Вы находитесь на странице: 1из 43

S. K. Ghosh Associates Inc.

FREQUENTLY MISUNDERSTOOD
IBC/ASCE 7 STRUCTURAL PROVISIONS

All sections
referenced
are from
ASCE 7-05,
unless
otherwise
noted.

S. K. Ghosh and Susan Dowty


S. K. Ghosh Associates Inc.
Palatine, IL and Aliso Viejo, CA

www.skghoshassociates.com

PROVISION
#1

Enclosure Classification
For Wind Design

Internal Pressure

Enclosure Classification
Section 6.2 Definitions

Open
 Partially

Enclosed (can experience

ballooning or suction effects caused by the


build-up of internal pressure)

 Enclosed

www.skghoshassociates.com
1

S. K. Ghosh Associates Inc.

Enclosure Classification
Section 6.2 Definitions

Enclosure Classification
Section 6.2 Definitions

OPEN
A building having each wall at least 80% open.

Ao 0.8 Ag
for EACH side of the building
AO = A1 + A2 + A3

Enclosure Classification
Section 6.2 Definitions

Ag = H W

Enclosure Classification
Section 6.2 Definitions

Do stacks of hay
obstruct flow of wind?

Enclosure Classification
Section 6.2 Definitions

Enclosure Classification
Section 6.2 Definitions

PARTIALLY ENCLOSED

Ao = total area of openings in a wall that receives


positive external pressure

1.Ao 1.10Aoi

Aoi = sum of the areas of openings in the building


envelope (walls and roof) not including Ao

2.Ao > 4 sq ft AND > 0.01Ag

Ag = gross area of that wall in which Ao is


identified

3. Aoi/Agi 0.20

Agi = the sum of the gross surface areas of the


building envelope not including Ag

www.skghoshassociates.com
2

S. K. Ghosh Associates Inc.

Enclosure Classification
Section 6.2 Definitions

Enclosure Classification
Section 6.2 Definitions

Note: Ao, Ag refer to wall that


receives positive external pressure

Openings : apertures or holes in the


building envelope which allow air to

Aoi , Agi refer to building envelope


(walls and roof)

flow through the building envelope


and which are designed as open
during design winds

Enclosure Classification
Section 6.2 Definitions

Q: A: for Enclosure Classification

Q:

Is a fixed glazed opening

ENCLOSED

considered an opening?

A:

A building that does not qualify as


OPEN or PARTIALLY ENCLOSED.

NO.

Enclosure Classification

Enclosure Classification
Section 6.2 Definitions

Figure 6-5 Internal Pressure Coefficients,


GCpi

www.skghoshassociates.com
3

S. K. Ghosh Associates Inc.


ASCE 7-98
Positive Internal Pressure

Basic Wind Equation


For buildings with External and
Internal Pressure:

p = qGCp qiGCpi
qi = Velocity pressure calculated for
internal pressure.

ASCE 7-98
Negative Internal Pressure

Q: A: for Enclosure Classification

Q:

Why does a building need to be

enclosed to use the Simplified Procedure?

A:

See C6.4. GCpi = 0.18 is assumed in the

tables. In a simple diaphragm building,


internal pressures cancel out for the walls
but not for the roof.

Q: A: for Enclosure Classification

PROVISION
#2

Q: Should we treat roll-down doors and


operable louvers as openings?

Seismic and Wind


Design of Parapets

A: Yes and No.

www.skghoshassociates.com
4

S. K. Ghosh Associates Inc.


13.3.1 Nonstructural Component
Seismic Design Force

Common Earthquake Damage to


Parapets

Fp =

0.4 ap SDS
(Rp / Ip)

1+

2z
h

Wp

Fp (min) = 0.3 SDS Ip Wp

for SDS = 1.00,


Fp = 0.30 IpWp

Fp (max) = 1.6 SDS Ip Wp

for SDS = 1.00,


Fp = 1.60 IpWp

13.1.3Nonstructural Component
Importance Factor, Ip

Nonstructural Component ap and


Rp

Ip is based on

The values of ap range from 1.0 to 2.5 and

1. Whether component must function after


the design earthquake or

can be taken as less than 2.5 based on

2. Occupancy Category or

dynamic analysis.

3. Whether component contains hazardous

Rp values range from 1.0 to 12.0 (Tables

materials.

13.5-1 and 13.6-1).

Parapets: Ip is based on Occupancy


Category

Table 13.5-1 ap and Rp for


Architectural Components

Explanation of Fp Equation
1.2SDS

Component
Cantilever Parapets

AB = 0.4SDS (1+2zB/h)

ASCE 7-05

Architectural
ap

Rp

2.5

2.5

B
Floor
Acceleration
Distribution
AA= 0.4SDS (1+2zA/h)
0.4SDS

Z = h for parapet design

www.skghoshassociates.com
5

h
zB
A
zA

S. K. Ghosh Associates Inc.


Example: Seismic Design of
Parapets

Example: Seismic Design of


Parapets
The 7-in. concrete parapet shown forms
part of a building assigned to SDC D with
a component importance factor of 1.0.
SDS= 1.0g at the site. Determine the
strength-level seismic design moment in
the parapet.

Example: Seismic Design of


Parapets

Example: Seismic Design of


Parapets

Weight of the parapet per linear foot is

SDS = 1.0g

Wp = 150 x 3 x 7/12 = 262.50 lb/ft


The seismic lateral force acting at the
centroid of the parapet is given by
ASCE Equation (13.3-1) as
Fp = (0.4apSDSIp / Rp)(1 + 2z/h )Wp
Where Ip = component importance
factor = 1.0

Wp = weight of parapet = 262.5 lb/ft


ap = component amplification factor from ASCE
Table 13.5-1 = 2.5
h = height of roof above the base = 20 ft
z = height of parapet at point of attachment =
20 ft

Example: Seismic Design of


Parapets

Wind Forces on Parapets

Rp = component response modification factor


from ASCE Table 13.5-1 = 2.5
Fp = (0.4 x 2.5 x 1.0

1.0 / 2.5) (1 + 2 x 20/20)Wp

= 1.2Wp = 315 lb/ft


Neither ASCE Equation (13.3-2) nor (13.3-3)
governs, and the bending moment at the
base of the parapet is
Mp = 1.5 Fp = 472.5 lb-ft/ft
ASCE 7-05 Figure C6-12

www.skghoshassociates.com
6

S. K. Ghosh Associates Inc.


Wind Forces on Parapets
Wind Forces on Parapets
ASCE 7-05 C6.5.11.5 For simplicity, the
front and back pressures on the parapet
have been combined into one coefficient
for MWFRS design.

ASCE 7-05 Figure C6-12

Design Example

Example Building

The main wind force-resisting system of a


5-story reinforced concrete office building
is designed following the requirements of
the 2009 IBC/ASCE 7-05 wind provisions.

Design Criteria

Example Building
3 ft parapet

Location of building: Los Angeles, California


V=

85 mph (ASCE 7-05 Fig. 6-1)

Building is enclosed per definition under ASCE


7-05 Sec. 6.2
Assume Exposure B (ASCE 7-05 Sec. 6.5.6.3)
Occupancy Category: II,
Table 6-1)

www.skghoshassociates.com
7

I = 1.0 (ASCE 7-05

S. K. Ghosh Associates Inc.


Velocity Pressure Exposure
Coefficient, Kz

Effects of Parapets on MWFRS loads


ASCE 7-05 Section 6.5.12.2.4:

At top of parapet, h = 67.5 + 3 = 70.5 ft


pp = qpGCpn (ASCE 7-05 Eq. 6-20)
qp = velocity pressure evaluated at the top of

Kz = 2.01(z/zg)2/ = 2.01(70.5/1200)2/7 = 0.894

the parapet

(from ASCE 7-05 Table 6-3)

= 0.00256 Kz Kzt Kd V2 I
( = 7, zg = 1200 ft for Exposure B from

GCpn = combined net pressure coefficient


= +1.5 for windward parapet

ASCE 7-05 Table 6-2)

= -1.0 for leeward parapet

Topographic Effect Factor, Kzt


Wind Directionality Factor, Kd

Effects of Parapets on MWFRS loads


qp = 0.00256 Kz Kzt Kd V2 I =

Kzt = 1.0

0.00256 0.894 1 0.85 852 1 = 14.06 psf

(Assuming the example building to be situated

For windward parapet:

on level ground, i.e., with H, as shown in ASCE

pp = qpGCpn = 14.06 1.5 = 21.1 psf

7-05 Fig. 6-4, equal to zero).

Force = 21.1 3 66 / 1000 = 4.18 kips

Kd = 0.85

For leeward parapet:

(from ASCE 7-05 Table 6-4 for main wind force-

pp = qpGCpn = 14.06 (-1.0) = -14.06 psf

resisting system)

Force = -14.06 3 66 / 1000 = -2.78 kips

Effects of Parapets on MWFRS loads

Design of Parapets as Component

At the roof level, 4.18 + 2.78 = 6.96 kips is to be

ASCE 7-05 Section 6.5.12.4.4:

added to the design wind force for MWFRS


p = qp(GCp GCpi)

computed from the windward and leeward walls

(ASCE 7-05 Eq. 6-24)

qp = velocity pressure evaluated at the top of


the parapet
= 0.00256 Kz Kzt Kd V2 I = 14.06 psf
GCp = External pressure coefficient from Figs.
6-11 through 6-17
GCpi = Internal pressure coefficient from Fig.
6-5

www.skghoshassociates.com
8

S. K. Ghosh Associates Inc.


External Pressure Coefficient, GCp

External Pressure Coefficient, GCp

Load Case A (ASCE 7-05 Section 6.5.12.4.4)


Effective wind area of the parapet:

Positive wall GCp = 0.68 (Figure 6-17 Zones 4

Span = 3 ft

and 5)

Width = 66 ft (> span/3)

Applied to front surface of the parapet

A = 3x66 = 198 ft2

External Pressure Coefficient, GCp

External Pressure Coefficient, GCp

Load Case A (ASCE 7-05 Section 6.5.12.4.4)

Load Case A (ASCE 7-05 Section 6.5.12.4.4)

Negative roof edge GCp = -1.76 (Figure 6-17


Zone 2*)

GCp = 0.68 (-1.76) = 2.44

Applied to back surface of the parapet

GCpi = -0.18 for enclosed building (uniform


porosity)

*Corner Zone 3 is treated as Zone 2 because the parapet is 3 ft high


(Figure 6-17 Note 7)

However, internal pressures on both surfaces of


the parapet cancel each other out.
p = 14.06 x 2.44 = 34.31 psf

External Pressure Coefficient, GCp

External Pressure Coefficient, GCp


Load Case B (ASCE 7-05 Section 6.5.12.4.4)

Load Case B (ASCE 7-05 Section 6.5.12.4.4)


Effective wind area = 198

ft2
Negative wall GCp = -0.76 (Figure 6-17 Zone 4)

Positive wall GCp = 0.68 (Figure 6-17 Zones 4 and

= -1.23 (Figure 6-17 Zone 5)

5)
Applied to back surface of the parapet

Applied to front surface of the parapet

www.skghoshassociates.com
9

S. K. Ghosh Associates Inc.


External Pressure Coefficient, GCp

Design of Parapets as Component

Load Case B (ASCE 7-05 Section 6.5.12.4.4)


GCp = 0.68 (-0.76) = 1.44 (For Zone 4)

Clearly, Load Case A governs

= 0.68 (-1.23) = 1.91 (For Zone 5)


GCpi = -0.18 for enclosed building (uniform

Thus, design uniform wind pressure on the

porosity)

whole width of the parapet

However, internal pressures on both surfaces of


the parapet cancel each other out.

p = 34.31 psf

p = 14.06 x 1.44 = 20.24 psf (Zone 4)


= 14.06 x 1.91 = 26.85 psf (Zone 5)

Q: A: for Wind Design of Parapet


Q: A: for Wind Design of Parapet

A: In the case of parapets, it is expected

Q: In Section 6.5.12.4.4 (parapets for

most cases to have uniform porosity, so the

C&C), the definition for the factor GCpi is

"enclosed" classification (+0.18, - 0.18)

based on the porosity of the parapet

would be appropriate. However, if the two


surfaces of the parapet are very different

envelope. How is the porosity of the

(one has openings, the other is fully

parapet determined?

sealed), the partially-enclosed case might


be relevant.

Q: A: for Wind Design of Parapet

Q:

PROVISION
#3

What is the wind load on the parapet using

Method 1, Simplified Procedure?

Torsion, Torsional
Irregularity and Direction
of Seismic Loading

A: There is no clear answer. Some


jurisdictions do not allow Method 1 to be
used for buildings with parapets.

www.skghoshassociates.com
10

S. K. Ghosh Associates Inc.

xe

QE

ASCE 7-05 12.8.4 Horizontal


Distribution of Forces
Rigid diaphragms
Seismic story shear is to be distributed to elements
of seismic-force-resisting system based on stiffness
of vertical-resisting elements

Flexible diaphragms
Seismic story shear is to be distributed to elements
of seismic-force-resisting system based on tributary
areas

ASCE 7-05 12.8.4 Horizontal


Distribution of Forces

Failure Torsion

Torsion
Torsional moment due to difference in location of center of
mass and center of resistance
must be considered for rigid diaphragms

Accidental torsion
For rigid diaphragms, must be included in addition to the
torsional moment
Displacement of center of mass = 5% building
dimension perpendicular to direction of applied forces
1976 Philippines

www.skghoshassociates.com
11

S. K. Ghosh Associates Inc.


Amplification of Torsion

Amplification of Torsion

For structures* assigned to SDC C, D, E, or F

A and B computed assuming Ax = 1.0

without flexible diaphragm and with horizontal


irregularity Type 1a or 1b (Torsional Irregularity
or Extreme Torsional Irregularity), the
accidental torsion Mta at each floor level needs
to be amplified by a factor:
Ax =

max
1.2avg

3.0
Adapted from ASCE 7-05 Figure 12.8-1

*Not applicable to light-frame construction

Torsional Irregularity

Torsional Irregularity
Referenced in:
Section 12.3.3.4 25% increase in seismic forces in
connections in diaphragms and collectors
Table 12.6-1 Permitted analytical procedure
Section 12.7.3 3-D structural model required
Section 12.8.4.3 Amplification of accidental torsion
Section 12.12.1 Design story drift based on largest
difference in deflection
Section 16.2.2 - 3-D structural model required in
nonlinear response history procedure

Extreme Torsional Irregularity

Extreme Torsional Irregularity

Referenced in:
Section 12.3.3.1 Prohibited in SDC E and F
Section 12.3.3.4 25% increase in seismic forces in
connections in diaphragms and collectors
Section 12.3.4.2 (Table 12.3-3) = 1.3
Table 12.6-1 Permitted analytical procedure
Section 12.7.3 3-D structural model required
Section 12.8.4.3 Amplification of accidental torsion
Section 12.12.1 Design story drift based on largest
difference in deflection
Section 16.2.2 - 3-D structural model required in
nonlinear response history procedure

www.skghoshassociates.com
12

S. K. Ghosh Associates Inc.

Section 12.5.2 Direction of


Loading

Q: A: for Torsional Irregularity

Q:

Do the torsional irregularity provisions


12.5.2 SDC B.

apply to light-frame constructions?

The design seismic forces are permitted to be

A:

applied independently in each of two

Most likely, no. The torsional irregularity

orthogonal directions and orthogonal

definition applies to diaphragms that are

interaction effects are permitted to be

rigid or semirigid, which is typically not the

neglected.

case for light-frame construction.

Section 12.5.2 Direction of


Loading

ASCE 7-05 12.5.2 Direction of


Loading
12.5.3 SDC C.

12.5.3 SDC C.

a. Orthogonal Combination Procedure.

Structures that have horizontal structural


irregularity Type 5 of Table 12.3-1, shall use

ELF, modal response spectrum, or linear

one of the following procedures.

response history analysis, with loading applied


independently in any two orthogonal
directions
100% + 30%

Section 12.5.2 Direction of


Loading
12.5.3 SDC C.
b.

Simultaneous Application of Orthogonal


Ground Motion.
Linear or nonlinear response history
analysis, with orthogonal pairs of ground
motion acceleration histories applied
simultaneously.

www.skghoshassociates.com
13

S. K. Ghosh Associates Inc.

Section 12.5.2 Direction of


Loading
12.5.4 SDC D, E or F.
The orthogonal combination procedure shall
additionally be required for any column or
wall that forms part of two or more
intersecting seismic-force-resisting systems
and is subjected to axial load due to seismic
forces acting along either principal plan axis
equaling or exceeding 20% of the axial load
design strength of the column or wall.

REDUNDANCY FACTOR,
ASCE 7-05 Section 12.3.4

PROVISION
#4

REDUNDANCY

SDC

NA

B&C

1.0

D, E & F

1.0 or 1.3

Note that = 1.0 when the SIMPLIFIED


PROCEDURE of Section 12.14 is used.

Section 12.3.4.1
for SDC D - F

REDUNDANCY FACTOR,
ASCE 7-05 Section 12.3.4
12.3.4

Redundancy

12.3.4.1

Conditions Where

1. Structures assigned to SDC B and C.

Value of is 1.0

2. Drift calculation and P-delta effects.

Redundancy

3. Design of nonstructural components.

Factor, , for SDC

4. Design of nonbuilding structures, not


similar to buildings.

12.3.4.2

= 1.0 for the following:

D through F

www.skghoshassociates.com
14

S. K. Ghosh Associates Inc.


Section 12.3.4.2
for SDC D - F

Section 12.3.4.1
for SDC D - F
= 1.0 or 1.3

= 1.0 for the following:


5. Design of collector elements, splices and their
connections for which load combinations with
overstrength are used.

= 1.3 unless ONE of two conditions is met.


If Condition # 1 is met, then = 1.0

6. Design of members or connections where load


combinations with overstrength are required for design.

If Condition #2 is met, then = 1.0

7. Diaphragm loads determined using Eq. 12.10-1.

Both conditions do NOT need to be met

8. Structures with damping systems designed in


accordance with ASCE 7-05 Chapter 18.

for = 1.0

Section 12.3.4.2
for SDC D - F

Section 12.3.4.2
for SDC D - F

CONDITION #1:

CONDITION #1 and CONDITION #2 only need to


be checked at each story resisting more than

Can an individual element be removed from

35% of the base shear.

the lateral-force-resisting-system without:


Causing the remaining structure to
suffer a reduction of story strength >
33%, or
Creating an extreme torsional
irregularity?

TABLE 12.3-3
REQUIREMENTS FOR EACH STORY RESISTING MORE
THAN 35% OF THE BASE SHEAR

Section 12.3.4.2
for SDC D - F
CONDITION #2
If a structure is regular in plan and there are at
least 2 bays of seismic force-resisting perimeter
framing on each side of the structure in each
orthogonal direction at each story resisting >
35% of the base shear.

www.skghoshassociates.com
15

S. K. Ghosh Associates Inc.


Section 12.3.4.2
for SDC D - F

Q: A: for Redundancy

Q: How many bays are in a shear wall?

Seismic Force-Resisting
Perimeter Framing
Two Bays

A: Length of shear wall/ story heightor for


light-framed construction (defined in
Section 11.2), 2 x length of shear wall/
story height

Q: A: for Redundancy

Q: A: for Redundancy

Q: I am using Condition #1 to determine


Q: Does the redundancy factor apply

for a wood-frame building. All of the


shear walls are relatively long; in other
words, the height of each shear wall (8)
is less than its length (9, 10, 12). Can I
assign = 1.0 because there are no
shear walls with a h/l ratio > 1.0?

to the design of foundations?

A: Yes.

A:

Q: A: for Redundancy

Yes.

Q: We have a building that is 325 feet tall (31


stories) with shear walls. We are using
Condition #1 to determine . When Table
12.3-3 uses the phrase height-to-length
ratio, is that the height-to-length ratio within
any story? Or is it referring to the overall
height-to-length ratio which, for our building,
would mean a height of 325 feet.

www.skghoshassociates.com
16

S. K. Ghosh Associates Inc.

Q: A: for Redundancy

Q: A: for Redundancy

A: The h/l ratio is intended to be


Q:

Can the value of be different at


each level of the same building?

story height-to-length ratio.


l < 10 ft

h = 10 ft

Q: A: for Redundancy

A:

Q: A: for Redundancy

No, cannot be different at each

Q:

Why doesnt Table 12.3-3


address dual systems? If you have
a dual system, can you assume =
1.0?

level of the same building. However,


depending on the structural system,
can be different in the two orthogonal
directions of the same building if
Condition #1 is used.

Q: A: for Redundancy

A: No..

Braced frame, moment frame and shear wall


systems have to conform to redundancy
requirements. Dual systems are also included,
but in most cases are inherently redundant.
Shear walls with a height-to-length aspect ratio
greater than 1.0 have been included, even
though the issue has been essentially solved by
requiring collector elements and their connection
to be designed for 0 times the design force.

www.skghoshassociates.com
17

S. K. Ghosh Associates Inc.

Q: A: for Redundancy

Q:

Q: A: for Redundancy

A:

Do you need to determine the

You need to determine the redundancy

factor. If the code did not intend that the


redundancy factor be determined for
Nonbuilding structures similar to
buildings, there would be an exception to
Section 15.5.1 as is done in Section 15.6.

redundancy factor for nonbuilding


structures similar to buildings or can you
assume the redundancy factor equals 1?

Q: A: for Redundancy

Q:

Does the redundancy factor need


to be determined if dynamic
analysis is used?

A:

Yes.

REDUNDANCY EXAMPLE
Wall E
Stiffness Ke

REDUNDANCY EXAMPLE

Wall F
Stiffness Kf

Wall A
Stiffness Ka

Wall C
Stiffness Kc

Wall B
Stiffness Kb

Wall D
Stiffness Kd

SDC D
one story concrete shear wall building
Ka = Kb = Kc = Kd = Ke = Kf = Kg = Kh = K
All walls have the same nominal shear
strength, Vn.
The story height is 18 feet.
The length of each shear wall is 15 feet.
Let a denote the horizontal dimension of
this building.

Wall G
Stiffness Kg

Wall H
Stiffness Kh

www.skghoshassociates.com
18

S. K. Ghosh Associates Inc.

REDUNDANCY EXAMPLE
CONDITION #1

CONDITION #2

Step 1:

Step 1:

Remove shear wall and see

Check if structure is regular

if story strength is reduced

in plan.

REDUNDANCY EXAMPLE
Check Condition #2 first (its easier)
Q: How many bays are in a shear wall?
A: Length of shear wall/ story heightor

by more than 33%.

for light-framed construction, 2 x length

Step 2:

Step 2:

See if there is an extreme

Are there at least 2 bays

torsional irregularity created.

of.on each side in each

of shear wall/ story height.


For example: (15/18)(2) = 1.67 < 2

orthogonal direction?

REDUNDANCY EXAMPLE

REDUNDANCY EXAMPLE

CONDITION #1:

CONDITION #1

Removal of a shear wall or wall pier with a


height-to-length ratio greater than 1.0 within
any story, or collector connections thereto,
would not result in more than a 33% reduction
in story strength, nor does the resulting system
have an extreme torsional irregularity
(horizontal structural irregularity Type 1b).

Step 1:
Remove shear wall and see if
story strength is reduced by
more than 33%.

Step 2:
See if there is an extreme
torsional irregularity created by
doing so.

REDUNDANCY EXAMPLE
Wall E
Stiffness Ke

REDUNDANCY EXAMPLE
Definition of Extreme Torsional
Irregularity in ASCE 7-05 Table 12.3-1:

Wall F
Stiffness Kf

Extreme Torsional Irregularity exists where


the maximum story drift, computed
including accidental torsion, at one end of
the structure transverse to an axis is more
than 1.4 times the average of the story
drifts at the two ends of the structure.

Wall A
Stiffness Ka

a
Wall B
Stiffness Kb

Wall D
Stiffness Kd
Wall G
Stiffness Kg

Wall H
Stiffness Kh

www.skghoshassociates.com
19

S. K. Ghosh Associates Inc.

REDUNDANCY EXAMPLE

REDUNDANCY EXAMPLE
The determination of extreme torsional

The torsional stiffness about the center


of rigidity (CR) is determined as:

irregularity requires the evaluation of the


story drifts a and b, as shown below.
b

a
a/3
CR

2a/3
CM
a/6

REDUNDANCY EXAMPLE

REDUNDANCY EXAMPLE
Assume that the story drift caused only by
the lateral force V is equal to , and that
is the rotation caused by the torsion T, then

According to ASCE 7-05 Table 12.3-1,


extreme torsional irregularity does not exist
when

This can be transformed to


This ratio is less than 2.33 only if /(a) is
larger than 1.08.

REDUNDANCY EXAMPLE

PROVISION
#5
Therefore, no extreme torsional irregularity is created
and = 1.0.
(Note that the term 0.05a is for accidental torsion)

SEISMIC ANALYSIS
PROCEDURE SELECTION

Thus, the horizontal structural irregularity Type 1b does


not exist and the configuration qualifies for a factor
of 1.0.

www.skghoshassociates.com
20

S. K. Ghosh Associates Inc.

Seismic Analysis Procedure Selection

STATIC ANALYSIS
PROCEDURES

ASCE 7-05
SECTION

Simplified Design
Procedure
Equivalent Lateral Force
Procedure

12.14

Seismic Analysis Procedure Selection

12.8

Simplified Design Procedure


Exception to Section 12.1

DYNAMIC ANALYSIS
PROCEDURES

ASCE 7-05
SECTION

Modal Response
Spectrum Analysis
Linear Response History
Analysis

12.9

Nonlinear Response
History Analysis

16.2

16.1

Simplified Design Procedure


Section 12.14
1. Occupancy Category I or II
2. Site Class A, B, C, or D
3. Three stories or less in height
4. Bearing wall system or building
frame system
5. through 12

EXCEPTION: As an alternative, the simplified


design procedure of Section 12.14 is
permitted to be used in lieu of the
requirements of Sections 12.1 through 12.12,
subject to all of the limitations contained in
Section 12.14.
Note: Section 12.13 is Foundation Design

Seismic Analysis Procedure Selection


Table 12.6-1

Q: A: for Simplified Design Procedure

Q: What are the benefits of using the


Simplified Design Procedure?

A:

Here are the benefits:

= 1, o = 2.5.
No period (T) determination.
No triangular distribution of seismic forces.
Determination of Fa simplified; Ss need not
exceed 1.5g.
Drift need not be calculated

* 12.3-1
*
**

www.skghoshassociates.com
21

** 12.3-2

S. K. Ghosh Associates Inc.


Seismic Analysis Procedure Selection

Seismic Analysis Procedure Selection


Table 12.6-1
If a building is assigned SDC D, E, or F
and has a T 3.5 Ts, then dynamic
analysis procedure must be used.
(Ts is the period at which the flat-top portion of
the response spectrum transitions to the
descending (period-dependent) branch.)

Seismic Analysis Procedure Selection


Table 12.6-1

Seismic Analysis Procedure Selection

Dynamic Analysis is required if a building


meets all of the following conditions:
 SDC D, E, or F
 Not of light-frame construction
 Contains one of the following
irregularities:
Torsional or Extreme Torsional
Stiffness-Soft Story, Stiffness Extreme Soft
Story, Weight (Mass) or Vertical Geometric

Seismic Analysis Procedure Selection


Table 12.6-1

Seismic Analysis Procedure Selection


Table 12.6-1
All structures of light frame

Occupancy Category I or II buildings of

construction, irrespective of height

other construction not exceeding two


stories in height

Dynamic analysis never required

Dynamic analysis not required

www.skghoshassociates.com
22

S. K. Ghosh Associates Inc.

Seismic Analysis Procedure Selection

Seismic Analysis Procedure Selection

Q:

A:

In Table 12.6-1, it states Regular

Structures with T < 3.5Ts and all structures of

It does not mean "and." It means

"or." Regular Structures with T <

light frame construction are permitted to use

3.5Ts are permitted to use Equivalent

an Equivalent Lateral Force Analysis. Does


this mean that the building must meet both

Lateral Force Analysis. All structures of

conditions (regular with T < 3.5Ts and light

light frame construction, irrespective of

frame construction), or does only one of these

height, are also permitted to

two characteristics need to be satisfied?

use Equivalent Lateral Force Analysis.

xe

QE

PROVISION
#6

DRIFT AND BUILDING


SEPARATION
V

Drift Determination
Section 12.8.6

Drift Determination
Section 12.8.6

Step 1: Determine xe at each floor level


where xe is the lateral deflection at floor
level x determined by elastic analysis

Step 3: Divide xeCd by I, Importance


Factor: x = xeCd /I

under code-prescribed seismic forces.

Step 4: Determine design story drift:


Step 2: Multiply xe by Cd given in Table

x = x (x 1)

12.12-1, the product representing the


estimated design earthquake
displacement.

www.skghoshassociates.com
23

S. K. Ghosh Associates Inc.


Drift Determination
Section 12.8.6

Story Drift
x = x x-1 < a
x = Cd xe / I
Cd = deflection amplification factor

Allowable Drift Additional


Requirement

Allowable Drift
ASCE 7-05 Table 12.12-1

ASCE 7-05 Section 12.12.1.1


Occupancy Category
Structure
I or II

III

For seismic forceresisting systems comprised

IV

Structures, other than masonry shear wall


structures, 4 stories or less with interior walls,
partitions, ceilings, and exterior wall systems
that have been designed to accommodate the
story drift.

0.025hsx 0.020hsx 0.015hsx

Masonry cantilever shear wall structures

0.010hsx 0.010hsx 0.010hsx

Other masonry shear wall structures

0.007hsx 0.007hsx 0.007hsx

All other structures

0.020hsx 0.015hsx 0.010hsx

solely of moment frames in structures assigned


to Seismic Design Categories D, E, or F, the
design story drift shall not exceed a / for any
story. shall be determined in accordance with
Section 12.3.4.2.

Q: A: for Drift Determination

Q:

Q: A: for Drift Determination

Q:

Why is drift divided by the Importance

allowable stress design (ASD) than for


strength design (SD)?

Factor?

A:

Is drift determined differently for

Because the forces under which xe

A:

are computed are already amplified by I,


and the drift limits set forth in Table
12.12-1 are more restrictive for higher
occupancy category buildings.

No. The same procedure is used

regardless of whether ASD or SD is


used.

www.skghoshassociates.com
24

S. K. Ghosh Associates Inc.

Q: A: for Drift Determination

Q: A: for Drift Determination

Q: Does minimum base shear need to be

Q: Does the upper-bound limitation on

considered for drift determination?

A:

period T need to be considered for drift


determination?

Yes, Section 12.8.6.1 requires that all

A:

of the requirements of Section 12.8 be


satisfied for the purpose of computing
drift.

No. Section 12.8.6.2 does not require

the period to be subject to the upper


limit of CuTa for the purpose of drift
determination.

Building Separation
Section 12.12.3

Building Separation
Section 12.12.3
 This section applies to SDCs B
through F.

12.12.3 Building Separation. All portions


of the structure shall be designed and
constructed to act as an integral unit in
resisting seismic forces unless
separated structurally by a distance
sufficient to avoid damaging contact
under total deflection as determined in
Section 12.8.6.

 Does not address adjacent


buildings on the same property.
 Does not address minimum
setback distance from property line.

Building Separation
2009 IBC Section 1613.6.7

Building Separation
Section 12.12.3

Code Requirement

2006 IBC/
ASCE 7-05

2009 IBC/
ASCE 7-05

No
requirement

2009 IBC
Section
1613.6.7

BUILDING SEPARATIONS (paraphrased):

Code Requirement

PORTIONS OF THE SAME STRUCTURE:


All portions of the structure shall be designed
and constructed to act as an integral unit in
resisting seismic forces unless separated
structurally by a distance sufficient to avoid
damaging contact under total deflection (x) as
determined in Section 12.8.6.

2006 IBC/
ASCE 7-05

2009 IBC/
ASCE 7-05

ASCE 7-05
Section 12.12.3
(applies to all
SDCs)

ASCE 7-05
Section 12.12.3
(applies to all
SDCs)

All structures shall be separated from adjoining structures.


Separations shall allow for the maximum inelastic
displacement M (including torsion).
Adjacent buildings on the same property shall be separated
by at least MT where

When a structure adjoins a property line not common to a


public way, that structure shall also be set back from the
property line by at least the displacement, M, of that
structure.
Continued on next page

Exception: Smaller separations or property line setbacks


shall be permitted when justified by rational analyses based
on maximum expected ground motions.

www.skghoshassociates.com
25

S. K. Ghosh Associates Inc.


Building Separation
2009 IBC Section 1613.6.7

Building Separation
2009 IBC Section 1613.6.7
Note difference between x and M
The deflections of Level x at the center of
mass (12.8.6),
x = Cd xe / I
M = Cd max / I

(Equation 16-44)

max = the maximum displacement at Level x


computed assuming Ax = 1 (12.8.4.3)

Building Separation
2009 IBC Section 1613.6.7

Building Separation
2009 IBC Section 1613.6.7

10 separation
M2 at adjacent edge = 8
M1 at edge = 6

Separation of Two Adjacent Buildings

Q:A: for Building Separation

Q:

Q:A: for Building Separation

ASCE 7-05 Section 12.12.3 contains the

Q:

language sufficient to avoid damaging


contact. What is damaging contact?

A:

I do not understand the logic of

requiring less separation between two


buildings on the same property than
between two identical buildings on different
sides of the property line.

To avoid any contact at all, the separation

distance would have to be the arithmetic sum of


M1 and M2. To avoid damaging contact, ASCE
7 allows the separation distance to be the
statistical sum of M1 and M2, which is less than
the arithmetic sum.

www.skghoshassociates.com
26

S. K. Ghosh Associates Inc.

Q:A: for Building Separation

A:

The first provision is concerned with

PROVISION
#7

damaging contact from pounding of


buildings belonging to presumably the
same owner. The property line setback
requirement is based on consideration
that one owner should not encroach
onto another property.

R, Cd and 0 Values for


Horizontal and Vertical
Combinations

Section 12.2.2 Combinations of


Framing Systems in Different
Directions

R, Cd and o Values for Horizontal


and Vertical Combinations

Different seismic force-resisting systems

Horizontal Combinations can be

may be used to resist seismic forces along

either.

each of two orthogonal plan axes.


The respective R, Cd, and o coefficients

In different directions

shall apply to each system, including the

In same direction

limitations on system use contained in


Table 12.2-1.

Section 12.2.2 Combinations of


Framing Systems in Different
Directions

Section 12.2.3 Combinations of


Framing Systems in the Same
Direction
Where different seismic force-resisting systems
are used in combination to resist seismic
forces in the same direction of structural

R =5
Cd = 5
o = 2

response, other than those combinations


considered as dual systems, the more
stringent system limitation contained in Table
12.2-1 shall apply and the design shall comply

R = 8, Cd = 5 , o = 3

with the requirements of this section.

www.skghoshassociates.com
27

S. K. Ghosh Associates Inc.

12.2.3.2 Horizontal Combinations

12.2.3.1 Vertical Combinations


R=8, Cd=5.5, 0=3

8, 5.5, 3

R=5, Cd=5, 0=2.5

5, 5, 2.5

8, 5.5, 3

R=5, Cd=5, 0=2.5

8, 5.5, 3

5, 5, 2.5

5, 5.5, 3

5, 5.5, 3

5, 5.5, 3

R=8, Cd=5.5, 0=3

5, 5.5, 3

R=8, Cd=5.5, 0=3

5, 5.5, 3

12.2.3.2 Where a combination of different


structural systems is utilized to resist lateral
forces in the same direction, value of R used
for design in that direction shall not be greater
than the least value of R for any of the systems
utilized in that direction.

8, 5.5, 3

8, 5.5, 3

5, 5, 2.5

R=5, Cd=5, 0=2.5

5, 5.5, 3

5, 5.5, 3

R=8, Cd=5.5, 0=3

5, 5.5, 3

5, 5.5, 3
5, 5.5, 3

R: Cannot increase as you go down


Cd and 0: Cannot decrease as you go down

12.2.3.2 Horizontal Combinations


12.2.3.2 Horizontal Combinations

12.2.3.2 Resisting elements are permitted to be


designed using the least value of R for the
different structural systems found in each
independent line of resistance if the following
three conditions are met: 1) Occupancy Category
I or II building, 2) two stories or less in height, and
3) use of light frame construction or flexible
diaphragms.

The deflection amplification factor, Cd, and the


system overstrength factor, 0 , in the direction
under consideration at any story shall not be
less than the largest value of this factor for the
R factor used in the same direction being

The value of R used for design of diaphragms in


such structures shall not be greater than the least
value for any of the systems utilized in that same
direction.

considered.

12.2.3.2 Horizontal Combinations

12.2.3.2 Horizontal Combinations


The other possible interpretation is that the Cd-

The second paragraph of ASCE 7-05 Section

and 0-values shall correspond to the least R-

12.2.3.2 is far from clear.

value of all the individual structural systems.

One possible interpretation is that when different

The second interpretation appears to be the

structural systems are combined in the same

more logical in view of the following example

direction of a building or other structure, the

(discussion is continued in terms of Cd alone).

largest Cd- and 0-values of all the individual


structural systems shall be used.

www.skghoshassociates.com
28

S. K. Ghosh Associates Inc.

12.2.3.2 Horizontal Combinations

12.2.3.2 Horizontal Combinations

Consider a rather extreme example where a

First, the combined system is much more rigid

prestressed masonry shear wall (R = 1.5, Cd =

than the special steel moment frame itself.

1.75) is combined with a special steel moment-

Until the prestressed masonry shear wall

resisting frame (R = 8, Cd = 5.5). There is no

hinges at its base, which is extremely unlikely

question that the R-value is 1.5. The question is

in view of the large design forces that would

whether the Cd-value is 1.75 or 5.5. 5.5 does not

result from an R = 1.5, large inelastic

seem logical for two reasons.

displacements do not seem to be possible.

12.2.3.2 Horizontal Combinations

12.2.3.2 Horizontal Combinations

Second, large values of xe would automatically

The proposed rewrite provides clarification of the

result from the low value of R used in design.

second paragraph of ASCE 7-05 Section

These, multiplied by the Cd of 5.5 would yield

12.2.3.2. The rewrite also offers clarification

unrealistically large total displacements. Cd of

concerning another complication that may

1.75 appears to be much more logical.

arise, which is that different structural systems

This second interpretation was implicit in the

having the same R-value sometimes have

1997 Uniform Building Code, where 0.7R was

different Cd- and 0-values.

used in place of Cd.

12.2.3.2 Horizontal Combinations


Table 12.2.3.2 R, Cd, and o Values for Combination of

Vertical combinations

Different Structural Systems Used in Same Direction


R value

The least value of R for any of the systems used.

R = 8, Cd = 5.5, 0 = 3

Exception: Resisting elements are permitted to be designed using the

8, 5.5, 3

least value of R for the different structural systems found in each


independent line of resistance if the following three conditions are met: 1)

R = 5, Cd = 5, 0 = 2.5

of the systems used. In the case where two or more systems have the

5, 5, 2.5
5, 5, 2.5

R = 8, Cd = 5.5, 0 = 3

5, 5, 2.5

R = 5, Cd = 5, 0 = 2.5

used.

5, 5, 2.5

R: Cannot increase as you go down


Cd and 0: Always correspond to R

of the systems used. In the case where two or more systems have the

ASCE 7-10 Section 12.2.3.1 Vertical Combinations

same least value of R, the largest of the corresponding values of o shall be


used.

www.skghoshassociates.com
29

5, 5, 2.5
5, 5, 2.5

R = 8, Cd = 5.5, 0 = 3

same least value of R, the largest of the corresponding values of Cd shall be


o value The o value corresponding to the system with the least value of R for any

8, 5.5, 3
8, 5.5, 3

5, 5, 2.5

5, 5, 2.5
R = 5, Cd = 5, 0 = 2.5

The Cd value corresponding to the system with the least value of R for any

R = 8, Cd = 5.5, 0 = 3

5, 5, 2.5
5, 5, 2.5

8, 5.5, 3

Occupancy Category I or II building, 2) two stories or less in height, and 3)


use of light frame construction or flexible diaphragms.
Cd value

5, 5, 2.5

8, 5.5, 3

5, 5, 2.5
5, 5, 2.5

S. K. Ghosh Associates Inc.


Q: A: for Combinations

12.2.4 Combination Framing


Detailing Requirements

Q: I am designing a building that has a combination of special


reinforced masonry shear walls and special steel braced frames
in the same direction. R values are 5.5 and 6, respectively. I

Structural components common to different

understand that I should design the building with the smaller R

framing systems used to resist seismic

= 5.5 for both the masonry shear walls and steel braced frames

motions in any direction shall be designed

in this direction for seismic design in accordance with ASCE 7-

using the detailing requirements of Chapter 12

05 Section 12.2.3.2. But someone told me that the building

required by the highest response modification

should be designed by analyzing the entire building twice: use


R = 5.5 for the entire building to analyze and design the

coefficient, R, of the connected framing

masonry shear walls and use R = 6 for the entire building to

systems.

design the steel frames. I don't think this is right. What is your
thought on this?

Q: A: for Combinations

A:

PROVISION
#8

What you understand is correct. The latter

interpretation is unfamiliar and incorrect.

MINIMUM SEISMIC
BASE SHEAR

ASCE 7-05 12.8.1


Design Base Shear

CodeMaster
2009 IBC Seismic Design

www.skghoshassociates.com
30

S. K. Ghosh Associates Inc.


ASCE 7-05 12.8 Equivalent Lateral
Force Procedure

Revisions to ASCE 7-05 Seismic


Provisions
Building Code
1997 UBC

Vmin = 0.11 Ca I W

2000 & 2003 IBC

ASCE 7-05 w/ Supplement No. 2


Design Base Shear

Minimum Base Shear


Applicable in All SDCs

Vmin = 0.044 SDS I W

2006 IBC & ASCE 7-05 w/ Supplement No. 1

Vmin = 0.01 W

2009 IBC & ASCE 7-05 w/ Supplement Nos. 1


and 2

Vmin = 0.044 SDS I W


0.01W

Section 1613
Earthquake Loads
Section 1613.1 references ASCE 7
Chapter 35 entry for ASCE 7 reads as
follows:
ASCE 7-05 Minimum Design Loads for Buildings
and Other Structures including Supplements
No. 1 and 2, excluding Chapter 14 and Appendix
11A

ASCE 7-05 Including


Supplement No. 1

ASCE 7-05 Supplement No. 2


Supplement No. 2 modifies Eqs. 12.8-5,
15.4-1 and 15.4-3 as shown below:
CS = 0.01 0.044SDSI 0.01 (Eq. 12.8-5) [applicable

Including Supplement No. 1

to buildings]
CS = 0.03 0.044SDSI 0.03 (Eq. 15.4-1) [applicable
to nonbuilding structures not similar to buildings]
CS = 0.01 0.044SDSI 0.01 (Eq. 15.4-3) [applicable
to an exception for nonbuilding structures not
similar to buildings]

www.skghoshassociates.com
31

S. K. Ghosh Associates Inc.


Minimum Seismic Base Shear
vs. Ground Motion

Minimum Seismic Base Shear

0.044SDSI 0.01 or SDSI 0.227


or SS value given in table
Site Class

I=1

I = 1.25

I = 1.5

0.426

0.341

0.284

0.341

0.273

0.227

0.284

0.227

0.189

0.213

0.170

0.142

0.136

0.109

0.091

Minimum Seismic Base Shear Example

Minimum Seismic Base Shear

Concrete SMRF building - R = 8, I = 1.0

For special reinforced concrete moment

Height = 120 ft, SDS = 1.00, SD1 = 0.40

frames,

Ta = 0.016(120)0.9 = 1.19 sec

0.016h0.9 9/8

h (70.31)1/0.9 = 113 ft

Governs
Does not govern

ASCE 7-05 Supplement No. 2

Q: A: for ASCE 7-05 Supplement


No. 2

Q: Does ASCE 7-05 Supplement No. 2

Q: Where does ASCE officially announce ASCE 705 Supplement No. 2?

minimum base shear need to be considered


for drift determination?

A:

http://content.seinstitute.org/files/pdf/

A:

SupplementNo2ofthe2005EditionofASCE7.pdf

Yes, Section 12.8.6.1 requires that all of the

requirements of Section 12.8 be satisfied for


the purpose of computing drift.

www.skghoshassociates.com
32

S. K. Ghosh Associates Inc.


Q: A: for ASCE 7-05 Supplement
No. 2

Q: Is ASCE 7-05 going to be published with


PROVISION
#9

errata and Supplement No. 2 incorporated?

A: Additional printings will, to the extent

FLEXIBLE VS. RIGID


DIAPHRAGMS

possible, include as extra pages the


supplements and errata. However there's a
conscious decision not to integrate them
directly into the text so as to minimize
confusion between one book and another.

2006 and 2009 IBC Section 1602


Definition for Diaphragms

FLEXIBLE
DIAPHRAGMS

DIAPHRAGM
Diaphragm, blocked

Prescriptive Approach

Diaphragm boundary

&

Diaphragm chord

Calculation Approach

Diaphragm, flexible
Diaphragm, rigid
Diaphragm, unblocked

ASCE 7-05 Section 12.3.1.1


Definition for Flexible Diaphragm
(Prescriptive)

2006 and 2009 IBC Section 1602


Definition for Flexible Diaphragm

12.3.1.1 Flexible Diaphragm


Condition. Diaphragms constructed of untopped
steel decking or wood structural panels are
permitted to be idealized as flexible in structures
in which the vertical elements are steel or
composite steel and concrete braced frames, or
concrete, masonry, steel, or composite shear
walls. Diaphragms of wood structural panels or
untopped steel decks in one- and two-family
residential buildings of light-frame construction
shall also be permitted to be idealized as flexible.

Diaphragm, flexible.
A diaphragm is flexible for the purpose of distribution
of story shear and torsional moment where so
indicated in Section 12.3.1 of ASCE 7, as modified in
Section 1613.6.1.

www.skghoshassociates.com
33

S. K. Ghosh Associates Inc.


ASCE 7-05 Section 12.3.1.3
Definition for Flexible Diaphragms
by Calculation

ASCE 7-05 Figure 12.3-1


Definition for Flexible Diaphragm
by Calculation

12.3.1.3 Calculated Flexible Diaphragm


Condition. Diaphragms are permitted to be
idealized as flexible where the computed
maximum in-plane deflection of the diaphragm
under lateral load is more than two times the
average story drift of adjoining vertical
elements of the seismic force resisting system
of the associated story under equivalent
tributary lateral load as shown in Fig. 12.3-1.

De
MAXIMUM DIAPHRAGM
DEFLECTION (MDD)

SEISMIC LOADING

AVERAGE DRIFT OF
VERTICAL ELEMENT
(ADVE)

Note: Diaphragm is flexible If MDD > 2 (ADVE).

2006 and 2009 IBC Section 1613.6.1


Definition for Flexible Diaphragm
(Prescriptive)

2006 and 2009 IBC Section 1613.6.1


Definition for Flexible Diaphragm

1613.6.1 Assumption of flexible


diaphragm. Add the following text at the
end of Section 12.3.1.1 of ASCE 7:

Condition #1:
Toppings of concrete or similar materials
are not placed over wood structural

Diaphragms constructed of wood structural


panels or untopped steel decking shall
also be permitted to be idealized as
flexible, provided four given conditions
are met

panel diaphragms except for


nonstructural toppings no greater than 1
inches thick.

2006 and 2009 IBC Section 1613.6.1


Definition for Flexible Diaphragm

2006 and 2009 IBC Section 1613.6.1


Definition for Flexible Diaphragm

Condition #2:

Condition #3:

Each line of vertical elements of the

Vertical elements of the lateral-force-

lateral force-resisting system complies

resisting system are light-framed walls

with the allowable story drift of Table

sheathed with wood structural panels

12.12-1.

rated for shear resistance or steel


sheets.

www.skghoshassociates.com
34

S. K. Ghosh Associates Inc.


2006 and 2009 IBC Section 1613.6.1
Definition for Flexible Diaphragm

ASCE 7-05 Section 12.3.1.2


Definition for Rigid Diaphragm
(Prescriptive)
12.3.1.2 Rigid Diaphragm

Condition #4:

Condition. Diaphragms of concrete slabs or

Portions of wood structural panel diaphragms that


cantilever beyond the vertical elements of the lateral-

concrete filled metal deck with span-to-depth

force-resisting system are designed in accordance

ratios of 3 or less in structures that have no

with [2006 IBC: Section 2305.2.5] [2009 IBC: Section

horizontal irregularities are permitted to be

4.2.5.2 of AF&PA SDPWS].

idealized as rigid.

2006 and 2009 IBC Section 1602.1


Definition for Rigid Diaphragm
(Calculation)

ASCE 7-05 Figure 12.3-1


Definition for Diaphragm

Diaphragm, rigid
De

A diaphragm is rigid for the purpose of

MAXIMUM DIAPHRAGM
DEFLECTION (MDD)

SEISMIC LOADING

AVERAGE DRIFT OF
VERTICAL ELEMENT
(ADVE)

distribution of story shear and torsional


S

moment when the lateral deformation of the


Note: Diaphragm is flexible If MDD > 2 (ADVE).

diaphragm is less than or equal to two times

Note: Per 2009 IBC Section 1602.1, diaphragm is


rigid if MDD 2(ADVE)

the average story drift.

Is any of the following true?

ASCE 7-05 Section 12.3.1


Definition for Diaphragms
12.3.1 Diaphragm Flexibility.Unless a

1- & 2-family dwelling of Vertical elements one of the following:


light-frame construction Steel braced frames
Composite steel and concrete braced
Four conditions in 2009
frames
IBC Section 1613.6.1
Concrete, masonry, steel or composite
are met
shear walls

diaphragm can be idealized as either flexible


START

or rigid in accordance with Sections 12.3.1.1,


12.3.1.2, or 12.3.1.3, the structural analysis

Is diaphragm wood
structural panels or
untopped steel
decking?

N
See Next Slide

shall explicitly include consideration of the


N

stiffness of the diaphragm (i.e. semirigid


modeling assumption).

Is diaphragm
Concrete slab?
Concrete filled metal deck?

www.skghoshassociates.com
35

Assume Flexible

Assume Rigid

N
Y

Y
Is span-to-depth ratio
3 and no horizontal
irregularities?

S. K. Ghosh Associates Inc.

Is MDD > 2 (ADVE)?


De
MAXIMUM DIAPHRAGM
DEFLECTION (MDD)

SEISMIC LOADING

AVERAGE DRIFT OF
VERTICAL ELEMENT
(ADVE)

Assume Rigid
Assume Flexible

2006 IBC 1605.4 Special Seismic


Load Combinations

PROVISION
#10

Section 1605.4 is deleted in its entirety in


the 2009 IBC.

Special Seismic Load


Combinations

SPECIAL SEISMIC LOAD COMBINATIONS


is replaced with
LOAD COMBINATIONS WITH OVERSTRENGTH FACTORS
of ASCE 7-05

Why Was 2006 IBC Section 1605.4


Deleted?

Why Was 2006 IBC Section 1605.4


Deleted?
To eliminate a disconnect between IBC and ASCE 7-

To eliminate a disconnect between IBC and

05 (cont.):

ASCE 7-05:

2006 IBC had separate, unique load

2006 IBC Section 1605.4 had one set of

combinations that were to be applied where

special seismic load combinations

specifically required.

applicable to both ASD and strength design.

ASCE 7-05 prescribes an equation for Em that

ASCE 7-05 has two sets of load combinations

is to be used in ASCE 7-05 Ch. 2 load

with overstrength factorsone for ASD and

combinations.

one for strength design.

www.skghoshassociates.com
36

S. K. Ghosh Associates Inc.


1605.4 Special Seismic Load
Combinations (2006 IBC)

12.4.3.2 Load Combinations with


Overstrength Factor (ASCE 7-05)
Basic Combinations for Strength Design

1.2D + f1L + Em

(Equation 16-22)

0.9D + Em

(Equation 16-23)

with Overstrength Factor


(1.2 + 0.2SDS)D + 0QE + L + 0.2S
(0.9 0.2SDS)D + 0QE + 1.6H

Em = 0 QE + 0.2 SDSD, while


E = QE + 0.2 SDSD

12.4.3.3 Load Combinations with


Overstrength Factor (ASCE 7-05)

12.4.3.2 Load Combinations with


Overstrength Factor (ASCE 7-05)

Where allowable stress design methodologies are


Basic Combinations for Allowable Stress Design

used, allowable stresses are permitted to be

with Overstrength Factor

determined using an allowable stress increase of

(1.0 + 0.14SDS)D + H + F + 0.7


0QE

1.2.

(1.0 + 0.105SDS)D + H + F + 0.525


0QE + 0.75L

This increase shall not be combined with increases

+ 0.75(Lr or S or R)

in allowable stresses or load combination


reductions except that combination with the

(0.6 0.14SDS)D + 0.7


0QE + H

duration of load increases permitted in AF&PA


NDS is permitted.

1617.1.2 Maximum Seismic Load


Effect, Em (2000, 2003 IBC)

What Takes the Place of Deleted


2006 IBC Section 1605.4?

Where allowable stress design


methodologies are used with the special

New language in 2009 IBC

load combinations of Section 1605.4,

Section 1605.1.

design strengths are permitted to be


determined using an allowable stress
increase of 1.7 .

www.skghoshassociates.com
37

S. K. Ghosh Associates Inc.


What Takes the Place of Deleted
2006 IBC Section 1605.4?

Q: A: for Load Combinations with


Overstrength Factor

1605.1 General. Buildings and other structures and


portions thereof shall be designed to resist:

Q: Section 1605.1 of the 2009 IBC requires

1. The load combinations specified in Section 1605.2,


1605.3.1 or 1605.3.2,
2. The load combinations specified in Chapters 18 through
23, and
3. The load combinations with overstrength factor
specified in Section 12.4.3.2 of ASCE 7 where required
by Section 12.2.5.2, 12.3.3.3 or 12.10.2.1 of ASCE 7.
With the simplified procedure of ASCE 7 Section 12.14,
the load combinations with overstrength factor of
Section 12. 14.3.2 of ASCE 7 shall be used.

buildings and other structures and portions


thereof to be designed to resist the load
combinations with overstrength factor
specified in Section 12.4.3.2 of ASCE 7-05
where required by Section 12.2.5.2, 12.3.3.3, or
12.10.2.1. Can you elaborate?

Q: A: for Load Combinations with


Overstrength Factor

Q: A: for Load Combinations with


Overstrength Factor

A:

Cantilever Column Systems

A:

12.2.5.2
SDC B - F

Elements Supporting
Discontinuous Walls or Frames

12.3.3.3
SDC B - F

Foundation and other


elements used to provide
overturning resistance at
the base of cantilever
column elements shall
have the strength to
resist the load
combinations with over
strength factor of Section
12.4.3.2.

Q: A: for Load Combinations with


Overstrength Factor

Q: A: for Load Combinations with


Overstrength Factor

www.skghoshassociates.com
38

S. K. Ghosh Associates Inc.


Q: A: for Load Combinations with
Overstrength Factor

A:

Collector Elements

Q: A: for Load Combinations with


Overstrength Factor

12.10.2.1 (SDC C - F)

Load Combinations with


Overstrength Factor

Thank You!!

Chapter 18 References:

For more information

1810.3.6.1 Splices of deep foundation elements,


SDC C through F

www.skghoshassociates.com

1810.3.9.4 Seismic reinforcement, SDC C and


above, Exception 3

Main Office
334 East Colfax Street, Unit E
Palatine, IL 60067
Phone: (847) 991-2700
Fax: (847) 991-2702
Email: skghoshinc@gmail.com

1810.3.11.2 Deep foundation element resistance to


uplift forces, SDC D through F
1810.3.12 Grade beams, SDC D through F

www.skghoshassociates.com
39

West Coast Office


43 Vantis Drive
Aliso Viejo, CA 92656
Phone: (949) 215-6560
Email: susandowty@gmail.com

2005EditionofASCE7
MinimumDesignLoadsforBuildingandOtherStructures
SupplementNo.2
Supplement No. 2 of ASCE 705 revises the minimum base shear equations for both
buildings and nonbuilding structures. The need for this change was indicated by the
results from the 75% Draft ofATC63, Quantification ofBuilding System Performance
andResponseParameters,whichindicatethattallbuildingsmayfailatanunacceptably
lowseismiclevelandthereforetheminimumbaseshearequationforbuildingsisbeing
restoredtothatwhichappearedinthe2002editionofASCE7.
Becausenonbuilding structuresnotsimilartobuildings have lowRvaluescomparedto
thespecialreinforcedconcretemomentframesstudiedinATC63,theASCE7standards
committeechosenottorestorethehighminimumbaseshearsfornonbuildingstructures
notsimilartobuildings found in ASCE702.In manycases,theseprevious minimum
baseshearsgavemanynonbuildingstructuresnotsimilartobuildingseffectiveRvalues
less than 1.0. Therefore, the Seismic Subcommittee believes that the minimum base
shear equation of 0.044SDSI used for buildings should also be applied to nonbuilding
structuresnotsimilartobuildings.
SupplementNo.2modifiesthreeequationsofthestandard(Eq.12.85,15.41and15.4
3)asshownbelow:

SupplementNo.2toASCE705:

Revise Equation 12.85 of Section 12.8.1.1 of ASCE 705 as shown


below:
12.8.1.1CalculationofSeismicResponseCoefficient. Theseismicresponsecoeffi
cient,Cs,shall bedeterminedinaccordancewithEq.12.82.
Cs =

SDS

(Eq.12.82)

R

I

where:
SDS= thedesignspectralresponseaccelerationparameterintheshortperiod
rangeasdeterminedfromSection11.4.4
R = theresponsemodificationfactorinTable12.21,and

I = theoccupancyimportancefactordeterminedinaccordancewithSection
11.5.1

Thevalueof Cs computedinaccordancewithEq.12.82neednotexceedthefollowing:
C s =

SD1
R
T
I

S T
C s = D1 L
R
T2
I

for T TL

(Eq.12.83)

for T > TL

(Eq.12.84)

Cs shallnotbelessthan
Cs =0.01 0.044SDSI0.01

(Eq.12.85)

Inaddition,forstructureslocatedwhereS1 isequaltoorgreaterthan0.6g,Csshallnotbe
lessthan
Cs =

0.5S1
R

I

(Eq.12.86)

whereIandRareasdefinedin Section12.8.1.1and
SD1= thedesignspectralresponseaccelerationparameterataperiodof1.0sec,
asdeterminedfromSection11.4.4
T
=
thefundamentalperiodofthestructure(sec)determinedinSection
12.8.2
TL
=
longperiodtransitionperiod(sec)determinedinSection11.4.5
S1
=
themappedmaximumconsideredearthquakespectral
responseaccelerationparameterdeterminedinaccordancewithSection
11.4.1

Revise Equations 15.41 and 15.42 of Section 15.4.1, item 2, as shown


below:
2. Fornonbuildingsystemsthathavean RvalueprovidedinTable15.42,the
seismicresponsecoefficient(Cs)shallnotbetakenlessthan
Cs =0.030.044SDSI 0.03

(15.41)

andfornonbuildingstructureslocatedwhereS1 0.6g,Cs shallnotbetakenless


than

Cs =

0.8S1
R

I

(15.42)

EXCEPTION:TanksandvesselsthataredesignedtoAWWAD100,AWWA
D103,API650AppendixE,andAPI620AppendixLasmodifiedbythis
standard,shallbesubjecttothelargeroftheminimumbaseshearvaluesdefined
bythereferencedocumentorthefollowingequations:
Cs =0.010.044SDSI 0.01

(15.43)

andfornonbuildingstructureslocatedwhereS1 0.6g,Cs shallnotbetakenless


than
Cs =

0.5S1
R

I

(15.44)

Minimumbaseshearrequirementsneednotapplytotheconvective(sloshing)
componentofliquidintanks.

Вам также может понравиться