Академический Документы
Профессиональный Документы
Культура Документы
7-1
Section 7
Boilers and Thermal Oil Systems
I. Boilers
A.
General
1.
Scope
1.1
For the purpose of these Rules, the term
"boiler" includes all closed vessels and piping systems
used for:
a)
above
b)
4.
1.2
Steam and hot water generators as defined in
1.1 are subject to the Rules set out in B. to F., or, if
appropriate, in G.
4.2
The maximum allowable working pressure
(PB, design pressure) is the approved steam pressure
in bar (gauge pressure) in the saturated steam space
prior to entry into the superheater. In continuous flow
boilers, the maximum allowable working pressure is
the pressure at the superheater outlet or, in the case of
continuous flow boilers without a superheater, the
steam pressure at the steam generator outlet.
Other Rules
4.1
Steam boiler walls are the walls of the steam
and water spaces located between the boiler isolating
devices. The bodies of these isolating devices form
part of the boiler walls.
4.3
The heating surface is that part of the boiler
walls through which heat is supplied to the system,
a)
b)
2.1
As regards their construction and installation,
steam boiler plants are also required to comply with
the applicable statutory requirements and regulations
of the ship's country of registration.
3.
Definitions
H [m2]
N 860
18000
7-2
5.1
The highest flue is the highest point on the
side of the heating surface which is in contact with the
water and which is exposed to flame radiation or
heated by gases which temperature exceeds 4000C at
maximum continuous power. The highest flue on
water tube boilers with an upper steam drum is the top
edge of the highest gravity tubes.
5.2
The requirements relating the highest flue do
not apply to
Water tube boiler risers up to 102 mm outer
diameter
Once-through forced flow boilers
Superheaters
Flues and exhaust gas heated parts in which
the temperature of the heating gases does not
exceed 4000C at maximum continuous power
5.3
The lowest water level must lie at least 150
mm above the highest flue also when the ship heels 40
to either side. Heated surfaces with a set highest flue
must remain wetted even when the ship is at the static
heeling angles laid down in Section 1, Table 1.1. The
height of the water level is critical to the response of
the water level limiters.
5.4
The heat accumulated in furnaces and other
heated boiler parts may not lead to any undue
lowering of the water level due to subsequent
evaporation when the firing system is swiched off.
The lowest water level is to be set so that the dropping
time does not exceed 5 minutes.
5.5
The "dropping time" is the time taken by the
water level, under conditions of interrupted feed and
allowable steam output, to drop from the lowest
working level to the level of the highest point of the
gas or flame path, i.e.:
t
t
V
D
v'
V
D v
6.
6.1
The facility is to be provided for manual
operation. At least the water level limiters must
remain active even in manual operation.
6.2
Manual operation demands constant and
direct supervision of the system.
6.3
For detailed requirements in respect of
manual operation of the firing system see Section 9.
7.
B.
Materials
1.
General requirements
Approved materials
Material testing
3.1
The materials of boiler parts subject to
pressure, including exhaust gas economizer tubes,
must be tested by the Society in accordance with the
Rules for Materials (cf. Table 7.1). Material testing by
the Society may be waived in the case of:
a)
b)
5.6
The lowest specified water level is to be
indicated permanently on the boiler shell by means of
a water level pointer. Reference plates are to be
attached additionally beside or behind the water level
gauges pointing at the lowest water level.
Manual operation
7-3
Approved materials
Limits of application
Steel pipes
DIN 267
Parts 3 and 4
or other equivalent standards
Cast steel for boilers, pressure
vessels and pipelines.
Steel castings
300 C
300 C
40 bar
DN 175 for valves
and fittings
200 C
10 bar
200 mm diameter
200 C
10 bar
DN 175
52 bar
smoke gas temperature
600 C
water outlet temperature
245 C
100 bar
smoke gas temperature
700 C
water outlet temperature
260 C
7-4
3.2
Special agreements may be made regarding the
testing of unalloyed steels to recognized standards.
3.3
The materials of valves and fittings must be
tested by the Society in accordance with the datas
specified in Table 7.2.
3.4
Parts not subject to material testing, such as
external supports, lifting brackets, pedestals etc. must be
made of materials suitable for the intended purpose and
in accordance with accepted engineering practice.
C.
1.
Type of
materials 1)
Steel, cast steel
Service
temperature
[ C]
Testing required
for: PB in [bar]
DN in [mm]
> 300
DN > 32
300
PB x DN > 2500 2)
or
DN > 250
Copper alloys
225
PB x DN > 1500 2)
2.
32 mm.
Welding
Riveting
Tube expansion
5.1
Stays, stay tubes and stay bolts are to be
arranged that they are not subjected to undue bending or shear forces.
Stress concentrations at changes in cross-section,
in screw threads and at welds are to be minimized
by suitable component geometry.
5.2
Stays and stay bolts are to be welded by
full penetration preferably. Any vibrational stresses
are to be considered for long stays.
5.3
Stays are to be drilled at both ends in such
a way that the holes extend at least 25 mm into the
water or steam space. Where the ends have been
upset, the continuous shank must be drilled to a
distance of at least 25 mm.
5.4
Wherever possible, the angle made by gusset stays and the longitudinal axis of the boiler
shall not exceed 30 . Stress concentrations at the
welds of gusset stays are to be minimized by
suitable component geometry. Welds are to be
executed as full-strength welds. In firetube boilers,
gusset stays are to be located at least 200 mm from
the firetube.
5.5
Where flat surfaces exposed to flames are
stiffened by stay bolts, the distance between
centers of the stay bolts shall not generally exceed
200 mm.
6.
6.1
Where flat end surfaces are stiffened by
profile sections or ribs, the latter shall transmit
their load directly (i.e. without welded-on straps) to
the boiler shell.
6.2
Doubling plates may not be fitted at
pressure parts subject to flame radiation.
Where necessary to protect the walls of the boiler,
strengthening plates are to be fitted below supports
and lifting brackets.
7.
7-5
D.
Design Calculation
1.
Design principles
1.1
Range of
formulae
applicability
of design
9.1
Steam boilers are to be provided with openings
through which the space inside can be cleaned and
inspected. Boiler vessels with an inside diameter of more
than 1200 mm and those measuring over 800 mm in
diameter and 2000 mm in length are to be provided with
means of access. Parts inside drums must not obstruct
inner inspection or must be capable of being removed.
1.1.1 The following strength calculations represent the minimum requirements for normal
operating conditions with mainly static loading.
Separate allowance must be made for additional
forces and moments of significant magnitude.
Proper treatment and adequate monitoring of the
feedwater are assumed to be carried out.
9.2
Inspection and access openings are required to
have the following minimum dimensions:
Manholes
Headholes
1.2
Handholes
87 x 103 mm
Sight holes
9.3
The edges of manholes and other openings, e.g.
for domes, are to be effectively strengthened if the plate
has been unacceptably weakened by the cutouts. The
edges of openings closed with covers are to be reinforced
by flanging or by welding on edge-stiffeners if it is likely
that the tightening of the crossbars etc. would otherwise
cause undue distortion of the edge of the opening.
9.4
Cover plates, manhole stiffeners and crossbars
must be made of ductile material (not grey or malleable
cast iron). Grey cast iron (at least GG-20) may be used
for handhole cover crossbars of headers and sectional
headers, provided that the crossbars arc not located in the
heating gas flow. Unless metal packings are used, cover
plates must be provided on the external side with a rim or
spigot to prevent the packing from being forced out. The
gap between this rim or spigot and the edge of the
opening is to be uniform round the periphery and may not
exceed 2 mm for boilers with a working pressure of less
than 32 bar, or 1 mm where the pressure is 32 bar or
over. The height of the rim or spigot must be at least 5
mm greater than the thickness of the packing.
9.5
Design pressure pc
!
"
7-6
1.3
Design temperature t
Design temperatures
Allowance to be added
Reference
temperature Unheated
parts
radiation
c)
Grey cast
iron :
Rm,20
11
1.4.3
Special arrangements may be agreed for
high-ductility austenitic steels.
1.4.4
In the case of cylinder shells with cutouts
and in contact with water, a nominal stress of 170
N/mm shall not be exceeded in view of the protective magnetite layer.
1.4.5
Mechanical characteristics are to be taken
from the Rules for Materials or from the standards
specified therein.
1.5
Saturation
temperature
at m.a.w.p
0 C
25 C
50 C
Superheated
steam
temperature
15 C 1)
35 C
50 C
1.6
1)
1.4
Allowable stress
$
%
at room
where ReH,t = gu a r a n t e e d yi e l d p o i n t o r
minimum 0,2 % proof stress at
design temperature t.
where Rm100000,t=
1.4.2
Cast materials
a)
Cast steel :
b)
Rm,20
Nodular cast
3,2
ReH,t
Rm,20
4,8
2,0
;
Cylindrical
pressure
2.1
Scope
3,0
shells
under
internal
Symbols
pc
Di
Da
design
Rm,100000,t
ReH,t
Special cases
2,0
t,tl,tu
[-]
perm
cumferential seams)
2.3.3
weakening factor
for welds :
the qualitative ratio of the welded
joints to the plate (weld quality rating)
Table 7.4
Construction
Weakening factor v
Seamless shell
rings and drums
1,0
sA
sS
ls
l's
Ap
Weakening factor v
Weakening factor v
Rows of holes1)
2.3.4
Weakening effects due to cutouts or individual branch pipes are to be taken into account by
area compensation in accordance with the
expression:
Pc
10
Ap
A
1
2
(2)
perm
Fig. 7.1
2.3
7-7
Design calculations
2.3.1
The necessary wall thickness s is given by the
expression :
s
Da pc
20
perm
pc
(1)
2.3.2
In the case of heated drums and headers with a
max. allowable working pressure of more than 25 bar,
special attention is to be given to thermal stresses.
For heated drums not located in the first pass (gas
temperature up to 1000 C max.), special certification in
respect of thermal stresses may be waived subject to the
following provision:
Wall thickness up to 30 mm and adequate cooling of the
walls by virtue of close tube arrangement. The
description "close tube arrangement" is applicable if the
ligament perpendicular to the direction of gas flow and
parallel to the direction of gas flow does not exceed 50
mm and 100 mm respectively.
Fig. 7.2
The values of the supporting lengths may not
exceed:
for the parent
component
( Di
for the
branch pipe ls 1,25 ( d
sA
sS
c ) ( sA
c ) ( sS
c)
c)
7-8
2 ( Di
sA
c) ( sA
c)
3.1
Scope
Symbols
pc
[bar]
design pressure
[mm]
wall thickness
[mm]
da
[mm]
di
[mm]
[mm]
[mm]
[mm]
[%]
percentage out-of-roundness of
tube
[mm]
Fig. 7.3
[N/mm]
allowable stress
Et
[N/mm]
SK
[-]
[-]
3.3
Design calculations
3.3.1
sS
sA
2.4
perm
Pc
2 (s c)
10 perm
1 0,1
1 0,03
d
s c
d
l
(3)
1 5
d
l
pc
20
Et
Sk
s c
da
(n
1) 1
s c
da
n
Z
3 (1
7-9
n2 1
n
Z
(4)
3.8
Modulus of elasticity
where :
and
da
Z
n
2 l
n>Z
n (integer) is to be chosen as to reduce pc to its minimum
value. n represents the number of buckled folds occurring
round the periphery in the event of failure. n can be
estimated by applying the following approximation
formula:
4
1,63
da
t = saturation
temperature
+ 4 . s + 30 oC
corrugated
tubes
t = saturation
temperature
+ 3 . s + 30 oC
3.4
pc
20
di
t = saturation temperature + 2 . s
+ 15 oC
1 mm
(5)
perm
Allowable stress
3.5
Re,H,t
Re,H,t
2,0
Re,H,t
2,8
Re,H,t
2,0
Design temperature
Stiffening
Fig. 7.4
Table 7.6 Values for the modulus of elasticity
2,5
but at least
250 oC
da
s
plain tubes
Safety factor Sk
3.9
Design
temperature
[oC]
Et 1 )
[N/mm2]
20
250
300
400
500
600
206000
186400
181500
171700
161900
152100
7-10
Wall thickness s
[mm]
2 (dmax
dmax
dmin)
dmin
up to 50
over 50 up to 80
over 80 up to 100
over 100 up to 120
over 120
100
4 a
100
d
h
[mm]
150
120
100
75
50
4.1.2
These Rules also apply to welded
end-plates. Due account is to be taken of the
quality rating of the weld (cf. 4.5 ).
4.2 Symbols
&
3.13
Out-of-roundness
'
pc
Da
Firetube spacing
4.1
Scope
4.1.1
The following Rules apply to the design of
unstayed dished end-plates under internal or external
perm
7-11
Fig. 7.6
[-] coefficient of stress in spherical
section
Et
sA
Ss
of
parent
Design coefficients
and
) *
and s / Da.
[mm] supporting
component
ls
l's
Ap
Sk
S'k
4.3
Da pc
40
perm
(6)
0,1935 Da + 0,55 s
7-12
7-13
Ap
1
2
perm
(7)
Fig. 7.9
pc
Fig. 7.8
For calculation of reinforcements and supporting
lengths the formulae and prerequsites in 2.3.4 are
applicable.
The relationship between respective areas of cutouts
exerting a mutual effect is shown in Fig. 7.9.
The edge of disk-shaped reinforcements may not
extend beyond 0,8 D a .
sA
4.4
Sk
(8)
Table 7.8
Et
3,66
s-c
R
Sk1)
Sk'1)
0,001
5,5
4,0
0,003
4,0
2,9
0,005
3,7
2,7
0,01
3,5
2,6
0,1
3,0
2,2
7-14
4.5
bending moment
Fig. 7.10
4.6
[mm]
da
[mm]
a, b
[mml
tl, t2
[mm]
e1, e2
[mm]
[mm2]
rK
[mm]
[mm]
inner depth of a
welding-neck end-plate
[-]
design coefficient
[-]
ratio
Flat surfaces
5.1
Scope
perm
de
Symbols
pc
[bar]
design pressure
[mm]
wall thickness
s1
[mm]
s2
[mm]
Db
[mm]
D 1, D 2
[mm]
Dl
[mm]
[N/mm2]
[mm]
5.3
flat,
5.3.1
Flat, circular, flanged, unpierced end-plates
(cf.Fig.7.11).
The necessary wall thickness s is given by the
expression:
5.3.2
C ( Db
rK )
pc
10
c
perm
Circular plates
Fig. 7.11
(9)
7-15
Fig. 7.15
The required wall thickness s is given by the
expression:
s
C b y
5.3.4
pc
10
(11)
c
perm
Welding-neck end-plates.
Fig. 7.17
Fig. 7.13
s1
0,77 s2
s1
0,55 s2
Fig. 7.14
C Db
pc
10
c
perm
s1
pc
10
Db
2
rK
1,3
(12)
perm
(10)
and for rectangular end-plates:
s1
pc
a b 1,3
10 a b perm
(13)
7-16
5.4.1
For flat surfaces which are uniformly braced
by stay bolts, circular stays or stay tubes, cf. Fig. 7.18.
C de
pc
10
(16)
c
perm
or
s
Fig. 7.18
Fig. 7.19
10
10
(17)
c
perm
5.4.4
Flat annular plates with central longitudinal
staying, see Fig. 7.21.
pc ( t1
pc
Cby
t2 )
(14)
perm
5.4.2
For flat plates which are nonuniformly
braced by stay bolts, circular stays and stay tubes, cf.
Fig. 7.19.
The necessary wall thickness s inside the stayed areas
is given by the expression:
s
e1
e2
2
pc
10
Fig. 7.21
The required wall Thickness s is given by the
expression:
(15)
perm
5.4.3
For flat plates which are braced by gusset
stays, supports or other means and flat plates between
arrays of stays and tubes, cf. Fig. 7.20.
5.5
0,25 ( D1
D2
rK1
rK2 )
pc
10
(18)
perm
5.5.1
Application of the above formulae to flanged
end-plates and to flanges as a means of staying is
subject to the provision that the corner radii of the
flanges should have the following minimum values in
relation to the outside diameter of the endplate (cf.
Table 7.9).
In addition, the flange radii rK (Figs. 7.11, 7.20 and
7.21) must be equal to at least 1,3 times the wall
thickness.
Fig. 7.20
5.5.2
In the case of welding-neck end-plates
without a stress relieving groove for headers, the
flange radius must be rK
1/3 s, subject to a
minimum of 8 mm, and the inside depth of the
end-plate must be h
s, s for end-plates with
openings being the thickness of an unpierced
over 500
over1400
over 1600
over 1900
5.6
Corner radius of
flanges
[mm]
30
35
40
45
50
Ratio b/a 1)
0,75
0,5
0,25
0,1
Rectangle
1,10
1,26
1,40
1,52
1,56
Ellipse
1,00
1,15
1,30
---
---
5.7
Values of ratio y
1,0
C 1)
Shape
Ratio y
Table 7.10
7-17
Plates which are bolted at their circumference and are thereby subjected to an
additional bending moment according to the
ratio :
Dl/Db = 1,0
0,45
Coefficient C
= 1,1
0,50
= 1,2
0,55
= 1,3
0,60
0,35
C = (C1 + C2 ......Cn) / n
0,40
5.8
5.9
0,45
5.9.1
With expanded tubes, the minimum plate
thickness is 12 mm. Concerning safeguards against
the dislodging of expanded tubes, see 6.3.2.
Table 7.11
5.9.2
The wall thickness of flat end-plates should
not exceed 30 mm in the heated portion.
steel
f [mm2] = 15 + 3,4 da
5.10
Reinforcement of openings
7-18
A1
(19)
perm
6.3.2
Where expanded tubes are used, a sufficient
safety margin must additionally be applied to prevent
the tubes from being pulled out of the tube plate. Such
a safety margin is deemed to be achieved if the
permissible load on the supporting area does not
exceed the values specified in Table 7.13.
6.1
Scope
The following Rules apply to longitudinal stays, gusset stays, stay tubes, stay bolts and stiffening girders
of steel or copper and are subject to the requirements
set out in C.5.
6.2
[bar]
[N]
A2 = 0,1 da lo
Table 7.13
[mm ]
Type of
expanded
connection
Permissible load on
supporting area
[N/mm2]
F / A2
150
With groove
F / A2
300
With flange
F / A2
400
calculated
required
cross-section area of stays, stay
bolts and stay tubes
supported area of expanded
tubes
Ap
[mm2]
da
[mml
di
[mm]
lo
[mm]
a1
[mm]
[N/mm2]
Plain
[mm2]
6.3
subject to a maximum
of :
design pressure
A2
perm
A2 = (da - di) lo
Symbols
pc
A1
allowable stress
Design calculation
a1
1,25 A1
(20)
Allowable stress
Re,H,t
1,8
7.1
Scope
7-19
7.2
8.
8.1
Symbols
Symbols
pc
[bar]
design pressure
[mm]
wall thickness
da
[mm]
perm
[N/mm2]
[-]
7.3
allowable stress
weld quality rating of
longitudinally welded tubes
pc
[bar]
design pressure
[mm]
wall thickness
2m
[mm]
2n
[mm]
clear
width of the
rectangular-tube perpendicular
to the wall in question
[mm]
coefficient according
formula (23)
[mm]
[mm]
pitch of holes
[mm]
hole diameter
[-]
v'
[-]
7.4
da pc
20
perm
pc
(21)
Design temperature t
Allowable stress
ReH,t
2,0
7.6
is to be applied.
Quality rating of weld, v
[mm]
perm
8.2
[N/mm]
to
Design calculation
8.2.1
The wall thickness is to be calculated for the
center of the side and for the ligaments between the
holes. The maximum calculated wall thickness shall
govern the wall thickness of the entire rectangular
tube.
The following method of calculation is based on the
assumption that the tube connection stubs have been
properly mounted, so that the wall is adequately
stiffened.
8.2.2
The required wall thickness is given by the
expression :
If there are several different rows of holes, the
necessary wall thickness is to be determined for each
row.
s
pc n
20
perm
4,5 Z pc
v
10
perm
v,
(22)
8.2.3
Z
(m2
3 m n 2
a 2)
(23)
7-20
Where Z has a negative value, the sign is to be disregarded when incorporating the term into formula (22).
8.5
8.3
8.5.1
The minimum wall thickness for expanded
tubes shall be 14 mm.
Weakening factor v
8.3.1
If there is only one row of holes, or if there
are several parallel rows not staggered in relation to
each other, the weakening factors v and v' are to be
determined as follows :
v
v
v
d
t
v
t
d
t
0,6 m
for wholes where d > 0,6 m
t
8.3.2
In determining the values of v and v' for
elliptical holes, d is to be taken as the clear width of
the holes in the longitudinal direction of the
rectangular tube. However, for the purpose of
deciding which formula is to be used for determining
v', the value of d in the expressions d > 0,6 m and
d < 0,6 m is to be the clear width of the hole
perpendicular to the longitudinal axis.
8.3.3
In calculating the weakening factor for
staggered rows of holes, t is to be substituted in the
formula by t for the oblique ligaments (Fig. 7.25).
8.3.4
For oblique ligaments, the value of Z to be
used in formula (22) is that determined by applying
formula (23), with a = 0, and multiplying by cos .
8.5.2
The width of a ligament between two
openings or tube holes may not be less than 1/4 of the
distance between the tube centers.
9.
9.1
Scope
8.4
Stress at corners
General
Symbols
pc
[bar]
[N]
[mm]
[mm]
[mm]
thickness of girder
[mm]
height of girder
[mm3]
[Nmm]
[-]
z
Fig. 7.25
perm
9.4
[N/mm ]
design pressure
load carried by one girder
Design calculation
9.4.1
The simply supported combustion chamber
girder shown in Fig. 7.26 is to be treated as a simply
supported beam of length l. The support afforded by
the plate material crown may also be taken into
consideration.
Fig. 7.26
Mmax
1,3
perm
b h2
6
(24)
Fl
8
(25)
Symbols
pc
[bar]
design pressure
p'
[bar]
test pressure
FS
[N]
F'S
[N]
FSo
[N]
FB
[N]
FD
[N]
FDo
[N]
FZ
[N]
Db
[mm]
di
[mm]
ds
[mm]
shank diameter
necked-down bolt
dk
[mm]
[-]
where
F
10.
Bolts
10.1
Scope
pc
10
l e
(26)
General
7-21
perm
[N/mm2]
[-]
number of
connection
bolts
of
in
forming
allowable stress
surface finish coefficient
[mm]
additional allowance
k1
[mm]
ko
[mm]
KD
[N/mm2]
10.4
Design calculation
Service conditions
(design pressure pc and design temperature
t),
b)
7-22
4 Fs
perm
(27)
FB
FD
Db
(28)
pc
(29)
10
Db k1
pc
10
(30)
FZ
b)
pc
10
p
FB
pc
FD
1,2
(31)
0.8
FS FDO
(34)
steam temperature - 30 C
Fixed flange
+ loose flange
steam temperature - 25 C
Fixed flange
+ fixed flange
FZ
0,2 FDO
10.5
1,2
di
FDO
Allowable stress
perm
are shown in
c)
(32)
FDO = Db
(33)
ko KD
Table 7.14
Condition
Service
condition
Allowable stress
perm
Re,H,t
Re,H,t
1,5
1,6
Test pressure
and zeropressure
assembled
condition
10.7
Re,H,20
Re,H,20
1,2
1,1
Additional allowance c
Additional allowances c
Condition
For service conditions :
up to M 24
M 27 up to M 45
M 48 and over
c [mm]
3
5 - 0,1 . dk
1
E.
1.
General
1.1
The following requirements apply to steam
boilers which are not constantly and directly
monitored during operation. Note is also to be taken
of the official regulations of the flag country of the
vessel, where appropriate.
1.2 In the case of steam boilers which are monitored
constantly and directly during operation, some easing
of the following requirements may be permit ted,
while maintaining the operational safety of the vessel.
7-23
Safety valves
2.1 Any steam boiler which has its own steam space
is to be equipped with at least two reliable, springloaded safety valves. At least one safety valve is to be
set to respond if the maximum allowable working
pressure is exceeded.
In combination, the safety valves must be capable of
discharging the maximum quantity of steam which can
be produced by the steam boiler during continuous
operation without the maximum allowable working
pressure being exceeded by more than 10 %.
2.2 Any steam boiler which has a shut-off but which
does not have its own steam space is to have at least
one reliable, spring-loaded safety valve fitted at its
outlet. At least one safety valve is to be set to respond
if the maximum allowable working pressure is
exceeded. The safety valve or safety valves are to be
designed so that the maximum quantity of steam
which can be produced by the steam boiler during
continuous operation can be discharged without the
maximum allowable working pressure being exceeded
by more than 10 %.
2.3 External steam drums are to be fitted with at
least two reliable, spring-loaded safety valves. At least
one safety valve is to be set to respond if the
allowable working pressure is exceeded. In
combination, the safety valves must be capable of
discharging the maximum quantity of steam which can
be produced in continuous operation by all connected
steam generators without the maximum allowable
working pressure of the steam drum being exceeded
by more than 10 %.
2.4 The closing pressure of the safety valves shall
be no more than 10 % below the response pressure.
2.5 The minimum flow diameter of the safety valves
must be 15 mm.
2.6 Servo-controlled safety valves are permitted
wherever they are reliably operated without any
external energy source.
2.7 The safety valves are to be fitted to the saturated
steam part or, in the case of steam boilers which do
not have their own steam space, to the steam-water
outlet of the boiler.
7-24
Pressure gauges
4.1
Each steam boiler is to be fitted with two
pressure gauges which are linked to the steam space.
The allowable maximum working pressure is to be
marked on the dial by means of a permanent and
easily visible red mark. The display range of the
pressure gauge must include the test pressure. One
pressure gauge must be located on the boiler and
another at the machinery control station or at some
other appropriate site.
Where several steam boilers are incorporated on one
ship, the steam chambers of which are linked together,
one pressure gauge is sufficient at the machinery
control station or at some other suitable location, in
addition to the pressure gauges on each boiler.
4.2
The pipe to the pressure gauge must have a
water trap and must be of a blow-off type. A
connection for a test gauge must be installed close to
the pressure gauge. In the case of pressure gauges
which are set off at a lower position the test
connection must be provided close to the pressure
gauge and also close to the connection piece of the
pressure gauge pipe.
4.3
Pressure gauges are to be protected against
radiant heat and must be well illuminated.
5.
Temperature gauges
5.1
A temperature gauge is to be fitted to the flue
gas outlets of fired steam boilers.
6.1
With the exception of boilers which are
heated by exhaust gas, steam boilers are to be
operated with rapid-control, automatic firing systems.
In main boilers, the control facility must be capable of
safely controlling all rates of speed and manoeuvres
so that the steam pressure and the temperature of the
super-heated steam stay within safe limits and the
supply of feed water is guaranteed. Auxiliary boilers
are subject to the same requirements within the scope
of potential load changes.
7-25
7.5
Where there is a possibility of oil or grease
getting into the steam or condensate system, a suitable
automatic and continuously operating unit is to be
installed which trips an alarm and cuts off the feed
water supply if the concentration at which boiler
operation is put at risk is exceeded.
7.6
Where there is a possibility of acid, lye or
seawater getting into the steam or condensate system,
a suitable automatic and continuously operating unit
is to be installed which trips an alarm and cuts off the
feed water supply if the concentration at which boiler
operation is put at risk is exceeded.
7.7
It must be possible to carry out function testing of the monitoring devices, even during operation,
if an equivalent degree of safety is not attained by
self-monitoring of the equipment.
7.8
The monitoring devices must trip visual and
audible fault warnings in the boiler room or in the
machinery control room or any other suitable site. Cf
Rules for Automation, Volume VII.
6.2
Steam pressure must be automatically regulated by controlling the supply of heat. The steam
pressure of boilers heated by exhaust gas may also be
regulated by condensing the excess steam.
8.1
The suitability of safety devices for marine
use is to be proven by type testing.
6.3
In the case of boilers which have a specified
minimum water level, the water level must be regulated automatically by controlling the supply of feed
water.
8.2
Fired boilers are to be equipped with a reliable pressure limiter which cuts out and interlocks the
firing system when the maximum allowable working
pressure is exceeded.
6.4
In the case of forced-circulation boilers
whose heating surface consists of a steam coil and
once-through forced flow boilers, the supply of feed
water may be regulated as a function of fuel supply.
8.3
In steam boilers on whose heating surfaces a
highest flue is specified, two reliable, mutually
independent water level limiters must respond to cut
out and interlock the firing system when the water
falls below the specified minimum water level. The
water level limiter must also be independent of the
water level control devices.
6.5
In the case of steam boilers which are fitted
with superheaters, the temperature of the superheated
steam must be automatically regulated unless the
calculated temperature is higher than the maximum
attainable temperature of the superheater walls.
7.
7.1
A warning device is to be fitted which is
tripped when the specified maximum water level is
exceeded.
7.2
In exhaust-gas heated boilers, a warning
device is to be fitted which is tripped when the
maximum allowable working pressure is exceeded.
7.3
In exhaust-gas heated boilers with a specified
minimum water level, a warning device is to be fitted
which is tripped when the water falls below this level.
7.4
Exhaust gas boilers with finned tubes are to
have a temperature monitor fitted in the exhaust gas
pipe which trips an alarm in the event of fire. Cf.
Rules for Automation, Volume VII.
8.
8.4
The receptacles for water level limiters
located outside the boiler must be connected to the
boiler by means of lines which have a minimum inner
diameter of 20 mm. Shut-off devices in these lines
must have a nominal diameter of at least 20 mm and
must indicate their open or closed position. Where
water level limiters are connected by means of
common connection lines, the connection pipes on the
water side must have an inner diameter of at least
40 mm.
Operation of the firing system may only be possible
when the shut-off devices are open or else, after
closure, the shut-off devices must reopen
automatically and in a reliable manner.
Water level limiter receptacles which are located
outside the boiler are to be designed in such a way
that a compulsory and periodic blow-through of the
receptacles and lines can be carried out.
8.5
7-26
9.1
For details of boiler feed and circulation devices, see Section 11, F. The following requirements
are also to be noted:
9.2
The feed devices are to be fitted to the steam
boiler in such a way that it cannot be drained lower
than 50 mm above the highest flue when the non-return valve is not tight.
9.3 The feed water is to be introduced into the
boiler in such a way as to prevent damage occurring to
the boiler walls and to heated surfaces.
10.
Shut-off devices
Name plate
c)
Manufacturer,
7-27
14.
Installation of boilers
14.1
Mounting
13.
14.2
13.1 Materials
Valves and fittings for boilers must be made of ductile
materials as specified in Table 7.1 and all their
components must be able to withstand the loads
imposed in operation, in particular thermal loads and
possible stresses due to vibration. Grey cast iron may
be used within the limits specified in Table 7.1, but
may not be employed for valves and fittings which are
subjected to dynamic loads, e.g. safety valves and
blow-off valves.
Fire precautions
F.
Testing of Boilers
1.
Constructional test
Care is to be taken to ensure that the bodies of shutoff gate valves cannot be subjected to unduly high
pressure due to heating of the enclosed water. Valves
with screw-on bonnets must be safeguarded to prevent
unintentional loosening of the bonnet.
13.3
2.
Design
a)
Tightness test with air (test pressure approximately 0,1 x working pressure; maximum 2 bar);
b)
7-28
economizer.
G.
1.
Design
Equipment
Testing
Equipment
H.
1.
Definition
Materials
See under B.
3.
Design calculation
7-29
5.
6.
Tests
Name plate
7-30
Table 7.16
Jointing factors
Jointing Factor 1)
Shape
Description
Material
for liquids
assembly2)
assembly2)
service
ko . KD
k1
ko
ko . KD
k1
[mm]
[N/mm]
[mm]
[mm]
[N/mm]
[mm]
impregnated
sealing
material
20 bD
bD
rubber
bD
0,5 bD
2 bD
0,5 bD
Teflon
20 bD
1,1 bD
25 bD
1,1 bD
It
15 bD
bD
ko
flat seals to
DIN 2690
up to
DIN 2692
1,3 bD
bD
200
spirally
wound
gasket
hD
unalloyed
steel
15 bD
bD
50 bD
1,3 bD
Al
8 bD
0,6 bD
30 bD
0,6 bD
Cu, Brass
9 bD
0,6 bD
35 bD
0,7 bD
mild steel
10 bD
0,6 bD
45 bD
1,0 bD
Al
10 bD
bD
50 bD
1,4 bD
Cu, Brass
20 bD
bD
60 bD
1,6 bD
mild steel
40 bD
bD
70 bD
1,8 bD
flat gasket
to
DIN 2694
0,8 bD
bD+5
bD
bD+5
diamont
gasket
0,8
corrugated
gasket
metalsheated
gasket
Table 7.16
7-31
Shape
Description
Material
assembly2)
service
ko
ko . KD
k1
[mm]
[N/mm]
[mm]
ko
ko . KD
[mm] [N/mm]
service
k1
[mm]
oval
gasket
1,6
round
gasket
1,2
1,5
ring
gasket
1,6
U-shaped
gasket to
DIN 2696
1,6
9+0,2.Z
9+0,2.Z
corrugated
gasket to
DIN 2697
membrane
welded
gasket to
DIN 2695
0,4 Z
0,5 Z
Deformation factor KD
[N/mm]
7-32
492
185
343
392
441
491
NOTE :
At room temperature KD is to be substituted by the deformation factor at 10
% compression 10 or alternatively by the tensile strength Rm
Fig.7.27
Weakening factor v for cylindrical shells with symmetrically staggered rows of holes
7-33
7-34
A.
General
1.
Scope
3.3
The "discharge temperature" is the
temperature of the thermal oil immediately at the
heater outlet.
3.4
The "return temperature" is the temperature
of the thermal oil immediately at the heater inlet.
3.5
The "film temperature" is the wall
temperature on the thermal oil side. In the case of
heated surfaces, this may differ considerably from the
temperature of the thermal oil.
4.
For materials,
fabrication and design
of the heaters
5.
For automated
machinery systems
3.
Definitions
3.1
The "maximum allowable working pressure"
is the maximum pressure which may occur in the individual parts of the equipment under service conditions.
3.2
The "thermal oil temperature" is the
temperature of the thermal oil at the center of the flow
cross-section.
7-35
6.
Manual operation
B.
Heaters
1.
Acceptable materials
Testing of materials
Design
4.
Equipment
4.2.1
Temperature measuring devices are to be
fitted at the discharge and return line of both oil fired
heaters and heaters heated by exhaust gas.
4.2.2
Temperature measuring devices are also to be
fitted in the flue gas or exhaust gas stream at the
heaters outlet.
4.2.3
The flow of the thermal oil must be
indicated.
4.3
Temperature control
4.3.1
For automatic control of the discharge
temperature, oil fired heaters are to be equipped with
an automatic rapidly adjustable heat supply in
accordance with Section 9, A. and B.
4.3.2
The discharge temperature of heaters heated
by exhaust gas must be controlled by automatic
regulation of the heat input or by recooling the
thermal oil in a dumping cooler, but independently
from the control of the engine output.
4.4
Temperature monitoring
4.4.1
If the allowable discharge temperature is
exceeded, for oil fired heaters the heat supply must be
switched off and interlocked by a temperature limiter.
4.4.2
If the allowable discharge temperature is
exceeded for heaters heated by exhaust gas an alarm
must be tripped.
4.4.3
The discharge temperature of parallelconnected heating surfaces in the heater must be
monitored individually at the outlet of each heating
surface.
7-36
Flow monitoring
4.5.1
Precautions must be taken to ensure that the
maximum allowable film temperature of the thermal
4.6
Leakage monitoring
4.6.1
Oil fired heaters are to be equipped with a
leakage detector which, when actuated, shuts down
and interlocks the firing system. If the oil fired heater
is in "stand-by" the starting of the burner must be
blocked if the leakage detector is actuated.
4.6.2 Heaters heated by exhaust gas are to be
equipped with a leakage detector which, when
actuated, trips an alarm, and a reference shall be
provided to reduce the power of engine, which
delivers exhaust gas to the heater.
4.7
Shut-off devices
4.7.1
Both oil fired heaters and heaters heated by
exhaust gas are to be fitted with shut-off devices and,
if necessary with by-pass valves, which can also be
operated from a position outside the immediate area in
which the heater is installed.
4.7.2
It is advisable for the heater to be capable of
being drained and ventilated from the same position.
4.8
4.8.1
The temperature switch for fire detection,
required according to Section 12, C.4.3 must be
provided additionally to the temperature switch
according to 4.4.5 and shall be set to a temperature 50
to 80 C higher. If actuated alarm shall be given by
group alarm.
1.
Approved materials
Testing of materials
Design
4.8.2
Thermal oil heaters heated by exhaust gas are
to be fitted with a permanent system for extinguishing
and cooling in the event of fire, e.g. a pressure water
spraying system. For details see Section 12, Table
12.1 and paragraph L.2.2.
4.1.1
The expansion vessel must be equipped with
a liquid level gauge with a mark indicating the lowest
allowable liquid level.
C.
4.1.2
Level gauges made of glass or plastic are not
allowed.
Vessels
4.1
Level indication
4.2.1
A limit switch is to be fitted which shuts
down and interlocks the firing system and switches
off the circulating pumps if the liquid level falls below
the allowable minimum.
7-37
tank
5.1
Both tanks are to be equipped with an air
duct and a drain.
5.2
Air ducts are to be installed above the free
deck and are to be fitted with automatic air duct
closing devices, see Section 11, R.1..
4.2.2
Additionally a pre-alarm for low liquid level
is to be installed, e.g. by means of an adjustable level
switch on the liquid level gauge which gives an early
warning of a falling liquid level (e.g. in the event of a
leakage).
5.4
4.2.3
An alarm is also to be provided for the
maximum liquid level.
5.5
The storage of thermal oils is governed by
Section 10.
4.3
4.3.1
For rapid drainage in case of danger, a quick
drainage valve is to be fitted directly to the vessel with
remote control from outside the space in which the
equipment is installed.
4.3.2
Automatic means must be provided to ensure
a sufficient air supply to the expansion vessel when
the quick drainage valve is operated.
4.3.3
Where the expansion vessel is installed outside the engine room, the quick drainage valve may be
replaced by an emergency shut-off device.
4.3.4
The opening of the quick drainage valve or
the operation of the emergency shut-off device, as
applicable, must cause the automatic shutdown of the
firing system and the circulating pumps.
4.4
Connection lines
4.4.1
A safety expansion line must connect the
system to the expansion vessel. This must be installed
with a continuous positive gradient and must be dimensioned that a pressure rise of more than 10 %
above the maximum allowable working pressure in
the system is avoided.
4.4.2
The expansion vessel is to be provided with
an overflow line leading to the drainage tank.
4.4.3
The quick drainage line may be routed jointly
with the overflow line to the drainage tank.
4.4.4
All parts of the system in which thermal oil
can expand due to the absorption of heat from outside
must be safeguarded against excessive pressure. Any
thermal oil emitted is to be safely drained off.
4.5
Closed system
4.5.1
In systems operating with an inert gas
blanket, provision must be made for a constant gas
supply.
4.5.2
The pressure in the expansion vessel must be
indicated and safeguarded against overpressure.
5.
5.3
Drains must be self-closing if the vessels are
located above the double bottom.
For sounding pipes, see Section 11, R.2
D.
Equipment Items
1.
Acceptable materials
1.1
Materials for pipes, valves and pumps see
Section 11, B.
1.2
Grey cast iron is unacceptable for equipment
items in the hot thermal oil circuit and for safety
valves.
2.
Testing of materials
Equipment
3.1
Pipes, valves and pumps are governed, in
addition to the following specifications, by the
provisions of Section 11, Q.
3.2
The outlets of the circulating pumps are to be
equipped with pressure gauges.
3.3
It must be possible to shut down the
circulating pumps by an emergency switch which can
also be operated from a position outside the room in
which they are installed.
3.4
Devices for safe sampling are to be provided
at a suitable location in the thermal oil circuit.
3.5
Means of venting are to be provided at the
highest points of the isolatable section of the thermal
oil system and drains or drainage devices at the lowest
points.
Venting and drainage via open funnels are to be
avoided.
3.6
Q.1.2.
3.7
Electric equipment items are governed by the
Rules for Electrical Installations, Volume IV.
7-38
E.
Marking
1.
Heaters
2.2
For vessels with an open connection to the
atmosphere, the maximum allowable operating
pressure is to be shown on the nameplate as "0" or
"Atm.", even though a gauge pressure of 2 bar is
taken as the design basis in accordance with C.
Capacity
Serial number
Year of manufacture
F.
Liquid capacity
2.
Vessels
2.1
Vessels are to be fitted with nameplate
bearing the following information:
-
Serial number
Year of manufacture
G.
1.
Fire Precautions
Testing
Heaters