Bulkhead Cap

SHEET PILE DESIGN CRITERIA AND NOTES

(See Bulkhead Plans


for actual Cap outline)
DESCRIPTION:
This Design Standard includes details for five types of piles with two thicknesses.
Types "B1", "B2", "C1" and "C2" piles (corner piles) are of reinforced concrete construction, and Type "A" is of

Compacted Fill

the requirements of the contract documents.

(
M in.
)

1
-0"

prestressed concrete construction. The piles shall be manufactured, cured and installed in accordance with

MATERIALS: (for materials not listed refer to the Specifications)


CONCRETE
Class:

V (Special) for slightly and moderately aggressive environments


V (Special w/ Silica Fume) for extremely aggressive environment

Plastic Filter Fabric


(Continuous)

Sheet pile

Unit weight:

150 pcf

Modulus of Elasticity:

Based on the use of Florida limerock concrete

REINFORCING STEEL
ASTM A615 Grade 60

PRESTRESSING STEEL
ASTM A416 Grade 270 (Low-Relaxation Strand)

Existing Ground
(Mud Line)
CROSS REFERENCES:

DESIGN PARAMETERS:

For Dimensions L and X see Sheet

Type "A"
1
-8"

Pile Wall Data Table in Structures Plans.

Concrete Compressive Strength at release of prestressing:

4000 psi minimum

Uniform compression after prestressing losses:

1000 psi minimum

Pick-up, Storage and Transportation:

0.0 psi tension with 1.5 times pile self weight

Types "B1", "B2", "C1" & "C2"


Bottom of Dim. X

Pick-up, Storage and Transportation:

Minimum compressive strength fci = 4000 psi required.

and Filter Fabric


ENVIRONMENT:
The pile designs are applicable to all Environments.

SECTION THRU BULKHEAD


PLASTIC FILTER FABRIC:
(Showing Plastic Filter Fabric)

The plastic filter fabric shall extend to the bottom of the "X" dimension.

PILE PICK-UP AND HANDLING:


Type "A"

Grout (Typ.) (See Specifications)

Pick-up of pile may be either a single point pick-up or a two point pick-up as shown below.
Types "B1", "B2", "C1" & "C2"

C:
\d\projects\standards\structures\2013book\06040-1of4.
dgn

2-6"

Two point pick-up for lifting out of forms & two point support for storage & transportation.
Type "A" (Typ.)

Single point pick-up for installation only.

PILE FIT-UP:

90

The 2-6" Sheet Pile dimension is nominal. This dimension may be shortened by the Manufacturer up to b" to
allow for Sheet Pile fit-up in its final position. Minimum Sheet Pile width is 2-5b". No changes shall be made
to the tongues or grooves.
Type "A"

Type "A"
Type "C1"

Type "A"

Starter Pile

Type "B1" or "B2"

Plastic Filter Fabric

or "C2"

DETAIL "A"
(Cap and Anchoring System Not Shown)
(Section Taken Above Dimension X)
NOTE: Detail "A" shows a Part-Plan View of an assumed bulkhead.
See Bulkhead plans for actual Plan View.
1-3"
Pile and
Starter Pile
Single Point

rd960rh

2 Point Pick-up, Tie Down and Support Points

Pick-up

1-3"

T
1
y
C
o pi -3
r
"
n ca
e
l
r
f
o
P
il r
e
s

11:
48:
40 AM

0.21 L

DETAIL "A"

0.21 L

PILE STORAGE AND TRANSPORTATION SUPPORT DETAILS

(Section Taken Below Dimension X)


6/28/2012

0.58 L

Type "C2" Shown,

Type "B2" Shown,

Type "C1" Opposite Hand

Type "B1" Opposite Hand

REVISION

07/01/12

REVISIO N

NOTES AND DETAILS


LAST

DESCRIPTION:

INDEX

FDOT DESIGN STANDARDS


2013

PRECAST CONCRETE SHEET PILE WALL

NO.

6040

SHEET
NO.

BAR BENDING DIAGRAMS

4" (Typ.)
11"

(Typ.)
Slope only on the tongue side
10"

S2

Bar S5
Bar S4

45

S1

"

Bars

"
0
1

Bars

BAR A

4b "

2-PIECE
Spaced at 1-0" Maximum

1-6

S5

1-10

"
"

S6

11"

S7

1-7 "

T=10 in.

4"

T=12 in.

6"

7"

6 sp. @ 4"

2-2"

S4

DIMENSION B
B

"

1-9b "

S3
A

Varies

1-11

S2

Pick-up Strand(S)

1
-0

11"

(
Typ.
)

S1

Strands

1
-3"

2 ~ Bars A

DIMENSION A

(Typ.)

Prestressed

(
M in. Lap)

3 "

6 sp. @ 4"

1-PIECE

BAR S

Spacing for
Bars S
NOTES:

TYPICAL PILE

1. Intermediate Prestress Strands not shown in Elevations and Sections.


2. All bar dimensions are out-to-out.

SHEET PILE DIMENSIONS

T(in.)
Y(in.)
11"

10

Z(in.)

3.

12

Bars A are #5 and Bars S are #4.

4. At the Contractors option Bars S may be fabricated as a two piece bar


as shown in the Bar Bending Diagram.
5. The Contractor may use Deformed Welded Wire Reinforcement conforming to

(Typ.)

specification ASTM A497 in lieu of Bars A and Bars S if the wire size and
spacing provide the same area of reinforcing steel per foot as the Bars shown.
10"

2 "
D

(Typ.)

Bars A

(
Strands)

(Typ.)

Bars S2
3" Cover

n sp. @

D
Bars S1
3" Cover

T
See Detail "D"

2
-6"

2 "
n sp. @

"
1
-0

2
-6"

Bar S7
Bar S6

Bars A
n sp. @

S2

See Detail "E"

2
-6"

Bars

S3

(
Strands)

Strand(S)
Bars

11"

(
Typ.
)

Bars S3
3" Cover
(Typ.)

6 sp. @ 4"

Spaced at 1-0" Maximum

6 sp. @ 4"

3 "

SECTION A-A
Y

STARTER PILE

b" 2
Thickness

(in.)

T=10 in.

0.5

28-0"

0.6

27-0"

0.5

31-0"

0.6

30-0"

T=12 in.

D
(in.)
3
5
2
4

TOTAL # OF
STRANDS

SECTION
MODULUS (in.)

"

b"

b"

4"

3"

2"

2 "

SECTION C-C

b"

* STRESS
(psi)

14

500

1150

10

500

1160

16

720

1100

12

720

1160

2 "

MAXIMUM

"

SECTION B-B

2"

rd960rh
11:
48:
42 AM

STRAND DIA.

2"

Spacing for
Bars S

Wall

Cover

4b "

7"

Cover

2 ~ Bars A

Cover

Bars A

2"

C:
\d\projects\standards\structures\2013book\06040-2of4.
dgn

Pick-up

2" Cover

T
See Detail "D"

(
Strands)

Strands

2" Cover

(Typ.)

Prestressed

2 ~ Bars A

2" Cover

6. For Dimensions L and X see Sheet Pile Data Table in Structures Plans.

6/28/2012

* Unit Prestress after losses.

DETAIL "D"

DETAIL "E"

(Typical Tongue)

(Typical Groove)

LAST
REVISION

01/01/11

REVISIO N

TYPE "A" STANDARD SECTION


DESCRIPTION:

INDEX

FDOT DESIGN STANDARDS


2013

PRECAST CONCRETE SHEET PILE WALL

NO.

6040

SHEET
NO.

See Detail "D"


L
Bars A1
11" Slope is to
11"

this point

Bars A3

2-2"

Bars A2

Bars A3
Bars A3

Bars A1

Bars A2

Bars A2

Bars A1

7"

Bars A3

Bars A4

Bars A3

Bars A4
Bars A4

Bars S1

"
-3
1

Slope only on

Bars A4

Bars A4

tongue side

Bars S2

Bars A4
S2

Bars A4

Bars A4

S1

Bars A4

4"

Bars A4

Bars A4

Pick-up Strand(s)

Bars A4
3" Cover

Bars S3

(Typ.)

See Detail "D"

3" Cover

1
-3
"

(Typ.)
Bars S4

SECTION A-A

SECTION B-B
T

bT

Bars A4

10"

bT

b"

VIEW C-C
6 sp. @ 4"

Spaced @ 1-0" Maximum

6 sp. @ 4"

3 "

2"

4 "

Spacing for

Y
"
b"

Bars S

T (in.)

2"
Co
ve
r

ELEVATION

SHEET PILE DIMENSIONS

(TYPE "B1" PILE SHOWN, TYPE "B2" PILE OPPOSITE HAND)

Y (in.)
Z (in.)

BAR BENDING DIAGRAMS

STIRRUP DIMENSIONS (T = 10")

10

12

Bars S

Bars A2

STIRRUP DIMENSIONS (T = 12")


Bars A1 or A4

R3

R4

R5

R6

11 "

"

1-6b "

2b "

5"

S2

1-1b "

"

1-8

2b "

4b "

"

R8

5b "

4 "

5b "

4 "
5"

S3

11b "

"

"

BAR MARK

R1

S1

11b "

S2

30

1-1

"

R2

R3

R4

R5

R6

10"

1-6"

3b "

7"

10"

1-8 "

3b "

6b "

2"

R7

R8

"

"

6"

5 "

"

6"

30
S3

11 "

8"

S4

11 "

4 "

S1

11b "

8"

S2

1-1

"

8"

1-6"
1-1

"

1 "

5"

4b "

4b "

7"

"

4b "

7 "

5"

2b "

6 "

S4

11b "

4"

1-1 "

2 "

7"

"

2b "

8 "

S1

1-0"

8b "

1-3 "

5 "

7b "

6 "

8b "

5 "

b"

S2

1-2 "

8b "

1-5b "

5 "

6b "

7 "

8b "

5 "

5b "

S3

1-0"

7"

1-4"

3"

7b "

7"

7 "

3b "

7"

S4

1-0"

3b "

11

"

3b "

9"

7 "

10 "

3"

S1

1-0b "

6 "

11

"

7"

10b "

3"

S2

1-2

6 "

1-2"

7"

1-4"
1-5

"

S1

R7

"

"

"

4"

5b "

6b "

8"

4"

4"

4b "

7b "

8"

4"

45

1-5

"

b"
3"

S3

11b "

"

1-4"

2 "

5b "

S4

11b "

3b "

1-0"

3"

5b "

S1

1-0"

6"

1-0

"

5 "

S2

1-2"

6"

1-2

"

5 "

"

"

"

Z
4"

45

bT
bT
T

6"
4

"

5"

"

"

"

7b "
8"
6

"

5"
6

"

8"

10

"

4"

10

"

4"

60

60
S3

1-0"

S4

1-0"

2b "

"

1-1b "

3 "

6"

10"

4b "

6"

8"
5

"

4"

"

5 "

S3

1-0b "

5"

1-1b "

4"

8"

8"

9"

7"

7b "

S4

1-0b "

2b "

9b "

5b "

8"

5b "

4 "

9 "

DETAIL "D"
(TYPE "B1" PILE SHOWN, TYPE "B2" PILE OPPOSITE HAND)

NOTES:

R6

4"

R5

R6

(
Typ.
)

4"

(
Typ.
)

1. This drawing includes details for precast concrete corner piles for 10"
R5

R5

and 12" thick sheet pile systems. The details apply equally to both thicknesses.

R6

2. The bar configurations shown in Sections A-A and B-B shall be used for
angles between 15 and 75. For angles not shown, the reinforcing bar

3. All bar dimensions are out-to-out.


Varies

R3

R1

R3

R1

R3

R1

dimensions may be interpolated or extrapolated from the stirrup dimensions shown.

4.

Bars A are #8 and Bars S are #4.

5. Values for Stirrup Dimensions are shown for equal to 30, 45 & 60 only.

R2

R2

6. At the Contractors option Bars S may be fabricated as a 2 piece bar with

R7

R8

45

R7

R8

R4

R4

R4

R2

rd960rh

R2

"
0
1

11:
48:
45 AM

R1

2"
r
ve
Co

C:
\d\projects\standards\structures\2013book\06040-3of4.
dgn

BAR MARK

R7

BAR A2

R8

a minimum lap length of 1-6", as shown in Bar Bending Diagrams.


7. If Type "B1" or "B2" pile is used as a Starter Pile show tongue on both sides of pile
from Dim. X down. Show dimensions for Bars S2, S3 & S4 in shop drawings.
8. If tongue must be on the opposite side from that shown all dimensions and Bars A,
S2, S3 and S4 will be the same but opposite hand.

6/28/2012

9. For Dimensions L, X and Angle , see Sheet Pile Data Table in Structures Plans.

1 - PIECE

2 - PIECE

BARS S3 & S4
TYPE "B1" AND "B2" - VARIABLE ANGLE CORNER PILE

LAST
REVISION

07/01/12

REVISIO N

BARS S1 & S2
DESCRIPTION:

INDEX

FDOT DESIGN STANDARDS


2013

PRECAST CONCRETE SHEET PILE WALL

NO.

6040

SHEET
NO.

here if T=12"

Bars A1

2 ~ Bars A2

10"

Bar A4

(Typ.)

Bars S3

See
Section C-C

* Bar A4

* Bar A4

Bar A6

Bar A6

Pick-up

Bars A2

** Bar A4

** Bar A4

Bar A5
1
-9"

1
-8"

1
-9"

1
-8"

Bars S1
Bar A5

Bars S4

S2
3" Cover

Bars A1

Bars S5

2"

2-2"

(
Typ.
)

"

This A4 bar ends


T

For 12" Pile

10

1-4"

For 10" Pile

Strand(s)

For 12" Pile

For 10" Pile

Bars A5

3"

1-8"

(Typ.)

1-9"

Bars A3

Bars S2

Bars A3

Bars A3

7"

2" (Typ.)

3" Cover

See Section C-C

Bars S1

END VIEW
4"

Spaced @ 1-0" Maximum

6 sp. @ 4"

3 "

6 sp. @ 4"

Spacing for

SECTION A-A

1-8"

For 10" Pile

1-9"

For 12" Pile

SECTION B-B

Bars S

ELEVATION
(TYPE "C1" PILE SHOWN, TYPE "C2" PILE OPPOSITE HAND)

* This Bar A4 shall be 1-2" shorter than other A4 bars for T = 12".

Bars A2

** This Bar A4 (not shown in elevation) is included only if T = 12".

T
Bar A4
3

"

BAR BENDING DIAGRAMS

Bar S2

Y
Bar S3
Bar A5

"

R2

STIRRUP DIMENSIONS

R3

b"
T (in.)

Bar S4

BAR MARK

R1

S1

7"

R2

R2

b"

R3

10

Bar A6

"

"

S4

5b "

6b "

"

S5

"

"

"

"

12

Bars S2

S1

9"

S2

9"

7"

"

S3

8 "

6 "

"

S4

7b "

5b "

"

S5

"

9"

6"

6"

5"
5"

1-3"

For 10" Pile

1-3"

For 12" Pile

For 12" Pile

3"
b"

For 10" Pile

45
-

(Bars A2 only)

BARS A

Bar S2
Bar S3

Bar A5

Note: All Bar dimensions are out-to-out.

SHEET PILE DIMENSIONS


Bar S4
Bar A4

T (in.)

10

12

Y (in.)
Z (in.)

SECTION C-C (T=10" or 12")

Bar A6

NOTES:
1. All bar dimensions are out-to-out.

Bar S5

Bars

A3
rd960rh

"

"
0

2 "

Bul

"

Varies

1-2"

4"

Bars A2
Bar A6

STIRRUPS S
0" A5

Bars A3

Bar A4

4"

8"
7 "

90

SECTION D-D (T=10")


b"

7"
6 "

3b "A3

** Bar A4

S2
S3

2b " A4

1
-3"

Bars A2

7"

4"

1
-3"

Bar A5

"

4b "A2 & A6

2"

A3

R1

Bar S5

*Bar A4

C:
\d\projects\standards\structures\2013book\06040-4of4.
dgn

2"

Bars

2.

Bars A are #8 and Bars S are #4.

3. This drawing includes information for precast Corner Piles for 10" and 12"
thick Sheet Pile systems. The details apply to both thicknesses but the bar
configurations change slightly according to the thickness values used.
4. If Type "C1" or "C2" pile is used as a Starter Pile show tongue on both sides of

11:
48:
47 AM

pile from Dim. X down. Show dimensions for Bars S2, S3, S4 & S5 in
shop drawings.
5. If tongue must be on opposite side (Groove Side) from that shown,
all dimensions and reinforcement shall follow the corresponding Tongue
or Groove side.

6/28/2012

SECTION D-D (T=12")

6. For Dimensions L and X see Sheet Pile Data Table in Structures Plans.

LAST
REVISION

07/01/12

REVISIO N

TYPE "C1" AND "C2" - RIGHT ANGLE CORNER PILE


DESCRIPTION:

INDEX

FDOT DESIGN STANDARDS


2013

PRECAST CONCRETE SHEET PILE WALL

NO.

6040

SHEET