CONTRACTORS GUIDE
YCAL 15 to 65 TONS
AIR COOLED SCROLL CHILLER
AIR-COOLED
YCAL
15 TO 40
Pages 12-23
YCAL
41 TO 65
Pages 24-29
CHILLER REPLACEMENT
CONTRACTORS GUIDE
YLAA
70 TO 90
Pages 36-43
YLAA
91 TO 130
YCAL 15 to 65 TONS
AIR COOLED SCROLL CHILLER
Pages 44-53
YLAA
131 TO 175
Pages 54-63
YVAA
150 TO 200
Pages 68-73
YVAA
201 TO 500
Pages 74-85
WATER COOLED
YCWL
50 TO 90
Pages 92-109
YCWL
91 TO 130
Pages 110-117
YCWL
131 TO 200
Pages 118-125
Unit Benefits
Air-cooled Scroll Chillers
Air-cooled chillers using scroll-compressor technology ranging from 15 to 175 tons. Standard feature include:
Air-cooled chillers using YORK VSD Screw technology ranging from 150 to 500 tons. Standard features include:
JOHNSON CONTROLS
1-800-JCI-RNTL (1800-524-7685)
www.johnsoncontrols.com/rental
Your brand HVAC parts source for air cooled, water cooled,
and absorption chillers. We are able to ship out the HVAC
parts that you need as soon as possible. If you need items
urgently (for a hospital, school or other critical application) we
can prioritize this requirement and work with our supplier for
expediting. If you have a need for replacement parts please
contact the JCI Parts Department at :
jOHNSON CONTROLS
1-800-932-1701
$2,100
$3,500
OPTION II
Use Energy Performance to Differentiate Your Replacement Offering
The YORK Latitude variable speed air-cooled chiller allows you as the installing contractor to offer your customers
a replacement alternative that is as much as 25% more efficient than existing chillers.
For Example: Your customer wants to replace an existing 350-ton chiller. You as the installing contractor can
offer either a standard efficiency chiller or the YORK optimized variable speed chiller. The optimized offering will
save the customer over $17,000/year*. With this level of annual savings, you can offer your customer a $21,250
additive alternate with a 1.25 year simple payback. The price premium for the optimized offering is $7,000, which
allows you to capture $14,250 of additional gross profit.
*see the next page for the Average Energy Cost (AEC) calculation
JOHNSON CONTROLS
Input Variables:
Example
Input Variables:
IPLV Existing or Base Bid = 15.4 EER
IPLV New = 19.0 EER
FLT Existing or Base Bid = 350 tons
FLT New = 350 tons
RATE = $0.1016/kWh
OH = 5000 hrs
Calculations:
AEC Existing or Base Bid = (IPLV) x (ACL) x (RATE) x (OH)
AEC Existing or Base Bid = (12 / (IPLV EER)) x ((FLT) x (0.58)) x (RATE) x (OH)
AEC Existing or Base Bid = (12 / 15.4 EER) x (350 tons x 0.58) x ($0.1016/kWh) x (5000 hrs)
AEC Existing or Base Bid = $80,356.36
AEC New = (IPLV) x (ACL) x (RATE) x (OH)
AEC New = (12 / (IPLV EER)) x ((FLT) x (0.58)) x (RATE) x (OH)
AEC New = (12 / 19.0 EER) x (350 tons x 0.58) x ($0.1016/kWh) x (5000 hrs)
AEC New = $65,130.95
Annual Savings = AEC Existing or Base Bid AEC New
Annual Savings = $80,356.36 - $65,130.95
Annual Savings = $15,225.41 / year
jOHNSON CONTROLS
JOHNSON CONTROLS
YCAL
15 to 65 Tons
Air Cooled Scroll Chiller
jOHNSON CONTROLS
JOHNSON CONTROLS
YCAL Rigging
WARNING To ensure warranty coverage, this equipment must be commissioned and serviced
by an authorized Johnson Controls Service Mechanic or a qualified service person experienced in
chiller installation. Installation must comply with all applicable codes, particularly in regard to electrical wiring and other safety elements such as relief valves, HP cutout settings, design working
pressures, and ventilation requirements consistent with the amount and type of refrigerant charge.
Lethal voltages exist within the control panels. Before servicing, open and tag all disconnect
switches.
Installation Check List
The following items must be checked before placing the units in operation.
1.Inspect the unit for shipping damage.
2. Rig Unit using spreader bars.
3.Open the unit only to install water piping system. Do not remove protective covers from water connections
until piping is ready for attachment. Check water piping to ensure cleanliness.
4. Pipe unit using good piping practice (see ASHRAE handbook section 215 and 195).
5.Check to see that the unit is installed and operated within limitations (Refer to Operational and Voltage
Limitations located in Section 1 of the YCAL Operations and Maintenance Guide [Form 150.62-NM8]).
The following pages outline detailed procedures to be followed to install and startup the chiller.
Handling
These units are shipped as completely assembled units containing full operating charge, and care should be taken to
avoid damage due to rough handling.
WARNING The unit should be lifted by inserting hooks through the holes provided in the unit
base rails. Spreader bars should be used to avoid crushing the unit frame rails with lifting chains.
Inspection
Immediately upon receiving the unit, it should be inspected for possible damage which may have occurred during transit. If damage is
evident, it should be noted in the carriers freight bill. A written request
for inspection by the carriers agent should be made at once. See
Instruction manual, Form 50.15-NM for more information and details.
Location and Clearances
These units are designed for outdoor installations on ground level,
rooftop, or beside a building. Location should be selected for minimum sun exposure and to insure adequate supply of fresh air for the
condenser. The units must be installed with sufficient clearances for
air entrance to the condenser coil, for air discharge away from the
condenser, and for servicing access.
In installations where winter operation is intended and show accumulations are expected, additional height must be provided to ensure
normal condenser air flow.
Clearances are listed under Dimensions in Section 1 of the YCAL
Operations and Maintenance Guide form 150.62-NM8.
jOHNSON CONTROLS
10
JOHNSON CONTROLS
PACKAGE DESCRIPTION:
Cooler:
Compressors:
Suction-gas cooled, hermetic scroll compressors
Large internal volume and oil reservoir provides
greater liquid tolerance
Crankcase heaters for extra protection against
liquid migration
Condenser:
Low noise, direct drive, maximum efficiency fans
with corrosion resistant aluminum hub and composite blades; statically and dynamically balanced
Totally enclosed air over (TEAO) type fan motors,
current protected and permanently sealed
Seamless, internally enhanced copper fin & tube
coils arranged in staggered rows; mechanically
expanded to full-height aluminum fins
Design Working Pressure 650 PSIG
Integral subcooling included
jOHNSON CONTROLS
11
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0019EE46
15.4
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
54.0
44.0
37.0
6.3
Water
0.00010
3.3
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)
95.0
0
25.0
115.0
Electrical Data
2
1
18.6/18.6
114.0/114.0
2/1.3
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.0 / 2.9
14.6 / 4.3
1454
1481
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
44.9
60
50
60
50
60
1
(1)#14 - #2/0
39.8
114.0
Across the Line
Notes:
Compressor kW
Total Fan kW
Total kW
17.6
1.0
18.6
Load %
100.0
50.0
12
Ambient (F)
95.0
70.2
Compressor kW
17.6
6.3
Unit Efficiency
10.0 / 2.9
16.0 / 4.7
JOHNSON CONTROLS
jOHNSON CONTROLS
LEFT END
44 5/16"
BASE WIDTH
8 5/16"
18 3/4"
11"
BOTTOM OF PANEL
VIEW B-B
7/8" TYP.
8 5/16"
2" VICTAULIC CONN (TYP)
LIQUID OUT
11 5/8"
PRODUCT DRAWING
2 1/4"
46 1/16"
45 1/4"
3 15/16"
3 1/4"
6 3/4"
13 3/4"
38 3/16"
2 1/4"
3 3/8"
CONTROL
PANEL
R-410A CHILLER
C
G
ORIGIN
6 1/8"
CONTROL
PANEL
44 3/8"
END
END CAP
WIDTH
32 1/8"
1 1/16"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 1,454, OPERATING - 1,481.
3. CENTER OF GRAVITY FROM ORIGIN: X= 58.6", Y= 22.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
44 1/2"
15 5/8"
9 1/16"
374
FRONT VIEW
109 3/16"
74 1/2"
97 1/8"
5"
1 1/16"
COMPR
END
340
365
TOP VIEW
Date :
Rev. Date :
Form : 150.64-EG1
Dwg. Lev. : 03/05
Dwg. Scale : NTS
1"
17"
2 1/4"
402
MODEL: YCAL0019EE46
AHRI CAPACITY 15.4 TONS
YCAL
15 TO 40
13
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0022EE46
18.7
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)
54.0
44.0
44.8
4.9
Water
0.00010
3.6
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)
95.0
0
25.0
115.0
Electrical Data
2
1
20.0/20.0
125.0/125.0
2/1.3
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.0 / 2.9
15.5 / 4.5
1567
1597
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
48.1
60
60
60
60
60
1
(1)#14 - #2/0
42.6
125.0
Across the Line
48.1
Notes:
Compressor kW
Total Fan kW
Total kW
21.5
1.0
22.5
Load %
100.0
50.0
14
Ambient (F)
95.0
72.1
Compressor kW
21.5
7.2
Unit Efficiency
10.0 / 2.9
16.9 / 5.0
JOHNSON CONTROLS
jOHNSON CONTROLS
LEFT END
44 5/16"
BASE WIDTH
8 5/16"
18 3/4"
11"
BOTTOM OF PANEL
VIEW B-B
7/8" TYP.
8 5/16"
2" VICTAULIC CONN (TYP)
LIQUID OUT
11 5/8"
PRODUCT DRAWING
2 1/4"
46 1/16"
45 1/4"
3 15/16"
3 1/4"
6 3/4"
13 3/4"
38 3/16"
2 1/4"
3 3/8"
CONTROL
PANEL
R-410A CHILLER
C
G
ORIGIN
6 1/8"
CONTROL
PANEL
44 3/8"
END
END CAP
WIDTH
32 1/8"
1 1/16"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 1,567, OPERATING - 1,597.
3. CENTER OF GRAVITY FROM ORIGIN: X= 58.5", Y= 22.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
44 1/2"
15 5/8"
9 1/16"
403
FRONT VIEW
109 3/16"
74 1/2"
97 1/8"
5"
1 1/16"
COMPR
END
366
394
TOP VIEW
Date :
Rev. Date :
Form : 150.64-EG1
Dwg. Lev. : 03/05
Dwg. Scale : NTS
1"
17"
2 1/4"
434
MODEL: YCAL0022EE46
AHRI CAPACITY 18.7 TONS
YCAL
15 TO 40
15
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0028EE46
25.6
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)
54.0
44.0
61.3
8.9
Water
0.00010
2.5
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)
95.0
0
25.0
115.0
Electrical Data
2
1
23.1/26.9
150.0/187.0
2/4.0
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.1 / 3.0
13.4 / 3.9
1798
1835
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
64.7
100
80
90
80
90
1
(1)#14 - #2/0
58.0
187.0
Across the Line
Notes:
Compressor kW
Total Fan kW
Total kW
27.5
3.0
30.5
Load %
100.0
50.8
16
Ambient (F)
95.0
71.9
Compressor kW
27.5
11.7
Unit Efficiency
10.1 / 3.0
14.3 / 4.2
JOHNSON CONTROLS
jOHNSON CONTROLS
15 1/2"
49 1/4"
LEFT END
44 5/16"
BASE WIDTH
19"
8 5/16"
10 3/4"
8 1/2"
PRODUCT DRAWING
VIEW B-B
BOTTOM OF PANEL
7/8" TYP.
8 5/16"
2" VICTAULIC CONN (TYP)
LIQUID OUT
2 1/4"
50 1/16"
3 15/16"
3 1/4"
6 3/4"
2 1/4"
3 3/8"
CONTROL
PANEL
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
17 3/4"
42 1/8"
C
G
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
1 1/16"
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
CONTROL
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
PANEL
44 3/8"
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
END
END CAP
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
WIDTH
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
32 1/8"
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
6 1/8"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 1,798, OPERATING - 1,835.
3. CENTER OF GRAVITY FROM ORIGIN: X= 63.1", Y= 22.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
ORIGIN
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
Y
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
1"
17"
TOP VIEW
50 1/2"
15 5/8"
9"
Date :
Rev. Date :
Form : 150.64-EG1
Dwg. Lev. : 03/05
Dwg. Scale : NTS
FRONT VIEW
118 5/16"
105 1/16"
80 1/2"
5"
1 1/16"
COMPR
END
423
456
R-410A CHILLER
460
1 7/8"
495
MODEL: YCAL0028EE46
AHRI CAPACITY 25.6 TONS
YCAL
15 TO 40
17
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0033EE46
28.6
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)
54.0
44.0
68.4
11.0
Water
0.00010
5.2
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)
95.0
0
25.0
115.0
Electrical Data
2
1
26.9/26.9
187.0/187.0
2/4.0
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.5 / 3.1
14.5 / 4.2
2034
2077
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
66.7
100
80
90
80
90
1
(1)#14 - #2/0
61.8
187.0
Across the Line
Notes:
Compressor kW
Total Fan kW
Total kW
29.6
3.0
32.6
Load %
100.0
50.0
18
Ambient (F)
95.0
70.0
Compressor kW
29.6
11.2
Unit Efficiency
10.5 / 3.1
15.7 / 4.6
JOHNSON CONTROLS
jOHNSON CONTROLS
15 1/2"
49 1/4"
LEFT END
44 5/16"
BASE WIDTH
19"
8 5/16"
10 3/4"
8 1/2"
PRODUCT DRAWING
VIEW B-B
BOTTOM OF PANEL
7/8" TYP.
8 5/16"
2" VICTAULIC CONN (TYP)
LIQUID OUT
2 1/4"
50 1/16"
3 15/16"
3 1/4"
6 3/4"
2 1/4"
3 3/8"
CONTROL
PANEL
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
17 3/4"
42 1/8"
C
G
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
1 1/16"
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
CONTROL
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
PANEL
44 3/8"
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
END
END CAP
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
WIDTH
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
32 1/8"
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
6 1/8"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 2,034, OPERATING - 2,077.
3. CENTER OF GRAVITY FROM ORIGIN: X= 67.1", Y= 23.1" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
ORIGIN
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
Y
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
1"
17"
TOP VIEW
50 1/2"
15 5/8"
9"
Date :
Rev. Date :
Form : 150.64-EG1
Dwg. Lev. : 03/05
Dwg. Scale : NTS
FRONT VIEW
118 5/16"
105 1/16"
80 1/2"
5"
1 1/16"
COMPR
END
516
565
R-410A CHILLER
475
1 7/8"
520
MODEL: YCAL0033EE46
AHRI CAPACITY 28.6 TONS
YCAL
15 TO 40
19
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0043EE46
37.2
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)
54.0
44.0
89.2
6.1
Water
0.00010
2.7
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)
95.0
0
25.0
115.0
Electrical Data
2
20.0/20.0
125.0/125.0
2/3.4
1
20.0/20.0
125.0/125.0
2/3.4
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.1 / 3.0
14.5 / 4.2
2942
2967
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
99.2
150
110
110
110
110
1
(1)#14 - #2/0
93.7
125.0
Across the Line
Notes:
Compressor kW
Total Fan kW
Total kW
38.8
5.6
44.4
Load %
100.0
75.0
50.0
25.0
20
Ambient (F)
95.0
83.3
69.0
55.0
Compressor kW
38.8
24.4
14.2
6.6
Unit Efficiency
10.1 / 3.0
12.0 / 3.5
14.9 / 4.4
17.3 / 5.1
JOHNSON CONTROLS
jOHNSON CONTROLS
46 15/16"
LIQUID IN
LEFT END
45 1/8"
90 1/4" BASE WIDTH
LIQUID OUT
3" VICTAULIC (TYP)
VIEW B-B
BOTTOM OF PANEL
7/8" TYP.
12 5/8"
25 3/16"
9 7/8"
15 3/4"
ELECTRICAL ACCESS
PANEL
PRODUCT DRAWING
47 3/4"
3 15/16"
6 3/4"
3 1/4"
C
G
15 1/16"
13 5/8"
25 3/8"
5 5/16"
18 1/2"
ORIGIN
45 1/8"
COOLER
END
1 1/16"
90 9/16"
END CAP
WIDTH
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 2,942, OPERATING - 2,967.
3. CENTER OF GRAVITY FROM ORIGIN: X= 59.6", Y= 43.6" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
925
862
CONTROLPANEL
TOP VIEW
Date :
Rev. Date :
Form : 150.62-EG1
Dwg. Lev. : 01/02
Dwg. Scale : NTS
13 15/16"
611
569
9 13/16"
1 1/16"
COIL
END
FRONT VIEW
144 13/16"
38"
9 13/16"
MODEL: YCAL0043EE46
AHRI CAPACITY 37.2 TONS
YCAL
15 TO 40
21
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0046EE46
39.4
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)
54.0
44.0
94.5
5.1
Water
0.00010
3.5
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)
95.0
0
25.0
115.0
Electrical Data
2
20.0/20.0
125.0/125.0
2/3.4
1
20.7/20.7
125.0/125.0
2/3.4
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.2 / 3.0
14.7 / 4.3
2968
3000
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
100.8
150
110
110
110
110
1
(1)#14 - #2/0
95.1
125.0
Across the Line
Notes:
Compressor kW
Total Fan kW
Total kW
41.0
5.6
46.6
Load %
100.0
73.2
50.0
23.2
22
Ambient (F)
95.0
82.9
69.1
55.0
Compressor kW
41.0
25.2
14.9
6.5
Unit Efficiency
10.2 / 3.0
12.3 / 3.6
15.2 / 4.5
17.5 / 5.1
JOHNSON CONTROLS
jOHNSON CONTROLS
46 15/16"
45 1/8"
LEFT END
12 5/8"
PRODUCT DRAWING
15 3/4" 25 3/16"
ELECTRICAL ACCESS
PANEL
9 7/8"
LIQUID IN
LIQUID OUT
3" VICTAULIC (TYP)
VIEW B-B
BOTTOM OF PANEL
7/8" TYP.
47 3/4"
3 15/16"
6 3/4"
3 1/4"
X
15 1/16"
13 5/8"
25 3/8"
5 5/16"
C
G
16 11/16"
ORIGIN
45 1/8"
COOLER
END
1 1/16"
90 9/16"
END CAP
WIDTH
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 2,968, OPERATING - 3,000.
3. CENTER OF GRAVITY FROM ORIGIN: X= 59.2", Y= 43.5" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
941
875
CONTROLPANEL
TOP VIEW
Date :
Rev. Date :
Form : 150.62-EG1
Dwg. Lev. : 01/02
Dwg. Scale : NTS
13 15/16"
613
570
9 13/16"
1 1/16"
COIL
END
FRONT VIEW
144 13/16"
38"
9 13/16"
MODEL: YCAL0046EE46
AHRI CAPACITY 39.4 TONS
YCAL
15 TO 40
23
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0052EE46
46.2
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)
54.0
44.0
110.8
9.2
Water
0.00010
3.5
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)
95.0
0
25.0
115.0
Electrical Data
2
23.1/23.1
150.0/150.0
2/4.0
1
23.1/23.1
150.0/150.0
2/4.0
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.2 / 3.0
15.1 / 4.4
3170
3208
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
114.2
150
125
125
125
125
1
(1)#14 - #2/0
108.4
150.0
Across the Line
Notes:
Compressor kW
Total Fan kW
Total kW
47.9
6.7
54.6
Load %
100.0
75.0
50.0
25.0
24
Ambient (F)
95.0
83.4
69.5
55.0
Compressor kW
47.9
30.7
17.6
7.8
Unit Efficiency
10.2 / 3.0
12.0 / 3.5
15.2 / 4.5
19.1 / 5.6
JOHNSON CONTROLS
jOHNSON CONTROLS
61 7/8"
45 1/8"
LIQUID OUT
3" VICTAULIC (TYP)
VIEW B-B
BOTTOM OF PANEL
7/8" TYP.
12 5/8"
25 3/16"
9 13/16"
15 3/4"
ELECTRICAL ACCESS
PANEL
LIQUID IN
PRODUCT DRAWING
62 5/8"
3 15/16"
6 3/4"
3 1/4"
X
15 1/16"
13 5/8"
25 3/8" B
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
C
G
18 1/2"
ORIGIN
9 13/16"
TOP VIEW
Date :
Rev. Date :
Form : 150.62-EG1
Dwg. Lev. : 01/02
Dwg. Scale : NTS
FRONT VIEW
144 13/16"
713
623
1 1/16"
COIL
END
13 15/16"
9 13/16"
CONTROL
PANEL
5 5/16"
38"
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
873
1 1/16"
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
COOLER
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
END
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
90 9/16"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
END CAP
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
WIDTH
2. WEIGHTS (LB):SHIPPING - 3,170, OPERATING - 3,208.
3. CENTER OF GRAVITY FROM ORIGIN: X= 61.9", Y= 42.2" .
45 1/8"
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
999
MODEL: YCAL0052EE46
AHRI CAPACITY 46.2 TONS
YCAL
41 TO 65
25
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0056EE46
56.2
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)
54.0
44.0
134.7
9.9
Water
0.00010
4.1
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)
95.0
0
25.0
115.0
Electrical Data
2
26.9/26.9
187.0/187.0
2/4.0
1
26.9/26.9
187.0/187.0
2/4.0
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.1 / 3.0
14.7 / 4.3
3206
3244
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
130.3
150
150
150
150
150
1
(1)#14 - #2/0
123.6
187.0
Across the Line
Notes:
Compressor kW
Total Fan kW
Total kW
60.3
6.7
67.0
Load %
100.0
75.0
50.0
25.0
26
Ambient (F)
95.0
83.6
69.4
55.0
Compressor kW
60.3
38.8
22.6
10.2
Unit Efficiency
10.1 / 3.0
12.0 / 3.5
14.9 / 4.4
18.1 / 5.3
JOHNSON CONTROLS
jOHNSON CONTROLS
61 7/8"
45 1/8"
LIQUID OUT
3" VICTAULIC (TYP)
VIEW B-B
BOTTOM OF PANEL
7/8" TYP.
PRODUCT DRAWING
15 3/4"
12 5/8"
9 7/8"
25 3/16"
ELECTRICAL ACCESS
PANEL
LIQUID IN
62 5/8"
3 15/16"
6 3/4"
3 1/4"
X
15 1/16"
28 9/16"
25 3/8" B
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
C
G
16 11/16"
ORIGIN
9 13/16"
TOP VIEW
Date :
Rev. Date :
Form : 150.62-EG1
Dwg. Lev. : 01/02
Dwg. Scale : NTS
FRONT VIEW
144 13/16"
715
625
1 1/16"
COIL
END
14"
9 13/16"
CONTROL
PANEL
5 3/16"
38"
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
889
1 1/16"
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
COOLER
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
END
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
90 9/16"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
END CAP
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
WIDTH
2. WEIGHTS (LB):SHIPPING - 3,206, OPERATING - 3,244.
3. CENTER OF GRAVITY FROM ORIGIN: X= 61.5", Y= 42.2" .
45 1/8"
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
1,015
MODEL: YCAL0056EE46
AHRI CAPACITY 56.2 TONS
YCAL
41 TO 65
27
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCAL0066EE46
66.1
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)
54.0
44.0
158.4
8.3
Water
0.00010
4.9
Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)
95.0
0
25.0
115.0
Electrical Data
2
26.9/26.9
187.0/187.0
2/1.3
1
33.9/33.9
250.0/250.0
2/4.0
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
10.1 / 3.0
15.1 / 4.4
4097
4142
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)
146.0
200
175
175
175
175
1
(1)#6 - 350
137.6
250.0
Across the Line
Notes:
Compressor kW
Total Fan kW
Total kW
72.1
6.7
78.8
Load %
100.0
71.5
50.0
21.5
28
Ambient (F)
95.0
82.6
69.3
55.0
Compressor kW
72.1
42.2
26.6
10.3
Unit Efficiency
10.1 / 3.0
12.9 / 3.8
15.2 / 4.5
18.5 / 5.4
JOHNSON CONTROLS
jOHNSON CONTROLS
61 7/8"
43 1/8"
LIQUID OUT
3" VICTAULIC (TYP)
VIEW B-B
BOTTOM OF PANEL
7/8" TYP.
PRODUCT DRAWING
15 3/4"
12 5/8"
9 3/4"
25 1/16"
ELECTRICAL ACCESS
PANEL
LIQUID IN
62 5/8"
3 15/16"
6 3/4"
3 1/4"
X
15 1/16"
28 9/16"
25 3/8" B
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
C
G
12 13/16"
ORIGIN
9 13/16"
TOP VIEW
Date :
Rev. Date :
Form : 150.62-EG1
Dwg. Lev. : 01/02
Dwg. Scale : NTS
FRONT VIEW
153 5/8"
776
768
1 1/16"
COIL
END
16"
9 13/16"
CONTROL
PANEL
5 3/16"
38"
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
1,292
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
1 1/16"
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
COOLER
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
END
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
90 9/16"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
END CAP
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
WIDTH
2. WEIGHTS (LB):SHIPPING - 4,097, OPERATING - 4,142.
3. CENTER OF GRAVITY FROM ORIGIN: X= 59.7", Y= 44.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
43 1/8"
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
1,306
MODEL: YCAL0066EE46
AHRI CAPACITY 66.1 TONS
YCAL
41 TO 65
29
30
JOHNSON CONTROLS
YLAA
70 to 175 Tons
Air Cooled Scroll Chiller
jOHNSON CONTROLS
31
32
JOHNSON CONTROLS
YLAA RIGGING
jOHNSON CONTROLS
33
BENEFITS
Optimized design for R-410A refrigerant (No EPA Phase out date)
Available in 2-tiers of efficiency:
Standard Efficiency: 9.6 10.0 EER
High Efficiency: 10.1 an above EER
Best Part Load Efficiency with an IPLV as high as 15.9.
The YLAA always qualifies for LEED credit through Enhanced Refrigerant Management.
This chiller utilizes 30-50% less refrigerant than conventional scroll chiller design.
Standard ambient operation from 30 to 115-deg F
Maintenance free, hermetic scroll compressor utilizes fewer moving parts to minimize breakdown
Components and circuitry designed for lower minimum circuit ampacities (MCA) to allow use of smaller
wire for reduced power wiring costs
Electronic, digital-based controls ensure reliable, solid-state monitoring and control
Units ship evacuated with initial oil charge and undergo factory pressure and operational testing to
minimize field setup time
Two refrigerant circuits allows redundant operation.
Industrys only 18-month air cooled warranty that covers all parts
Wide range of options to fit any design requirement. (Acoustical treatments, Hydrokit packages etc)
UPGRADE OPTIONS
Remote Cooler
Power Options --> 200, 230, 380, 460, 575 (Not available on all models, refer to Engineering Guide):
Single Point Terminal Block, Terminal Block with Individual Circuit Breakers, Circuit Breaker, Non-fused
Disconnect Switch or Non-fused Disconnect Switch with Individual System Circuit Breakers
Control Options: Low Ambient Kit extends operating range to 0 deg. F from +30 deg. F
Discharge Pressure Transducers and Readout Capability allows unit to sense and display discharge
pressure
Low Temperature Brine for chilling below 30 deg. F (which includes Electronic Expansion Valve)
Motor Current Module allows monitoring of compressor motor current, provides extra protection against
compressor reverse rotation, phase-loss and phase imbalance
Hot Gas Bypass for continuous, stable operation at capacities as low as 5% capacity
Service Isolation Valve - suction and discharge (ball type) isolation valves are added to unit per system;
includes a system high pressure relief valve in compliance with ASHRAE 15
Post-coated Epoxy Dipped
Unit Enclosure Options:
Wire Panels (full unit): coated, heavy gauge welded wire mesh mounted on exterior of unit to prevent
unauthorized access
Louvered Panels (condenser coils only): louvered panels mounted over exterior condenser coil faces to
protect coils
Louvered Panels (full unit): to protect condenser coils, visually screen internal components and prevent
unauthorized access
Louvered (condensers)/Wire Panels (mechanicals): Louvered steel panels on external condenser coil
faces, heavy-gauge welded-wire mesh around base
Sound Attenuation:
Compressor Acoustic Sound Blanket
Ultra Quiet fans
Vibration Isolators - 1" spring, 2" spring or neoprene pad isolators for mounting under unit base rails
34
JOHNSON CONTROLS
PACKAGE DESCRIPTION:
Evaporator:
Compressors:
Suction-gas cooled, hermetic scroll compressors
Large internal volume and oil reservoir provides
greater liquid tolerance
Crankcase heaters for extra protection against
liquid migration
Condenser:
Low noise, direct drive, maximum efficiency fans
with corrosion resistant aluminum hub and composite blades; statically and dynamically balanced
The fan motors are Totally Enclosed Air-Over,
current protected. They feature ball bearings that
are double-sealed and permanently lubricated.
Condenser coils are made of a single material to
avoid galvanic corrosion due to dissimilar metals.
Coils and headers are brazed as one piece.
Design Working Pressure 650 PSIG
Integral subcooling included
jOHNSON CONTROLS
Controls:
All controls housed in a NEMA 3R/12 cabinet
with gasket sealed, hinged & latched door
LCD, 40-character display with backlight
Color coded, sealed keypad
Standard controls permit operation from 30 to
115 deg F.
35
YLAA-B0070SE
6
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
ft
USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
F
F
ft
cfm
kW
A
A
A
lb
lb
lb
in
in
in
R410A
71.8
84.8
10.2
16
16
87
3.3
95
122.5 / 122.5
4
0
59329
6.7
460-3-60 / 414-506
160
175
175
1
#4 - 500 kcmil
3578
3623
101
116.1
88.3
94.2
JOHNSON CONTROLS
MODEL: YLAA0070SE46
NOT FOR CONSTRUCTION
Project Name :
YLAA
Location :
Engineer :
Contractor :
For :
PRODUCT DRAWING
81 13/16"
ORIGIN
3 1/4"
C
G
Y
X
76 5/8"
23 3/16"
UNIT0
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
732
5 5/8"
1,030
23 3/16"
19 5/8"
1,087
774
46 3/8"
46 1/2"
3" OUTLET
3" INLET
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 3,578, OPERATING - 3,622.
3. CENTER OF GRAVITY FROM ORIGIN: X= 56.8", Y= 51.3" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
10"
jOHNSON CONTROLS
42 11/16"
5/8" DIA
MOUNTING
HOLES (TYP)
MODEL: YLAA-B0070SE
AHRI CAPACITY 71.8 TONS
YLAA
70 TO 90
37
1 1/16"
YLAA-B0080SE
6
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
ft
USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
F
F
ft
cfm
kW
A
A
A
lb
lb
lb
in
in
in
R410A
77.7
94.4
9.9
15.4
15.4
88
3.3
95
126.1 / 122.9
4
0
59329
6.7
460-3-60 / 414-506
173
200
200
1
#4 - 500 kcmil
3898
3954
106
116.1
88.3
94.2
JOHNSON CONTROLS
MODEL: YLAA0080SE46
NOT FOR CONSTRUCTION
Project Name :
YLAA
Location :
Engineer :
Contractor :
For :
PRODUCT DRAWING
81 13/16"
ORIGIN
3 1/4"
C
G
Y
X
76 5/8"
23 3/16"
UNIT0
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
750
5 5/8"
1,135
23 3/16"
19 5/8"
1,246
822
46 3/8"
46 1/2"
3" OUTLET
3" INLET
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 3,898, OPERATING - 3,953.
3. CENTER OF GRAVITY FROM ORIGIN: X= 56.1", Y= 52.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
10"
jOHNSON CONTROLS
42 11/16"
5/8" DIA
MOUNTING
HOLES (TYP)
MODEL: YLAA-B0080SE
AHRI CAPACITY 77.7 TONS
YLAA
70 TO 90
39
1 1/4"
YLAA-B0090SE
5
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
ft
USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
F
F
ft
cfm
kW
A
A
A
lb
lb
lb
in
in
in
R410A
83.9
103.4
9.7
15.5
15.5
88
3.3
95
126.1 / 127.2
4
0
59329
6.7
460-3-60 / 414-506
192
225
225
1
#4 - 500 kcmil
4169
4241
115
116.1
88.3
94.2
JOHNSON CONTROLS
MODEL: YLAA0090SE46
NOT FOR CONSTRUCTION
Project Name :
YLAA
Location :
Engineer :
Contractor :
For :
PRODUCT DRAWING
81 13/16"
3" INLET
3" OUTLET
ORIGIN
3 1/4"
C
G
Y
X
76 5/8"
23 3/16"
UNIT0
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
831
5 5/8"
1,310
23 3/16"
19 5/8"
1,285
816
46 3/8"
46 1/2"
3" OUTLET
3" INLET
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 4,169, OPERATING - 4,242.
3. CENTER OF GRAVITY FROM ORIGIN: X= 58.1", Y= 53.7" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
10"
jOHNSON CONTROLS
42 11/16"
5/8" DIA
MOUNTING
HOLES (TYP)
MODEL: YLAA-B0090SE
AHRI CAPACITY 83.9 TONS
YLAA
70 TO 90
41
1 1/16"
YLAA-B0091HE
4
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
ft
USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
F
F
ft
cfm
kW
A
A
A
lb
lb
lb
in
in
in
R410A
88.2
98.3
10.8
15
14.9
88
3.3
95
117.7 / 117.7
6
0
88993
10.1
460-3-60 / 414-506
200
250
225
1
#4 - 500 kcmil
4718
4791
115
142.7
88.3
94.2
JOHNSON CONTROLS
MODEL: YLAA0091HE46
NOT FOR CONSTRUCTION
Project Name :
YLAA
Location :
Engineer :
Contractor :
For :
PRODUCT DRAWING
81 13/16"
42 11/16"
ORIGIN
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 4,718, OPERATING - 4,791.
3. CENTER OF GRAVITY FROM ORIGIN: X= 67.8", Y= 52.1" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
3 1/4"
C
G
884
571
23 5/16"
47 3/8"
UNIT1
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
69 3/4"
23 1/8"
7 11/16"
1,290
840
5 5/8"
672
534
46 3/8"
46 1/2"
3" OUTLET
3" INLET
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
jOHNSON CONTROLS
10"
5/8" DIA
MOUNTING
HOLES (TYP)
MODEL: YLAA-B0091HE
AHRI CAPACITY 88.2 TONS
YLAA
91 TO 130
43
1 1/16"
YLAA-B0100SE
5
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
ft
USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
F
F
ft
cfm
kW
A
A
A
lb
lb
lb
in
in
in
R410A
95.8
119.1
9.7
14.3
14.3
88
3.3
95
122.7 / 123.6
5
0
74161
8.4
460-3-60 / 414-506
223
250
250
1
#4 - 500 kcmil
4791
4864
112
142.7
88.3
94.2
JOHNSON CONTROLS
MODEL: YLAA0100SE46
NOT FOR CONSTRUCTION
Project Name :
YLAA
Location :
Engineer :
Contractor :
For :
PRODUCT DRAWING
81 13/16"
42 11/16"
ORIGIN
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 4,791, OPERATING - 4,863.
3. CENTER OF GRAVITY FROM ORIGIN: X= 69.6", Y= 53.5" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
3 1/4"
C
G
800
542
23 5/16"
47 3/8"
UNIT1
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
69 3/4"
23 1/8"
7 11/16"
1,459
836
5 5/8"
703
520
46 3/8"
46 1/2"
3" OUTLET
3" INLET
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
jOHNSON CONTROLS
10"
5/8" DIA
MOUNTING
HOLES (TYP)
MODEL: YLAA-B0100SE
AHRI CAPACITY 95.8 TONS
YLAA
91 TO 130
45
1 1/16"
YLAA-B0101HE
5
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
ft
USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
F
F
ft
cfm
kW
A
A
A
lb
lb
lb
in
in
in
R410A
98.5
116.1
10.2
15.4
15.4
89
3.3
95
125.2 / 117.7
6
0
88993
10.1
460-3-60 / 414-506
227
250
250
1
#4 - 500 kcmil
4954
5026
126
142.7
88.3
94.2
JOHNSON CONTROLS
MODEL: YLAA0101HE46
NOT FOR CONSTRUCTION
Project Name :
YLAA
Location :
Engineer :
Contractor :
For :
PRODUCT DRAWING
81 13/16"
42 11/16"
ORIGIN
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 4,954, OPERATING - 5,027.
3. CENTER OF GRAVITY FROM ORIGIN: X= 69.8", Y= 53.2" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
3 1/4"
C
G
818
560
23 5/16"
47 3/8"
UNIT1
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
69 3/4"
23 1/8"
7 11/16"
1,501
875
5 5/8"
728
545
46 3/8"
46 1/2"
3" OUTLET
3" INLET
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
jOHNSON CONTROLS
10"
5/8" DIA
MOUNTING
HOLES (TYP)
MODEL: YLAA-B0101HE
AHRI CAPACITY 98.5 TONS
YLAA
91 TO 130
47
1 1/16"
YLAA-B0115SE
4
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
ft
USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
F
F
ft
cfm
kW
A
A
A
lb
lb
lb
in
in
in
R410A
113.9
140.9
9.7
14.6
14.6
88
3.3
95
124 / 124
6
0
88993
10.1
460-3-60 / 414-506
256
300
300
1
#4 - 500 kcmil
5029
5101
119
142.7
88.3
94.2
JOHNSON CONTROLS
MODEL: YLAA0115SE46
NOT FOR CONSTRUCTION
ORIGIN
81 13/16"
42 11/16"
PRODUCT DRAWING
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 5,029, OPERATING - 5,102.
3. CENTER OF GRAVITY FROM ORIGIN: X= 68", Y= 53.5" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
3 1/4"
C
G
941
582
23 5/16"
47 3/8"
UNIT0
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
69 3/4"
23 1/8"
7 11/16"
1,442
866
5 5/8"
728
545
46 1/2"
46 3/8"
3" OUTLET
3" INLET
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
jOHNSON CONTROLS
10"
5/8" DIA
MOUNTING
HOLES (TYP)
MODEL: YLAA-B0115SE
AHRI CAPACITY 113.9 TONS
YLAA
91 TO 130
49
1 1/16"
YLAA-B0120SE
4
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
ft
USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
F
F
ft
cfm
kW
A
A
A
lb
lb
lb
in
in
in
R410A
119.6
143.3
10
14.8
14.8
88
3.3
95
125.1 / 125.1
6
0
88993
10.1
460-3-60 / 414-506
256
300
300
1
#4 - 500 kcmil
5183
5293
128
142.7
88.3
94.2
JOHNSON CONTROLS
MODEL: YLAA0120SE46
NOT FOR CONSTRUCTION
ORIGIN
81 13/16"
42 11/16"
PRODUCT DRAWING
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 5,183, OPERATING - 5,293.
3. CENTER OF GRAVITY FROM ORIGIN: X= 69.5", Y= 53.2" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
3 1/4"
C
G
937
578
23 5/16"
47 3/8"
UNIT0
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
69 3/4"
23 1/8"
7 11/16"
1,486
906
5 5/8"
789
600
46 1/2"
46 3/8"
3" OUTLET
3" INLET
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
jOHNSON CONTROLS
10"
5/8" DIA
MOUNTING
HOLES (TYP)
MODEL: YLAA-B0120SE
AHRI CAPACITY 119.6 TONS
YLAA
91 TO 130
51
1 1/16"
YLAA-B0136SE
6
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
USGPM
USGPM
F
F
ft
cfm
kW
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Unit Short Circuit Current Withstand
Wire Lugs Per Phase
Wire Range (Lug Size)
A
A
A
[kA]
lb
lb
lb
in
in
in
R410A
129.9
154.3
10.1
15.5
16.5
93
95
126.9 / 113.2
8
0
120776
13.4
460-3-60 / 414-506
285
300
300
5
1
#4 - 500 kcmil
6103
6187
146
187.7
88.3
94.2
YW13.02a
Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power
52
JOHNSON CONTROLS
MODEL: YLAA0136SE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
Y
C
G
23 3/16"
ORIGIN
3 5/16"
81 5/8"
jOHNSON CONTROLS
X
6 1/2"
69"
58"
59 13/16"
75 1/2"
UNIT1
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5/8" DIA
MOUNTING
HOLES (TYP)
1 3/16"
4" OUTLET
4" INLET
5 3/8"
46 3/8"
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
10"
NOTES:
MODEL: YLAAB0136SE
AHRI CAPACITY 129.9 TONS
YLAA
91 TO 130
53
YLAA-B0142HE
6
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
USGPM
USGPM
F
F
ft
cfm
kW
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Unit Short Circuit Current Withstand
Wire Lugs Per Phase
Wire Range (Lug Size)
A
A
A
[kA]
lb
lb
lb
in
in
in
R410A
132.1
152.3
10.4
14.4
16.2
96
95
123.1 / 116.4
8
0
120776
13.4
460-3-60 / 414-506
285
300
300
5
1
#4 - 500 kcmil
6333
6444
157
187.7
88.3
94.2
YW13.02a
Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power
54
JOHNSON CONTROLS
MODEL: YLAA0142HE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
Y
C
G
23 3/16"
ORIGIN
3 5/16"
81 5/8"
jOHNSON CONTROLS
X
6 1/2"
69"
58"
59 13/16"
75 1/2"
UNIT2
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5/8" DIA
MOUNTING
HOLES (TYP)
1 3/16"
4" OUTLET
4" INLET
5 3/8"
46 3/8"
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
13/16"
32 3/8"
10"
NOTES:
MODEL: YLAAB0142HE
AHRI CAPACITY 132.1 TONS
YLAA
131 TO 175
55
YLAA-B0156HE
5
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
USGPM
USGPM
F
F
ft
cfm
kW
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Unit Short Circuit Current Withstand
Wire Lugs Per Phase
Wire Range (Lug Size)
A
A
A
[kA]
lb
lb
lb
in
in
in
R410A
147.3
173.2
10.2
15.5
15.8
97
95
118.8 / 117.1
10
0
150440
16.8
460-3-60 / 414-506
319
350
350
5
1
#4 - 500 kcmil
7269
7353
172
232.7
88.3
94.2
YW13.02a
Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power
56
JOHNSON CONTROLS
MODEL: YLAA0156HE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
23 3/16"
ORIGIN
81 5/8"
C
G
3 5/16"
jOHNSON CONTROLS
X
7 11/16"
69"
58"
UNIT3
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
43"
42 1/2"
5/8" DIA
MOUNTING
HOLES (TYP)
82 7/8"
93 5/8"
1 3/8"
4" OUTLET
4" INLET
13/16"
46 3/8"
5 3/8"
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
32 3/8"
10"
NOTES:
MODEL: YLAAB0156SE
AHRI CAPACITY 147.3 TONS
YLAA
131 TO 175
57
YLAA-B0170SE
6
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
USGPM
USGPM
F
F
ft
cfm
kW
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Unit Short Circuit Current Withstand
Wire Lugs Per Phase
Wire Range (Lug Size)
A
A
A
[kA]
lb
lb
lb
in
in
in
R410A
170.5
208.6
9.8
15.1
15.9
97
95
121.3 / 121.3
10
0
150440
16.8
460-3-60 / 414-506
372
400
400
5
2
#4 - 500 kcmil
7624
7708
179
232.7
88.3
94.2
YW13.02a
Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power
58
JOHNSON CONTROLS
MODEL: YLAA0170SE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
23 3/16"
ORIGIN
81 5/8"
C
G
3 5/16"
jOHNSON CONTROLS
X
7 11/16"
69"
58"
UNIT4
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
43"
42 1/2"
5/8" DIA
MOUNTING
HOLES (TYP)
82 7/8"
93 5/8"
1 3/8"
4" OUTLET
4" INLET
13/16"
46 3/8"
5 3/8"
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
32 3/8"
10"
NOTES:
MODEL: YLAAB0170SE
AHRI CAPACITY 170.5 TONS
YLAA
131 TO 175
59
YLAA-B0175HE
6
Scroll - Hermetic
2
TR
kW
EER
EER
EER
dB(A)
USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
USGPM
USGPM
F
F
ft
cfm
kW
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Unit Short Circuit Current Withstand
Wire Lugs Per Phase
Wire Range (Lug Size)
A
A
A
[kA]
lb
lb
lb
in
in
in
R410A
176
211.1
10
15.1
16
97
95
122 / 122
10
0
150440
16.8
460-3-60 / 414-506
372
400
400
5
2
#4 - 500 kcmil
7772
7891
187
232.7
88.3
94.2
YW13.02a
Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power
60
JOHNSON CONTROLS
MODEL: YLAA0175HE46
NOT FOR CONSTRUCTION
PRODUCT DRAWING
23 3/16"
ORIGIN
81 5/8"
C
G
3 5/16"
jOHNSON CONTROLS
X
7 11/16"
69"
58"
UNIT5
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
43"
42 1/2"
5/8" DIA
MOUNTING
HOLES (TYP)
82 7/8"
93 5/8"
1 3/8"
4" OUTLET
4" INLET
13/16"
46 3/8"
5 3/8"
CONTROL PANEL
BOTTOM DETAIL
POWER ENTRY
13" WIDE X 7" HIGH
32 3/8"
10"
NOTES:
MODEL: YLAAB0175HE
AHRI CAPACITY 176 TONS
YLAA
131 TO 175
61
62
JOHNSON CONTROLS
YVAA
jOHNSON CONTROLS
63
YVAA RIGGING
Lifting Unit
Container lugs should be inserted into the holes provided in the bottom of the frame rail.
Use spreader bars to avoid lifting chains hitting the chiller. Various methods of spreader bar arrangements may
be used; keeping in mind the intent is to keep the unit stable and to keep the chains from hitting the chiller and
causing damage.
WARNING Never lift the chiller using a forklift or by hooking the top rails. Use only the lifting
holes provided.
Lifting instructions are placed on a label on the chiller and on the shipping bag.
64
JOHNSON CONTROLS
jOHNSON CONTROLS
65
BENEFITS
Continuous function, microprocessor controlled Variable Speed Drive (VSD) for valve less, smooth capacity
control to 10% of chiller capacity
Chiller speed matched to system requirements at off-peak conditions resulting in lower energy usage
Use of VSD reduces compressor moving parts by 50%
Soft motor start with no electrical inrush reduces components stress, heat buildup
Operating efficiencies at off-design conditions results in IPLVs as high as 19.8 EER
Standard full load power factor of 95%, maintained throughout operating range resulting in improved
energy savings
Superior acoustic operation at off-design conditions
HFC-R134a standard for long term availability and zero ODP
Wide range of options to fit any design requirement
Competitors MCA is an average of 10% higher than YORKs
Lower MCA allows for smaller wiring and smaller circuit breakers therefore lower costs
Allows for replacing chiller and increasing tonnage without replacing electrical components
Industrys only 18-month air cooled warranty that covers all parts.
UPGRADE OPTIONS
Remote Cooler
Factory mounted non-fused disconnect switch or circuit breaker
Epoxy Post Coated, Pre Coated or Post Coated for tube and fin
Seamless internally enhanced copper fin & tube coils arranged in staggered rows; mechanically bonded to
full eight aluminum fins
Evaporator Options:
1-1/2" Insulation (double thickness)
Raised Face Flange Accessory for cooler nozzles
Flow Switch Accessory: Vapor proof, SPDT, NEMA 3R switch, 150psig
Suction service isolation valve per circuit (discharge valve standard)
Unit Enclosure Options:
Wire Panels (full unit): coated, heavy gauge welded wire mesh mounted on exterior of unit to prevent
unauthorized access to refrigerant components
Louvered Panels (condenser coils only): Painted to match unit; louvered panels mounted over exterior
condenser coils faces to visually screen unit, protects coils
Louvered Panels (full unit): Painted to match unit; to protect condenser coils, visually screen internal
components and prevent unauthorized access
Louvered (condensers)/Wire Panels (mechanicals): Louvered steel panels on external condenser coil
faces, heavy-gauge welded-wire mesh around base to prevent unauthorized access
Sound Attenuation:
SilentNightTM controls to force lower sound levels on demand or per user schedule
Ultra quiet fans, compressor sound blankets and/or acoustical enclosures
Vibration Isolation: Neoprene, 1" spring isolators or 2" spring isolators
66
JOHNSON CONTROLS
PACKAGE DESCRIPTION:
Evaporator:
Compressors:
Reliable VSD driven semi-hermetic twin screw
High efficiency, accessible hermetic motor with
redundant overload protection
Temperature actuated body cartridge heater
Acoustically tuned discharge gas muffler
Design pressure of compressor 450 PSIG
Condenser:
Low noise, full airflow cross section fans for
maximum efficiency; statically & dynamically balanced for low vibration operation; positioned in
extended orifices for low sound
High efficiency, direct drive, 3-phase totally
enclosed fan motors with double sealed, permanently lubricated ball bearings
Condenser coils are made of a single material to
avoid galvanic corrosion due to dissimilar metals.
Coils and headers are brazed as one piece
Design Working Pressure 450 PSIG
Electrical:
Competitors MCA is an average of 10% higher
than YORKs
Lower MCA allows for smaller wiring and smaller
circuit breakers therefore lower costs
Allows for replacing chiller and increasing tonnage without replacing electrical components
jOHNSON CONTROLS
Refrigerant circuit:
Independent circuits per compressor
Computer controlled bending of refrigerant pipe
reduces over 60% of pipe brazed joints
Liquid line components include: manual shutoff
valve with charging port, removable core filterdrier, solenoid valve, sight glass with moisture
indicator, electronic expansion valves
Discharge line proided with manual compressor
shutoff service valve
External Oil separators with no moving parts, 450
PSIG design working pressure
Controls:
All controls housed in a NEMA 3R cabinet with
gasket sealed, hinged & latched door
VSD section includes dedicated inverter for each
compressor
Control display accessible without opening main
cabinet doors
LCD, 80-character display with backlight
Color coded, sealed keypad
Standard controls permit operation from 0 to
125 deg F ambient temperature
67
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YVAA0153BAF46
150.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
CONTROLS
PIPING
COMP
EVAPORATOR
COND
CABINET
MISC
WARR
YVAA0153BAF46BA VSXX XTAXLXXXX60 44XOXXX S189W 1SXXA2B MXF PXXXX XXXX BXSX
10
15
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
20
54.0
44.0
359.6
5.6
Water
0.00010
58.0
25
30
35
40
45
250.0
950.0
Condenser Data
Ambient Temp. Design (F)
Altitude (ft.)
Ambient Temp. Min (F)
95.0
0
0.0
Circuit
55
60
65
Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
109
4/3.3
1
109
4/3.3
Compressor RLA
Fan QTY/FLA (each)
50
10.1 / 3.0
15.1 / 4.4
10 %
11518
11979
Single Point
Min. Circuit Ampacity
275
350
350
Notes:
350
30kA
2
#2 - 600 KCM
0.95
2.0
VSD
Ambient (F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.1 / 3.0
13.3 / 3.9
16.3 / 4.8
17.6 / 5.2
Compressor kW
162.6
86.2
43.0
18.2
SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0153BAF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (F)
95.0
80.0
65.0
55.0
63
95.0
95.0
94.0
91.0
125
95.0
95.0
94.0
91.0
250
96.0
96.0
95.0
92.0
500
98.0
95.0
94.0
91.0
1K
95.0
92.0
91.0
88.0
2K
87.0
86.0
85.0
82.0
4K
83.0
82.0
81.0
78.0
8K
78.0
78.0
77.0
73.0
LWA
99.0
97.0
96.0
92.0
2K
60.0
59.0
58.0
55.0
4K
56.0
55.0
54.0
51.0
8K
51.0
51.0
50.0
46.0
dBA
72.0
70.0
69.0
65.0
1K
68.0
65.0
64.0
61.0
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.1 / 3.0
EER IPLV/COP IPLV
15.1 / 4.4
Capacity (Tons)
150.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
68
JOHNSON CONTROLS
15 1/8"
PRODUCT DRAWING
88 3/16"
44 1/8"
26 9/16"
C
G
Y
X
780
644
2,116
2,147
75 15/16"
48 11/16"
6 15/16"
56 1/8"
41 1/4"
62 9/16"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
203 1/4"
71 1/4"
2,116
2,147
1,052
978
jOHNSON CONTROLS
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 11,518, OPERATING - 11,980.
3. CENTER OF GRAVITY FROM ORIGIN: X= 101.8", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
14 1/8"
18 1/4"
47 5/16"
10 3/8"
60"
94 1/2"
4"
VIEW B-B
12"
VIEW A-A
2 15/16"
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
1 1/2"
POWER ENTRY
10" WIDE X 13" HIGH
YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.
1 3/8" (TYP)
MODEL: YVAA0153BAF46
AHRI CAPACITY 150.0 TONS
YVAA
150 TO 200
69
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YVAA0183ABF46
175.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
CONTROLS
PIPING
COMP
EVAPORATOR
COND
CABINET
MISC
WARR
YVAA0183ABF46BA VSXX XTAXLXXXX60 44XOXXX S192W 1SXXA2B MXF PXXXX XXXX BXSX
10
15
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
20
54.0
44.0
419.5
11.4
Water
0.00010
48.0
25
30
35
40
45
200.0
750.0
Condenser Data
Ambient Temp. Design (F)
Altitude (ft.)
Ambient Temp. Min (F)
95.0
0
0.0
Circuit
55
60
65
Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
111
4/3.3
1
139
6/3.3
Compressor RLA
Fan QTY/FLA (each)
50
10.4 / 3.0
15.4 / 4.5
10 %
12019
12460
Single Point
Min. Circuit Ampacity
322
450
450
Notes:
450
30kA
2
#2 - 600 KCM
0.95
2.0
VSD
Ambient (F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.4 / 3.0
13.5 / 4.0
16.5 / 4.8
17.9 / 5.2
Compressor kW
184.4
97.8
49.4
22.0
SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0183ABF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (F)
95.0
80.0
65.0
55.0
63
96.0
96.0
94.0
91.0
125
96.0
96.0
95.0
91.0
250
97.0
97.0
95.0
92.0
500
98.0
96.0
95.0
91.0
1K
94.0
94.0
91.0
88.0
2K
88.0
87.0
86.0
82.0
4K
84.0
83.0
82.0
78.0
8K
80.0
79.0
78.0
73.0
LWA
99.0
98.0
96.0
93.0
2K
61.0
60.0
59.0
55.0
4K
57.0
56.0
55.0
51.0
8K
53.0
52.0
51.0
46.0
dBA
72.0
71.0
69.0
66.0
1K
67.0
67.0
64.0
61.0
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.4 / 3.0
EER IPLV/COP IPLV
15.4 / 4.5
Capacity (Tons)
175.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
70
JOHNSON CONTROLS
14 1/8"
PRODUCT DRAWING
88 3/16"
44 1/8"
25 9/16"
C
G
Y
X
38 3/4"
47 5/8"
1,654
1,659
247"
82 13/16"
1,084
1,088
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
77 1/4"
1,084
1,729
46 3/4"
1,088
17 11/16"
1,660
42 1/16"
66 1/8"
711
704
jOHNSON CONTROLS
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 12,019, OPERATING - 12,460.
3. CENTER OF GRAVITY FROM ORIGIN: X= 128.4", Y= 44.2".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
14 1/8"
94 1/2"
4"
VIEW B-B
12"
VIEW A-A
2 15/16"
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
1 1/2"
POWER ENTRY
10" WIDE X 13" HIGH
YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.
18 1/4"
47 5/16"
10 3/8"
60"
1 1/4" (TYP)
MODEL: YVAA0183ABF46
AHRI CAPACITY 175.0 TONS
YVAA
150 TO 200
71
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YVAA0233BEF46
200.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
CONTROLS
PIPING
COMP
EVAPORATOR
COND
CABINET
MISC
WARR
YVAA0233BEF46BA VSXX XTAXLXXXX60 44XOXXX S176W 1SXXA2B MXF PXXXX XXXX BXSX
10
15
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
20
54.0
44.0
479.4
9.2
Water
0.00010
58.0
25
30
35
40
45
250.0
950.0
Condenser Data
Ambient Temp. Design (F)
Altitude (ft.)
Ambient Temp. Min (F)
95.0
0
0.0
Circuit
55
60
65
Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
135
5/3.3
1
158
7/3.3
Compressor RLA
Fan QTY/FLA (each)
50
10.5 / 3.1
15.2 / 4.5
10 %
13288
13750
Single Point
Min. Circuit Ampacity
375
500
500
Notes:
500
30kA
2
#2 - 600 KCM
0.95
2.0
VSD
Ambient (F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.5 / 3.1
13.5 / 4.0
16.2 / 4.7
17.3 / 5.1
Compressor kW
208.4
111.2
56.5
23.9
SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0213ADF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (F)
95.0
80.0
65.0
55.0
63
97.0
97.0
96.0
93.0
125
97.0
97.0
96.0
93.0
250
98.0
98.0
97.0
94.0
500
97.0
97.0
96.0
94.0
1K
94.0
93.0
93.0
90.0
2K
88.0
88.0
87.0
84.0
4K
84.0
84.0
83.0
80.0
8K
80.0
80.0
78.0
76.0
LWA
99.0
99.0
97.0
95.0
2K
61.0
61.0
60.0
57.0
4K
57.0
57.0
56.0
53.0
8K
53.0
53.0
51.0
49.0
dBA
72.0
72.0
70.0
68.0
1K
67.0
66.0
66.0
63.0
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.5 / 3.1
EER IPLV/COP IPLV
15.2 / 4.5
Capacity (Tons)
200.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
72
JOHNSON CONTROLS
15 1/8"
PRODUCT DRAWING
88 3/16"
44 1/8"
26 9/16"
C
G
Y
X
670
659
57 5/8"
72 5/16"
73 5/16"
670
659
38 3/4"
933
1,430
291 3/16"
76 13/16"
41 5/8"
947
1,423
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
77 5/8"
51 3/4"
2,247
2,230
42 1/16"
66 1/8"
947
933
jOHNSON CONTROLS
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 13,288, OPERATING - 13,750.
3. CENTER OF GRAVITY FROM ORIGIN: X= 134.7", Y= 44.1".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
14 1/8"
94 1/2"
4"
VIEW B-B
12"
VIEW A-A
2 15/16"
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
1 1/2"
POWER ENTRY
10" WIDE X 13" HIGH
YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.
18 1/4"
47 5/16"
10 3/8"
60"
1 1/4" (TYP)
MODEL: YVAA0233BEF46
AHRI CAPACITY 200.0 TONS
YVAA
150 TO 200
73
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YVAA0273DGF46
250.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
CONTROLS
PIPING
COMP
EVAPORATOR
COND
CABINET
MISC
WARR
YVAA0273DGF46BA VSXX XTAXLXXXX60 44XOXXX S188W 1SXXA2B MXF XXXXX XXXX BXSX
10
15
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
20
54.0
44.0
598.3
15.2
Water
0.00010
82.0
25
30
35
40
45
Circuit
55
60
65
Performance Data
EER / COP
NPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
175
7/3.3
1
175
7/3.3
Compressor RLA
Fan QTY/FLA (each)
95.0
0
0.0
50
10.8 / 3.2
16.0 / 4.7
10 %
16275
17103
Single Point
Min. Circuit Ampacity
444
600
600
Notes:
600
30kA
2
#2 - 600 KCM
0.95
2.0
VSD
Load %
100.0
75.0
50.0
25.0
Ambient (F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.8 / 3.2
14.0 / 4.1
17.2 / 5.0
18.9 / 5.5
Compressor kW
253.5
135.2
68.3
29.0
SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0273DGF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (F)
95.0
80.0
65.0
55.0
63
97.0
97.0
96.0
93.0
125
97.0
97.0
96.0
93.0
250
98.0
98.0
97.0
94.0
500
97.0
97.0
96.0
94.0
1K
94.0
93.0
93.0
90.0
2K
88.0
88.0
87.0
84.0
4K
84.0
84.0
83.0
80.0
8K
80.0
80.0
78.0
76.0
LWA
99.0
99.0
97.0
95.0
2K
63.0
62.0
61.0
58.0
4K
59.0
58.0
57.0
54.0
8K
54.0
53.0
52.0
49.0
dBA
74.0
72.0
71.0
68.0
1K
70.0
67.0
66.0
63.0
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.8 / 3.2
EER IPLV/COP IPLV
16.0 / 4.7
Capacity (Tons)
249.9
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
74
JOHNSON CONTROLS
44 1/8"
15 5/16"
PRODUCT DRAWING
88 3/16"
26 3/4"
59 1/8"
C
G
1,518
1,389
1,946
2,135
83 1/4"
100 5/16"
42 7/8"
60 3/16"
335 3/16"
79 13/16"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
40 3/16"
3,036
2,778
48 5/16"
1,372
1,539
60 1/4"
70 5/8"
710
14 1/8"
12 3/8"
47 1/2"
10 3/8"
60"
4"
VIEW B-B
POWER ENTRY
10" WIDE X 13" HIGH
12"
VIEW A-A
2 15/16"
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
1 1/2"
94 11/16"
1 5/16" (TYP)
YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.
681
jOHNSON CONTROLS
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 16,275, OPERATING - 17,103.
3. CENTER OF GRAVITY FROM ORIGIN: X= 168.3", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
MODEL: YVAA0273DGF46
AHRI CAPACITY 250.0 TONS
YVAA
201 TO 500
75
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YVAA0343EKF46
300.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
CONTROLS
PIPING
COMP
EVAPORATOR
COND
CABINET
MISC
WARR
YVAA0343EKF46BA VSXX XTAXLXXXX60 44XOXXX S179W 1SXXA2B MXF PXXXX XXXX BXSX
10
15
20
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
54.0
44.0
719.1
11.8
Water
0.00010
113.0
25
30
35
40
45
Circuit
55
60
65
Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
209
9/3.3
1
209
9/3.3
Compressor RLA
Fan QTY/FLA (each)
95.0
0
0.0
50
10.9 / 3.2
15.5 / 4.5
10 %
19315
20175
Single Point
Min. Circuit Ampacity
533
700
700
Notes:
700
30kA
3
#2 - 600 KCM
0.95
2.0
VSD
Ambient (F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.9 / 3.2
13.9 / 4.1
16.5 / 4.8
17.8 / 5.2
Compressor kW
300.3
162.5
85.1
38.1
SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0343EKF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (F)
95.0
80.0
65.0
55.0
63
99.0
99.0
97.0
94.0
125
99.0
99.0
97.0
94.0
250
100.0
100.0
98.0
95.0
500
99.0
100.0
98.0
94.0
1K
98.0
98.0
95.0
92.0
2K
92.0
91.0
89.0
87.0
4K
87.0
88.0
85.0
83.0
8K
83.0
84.0
81.0
79.0
LWA
102.0
102.0
100.0
96.0
2K
65.0
64.0
62.0
60.0
4K
60.0
61.0
58.0
56.0
8K
56.0
57.0
54.0
52.0
dBA
75.0
75.0
73.0
69.0
1K
71.0
71.0
68.0
65.0
54.0
44.0
719.1
11.8
Water
0.00010
113.0
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.9 / 3.2
EER IPLV/COP IPLV
15.5 / 4.5
Capacity (Tons)
300.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
76
JOHNSON CONTROLS
44 1/8"
15 1/2"
PRODUCT DRAWING
88 3/16"
29 1/2"
1000"
C
G
423 1/8"
40 3/16"
79 13/16"
48 5/16"
1,966
1,995
60 3/16"
2,259
2,260
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
61 3/4"
2,259
97 1/2"
1,951
863
84 7/16"
2,260
1,910
863
132 3/16"
790
14 1/8"
12 3/8"
47 1/2"
10 1/4"
60"
4"
VIEW B-B
POWER ENTRY
10" WIDE X 13" HIGH
12"
VIEW A-A
2 15/16"
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
1 1/2"
94 11/16"
1 3/8" (TYP)
YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.
60 1/4"
70 5/8"
801
jOHNSON CONTROLS
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 19,316, OPERATING - 20,175.
3. CENTER OF GRAVITY FROM ORIGIN: X= 187.5", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
MODEL: YVAA0343EKF46
AHRI CAPACITY 300.0 TONS
YVAA
201 TO 500
77
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YVAA0373FJF46
350.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
YVAA0373FJF46BA
10
CONTROLS
15
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
20
54.0
44.0
837.7
11.2
Water
0.00010
96.0
PIPING
25
30
COMP
35
EVAPORATOR
40
45
Circuit
CABINET
50
MISC
55
WARR
60
65
Performance Data
EER / COP
NPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
178
7/3.3
1
327
7/3.3
Compressor RLA
Fan QTY/FLA (each)
95.0
0
0.0
COND
10.4 / 3.0
15.0 / 4.4
10 %
22346
23405
Single Point
Min. Circuit Ampacity
658
800
800
Notes:
800
30kA
2
#2 - 600 KCM
0.95
3.0
VSD
Load %
100.0
75.0
50.0
25.0
Ambient (F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.4 / 3.0
13.3 / 3.9
16.1 / 4.7
17.4 / 5.1
Compressor kW
372.6
203.4
105.5
44.4
SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0373FJF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (F)
95.0
80.0
65.0
55.0
63
99.0
99.0
98.0
96.0
125
99.0
100.0
98.0
96.0
250
100.0
100.0
99.0
97.0
500
103.0
100.0
98.0
97.0
1K
100.0
97.0
95.0
92.0
2K
97.0
91.0
89.0
87.0
4K
96.0
88.0
86.0
84.0
8K
85.0
83.0
83.0
81.0
LWA
105.0
102.0
100.0
98.0
2K
70.0
64.0
62.0
60.0
4K
69.0
61.0
59.0
57.0
8K
58.0
56.0
56.0
54.0
dBA
78.0
75.0
73.0
71.0
1K
73.0
70.0
68.0
65.0
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.4 / 3.0
EER IPLV/COP IPLV
15.0 / 4.4
Capacity (Tons)
349.9
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
78
JOHNSON CONTROLS
jOHNSON CONTROLS
88
5/16"
44 1/8"
15
13/16"
28
13/16"
94
11/16"
PRODUCT DRAWING
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 22,346, OPERATING - 23,405.
3. CENTER OF GRAVITY FROM ORIGIN: X= 200.3", Y= 46.6".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
142
11/16"
467 1/8"
56 5/8"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
63 7/8"
78
11/16"
60 5/8"
108 1/2"
63 7/8"
10
5/16"
12
5/16"
42 1/8"
END VIEW
SECTION
12"
2 15/16"
A-A
B-B
POWER ENTRY
10" WIDE X 13" HIGH
SECTION
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
2 1/2"
2 1/2"
YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.
60
5/16"
70
11/16"
MODEL: YVAA0373EKF46
AHRI CAPACITY 350.0 TONS
YVAA
201 TO 500
79
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YVAA0443FMF46
400.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
CONTROLS
PIPING
COMP
EVAPORATOR
COND
CABINET
MISC
WARR
YVAA0443FMF46BA VDXX XTAXLXXXX60 44XOXXX S172W 1SXXA2B MXF PXXXX XXXX BXSX
10
15
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
20
54.0
44.0
958.8
14.3
Water
0.00010
96.0
Circuit
25
30
35
45
95.0
0
0.0
50
55
60
65
Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
287
12/3.3
1
287
12/3.3
Compressor RLA
Fan QTY/FLA (each)
40
10.6 / 3.1
14.8 / 4.3
10 %
25942
27001
Single Point
Min. Circuit Ampacity
398
398
600
600
600
600
600
600
600
#2 - 600 KCM
0.95
3.0
VSD
600
600
600
#2 - 600 KCM
0.95
Notes:
Ambient (F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.6 / 3.1
13.2 / 3.9
15.8 / 4.6
17.3 / 5.1
Compressor kW
414.4
231.7
120.9
53.3
SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0443FMF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (F)
95.0
80.0
65.0
55.0
63
100.0
100.0
99.0
96.0
125
100.0
100.0
99.0
96.0
250
101.0
101.0
100.0
97.0
500
102.0
102.0
100.0
98.0
1K
99.0
100.0
96.0
93.0
2K
95.0
92.0
90.0
87.0
4K
93.0
90.0
87.0
84.0
8K
88.0
85.0
85.0
82.0
LWA
104.0
104.0
101.0
98.0
2K
68.0
65.0
63.0
60.0
4K
66.0
63.0
60.0
57.0
8K
61.0
58.0
58.0
55.0
dBA
77.0
77.0
74.0
71.0
1K
72.0
73.0
69.0
66.0
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.6 / 3.1
EER IPLV/COP IPLV
14.8 / 4.3
Capacity (Tons)
400.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
80
JOHNSON CONTROLS
jOHNSON CONTROLS
88"
44 1/8"
16"
29"
95"
PRODUCT DRAWING
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 25,942, OPERATING - 27,001.
3. CENTER OF GRAVITY FROM ORIGIN: X= 213.7", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
42"
56"
67"
88"
56"
143"
146"
287"
52"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
555"
79"
57"
51"
109"
60"
71"
12"
10"
SECTION
42"
12"
3"
END
VIEW
SECTION
A-A
B-B
POWER ENTRY
10" WIDE X 13" HIGH
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
2 1/2"
2 1/2"
YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.
73"
MODEL: YVAA0443FMF46
AHRI CAPACITY 400.0 TONS
YVAA
201 TO 500
81
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YVAA0523HMF46
450.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
CONTROLS
PIPING
COMP
EVAPORATOR
COND
CABINET
MISC
WARR
YVAA0523HMF46BA VDXX XTAXLXXXX60 44XOXXX S183W 1SXXA2B MXF PXXXX XXXX BXSX
10
15
20
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
54.0
44.0
1078.7
14.8
Water
0.00010
147.0
Circuit
25
30
35
45
95.0
0
0.0
50
55
60
65
Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
312
13/3.3
1
312
13/3.3
Compressor RLA
Fan QTY/FLA (each)
40
10.9 / 3.2
15.4 / 4.5
10 %
28427
29784
Single Point
Min. Circuit Ampacity
423
423
700
700
700
700
700
700
700
#2 - 600 KCM
0.95
3.0
VSD
700
700
700
#2 - 600 KCM
0.95
Notes:
Ambient (F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.9 / 3.2
13.7 / 4.0
16.4 / 4.8
18.2 / 5.3
Compressor kW
452.4
251.2
131.9
58.2
SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0523HMF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (F)
95.0
80.0
65.0
55.0
63
101.0
100.0
99.0
96.0
125
101.0
101.0
99.0
96.0
250
102.0
102.0
100.0
97.0
500
102.0
103.0
100.0
97.0
1K
101.0
100.0
96.0
93.0
2K
96.0
93.0
91.0
87.0
4K
92.0
92.0
87.0
84.0
8K
87.0
86.0
85.0
81.0
LWA
104.0
104.0
101.0
98.0
2K
69.0
66.0
64.0
60.0
4K
65.0
65.0
60.0
57.0
8K
60.0
59.0
58.0
54.0
dBA
77.0
77.0
74.0
71.0
1K
74.0
73.0
69.0
66.0
54.0
44.0
1078.6
14.8
Water
0.00010
147.0
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.9 / 3.2
EER IPLV/COP IPLV
15.4 / 4.5
Capacity (Tons)
450.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
82
JOHNSON CONTROLS
jOHNSON CONTROLS
88"
44 1/8"
16"
30"
95"
PRODUCT DRAWING
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 28,427, OPERATING - 29,784.
3. CENTER OF GRAVITY FROM ORIGIN: X= 222.4", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
79"
132"
57"
59"
78"
309"
146"
599"
52"
79"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
143"
57"
51"
109"
60"
71"
12"
10"
42"
SECTION
END
END
VIEW
VIEW
SECTION
12"
3"
B-B
A-A
POWER ENTRY
10" WIDE X 13" HIGH
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
2 1/2"
2 1/2"
YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.
73"
MODEL: YVAA0523HMF46
AHRI CAPACITY 450.0 TONS
YVAA
201 TO 500
83
Qty.
Model No.
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YVAA0523HMG46
500.0
460/3/60
R134a
Pin:
BASE MODEL
POWER
CONTROLS
PIPING
COMP
EVAPORATOR
COND
CABINET
MISC
WARR
YVAA0523HMG46BA VDXX XTAXLXXXX60 44XOXXX S200W 1SXXA3B MXG XXXXX XXXX BXSX
10
15
20
Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)
54.0
44.0
1199.9
51.4
Water
0.00010
147.0
Circuit
25
30
35
45
95.0
0
0.0
50
55
60
65
Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)
Electrical Data
2
341
13/5.1
1
341
13/5.1
Compressor RLA
Fan QTY/FLA (each)
40
10.5 / 3.1
14.4 / 4.2
10 %
29365
30722
Single Point
Min. Circuit Ampacity
478
478
800
800
800
800
800
800
800
#2 - 600 KCM
0.95
3.0
VSD
800
800
800
#2 - 600 KCM
0.95
Notes:
Ambient (F)
95.0
80.0
65.0
55.0
Unit Efficiency
10.5 / 3.1
12.8 / 3.8
15.5 / 4.5
16.2 / 4.7
Compressor kW
495.3
272.8
151.9
63.4
SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0523HMG46 ( Equipped with High Airflow Fans )
Load %
100.0
75.0
50.0
25.0
Ambient (F)
95.0
80.0
65.0
55.0
63
103.0
103.0
101.0
99.0
125
117.0
117.0
115.0
113.0
250
116.0
116.0
114.0
112.0
500
110.0
110.0
107.0
105.0
1K
107.0
106.0
103.0
101.0
2K
103.0
102.0
99.0
97.0
4K
96.0
94.0
91.0
90.0
8K
90.0
89.0
87.0
85.0
LWA
113.0
112.0
110.0
108.0
2K
76.0
75.0
72.0
70.0
4K
69.0
67.0
64.0
63.0
8K
63.0
62.0
60.0
58.0
dBA
86.0
85.0
83.0
81.0
1K
80.0
79.0
76.0
74.0
54.0
44.0
1199.9
51.4
Water
0.00010
147.0
Condenser Data
Ambient Temp. (F)
Altitude (ft.)
95.0
0
Performance Data
EER / COP
10.5 / 3.1
EER IPLV/COP IPLV
14.4 / 4.2
Capacity (Tons)
500.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
84
JOHNSON CONTROLS
jOHNSON CONTROLS
16"
PRODUCT DRAWING
88"
44 1/8"
95"
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 29,365, OPERATING - 30,722.
3. CENTER OF GRAVITY FROM ORIGIN: X= 225.1", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
59"
78"
146"
599"
52"
79"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
143"
79"
132"
57"
309"
528 5/16"
57"
51"
109"
73"
60"
71"
12"
10"
END
END
VIEW
VIEW
A-A
30"
42"
SECTION
12"
3"
B-B
POWER ENTRY
10" WIDE X 13" HIGH
SECTION
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
2 1/2"
2 1/2"
MODEL: YVAA0523HMG46
AHRI CAPACITY 500.0 TONS
YVAA
201 TO 500
85
86
JOHNSON CONTROLS
YCWL
50 to 200 Tons
Water Cooled Scroll Chiller
jOHNSON CONTROLS
87
88
JOHNSON CONTROLS
YCWL RIGGING
Delivery and Storage
To ensure consistent quality and maximum reliability, all units are
tested and inspected before leaving the factory. Units are shipped
completely assembled and containing refrigerant under pressure.
Units are shipped without export crating unless this has been
specified on the Sales Order.
If the unit is to be put into storage, before installation, the following
precautions should be observed:
Ensure that all openings, such as water connections, are securely
capped.
Do not store where exposed to ambient air temperatures exceeding
107F (42C).
The unit should be stored in a location where there is minimal activity
to limit the risk of accidental physical damage.
To prevent inadvertent operation of the pressure relief devices the
unit must not be steam cleaned.
It is recommended that the unit is periodically inspected during
storage.
Inspection
Immediately upon receiving the unit, it should be inspected for possible damage which may have occurred during transit. If damage
is evident, it should be noted in the carriers freight bill. A written
request for inspection by the carriers agent should be made at once.
See Instruction Manual, Form 50.15-NM for more information and details.
Major damage must be reported immediately to your local Johnson Controls representative.
Moving the Unit
Before moving the unit, ensure that the installation site is suitable for installing the unit and is capable of supporting
the weight of the unit and all associated services.
The units are designed to be lifted using either lifting chains or a fork lift.
Lifting by Crane / Hoist
A spreader frame should be used to prevent damage to the unit from the lifting chains (Refer to page 34 of the
Operations and Maintenance Guide [Form 201.26-NM1]).
NOTE: The unit must only be lifted a the points provided.
jOHNSON CONTROLS
89
BENEFITS
UPGRADE OPTIONS
Low temperature brine chilling to 15F
Power Options:
Single Point Power Connection to Terminal Block, Non-fused Disconnect or Circuit Breaker
Multiple Point Power Connection to Circuit Breakers for retrofit projects
Compressor Overloads to limit MCA (ideal for retrofit applications)
Heat Pump (non-reversing) option to 130F leaving condenser water temperature for energy conservation
Remote Condenser YCRL variant for remote condenser applications
Evaporator Options:
Victaulic Flange Accessory for cooler nozzles
Flow switch: Vapor proof, SPDT, NEMA 4X switch, 150 psig
Vibration Isolators - Neoprene isolators, 1" spring isolators or 2" spring isolators
90
JOHNSON CONTROLS
PACKAGE DESCRIPTION:
Evaporator:
Compressors:
Reliable suction-gas cooled hermetic scrolls
High efficiency motors with redundant overload
protection
Microprocessor controlled compressor staging
regulates chiller capacity to 15% of maximum
Design Working Pressure 560 PSIG
Condenser:
Refrigerant Circuit:
Tandem or trio compressors per circuit
Liquid line components include: shut-off valve
with charging port, high-absorption removable
core filter-drier, solenoid valve, sight glass with
moisture indicator, thermal or electronic expansion valves (depending on options)
Entire suction line and liquid line between expansion valve and cooler insulated with flexible
closed-cell foam insulation
Controls:
All controls housed in a NEMA 1 cabinet with
gasket sealed, hinged & latched door
LCD, 40-character display with backlight
Color coded, 32-button sealed keypad
jOHNSON CONTROLS
91
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0056SE46
52.4
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
125.6
12.2
Water
0.00010
22.4
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
23.1/23.1
150.0/150.0
85.0
95.0
153.2
10.6
Water 0.0
0.00025
19.4
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.1 / 4.7
21.3 / 6.2
Electrical Data
2
23.1/23.1
150.0/150.0
3515
3648
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
110.0
(1)#12 - #1
92.4
150.0
Across the Line
39.2
39.2
Load %
100.0
75.0
50.0
25.0
92
98.0
150.0
110.0
Capacity (Tons)
52.4
41.1
29.0
14.2
Compressor kW
39.2
26.3
15.4
7.3
Unit Efficiency
16.1 / 4.7
18.8 / 5.5
22.6 / 6.6
23.3 / 6.8
JOHNSON CONTROLS
jOHNSON CONTROLS
29"
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
64 1/2"
WATER OUTLET
VICTAULIC
CONNECTION
PRODUCT DRAWING
14 1/2"
35 1/2"
29"
17 11/16"
34 5/8"
OVERALL WIDTH
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 3,515, OPERATING - 3,648.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.9", Y= 9.8"
9 1/16"
34"
9"
50"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
84 1/2"
25 7/8"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 1/8"
5 1/2"
6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
23 1/2"
50"
909 (LB)
915 (LB)
15 1/16"
119 5/8"
101 13/16"
9 7/8"
9 7/8"
ORIGIN
8 5/8"
30 3/8"
6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
909 (LB)
915 (LB)
MODEL: YCWL0056SE46
AHRI CAPACITY 52.4 TONS
YCWL
50 TO 90
93
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0064SE46
59.9
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
143.6
15.7
Water
0.00010
22.4
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
26.9/26.9
187.0/187.0
85.0
95.0
175.8
13.4
Water 0.0
0.00025
19.4
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
15.7 / 4.6
19.9 / 5.8
Electrical Data
2
26.9/26.9
187.0/187.0
3883
4016
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
125.0
(1)#10 - 300
107.6
187.0
Across the Line
45.7
45.7
Load %
100.0
75.0
50.0
25.0
94
114.0
150.0
125.0
Capacity (Tons)
59.9
47.1
33.3
16.3
Compressor kW
45.7
31.1
19.1
9.2
Unit Efficiency
15.7 / 4.6
18.2 / 5.3
20.9 / 6.1
21.2 / 6.2
JOHNSON CONTROLS
jOHNSON CONTROLS
29"
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
64 1/2"
WATER OUTLET
VICTAULIC
CONNECTION
PRODUCT DRAWING
14 1/2"
35 1/2"
29"
17 11/16"
34 5/8"
OVERALL WIDTH
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 3,883, OPERATING - 4,016.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.9", Y= 10.3"
9 1/16"
50"
34"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 1/8"
5 1/2"
6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
23 1/2"
9"
50"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
84 1/2"
25 7/8"
1,042 (LB)
966 (LB)
15 1/16"
119 5/8"
101 13/16"
9 7/8"
9 7/8"
ORIGIN
8 5/8"
30 3/8"
6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
1,042 (LB)
966 (LB)
MODEL: YCWL0064SE46
AHRI CAPACITY 59.9 TONS
YCWL
50 TO 90
95
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0064HE46
62.4
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
149.6
7.4
Water
0.00010
59.8
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
26.9/26.9
187.0/187.0
85.0
95.0
181.7
6.6
Water 0.0
0.00025
26.9
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.5 / 4.8
20.2 / 5.9
Electrical Data
2
26.9/26.9
187.0/187.0
4533
4848
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
125.0
(1)#10 - 300
107.6
187.0
Across the Line
45.5
45.5
Load %
100.0
75.0
50.0
25.0
96
114.0
150.0
125.0
Capacity (Tons)
62.4
48.5
33.4
16.3
Compressor kW
45.5
31.0
18.9
9.2
Unit Efficiency
16.5 / 4.8
18.8 / 5.5
21.2 / 6.2
21.3 / 6.2
JOHNSON CONTROLS
jOHNSON CONTROLS
29"
67 5/8"
1"
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
PRODUCT DRAWING
14 1/2"
35 1/2"
29"
17 11/16"
33 13/16"
OVERALL WIDTH
23 1/2"
8 1/4"
50"
25 7/8"
34"
9"
124 3/8"
50"
101 13/16"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
85"
1,250 (LB)
1,174 (LB)
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 1/8"
7 1/8"
6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,533, OPERATING - 4,848.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.2"
19 13/16"
9 7/8"
9 7/8"
ORIGIN
8 3/8"
32"
6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
1,250 (LB)
1,174 (LB)
MODEL: YCWL0064HE46
AHRI CAPACITY 62.4 TONS
YCWL
50 TO 90
97
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0074SE46
67.8
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
162.5
19.9
Water
0.00010
22.4
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
30.4/30.4
225.0/225.0
85.0
95.0
200.2
16.8
Water 0.0
0.00025
19.4
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
15.2 / 4.5
20.2 / 5.9
Electrical Data
2
26.9/26.9
187.0/187.0
4061
4194
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
150.0
(1)#10 - 300
114.6
225.0
Across the Line
53.6
53.6
Load %
100.0
72.2
50.0
22.2
98
122.0
150.0
150.0
Capacity (Tons)
67.8
52.5
38.7
16.2
Compressor kW
53.6
34.1
21.8
9.2
Unit Efficiency
15.2 / 4.5
18.5 / 5.4
21.2 / 6.2
21.2 / 6.2
JOHNSON CONTROLS
jOHNSON CONTROLS
29"
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
PRODUCT DRAWING
14 1/2"
35 1/2"
29"
17 11/16"
33 13/16"
OVERALL WIDTH
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,061, OPERATING - 4,194.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.9", Y= 10.4"
23 1/2"
9 1/16"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 1/8"
5 1/2"
6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
1"
50"
34"
9"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
84 1/2"
9 7/8"
9 7/8"
ORIGIN
8 5/8"
30 3/8"
6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
1,106 (LB)
50"
990 (LB)
25 7/8"
101 13/16"
125 15/16"
990 (LB)
21 3/8"
MODEL: YCWL0074SE46
AHRI CAPACITY 67.8 TONS
YCWL
50 TO 90
99
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0074HE46
72.7
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
174.4
6.0
Water
0.00010
59.8
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
30.4/30.4
225.0/225.0
85.0
95.0
212.0
8.6
Water 0.0
0.00025
26.9
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.3 / 4.8
20.7 / 6.1
Electrical Data
2
26.9/26.9
187.0/187.0
4911
5406
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
150.0
(1)#10 - 300
114.6
225.0
Across the Line
53.4
53.4
Load %
100.0
72.2
50.0
22.2
100
122.0
150.0
150.0
Capacity (Tons)
72.7
54.6
38.9
16.2
Compressor kW
53.4
33.7
21.4
9.1
Unit Efficiency
16.3 / 4.8
19.4 / 5.7
21.9 / 6.4
21.3 / 6.2
JOHNSON CONTROLS
jOHNSON CONTROLS
14 1/2"
29"
74 5/8"
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
PRODUCT DRAWING
40"
29"
17 11/16"
33 13/16"
OVERALL WIDTH
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,911, OPERATING - 5,406.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.3"
1"
5 1/8"
7 1/8"
34"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
8 1/4"
8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
23 1/2"
50"
29"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
83"
ORIGIN
Y
9 3/8"
33 1/4"
8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
9 7/8"
9 7/8"
1,409 (LB)
1,294 (LB)
50"
101 13/16"
123 5/16"
9"
1,409 (LB)
1,294 (LB)
18 3/4"
MODEL: YCWL0074HE46
AHRI CAPACITY 72.7 TONS
YCWL
50 TO 90
101
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0084SE46
76.6
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
183.5
24.9
Water
0.00010
22.4
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
30.4/30.4
225.0/225.0
85.0
95.0
224.6
9.5
Water 0.0
0.00025
26.9
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
15.8 / 4.6
21.4 / 6.3
Electrical Data
2
30.4/30.4
225.0/225.0
4489
4684
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
150.0
(1)#10 - 300
121.6
225.0
Across the Line
58.3
58.3
Load %
100.0
75.0
50.0
25.0
102
129.0
150.0
150.0
Capacity (Tons)
76.6
61.0
44.3
21.9
Compressor kW
58.3
39.7
23.5
11.1
Unit Efficiency
15.8 / 4.6
18.4 / 5.4
22.7 / 6.7
23.8 / 7.0
JOHNSON CONTROLS
jOHNSON CONTROLS
14 1/2"
29"
PRODUCT DRAWING
35 1/2"
29"
17 11/16"
33 13/16"
OVERALL WIDTH
68 7/8"
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,489, OPERATING - 4,684.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.6"
1"
5 1/8"
7 1/8"
34"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
8 1/4"
6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
23 1/2"
50"
84 1/2"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
X
Y
9 7/8"
8 5/8"
30 3/8"
6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
1,249 (LB)
50"
101 13/16"
125 15/16"
1,249 (LB)
9"
25 7/8"
1,093 (LB)
21 3/8"
MODEL: YCWL0084SE46
AHRI CAPACITY 76.6 TONS
YCWL
50 TO 90
103
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0084HE46
82.6
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
198.0
7.6
Water
0.00010
59.8
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
30.4/30.4
225.0/225.0
85.0
95.0
239.5
10.6
Water 0.0
0.00025
26.9
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.8 / 4.9
21.9 / 6.4
Electrical Data
2
30.4/30.4
225.0/225.0
5089
5584
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
150.0
(1)#10 - 300
121.6
225.0
Across the Line
58.9
58.9
Load %
100.0
75.0
50.0
25.0
104
129.0
150.0
150.0
Capacity (Tons)
82.6
64.4
44.7
21.9
Compressor kW
58.9
39.7
23.0
11.0
Unit Efficiency
16.8 / 4.9
19.5 / 5.7
23.3 / 6.8
23.8 / 7.0
JOHNSON CONTROLS
jOHNSON CONTROLS
14 1/2"
29"
74 5/8"
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
PRODUCT DRAWING
40"
29"
17 11/16"
33 13/16"
OVERALL WIDTH
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,089, OPERATING - 5,584.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.5"
1"
5 1/8"
7 1/8"
34"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
8 1/4"
8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
23 1/2"
50"
29"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
83"
ORIGIN
Y
9 3/8"
33 1/4"
8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
9 7/8"
9 7/8"
1,474 (LB)
1,318 (LB)
50"
101 13/16"
125 11/16"
9"
1,474 (LB)
1,318 (LB)
21 1/8"
MODEL: YCWL0084HE46
AHRI CAPACITY 82.6 TONS
YCWL
50 TO 90
105
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0094SE46
85.9
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
205.8
13.2
Water
0.00010
37.3
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
42.9/42.9
250.0/250.0
85.0
95.0
250.8
11.5
Water 0.0
0.00025
85.0
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.2 / 4.7
21.5 / 6.3
Electrical Data
2
30.4/30.4
225.0/225.0
5023
5338
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
200.0
(1)#10 - 300
146.6
250.0
Across the Line
63.8
63.8
Load %
100.0
72.6
50.0
22.6
106
157.0
200.0
175.0
Capacity (Tons)
85.9
66.6
47.8
21.9
Compressor kW
63.8
41.6
25.4
11.0
Unit Efficiency
16.2 / 4.7
19.2 / 5.6
22.5 / 6.6
23.8 / 7.0
JOHNSON CONTROLS
jOHNSON CONTROLS
29"
33 13/16"
OVERALL WIDTH
PRODUCT DRAWING
14 1/2"
35 1/2"
29"
17 11/16"
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
72 1/4"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,023, OPERATING - 5,338.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.9", Y= 10.7"
8 1/4"
23 1/2"
50"
34"
9"
125 15/16"
85"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
8 3/8"
32"
6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
9 7/8"
9 7/8"
50"
101 13/16"
1,427 (LB)
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 1/8"
7 1/8"
6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
1"
25 7/8"
1,242 (LB)
21 3/8"
MODEL: YCWL0094SE46
AHRI CAPACITY 85.9 TONS
YCWL
50 TO 90
107
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0094HE46
89.4
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
214.3
8.7
Water
0.00010
59.8
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
42.9/42.9
250.0/250.0
85.0
95.0
258.5
5.4
Water 0.0
0.00025
44.1
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.9 / 5.0
21.9 / 6.4
Electrical Data
2
30.4/30.4
225.0/225.0
5773
6412
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
200.0
(1)#10 - 300
146.6
250.0
Across the Line
63.5
63.5
Load %
100.0
72.6
50.0
22.6
108
157.0
200.0
175.0
Capacity (Tons)
89.4
68.5
47.9
21.9
Compressor kW
63.5
41.1
25.1
10.9
Unit Efficiency
16.9 / 5.0
20.0 / 5.9
23.0 / 6.7
24.1 / 7.1
JOHNSON CONTROLS
jOHNSON CONTROLS
15"
30"
PRODUCT DRAWING
42"
29"
33 7/8"
OVERALL WIDTH
17 11/16"
5 9/16" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
5 9/16" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
76 5/8"
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,773, OPERATING - 6,412.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.6"
5 3/16"
8 5/8"
34"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
8 1/2"
8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
23 1/2"
50"
83"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
108 3/4"
9 7/8"
9 3/8"
35 1/4"
8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
1,696 (LB)
50"
101 13/16"
1,696 (LB)
9"
27 1/2"
1,510 (LB)
17 3/16"
121 3/4"
MODEL: YCWL0094HE46
AHRI CAPACITY 89.4 TONS
YCWL
50 TO 90
109
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0104SE46
92.8
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
222.5
11.0
Water
0.00010
37.3
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
42.9/42.9
250.0/250.0
85.0
95.0
271.0
13.1
Water 0.0
0.00025
26.9
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.2 / 4.7
20.9 / 6.1
Electrical Data
2
42.9/42.9
250.0/250.0
5157
5472
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
225.0
(1)#4 - 500
171.6
250.0
Across the Line
68.9
68.9
Load %
100.0
75.0
50.0
25.0
110
182.0
200.0
200.0
Capacity (Tons)
92.8
72.6
50.9
24.9
Compressor kW
68.9
46.5
27.6
13.2
Unit Efficiency
16.2 / 4.7
18.7 / 5.5
22.2 / 6.5
22.6 / 6.6
JOHNSON CONTROLS
jOHNSON CONTROLS
14 1/2"
29"
71 3/4"
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
PRODUCT DRAWING
38 1/2"
29"
17 11/16"
33 13/16"
OVERALL WIDTH
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,157, OPERATING - 5,472.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.8"
8 1/4"
6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
34"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 1/8"
7 1/8"
23 1/2"
50"
9"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
85"
32"
6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
9 7/8"
9 7/8"
ORIGIN
8 3/8"
1,476 (LB)
1,260 (LB)
50"
124 1/8"
101 13/16"
1,476 (LB)
25 7/8"
1,260 (LB)
19 9/16"
MODEL: YCWL0104SE46
AHRI CAPACITY 92.8 TONS
YCWL
91 TO 130
111
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0118SE46
110.5
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
264.8
15.1
Water
0.00010
37.3
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
54.5/54.5
310.0/310.0
85.0
95.0
324.5
17.8
Water 0.0
0.00025
26.9
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
15.6 / 4.6
23.5 / 6.9
Electrical Data
2
42.9/42.9
250.0/250.0
4983
5298
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
310.0
(1)#4 - 500
194.8
310.0
Across the Line
84.9
84.9
Load %
100.0
71.8
50.0
21.8
112
208.4
250.0
225.0
Capacity (Tons)
117.2
89.7
64.4
27.7
Compressor kW
83.1
49.7
29.4
11.9
Unit Efficiency
16.9 / 5.0
21.7 / 6.4
26.3 / 7.7
27.9 / 8.2
JOHNSON CONTROLS
jOHNSON CONTROLS
14 1/2"
29"
71 3/4"
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
PRODUCT DRAWING
38 1/2"
29"
17 11/16"
33 13/16"
OVERALL WIDTH
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,983, OPERATING - 5,298.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.8"
8 1/4"
6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
34"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 1/8"
7 1/8"
23 1/2"
50"
9"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
107 3/4"
85"
32"
6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
9 7/8"
9 7/8"
ORIGIN
8 3/8"
1,413 (LB)
1,236 (LB)
50"
124 1/8"
101 13/16"
1,413 (LB)
25 7/8"
1,236 (LB)
19 9/16"
MODEL: YCWL0118SE46
AHRI CAPACITY 110.5 TONS
YCWL
91 TO 130
113
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0118HE46
117.2
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
280.8
14.1
Water
0.00010
59.8
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
54.5/54.5
310.0/310.0
85.0
95.0
334.0
8.4
Water 0.0
0.00025
44.1
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.9 / 5.0
24.7 / 7.2
Electrical Data
2
42.9/42.9
250.0/250.0
5733
6372
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
310.0
(1)#4 - 500
194.8
310.0
Across the Line
83.1
83.1
Load %
100.0
71.8
50.0
21.8
114
208.4
250.0
225.0
Capacity (Tons)
117.2
89.7
64.4
27.7
Compressor kW
83.1
49.7
29.4
11.9
Unit Efficiency
16.9 / 5.0
21.7 / 6.4
26.3 / 7.7
27.9 / 8.2
JOHNSON CONTROLS
jOHNSON CONTROLS
15"
30"
PRODUCT DRAWING
42"
29"
33 7/8"
OVERALL WIDTH
17 11/16"
5 9/16" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
5 9/16" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
76 5/8"
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,733, OPERATING - 6,372.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.7"
5 3/16"
8 5/8"
34"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
8 1/2"
8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
23 1/2"
50"
83"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
108 3/4"
9 7/8"
9 3/8"
35 1/4"
8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
1,681 (LB)
50"
101 13/16"
1,681 (LB)
9"
25 7/8"
1,505 (LB)
18 3/4"
123 5/16"
MODEL: YCWL0118HE46
AHRI CAPACITY 117.2 TONS
YCWL
91 TO 130
115
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0132SE46
127.4
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
305.3
16.5
Water
0.00010
59.8
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
54.5/54.5
310.0/310.0
85.0
95.0
372.0
14.8
Water 0.0
0.00025
35.2
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.1 / 4.7
23.4 / 6.9
Electrical Data
2
54.5/54.5
310.0/310.0
5463
6027
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
310.0
(1)#4 - 500
218.0
310.0
Across the Line
94.7
94.7
Load %
100.0
75.0
50.0
25.0
116
231.6
400.0
310.0
Capacity (Tons)
127.4
100.2
70.8
34.7
Compressor kW
94.7
61.0
33.7
15.9
Unit Efficiency
16.1 / 4.7
19.7 / 5.8
25.2 / 7.4
26.2 / 7.7
JOHNSON CONTROLS
jOHNSON CONTROLS
29"
5 9/16" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
5 9/16" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
74 1/2"
PRODUCT DRAWING
14 1/2"
40"
29"
17 11/16"
33 13/16"
OVERALL WIDTH
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,463, OPERATING - 6,027.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.7"
7 3/4"
8 1/8"
8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
34"
9"
123 5/16"
101 13/16"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
108 1/4"
83"
X
Y
9 3/8"
33 1/4"
8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
9 7/8"
9 7/8"
1,598 (LB)
5/8" MOUNTING HOLES (TYP)
50"
1,598 (LB)
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 1/4"
23 1/2"
50"
25 7/8"
1,415 (LB)
18 3/4"
MODEL: YCWL0132SE46
AHRI CAPACITY 127.4 TONS
YCWL
91 TO 130
117
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0157SE46
144.0
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
345.1
17.3
Water
0.00010
57.6
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
54.5/54.5
310.0/310.0
85.0
95.0
419.0
15.3
Water 0.0
0.00025
52.4
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.5 / 4.8
23.5 / 6.9
Electrical Data
2
54.5/54.5
310.0/310.0
6163
6891
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
231.6
400.0
250.0
250.0
() -
Notes:
104.7
104.7
Load %
100.0
75.0
50.0
25.0
118
218.0
310.0
Across the Line
Capacity (Tons)
144.0
113.5
80.2
39.3
Compressor kW
104.7
68.1
38.0
17.9
Unit Efficiency
16.5 / 4.8
20.0 / 5.9
25.3 / 7.4
26.3 / 7.7
JOHNSON CONTROLS
MODEL: YCWL0157SE46
AHRI CAPACITY 144.0 TONS
YCWL
131 TO 200
jOHNSON CONTROLS
119
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0157HE46
148.5
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
355.9
11.6
Water
0.00010
77.0
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
54.5/54.5
310.0/310.0
85.0
95.0
422.4
12.4
Water 0.0
0.00025
59.1
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
17.1 / 5.0
24.2 / 7.1
Electrical Data
2
54.5/54.5
310.0/310.0
6863
7807
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
231.6
400.0
250.0
250.0
() -
Notes:
104.3
104.3
Load %
100.0
75.0
50.0
25.0
120
218.0
310.0
Across the Line
Capacity (Tons)
148.5
116.8
81.4
39.9
Compressor kW
104.3
67.2
37.7
17.8
Unit Efficiency
17.1 / 5.0
20.9 / 6.1
25.9 / 7.6
26.9 / 7.9
JOHNSON CONTROLS
MODEL: YCWL0157HE46
AHRI CAPACITY 148.5 TONS
YCWL
131 TO 200
jOHNSON CONTROLS
121
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0177SE46
166.6
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
399.3
14.2
Water
0.00010
77.0
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
49.2/49.2/49.2
242.0/242.0/242.0
85.0
95.0
477.9
15.3
Water 0.0
0.00025
59.1
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
17.1 / 5.0
25.4 / 7.4
Electrical Data
2
49.2/49.2
242.0/242.0
7318
8262
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
300.0
(1)#4 - 500
246.0
242.0
Across the Line
117.1
117.1
Load %
100.0
80.0
60.0
40.0
20.0
122
258.0
400.0
300.0
Capacity (Tons)
166.6
141.0
108.3
73.3
35.6
Compressor kW
117.1
80.8
52.8
31.0
15.2
Unit Efficiency
17.1 / 5.0
20.9 / 6.1
24.6 / 7.2
28.4 / 8.3
28.2 / 8.3
JOHNSON CONTROLS
jOHNSON CONTROLS
15"
30"
23 1/2"
9"
8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
5 9/16" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
5 9/16" CONDENSER
WATER OUTLET
VICTAULIC
77 1/2"
CONNECTION
PRODUCT DRAWING
41"
29"
17 11/16"
34 13/16"
OVERALL WIDTH
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 7,318, OPERATING - 8,262.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 62.9", Y= 11.7"
34"
9"
50"
132 3/4"
102"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
37 5/8"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 3/16"
7 1/8"
50"
2,229 (LB)
1,902 (LB)
14 7/8"
143 7/16"
125 13/16"
Y
11 7/8"
36 1/4"
8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
10 3/8"
2,229 (LB)
MODEL: YCWL0177SE46
AHRI CAPACITY 166.6 TONS
YCWL
131 TO 200
123
Capacity (Tons)
Volts/Ph/Hz
Refrigerant
YCWL0198SE46
198.4
460/3/60
R410A
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
Condenser Data
54.0
44.0
475.6
19.6
Water
0.00010
77.0
Circuit
Compressor RLA
Compressor Start Current (LRA)
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)
1
49.2/49.2/49.2
242.0/242.0/242.0
85.0
95.0
566.2
20.4
Water 0.0
0.00025
59.1
Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data
16.8 / 4.9
24.8 / 7.3
Electrical Data
2
49.2/49.2/49.2
242.0/242.0/242.0
7673
8617
Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type
Notes:
350.0
(1)#4 - 500
295.2
242.0
Across the Line
141.9
141.9
Load %
100.0
83.3
66.7
50.0
33.3
16.7
124
308.0
400.0
350.0
Capacity (Tons)
198.4
172.0
144.2
110.2
73.0
35.8
Compressor kW
141.9
106.6
76.0
50.6
31.5
15.5
Unit Efficiency
16.8 / 4.9
19.4 / 5.7
22.8 / 6.7
26.1 / 7.6
27.8 / 8.1
27.7 / 8.1
JOHNSON CONTROLS
jOHNSON CONTROLS
15"
30"
23 1/2"
9"
8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION
5 9/16" CONDENSER
WATER INLET
VICTAULIC
CONNECTION
5 9/16" CONDENSER
WATER OUTLET
VICTAULIC
77 1/2"
CONNECTION
PRODUCT DRAWING
41"
29"
17 11/16"
34 13/16"
OVERALL WIDTH
1"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 7,673, OPERATING - 8,617.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 62.9", Y= 11.7"
34"
9"
143 7/16"
50"
102"
Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS
132 3/4"
125 13/16"
37 5/8"
Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:
5 3/16"
7 1/8"
50"
2,371 (LB)
1,938 (LB)
14 7/8"
Y
11 7/8"
36 1/4"
8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION
10 3/8"
2,371 (LB)
MODEL: YCWL0198SE46
AHRI CAPACITY 198.4 TONS
YCWL
131 TO 200
125
126
JOHNSON CONTROLS