Академический Документы
Профессиональный Документы
Культура Документы
1
APPENDIX 4
SSEG DETAILS
SSEG Type reference: Eaton ISG1I-4000/1 , ISG1O-4000/1 , ISG1I-4000/1-I , ISG1O-4000/1-I
SSEG Technology (As per Annex): Photo-voltaic
Manufacturer:
Tel: (+886-2)66006688
Address:
Fax: (+886-2)66068703
Co., LTD.
Telephone number
(+886-2)66006688
Facsimile number
(+886-2)66068703
E-mail address
YCLiu@eaton.com
TEST DETAILS
Date of test
2011.12.14
Name of tester
Davis Cheng
Signature of tester
Test location if different from
above
Same as above
2
POWER QUALITY
Harmonic
Limit *
Test
value
nd
rd
13t
15t n40t
h
1.08
2.3
1.14
0.77
0.4
0.33
0.21
0.15 (15/n)
0.107
0.224
0.221
0.173
0.163
0.147
0.131
0.096 max.
Starting
Stopping
Running
4%
4%
Pst = 1.0
Plt = 0.65
-0.17
-0.17
0.16
0.16
DC injection
G83/1-1
Limit
Test level
Test value #
Power factor
0.25% rated current, tested at three 0.95 lag- 0.95 lead at three voltage
power levels * *
levels
10%
55%
100%
212 V
230 V
248 V
-0.0154
0.0070
0.0070
0.9969
0.9959
0.9948
* Indicative values are shown for minimum, medium and maximum power levels.
# Insert maximum value of dc injection and worst case PF value recorded during testing.
Over Frequency
Frequency
Time
Frequency
Time
G83/1-1 Limit
47 Hz
0.5 sec *
50.5 Hz
0.5 sec *
Actual setting
47 Hz
0.08 sec
50.5 Hz
0.08 sec
Trip value
47 Hz
0.096 sec
50.5 Hz
0.167 sec
3
UNDER / OVER VOLTAGE TESTS
Under Voltage
Parameter
Over Voltage
Voltage
Time
Voltage
Time
G83/1-1 Limit
207 V
1.5 sec *
264 V
1.5 sec *
Actual setting
207 V
0.08 sec
264.5 V
0.08 sec
Trip value
207 V
0.078 sec
264.5V
0.077 sec
* For SSEG units that can withstand being re-energised from a source that is 180 degrees out of phase
with the SSEG output, it is permissible to extend the operating time of the interface protection to 5.0
seconds, as described in 5.3.1 Table 1.
10%
55%
100%
Trip setting
5 sec
5 sec
5 sec
Trip value
0.038 Sec
1.321 Sec
1.083 Sec
* Indicative values are shown for minimum, medium and maximum power levels.
RECONNECTION TIMES
Reconnection Time
Under / Over
Voltage
Under / Over
Frequency
Loss of Mains
Minimum value
180 seconds
180 seconds
180 seconds
Actual Setting
180 seconds
180 seconds
180 seconds
Recorded value
180 seconds
180 seconds
180 seconds
For rotating machines and linear piston machines the test should produce a 0 2.0 second plot of
the short circuit current as seen at the SSEG terminals.
SSEG Short Circuit Parameters
Parameter
Symbol
Value
Ip
N/A
N/A
Ik
N/A
iDC
N/A
x/R
N/A
* Values for these parameters should be provided where the short circuit duration is sufficiently
long to enable interpolation of the plot.
Note: PV inverter automatically considered complying with this without test.
Yes / No
N/A