of fan blade


Old fan (13 blades)

450

420

350.5

New fan (7 blades)

(Unit : mm)

(Unit : mm)

Wide air flow


Larger air flap distributes the outlet air flow a longer distance in the horizontal direction.
Old model

New model

- (04 - 10) -

INDOOR
UNIT

Setting space

940

Depth

Small and compact body


allows space saving installation.
New mechanism allows the
cassette body to move 35mm
downward and contributes to
keeping the ceiling surface clean.

320

INDOOR
UNIT

Flexible installation

Auto air flow direction and auto swing

Harmonized design

Swing
Steps

Simple maintenance
Control box is installed in the
grille for easy maintenance.
Wide opening facilitates
maintenance.

Wide opening and


Long-Life Filter.

4 steps swing

4 steps swing

Detachable,
washable air
intake grille

Long-life filter
High efficiency long-life
filter that extends the
cleaning cycle up to 2
times that of the current
model is mounted as
standard.

4-way air flow system

Long-life filter

INDOOR
UNIT

INDOOR
UNIT

2-way

3-way
4-way

Air flow volume can be switched


High ceiling mode (air flow up) and low-noise (air flow down) can be switched
according to the height of the ceiling and other conditions by means of a PCB DIP switch.

Duct connection hole opening


Fresh air can be introduced through this opening.

Conditioned air can be distributed by means of a


distribution duct.
Two-way

Distribution duct

Fresh air

Distribution duct

One-way

Drain water pipe lifted


to 800mm
800mm

Others
Auto Restart
Auto Shut Flaps

- (04 - 11) -

New grill design


Symmetrical design
New "Punch hole" grill harmonizes
with any interior design, even when
several units are installed in one room.

Easy cleaning
Auto-shut flap without velvet coating

INDOOR
UNIT

Thin type grill

INDOOR
UNIT

Thin grill, auto-close flaps without


velvet coating and flat surface
allow easy cleaning.

Easy installation
Since the cassette body can be installed using a grill frame, it is easy to fit in the ceiling surface.

Thin type grill

Grill frame

Detailed setting

Drain water pipe lifted


to 800mm
800mm

Others
Auto Restart
Auto Shut Flaps

- (04 - 12) -

4-2-8 WALL MOUNTED TYPE


MODELS : AS18, AS24, AS30
Vertical and horizontal symmetrical
design matched to the interior decor
Easy-to-read center display
Big wide flaps with a powerful image

FEATURES
Fine symmetry design

INDOOR
UNIT

INDOOR
UNIT

H320 x W1,120 x D220 (mm)

Big wide flaps with a powerful image

Vertical and horizontal symmetrical


design matched to the interior decor

Easy-to-read center display

Low-noise

Multi air flow

High efficiency fan construction


7mm Lambda type evaporator improves
the airflow path
Large air diffuser

Large independently driven power diffusers used


Heating: Wide down flow
Cooling: Horizontal concentration and other air
direction control
Cooling

7 lambda type evaporator

Large
independently
driven
power diffuser

1
2

Large air diffuser

Large independently
driven power diffuser

Horizontal concentration
and other air direction control

Steps

Heating

Swing

Other features include continuation


of the functions of the existing wall
mounted type.

Wide down flow

2
3

Double auto swing


2-way draining route

Others

Easier installation

Auto Restart

Expanded work space at bottom of casing


Increases piping space by 15%

Double auto swing


Increases piping
space by 15%

- (04 - 13) -

4-2-9 CEILING WALL TYPE


MODELS : AW7, AW9, AW12, AW14, AW18, AW24, AW30

FEATURES
Large & wide airflow
0 (m)
1

Large, wide airflow

Floor level heating


0 (m)

1
2

4
5

0 (m)
1

2
3

5
6

4
5

2
3

4
5

1
2
5
6

3
4
5
6

0 (m)

0 (m)

0 (m)

High efficiency

Large center display

High output and high efficiency are achieved by


using a DC motor.

Color - coding the operation state


lets you check the unit's operation
status at a glance.

7High efficiency
heat exchanger

Cool/Dry/Fan

High efficiency
DC motor

Heat

Easy maintenance
One-touch long-life filter.

Low noise
Suppressing the turbulence by providing vertical
grooves on the quiet louver and the right/left louver
reduces annoying noise. Large airflow and low noise
achieved by top air intake.

Existing louver

New quiet louver

Outlet louver
reduces
annoying noise

Removable,
washable drain pan.

Others
Auto Restart

Double auto swing


- (04 - 14) -

INDOOR
UNIT

INDOOR
UNIT

Horizontal cooling

4-3 SPECIFICATIONS
4-3-1 UNIVERSAL FLOOR / CEILING TYPE
AB12

AB14

Power

220-240V

AB24

50Hz

[kW]

3.50

4.05

5.30

6.60

[BTU/h]

11,900

13,800

18,100

22,500

[kW]

4.10

5.00

5.60

7.70

[BTU/h]

14,000

17,100

19,100

26,300

Input

[W]

57

57

88

88

Current

[A]

0.25

0.25

0.38

0.38

Max Current

[A]

0.30

0.30

0.45

0.45

640

640

770

900

560

560

680

780

Low

480

480

560

660

High

850

850

1,030

1,180

760

760

890

1,040

670

670

770

900

16

16

30

40

40

40

46

49

37

37

41.5

45

34

34

37

41

Cooling capacity

Heating capacity

High
INDOOR
UNIT

AB18

Air Circulation

Fan Speed

Med

Med

[m 3/h]

[r.p.m.]

Low
Fan Motor Output

[W]
High

Noise Level
(Sound Pressure)

Med

[dB (A)]

Low
Fan Type x Q'ty

Sirocco x 2

Heat Exchanger

Plate Fin Coil

Dimensions

Net

(H x W x D)

Gross

Weights

Pipe size

Net
Gross
Liquid
Gas

199 x 990 x 655

[mm]

[kg]

[mm]

320 x 1,150 x 790


28

28

28

30

37

37

37

39

6.35

6.35

12.70

15.88

Pipe Connection Method


Operation Range

Cooling
Heating

Flare
18 to 30

[C]

16 to 30

- (04 - 15) -

INDOOR
UNIT

Model

4-3-2 LARGE CEILING TYPE


AB30

Power

AB45

220-240V

AB54

50Hz

[kW]

8.80

10.5

12.7

14.1

[BTU/h]

30,000

36,000

43,500

48,200

[kW]

9.10

10.7

13.7

15.8

[BTU/h]

31,000

36,500

47,000

54,000

Input

[W]

124

144

160

180

Current

[A]

1.14

1.16

1.17

1.17

Max Current

[A]

1.36

1.39

1.40

1.40

1,620

1,890

2,110

2,350

1,540

1,710

1,890

2,180

Low

1,360

1,450

1,630

1,900

High

850

1,000

1,100

1,250

800

900

1,000

1,150

700

750

850

1,000

Cooling capacity

Heating capacity

High
INDOOR
UNIT

AB36

Air Circulation

Fan Speed

Med

Med

[m 3/h]

[r.p.m.]

Low
Fan Motor Output
High
Noise Level
(Sound Pressure)

160

[W]

Med

[dB (A)]

Low

41.5

47

50

52

38

44

48

50

34.5

39

44

46

Fan Type x Q'ty

Sirocco x 4

Heat Exchanger

Plate Fin Coil

Dimensions

Net

(H x W x D)

Gross

Weights

Pipe size

Net
Gross
Liquid
Gas

240 x 1,660 x 700

[mm]

[kg]

[mm]

318 x 1,800 x 790


48

48

48

48

61

61

61

61

9.52
15.88

Pipe Connection Method


Operation Range

Cooling
Heating

19.05
Flare
18 to 30

[C]

16 to 30

- (04 - 16) -

INDOOR
UNIT

Model

4-3-3 COMPACT DUCT TYPE


AR7

AR9

AR12

220-240V

Power

AR14

AR18

50Hz

[kW]

2.15

2.80

3.50

4.00

5.30

[BTU/h]

7,300

9,600

11,900

13,700

18,100

[kW]

2.45

3.10

4.10

4.80

5.60

[BTU/h]

8,400

10,600

14,000

16,400

19,100

Input

[W]

40

43

34

50

62

Current

[A]

0.21

0.21

0.20

0.23

0.27

Max Current

[A]

0.25

0.25

0.24

0.27

0.32

340

420

460

640

750

320

390

430

560

700

Low

290

360

390

480

640

High

780

960

640

840

960

720

880

610

740

900

660

810

580

650

840

12

14

16

18

21

31

35

28

34

36

28

33

27

32

35

26

31

26

30

33

Cooling capacity

Heating capacity

High
INDOOR
UNIT

Air Circulation

Fan Speed

Med

Med

[m 3/h]

[r.p.m.]

Low
Fan Motor Output

[W]
High

Noise Level
(Sound Pressure)

Med

[dB (A)]

Low

Fan Type x Q'ty

Sirocco x 1

Heat Exchanger

Plate Fin Coil

Dimensions

Net

(H x W x D)

Gross

Weights

Pipe size

Net
Gross
Liquid
Gas

[mm]

[kg]

[mm]

217 x 663 x 595

217 x 953 x 595

324 x 785 x 686

324 x 1,075 x 686

18

25

22

29
6.35

Cooling
Heating

6.35

9.52

Pipe Connection Method


Operation Range

Sirocco x 2

12.70
Flare
18 to 30

[C]

16 to 30

- (04 - 17) -

15.88

INDOOR
UNIT

Model

4-3-4. DUCT TYPE


AR25

AR30

Power

AR36

220-240V

AR45

50Hz

[kW]

7.05

8.80

10.5

12.7

[BTU/h]

24,100

30,000

36,000

43,500

[kW]

7.85

9.10

10.7

13.7

[BTU/h]

26,800

31,000

36,500

47,000

Input

[W]

155

240

265

315

Current

[A]

0.68

1.06

1.16

1.44

Max Current

[A]

0.84

1.58

1.58

1.84

1,200

1,650

2,000

2,200

1,100

1,550

1,800

2,000

Low

1,000

1,350

1,600

1,800

High

890

1,240

1,280

1,320

820

1,140

1,200

1,270

745

1,040

1,130

1,200

Cooling capacity

Heating capacity

High
INDOOR
UNIT

Air Circulation

Fan Speed

Med

Med

[m 3/h]

[r.p.m.]

Low
Fan Motor Output

[W]
High

Noise Level
(Sound Pressure)

Med

[dB (A)]

Low

70

275

44

47

47

49

42

45

45

47

40

43

43

45

Fan Type x Q'ty

Sirocco x 2

Heat Exchanger

Plate Fin Coil

Dimensions

Net

(H x W x D)

Gross

Weights

Pipe size

Net
Gross
Liquid
Gas

270 x 1,210 x 700

[mm]

[kg]

[mm]

330 x 1,300 x 790


43

43

45

45

53

53

55

55

9.52

6.35

15.88

Pipe Connection Method


Operation Range

Cooling
Heating

19.05
Flare
18 to 30

[C]

16 to 30

- (04 - 18) -

INDOOR
UNIT

Model

4-3-5 HIGH STATIC PRESSURE DUCT TYPE


AR36H

AR45H
220-240V

Power

AR60H
50Hz

[kW]

10.5

12.7

17.0

[BTU/h]

36,000

43,500

58,000

[kW]

10.7

13.7

17.6

[BTU/h]

36,500

47,000

60,100

Input

[W]

445

463

733

Current

[A]

2.35

2.35

3.58

Max Current

[A]

3.02

3.02

4.81

2,000

2,200

3,000

1,700

1,900

2,750

Low

1,400

1,600

2,500

High

760

890

1,150

690

820

1,075

630

760

1,000

Cooling capacity

Heating capacity

High
INDOOR
UNIT

Air Circulation

Fan Speed

Med

Med

[m 3/h]

[r.p.m.]

Low
Fan Motor Output

[W]
High

Noise Level
(Sound Pressure)

Med

[dB (A)]

Low

350

500

47

48

53

45

46

52

43

44

51

Fan Type x Q'ty

Sirocco x 2

Heat Exchanger

Plate Fin Coil

Dimensions

Net

(H x W x D)

Gross

Weights

Pipe size

Net
Gross
Liquid
Gas

400 x 1,250 x 800

[mm]

500 x 1,430 x 930


75

[ kg ]

90
9.52

[mm]

19.05

Pipe Connection Method


Operation Range

Cooling
Heating

Flare
18 to 30

[C]

16 to 30

- (04 - 19) -

INDOOR
UNIT

Model

4-3-6 COMPACT CASSETTE TYPE

AU7

Model

AU9

Power

AU12
220-240

AU14

AU18

50Hz

[kW]

2.15

2.80

3.60

4.00

5.00

[BTU/h]

7,400

9,600

12,300

13,700

17,100

[kW]

2.45

3.10

4.10

4.50

5.45

[BTU/h]

8,400

10,600

14,000

15,400

18,600

Cooling capacity

Input

[W]

28

28

52

52

50

Current

[A]

0.13

0.13

0.23

0.23

0.22

Max Current

[A]

0.15

0.15

0.27

0.27

0.26

530

530

580

580

640

480

480

520

520

540

Low

410

410

460

460

470

High

630

630

690

690

750

570

570

610

610

640

480

480

540

540

540

High
Air Circulation

Fan Speed

Med

Med

[m 3/h]

[r.p.m.]

Low
Fan Motor Output

[W]
High

Noise Level
(Sound Pressure)

Med

[dB (A)]

Low

9
38

38

41

41

44

35

35

37

37

38

31

31

34

34

35

Fan Type x Q'ty

Turbo x 1

Heat Exchanger

Plate Fin Coil

Dimensions

Net

(H x W x D)

Gross

Weights

230 x 570 x 570

[mm]

280 x 710 x 750

Net

18

[kg]
Gross

Pipe size

23

Liquid

6.35

[mm]
9.52

Gas
Pipe Connection Method
Operation Range

15

10

12.70
Flare

Cooling

18 to 30
[C]

Heating

16 to 30

- (04 - 20) -

15.88

INDOOR
UNIT

INDOOR
UNIT

Heating capacity

4-3-7 CASSETTE TYPE


AU20

220-240V

Power

AU30
50Hz

[kW]

5.70

7.05

8.80

[BTU/h]

19,500

24,100

30,000

[kW]

5.80

7.85

9.10

[BTU/h]

19,800

26,800

31,100

Input

[W]

104

124

140

Current

[A]

0.60

0.64

0.67

Max Current

[A]

0.72

0.77

0.80

1,000

1,100

1,200

840

940

1,050

Low

700

780

840

High

450

490

540

390

430

480

330

360

390

Cooling capacity

Heating capacity

High
INDOOR
UNIT

AU25

Air Circulation

Fan Speed

Med

Med

[m 3/h]

[r.p.m.]

Low
Fan Motor Output

[W]
High

Noise Level
(Sound Pressure)

Med

[dB (A)]

Low

42
42

44

46

38

42

44

35

39

41

Fan Type x Q'ty

Turbo x 1

Heat Exchanger

Plate Fin Coil

Dimensions

Net

(H x W x D)

Gross

Weights

Pipe size

Net
Gross
Liquid
Gas

246 x 830 x 830

[mm]

385 x 1,045 x 1,015


34

[ kg ]

45
6.35

[mm]

15.88

Pipe Connection Method


Operation Range

Cooling
Heating

9.52

Flare
18 to 30

[C]

16 to 30

- (04 - 21) -

INDOOR
UNIT

Model

4-3-7 CASSETTE TYPE


AU36

220-240V

Power

AU54
50Hz

[kW]

10.5

12.7

14.1

[BTU/h]

35,800

43,400

48,100

[kW]

10.7

13.7

15.8

[BTU/h]

36,500

46,800

53,900

Input

[W]

175

190

219

Current

[A]

0.92

0.94

0.95

Max Current

[A]

1.10

1.12

1.14

1,500

1,650

1,780

1,300

1,450

1,550

Low

1,100

1,200

1,300

High

580

620

680

500

550

580

420

470

500

Cooling capacity

Heating capacity

High
INDOOR
UNIT

AU45

Air Circulation

Fan Speed

Med

Med

[m 3/h]

[r.p.m.]

Low
Fan Motor Output

[W]
High

Noise Level
(Sound Pressure)

Med

[dB (A)]

Low

90
48

49

52

44

47

48.5

41

43

45

Fan Type x Q'ty

Turbo x 1

Heat Exchanger

Plate Fin Coil

Dimensions

Net

(H x W x D)

Gross

Weights

Pipe size

Net
Gross
Liquid
Gas

296 x 830 x 830

[mm]

435 x 1,045 x 1,015


40

[ kg ]

53
9.52

[mm]

19.05

Pipe Connection Method


Operation Range

Cooling
Heating

Flare
18 to 30

[C]

16 to 30

- (04 - 22) -

INDOOR
UNIT

Model

4-3-8 WALL MOUNTED TYPE


AS18

AS24
220-240V

Power
[kW]

Cooling capacity

[BTU/h]
[kW]

Heating capacity

50Hz

6.90

18,400

23,600

5.60

7.80

8.00
27,300
8.80

[BTU/h]

19,100

26,600

30,000

Input

[W]

38

50

60

Current

[A]

0.18

0.24

0.28

Max Current

[A]

0.22

0.29

0.34

840

950

1,050

700

800

940

Low

600

670

780

High

1,080

1,190

1,320

940

1,030

1,210

810

900

1,030

High
INDOOR
UNIT

5.40

AS30

Air Circulation

Fan Speed

Med

Med

[m 3/h]

[r.p.m.]

Low
Fan Motor Output

[W]
High

Noise Level
(Sound Pressure)

Med

[dB (A)]

Low

38
42

45

48

39

42

45

35

38

42

Fan Type x Q'ty

Cross Flow x 1

Heat Exchanger

Plate Fin Coil

Dimensions

Net

(H x W x D)

Gross

Weights

Pipe size

Net
Gross
Liquid
Gas

320 x 1,120 x 220

[mm]

348 x 1,240 x 427


16

[ kg ]

22
6.35

[mm]

15.88

Pipe Connection Method


Operation Range

Cooling
Heating

9.52

Flare
18 to 30

[C]

16 to 30

- (04 - 23) -

INDOOR
UNIT

Model

4-3-9 CEILING WALL TYPE

AW7

Power

220-240V

Cooling capacity

Heating capacity

INDOOR
UNIT

AW9

AW12

50Hz

[kW]

2.15

2.80

3.60

[BTU/h]

7,400

9,600

12,300

[kW]

2.45

3.10

4.10

[BTU/h]

8,400

10,600

14,000

Input

[W]

16

19

20

Current

[A]

0.08

0.09

0.10

Max Current

[A]

0.10

0.11

0.12

380

480

600

330

420

520

Low

290

390

470

High

1,090

1,310

950

980

1,180

860

900

1,100

800

High
Air Circulation

Fan Speed

Med

Med

[m 3/h]

[r.p.m.]

Low
Fan Motor Output

[W]
High

Noise Level
(Sound Pressure)

Med

[dB (A)]

Low

32
34

35

35

32

32

33

30

31

31

Fan Type x Q'ty

Cross Flow x 1

Heat Exchanger

Plate Fin Coil

Dimensions

Net

(H x W x D)

Gross

Weights

Pipe size

Net
Gross
Liquid
Gas

270 x 1,150 x 285

[mm]

400 x 1,260 x 380


16

[kg]

20
6.35

[mm]

9.52

Pipe Connection Method


Operation Range

Cooling
Heating

12.70
Flare
18 to 30

[C]

16 to 30

- (04 - 24) -

INDOOR
UNIT

Model

4-3-10 CEILING WALL TYPE

AW14

AW18

Power

220-240V

Cooling capacity

Heating capacity

INDOOR
UNIT

AW24

AW30

50Hz

[kW]

4.30

5.40

6.90

8.00

[BTU/h]

14,700

18,400

23,600

27,300

[kW]

4.90

5.60

7.80

8.80

[BTU/h]

16,700

19,100

26,600

30,000

Input

[W]

21

30

40

50

Current

[A]

0.10

0.14

0.19

0.24

Max Current

[A]

0.12

0.17

0.23

0.29

650

760

900

950

570

660

780

870

Low

490

560

650

780

High

1,000

1,150

1,300

1,380

910

1,030

1,160

1,280

820

930

1,020

1,180

High
Air Circulation

Fan Speed

Med

Med

[m 3/h]

[r.p.m.]

Low
Fan Motor Output

[W]
High

Noise Level
(Sound Pressure)

Med

[dB (A)]

Low

32
37

40

44

47

35

37

41

45

32

34

37

42

Fan Type x Q'ty

Cross Flow x 1

Heat Exchanger

Plate Fin Coil

Dimensions

Net

(H x W x D)

Gross

Weights

Pipe size

Net
Gross
Liquid
Gas

270 x 1,150 x 285

[mm]

400 x 1,260 x 380


16

[kg]
[mm]

20

12.70

Pipe Connection Method


Operation Range

Cooling
Heating

9.52

6.35

15.88
Flare
18 to 30

[C]

16 to 30

- (04 - 25) -

INDOOR
UNIT

Model

4-4. ELECTRIC CHARCTERISTICS


UNIVERSAL FLOOR/CEILING TYPE
Model Name
AB

12
14
18
24

Voltage Frequency
(V)
(Hz)
220-240

50

Input
(W)
57
57
88
88

Current
(A)
0.25
0.25
0.38
0.38

Max Crrent
(A) (MLC)
0.30
0.30
0.45
0.45

Input
(W)
124
144
160
180

Current
(A)
1.14
1.16
1.17
1.17

Max Crrent
(A) (MLC)
1.36
1.39
1.40
1.40

Input
(W)
40
43
34
50
62

Current
(A)
0.21
0.21
0.20
0.23
0.27

Max Crrent
(A) (MLC)
0.25
0.25
0.24
0.27
0.32

Input
(W)
155
240
265
315

Current
(A)
0.68
1.06
1.16
1.44

Max Crrent
(A) (MLC)
0.84
1.58
1.58
1.84

LARGE CEILING TYPE

INDOOR
UNIT

AB

30
36
45
54

Voltage Frequency
(V)
(Hz)
220-240

50

INDOOR
UNIT

Model Name

COMPACT DUCT TYPE


Model Name

AR

7
9
12
14
18

Voltage Frequency
(V)
(Hz)
220-240

50

DUCT TYPE
Model Name
AR

25
30
36
45

Voltage Frequency
(V)
(Hz)
220-240

50

HIGH STATIC PRESSURE DUCT TYPE


Model Name
AR

36H
45H
60H

Voltage Frequency
(V)
(Hz)
220-240

50

Input
(W)
445
463
733

Current
(A)
2.35
2.35
3.58

Max Crrent
(A) (MLC)
3.02
3.02
4.81

Input
(W)
28
28
52
52
50

Current
(A)
0.13
0.13
0.23
0.23
0.22

Max Crrent
(A) (MLC)
0.15
0.15
0.27
0.27
0.26

COMPACT CASSETTE TYPE


Model Name

AU

7
9
12
14
18

Voltage Frequency
(V)
(Hz)
220-240

50

- (04 - 26) -

CASSETTE TYPE
Input

Current

(W)

(A)

20

104

0.60

0.72

25

124

0.64

0.77

140

0.67

0.80

175

0.92

1.10

45

190

0.94

1.12

54

219

0.95

1.14

Input

Current

(W)

(A)

38

0.18

0.22

50

0.24

0.29

60

0.28

0.34

Input

Current

(W)

(A)

16

0.08

0.10

19

0.09

0.11

12

21

0.10

0.12

21

0.10

0.12

20

30

0.14

0.17

24

40

0.19

0.23

30

50

0.24

0.29

Model Name

AU

30
36

Voltage Frequency
(V)
(Hz)

220-240

50

Max Crrent
(MLC)
(A)

WALL MOUNTED TYPE

18
INDOOR
UNIT

AS

24

Voltage Frequency
(V)
(Hz)
220-240

50

30

Max Crrent
(MLC)
(A)

INDOOR
UNIT

Model Name

CEILING WALL TYPE

14

220-240

50

Max Crrent
(MLC)
(A)

FUSE AMP. Is calculated by follwing method.


FUSE AMP. (MLC of Indoor unit A + MLC of Indoor unit B

*)

AW

Voltage Frequency
(V)
(Hz)

Model Name

S : Safety Factor
According to country regulation

- (04 - 27) -

2)

FUSE AMP. = (0.45 + 1.58 + 0.27 + 0.77 + 0.12


Use 7.45 or more FUSE AMP. capacity

In case of 1system:AB18 1, AR30 1, AU14 1, AU25 1, AW14 2

EX)

2.25 = 7.45

4-5 DIMENSIONS
4-5-1 UNIVERSAL FLOOR / CELING TYPE
MODELS : AB12, AB14, AB18, AB24

(Unit : mm)

INDOOR
UNIT

INDOOR
UNIT

2
1
2

Left

Right

300 or more

3
1

Refrigerant piping flare connection (Gas)

Refrigerant piping flare connection (Liquid)

Drain piping connection (Drain pipe : I.D. 25 O.D. 29 L 700)

Knock out hole for drain piping

Knock out hole for refrigerant piping

Hole for lifting bolt (Use M10 screw bolt)

300 or more

990

Ceiling
Left

Indoor unit

500

245

Right

Wall bracket
Side of set

300 or more
Ceiling

65
100 hole

530

150 or more

655

50 hole

65

45

125
100 hole

20 or more

- (04 - 28) -

4-5-2 LARGE CEILING TYPE


MODELS : AB30, AB36, AB45, AB54

(Unit : mm)

INDOOR
UNIT

INDOOR
UNIT

Ceiling
INDOOR UNIT

Ceiling

80 or over

Suspension bolt pitch

30

150 or over

1,600

30

Dimensions
(Space Required
for Installation)
10
155

10 or over

INDOOR UNIT (TOP VIEW)

300

Ceiling panel
INDOOR UNIT

INDOOR UNIT
80 or over

Ceiling panel

150 or over

10 or over

Suspension bolt
should extend
outward 30 to 75.

Refrigerant piping flare connection (Gas)

Refrigerant piping flare connection (Liquid)

Drain piping connection (Drain pipe : I.D. 22 O.D. 25.6)

Knock out hole for fresh air

Knock out hole for refrigerant piping

Hole for lifting bolt (Use M10 screw bolt)

- (04 - 29) -

4-5-3. COMPACT DUCT TYPE


MODELS : AR7, AR9
(Unit : mm)

INDOOR
UNIT

INDOOR
UNIT

Rear view

Side view

Top view

Front view
Bottom view

Refrgerant pipe flare


connection

Drain pipe connection

Liquid
Gas
Drain pipe
- (04 - 30) -

AR7, AR9
6.35mm
9.52mm
I.D. 21.5mm ; O.D. 26mm

BIRD'S-EYE VIEW

INDOOR
UNIT

INDOOR
UNIT

MAINTENANCE HOLE

MOUNTING POSITION
Left
side

Strong and durable ceiling

Right
side

Indoor unit

100 mm
or more
Left
side

300 mm
or more
Right side
(PIPE side)

Strong and
durable floor
100 mm
or more

30mm

300 mm
or more

or more

- (04 - 31) -

30mm

or more

MODELS : AR12, AR14, AR18, AR22


(Unit : mm)

INDOOR
UNIT

INDOOR
UNIT

Rear view

Side view
Top view

Front view

Bottom view

AR12, AR14
6.35mm
12.70mm

Refrgerant pipe flare


connection

Liquid
Gas

Drain pipe connection

Drain pipe

- (04 - 32) -

I.D. 21.5mm ;

AR18, AR22
6.35mm
15.88mm
O.D. 26mm

BIRD'S-EYE VIEW

100 mm
or more

INDOOR
UNIT

INDOOR
UNIT

MAINTENANCE HOLE

300 mm
or more

MOUNTING POSITION

100 mm
or more

300 mm
or more

30mm

or more
- (04 - 33) -

30mm

or more

4-5-4. DUCT TYPE


MODELS: AR25, AR30, AR36, AR45

(Unit : mm)

Front view

INDOOR
UNIT

INDOOR
UNIT

Side view(L)

Side view(R)

Top view

Rear view

Bottom view

1
2
3
4
5

Refrgerant pipe flare


connection
Drain pipe connection
Knock out hole for fresh air

AR25
6.35mm
15.88mm

Liquid
Gas
Drain pipe
Drain pipe
with cap

AR30
9.52mm
15.88mm

I.D. 35.7mm , O.D. 38.1mm


-

- (04 - 34) -

AR36, AR45
9.52mm
19.05mm

MAINTENANCE HOLE
Reference B

500mm

300mm

Unit: (mm)

Service hole

Control box metal

Vertical dimension
500 mm from 50 mm below reference A
Horizontal dimension
600 mm from 300 mm from the left from reference B

INDOOR
UNIT

INDOOR
UNIT

600mm

50mm

Reference A

MOUNTING POSITION

300mm
or more

150mm
or more

WHEN USING A SQUARE DUCT

- (04 - 35) -

4-5-5. HIGH STATIC PRESSURE DUCT TYPE


MODELS : AR36H, AR45H, AR60H

(Unit : mm)

BRACKET
COUPLING PIPE ASSY

AIR FLOW OUTLET

AUX. PIPE

RECTANGULAR FLANGE

DRAIN PORT ( 38.5)


CONTROL BOX

295

Refrigerant piping flare connection (Gas)

Refrigerant piping flare connection (Liquid)

Drain piping connection (I.D. 36 O.D. 38)


359

1,300

40

138

600

103

40

1,250

38

395

295

45

483

800

710

134

1,063

SERVICE HOLE DIMENSIONS


Service hole

.
Open a service hole with the dimension
shown right.
Unit

100 mm
or more

Control box

- (04 - 36) -

500 mm
or more

INDOOR
UNIT

INDOOR
UNIT

1,063

4-5-6. COMPACT CASSETTE TYPE

570

230

35

(Unit : mm)

INDOOR
UNIT

INDOOR
UNIT

650

20

MODELS : AU7, AU9, AU12, AU14, AU18

570

245

650

(Grille measurement)
650
(Hanging bolt position)
400
1
2

46
86

245

54

41

126
111

(Hanging bolt position)


606

40

600
(Ceiling opening measurement)

100 or more

(4 directions)
(3 directions)
Piping position

100 or more

100 or more

(2 directions)

Refrgerant pipe flare


connection

Liquid
Gas

Drain pipe connection

Drain pipe

(2 directions)

100 or more

AU7, AU9
6.35mm
9.52mm

AU12, AU14
6.35mm
12.70mm
I.D. 32mm ;

- (04 - 37) -

O.D. 37mm

AU18
6.35mm
15.88mm

4-5-7. CASSETTE TYPE


MODELS : AU20, AU25, AU30

INDOOR
UNIT

INDOOR
UNIT

750

940

30

245

(Unit : mm)

298
248

200

100 or more

100 or more

(4 directions)
(3 directions)
Piping position

Refrgerant pipe flare


connection

Liquid
Gas

Drain pipe connection

Drain pipe

305

100 or more

(2 directions)
(2 directions)
100 or more

AU20, AU25
6.35mm
15.88mm
I.D. 32mm ;

- (04 - 38) -

AU30
9.52mm
15.88mm
O.D. 37mm

100
(Small pipe)

298
248

70
(Large pipe)

305

60
(Drain pipe)

100
(Small pipe)

Drain inside Dia. 32


outside Dia. 37

70
(Large pipe)

750

235

60
(Drain pipe)

940

MODELS : AU36, AU45, AU54

INDOOR
UNIT

INDOOR
UNIT

750

940

30

296

(Unit : mm)

750

100 or more

(4 directions)
(3 directions)
Piping position

100 or more

(2 directions)
(2 directions)
100 or more

Liquid

Refrgerant pipe flare


connection

Drain pipe connection

Drain pipe

100 or more

AU36, AU45, AU54


9.52mm
19.05mm

Gas

I.D. 32mm ;

- (04 - 39) -

O.D. 37mm

150

(Small pipe)

248

120

305

(Large pipe)

60

(Drain pipe)

298

250

150

(Small pipe)

248

2
120

305

(Large pipe)

298

285

60

(Drain pipe)

940
3

4-5-8. WALL MOUNTED TYPE


MODELS : AS18, AS24, AS30

INDOOR
UNIT

INDOOR
UNIT

(Unit : mm)

AS18, AS24
6.35mm
15.88mm

Refrgerant pipe flare


connection

Liquid
Gas

Drain pipe connection

Drain pipe

I.D. 17mm ; O.D. 24mm

- (04 - 40) -

AS30
9.52mm
15.88mm
L=670mm

4-5-9. CEILING WALL TYPE


MODELS : AW7, AW9, AW12, AW14, AW18,AW24, AW30

(Unit : mm)

285

270

1,150

600
2

690
INDOOR
UNIT

INDOOR
UNIT

600
690

2
3

Refrigerant piping flare connection (Gas)


Refrigerant piping flare connection (Liquid)
Drain piping connection (Drain pipe : I.D. 14 O.D. 28 L670)

Wall hook bracket

2-11 x 43 holes

575
470

575

264

155

55

145

292

470

65

30
60

85
55

55

145

Piping
inlet

37 - 6 holes
for tapping screw

212
252

Piping inlet

436

434
5 - 12 x 18 holes
for bolt

- (04 - 41) -

270

4-6. WIRING DIAGRAMS


4-6-1. UNIVERSAL FLOOR / CEILING TYPE

INDOOR
UNIT

INDOOR
UNIT

MODELS : AB12, AB14, AB18, AB24

- (04 - 42) -

4-6-2. LARGE CEILING TYPE

INDOOR
UNIT

INDOOR
UNIT

MODELS : AB30, AB36, AB45, AB54

- (04 - 43) -

4-6-3. COMPACT DUCT TYPE

INDOOR
UNIT

INDOOR
UNIT

MODELS : AR7, AR9, AR12, AR14, AR18

- (04 - 44) -

4-6-4. DUCT TYPE

INDOOR
UNIT

INDOOR
UNIT

MODELS : AR25

- (04 - 45) -

INDOOR
UNIT

INDOOR
UNIT

MODELS : AR30, AR36, AR45

- (04 - 46) -

4-6-5. HIGH STATIC PRESSURE DUCT TYPE

INDOOR
UNIT

INDOOR
UNIT

MODELS : AR36H, AR45H, AR60H

- (04 - 47) -

4-6-6. COMPACT CASSETTE TYPE

INDOOR
UNIT

INDOOR
UNIT

MODELS : AU7, AU9, AU12, AU14, AU18

- (04 - 48) -

4-6-7. CASSETTE TYPE

INDOOR
UNIT

INDOOR
UNIT

MODELS : AU20, AU25, AU30

- (04 - 49) -

INDOOR
UNIT

INDOOR
UNIT

MODELS : AU36, AU45, AU54

- (04 - 50) -

4-6-8. WALL MOUNTED TYPE

INDOOR
UNIT

INDOOR
UNIT

MODELS : AS18, AS24, AS30

- (04 - 51) -

4-6-9. CEILING WALL TYPE

INDOOR
UNIT

INDOOR
UNIT

MODELS : AW7, AW9, AW12, AW14, AW18, AW24, AW30

- (04 - 52) -

4-7. PIPING DIAGRAM


INDOOR UNIT
THOA

THIA :Indoor room temp. thermistor


Strainer
THHM

THOA :Outlet air thermistor


THHM :Heat exchanger middle thermistor

E.E.V.

E.E.V.:Electronic expansion valve


FAN
Strainer

THIA

INDOOR
UNIT

LIQUID PIPE

INDOOR
UNIT

GAS PIPE

REFRIGERATION PIPE DIAMETER


MODEL CODE

GAS PIPE
Size (Thickness)

LIQUID PIPE
Size (Thickness)

9.52 (0.8)

6.35 (0.8)

12, 14

12.70 (0.8)

6.35 (0.8)

18, 20, 24, 25

15.88 (1.0)

6.35 (0.8)

30

15.88 (1.0)

9.52 (0.8)

36, 45, 54, 60

19.05 (1.0)

9.52 (0.8)

7, 9

- (04 - 53) -

COOLING CAPACITY
4-8. CAPACITY TABLE COOLING
4-8-1. UNIVERSAL FLOOR / CEILING TYPE
MODEL : AB12
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
2.68
1.90
2.68
1.90
2.68
1.90
2.68
1.90
2.68
1.90
2.68
1.90
2.68
1.90
2.68
1.90
2.68
1.90
2.68
1.90
2.68
1.90
2.68
1.90
2.68
1.90

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
2.88
2.28
2.88
2.28
2.88
2.28
2.88
2.28
2.88
2.28
2.88
2.28
2.88
2.28
2.88
2.28
2.88
2.28
2.88
2.28
2.88
2.28
2.88
2.28
2.88
2.28

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
3.29
2.41
3.29
2.41
3.29
2.41
3.29
2.41
3.29
2.41
3.29
2.41
3.29
2.41
3.29
2.41
3.29
2.41
3.29
2.41
3.29
2.41
3.29
2.41
3.29
2.41

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB
82 FDB/68 FWB
TC
SHC
TC
SHC
3.50
2.42
3.71
2.45
3.50
2.42
3.71
2.45
3.50
2.42
3.71
2.45
3.50
2.42
3.71
2.45
3.50
2.42
3.71
2.45
3.50
2.42
3.71
2.45
3.50
2.42
3.71
2.45
3.50
2.42
3.71
2.45
3.50
2.42
3.71
2.45
3.50
2.42
3.71
2.45
3.50
2.42
3.71
2.45
3.50
2.42
3.65
2.42
3.36
2.32
3.44
2.41

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
4.12
2.48
4.12
2.48
4.12
2.48
4.12
2.48
4.12
2.48
4.12
2.48
4.12
2.48
4.12
2.48
4.10
2.47
4.04
2.44
3.96
2.42
3.81
2.37
3.59
2.30

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
4.32
2.52
4.32
2.52
4.32
2.52
4.32
2.52
4.32
2.52
4.32
2.52
4.32
2.52
4.24
2.51
4.18
2.48
4.12
2.48
4.04
2.43
3.88
2.38
3.66
2.31

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
3.81
2.90
3.81
2.90
3.81
2.90
3.81
2.90
3.81
2.90
3.81
2.90
3.81
2.90
3.81
2.90
3.81
2.90
3.81
2.90
3.81
2.90
3.81
2.90
3.81
2.90

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB
82 FDB/68 FWB
TC
SHC
TC
SHC
4.05
2.92
4.29
2.96
4.05
2.92
4.29
2.96
4.05
2.92
4.29
2.96
4.05
2.92
4.29
2.96
4.05
2.92
4.29
2.96
4.05
2.92
4.29
2.96
4.05
2.92
4.29
2.96
4.05
2.92
4.29
2.96
4.05
2.92
4.29
2.96
4.05
2.92
4.29
2.96
4.05
2.92
4.29
2.96
4.05
2.92
4.23
2.91
3.89
2.84
3.98
2.91

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
4.76
2.99
4.76
2.99
4.76
2.99
4.76
2.99
4.76
2.99
4.76
2.99
4.76
2.99
4.76
2.99
4.74
2.98
4.68
2.93
4.58
2.92
4.40
2.85
4.15
2.78

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
5.00
3.04
5.00
3.04
5.00
3.04
5.00
3.04
5.00
3.04
5.00
3.04
5.00
3.04
4.90
3.03
4.84
2.99
4.77
2.99
4.67
2.93
4.49
2.87
4.24
2.79

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
4.99
3.69
4.99
3.69
4.99
3.69
4.99
3.69
4.99
3.69
4.99
3.69
4.99
3.69
4.99
3.69
4.99
3.69
4.99
3.69
4.99
3.69
4.99
3.69
4.99
3.69

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB
82 FDB/68 FWB
TC
SHC
TC
SHC
5.30
3.71
5.61
3.76
5.30
3.71
5.61
3.76
5.30
3.71
5.61
3.76
5.30
3.71
5.61
3.76
5.30
3.71
5.61
3.76
5.30
3.71
5.61
3.76
5.30
3.71
5.61
3.76
5.30
3.71
5.61
3.76
5.30
3.71
5.61
3.76
5.30
3.71
5.61
3.76
5.30
3.71
5.61
3.76
5.30
3.71
5.53
3.70
5.09
3.56
5.21
3.70

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
6.24
3.80
6.24
3.80
6.24
3.80
6.24
3.80
6.24
3.80
6.24
3.80
6.24
3.80
6.24
3.80
6.21
3.79
6.12
3.73
5.99
3.71
5.76
3.63
5.43
3.53

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
6.55
3.86
6.55
3.86
6.55
3.86
6.55
3.86
6.55
3.86
6.55
3.86
6.55
3.86
6.42
3.85
6.33
3.80
6.24
3.81
6.11
3.73
5.88
3.65
5.54
3.55

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
6.21
4.40
6.21
4.40
6.21
4.40
6.21
4.40
6.21
4.40
6.21
4.40
6.21
4.40
6.21
4.40
6.21
4.40
6.21
4.40
6.21
4.40
6.21
4.40
6.21
4.40

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB
82 FDB/68 FWB
TC
SHC
TC
SHC
6.60
4.42
6.99
4.48
6.60
4.42
6.99
4.48
6.60
4.42
6.99
4.48
6.60
4.42
6.99
4.48
6.60
4.42
6.99
4.48
6.60
4.42
6.99
4.48
6.60
4.42
6.99
4.48
6.60
4.42
6.99
4.48
6.60
4.42
6.99
4.48
6.60
4.42
6.99
4.48
6.60
4.42
6.99
4.48
6.60
4.42
6.89
4.42
6.34
4.25
6.49
4.41

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
7.76
4.53
7.76
4.53
7.76
4.53
7.76
4.53
7.76
4.53
7.76
4.53
7.76
4.53
7.76
4.53
7.73
4.51
7.62
4.45
7.46
4.43
7.18
4.33
6.76
4.21

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
8.15
4.60
8.15
4.60
8.15
4.60
8.15
4.60
8.15
4.60
8.15
4.60
8.15
4.60
7.99
4.59
7.88
4.53
7.78
4.54
7.61
4.44
7.32
4.35
6.90
4.23

INDOOR
UNIT

( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
3.10
2.29
3.10
2.29
3.10
2.29
3.10
2.29
3.10
2.29
3.10
2.29
3.10
2.29
3.10
2.29
3.10
2.29
3.10
2.29
3.10
2.29
3.10
2.29
3.10
2.29

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
3.34
2.74
3.34
2.74
3.34
2.74
3.34
2.74
3.34
2.74
3.34
2.74
3.34
2.74
3.34
2.74
3.34
2.74
3.34
2.74
3.34
2.74
3.34
2.74
3.34
2.74

MODEL : AB18
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
4.05
2.92
4.05
2.92
4.05
2.92
4.05
2.92
4.05
2.92
4.05
2.92
4.05
2.92
4.05
2.92
4.05
2.92
4.05
2.92
4.05
2.92
4.05
2.92
4.05
2.92

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
4.36
3.49
4.36
3.49
4.36
3.49
4.36
3.49
4.36
3.49
4.36
3.49
4.36
3.49
4.36
3.49
4.36
3.49
4.36
3.49
4.36
3.49
4.36
3.49
4.36
3.49

MODEL : AB24
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

20 CDB/15 CWB 23 CDB/16 CWB


68 FDB/59 FWB
73 FDB/61 FWB
( FDB)
TC
SHC
TC
SHC
50
5.05
3.48
5.44
4.16
59
5.05
3.48
5.44
4.16
68
5.05
3.48
5.44
4.16
73
5.05
3.48
5.44
4.16
77
5.05
3.48
5.44
4.16
81
5.05
3.48
5.44
4.16
86
5.05
3.48
5.44
4.16
91
5.05
3.48
5.44
4.16
95
5.05
3.48
5.44
4.16
99
5.05
3.48
5.44
4.16
104
5.05
3.48
5.44
4.16
113
5.05
3.48
5.44
4.16
125
5.05
3.48
5.44
4.16
TC : Total Capacity kW
SHC : Sensible Heat Capacity kW

- (04 - 54) -

INDOOR
UNIT

MODEL : AB14
Outdoor
Temperature

COOLING CAPACITY
4-8-2. LARGE CEILING TYPE
MODEL : AB30
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
6.73
4.91
6.73
4.91
6.73
4.91
6.73
4.91
6.73
4.91
6.73
4.91
6.73
4.91
6.73
4.91
6.73
4.91
6.73
4.91
6.73
4.91
6.73
4.91
6.73
4.91

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
7.25
5.88
7.25
5.88
7.25
5.88
7.25
5.88
7.25
5.88
7.25
5.88
7.25
5.88
7.25
5.88
7.25
5.88
7.25
5.88
7.25
5.88
7.25
5.88
7.25
5.88

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
8.28
6.22
8.28
6.22
8.28
6.22
8.28
6.22
8.28
6.22
8.28
6.22
8.28
6.22
8.28
6.22
8.28
6.22
8.28
6.22
8.28
6.22
8.28
6.22
8.28
6.21

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
8.80
6.25
9.32
6.33
8.80
6.25
9.32
6.33
8.80
6.25
9.32
6.33
8.80
6.25
9.32
6.33
8.80
6.25
9.32
6.33
8.80
6.25
9.32
6.33
8.80
6.25
9.32
6.33
8.80
6.25
9.32
6.33
8.80
6.25
9.32
6.33
8.80
6.25
9.32
6.33
8.80
6.25
9.32
6.33
8.80
6.25
9.18
6.24
8.45
6.00
8.65
6.23

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
10.4
6.41
10.4
6.41
10.4
6.41
10.4
6.41
10.4
6.41
10.4
6.41
10.4
6.41
10.4
6.41
10.3
6.38
10.2
6.29
9.94
6.25
9.57
6.11
9.02
5.95

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
10.9
6.51
10.9
6.51
10.9
6.51
10.9
6.51
10.9
6.51
10.9
6.51
10.9
6.50
10.7
6.49
10.5
6.40
10.4
6.41
10.1
6.28
9.76
6.14
9.21
5.98

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
9.88
7.63
9.88
7.63
9.88
7.63
9.88
7.63
9.88
7.63
9.88
7.63
9.88
7.63
9.88
7.63
9.88
7.63
9.88
7.63
9.88
7.63
9.88
7.63
8.88
7.62

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
10.5
7.67
11.1
7.77
10.5
7.67
11.1
7.77
10.5
7.67
11.1
7.77
10.5
7.67
11.1
7.77
10.5
7.67
11.1
7.77
10.5
7.67
11.1
7.77
10.5
7.67
11.1
7.77
10.5
7.67
11.1
7.77
10.5
7.67
11.1
7.77
10.5
7.67
11.1
7.77
10.5
7.67
11.1
7.77
10.5
7.67
11.0
7.65
10.1
7.36
10.3
7.64

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
12.4
7.86
12.4
7.86
12.4
7.86
12.4
7.86
12.4
7.86
12.4
7.86
12.4
7.86
12.4
7.86
12.3
7.82
12.1
7.71
11.9
7.67
11.4
7.50
10.8
7.29

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
13.0
7.98
13.0
7.98
13.0
7.98
13.0
7.98
13.0
7.98
13.0
7.98
13.0
7.98
12.7
7.96
12.5
7.85
12.4
7.87
12.1
7.70
11.7
7.53
11.0
7.33

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
12.0
8.85
12.0
8.85
12.0
8.85
12.0
8.85
12.0
8.85
12.0
8.85
12.0
8.85
12.0
8.85
12.0
8.85
12.0
8.85
12.0
8.85
12.0
8.85
11.9
8.84

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
12.7
8.89
13.4
8.87
12.7
8.89
13.4
8.87
12.7
8.89
13.4
8.87
12.7
8.89
13.4
8.87
12.7
8.89
13.4
8.87
12.7
8.89
13.4
8.87
12.7
8.89
13.4
8.87
12.7
8.89
13.4
8.87
12.7
8.89
13.4
8.87
12.7
8.89
13.4
8.87
12.7
8.89
13.4
8.87
12.7
8.89
13.3
8.75
12.2
8.54
12.5
8.74

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
14.9
8.96
14.9
8.96
14.9
8.96
14.9
8.96
14.9
8.96
14.9
8.96
14.9
8.96
14.9
8.96
14.9
8.93
14.7
8.80
14.4
8.75
13.8
8.56
13.0
8.20

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
15.7
9.26
15.7
9.26
15.7
9.26
15.7
9.26
15.7
9.26
15.7
9.26
15.7
9.25
15.4
9.23
15.2
9.10
15.0
9.13
14.6
8.93
14.1
8.74
13.3
8.37

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
13.3
9.96
13.3
9.96
13.3
9.96
13.3
9.96
13.3
9.96
13.3
9.96
13.3
9.96
13.3
9.96
13.3
9.96
13.3
9.96
13.3
9.96
13.3
9.96
13.3
9.96

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
14.1
10.0
14.9
9.99
14.1
10.0
14.9
9.99
14.1
10.0
14.9
9.99
14.1
10.0
14.9
9.99
14.1
10.0
14.9
9.99
14.1
10.0
14.9
9.99
14.1
10.0
14.9
9.99
14.1
10.0
14.9
9.99
14.1
10.0
14.9
9.99
14.1
10.0
14.9
9.99
14.1
10.0
14.9
9.99
14.1
10.0
14.7
9.85
13.5
9.62
13.9
9.84

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
16.6
10.1
16.6
10.1
16.6
10.1
16.6
10.1
16.6
10.1
16.6
10.1
16.6
10.1
16.6
10.1
16.5
10.1
16.3
9.91
15.9
9.86
15.3
9.64
14.5
9.23

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
17.1
10.4
17.1
10.4
17.1
10.4
17.1
10.4
17.1
10.4
17.1
10.4
17.1
10.4
17.1
10.4
16.8
10.3
16.6
10.3
16.3
10.1
15.6
9.84
14.8
9.43

INDOOR
UNIT

( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
8.03
6.03
8.03
6.03
8.03
6.03
8.03
6.03
8.03
6.03
8.03
6.03
8.03
6.03
8.03
6.03
8.03
6.03
8.03
6.03
8.03
6.03
8.03
6.03
8.03
6.03

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
8.65
7.21
8.65
7.21
8.65
7.21
8.65
7.21
8.65
7.21
8.65
7.21
8.65
7.21
8.65
7.21
8.65
7.21
8.65
7.21
8.65
7.21
8.65
7.21
8.65
7.21

MODEL : AB45
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
9.71
6.99
9.71
6.99
9.71
6.99
9.71
6.99
9.71
6.99
9.71
6.99
9.71
6.99
9.71
6.99
9.71
6.99
9.71
6.99
9.71
6.99
9.71
6.99
9.71
6.99

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
10.5
8.37
10.5
8.37
10.5
8.37
10.5
8.37
10.5
8.37
10.5
8.37
10.5
8.37
10.5
8.37
10.5
8.37
10.5
8.37
10.5
8.37
10.5
8.37
10.5
8.37

MODEL : AB54
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

20 CDB/15 CWB 23 CDB/16 CWB


68 FDB/59 FWB 73 FDB/61 FWB
( FDB)
TC
SHC
TC
SHC
50
10.8
7.87
11.6
9.42
59
10.8
7.87
11.6
9.42
68
10.8
7.87
11.6
9.42
73
10.8
7.87
11.6
9.42
77
10.8
7.87
11.6
9.42
81
10.8
7.87
11.6
9.42
86
10.8
7.87
11.6
9.42
91
10.8
7.87
11.6
9.42
95
10.8
7.87
11.6
9.42
99
10.8
7.87
11.6
9.42
104
10.8
7.87
11.6
9.42
113
10.8
7.87
11.6
9.42
125
10.8
7.87
11.6
9.42
TC : Total Capacity kW
SHC : Sensible Heat Capacity kW

- (04 - 55) -

INDOOR
UNIT

MODEL : AB36
Outdoor
Temperature

COOLING CAPACITY
4-8-3. COMPACT DUCT TYPE (1/2)
MODEL : AR7

INDOOR
UNIT

( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
1. 64
1. 30
1. 64
1. 30
1. 64
1. 30
1. 64
1. 30
1. 64
1. 30
1. 64
1. 30
1. 64
1. 30
1. 64
1. 30
1. 64
1. 30
1. 64
1. 30
1. 64
1. 30
1. 64
1. 30
1. 64
1. 30

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
1. 77
1. 56
1. 77
1. 56
1. 77
1. 56
1. 77
1. 56
1. 77
1. 56
1. 77
1. 56
1. 77
1. 56
1. 77
1. 56
1. 77
1. 56
1. 77
1. 56
1. 77
1. 56
1. 77
1. 56
1. 77
1. 56

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
2. 02
1. 65
2. 02
1. 65
2. 02
1. 65
2. 02
1. 65
2. 02
1. 65
2. 02
1. 65
2. 02
1. 65
2. 02
1. 65
2. 02
1. 65
2. 02
1. 65
2. 02
1. 65
2. 02
1. 65
2. 02
1. 65

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
2. 15
1. 66
2. 28
1. 68
2. 15
1. 66
2. 28
1. 68
2. 15
1. 66
2. 28
1. 68
2. 15
1. 66
2. 28
1. 68
2. 15
1. 66
2. 28
1. 68
2. 15
1. 66
2. 28
1. 68
2. 15
1. 66
2. 28
1. 68
2. 15
1. 66
2. 28
1. 68
2. 15
1. 66
2. 28
1. 68
2. 15
1. 66
2. 28
1. 68
2. 15
1. 66
2. 28
1. 68
2. 15
1. 66
2. 24
1. 65
2. 07
1. 59
2. 11
1. 65

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
2. 53
1. 70
2. 53
1. 70
2. 53
1. 70
2. 53
1. 70
2. 53
1. 70
2. 53
1. 70
2. 53
1. 70
2. 53
1. 70
2. 52
1. 69
2. 48
1. 67
2. 43
1. 66
2. 34
1. 62
2. 20
1. 58

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
2. 66
1. 72
2. 66
1. 72
2. 66
1. 72
2. 66
1. 72
2. 66
1. 72
2. 66
1. 72
2. 66
1. 72
2. 60
1. 72
2. 57
1. 70
2. 53
1. 70
2. 48
1. 66
2. 39
1. 63
2. 25
1. 58

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
2. 31
1. 95
2. 31
1. 95
2. 31
1. 95
2. 31
1. 95
2. 31
1. 95
2. 31
1. 95
2. 31
1. 95
2. 31
1. 95
2. 31
1. 95
2. 31
1. 95
2. 31
1. 95
2. 31
1. 95
2. 31
1. 95

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
2. 64
2. 06
2. 64
2. 06
2. 64
2. 06
2. 64
2. 06
2. 64
2. 06
2. 64
2. 06
2. 64
2. 06
2. 64
2. 06
2. 64
2. 06
2. 64
2. 06
2. 64
2. 06
2. 64
2. 06
2. 63
2. 06

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
2. 80
2. 07
2. 96
2. 10
2. 80
2. 07
2. 96
2. 10
2. 80
2. 07
2. 96
2. 10
2. 80
2. 07
2. 96
2. 10
2. 80
2. 07
2. 96
2. 10
2. 80
2. 07
2. 96
2. 10
2. 80
2. 07
2. 96
2. 10
2. 80
2. 07
2. 96
2. 10
2. 80
2. 07
2. 96
2. 10
2. 80
2. 07
2. 96
2. 10
2. 80
2. 07
2. 96
2. 10
2. 80
2. 07
2. 92
2. 07
2. 69
1. 99
2. 75
2. 07

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
3. 29
2. 12
3. 29
2. 12
3. 29
2. 12
3. 29
2. 12
3. 29
2. 12
3. 29
2. 12
3. 29
2. 12
3. 29
2. 12
3. 28
2. 11
3. 23
2. 09
3. 16
2. 07
3. 04
2. 03
2. 87
1. 97

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
3. 46
2. 16
3. 46
2. 16
3. 46
2. 16
3. 46
2. 16
3. 46
2. 16
3. 46
1. 16
3. 46
2. 16
3. 39
2. 15
3. 34
2. 12
3. 30
2. 13
3. 23
2. 08
3. 11
2. 04
2. 93
1. 98

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
3. 29
2. 47
3. 29
2. 47
3. 29
2. 47
3. 29
2. 47
3. 29
2. 47
3. 29
2. 47
3. 29
2. 47
3. 29
2. 47
3. 29
2. 47
3. 29
2. 47
3. 29
2. 47
3. 29
2. 47
3. 29
2. 47

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
3. 50
2. 49
3. 71
2. 48
3. 50
2. 49
3. 71
2. 48
3. 50
2. 49
3. 71
2. 48
3. 50
2. 49
3. 71
2. 48
3. 50
2. 49
3. 71
2. 48
3. 50
2. 49
3. 71
2. 48
3. 50
2. 49
3. 71
2. 48
3. 50
2. 49
3. 71
2. 48
3. 50
2. 49
3. 71
2. 48
3. 50
2. 49
3. 71
2. 48
3. 50
2. 49
3. 71
2. 48
3. 50
2. 49
3. 65
2. 44
3. 36
2. 39
3. 44
2. 44

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
4. 12
2. 51
4. 12
2. 51
4. 12
2. 51
4. 12
2. 51
4. 12
2. 51
4. 12
2. 51
4. 12
2. 51
4. 12
2. 51
4. 10
2. 49
4. 04
2. 46
3. 96
2. 45
3. 81
2. 39
3. 59
2. 29

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
4. 32
2. 59
4. 32
2. 59
4. 32
2. 59
4. 32
2. 59
4. 32
2. 59
4. 32
2. 59
4. 32
2. 59
4. 24
2. 58
4. 18
2. 54
4. 12
2. 55
4. 04
2. 50
3. 88
2. 44
3. 66
2. 34

INDOOR
UNIT

Outdoor
Temperature

MODEL : AR9
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
2. 14
1. 63
2. 14
1. 63
2. 14
1. 63
2. 14
1. 63
2. 14
1. 63
2. 14
1. 63
2. 14
1. 63
2. 14
1. 63
2. 14
1. 63
2. 14
1. 63
2. 14
1. 63
2. 14
1. 63
2. 14
1. 63

MODEL : AR12
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
2. 68
1. 95
2. 68
1. 95
2. 68
1. 95
2. 68
1. 95
2. 68
1. 95
2. 68
1. 95
2. 68
1. 95
2. 68
1. 95
2. 68
1. 95
2. 68
1. 95
2. 68
1. 95
2. 68
1. 95
2. 68
1. 95

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
2. 88
2. 34
2. 88
2. 34
2. 88
2. 34
2. 88
2. 34
2. 88
2. 34
2. 88
2. 34
2. 88
2. 34
2. 88
2. 34
2. 88
2. 34
2. 88
2. 34
2. 88
2. 34
2. 88
2. 34
2. 88
2. 34

TC : Total Capacity kW
SHC : Sensible Heat Capacity kW

- (04 - 56) -

COOLING CAPACITY
4-8-3. COMPACT DUCT TYPE (2/2)
MODEL : AR14

INDOOR
UNIT

( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
3.06
2.42
3.06
2.42
3.06
2.42
3.06
2.42
3.06
2.42
3.06
2.42
3.06
2.42
3.06
2.42
3.06
2.42
3.06
2.42
3.06
2.42
3.06
2.42
3.06
2.42

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
3.29
2.90
3.29
2.90
3.29
2.90
3.29
2.90
3.29
2.90
3.29
2.90
3.29
2.90
3.29
2.90
3.29
2.90
3.29
2.90
3.29
2.90
3.29
2.90
3.29
2.90

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
3.76
3.06
3.76
3.06
3.76
3.06
3.76
3.06
3.76
3.06
3.76
3.06
3.76
3.06
3.76
3.06
3.76
3.06
3.76
3.06
3.76
3.06
3.76
3.06
3.76
3.06

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
4.00
3.08
4.24
3.07
4.00
3.08
4.24
3.07
4.00
3.08
4.24
3.07
4.00
3.08
4.24
3.07
4.00
3.08
4.24
3.07
4.00
3.08
4.24
3.07
4.00
3.08
4.24
3.07
4.00
3.08
4.24
3.07
4.00
3.08
4.24
3.07
4.00
3.08
4.24
3.07
4.00
3.08
4.24
3.07
4.00
3.08
4.17
3.03
3.84
2.96
3.93
3.03

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
4.71
3.11
4.71
3.11
4.71
3.11
4.71
3.11
4.71
3.11
4.71
3.11
4.71
3.11
4.71
3.11
4.69
3.09
4.62
3.05
4.52
3.03
4.35
2.97
4.10
2.84

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
4.94
3.21
4.94
3.21
4.94
3.21
4.94
3.21
4.94
3.21
4.94
3.21
4.94
3.21
4.84
3.20
4.78
3.15
4.71
3.16
4.61
3.09
4.44
3.03
4.18
2.90

MODEL : AR18
Outdoor
Temperature

( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
4.05
3.04
4.05
3.04
4.05
3.04
4.05
3.04
4.05
3.04
4.05
3.04
4.05
3.04
4.05
3.04
4.05
3.04
4.05
3.04
4.05
3.04
4.05
3.04
4.05
3.04

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
4.36
3.64
4.36
3.64
4.36
3.64
4.36
3.64
4.36
3.64
4.36
3.64
4.36
3.64
4.36
3.64
4.36
3.64
4.36
3.64
4.36
3.64
4.36
3.64
4.36
3.64

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
4.99
3.85
4.99
3.85
4.99
3.85
4.99
3.85
4.99
3.85
4.99
3.85
4.99
3.85
4.99
3.85
4.99
3.85
4.99
3.85
4.99
3.85
4.99
3.85
4.99
3.85

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
5.30
3.87
5.61
3.86
5.30
3.87
5.61
3.86
5.30
3.87
5.61
3.86
5.30
3.87
5.61
3.86
5.30
3.87
5.61
3.86
5.30
3.87
5.61
3.86
5.30
3.87
5.61
3.86
5.30
3.87
5.61
3.86
5.30
3.87
5.61
3.86
5.30
3.87
5.61
3.86
5.30
3.87
5.61
3.86
5.30
3.87
5.53
3.81
5.09
3.72
5.21
3.80

TC : Total Capacity kW
SHC : Sensible Heat Capacity kW

- (04 - 57) -

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
6.24
3.90
6.24
3.90
6.24
3.90
6.24
3.90
6.24
3.90
6.24
3.90
6.24
3.90
6.24
3.90
6.21
3.88
6.12
3.83
5.99
3.81
5.76
3.73
5.43
3.57

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
6.55
4.03
6.55
4.03
6.55
4.03
6.55
4.03
6.55
4.03
6.55
4.03
6.55
4.03
6.42
4.02
6.33
3.96
6.24
3.97
6.11
3.89
5.88
3.80
5.54
3.64

INDOOR
UNIT

Outdoor
Temperature

COOLING CAPACITY
4-8-4. DUCT TYPE
MODEL : AR25
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
5. 39
4. 10
5. 39
4. 10
5. 39
4. 10
5. 39
4. 10
5. 39
4. 10
5. 39
4. 10
5. 39
4. 10
5. 39
4. 10
5. 39
4. 10
5. 39
4. 10
5. 39
4. 10
5. 39
4. 10
5. 39
4. 10

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
5. 81
4. 91
5. 81
4. 91
5. 81
4. 91
5. 81
4. 91
5. 81
4. 91
5. 81
4. 91
5. 81
4. 91
5. 81
4. 91
5. 81
4. 91
5. 81
4. 91
5. 81
4. 91
5. 81
4. 91
5. 81
4. 91

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
6. 64
5. 19
6. 64
5. 19
6. 64
5. 19
6. 64
5. 19
6. 64
5. 19
6. 64
5. 19
6. 64
5. 19
6. 64
5. 19
6. 64
5. 19
6. 64
5. 19
6. 64
5. 19
6. 64
5. 19
6. 63
5. 19

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
7. 05
5. 22
7. 46
5. 21
7. 05
5. 22
7. 46
5. 21
7. 05
5. 22
7. 46
5. 21
7. 05
5. 22
7. 46
5. 21
7. 05
5. 22
7. 46
5. 21
7. 05
5. 22
7. 46
5. 21
7. 05
5. 22
7. 46
5. 21
7. 05
5. 22
7. 46
5. 21
7. 05
5. 22
7. 46
5. 21
7. 05
5. 22
7. 46
5. 21
7. 05
5. 22
7. 46
5. 21
7. 05
5. 22
7. 36
5. 13
6. 77
5. 01
6. 93
5. 13

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
8. 29
5. 26
8. 29
5. 26
8. 29
5. 26
8. 29
5. 26
8. 29
5. 26
8. 29
5. 26
8. 29
5. 26
8. 29
5. 26
8. 26
5. 24
8. 14
5. 16
7. 97
5. 14
7. 67
5. 02
7. 23
4. 81

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
8. 71
5. 43
8. 71
5. 43
8. 71
5. 43
8. 71
5. 43
8. 71
5. 43
8. 71
5. 43
8. 71
5. 43
8. 54
5. 41
8. 42
5. 34
8. 31
5. 36
8. 13
5. 24
7. 82
5. 13
7. 38
4. 91

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
8. 28
6. 22
8. 28
6. 22
8. 28
6. 22
8. 28
6. 22
8. 28
6. 22
8. 28
6. 22
8. 28
6. 22
8. 28
6. 22
8. 28
6. 22
8. 28
6. 22
8. 28
6. 22
8. 28
6. 22
8. 28
6. 21

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
8. 80
6. 25
9. 32
6. 24
8. 80
6. 25
9. 32
6. 24
8. 80
6. 25
9. 32
6. 24
8. 80
6. 25
9. 32
6. 24
8. 80
6. 25
9. 32
6. 24
8. 80
6. 25
9. 32
6. 24
8. 80
6. 25
9. 32
6. 24
8. 80
6. 25
9. 32
6. 24
8. 80
6. 25
9. 32
6. 24
8. 80
6. 25
9. 32
6. 24
8. 80
6. 25
9. 32
6. 24
8. 80
6. 25
9. 18
6. 15
8. 45
6. 00
8. 65
6. 14

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
10. 4
6. 30
10. 4
6. 30
10. 4
6. 30
10. 4
6. 30
10. 4
6. 30
10. 4
6. 30
10. 4
6. 30
10. 4
6. 30
10. 3
6. 27
10. 2
6. 19
9. 94
6. 15
9. 57
6. 02
9. 02
5. 76

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
10. 9
6. 51
10. 9
6. 51
10. 9
6. 51
10. 9
6. 51
10. 9
6. 51
10. 9
6. 51
10. 9
6. 50
10. 7
6. 49
10. 5
6. 40
10. 4
6. 41
10. 1
6. 28
9. 76
6. 14
9. 21
5. 88

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 0
7. 23
10. 1
7. 06
10. 3
7. 22

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
12. 4
7. 41
12. 4
7. 41
12. 4
7. 41
12. 4
7. 41
12. 4
7. 41
12. 4
7. 41
12. 4
7. 41
12. 4
7. 41
12. 3
7. 38
12. 1
7. 28
11. 9
7. 24
11. 4
7. 08
10. 8
6. 78

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
13. 0
7. 65
13. 0
7. 65
13. 0
7. 65
13. 0
7. 65
13. 0
7. 65
13. 0
7. 65
13. 0
7. 65
12. 7
7. 63
12. 5
7. 53
12. 4
7. 55
12. 1
7. 38
11. 7
7. 22
11. 0
6. 92

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
11. 9
8. 97

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 3
8. 87
12. 2
8. 66
12. 5
8. 86

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
14. 9
8. 09
14. 9
8. 09
14. 9
8. 09
14. 9
8. 09
14. 9
8. 09
14. 9
8. 09
14. 9
8. 09
14. 9
9. 09
14. 9
9. 05
14. 7
8. 93
14. 4
8. 88
13. 8
8. 68
13. 0
8. 32

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
15. 7
9. 39
15. 7
9. 39
15. 7
8. 39
15. 7
8. 39
15. 7
8. 39
15. 7
9. 39
15. 7
9. 39
15. 4
9. 36
15. 2
9. 23
15. 0
9. 26
14. 6
9. 06
14. 1
8. 86
13. 3
8. 49

INDOOR
UNIT

( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
6. 73
4. 91
6. 73
4. 91
6. 73
4. 91
6. 73
4. 91
6. 73
4. 91
6. 73
4. 91
6. 73
4. 91
6. 73
4. 91
6. 73
4. 91
6. 73
4. 91
6. 73
4. 91
6. 73
4. 91
6. 73
4. 91

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
7. 25
5. 88
7. 25
5. 88
7. 25
5. 88
7. 25
5. 88
7. 25
5. 88
7. 25
5. 88
7. 25
5. 88
7. 25
5. 88
7. 25
5. 88
7. 25
5. 88
7. 25
5. 88
7. 25
5. 88
7. 25
5. 88

MODEL : AR36
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92

MODEL : AR45
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49

TC : Total Capacity kW
SHC : Sensible Heat Capacity kW

- (04 - 58) -

INDOOR
UNIT

MODEL : AR30
Outdoor
Temperature

COOLING CAPACITY
4-8-5. HIGH STATIC PRESSURE DUCT TYPE
MODEL : AR36H
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78
8. 03
5. 78

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92
8. 65
6. 92

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31
9. 88
7. 31

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 1
7. 34
10. 5
7. 35
11. 0
7. 23
10. 1
7. 06
10. 3
7. 22

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
12. 4
7. 41
12. 4
7. 41
12. 4
7. 41
12. 4
7. 41
12. 4
7. 41
12. 4
7. 41
12. 4
7. 41
12. 4
7. 41
12. 3
7. 38
12. 1
7. 28
11. 9
7. 24
11. 4
7. 08
10. 8
6. 78

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
13. 0
7. 65
13. 0
7. 65
13. 0
7. 65
13. 0
7. 65
13. 0
7. 65
13. 0
7. 65
13. 0
7. 65
12. 7
7. 63
12. 5
7. 53
12. 4
7. 55
12. 1
7. 38
11. 7
7. 22
11. 0
6. 92

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
12. 0
8. 97
11. 9
8. 97

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 4
9. 00
12. 7
9. 02
13. 3
8. 87
12. 2
8. 66
12. 5
8. 74

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
14. 9
9. 09
14. 9
9. 09
14. 9
9. 09
14. 9
9. 09
14. 9
9. 09
14. 9
9. 09
14. 9
9. 09
14. 9
9. 09
14. 9
9. 05
14. 7
8. 93
14. 4
8. 88
13. 8
8. 68
13. 0
8. 32

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
15. 7
9. 39
15. 7
9. 39
15. 7
9. 39
15. 7
9. 39
15. 7
9. 39
15. 7
9. 39
15. 7
9. 39
15. 4
9. 36
15. 2
9. 23
15. 0
9. 26
14. 6
9. 06
14. 1
8. 86
13. 3
8. 49

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
16. 0
12. 2
16. 0
12. 2
16. 0
12. 2
16. 0
12. 2
16. 0
12. 2
16. 0
12. 2
16. 0
12. 2
16. 0
12. 2
16. 0
12. 2
16. 0
12. 2
16. 0
12. 2
16. 0
12. 2
16. 0
12. 2

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
17. 0
12. 2
18. 0
12. 2
17. 0
12. 2
18. 0
12. 2
17. 0
12. 2
18. 0
12. 2
17. 0
12. 2
18. 0
12. 2
17. 0
12. 2
18. 0
12. 2
17. 0
12. 2
18. 0
12. 2
17. 0
12. 2
18. 0
12. 2
17. 0
12. 2
18. 0
12. 2
17. 0
12. 2
18. 0
12. 2
17. 0
12. 2
18. 0
12. 2
17. 0
12. 2
18. 0
12. 2
17. 0
12. 2
17. 7
12. 0
16. 3
11. 9
16. 7
12. 0

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
20. 0
12. 3
20. 0
12. 3
20. 0
12. 3
20. 0
12. 3
20. 0
12. 3
20. 0
12. 3
20. 0
12. 3
20. 0
12. 3
19. 9
12. 3
19. 6
12. 1
19. 2
12. 1
18. 5
11. 8
17. 4
11. 3

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
21. 0
12. 7
21. 0
12. 7
21. 0
12. 7
21. 0
12. 7
21. 0
12. 7
21. 0
12. 7
21. 0
12. 7
20. 6
12. 7
20. 3
12. 5
20. 0
12. 6
19. 6
12. 3
18. 9
12. 0
17. 8
11. 5

( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09
9. 71
7. 09

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49
10. 5
8. 49

MODEL : AR60H
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
13. 0
9. 63
13. 0
9. 63
13. 0
9. 63
13. 0
9. 63
13. 0
9. 63
13. 0
9. 63
13. 0
9. 63
13. 0
9. 63
13. 0
9. 63
13. 0
9. 63
13. 0
9. 63
13. 0
9. 63
13. 0
9. 63

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
14. 0
11. 5
14. 0
11. 5
14. 0
11. 5
14. 0
11. 5
14. 0
11. 5
14. 0
11. 5
14. 0
11. 5
14. 0
11. 5
14. 0
11. 5
14. 0
11. 5
14. 0
11. 5
14. 0
11. 5
14. 0
11. 5

TC : Total Capacity kW
SHC : Sensible Heat Capacity kW

- (04 - 59) -

INDOOR
UNIT

INDOOR
UNIT

MODEL : AR45H
Outdoor
Temperature

COOLING CAPACITY
4-8-6. COMPACT CASSETTE TYPE (1/2)

MODEL : AU7
20 CDB/15 CWB
TC
SHC
1.64
1.20
1.64
1.20
1.64
1.20
1.64
1.45
1.64
1.20
1.64
1.20
1.64
1.20
1.64
1.20
1.64
1.20
1.64
1.20
1.64
1.20
1.64
1.20
1.64
1.20

23 CDB/16 CWB
TC
SHC
1.77
1.44
1.77
1.44
1.77
1.44
1.77
1.44
1.77
1.44
1.77
1.44
1.77
1.44
1.77
1.44
1.77
1.44
1.77
1.44
1.77
1.44
1.77
1.44
1.77
1.44

26 CDB/18 CWB
TC
SHC
2.02
1.52
2.02
1.52
2.02
1.52
2.02
1.52
2.02
1.52
2.02
1.52
2.02
1.52
2.02
1.52
2.02
1.52
2.02
1.52
2.02
1.52
2.02
1.52
2.02
1.52

Indoor Temperature
27 CDB/19 CWB
TC
SHC
2.15
1.53
2.15
1.53
2.15
1.53
2.15
1.53
2.15
1.53
2.15
1.53
2.15
1.53
2.15
1.53
2.15
1.53
2.15
1.53
2.15
1.53
2.15
1.53
2.07
1.47

28 CDB/20 CWB
TC
SHC
2.28
1.52
2.28
1.52
2.28
1.52
2.28
1.52
2.28
1.52
2.28
1.52
2.28
1.52
2.28
1.52
2.28
1.52
2.28
1.52
2.28
1.52
2.24
1.50
2.11
1.50

30 CDB/22 CWB
TC
SHC
2.53
1.54
2.53
1.54
2.53
1.54
2.53
1.54
2.53
1.54
2.53
1.54
2.53
1.54
2.53
1.54
2.52
1.53
2.48
1.51
2.43
1.50
2.34
1.47
2.20
1.41

32 CDB/23 CWB
TC
SHC
2.66
1.59
2.66
1.59
2.66
1.59
2.66
1.59
2.66
1.59
2.66
1.59
2.66
1.59
2.60
1.58
2.57
1.56
2.53
1.57
2.48
1.53
2.39
1.50
2.25
1.44

23 CDB/16 CWB
TC
SHC
2.31
1.84
2.31
1.84
2.31
1.84
2.31
1.84
2.31
1.84
2.31
1.84
2.31
1.84
2.31
1.84
2.31
1.84
2.31
1.84
2.31
1.84
2.31
1.84
2.31
1.84

26 CDB/18 CWB
TC
SHC
2.64
1.95
2.64
1.95
2.64
1.95
2.64
1.95
2.64
1.95
2.64
1.95
2.64
1.95
2.64
1.95
2.64
1.95
2.64
1.95
2.64
1.95
2.64
1.95
2.63
1.95

Indoor Temperature
27 CDB/19 CWB
TC
SHC
2.80
1.96
2.80
1.96
2.80
1.96
2.80
1.96
2.80
1.96
2.80
1.96
2.80
1.96
2.80
1.96
2.80
1.96
2.80
1.96
2.80
1.96
2.80
1.96
2.69
1.88

28 CDB/20 CWB
TC
SHC
2.96
1.96
2.96
1.96
2.96
1.96
2.96
1.96
2.96
1.96
2.96
1.96
2.96
1.96
2.96
1.96
2.96
1.96
2.96
1.96
2.96
1.96
2.92
1.93
2.75
1.93

30 CDB/22 CWB
TC
SHC
3.29
1.98
3.29
1.98
3.29
1.98
3.29
1.98
3.29
1.98
3.29
1.98
3.29
1.98
3.29
1.98
3.28
1.97
3.23
1.94
3.16
1.93
3.04
1.89
2.87
1.81

32 CDB/23 CWB
TC
SHC
3.46
2.04
3.46
2.04
3.46
2.04
3.46
2.04
3.46
2.04
3.46
2.04
3.46
2.04
3.39
2.03
3.34
2.01
3.30
2.01
3.23
1.97
3.11
1.93
2.93
1.85

23 CDB/16 CWB
TC
SHC
2.96
2.41
2.96
2.41
2.96
2.41
2.96
2.41
2.96
2.41
2.96
2.41
2.96
2.41
2.96
2.41
2.96
2.41
2.96
2.41
2.96
2.41
2.96
2.41
2.41
2.96

26 CDB/18 CWB
TC
SHC
3.39
2.54
3.39
2.54
3.39
2.54
3.39
2.54
3.39
2.54
3.39
2.54
3.39
2.54
3.39
2.54
3.39
2.54
3.39
2.54
3.39
2.54
3.39
2.54
3.39
2.54

Indoor Temperature
27 CDB/19 CWB
TC
SHC
3.60
2.56
3.60
2.56
3.60
2.56
3.60
2.56
3.60
2.56
3.60
2.56
3.60
2.56
3.60
2.56
3.60
2.56
3.60
2.56
3.60
2.56
3.60
2.56
3.46
2.46

28 CDB/20 CWB
TC
SHC
3.81
2.55
3.81
2.55
3.81
2.55
3.81
2.55
3.81
2.55
3.81
2.55
3.81
2.55
3.81
2.55
3.81
2.55
3.81
2.55
3.81
2.55
3.76
2.51
2.51
3.54

30 CDB/22 CWB
TC
SHC
4.24
2.58
4.24
2.58
4.24
2.58
4.24
2.58
4.24
2.58
4.24
2.58
4.24
2.58
4.24
2.58
4.22
2.57
4.16
2.53
4.07
2.52
3.91
2.46
3.69
2.36

32 CDB/23 CWB
TC
SHC
4.45
2.66
4.45
2.66
4.45
2.66
4.45
2.66
4.45
2.66
4.45
2.66
4.45
2.66
4.36
2.65
4.30
2.62
4.24
2.62
4.15
2.57
3.99
2.51
2.41
3.77

INDOOR
UNIT

INDOOR
UNIT

Outdoor
Temperature
( CDB) ( FDB)
10
50
15
59
20
68
23
73
25
77
27
81
30
86
33
91
35
95
37
99
40
104
45
113
52
125

MODEL : AU9
Outdoor
Temperature
( CDB) ( FDB)
10
50
15
59
20
68
23
73
25
77
27
81
30
86
33
91
35
95
37
99
40
104
45
113
52
125

20 CDB/15 CWB
TC
SHC
2.14
1.54
2.14
1.54
2.14
1.54
2.14
1.54
2.14
1.54
2.14
1.54
2.14
1.54
2.14
1.54
2.14
1.54
2.14
1.54
2.14
1.54
2.14
1.54
2.14
1.54

MODEL : AU12
Outdoor
20 CDB/15 CWB
Temperature
TC
SHC
( CDB) ( FDB)
2.75
2.01
10
50
15
59
2.75
2.01
20
68
2.75
2.01
23
73
2.75
2.01
25
77
2.75
2.01
27
81
2.75
2.01
30
86
2.75
2.01
33
91
2.75
2.01
35
95
2.75
2.01
37
99
2.75
2.01
40
104 2.75
2.01
45
113 2.75
2.01
52
125 2.75
2.01

TC : Total Capacity kW
SHC : Sensible Heat Capacity kW

- (04 - 60) -

COOLING CAPACITY
4-8-6. COMPACT CASSETTE TYPE (2/2)

MODEL : AU14
Outdoor
Temperature

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
3. 76
2. 83
3. 76
2. 83
3. 76
2. 83
3. 76
2. 83
3. 76
2. 83
3. 76
2. 83
3. 76
2. 83
3. 76
2. 83
3. 76
2. 83
3. 76
2. 83
3. 76
2. 83
3. 76
2. 83
3. 76
2. 82

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
4. 00
2. 84
4. 24
2. 84
4. 00
2. 84
4. 24
2. 84
4. 00
2. 84
4. 24
2. 84
4. 00
2. 84
4. 24
2. 84
4. 00
2. 84
4. 24
2. 84
4. 00
2. 84
4. 24
2. 84
4. 00
2. 84
4. 24
2. 84
4. 00
2. 84
4. 24
2. 84
4. 00
2. 84
4. 24
2. 84
4. 00
2. 84
4. 24
2. 84
4. 00
2. 84
4. 24
2. 84
4. 00
2. 84
4. 17
2. 79
3. 84
2. 73
3. 93
2. 79

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
4. 71
2. 86
4. 71
2. 86
4. 71
2. 86
4. 71
2. 86
4. 71
2. 86
4. 71
2. 86
4. 71
2. 86
4. 71
2. 86
4. 69
2. 85
4. 62
2. 81
4. 52
2. 80
4. 35
2. 74
4. 10
2. 62

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
4. 94
2. 96
4. 94
2. 96
4. 94
2. 96
4. 94
2. 96
4. 94
2. 96
4. 94
2. 96
4. 94
2. 96
4. 84
2. 95
4. 78
2. 91
4. 71
2. 92
4. 61
2. 85
4. 44
2. 79
4. 18
2. 67

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
4. 71
3. 53
4. 71
3. 53
4. 71
3. 53
4. 71
3. 53
4. 71
3. 53
4. 71
3. 53
4. 71
3. 53
4. 71
3. 53
4. 71
3. 53
4. 71
3. 53
4. 71
3. 53
4. 71
3. 53
4. 70
3. 53

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
5. 00
3. 55
5. 29
3. 54
5. 00
3. 55
5. 29
3. 54
5. 00
3. 55
5. 29
3. 54
5. 00
3. 55
5. 29
3. 54
5. 00
3. 55
5. 29
3. 54
5. 00
3. 55
5. 29
3. 54
5. 00
3. 55
5. 29
3. 54
5. 00
3. 55
5. 29
3. 54
5. 00
3. 55
5. 29
3. 54
5. 00
3. 55
5. 29
3. 54
5. 00
3. 55
5. 29
3. 54
5. 00
3. 55
5. 22
3. 49
4. 80
3. 41
4. 91
3. 49

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
5. 88
3. 58
5. 88
3. 58
5. 88
3. 58
5. 88
3. 58
5. 88
3. 58
5. 88
3. 58
5. 88
3. 58
5. 88
3. 58
5. 86
3. 56
5. 77
3. 51
5. 65
3. 50
5. 44
3. 42
5. 12
3. 27

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
6. 18
3. 70
6. 18
3. 70
6. 18
3. 70
6. 18
3. 70
6. 18
3. 70
6. 18
3. 70
6. 17
3. 70
6. 05
3. 68
5. 97
3. 64
5. 89
3. 64
5. 76
3. 57
5. 55
3. 49
5. 23
3. 34

INDOOR
UNIT

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
3. 29
2. 67
3. 29
2. 67
3. 29
2. 67
3. 29
2. 67
3. 29
2. 67
3. 29
2. 67
3. 29
2. 67
3. 29
2. 67
3. 29
2. 67
3. 29
2. 67
3. 29
2. 67
3. 29
2. 67
3. 29
2. 67

INDOOR
UNIT

( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
3. 06
2. 23
3. 06
2. 23
3. 06
2. 23
3. 06
2. 23
3. 06
2. 23
3. 06
2. 23
3. 06
2. 23
3. 06
2. 23
3. 06
2. 23
3. 06
2. 23
3. 06
2. 23
3. 06
2. 23
3. 06
2. 23

MODEL : AU18
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
3. 82
2. 79
3. 82
2. 79
3. 82
2. 79
3. 82
2. 79
3. 82
2. 79
3. 82
2. 79
3. 82
2. 79
3. 82
2. 79
3. 82
2. 79
3. 82
2. 79
3. 82
2. 79
3. 82
2. 79
3. 82
2. 79

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
4. 12
3. 34
4. 12
3. 34
4. 12
3. 34
4. 12
3. 34
4. 12
3. 34
4. 12
3. 34
4. 12
3. 34
4. 12
3. 34
4. 12
3. 34
4. 12
3. 34
4. 12
3. 34
4. 12
3. 34
4. 12
3. 34

TC : Total Capacity kW
SHC : Sensible Heat Capacity kW

- (04 - 61) -

COOLING CAPACITY
4-8-7. CASSETTE TYPE (1/2)
MODEL : AU20
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
4. 36
3. 14
4. 36
3. 14
4. 36
3. 14
4. 36
3. 14
4. 36
3. 14
4. 36
3. 14
4. 36
3. 14
4. 36
3. 14
4. 36
3. 14
4. 36
3. 14
4. 36
3. 14
4. 36
3. 14
4. 36
3. 14

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
4. 69
3. 76
4. 69
3. 76
4. 69
3. 76
4. 69
3. 76
4. 69
3. 76
4. 69
3. 76
4. 69
3. 76
4. 69
3. 76
4. 69
3. 76
4. 69
3. 76
4. 69
3. 76
4. 69
3. 76
4. 69
3. 76

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
5. 36
3. 97
5. 36
3. 97
5. 36
3. 97
5. 36
3. 97
5. 36
3. 97
5. 36
3. 97
5. 36
3. 97
5. 36
3. 97
5. 36
3. 97
5. 36
3. 97
5. 36
3. 97
5. 36
3. 97
5. 36
3. 97

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
5. 70
3. 99
6. 04
3. 98
5. 70
3. 99
6. 04
3. 98
5. 70
3. 99
6. 04
3. 98
5. 70
3. 99
6. 04
3. 98
5. 70
3. 99
6. 04
3. 98
5. 70
3. 99
6. 04
3. 98
5. 70
3. 99
6. 04
3. 98
5. 70
3. 99
6. 04
3. 98
5. 70
3. 99
6. 04
3. 98
5. 70
3. 99
6. 04
3. 98
5. 70
3. 99
6. 04
3. 98
5. 70
3. 99
5. 95
3. 93
5. 48
3. 83
5. 60
3. 92

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
6. 71
4. 00
6. 71
4. 02
6. 71
4. 02
6. 71
4. 02
6. 71
4. 02
6. 71
4. 02
6. 71
4. 02
6. 71
4. 02
6. 68
4. 01
6. 58
3. 95
6. 44
3. 93
6. 20
3. 84
5. 84
3. 68

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
7. 04
4. 15
7. 04
4. 15
7. 04
4. 15
7. 04
4. 15
7. 04
4. 15
7. 04
4. 15
7. 04
4. 15
6. 90
4. 14
6. 81
4. 09
6. 72
4. 10
6. 57
4. 01
6. 32
3. 92
5. 96
3. 76

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
6. 64
5. 12
6. 64
5. 12
6. 64
5. 12
6. 64
5. 12
6. 64
5. 12
6. 64
5. 12
6. 64
5. 12
6. 64
5. 12
6. 64
5. 12
6. 64
5. 12
6. 64
5. 12
6. 64
5. 12
6. 63
5. 12

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
7. 05
5. 15
7. 46
5. 14
7. 05
5. 15
7. 46
5. 14
7. 05
5. 15
7. 46
5. 14
7. 05
5. 15
7. 46
5. 14
7. 05
5. 15
7. 46
5. 14
7. 05
5. 15
7. 46
5. 14
7. 05
5. 15
7. 46
5. 14
7. 05
5. 15
7. 46
5. 14
7. 05
5. 15
7. 46
5. 14
7. 05
5. 15
7. 46
5. 14
7. 05
5. 15
7. 46
5. 14
7. 05
5. 15
7. 36
5. 06
6. 77
4. 94
6. 93
5. 06

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
8. 29
5. 19
8. 29
5. 19
8. 29
5. 19
8. 29
5. 19
8. 29
5. 19
8. 29
5. 19
8. 29
5. 19
8. 29
5. 19
8. 26
5. 17
8. 14
5. 09
7. 97
5. 07
7. 67
4. 96
7. 23
4. 75

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
8. 71
5. 36
8. 71
5. 36
8. 71
5. 36
8. 71
5. 36
8. 71
5. 36
8. 71
5. 36
8. 71
5. 36
8. 54
5. 34
8. 42
5. 27
8. 31
5. 28
8. 13
5. 17
7. 82
5. 06
7. 38
4. 85

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
8. 28
6. 05
8. 28
6. 05
8. 28
6. 05
8. 28
6. 05
8. 28
6. 05
8. 28
6. 05
8. 28
6. 05
8. 28
6. 05
8. 28
6. 05
8. 28
6. 05
8. 28
6. 05
8. 28
6. 05
8. 28
6. 05

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
8. 80
6. 08
9. 32
6. 07
8. 80
6. 08
9. 32
6. 07
8. 80
6. 08
9. 32
6. 07
8. 80
6. 08
9. 32
6. 07
8. 80
6. 08
9. 32
6. 07
8. 80
6. 08
9. 32
6. 07
8. 80
6. 08
9. 32
6. 07
8. 80
6. 08
9. 32
6. 07
8. 80
6. 08
9. 32
6. 07
8. 80
6. 08
9. 32
6. 07
8. 80
6. 08
9. 32
6. 07
8. 80
6. 08
9. 18
5. 99
8. 45
5. 85
8. 65
5. 97

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
10. 4
6. 14
10. 4
6. 14
10. 4
6. 14
10. 4
6. 14
10. 4
6. 14
10. 4
6. 14
10. 4
6. 14
10. 4
6. 14
10. 3
6. 11
10. 2
6. 02
9. 94
5. 99
9. 57
5. 86
9. 02
5. 61

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
10. 9
6. 34
10. 9
6. 34
10. 9
6. 34
10. 9
6. 34
10. 9
6. 34
10. 9
6. 34
10. 9
6. 33
10. 7
6. 32
10. 5
6. 23
10. 4
6. 25
10. 1
6. 11
9. 76
5. 98
9. 21
5. 73

Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
5. 39
4. 05
5. 39
4. 05
5. 39
4. 05
5. 39
4. 05
5. 39
4. 05
5. 39
4. 05
5. 39
4. 05
5. 39
4. 05
5. 39
4. 05
5. 39
4. 05
5. 39
4. 05
5. 39
4. 05
5. 39
4. 05

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
5. 81
4. 84
5. 81
4. 84
5. 81
4. 84
5. 81
4. 84
5. 81
4. 84
5. 81
4. 84
5. 81
4. 84
5. 81
4. 84
5. 81
4. 84
5. 81
4. 84
5. 81
4. 84
5. 81
4. 84
5. 81
4. 84

MODEL : AU30
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
6. 73
4. 79
6. 73
4. 79
6. 73
4. 79
6. 73
4. 79
6. 73
4. 79
6. 73
4. 79
6. 73
4. 79
6. 73
4. 79
6. 73
4. 79
6. 73
4. 79
6. 73
4. 79
6. 73
4. 79
6. 73
4. 79

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
7. 25
5. 73
7. 25
5. 73
7. 25
5. 73
7. 25
5. 73
7. 25
5. 73
7. 25
5. 73
7. 25
5. 73
7. 25
5. 73
7. 25
5. 73
7. 25
5. 73
7. 25
5. 73
7. 25
5. 73
7. 25
5. 73

TC : Total Capacity kW
SHC : Sensible Heat Capacity kW

- (04 - 62) -

INDOOR
UNIT

INDOOR
UNIT

MODEL : AU25

COOLING CAPACITY
4-8-7. CASSETTE TYPE (2/2)

INDOOR
UNIT

( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
8. 03
5. 62
8. 03
5. 62
8. 03
5. 62
8. 03
5. 62
8. 03
5. 62
8. 03
5. 62
8. 03
5. 62
8. 03
5. 62
8. 03
5. 62
8. 03
5. 62
8. 03
5. 62
8. 03
5. 62
8. 03
5. 62

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
8. 65
6. 72
8. 65
6. 72
8. 65
6. 72
8. 65
6. 72
8. 65
6. 72
8. 65
6. 72
8. 65
6. 72
8. 65
6. 72
8. 65
6. 72
8. 65
6. 72
8. 65
6. 72
8. 65
6. 72
8. 65
6. 72

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
9. 88
7. 10
9. 88
7. 10
9. 88
7. 10
9. 88
7. 10
9. 88
7. 10
9. 88
7. 10
9. 88
7. 10
9. 88
7. 10
9. 88
7. 10
9. 88
7. 10
9. 88
7. 10
9. 88
7. 10
9. 88
7. 10

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
10. 5
7. 14
11. 1
7. 24
10. 5
7. 14
11. 1
7. 24
10. 5
7. 14
11. 1
7. 24
10. 5
7. 14
11. 1
7. 24
10. 5
7. 14
11. 1
7. 24
10. 5
7. 14
11. 1
7. 24
10. 5
7. 14
11. 1
7. 24
10. 5
7. 14
11. 1
7. 24
10. 5
7. 14
11. 1
7. 24
10. 5
7. 14
11. 1
7. 24
10. 5
7. 14
11. 1
7. 24
10. 5
7. 14
11. 0
7. 13
10. 1
6. 86
10. 3
7. 12

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
12. 4
7. 32
12. 4
7. 32
12. 4
7. 32
12. 4
7. 32
12. 4
7. 32
12. 4
7. 32
12. 4
7. 32
12. 4
7. 32
12. 3
7. 29
12. 1
7. 19
11. 9
7. 15
11. 4
6. 99
10. 8
6. 80

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
13. 0
7. 43
13. 0
7. 43
13. 0
7. 43
13. 0
7. 43
13. 0
7. 43
13. 0
7. 43
13. 0
7. 43
12. 7
7. 41
12. 5
7. 31
12. 4
7. 33
12. 1
7. 17
11. 7
7. 02
11. 0
6. 83

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
12. 0
8. 85
12. 0
8. 85
12. 0
8. 85
12. 0
8. 85
12. 0
8. 85
12. 0
8. 85
12. 0
8. 85
12. 0
8. 85
12. 0
8. 85
12. 0
8. 85
12. 0
8. 85
12. 0
8. 85
11. 9
8. 84

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
12. 7
8. 89
13. 4
8. 87
12. 7
8. 89
13. 4
8. 87
12. 7
8. 89
13. 4
8. 87
12. 7
8. 89
13. 4
8. 87
12. 7
8. 89
13. 4
8. 87
12. 7
8. 89
13. 4
8. 87
12. 7
8. 89
13. 4
8. 87
12. 7
8. 89
13. 4
8. 87
12. 7
8. 89
13. 4
8. 87
12. 7
8. 89
13. 4
8. 87
12. 7
8. 89
13. 4
8. 87
12. 7
8. 89
13. 3
8. 75
12. 2
8. 54
12. 5
8. 74

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
14. 9
8. 96
14. 9
8. 96
14. 9
8. 96
14. 9
8. 96
14. 9
8. 96
14. 9
8. 96
14. 9
8. 96
14. 9
8. 96
14. 9
8. 93
14. 7
8. 80
14. 4
8. 75
13. 8
8. 56
13. 0
8. 20

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
15. 7
9. 26
15. 7
9. 26
15. 7
9. 26
15. 7
9. 26
15. 7
9. 26
15. 7
9. 26
15. 7
9. 25
15. 4
9. 23
15. 2
9. 10
15. 0
9. 13
14. 6
8. 93
14. 1
8. 74
13. 3
8. 37

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
13. 3
9. 70
13. 3
9. 70
13. 3
9. 70
13. 3
9. 70
13. 3
9. 70
13. 3
9. 70
13. 3
9. 70
13. 3
9. 70
13. 3
9. 70
13. 3
9. 70
13. 3
9. 70
13. 3
9. 70
13. 3
9. 70

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
14. 1
9. 75
14. 9
9. 73
14. 1
9. 75
14. 9
9. 73
14. 1
9. 75
14. 9
9. 73
14. 1
9. 75
14. 9
9. 73
14. 1
9. 75
14. 9
9. 73
14. 1
9. 75
14. 9
9. 73
14. 1
9. 75
14. 9
9. 73
14. 1
9. 75
14. 9
9. 73
14. 1
9. 75
14. 9
9. 73
14. 1
9. 75
14. 9
9. 73
14. 1
9. 75
14. 9
9. 73
14. 1
9. 75
14. 7
9. 59
13. 5
9. 37
13. 9
9. 56

MODEL : AU45
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
9. 71
6. 99
9. 71
6. 99
9. 71
6. 99
9. 71
6. 99
9. 71
6. 99
9. 71
6. 99
9. 71
6. 99
9. 71
6. 99
9. 71
6. 99
9. 71
6. 99
9. 71
6. 99
9. 71
6. 99
9. 71
6. 99

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
10. 5
8. 37
10. 5
8. 37
10. 5
8. 37
10. 5
8. 37
10. 5
8. 37
10. 5
8. 37
10. 5
8. 37
10. 5
8. 37
10. 5
8. 37
10. 5
8. 37
10. 5
8. 37
10. 5
8. 37
10. 5
8. 37

MODEL : AU54
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
10. 8
7. 67
10. 8
7. 67
10. 8
7. 67
10. 8
7. 67
10. 8
7. 67
10. 8
7. 67
10. 8
7. 67
10. 8
7. 67
10. 8
7. 67
10. 8
7. 67
10. 8
7. 67
10. 8
7. 67
10. 8
7. 67

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
11. 6
9. 18
11. 6
9. 18
11. 6
9. 18
11. 6
9. 18
11. 6
9. 18
11. 6
9. 18
11. 6
9. 18
11. 6
9. 18
11. 6
9. 18
11. 6
9. 18
11. 6
9. 18
11. 6
9. 18
11. 6
9. 18

TC : Total Capacity kW
SHC : Sensible Heat Capacity kW

- (04 - 63) -

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
16. 6
9. 83
16. 6
9. 83
16. 6
9. 83
16. 6
9. 83
16. 6
9. 83
16. 6
9. 83
16. 6
9. 83
16. 6
9. 83
16. 5
9. 79
16. 3
9. 65
15. 9
9. 60
15. 3
9. 39
14. 5
8. 99

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
17. 4
10. 2
17. 4
10. 2
17. 4
10. 2
17. 4
10. 2
17. 4
10. 2
17. 4
10. 2
17. 4
10. 1
17. 1
10. 1
16. 8
9. 98
16. 6
10. 0
16. 3
9. 79
15. 6
9. 58
14. 8
9. 18

INDOOR
UNIT

MODEL : AU36
Outdoor
Temperature

COOLING CAPACITY
4-8-8. WALL MOUNTED TYPE
MODEL : AS18
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
4. 13
3. 06
4. 13
3. 06
4. 13
3. 06
4. 13
3. 06
4. 13
3. 06
4. 13
3. 06
4. 13
3. 06
4. 13
3. 06
4. 13
3. 06
4. 13
3. 06
4. 13
3. 06
4. 13
3. 06
4. 13
3. 06

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
4. 45
3. 66
4. 45
3. 66
4. 45
3. 66
4. 45
3. 66
4. 45
3. 66
4. 45
3. 66
4. 45
3. 66
4. 45
3. 66
4. 45
3. 66
4. 45
3. 66
4. 45
3. 66
4. 45
3. 66
4. 45
3. 66

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
5. 08
3. 87
5. 08
3. 87
5. 08
3. 87
5. 08
3. 87
5. 08
3. 87
5. 08
3. 87
5. 08
3. 87
5. 08
3. 87
5. 08
3. 87
5. 08
3. 87
5. 08
3. 87
5. 08
3. 87
5. 08
3. 87

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
5. 40
3. 89
5. 72
3. 94
5. 40
3. 89
5. 72
3. 94
5. 40
3. 89
5. 72
3. 94
5. 40
3. 89
5. 72
3. 94
5. 40
3. 89
5. 72
3. 94
5. 40
3. 89
5. 72
3. 94
5. 40
3. 89
5. 72
3. 94
5. 40
3. 89
5. 72
3. 94
5. 40
3. 89
5. 72
3. 94
5. 40
3. 89
5. 72
3. 94
5. 40
3. 89
5. 72
3. 94
5. 40
3. 89
5. 63
3. 88
5. 19
3. 74
5. 31
3. 88

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
6. 35
3. 99
6. 35
3. 99
6. 35
3. 99
6. 35
3. 99
6. 35
3. 99
6. 35
3. 99
6. 35
3. 99
6. 35
3. 99
6. 32
3. 97
6. 24
3. 91
6. 10
3. 89
6. 87
3. 81
5. 53
3. 70

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
6. 67
4. 05
6. 67
4. 05
6. 67
4. 05
6. 67
4. 05
6. 67
4. 05
6. 67
4. 05
6. 67
4. 05
6. 54
4. 04
6. 45
3. 98
6. 36
3. 99
6. 23
3. 91
5. 99
3. 82
5. 65
3. 72

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
6. 49
4. 87
6. 49
4. 87
6. 49
4. 87
6. 49
4. 87
6. 49
4. 87
6. 49
4. 87
6. 49
4. 87
6. 49
4. 87
6. 49
4. 87
6. 49
4. 87
6. 49
4. 87
6. 49
4. 87
6. 49
4. 87

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
6. 90
4. 90
7. 31
4. 89
6. 90
4. 90
7. 31
4. 89
6. 90
4. 90
7. 31
4. 89
6. 90
4. 90
7. 31
4. 89
6. 90
4. 90
7. 31
4. 89
6. 90
4. 90
7. 31
4. 89
6. 90
4. 90
7. 31
4. 89
6. 90
4. 90
7. 31
4. 89
6. 90
4. 90
7. 31
4. 89
6. 90
4. 90
7. 31
4. 89
6. 90
4. 90
7. 31
4. 89
6. 90
4. 90
7. 20
4. 82
6. 63
4. 71
6. 78
4. 81

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
8. 12
4. 94
8. 12
4. 94
8. 12
4. 94
8. 12
4. 94
8. 12
4. 94
8. 12
4. 94
8. 12
4. 94
8. 12
4. 94
8. 08
5. 92
7. 97
5. 85
7. 80
5. 82
7. 50
4. 72
7. 07
4. 52

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
8. 52
5. 10
8. 52
5. 10
8. 52
5. 10
8. 52
5. 10
8. 52
5. 10
8. 52
5. 10
8. 52
5. 10
8. 36
5. 08
8. 24
5. 02
8. 13
5. 03
7. 95
4. 92
7. 66
4. 81
7. 22
4. 61

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
7. 53
5. 65
7. 53
5. 65
7. 53
5. 65
7. 53
5. 65
7. 53
5. 65
7. 53
5. 65
7. 53
5. 65
7. 53
5. 65
7. 53
5. 65
7. 53
5. 65
7. 53
5. 65
7. 53
5. 65
7. 53
5. 65

Indoor Temperature
27 CDB/19 CWB 28 CDB/20 CWB
81 FDB/66 FWB 82 FDB/68 FWB
TC
SHC
TC
SHC
8. 00
5. 68
8. 47
5. 67
8. 00
5. 68
8. 47
5. 67
8. 00
5. 68
8. 47
5. 67
8. 00
5. 68
8. 47
5. 67
8. 00
5. 68
8. 47
5. 67
8. 00
5. 68
8. 47
5. 67
8. 00
5. 68
8. 47
5. 67
8. 00
5. 68
8. 47
5. 67
8. 00
5. 68
8. 47
5. 67
8. 00
5. 68
8. 47
5. 67
8. 00
5. 68
8. 47
5. 67
8. 00
5. 68
8. 35
5. 59
7. 69
5. 46
7. 86
5. 58

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
9. 41
5. 73
9. 41
5. 73
9. 41
5. 73
9. 41
5. 73
9. 41
5. 73
9. 41
5. 73
9. 41
5. 73
9. 41
5. 73
9. 37
5. 70
9. 24
5. 62
9. 04
5. 59
8. 70
5. 47
8. 20
5. 24

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
9. 88
5. 91
9. 88
5. 91
9. 88
5. 91
9. 88
5. 91
9. 88
5. 91
9. 88
5. 91
9. 88
5. 91
9. 69
5. 90
9. 56
5. 82
9. 42
5. 83
9. 22
5. 71
8. 88
5. 58
8. 37
5. 35

Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
5. 28
3. 85
5. 28
3. 85
5. 28
3. 85
5. 28
3. 85
5. 28
3. 85
5. 28
3. 85
5. 28
3. 85
5. 28
3. 85
5. 28
3. 85
5. 28
3. 85
5. 28
3. 85
5. 28
3. 85
5. 28
3. 85

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
5. 68
4. 61
5. 68
4. 61
5. 68
4. 61
5. 68
4. 61
5. 68
4. 61
5. 68
4. 61
5. 68
4. 61
5. 68
4. 61
5. 68
4. 61
5. 68
4. 61
5. 68
4. 61
5. 68
4. 61
5. 68
4. 61

MODEL : AS30
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
6. 12
4. 47
6. 12
4. 47
6. 12
4. 47
6. 12
4. 47
6. 12
4. 47
6. 12
4. 47
6. 12
4. 47
6. 12
4. 47
6. 12
4. 47
6. 12
4. 47
6. 12
4. 47
6. 12
4. 47
6. 12
4. 47

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
6. 59
5. 35
6. 59
5. 35
6. 59
5. 35
6. 59
5. 35
6. 59
5. 35
6. 59
5. 35
6. 59
5. 35
6. 59
5. 35
6. 59
5. 35
6. 59
5. 35
6. 59
5. 35
6. 59
5. 35
6. 59
5. 35

TC : Total Capacity kW
SHC : Sensible Heat Capacity kW

- (04 - 64) -

INDOOR
UNIT

INDOOR
UNIT

MODEL : AS24

COOLING CAPACITY
4-8-9. CEILING WALL TYPE (1/2)

MODEL : AW7
20 CDB/15 CWB
TC
SHC
1.64
1.23
1.64
1.23
1.64
1.23
1.64
1.23
1.64
1.23
1.64
1.23
1.64
1.23
1.64
1.23
1.64
1.23
1.64
1.23
1.64
1.23
1.64
1.23
1.64
1.23

23 CDB/16 CWB
TC
SHC
1.77
1.48
1.77
1.48
1.77
1.48
1.77
1.48
1.77
1.48
1.77
1.48
1.77
1.48
1.77
1.48
1.77
1.48
1.77
1.48
1.77
1.48
1.77
1.48
1.77
1.48

Indoor Temperature
26 CDB/18 CWB 27 CDB/19 CWB
TC
SHC
TC
SHC
2.02
1.56
2.15
1.57
2.02
1.56
2.15
1.57
2.02
1.56
2.15
1.57
2.02
1.56
2.15
1.57
2.02
1.56
2.15
1.57
2.02
1.56
2.15
1.57
2.02
1.56
2.15
1.57
2.02
1.56
2.15
1.57
2.02
1.56
2.15
1.57
2.02
1.56
2.15
1.57
2.02
1.56
2.15
1.57
2.02
1.56
2.15
1.57
2.02
1.56
2.07
1.51

28 CDB/20 CWB
TC
SHC
2.28
1.57
2.28
1.57
2.28
1.57
2.28
1.57
2.28
1.57
2.28
1.57
2.28
1.57
2.28
1.57
2.28
1.57
2.28
1.57
2.28
1.57
2.24
1.54
2.11
1.54

30 CDB/22 CWB
TC
SHC
2.53
1.58
2.53
1.58
2.53
1.58
2.53
1.58
2.53
1.58
2.53
1.58
2.53
1.58
2.53
1.58
2.52
1.53
2.48
1.55
2.43
1.55
2.34
1.51
2.20
1.45

32 CDB/23 CWB
TC
SHC
2.66
1.63
2.66
1.63
2.66
1.63
2.66
1.63
2.66
1.63
2.66
1.63
2.66
1.63
2.60
1.63
2.57
1.61
2.53
1.61
2.48
1.58
2.39
1.54
2.25
1.48

Indoor Temperature
26 CDB/18 CWB 27 CDB/19 CWB
TC
SHC
TC
SHC
2.64
2.03
2.80
2.04
2.64
2.03
2.80
2.04
2.64
2.03
2.80
2.04
2.64
2.03
2.80
2.04
2.64
2.03
2.80
2.04
2.64
2.03
2.80
2.04
2.64
2.03
2.80
2.04
2.64
2.03
2.80
2.04
2.64
2.03
2.80
2.04
2.64
2.03
2.80
2.04
2.64
2.03
2.80
2.04
2.64
2.03
2.80
2.04
2.63
2.03
2.69
1.96

28 CDB/20 CWB
TC
SHC
2.96
2.04
2.96
2.04
2.96
2.04
2.96
2.04
2.96
2.04
2.96
2.04
2.96
2.04
2.96
2.04
2.96
2.04
2.96
2.04
2.96
2.04
2.92
2.01
2.75
2.01

30 CDB/22 CWB
TC
SHC
3.29
2.06
3.29
2.06
3.29
2.06
3.29
2.06
3.29
2.06
3.29
2.06
3.29
2.06
3.29
2.06
3.28
2.05
3.23
2.02
3.16
2.01
3.04
1.97
2.87
1.89

32 CDB/23 CWB
TC
SHC
3.46
2.13
3.46
2.13
3.46
2.13
3.46
2.13
3.46
2.13
3.46
2.13
3.46
2.13
3.39
2.12
3.34
2.09
3.30
2.10
3.23
2.05
3.11
2.01
2.93
1.92

Indoor Temperature
26 CDB/18 CWB 27 CDB/19 CWB
TC
SHC
TC
SHC
3.39
2.61
3.60
2.63
3.39
2.61
3.60
2.63
3.39
2.61
3.60
2.63
3.39
2.61
3.60
2.63
3.39
2.61
3.60
2.63
3.39
2.61
3.60
2.63
3.39
2.61
3.60
2.63
3.39
2.61
3.60
2.63
3.39
2.61
3.60
2.63
3.39
2.61
3.60
2.63
3.39
2.61
3.60
2.63
3.39
2.61
3.60
2.63
3.39
2.61
3.46
2.52

28 CDB/20 CWB
TC
SHC
3.81
2.62
3.81
2.62
3.81
2.62
3.81
2.62
3.81
2.62
3.81
2.62
3.81
2.62
3.81
2.62
3.81
2.62
3.81
2.62
3.81
2.62
3.76
2.59
2.58
3.54

30 CDB/22 CWB
TC
SHC
4.24
2.65
4.24
2.65
4.24
2.65
4.24
2.65
4.24
2.65
4.24
2.65
4.24
2.65
4.24
2.65
4.22
2.64
4.16
2.60
4.07
2.59
3.91
2.53
3.69
2.42

32 CDB/23 CWB
TC
SHC
4.45
2.74
4.45
2.74
4.45
2.74
4.45
2.74
4.45
2.74
4.45
2.74
4.45
2.74
4.36
2.73
4.30
2.69
4.24
2.70
4.15
2.64
3.99
2.58
2.47
3.77

INDOOR
UNIT

INDOOR
UNIT

Outdoor
Temperature
( CDB) ( FDB)
10
50
15
59
20
68
23
73
25
77
27
81
30
86
33
91
35
95
37
99
40
104
45
113
52
125

MODEL : AW9
Outdoor
Temperature
( CDB) ( FDB)
10
50
15
59
20
68
23
73
25
77
27
81
30
86
33
91
35
95
37
99
40
104
45
113
52
125

20 CDB/15 CWB
TC
SHC
2.14
1.61
2.14
1.61
2.14
1.61
2.14
1.61
2.14
1.61
2.14
1.61
2.14
1.61
2.14
1.61
2.14
1.61
2.14
1.61
2.14
1.61
2.14
1.61
2.14
1.61

23 CDB/16 CWB
TC
SHC
2.31
1.92
2.31
1.92
2.31
1.92
2.31
1.92
2.31
1.92
2.31
1.92
2.31
1.92
2.31
1.92
2.31
1.92
2.31
1.92
2.31
1.92
2.31
1.92
2.31
1.92

MODEL : AW12
Outdoor
Temperature
( CDB) ( FDB)
10
50
15
59
20
68
23
73
25
77
27
81
30
86
33
91
35
95
37
99
40
104
45
113
52
125

20 CDB/15 CWB
TC
SHC
2.75
2.07
2.75
2.07
2.75
2.07
2.75
2.07
2.75
2.07
2.75
2.07
2.75
2.07
2.75
2.07
2.75
2.07
2.75
2.07
2.75
2.07
2.75
2.07
2.75
2.07

23 CDB/16 CWB
TC
SHC
2.96
2.47
2.96
2.47
2.96
2.47
2.96
2.47
2.96
2.47
2.96
2.47
2.96
2.47
2.96
2.47
2.96
2.47
2.96
2.47
2.96
2.47
2.96
2.47
2.47
2.96

TC : Total Capacity kW
SHC : Sensible Heat Capacity kW

- (04 - 65) -

COOLING CAPACITY
4-8-9. CEILING WALL TYPE (2/2)
MODEL : AW14
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
3.29
2.47
3.29
2.47
3.29
2.47
3.29
2.47
3.29
2.47
3.29
2.47
3.29
2.47
3.29
2.47
3.29
2.47
3.29
2.47
3.29
2.47
3.29
2.47
3.29
2.47

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
3.54
2.95
3.54
2.95
3.54
2.95
3.54
2.95
3.54
2.95
3.54
2.95
3.54
2.95
3.54
2.95
3.54
2.95
3.54
2.95
3.54
2.95
3.54
2.95
3.54
2.95

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
4.05
3.12
4.05
3.12
4.05
3.12
4.05
3.12
4.05
3.12
4.05
3.12
4.05
3.12
4.05
3.12
4.05
3.12
4.05
3.12
4.05
3.12
4.05
3.12
4.05
3.12

Indoor Temperature
27 CDB/19 CWB
81 FDB/66 FWB
TC
SHC
4.30
3.14
4.30
3.14
4.30
3.14
4.30
3.14
4.30
3.14
4.30
3.14
4.30
3.14
4.30
3.14
4.30
3.14
4.30
3.14
4.30
3.14
4.30
3.14
4.30
3.02

28 CDB/20 CWB
82 FDB/68 FWB
TC
SHC
4.55
3.13
4.55
3.13
4.55
3.13
4.55
3.13
4.55
3.13
4.55
3.13
4.55
3.13
4.55
3.13
4.55
3.13
4.55
3.13
4.55
3.13
4.49
3.09
4.23
3.13

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
5.06
3.17
5.06
3.17
5.06
3.17
5.06
3.17
5.06
3.17
5.06
3.17
5.06
3.17
5.06
3.17
5.04
3.15
4.97
3.11
4.86
3.09
4.68
3.02
4.41
2.90

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
5.31
3.27
5.31
3.27
5.31
3.27
5.31
3.27
5.31
3.27
5.31
3.27
5.31
3.27
5.21
3.26
5.14
3.21
5.07
3.22
4.96
3.15
4.77
3.08
4.50
2.96

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
5.08
3.87
5.08
3.87
5.08
3.87
5.08
3.87
5.08
3.87
5.08
3.87
5.08
3.87
5.08
3.87
5.08
3.87
5.08
3.87
5.08
3.87
5.08
3.87
5.08
3.87

Indoor Temperature
27 CDB/19 CWB
81 FDB/66 FWB
TC
SHC
5.40
3.89
5.40
3.89
5.40
3.89
5.40
3.89
5.40
3.89
5.40
3.89
5.40
3.89
5.40
3.89
5.40
3.89
5.40
3.89
5.40
3.89
5.40
3.89
5.19
3.79

28 CDB/20 CWB
82 FDB/68 FWB
TC
SHC
5.72
3.88
5.72
3.88
5.72
3.88
5.72
3.88
5.72
3.88
5.72
3.88
5.72
3.88
5.72
3.88
5.72
3.88
5.72
3.88
5.72
3.88
5.63
3.82
5.31
3.82

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
6.35
3.92
6.35
3.92
6.35
3.92
6.35
3.92
6.35
3.92
6.35
3.92
6.35
3.92
6.35
3.92
6.32
3.90
6.24
3.85
6.10
3.83
6.87
3.74
5.53
3.59

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
6.67
4.05
6.67
4.05
6.67
4.05
6.67
4.05
6.67
4.05
6.67
4.05
6.67
4.05
6.54
4.04
6.45
3.98
6.36
3.99
6.23
3.91
5.99
3.82
5.65
3.66

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
6.49
4.87
6.49
4.87
6.49
4.87
6.49
4.87
6.49
4.87
6.49
4.87
6.49
4.87
6.49
4.87
6.49
4.87
6.49
4.87
6.49
4.87
6.49
4.87
6.49
4.87

Indoor Temperature
27 CDB/19 CWB
81 FDB/66 FWB
TC
SHC
6.90
4.90
6.90
4.90
6.90
4.90
6.90
4.90
6.90
4.90
6.90
4.90
6.90
4.90
6.90
4.90
6.90
4.90
6.90
4.90
6.90
4.90
6.90
4.90
6.63
4.71

28 CDB/20 CWB
82 FDB/68 FWB
TC
SHC
7.31
4.89
7.31
4.89
7.31
4.89
7.31
4.89
7.31
4.89
7.31
4.89
7.31
4.89
7.31
4.89
7.31
4.89
7.31
4.89
7.31
4.89
7.20
4.82
6.78
4.81

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
8.12
4.94
8.12
4.94
8.12
4.94
8.12
4.94
8.12
4.94
8.12
4.94
8.12
4.94
8.12
4.94
8.08
4.92
7.97
4.85
7.80
4.82
7.50
4.72
7.07
4.52

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
8.52
5.10
8.52
5.10
8.52
5.10
8.52
5.10
8.52
5.10
8.52
5.10
8.52
5.10
8.36
5.08
8.24
5.02
8.13
5.03
7.95
4.92
7.66
4.81
7.22
4.61

26 CDB/18 CWB
79 FDB/64 FWB
TC
SHC
7.53
5.65
7.53
5.65
7.53
5.65
7.53
5.65
7.53
5.65
7.53
5.65
7.53
5.65
7.53
5.65
7.53
5.65
7.53
5.65
7.53
5.65
7.53
5.65
7.53
5.65

Indoor Temperature
27 CDB/19 CWB
81 FDB/66 FWB
TC
SHC
8.00
5.68
8.00
5.68
8.00
5.68
8.00
5.68
8.00
5.68
8.00
5.68
8.00
5.68
8.00
5.68
8.00
5.68
8.00
5.68
8.00
5.68
8.00
5.68
7.69
5.46

28 CDB/20 CWB
82 FDB/68 FWB
TC
SHC
8.47
5.67
8.47
5.67
8.47
5.67
8.47
5.67
8.47
5.67
8.47
5.67
8.47
5.67
8.47
5.67
8.47
5.67
8.47
5.67
8.47
5.67
8.35
5.59
7.86
5.58

30 CDB/22 CWB
86 FDB/72 FWB
TC
SHC
9.41
5.73
9.41
5.73
9.41
5.73
9.41
5.73
9.41
5.73
9.41
5.73
9.41
5.73
9.41
5.73
9.37
5.70
9.24
5.62
9.04
5.59
8.70
5.47
8.20
5.24

32 CDB/23 CWB
90 FDB/73 FWB
TC
SHC
9.88
5.91
9.88
5.91
9.88
5.91
9.88
5.91
9.88
5.91
9.88
5.91
9.88
5.91
9.69
5.90
9.56
5.82
9.42
5.83
9.22
5.71
8.88
5.58
8.37
5.35

INDOOR
UNIT

( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
4.13
3.06
4.13
3.06
4.13
3.06
4.13
3.06
4.13
3.06
4.13
3.06
4.13
3.06
4.13
3.06
4.13
3.06
4.13
3.06
4.13
3.06
4.13
3.06
4.13
3.06

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
4.45
3.66
4.45
3.66
4.45
3.66
4.45
3.66
4.45
3.66
4.45
3.66
4.45
3.66
4.45
3.66
4.45
3.66
4.45
3.66
4.45
3.66
4.45
3.66
4.45
3.66

MODEL : AW24
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
5.28
3.85
5.28
3.85
5.28
3.85
5.28
3.85
5.28
3.85
5.28
3.85
5.28
3.85
5.28
3.85
5.28
3.85
5.28
3.85
5.28
3.85
5.28
3.85
5.28
3.85

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
5.68
4.61
5.68
4.61
5.68
4.61
5.68
4.61
5.68
4.61
5.68
4.61
5.68
4.61
5.68
4.61
5.68
4.61
5.68
4.61
5.68
4.61
5.68
4.61
5.68
4.61

MODEL : AW30
Outdoor
Temperature
( CDB)
10
15
20
23
25
27
30
33
35
37
40
45
52

( FDB)
50
59
68
73
77
81
86
91
95
99
104
113
125

20 CDB/15 CWB
68 FDB/59 FWB
TC
SHC
6.12
4.47
6.12
4.47
6.12
4.47
6.12
4.47
6.12
4.47
6.12
4.47
6.12
4.47
6.12
4.47
6.12
4.47
6.12
4.47
6.12
4.47
6.12
4.47
6.12
4.47

23 CDB/16 CWB
73 FDB/61 FWB
TC
SHC
6.59
5.35
6.59
5.35
6.59
5.35
6.59
5.35
6.59
5.35
6.59
5.35
6.59
5.35
6.59
5.35
6.59
5.35
6.59
5.35
6.59
5.35
6.59
5.35
6.59
5.35

TC : Total Capacity kW
SHC : Sensible Heat Capacity kW

- (04 - 66) -

INDOOR
UNIT

MODEL : AW18
Outdoor
Temperature

HEATING CAPACITY
4-9. CAPACITY TABLE HEATING
4-9-1. UNIVERSAL FLOOR / CEILING TYPE
MODEL : AB12
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
2. 75
2. 66
2. 60
2. 50
2. 44
2. 37
3. 12
3. 03
2. 96
2. 87
2. 80
2. 74
3. 55
3. 45
3. 38
3. 28
3. 22
3. 14
4. 02
3. 92
3. 85
3. 69
3. 42
3. 14
4. 55
4. 37
4. 10
3. 69
3. 42
3. 14
4. 77
4. 37
4. 10
3. 69
3. 42
3. 14
4. 78
4. 37
4. 10
3. 69
3. 42
3. 14
4. 78
4. 37
4. 10
3. 69
3. 42
3. 14

MODEL : AB14
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
3. 36
3. 24
3. 16
3. 05
2. 97
2. 89
3. 81
3. 69
3. 61
3. 50
3. 42
3. 34
4. 33
4. 20
4. 12
4. 00
3. 92
3. 83
4. 90
4. 77
4. 69
4. 50
4. 17
3. 83
5. 55
5. 33
5. 00
4. 50
4. 17
3. 83
5. 82
5. 33
5. 00
4. 50
4. 17
3. 83
5. 83
5. 33
5. 00
4. 50
4. 17
3. 83
5. 83
5. 33
5. 00
4. 50
4. 17
3. 83

MODEL : AB18
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
3. 76
3. 63
3. 54
3. 42
3. 33
3. 24
4. 26
4. 13
4. 05
3. 92
3. 83
3. 74
4. 84
4. 71
4. 62
4. 48
4. 39
4. 29
5. 49
5. 35
5. 25
5. 04
4. 67
4. 29
6. 21
5. 97
5. 60
5. 04
4. 67
4. 29
6. 51
5. 97
5. 60
5. 04
4. 67
4. 29
6. 53
5. 97
5. 60
5. 04
4. 67
4. 29
6. 53
5. 97
5. 60
5. 04
4. 67
4. 29

MODEL : AB24
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
5. 17
4. 99
4. 87
4. 70
4. 58
4. 46
5. 86
5. 68
5. 56
5. 38
5. 26
5. 14
6. 66
6. 48
6. 35
6. 17
6. 04
5. 90
7. 55
7. 35
7. 22
6. 93
6. 42
5. 90
8. 54
8. 21
7. 70
6. 93
6. 42
5. 90
8. 96
8. 21
7. 70
6. 93
6. 42
5. 90
8. 98
8. 21
8. 70
6. 93
6. 42
5. 90
8. 98
8. 21
8. 70
6. 93
6. 42
5. 90

TC : Total Capacity kW

- (04 - 67) -

INDOOR
UNIT

INDOOR
UNIT

Outdoor
Temperature

HEATING CAPACITY
4-9-2. LARGE CEILING TYPE
MODEL : AB30
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
6. 11
5. 90
5. 76
5. 55
5. 41
5. 27
6. 93
6. 72
6. 58
6. 36
6. 22
6. 08
7. 87
7. 65
7. 51
7. 29
7. 14
6. 98
8. 92
8. 69
8. 54
8. 19
7. 58
6. 98
10. 1
9. 71
9. 10
8. 19
7. 58
6. 98
10. 6
9. 71
9. 10
8. 19
7. 58
6. 98
10. 6
9. 71
9. 10
8. 19
7. 58
6. 98
10. 6
9. 71
9. 10
8. 19
7. 58
6. 98

MODEL : AB36
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32
41 RH85%
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
7. 19
6. 94
6. 77
6. 53
6. 36
6. 20
8. 15
7. 90
7. 73
7. 48
7. 32
7. 15
9. 26
9. 00
8. 83
8. 57
8. 40
8. 20
10. 5
10. 2
10. 0
9. 63
8. 92
8. 20
11. 9
11. 4
10. 7
9. 63
8. 92
8. 20
12. 4
11. 4
10. 7
9. 63
8. 92
8. 20
12. 5
11. 4
10. 7
9. 63
8. 92
8. 20
12. 5
11. 4
10. 7
9. 63
8. 92
8. 20

MODEL : AB45
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32
41 RH85%
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
9. 20
8. 88
8. 67
8. 35
8. 14
7. 93
10. 4
10. 1
9. 90
9. 58
9. 37
9. 15
11. 9
11. 5
11. 3
11. 0
10. 7
10. 5
13. 4
13. 1
12. 8
12. 3
11. 4
10. 5
15. 2
14. 6
13. 7
12. 3
11. 4
10. 5
15. 9
14. 6
13. 7
12. 3
11. 4
10. 5
16. 0
14. 6
13. 7
12. 3
11. 4
10. 5
16. 0
14. 6
13. 7
12. 3
11. 4
10. 5

MODEL : AB54
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32
41 RH85%
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
10. 6
10. 2
10. 0
9. 64
9. 39
9. 15
12. 0
11. 7
11. 4
11. 0
10. 8
10. 6
13. 7
13. 3
13. 0
12. 7
12. 4
12. 1
15. 5
15. 1
14. 8
14. 2
13. 2
12. 1
17. 5
16. 9
15. 8
14. 2
13. 2
12. 1
18. 4
16. 9
15. 8
14. 2
13. 2
12. 1
18. 4
16. 9
15. 8
14. 2
13. 2
12. 1
18. 4
16. 9
15. 8
14. 2
13. 2
12. 1

TC : Total Capacity kW

- (04 - 68) -

INDOOR
UNIT

INDOOR
UNIT

Outdoor
Temperature

HEATING CAPACITY
4-9-3. COMPACT DUCT TYPE
MODEL : AR7
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
1. 65
1. 59
1. 55
1. 49
1. 46
1. 42
1. 87
1. 81
1. 77
1. 71
1. 68
1. 64
2. 12
2. 06
2. 02
1. 96
1. 92
1. 88
2. 40
2. 34
2. 30
2. 21
2. 04
1. 88
2. 72
2. 61
2. 45
2. 21
2. 04
1. 88
2. 85
2. 61
2. 45
2. 21
2. 04
1. 88
2. 86
2. 61
2. 45
2. 21
2. 04
1. 88
2. 86
2. 61
2. 45
2. 21
2. 04
1. 88

MODEL : AR9
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
2. 08
2. 01
1. 96
1. 89
1. 84
1. 79
2. 36
2. 29
2. 24
2. 17
2. 12
2. 07
2. 68
2. 61
2. 56
2. 48
2. 43
2. 38
3. 04
2. 96
2. 91
2. 79
2. 58
2. 38
3. 44
3. 31
3. 10
2. 79
2. 58
2. 38
3. 61
3. 31
3. 10
2. 79
2. 58
2. 38
3. 62
3. 31
3. 10
2. 79
2. 58
2. 38
3. 62
3. 31
3. 10
2. 79
2. 58
2. 38

MODEL : AR12
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
2. 75
2. 66
2. 60
2. 50
2. 44
2. 37
3. 12
3. 03
2. 96
2. 87
2. 80
2. 74
3. 55
3. 45
3. 38
3. 28
3. 22
3. 14
4. 02
3. 92
3. 85
3. 69
3. 42
3. 14
4. 55
4. 37
4. 10
3. 69
3. 42
3. 14
4. 77
4. 37
4. 10
3. 69
3. 42
3. 14
4. 78
4. 37
4. 10
3. 69
3. 42
3. 14
4. 78
4. 37
4. 10
3. 69
3. 42
3. 14

MODEL : AR14
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
3. 22
3. 11
3. 04
2. 93
2. 85
2. 78
3. 65
3. 54
3. 47
3. 36
3. 28
3. 21
4. 15
4. 04
3. 96
3. 84
3. 77
3. 68
4. 71
4. 58
4. 50
4. 32
4. 00
3. 68
5. 32
5. 12
4. 80
4. 32
4. 00
3. 68
5. 58
5. 12
4. 80
4. 32
4. 00
3. 68
5. 60
5. 12
4. 80
4. 32
4. 00
3. 68
5. 60
5. 12
4. 80
4. 32
4. 00
3. 68

MODEL : AR18
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
3. 76
3. 63
3. 54
3. 42
3. 33
3. 24
4. 26
4. 13
4. 05
3. 92
3. 83
3. 74
4. 84
4. 71
4. 62
4. 48
4. 39
4. 29
5. 49
5. 35
5. 25
5. 04
4. 67
4. 29
6. 21
5. 97
5. 60
5. 04
4. 67
4. 29
6. 51
5. 97
5. 60
5. 04
4. 67
4. 29
6. 53
5. 97
5. 60
5. 04
4. 67
4. 29
6. 53
6. 97
5. 60
5. 04
4. 67
4. 29

TC : Total Capacity kW

- (04 - 69) -

INDOOR
UNIT

INDOOR
UNIT

Outdoor
Temperature

HEATING CAPACITY
4-9-4. DUCT TYPE
MODEL : AR25
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
5. 27
5. 09
4. 97
4. 79
4. 67
4. 55
5. 98
5. 79
5. 67
5. 49
5. 37
5. 25
6. 79
6. 60
6. 48
6. 29
6. 16
6. 02
7. 70
7. 50
7. 36
7. 07
6. 54
6. 02
8. 71
8. 37
7. 85
7. 07
6. 54
6. 02
9. 13
8. 37
7. 85
7. 07
6. 54
6. 02
9. 16
8. 37
7. 85
7. 07
6. 54
6. 02
9. 16
8. 37
7. 85
7. 07
6. 54
6. 02

MODEL : AR30
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
6. 11
5. 90
5. 76
5. 55
5. 41
5. 27
6. 93
6. 72
6. 58
6. 36
6. 22
6. 08
7. 87
7. 65
7. 51
7. 29
7. 14
6. 98
8. 92
8. 69
8. 54
8. 19
7. 58
6. 98
10. 1
9. 71
9. 10
8. 19
7. 58
6. 98
10. 6
9. 71
9. 10
8. 19
7. 58
6. 98
10. 6
9. 71
9. 10
8. 19
7. 58
6. 98
10. 6
9. 71
9. 10
8. 19
7. 58
6. 98

MODEL : AR36
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
7. 19
6. 94
6. 77
6. 53
6. 36
6. 20
8. 15
7. 90
7. 73
7. 48
7. 32
7. 15
9. 26
9. 00
8. 83
8. 57
8. 40
8. 20
10. 5
10. 2
10. 0
9. 63
8. 92
8. 20
11. 9
11. 4
10. 7
9. 63
8. 92
8. 20
12. 4
11. 4
10. 7
9. 63
8. 92
8. 20
12. 5
11. 4
10. 7
9. 63
8. 92
8. 20
12. 5
11. 4
10. 7
9. 63
8. 92
8. 20

MODEL : AR45
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
9. 20
8. 88
8. 67
8. 35
8. 14
7. 93
10. 4
10. 1
9. 90
9. 58
9. 37
9. 15
11. 9
11. 5
11. 3
11. 0
10. 7
10. 5
13. 4
13. 1
12. 8
12. 3
11. 4
10. 5
15. 2
14. 6
13. 7
12. 3
11. 4
10. 5
15. 9
14. 6
13. 7
12. 3
11. 4
10. 5
16. 0
14. 6
13. 7
12. 3
11. 4
10. 5
16. 0
14. 6
13. 7
12. 3
11. 4
10. 5

TC : Total Capacity kW

- (04 - 70) -

INDOOR
UNIT

INDOOR
UNIT

Outdoor
Temperature

HEATING CAPACITY
4-9-5. HIGH STATIC PRESSURE DUCT TYPE
MODEL : AR36H
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
7. 19
6. 94
6. 77
6. 53
6. 36
6. 20
8. 15
7. 90
7. 73
7. 48
7. 32
7. 15
9. 26
9. 00
8. 83
8. 57
8. 40
8. 20
10. 5
10. 2
10. 0
9. 63
8. 92
8. 20
11. 9
11. 4
10. 7
9. 63
8. 92
8. 20
12. 4
11. 4
10. 7
9. 63
8. 92
8. 20
12. 5
11. 4
10. 7
9. 63
8. 92
8. 20
12. 5
11. 4
10. 7
9. 63
8. 92
8. 20

MODEL : AR45H
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
9. 20
8. 88
8. 67
8. 35
8. 14
7. 93
10. 4
10. 1
9. 90
9. 58
9. 37
9. 15
11. 9
11. 5
11. 3
11. 0
10. 7
10. 5
13. 4
13. 1
12. 8
12. 3
11. 4
10. 5
15. 2
14. 6
13. 7
12. 3
11. 4
10. 5
15. 9
14. 6
13. 7
12. 3
11. 4
10. 5
16. 0
14. 6
13. 7
12. 3
11. 4
10. 5
16. 0
14. 6
13. 7
12. 3
11. 4
10. 5

MODEL : AR60H
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
11. 8
11. 4
11. 1
10. 7
10. 5
10. 2
13. 4
13. 0
12. 7
12. 3
12. 0
11. 8
15. 2
14. 8
14. 5
14. 1
13. 8
13. 5
17. 3
16. 8
16. 5
15. 8
14. 7
13. 5
19. 5
18. 8
17. 6
15. 8
14. 7
13. 5
20. 5
18. 8
17. 6
15. 8
14. 7
13. 5
20. 5
18. 8
17. 6
15. 8
14. 7
13. 5
20. 5
18. 8
17. 6
15. 8
14. 7
13. 5

TC : Total Capacity kW

- (04 - 71) -

INDOOR
UNIT

INDOOR
UNIT

Outdoor
Temperature

HEATING CAPACITY
4-9-6. COMPACT CASSETTE TYPE

MODEL : AU7
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
1. 65
1. 59
1. 55
1. 49
1. 46
1. 42
1. 87
1. 81
1. 77
1. 71
1. 68
1. 64
2. 12
2. 06
2. 02
1. 96
1. 92
1. 88
2. 40
2. 34
2. 30
2. 21
2. 04
1. 88
2. 72
2. 61
2. 45
2. 21
2. 04
1. 88
2. 85
2. 61
2. 45
2. 21
2. 04
1. 88
2. 86
2. 61
2. 45
2. 21
2. 04
1. 88
2. 86
2. 61
2. 45
2. 21
2. 04
1. 88

MODEL : AU9
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
2. 08
2. 01
1. 96
1. 89
1. 84
1. 79
2. 36
2. 29
2. 24
2. 17
2. 12
2. 07
2. 68
2. 61
2. 56
2. 48
2. 43
2. 38
3. 04
2. 96
2. 91
2. 79
2. 58
2. 38
3. 44
3. 31
3. 10
2. 79
2. 58
2. 38
3. 61
3. 31
3. 10
2. 79
2. 58
2. 38
3. 62
3. 31
3. 10
2. 79
3. 58
2. 38
3. 62
3. 31
3. 10
2. 79
3. 58
2. 38

MODEL : AU12
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
2. 75
2. 66
2. 60
2. 50
2. 44
2. 37
3. 12
3. 03
2. 96
2. 87
2. 80
2. 74
3. 55
3. 45
3. 38
3. 28
3. 22
3. 14
4. 02
3. 92
3. 85
3. 69
3. 42
3. 14
4. 55
4. 37
4. 10
3. 69
3. 42
3. 14
4. 77
4. 37
4. 10
3. 69
3. 42
3. 14
4. 78
4. 37
4. 10
3. 69
3. 42
3. 14
4. 78
4. 37
4. 10
3. 69
3. 42
3. 14

MODEL : AU14
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
3. 03
2. 92
2. 85
2. 74
2. 67
2. 61
3. 43
3. 32
3. 25
3. 15
3. 08
3. 01
3. 89
3. 78
3. 71
3. 60
3. 53
3. 45
4. 41
4. 30
4. 22
4. 05
3. 75
3. 45
4. 99
4. 80
4. 50
4. 05
3. 75
3. 45
5. 23
4. 80
4. 50
4. 05
3. 75
3. 45
5. 25
4. 80
4. 50
4. 05
3. 75
3. 45
5. 25
4. 80
4. 50
4. 05
3. 75
3. 45

MODEL : AU18
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
3. 66
3. 53
3. 45
3. 32
3. 24
3. 16
4. 15
4. 02
3. 94
3. 81
3. 73
3. 64
4. 71
4. 58
4. 50
4. 36
4. 28
4. 18
5. 34
5. 20
5. 11
4. 91
4. 54
4. 18
6. 04
5. 81
5. 45
4. 91
4. 54
4. 18
6. 34
5. 81
5. 45
4. 91
4. 54
4. 18
6. 36
5. 81
5. 45
4. 91
4. 54
4. 18
6. 36
5. 81
5. 45
4. 91
4. 54
4. 18

TC : Total Capacity kW

- (04 - 72) -

INDOOR
UNIT

INDOOR
UNIT

Outdoor
Temperature

HEATING CAPACITY
4-9-7. CASSETTE TYPE (1/2)
MODEL : AU20
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
3. 89
3. 76
3. 67
3. 54
3. 45
3. 36
4. 42
4. 28
4. 19
4. 06
3. 97
3. 88
5. 02
4. 88
4. 78
4. 64
4. 55
4. 45
5. 69
5. 54
5. 44
5. 22
4. 83
4. 45
6. 43
6. 19
5. 80
5. 22
4. 83
4. 45
6. 75
6. 19
5. 80
5. 22
4. 83
4. 45
6. 77
6. 19
5. 80
5. 22
4. 83
4. 45
6. 77
6. 19
5. 80
5. 22
4. 83
4. 45

MODEL : AU25
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
5. 27
5. 09
4. 97
4. 79
4. 67
4. 55
5. 98
5. 79
5. 67
5. 49
5. 37
5. 25
6. 79
6. 60
6. 48
6. 29
6. 16
6. 02
7. 70
7. 50
7. 36
7. 07
6. 54
6. 02
8. 71
8. 37
7. 85
7. 07
6. 54
6. 02
9. 13
8. 37
7. 85
7. 07
6. 54
6. 02
9. 16
8. 37
7. 85
7. 07
6. 54
6. 02
9. 16
8. 37
7. 85
7. 07
6. 54
6. 02

MODEL : AU30
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
6. 11
5. 90
5. 76
5. 55
5. 41
5. 27
6. 93
6. 72
6. 58
6. 36
6. 22
6. 08
7. 87
7. 65
7. 51
7. 29
7. 14
6. 98
8. 92
8. 69
8. 54
8. 19
7. 58
6. 98
10. 1
9. 71
9. 10
8. 19
7. 58
6. 98
10. 6
9. 71
9. 10
8. 19
7. 58
6. 98
10. 6
9. 71
9. 10
8. 19
7. 58
6. 98
10. 6
9. 71
9. 10
8. 19
7. 58
6. 98

TC : Total Capacity kW

- (04 - 73) -

INDOOR
UNIT

INDOOR
UNIT

Outdoor
Temperature

HEATING CAPACITY
4-9-7. CASSETTE TYPE (2/2)
MODEL : AU36
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
7. 19
6. 94
6. 77
6. 53
6. 36
6. 20
8. 15
7. 90
7. 73
7. 48
7. 32
7. 15
9. 26
9. 00
8. 83
8. 57
8. 40
8. 20
10. 5
10. 2
10. 0
9. 63
8. 92
8. 20
11. 9
11. 4
10. 7
9. 63
8. 92
8. 20
12. 4
11. 4
10. 7
9. 63
8. 92
8. 20
12. 5
11. 4
10. 7
9. 63
8. 92
8. 20
12. 5
11. 4
10. 7
9. 63
8. 92
8. 20

MODEL : AU45
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
9. 20
8. 88
8. 67
8. 35
8. 14
7. 93
10. 4
10. 1
9. 90
9. 58
9. 37
9. 15
11. 9
11. 5
11. 3
11. 0
10. 7
10. 5
13. 4
13. 1
12. 8
12. 3
11. 4
10. 5
15. 2
14. 6
13. 7
12. 3
11. 4
10. 5
15. 9
14. 6
13. 7
12. 3
11. 4
10. 5
16. 0
14. 6
13. 7
12. 3
11. 4
10. 5
16. 0
14. 6
13. 7
12. 3
11. 4
10. 5

MODEL : AU54
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB 18 CDB 20 CDB 23 CDB 25 CDB 27 CDB


59 FDB 64 FDB 68 FDB 73 FDB 77 FDB 81 FDB
TC
TC
TC
TC
TC
TC
10. 6
10. 2
10. 0
9. 64
9. 39
9. 15
12. 0
11. 7
11. 4
11. 0
10. 8
10. 6
13. 7
13. 3
13. 0
12. 7
12. 4
12. 1
15. 5
15. 1
14. 8
14. 2
13. 2
12. 1
17. 5
16. 9
15. 8
14. 2
13. 2
12. 1
18. 4
16. 9
15. 8
14. 2
13. 2
12. 1
18. 4
16. 9
15. 8
14. 2
13. 2
12. 1
18. 4
16. 9
15. 8
14. 2
13. 2
12. 1

TC : Total Capacity kW

- (04 - 74) -

INDOOR
UNIT

INDOOR
UNIT

Outdoor
Temperature

HEATING CAPACITY
4-9-8. WALL MOUNTED TYPE
MODEL : AS18
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB
59 FDB
TC
3.76
4.26
4.84
5.49
6.21
6.51
6.53
6.53

18 CDB
64 FDB
TC
3.63
4.13
4.71
5.35
5.97
5.97
5.97
5.97

20 CDB
68 FDB
TC
3.54
4.05
4.62
5.25
5.60
5.60
5.60
5.60

18 CDB
64 FDB
TC
5.06
5.76
6.56
7.45
8.32
8.32
8.32
8.32

20 CDB
68 FDB
TC
4.94
5.64
6.43
7.32
7.80
7.80
7.80
7.80

18 CDB
64 FDB
TC
5. 90
6. 72
7. 65
8. 69
9. 71
9. 71
9. 71
9. 71

20 CDB
68 FDB
TC
5. 76
6. 58
7. 51
8. 54
9. 10
9. 10
9. 10
9. 10

23 CDB
73 FDB
TC
3.42
3.92
4.48
5.04
5.04
5.04
5.04
5.04

25 CDB
77 FDB
TC
3.33
3.83
4.39
4.67
4.67
4.67
4.67
4.67

27 CDB
81 FDB
TC
3.24
3.74
4.29
4.29
4.29
4.29
4.29
4.29

25 CDB
77 FDB
TC
4.64
5.33
6.12
6.50
6.50
6.50
6.50
6.50

27 CDB
81 FDB
TC
4.52
5.21
5.98
5.98
5.98
5.98
5.98
5.98

25 CDB
77 FDB
TC
5. 41
6. 22
7. 14
7. 58
7. 58
7. 58
7. 58
7. 58

27 CDB
81 FDB
TC
5. 27
6. 08
6. 98
6. 98
6. 98
6. 98
6. 98
6. 98

MODEL : AS24
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB
59 FDB
TC
5.24
5.94
6.75
7.65
8.65
9.07
9.10
9.10

23 CDB
73 FDB
TC
4.76
5.45
6.25
7.02
7.02
7.02
7.02
7.02

MODEL : AS30
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB
59 FDB
TC
6. 11
6. 93
7. 87
8. 92
10. 1
10. 6
10. 6
10. 6

23 CDB
73 FDB
TC
5. 55
6. 36
7. 29
8. 19
8. 19
8. 19
8. 19
8. 19

TC : Total Capacity kW

- (04 - 75) -

INDOOR
UNIT

INDOOR
UNIT

Outdoor
Temperature

HEATING CAPACITY
4-9-9. CEILING WALL TYPE (1/2)
MODEL : AW7
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB
59 FDB
TC
1. 65
1. 87
2. 12
2. 40
2. 72
2. 85
2. 86
2. 86

18 CDB
64 FDB
TC
1. 59
1. 81
2. 06
2. 34
2. 61
2. 61
2. 61
2. 61

20 CDB
68 FDB
TC
1. 55
1. 77
2. 02
2. 30
2. 45
2. 45
2. 45
2. 45

18 CDB
64 FDB
TC
2. 01
2. 29
2. 61
2. 96
3. 31
3. 31
3. 31
3. 31

20 CDB
68 FDB
TC
1. 96
2. 24
2. 56
2. 91
3. 10
3. 10
3. 10
3. 10

18 CDB
64 FDB
TC
2. 66
3. 03
3. 45
3. 92
4. 37
4. 37
4. 37
4. 37

20 CDB
68 FDB
TC
2. 60
2. 96
3. 38
3. 85
4. 10
4. 10
4. 10
4. 10

23 CDB
73 FDB
TC
1. 49
1. 71
1. 96
2. 21
2. 21
2. 21
2. 21
2. 21

25 CDB
77 FDB
TC
1. 46
1. 68
1. 92
2. 04
2. 04
2. 04
2. 04
2. 04

27 CDB
81 FDB
TC
1. 42
1. 64
1. 88
1. 88
1. 88
1. 88
1. 88
1. 88

25 CDB
77 FDB
TC
1. 84
2. 12
2. 43
2. 58
2. 58
2. 58
3. 58
3. 58

27 CDB
81 FDB
TC
1. 79
2. 07
2. 38
2. 38
2. 38
2. 38
2. 38
2. 38

25 CDB
77 FDB
TC
2. 44
2. 80
3. 22
3. 42
3. 42
3. 42
3. 42
3. 42

27 CDB
81 FDB
TC
2. 37
2. 74
3. 14
3. 14
3. 14
3. 14
3. 14
3. 14

INDOOR
UNIT

Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

15 CDB
59 FDB
TC
2. 08
2. 36
2. 68
3. 04
3. 44
3. 61
3. 62
3. 62

Indoor Temperature

23 CDB
73 FDB
TC
1. 89
2. 17
2. 48
2. 79
2. 79
2. 79
2. 79
2. 79

MODEL : AW12
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB
59 FDB
TC
2. 75
3. 12
3. 55
4. 02
4. 55
4. 77
4. 78
4. 78

23 CDB
73 FDB
TC
2. 50
2. 87
3. 28
3. 69
3. 69
3. 69
3. 69
3. 69

TC : Total Capacity kW

- (04 - 76) -

INDOOR
UNIT

MODEL : AW9

HEATING CAPACITY
4-9-9. CEILING WALL TYPE (2/2)
MODEL : AW14
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

15 CDB
59 FDB
TC
3.22
3.65
4.15
4.71
5.32
5.58
5.60
5.60

Indoor Temperature

18 CDB
64 FDB
TC
3.11
3.54
4.04
4.58
5.12
5.12
5.12
5.12

20 CDB
68 FDB
TC
3.04
3.47
3.96
4.50
4.80
4.80
4.80
4.80

18 CDB
64 FDB
TC
3.76
4.28
4.88
5.54
6.19
6.19
6.19
6.19

20 CDB
68 FDB
TC
3.67
4.19
4.78
5.44
5.80
5.80
5.80
5.80

18 CDB
64 FDB
TC
4.99
5.68
6.48
7.35
8.21
8.21
8.21
8.21

20 CDB
68 FDB
TC
4.87
5.56
6.35
7.22
7.70
7.70
7.70
7.70

18 CDB
64 FDB
TC
5.71
6.50
7.40
8.40
9.39
9.39
9.39
9.39

20 CDB
68 FDB
TC
5.57
6.36
7.26
8.25
8.80
8.80
8.80
8.80

23 CDB
73 FDB
TC
2.93
3.36
3.84
4.32
4.32
4.32
4.32
4.32

25 CDB
77 FDB
TC
2.85
3.28
3.77
4.00
4.00
4.00
4.00
4.00

27 CDB
81 FDB
TC
2.78
3.21
3.68
3.68
3.68
3.68
3.68
3.68

25 CDB
77 FDB
TC
3.45
3.97
4.55
4.83
4.83
4.83
4.83
4.83

27 CDB
81 FDB
TC
3.36
3.88
4.45
4.45
4.45
4.45
4.45
4.45

25 CDB
77 FDB
TC
4.58
5.26
6.04
6.42
6.42
6.42
6.42
6.42

27 CDB
81 FDB
TC
4.46
5.14
5.90
5.90
5.90
5.90
5.90
5.90

25 CDB
77 FDB
TC
5.23
6.02
6.90
7.33
7.33
7.33
7.33
7.33

27 CDB
81 FDB
TC
5.10
5.88
6.75
6.75
6.75
6.75
6.75
6.75

MODEL : AW18
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB
59 FDB
TC
3.89
4.42
5.02
5.69
6.43
6.75
6.77
6.77

23 CDB
73 FDB
TC
3.54
4.06
4.64
5.22
5.22
5.22
5.22
5.22

MODEL : AW24
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

Indoor Temperature

15 CDB
59 FDB
TC
5.17
5.86
6.66
7.55
8.54
8.96
8.98
8.98

23 CDB
73 FDB
TC
4.70
5.38
6.17
6.93
6.93
6.93
6.93
6.93

MODEL : AW30
Outdoor
Temperature
( CDB)
-15
-10
-5
0
5
7
10
15

( FDB)
RH
5
14
23
32 RH85%
41
45
50
59

15 CDB
59 FDB
TC
5.91
6.70
7.61
8.63
9.76
10.2
10.3
10.3

Indoor Temperature

23 CDB
73 FDB
TC
5.37
6.15
7.05
7.92
7.92
7.92
7.92
7.92

TC : Total Capacity kW

- (04 - 77) -

INDOOR
UNIT

INDOOR
UNIT

Outdoor
Temperature

4-10. AIR VELOCITY DISTRIBUTION


4-10-1. UNIVERSAL FLOOR / CEILING TYPE
MODELS : AB12, AB14 (FLOOR CONSOLE)
Unit: m/s

(m) 2
1

TOP VIEW
VERTICAL : Forward
HORIZONTAL : Center

0.5

1.0

2.0

0.25

1
0

(m)

Unit: m/s

(m)

INDOOR
UNIT

INDOOR
UNIT

3
0.25

0.5

1
TOP VIEW
0
VERTICAL : Forward
1
HORIZONTAL : Right & Left

1.0

HORIZONTAL: Right

1.0

HORIZONTAL: Left

2.0

Condition
Fan speed : High
Operation mode : Fan
Voltage : 240V

0.5

0.25

3
0

(m)

Unit: m/s

(m)
3
2
SIDE VIEW
VERTICAL : Forward
HORIZONTAL : Center

1.0

2.0

Unit: m/s

(m)

(m)

Unit: m/s
0.5
0.25

1.0

2.0

1
2

2.0

0.25

1.0

(m)

0.5

0.25

0.5

(m)

SIDE VIEW
VERTICAL : Center
HORIZONTAL : Center

SIDE VIEW
VERTICAL : Upward
HORIZONTAL : Center

- (04 - 78) -

(m)

MODELS : AB12, AB14 (UNDER CEILING)


(m)
2

Unit: m/s

TOP VIEW
VERTICAL : Upward

HORIZONTAL : Center

1
2

0.5

1.0

2.0

0.25

(m)

Unit: m/s

(m)
3
0.25
0.5

1
0
TOP VIEW

HORIZONTAL: Right

1.0

HORIZONTAL: Left

2.0

Condition

VERTICAL : Upward

1.0

Fan speed : High


Operation mode : Fan

0.5

HORIZONTAL : Right & Left 2

Voltage : 240V

0.25

3
0

(m)

Unit: m/s

(m)
3
SIDE VIEW

2.0

VERTICAL : Upward
HORIZONTAL : Center

1.0

Unit: m/s

(m)
3

0.5

0.25

(m)

Unit: m/s

(m)
3

2.0

2.0

1
1.0

0.5

1.0

0.25

0.5

(m)

0.25

SIDE VIEW

SIDE VIEW

VERTICAL : Center

VERTICAL : Downward

HORIZONTAL : Center

HORIZONTAL : Center

- (04 - 79) -

(m)

INDOOR
UNIT

INDOOR
UNIT

MODEL : AB18 (FLOOR CONSOLE)


Unit: m/s

(m) 2

TOP VIEW
VERTICAL : Forward
HORIZONTAL : Center

0.5

1.0

2.0

0.25

1
2

Unit: m/s

(m)

0.25

0.5

HORIZONTAL : Right & Left

1.0

HORIZONTAL: Right

Condition
Fan speed : High

2.0
1.0

Operation mode : Fan


Voltage : 240V

HORIZONTAL: Left

0.5

0.25

(m)

9
Unit: m/s

(m)

3
2
SIDE VIEW
VERTICAL : Forward

0.25

0.5

1.0
2.0

HORIZONTAL : Center

Unit: m/s

(m)

0.5

Unit: m/s

1.0

2
1
0

2.0

1
2

(m)

0.25

1.0

2
2.0

(m)

(m)
0.5

0.25

SIDE VIEW

SIDE VIEW

VERTICAL : Center

VERTICAL : Up

HORIZONTAL : Center

HORIZONTAL : Center

- (04 - 80) -

(m)

INDOOR
UNIT

INDOOR
UNIT

1
TOP VIEW
VERTICAL : Forward

(m)

MODEL : AB18 (UNDER CEILING)


Unit: m/s

(m) 2
1
TOP VIEW
VERTICAL : Up
HORIZONTAL : Center

0.5

1.0

2.0

0.25

1
2

Unit: m/s

(m)
3

0.25
0.5
1.0

1
0

HORIZONTAL: Right

2.0

Condition
Fan speed : High
Operation mode : Fan
Voltage : 240V

HORIZONTAL: Left
1.0

0.5

0.25

(m)

Unit: m/s

(m)
3
SIDE VIEW
VERTICAL : Forward
HORIZONTAL : Center

2.0

1.0

Unit: m/s

(m)
3

0.25

0.5

(m)

Unit: m/s

(m)
3

2.0

2.0

1
1.0

0.5

0.25

1.0

(m)

SIDE VIEW
VERTICAL : Center
HORIZONTAL : Center

0.25

0.5

SIDE VIEW
VERTICAL : Down
HORIZONTAL : Center

- (04 - 81) -

(m)

INDOOR
UNIT

INDOOR
UNIT

2
TOP VIEW
VERTICAL : Up
HORIZONTAL : Right & Left

(m)

MODEL : AB24 (FLOOR CONSOLE)


Unit: m/s

(m) 2

1
TOP VIEW

VERTICAL : Forward
HORIZONTAL : Center

2.0

0.5

1.0

0.25

1
2

0.25
0.5

2
1.0

HORIZONTAL: Right

Condition

2.0

HORIZONTAL: Left

1.0

Fan speed : High


Operation mode : Fan
Voltage : 240V (50Hz)
220V (60Hz)

0.5

0.25

(m)

Unit: m/s

(m)

3
0.25

0.5

SIDE VIEW

1.0
2.0

VERTICAL : Forward
HORIZONTAL : Center

Unit: m/s

(m)
0.5

1.0

0.25

(m)

Unit: m/s
1.0

(m)

2.0

0.5 0.25

2.0

1
0

(m)

SIDE VIEW
VERTICAL : Center

SIDE VIEW
VERTICAL : Up

HORIZONTAL : Center

HORIZONTAL : Center

- (04 - 82) -

(m)

INDOOR
UNIT

INDOOR
UNIT

HORIZONTAL : Right & Left

(m)

Unit: m/s

(m)

TOP VIEW
VERTICAL : Forward

MODEL : AB24 (UNDER CEILING)


(m)

Unit: m/s

2
1

TOP VIEW
VERTICAL : Up
HORIZONTAL : Center

2.0

0.5

1.0

1
2

0.25
0.5

1.0

2.0

Condition
Fan speed : High
Operation mode : Fan
Voltage : 240V (50Hz)
220V (60Hz)

HORIZONTAL: Left
1.0

0.5

3
0

0.25

(m)

9
Unit: m/s

(m)

3
2

2.0

SIDE VIEW
VERTICAL : Up
HORIZONTAL : Center

1.0

Unit: m/s

(m)

0.5

0.25

(m)

Unit: m/s

(m)

2
2.0

0.5

1.0

2.0

1
3

0.25

0.5

1.0
(m)

SIDE VIEW
VERTICAL : Center
HORIZONTAL : Center

0.25

SIDE VIEW
VERTICAL : Down
HORIZONTAL : Center

- (04 - 83) -

(m)

INDOOR
UNIT

HORIZONTAL: Right

1
TOP VIEW
VERTICAL : Up
HORIZONTAL : Right & Left

(m)

Unit: m/s

(m)

INDOOR
UNIT

0.25

4-10-2. LARGE CEILING TYPE


MODEL : AB30
Unit : (m / s)

(m)
4
3
2
1
0

0.5

0.25

Unit : (m / s)

(m)

2
3

2
3 4

6 7

9 10 11 12 13 14 15 16 17 18 ( m )

INDOOR
UNIT

TOP VIEW
VERTICAL : UP
HORIZONTAL : CENTER

2
1

0.5
0

0 1 2

3 4

6 7

0.25
8

9 10 11 12 13 14 ( m )

SIDE VIEW
FLAP : CENTER
HORIZONTAL : CENTER
Unit : (m / s)

(m)
4
3
2
1
0

0.5

0.25

0.5

0.25

Unit : (m / s)

(m)

3
4

3
0 1 2

3 4

6 7

9 10 11 12 13 14 15 16 17 18 ( m )

2
2

TOP VIEW
VERTICAL : UP
HORIZONTAL : RIGHT AND LEFT

1
0.5 0.25

0
Unit : (m / s)

(m)
3

0.5

0.25

2
1
0

0 1 2

3 4

6 7

9 10 11 12 13 14 15 16 17 18 ( m )

SIDE VIEW
FLAP : UP
HORIZONTAL : CENTER

- (04 - 84) -

0 1 2

3 4

6 7

9 10 11 12 13 14 ( m )

SIDE VIEW
FLAP : DOWN
HORIZONTAL : CENTER

INDOOR
UNIT

0 1 2

MODEL : AB36
Unit : (m / s)

(m)
4
3
2
1
0

0.5

0.25

Unit : (m / s)

(m)

2
3

2
3 4

6 7

9 10 11 12 13 14 15 16 17 18 ( m )

TOP VIEW
VERTICAL : UP
HORIZONTAL : CENTER

0.5
0 1 2

INDOOR
UNIT

3 4

6 7

0.25
8

9 10 11 12 13 14 ( m )

INDOOR
UNIT

0 1 2

SIDE VIEW
FLAP : CENTER
HORIZONTAL : CENTER
Unit : (m / s)

(m)
4
3
2
1
0

0.5

0.25

0.5

0.25

1
1

Unit : (m / s)

(m)

3
4

3
0 1 2

3 4

6 7

9 10 11 12 13 14 15 16 17 18 ( m )
2

TOP VIEW
VERTICAL : UP
HORIZONTAL : RIGHT AND LEFT

2
1
0.5 0.25

0
Unit : (m / s)

(m)
3

0.5

0.25

2
1
0

0 1 2

3 4

6 7

9 10 11 12 13 14 15 16 17 18 ( m )

SIDE VIEW
FLAP : UP
HORIZONTAL : CENTER

- (04 - 85) -

0 1 2

3 4

6 7

9 10 11 12 13 14 ( m )

SIDE VIEW
FLAP : DOWN
HORIZONTAL : CENTER

MODEL : AB45
Unit : (m / s)

(m)
4
3
2
1
0

0.5

0.25

Unit : (m / s)

(m)

2
3

2
3 4

6 7

9 10 11 12 13 14 15 16 17 18 ( m )

TOP VIEW
VERTICAL : UP
HORIZONTAL : CENTER

2
1

0.25
0.5

0 1 2

INDOOR
UNIT

3 4

6 7

9 10 11 12 13 14 ( m )

INDOOR
UNIT

0 1 2

SIDE VIEW
FLAP : CENTER
HORIZONTAL : CENTER
Unit : (m / s)

(m)
4
3
2
1
0

0.5

0.25

0.5

0.25

1
1

Unit : (m / s)

(m)

3
4

3
0 1 2

3 4

6 7

9 10 11 12 13 14 15 16 17 18 ( m )
2

TOP VIEW
VERTICAL : UP
HORIZONTAL : RIGHT AND LEFT

1
0
Unit : (m / s)

(m)
3

0.5

0.25

2
1
0

0 1 2

3 4

6 7

9 10 11 12 13 14 15 16 17 18 ( m )

SIDE VIEW
FLAP : UP
HORIZONTAL : CENTER

- (04 - 86) -

2
1

0.25
0.5
0 1 2 3 4 5

6 7

9 10 11 12 13 14 ( m )

SIDE VIEW
FLAP : DOWN
HORIZONTAL : CENTER

MODELS : AB54

TOP VIEW
VERTICAL : UP
HORIZONTAL : CENTER

INDOOR
UNIT

INDOOR
UNIT

Condition
Fan speed : High
Operation mode : Fan
Voltage : 240V

SIDE VIEW
FLAP : CENTER
HORIZONTAL : CENTER

TOP VIEW
VERTICAL : UP
HORIZONTAL : RIGHT AND LEFT

SIDE VIEW
FLAP : DOWN
HORIZONTAL : CENTER

SIDE VIEW
FLAP : UP
HORIZONTAL : CENTER

- (04 - 87) -

4-10-3. COMPACT CASSETTE TYPE

INDOOR
UNIT

INDOOR
UNIT

MODELS : AU7,AU9

- (04 - 88) -

INDOOR
UNIT

INDOOR
UNIT

MODELS : AU12, AU14

AIR DISCHARGE ANGLE

Upward
3

Downward

- (04 - 89) -

INDOOR
UNIT

INDOOR
UNIT

MODEL : AU18

AIR DISCHARGE ANGLE

Up
3

Down

- (04 - 90) -

4-10-4. CASSETTE TYPE

INDOOR
UNIT

INDOOR
UNIT

MODEL : AU20

- (04 - 91) -

MODEL : AU25
(m) 4-W AY AIR OUTLET

UNIT : m/s
0.5

Note :
Condition
Fan speed : High
Operation mode : FAN
Voltage : 240V

0.25

2
2

1
0

0.25

0.5

0.5

0.25
TOP VIEW
AIR FLOW DIRECTION
: Upward

1
0.5

0.25

1
0.25

0.5

SIDE VIEW
AIR FLOW DIRECTION
: Upward

0.5

0.25

(m)

UNIT : m/s

(m)
2

0.5

0.25

SIDE VIEW
HORIZONTAL LOUVER
: Downward

0.5

(m)

(m)

UNIT : m/s

(m)

INDOOR
UNIT

INDOOR
UNIT

0.25

(m)

2-W AY AIR OUTLET

UNIT : m/s

1
0

0.25

0.5

0.5

0.25

TOP VIEW
AIR FLOW DIRECTION
: Upward

1
8

(m)

UNIT : m/s

(m)

1
0

0.25

0.5

SIDE VIEW
AIR FLOW DIRECTION
: Upward

1
0.5

- (04 - 92) -

0.25

(m)

MODEL : AU30
(m) 4-W AY AIR OUTLET

UNIT : m/s
0.5

Note :
Condition
Fan speed : High
Operation mode : FAN
Voltage : 240V

0.25

2
2

1
0

0.25

0.5

0.5

0.25
TOP VIEW
AIR FLOW DIRECTION
: Upward

0.5

0.25

(m)

2
1

1
8

SIDE VIEW
AIR FLOW DIRECTION
: Upward

0.5

0.25

0.5

0.25

(m)

UNIT : m/s

(m)
2

0.5

0.25

SIDE VIEW
HORIZONTAL LOUVER
: Downward

0.5

(m)

UNIT : m/s

(m)

INDOOR
UNIT

INDOOR
UNIT

0.25

(m)

2-W AY AIR OUTLET

UNIT : m/s

1
0

0.25

0.5

0.5

0.25

TOP VIEW
AIR FLOW DIRECTION
: Upward

1
8

(m)

UNIT : m/s

(m)

1
0

0.25

0.5

SIDE VIEW
AIR FLOW DIRECTION
: Upward

1
0.5

- (04 - 93) -

0.25

(m)

MODEL : AU36
4-WAY AIR OUTLET

UNIT : m/s
0.5

Note :
Condition
Fan speed : High
Operation mode : FAN
Voltage : 240V

0.25

2
2

1
0

0.25

0.5

0.5

0.25
TOP VIEW
AIR FLOW DIRECTION
: Upward

2
1

INDOOR
UNIT

3
8

0.5

0.25

(m)

1
8

0.25

SIDE VIEW
AIR FLOW DIRECTION
: Upward

0.5

0.5

0.25

(m)

UNIT : m/s

(m)
2

0.5

0.5

0.25

SIDE VIEW
AIR FLOW DIRECTION
: Downward

(m)

UNIT : m/s

(m)

INDOOR
UNIT

(m)

0.25

(m)

2-WAY AIR OUTLET

UNIT : m/s

1
0 0.25

0.5

0.5

0.25

TOP VIEW
AIR FLOW DIRECTION
: Upward

1
8

(m)

UNIT : m/s

(m)

1
0

1
0.25

0.5

SIDE VIEW
AIR FLOW DIRECTION
: Upward

1
0.5

- (04 - 94) -

0.25

(m)

MODEL : AU45
(m) 4-WAY AIR OUTLET

UNIT : m/s
0.5

Note :
Condition
Fan speed : High
Operation mode : FAN
Voltage : 240V

0.25

2
2

1
0.25

0.5

0.5

0.25
TOP VIEW
AIR FLOW DIRECTION
: Upward

2
1

INDOOR
UNIT

3
8

0.5

0.25

(m)

1
8

SIDE VIEW
AIR FLOW DIRECTION
: Upward

0.5

0.25

0.5

0.25

(m)

UNIT : m/s

(m)
2

0.25

SIDE VIEW
AIR FLOW DIRECTION
: Downward

(m)

UNIT : m/s

(m)

INDOOR
UNIT

0.5

0.5

0.25

(m)

2-WAY AIR OUTLET

UNIT : m/s

1
0 0.25

0.5

0.5

0.25

TOP VIEW
AIR FLOW DIRECTION
: Upward

1
8

(m)

UNIT : m/s

(m)

1
0

0.5

0.25

SIDE VIEW
AIR FLOW DIRECTION
: Upward

0.5

- (04 - 95) -

0.25

(m)

MODEL : AU54
(m) 4-WAY AIR OUTLET

UNIT : m/s

0.5

Note :
Condition
Fan speed : High
Operation mode : FAN
Voltage : 240V

0.25

2
2

1
0

0.5

0.25

0.5

0.25

TOP VIEW
AIR FLOW DIRECTION
: Upward

INDOOR
UNIT

0.5

0.25

(m)

UNIT : m/s

(m)

SIDE VIEW
AIR FLOW DIRECTION
: Upward

1
8

0.5

0.25

0.5

0.25

(m)

UNIT : m/s

(m)
2

2
1

SIDE VIEW
AIR FLOW DIRECTION
: Downward

1
0.25

0
(m)

0.5

0.5

0.25

(m)

2-WAY AIR OUTLET

UNIT : m/s

1
0
1

0.25

0.5

0.5

TOP VIEW
AIR FLOW DIRECTION
: Upward

0.25

(m)

UNIT : m/s

(m)

SIDE VIEW
AIR FLOW DIRECTION
: Upward

2
2

1
0

INDOOR
UNIT

0.5

0.25

- (04 - 96) -

0.5

0.25

(m)

4-10-5. WALL MOUNTED TYPE


MODEL : AS18

INDOOR
UNIT

INDOOR
UNIT

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Center

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Right & Left

SIDE VIEW
FRONT CONTROL PANEL : Horiz.
LOUVER : Center

SIDE VIEW
FLOW CONTROL PANEL : Vert.
LOUVER : Center

- (04 - 97) -

MODEL : AS24

INDOOR
UNIT

INDOOR
UNIT

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Center

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Right & Left

Condition
Fan speed : High
Operation mode : Fan
Voltage : 240V

SIDE VIEW
FRONT CONTROL PANEL : Horiz.
LOUVER : Center

SIDE VIEW
FLOW CONTROL PANEL : Vert.
LOUVER : Center

- (04 - 98) -

MODEL : AS30

INDOOR
UNIT

INDOOR
UNIT

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Center

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Right & Left
Condition
Fan speed : High
Operation mode : Fan
Voltage : 240V

SIDE VIEW
FRONT CONTROL PANEL : Horiz.
LOUVER : Center

SIDE VIEW
FLOW CONTROL PANEL : Vert.
LOUVER : Center

- (04 - 99) -

4-10-6. CEILING WALL TYPE

Condition
Fan speed :
High
Operation mode : Fan
Voltage : 240V (50Hz)

MODEL : AW7

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Right & Left

INDOOR
UNIT

INDOOR
UNIT

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Center

SIDE VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Center

SIDE VIEW
FLOW CONTROL PANEL : Vert.
LOUVER : Center

- (04 - 100) -

Condition
Fan speed :
High
Operation mode : Fan
Voltage : 240V (50Hz)

MODEL : AW9

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Right & Left

INDOOR
UNIT

INDOOR
UNIT

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Center

SIDE VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Center

SIDE VIEW
FLOW CONTROL PANEL : Vert.
LOUVER : Center

- (04 - 101) -

MODEL : AW12

Condition
Fan speed :
High
Operation mode : Fan
Voltage : 240V (50Hz)

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Right & Left

INDOOR
UNIT

INDOOR
UNIT

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Center

SIDE VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Center

SIDE VIEW
FLOW CONTROL PANEL : Vert.
LOUVER : Center

- (04 - 102) -

MODEL : AW14

Condition
Fan speed :
High
Operation mode : Fan
Voltage : 240V (50Hz)

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Right & Left

INDOOR
UNIT

INDOOR
UNIT

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Center

SIDE VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Center

SIDE VIEW
FLOW CONTROL PANEL : Vert.
LOUVER : Center

- (04 - 103) -

MODEL : AW18

Condition
Fan speed : High
Operation mode : Fan
Voltage : 240V

TOP VIEW
FLOW CONTROL PANEL : Horiz.

INDOOR
UNIT

INDOOR
UNIT

LOUVER : Center

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Right & Left

SIDE VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Center

SIDE VIEW
FLOW CONTROL PANEL : Vert.
LOUVER : Center

- (04 - 104) -

MODEL : AW24

INDOOR
UNIT

INDOOR
UNIT

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Center

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Right & Left

SIDE VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Center

SIDE VIEW
FLOW CONTROL PANEL : Vert.
LOUVER : Center

- (04 - 105) -

MODEL : AW30

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Right & Left

INDOOR
UNIT

INDOOR
UNIT

TOP VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Center

SIDE VIEW
FLOW CONTROL PANEL : Horiz.
LOUVER : Center

SIDE VIEW
FLOW CONTROL PANEL : Vert.
LOUVER : Center

- (04 - 106) -

4-11. FAN PERFORMANCE AND AIR FLOW


4-11-1. FAN CURVE ( COMPACT DUCT TYPE )
MODELS : AR7, AR9, AR12, AR14, AR18

AR9
Recommended Range

Recommended Range

40

Extermal Static Pressure

Extermal Static Pressure

50

(Pa)

50

(Pa)

HIGH

LOW

30
20
10
0
100

200

300

400

500

40
LOW

30
20
10
0
100

(m3 /h)

200

300

Air Flow

INDOOR
UNIT

HIGH

AR14

AR12

(Pa)

Extermal Static Pressure

Extermal Static Pressure

50
40
HIGH
30
LOW
20
10
0
200

300

400

500

600

(m3 /h)

Air Flow

Recommended Range

Extermal Static Pressure

50
40
HIGH
30
LOW
20
10
0
400

500

600

(m3 /h)

700

(m3 /h)

50
40
LOW

HIGH

30
20
10
0
300

400

500
Air Flow

AR18

(Pa)

500

Recommended Range

Recommended Range

(Pa)

400

Air Flow

700

800

(m3 /h)

Air Flow

- (04 - 107) -

INDOOR
UNIT

AR7

600

CAPACITY BY AIR FLOW


COOLING

HEATING

6.0

6.0

5.5

5.5

5.0

5.0

4.0

3.5

Capacity (kW)

4.5
AR18
AR14
AR12
AR9
AR7

3.5

3.0

3.0

2.5

2.5

2.0

2.0

1.5

AR18
AR14
AR12
AR9
AR7

4.0

INDOOR
UNIT

INDOOR
UNIT

Capacity (kW)

4.5

1.5
200

300

400

500

600

700

200

800

300

400

500

600

700

800

Air Flow (m3/h)

Air Flow (m /h)


3

OUTLET AIR TEMPERATURE


COOLING

HEATING
48

14

47
13
46

45

AR18
AR14
AR12
AR9
AR7

11

Temperature ( C)

Temperature ( C)

12

AR18
AR14
AR12
AR9
AR7

44

43

42

10

41
9
40

8
200

300

400

500

600

700

800

39
200

300

400

500

Air Flow (m3/h)

Air Flow (m /h)


3

- (04 - 108) -

600

700

800

4-11-2. FAN CURVE (DUCT TYPE)


MODELS : AR25, AR30, AR36, AR45

AR25

Recommended Range
20

196
(Pa)

External
Static
Pressure

(mmAq)

18
16
14

HIGH

12
10

98

LOW

8
6
4
2

600

800

1,000

1,200

1,400

1,600

1,800

Air Flow (m /h)

AR30
External
Static
Pressure

INDOOR
UNIT

INDOOR
UNIT

Recommended Range
196
(Pa)

20
18

(mmAq)

16

HIGH

14
12

LOW

98

10
8
6
4
2

400

600

800

1,000

1,200

1,400

1,600

1,800

2,000

2,200

2,400

Air Flow (m 3/h)

AR36

Recommended Range
20

196
External
(Pa)
Static
Pressure

18

(mmAq)

16
14

HIGH

12
10

98

LOW

6
4
2

800

1,000 1,200 1,400 1,600 1,800 2,000 2,200 2,400 2,600

Air Flow (m 3/h)

AR45
External
Static
Pressure

Recommended Range
20

196
(Pa)

18
16

HIGH

14
12
10

98

LOW

6
4
2

800

1,000 1,200 1,400 1,600 1,800 2,000 2,200 2,400 2,600


Air Flow (m3/h)

- (04 - 109) -

(mmAq)

4-11-3. CAPACITY BY AIR FLOW


(DUCT TYPE)
MODELS : AR25, AR30

Cooling

Heating

(Condition : Inlet Air Temp. 27

, Outdoor Temp. 35

.)

(Condition : Inlet Air Temp. 20

Recommended Range AR30

Recommended Range AR25


12

10

10

INDOOR
UNIT

Capacity (kW)

12

Capacity (kW)

.)

Recommended Range AR30

Recommended Range AR25

400

600

800

1000

1200 1400 1600


Air Flow (m3/h)

1800

2000

2200

2400

400

600

800

1000

1200 1400 1600


Air Flow (m3/h)

1800

2000

2200

2400

MODELS : AR36, AR45


Heating

Cooling
(Condition : Inlet Air Temp. 27

, Outdoor Temp. 35

(Condition : Inlet Air Temp. 20

.)

13

15

12

14

11

13

Capacity (kW)

16

10
9

12
11

10

9
800

1000

1200

1400

1600
1800
Air Flow (m3/h)

2000

.)

Recommended Range AR36

Recommended Range AR36


14

, Outdoor Temp. 7

Recommended Range AR45

Recommended Range AR45

Capacity (kW)

INDOOR
UNIT

, Outdoor Temp. 7

2200

2400

2600

- (04 - 110) -

800

1000

1200

1400

1600
1800
Air Flow (m3/h)

2000

2200

2400

2600

4-11-4. OUTLET AIR TEMPERATURE


(DUCT TYPE)
MODELS : AR25, AR30
Cooling

Heating

(Condition : Inlet Air Temp. 27

, Outdoor Temp. 35

.)

(Condition : Inlet Air Temp. 20

Recommended Range AR30

, Outdoor Temp. 7

.)

Recommended Range AR30

Recommended Range AR25

Recommended Range AR25

18
17

50
48
Temp (C)

15
14
13

46
44
42

12

40

11

38

10

400

600

800

1000

1200 1400 1600


Air Flow (m3/h)

1800

2000

2200

2400

INDOOR
UNIT

INDOOR
UNIT

Temp (C)

16

36
400

800

600

1000

1200

1400

1600

1800

2000

2200

2400

2400

2600

Air Flow (m3/h)

MODELS : AR36, AR45


Heating

Cooling
(Condition : Inlet Air Temp. 27

, Outdoor Temp. 35

.)

(Condition : Inlet Air Temp. 20

.)

Recommended Range AR45

Recommended Range AR45

Recommended Range AR36

Recommended Range AR36


20

52

18

50

16

48

14
Temp.(C)

Temp.(C)

, Outdoor Temp. 7

12
10
8

46
44
42
40

38
800

1000

1200

1400

1600
1800
Air Flow (m3/h)

2000

2200

2400

2600

36
800

1000

1200

1400

1600

1800

Air Flow (m3/h)

- (04 - 111) -

2000

2200

4-11-5. FAN CURVE ( HIGH STATIC PRESSURE DUCT TYPE )


MODELS : AR36H,AR45H,AR60H
AR36H

AR45H

AR60H

Recommended Range

Recommended Range

Recommended Range

300

HIGH
200

150
LOW
100

HIGH
200

150
LOW
100

50

50

1,000

2,000

3.4
CAPACITY

3,000 (m3/ h)

200
HIGH
150
LOW
100

50

1,000

3
3,000 (m/h)

2,000

2,000

3,000

COOLING

HEATING

20.0

20.0

AR60H

AR60H

15.0

Capacity (kW)

Capacity (kW)

15.0

AR45H
AR36H
10.0

5.0
1,000

AR45H

AR36H

10.0

2,000

3,000

5.0
1,000

4,000

2,000

Air Flow (m / h)

4,000

3,000

4,000

AIR TEMPERATURE
COOLING

HEATING
50.0

20.0

AR45H

AR60H
AR45H

AR36H

AR60H

45.0

Temp. ( C)

15.0

AR36H

40.0

10.0

5.0
1,000

3,000

Air Flow (m / h)

3.5
OUTLET

4,000 (m3/ h)

BY AIR FLOW

Temp. ( C)

INDOOR
UNIT

250

External Static Pressure (Pa)

250

External Static Pressure (Pa)

External Static Pressure (Pa)

250

300

35.0
2,000

3,000

4,000

Air Flow (m 3/ h)

1,000

2,000
Air Flow (m 3/ h)

- (04 - 112) -

INDOOR
UNIT

300

4-12. FRESH AIR

AB30-54 FRESH AIR CHARACTERISTIC


(mmAq)
10

(Pa) 98

54

INDOOR
UNIT

INTAKE DUCT STATIC PRESSURE

INDOOR
UNIT

45

49

36
30

4
3

AIR FLOW (m /min)

- (04 - 113) -

DUCT CONNECTION
OUTLET AIR
MODEL : AU7, AU9, AU12, AU14, AU18
(Pa)
78

AU18
L=5m

AU12,14

Duct (inside dia. 150mm)

AU7,9

DUCT
39
STATIC
PRESSURE

L
0

4
(m3/ min)

(mmAq)
8
7
6
5
4
3
2
1
0

MODEL : AU7, AU9, AU12, AU14, AU18


Duct (inside dia. 150mm)

(mmAq)
7

(Pa)

58.8

DUCT
STATIC
PRESSURE

Duct Fan

39.2

3
19.6

2
1

DIMENSION

Static pressure required


to take in fresh air

OUTLET AIR PORT

1.0

(m / min)

2.0

Unit : mm

Self tapping screw holes(for 4mm)


P.D 170

FRESH AIR PORT

- (04 - 114) -

INDOOR
UNIT

INDOOR
UNIT

FRESH AIR

OUTLET AIR
MODELS : AU20, AU25, AU30
(Pa)

(mmAq)
10

98
L=5m

L=3m

Duct
(Inside Dia. 100mm)
DUCT
STATIC
PRESSURE

L=1m

49

AU30
AU25

AU20

2
0
0

INDOOR
UNIT

Duct
(Inside Dia. 100mm)

(m /min)
3

(mmAq)
10

98

L=5m

L=3m
L=1m
DUCT
STATIC
PRESSURE

AU30

49

AU25

AU20

2
0
0

FRESH AIR

(m /min)
3

MODELS : AU20, AU25, AU30


(mmAq)
7

(mmAq)

(Pa)
58.8

Duct
(Inside Dia. 70mm)

5
DUCT
39.2
STATIC
PRESSURE

Duct Fan

4
3

19.6

2
1

Static pressure required


to take in fresh air

0
0

0.1

DIMENSION

0.2

0.3
0.4
(m3/min)

P.D 120

0.5

0
0.6

P.D 88

45

45

00
1

160

334.2

12-3.3 Self tapping screw holes (for 4mm)

OUTLET AIR PORT

- (04 - 115) -

FRESH AIR PORT

0
5

INDOOR
UNIT

(Pa)

OUTLET AIR
MODELS : AU36, AU45, AU54
(Pa)

(mmAq)
10

(mmAq)

98

L=5m

AU54

Duct
(Inside Dia. 100mm)

L=3m

DUCT
STATIC
PRESSURE

L=1m

AU45
AU36

49

4
2

(Pa)
INDOOR
UNIT

Duct
(Inside Dia. 100mm)

(m /min)
3

L=5m

AU54

L=3m

AU45

L=1m

AU36
DUCT
STATIC
PRESSURE

(mmAq)
10

(mmAq)

98

8
6

49

4
2

0
0

FRESH AIR

(m /min)
3

MODELS : AU36, AU45, AU54


(Pa)

(mmAq)
7

(mmAq)

58.8
Duct
(Inside Dia. 70mm)

Duct Fan

5
DUCT
STATIC
PRESSURE

39.2

4
3

19.6

2
1

Static pressure required


to take in fresh air

0
0

0.1

DIMENSION

0.2

0.3
0.4
(m3/min)

P.D 120

0.5

0
0.6

P.D 88

45

45

00
1

160

334.2

12-3.3 Self tapping screw holes (for 4mm)

OUTLET AIR PORT

- (04 - 116) -

FRESH AIR PORT

0
5

INDOOR
UNIT

0
0

4-13. NOISE LEVEL CURVE


Condition

4-13-1. UNIVERSAL FLOOR / CEILING TYPE

Fan speed
: High
Operation mode: FAN
Voltage
: 230V

MODEL : AB12

MODEL : AB14

80

80

70

70

NC-55
50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

INDOOR
UNIT

NC-60

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

NC-65

10

NC-25
20

NC-20
NC-15

10

63

125

250

500

1,000

2,000

4,000

8,000

63

125

Octave band center frequency,Hz

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

MODEL : AB18

MODEL : AB24

80

80

70

70

NC-65

NC-65
60

NC-60

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

INDOOR
UNIT

NC-65
60

NC-55
50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

10

10

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

63

125

250

500

1,000

2,000

Octave band center frequency,Hz

- (04 - 117) -

4,000

8,000

Condition

4-13-2. LARGE CEILING TYPE

Fan speed
: High
Operation mode: FAN
Voltage
: 230V

MODEL : AB30

MODEL : AB36

80

80

70

70

NC-55
50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

INDOOR
UNIT

NC-60

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

NC-65

10

NC-25
20

NC-20
NC-15

10

63

125

250

500

1,000

2,000

4,000

8,000

63

125

Octave band center frequency,Hz

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

MODEL : AB45

MODEL : AB54

80

80

70

70

NC-65
60

NC-65

NC-60

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

INDOOR
UNIT

NC-65
60

NC-55
50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

10

10

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

63

125

250

500

1,000

2,000

Octave band center frequency,Hz

- (04 - 118) -

4,000

8,000

Condition

4-13-3. COMPACT DUCT TYPE

Fan speed
: High
Operation mode: FAN
Voltage
: 230V
Static pressure : 0 Pa

MODEL : AR7

MODEL : AR9

80

80

70

70

NC-65

NC-55
50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

INDOOR
UNIT

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

NC-60

10

NC-25
20

NC-20
NC-15

10

63

125

250

500

1,000

2,000

4,000

8,000

63

125

Octave band center frequency,Hz

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

MODEL : AR12

MODEL : AR14

80

80

70

70

NC-65
60

NC-65

NC-60

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

INDOOR
UNIT

NC-65
60

NC-55
50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

10

10

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

63

125

250

500

1,000

2,000

Octave band center frequency,Hz

- (04 - 119) -

4,000

8,000

Condition

Fan speed
: High
Operation mode: FAN
Voltage
: 230V
Static pressure : 0 Pa

MODEL : AR18
80

70

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

INDOOR
UNIT

Octave band sound pressure level, dB:(0dB=0.0002bar)

INDOOR
UNIT

NC-65
60

NC-25
20

NC-20
NC-15

10

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

- (04 - 120) -

4-13-4. DUCT TYPE


Condition

Condition

Fan speed
: High
Operation mode: FAN
Voltage
: 230V
Static pressure : 100Pa

MODEL : AR30

80

80

70

70

NC-65

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

10

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

10

63

125

250

500

1,000

2,000

4,000

8,000

63

125

Octave band center frequency,Hz

250

500

2,000

4,000

8,000

Condition

Fan speed
: High
Operation mode: FAN
Voltage
: 230V
Static pressure : 100Pa

MODEL : AR36

1,000

Octave band center frequency,Hz

Condition

Fan speed
: High
Operation mode: FAN
Voltage
: 230V
Static pressure : 100Pa

MODEL : AR45

80

80

70

70

NC-65
60

NC-65

NC-60

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

INDOOR
UNIT

NC-65
60

INDOOR
UNIT

MODEL : AR25

Fan speed
: High
Operation mode: FAN
Voltage
: 230V
Static pressure : 120Pa

NC-55
50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

10

10

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

63

125

250

500

1,000

2,000

Octave band center frequency,Hz

- (04 - 121 ) -

4,000

8,000

Condition

4-13-5. HIGH STATIC PRESSURE DUCT TYPE

Fan speed
: High
Operation mode: FAN
Voltage
: 230V
Static pressure : 200Pa

MODEL : AR36H

MODEL : AR45H

80

80

70

70

NC-65

NC-55
50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

INDOOR
UNIT

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

NC-60

10

NC-25
20

NC-20
NC-15

10

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

80

70

NC-65
60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

10

63

125

250

500

1,000

2,000

63

125

250

500

1,000

2,000

Octave band center frequency,Hz

MODEL : AR60H

Octave band sound pressure level, dB:(0dB=0.0002bar)

INDOOR
UNIT

NC-65
60

4,000

8,000

Octave band center frequency,Hz

- (04 - 122) -

4,000

8,000

Condition

4-13-6. COMPACT CASSETTE TYPE

Fan speed
: High
Operation mode: FAN
Voltage
: 230V

MODEL : AU7

MODEL : AU9

80

80

70

70

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

INDOOR
UNIT

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

NC-65

10

NC-25
20

NC-20
NC-15
10

63

125

250

500

1,000

2,000

4,000

8,000

63

125

Octave band center frequency,Hz

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

MODEL : AU12

MODEL : AU14

80

80

70

70

NC-65
60

NC-65

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

INDOOR
UNIT

NC-65
60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15
10

10

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

63

125

250

500

1,000

2,000

Octave band center frequency,Hz

- (04 - 123) -

4,000

8,000

Condition

Fan speed
: High
Operation mode: FAN
Voltage
: 230V

MODEL : AU18
80

70

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

INDOOR
UNIT

Octave band sound pressure level, dB:(0dB=0.0002bar)

INDOOR
UNIT

NC-65
60

NC-25
20

NC-20
NC-15
10

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

- (04 - 124) -

Condition

4-13-7. CASSETTE TYPE

Fan speed
: High
Operation mode: FAN
Voltage
: 230V

MODEL : AU20

MODEL : AU25

80

80

70

70

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

INDOOR
UNIT

NC-55
50

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

NC-60

NC-65

10

NC-25
20

NC-20
NC-15

10

63

125

250

500

1,000

2,000

4,000

8,000

63

125

Octave band center frequency,Hz

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

MODEL : AU30

MODEL : AU36

80

80

70

70

NC-65

NC-65
60

NC-60

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

INDOOR
UNIT

NC-65
60

NC-55
50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

10

10

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

63

125

250

500

1,000

2,000

Octave band center frequency,Hz

- (04 - 125) -

4,000

8,000

Condition

Fan speed
: High
Operation mode: FAN
Voltage
: 230V

MODEL : AU45

MODEL : AU54

80

80

70

70

NC-65

NC-55
50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

10

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

INDOOR
UNIT

NC-60

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

INDOOR
UNIT

NC-65
60

NC-25
20

NC-20
NC-15

10

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

63

125

250

500

1,000

2,000

Octave band center frequency,Hz

- (04 - 126) -

4,000

8,000

Condition

4-13-8. WALL MOUNTED TYPE

Fan speed
: High
Operation mode: FAN
Voltage
: 230V

MODEL : AS18

MODEL : AS24

80

80

70

70

NC-55
50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

INDOOR
UNIT

NC-60

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

NC-65

10

NC-25
20

NC-20
NC-15

10

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

80

70

NC-65
60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

10

63

125

250

500

1,000

2,000

63

125

250

500

1,000

2,000

Octave band center frequency,Hz

MODEL : AS30

Octave band sound pressure level, dB:(0dB=0.0002bar)

INDOOR
UNIT

NC-65
60

4,000

8,000

Octave band center frequency,Hz

- (04 - 127) -

4,000

8,000

Condition

4-13-9. CEILING WALL TYPE

Fan speed
: High
Operation mode: FAN
Voltage
: 230V

MODEL : AW7

MODEL : AW9

80

80

70

70

NC-55
50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

INDOOR
UNIT

NC-60

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

NC-65

10

NC-25
20

NC-20
NC-15

10

63

125

250

500

1,000

2,000

4,000

8,000

63

125

Octave band center frequency,Hz

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

MODEL : AW12

MODEL : AW14

80

80

70

70

NC-65
60

NC-65

NC-60

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

INDOOR
UNIT

NC-65
60

NC-55
50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

10

10

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

63

125

250

500

1,000

2,000

Octave band center frequency,Hz

- (04 - 128) -

4,000

8,000

Condition

Fan speed
: High
Operation mode: FAN
Voltage
: 230V

MODEL : AW18

MODEL : AW24

80

80

70

70

NC-55
50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

INDOOR
UNIT

NC-60

Octave band sound pressure level, dB:(0dB=0.0002bar)

Octave band sound pressure level, dB:(0dB=0.0002bar)

NC-65

10

NC-25
20

NC-20
NC-15

10

63

125

250

500

1,000

2,000

4,000

8,000

Octave band center frequency,Hz

80

70

NC-65
60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20
NC-15

10

63

125

250

500

1,000

2,000

63

125

250

500

1,000

2,000

Octave band center frequency,Hz

MODEL : AW30

Octave band sound pressure level, dB:(0dB=0.0002bar)

INDOOR
UNIT

NC-65
60

4,000

8,000

Octave band center frequency,Hz

- (04 - 129) -

4,000

8,000

SOUND LEVEL CHECK POINT

UNIVERSAL FLOOR / CEILING TYPE


LARGE CEILING TYPE

UNIVERSAL FLOOR / CEILING TYPE

1m

1m

1m

MIC

0.8m (For AB12


1m (For AB30

AB24)
AB54)

INDOOR
UNIT

INDOOR
UNIT

MIC

COMPACT CASSETTE TYPE


CASSETTE TYPE

COMPACT DUCT TYPE


DUCT TYPE
2m

1.5m

2m

1.5m

MIC

MIC

WALL MOUNTED TYPE


CEILING WALL TYPE

1m

1m

MIC

- (04 - 130) -

4-14. SAFETY DEVICE

UNIVERSAL
FLOOR / CEILING
TYPE

LARGE CEILING
TYPE

INDOOR
UNIT

COMPACT DUCT
TYPE

DUCT TYPE

HIGH STATIC
PRESSURE
DUCT TYPE
COMPACT
CASSETTE
TYPE

CASSETTE
TYPE

WALL MOUNTED
TYPE

CEILING WALL
TYPE

*1

AB12
AB14
AB18
AB24
AB30
AB36
AB45
AB54
AR7
AR9
AR12
AR14
AR18
AR25
AR30
AR36
AR45
AR36
AR45

FAN MOTOR
THERMAL
PROTECTOR

250V 3.15A

135

OFF

250V 3.15A

120

OFF

250V 3.15A

135

OFF

250V 3.15A

135

OFF

250V 3.15A

135

OFF

TERMINAL
THERMAL
FUSE

*1

AR60
AU7
AU9
AU12
AU14
AU18
AU20
AU25
AU30
AU36
AU45
AU54
AS18
AS24
AS30

250V 3.15A

102

OFF

135

OFF

250V 3.15A

130

OFF

102

OFF

250V 3.15A

120

OFF

102

OFF

250V 3.15A

120

OFF

102

OFF

AW7
AW9
AW12
AW14
AW18
AW24
AW30

Including the drain pump kit (option parts)

- (04 - 131) -

FLOAT
SWITCH

INDOOR
UNIT

P.C.B
FUSE

MODEL NAME

R407C

TM

SERIES

5 . INSTALLATION

5-1 PIPING DESIGN


5-1-1 PIPING METHOD
SUMMARY OF PIPING SYSTEM

Heat Recovery Type


Outdoor
unit

Separation
tube
RB unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Separation of piping :
Separation tube system and header system
Number of piping :
3 each of outdoor unit - RB unit,2 pipe for indoor unit
RB unit :
Individual branching and 4 unit branching

- (05 - 01) -

INSTALLATION

INSTALLATION

RB unit

TYPE OF PIPING SYSTEM


Line Piping System
Outdoor
unit

Separation
tube
RB unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Header Piping System


Header

Outdoor
unit

INSTALLATION

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Combined (Separation tube/Header) Piping System


Outdoor
unit

Separation
tube

Header

RB unit

Indoor
unit

Outdoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Separation
tube

Indoor
unit

RB unit

Indoor
unit
Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Separation after header separation is not possible

- (05 - 02) -

Indoor
unit

INSTALLATION

RB unit

5-1-2. LIMITATIONS
EXAMPLE 2
Branch kit : Separation tube

EXAMPLE 1
Branch kit : Header
Outdoor
unit

Outdoor
unit
a

a
b
H1

c
RB
unit
Indoor
unit

d
RB
unit
Indoor
unit

RB
unit

H3

Indoor
unit

H2

RB
unit

e
f

RB
unit

H1
h

Indoor
unit

H4, f

RB
unit
Indoor
unit

RB
unit
Indoor
unit

RB
unit
Indoor
unit

RB
unit
Indoor
unit

H3
H2

RB
unit

H4

Indoor
unit

Indoor
unit

EXAMPLE 3
Branch kit : Separation tube + Header
Outdoor
unit
b

RB unit
4 branch
H1

RB
h unit
RB
unit

Indoor
unit

Indoor
unit

H2

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

INSTALLATION

INSTALLATION

H4

H3

CAUTIONS
Keep the length of straight portion of pipe between two branch kits longer than 0.5m.
Don't use separation tube in the downstream of header.
Install separation tube and header in the corrent direction specified in installation.
Maximum allowable length (actual pipe length)

Between outdoor unit and the


farthest indoor unit

100 m

Total pipe length

200 m

Between outdoor unit and the 1st


branch kit

70 m

Between the 1st branch kit and the


farthest indoor unit

40 m

Between indoor unit and RB unit

40 m

Maximum allowable height difference


Between outdoor unit and indoor
units
Between indoor units
Between RB units
Between RB unit and indoor unit

EXAMPLE 1

EXAMPLE 2

EXAMPLE 3

a+b
a+c
a+d
a+e
-

a+g
a+g+h
a+b+h
a+g+i
a+b+c+i
a+b+c
a+b+c+d+j
a+b+d
a+b+c+d+e+k
a+b+e
a+b+c+d+ e+f
a+b+f
a+b+c+d+e+f+g a+b+c+d+e
a+b+c+d+e
+h+i+j+k
+f+g+h+i
a
b
c
d
e
f

g
b+h
b+c+i
b+c+d+j
b+c+d+e+k
b+c+d+ e+f

g+h
g+i
b+c
b+d
b+e
b+f
c, d, e, f

EXAMPLE 1

EXAMPLE 2

EXAMPLE 3

50 m
40 m
15 m
15 m
5m

H1
H1

- (05 - 03) -

(If outdoor unit is in the upper side)


(If outdoor unit is in the lower side)
H2
H3
H4

5-1-3 PIPE SIZE


HEAT RECOVERY MODEL
Pipe size connected to outdoor unit.
(unit : mm)

Suction Gas Pipe Discharge Gas Pipe


size ( thickness )
size ( thickness )

Model
AO 90

28.58 ( 1.2 )

Liquid Pipe
size ( thickness )

19.05 ( 1.0 )

12.70 ( 0.8 )

Between two adjacent refrigerant branch kits.


(unit : mm)

Suction Gas Pipe


size ( thickness )

Discharge Gas Pipe


size ( thickness )

Liquid Pipe
size ( thickness )

Separation Kit

Less than 30

15.88 ( 1.0 )

12.70 ( 0.8 )

9.52 ( 0.8 )

31 or more to 60

19.05 ( 1.0 )

15.88 ( 1.0 )

9.52 ( 0.8 )

61 or more

28.58 ( 1.2 )

19.05 ( 1.0 )

12.70 ( 0.8 ) UTR-BP90MA

Connection pipe size of indoor unit.


Model code of indoor unit

(unit : mm)

Gas Pipe
size ( thickness )

Liquid Pipe
size ( thickness )

7, 9

9.52 ( 0.8 )

6.35 ( 0.8 )

12, 14

12.70 ( 0.8 )

6.35 ( 0.8 )

18, 20, 24, 25

15.88 ( 1.0 )

30
36, 45, 54, 60

15.88 ( 1.0 )
19.05 ( 1.0 )

6.35 ( 0.8 )
9.52 ( 0.8 )

- (05 - 04) -

9.52 ( 0.8 )

UTR-BP54MA

INSTALLATION

INSTALLATION

Total model code of


indoor unit

5-1-4. SELECTION OF PIPE HEAT INSULATING MATERIAL


1. Always insulate the refrigerant pipe to prevent condensation and water droplets by the refrigerant pipe.
2. Decide the thickness of the heat insulating material by referring to the recommended minimum thickness
in Table 1.
(For installation condition T=32 C(DB),humidity<70%, humidity<75%, humidity<80%, humidity<85%)
3. When the outdoor unit is installed at a higher position than the indoor unit, fill the connecting part gap with
putty, etc. to prevent the dew condensation water of the valve of the outdoor unit from flowing to the indoors from the gap between the pipe and the heat insulating material.
4.

Liquid pipe and gas pipe should be completely insulated with same specification and sealed.

5. In case not to insulate and not to seal refrigerant pipe completely, it will become the cause of water leak.

Table 1 Size of refrigerant pipe and recommended minimum thickness of heat insulating material
(In case a heat insulating material which thermal conductivity is equal to or less than 0.040 W/(mk) is used. )

INSTALLATION

Relative humidity

Refrigerant
pipe
Outside
diameter
mm(in)

6.35 (1/4")
9.53 (3/8")

< 70%
8
9

< 75%
10
11

< 80%
13
14

< 85%
17
18

12.70 (1/2")
15.88 (5/8")
19.05 (3/4")

10
10
10

12
12
13

15
16
16

19
20
21

22.22 (7/8")
25.40 (1")
28.58 (1 1/8")

11
11
11

13
13
14

17
17
18

22
22
23

When an ambient temperature and relative humidity exceed 32 C (DB)and>85%, respectively please
strengthen heat insulation of refrigerant pipe. When not strengthening heat insulation of refrigerant
pipe, the surface of the heat insulation may be dewed.
Since gas pipe becomes high temperature at heating operation,
for heatpump type, please select the heat insulating material which heat-resistant temperature
is 120 C or more.

- (05 - 05) -

INSTALLATION

Recommended minimum thickness


for heat insulating material (mm)

5-1-5. ADDITIONAL CHARGE CALCULATION


Application models
AO 90MPBMF

Additional charge for pipe length


Liquid pipe outside
diameter
(mm)

12.70

9.52

6.35

Additional refrigerant
(kg/m)

0.136

0.063

0.025

The amount of additional charge C (kg)

Total length x 0.063


of 9.52mm
kg/m
liquid pipe

INSTALLATION

m
kg

Total length x 0.025


of 6.35mm
kg/m
liquid pipe

Total

m
kg

kg

Round up C to 2 decimal place.

Example : When the outdoor unit model is AO 90MPBMF and liquid pipe length are
20m (12.70mm), 15m (9.52mm), and 20m (6.35mm), respectively.
Additional charge :
C = 20(m) x 0.136(kg/m) +15(m) x 0.063(kg/m) + 20(m) x 0.025(kg/m) = 4.17(kg)

- (05 - 06) -

kg

INSTALLATION

C=

Total length x 0.136


of 12.70mm
kg/m
liquid pipe

5-1-6. EXAMPLE OF PIPING DESIGN


HEAT RECOVERY MODEL

(1) Refrigerant system


Outdoor
unit

AO90
MPBMF

c
B

A
d
RB
unit

e
RB
unit

RB
unit

m n

10

11

12

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Example 1
INSTALLATION

Capacity(kW)

Example 2
Capacity(kW)

11

12

AU9

AU9

2.8

2.8

10

AU9

AU9

AU9

AU9

AU7

AU7

AU7

AU7

AU7

AU7

2.8

2.8

2.8

2.8

2.15

2.15

2.15

2.15

2.15

2.15

AU9

AU9

AU9

AU9

AU7

AU7

AU7

AU7

AU7

AU7

2.8

2.8

2.8

2.8

2.15

2.15

2.15

2.15

2.15

2.15

Total capacity

29.7

AU25 AU25
7.05

7.05

38.2

Total indoor unit capacity (1 refrigerant system)


36.4
Example1 : Total capacity = 29.7
Example2 : Total capacity = 38.2
36.4

Example 2 cannot be selected

Selection of pipe size (Example 1)


Suction Gas Pipe
Discharge Gas Pipe
Gas Pipe
Liquid Pipe
Length [m] (Example)

(unit : mm)

a
28.58

b
19.05

c
19.05

d
19.05

e
15.88

19.05

15.88

15.88

15.88

12.70

9.52

9.52

12.70

9.52

9.52

9.52

9.52

6.35

6.35

10

10

15

10

9.52
6.35

9.52
6.35

9.52
6.35

9.52
6.35

9.52

9.52

9.52

9.52

9.52

9.52

10

10

6.35
5

6.35
10

6.35
10

6.35
5

6.35
5

6.35
10

- (05 - 07) -

INSTALLATION

System configuration

Pipe length
a+b+c+q=45
100m (actual pipe length)
b+c+q=35
40m (actual pipe length)
a+b+c+d+e+f+g+h+i+j+k+l+m+n+o+p+q=135
200m (total pipe length)
Difference in height between outdoor unit and indoor units maximum 50m.
Difference in height between highest and lowest indoor unit maximum 15m.

Selection of separation tube and header


A
Model name

UTR-BP90MA UTR-BP54MA UTF-Y90A4A UTF-Y90A4A UTF-Y90A4A

Liquid pipe (mm)


INSTALLATION

Additional refrigerant
(R407C)

(kg/m)

Liquid pipe length (m)

12.70

9.52

6.35

0.136

0.063

0.025

10

35

90

Additional refrigerant
(0.136 x 10) + (0.063 x 35) + (0.025 x 90) = 5.82 (kg)

- (05 - 08) -

INSTALLATION

Additional charge

(2) Refrigerant system


Outdoor
unit

AO90
MPBMF

c
RB
unit

RB
unit

RB
unit

e
RB
unit

E
h

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

NOTE:
Liquid pipe does not pass
through theRB unit

System configuration
1

Total capacity

Example 1 AR18 AR18 AR30 AR36


5.3

Capacity(kW)

5.3

8.8

10.5

29.9

8.8

Capacity(kW)

8.8

8.8

12.7

39.1

INSTALLATION

INSTALLATION

Example 2 AR30 AR30 AR30 AR45

Total capacity of indoor unit (1 refrigerant system)


Example1 : Total capacity = 29.9 36.4
Example2 : Total capacity = 39.1 36.4
Example 2 cannot be selected.

Selection of pipe size (Example 1)


Suction Gas Pipe
Discharge Gas Pipe
Gas Pipe
Liquid Pipe
Length [m] (Example)
h

a
28.58
19.05
12.70
20

(unit : mm)

b
15.88
12.70

c
15.88
12.70

6.35
10

6.35
5

d
15.88
12.70
9.52
5

e
19.05
15.88
9.52
10

15.88
6.35
2

15.88
6.35
2

15.88

19.05

9.52
2

9.52
2

Pipe length
a+b=32m 100m (actual pipe length)
Difference in height between outdoor unit and indoor unit maximum 50m.
Difference in height between the highest and the lowest indoor unit maximum 15m.
Form outdoor unit to the first header tube a=20m 70m (actual pipe length)
From the first header tube to the farthest indoor unit e=12m 40m (actual pipe length)
200m (total pipe length)
a+b+c+d+e+f+g+h+i=58
- (05 - 09) -

Selection of separation tube and RB unit


A
Model name

UTR-HD906R UTF-Y54A1A UTF-Y54A1A UTF-Y54A1A UTF-Y54A1A

Additional charge
Liquid pipe (mm)
Additional refrigerant

(R407C)

(kg/m)

Liquid pipe length (m)

12.70

9.52

6.35

0.136

0.063

0.025

20

19

19

Additional refrigerant

INSTALLATION

INSTALLATION

(0.136 x 20) + (0.063 x 19) + (0.025 x 19) = 4.40 (kg)

- (05 - 10) -

(3) Refrigerant system


Outdoor
unit

AO90
MPBMF

A
B

NOTE:
Liquid pipe do not pass
C
through the RB unit C and D
f

RB
unit

RB
unit

RB
unit

D
h

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

System configuration
1

Example 1 AW24 AB36 AR9


6.8

Capacity (kW)

10.5

2.8

AR9

AR9

AR9

2.8

2.8

2.8

Total capacity

28.5

8.8

Capacity (kW)

14.1

4.0

4.0

4.0

4.0

38.9

INSTALLATION

INSTALLATION

Example 2 AW30 AB54 AR14 AR14 AR14 AR14

Total capacity of indoor unit (1 refrigerant system)


Example1 : Total capacity = 28.5 36.4
Example2 : Total capacity = 38.9 36.4
Example 2 cannot be selected.

Selection of pipe size (Example 1)


Suction Gas Pipe
Discharge Gas Pipe
Gas Pipe
Liquid Pipe
Length[m](Example)

a
28.58
19.05
12.70
10

9.52
6.35
10

9.52
6.35
5

9.52
6.35
5

9.52
6.35
10

(unit : mm)

19.05
15.88
9.52
20

19.05
15.88
9.52
5

d
15.88
12.70
6.35
5

e
19.05
15.88
9.52
10

15.88
6.35
2

Pipe length
a+b+k = 40 100m (actual pipe length)
b+k = 30 40m (actual pipe length)
a+b+c+d+e+f+g+h+i+j+k= 84
200m (total pipe length)
Difference in height between outdoor unit and indoor units maximum 50m.
Difference in height between highest and lowest indoor unit maximum 15m.
- (05 - 11) -

19.05
9.52
2

Selection of separation tube and RB unit


A

Model name

UTR-BP90MA UTR-BP54MA UTF-Y54A1A

UTF-Y54A1A

UTF-Y90A4A

Additional charge
Liquid pipe (mm)

12.70

9.52

6.35

Additional refrigerant
(R407C)
(kg/m)

0.136

0.063

0.025

Liquid pipe length (m)

10

37

37

Additional refrigerant

INSTALLATION

INSTALLATION

(0.136 x 10) + (0.063 x 37) + (0.025 x 37) = 4.62 (kg)

- (05 - 12) -

5-2. WIRING DESIGN


5-2-1. WIRING SPECIFICATION
Use

Size

Outdoor
Power supply unit
2

cable (mm )

Indoor
unit

Maximum

8.0

Minimum

6.0

Maximum

2.5

Minimum

1.5

Transmission cable
2
(mm )

0.33

Remote controller cable


2
(mm )

0.33

Remote controller cable


2
(mm )

0.33

External input cable


2
(mm )

0.33

Wire type

Remarks

H07RN-F or
equivalent

Three phase, 50Hz, 380-415V


4 Wire + Ground

H07RN-F or
equivalent

Single phase, 50Hz, 220-240V

1
2

2 Wire + Ground

Shielded Level 4 Non-polar, Twisted pair,


22AWG (0.65mm) Solid core diameter 0.65mm
Sheathed vinyl
cord cable

Polar 3-core

Wired remote controller


Simple remote controller

Shield

Polar 3-core

Group remote controller


External switch controller

Shield

Twist pair polar 2-core

External switch controller

1,2 The ground wire is not included in this cable.


Always ground the unit.
3

Use the shielded wire specified and always ground it.


22AWG Level 4 cable with shielded(National Electrical Manufacturers Association (NEMA)
**differs from the Category 4 specification proposed by the Electronic Industries Association/
Telecommunication Industry Association (EIA/TIA)**

Total wiring length 2000m. However, when wiring length exceeds 500m, a signal
amplifier (option) is required.
Do not bundle the transmission cable with other wires. Otherwise, transmit-receive
with a transmission line is not only impossible, but a malfunction may occur.
4

10m cable attached.(excluded some models)


Use the shielded cable in accordance with the standards
of the country.
Wiring length of a remote controller group should be
within 500m.

Model
Fuse
capacity

5
6

Field fuse

Circuit breaker

Outdoor
unit

40A

40A 100mA 0.1sec or less

Indoor
unit

20A

20A 40mA 0.1sec or less

per outdoor unit


per refrigerant system.
Install the knife switch (contact gap 3mm or more) near the indoor unit
for ease of maintenance.(A breaker can be used instead of the knife swicth
for the outdoor unit.

- (05 - 13) -

INSTALLATION

INSTALLATION

NOTE:Install in accordance with local rules and regulations.

5-2-2. POWER SUPPLY CABLE WIRING


POWER SUPPLY CABLE SPECIFICATION
A separated power supply cable must be provided for the outdoor unit and indoor unit.
Outdoor unit : 3 4W 50Hz 380 - 415V
Indoor unit : 1
50Hz 220 - 240V
For heat recovery type, the wiring from refrigerant branch unit is connected to the
indoor unit (solenoid valve operation for cooling/heating switching --- Ex.1).

Use terminal board available on the market, when the number of indoor units connected
to outdoor unit increases. (Ex.2)
Use a circuit breaker of 40A or more for every outdoor unit.
The indoor unit shall be connected up to one refrigerant system, and a circuit breaker
of 20A or more should be used.

Outdoor unit power supply


3 4W 50Hz 380 - 415V
Indoor unit power supply
1 50Hz 220 - 240V

Outdoor
unit

40A

INSTALLATION

INSTALLATION

Example 1: Power supply cable wiring for heat recovery type. (wiring connection)

20A
Indoor
unit

Indoor
unit

Breaker on hand
Refrigerant
branch unit

Power supplied from indoor unit

Refrigerant
branch unit

Example 2: Power supply cable wiring for heat recovery type. (using terminal board)
Outdoor
unit

40A

Outdoor unit power supply


3 4W 50Hz 380 - 415V

20A

Indoor unit power supply


1 50Hz 220 - 240V
Breaker on hand

Indoor
unit

Indoor
unit

Terminal board

Power for refrigerant branchunit


supplied directly from relay circuit
on circuit board of indoor unit.

Refrigerant branch unit

- (05 - 14) -

Refrigerant branch unit

5-2-3. TRANSMISSION LINE


TRANSMISSION WIRING SPECIFICATIONS
Non-polar 2-core
Shielded level 4, 22AWG, Twist pair wire.

NOTE
Do not bundle and wire transmission line with other wiring.

WIRING RULES
In the following case, SIGNAL AMPLIFIER is required.
(1) When the total length of the transmission cord exceeded 500 m.
AB+BC+BD+DE+EF > 500 m (Fig. 1)
Fig. 1
OUTDOOR
UNIT
B

A
TERMINAL
RESISTOR

C
E

INDOOR UNIT

PC CONTROLLER

SIGNAL AMPLIFIER
is required.

(2) When the number of total unit* is over 64.

CENTRAL
REMOTE
CONTROLLER

INSTALLATION

INSTALLATION

TRANSMISSION CORD

Transmission cord length between each unit* : MAX 200 m


Total transmission cord length : MAX 2000 m
AB+BC+BD+DE+EF+EG+GH < 2000 m (Fig. 2)

When a SIGNAL AMPLIFIER is installed, network is divided into two network segments.
In a network segment (NS), divided by a SIGNAL AMPLIFIER, have to keep the following facts.
(1)Total transmission cord length : MAX 500 m

Fig. 2

AB+BC+BD < 500 m (Fig. 2)

OUTDOOR
UNIT

(2)The number of total unit* : MAX 64


B

(3)The number of terminal resistor : 1

NS 1

A
TRANSMISSION CORD
C

D
TERMINAL RESISTOR NS 2
E
F
G

NS 3
INDOOR UNIT

TERMINAL
RESISTOR
CENTRAL
REMOTE
CONTROLLER
PC CONTROLLER

NS 4
H
SIGNAL AMPLIFIER

Arrange so that there is one terminal resistor for each network segment.
If necessary, remove the terminal resistor which connected temporarily to the outdoor unit.
Only ground one side of the ground for transmission cord.
Note : Unit* means indoor unit, outdoor unit, central remote controller (CRC) and PC controller.

- (05 - 15) -

CHECK POINT
Arrange so that there is no transmission cord between each network segment except the
transmission cord which passed through the signal amplifier.
Arrange so that there is one terminal resistor for each network segment.
If necessary,remove the terminal resistor which connected temporarily to the CN22 terminator
of the circuit board for the outdoor unit.
Fig. 3
NS 1

OUTDOOR
UNIT

A
TRANSMISSION CORD
C

B
D

TERMINAL RESISTOR NS 2
E
F
G

NS 3

INDOOR UNIT

CENTRAL
REMOTE
CONTROLLER
PC CONTROLLER

NS 4
H
SIGNAL AMPLIFIER

FUSE(3A)

1 2 E 1 A 2 1B 2 E
POWER TRANSMISSION
TERMINAL TERMINAL

1 2 3 1 2 E
2 1 E
RC TRANSMISSION POWER
TERMINAL

TERM.A TERM.B
SIGNAL AMPLIFIER

INDOOR UNIT

SW7

TERMINAL
RESISTOR

SW3 SW2 SW1

TERMINAL
RESISTOR

CN2

E1

SW9 SW8

123
12E
21E
RC TRANSMISSION POWER
TERMINAL

ACIN

OUTDOOR BOARD
OUTDOOR UNIT

TERMINAL RESISTOR

INDOOR UNIT

- (05 - 16) -

INDOOR UNIT

INSTALLATION

NS 3 NS 4
SWITCH

CN22

INSTALLATION

1 50Hz
220-240V

TERMINAL
RESISTOR

EXAMPLE OF INSTALL SIGNAL AMPLIFIER (UTR-YRPC)

Example 1 : In case of series connection


NS1
Terminal resister

A
B Signal amplifier

NS2

Terminal resister

between A and C
NS1 : between A and B
NS2 : between B and C

800m
400m 500m
400m 500m

A
Terminal resister

Signal amplifier

Terminal resister

between A and B
between B and C
between B and D
between D and E
between E and F
between E and G
Total wiring length
NS1 : AB+BC+BD
NS2 : DE+EF+EG

100m
200m
200m
200m
100m
100m
900m
500m
500m

Note

Install the unit in a place where the total length of the


wiring below the signal amplifier is within 500m.

- (05 - 17) -

INSTALLATION

INSTALLATION

Example 2 : In case of branch connection

Example 3 : Branch connection and in case of over 64 units


Terminal
resistor

NS1

A
Terminal
box

NS2

Signal amplifier
Terminal resistor

C
G

D
1

63 64

NS3

Signal amplifier
Terminal resistor

between A and B 100m


between B and C 100m
between B and D 200m
between C and E 500m
between C and F 100m
between C and G 100m
between B and H
10m
between C and I
10m

Number of indoor unit 64

Total wiring length 1100m


NS1 : AB+BC+CG+CF+BH+CI
500m
NS2 : Total equipments between H and D
NS3 : IE 500m

- (05 - 18) -

64

INSTALLATION

INSTALLATION

5-2-4. WIRING SEPARATION


TRANSMISSION LINE SEPARATION RULES
Up to 16 separations is possible.
The transmission wiring between indoor unit, outdoor unit and controllers can be
connected by one wire.
Terminal board available on the market or the terminal inside the indoor unit or
outdoors should be used for transmission line separation.

NOTE
Do not loop.

If number of separation is extreme


it may cause an erroneous operation.

Refrigerant
system 1

Refrigerant
system 2

Refrigerant
system 3

Signal amplifier

Example 2 : Separating transmission line.


Refrigerant
system 1

Separate on
the terminal for
transmission line.

Refrigerant
system 2

Refrigerant
system 3

Separation using
terminal board

Central
remote controller

- (05 - 19) -

INSTALLATION

INSTALLATION

Example 1 : Connecting each outdoor and indoor unit with one connection wiring.

Example 3 : Separation wiring from one terminal board radially.


Terminal board
Refrigerant
system 1

Refrigerant
system 2

Central remote controller

Example 4 : Combination of example 2 and 3


Possible to 16 branches
Refrigerant
system 1

Refrigerant
system 2

Refrigerant
system 3

Terminal board

Central remote controller

- (05 - 20) -

INSTALLATION

INSTALLATION

Refrigerant
system 3

5-2-5. WIRING EXAMPLE


OUTDOOR UNIT

Power

Terminal
Transmission

RS T NE

E1 2

Terminal

INDOOR UNIT

INDOOR UNIT

Terminal
Trans- Power
RC mission

3 4W 50Hz
380-415V

12 3

12E

2 1

INDOOR UNIT

Terminal
Trans- Power
RC mission
E

12 3

1 2E

2 1

INDOOR UNIT

Terminal
Trans- Power
RC mission

Terminal
Trans- Power
RC mission
E

1 2 3

1 2E

2 1

12 3

1 2E

2 1

OUTDOOR UNIT

Power

Terminal
Transmission

RS TNE

E1 2

Terminal

150Hz
220-240V

WIRED REMOTE
CONTROLLER

WIRED REMOTE
CONTROLLER

SIMPLE REMOTE
CONTROLLER

3 4W 50Hz
380-415V

Power

Terminal
Transmission

RS TNE

E1 2

INSTALLATION

Terminal

INDOOR UNIT

3 4W 50Hz
380-415V

INDOOR UNIT

12 3

12E

2 1

INDOOR UNIT

Terminal
Trans- Power
RC mission

Terminal
Trans- Power
RC mission
E

1 2 3

1 2E

2 1

INSTALLATION

OUTDOOR UNIT

Terminal
Trans- Power
RC mission
E

1 2 3

1 2E

2 1

150Hz
220-240V

2 REMOTE CONTROLLER
WIRELESS REMOTE
CONTROLLER

2 REMOTE CONTROLLER

CENTRAL REMOTE
CONTROLLER

TRANSMISSION
ADAPTOR
RS-232C

Terminal
Transmission
E 2

Terminal
Power
E 2 1

Terminal
Transmission
E 2 1

Terminal
Power

PC CONTROLLER

E2 1

{ 150Hz
220-240V

- (05 - 21) -

5-3. SYSTEM SETTING


5-3-1. SYSTEM TYPE SETTING
Set the DIP switch to the corresponding system type as shown in the Table.
Do not use a nonexistent switch combination.

WIRED,SIMPLE REMOTE CONTROLLER


Factory setting

SW 4
OFF

INSTALLATION

ON

INSTALLATION

Heat pump
Heat recovery
Cooling only

- (05 - 22) -

5-3-2. ADDRESS SETTING


With this system, an address must be set for the indoor unit, outdoor
unit and remote controller and central remote controller.

(1) KINDS OF ADDRESS AND SETTING RANGE


SETTING

SETTING
RANGE

Outdoor
unit

Refrigerant
circuit address

0 99

Setting
example
0

SW 9

SW 8

SW 8

Indoor unit address

INSTALLATION

SW 9

Indoor
unit

Shown in the next page

Setting
example
63

0 99

REMARKS

Refrigerant
circuit address

TYPE OF SWITCH

Setting
example
2

0 15

SW 6

SW 7

Remote controller
address

Setting
example
0

0 3

Always SW 7 set "0"

SW 10

Remote
controller
(wired,simple)

Central
remote
controller

Dual remote controller


switch 1

ON/OFF

DIP SW1

OFF : Not terminated


ON : Terminated

Dual remote controller


switch 2

ON/OFF

DIP SW2

OFF : Master
ON : Slave

Group control setting

ON/OFF

DIP SW3

Number of indoor unit


OFF : 1 unit
ON : multiple unit

0 15

Initial setting

Central remote
controller address

- (05 - 23) -

INSTALLATION

UNIT

Refrigerant circuit address conversion table


Outdoor unit
Rotary switch (SW 8)- - - Factory setting "0"
Rotary switch (SW 9)- - - Factory setting "0"
Indoor Unit
Rotary switch (SW 8)- - - Factory setting "0"
Rotary switch (SW 9)- - - Factory setting "0"
In the case of a multiple refrigerant system, each refrigerant system (outdoor unit and indoor unit)
must be set an exclusive refrigerant circuit address.
Please use the rotary switches(SW8,SW9) to set the address.A conversion table of refrigerant
circuit address and rotary switch setting is shown in the table below.
Do not use a nonexistent switch setting combination.

INSTALLATION

INSTALLATION

Example : When SW 9 is set to "1" and SW 8 is set to "14" the refrigerant


circuit address will be "30".

Refrigerant
Refrigerant
Refrigerant Rotary
Refrigerant
Refrigerant
Rotary
Rotary
Rotary
Rotary
circuit
circuit
circuit
circuit
Switch setting circuit
Switch setting
Switch setting
Switch setting
Switch setting
address
address
address
address
address

0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19

SW9

SW8

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1

0
1
2
3
4
5
6
7
8
9
10 (A)
11 (B)
12 (C)
13 (D)
14 (E)
15 (F)

0
1
2
3

SW9 SW8

20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39

1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2

4
5
6
7
8
9
10(A)
11(B)
12(C)
13(D)
14(E)
15(F)

0
1
2
3
4
5
6
7

SW9 SW8

40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59

2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
3
3
3
3

- (05 - 24) -

8
9
10(A)
11(B)
12(C)
13(D)
14(E)
15(F)

0
1
2
3
4
5
6
7
8
9
10
11

SW9 SW8

60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79

3
3
3
3
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

12
13
14
15
0
1
2
3
4
5
6
7
8
9
10 (A)
11 (B)
12 (C)
13 (D)
14 (E)
15 (F)

SW9 SW8

80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99

5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
6
6
6
6

0
1
2
3
4
5
6
7
8
9
10(A)
11(B)
12(C)
13(D)
14(E)
15(F)

0
1
2
3

(2) SETTING EXAMPLE


The following example apply to all indoor units expect for compact wall mounted type indoor unit.

9 8

0
Transmission line
(Non-polar 2 core)

9 8

9 8

10

0 0 0

10

0 1 1

9 8

10

0 2 0

9 8

10

0 3 0

9 8

9 8

10

10

0 5 1

0 4 0

9 8

10

9 8

0 14 0

10

0 15 0

2 Indoor units
(Max.4)
DSW 1 OFF
DSW 2 OFF
DSW 3 OFF

9 8

63

ON
ON
OFF

ON
OFF
ON

DSW 1 ON
DSW 2 OFF
DSW 3 OFF

2 Remote controller

9 8

10

63 0 0

9 8

10

63 1 0

9 8

10

63 2 0

9 8

10

63 3 1

9 8

9 8

10

63 4 2

10

63 5 0

9 8

10

63 6 0

9 8

10

63 7 0

INSTALLATION

DSW 1 ON
DSW 2 OFF
DSW 3 ON

00

01

02

03

04

Central remote controller (Max.16)

Outdoor unit

Indoor unit
Refrigerant
circuit address
Rotary-SW9,8

Refrigerant
circuit address
Rotary-SW9,8

9 8

63

9 8

10

63 6 0

Remote controller

DSW 1 OFF
DSW 2 OFF
DSW 3 OFF

Indoor unit address


Rotary-SW6

Remote controller address


Rotary-SW10

ON
ON
OFF

Dual remote controller switch1


Dual remote controller switch2
Group control setting

Central remote controller


00

Central remote controller address

Instructions for setting up the address


1 The Refrigerant circuit address of the indoor and outdoor units can be set to optional
numbers in the range of 0 to 99.
2 The Indoor unit address can be set to optional numbers in the range of 0 to 15.
3 Set the Remote controller address in the order of 0,1,2,3. (Blank is impossible)
4 The Central remote controller address can be set to optional numbers in the range of
0 to 15.

- (05 - 25) -

INSTALLATION

3 Indoor units

Refrigerant circuit address (Outdoor unit)


Refrigerant circuit address (Indoor unit)
Refrigerant circuit 1

Refrigerant circuit 2

1 00 0

1 01 1

1 02 2

2 00 0

Outdoor unit PCB (Address setting No.0

99)

2 01 1

2 02 2

Indoor unit PCB (Address setting No.0

Setting by rotary SW8,9

99)

Setting by rotary SW8,9

INSTALLATION

INSTALLATION

Indoor unit address


0

0 00 0

0 01 1

0 02 2

0 03 3

0 13 0

0 14 1

Indoor unit PCB (Address setting No. 0 15)


Rotary SW6, SW7 (Always set Rotary SW7 at 0)

Remote controller address (Indoor unit)

0 00 0

0 01 1

0 02 2

0 03 3

0 04 0

0 05 0

Indoor unit PCB (Address setting No.0 3)


Setting by rotary SW10

- (05 - 26) -

0 15 0

Remote controller switch 1


If 2 sets of wired remote controllers are connected to the remote control group,
turn the DIP SW 1-1 of Master Remote Controller off.

SW1-1 OFF ON

ON

[Master] [Slave]

[Master]

Remote controller unit PCB

When only 1 remote controller will connect,

Setting by DIP SW 1-1

this switch must be set ON.

INSTALLATION

INSTALLATION

Number of indoor unit connection

4
ON

2
ON

Remote controller PCB


Setting by DIP SW 1-2

- (05 - 27) -

1
OFF

Remote controller switch 2 (Remote controller)

OFF ON

OFF ON

[Master] [Slave]

[Master] [Slave]

Remote controller unit PCB


Setting by DIP SW 1 - 4

INSTALLATION

INSTALLATION

Central remote controller address

00

01

02

03

Central remote controller (Max. 16)

Set central remote controller address first, to conduct the initial setting of it.

- (05 - 28) -

5-4. FUNCTION SETTING


5-4-1. OUTDOOR UNIT
Outdoor unit

SW 2

SW 3

SW 4

DIP SW

SW 5

SW 7

SW 8
SW 9

ROTARY SW

Forbidden
Forbidden
Base heater validity / invalidity
Forbidden
Forbidden
Forbidden
Forbidden
Forbidden
System type switch 1
System type switch 2
Forbidden
Forbidden
Refrigeration circuit address 1
Refrigeration circuit address 2

SWITCH POSITION
Outdoor unit control circuit board
9

Rotary-SW

2 Dip- SW1

CN50CN49

CN48

CN22

CN5

INSTALLATION

SW 6

Test run(Cooling)
Test run(Heating)
Pump down operation
Forced defrost operation
Silent operation fan mode
Snow falling protection fan mode
EEV initialize
Forced oil recovery operation
Forbidden
Forbidden
Forbidden
Forbidden
Forbidden
Forbidden
Forbidden
Forbidden

INSTALLATION

1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4

SW 1

- (05 - 29) -

5-4-2. SWITCH FUNCTION (OUTDOOR UNIT)


DIP SWITCH SETTING

(1) SW1 setting


1-1 Test run ( cooling & Heating )
All the indoor units connected to the outdoor unit can be test-operated by DIP switch setting.
SELECTOR SWITCH FOR TEST RUN AND NORMAL OPERATION (
SW1-1

SW1-2

Test Run

Remarks

OFF

OFF

Normal operation

ON

OFF

Cooling test run

(OFF-ON) and (operated continuously


more than 1 min. with ON state)

OFF

ON

Heating test run

Same as above

ON

ON

Normal operation

(when release ON

1-2 Pump down operation


Pump down operation is set with SW1- 3
PUMP DOWN OPERATION (
SW1-3

Pump down operation

OFF

Release

ON

Operate

OFF)

Factory setting)
Remarks

(OFF-ON) and (operated continuously


more than 30 sec. with ON state)

1-3 Forced defrost operation


Forced oil recovery operation is set with SW1- 4
FORCED DEFROST OPERATION
SW1-4

Factory setting)

Forced defrost

OFF

Release

ON

Operate

Remarks

(OFF-ON) and (operated continuously


more than 30 sec. with ON state)

(2) SW2 setting


2-1 Silent operation mode
For a reduction of noise level at night, the operating mode of the outdoor unit can be switched.
(In the cooling mode only.)
SILENT OPERATION MODE

SW 2-1

Silent operation mode

OFF

Release

ON

Operate

Factory setting)

2-2 Snow falling protection fan mode


When snowing , to prevent the unit from being covered with snow, the outdoor fan is periodically
operated by this switch even when the compressor is stopped.
SNOW FALLING PROTECTION FAN MODE (
SW2-2

Snow falling protection fan mode

OFF

Release

ON

Operate

Factory setting)

- (05 - 30) -

INSTALLATION

INSTALLATION

Factory setting)

2-3 Expansion valve initialize


This switch initializes the number of pulses of the expansion valve when the outdoor unit is stopped.
ELECTRONIC EXPANSION VALVE INITIALIZATION
(
DIP SW2-3

Initialization

OFF

Release

ON

Operate

Factory setting)

2-4 Forced oil recoverry operation.


Oil recovery is started manually by DIP SW 2-4 on the PCB.
FORCED OIL RECOVERY
Factory setting)

DIP SW2-4

Forced oil recovery

OFF

Release

ON

Operate

(3). SW3 setting

INSTALLATION

INSTALLATION

Dip SW3-1,3-2,3-3,3-4 setting forbidden.

(4).SW4 setting
Dip SW4-1,4-2,4-3,4-4 setting forbidden.

(5). SW5 setting


5-1 Dip SW 5-1,5-2,5-4 setting forbidden
5-2 Base heater validity/invalidity
This switch sets the output of the base heater (CN5) on the PCB.
BASE HEATER SWITCH
(
DIP SW5-3

Factory setting)
Base heater

OFF

Invalidity

ON

validity

The base heater output turns ON at an outside temperature of 2 C or less


and during heating operation.
Base heater : available in the field 220-240V AC , 35W

- (05 - 31) -

(6) SW6 setting


DIP SW 6-1,6-2,6-3 and 6-4 setting forbidden
DIP SW6-1

OFF

DIP SW6-2

OFF

DIP SW6-3

OFF

DIP SW6-4

OFF

(7) SW7 setting (Never change at the site)


7-1 System type switch
The outdoor unit model can be selected by setting DIP switches 7-2 and 7-1 on the PCB.
(

OUTDOOR UNIT TYPE SELECTION

SW7-2

Type selection

OFF

OFF

Forbidden

ON

OFF

Forbidden

OFF

ON

Heat recovery

ON

ON

Forbidden

INSTALLATION

INSTALLATION

SW7-1

Factory setting)

7-2 Dip SW 7-3 & 7-4 setting forbidden


DIP SW7-3

OFF

DIP SW7-4

OFF

ROTARY SWITCH SETTING


SW8,9 setting
Rotary SW
8
9

Description
Refrigerant circuit
address SW 1
Refrigerant circuit
address SW 2

Remarks
Refrigerant circuit
address (the first digit)
Refrigerant circuit
address (the second digit)

EXTERNAL INPUT AND OUTPUT


Connector

Output

CN48

Error Display (DC12V)

- (05 - 32) -

5-4-3. INDOOR UNIT


Indoor unit
SW 1

SW 2
DIP SW
SW 3

INSTALLATION

SW 4

SW 5
SW 6
SW 7
Rotary SW SW 8
SW 9
SW 10

Ceiling height setting 1


Ceiling height setting 2
Room temp correct coefficient of heating 1
Room temp correct coefficient of heating 2
Room temp correct coefficient of cooling
Forbidden
Filter check validity / invalidity
Auto restart validity / invalidity
Forbidden(Indoor unit fan speed switch 1)
Forbidden(Indoor unit fan speed switch 2)
Forbidden(Indoor unit fan speed switch 3)
External input select edge / pulse
Forbidden(Indoor unit model code)
Forbidden(Indoor unit model code)
Forbidden(Indoor unit model code)
Forbidden(Indoor unit model code)
Wireless remote controller custom code switch 1
Wireless remote controller custom code switch 2
Forbidden
Draft prevention setting switch
Indoor unit address switch
Forbidden
Refrigerant circuit address 1
Refrigerant circuit address 2
Remote controller address

SWITCH POSITION
Indoor unit control circuit board
For AB / AU / AR type indoor unit

For AS / AW types indoor unit


CN24
CN23
CN22
CN21

CN24

SW10

CN27
CN22 CN23

SW1

SW9

SW8

SW2

SW3 SW4 SW5

SW6 SW4
SW8 SW10

SW6 SW7
SW1

SW9 SW5
SW7 SW3

SW2

- (05 - 33) -

INSTALLATION

1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4

5-4-4. SWITCH FUNCTION (INDOOR UNIT)


DIP SWITCH SETTING

(1) SW1 setting


1-1 Ceiling height setting
CEILING HEIGHT SETTING (CASSETTE TYPE)
SW1-1

SW1-2

Standard

OFF

OFF

2.5~3

High ceiling 1

ON

OFF

3~3.5

High ceiling 2

OFF

ON

more than 3.5

Low ceiling

ON

ON

less than 2.5

suitable ceiling height (m)

This function is validity only cassette type

1-2 Room temperature correct coefficient of heating.


Decide the heating temperature correct coefficient value of heating.
SW1-3

SW1-4

Coefficient value

OFF

OFF

+ 4 deg

ON

OFF

+ 8 deg

OFF

ON

0 deg

ON

ON

+ 12 deg

Factory setting)

INSTALLATION

INSTALLATION

HEATING TEMPERATURE CORRECTION (

(2) SW2 setting


2-1 Room temperature correct coefficient of cooling.
Decide the cooling temperature correct coefficient value of cooling.
COOLING TEMPERATURE CORRECTION (
SW2-1

Factory setting)

Coefficient value

OFF

0 deg

ON

+ 2 deg

2-2 Dip SW 2-2 setting forbidden


(

SW2-2

Factory setting)

OFF

2-3 Filter check validity / invalidity.


Filter check is set with Dip SW 2-3
FILTER CLEANING FUNCTION (
SW2-3

Filter check

OFF

Invalidity

ON

Validity

Factory setting)

- (05 - 34) -

2-4 Auto restart validity / invalidity.


Control the auto restart function by turning this switch ON/OFF.
AUTO RESTART SETTING (
SW2-4

Auto restart

OFF

Invalidity

ON

Validity

Factory setting)

SW3 setting (Never change at the site)


3-1 Indoor unit fan speed switch
This switch can select fan speed corresponding to each model.

Large ceiling type


AB30

AB36

AB45

AB54

SW3-1

OFF

OFF

OFF

OFF

SW3-2

OFF

ON

OFF

ON

SW3-3

OFF

OFF

ON

ON

AU54

AU45

AU36

AU30

AU25

AU20

SW3-1

OFF

ON

OFF

OFF

OFF

ON

SW3-2

OFF

OFF

ON

OFF

ON

ON

SW3-3

OFF

OFF

OFF

ON

ON

ON

AS18

AS24

AS30

SW3-1

OFF

OFF

ON

SW3-2

OFF

ON

ON

SW3-3

ON

ON

ON

AW7

AW9

AW12

AW14

AW18

AW24

AW30

SW3-1

OFF

ON

OFF

ON

OFF

OFF

ON

SW3-2

OFF

OFF

ON

ON

OFF

ON

ON

SW3-3

OFF

OFF

OFF

OFF

ON

ON

ON

INSTALLATION

INSTALLATION

Cassette type

Wall mounted type

Ceiling wall type

Other model (Default)


SW3-1

OFF

SW3-2

OFF

SW3-3

OFF

3-2 DIP SW 3-4 setting


This switch is used to select the format of external input command as shown in
the table below.
(

Factory setting)

SW3-4

External input select

OFF

Edge

ON

Pulse
- (05 - 35) -

(3) SW4 setting (Never change at the site)


Indoor unit model code.
This switch for changing the model code information of indoor unit PCB.
INDOOR UNIT MODEL CODE
Capacity

60

54

45

36

30

25(24)

20

18

14

12

SW4-1

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

ON

OFF

SW4-2

ON

ON

OFF

OFF

ON

ON

OFF

OFF

ON

ON

OFF

OFF

SW4-3

OFF

OFF

OFF

OFF

ON

ON

ON

ON

OFF

OFF

OFF

OFF

SW4-4

ON

ON

ON

ON

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

Type

(4) SW5 setting


5-1 Wireless remote controller custom code switch
Decid the custom code and restrict the type of infrared control signal, in order to prevent
mixing of multiple indoor unit signals.

Remote controller custom code switch


Factory setting)

SW5-1

SW5-2

Custom code

OFF

OFF

Type A

ON

OFF

Type B

OFF

ON

Type C

ON

ON

Type D

1. Press the MASTER CONTROL button for


more than five seconds to start the code
change.
2. Press the (+) or (-) button to select the
desired code.
A
B
C
D
3. Press the MASTER CONTROL button again
to end the code change.

5-2 DIP SW 5-3 setting forbidden


(

SW5-3

Factory setting)

OFF

5-3 Draft prevention setting switch (only for cassette type)


Set the flap angle of cassette type unit.

Draft prevention switch


(

Factory setting)

SW5-4

flap angle

OFF

Normal position

ON

Draft prevention position

Normal position

Flap angle
35 - 65

Draft prevention position

Flap angle
25 - 65

An air flow direction, by moving the flap angle horizontally,


It can prevent that a cold wind directly hits.
*If air conditioning cooling operation is performed in
long time and a humid place, there is a possibility
that waterdrop may hang down from a blow-off mouth.

- (05 - 36) -

INSTALLATION

INSTALLATION

ROTARY SWITCH SETTING


1.SW6 setting
Indoor unit address switch
Sets the indoor unit addresses.
(Factory setting : 0)

INDOOR UNIT ADDRESS SWITCH


Rotary SW

Description

Remarks

Indoor unit
address SW

Indoor unit address


( 0~15 )

2.SW7 setting forbidden


Rotary SW7

3.SW8,9 setting
Refrigerant circuit address switch
Sets the refrigerant circuit.
Rotary SW
8

INSTALLATION

Description

Remarks

Refrigerant circuit
address SW 1
Refrigerant circuit
address SW 2

Refrigerant circuit
address (the first digit)
Refrigerant circuit
address (the second digit)

4.SW10 setting
Remote controller address switch
When the indoor unit is wired by remote controller group, to identity the indoor unit in the remote
controller group, the number (remote controller address) in the remote controller group is set.
Set the remote controller address in the 0.1.2,~,15 order (Blank is not allowed)
REMOTE CONTROLLER ADDRESS SWITCH (Factory setting : 0)
Rotary SW
10

Description

Remarks

Remote controller
address SW

Remote controller
address

EXTERNAL INPUT AND OUTPUT


Connector

Indoor unit type

CN21

Wall mounted /
Ceiling wall types

CN27

Other types

Input

Output

Remarks

CONTROL INPUT
(OPERATION / STOP)

CN22

OPERATION DISPLAY
(DC12V)

CN23

ERROR DISPLAY
(DC12V)

All types

INDOOR UNIT FAN


STATUS DISPLY(DC12V)

CN24

- (05 - 37) -

See 5-5-1
for details

INSTALLATION

REFRIGERANT CIRCUIT ADDRESS SWITCH (Factory setting SW 8: 0 SW 9: 0)

5-4-5. WIRED, SIMPLE REMOTE CONTROLLER

Wired, simple remote controller

DIP SW

1
2

Dual remote controller setting

Group control setting

Model setting

5
6

Auto changeover setting


Memory backup setting (Wired remote controller only)

SWITCH POSITION
Wired remote controller
Front case (back side)

ON

INSTALLATION

INSTALLATION

OFF

1
2
3
4
5
6

DIP Switch

Simple remote controller

DIP switch

(UTB-YRA / UTB-GRA / UTB-TRA)

ON

OFF

OFF

1
2
3
4
5
6

ON

DIP switch

- (05 - 38) -

1
2
3
4
5
6

(UTB-YPB / UTB-GPB / UTB-TPB)

5-4-6. DIP-SW FUNCTION (WIRED,SIMPLE REMOTE CONTROLLER)


DIP SWITCH SETTING
(1) SW1 setting
1-1 Dual remote controller setting

Indoor unit

Set the remote controller DIP switch No.1 and 2


according to the following table.
(

Factory setting)

Master unit

When ground wire


is necessary

Slave unit

DIP-SW DIP-SW DIP-SW DIP-SW


No.1
No.2
No.1
No.2

1 (Normal)

ON

OFF

2 (Dual)

OFF

OFF

ON

ON

INSTALLATION

1 2 3

1 2 3

Master unit

Slave unit

Remote controller

1-2 Group control setting

Indoor unit 0

Number of indoor unit connection (One/Multiple)


This is switched according to the number of
connected indoor units.
(

Remote controller cable

1 2 3

Indoor unit 1

1 2 3

Indoor unit 2

1 2 3

Factory setting)

DIP-SW
No.3

Number of indoor unit

OFF

One unit connection

ON

Multiple unit connection

1 2 3
Remote
controller cable
Remote controller
When ground wire is necessary

1-3 Model setting


The system type of the outdoor unit can be selected by setting up DIP switch No.4 as follows.
(

Factory setting)

DIP-SW
No.4

Model

OFF

Heat Pump model or


Heat Recovery model

ON

Cooling only model

- (05 - 39) -

Indoor unit 3

1 2 3

INSTALLATION

Number of
remote
controller

1 2 3

1-4 Auto changeover setting


Selecting auto changeover validity / invalidity.
Set to OFF for AIRSTAGETM (VRF system) Heat Pump models.
(
DIP-SW
No.5

Factory setting)
Auto changeover

OFF

Invalidity

ON

Validity

1-5 Memory backup setting (Wired remote controller only)


Set to ON to use batteries for thr memory backup.
If batteries are not used, all of the settings stored
in memory will be deleted if there is a power failure.
(

Factory setting)

DIP-SW
No.6

Memory backup

OFF

Invalidity

ON

Validity

INSTALLATION

INSTALLATION

Never turn it ON in the case of simple remote controller.

- (05 - 40) -

5-4-7. GROUP REMOTE CONTROLLER


Group remote controller
DIP SW

Factory setting

Memory backup setting

OFF

Forbidden

OFF

SWITCH POSITION
Group remote controller
Front case (back side)

OFF

ON

1
2

ON

5-4-8. SWITCH FUNCTION (GROUP REMOTE CONTROLLER)


DIP SWITCH SETTING
(1) SW1 setting

Set SW1 to ON to enable the memory backup.


If there is a power failure when the memory backup is enabled, the setting stored in the memory will be saved.

. . . Factory setting)

SW1

Memory backup

OFF

Invalidity

ON

Validity

(2) SW2 setting : Forbidden

- (05 - 41) -

INSTALLATION

INSTALLATION

DIP switch

5-4-9. CENTRAL REMOTE CONTROLLER


Central remote controller

DIP-SW

SW 3

INSTALLATION

SW 42

External Input validity / invalidity


External Input select Edge / pulse
Filter sign indication ON / OFF
o

C / F switch
RC operation prohibit function validity / invalidity
Forbidden
Forbidden
SRAM battery ON / OFF
Forbidden
Forbidden
Forbidden
Forbidden
Initial setting
INSTALLATION

SW 2

1
2
3
4
5
6
7
8
1
2
3
4

SWITCH POSITION
Central remote controller

DIP SW2
SWITCH 42

DIP SW3

- (05 - 42) -

5-4-10. DIP-SW FUNCTION (CENTRAL REMOTE CONTROLLER)


DIP SWITCH SETTING
(1) DIP-SW2 SETTING
1-1 DIP SW2-1 setting.
For validity / invalidity the external input function.
(
SW2-1

Factory setting)

External input function

OFF

Invalidity

ON

Validity

1-2 DIP SW2-2 setting.


Select the external input command function.
(

Factory setting)

External input select

OFF

Edge

ON

Pulse

(Refer to 5-4-4 and 5-4-6 external input & output)


1-3 DIP SW2-3 setting.
Filter check sign indication or not when filter check signal come from indoor unit.
(
SW2-3

Factory setting)

Filter check sign indication

OFF

Non-Display

ON

Display

1-4 DIP SW2-4 setting.


C / F switch
Temperature display is centigrade( C ) / Fahrenheit( F )
(

Factory setting)

SW2-4

C/F

OFF

ON

1-5 DIP SW2-5 setting


For validity / invalidity the wired ,simple and wireless remote controller operation prohibit function.
Factory setting)

(
SW2-5

RC operation prohibit function

OFF

Validity

ON

Invalidity

- (05 - 43) -

INSTALLATION

INSTALLATION

SW2-2

1-6 DIP SW2-6 2-7 setting forbidden.


DIP SW 2-6

OFF

DIP SW 2-7

OFF

1-7 DIP SW2-8 setting.


SRAM Battery ON / OFF
When installing the central remote controller, this switch must be set to ON.
(factory setting : OFF)
(

Factory setting)

SW2-8

SRAM Battery

OFF

OFF

ON

ON

1-8 SW42 Initial setting button


This switch is used when initializing the central remote controller.

- (05 - 44) -

INSTALLATION

INSTALLATION

At the time of shipment, the battery is turned off to avoid electricity consumption.
Be sure to set this switch to ON.

5-5.EXTERNAL INPUT & OUTPUT


5-5-1. INDOOR UNIT
(1) Control input (Operation/Stop)
Indoor unit can be operated or stopped by using indoor unit PCB
CN 21 (Wall mounted type / ceiling wall type) or CN27 (other types)
Resistance < 500(ohm)
( Switch : ON )
Resistance > 100(Kilo-ohm) ( Switch : OFF )
A twisted-pair cable(AWG22) shoud be used maximum length of cable is 25m.

1 Input select
Input select

OFF

Edge

ON

Pulse

2 In the case of "Edge" input


CONNECTOR

INSTALLATION

Ch1 of
CN21*1) (RED)
or
CN27*2)(RED)

Ch 1

INPUT SIGNAL

COMMAND

OFF

ON

Operation

ON

OFF

Stop

Ch 2

NOTE
1. The last command has priority.
2. The indoor units within the same
remote controller group operates
in the same mode.
3.The wire connection shall be
separate from the power cable line.

On

Operation
Stop

3 In the case of "pulse" input


CONNECTOR

CN21*1) (RED)
or
CN27 *2)(RED)

INPUT SIGNAL

COMMAND

Ch1

OFF

ON

Operation

Ch2

OFF

ON

Stop

The width of pulse must be longer than 200ms.


On

Ch1
CN21 *1)
or
CN27 *2)

Off
On

Ch2

Off
Operation

Indoor
Unit

or

*1) For Wall mounted type / Ceiling wall type.


*2) For other types

Off

Remote
Controller

Indoor
Unit

CN 21(RED) *1)
CN 27(RED) *2)

On

Ch1 of
CN21 *1) or
CN27 *2)

1
2

Stop

- (05 - 45) -

INSTALLATION

Dip SW3-4

(2) Output
CONNECTOR OUT VOLTAGE
CN22

CN23

CN24

STATUS

12V

Operation

0V

Stop

12V

Error

0V

Normal

12V

Fan run

0V

Fan stop

1 Operation display
Indoor
unit
CN 22

Operation

+
Operation
Indicator

Stop

1
2

12V

CN 22
-

(WHITE)

0V

Indoor
unit
CN 23

Error

+
Error
Indicator

Normal

1
2

12V

CN 23
-

(WHITE)

0V

3 Inter locking output with indoor unit fan


Indoor
unit
CN 24

Fan run
Indoor unit
fan status
Indicator

Fan stop
12V
0V

EX) Used for inter lock energize for exhaust fan.

(3) Parts
Following cord (service parts) is required. Please use the parts number shown below
to order the cord from your sales representative.
Usage

Name and shapes

Q'ty

Parts No.

For output port

EXTERNAL
INPUT WIRE

9368778002

For control
input port

EXTERNAL
INPUT WIRE

9368779009

- (05 - 46) -

1
2

CN 24
-

(WHITE)

INSTALLATION

INSTALLATION

2 Error display

5-5-2. OUTDOOR UNIT


(1) Input
Not use

(2) Output
+

1 Error display
This output indicates the outdoor unit and connected indoor
unit's "Normal" or "Error" status.

CONNECTOR OUTPUT VOLTAGE

CN48
(BLACK)

Normal

12V

Error

P.C.B

CN 48
-

(BLACK)

Error

STATUS

0V

Error
Indicator

1
2

CN48

Normal
12V
0V

2 Base heater output

CN 5
(GREEN)

1
2

Base heater
(Field supply)
AC220 - 240V, 35W

3
4

(3) Parts
Following cord (service parts) is required. Please use the parts number shown below
to order the cord from your sales representative.
Name and shapes

Q'ty

Parts No.

BASE
HEATER
WIRE

9368776008

EXTERNAL
INPUT
WIRE

9368777005

- (05 - 47) -

INSTALLATION

INSTALLATION

Turn ON when the ambient temperature is low in heating mode.(2 C or less)

5-5-3. CENTRAL REMOTE CONTROLLER / PC CONTROLLER


(1) Input
1 Control input (All on / All off)
Indoor units which stored into Central R.C. or PC controller can be operated
or stopped by this input.
a) Input select

Central remote controller


DipSW2-1

DipSW2-2

Input select

ON

OFF

"Edge"

ON

ON

"Pulse"

PC controller

b) In the case of "Edge" input


INSTALLATION

CONNECTOR

CN9
(RED)

Ch1

Ch1

INPUT SIGNAL

COMMAND

OFF

ON

All ON

ON

OFF

All OFF

Ch2

1
2
3

CN9
(RED)

P.C.B
On

CN9
Ch1

Off

Indoor
Unit

All ON
All OFF

c) In the case of "Pulse" input


CONNECTOR

CN9
(RED)

INPUT SIGNAL

COMMAND

Ch1

OFF

ON

All ON

Ch2

OFF

ON

All OFF

The width of pulse must be longer than 300ms.


On

CN9
Ch1

Off
On

CN9
Ch2

Off
All ON

Indoor
Unit

All ON

- (05 - 48) -

INSTALLATION

Input select can be set in environmental set up.


(Please refer to PC Controller's setting manual.)

(2) Output
1 Operation display
This output indicates the indoor unit's "Operate" or "Stop" status.
OUTPUT
SIGNAL

CONNECTOR

CN1
(WHITE)

Ch1

STATUS

open

All of indoor units "OFF"

short

At least one more indoor units "ON"


1

Indoor
Unit
CN1
Ch1

ON

ON /OFF
Indicator

OFF
short

Error
Indicator

open

2
Ch1
Ch2

Com

1
2
3

CN1
(WHITE)

P.C.B
1

Necessary to insert a diode


on both ends of relay coil.
max 15V,70mA

2 Error display
This output indicates the indoor unit's "Normal" or "Error" status.
CONNECTOR

CN1
(WHITE)

Indoor
Unit
CN1
Ch2

Ch2

OUTPUT
SIGNAL

STATUS

open

All of indoor units "Normal"

short

At least one more indoor units "Error"

Error
Normal
short
open

(3) Parts
Following cord (service parts) is required. Please use the parts number shown below
to order the cord from your sales representative.
Name and shapes
EXTERNAL
INPUT
WIRE

Q'ty

Parts No.

9368779009

- (05 - 49) -

INSTALLATION

INSTALLATION

Pin1 - Pin3
Pin2 - Pin3

5-6. INSTALLATION WORK


5-6-1. INSTALLATION THE OUTDOOR UNIT
SELECTING THE MOUNTING POSITION
WARNING
Install the unit where it will not be tilted by more than 3 .
When installing the outdoor unit it may be exposed to strong wind, fasten it securely.

If possible, do not install the unit where it will be exposed to direct sunlight.
(If necessary ,install a blind that does not interfere with the air flow.
Install the outdoor unit in a location where it will avoid getting
dirty and getting wet from rain.

Installing the unit individually


10 mm or more

Install the unit where connection to the indoor unit is easy.


During heating operation, drain water flows from the outdoor unit.
Therefore, install the outdoor unit in a place where drain water
flow will not be obstructed. (Reverse cycle model only)
Front side

300 mm
or more

500 mm
or more

Take the air conditioner weight into account and select a


place where noise and vibration will be flow.
Select a location so that the warm exhaust air and noise
from the outdoor unit do not disturb neighbors.

10 mm or more

While the gap in the rear side requires at


least 300mm for inlet ventilation, but keep
an enough spacing by considering the
future servicing and constructions from
the rear.

Install inlet and outlet ducts in order to maintain stable


operation in cold or snowy regions.

If the wall height exceeds 1,200 mm, add dimension (h) to the
respective space dimensions L1 and L2.
H 1,200 : L1 500, L2 300
H > 1,200 : L1 > 500+h, L2 > 300+h

Front
air
intake

The dimensions shown above are minimum required limit to prevent a


decline in performance. The space provided should be increased in
consideration of passageways and room for maintenance.
Note: For the installation of multiple units and the duct connections, please refer to the section
3-5 INSTALLATION SPACE.

- (05 - 50) -

L2
h

Top blower
outlet

Rear
air
intake

H (1,200 mm or less)

The height of the wall (H) on the front side and rear side should be
1,200 mm or less.

L1
h

Provide the required space shown in Figure so that the air flow is
not blocked.

INSTALLATION

Do not place animals and plants in the path of the warm air.

H (1,200 mm or less)

INSTALLATION

Rear side

HOISTING METHOD

Weight
approx.300kg

Outdoor unit

If suspending the unit and conveying it to its installation


location, place the ropes under the bottom, using the four
cutouts places on the front and rear provided for
suspending it.
Protective boards

Use rope made of strong material enough to bear


the unit's weight.
Be sure to suspend the unit with ropes from 4 places
and be careful not to subject
it to impacts.
.
Place protective boards on the unit so the rope
doesn't make contact with the bell mouth.

INSTALLATION

Rope suspension area

The distance between the left and right anchor


bolts should be at least 850 mm.
Set the unit on a strong stand, such as concrete
blocks to minimize shock and vibration.
Do not set the unit directly on the ground
because it will cause problems.
When the outdoor unit will be exposed to strong
wind, fasten it strongly with anchor bolts.

- (05 - 51) -

1,300 mm
1,000 mm
850 mm

678 mm

ANCHOR BOLT POSITIONS

650 mm

INSTALLATION

Use 2 ropes which are 7 m in length or longer

5-6-2. INSTALLATION SPACE


UNIVERSAL / FLOOR CEILING TYPE

150mm
or more

300mm or more

300mm
or more

300mm or more

20mm or more

Ceiling panel

INSTALLATION

Ceiling
INDOOR UNIT

80 mm
or more

INDOOR UNIT

150 mm
or more

Ceiling

80 mm Ceiling panel
or more

150 mm
or more

10 mm
or more

10 mm
or more

COMPACT DUCT TYPE


Right side
(PIPE side)

Left
side
Left
Right
side Strong and durable ceiling side
Indoor unit

100 mm
or more

Inlet
air

300 mm
or more

Strong and
durable floor
100 mm
or more

- (05 - 52) -

300 mm
or more

30 mm
or more

30 mm
or more

INSTALLATION

LARGE CEILING TYPE

DUCT TYPE

HIGH PRESSURE DUCT TYPE


Strong and durable ceiling
INDOOR UNIT
Left
side

Right
side
AIR FLOW

150 mm
or more

150 mm or more

150 mm
or more

500 mm or more

COMPACT CASSETTE TYPE

INSTALLATION

245 mm
or more

1,000 mm
or more

1,000 mm
or more
Obstruction

CASSETTE TYPE
You can select 2-way setting

Strong and durable ceiling

(A) Standard setting

(B) Slender setting

235 mm

200 mm
or more

AU20 - 30

Obstruction

1,000 mm
or more

AU36 - 54

- (05 - 53) -

250 mm
or more

1,200 mm
or more

285 mm

INSTALLATION

Strong and durable ceiling

WALL MOUNTED TYPE

60 mm or over

Left side
50 mm
or over

Right side
200 mm
or over

1500 mm
or over

1500 to 2000 mm

CEILING WALL TYPE

CAUTION
1500 mm
or over

Ceiling protrusion
1500 to 2500 mm

- (05 - 54) -

If there is a section of the ceiling that protrudes, mount in a


position that allows for 40 mm
or more of space between the
unit and the protrusion.

INSTALLATION

Right side
200 mm
or over

40 mm or over

INSTALLATION

40 mm or over
Left side
50 mm
or over

CAUTION
WARNING
Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not topple or fall.

CAUTION
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near a source of heat, steam, or flammable gas.
If children under 10 years old may approach the unit, take preventive measures so that they
cannot reach the unit.

Decide the mounting position with the customer as follows:


Install the indoor unit on a strong wall which is not subject to vibration.

Do not install the unit where it will be exposed to direct sunlight.


Install the unit where the connection pipe can be easily installed.
Install the unit where the drain pipe can be easily installed.
Take servicing, etc. into consideration and leave the spaces.
Also install the unit where the filter can be removed.

- (05 - 55) -

INSTALLATION

INSTALLATION

The inlet and outlet ports should not be obstructed :the air should be able to blow all over the room.

5-6-3. PIPING CONNECTION


CAUTION
Use the designated size ( Diameter & thickness ) of refrigerant pipes
Those pipes purchased locally may contain dust inside.
Please blow out the dust by dried inert gas when using
Be careful to avoid the dust or water falling into the pipe when performing piping
process and piping installation.
When processing the pipe, make the number of bending portion as few as possible,
and the bending radius as large as possible.
To process the branch, do not use T-shaped pipe, which causes a uneven refrigerant
flow. Use the optionally available standard branch kit.

Separation Tube
(Standard parts)

If the diameter of the required pipe is different from the branch unit, either cut it out or
use the reducer.
Keep the permissible length of every piping limitation to prevent a defect or cooling/heating
failure.
When replacing the unit, never use piping which has been used for previous installations.
Only use the new piping.
While welding the pipes, be sure to blow dry nitrogen gas through them.

Pressure hose

Bello ws v alve

Nitr og en gas
Rubber stopper

Make sure to insulate the refrigeration pipes separately with ample thickness of
heat-resistant polyethylene form etc. For the connecting portion, apply the enough
insulation to avoid any gap.

- (05 - 56) -

INSTALLATION

INSTALLATION

T - tube

CAUTION
Welding
While welding the pipe, be sure to blow dry nitrogen gas through the pipes.
If not used, it will be caused to damage for compressor and clog the strainer and
Electronic Expansion Valve.
Example) Inside state of welding pipe section

Nitrogen Gas does not used

INSTALLATION

Nitrogen Gas used but not sufficient


(Oxygen gas still inside the pipe)

INSTALLATION

Nitrogen Gas used

- (05 - 57) -

OUTDOOR UNIT PIPE CONNECTION


Piping mounting direction (4-way mounting possible)
There are four possible ways to connect the piping to the outdoor unit.
Knockouts are provided all the place where the pipes need to be connected.

Rear piping

If the wild animals may get in the unit,


close up the space after the piping work.
(where opened the hole for connecting the pipe)

Bottom piping

If the piping is connected from the rear or bottom, be sure that there is
enough space around the unit to make connections.
When connecting the piping to the bottom of the unit,open a knockout
hole at the bottom of the unit.

75

(Unit: mm)

Knockout hole

210

30

36

INSTALLATION

INSTALLATION

Right piping

Front piping

- (05 - 58) -

Before connecting flange joint assembly to ball valve.


Remove bolts, valve plate and gasket.
ACCESSORY PARTS

Ball valve

Description Q'ty
Flange joint
assembly

Gasket
Valve plate

Washer

Gasket
(Accessory)*

Bolt (short)

Flange joint
assembly

Gasket

Washer

Connecting the flange joint pipe.

*Use the provided accessory parts.


Never use the other or used parts.
INSTALLATION

INSTALLATION

Bolt (long)

Bolt (long)
(Accessory)*

Torque wrench

Gasket (Accessorie)
Flange joint assembly

Flange joint pipe


Flare nut

Flare nut
Washer

Connection pipe

Leave the valve of Outdoor Unit fully close and do not operate until all the piping connections
are done and the pressure test and air vacuum have been successfully completed.

Flare nut tightening torque


Pipe

Tightening torque

Liquid pipe

500 to 550 kgf.cm (49 to 53.9 N.m)

Suction gas pipe (Bolt)

350 to 400 kgf.cm (34.3 to 39.2 N.m)

Discharge gas pipe

800 to 1000 kgf.cm (78.4 to 98 N.m)

Pipe diameter

Unit:mm

Suction gas

Discharge gas

28.58(1.2)

19.05(1.0)

Liquid
12.70(0.8)
( ):thickness

- (05 - 59) -

Bolt (long)
(Accessorie)

SEPARATION TUBE
Separation tube selection
Total capacity of
indoor units

Model name of separation tube to be used

Less than 60
61 or more

Heat recovery model

UTR-BP54MA
UTR-BP90MA

Outdoor unit or
Refrigerant branch kit

Indoor unit or
Refrigerant branch kit

Installation angle
Install the separation tube so that it branches either horizontally or vertically.

INSTALLATION

Vertical

INSTALLATION

Horizontal

30

Horizontal line

Installation
Use the pipe cutter to cut at the location which matches the piping size when the
piping size is different.

Pipe cutter

15 mm or more

stopper

After brazing the piping, attach heat insulation to the separation tube.
Remove the protective paper for the tape attached to the heat insulation for the separation tube.
Tighten by using binders in two locations.

Binder

- (05 - 60) -

Header installation
Caution
Separation after header is not allowed.
Header

Outdoor
unit

Header

Outdoor
unit

Indoor
unit
Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

Header selection
Number of branches
(Number of indoor units
connected)

Model name of header to be used


Cooling only model
Heat pump model

UTR-HD906R
UTR-HD908R

Piping connection
(1) When connecting the connection pipes from the indoor units, connect them to the header branch
pipes in the order 1, 2, 3, etc.
Gas pipe

Liquid pipe
1
2
3
4

Outdoor unit or
separation tube

Outdoor unit or
separation tube

4
6

(2) Use a pipe cutter to cut at the location that matches the piping size.
Be sure to cut the piping off at least 15 mm from the piping stopper
If the piping is cut too short, leaks can occur. After cutting the piping off, be sure to deburr it.
Make sure that dirt or water does not enter the piping when connecting the piping.
Pipe cutter

15 mm
or more

(3) Attach a plugging pipe provided if there is no piping connected at the headers.

Plugging pipe

- (05 - 61) -

INSTALLATION

INSTALLATION

6 units or less
7 to 8 units

Installation
Install the header so that it branches horizontally.
Use a level to make sure that the header is positioned as shown in following figure,
and then, secure it in place.
Liquid pipe

Gas pipe
A

Outdoor
unit side

Horizontal
line

Brazing
point

H1
1

VIEW A

Outdoor
unit side

Horizontal
line

Brazing
point
Vertical
line

H2

H 2= 0 mm ~ 10 mm

H1= 0 mm ~ 10 mm
Horizontal (
1 : 0 ~ 1)
line
1: -10 ~ 10

2
VIEW B

( 2 : 0 ~ 1)
2: -10 ~ 10

Heat insulation installation


After brazing the piping, attach heat insulation.
Remove the protective paper for the tape on the heat insulation for the header and attach it.
Tighten by using binders in five locations.
INSTALLATION

INSTALLATION

Binder

Cover the plugging pipe with heat insulation and seal with tape.

Tape

Plugging pipe
Heat insulation for header
Heat insulation for plugging pipe
Heat insulation for
plugging pipe

- (05 - 62) -

(Procure locally)

RB UNIT
RB unit selection
Number of branches
(Number of indoor units connected)

Model name of RB unit to be used

1 units

UTF-Y54A1A

1 to 4 units

UTF-Y90A4A

Selecting the mouhting position


(1) Install the RB unit on a place having a sufficient strength so that it withstands against
the weight of the RB unit.
(2) Leave the space required to service the RB unit.
(3) The ceiling rear height as shown below.
(4) Install the unit where noise and vibrations are not amplified.
UTF - Y54A1A

UTF - Y90A4A

100 mm or more
Strainer

Strainer
400 mm or more

400 mm or more

400 mm or more

100 mm
or more

Strainer

400 mm or more

Position the Hanging Bolt


UTF - Y54A1A

UTF - Y90A4A
Hanging bolt position 610 mm

Hanging bolt position


227 mm

- (05 - 63) -

INSTALLATION

INSTALLATION

Strainer

Connection pipe outline


UTF - Y54A1A

UTF - Y90A4A

Outdoor unit or
Refrigerant Branch Kit.

Suction
Gas pipe

Outdoor unit or
Refrigerant Branch Kit.
Suction
Gas pipe

Discharge
Gas pipe

Liquid
pipe
Discharge Gas
pipe

Liquid
pipe

RB unit

RB unit
Liquid pipe
Gas pipe

Gas
pipe

Indoor unit
Indoor
unit

Indoor
unit

Indoor
unit

Indoor
unit

RB unit pipe size

unit : mm

Suction
Gas pipe
Side of Outdoor unit

Discharge
Gas Pipe

19.05

Side of Indoor unit

15.88

UTF - Y90A4A
Suction
Gas pipe

Discharge
Gas Pipe

28.58

15.88

Liquid pipe

19.05

INSTALLATION

INSTALLATION

UTF - Y54A1A

12.70

15.88 x 4

9.52 x 4

Conection pipe size


UTF - Y54A1A

Outdoor
unit

Indoor
unit

Model code of
Indoor unit

Suction
Gas Pipe

Discharge
Gas Pipe

Less than 30

* 15.88

31 or more to 60

UTF - Y90A4A

unit : mm

19.05

12.70
15.88

Outdoor
unit

Model code of
Indoor unit

Suction
Gas Pipe

Discharge
Gas Pipe

Less than 30

* 15.88

19.05

15.88

28.58

19.05

9.52

61 or more

12, 14

12.70

7, 9

9.52

12, 14

12.70

15.88

36, 45, 54, 60

19.05

Indoor
unit

12.70

31 or more to 60

7, 9

18, 20, 24, 25, 30

unit : mm

18, 20, 24, 25

9.52
12.70

*
6.35

15.88

30
36, 45, 54, 60

Liquid
Pipe

19.05

9.52

If there is (*) shown, a reducer will be needed when connecting the piping.
As shown in the illustration below, flare the reducer provided or cut with a
pipe cutter at the location that matches the diameter
Pipe Cutter

Reducer

- (05 - 64) -

Installation
Procedure for connecting pipe
Make sure to install "strainer" as shown below.
Coupler heat
insulation
(large)

Strainer
(small) 4
Strainer

(small)
Cap
Strainer
(large)

Strainer
(large)

(large)

UTF - Y54A1A

Coupler
heat insulation
(large) 4

UTF - Y90A4A

If a reducer is used, flare it before connecting

Flare nut tightening torque

Strainer

Reducer
Reducer

Flare nut

Tightening torque

9.52 mm dia.

30.4 to 34.3 N . m
310 to 350 kgf . cm

12.70 mm dia.

49.0 to 53.9 N . m
500 to 550 kgf . cm

15.88 mm dia.

73.5 to 78.4 N . m
750 to 800 kgf . cm

19.05 mm dia.

78.4 to 98 N . m
800 to 1,000 kgf . cm

Electrical wiring
Pull the RB unit cord into the indoor unit control box and connect it to the connector (white) from the
circuit board.
The RB unit cord is 10 meters long. If the distance to the indoor unit exceeds the length of the RB cord,
procure a cord locally and extend the length. The specifications for the cord are as follows. The length
of the cord can be extended a maximum of 40 m.
Specifications: 4 core shielded cord 0.75 mm2 or more

RB unit cord

RB unit cord

RB unit cord
- (05 - 65) -

INSTALLATION

INSTALLATION

(small)

AIR TIGHT TEST


After the piping has been installed, perform a sealing test.
Charge the piping with nitrogen to within the sealing test pressure (2.94 MPa).
After 24 hours, check that the pressure has not fallen.
Make sure to add the pressure to both Gas pipe and Liquid pipe.
Perform the leak test on all flared and brazed parts.
Note: When the ambient temperature changes 5 deg. ,the test pressure changes 0.05MPa.

VACUUM PROCESS
CAUTION

Do not purge the air with refrigerant but use a vacuum pump to remove air from the indoor unit
and connection pipes!

Ball valve (Suction Gas)


Tightening torque
Ball valve
Spindle
(handle)
Cap

15 kgf cm (1.47 N m) or less


150 to 200 kgf cm
(14.7 to 19.6 N m)

Open valve state

Closed valve state

3 way valve
100 to 120 kgf cm
(9.8 to 11.7 N m)
200 to 250 kgf cm
(19.6 to 24.5 N m)

Ball valve (Discharge Gas)


Open valve state

Closed valve state

3 way valve
3 way valve
Spindle
Hexagon wrench
Open

Small pipe

Close

Large pipe
Charging valve
Middle pipe

Cap

- (05 - 66) -

If the spindle (handle) is not fully open,


performance will degrade and an abnormal
sound will be generated.

INSTALLATION

INSTALLATION

Remove the cap, and connect the gauge manifold and the vacuum pump to the charging
valve by the service hoses.
Vacuum the indoor unit and the connecting pipes until the pressure gauge indicates -76 cmHg.
When -76 cmHg is reached, operate the vacuum pump for at least 1 hour.
After vacuuming inside the indoor unit and connecting pipes,remove the cap of the three valves.
Open the handle (spindle) of the Large and middle valves(Ball valve).
Open the spindle of the Small valve(3 way valve) with a hexagon wrench.
Tighten the cap of the three valves to the specified torque.

ADDITIONAL CHARGE
Always add the refrigerant for the appropriate amount.
Refer the additional refrigent charge amount to item 5-1-4 "ADDITIONAL CHARGE
CALCULATION".
Either larger or smaller refrigerant charge amount leads to the cause of trouble.
For after service purpose , the added refrigerant charge amount and the calculation shall be
indicated firmily on the service label over the control box cover.

CAUTION

When moving and installing the air conditioner,do not mix gas other than the specified refrigerant inside the refrigerant circuit.
When chaging the refrigerant ,always use an electronic balance for refrigerant chaging
(to measure the refrigerant by weight).
Add refrigerant from the charging valve after the completion of the work.

INSTALLATION

INSTALLATION

The maximum length of the piping is 100 m (actual pipe length). If the units are further apart
than this, correct operation can not be guaranteed.

Pressure gauge

Refrigerant
container

Vacuum pump
.

- (05 - 67) -

Scale

Pressure reduction valve

Nitrogen

5-6-4. ELECTRICAL WIRING


Always perform the installation referring to the installation instruction sheet, based on your local
regions related laws and regurations,and electric company

WARNING
Before starting work, check that power is not being supplied to the outdoor unit.
Connect the connection cord firmly to the terminal board. Imperfect installation
may cause a fire.
Always fasten the outside covering of the connection cord with the cord clamp.
(If the insulator is chafed,electric leakage may occur.)
Always connect the ground wire.

Connect wiring to the terminals

Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
Shape the loop wire properly, place it on the terminal board and
tighten securely with the terminal screw using a screwdriver.

A. Solid wire
Loop

INSTALLATION

Using a screwdriver, remove the terminal screw(s) on the terminal board.

Strip 15/16"
(25 mm)

Cut the wire end with a wire cutter or wire-cutting pliers, then strip the
insulation to about 15/16"(25 mm) to expose the solid wire.

Insulation

B. For strand wiring


Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation
to about 3/8" (10 mm) to expose the strand wiring.
Using a scre wdriver, remove the terminal screw(s) on the terminal board.
Using a round terminal fastener or pliers, securely clamp a round terminal
to each stripped wire end.

Strip 3/8"
(10 mm)

INSTALLATION

A. For solid core wiring (or F-cable)

B. Strand wire
Round terminal

Position the round terminal wire, and replace and tighten the terminal screw
using a screwdriver.
Screw with
special washer

Screw with
special washer
Round
terminal

Wire

Round
terminal
Terminal
board

Wire
Terminal block

- (05 - 68) -

Fix the connection cord and power supply cord at the cord clamp
After passing the transmission cord and power supply cord through the
insulation tube, fasten it with the cord clamp.
Use VW-1,0.5 to 1.0mm thick, PVC tube as the insulation tube.

OUTDOOR UNIT

INSTALLATION

INSTALLATION

(1) Remove the front panel right.

Front panel right

(2) Remove control box metal cover and connect the power
supply cord and transmission cord.

Terminal board

Control box metal

Cord clamp

Control box metal cover


Cable crip

Insulation tube
Power supply cord Transmission cord

- (05 - 69) -

INDOOR UNIT

1 2 3 1 2 1 2
REMOTE TRANS POWER
CONTROL MISSION SUPPLY

Indoor unit wiring

Transmission
cord

1 2 3 1 2 1 2
REMOTE TRANS POWER
CONTROL MISSION SUPPLY

Power supply cord

RB unit cord

Remote control cord


Remote control unit
Refrigerant branch unit
(Heat recovery model only)
380-415 V 3

50Hz

T
N
POWER

220-240 V 1

50Hz

2 1
TRANSMISSION

Transmission
cord

CAUTION

Use care to wire properly. (Miss-wiring will result in damage.)


Never bundle the power supply cord, transmission cord and remote controller cord together.
Bundling these cords together will cause misoperation.
The total length of the transmission cord should not exceed 500 meters. Note that the total
length of the transmission cord can be extended to 2,000 meters if the optional signal amplifier
is used.
The power source capacity must be the sum of the air conditioner current and the current of other
electrical appliances.When the current contracted capacity is insufficient,change the contracted
capacity.

When the voltage is low and the air conditioner is difficult to start, contact the power company
to raise electrical voltage.
WARNING

[1 phase TYPE]
The rated voltage of this product is 220-240V A.C.50 Hz.
Before turning on verify that the voltage is within the 198 V to 264 V range.
[3 phase TYPE]
The rated voltage of this product is 380-415 V 3 50 Hz.
Before turning on verify that the voltage is within the 342 V to 457 V range.
Always use a special branch circuit and install a special receptacle to supply power to the air
conditioner.
Use a circuit breaker and receptacle matched to the capacity of the air conditioner.
Perform wiring work in accordance with standards so that the air conditioner can be operated
safely and positively.
Install a leakage circuit breaker in accordance with the related laws and regulations and electric
company standards.

- (05 - 70) -

INSTALLATION

INSTALLATION

Outdoor unit wiring


Power supply
cord

5-6-5. DRAIN PROCESSING


OUTDOOR UNIT
Please connect the hose when the processing of the drain water of the installation in the room
etc. is necessary by the following method.

Rear panel

Remove the rear panel.


Since the drain water flows out of the outdoor unit
during heating operation, install the drain pipe and
connect it to an commercial 16 mm hose.
(When heating the outdoor temperature is 0 C or
less, construct so that drain water from the outdoorunit will not freeze in the drain pipe.)

Knockout hole
Drain pipe mounting holes

Always use a drain pipe at three places.

Hose

Drain pipe

CAUTION
Drain water will leak from the bottom of outdoor unit during cooling / heating operation,even if the
drain pipe is connected.To prevent the area surrounding the outdoor unit from getting wet,install
a gutter surrounding the outdoor unit as shown in the figure below for drain water.
Outdoor unit

50mm or more

Gutter

10mm or more
Drain channel
(with gradient 1/100)

Gutter

- (05 - 71) -

INSTALLATION

Drain pan

INSTALLATION

Rear panel

INDOOR UNIT
NOTE : Install the drain pipe.
Install the drain pipe with downward gradient(1/50 to 1/100) and so there are
no rises or traps in the pipe.
Use general hard polyvinyl chloride pipe (VP25) and connect it with adhesive
(polyvinyl chloride) so that there is no leakage.
When the pipe is long, install supporters.
Do not perfrom air bleeding.
Always heat insulate the indoor side of the drain pipe.

UNIVERSAL FLOOR / CEILING TYPE


A.UNDER CEILING SETTING

B.FLOOR CONSOLE SETTING

Remove the hole cover.

NO

INSTALLATION

NO

INSTALLATION

OK

VT wire
hole

Base (bottom)

Drain hose
VT wire

Intake grille
Pass the drain hose
through here.

Cut the grille

Drain hose

*Do not install the unit so that the drain hose side
is too high.
Height A should be less than 5mm.

- (05 - 72) -

CEILING TYPE

Drain port : O.D

38mm

Drain pipe

Lifted up

GOOD

Arrange the drain pipe


lower than this portion.

BAD

Wave

BAD

End in water
Supporer
1.5 to 2 m
(5 to 6.5 ft)

(1) Install insulation for the drain pipe.


Cut the included insulation material to an appropriate size and adhere it to the pipe.
Drain pipe insulation
Drain pipe

Drain pipe

10 mm or more

No gap

VT wire

(2) If "1 Right rear piping" :fasten the drain pipe


with VT wire so that the pipe slopes correctly
within the indoor unit .

Drain hose

Indoor unit (rear view)

COMPACT DUCT TYPE

Drain port : O.D

26mm

B. FLOOR STANDING CONCEALED SETTING

A. CEILING CONCEALED SETTING


Outlet air
flow

Drain hose

OK
Arrange the drain hose
lower than this portion

Trap

NO

Rise
NO

Supporter
Air bleeding

OK

NO

NO

1.5 to 2 m
(5 to 6.5 ft)

CAUTION

Connect the drain hose so that the control box cover can easily be removed for servicing
when necessary.
In order to prevent water from leaking into the control box, make sure that the piping is
well insulated.
After finishing the piping, the drain hose installation and the wiring, seal the holes in the wall.

- (05 - 73) -

INSTALLATION

INSTALLATION

Indoor unit (drain port)

Indoor unit

Insulation for Drain pipe


(To be obtained locally.
Length should be at least 8 mm.)
Drain pipe insulation (accessories)

DUCT TYPE
Outlet
air
flow

Drain port : O.D

38mm
Trap

Drain
hose

OK

Rise

NO

NO

Arrange the drain hose


lower than this portion.
Supporter
Air bleeding

1.5 to 2 m
(5 to 6.5 ft)

The outside diameter of the drain port is 38 mm. Use a suitable drain hose.
There is a drain port on both the left and right sides. Select the drain port to match
the local conditions
Nylon fastener

INSTALLATION

Drain cap

INSTALLATION

Drain port

Drain hose

CAUTION

Always check that the drain cap is installed to the unused drain port and is fastened with the
nylon fastener. If the drain cap is not installed, or is not sufficiently fastened by the nylon
fastener, water may drip during the cooling operation.

HIGH PRESSURE DUCT TYPE


Outlet air
flow

Drain port : O.D

Rise

H2 H1

Drain hose H1 = 100 mm (approx.)


H2 = 50~100 mm
OK

38mm

NO
Supporter
Air bleeding

1.5 to 2 m

Install the drain hose so that there is a trap.


The position of the installed drain hose should have a downward gradient of (1/50 to 1/100).
Make sure that the drain hose is installed without rises.
Make the trap near to the indoor unit.

- (05 - 74) -

COMPACT CASSETTE TYPE

Drain port : O.D

32mm

Supporter

Rise
Trap
Air bleeding

150 mm (60'') or less

1.5 to 2 m
(5 to 6.5 ft)

Max. 400 mm
(15'')

When desiring a high drain pipe height, raise it up to 400 mm (15'') or less from the ceiling
within a range of 150 mm (6'') from the body.
A rise dimension over this range will cause leakage.

CASSETTE TYPE

Drain port : O.D

32mm

Rise
Trap
Air bleeding

150 mm (60'') or less

1.5 to 2 m
(5 to 6.5 ft)

Max. 800 mm
(31'')

When desiring a high drain pipe height, raise it up to 800 mm (31'') or less from the ceiling
within a range of 150 mm (6'') from the body.
A rise dimension over this range will cause leakage.

- (05 - 75) -

INSTALLATION

INSTALLATION

Supporter

WALL MOUNTED TYPE

Drain hose is attached.

Left side
Drain hose

Check the following:

Right side

GOOD
BAD
Drain hose

Drain cap
Drain hose

BAD

BAD

Drain cap

CEILING WALL TYPE

INSTALLATION

Lifted up
Saddle

Insert the drain hose until it


butts against the drain port.

Wave

End in water

Drain hose is attached.

Mount the drain hose to the drain


port on the right side.

Remove the drain cap and mount to the drain port on the right side.
Mount the drain hose to the drain port on the left side.

Left side

Left side

Drain hose

Right side

Right side
Drain hose

Drain cap

Drain hose
Drain hose
Insert the drain hose until it butts
against the drain port.

Drain cap
Insert the drain cap until it
butts against the drain port.

Check the following:


GOOD

Drain
hose

BAD

BAD

BAD

Saddle
Lifted up
Wave

End in water

- (05 - 76) -

Insert the drain hose until it


butts against the drain port.

INSTALLATION

Insert the drain cap until it


butts against the drain port.

DRAIN PIPE INSULATION


Please confirm water is injected into Drain pan of the indoor unit, and drain is done normally
when the connection of Drain hose is completed.
Please check whether there is water leak part in the Drain piping.
Please insulate it from heat by the heat insulator of enough thickness so that there is no be
dewy when the confirmation ends. It causes the water leak like being imperfect.
Drain hose
insulation

Drain hose
insulation
Unit
Unit

Drain hose insulation

Drain hose
insulation

INSTALLATION

INSTALLATION

Drain hose

0 mm

Drain hose

Unit

Unit

Drain cap

* Please roll the heat insulator also on the


Drain cap side.(some models)

0 mm

Outside
wall cap

Saddle

Sealer
putty

Wall

(Outdoors)

Pipe

* Please cover the space with the putty etc. when


you put out Drain hose from the wall.

CENTRAL DRAIN PROCESSING


When converging multiple drain pipes , install according to the procedure shown below.

Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.
- (05 - 77) -

5-6-6. SYSTEM & FUNCTION SETTING


All of the models require to perform ADDRESS SETTING.
Proceed the set-up referring to 5-3, 5-4 without fail.
If necessary, set up the function setting consulting with the user.
Be sure to record the set-up address etc. for after service purpose.
System setting
Address setting
Function setting

5-6-7. TEST RUN


TEST RUN METHOD
The procedures for performing the test run are desribed below.
(Supply power for at least 12 hours before starting operation in the winter.)
(1) Perform a test run (cooling) separately for each indoor unit that is connected to the
refrigerant system,and check the operation in order to confirm there is no problem on
the wiring connection and the address.

Test operation using circuit board (Outdoor unit)


If the test operation is to be done for cooling operation, set DIP switch (SW1-1) to on. If the test
operation is to be done for heating, set DIP switch (SW1-2) to on.

Test operation using remote controller


Refer to the installation instruction sheet for the indoor unit.

CHECK LIST
Check item

Checking Method

Standard

After operating the indoor unit,


the compressor operates?

Check operation sound and


the LED of outdoor unit PCB.

Outdoor unit LED 3 :flushing

High pressure and low pressure


are normal?

Confirm with a pressure gauge

Cooling : Low pressure 0.4 MPa (approx.)


Heating : High pressure 2.0 MPa (approx.)

Intake and outlet air Temperature


of indoor unit are normal?

Check that there is a difference


between the intake and outlet air
temperatures.

Cooling : Below -10 C (approx.)


Heating : Above 15 C (approx.)

Water is drained from drain hose


or by the drain pump smoothly?
(Only for cooling mode)

Expansion valve of the stopped


indoor unit are normal?

Check operation sound of the


drain pump.
Confirm water is draining.
Check the refrigerant flows to the
heat exchanger.(Wait at least 5
minutes after the indoor unit has
stopped before checking the
refrigerant.)

- (05 - 78) -

Cooling : No refrigerant flow


Heating : A little refrigerant flow

INSTALLATION

INSTALLATION

(2)Perform a test run (cooling) simultaneously for all indoor units are connected to the
refrigerant system,and check the operation in order to confirm all installation is completed.

5-7. COMPATIBILITY
COMPATIBILITY OF EQUIPMENT

1. OUTDOOR UNIT AND INDOOR UNIT


Compatibility table between Indoor unit and Outdoor unit
Indoor unit

Model change code

Outdoor
unit

Heat recovery type

A (20002005)
B (2005)

Heat pump type


Cooling only type

B (2002)
C (2005)

All model

Except for AS7-14

AS7-14

A or B
(20002002)

C
(2002)

C (20022004)
D (2005)

( "A", "B", "C" ,"D" : MODEL CHANGE CODE )

Ex.1)

OUTDOOR UNIT

INSTALLATION

A or B
B or C

Heat recovry

INDOOR UNIT

Heat pump/Cooling only

A or B

B or C

Model change code

Model change code

Wired remote
controller

Ex.2)

Simple remote
controller

Wireless remote
controller

Heat recovery type

A or B

Heat pump/
Cooling only type
B or C

Compact wall mounted type indoor unit (AS7 - 14) can't be operated
by Heat recovery type outdoor unit.
In case of making remote controller group, refer to next page.

- (05 - 79) -

INSTALLATION

Heat recovery type


or
Heat pump/Cooling only type

2. Remote controller and remote controller group


Compatibility table
Combination of
remote controller
Combination of
Indoor unit

1 Wired
remote
controller

1 Simple
remote
controller

1 Wireless
remote
controller

COMBINATION OF
2 REMOTE
CONTROLLERS

"A" "B"

Indoor unit

"C"
"A" & "A"
"A" & "B"
"B" & "B"
"C" & "C"
"C" & "D"
"D" & "D"
"A" or "B"
&
"C" or "D"

Remote controller
group
(Combination of
indoor unit)

See table below


(Remote controller
compatibility table)

Remote controller compatibility table

UTB- UB
UTB- UA
INSTALLATION

UTB- LB

UTB- LA

* 2)

UTB- UB
Wired

* 2)

Wireless * 1)
UTB- VB
UTB- VA
UTB- SA

Simple
UTB- PA
UTB- PB
UTB- RA

, UTB- UA

UTB- LB

UTB- LA

Wireless UTB- VB, UTB- VA, UTB- SA


Simple

UTB- PA, UTB- PB, UTB- RA

* 1) AS7 - AS14 are only available for wireless remote controller.


* 2) Build-in thermo sensor doesn't work in S series system.

Ex.)

[ Remote controller group ]


Combined "A" & "C" indoor unit

[ 2 Remote controllers ]
Combined Wired(UTB- LA) + Simple
remote controllers(UTB- PA)

INDOOR UNIT

C
MODEL CHANGE
CODE

WIRED
REMOTE
CONTROLLER

SIMPLE
REMOTE
CONTROLLER

WIRELESS
REMOTE
CONTROLLER

- (05 - 80) -

[ 2 Remote controllers ]
Combined Wired(UTB- LB) + Simple
remote controllers(UTB- PA)

INSTALLATION

Wired

5-8. STANDARD ACCESSORIES


5-8-1. OUTDOOR UNIT
AO90MPBMF (Heat recovery type)
The following installation parts are supplied. Use them as required.
Description

Q'ty

Flange joint
assembly

Application

Description

For connecting the piping

Drain pipe

Q'ty
3

Gasket
1

Installation between
flange joint assembly and
valve B

Hexagon
wrench

For opening the refrigerant


valve on the outdoor unit

For fixing the flange joint


assembly

INSTALLATION

Bolt

For outdoor side pipe


joint

INSTALLATION

For outdoor unit drain


piping work (Reverse
cycle model only)
For connecting the piping

Auxiliary pipe assembly


Coupler heat
insulation

Application

- (05 - 81) -

5-8-2. INDOOR UNIT


UNIVERSAL FLOOR CEILING TYPE
Q'ty

Application

Description
Tapping screw
(4 x 20)

Cover plate (left)


1
Cover plate (right)

Coupler heat insulation


(large)

1
Tapping screw
(4 x 10)

Installation
template

Bracket (left)
1
INSTALLATION

Coupler heat insulation


(small)

For positioning the indoor


unit
For under ceiling type

Nylon fastener

For suspending the


indoor unit from ceiling

For fixing the wall bracket


6

For fixing the coupler


heat insulation
Large 2 (This part is enclosed
with the 12,000 and
14,000 BTU/h)

1
Insulation (drain hose)

Adhesive type 70 x 230


1

Spring washer

VT wire
4

Special nut
4

For suspending the


indoor unit on the wall

OPTIONAL PARTS FOR INDOOR UNIT


Part No.

Joint pipe-A
9302812021

For indoor side pipe joint


(small pipe)

Drain hose

Anchor bolt (M12)

For indoor side pipe joint


(large pipe)

For power supply,


Small 2 transmission and remote
control cord binding

Wall bracket

Application

Medium 1 For fixing the drain hose

Bracket (right)

Description

Q'ty

Application
For indoor side pipe joint
(18,000 and 24,000 BTU/h
model)

- (05 - 82) -

For fixing the drain hose


L 280 mm

INSTALLATION

Description

LARGE CEILING TYPE


Description

Q'ty

Drain hose insulation

Description

Application

Special nut A
(large flange)

Adhesive type 70 x 230


1

VT wire
1

Coupler heat insulation


(large)

Coupler heat insulation


(small)

Nylon fastener

For fixing the drain hose


L 280 mm

For indoor side pipe joint


(large pipe)

For indoor side pipe joint


(small pipe)

Special nut B
(small flange)

Installation
template

Q'ty

Application
For installing indoor unit

For installing indoor unit


4

Auxiliary pipe

For positioning the indoor


unit

For connecting the piping


1

Large For fixing the coupler


heat insulation
4
Medium
4

COMPACT DUCT TYPE


Name and Shape
Installation
template

Q'ty

Hanger
4

Tapping screw
(4 x 10)

Special nut A
(large flange)

Special nut B
(small flange)

Coupler
heat insulation
(large)

Application

Name and Shape

For positioning the indoor


unit

Coupler
heat insulation
(small)

For suspending the


indoor unit from ceiling

Binder

Filter

For suspending the


indoor unit from ceiling

For indoor side pipe joint


(small pipe)

For power supply,


Small transmission and remote
2
control cord binding.

AR7, AR9

AR12, AR14, AR18

Insulates the drain hose


and vinyl hose connection

Drain hose insulation

Application

Large For fixing the coupler


4
heat insulation

For installing the hanger

Q'ty

For indoor side pipe joint


(large pipe)

- (05 - 83) -

INSTALLATION

INSTALLATION

For power supply,


Small
transmission and remote
2
control cord binding

DUCT TYPE
Name and Shape
Installation
template

Q'ty
1

Hanger
4

Special nut A
(large flange)

Special nut B
(small flange)

Name and Shape

Application
For positioning the indoor
unit

For suspending the


indoor unit from ceiling

Coupler heat
insulation
(small)

Nylon fastener

Q'ty

For power supply,


Small
transmission and remote
2
control cord binding

For suspending the


indoor unit from ceiling
Auxiliary pipe

For pipe connection


(gas side)

For indoor side pipe joint


(large pipe)

Insulates the drain hose


and vinyl hose connection

INSTALLATION

INSTALLATION

For indoor side pipe joint


(small pipe)

Large For fixing the drain hose


1

Drain hose insulation


Coupler heat
insulation (large)

Application

DUCT TYPE (HIGH PRESSURE)


Name and Shape
Installation
template

Special nut A
(large flange)

Q'ty

Application

Name and Shape

For positioning the indoor


unit

Nylon fastener

Q'ty

Application

Large For fixing the drain hose


1
For power supply,
Small
transmission and remote
2
control cord binding

For suspending the


indoor unit from ceiling

Auxiliary pipe

For pipe connection


(gas side)
1

Special nut B
(small flange)

Coupler heat
insulation (large)

Drain hose insulation


1

For indoor side pipe joint


(large pipe)
Drain pipe insulation

1
Coupler heat
insulation
(small)

For indoor side pipe joint


(small pipe)

- (05 - 84) -

Insulates the drain hose


and drain hose connection

For insulating the drain


pipe

COMPACT CASSETTE TYPE


Indoor unit accessories
Name and Shape
Coupler heat
insulation

Special nut A
(large flange)

Special nut B
(small flange)

Q'ty

Grille accessories
Application

Name and Shape

For indoor side pipe joint

Q'ty

Bolt

Application
For mounting grille

For installing indoor unit

Washer

For mounting grille


4

For installing indoor unit

For discharged air

Blower cover insulation

2
For ceiling hole cutting

Template
1

INSTALLATION

For power supply,


transmission and remote
control cord binding

INSTALLATION

Binder

CASSETTE TYPE
Name and Shape
Coupler heat
insulation

Special nut A
(large flange)

Special nut B
(small flange)

Q'ty

Application

Name and Shape

For indoor side pipe joint

Template

Application
For ceiling hole cutting

1
For installing indoor unit

Blower cover insulation

For discharged air


2

For installing indoor unit


4

Q'ty

Hook wire

For installing intake grille


2

Binder
2

- (05 - 85) -

For power supply,


transmission and remote
control cord binding

WALL MOUNTED TYPE


Name and Shape

Q'ty

Use

Name and Shape


Tapping screw (big)
(4 x 20)

Wall hook bracket


1

For indoor unit installation

Q'ty

12

Binder
Wire assembly
1

EMI FILTER
(ZCAT1518-0730)

For wired remote controller installation

Use
For wall hook bracket
installation

For wire assembly


binding

For wire assembly


installation

Name and Shape

Q'ty

Use

Name and Shape


Tapping screw (big)
(4 x 20)

Wall hook bracket


1

For indoor unit installation

Q'ty

12

Binder
Wire assembly
1

EMI FILTER
(ZCAT1518-0730)

For wired remote controller installation

For wire assembly


installation

- (05 - 86) -

Use
For wall hook bracket
installation

For wire assembly


binding

INSTALLATION

INSTALLATION

CEILING WALL TYPE

5-9. REFRIGERANT LEAKAGE CAUTION


The installer and system specialist shall secure safety against leakage according to local
regulations or standards. The following standards may be applicable if local regulations
are not available.

5-9-1. INTRODUCTION
Almost all our VRF type air conditioners use R22 or R407C as refrigerant. Though R22 and
R407C are harmless and incombustible in themselves, the room in which the air conditioner
is installed should be large enough that the refrigerant gas will not exceed the concentration
limit even if the refrigerant gas leaks.

Concentration limit
Concentration limit is the limit of Freon gas concentration where immediate measures
can be taken without hurting the human body when refrigerant leaks in to the air. The
concentration limit shall be described in units of Kg/m3 (Freon gas weight in /m3 air) to
facilite calculation.
(R22),0.31kg/m 3 (R407C) (ISO5149,prEN378-1)

Concentration limit : 0.3kg/m 3

(No.1 system)

Flow of
refrigerant

Room where refrigerant leaks


(Refrigerant of the whole No.1
system flows out.)

Indoor unit

5-9-2. CHECKING CONCENTRATION LIMIT


Check concentration limit following steps 1 ~ 2 , and take appropriate measures depending
on the situation.
1

Calculate amount of all replenished refrigerant (kg)


per refrigerant system.
Amount of replenished refrigerant
per refrigerant system

Amount of replenished refrigerant


at factory shipment
2

Calculate minimum room capacity.


Calculate room capacity by regarding

Amount of additional
replenished refrigerant

Total amount of replenished


= refrigerant in refrigerant facility
(kg)

Amount of additionally replenished


refrigerant depending on piping length ,
piping diameter and indoorunit model
at customer.
portion as one room or the smallest room.

Note : When one refrigerant facility is divided


into 2 or more refrigerant systems and
each system is Independent, total amount
of replenished refrigerant of each system
shall be adopted.

(a) Without partition


Outdoor unit

Outdoor unit

Indoor unit

Indoor unit

Opening
Partition

- (05 - 87) -

In the case of opening


without door, or 0.15
% or more openings
(to floor space) both
above and below door)

INSTALLATION

INSTALLATION

Outdoor unit

Outdoor unit

(b) With partition and without opening which serve as


passage of air to adjoining room.

Indoor unit

smallest
room

3 Calculate refrigerant concentration from the results of 1 and 2

When the result of calculation exceeds


the limiting concentration,perform the
=Refrigerant concentration(kg/m3 )
same calculations by shifting to the
second smallest,and the third smallest
(R22 or R407C)
rooms until the final result is below the
limiting concentration.

Total amount of replenished refrigerant


in refrigerant facility(kg)
Capacity of smallest room where
Indoor unit is installed(m3 )

When concentration limit is exceeded

Countermeasure 1
Provide opening for ventilation.
Provide 0.15% or more opening to floor space both above and below or provide opening without door.
Countermeasure 2
Provide gas leak alarm linked with mechanical ventilator.
Gas leak alarm
Countermeasure 2
Mechanical ventilator

Indoor unit

Countermeasure 1 Opening effective to ventilation

Pay special attention to the place, such as a basement, etc. When refrigerant can accummalate,
since refrigerant is heavier than air.

- (05 - 88) -

INSTALLATION

INSTALLATION

When the concentration limit is exceeded,change the original plan or take one of the countermeasures
shown below.

R407C

TM

SERIES

6 . TROUBLE SHOOTING

6-1 TROUBLE SHOOTING


6-1-1 OUTDOOR UNIT
NORMAL OPERATING MODE
LED 1

Display type

LED 2 LED 3

Cooling operation
Heating operation
Cooling main operation
Heating main operation
Same performance operation

LED 4

LED 5

LED 6

(1)
(2)
(3)
(4)
(5)

Compressor output STEP 1


Compressor output STEP 2
Compressor output STEP 3
Compressor output STEP 4
Compressor output STEP 5
Compressor output STEP 6
Heat exchanger usage capacity STEP 1
Heat exchanger usage capacity STEP 2
Heat exchanger usage capacity STEP 3
Heat exchanger usage capacity STEP 4
Heat exchanger usage capacity STEP 5
Heat exchanger usage capacity STEP 6
Oil recovery
Defrosting
Test operation

(1)
(2)
(3)
(4)
(5)
(6)
(1)
(2)
(3)
(4)
(5)
(6)
(1)
(2)
(3)

Medium pressure
Low pressure by-pass
High pressure
Low pressure by-pass

(1)
(2)

Display Method

TROUBLE
SHOOTING

TROUBLE
SHOOTING

Under initialization of expansion valve


: Lighted continuously
: 0.5sec ON/0.5sec OFF flashing
( ) : Flashing times

Operation display

Outdoor printed circuit board layouts

ON
LED 1
LED 4
LED 5

OFF
0.5SEC
0.5SEC

IC

2SEC

LED 6

ON
LED 2-6
OFF

- (06 - 01) -

LED 1
LED 2
LED 3

ABNORMAL MODE
Display type

LED 1 LED 2 LED 3 LED 4 LED 5 LED 6


(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)

Discharge temperature thermistor1 error


Discharge temperature thermistor2 error
Discharge temperature thermistor3 error
Heat exchanger outlet thermistor1 error
Heat exchanger outlet thermistor2 error
Heat exchanger outlet thermistor3 error
Heat exchanger inlet thermistor1 error
Heat exchanger inlet thermistor2 error
Heat exchanger inlet thermistor3 error
Suction thermistor error
Outdoor thermistor error
Discharge pressure sensor error
Liquid pressure sensor error
Suction pressure sensor error
Oil sensor error
Oil recovery error
Reverse phase blocker error
Reverse phase blocker error
Power supply frequency faulty
Model information error
EEPROM access error
EEPROM deletion error
Outdoor unit circuit bord error 1
Outdoor unit circuit bord error 2
Outdoor unit circuit bord error 2
Transmission error
Node setting error
Indoor unit error

Display method

(1)
(2)
(3)
(4)
(7)
(1)
(2)

TROUBLE
SHOOTING

TROUBLE
SHOOTING

Compressor1 error
Compressor2 error
Compressor3 error
Discharge temprature1 error
Discharge temprature2 error
Discharge temprature3 error
High-pressure error
Low-pressure error
Pump down error

(3)
(4)
(6)
(7)
(8)
(9)
(1)

: 0.1 sec ON / 0.1 sec OFF flashing


: 0.3 sec ON / 0.3 sec OFF flashing
( ) : Flashing times

Error display
0.1SEC
0.3SEC

ON
0.1 sec
ON/OFF
repeated

LED 1
OFF

ON

LED 2 - 6
OFF

0.1SEC

- (06 - 02) -

2SEC
0.3SEC

6-1-2. INDOOR UNIT


Error display

0.1sec
ON/OFF

3 times
flashing

0.1 sec
ON/OFF
0.1 sec
ON/OFF
0.1 sec
ON/OFF
0.1 sec
ON/OFF

3 times
flashing

VERTICAL
SWING lamp

Error contents

HORIZONTAL
SWING lamp
Goes off

Model information abnormal

0.1 sec
ON/OFF

Power supply frequency abnormal

Goes off

Room temperature thermistor error

1 times
flashing

Goes off

Indoor unit heat exchanger thermistor (inlet) error

0.1 sec
ON/OFF

2 times
flashing

Goes off

Indoor unit heat exchanger thermistor (middle) error

3 times
flashing

0.1 sec
ON/OFF

3 times
flashing

Goes off

Indoor unit heat exchanger thermistor (outlet) error

4 times
flashing

0.1 sec
ON/OFF

Goes off

Drain abnormal

5 times
flashing

0.1 sec
ON/OFF

1 times
flashing

Goes off

Communication error 1
Wired / Simple remote controller)
(indoor unit

5 times
flashing

0.1 sec
ON/OFF

2 times
flashing

Goes off

Microcomputer error

5 times
flashing

0.1 sec
ON/OFF

4 times
flashing

Goes off

Communication error 2
Wired / Simple remote controller)
(indoor unit

6 times
flashing

0.1 sec
ON/OFF

Goes off

Indoor unit fan error

7 times
flashing

0.1 sec
ON/OFF

Goes off

Blower temperature thermistor error

0.1 sec
ON/OFF

3 times
flashing

3 times
flashing

Goes off

Outdoor unit error

0.1 sec
ON/OFF

4 times
flashing

Goes off

EEPROM access error

0.1 sec
ON/OFF
0.1 sec
ON/OFF
0.1 sec
ON/OFF
0.1 sec
ON/OFF
0.1 sec
ON/OFF

4 times
flashing
5 times
flashing
5 times
flashing
6 times
flashing

1 times
flashing
2 times
flashing

Goes off

EEPROM deletion error

1 times
flashing

Goes off

Transmission error

2 times
flashing

Goes off

Node setting error

Goes off

Parallel communication error

Goes off

Room temperature abnormal

0.1sec
ON/OFF
2 times
flashing

TROUBLE
SHOOTING

TIMER
lamp

7 times
flashing

0.1 sec
ON/OFF

- (06 - 03) -

TROUBLE
SHOOTING

OPERATION
lamp

6-1-3. WIRED,SIMPLE REMOTE CONTROLLER

TROUBLE
SHOOTING

E : 00

No error

E : 02

Model information abnormal

E : 04

Power supply frequency abnormal

E : 06

EEPROM access error

E : 07

EEPROM deletion error

E : 09

Room temperature thermistor error

E : 0A

Indoor unit heat exchanger thermistor (middle) error

E : 0b

Indoor unit heat exchanger thermistor (inlet) error

E : 0C

Indoor unit heat exchanger thermistor (outlet) error

E : 0d

Blower temperature thermistor error

E : 11

Drain abnormal

E : 12

Room temperature abnormal

E : 13

indoor unit fan error

E : 1F

Transmission error

E : 20

Node setting error

E : 21

Parallel communication error

E : 32

Outdoor unit error

- (06 - 04) -

TROUBLE
SHOOTING

Error contents

Error cord

6-1-4. GROUP REMOTE CONTROLLER


GROUP REMOTE CONTROLLER
Indoor unit error

Outdoor unit error

Group remote controller error


Convertor error

00
01

No error

No error

No error

02
03

Model information abnormal


Microcomputer communication error

Model information abnormal


Microcomputer communication error

Microcomputer communication error

04
05

Power supply frequency abnormal

Power supply frequency abnormal

06
07

EEPROM access error


EEPROM deletion error

EEPROM access error


EEPROM deletion error

Parallel communication error


EEPROM access error

08
09

Compressor 1 error

Room temperature thermistor error

0A
0b

Compressor 2 error
Compressor 3 error

Heat exchanger thermistor (middle) error


Heat exchanger thermistor (inlet) error

0C
0d

Discharge temperature thermistor 1 error

Heat exchanger thermistor (outlet) error


Blower temperature thermistor error

0E
0F

Discharge temperature thermistor 2 error


Discharge temperature thermistor 3 error

10
11

Outdoor temperature thermistor error


Heat exchanger inlet thermistor 1 error

Drain abnormal

12
13

Heat exchanger inlet thermistor 2 error


Heat exchanger inlet thermistor 3 error

Room temperature abnormal


Indoor unit fan error

14
15

Heat exchanger outlet thermistor 1 error


Heat exchanger outlet thermistor 2 error

16
17

Heat exchanger outlet thermistor 3 error


Suction temperature thermistor error

18
19

Discharge pressure sensor error

1A
1b

Liquid pressure sensor error


Suction pressure sensor error

Address setting error

1C
1d

Oil sensor error

Connection error
System error

Standard wired remote control communication error

1E
1F

Transmission error

20
21

Discharge temperature 1 error

22
23

Discharge temperature 2 error


Discharge temperature 3 error

24
25

High-pressure error
Low-pressure error

26
27

Oil recovery error

28

Pump down error

Transmission error

- (06 - 05) -

Transmission error

TROUBLE
SHOOTING

TROUBLE
SHOOTING

Err or
Code

NETWORK CONVERTOR
Error code

Error contents
No error (operation mode)
Initial setting
Circuit board error 1
Circuit board error 2
Transmission error with wired RC
Transmission error with indoor unit *1
Transmission error with VRF system
Software error
Indoor or outdoor unit error *1

*1 Displayed only when used as a single split type network convertor.

D129
SW104

SW101

SW102

CN109

SW107 SW108 SW109 SW103


CN108
CN105
SW110

SW111

SW105

- (06 - 06) -

TROUBLE
SHOOTING

TROUBLE
SHOOTING

Circuit board and LED layouts

6-1-5. CENTRAL REMOTE CONTROLLER / PC CONTROLLER

00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0F
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D
1E
1F
20
21
22
23
24
25
26
27
28

Indoor unit error


No error

Outdoor unit error

Central remote controller

No error

No error

Model information abnormal

Model information error

Printed circuit board error (Control panel)

Microcomputer communication error

Microcomputer communication error

Printed circuit board error (Transmission adaptor)

Power supply frequency abnormal

Power supply frequency abnormal

Memory error

Reverse phase blocker error

Node setting error

EEPROM access error

EEPROM access error

Parallel communication error

EEPROM deletion error

Room temperature thermistor error

Compressor 1 error

Heat exchanger thermistor (middle) error

Compressor 2 error

Heat exchanger thermistor (inlet) error

Compressor 3 error

Heat exchanger thermistor (outlet) error

Blower temperature thermistor error

Discharge temperature thermistor 1 error

Discharge temperature thermistor 2 error

Discharge temperature thermistor 3 error

Outdoor temperature thermistor error

Drain abnormal

Heat exchanger inlet thermistor 1 error

Room temperature abnormal

Heat exchanger inlet thermistor 2 error

Indoor unit fan error

Heat exchanger inlet thermistor 3 error

Heat exchanger outlet thermistor 1 error

Heat exchanger outlet thermistor 2 error

Heat exchanger outlet thermistor 3 error

Suction thermistor error

Standard wired remote controller communication error 1,2

Discharge pressure sensor error

Liquid pressure sensor error

Suction pressure sensor error

Connection error

Initial setting error

Manual storing 2 error

Transmission error

Transmission error

Transmission error

Discharge temperature 1 error

Software error (Output)

Discharge temperature 2 error

Software error (Input)

Discharge temperature 3 error

High-pressure error

Low-pressure error

Pump down error

- (06 - 07) -

TROUBLE
SHOOTING

TROUBLE
SHOOTING

Error
Code

6-1-6. CASES SUCH AS THESE ARE NORMAL


OPERATION NOT TROUBLE
From the standpoint of control, the following operations are incorporated for air conditioner
operation and protection. They do not indicate trouble.

Red and green lamps flash


alternately, or simultaneously.

Red lamp flashes.

Indoor unit fan does not operate


even through the RUN signal has
entered.

Operation is stopped and refrigerant is passed through


the indoor unit to remove the outdoor unit frost
(defrosting operation) or to recover the refrigerant oil
(oil recovery operation). The indoor unit stops in about
5-10 minutes.
The fan is stopped to prevent blowing out of cold air
when the machine is still not warm at the start of
heating operation. About 3 minutes are necessary.

Indoor unit
The red and green lamps flash
alternately in the operation stop
state.

Remote indication

The red and green lamps flash


simultaneously in the operation
state.

TEST

The fan stops and the refrigerant


passes through. The red lamp
flashes slowly.

DEFROST

The fan stops and the red lamp


lights steadily.

Fan turns on/off periodically.

When the room temperature at heating operation reaches


the set temperature, the FAN is stopped and room
temperature rise is prevented. At this time, the fan is
operated periodically to detect the room temperature.
(4 minutes stop, 1minute operate)

The fan continues to operate and


the red lamp lights steadily.

Remote controller airflow indication


flashes.

This is the filter cleaning time. After cleaning the filter,


press the ZONE/SET key for a few seconds to be
released .

Same as normal.

Airflow indication
flashes

Heating operation is performed


when stopped.

Anti-freeze operation is set so that the water pipe and


electronic devices do not freeze. Operation starts at
room temperature 5 C or less and continues until the
room temperature reaches 8 C or more.

At standby, the red lamp flashes


and the fan continues to operate.
At operation, the heating operation
is performed.

ANTIFREEZE

When operation is inhibited during central control by


central remote controller, the buzzer that denies the
wireless remote controller signals sounds.

Buzzer buzzes 5 times and setting


is not received. Operation before
setting continues.

CENTRAL

When an [AUTO], [FAN] and an operation other than the


operation another indoor unit is already performing at
cooling/heating selection type or [HEAT] operation at a
cooling only unit is commanded, operation cannot be
performed at that setting.

Buzzer buzzes 5 times and setting


is not received. Operation before
setting continues.

RUN signal is input, but is not


accepted. Buzzer sounds.

TROUBLE
SHOOTING

Description
Indicates that the power came on normally when power
was applied (at power failure recovery). Indication is
cleared by RUN command.
When test run is performed, the unit operates
without regard to the temperature setting. Stopped by
remote controller stop. or reset after 60 minutes.

Timer setting cannot be performed by wireless remote


controller at an indoor unit with wired remote controller
connected. Set the timer from the wired remote
controller.
The valve opens to return the refrigerant collected
inside the indoor unit to the outdoor unit even after
Makes a sound even after operation
operation stops. Remains for about 4 minutes maximum.
stops.
After cooling operation stops, the drain pump is
operated. Remains for 3 minutes.

Makes a sound
while operating.

Flowing liquid
sound during
operation

A sound changed by the refrigerant flow may be made


by operation of another indoor unit connected to the
same outdoor unit. A switching sound may be made at
the start and after the end of defrosting operation and
oil recovery operation.

Squeaking sound

This is due to expansion and contraction of resin parts


by the temperature change during heating operation
and oil recovery operation.

Switching sound

A sound is generated when the internal valve is


switched at operation switching and at the start
of defrosting operation and oil recovery operation.

Buzzer buzzes 5 times and setting


is not received. Operation before
setting continues.

When operation and indication other than the above occurs, call the manager.

- (06 - 08) -

TROUBLE
SHOOTING

Operation

R407C

TM

SERIES

7 . OPTIONAL PARTS

7-1 RB (REFRIGERANT BRANCH) UNIT


UTF-Y90A4A

Top side

12.70

12.70

Possible to connect 4 unit max.


Possible to connect from either of right and left and install flexibly.
(however,impossible to connect behind the RB unit.)
(Connect this unit with the attached reducer according to a pipe diameter of the indoor unit.)

Description

Q'ty

Application

Description

Strainer (Large)

Reducer

Q'ty

For connecting the piping

6.35(I.D.)

Application

4
9.52

Special nut A
(large flange)

Reducer

19.05(I.D.)

For connecting the piping

OPTIONAL
PARTS

Special nut B
(small flange)

For installing RB unit


2

For installing RB unit


2

15.88

Reducer

For connecting the piping

12.7 0(I.D.)
15.88 (I.D.)

Coupler heat
insulation

small
1

19.05

Reducer

For connecting the piping

9.52 (I.D.)

12.7 0(I.D.)

4
15.88

Reducer

19.05(I.D.)

For connecting the piping


1

28.58

Reducer

For connecting the piping

9.52 (I.D.)

Large
5

1
12.70

- (07 - 01) -

For pipe joint

OPTIONAL
PARTS

Strainer (Small)

UTF-Y54A1A

(Connect this unit with the attached reducer according to a pipe diameter of the indoor unit.)
Description

Q'ty

Description

Application

Special nut A
(large flange)

Strainer
2
19.05(I.D.)

Reducer

Q'ty

Application
For installing RB unit

For connecting the piping


Special nut B
(small flange)

For installing RB unit


2

15.88

Reducer

For connecting the piping

12.7 0(I.D.)

Coupler heat
insulation

15.88 (I.D.)

Large
2
small
1

19.05

Reducer

For pipe joint

For connecting the piping

9.52 (I.D.)

12.70(I.D.)

SPECIFICATION
Model

UTF - Y54A1A

Power supply

Power supply from indoor unit by using attached cable


1

4 max.

mm

160 x 180 x 220

200 x 560 x 280

Weight (kg)

kg

Liquid pipe

mm

Gas pipe

mm

Liquid pipe

mm

Number of connectable indoor units


Dimension(HxWxD) (mm)

to indoor unit

to outdoor unit Dischrage Gas pipe


Suction Gas pipe
Max Length
Max Height
difference

UTF - Y90A4A

22
9.52 (flare)

15.88 (flare)

15.88 (flare)
12.70 (flare)

mm

15.88 (flare)

19.05 (flare)

mm

19.05 (flare)

28.58 (Blazing)

RB unit - indoor unit

40

RB unit - indoor unit

RB unit - RB unit

15

Standard Accessories

Strainer,Reducer,Special nut, Coupler heat insulation,


Connection Cable(10m),Installtion Instruction Sheet

- (07 - 02) -

OPTIONAL
PARTS

OPTIONAL
PARTS

15.88

7-2 SEPARATION TUBE


UTR - BP90MA
+

SEPARATION
TUBE
SUCTION GAS
PIPE side

Q'ty 1

. +
+

SEPARATION
TUBE
DISCHARGE GAS
PIPE side

+
15.88

Q'ty 1

+
+

SEPARATION
TUBE
LIQUID PIPE side

OPTIONAL
PARTS

SEPARATION TUBE INSULATION


SUCTION GAS PIPE side

Q'ty 1

BINDER

SEPARATION TUBE INSULATION


DISCHARGE GAS PIPE side

Q'ty 1

Q'ty 6

- (07 - 03) -

SEPARATION TUBE INSULATION


LIQUID PIPE side

Q'ty 1

OPTIONAL
PARTS

Q'ty 1

UTR - BP54MA

SEPARATION
TUBE
+

SUCTION GAS
PIPE side
DISCHARGE GAS
PIPE side

Q'ty 2

15.88

Note) This SEPARATION TUBE can be used for both SUCTION GAS PIPE and DISCHARGE GAS PIPE side.
Be careful not to make a mistake of pipe connection.

SEPARATION
TUBE
LIQUID PIPE side

+
+

Q'ty 1

SEPARATION TUBE INSULATION


SUCTION GAS PIPE side
DISCHARGE GAS PIPE side

SEPARATION TUBE INSULATION

OPTIONAL
PARTS

OPTIONAL
PARTS

LIQUID PIPE side

Q'ty 2

BINDER

Q'ty 1

Q'ty 6

- (07 - 04) -

7-3 HEADER
UTR - HD908R

BRANCH
HEADER A
Q'ty 1

BRANCH
HEADER B
Q'ty 1

BRANCH
HEADER C
Q'ty 1

HEADER INSULATION- A

REDUCER I

Q'ty 1

Q'ty 2

REDUCER F

Q'ty 8

REDUCER J

Q'ty 2

HEADER INSULATION- B

Q'ty 1

Q'ty 1

CLOSED PIPE B

Q'ty 1

CLOSED PIPE C

Q'ty 2

HEADER INSULATION- C
CLOSED PIPE E

Q'ty 1
Q'ty 1

- (07 - 05) -

CLOSED PIPE INSULATION

OPTIONAL
PARTS

OPTIONAL
PARTS

CLOSED PIPE A

UTR - HD906R

BRANCH
HEADER D

Q'ty 1

BRANCH
HEADER E

Q'ty 1

BRANCH
HEADER F

HEADER INSULATION D

OPTIONAL
PARTS

Q'ty 1

REDUCER I

REDUCER F

REDUCER J

Q'ty 4

Q'ty 6

Q'ty 1

HEADER INSULATION E
CLOSED PIPE A

Q'ty 3

CLOSED PIPE C

Q'ty 7

Q'ty 1
HEADER INSULATION F
CLOSED PIPE INSULATION

Q'ty 1

- (07 - 06) -

CLOSED PIPE E

Q'ty 4

OPTIONAL
PARTS

Q'ty 1

7-4. CONTROLLER
WIRED REMOTE CONTROLLER

SIMPLE REMOTE CONTROLLER

UTB-YUB
UTB-GUB
UTB-TUB

On/Off weekly timer


Double auto swing louver

WIRELESS REMOTE CONTROLLER

UTB-YPB
UTB-GPB
UTB-TPB

UTB-YRA
UTB-GRA
UTB-TRA

With MASTER
control button

Without MASTER
control button

Background light
Easy operation

CENTRAL REMOTE CONTROLLER


UTB-YCA
UTB-GCA

UTB-YVB
UTB-GVB

ALL
ON

OPTIONAL
PARTS

GROUP REMOTE CONTROLLER


UTB-YDB
UTB-GDB

UTR-YOTB

ALL

Maximum 400 groups/400


indoor units can be controlled.
Monitoring state of operation

32 indoor units can be controlled.


With weekly timer

- (07 - 07) -

OPTIONAL
PARTS

Up to 64 groups/400 indoor units


can be controlled.
With weekly timer

On/Off sleep timer


Double auto swing louver

PC CONTROLLER [SOFTWARE]

OFF

7-5. ADAPTOR / CONVERTOR


NETWORK CONVERTOR

NETWORK CONVERTOR
UTR-YLLA

UTR-YRDA

(SPLIT SYSTEM CONVERTOR)


(GROUP REMOTE CONVERTOR)

(LON / LON CONVERTOR)

SIGNAL AMPLIFIER

BACnet Gateway [SOFTWARE]


UTR-YLBA

UTR-YRPC

CD-ROM
Software Protection key

TRANSMISSION ADAPTOR

EXTERNAL SWITCH CONTROLLER

UTR-YTMA

UTR-YESA

- (07 - 08) -

OPTIONAL
PARTS

OPTIONAL
PARTS

(VRF / BMS CONVERTOR)

7-6. OTHERS
FLANGE (round)

Model : UTDSF045T
For duct type

Model : UTDRF204
For duct type

17

17

206

17

1,0
3.5

93
17

3.5
17

1,0

10
103

17

63

7.5
97

40

4
17

20

234

21 164 21

20

17

(Unit : mm)

205

10

195

7.5

FLANGE (square)

22

235

4
17

85

32 - 5 holes

17

4
17

4
97

FLEXIBLE DUCT

OUTLET CHAMBER

Model : UTD-RD202
For duct / high static pressure duct type

Model : UTD-BC200
For high static pressure duct type

200 mm L 2 m
85

1,0

20

66

Model : UTD-LF270
For duct type

Model : UTD-LF400
For high static pressure duct type
27

.6

7.6

294.6

10

10

59

56

59

56

- (07 - 09) -

OPTIONAL
PARTS

297
0

40

204.6

OPTIONAL
PARTS

19

LONG-LIFE FILTER

IR RECEIVER UNIT
Model : UTB-YWA

REMOTE SENSOR UNIT


Model : UTD-RS100

DRAIN WATER RISER KIT


Model : UTR-DPB241
For large ceiling type

Model : UTG-UDYD-W
UTG-UDGD-W
For compact cassette type

OPTIONAL
PARTS

OPTIONAL
PARTS

GRILLE KIT

- (07 - 10) -

TM

SERIES

1116, Suenaga, Takatsu-ku, Kawasaki 213-8502, Japan

Product specifications are subject to change without notice.

"

TM

" is a worldwide trademark of FUJITSU GENERAL LIMITED.

Copyright 2002 Fujitsu General Limited. All rights reserved.

Printed in Japan 2006.03.20


VD001E/07

Вам также может понравиться