Table A
Item
1.
Parameters
Units of measurement
Colour
Turbidity
NTU
15.0
2.
4.0
(including suspended solids)
Odour
3.
Dilution number
Unobjectionable
Dilution number
Unobjectionable
Taste
100 (minimum)
mg/l
1000 (maximum)
6.
Calcium Hardness *
mg/l as CaCO3
200 at 25 C
7.
Total Hardness *
mg/l as CaCO3
300 at 25C
8.
0.0 (minimum)
0.5 (maximum)
7.0 (minimum)
9.
Hydrogen Ion
pH value
9.2 (maximum)
0.2 (minimum)
10.
mg/l Cl2
0.5 (maximum)
Document
ED/R01/001
Version
0
Page 21 of 52
Publication date
17 July 2013
Approved by
NC
Remarks:
i.
The Total Dissolved Solids (TDS) shall be measured using the Guide to TDS calculation
which is the Summation Method (Anions and cations) measured according to the
Standard Method at a frequency specified in the Guide for the TDS Calculations to
establish k factor. The k factor is the Ratio adopted in determining the TDS from the
measurement of Electric Conductivity in mhos/cm. Where the TDS (by summation
method) = k x EC in mg/l. Where K can be only is in the range of 0.55 to 0.8
ii.
Residual chlorine ideal concentration shall be between 0.2 to 0.5 mg/l however it may
increase to 1.00mg/l or even above in situations where the Licensed Supplier or the
Transmission System Operator request it in accordance with the Water Transmission
Code or for the purpose of controlling possible bacteriological contamination.
iii.
*Produced water minimum limit for Calcium Hardness, Total Hardness, Calcium content
Hydrogen Bicarbonate Contents (HCO3) and maximum limit for TDS (<200mg/l), shall be
according to the water quality exit specification composition requirements of the relevant
Plants to ensure meeting the remineralisation limits in the water desalination processes.
Document
ED/R01/001
Version
0
Page 22 of 52
Publication date
17 July 2013
Approved by
NC
Table B
Item
Parameters
Units of measurement
1.
Sulphate
mg SO4 /l
250
2.
Magnesium
mg Mg/l
30.0
3.
Sodium
mg Na/l
150
4.
Potassium
mg K/l
12.0
5.
Chlorides
mg Cl/l
250
6.
Nitrate
mg NO3/l
50.0
7.
Nitrite
mg NO2/l
3.0
mg NH4/l
0.5
mg C/l
1.0
Ammonium
8.
(ammonia and ammonium ions)
10.
Aluminium
mg Al/l
0.2
11.
Iron
mg Fe/l
0.2
12.
Copper
mg Cu/l
1.0
13.
Zinc
mg Zn/l
5.0
14.
Phosphorus
mg P/l
2.2
Document
ED/R01/001
Version
0
Page 23 of 52
Publication date
17 July 2013
Approved by
NC
Remarks:
i.
The normally observed value of TOC in the network is < 1 mg C/l during the normal
operation and < 2 mg C/l in newly commissioned or repaired systems. Any increase over
these values requires further investigation
Table C
Item
Parameters
1.
Arsenic
2.
Cadmium
3.
Chromium
4.
Mercury
5.
Nickel
6.
Lead
7.
Antimony
8.
Selenium
9.
Barium
10.
Boron
11.
Manganese
12.
Fluoride
Units of measurement
As g/l
10.0
Cd g/l
3.0
Cr g/l
50.0
Hg g/l
3.0
Ni g/l
70.0
Pb g/l
10.0
Sb g/l
20.0
Se g/l
40.0
Ba g/l
700
B g/l
2400
Mn g/l
400
F g/l
1500
Document
ED/R01/001
Version
0
Page 24 of 52
Publication date
17 July 2013
Approved by
NC
Table D
Item
1.
Parameters
Units of measurement
Endrine
0.6
g /l
g /l
2.
2.0
Lindane
g /l
3.
Methoxychlor
4.
5.
20.0
g /l
30.0
g /l
9.0
g /l
6.
0.5
Phenols
g /l
7.
0.03
Heptachlor
g /l
8.
0.03
Aldrin
g /l
9.
DDT
10.
Chlordane
1.0
g /l
0.2
g /l
11.
0.03
Dieldrin
g /l
12.
0.03
Heptachlor epoxide
g /l
13.
70.0
Cyanide
g /l
14.
0.5
Document
ED/R01/001
Version
0
Page 25 of 52
Publication date
17 July 2013
Approved by
NC
Remarks:
i.
Total Pesticides means the sum of all individual pesticides detected and quantified in
the monitoring procedure. Those pesticides can be from the list of individual Parameters
in the table above or outside it. Form of Pesticides can be, but not limited to organic
insecticides, herbicides and fungicides.
Table E
Item
Parameters
Units of measurement
20.0
1.
2.
Trichloroethene
Tetrachloroethene
4.
1,2 Dichloroethane
5.
Benzene
7.
8.
9.
g /l
3.0
g /l
40.0
g /l
30.0
g /l
10.0
g /l
0.7
g /l
20.0
g /l
300
g /l
50.0
g /l
700
g /l
1000
g /l
300
g /l
0.3
Tetrachloromethane
3.
6.
g /l
Benzo(a)pyrene
Dichloromethane
Chlorobenzene
1,2-Dichloroethene
Toluene
10.
11.
1,2-Dichlorobenzene
12.
1,4-Dichlorobenzene
13.
Vinyl Chloride
Document
ED/R01/001
Version
0
Page 26 of 52
Publication date
17 July 2013
Approved by
NC
Table F
Item
Parameters
Units of measurement
1.
Total coliforms
Number/100ml
2.
Number/100ml
3.
Enterococci
Number/100 ml
4.
Number/1 ml at 37C
10 at 37 C
Remarks:
a) Immediate action must be taken if either E.Coli or Total coliform bacteria are detected.
b) Legionella, Pseudomonas aeruginosa and Sulphite reducing bacteria testing needs to be
conducted randomly in the in the distribution network as an indicator for detecting
possible contamination or where observations associated with taste, odour and colour
problems. Target should be Zero organism.
c) Drinking water shall be free at all times from algae, mould, parasites, insects and their
eggs, larvae, protozoa including Amebo.
d) Total Bacterial Count limit shown above is an indicator for disinfection efficiency and the
risk of potential contamination; hence Suppliers shall take immediate remedial measures
where significant increase over that normally observed levels is detected which is 100 at
37 C or above.
Document
ED/R01/001
Version
0
Page 27 of 52
Publication date
17 July 2013
Approved by
NC
Table G
Item
1.
2.
Parameters
Units of measurement
Gross
Bq/l
0.5
Gross
Bq/l
Remarks:
Initial screening for gross / or gross activity to determine whether the activity concentrations
are below levels at which no further action is required. If initial screening levels exceed the above
then investigation and monitoring of individual radionuclide should follow immediately. The limits
for the individual radionuclide should be in accordance with guidance level (WHO Water Quality
Guidelines) as follows:
Item
Parameters
Units of Measurement
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
Uranium-238
Uranium-234
Thorium-230
Radium-226
Lead-210
Polonium-210
Thorium-232
Radium-228
Thorium-228
Caesium-134
Caesium-137
Strontium-90
Iodine-131
Tritium
Carbon-14
Plutonium-239
Americium-241
Bq/l
Bq/l
Bq/l
Bq/l
Bq/l
Bq/l
Bq/l
Bq/l
Bq/l
Bq/l
Bq/l
Bq/l
Bq/l
Bq/l
Bq/l
Bq/l
Bq/l
Concentration or
Value
10
1
1
1
0.1
0.1
1
0.1
1
10
10
10
10
10000
100
1
1
Document
ED/R01/001
Version
0
Page 28 of 52
Publication date
17 July 2013
Approved by
NC
Document
ED/R01/001
Version
0
Page 29 of 52
Publication date
17 July 2013
Approved by
NC
Table H
Item
Parameters
Units of measurement
Bromate (i)
mg/l
0.01
Chlorate
mg/l
0.7
3.
Chlorite
mg/l
0.7
4.
Bromoform
mg/l
0.1
5.
Bromodichloromethane (BDCM)
mg/l
0.06
6.
Chloroform
mg/l
0.3
7.
Dibromochloromethane (DBCM)
mg/l
0.1
8.
THMs (ii)
1.
2.
Remarks:
i.
Licensed Suppliers shall target to maintain at all times the bromide ion concentration to
less than 0.05 mg/l and sample according to the same sampling frequency as Bromate.
------------------PCV Bromoform
C DBCM
C BDCM
--------------- +
--------------
PCV DBCM
PCV BDCM
C Chloroform
+
-----------------PVC Chloroform
Document
ED/R01/001
Version
0
Page 30 of 52
Publication date
17 July 2013
Approved by
NC