AFFICHEURS DPORTS

- REMOTE INTERFACES

ATyS D10 & D20


Notice dutilisation - Operating instructions
F

GB

SOCOMEC GROUP SWITCHING PROTECTION & UPS

MAKE YOUR BUSINESS SAFE

9/02/05

9:00

Page 2

Sommaire

F
PRSENTATION GNRALE ATyS D10 et D20 _______3
INSTALLATION ATyS D10 et D20 ___________________4
Montage _______________________________________4
Raccordements _________________________________4
Caractristiques_________________________________4
UTILISATION ATyS D10 ___________________________5
Affichage_______________________________________5
UTILISATION ATyS D20 ___________________________6
Affichage_______________________________________6
Clavier _________________________________________7
Version logiciel __________________________________7
Programmation _________________________________8
Exploitation____________________________________18
Fonctionnement________________________________20
Visualisation ___________________________________20

Summary

532_212_a

GENERAL PRESENTATION ATyS D10 & D20________23


INSTALLATION ATyS D10 & D20___________________24
Mounting _____________________________________24
Connection____________________________________24
Characteristics_________________________________24
OPERATION ATYS D10___________________________25
Display _______________________________________25
OPERATION ATyS D20 ___________________________26
Display _______________________________________26
Keypad _______________________________________27
Software version _______________________________27
Programming __________________________________28
Control and Test modes _________________________38
Operational sequences__________________________40
Visualisation ___________________________________40

GB

SOCOMEC - Rf. : 532 212 A

532_212_a

9/02/05

9:00

Page 23

Remote interfaces ATyS

GENERAL PRESENTATION
ATyS D10 & D20

ATyS D10 and D20 models are remote interfaces


designed for easy integration on front panels. They can
be connected to ATyS 6e, 6m and C30 products to allow
remote access to display or control features.

SOCOMEC - Rf.: 532 212 A

23

9/02/05

9:00

Page 24

Remote interfaces ATyS

INSTALLATION
ATyS D10 & D20

Mounting
Door fixing: 2 holes, diameter 22.5 mm
Maximum thickness of the door: 20 mm
22.5

Door drilling

ATYS 147 A

20

40

36

96 x 96

ATYS 161 A

(1) RJ45 plug for ATyS connection

Connection
Connection only on AtyS 6e, 6m or C30 products.

ATyS C30

> Cable

Type RJ45

RJ45 type 8 / 8 not isolated

> Maximum cable length


3m
4

> Tightning torque

3
2
1

4 N.m

ATYS 313 A GB

532_212_a

ATyS D10/D20

Characteristics
> IP
IP21 standard
IP54 using gasket

> Operation
Temperature: -10 to + 55 C
hygrometry: 80 % humidity at 55 C
95 % humidity at 40 C

24

SOCOMEC - Rf.: 532 212 A

532_212_a

9/02/05

9:00

Page 25

Remote interfaces ATyS

OPERATION
ATyS D10

Display
ATyS D10 allows remote display of transfer system
positions, sources availability and operational mode.
Programming and operations remain available directly on
master product (ATyS 6e, 6m or C30).

Source 1 available

ATyS Product faulty, transfer error


Possible to reset after error
disappearance the power supplies
of the master product (ATyS 6e,
6m, C30) for 3 minutes

Power On

Source 2 available

ATYS 145 B

Transfer system in
position 1

Transfer system in
Automatic mode

SOCOMEC - Rf.: 532 212 A

Transfer system in
position 0

Transfer system in
position 2

25

9/02/05

9:00

Page 26

Remote interfaces ATyS

Display
Keypad
Software version
Programming
Control and Test modes
Operational sequences
Visualisation

OPERATION
ATyS D20

Display
ATyS D20 allows remote display of transfer system
positions, sources availability, operational mode and
metering. Programming and operations (Test and
Control) are also available. Master product (ATyS 6e, 6m
or C30) display is deactivated as soon as the remote
interface is connected.

Manual
mode
active

Power On

Padlock*

Product faulty, transfer error


Possible to reset after error
disappearance: switch off the
power supplies of the master
product (ATyS 6e, 6m, C30)
for 3 minutes

Source 1 available

Source 2 available

Transfer system in
position 1

Transfer system
in position 2
Transfer system
in position 0

Transfer system in
automatic mode

ATYS 146 B

532_212_a

Control mode active

Test mode active

Programming mode active

* only on ATyS 6e and 6m

26

SOCOMEC - Rf.: 532 212 A

532_212_a

9/02/05

9:00

Page 27

Remote interfaces ATyS

OPERATION

Display
Priority source

Phases (wires) displayed

Units

ATYS 318 A

Informations
source 1
source 2
sources 1 & 2
(split screen)

Power factor
Capacitive or inductive

Signed
values
(power)

Values

ATYS 146 C

Keypad

Access to AUT, Test,


Control and Prog modes

Direct Access to Test and Control


functionalities or navigation

Allows main menu access


in visualisation mode or
validation

Software version

ATYS 319 A

Software version of the master product is displayed


immediately after ATyS 6e, 6m or C30 power on.

SOCOMEC - Rf.: 532 212 A

27

532_212_a

9/02/05

9:00

Page 28

Remote interfaces ATyS

Display
Keypad
Software version
Programming
Control and Test modes
Operational sequences
Visualisation

OPERATION
ATyS D20

Programming
> Enter into programming mode
Step 1: Press the mode push button until Prog led is blinking

Step 2: Press validation push button. PROG led becomes fixed and access code is displayed

Step 3: Enter access code (1000 factory default) using keypad left,
right, top and bottom

Step 4: Press validation push button to enter programming mode

> Programming mode exit


Step 1: Press the ESC push button when not entering any value, to come back to main
programming menu

Step 2: Press again on ESC push button to exit programming

New Active mode (Automatic or Manual) depends on information from the master device (ATyS 6e, 6m ou C30)

28

SOCOMEC - Rf.: 532 212 A

532_212_a

9/02/05

9:00

Page 29

Remote interfaces ATyS

OPERATION

Programming
> Navigation in programming mode
Step 1: To access required menu, press navigation push buttons
left and right

Step 2: To access parameter to modify


press navigation push buttons top and bottom

Step 3: To modify the parameter, press push button right


to make the required parameter blinking

Step 4: Press push buttons top and bottom to increment or


decrement the value of the parameter

Step 5: Press validation push button to validate

In case of parameter displayed on 2 lines, press validation push button after first line modification
to access next one

ESC push button allows to come back to main menu or to cancel the modification

SOCOMEC - Rf.: 532 212 A

29

9/02/05

9:00

Page 30

Remote interfaces ATyS

Display
Keypad
Software version
Programming
Control and Test modes
Operational sequences
Visualisation

OPERATION
ATyS D20

Programming

**

**

**
**

**
*

**

**
**

**

**
**

**

**
**

ARCHITECTURE OF THE PROGRAMMING MENU

ATYS 327 A

532_212_a

30

SOCOMEC - Rf.: 532 212 A

SOCOMEC - Rf.: 532 212 A

*
**
***
****

only on Atys 6m
option on ATyS 6e & 6m
only on ATyS C30
visible if option LS selected and active

**

***

****

**

***

9:00

**

9/02/05

***

**

**

532_212_a
Page 31

Remote interfaces ATyS

OPERATION

31

532_212_a

9/02/05

9:00

Page 32

Remote interfaces ATyS

OPERATION
ATyS D20

Display
Keypad
Software version
Programming
Control and Test modes
Operational sequences
Visualisation

Programming
VARIABLES CHARACTERISTICS
> Setup
LCD

Denomination

Setting range

Default values

nt

Type of network
(cf. ATyS 6 or C30 instruction manual)

1BL, 2BL, 2NBL 4NBL


3NBL, 4NBL,
41NBL, 42NBL

Un

Network Nominal voltage


Phase-Neutral voltage for 1BL & 41NBL
Phase-Phase voltage for others

100 to 480 V

ScE**

Source 1 - Switch I or II configuration


I, II
Source 1 (controlled and displayed) linked to switch I or II (depending on cabling)

Fn

Network nominal Frequency

50 or 60 Hz

50 Hz

Ct*

CTs primary current


(5 A secondary CT)

50 to 5000 / 5 A

500 / 5 A

Gen

Genset start signal state


Normally opened or closed

NO, NC

NO

Pri

Network priority selection


Keypad selection (1 or 2)
Also possible via external contact
Using option

1, 2

Mtf

Manual Retransfer
Activation of the feature

Yes, No

No

LoG

Type of control logic selection


Impulse, contactor or breaker***

IMP, CON, brE*** IMP

AC***

Number of position auxiliary contacts used, depending on transfer


device type (switch, contactor, breaker)

0, 2, 3

rn1

Allows 0 position command after loss of main source (source 1)

Yes, No

No

rn2

Allows 0 position command after loss of emergency source (source 2)

Yes, No

No

CrS

Number of permutation counter Reset

Yes, No

No

CP

Programming code modification


Possible to change the code

0001 to 9999

1000

400 V

* only on AtyS 6m
** only on ATyS 6e & 6m
*** only on ATyS C30.

32

SOCOMEC - Rf.: 532 212 A

532_212_a

9/02/05

9:00

Page 33

Remote interfaces ATyS

OPERATION

Programming
> Voltage thresholds
LCD

Denomination

Setting range

Default values

oU

Network 1 over voltage threshold

102 - 120 %

115 %

oUh

Network 1 over voltage threshold hysteresis

101 - 119 %
(< oU)

110 %

uU

Network 1 under voltage threshold

80 - 98 %

85 %

uUh

Network 1 under voltage threshold hysteresis

81 - 99 %
(> uU)

95 %

oU

Network 2 over voltage threshold

102 - 120 %

115 %

oUh

Network 2 over voltage threshold hysteresis

101 - 119 %
(< oU)

110 %

uU

Network 2 under voltage threshold

80 - 98 %

85 %

uUh

Network 2 under voltage threshold hysteresis

81 - 99 %
(> uO)

95 %

Values defined are % of nominal values.


Hysteresis thresholds must be programmed according to over and under voltage thresholds (respectively under & above).

> Frequency thresholds


LCD

Denomination

Setting range

Default values

oF

Network 1 over frequency threshold

101 to 120 %

105 %

oFh

Network 1 over frequency threshold hysteresis

100.5 - 119.5 % 103 %


(< oF)

uF

Network 1 under frequency threshold

80 - 99 %

95 %

uFh

Network 1 under frequency threshold hysteresis

80.5 - 99.5 %
(> uF)

97 %

oF

Network 2 over frequency threshold

101 - 120 %

105 %

oFh

Network 2 over frequency threshold hysteresis

100.5 - 119.5 % 103 %


(< oF)

uF

Network 2 under frequency threshold

80 - 99 %

95 %

uFh

Network 2 under frequency threshold hysteresis

80.5 - 99.5 %
(> uF)

97 %

Values defined are % of nominal values.


Hysteresis thresholds must be programmed according to over and under frequency thresholds (respectively under & above).

SOCOMEC - Rf.: 532 212 A

33

532_212_a

9/02/05

9:00

Page 34

Remote interfaces ATyS

OPERATION
ATyS D20

Display
Keypad
Software version
Programming
Control and Test modes
Operational sequences
Visualisation

Programming
> Timers
LCD

Denomination

Setting range

Default values

Mft

Main Failure Timer


Delays priority network failure detection

From 0 to 60 s

5s

dtt

Delay on transfer timer


Emergency network stability validation before transfer

From 0 to 60 s

5s

OMf

O Main Failure Timer


Rest in O position when transferring
from main network to emergency network

From 0 to 20 s

0s

Mrt

Main Return Timer


Main network stability validation before re-transfer

From 0 to 30 min 1 min

OMr

O Main Return Timer


From 0 to 20 s
Rest in O position when re-transferring from emergency network to main network

Cdt

Cool Down Timer


Allows generator cooling down period after loads
retransfer from emergency source (generator) to Main source

5s

From 0 to 10 min 4 min

> Communication
Only on ATyS 6e or 6m in case of optional communication module.
LCD

Denomination

Setting range

Default values

Add

Device address

1 to 247

bd

Communication speed

2400, 4800, 9600, 9600


19200, 38400

StoP

Stop bit

1, 2

PAr

Parity bit

No, Odd, Even

No

34

SOCOMEC - Rf.: 532 212 A

532_212_a

9/02/05

9:00

Page 35

Remote interfaces ATyS

OPERATION

Programming
> Inputs/Outputs
2 inputs (In1, In2) and 2 outputs (Ou1, Ou2) as standard
on ATyS C30.

Refer to ATyS C30, 6e or 6m instruction manual


for terminals identification.

Possibility to connect 2 modules 2 Inputs / 2 Outputs


on ATyS 6e & 6m.
- First module: In1, In2, Ou1, Ou2
- Second module In3, In4, Ou3, Ou4.
Input / Output

Function

Relay State

I1 to I4

Ft1, Ft2, Ft3, Ft4, Pri,


Mtf, S2A, Man, TOL, TFL, EJP, CTS

NO or NC

O1 to O4

S1A, S2A, LS, /

NO

Input (In2, Ft2) and output (Ou1, S1A) programming example:

Step 1: Press right push button to make


first variable blinking (Ft2 ou S1A)
Step 2: press top and bottom
push buttons to modify the variable
Step 3: press validation

ATYS 328 A

Step 4: press bottom push button to


acces nO variable selection

SOCOMEC - Rf.: 532 212 A

35

532_212_a

9/02/05

9:00

Page 36

Remote interfaces ATyS

OPERATION
ATyS D20

Display
Keypad
Software version
Programming
Control and Test modes
Operational sequences
Visualisation

Programming
Variables description
Inputs
Variable

Description

Ft1

Fault input 1. The fault led is blinking as soon as the input is active and
Ft1 is displayed on LCD. Reset when the input is de-activated

Ft2

Fault input 2. The fault led is blinking as soon as the input is active and Ft2 is displayed on LCD.
Reset when the input is de-activated

Ft3*

Fault input 3. The fault led is blinking as soon as the input is active and Ft3 is displayed on LCD.
The transfer switch is immediately driven in 0 position.
Keypad action (Esc) necessary to Reset the fault

Ft4*

Fault input 4. The fault led is blinking as soon as the input is active and Ft4 is displayed on LCD.
The transfer switch is immediately driven in 0 position.
Keypad action (Esc) necessary to Reset the fault

Pri

Priority network selection.


Network 1 has priority when input is not activated. Network 2 has priority if input is active

Mtf

Remote manuel re-transfer. Feature identical to manual re transfert on keypad.


Re-transfer from priority network to backup network is allowed from input activation (1 s front).
The Mtf variable in the setup menu must be selected (Yes) to allow input recognition

S2A

Information source 2 available (Genset) used instead of voltage / frequency measurement


from ATyS (inhibited when S2A is selected)

Man**

Information transfer system in manual mode.


All automatic commands (+ test on load and control commands) are inhibited as soon as the input is activated

CTS**

Remote transfer control. Possible to initiate transfer from priority source to backup source
before DTT ends. If DTT is set to its maximum value (60s), the transfer is initiated as soon as
the input is activated (1 s front)

TOL**

Remote test on load. Started from input activation.


Re-transfer is blocked until input de-activation

TFL

Remote test off load.


Started from input activation (remote genset start / stop)

EJP

2 inputs one automatically affected to EJP


input 1 for EJP advice, to start generator
input 2 to transfer on emergency source
Retransfer is activated when input 2 disapears

* only on ATyS C30, specific fault operation (Ft2 and Ft3)


** only as option on ATyS C30, standard features on ATyS 6e et 6m.

Outputs
Variable

Description

S1A

Source 1 available.
Output activated as soon as source 1 is considered available (similar to front led source 1)

S2A

Source 2 available.
Output activated as soon as source 2 is considered available (similar to front led source 2)

LS

Load shedding relay. LS timer corresponds to time available to disconnect the shed loads.
The relay is activated before permutation on standby network according to LS timer.
The relay is de-activated after retransfer on mains network and LS timer countdown

36

SOCOMEC - Rf.: 532 212 A

532_212_a

9/02/05

9:00

Page 37

Remote interfaces ATyS

OPERATION

Programming
LOAD SHEDDING CONFIGURATION
LS variable allows associated LS timer configuration.
Output

Associated funciton

Setting range

Default value

O1 to O4

LS

0 to 60 s ( DTT)*

* In case of DTT variable configuration below LS, LS will be automatically set to to DTT value.

> Example: load shedding configuration


Step 1: Press right push button to make
first variable blinking (LS)

function

Step 2: press push buttons top and


bottom to modify the variable
Step 3: Press validation

ATYS 329 A GB

Step 4: Press bottom push button


to access timer value configuration

timer

SOCOMEC - Rf.: 532 212 A

37

532_212_a

9/02/05

9:00

Page 38

Remote interfaces ATyS

Display
Keypad
Software version
Programming
Control and Test modes
Operational sequences
Visualisation

OPERATION
ATyS D20

Control and Test modes


It is possible to start test sequences or to control
electrically the changeover system from keypad.

NAVIGATION
> Enter Control or Test modes
Step 1: Press mode push button to make test or control led blinking
Step 2: Press validation push button to make control or test led become fixed

CONTROL MODE
Access code is displayed directly

TEST MODE
It is possible to test leds and LCD without entering any code by pressing directly
Test on load or test off load access codes are displayed after pressing

or

Enter the code 4000 using left, right, top


and bottom push buttons

Press validation push button to enter

38

SOCOMEC - Rf.: 532 212 A

532_212_a

9/02/05

9:00

Page 39

Remote interfaces ATyS

OPERATION

Control and Test modes


> Exit control or test modes
Press ESC push button
The new operational mode (automatic or manual) depends on information from master
ATyS (6e, 6m ou C30)

> Control or Test modes use


Direct access by pressing

and

To start a test (off load or on load) or to control the changeover switch electrically,

press

SOCOMEC - Rf.: 532 212 A

and

push buttons

39

9/02/05

9:00

Page 40

Remote interfaces ATyS

Display
Keypad
Software version
Programming
Control and Test modes
Operational sequences
Visualisation

OPERATION
ATyS D20

Operational sequences
Refer to ATyS 6e, 6m or C30 manuals for more
information on operational sequences and controls:
sources control,
tests cycles,
loss of priority source sequence,
priority source return sequence.

Visualisation
Without keypad activation or any operational sequence
during 5 minutes, the LCD comes back to default display
mode and stops the backlight.

> If both sources are available:

> If only one source is present:

One visualisation screen is split into 2 parts and


displays simultaneously voltage and frequency values
on both networks.
If a timer is active, on one of the source, its countdown is displayed instead of voltage and frequency
values.

During permutation cycle, voltage and frequency


values of the available source (active) are displayed
on 2 lines. The name of the active timer and its countdown are displayed on remaining 2 lines.
Out of a permutation cycle, phase to phase voltages
and frequency are displayed.

Examples:

Examples:

ATYS 332 A

It is possible to display controlled parameters in both


automatic and manual modes (but not during programming).
No code is required to perform visualisation.
Permutation cycles have priority over visualisation and
display timer countdown during cycle operation.

ATYS 331 A

532_212_a

Press left, right, top & bottom push buttons


to access available screens

Press navigation push button to navigate in visualisation, displaying all available screens

40

SOCOMEC - Rf.: 532 212 A

532_212_a

9/02/05

9:00

Page 41

Remote interfaces ATyS

OPERATION

Visualisation
ARCHITECTURE OF VISUALISATION MENU
***

***

***

***

**

ATYS 333 A

***

****
*
**
***
****

SOCOMEC - Rf.: 532 212 A

only on AtyS 6e & 6m


only U3-1 on AtyS C30
only on ATyS 6m
visible if option LS selected and active

41

532_212_a

9/02/05

9:00

Page 42

532_212_a

9/02/05

9:00

Page 43

532_212_a

9/02/05

9:00

Page 44

SOCOMEC - Ref.: 532 212 A - 02 / 05

HEAD OFFICE

SALES MANAGEMENT DIVISION

SOCOMEC GROUP SWITCHGEAR AND UPS


S.A. capital 10 923 800 - R.C. Strasbourg 548500 149 B
1, rue de Westhouse - B.P. 10 - 67235 Benfeld Cedex
Tl. + 33 03 88 57 41 41
Fax + 33 03 88 57 78 78

SOCOMEC
95, rue Pierre Grange
94132 Fontenay-sous-Bois Cedex
Tl. + 33 01 45 14 63 90
Fax + 33 01 45 14 63 38

www.socomec.com

This document is not contractual. SOCOMEC reserves


the right to modify features without prior notice in view of
continued improvements.