Вы находитесь на странице: 1из 4

Engineering Recommendation G83

Eaton Phoenixtec MMPL Co. Ltd.

1
APPENDIX 4

TYPE VERIFICATION TEST SHEET

SSEG DETAILS
SSEG Type reference: Eaton ISG1I-4000/1 , ISG1O-4000/1 , ISG1I-4000/1-I , ISG1O-4000/1-I
SSEG Technology (As per Annex): Photo-voltaic
Manufacturer:

Tel: (+886-2)66006688

Address:

Eaton Phoenixtec MMPL

Fax: (+886-2)66068703

No.93 Shin Hu 3rd RD., Neihu, Taipei, 114


Taiwan, R.O.C.

Co., LTD.

Technical file reference No:


Maximum export capability:
Output: 230Vac, 50Hz, 4000W, 17.4A
(SSEG rating less parasitic load)

TEST HOUSE DETAILS


Name and address of test
house

Eaton Phoenixtec MMPL Co., LTD.

Telephone number

(+886-2)66006688

Facsimile number

(+886-2)66068703

E-mail address

YCLiu@eaton.com

No.93 Shin Hu 3rd RD., Neihu, Taipei, 114 Taiwan, R.O.C.

TEST DETAILS
Date of test

2011.12.14

Name of tester

Davis Cheng

Signature of tester
Test location if different from
above

Same as above

Engineering Recommendation G83

Eaton Phoenixtec MMPL Co. Ltd.

2
POWER QUALITY

Harmonic
Limit *
Test
value

nd

rd

Harmonic current emissions (A)


h
h
h
h
5t
7t
9t
11t

13t

15t n40t
h

1.08

2.3

1.14

0.77

0.4

0.33

0.21

0.15 (15/n)

0.107

0.224

0.221

0.173

0.163

0.147

0.131

0.096 max.

* Maximum permissible harmonic current As per BS EN 61000-3-2 Class A


Voltage Fluctuations and Flicker
Limit *
Test
value

Starting

Stopping

Running

4%

4%

Pst = 1.0

Plt = 0.65

-0.17

-0.17

0.16

0.16

* Maximum permissible voltage fluctuation (expressed as a percentage of nominal voltage at 100%


power) and flicker. As per BS EN 61000-3-3.

DC injection
G83/1-1
Limit
Test level
Test value #

Power factor

0.25% rated current, tested at three 0.95 lag- 0.95 lead at three voltage
power levels * *
levels
10%

55%

100%

212 V

230 V

248 V

-0.0154

0.0070

0.0070

0.9969

0.9959

0.9948

* Indicative values are shown for minimum, medium and maximum power levels.
# Insert maximum value of dc injection and worst case PF value recorded during testing.

UNDER / OVER FREQUENCY TESTS


Under Frequency
Parameter

Over Frequency

Frequency

Time

Frequency

Time

G83/1-1 Limit

47 Hz

0.5 sec *

50.5 Hz

0.5 sec *

Actual setting

47 Hz

0.08 sec

50.5 Hz

0.08 sec

Trip value

47 Hz

0.096 sec

50.5 Hz

0.167 sec

Engineering Recommendation G83

Eaton Phoenixtec MMPL Co. Ltd.

3
UNDER / OVER VOLTAGE TESTS
Under Voltage
Parameter

Over Voltage

Voltage

Time

Voltage

Time

G83/1-1 Limit

207 V

1.5 sec *

264 V

1.5 sec *

Actual setting

207 V

0.08 sec

264.5 V

0.08 sec

Trip value

207 V

0.078 sec

264.5V

0.077 sec

* For SSEG units that can withstand being re-energised from a source that is 180 degrees out of phase
with the SSEG output, it is permissible to extend the operating time of the interface protection to 5.0
seconds, as described in 5.3.1 Table 1.

LOSS OF MAINS TEST


Method used

Frequency shift with resonant circuit

Output power level *

10%

55%

100%

Trip setting

5 sec

5 sec

5 sec

Trip value

0.038 Sec

1.321 Sec

1.083 Sec

* Indicative values are shown for minimum, medium and maximum power levels.

RECONNECTION TIMES
Reconnection Time

Under / Over
Voltage

Under / Over
Frequency

Loss of Mains

Minimum value

180 seconds

180 seconds

180 seconds

Actual Setting

180 seconds

180 seconds

180 seconds

Recorded value

180 seconds

180 seconds

180 seconds

FAULT LEVEL CONTRIBUTION


SSEG Short Circuit Test
This test should determine the value of short circuit current at the SSEG terminals as described in
clause 5.7 in Engineering Recommendation G83/1-1.

Eaton Phoenixtec MMPL Co. Ltd.

Engineering Recommendation G83


4

For rotating machines and linear piston machines the test should produce a 0 2.0 second plot of
the short circuit current as seen at the SSEG terminals.
SSEG Short Circuit Parameters
Parameter

Symbol

Value

Peak short-circuit current

Ip

N/A

Initial value of aperiodic component

N/A

Initial symmetrical short-circuit current *

Ik

N/A

Decaying (aperiodic) component of short-circuit


current *

iDC

N/A

Reactance / Resistance Ratio of Source *

x/R

N/A

* Values for these parameters should be provided where the short circuit duration is sufficiently
long to enable interpolation of the plot.
Note: PV inverter automatically considered complying with this without test.

SELF MONITORING SOLID STATE SWITCHING


Test
It has been verified that in the event of the solid state switching device
failing to disconnect the SSEG, the voltage on the output side of the

Yes / No
N/A

switching device is reduced to a value below 50 volt within 0.5 sec.


COMMENTS
The DC injection of the PV inverter may be drifted as per ambient (working) temperature of the
equipment. The value shown above was measured at an ambient temperature of 25 and 20 min
operation. It is noted that the DC injection may be measured over 0.25% AC rated current when
the operation time is long enough or the ambient temperature is varied. If this is concerned, an
installation of a transformer on the ac side of the inverter may be required.