Академический Документы
Профессиональный Документы
Культура Документы
Voltage Regulation
Service continuity
Flexibility
Efficiency
Cost
Restoration of power supply
Voltage Standards
Statutory Limits as per section of IE
Rules, 1956
Type
Magnitude
Low
Voltage
Medium
Voltage
High
Voltage
Extra High
Voltage
Limits
under IE
Rule
6%
6%
+ 6% to
-9%
+ 10% to
-12.5%
As per IEGC
Maximum KV
IEGC
IE
RULE
+10%
400 KV 420
440
(+5%)
220 KV 245
245
(+10%)
132 KV 145
145
(+10%)
EHV
Voltage
Minimum KV
IEGC
IE
RULE
-12.5%
360
350
(-10%)
200
193
( -10%)
120
115
( -10%)
Frequency Standards
a)
Frequency
band
for
safe
operation
of
steam
turbines,adopted in IEGC =
49-50 Hz.
3 % statutory limit as per section
55 of IE Rule 1956.
Declared frequency of supply to
consumer :- Except with written
consent of consumer or with
previous sanction of the state
government, a supplier shall not
permit the frequency of an AC
supply to vary from the declared
frequency by more than 3%
b)
c)
2
3
4
5
6
network
Sub-Transmission lines
Distribution Substation
Primary feeders
Distribution Transformers
Secondary Feeders
Consumers Service Main
7
8
9
10
11
12
Fig. 1
Index for Fig.1
1. Bulk Power supply Source
2. Sub-Transmission Line
3. Distribution Sub- Station ( HT
Bus)
4. HT incomer
5. Distribution
SubStation
Transformer
6. LT incomer
7. Distribution Sub- Station ( LT
Bus)
8. Primary Feeder
9. Distribution Transformer
10. Incomer of Secondaries
11. Secondaries
12. Consumer Services
TYPES OF DISTRIBUTION
I. On the basis of current
i.
AC Distribution
ii. DC Distribution
II. On the basis of arrangement
i.
Radial System
ii. Parallel or Loop Circuit
iii. Interconnected system
2.1 Radial System
Basically for this system the
primary feeders (Distribution Feeders)
from distribution sub-station, distribute
loads directly to the consumers via
distribution transformers and secondary
feeders, as like shown in fig.2. It is
actually a system having a single path,
over which current flows a part or all the
way from sub-station to the consumer
premises.
2.1.1 Protection Control
The general control arrangement
has been shown in the fig.2. In actual
practice for such system fuse controls
are provided on both side of the
distribution transformers and on the
secondaries
(Sub-feeders).
Subtransmission
transformers,
Subtransmission feeders etc are provided
with breaker controls. The relaying
protections are also given for these
breakers.
The branch fuses, transformer
fuses, relaying protection are properly
time graded and co-coordinated, for
which fault on any circuit opens the
affected portion and results minimum
outage.
The main disadvantage of this
system is that, for the case of permanent
fault at the starting end (Sub-
iv.
Load Distributions
Topography
(
Physical
position of area loads)
Location and number of subtransmission lines ( Bulk
supplies )
Protection
and
system
flexibility
v.
calculation
at
different
bus/tie/substation etc
b) The inter tripping facility should also
be provided for each tie.
2.3 Inter Connected System
For this system each and every
centers (Distribution sub-station) are tied
with one or multiple ties. One or more
feeding sources are also given for
maintaining the system stability. One of
the typical interconnected systems has
been shown in Fig. 6.
2.3.1 Design Criteria
For designing this system the
following points are considered
1. Location, size and character of large
loads
2. Location, size and character of small
loads
3. Expected load growth of the area
4. Location of bulk power supplies
5. Location and capacity of existing
distribution circuits ( transformers,
sub-station and equipments )
6. Available site for sub-stations
7. Topography ( Available route for
distribution circuits)
2.3.2 Advantages:1. Voltage
regulation:
For
interconnection of sub stations,
proper voltages are obtained at the
consumers premises.
2. Consumer
outage:
Consumer
outage gets reduced. So reliability of
power supply increases. For fault on
any tie, the power gets extended
through other ties and avoids the
power interruption.
realization
on
the
Note:
For this fault the *transformer
protection relays if such provided also
take care to isolate transformer from the
supply.
E. Fault on outgoing primary feeder
The non-directional relay on the
corresponding feeder only actuates to
isolate the faulty feeder from the circuit.
F. Fault on Sub-Station Bus ( LT
Side )
Occurrence of bus fault is very
rare. If this happens then the entire
feeders connected to this bus will be
affected. So, the load areas depending
upon the out going feeders will be
suffered with outage of power supply
this difficult can not be easily overcome
by the procedure as described in fig. 6.
By the use of bus- sectionaliser,
the faulty portion of the bus can be
isolated to extend the power supply
through healthy part of the bus. The use
of multi-bus system can also solve this
type of problem. This spare bus is
utilized to extend the power through out
going feeders to the consumers.
of
the
type
of
BUS
BAR
CONCLUSION
Interconnected
distribution
system is relatively advantageous as
compared to the other system. The relay
coordination on the basis of power flow
study becomes difficult for this
interconnected distribution system