1. Introduction
This specification is applied for the design, construction and test of cast
resin transformer. The cast resin transformer is used for power supply of
" VAN PHONG " project. If any statement specified here in is conflict
with the reference standard or other requirements, the statement governs
to the extent of such conflict.
2. Reference Standard
The transformer is designed, constructed and tested in accordance with
all applicable section of the latest issue of the following standard.
IEC 60076-11: Dry-type transformers
3. Service Conditions
The transformer is operated under the service conditions as follows;
Ambient Temperature: -25 Degree C ~ 40 Degree C
Altitude: Below 1000m above sea level
Installation: Indoor use
4. General Specification
NO.
Primary
Secondary
Rated
Capacity
[kVA] AN
22000
400-231
250
TR-3
TR-4
TR-1
Phase
TR-2
5. Structure
5.1 Core
3/6
Connection
Quantity
Dyn11
6. Accessory
Each transformer is provided with accessories as follows;
6.1 Name plate
6.2 Primary and secondary terminals
6.3 No voltage tap changer
6.4 Caution label
6.5 Lifting lugs
6.6 Earthing terminal
6.7 Cooling Fan & Digital Thermometer(P-300C) with
Three PT-100Sensors.
6.8 Wheels
7. Test
The following tests shall be performed.
4/6
8. Drawing List
ITEM
TR-1
TR-2
TR-3
Name Plate
MR534115B
Outline DWG.
MR435126WF
5/6
N
O
ITEM
Capacity (AN)
Phase
Frequency
TR-1
[kVA]
250
3
[Hz]
50
Primary voltage
[V]
22000
Secondary voltage
[V]
400-231
[V]
F23100F22550R22000-2145020900
Connection
Efficiency
[%]
98.3
[%]
1.5
10
[%]
2.0
11
[k]
HV
LV
100
100
12
[kV]
HV
LV
50
3
13
Impulse Voltage
HV
LV
125
-
14
Insulation Class
HV
LV
F
F
15
Percent Impedance
[%]
6.0
16
[W]
900
17
[W]
3,250
18
[dB]
53
19
Winding materials
-Y (Dyn11)