Вы находитесь на странице: 1из 6

Project No.

431330028

LS Cast Resin Transformer


Specification for Approve

Customer HOANG PHAP, VIETNAM


Project

VAN PHONG

Approved by
Name, Title
Signature
(Seal)
Date

August 19, 2013

Submitted by

Mold Transformer Design & Mfg. Team

Rev.

Date

Description

Designed by

Checked by

Approved by

00

2013-08-19

For Approval

D.K.Jeon

J.S.Oh

G.S.Jung

Southeast Asia Dept., Global Business Group, Seoul Korea


+82.2.2034-4864 sjbaik@www.lsis.biz

1/6

Project No. 431330028

- Contents Section

Item

Page

Introduction

Reference Standard

Service Conditions

General Specification

Structure

5.1

Core

5.2

Winding

5.3

No Voltage Tap Changer

Accessory

Test

7.1

Routine Test

7.2

Type Test

Drawing List

Technical Data Sheet

2/6

Project No. 431330028

1. Introduction
This specification is applied for the design, construction and test of cast
resin transformer. The cast resin transformer is used for power supply of
" VAN PHONG " project. If any statement specified here in is conflict
with the reference standard or other requirements, the statement governs
to the extent of such conflict.

2. Reference Standard
The transformer is designed, constructed and tested in accordance with
all applicable section of the latest issue of the following standard.
IEC 60076-11: Dry-type transformers

3. Service Conditions
The transformer is operated under the service conditions as follows;
Ambient Temperature: -25 Degree C ~ 40 Degree C
Altitude: Below 1000m above sea level
Installation: Indoor use

4. General Specification
NO.

Primary

Secondary

Rated
Capacity
[kVA] AN

22000

400-231

250

TR-3

TR-4

TR-1

Phase

Rated voltage [V]

TR-2

5. Structure
5.1 Core
3/6

Connection

Quantity

Dyn11

Project No. 431330028

Cold rolled oriented silicon steel sheet with excellent characteristics is


employed for the core. The cores are constructed from high quality, cold
rolled, grain orientated, stress relieved silicon steel laminations,
insulated on one side. Joints and clamping structure are design in such
a way to match the excellent characteristics of the core material. Core
legs are clamped with tape of adequate mechanical strength. The core
frame shall incorporate lifting lugs and be mounted on a base frame
having towing holes.
5.2 Winding
One of the most outstanding characteristics of LS Cast Resin
Transformer originates in the construction of the windings. The high and
low voltage windings are arranged coaxially on the core legs and
separated unit. Cooling ducts are provided between high and low
voltage windings to ensure effective heat dissipation.
5.3 No Voltage Tap Changer
LS Cast Resin Transformer are provided with a re-connectable link tap
changing device on the high voltage side of the transformer which will,
when operated with the transformer de-energized, change the ratio of
the transformer. The device is sturdy in construction and links are clearly
identifiable as to the tap selected.

6. Accessory
Each transformer is provided with accessories as follows;
6.1 Name plate
6.2 Primary and secondary terminals
6.3 No voltage tap changer
6.4 Caution label
6.5 Lifting lugs
6.6 Earthing terminal
6.7 Cooling Fan & Digital Thermometer(P-300C) with
Three PT-100Sensors.
6.8 Wheels

7. Test
The following tests shall be performed.
4/6

Project No. 431330028

7.1. Visual inspection


7.2. Measurement of winding resistance
7.3. Measurement of voltage ratio and check of phase displacement
7.4. Measurement of short-circuit impedance and load loss
7.5. Measurement of no-load loss and current
7.6. Separate-source AC withstand voltage test
7.7. Induced AC withstand voltage test
7.8. Efficiency and voltage regulation test
7.9. Partial discharge measurement
7.10. Sound Level measurement

8. Drawing List
ITEM

TR-1

TR-2

TR-3

Name Plate

MR534115B

Outline DWG.

MR435126WF

9. Technical Data Sheet


(P.F.=1.0, At 75, Based on AN)
Reference Std.: IEC60076-11

5/6

Project No. 431330028

N
O

ITEM

Capacity (AN)

Phase

Frequency

TR-1
[kVA]

250
3

[Hz]

50

Primary voltage

[V]

22000

Secondary voltage

[V]

400-231

Primary tap voltage (tolerance:0.5%)

[V]

F23100F22550R22000-2145020900

Connection

Efficiency

[%]

98.3

Percent exciting current at rated voltage

[%]

1.5

10

Regulation at full load

[%]

2.0

11

Winding Temperature Rise

[k]

HV
LV

100
100

12

Applied potential Test (1min)

[kV]

HV
LV

50
3

13

Impulse Voltage

HV
LV

125
-

14

Insulation Class

HV
LV

F
F

15

Percent Impedance

[%]

6.0

16

No load losses (tolerance:15%)

[W]

900

17

Load losses (tolerance:15%)

[W]

3,250

18

Sound level (at 1M)

[dB]

53

19

Winding materials

-Y (Dyn11)

[kV]

Copper (HV) / Copper (LV)

6/6

Вам также может понравиться