Test Object - Device Settings
.
.
.
Substation address:
Bay address:
112
bay address
Manufacturer:
Device address:
ABB
0
Number of phases:
V primary:
I primary:
3
132.0 kV
800.0 A
IN / I nom:
1.000
I max:
50.00 A
Deglitch time:
0.000 s
Substation/Bay:
Substation:
Bay:
New Karak
bay
.
Device:
Name/description:
Device type:
Serial/model number:
Additional info 1:
Additional info 2:
REL650-A01
Line Protection
1VHR91010439
protected object name
information
.
Nominal Values:
f nom:
V nom (secondary):
I nom (secondary):
50.00 Hz
110.0 V
1.000 A
.
Residual Voltage/Current Factors:
VLN / VN:
1.732
.
Limits:
V max:
240.0 V
.
Debounce/Deglitch Filters:
Debounce time:
3.000 ms
.
Overload Detection:
Suppression time:
50.00 ms
Name
NAMECH1
InputType1
CTStarPoint1
CTsec1
CTprim1
NAMECH2
InputType2
CTStarPoint2
CTsec2
CTprim2
NAMECH3
InputType3
CTStarPoint3
CTsec3
CTprim3
NAMECH4
InputType4
CTStarPoint4
CTsec4
CTprim4
NAMECH5
InputType5
Value
LINE_CT_L1
Current
ToObject
1.0 A
800 A
LINE_CT_L2
Current
ToObject
1.0 A
800 A
LINE_CT_L3
Current
ToObject
1.0 A
800 A
CT_IN
Current
ToObject
1.0 A
800 A
CT_IN
CurrentSensitive
CTStarPoint5
CTsec5
CTprim5
NAMECH6
InputType6
VTsec6
VTprim6
NAMECH7
InputType7
VTsec7
VTprim7
NAMECH8
InputType8
VTsec8
VTprim8
NAMECH9
InputType9
VTsec9
VTprim9
NAMECH10
InputType10
VTsec10
VTprim10
ToObject
1.0 A
800 A
BUS_VT_L1
Voltage
110.000 V
132.000 kV
BUS_VT_L2
Voltage
110.000 V
132.000 kV
BUS_VT_L3
Voltage
110.000 V
132.000 kV
BUS1_VT_SYNC_
Voltage
63.500 V
76.210 kV
LINE VT RPH
Voltage
63.500 V
76.210 kV
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HW Configuration \ BIO_3
Description
Station battery voltage
User define string for binary input 1
Threshold in percentage of station battery voltage for input 1
Debounce time for input 1
Oscillation count for input 1
Oscillation time for input 1
User define string for binary input 2
Threshold in percentage of station battery voltage for input 2
Debounce time for input 2
Oscillation count for input 2
Oscillation time for input 2
User define string for binary input 3
Threshold in percentage of station battery voltage for input 3
Debounce time for input 3
Oscillation count for input 3
Oscillation time for input 3
User define string for binary input 4
Threshold in percentage of station battery voltage for input 4
Debounce time for input 4
Oscillation count for input 4
Oscillation time for input 4
User define string for binary input 5
Threshold in percentage of station battery voltage for input 5
Debounce time for input 5
Oscillation count for input 5
Oscillation time for input 5
User define string for binary input 6
Threshold in percentage of station battery voltage for input 6
Debounce time for input 6
Oscillation count for input 6
Oscillation time for input 6
User define string for binary input 7
Threshold in percentage of station battery voltage for input 7
Debounce time for input 7
Oscillation count for input 7
Oscillation time for input 7
User define string for binary input 8
Threshold in percentage of station battery voltage for input 8
Debounce time for input 8
Oscillation count for input 8
Oscillation time for input 8
User define string for binary input 9
Name
BatteryVoltage
BINAME1
Threshold1
DebounceTime1
OscillationCount1
OscillationTime1
BINAME2
Threshold2
DebounceTime2
OscillationCount2
OscillationTime2
BINAME3
Threshold3
DebounceTime3
OscillationCount3
OscillationTime3
BINAME4
Threshold4
DebounceTime4
OscillationCount4
OscillationTime4
BINAME5
Threshold5
DebounceTime5
OscillationCount5
OscillationTime5
BINAME6
Threshold6
DebounceTime6
OscillationCount6
OscillationTime6
BINAME7
Threshold7
DebounceTime7
OscillationCount7
OscillationTime7
BINAME8
Threshold8
DebounceTime8
OscillationCount8
OscillationTime8
BINAME9
Value
110 V
BI1
65 %UB
0.005 s
0
0.000 s
BI2
65 %UB
0.005 s
0
0.000 s
BI3
65 %UB
0.005 s
0
0.000 s
SPARE
65 %UB
0.005 s
0
0.000 s
BI5
65 %UB
0.005 s
0
0.000 s
BI6
65 %UB
0.005 s
0
0.000 s
BI7
65 %UB
0.005 s
0
0.000 s
BI8
65 %UB
0.005 s
0
0.000 s
BI9
Threshold9
DebounceTime9
OscillationCount9
OscillationTime9
65 %UB
0.005 s
0
0.000 s
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HW Configuration \ BIO_4
Description
Station battery voltage
User define string for binary input 1
Threshold in percentage of station battery voltage for input 1
Debounce time for input 1
Oscillation count for input 1
Oscillation time for input 1
User define string for binary input 2
Threshold in percentage of station battery voltage for input 2
Debounce time for input 2
Oscillation count for input 2
Oscillation time for input 2
User define string for binary input 3
Threshold in percentage of station battery voltage for input 3
Debounce time for input 3
Oscillation count for input 3
Oscillation time for input 3
User define string for binary input 4
Threshold in percentage of station battery voltage for input 4
Debounce time for input 4
Oscillation count for input 4
Oscillation time for input 4
User define string for binary input 5
Threshold in percentage of station battery voltage for input 5
Debounce time for input 5
Oscillation count for input 5
Oscillation time for input 5
User define string for binary input 6
Threshold in percentage of station battery voltage for input 6
Debounce time for input 6
Oscillation count for input 6
Oscillation time for input 6
User define string for binary input 7
Threshold in percentage of station battery voltage for input 7
Debounce time for input 7
Oscillation count for input 7
Oscillation time for input 7
User define string for binary input 8
Threshold in percentage of station battery voltage for input 8
Debounce time for input 8
Oscillation count for input 8
Oscillation time for input 8
User define string for binary input 9
Threshold in percentage of station battery voltage for input 9
Debounce time for input 9
Oscillation count for input 9
Oscillation time for input 9
Name
BatteryVoltage
BINAME1
Threshold1
DebounceTime1
OscillationCount1
OscillationTime1
BINAME2
Threshold2
DebounceTime2
OscillationCount2
OscillationTime2
BINAME3
Threshold3
DebounceTime3
OscillationCount3
OscillationTime3
BINAME4
Threshold4
DebounceTime4
OscillationCount4
OscillationTime4
BINAME5
Threshold5
DebounceTime5
OscillationCount5
OscillationTime5
BINAME6
Threshold6
DebounceTime6
OscillationCount6
OscillationTime6
BINAME7
Threshold7
DebounceTime7
OscillationCount7
OscillationTime7
BINAME8
Threshold8
DebounceTime8
OscillationCount8
OscillationTime8
BINAME9
Threshold9
DebounceTime9
OscillationCount9
OscillationTime9
Value
110 V
BI1
65 %UB
0.005 s
0
0.000 s
BI2
65 %UB
0.005 s
0
0.000 s
LINE_MCB_FF
65 %UB
0.005 s
0
0.000 s
QB9_OPEN
65 %UB
0.005 s
0
0.000 s
THL_RESET
65 %UB
0.005 s
0
0.000 s
QB1_CLOSED
65 %UB
0.005 s
0
0.000 s
QB1_OPEN
65 %UB
0.005 s
0
0.000 s
QB2_CLOSED
65 %UB
0.005 s
0
0.000 s
QB2_OPEN
65 %UB
0.005 s
0
0.000 s
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HW Configuration \ COM_101
Description
Station battery voltage
User define string for binary input 1
Threshold in percentage of station battery voltage for input 1
Debounce time for input 1
Oscillation count for input 1
Oscillation time for input 1
User define string for binary input 2
Threshold in percentage of station battery voltage for input 2
Debounce time for input 2
Name
BatteryVoltage
BINAME1
Threshold1
DebounceTime1
OscillationCount1
OscillationTime1
BINAME2
Threshold2
DebounceTime2
Value
110 V
BI1
65 %UB
0.005 s
0
0.000 s
BI2
65 %UB
0.005 s
OscillationCount2
OscillationTime2
BINAME3
Threshold3
DebounceTime3
OscillationCount3
OscillationTime3
BINAME4
Threshold4
DebounceTime4
OscillationCount4
OscillationTime4
BINAME5
Threshold5
DebounceTime5
OscillationCount5
OscillationTime5
BINAME6
Threshold6
DebounceTime6
OscillationCount6
OscillationTime6
BINAME7
Threshold7
DebounceTime7
OscillationCount7
OscillationTime7
BINAME8
Threshold8
DebounceTime8
OscillationCount8
OscillationTime8
BINAME9
Threshold9
DebounceTime9
OscillationCount9
OscillationTime9
BINAME10
Threshold10
DebounceTime10
OscillationCount10
OscillationTime10
BINAME11
Threshold11
DebounceTime11
OscillationCount11
OscillationTime11
BINAME12
Threshold12
DebounceTime12
OscillationCount12
OscillationTime12
BINAME13
Threshold13
DebounceTime13
OscillationCount13
OscillationTime13
BINAME14
Threshold14
DebounceTime14
OscillationCount14
OscillationTime14
0
0.000 s
BI3
65 %UB
0.005 s
0
0.000 s
BI4
65 %UB
0.005 s
0
0.000 s
BI5
65 %UB
0.005 s
0
0.000 s
BI6
65 %UB
0.005 s
0
0.000 s
BI7
65 %UB
0.005 s
0
0.000 s
BI8
65 %UB
0.005 s
0
0.000 s
BI9
65 %UB
0.005 s
0
0.000 s
BI10
65 %UB
0.005 s
0
0.000 s
BI11
65 %UB
0.005 s
0
0.000 s
BI12
65 %UB
0.005 s
0
0.000 s
BI13
65 %UB
0.005 s
0
0.000 s
BI14
65 %UB
0.005 s
0
0.000 s
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Activate setting group \
SETGRPS: 1
Description
ActiveSettingGroup
Name
ActiveSetGrp
Value
SettingGroup1
MaxNoSetGrp
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Time \ System time \
SYSTEMTIME: 1
Description
System time
Name
SystemTime
Value
2014-12-08 08:06:35
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Time \ System time \
DSTBEGIN: 1
Description
Month in year when daylight time starts
Day in week when daylight time starts
Week in month when daylight time starts
UTC Time of day in hours when daylight time starts
Name
MonthInYear
DayInWeek
WeekInMonth
UTCTimeOfDay
Value
March
Sunday
Last
1:00
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Time \ System time \
DSTEND: 1
Description
Month in year when daylight time ends
Day in week when daylight time ends
Week in month when daylight time ends
UTC Time of day in hours when daylight time ends
Name
MonthInYear
DayInWeek
WeekInMonth
UTCTimeOfDay
Value
October
Sunday
Last
1:00
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Time \ System time \
TIMEZONE: 1
Description
Number of half-hours from UTC
Name
NoHalfHourUTC
Value
0
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Time \ Synchronisation \
TIMESYNCHGEN: 1
Description
Coarse time synchronization source
Fine time synchronization source
Activate IED as synchronization master
Name
CoarseSyncSrc
FineSyncSource
SyncMaster
Value
Off
Off
Off
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Time \ Synchronisation \
IRIG-B: 1
Description
Time domain
Type of encoding
Time zone as in 1344 standard
Name
TimeDomain
Encoding
TimeZoneAs1344
Value
LocalTime
IRIG-B
PlusTZ
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Time \ Synchronisation \
SNTP: 1
Description
Server IP-address
Redundant server IP-address
Name
ServerIP-Add
RedServIP-Add
Value
0.0.0.0
0.0.0.0
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Power system \ Primary
values \ PRIMVAL: 1
Description
Rated system frequency
System phase rotation
Name
Frequency
PhaseRotation
Value
50.0 Hz
Normal=L1L2L3
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Power system \ Global base
values \ GBASVAL: 1
Description
Global base voltage
Global base current
Global base apparent power
Name
UBase
IBase
SBase
Value
132.00 kV
800 A
105.000 MVA
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Power system \ Global base
values \ GBASVAL: 2
Description
Global base voltage
Global base current
Global base apparent power
Name
UBase
IBase
SBase
Value
132.00 kV
800 A
105.000 MVA
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Power system \ Global base
values \ GBASVAL: 3
Description
Global base voltage
Global base current
Global base apparent power
Name
UBase
IBase
SBase
Value
132.00 kV
800 A
105.000 MVA
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Power system \ Global base
values \ GBASVAL: 4
Description
Global base voltage
Global base current
Global base apparent power
Name
UBase
IBase
SBase
Value
132.00 kV
800 A
105.000 MVA
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Power system \ Global base
values \ GBASVAL: 5
Description
Global base voltage
Global base current
Global base apparent power
Name
UBase
IBase
SBase
Value
132.00 kV
800 A
105.000 MVA
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Power system \ Global base
values \ GBASVAL: 6
Description
Global base voltage
Global base current
Global base apparent power
Name
UBase
IBase
SBase
Value
132.00 kV
800 A
105.000 MVA
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Power system \ Identifiers \
TERMINALID: 1
Description
Station name
Station number
Object name
Name
StationName
StationNumber
ObjectName
Value
New Karak
112
REL650-A01
Object number
Unit name
Unit number
IED main function type for IEC60870-5-103
ObjectNumber
UnitName
UnitNumber
IEDMainFunType
0
Qatraneh Circuit
0
128
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Communication \ Station
communication \ DNP3.0 \ DNPGEN: 1
Description
Operation mode Off / On
Name
Operation
Value
Off
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Communication \ Station
communication \ DNP3.0 \ CH1TCP: 1
Description
Operation mode
Application layer maximum Rx fragment size
Application layer maximum Tx fragment size
TCP/IP listen port
UDP port to accept UDP datagrams from master
UDP port for initial NULL response
UDP port to remote client/master
Name
Operation
ApLayMaxRxSize
ApLayMaxTxSize
TCPIPLisPort
UDPPortAccData
UDPPortInitNUL
UDPPortCliMast
Value
Off
2048
2048
20000
20000
20000
0
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Communication \ Station
communication \ DNP3.0 \ CH2TCP: 2
Description
Operation mode
Application layer maximum Rx fragment size
Application layer maximum Tx fragment size
TCP/IP listen port
UDP port to accept UDP datagrams from master
UDP port for initial NULL response
UDP port to remote client/master
Name
Operation
ApLayMaxRxSize
ApLayMaxTxSize
TCPIPLisPort
UDPPortAccData
UDPPortInitNUL
UDPPortCliMast
Value
Off
2048
2048
20000
20000
20000
0
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Communication \ Station
communication \ DNP3.0 \ CH3TCP: 3
Description
Operation mode
Application layer maximum Rx fragment size
Application layer maximum Tx fragment size
TCP/IP listen port
UDP port to accept UDP datagrams from master
UDP port for initial NULL response
UDP port to remote client/master
Name
Operation
ApLayMaxRxSize
ApLayMaxTxSize
TCPIPLisPort
UDPPortAccData
UDPPortInitNUL
UDPPortCliMast
Value
Off
2048
2048
20000
20000
20000
0
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Communication \ Station
communication \ DNP3.0 \ CH4TCP: 4
Description
Operation mode
Application layer maximum Rx fragment size
Application layer maximum Tx fragment size
TCP/IP listen port
UDP port to accept UDP datagrams from master
UDP port for initial NULL response
UDP port to remote client/master
Name
Operation
ApLayMaxRxSize
ApLayMaxTxSize
TCPIPLisPort
UDPPortAccData
UDPPortInitNUL
UDPPortCliMast
Value
Off
2048
2048
20000
20000
20000
0
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Communication \ Station
Name
Operation
SlaveAddress
MasterAddres
ValMasterAddr
AddrQueryEnbl
tApplConfTout
ApplMultFrgRes
ConfMultFrag
UREnable
UREvClassMask
UROfflineRetry
tURRetryDelay
tUROfflRtryDel
UREvCntThold1
tUREvBufTout1
UREvCntThold2
tUREvBufTout2
UREvCntThold3
tUREvBufTout3
DelOldBufFull
ExtTimeFormat
DNPToSetTime
tSynchTimeout
TSyncReqAfTout
Averag3TimeReq
MasterIP-Addr
MasterIPNetMsk
Obj1DefVar
Obj2DefVar
Obj3DefVar
Obj4DefVar
Obj10DefVar
Obj20DefVar
Obj22DefVar
Obj30DefVar
Obj32DefVar
PairedPoint
tSelectTimeout
tBrokenConTout
tKeepAliveT
Value
Off
1
1
Yes
Yes
10.00 s
Yes
Yes
Yes
Off
5
5.00 s
30.00 s
5
5.00 s
5
5.00 s
5
5.00 s
No
UTC
No
1800 s
No
No
0.0.0.0
255.255.255.255
1:BISingleBit
3:BIChWithRelTime
1:DIWithoutFlag
3:DIChWithRelTime
2:BOStatus
5:BinCnt32WoutF
1:BinCnt32EvWoutT
3:AI32IntWithoutF
1:AI32IntEvWoutF
Yes
30.0 s
0 s
10 s
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Communication \ Station
communication \ DNP3.0 \ MST2TCP: 2
Description
Operation Off / On
Slave address
Master address
Validate source (master) address
Address query enable
Application layer confim timeout
Enable application for multiple fragment response
Confirm each multiple fragment
Unsolicited response enabled
Unsolicited response, event class mask
Unsolicited response retries before off-line retry mode
Unsolicited response retry delay in s
Unsolicited response off-line retry delay in s
Unsolicited response class 1 event count report treshold
Unsolicited response class 1 event buffer timeout
Unsolicited response class 2 event count report treshold
Unsolicited response class 2 event buffer timeout
Unsolicited response class 3 event count report treshold
Unsolicited response class 3 event buffer timeout
Delete oldest event when buffer is full
External time format
Name
Operation
SlaveAddress
MasterAddres
ValMasterAddr
AddrQueryEnbl
tApplConfTout
ApplMultFrgRes
ConfMultFrag
UREnable
UREvClassMask
UROfflineRetry
tURRetryDelay
tUROfflRtryDel
UREvCntThold1
tUREvBufTout1
UREvCntThold2
tUREvBufTout2
UREvCntThold3
tUREvBufTout3
DelOldBufFull
ExtTimeFormat
Value
Off
1
1
Yes
Yes
10.00 s
Yes
Yes
Yes
Off
5
5.00 s
30.00 s
5
5.00 s
5
5.00 s
5
5.00 s
No
UTC
DNPToSetTime
tSynchTimeout
TSyncReqAfTout
Averag3TimeReq
MasterIP-Addr
MasterIPNetMsk
Obj1DefVar
Obj2DefVar
Obj3DefVar
Obj4DefVar
Obj10DefVar
Obj20DefVar
Obj22DefVar
Obj30DefVar
Obj32DefVar
PairedPoint
tSelectTimeout
tBrokenConTout
tKeepAliveT
No
1800 s
No
No
0.0.0.0
255.255.255.255
1:BISingleBit
3:BIChWithRelTime
1:DIWithoutFlag
3:DIChWithRelTime
2:BOStatus
5:BinCnt32WoutF
1:BinCnt32EvWoutT
3:AI32IntWithoutF
1:AI32IntEvWoutF
Yes
30.0 s
0 s
10 s
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Communication \ Station
communication \ DNP3.0 \ MST3TCP: 3
Description
Operation Off / On
Slave address
Master address
Validate source (master) address
Address query enable
Application layer confim timeout
Enable application for multiple fragment response
Confirm each multiple fragment
Unsolicited response enabled
Unsolicited response, event class mask
Unsolicited response retries before off-line retry mode
Unsolicited response retry delay in s
Unsolicited response off-line retry delay in s
Unsolicited response class 1 event count report treshold
Unsolicited response class 1 event buffer timeout
Unsolicited response class 2 event count report treshold
Unsolicited response class 2 event buffer timeout
Unsolicited response class 3 event count report treshold
Unsolicited response class 3 event buffer timeout
Delete oldest event when buffer is full
External time format
Allow DNP to set time in IED
Time synch timeout before error status is generated
Time synchronization request after timeout
Use average of 3 time requests
Master IP-address
Master IP net mask
Object 1, default variation
Object 2, default variation
Object 3, default variation
Object 4, default variation
Object 10, default variation
Object 20, default variation
Object 22, default variation
Object 30, default variation
Object 32, default variation
Enable paired point
Select timeout
Broken connection timeout
Keep-Alive timer
Name
Operation
SlaveAddress
MasterAddres
ValMasterAddr
AddrQueryEnbl
tApplConfTout
ApplMultFrgRes
ConfMultFrag
UREnable
UREvClassMask
UROfflineRetry
tURRetryDelay
tUROfflRtryDel
UREvCntThold1
tUREvBufTout1
UREvCntThold2
tUREvBufTout2
UREvCntThold3
tUREvBufTout3
DelOldBufFull
ExtTimeFormat
DNPToSetTime
tSynchTimeout
TSyncReqAfTout
Averag3TimeReq
MasterIP-Addr
MasterIPNetMsk
Obj1DefVar
Obj2DefVar
Obj3DefVar
Obj4DefVar
Obj10DefVar
Obj20DefVar
Obj22DefVar
Obj30DefVar
Obj32DefVar
PairedPoint
tSelectTimeout
tBrokenConTout
tKeepAliveT
Value
Off
1
1
Yes
Yes
10.00 s
Yes
Yes
Yes
Off
5
5.00 s
30.00 s
5
5.00 s
5
5.00 s
5
5.00 s
No
UTC
No
1800 s
No
No
0.0.0.0
255.255.255.255
1:BISingleBit
3:BIChWithRelTime
1:DIWithoutFlag
3:DIChWithRelTime
2:BOStatus
5:BinCnt32WoutF
1:BinCnt32EvWoutT
3:AI32IntWithoutF
1:AI32IntEvWoutF
Yes
30.0 s
0 s
10 s
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Communication \ Station
Name
Operation
SlaveAddress
MasterAddres
ValMasterAddr
AddrQueryEnbl
tApplConfTout
ApplMultFrgRes
ConfMultFrag
UREnable
UREvClassMask
UROfflineRetry
tURRetryDelay
tUROfflRtryDel
UREvCntThold1
tUREvBufTout1
UREvCntThold2
tUREvBufTout2
UREvCntThold3
tUREvBufTout3
DelOldBufFull
ExtTimeFormat
DNPToSetTime
tSynchTimeout
TSyncReqAfTout
Averag3TimeReq
MasterIP-Addr
MasterIPNetMsk
Obj1DefVar
Obj2DefVar
Obj3DefVar
Obj4DefVar
Obj10DefVar
Obj20DefVar
Obj22DefVar
Obj30DefVar
Obj32DefVar
PairedPoint
tSelectTimeout
tBrokenConTout
tKeepAliveT
Value
Off
1
1
Yes
Yes
10.00 s
Yes
Yes
Yes
Off
5
5.00 s
30.00 s
5
5.00 s
5
5.00 s
5
5.00 s
No
UTC
No
1800 s
No
No
0.0.0.0
255.255.255.255
1:BISingleBit
3:BIChWithRelTime
1:DIWithoutFlag
3:DIChWithRelTime
2:BOStatus
5:BinCnt32WoutF
1:BinCnt32EvWoutT
3:AI32IntWithoutF
1:AI32IntEvWoutF
Yes
30.0 s
0 s
10 s
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Communication \ Station
communication \ IEC60870-5-103: 1
Description
Operation
Slave address
Baudrate on serial line
Invert polarity
Cyclic reporting time of measurments
Master time domain
Time synchronization mode
Evaluate time accuracy for invalid time
Event reporting mode
Name
Operation
SlaveAddress
BaudRate
RevPolarity
CycMeasRepTime
MasterTimeDomain
TimeSyncMode
EvalTimeAccuracy
EventRepMode
Value
Off
1
9600 Bd
On
5.0 s
UTC
IEDTime
Off
SeqOfEvent
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Communication \ Station
communication \ IEC61850-8-1: 1
Description
Operation Off/On
Port for GOOSE communication
Name
Operation
GOOSE
Value
On
LAN1
Name
IPAddress
IPMask
DHCPServer
Value
10.1.150.3
255.255.255.0
On
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Communication \ TCP-IP
configuration \ ETHLAN1: 1
Description
Link name to physical hardware
IP-Address
IP-Mask
Name
Link
IPAddress
IPMask
Value
LAN1
192.168.1.10
255.255.255.0
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Communication \ TCP-IP
configuration \ GATEWAY: 1
Description
Gateway address
Name
GWAddress
Value
10.1.150.1
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ Analog modules \ Reference
channel service values \ AISVBAS: 1
Description
Reference channel for phase angle presentation
Name
PhaseAngleRef
Value
TRM - Channel 6
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ Screen \ SCREEN: 1
Description
Local HMI display timeout
Contrast level for display
Default screen
Sort order of event list
Automatic indication of disturbance report
Substitute indication on single line diagram
Interlock indication on single line diagram
Enable bypass of commands
Name
DisplayTimeout
ContrastLevel
DefaultScreen
EvListSrtOrder
AutoIndicationDRP
SubstIndSLD
InterlockIndSLD
BypassCommands
Value
10 Min
0 %
Main menu
Latest on top
Off
No
No
No
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ Function key control \
Function key control LHMI \ Function key 1 \ FNKEYTY1: 1
Description
Function key type
Menu shortcut for function key
Name
Type
MenuShortcut
Value
Control
Main menu
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ Function key control \
Function key control LHMI \ Function key 1 \ AR ON/OFF; FNKEYMD1: 1
Description
Output operation mode
Pulse time for output controlled by LCDFn1
Label for LED on state
Label for LED off state
Name
Mode
PulseTime
LabelOn
LabelOff
Value
Toggle
1.000 s
AR_ON
AR_OFF
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ Function key control \
Function key control LHMI \ Function key 2 \ FNKEYTY2: 1
Description
Name
Value
Type
MenuShortcut
Off
Main menu
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ Function key control \
Function key control LHMI \ Function key 3 \ FNKEYTY3: 1
Description
Function key type
Menu shortcut for function key
Name
Type
MenuShortcut
Value
Control
Main menu
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ Function key control \
Function key control LHMI \ Function key 3 \ THOL RESET; FNKEYMD3: 1
Description
Output operation mode
Pulse time for output controlled by LCDFn3
Label for LED on state
Label for LED off state
Name
Mode
PulseTime
LabelOn
LabelOff
Value
Pulsed
1.000 s
THL_RESET_ON
THL_RESET_OFF
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ Function key control \
Function key control LHMI \ Function key 4 \ FNKEYTY4: 1
Description
Function key type
Menu shortcut for function key
Name
Type
MenuShortcut
Value
Off
Main menu
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ Function key control \
Function key control LHMI \ Function key 4 \ CLEAR LEDS; FNKEYMD4: 1
Description
Output operation mode
Pulse time for output controlled by LCDFn4
Label for LED on state
Label for LED off state
Name
Mode
PulseTime
LabelOn
LabelOff
Value
Pulsed
1.000 s
CLEAR LEDS ON
CLEAR LEDS
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ Function key control \
Function key control LHMI \ Function key 5 \ FNKEYTY5: 1
Description
Function key type
Menu shortcut for function key
Name
Type
MenuShortcut
Value
Control
Main menu
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ Function key control \
Function key control LHMI \ Function key 5 \ RESET LOCKOUT; FNKEYMD5: 1
Description
Output operation mode
Pulse time for output controlled by LCDFn5
Label for LED on state
Name
Mode
PulseTime
LabelOn
LabelOff
Value
Pulsed
1.000 s
RESET_LOCKOUT_O
N
RESET_LOCKOUT
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ LEDGEN: 1
Description
Operation Off/On
Defines the disturbance length
Maximum time for the definition of a disturbance
Name
Operation
tRestart
tMax
Value
On
0.0 s
0.0 s
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 1 \
DIST PR TRIP; GRP1_LED1: 1
Description
Sequence type for LED 1, local HMI alarm group 1
Label string shown when LED 1, alarm group 1 is off
Label string shown when LED 1, alarm group 1 is red
Label string shown when LED 1, alarm group 1 is yellow
Label string shown when LED 1, alarm group 1 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
SYNC OK
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 1 \
OC PR TRIP; GRP1_LED2: 1
Description
Sequence type for LED 2, local HMI alarm group 1
Label string shown when LED 2, alarm group 1 is off
Label string shown when LED 2, alarm group 1 is red
Label string shown when LED 2, alarm group 1 is yellow
Label string shown when LED 2, alarm group 1 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
LatchedAck-S-F
ZONE1 TRIP
ZONE1 TRIP
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 1 \
EF PR TRIP; GRP1_LED3: 1
Description
Sequence type for LED 3, local HMI alarm group 1
Label string shown when LED 3, alarm group 1 is off
Label string shown when LED 3, alarm group 1 is red
Label string shown when LED 3, alarm group 1 is yellow
Label string shown when LED 3, alarm group 1 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
LatchedAck-S-F
ZONE2 TRIP
ZONE2 TRIP
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 1 \
CAR AID TRIP; GRP1_LED4: 1
Description
Sequence type for LED 4, local HMI alarm group 1
Label string shown when LED 4, alarm group 1 is off
Label string shown when LED 4, alarm group 1 is red
Label string shown when LED 4, alarm group 1 is yellow
Label string shown when LED 4, alarm group 1 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
LatchedAck-S-F
ZONE3 TRIP
ZONE3 TRIP
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 1 \
VOLT PR TRIP; GRP1_LED5: 1
Description
Sequence type for LED 5, local HMI alarm group 1
Label string shown when LED 5, alarm group 1 is off
Label string shown when LED 5, alarm group 1 is red
Label string shown when LED 5, alarm group 1 is yellow
Label string shown when LED 5, alarm group 1 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
LatchedAck-S-F
ZONE4 TRIP
ZONE4 TRIP
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 1 \
GRP1_LED6: 1
Description
Sequence type for LED 6, local HMI alarm group 1
Label string shown when LED 6, alarm group 1 is off
Label string shown when LED 6, alarm group 1 is red
Label string shown when LED 6, alarm group 1 is yellow
Name
SequenceType
LabelOff
LabelRed
LabelYellow
Value
LatchedAck-S-F
SOTF TRIP
SOTF TRIP
LabelGreen
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 1 \
GRP1_LED7: 1
Description
Sequence type for LED 7, local HMI alarm group 1
Label string shown when LED 7, alarm group 1 is off
Label string shown when LED 7, alarm group 1 is red
Label string shown when LED 7, alarm group 1 is yellow
Label string shown when LED 7, alarm group 1 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
LatchedAck-S-F
R PH FAULT
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 1 \
GRP1_LED8: 1
Description
Sequence type for LED 8, local HMI alarm group 1
Label string shown when LED 8, alarm group 1 is off
Label string shown when LED 8, alarm group 1 is red
Label string shown when LED 8, alarm group 1 is yellow
Label string shown when LED 8, alarm group 1 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
LatchedAck-S-F
Y PH FAULT
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 1 \
BRC ALARM; GRP1_LED9: 1
Description
Sequence type for LED 9, local HMI alarm group 1
Label string shown when LED 9, alarm group 1 is off
Label string shown when LED 9, alarm group 1 is red
Label string shown when LED 9, alarm group 1 is yellow
Label string shown when LED 9, alarm group 1 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
LatchedAck-S-F
B PH FAULT
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 1 \
GRP1_LED10: 1
Description
Sequence type for LED 10, local HMI alarm group 1
Label string shown when LED 10, alarm group 1 is off
Label string shown when LED 10, alarm group 1 is red
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
LatchedAck-S-F
BROKEN
CONDUCTOR
BROKEN
CONDUCTOR
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 1 \
GRP1_LED11: 1
Description
Sequence type for LED 11, local HMI alarm group 1
Label string shown when LED 11, alarm group 1 is off
Label string shown when LED 11, alarm group 1 is red
Label string shown when LED 11, alarm group 1 is yellow
Label string shown when LED 11, alarm group 1 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
LatchedAck-S-F
PSB OPTD
PSB OPTD
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 1 \
GRP1_LED12: 1
Description
Sequence type for LED 12, local HMI alarm group 1
Label string shown when LED 12, alarm group 1 is off
Label string shown when LED 12, alarm group 1 is red
Label string shown when LED 12, alarm group 1 is yellow
Label string shown when LED 12, alarm group 1 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
FUSE FAIL
FUSE FAIL
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 1 \
GRP1_LED13: 1
Description
Sequence type for LED 13, local HMI alarm group 1
Label string shown when LED 13, alarm group 1 is off
Label string shown when LED 13, alarm group 1 is red
Label string shown when LED 13, alarm group 1 is yellow
Label string shown when LED 13, alarm group 1 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
LatchedAck-S-F
CARRIER SEND
CARRIER SEND
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 1 \
GRP1_LED14: 1
Description
Sequence type for LED 14, local HMI alarm group 1
Label string shown when LED 14, alarm group 1 is off
Label string shown when LED 14, alarm group 1 is red
Label string shown when LED 14, alarm group 1 is yellow
Label string shown when LED 14, alarm group 1 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
LatchedAck-S-F
AR OPTD
AR OPTD
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 1 \
GRP1_LED15: 1
Description
Sequence type for LED 15, local HMI alarm group 1
Label string shown when LED 15, alarm group 1 is off
Label string shown when LED 15, alarm group 1 is red
Label string shown when LED 15, alarm group 1 is yellow
Label string shown when LED 15, alarm group 1 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
LatchedAck-S-F
AR UNSUC
AR UNSUC
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 2 \
GEN START ZQ; GRP2_LED1: 1
Description
Sequence type for LED 1, local HMI alarm group 2
Label string shown when LED 1, alarm group 2 is off
Label string shown when LED 1, alarm group 2 is red
Label string shown when LED 1, alarm group 2 is yellow
Label string shown when LED 1, alarm group 2 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
GEN START ZM
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 2 \
GEN START OC; GRP2_LED2: 1
Description
Sequence type for LED 2, local HMI alarm group 2
Label string shown when LED 2, alarm group 2 is off
Label string shown when LED 2, alarm group 2 is red
Label string shown when LED 2, alarm group 2 is yellow
Label string shown when LED 2, alarm group 2 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
GEN START OC
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 2 \
GEN START EF; GRP2_LED3: 1
Description
Sequence type for LED 3, local HMI alarm group 2
Label string shown when LED 3, alarm group 2 is off
Label string shown when LED 3, alarm group 2 is red
Label string shown when LED 3, alarm group 2 is yellow
Label string shown when LED 3, alarm group 2 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
GEN START EF
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 2 \
GRP2_LED4: 1
Description
Sequence type for LED 4, local HMI alarm group 2
Label string shown when LED 4, alarm group 2 is off
Label string shown when LED 4, alarm group 2 is red
Label string shown when LED 4, alarm group 2 is yellow
Label string shown when LED 4, alarm group 2 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 2 \
GEN START OV; GRP2_LED5: 1
Description
Sequence type for LED 5, local HMI alarm group 2
Label string shown when LED 5, alarm group 2 is off
Label string shown when LED 5, alarm group 2 is red
Label string shown when LED 5, alarm group 2 is yellow
Label string shown when LED 5, alarm group 2 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
GEN START OV
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 2 \
GEN START L1; GRP2_LED6: 1
Description
Sequence type for LED 6, local HMI alarm group 2
Label string shown when LED 6, alarm group 2 is off
Label string shown when LED 6, alarm group 2 is red
Label string shown when LED 6, alarm group 2 is yellow
Label string shown when LED 6, alarm group 2 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
GEN START L1
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 2 \
GEN START L2; GRP2_LED7: 1
Description
Sequence type for LED 7, local HMI alarm group 2
Label string shown when LED 7, alarm group 2 is off
Label string shown when LED 7, alarm group 2 is red
Label string shown when LED 7, alarm group 2 is yellow
Label string shown when LED 7, alarm group 2 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
GEN START L2
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 2 \
GEN START L3; GRP2_LED8: 1
Description
Sequence type for LED 8, local HMI alarm group 2
Label string shown when LED 8, alarm group 2 is off
Label string shown when LED 8, alarm group 2 is red
Label string shown when LED 8, alarm group 2 is yellow
Name
SequenceType
LabelOff
LabelRed
LabelYellow
Value
Follow-S
GEN START L3
LabelGreen
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 2 \
GRP2_LED9: 1
Description
Sequence type for LED 9, local HMI alarm group 2
Label string shown when LED 9, alarm group 2 is off
Label string shown when LED 9, alarm group 2 is red
Label string shown when LED 9, alarm group 2 is yellow
Label string shown when LED 9, alarm group 2 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 2 \
GRP2_LED10: 1
Description
Sequence type for LED 10, local HMI alarm group 2
Label string shown when LED 10, alarm group 2 is off
Label string shown when LED 10, alarm group 2 is red
Label string shown when LED 10, alarm group 2 is yellow
Label string shown when LED 10, alarm group 2 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 2 \
GRP2_LED11: 1
Description
Sequence type for LED 11, local HMI alarm group 2
Label string shown when LED 11, alarm group 2 is off
Label string shown when LED 11, alarm group 2 is red
Label string shown when LED 11, alarm group 2 is yellow
Label string shown when LED 11, alarm group 2 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 2 \
GRP2_LED12: 1
Description
Sequence type for LED 12, local HMI alarm group 2
Label string shown when LED 12, alarm group 2 is off
Label string shown when LED 12, alarm group 2 is red
Label string shown when LED 12, alarm group 2 is yellow
Label string shown when LED 12, alarm group 2 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 2 \
GRP2_LED13: 1
Description
Sequence type for LED 13, local HMI alarm group 2
Label string shown when LED 13, alarm group 2 is off
Label string shown when LED 13, alarm group 2 is red
Label string shown when LED 13, alarm group 2 is yellow
Label string shown when LED 13, alarm group 2 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 2 \
GRP2_LED14: 1
Description
Sequence type for LED 14, local HMI alarm group 2
Label string shown when LED 14, alarm group 2 is off
Label string shown when LED 14, alarm group 2 is red
Label string shown when LED 14, alarm group 2 is yellow
Label string shown when LED 14, alarm group 2 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 2 \
GRP2_LED15: 1
Description
Sequence type for LED 15, local HMI alarm group 2
Label string shown when LED 15, alarm group 2 is off
Label string shown when LED 15, alarm group 2 is red
Label string shown when LED 15, alarm group 2 is yellow
Label string shown when LED 15, alarm group 2 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 3 \
GRP3_LED1: 1
Description
Sequence type for LED 1, local HMI alarm group 3
Label string shown when LED 1, alarm group 3 is off
Label string shown when LED 1, alarm group 3 is red
Label string shown when LED 1, alarm group 3 is yellow
Label string shown when LED 1, alarm group 3 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 3 \
GRP3_LED2: 1
Description
Sequence type for LED 2, local HMI alarm group 3
Label string shown when LED 2, alarm group 3 is off
Label string shown when LED 2, alarm group 3 is red
Label string shown when LED 2, alarm group 3 is yellow
Label string shown when LED 2, alarm group 3 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 3 \
GRP3_LED3: 1
Description
Sequence type for LED 3, local HMI alarm group 3
Label string shown when LED 3, alarm group 3 is off
Label string shown when LED 3, alarm group 3 is red
Label string shown when LED 3, alarm group 3 is yellow
Label string shown when LED 3, alarm group 3 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 3 \
GRP3_LED4: 1
Description
Sequence type for LED 4, local HMI alarm group 3
Label string shown when LED 4, alarm group 3 is off
Label string shown when LED 4, alarm group 3 is red
Label string shown when LED 4, alarm group 3 is yellow
Label string shown when LED 4, alarm group 3 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 3 \
GRP3_LED5: 1
Description
Sequence type for LED 5, local HMI alarm group 3
Label string shown when LED 5, alarm group 3 is off
Label string shown when LED 5, alarm group 3 is red
Label string shown when LED 5, alarm group 3 is yellow
Label string shown when LED 5, alarm group 3 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 3 \
GRP3_LED6: 1
Description
Sequence type for LED 6, local HMI alarm group 3
Label string shown when LED 6, alarm group 3 is off
Label string shown when LED 6, alarm group 3 is red
Label string shown when LED 6, alarm group 3 is yellow
Label string shown when LED 6, alarm group 3 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 3 \
GRP3_LED7: 1
Description
Sequence type for LED 7, local HMI alarm group 3
Label string shown when LED 7, alarm group 3 is off
Label string shown when LED 7, alarm group 3 is red
Label string shown when LED 7, alarm group 3 is yellow
Label string shown when LED 7, alarm group 3 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 3 \
GRP3_LED8: 1
Description
Sequence type for LED 8, local HMI alarm group 3
Label string shown when LED 8, alarm group 3 is off
Label string shown when LED 8, alarm group 3 is red
Label string shown when LED 8, alarm group 3 is yellow
Label string shown when LED 8, alarm group 3 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 3 \
GRP3_LED9: 1
Description
Sequence type for LED 9, local HMI alarm group 3
Label string shown when LED 9, alarm group 3 is off
Label string shown when LED 9, alarm group 3 is red
Label string shown when LED 9, alarm group 3 is yellow
Label string shown when LED 9, alarm group 3 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 3 \
Z BLOCK; GRP3_LED10: 1
Description
Sequence type for LED 10, local HMI alarm group 3
Name
SequenceType
Value
Follow-S
LabelOff
LabelRed
LabelYellow
LabelGreen
Z BLOCK
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 3 \
U BLOCK; GRP3_LED11: 1
Description
Sequence type for LED 11, local HMI alarm group 3
Label string shown when LED 11, alarm group 3 is off
Label string shown when LED 11, alarm group 3 is red
Label string shown when LED 11, alarm group 3 is yellow
Label string shown when LED 11, alarm group 3 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
U BLOCK
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 3 \
GRP3_LED12: 1
Description
Sequence type for LED 12, local HMI alarm group 3
Label string shown when LED 12, alarm group 3 is off
Label string shown when LED 12, alarm group 3 is red
Label string shown when LED 12, alarm group 3 is yellow
Label string shown when LED 12, alarm group 3 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 3 \
CB SUPV ALARM; GRP3_LED13: 1
Description
Sequence type for LED 13, local HMI alarm group 3
Label string shown when LED 13, alarm group 3 is off
Label string shown when LED 13, alarm group 3 is red
Label string shown when LED 13, alarm group 3 is yellow
Label string shown when LED 13, alarm group 3 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
CB SUPV ALARM
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 3 \
TCS ALARM; GRP3_LED14: 1
Description
Sequence type for LED 14, local HMI alarm group 3
Label string shown when LED 14, alarm group 3 is off
Label string shown when LED 14, alarm group 3 is red
Label string shown when LED 14, alarm group 3 is yellow
Label string shown when LED 14, alarm group 3 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
TCS ALARM
.
REL650 V1.1 \ Relay Parameter Section \ IED Configuration \ HMI \ LEDs \ Alarm group 3 \
ST BAT SUP; GRP3_LED15: 1
Description
Sequence type for LED 15, local HMI alarm group 3
Label string shown when LED 15, alarm group 3 is off
Label string shown when LED 15, alarm group 3 is red
Label string shown when LED 15, alarm group 3 is yellow
Label string shown when LED 15, alarm group 3 is green
Name
SequenceType
LabelOff
LabelRed
LabelYellow
LabelGreen
Value
Follow-S
BAT SUP ALARM
BAT SUP START
Name
Operation
PreFaultRecT
PostFaultRecT
TimeLimit
PostRetrig
MaxNoStoreRec
ZeroAngleRef
OpModeTest
Value
On
0.10 s
0.5 s
1.0 s
Off
100
1 Ch
Off
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Analog modules \ 3
phase analog group \ LINE VT 5ms; SMAI_20_1: 1
Description
User defined name for AI1
User defined name for AI2
User defined name for AI3
User defined name for AI4
Selection of one of the Global Base Value groups
DFT reference for external output
DFT reference
Input connection type
Negation
Limit for frequency calculation in % of UBase
Analog input signal type
Name
AI1NAME
AI2NAME
AI3NAME
AI4NAME
GlobalBaseSel
DFTRefExtOut
DFTReference
ConnectionType
Negation
MinValFreqMeas
AnalogInputType
Value
UL1
UL2
UL3
Not used
1
InternalDFTRef
InternalDFTRef
Ph-N
Off
10 %
Voltage
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Analog modules \ 3
phase analog group \ LINE VT 20ms; SMAI_20_1: 2
Description
User defined name for AI1
User defined name for AI2
User defined name for AI3
User defined name for AI4
Selection of one of the Global Base Value groups
DFT reference for external output
DFT reference
Input connection type
Negation
Limit for frequency calculation in % of UBase
Analog input signal type
Name
AI1NAME
AI2NAME
AI3NAME
AI4NAME
GlobalBaseSel
DFTRefExtOut
DFTReference
ConnectionType
Negation
MinValFreqMeas
AnalogInputType
Value
UL1
UL2
UL3
Not used
1
InternalDFTRef
InternalDFTRef
Ph-N
Off
10 %
Voltage
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Analog modules \ 3
phase analog group \ BusA_VT; SMAI_20_3: 2
Description
User defined name for AI1
User defined name for AI2
User defined name for AI3
User defined name for AI4
Selection of one of the Global Base Value groups
DFT reference
Input connection type
Negation
Limit for frequency calculation in % of UBase
Analog input signal type
Name
AI1NAME
AI2NAME
AI3NAME
AI4NAME
GlobalBaseSel
DFTReference
ConnectionType
Negation
MinValFreqMeas
AnalogInputType
Value
LINE VT RPH
Notused
Notused
Notused
1
InternalDFTRef
Ph-N
Off
10 %
Voltage
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Analog modules \ 3
phase analog group \ BusB_VT; SMAI_20_4: 2
Description
Name
Value
AI1NAME
AI2NAME
AI3NAME
AI4NAME
GlobalBaseSel
DFTReference
ConnectionType
Negation
MinValFreqMeas
AnalogInputType
UL1-L2
UL2-L3
UL3-L1
Not used
1
InternalDFTRef
Ph-N
Off
10 %
Voltage
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Analog modules \ 3
phase analog group \ SENSITIVE EF; SMAI_20_5: 2
Description
User defined name for AI1
User defined name for AI2
User defined name for AI3
User defined name for AI4
Selection of one of the Global Base Value groups
DFT reference
Input connection type
Negation
Limit for frequency calculation in % of UBase
Analog input signal type
Name
AI1NAME
AI2NAME
AI3NAME
AI4NAME
GlobalBaseSel
DFTReference
ConnectionType
Negation
MinValFreqMeas
AnalogInputType
Value
GRP5L1
GRP5L2
GRP5L3
SEF_IN
1
InternalDFTRef
Ph-N
Off
10 %
Current
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Analog modules \ 3
phase analog group \ LINE CT 5ms; SMAI_20_7: 1
Description
User defined name for AI1
User defined name for AI2
User defined name for AI3
User defined name for AI4
Selection of one of the Global Base Value groups
DFT reference
Input connection type
Negation
Limit for frequency calculation in % of UBase
Analog input signal type
Name
AI1NAME
AI2NAME
AI3NAME
AI4NAME
GlobalBaseSel
DFTReference
ConnectionType
Negation
MinValFreqMeas
AnalogInputType
Value
IL1
IL2
IL3
IN optional
1
InternalDFTRef
Ph-N
Off
10 %
Current
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Analog modules \ 3
phase analog group \ LINE CT 20ms; SMAI_20_7: 2
Description
User defined name for AI1
User defined name for AI2
User defined name for AI3
User defined name for AI4
Selection of one of the Global Base Value groups
DFT reference
Input connection type
Negation
Limit for frequency calculation in % of UBase
Analog input signal type
Name
AI1NAME
AI2NAME
AI3NAME
AI4NAME
GlobalBaseSel
DFTReference
ConnectionType
Negation
MinValFreqMeas
AnalogInputType
Value
IL1
IL2
IL3
IN optional
1
InternalDFTRef
Ph-N
Off
10 %
Current
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Analog modules \ 3
phase analog group \ MUTUAL COMP; SMAI_20_9: 1
Description
User defined name for AI1
User defined name for AI2
User defined name for AI3
User defined name for AI4
Name
AI1NAME
AI2NAME
AI3NAME
AI4NAME
Value
GRP9L1
GRP9L2
GRP9L3
PLineCT_IN
GlobalBaseSel
DFTReference
ConnectionType
Negation
MinValFreqMeas
AnalogInputType
1
InternalDFTRef
Ph-N
Off
10 %
Current
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Communication \
GOOSE binary receive \ GOOSEBINRCV: 1
Description
Operation Off/On
Name
Operation
Value
On
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Control \ LocalRemote \ LOCREM: 1
Description
Control mode for internal/external LR-switch
Name
ControlMode
Value
Internal LR-switch
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Control \ QCBAY: 1
Description
Priority of originators
Name
AllPSTOValid
Value
Priority
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Control \ SPC8GGIO:
1
Description
Operation Off/On
Setting for pulsed/latched mode for output 1
Output1 Pulse Time
Setting for pulsed/latched mode for output 2
Output2 Pulse Time
Setting for pulsed/latched mode for output 3
Output3 Pulse Time
Setting for pulsed/latched mode for output 4
Output4 Pulse Time
Setting for pulsed/latched mode for output 5
Output5 Pulse Time
Setting for pulsed/latched mode for output 6
Output6 Pulse Time
Setting for pulsed/latched mode for output 7
Output7 Pulse Time
Setting for pulsed/latched mode for output 8
Output8 pulse time
Name
Operation
Latched1
tPulse1
Latched2
tPulse2
Latched3
tPulse3
Latched4
tPulse4
Latched5
tPulse5
Latched6
tPulse6
Latched7
tPulse7
Latched8
tPulse8
Value
Off
Pulsed
0.10 s
Pulsed
0.10 s
Pulsed
0.10 s
Pulsed
0.10 s
Pulsed
0.10 s
Pulsed
0.10 s
Pulsed
0.10 s
Pulsed
0.10 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Control \
SESRSYN(25; SYNC): 1
Description
Selection of one of the Global Base Value groups
Measured voltage for Line 1
Measured voltage for Busbar 1
Measured voltage for Busbar 2
Name
GlobalBaseSel
MeasVoltLine1
MeasVoltBus1
MeasVoltBus2
Value
1
UL1L2
UL1L2
UL1L2
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Control \
SESRSYN(25; SYNC): 1 \ Setting Group1
Description
Operation Off / On
Phase shift
Name
Operation
PhaseShift
Value
On
0 Deg
Voltage ratio
Operation for synchronizing function Off/On
Minimum frequency difference limit for synchronizing
Maximum frequency difference limit for synchronizing
Maximum allowed frequency rate of change
Closing time of the breaker
Breaker closing pulse duration
Resets synchronization if no close has been made before set
time
Minimum time to accept synchronizing conditions
Operation for synchronism check function Off/On
Voltage difference limit in % of UBase
Frequency difference limit between bus and line Auto
Frequency difference limit between bus and line Manual
Phase angle difference limit between bus and line Auto
Phase angle difference limit between bus and line Manual
Time delay for synchrocheck Auto
Time delay for synchrocheck Manual
Automatic energizing check mode
Manual energizing check mode
Manual dead bus, dead line energizing
Time delay for automatic energizing check
Time delay for manual energizing check
URatio
OperationSynch
FreqDiffMin
FreqDiffMax
FreqRateChange
tBreaker
tClosePulse
tMaxSynch
1.00
On
0.100
0.200
0.300
0.080
0.200
10.00
tMinSynch
OperationSC
UDiffSC
FreqDiffA
FreqDiffM
PhaseDiffA
PhaseDiffM
tSCA
tSCM
AutoEnerg
ManEnerg
ManEnergDBDL
tAutoEnerg
tManEnerg
2.000 s
On
10.0 %UB
0.200 Hz
0.200 Hz
20.0 Deg
20.0 Deg
0.100 s
0.100 s
DLLB
Both
Off
0.100 s
0.100 s
Hz
Hz
Hz/s
s
s
s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Control \
SMBRREC(79; 0->1): 1 \ Setting Group1
Description
Off / ExternalCtrl / On
Maximum number of reclosing shots 1-5
To be set ON if AR is to be started by CB open position
Select CB auxilary contact type NC/NO for CBPOS input
Select type of circuit breaker ready signal CO/OCO
Open time for shot 1, delayed reclosing 3ph
Open time for shot 2, three-phase
Open time for shot 3, three-phase
Open time for shot 4, three-phase
Open time for shot 5, three-phase
Duration of the reclaim time
Maximum wait time for synchrocheck OK
Inhibit reclosing reset time
Maximum trip pulse duration
Advance to next shot if CB has been closed during dead time
Minimum time that CB must be closed before new sequence
allows
Continue with next reclosing-shot if breaker did not close
Wait time after close command before proceeding to next shot
Unsuccessful closing signal obtained by checking CB position
Block AR at unsuccessful reclosing
Wait time for CB before indicating Unsuccessful/Successful
Priority selection between adjacent terminals None/Low/High
Maximum wait time for release from Master
Coordination of down stream devices to local protection units
AR
Name
Operation
NoOfShots
StartByCBOpen
CBAuxContType
CBReadyType
t1 3Ph
t2 3Ph
t3 3Ph
t4 3Ph
t5 3Ph
tReclaim
tSync
tInhibit
tTrip
Follow CB
tCBClosedMin
Value
External ctrl
1
Off
NormOpen
CO
1.000 s
30.00 s
30.00 s
30.00 s
30.00 s
10.00 s
30.00 s
5.000 s
0.500 s
Off
5.00 s
AutoCont
tAutoContWait
UnsucClByCBChk
BlockByUnsucCl
tUnsucCl
Priority
tWaitForMaster
ZoneSeqCoord
Off
2.000 s
NoCBCheck
Off
30.00 s
None
60.00 s
Off
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Control \
STBRREC(79): 1 \ Setting Group1
Description
Off / ExternalCtrl / On
AR mode selection e.g. 3ph, 1/3ph
Maximum number of reclosing shots 1-5
To be set ON if AR is to be started by CB open position
Select CB auxilary contact type NC/NO for CBPOS input
Select type of circuit breaker ready signal CO/OCO
Open time for shot 1, single-phase
Open time for shot 1, delayed reclosing 3ph
Name
Operation
ARMode
NoOfShots
StartByCBOpen
CBAuxContType
CBReadyType
t1 1Ph
t1 3Ph
Value
External ctrl
1/3ph
1
Off
NormOpen
CO
1.000 s
6.000 s
t2 3Ph
t3 3Ph
t4 3Ph
t5 3Ph
tReclaim
tSync
Extended t1
tExtended t1
30.00
30.00
30.00
30.00
60.00
30.00
Off
0.500
s
s
s
s
s
s
tInhibit
tTrip
Follow CB
tCBClosedMin
5.000 s
0.200 s
Off
5.00 s
AutoCont
tAutoContWait
UnsucClByCBChk
BlockByUnsucCl
tUnsucCl
Priority
tWaitForMaster
ZoneSeqCoord
Off
2.000 s
NoCBCheck
Off
30.00 s
None
60.00 s
Off
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Logic \
PULSETIMER: 3
Description
Pulse time length
Name
t
Value
0.010 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Logic \
PULSETIMER: 4
Description
Pulse time length
Name
t
Value
0.010 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Logic \
PULSETIMER: 11
Description
Pulse time length
Name
t
Value
0.010 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Logic \
PULSETIMER: 12
Description
Pulse time length
Name
t
Value
0.010 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Logic \ SRMEMORY:
1 \ Setting Group1
Description
Operating mode of the memory function
Name
Memory
Value
On
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Logic \ SRMEMORY:
2 \ Setting Group1
Description
Operating mode of the memory function
Name
Memory
Value
On
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Logic \ GATE: 1 \
Setting Group1
Description
Operation Off/On
Name
Operation
Value
On
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Logic \ QA1 OPEN;
TIMERSET: 2 \ Setting Group1
Description
Operation Off/On
Delay for settable timer n
Name
Operation
t
Value
On
0.000 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Logic \ GATE: 13 \
Setting Group1
Description
Operation Off/On
Name
Operation
Value
On
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Logic \ GATE: 16 \
Setting Group1
Description
Operation Off/On
Name
Operation
Value
Off
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Logic \ SMPPTRC(94;
1->0): 1 \ Setting Group1
Description
Operation Off / On
On: Activate output (CLLKOUT) and trip latch, Off: Only output
On: Lockout from input (SETLKOUT) and trip, Off: Only input
Minimum duration of trip output signal
Name
Operation
TripLockout
AutoLock
tTripMin
Value
On
Off
Off
0.150 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Logic \
SPTPTRC(94): 1 \ Setting Group1
Description
Operation Off / On
Three phase / single or three phase
On: Activate output (CLLKOUT) and trip latch, Off: Only output
On: Lockout from input (SETLKOUT) and trip, Off: Only input
Minimum duration of trip output signal
Name
Operation
Program
TripLockout
AutoLock
tTripMin
Value
On
3 phase
Off
Off
0.150 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Logic \ TMAGGIO: 1 \
Setting Group1
Description
Operation Off / On
Output pulse time
Output on delay time
Output off delay time
Mode for output 1, steady or pulsed
Mode for output 2, steady or pulsed
Mode for output 3, steady or pulsed
Name
Operation
PulseTime
OnDelay
OffDelay
ModeOutput1
ModeOutput2
ModeOutput3
Value
On
0.150 s
0.000 s
0.000 s
Steady
Steady
Steady
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Logic \ TMAGGIO: 2 \
Setting Group1
Description
Operation Off / On
Output pulse time
Output on delay time
Output off delay time
Mode for output 1, steady or pulsed
Mode for output 2, steady or pulsed
Mode for output 3, steady or pulsed
Name
Operation
PulseTime
OnDelay
OffDelay
ModeOutput1
ModeOutput2
ModeOutput3
Value
On
0.150 s
0.000 s
0.000 s
Steady
Steady
Steady
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Logic \ TESTMODE
ON; TIMERSET: 1 \ Setting Group1
Description
Operation Off/On
Delay for settable timer n
Name
Operation
t
Value
On
1.000 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
FDPSPDIS: 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
FDPSPDIS: 1 \ Setting Group1
Description
Operation of impedance based measurement
Operation of current based measurement
3I0 limit for blocking Phase-to-Phase measuring loops
3I0 limit for releasing Phase-to-Earth measuring loops
Forward resistive reach within the load impedance area
Reverse resistive reach within the load impedance area
Load angle determining the load impedance area
Start value for phase selection by over-current element
Start value for trip from 3I0 over-current element
Positive sequence reactance reach
Zero sequence reactance reach
Fault resistance reach, Phase-Phase, forward
Fault resistance reach, Phase-Phase, reverse
Fault resistance reach, Phase-Earth, forward
Fault resistance reach, Phase-Earth, reverse
Operation mode Off / On of zone timer, Phase-Phase
Time delay to trip, Phase-Phase
Operation mode Off / On of zone timer, Phase-Earth
Time delay to trip, Phase-Earth
Minimum operate delta current for Phase-Phase loops
Minimum operate phase current for Phase-Earth loops
Name
OperationZ<
OperationI>
INBlockPP
INReleasePE
RLdFw
RLdRv
ArgLd
IPh>
IN>
X1
X0
RFFwPP
RFRvPP
RFFwPE
RFRvPE
TimerPP
tPP
TimerPE
tPE
IMinOpPP
IMinOpPE
Value
Off
Off
40 %IPh
20 %IPh
80.00 ohm/p
80.00 ohm/p
30 Deg
120 %IB
20 %IB
40.00
120.00
30.00 ohm/l
30.00 ohm/l
100.00 ohm/l
100.00 ohm/l
Off
3.000 s
Off
3.000 s
10 %IB
5 %IB
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZCVPSOF: 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZCVPSOF: 1 \ Setting Group1
Description
Operation Off / On
Mode of operation of SOTF Function
Automatic switch onto fault initialization
Name
Operation
Mode
AutoInit
Value
On
UILevel
On
IPh<
UPh<
tDuration
tSOTF
tDLD
20 %IB
20 %UB
0.020 s
1.000 s
0.200 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZDNRDIR(21D; Z<->): 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZDNRDIR(21D; Z<->): 1 \ Setting Group1
Description
Angle of blinder in second quadrant for forward direction
Angle of blinder in fourth quadrant for forward direction
Minimum operate phase current for Phase-Earth loops
Minimum operate delta current for Phase-Phase loops
Name
ArgNegRes
ArgDir
IMinOpPE
IMinOpPP
Value
115 Deg
15 Deg
5 %IB
10 %IB
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
FMPSPDIS: 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
FMPSPDIS: 1 \ Setting Group1
Description
Name
Delta current level in % of IBase
DeltaIMinOp
Delta voltage level in % of UBase
DeltaUMinOp
Positive sequence voltage limit for identification of three phase U1Level
fault
Positive sequence current level for identification of three phase I1LowLevel
fault in % of IBase
Minimum operate positive sequence voltage for phase selection U1MinOp
Minimum operate negative sequence voltage for phase
U2MinOp
selection
Maximum load for identification of three phase fault in % of
IMaxLoad
IBase
3I0 limit for release Phase-Earth measuring loops in % of
INRelPE
maximum phase current
3I0 limit for blocking Phase-to-Phase measuring loops in % of INBlockPP
maximum phase current
Load resistive reach in ohm/phase
RLd
Load encroachment inclination of load angular sector
ArgLd
Blinder angle
BlinderAng
Value
10 %IB
20 %UB
80 %UB
10 %IB
20 %UB
5 %UB
100 %IB
20 %IB
40 %IB
1.00 ohm/p
35 Deg
85 Deg
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZQDPDIS(21; Z<): 1 \ General
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZQDPDIS(21; Z<): 1 \ General \ Setting Group1
Description
Operation Off / On
Name
Operation
Value
On
IMinOpPP
IMinOpPE
IMinOpIN
LineAng
20 %IB
20 %IB
5 %IB
80 Deg
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZQDPDIS(21; Z<): 1 \ Zone 1 \ Setting Group1
Description
Fault resistance reach, Phase-Earth, zone 1
Fault resistance reach, Phase-Phase, zone 1
Positive sequence impedance reach for zone 1
Magnitude of earth return compensation factor KN for zone 1
Angle for earth return compensation factor KN for zone 1
Operation mode Off / On of zone timer, Phase-Earth of zone 1
Operation mode Off / On of zone timer, Phase-Phase of zone 1
Direction mode zone 1
Time delay to trip, Phase-Earth, zone 1
Time delay to trip, Phase-Phase, zone 1
Operation mode of zone 1
Name
RFPE1
RFPP1
Z1
KNMag1
KNAng1
OpModetPE1
OpModetPP1
DirMode1
tPE1
tPP1
OpMode1
Value
15.00 ohm/l
15.00 ohm/l
9.200
0.75
-7 Deg
On
On
Forward
0.000 s
0.000 s
Enable Ph-E PhPh
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZQDPDIS(21; Z<): 1 \ Zone 2 \ Setting Group1
Description
Name
Fault resistance reach, Phase-Earth, zone 2
RFPE2
Fault resistance reach, Phase-Phase, zone 2
RFPP2
Positive sequence impedance reach for zone 2
Z2
Magnitude of earth return compensation factor KN for zone 2, 3, KNMag2
4 and 5
Angle for earth return compensation factor for zone 2, 3, 4 and KNAng2
5
Operation mode Off / On of zone timer, Phase-Earth of zone 2 OpModetPE2
Operation mode Off / On of zone timer, Phase-Phase of zone 2 OpModetPP2
Direction mode zone 2
DirMode2
Time delay to trip, Phase-Earth, zone 2
tPE2
Time delay to trip, Phase-Phase zone 2
tPP2
Operation mode of zone 2
OpMode2
Value
20.00 ohm/l
20.00 ohm/l
15.800
0.75
-7 Deg
On
On
Forward
0.400 s
0.400 s
Enable Ph-E PhPh
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZQDPDIS(21; Z<): 1 \ Zone 3 \ Setting Group1
Description
Fault resistance reach, Phase-Earth, zone 3
Fault resistance reach, Phase-Phase, zone 3
Positive sequence impedance reach for zone 3
Operation mode Off / On of zone timer, Phase-Earth of zone 3
Operation mode Off / On of zone timer, Phase-Phase of zone 3
Direction mode zone 3
Time delay to trip, Phase-Earth, zone 3
Time delay to trip, Phase-Phase zone 3
Operation mode of zone 3
Name
RFPE3
RFPP3
Z3
OpModetPE3
OpModetPP3
DirMode3
tPE3
tPP3
OpMode3
Value
25.00 ohm/l
25.00 ohm/l
20.000
On
On
Forward
0.800 s
0.800 s
Enable Ph-E PhPh
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZQDPDIS(21; Z<): 1 \ Zone 4 \ Setting Group1
Description
Fault resistance reach, Phase-Earth, zone 4
Fault resistance reach, Phase-Phase, zone 4
Positive sequence impedance reach for zone 4
Operation mode Off / On of zone timer, Phase-Earth of zone 4
Operation mode Off / On of zone timer, Phase-Phase of zone 4
Direction mode zone 4
Time delay to trip, Phase-Earth, zone 4
Name
RFPE4
RFPP4
Z4
OpModetPE4
OpModetPP4
DirMode4
tPE4
Value
3.75 ohm/l
3.75 ohm/l
2.300
On
On
Reverse
0.800 s
tPP4
OpMode4
0.800 s
Enable Ph-E PhPh
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZQDPDIS(21; Z<): 1 \ Zone 5 \ Setting Group1
Description
Fault resistance reach, Phase-Earth, zone 5
Fault resistance reach, Phase-Phase, zone 5
Positive sequence impedance reach for zone 5
Operation mode Off / On of zone timer, Phase-Earth of zone 5
Operation mode Off / On of zone timer, Phase-Phase of zone 5
Direction mode zone 5
Time delay to trip, Phase-Earth, zone 5
Time delay to trip, Phase-Phase, zone 5
Operation mode of zone 5
Name
RFPE5
RFPP5
Z5
OpModetPE5
OpModetPP5
DirMode5
tPE5
tPP5
OpMode5
Value
100.00 ohm/l
30.00 ohm/l
30.000
Off
Off
Forward
0.000 s
0.000 s
Enable Ph-E PhPh
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZMOPDIS(21; Z<): 1 \ General
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZMOPDIS(21; Z<): 1 \ General \ Setting Group1
Description
Operation Off/On
Line Angle
Minimum operate phase current for Phase-Earth loops
Minimum operate delta current for Phase-Phase loops
Reset Delay
Name
Operation
LineAng
IMinOpPE
IMinOpPP
ResetDelay
Value
Off
60 Deg
20 %IB
20 %IB
0.015 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZMOPDIS(21; Z<): 1 \ Zone 1 \ Setting Group1
Description
Name
Magnitude of earth return compensation factor KN for zone 1
KNMag1
Angle for earth return compensation factor KN for zone 1
KNAng1
Operation mode Off / On of zone timer, Phase-Earth for zone 1 OpModetPE1
Time delay to trip of Phase-Earth elements for zone 1
tPE1
Operation mode Off / On of zone timer, Phase-Phase for zone 1 OpModetPP1
Time delay to trip of Phase-Phase elements for zone 1
tPP1
Operation mode of zone 1
OpMode1
Reverse positive sequence impedance setting for zone 1
Z1Rev
Positive sequence impedance setting for zone 1
Z1
Direction mode zone 1
DirMode1
Direction mode for offset mho of zone 1
OffsetMhoDir1
Blinder mode Off/On of zone 1
BlinderMode1
Load enchroachment mode Off/On of zone 1
LoadEnchMode1
Value
0.00
0 Deg
On
0.000 s
On
0.000 s
enable PhG PhPh
1.000 ohm/p
7.000 ohm/p
Offset
Non-directional
Off
On
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZMOPDIS(21; Z<): 1 \ Zone 2 \ Setting Group1
Description
Name
Magnitude of earth return compensation factor KN for zones
KNMag2
2,3,4,5
Angle for earth return compensation factor KN for zones 2,3,4,5 KNAng2
Operation mode Off / On of zone timer, Phase-Earth for zone 2 OpModetPE2
Time delay to trip of Phase-Earth elements for zone 2
tPE2
Operation mode Off / On of zone timer, Phase-Phase for zone 2 OpModetPP2
Time delay to trip of Phase-Phase elements for zone 2
tPP2
Value
0.80
-15 Deg
On
0.000 s
On
0.000 s
OpMode2
Z2Rev
Z2
DirMode2
OffsetMhoDir2
BlinderMode2
LoadEnchMode2
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZMOPDIS(21; Z<): 1 \ Zone 3 \ Setting Group1
Description
Name
Operation mode Off / On of zone timer, Phase-Earth for zone 3 OpModetPE3
Time delay to trip of Phase-Earth elements for zone 3
tPE3
Operation mode Off / On of zone timer, Phase-Phase for zone 3 OpModetPP3
Time delay to trip of Phase-Phase elements for zone 3
tPP3
Operation mode of zone 3
OpMode3
Reverse positive sequence impedance setting for zone 3
Z3Rev
Positive sequence impedance setting for zone 3
Z3
Direction mode zone 3
DirMode3
Direction mode for offset mho of zone 3
OffsetMhoDir3
Blinder mode Off/On of zone 3
BlinderMode3
Load enchroachment mode Off/On of zone 3
LoadEnchMode3
Value
On
0.000 s
On
0.000 s
enable PhG PhPh
30.000 ohm/p
30.000 ohm/p
Forward
Non-directional
Off
Off
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZMOPDIS(21; Z<): 1 \ Zone 4 \ Setting Group1
Description
Name
Operation mode Off / On of zone timer, Phase-Earth for zone 4 OpModetPE4
Time delay to trip of Phase-Earth elements for zone 4
tPE4
Operation mode Off / On of zone timer, Phase-Phase for zone 4 OpModetPP4
Time delay to trip of Phase-Phase elements for zone 4
tPP4
Operation mode of zone 4
OpMode4
Reverse positive sequence impedance setting for zone 4
Z4Rev
Positive sequence impedance setting for zone 4
Z4
Direction mode zone 4
DirMode4
Direction mode for offset mho of zone 4
OffsetMhoDir4
Blinder mode Off/On of zone 4
BlinderMode4
Load enchroachment mode Off/On of zone 4
LoadEnchMode4
Value
On
0.000 s
On
0.000 s
enable PhG PhPh
30.000 ohm/p
30.000 ohm/p
Forward
Non-directional
Off
Off
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZMOPDIS(21; Z<): 1 \ Zone 5 \ Setting Group1
Description
Name
Operation mode Off / On of zone timer, Phase-Earth for zone 5 OpModetPE5
Time delay to trip of Phase-Earth elements for zone 5
tPE5
Operation mode Off / On of zone timer, Phase-Phase for zone 5 OpModetPP5
Time delay to trip of Phase-Phase elements for zone 5
tPP5
Operation mode of zone 5
OpMode5
Reverse positive sequence impedance setting for zone 5
Z1Rev
Positive sequence impedance setting for zone 5
Z5
Direction mode zone 5
DirMode5
Direction mode for offset mho of zone 5
OffsetMhoDir5
Blinder mode Off/On of zone 5
BlinderMode5
Load enchroachment mode Off/On of zone 5
LoadEnchMode5
Value
On
0.000 s
On
0.000 s
enable PhG PhPh
30.000 ohm/p
30.000 ohm/p
Forward
Non-directional
Off
Off
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Impedance \
ZMRPSB(68): 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
Name
Operation
X1InFw
R1LIn
R1FInFw
X1InRv
R1FInRv
OperationLdCh
RLdOutFw
ArgLd
RLdOutRv
kLdRFw
kLdRRv
tP1
tP2
tW
tH
tR1
tR2
IMinOpPE
Value
Off
30.00 ohm
30.00 ohm
30.00 ohm
30.00 ohm
30.00 ohm
On
30.00 ohm
25 Deg
30.00 ohm
0.75 Mult
0.75 Mult
0.045 s
0.015 s
0.250 s
30.000 s
0.300 s
30.000 s
10 %IB
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
LMBRFLO \ LMBRFLO: 1
Description
Recorder input number recording phase current, IL1
Recorder input number recording phase current, IL2
Recorder input number recording phase current, IL3
Recorder input number recording residual current, IN
Recorder input number recording 3I0 on parallel line
Recorder input number recording phase voltage, UL1
Recorder input number recording phase voltage, UL2
Recorder input number recording phase voltage, UL3
Name
DrepChNoIL1
DrepChNoIL2
DrepChNoIL3
DrepChNoIN
DrepChNoIP
DrepChNoUL1
DrepChNoUL2
DrepChNoUL3
Value
1 Ch
2 Ch
3 Ch
0 Ch
0 Ch
5 Ch
6 Ch
7 Ch
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
LMBRFLO \ LMBRFLO: 1 \ Setting Group1
Description
Source resistance A (near end)
Source reactance A (near end)
Source resistance B (far end)
Source reactance B (far end)
Positive sequence line resistance
Positive sequence line reactance
Zero sequence line resistance
Zero sequence line reactance
Zero sequence mutual resistance
Zero sequence mutual reactance
Length of line
Name
R1A
X1A
R1B
X1B
R1L
X1L
R0L
X0L
R0M
X0M
LineLength
Value
2.000 ohm/p
12.000 ohm/p
2.000 ohm/p
12.000 ohm/p
2.000 ohm/p
12.500 ohm/p
9.200 ohm/p
42.100 ohm/p
0.000 ohm/p
0.000 ohm/p
40.0
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \ SSCBR:
1
Description
Operation Off / On
Accumulation energy initial value
Operation numbers counter initialization value
Initial value for the CB remaining life estimates
Alarm limit value of the inactive days counter
Initial value of the inactive days counter
Alarm time of the inactive days counter in hours
RMS current setting below which energy accumulation stops
Current exponent setting for energy calculation
Name
Operation
AccEnerInitVal
CountInitVal
CBRemLife
InactDayAlm
InactDayInit
InactHourAlm
AccDisLevel
CurrExp
Value
Off
0.00
0
5000
2000 Day
0 Day
0 Hour
10.00 A
2.00
RatedFaultCurr
RatedOpCurr
AccCurrAlmLvl
AccCurrLO
DirCoef
LifeAlmLevel
OpNumRatCurr
OpNumFaultCurr
OpNumAlm
OpNumLO
tOpenAlm
tCloseAlm
OpenTimeCorr
CloseTimeCorr
DifTimeCorr
5000.00 A
1000.00 A
2500.00
2500.00
-1.50
5000
10000
1000
200
300
40 ms
40 ms
10 ms
10 ms
5 ms
tSprngChrgAlm
tPressAlm
TPressLO
1.00 s
0.10 s
0.10 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \ CMMXU:
1
Description
Operation Off / On
Selection of one of the Global Base Value groups
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Zero point clamping
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Maximum value
Reporting type
Hysteresis value in % of range and is common for all limits
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Amplitude factor to calibrate current at 5% of Ir
Amplitude factor to calibrate current at 30% of Ir
Amplitude factor to calibrate current at 100% of Ir
Angle calibration for current at 5% of Ir
Angle calibration for current at 30% of Ir
Angle calibration for current at 100% of Ir
Name
Operation
GlobalBaseSel
ILDbRepInt
ILZeroDb
ILHiHiLim
ILHiLim
ILLowLim
ILLowLowLim
ILMin
ILMax
ILRepTyp
ILLimHys
ILAngDbRepInt
IAmpComp5
IAmpComp30
IAmpComp100
IAngComp5
IAngComp30
IAngComp100
Value
On
1
10 Type
500 m%
1200 A
1100 A
0 A
0 A
0 A
1300 A
Dead band
5.000 %
10 Type
0.000 %
0.000 %
0.000 %
0.000 Deg
0.000 Deg
0.000 Deg
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \ CMSQI:
1
Description
Operation Off / On
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Zero point clamping
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Maximum value
Reporting type
Hysteresis value in % of range and is common for all limits
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Zero point clamping
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Name
Operation
3I0DbRepInt
3I0ZeroDb
3I0HiHiLim
3I0HiLim
3I0LowLim
3I0LowLowLim
3I0Min
3I0Max
3I0RepTyp
3I0LimHys
3I0AngDbRepInt
I1DbRepInt
I1ZeroDb
I1HiHiLim
I1HiLim
I1LowLim
I1LowLowLim
I1Min
Value
On
10 Type
500 m%
3600 A
3300 A
0 A
0 A
0 A
3300 A
Dead band
5.000 %
10 Type
10 Type
500 m%
1200 A
1100 A
0 A
0 A
0 A
Maximum value
Reporting type
Hysteresis value in % of range and is common for all limits
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Zero point clamping
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Maximum value
Reporting type
Hysteresis value in % of range and is common for all limits
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
I1Max
I1RepTyp
I1LimHys
I1AngDbRepInt
I2DbRepInt
I2ZeroDb
I2HiHiLim
I2HiLim
I2LowLim
I2LowLowLim
I2Min
I2Max
I2RepTyp
I2LimHys
I2AngDbRepInt
1300 A
Dead band
5.000 %
10 Type
10 Type
500 m%
1200 A
1100 A
0 A
0 A
0 A
1300 A
Dead band
5.000 %
10 Type
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
CVMMXN: 1 \ General
Description
Operation Off / On
Selection of one of the Global Base Value groups
Selection of measured current and voltage
Amplitude factor to scale power calculations
Angle compensation for phase shift between measured I & U
Low pass filter coefficient for power measurement
Name
Operation
GlobalBaseSel
Mode
PowAmpFact
PowAngComp
k
Value
On
1
L1, L2, L3
1.000
0.0 Deg
0.00
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
CVMMXN: 1 \ Apparent power S
Description
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Zero point clamping in 0,001% of range
High High limit in % of SBase
High limit in % of SBase
Low limit in % of SBase
Low Low limit in % of SBase
Minimum value in % of SBase
Maximum value in % of SBase
Reporting type
Hysteresis value in % of range (common for all limits)
Name
SDbRepInt
SZeroDb
SHiHiLim
SHiLim
SLowLim
SLowLowLim
SMin
SMax
SRepTyp
SLimHyst
Value
10 Type
500 m%
150.0 %SB
120.0 %SB
80.0 %SB
60.0 %SB
50.0 %SB
200.0 %SB
Cyclic
5.000 %
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
CVMMXN: 1 \ Active power P
Description
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Zero point clamping
High High limit in % of SBase
High limit in % of SBase
Low limit in % of SBase
Low Low limit in % of SBase
Minimum value in % of SBase
Maximum value in % of SBase
Reporting type
Hysteresis value in % of range (common for all limits)
Name
PDbRepInt
PZeroDb
PHiHiLim
PHiLim
PLowLim
PLowLowLim
PMin
PMax
PRepTyp
PLimHyst
Value
10 Type
500 m%
150.0 %SB
120.0 %SB
-120.0 %SB
-150.0 %SB
-200.0 %SB
200.0 %SB
Cyclic
5.000 %
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
CVMMXN: 1 \ Reactive power Q
Description
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Zero point clamping
High High limit in % of SBase
Name
QDbRepInt
QZeroDb
QHiHiLim
Value
10 Type
500 m%
150.0 %SB
QHiLim
QLowLim
QLowLowLim
QMin
QMax
QRepTyp
QLimHyst
120.0 %SB
-120.0 %SB
-150.0 %SB
-200.0 %SB
200.0 %SB
Cyclic
5.000 %
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
CVMMXN: 1 \ Power factor PF
Description
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Zero point clamping
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Maximum value
Reporting type
Hysteresis value in % of range (common for all limits)
Name
PFDbRepInt
PFZeroDb
PFHiHiLim
PFHiLim
PFLowLim
PFLowLowLim
PFMin
PFMax
PFRepTyp
PFLimHyst
Value
10 Type
500 m%
1.000
0.800
-0.800
-1.000
-1.000
1.000
Cyclic
5.000 %
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
CVMMXN: 1 \ Voltage U
Description
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Zero point clamping
High High limit in % of UBase
High limit in % of UBase
Low limit in % of UBase
Low Low limit in % of UBase
Minimum value in % of UBase
Maximum value in % of UBase
Reporting type
Hysteresis value in % of range (common for all limits)
Amplitude factor to calibrate voltage at 5% of Ur
Amplitude factor to calibrate voltage at 30% of Ur
Amplitude factor to calibrate voltage at 100% of Ur
Name
UDbRepInt
UZeroDb
UHiHiLim
UHiLim
ULowLim
ULowLowLim
UMin
UMax
URepTyp
ULimHyst
UAmpComp5
UAmpComp30
UAmpComp100
Value
10 Type
500 m%
150.0 %UB
120.0 %UB
80.0 %UB
60.0 %UB
50.0 %UB
200.0 %UB
Cyclic
5.000 %
0.000 %
0.000 %
0.000 %
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
CVMMXN: 1 \ Current I
Description
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Zero point clamping
High High limit in % of IBase
High limit in % of IBase
Low limit in % of IBase
Low Low limit in % of IBase
Minimum value in % of IBase
Maximum value in % of IBase
Reporting type
Hysteresis value in % of range (common for all limits)
Amplitude factor to calibrate current at 5% of Ir
Amplitude factor to calibrate current at 30% of Ir
Amplitude factor to calibrate current at 100% of Ir
Angle calibration for current at 5% of Ir
Angle calibration for current at 30% of Ir
Angle calibration for current at 100% of Ir
Name
IDbRepInt
IZeroDb
IHiHiLim
IHiLim
ILowLim
ILowLowLim
IMin
IMax
IRepTyp
ILimHyst
IAmpComp5
IAmpComp30
IAmpComp100
IAngComp5
IAngComp30
IAngComp100
Value
10 Type
500 m%
150.0 %IB
120.0 %IB
80.0 %IB
60.0 %IB
50.0 %IB
200.0 %IB
Cyclic
5.000 %
0.000 %
0.000 %
0.000 %
0.000 Deg
0.000 Deg
0.000 Deg
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
CVMMXN: 1 \ Frequency Fr
Description
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Zero point clamping
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Maximum value
Reporting type
Hysteresis value in % of range (common for all limits)
Name
FrDbRepInt
FrZeroDb
FrHiHiLim
FrHiLim
FrLowLim
FrLowLowLim
FrMin
FrMax
FrRepTyp
FrLimHyst
Value
10 Type
500 m%
65.000 Hz
63.000 Hz
47.000 Hz
45.000 Hz
0.000 Hz
70.000 Hz
Cyclic
5.000 %
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \ VMMXU:
1
Description
Operation Off / On
Selection of one of the Global Base Value groups
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Zero point clamping
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Maximum value
Reporting type
Hysteresis value in % of range and is common for all limits
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Name
Operation
GlobalBaseSel
ULDbRepInt
ULZeroDb
ULHiHiLim
ULHiLim
ULLowLim
ULLowLowLim
ULMin
ULMax
ULRepTyp
ULLimHys
ULAngDbRepInt
Value
On
1
10 Type
500 m%
160000 V
150000 V
125000 V
115000 V
0 V
170000 V
Dead band
5.000 V
10 Type
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \ VMSQI:
1
Description
Operation Off / On
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Zero point clamping
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Maximum value
Reporting type
Hysteresis value in % of range and is common for all limits
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Zero point clamping
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Maximum value
Reporting type
Hysteresis value in % of range and is common for all limits
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Zero point clamping
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Maximum value
Name
Operation
3U0DbRepInt
3U0ZeroDb
3U0HiHiLim
3U0HiLim
3U0LowLim
3U0LowLowLim
3U0Min
3U0Max
3U0RepTyp
3U0LimHys
3U0AngDbRepInt
U1DbRepInt
U1ZeroDb
U1HiHiLim
U1HiLim
U1LowLim
U1LowLowLim
U1Min
U1Max
U1RepTyp
U1LimHys
U1AngDbRepInt
U2DbRepInt
U2ZeroDb
U2HiHiLim
U2HiLim
U2LowLim
U2LowLowLim
U2Min
U2Max
Value
On
10 Type
500 m%
288000 V
258000 V
213000 V
198000 V
0 V
318000 V
Dead band
5.000 %
10 Type
10 Type
500 m%
96000 V
86000 V
71000 V
66000 V
0 V
106000 V
Dead band
5.000 %
10 Type
10 Type
500 m%
96000 V
86000 V
71000 V
66000 V
0 V
106000 V
Reporting type
Hysteresis value in % of range and is common for all limits
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
U2RepTyp
U2LimHys
U2AngDbRepInt
Dead band
5.000 %
10 Type
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
VNMMXU: 1
Description
Operation Mode On / Off
Selection of one of the Global Base Value groups
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Zero point clamping in 0,001% of range
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Maximum value
Reporting type
Hysteresis value in % of range and is common for all limits
Cycl: Report interval (s), Db: In % of range, Int Db: In %s
Name
Operation
GlobalBaseSel
UDbRepInt
UZeroDb
UHiHiLim
UHiLim
ULowLim
ULowLowLim
UMin
UMax
URepTyp
ULimHys
UAngDbRepInt
Value
On
1
10 Type
500 m%
96000 V
86000 V
71000 V
66000 V
0 V
106000 V
Dead band
5.000 V
10 Type
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
Disturbance report \ A1RADR: 1 \ General
Description
User define string for analog input 1
Operation On/Off
Nominal value for analog channel 1
Use under level trigger for analog channel 1 (on) or not (off)
Under trigger level for analog channel 1 in % of signal
Use over level trigger for analog channel 1 (on) or not (off)
Over trigger level for analog channel 1 in % of signal
User define string for analog input 2
Operation On/Off
Nominal value for analog channel 2
Use under level trigger for analog channel 2 (on) or not (off)
Under trigger level for analog channel 2 in % of signal
Use over level trigger for analog channel 2 (on) or not (off)
Over trigger level for analog channel 2 in % of signal
User define string for analog input 3
Operation On/Off
Nominal value for analog channel 3
Use under level trigger for analog channel 3 (on) or not (off)
Under trigger level for analog channel 3 in % of signal
Use over level trigger for analog channel 3 (on) or not (off)
Overtrigger level for analog channel 3 in % of signal
User define string for analog input 4
Operation On/Off
Nominal value for analog channel 4
Use under level trigger for analog channel 4 (on) or not (off)
Under trigger level for analog channel 4 in % of signal
Use over level trigger for analog channel 4 (on) or not (off)
Over trigger level for analog channel 4 in % of signal
User define string for analog input 5
Operation On/Off
Nominal value for analog channel 5
Use under level trigger for analog channel 5 (on) or not (off)
Under trigger level for analog channel 5 in % of signal
Use over level trigger for analog channel 5 (on) or not (off)
Over trigger level for analog channel 5 in % of signal
User define string for analog input 6
Operation On/Off
Nominal value for analog channel 6
Use under level trigger for analog channel 6 (on) or not (off)
Under trigger level for analog channel 6 in % of signal
Use over level trigger for analog channel 6 (on) or not (off)
Name
NAME1
Operation01
NomValue01
UnderTrigOp01
UnderTrigLe01
OverTrigOp01
OverTrigLe01
NAME2
Operation02
NomValue02
UnderTrigOp02
UnderTrigLe02
OverTrigOp02
OverTrigLe02
NAME3
Operation03
NomValue03
UnderTrigOp03
UnderTrigLe03
OverTrigOp03
OverTrigLe03
NAME4
Operation04
NomValue04
UnderTrigOp04
UnderTrigLe04
OverTrigOp04
OverTrigLe04
NAME5
Operation05
NomValue05
UnderTrigOp05
UnderTrigLe05
OverTrigOp05
OverTrigLe05
NAME6
Operation06
NomValue06
UnderTrigOp06
UnderTrigLe06
OverTrigOp06
Value
LINE_IL1
On
0.0
Off
50 %
Off
200 %
LINE_IL2
On
0.0
Off
50 %
Off
200 %
LINE_IL3
On
0.0
Off
50 %
Off
200 %
LINE_IN
On
0.0
Off
50 %
Off
200 %
LINE_UL1
On
0.0
Off
50 %
Off
200 %
LINE_UL2
On
0.0
Off
50 %
Off
OverTrigLe06
NAME7
Operation07
NomValue07
UnderTrigOp07
UnderTrigLe07
OverTrigOp07
OverTrigLe07
NAME8
Operation08
NomValue08
UnderTrigOp08
UnderTrigLe08
OverTrigOp08
OverTrigLe08
NAME9
Operation09
NomValue09
UnderTrigOp09
UnderTrigLe09
OverTrigOp09
OverTrigLe09
NAME10
Operation10
NomValue10
UnderTrigOp10
UnderTrigLe10
OverTrigOp10
OverTrigLe10
200 %
LINE_UL3
On
0.0
Off
50 %
Off
200 %
LINE_UN
On
0.0
Off
50 %
Off
200 %
LINE_MUT_COMP
On
0.0
Off
50 %
Off
200 %
Not used
On
0.0
Off
50 %
Off
200 %
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
Disturbance report \ A1RADR: 1 \ IEC60870-5-103
Description
Function type for analog channel 1 (IEC-60870-5-103)
Information number for analog channel 1 (IEC-60870-5-103)
Function type for analog channel 2 (IEC-60870-5-103)
Information number for analog channel 2 (IEC-60870-5-103)
Function type for analog channel 3 (IEC-60870-5-103)
Information number for analog channel 3 (IEC-60870-5-103)
Function type for analog channel 4 (IEC-60870-5-103)
Information number for analog channel 4 (IEC-60870-5-103)
Function type for analog channel 5 (IEC-60870-5-103)
Information number for analog channel 5 (IEC-60870-5-103)
Function type for analog channel 6 (IEC-60870-5-103)
Information number for analog channel 6 (IEC-60870-5-103)
Function type for analog channel 7 (IEC-60870-5-103)
Information number for analog channel 7 (IEC-60870-5-103)
Function type for analog channel 8 (IEC-60870-5-103)
Information number for analog channel 8 (IEC-60870-5-103)
Function type for analog channel 9 (IEC-60870-5-103)
Information number for analog channel 9 (IEC-60870-5-103)
Function type for analog channel 10 (IEC-60870-5-103)
Information number for analog channel10 (IEC-60870-5-103)
Name
FunType1
InfNo1
FunType2
InfNo2
FunType3
InfNo3
FunType4
InfNo4
FunType5
InfNo5
FunType6
InfNo6
FunType7
InfNo7
FunType8
InfNo8
FunType9
InfNo9
FunType10
InfNo10
Value
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
Disturbance report \ B1RBDR: 1 \ General
Description
User define string for binary input 1
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 1
Indication mask for binary channel 1
Set LED on HMI for binary channel 1
User define string for binary input 2
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 2
Name
NAME1
TrigDR01
TrigLevel01
IndicationMa01
SetLED01
NAME2
TrigDR02
TrigLevel02
Value
TRIP
On
Trig on 1
Show
Trip
Not used
Off
Trig on 1
IndicationMa02
SetLED02
NAME3
TrigDR03
TrigLevel03
IndicationMa03
SetLED03
NAME4
TrigDR04
TrigLevel04
IndicationMa04
SetLED04
NAME5
TrigDR05
TrigLevel05
IndicationMa05
SetLED05
NAME6
TrigDR06
TrigLevel06
IndicationMa06
SetLED06
NAME7
TrigDR07
TrigLevel07
IndicationMa07
SetLED07
NAME8
TrigDR08
TrigLevel08
IndicationMa08
SetLED08
NAME9
TrigDR09
TrigLevel09
IndicationMa09
SetLED09
NAME10
TrigDR10
TrigLevel10
IndicationMa10
SetLED10
NAME11
TrigDR11
TrigLevel11
IndicationMa11
SetLED11
NAME12
TrigDR12
TrigLevel12
IndicationMa12
SetLED12
NAME13
TrigDR13
TrigLevel13
IndicationMa13
SetLED13
NAME14
TrigDR14
TrigLevel14
IndicationMa14
SetLED14
NAME15
TrigDR15
TrigLevel15
IndicationMa15
SetLED15
NAME16
TrigDR16
TrigLevel16
Hide
Off
Not used
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
TRIP_Z1
Off
Trig on 1
Hide
Off
START_Z1
Off
Trig on 1
Show
Off
TRIP_Z2
Off
Trig on 1
Hide
Off
START_Z2
Off
Trig on 1
Hide
Off
TRIP_Z3
Off
Trig on 1
Hide
Off
START_Z3
Off
Trig on 1
Hide
Off
TRIP_Z4
Off
Trig on 1
Hide
Off
START_Z4
Off
Trig on 1
Hide
Off
TRIP_Z5
Off
Trig on 1
Hide
Off
START_Z5
Off
Trig on 1
IndicationMa16
SetLED16
Hide
Off
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
Disturbance report \ B1RBDR: 1 \ IEC60870-5-103
Description
Function type for binary channel 1 (IEC -60870-5-103)
Information number for binary channel 1 (IEC -60870-5-103)
Function type for binary channel 2 (IEC -60870-5-103)
Information number for binary channel 2 (IEC -60870-5-103)
Function type for binary channel 3 (IEC -60870-5-103)
Information number for binary channel 3 (IEC -60870-5-103)
Function type for binary channel 4 (IEC -60870-5-103)
Information number for binary channel 4 (IEC -60870-5-103)
Function type for binary channel 5 (IEC -60870-5-103)
Information number for binary channel 5 (IEC -60870-5-103)
Function type for binary channel 6 (IEC -60870-5-103)
Information number for binary channel 6 (IEC -60870-5-103)
Function type for binary channel 7 (IEC -60870-5-103)
Information number for binary channel 7 (IEC -60870-5-103)
Function type for binary channel 8 (IEC -60870-5-103)
Information number for binary channel 8 (IEC -60870-5-103)
Function type for binary channel 9 (IEC -60870-5-103)
Information number for binary channel 9 (IEC -60870-5-103)
Function type for binary channel 10 (IEC -60870-5-103)
Information number for binary channel 10 (IEC -60870-5-103)
Function type for binary channel 11 (IEC -60870-5-103)
Information number for binary channel 11 (IEC -60870-5-103)
Function type for binary channel 12 (IEC -60870-5-103)
Information number for binary channel 12 (IEC -60870-5-103)
Function type for binary channel 13 (IEC -60870-5-103)
Information number for binary channel 13 (IEC -60870-5-103)
Function type for binary channel 14 (IEC -60870-5-103)
Information number for binary channel 14 (IEC -60870-5-103)
Function type for binary channel 15 (IEC -60870-5-103)
Information number for binary channel 15 (IEC -60870-5-103)
Function type for binary channel 16 (IEC -60870-5-103)
Information number for binary channel 16 (IEC -60870-5-103)
Name
FunType1
InfNo1
FunType2
InfNo2
FunType3
InfNo3
FunType4
InfNo4
FunType5
InfNo5
FunType6
InfNo6
FunType7
InfNo7
FunType8
InfNo8
FunType9
InfNo9
FunType10
InfNo10
FunType11
InfNo11
FunType12
InfNo12
FunType13
InfNo13
FunType14
InfNo14
FunType15
InfNo15
FunType16
InfNo16
Value
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
Disturbance report \ B2RBDR: 1 \ General
Description
User define string for binary input 17
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 17
Indication mask for binary channel 17
Set LED on HMI for binary channel 17
User define string for binary input 18
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 18
Indication mask for binary channel 18
Set LED on HMI for binary channel 18
User define string for binary input 19
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 19
Indication mask for binary channel 19
Set LED on HMI for binary channel 19
User define string for binary input 20
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 20
Indication mask for binary channel 20
Set LED on HMI for binary channel 20
User define string for binary input 21
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 21
Name
NAME17
TrigDR17
TrigLevel17
IndicationMa17
SetLED17
NAME18
TrigDR18
TrigLevel18
IndicationMa18
SetLED18
NAME19
TrigDR19
TrigLevel19
IndicationMa19
SetLED19
NAME20
TrigDR20
TrigLevel20
IndicationMa20
SetLED20
NAME21
TrigDR21
TrigLevel21
Value
SOTF-TRIP
Off
Trig on 1
Hide
Off
ZCOM-TRIP
Off
Trig on 1
Hide
Off
BI_ZCOM-CR
Off
Trig on 1
Hide
Off
ZCAL-TRWEI
Off
Trig on 1
Hide
Off
ZCAL-IREV
Off
Trig on 1
IndicationMa21
SetLED21
NAME22
TrigDR22
TrigLevel22
IndicationMa22
SetLED22
NAME23
TrigDR23
TrigLevel23
IndicationMa23
SetLED23
NAME24
TrigDR24
TrigLevel24
IndicationMa24
SetLED24
NAME25
TrigDR25
TrigLevel25
IndicationMa25
SetLED25
NAME26
TrigDR26
TrigLevel26
IndicationMa26
SetLED26
NAME27
TrigDR27
TrigLevel27
IndicationMa27
SetLED27
NAME28
TrigDR28
TrigLevel28
IndicationMa28
SetLED28
NAME29
TrigDR29
TrigLevel29
IndicationMa29
SetLED29
NAME30
TrigDR30
TrigLevel30
IndicationMa30
SetLED30
NAME31
TrigDR31
TrigLevel31
IndicationMa31
SetLED31
NAME32
TrigDR32
TrigLevel32
IndicationMa32
SetLED32
Hide
Off
ZCAL-ECHO
Off
Trig on 1
Hide
Off
PHS-STFWL1
Off
Trig on 1
Hide
Off
PHS-STFWL2
Off
Trig on 1
Hide
Off
PHS-STFWL3
Off
Trig on 1
Hide
Off
PHS-STFWPE
Off
Trig on 1
Hide
Off
PSB-START
Off
Trig on 1
Hide
Off
IEF-TRIP
Off
Trig on 1
Hide
Off
IOC-TRIP
Off
Trig on 1
Hide
Off
BI_LINE-DTTR
Off
Trig on 1
Hide
Off
STB-TRIP
Off
Trig on 1
Hide
Off
FF-BLKU
Off
Trig on 1
Hide
Off
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
Disturbance report \ B2RBDR: 1 \ IEC60870-5-103
Description
Function type for binary channel 17 (IEC -60870-5-103)
Information number for binary channel 17 (IEC -60870-5-103)
Function type for binary channel 18 (IEC -60870-5-103)
Information number for binary channel 18 (IEC -60870-5-103)
Function type for binary channel 19 (IEC -60870-5-103)
Information number for binary channel 19 (IEC -60870-5-103)
Name
FunType17
InfNo17
FunType18
InfNo18
FunType19
InfNo19
Value
0
0
0
0
0
0
FunType20
InfNo20
FunType21
InfNo21
FunType22
InfNo22
FunType23
InfNo23
FunType24
InfNo24
FunType25
InfNo25
FunType26
InfNo26
FunType27
InfNo27
FunType28
InfNo28
FunType29
InfNo29
FunType30
InfNo30
FunType31
InfNo31
FunType32
InfNo32
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
Disturbance report \ B3RBDR: 1 \ General
Description
User define string for binary input 33
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 33
Indication mask for binary channel 33
Set LED on HMI for binary channel 33
User define string for binary input 34
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 34
Indication mask for binary channel 34
Set LED on HMI for binary channel 34
User define string for binary input 35
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 35
Indication mask for binary channel 35
Set LED on HMI for binary channel 35
User define string for binary input 36
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 36
Indication mask for binary channel 36
Set LED on HMI for binary channel 36
User define string for binary input 37
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 37
Indication mask for binary channel 37
Set LED on HMI for binary channel 37
User define string for binary input 38
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 38
Indication mask for binary channel 38
Set LED on HMI for binary channel 38
User define string for binary input 39
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 39
Indication mask for binary channel 39
Set LED on HMI for binary channel 39
User define string for binary input 40
Trigger operation On/Off
Name
NAME33
TrigDR33
TrigLevel33
IndicationMa33
SetLED33
NAME34
TrigDR34
TrigLevel34
IndicationMa34
SetLED34
NAME35
TrigDR35
TrigLevel35
IndicationMa35
SetLED35
NAME36
TrigDR36
TrigLevel36
IndicationMa36
SetLED36
NAME37
TrigDR37
TrigLevel37
IndicationMa37
SetLED37
NAME38
TrigDR38
TrigLevel38
IndicationMa38
SetLED38
NAME39
TrigDR39
TrigLevel39
IndicationMa39
SetLED39
NAME40
TrigDR40
Value
BI_EXT_TR_3PH
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
BFP-TRBU
Off
Trig on 1
Hide
Off
BFP-TRRET
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
SDE-TRIP
Off
TrigLevel40
IndicationMa40
SetLED40
NAME41
TrigDR41
TrigLevel41
IndicationMa41
SetLED41
NAME42
TrigDR42
TrigLevel42
IndicationMa42
SetLED42
NAME43
TrigDR43
TrigLevel43
IndicationMa43
SetLED43
NAME44
TrigDR44
TrigLevel44
IndicationMa44
SetLED44
NAME45
TrigDR45
TrigLevel45
IndicationMa45
SetLED45
NAME46
TrigDR46
TrigLevel46
IndicationMa46
SetLED46
NAME47
TrigDR47
TrigLevel47
IndicationMa47
SetLED47
NAME48
TrigDR48
TrigLevel48
IndicationMa48
SetLED48
Trig on 1
Hide
Off
SDE-START
Off
Trig on 1
Hide
Off
SDE-STFW
Off
Trig on 1
Hide
Off
SDE-STRV
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
BI_CB_CLOSED
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
TESTMODE_ACTV
Off
Trig on 1
Hide
Off
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
Disturbance report \ B3RBDR: 1 \ IEC60870-5-103
Description
Function type for binary channel 33 (IEC -60870-5-103)
Information number for binary channel 33 (IEC -60870-5-103)
Function type for binary channel 34 (IEC -60870-5-103)
Information number for binary channel 34 (IEC -60870-5-103)
Function type for binary channel 35 (IEC -60870-5-103)
Information number for binary channel 35 (IEC -60870-5-103)
Function type for binary channel 36 (IEC -60870-5-103)
Information number for binary channel 36 (IEC -60870-5-103)
Function type for binary channel 37 (IEC -60870-5-103)
Information number for binary channel 37 (IEC -60870-5-103)
Function type for binary channel 38 (IEC -60870-5-103)
Information number for binary channel 38 (IEC -60870-5-103)
Function type for binary channel 39 (IEC -60870-5-103)
Information number for binary channel 39 (IEC -60870-5-103)
Function type for binary channel 40 (IEC -60870-5-103)
Information number for binary channel 40 (IEC -60870-5-103)
Function type for binary channel 41 (IEC -60870-5-103)
Information number for binary channel 41 (IEC -60870-5-103)
Function type for binary channel 42 (IEC -60870-5-103)
Information number for binary channel 42 (IEC -60870-5-103)
Name
FunType33
InfNo33
FunType34
InfNo34
FunType35
InfNo35
FunType36
InfNo36
FunType37
InfNo37
FunType38
InfNo38
FunType39
InfNo39
FunType40
InfNo40
FunType41
InfNo41
FunType42
InfNo42
Value
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
FunType43
InfNo43
FunType44
InfNo44
FunType45
InfNo45
FunType46
InfNo46
FunType47
InfNo47
FunType48
InfNo48
0
0
0
0
0
0
0
0
0
0
0
0
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
Disturbance report \ B4RBDR: 1 \ General
Description
User define string for binary input 49
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 49
Indication mask for binary channel 49
Set LED on HMI for binary channel 49
User define string for binary input 50
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 50
Indication mask for binary channel 50
Set LED on HMI for binary channel 50
User define string for binary input 51
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 51
Indication mask for binary channel 51
Set LED on HMI for binary channel 51
User define string for binary input 52
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 52
Indication mask for binary channel 52
Set LED on HMI for binary channel 52
User define string for binary input 53
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 53
Indication mask for binary channel 53
Set LED on HMI for binary channel 53
User define string for binary input 54
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 54
Indication mask for binary channel 54
Set LED on HMI for binary channel 54
User define string for binary input 55
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 55
Indication mask for binary channel 55
Set LED on HMI for binary channel 55
User define string for binary input 56
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 56
Indication mask for binary channel 56
Set LED on HMI for binary channel 56
User define string for binary input 57
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 57
Indication mask for binary channel 57
Set LED on HMI for binary channel 57
User define string for binary input 58
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 58
Indication mask for binary channel 58
Set LED on HMI for binary channel 58
User define string for binary input 59
Name
NAME49
TrigDR49
TrigLevel49
IndicationMa49
SetLED49
NAME50
TrigDR50
TrigLevel50
IndicationMa50
SetLED50
NAME51
TrigDR51
TrigLevel51
IndicationMa51
SetLED51
NAME52
TrigDR52
TrigLevel52
IndicationMa52
SetLED52
NAME53
TrigDR53
TrigLevel53
IndicationMa53
SetLED53
NAME54
TrigDR54
TrigLevel54
IndicationMa54
SetLED54
NAME55
TrigDR55
TrigLevel55
IndicationMa55
SetLED55
NAME56
TrigDR56
TrigLevel56
IndicationMa56
SetLED56
NAME57
TrigDR57
TrigLevel57
IndicationMa57
SetLED57
NAME58
TrigDR58
TrigLevel58
IndicationMa58
SetLED58
NAME59
Value
AR-CLOSECB
Off
Trig on 1
Hide
Off
CBREADY
Off
Trig on 1
Hide
Off
AR-UNSUCC
Off
Trig on 1
Hide
Off
AR-INPROGRESS
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
BI_START_AR
Off
Trig on 1
Hide
Off
BI_INHIBIT_AR
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
Not used
TrigDR59
TrigLevel59
IndicationMa59
SetLED59
NAME60
TrigDR60
TrigLevel60
IndicationMa60
SetLED60
NAME61
TrigDR61
TrigLevel61
IndicationMa61
SetLED61
NAME62
TrigDR62
TrigLevel62
IndicationMa62
SetLED62
NAME63
TrigDR63
TrigLevel63
IndicationMa63
SetLED63
NAME64
TrigDR64
TrigLevel64
IndicationMa64
SetLED64
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
Disturbance report \ B4RBDR: 1 \ IEC60870-5-103
Description
Function type for binary channel 49 (IEC -60870-5-103)
Information number for binary channel 49 (IEC -60870-5-103)
Function type for binary channel 50 (IEC -60870-5-103)
Information number for binary channel 50 (IEC -60870-5-103)
Function type for binary channel 51 (IEC -60870-5-103)
Information number for binary channel 51 (IEC -60870-5-103)
Function type for binary channel 52 (IEC -60870-5-103)
Information number for binary channel 52 (IEC -60870-5-103)
Function type for binary channel 53 (IEC -60870-5-103)
Information number for binary channel 53 (IEC -60870-5-103)
Function type for binary channel 54 (IEC -60870-5-103)
Information number for binary channel 54 (IEC -60870-5-103)
Function type for binary channel 55 (IEC -60870-5-103)
Information number for binary channel 55 (IEC -60870-5-103)
Function type for binary channel 56 (IEC -60870-5-103)
Information number for binary channel 56 (IEC -60870-5-103)
Function type for binary channel 57 (IEC -60870-5-103)
Information number for binary channel 57 (IEC -60870-5-103)
Function type for binary channel 58 (IEC -60870-5-103)
Information number for binary channel 58 (IEC -60870-5-103)
Function type for binary channel 59 (IEC -60870-5-103)
Information number for binary channel 59 (IEC -60870-5-103)
Function type for binary channel 60 (IEC -60870-5-103)
Information number for binary channel 60 (IEC -60870-5-103)
Function type for binary channel 61 (IEC -60870-5-103)
Information number for binary channel 61 (IEC -60870-5-103)
Function type for binary channel 62 (IEC -60870-5-103)
Information number for binary channel 62 (IEC -60870-5-103)
Function type for binary channel 63 (IEC -60870-5-103)
Information number for binary channel 63 (IEC -60870-5-103)
Function type for binary channel 64 (IEC -60870-5-103)
Information number for binary channel 64 (IEC -60870-5-103)
Name
FunType49
InfNo49
FunType50
InfNo50
FunType51
InfNo51
FunType52
InfNo52
FunType53
InfNo53
FunType54
InfNo54
FunType55
InfNo55
FunType56
InfNo56
FunType57
InfNo57
FunType58
InfNo58
FunType59
InfNo59
FunType60
InfNo60
FunType61
InfNo61
FunType62
InfNo62
FunType63
InfNo63
FunType64
InfNo64
Value
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Name
NAME65
TrigDR65
TrigLevel65
IndicationMa65
SetLED65
NAME66
TrigDR66
TrigLevel66
IndicationMa66
SetLED66
NAME67
TrigDR67
TrigLevel67
IndicationMa67
SetLED67
NAME68
TrigDR68
TrigLevel68
IndicationMa68
SetLED68
NAME69
TrigDR69
TrigLevel69
IndicationMa69
SetLED69
NAME70
TrigDR70
TrigLevel70
IndicationMa70
SetLED70
NAME71
TrigDR71
TrigLevel71
IndicationMa71
SetLED71
NAME72
TrigDR72
TrigLevel72
IndicationMa72
SetLED72
NAME73
TrigDR73
TrigLevel73
IndicationMa73
SetLED73
NAME74
TrigDR74
TrigLevel74
IndicationMa74
SetLED74
NAME75
TrigDR75
TrigLevel75
IndicationMa75
SetLED75
NAME76
TrigDR76
TrigLevel76
IndicationMa76
SetLED76
NAME77
TrigDR77
TrigLevel77
IndicationMa77
SetLED77
NAME78
Value
TEF-TRIP
Off
Trig on 1
Hide
Off
TEF-START
Off
Trig on 1
Hide
Off
TEF-STFW
Off
Trig on 1
Hide
Off
TEF-STRV
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
EFC-TRIP
Off
Trig on 1
Hide
Off
BI_EFC_CR
Off
Trig on 1
Hide
Off
EFCA-TRWEI
Off
Trig on 1
Hide
Off
EFCA-IRVL
Off
Trig on 1
Hide
Off
EFCA-ECHO
Off
Trig on 1
Hide
Off
TUV-TRIP
Off
Trig on 1
Hide
Off
TUV-START
Off
Trig on 1
Hide
Off
TOV-TRIP
Off
Trig on 1
Hide
Off
TOV-START
TrigDR78
TrigLevel78
IndicationMa78
SetLED78
NAME79
TrigDR79
TrigLevel79
IndicationMa79
SetLED79
NAME80
TrigDR80
TrigLevel80
IndicationMa80
SetLED80
Off
Trig on 1
Hide
Off
PDOP-TRIP
Off
Trig on 1
Hide
Off
PDUP-TRIP
Off
Trig on 1
Hide
Off
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
Disturbance report \ B5RBDR: 1 \ IEC60870-5-103
Description
Function type for binary channel 65 (IEC -60870-5-103)
Information number for binary channel 65 (IEC -60870-5-103)
Function type for binary channel 66 (IEC -60870-5-103)
Information number for binary channel 66 (IEC -60870-5-103)
Function type for binary channel 67 (IEC -60870-5-103)
Information number for binary channel 67 (IEC -60870-5-103)
Function type for binary channel 68 (IEC -60870-5-103)
Information number for binary channel 68 (IEC -60870-5-103)
Function type for binary channel 69 (IEC -60870-5-103)
Information number for binary channel 69 (IEC -60870-5-103)
Function type for binary channel 70 (IEC -60870-5-103)
Information number for binary channel 70 (IEC -60870-5-103)
Function type for binary channel 71 (IEC -60870-5-103)
Information number for binary channel 71 (IEC -60870-5-103)
Function type for binary channel 72 (IEC -60870-5-103)
Information number for binary channel 72 (IEC -60870-5-103)
Function type for binary channel 73 (IEC -60870-5-103)
Information number for binary channel 73 (IEC -60870-5-103)
Function type for binary channel 74 (IEC -60870-5-103)
Information number for binary channel 74 (IEC -60870-5-103)
Function type for binary channel 75 (IEC -60870-5-103)
Information number for binary channel 75 (IEC -60870-5-103)
Function type for binary channel 76 (IEC -60870-5-103)
Information number for binary channel 76 (IEC -60870-5-103)
Function type for binary channel 77 (IEC -60870-5-103)
Information number for binary channel 77 (IEC -60870-5-103)
Function type for binary channel 78 (IEC -60870-5-103)
Information number for binary channel 78 (IEC -60870-5-103)
Function type for binary channel 79 (IEC -60870-5-103)
Information number for binary channel 79 (IEC -60870-5-103)
Function type for binary channel 80 (IEC -60870-5-103)
Information number for binary channel 80 (IEC -60870-5-103)
Name
FunType65
InfNo65
FunType66
InfNo66
FunType67
InfNo67
FunType68
InfNo68
FunType69
InfNo69
FunType70
InfNo70
FunType71
InfNo71
FunType72
InfNo72
FunType73
InfNo73
FunType74
InfNo74
FunType75
InfNo75
FunType76
InfNo76
FunType77
InfNo77
FunType78
InfNo78
FunType79
InfNo79
FunType80
InfNo80
Value
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
Disturbance report \ B6RBDR: 1 \ General
Description
User define string for binary input 81
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 81
Indication mask for binary channel 81
Set LED on HMI for binary channel 81
User define string for binary input 82
Trigger operation On/Off
Trigger on positive (1) or negative (0) slope for binary input 82
Indication mask for binary channel 82
Set LED on HMI for binary channel 82
User define string for binary input 83
Name
NAME81
TrigDR81
TrigLevel81
IndicationMa81
SetLED81
NAME82
TrigDR82
TrigLevel82
IndicationMa82
SetLED82
NAME83
Value
TOC-TRIP
Off
Trig on 1
Hide
Off
TOC-START
Off
Trig on 1
Hide
Off
THL-TRIP
TrigDR83
TrigLevel83
IndicationMa83
SetLED83
NAME84
TrigDR84
TrigLevel84
IndicationMa84
SetLED84
NAME85
TrigDR85
TrigLevel85
IndicationMa85
SetLED85
NAME86
TrigDR86
TrigLevel86
IndicationMa86
SetLED86
NAME87
TrigDR87
TrigLevel87
IndicationMa87
SetLED87
NAME88
TrigDR88
TrigLevel88
IndicationMa88
SetLED88
NAME89
TrigDR89
TrigLevel89
IndicationMa89
SetLED89
NAME90
TrigDR90
TrigLevel90
IndicationMa90
SetLED90
NAME91
TrigDR91
TrigLevel91
IndicationMa91
SetLED91
NAME92
TrigDR92
TrigLevel92
IndicationMa92
SetLED92
NAME93
TrigDR93
TrigLevel93
IndicationMa93
SetLED93
NAME94
TrigDR94
TrigLevel94
IndicationMa94
SetLED94
NAME95
TrigDR95
TrigLevel95
IndicationMa95
SetLED95
NAME96
TrigDR96
TrigLevel96
IndicationMa96
SetLED96
Off
Trig on 1
Hide
Off
THL-START
Off
Trig on 1
Hide
Off
THL-ALARM
Off
Trig on 1
Hide
Off
BRC-TRIP
Off
Trig on 1
Hide
Off
BRC-ALARM
Off
Trig on 1
Hide
Off
LOV-TRIP
Off
Trig on 1
Hide
Off
LOV-START
Off
Trig on 1
Hide
Off
PHS-TRIP
Off
Trig on 1
Hide
Off
PHS-START
Off
Trig on 1
Hide
Off
BI_QB9_OPEN
Off
Trig on 1
Hide
Off
TCS_ALARM
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
Not used
Off
Trig on 1
Hide
Off
REC START
Off
Trig on 1
Hide
Start
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
Disturbance report \ B6RBDR: 1 \ IEC60870-5-103
Description
Function type for binary channel 81 (IEC -60870-5-103)
Information number for binary channel 81 (IEC -60870-5-103)
Function type for binary channel 82 (IEC -60870-5-103)
Information number for binary channel 82 (IEC -60870-5-103)
Function type for binary channel 83 (IEC -60870-5-103)
Information number for binary channel 83 (IEC -60870-5-103)
Function type for binary channel 84 (IEC -60870-5-103)
Information number for binary channel 84 (IEC -60870-5-103)
Function type for binary channel 85 (IEC -60870-5-103)
Information number for binary channel 85 (IEC -60870-5-103)
Function type for binary channel 86 (IEC -60870-5-103)
Information number for binary channel 86 (IEC -60870-5-103)
Function type for binary channel 87 (IEC -60870-5-103)
Information number for binary channel 87 (IEC -60870-5-103)
Function type for binary channel 88 (IEC -60870-5-103)
Information number for binary channel 88 (IEC -60870-5-103)
Function type for binary channel 89 (IEC -60870-5-103)
Information number for binary channel 89 (IEC -60870-5-103)
Function type for binary channel 90 (IEC -60870-5-103)
Information number for binary channel 90 (IEC -60870-5-103)
Function type for binary channel 91 (IEC -60870-5-103)
Information number for binary channel 91 (IEC -60870-5-103)
Function type for binary channel 92 (IEC -60870-5-103)
Information number for binary channel 92 (IEC -60870-5-103)
Function type for binary channel 93 (IEC -60870-5-103)
Information number for binary channel 93 (IEC -60870-5-103)
Function type for binary channel 94 (IEC -60870-5-103)
Information number for binary channel 94 (IEC -60870-5-103)
Function type for binary channel 95 (IEC -60870-5-103)
Information number for binary channel 95 (IEC -60870-5-103)
Function type for binary channel 96 (IEC -60870-5-103)
Information number for binary channel 96 (IEC -60870-5-103)
Name
FunType81
InfNo81
FunType82
InfNo82
FunType83
InfNo83
FunType84
InfNo84
FunType85
InfNo85
FunType86
InfNo86
FunType87
InfNo87
FunType88
InfNo88
FunType89
InfNo89
FunType90
InfNo90
FunType91
InfNo91
FunType92
InfNo92
FunType93
InfNo93
FunType94
InfNo94
FunType95
InfNo95
FunType96
InfNo96
Value
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Monitoring \
SPVNZBAT(U<>): 1
Description
Operation mode Off / On
Battery rated voltage
Lower limit for the battery terminal voltage
Upper limit for the battery terminal voltage
Delay time for alarm
Time delay for reset of alarm
Name
Operation
RtdBattVolt
BattVoltLowLim
BattVoltHiLim
tDelay
tReset
Value
On
110.00 V
70 %Ubat
120 %Ubat
0.200 s
0.000 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Scheme
communication \ ZCPSCH(85): 1 \ Setting Group1
Description
Operation Off / On
Scheme type
Co-ordination time for blocking communication scheme
Minimum duration of a carrier send signal
Operation mode of unblocking logic
Security timer for loss of carrier guard detection
Name
Operation
SchemeType
tCoord
tSendMin
Unblock
tSecurity
Value
On
Permissive UR
0.035 s
0.100 s
Off
0.035 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Scheme
communication \ ZCRWPSCH(85): 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Scheme
communication \ ZCRWPSCH(85): 1 \ Setting Group1
Description
Operating mode of Current Reversal Logic
Pickup time for current reversal logic
Time Delay to prevent Carrier send and local trip
Operating mode of WEI logic
Coordination time for the WEI logic
Phase to Phase voltage for detection of fault condition
Phase to Neutral voltage for detection of fault condition
Name
CurrRev
tPickUpRev
tDelayRev
WEI
tPickUpWEI
UPP<
UPN<
Value
Off
0.020 s
0.060 s
Off
0.010 s
70 %UB
70 %UB
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Scheme
communication \ ECPSCH(85): 1 \ Setting Group1
Description
Operation Off / On
Scheme type, Mode of Operation
Communication scheme coordination time
Minimum duration of a carrier send signal
Operation mode of unblocking logic
Security timer for loss of carrier guard detection
Name
Operation
SchemeType
tCoord
tSendMin
Unblock
tSecurity
Value
Off
Permissive UR
0.035 s
0.100 s
Off
0.035 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Scheme
communication \ ECRWPSCH(85): 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Scheme
communication \ ECRWPSCH(85): 1 \ Setting Group1
Description
Operating mode of Current Reversal Logic
Pickup time for current reversal logic
Time Delay to prevent Carrier send and local trip
Operating mode of WEI logic
Coordination time for the WEI logic
Neutral voltage setting for fault conditions measurement
Name
CurrRev
tPickUpRev
tDelayRev
WEI
tPickUpWEI
3U0>
Value
Off
0.020 s
0.060 s
Off
0.000 s
25 %UB
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
BRCPTOC(46; Iub): 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
BRCPTOC(46; Iub): 1 \ Setting Group1
Description
Operation Off / On
Unbalance current operation value in percent of max current
Minimum phase current for operation of Iub> in % of Ibase
Operate time delay
Name
Operation
Iub>
IP>
tOper
Value
Off
50 %IM
20 %IB
5.000 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
EF4PTOC(51N_67N; 4IN>): 1 \ General
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
EF4PTOC(51N_67N; 4IN>): 1 \ General \ Setting Group1
Description
Operation Off / On
Relay characteristic angle (RCA)
Type of polarization
Minimum voltage level for polarization in % of UBase
Minimum current level for polarization in % of IBase
Real part of source Z to be used for current polarisation
Imaginary part of source Z to be used for current polarisation
Residual current level for direction release in % of IBase
Second harmonic restrain operation in % of IN amplitude
Name
Operation
AngleRCA
polMethod
UPolMin
IPolMin
RNPol
XNPol
IN>Dir
2ndHarmStab
Value
Off
65 Deg
Voltage
1 %UB
5 %IB
5.00 ohm
40.00 ohm
10 %IB
20 %
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
EF4PTOC(51N_67N; 4IN>): 1 \ Step 1 \ Setting Group1
Description
Directional mode of step 1 (off, non-directional, forward,
reverse)
Time delay curve type for step 1
Operate residual current level for step 1 in % of IBase
Independent (definite) time delay of step 1
Time multiplier for the dependent time delay for step 1
Minimum operate current for step1 in % of IBase
Minimum operate time for inverse curves for step 1
Enable block of step 1 from harmonic restrain
Name
DirMode1
Value
Non-directional
Characterist1
IN1>
t1
k1
IMin1
t1Min
HarmRestrain1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
EF4PTOC(51N_67N; 4IN>): 1 \ Step 2 \ Setting Group1
Description
Directional mode of step 2 (off, non-directional, forward,
reverse)
Operate residual current level for step 2 in % of IBase
Independent (definite) time delay of step 2
Minimum operate current for step 2 in % of IBase
Enable block of step 2 from harmonic restrain
Name
DirMode2
Value
Non-directional
IN2>
t2
IMin2
HarmRestrain2
50 %IB
0.400 s
50 %IB
On
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
EF4PTOC(51N_67N; 4IN>): 1 \ Step 3 \ Setting Group1
Description
Directional mode of step 3 (off, non-directional, forward,
reverse)
Operate residual current level for step 3 in % of IBase
Independent (definite) time delay of step 3
Minimum operate current for step 3 in % of IBase
Enable block of step 3 from harmonic restrain
Name
DirMode3
Value
Off
IN3>
t3
IMin3
HarmRestrain3
33 %IB
0.800 s
33 %IB
On
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
EF4PTOC(51N_67N; 4IN>): 1 \ Step 4 \ Setting Group1
Description
Directional mode of step 4 (off, non-directional, forward,
reverse)
Time delay curve type for step 4
Operate residual current level for step 4 in % of IBase
Independent (definite) time delay of step 4
Name
DirMode4
Value
Off
Characterist4
IN4>
t4
k4
IMin4
t4Min
HarmRestrain4
0.05
17 %IB
0.000 s
On
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
EFPIOC(50N; IN>>): 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
EFPIOC(50N; IN>>): 1 \ Setting Group1
Description
Operation Off / On
Operate residual current level in % of IBase
Name
Operation
IN>>
Value
Off
200 %IB
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
GOPPDOP(32; P>): 1 \ General
Description
Selection of one of the Global Base Value groups
Mode of measurement for current and voltage
Name
GlobalBaseSel
Mode
Value
1
Pos Seq
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
GOPPDOP(32; P>): 1 \ General \ Setting Group1
Description
Operation Off / On
Low pass filter coefficient for power measurement, U and I
Name
Operation
k
Value
Off
0.00
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
GOPPDOP(32; P>): 1 \ Step 1 \ Setting Group1
Description
Operation mode 1
Power setting for stage 1 in % of calculated power base value
Characteristic angle for stage 1
Trip delay for stage 1
Name
OpMode1
Power1
Angle1
TripDelay1
Value
OverPower
1.0 %
0.0 Deg
1.000 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
GOPPDOP(32; P>): 1 \ Step 2 \ Setting Group1
Description
Operation mode 2
Power setting for stage 2 in % of calculated power base value
Characteristic angle for stage 2
Trip delay for stage 2
Name
OpMode2
Power2
Angle2
TripDelay2
Value
OverPower
1.0 %
0.0 Deg
1.000 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
GUPPDUP(37; P<): 1 \ General
Description
Selection of one of the Global Base Value groups
Mode of measurement for current and voltage
Name
GlobalBaseSel
Mode
Value
1
Pos Seq
Name
Operation
k
Value
Off
0.00
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
GUPPDUP(37; P<): 1 \ Step 1 \ Setting Group1
Description
Operation mode 1
Power setting for stage 1 in % of calculated power base value
Characteristic angle for stage 1
Trip delay for stage 1
Name
OpMode1
Power1
Angle1
TripDelay1
Value
UnderPower
1.0 %
0.0 Deg
1.000 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
GUPPDUP(37; P<): 1 \ Step 2 \ Setting Group1
Description
Operation mode 2
Power setting for stage 2 in % of calculated power base value
Characteristic angle for stage 2
Trip delay for stage 2
Name
OpMode2
Power2
Angle2
TripDelay2
Value
UnderPower
1.0 %
0.0 Deg
1.000 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \ LPTTR(26;
>): 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \ LPTTR(26;
>): 1 \ Setting Group1
Description
Operation Off / On
End temperature rise above ambient of the line when loaded
with IRef
Load current in % of IBase leading to TRef temperature
Time constant of the line
Temperature level for start (alarm)
Temperature level for trip
Temperature for reset of lockout after trip
External temperature sensor available
Ambient temperature used when AmbiSens is set to Off
Temperature raise above ambient temperature at startup
Name
Operation
TRef
Value
Off
90 Deg
IRef
Tau
AlarmTemp
TripTemp
ReclTemp
AmbiSens
DefaultAmbTemp
DefaultTemp
100 %IB
45 Min
80 Deg
90 Deg
75 Deg
Off
20 Deg
50 Deg
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
OC4PTOC(51_67; 4I>): 1 \ General
Description
Selection of one of the Global Base Value groups
Selection between DFT and RMS measurement
Name
GlobalBaseSel
MeasType
Value
1
DFT
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
OC4PTOC(51_67; 4I>): 1 \ General \ Setting Group1
Description
Operation Off / On
Name
Operation
Value
Off
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
OC4PTOC(51_67; 4I>): 1 \ Step 1 \ Setting Group1
Description
Directional mode of step 1 off / non-directional / forward /
reverse
Selection of time delay curve type for step 1
Phase current operate level for step1 in % of IBase
Definite time delay of step 1
Time multiplier for the inverse time delay for step 1
Minimum operate current for step1 in % of IBase
Minimum operate time for inverse curves for step 1
Name
DirMode1
Value
Non-directional
Characterist1
I1>
t1
k1
IMin1
t1Min
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
OC4PTOC(51_67; 4I>): 1 \ Step 2 \ Setting Group1
Description
Directional mode of step 2 off / non-directional / forward /
reverse
Phase current operate level for step 2 in % of IBase
Definite time delay of step 2
Name
DirMode2
Value
Non-directional
I2>
t2
500 %IB
0.400 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
OC4PTOC(51_67; 4I>): 1 \ Step 3 \ Setting Group1
Description
Directional mode of step 3 off / non-directional / forward /
reverse
Phase current operate level for step3 in % of IBase
Definite time delay of step 3
Name
DirMode3
Value
Off
I3>
t3
250 %IB
0.800 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
OC4PTOC(51_67; 4I>): 1 \ Step 4 \ Setting Group1
Description
Directional mode of step 4 off / non-directional / forward /
reverse
Selection of time delay curve type for step 4
Phase current operate level for step 4 in % of IBase
Definite time delay of step 4
Time multiplier for the inverse time delay for step 4
Minimum operate current for step4 in % of IBase
Minimum operate time for inverse curves for step 4
Name
DirMode4
Value
Off
Characterist4
I4>
t4
k4
IMin4
t4Min
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
OC4SPTOC(51_67): 1 \ General
Description
Selection of one of the Global Base Value groups
Selection between DFT and RMS measurement
Name
GlobalBaseSel
MeasType
Value
1
DFT
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
OC4SPTOC(51_67): 1 \ General \ Setting Group1
Description
Operation Off / On
Name
Operation
Value
Off
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
OC4SPTOC(51_67): 1 \ Step 1 \ Setting Group1
Description
Directional mode of step 1 off / non-directional / forward /
reverse
Selection of time delay curve type for step 1
Phase current operate level for step1 in % of IBase
Definite time delay of step 1
Time multiplier for the inverse time delay for step 1
Minimum operate current for step1 in % of IBase
Minimum operate time for inverse curves for step 1
Name
DirMode1
Value
Off
Characterist1
I1>
t1
k1
IMin1
t1Min
RI type
130 %IB
0.000 s
0.60
140 %IB
0.000 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
OC4SPTOC(51_67): 1 \ Step 2 \ Setting Group1
Description
Directional mode of step 2 off / non-directional / forward /
reverse
Phase current operate level for step 2 in % of IBase
Definite time delay of step 2
Name
DirMode2
Value
Off
I2>
t2
190 %IB
1.100 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
OC4SPTOC(51_67): 1 \ Step 3 \ Setting Group1
Description
Directional mode of step 3 off / non-directional / forward /
reverse
Phase current operate level for step3 in % of IBase
Definite time delay of step 3
Name
DirMode3
Value
Off
I3>
t3
220 %IB
0.600 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
OC4SPTOC(51_67): 1 \ Step 4 \ Setting Group1
Description
Directional mode of step 4 off / non-directional / forward /
reverse
Selection of time delay curve type for step 4
Phase current operate level for step 4 in % of IBase
Definite time delay of step 4
Time multiplier for the inverse time delay for step 4
Minimum operate current for step4 in % of IBase
Minimum operate time for inverse curves for step 4
Name
DirMode4
Value
Non-directional
Characterist4
I4>
t4
k4
IMin4
t4Min
RI type
130 %IB
0.000 s
0.60
200 %IB
0.000 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \ PHPIOC(50;
I>>): 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \ PHPIOC(50;
I>>): 1 \ Setting Group1
Description
Operation Off / On
Operate phase current level in % of IBase
Name
Operation
IP>>
Value
Off
200 %IB
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
SPTPIOC(50): 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
4
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
SPTPIOC(50): 1 \ Setting Group1
Description
Operation Off / On
Operate phase current level in % of IBase
Name
Operation
IP>>
Value
Off
300 %IB
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
SDEPSDE(67N; IN<->): 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
SDEPSDE(67N; IN<->): 1 \ Setting Group1
Description
Operation Off / On
Selection of operation mode for protection
Direction of operation forward or reverse
Relay characteristic angle RCA
Relay characteristic angle compensation
Relay open angle ROA used as release in phase mode
Set level for 3I0cosPhi, directional residual overcurrent, in % of
IBase
Set level for 3I0U0cosPhi, starting inverse time count, in % of
SBase
Set level for directional residual overcurrent protection, in % of
IBase
Definite time delay directional residual overcurrent
Reference value of residual power for inverse time count, in %
of SBase
Time multiplier setting for directional residual power mode
Operation of non-directional residual overcurrent protection
Set level for non-directional residual overcurrent, in % of IBase
Time delay for non-directional residual overcurrent
Operation curve selection for IDMT operation
Minimum operate time for IEC IDMT curves
IDMT time multiplier for non-directional residual overcurrent
Operation of non-directional residual overvoltage
Set level for non-dir residual voltage, % of UBase
Time delay for non-directional residual overvoltage
Residual release current for all directional modes, in % of IBase
Residual release volt for all dir modes, % of UBase
Name
Operation
OpMode
DirMode
RCADir
RCAComp
ROADir
INCosPhi>
Value
Off
3I0Cosfi
Forward
-90 Deg
0.0 Deg
90 Deg
1.00 %IB
SN>
10.00 %SB
INDir>
5.00 %IB
tDef
SRef
0.100 s
10.00 %SB
kSN
OpINNonDir>
INNonDir>
tINNonDir
TimeChar
tMin
kIN
OpUN>
UN>
tUN
INRel>
UNRel>
0.10
Off
10.00 %IB
1.000 s
IEC Norm. inv.
0.040 s
1.00
Off
20.00 %UB
0.100 s
1.00 %IB
3.00 %UB
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
STBPTOC(50STB; I>): 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
STBPTOC(50STB; I>): 1 \ Setting Group1
Description
Operation Off / On
Operate current level in % of IBase
Name
Operation
I>
Value
Off
200 %IB
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
CCRBRF(50BF): 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
CCRBRF(50BF): 1 \ Setting Group1
Description
Operation Off / On
Detection principle for back-up trip
Back-up trip mode
Operation mode of re-trip logic
Operate phase current level in % of IBase
Current for blocking of CB contact operation in % of IBase
Operate residual current level in % of IBase
Time delay of re-trip
Time delay of back-up trip
Name
Operation
FunctionMode
BuTripMode
RetripMode
IP>
I>BlkCont
IN>
t1
t2
Value
Off
Current
1 out of 3
Retrip Off
10 %IB
20 %IB
10 %IB
0.000 s
0.150 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
CSPRBRF(50BF): 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
CSPRBRF(50BF): 1 \ Setting Group1
Description
Operation Off / On
Detection principle for back-up trip
Back-up trip mode
Operation mode of re-trip logic
Operate phase current level in % of IBase
Current for blocking of CB contact operation in % of IBase
Operate residual current level in % of IBase
Time delay of re-trip
Time delay of back-up trip
Time delay of back-up trip at multi-phase start
Name
Operation
FunctionMode
BuTripMode
RetripMode
IP>
I>BlkCont
IN>
t1
t2
t2MPh
Value
Off
Current
1 out of 3
Retrip Off
10 %IB
20 %IB
10 %IB
0.000 s
0.150 s
60.000 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
CCRPLD(52PD): 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Current \
CCRPLD(52PD): 1 \ Setting Group1
Description
Operation Off / On
Time delay between trip condition and trip signal
Contact function selection
Current function selection
Unsym magn of lowest phase current compared to the highest.
Current magnitude for release of the function in % of IBase
Name
Operation
tTrip
ContSel
CurrSel
CurrUnsymLevel
CurrRelLevel
Value
Off
0.300 s
Off
Off
80 %
10 %IB
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Voltage \
LOVPTUV(27; U<): 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Voltage \
LOVPTUV(27; U<): 1 \ Setting Group1
Description
Operation Off/On
Operate voltage in% of base voltage Ubase
Operate time delay
Duration of TRIP pulse
Time delay to block when all 3ph voltages are not low
Time delay for enable the function after restoration
Name
Operation
UPE
tTrip
tPulse
tBlock
tRestore
Value
Off
70 %UB
7.000 s
0.150 s
5.000 s
3.000 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Voltage \
OV2PTOV(59; 2U>): 1 \ General
Description
Selection of one of the Global Base Value groups
Group selector for connection type
Name
GlobalBaseSel
ConnType
Value
1
PhN DFT
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Voltage \
OV2PTOV(59; 2U>): 1 \ General \ Setting Group1
Description
Operation Off / On
Name
Operation
Value
Off
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Voltage \
OV2PTOV(59; 2U>): 1 \ Step 1 \ Setting Group1
Description
Enable execution of step 1
Selection of time delay curve type for step 1
Number of phases required to operate (1 of 3, 2 of 3, 3 of 3)
from step 1
Voltage start value (DT & IDMT) in % of UBase for step 1
Definite time delay of step 1
Minimum operate time for inverse curves for step 1
Time multiplier for the inverse time delay for step 1
Name
OperationStep1
Characterist1
OpMode1
Value
On
Definite time
1 out of 3
U1>
t1
t1Min
k1
120 %UB
5.00 s
5.000 s
0.05
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Voltage \
OV2PTOV(59; 2U>): 1 \ Step 2 \ Setting Group1
Description
Enable execution of step 2
Number of phases required to operate (1 of 3, 2 of 3, 3 of 3)
from step 2
Voltage start value (DT & IDMT) in % of UBase for step 2
Definite time delay of step 2
Name
OperationStep2
OpMode2
Value
On
1 out of 3
U2>
t2
150 %UB
5.000 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Voltage \
UV2PTUV(27; 2U<): 1 \ General
Description
Selection of one of the Global Base Value groups
Group selector for connection type
Name
GlobalBaseSel
ConnType
Value
1
PhN DFT
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Voltage \
UV2PTUV(27; 2U<): 1 \ General \ Setting Group1
Description
Name
Value
Operation Off / On
Operation
Off
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Voltage \
UV2PTUV(27; 2U<): 1 \ Step 1 \ Setting Group1
Description
Enable execution of step 1
Selection of time delay curve type for step 1
Number of phases required to operate (1 of 3, 2 of 3, 3 of 3)
from step 1
Voltage start value (DT & IDMT) in % of UBase for step 1
Definite time delay of step 1
Minimum operate time for inverse curves for step 1
Time multiplier for the inverse time delay for step 1
Name
OperationStep1
Characterist1
OpMode1
Value
On
Definite time
1 out of 3
U1<
t1
t1Min
k1
70 %UB
5.00 s
5.000 s
0.05
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Voltage \
UV2PTUV(27; 2U<): 1 \ Step 2 \ Setting Group1
Description
Enable execution of step 2
Number of phases required to operate (1 of 3, 2 of 3, 3 of 3)
from step 2
Voltage start value (DT & IDMT) in % of UBase for step 2
Definie time delay of step 2
Name
OperationStep2
OpMode2
Value
On
1 out of 3
U2<
t2
50 %UB
5.000 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Secondary system
supervision \ SDDRFUF: 1
Description
Selection of one of the Global Base Value groups
Name
GlobalBaseSel
Value
1
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Secondary system
supervision \ SDDRFUF: 1 \ Setting Group1
Description
Operation Off / On
Operating mode selection
Operate level of residual overvoltage element in % of UBase
Operate level of residual undercurrent element in % of IBase
Operate level of neg seq overvoltage element in % of UBase
Operate level of neg seq undercurrent element in % of IBase
Operation of change based function Off/On
Operate level of change in phase voltage in % of UBase
Operate level of change in phase current in % of IBase
Operate level of phase voltage in % of UBase
Operate level of phase current in % of IBase
Seal in functionality Off/On
Operate level of seal-in phase voltage in % of UBase
Operate level for open phase current detection in % of IBase
Operate level for open phase voltage detection in % of UBase
Name
Operation
OpMode
3U0>
3I0<
3U2>
3I2<
OpDUDI
DU>
DI<
UPh>
IPh>
SealIn
USealln<
IDLD<
UDLD<
Value
Off
UZsIZs
30 %UB
10 %IB
30 %UB
10 %IB
Off
60 %UB
15 %IB
70 %UB
10 %IB
On
70 %UB
5 %IB
60 %UB
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Secondary system
supervision \ TCSSCBR: 1
Description
Operation Off/On
Operate time delay
Reset time delay
Name
Operation
tDelay
tReset
Value
Off
3.000 s
0.500 s
.
REL650 V1.1 \ Relay Parameter Section \ Application Configuration \ Metering \
ETPMMTR(Wh<->): 1
Description
Operation Off/On
Direction of active energy flow Forward/Reverse
Direction of reactive energy flow Forward/Reverse
Preset Initial value for forward active energy
Preset Initial value for reverse active energy
Preset Initial value for forward reactive energy
Preset Initial value for reverse reactive energy
Pulse quantity for active forward accumulated energy value
Pulse quantity for active reverse accumulated energy value
Pulse quantity for reactive forward accumulated energy value
Pulse quantity for reactive reverse accumulated energy value
Activate the accumulation of energy values
Time interval for energy calculation
Active energy limit
Reactive energy limit
Energy accumulated pulse ON time
Energy accumulated pulse OFF time
Enable of zero point clamping detection function
Zero point clamping level at active Power
Zero point clamping level at reactive Power
Name
Operation
DirEnergyAct
DirEnergyReac
EAFPrestVal
EARPrestVal
ERFPresetVal
ERRPresetVal
EAFAccPlsQty
EARAccPlsQty
ERFAccPlsQty
ERRAccPlsQty
StartAcc
tEnergy
EALim
ERLim
tEnergyOnPls
tEnergyOffPls
EnZeroClamp
LevZeroClampP
LevZeroClampQ
Value
On
Forward
Forward
0.000 MWh
0.000 MWh
0.000 MVArh
0.000 MVArh
100.000 MWh
100.000 MWh
100.000 MVArh
100.000 MVArh
Off
1 Minute
1000000.000 MWh
1000.000 MVArh
1.000 s
0.500 s
On
10.000 MW
10.000 MVAr
.
REL650 V1.1 \ Additional Information \ General - General Information
Description
Manufacturer
Serial number
Device type
Manufacturer HW code
Name
Manufacturer
Serial number
Device type
Hardware revision
Software revision
Feeder
Feeder address
Bay
Bay address
Protected object name
Description
Location
Software revision
Feeder
Feeder address
Bay
Bay address
Protected object name
Description
Location
Value
ABB
1VHR91010439
Line Protection
SBFCABACBBBZAZNA
XA
V1.1
feeder
feeder address
bay
bay address
protected object name
information
location
.
REL650 V1.1 \ Additional Information \ Relay Information \ Distance protection \ DSTPDIS
Description
Name
Value
Operation accuracy current abs 0.002 xIn
Operation accuracy current rel 1.0 %
Operation accuracy voltage abs 0.002 xUn
Operation accuracy voltage rel 1.5 %
Operation accuracy impedance 5.0 %
rel
Operation accuracy Angle abs 2.0
Start time and Min Op time as 30 ms
well
Reset time
35 ms
Reset Ratio
0.95
Operate time acc. DT mode abs30 ms
Operate time acc. DT mode rel 1.0 %
.
REL650 V1.1 \ Additional Information \ Relay Information \ Overcurrent \ PHPIOC
Description
Name
Value
Operation accuracy current abs 0.002 xIn
Operation accuracy current rel 1.0 %
Min. operate time
20 ms
Reset time
Reset Ratio
45 ms
0.95
.
REL650 V1.1 \ Additional Information \ Relay Information \ Overcurrent \ OC4PTOC
Description
Name
Value
Operation accuracy current abs 0.002 xIn
Operation accuracy current rel 1.0 %
Operation accuracy time abs 0.030 s
Operation accuracy time abs 0.050 s
[inverse char.]
Operation accuracy time rel
1.0 %
Operation accuracy time rel
5.0 %
[inverse char.]
Min. operation current abs
0.002 xIn
Min. operation current rel
1.0 %
Min. operate time [inverse
10 ms
char.] abs
Min. operate time [inverse
0.5 %
char.] rel
Min. operate time [non-dir.]
20 ms
Reset time [non-dir.]
25 ms
Reset Ratio
0.95
.
REL650 V1.1 \ Additional Information \ Relay Information \ Overcurrent \ EFPIOC
Description
Name
Value
Operation accuracy current abs 0.002 xIn
Operation accuracy current rel 1.0 %
Min. operate time
20 ms
Reset time
40 ms
Reset Ratio
0.95
.
REL650 V1.1 \ Additional Information \ Relay Information \ Overcurrent \ EF4PTOC
Description
Name
Value
Operation accuracy current abs 0.002 xIn
Operation accuracy current rel 1.0 %
Operation accuracy time abs 0.030 s
Operation accuracy time abs 0.050 s
[inverse char.]
Operation accuracy time rel
1.0 %
Operation accuracy time rel
5.0 %
[inverse char.]
Min. operate time
30 ms
Reset time
30 ms
Reset Ratio
0.95
.
REL650 V1.1 \ Additional Information \ Relay Information \ SOTF protection \ CVRSOF
Description
Name
Value
Operation accuracy current abs 0.002 xIn
Operation accuracy current rel 1.5 %
Operation accuracy voltage abs 0.002 xUn
Operation accuracy voltage rel 1.5 %
Operate time acc. DT mode abs35 ms
Operate time acc. DT mode rel 1.0 %
not im manual
Start time
35 ms
.
REL650 V1.1 \ Additional Information \ Circuit Breaker Information
Description
52ab Percentage
CB Trip Time
CB Close Time
Absolute t-Tolerance
Relative t-Tolerance
Name
52ab Percentage
CB Trip Time
CB Close Time
Abs. t-Tolerance
Rel. t-Tolerance
Value
20.00 %
50.00 ms
100.00 ms
0.00 ms
5 %
.
REL650 V1.1 \ Additional Information \ Test Configuration
Description
Pulse time of TIMER used for pick-up and trip signals
Name
Output pulse time
Value
150 ms
.
REL650 V1.1 \ Additional Information \ Test Tolerance
Description
Global test tolerance
Name
Test tolerance
Value
4.00 %
Description
CB trip time
CB close time
Times for 52a, 52b in percent of CB time
Name
CB trip time
CB close time
52a, 52b % of CB
Value
50.00 ms
100.00 ms
20.00 %
Line angle:
CT starpoint:
80.00
Dir. line
1.000 %
30.00 ms
5.000 %
Tol. T abs. -:
Tol. Z abs.:
30.00 ms
0.000
kL angle:
0.000000
System parameters:
Line length:
PT connection:
Impedance correction
1A/I nom:
Impedances in primary
values:
12.66
at line
no
yes
Tolerances:
Tol. T rel.:
Tol. T abs. +:
Tol. Z rel.:
.
Grounding factor:
kL mag.:
0.000000
Separate arc resistance: no
Zone Settings:
Label
Z Tripping 1
LE Quad
Z Tripping 1
LL Quad
Z Tripping 2
LE Quad
Type
Tripping
Tol.T rel
1.000 %
Tol.Z rel.
5.000 %
Tol.Z abs
2.436
Tripping
L-L
30.00 ms
1.000 %
30.00 ms
30.00 ms
5.000 %
641.1 m
Tripping
L-E
430.0 ms
1.000 %
30.00 ms
30.00 ms
5.000 %
4.236
Z Tripping 2
LL Quad
Z Tripping 3
LE Quad
Z Tripping 3
LL Quad
Z Tripping 4
LE Quad
Z Tripping 4
LL Quad
Tripping
L-L
430.0 ms
1.000 %
30.00 ms
30.00 ms
5.000 %
1.004
Tripping
L-E
830.0 ms
1.000 %
30.00 ms
30.00 ms
5.000 %
5.889
Tripping
L-L
830.0 ms
1.000 %
30.00 ms
30.00 ms
5.000 %
1.266
Tripping
L-E
830.0 ms
1.000 %
30.00 ms
30.00 ms
5.000 %
358.6 m
Tripping
L-L
830.0 ms
1.000 %
30.00 ms
30.00 ms
5.000 %
160.3 m
X/
35
30
25
20
15
10
5
0
-5
-10
-20
-10
10
20
30
R/
Unit
Value
XRIO Path
RIO.DEVICE.NOMINALVALUES.INOM In
1.00 A
RIO/Device/Nominal Values/In
RIO.DEVICE.NOMINALVALUES.VNOM V_nom 110.00 V RIO/Device/Nominal Values/V nom
Comment
Test Module
Name:
Test Start:
User Name:
Company:
Version:
Test End:
Manager:
3.00 SR 1
05-Dec-2014 10:30:47
VTest
kS = kL:
10.00 V
no
Test Settings
.
Test model:
Test model:
Allow reduction of
ITest/VTest:
ZS mag.:
kS mag.:
0.000
1.000
ZS angle:
kS angle:
0.00
0.00
1.000 s
500.0 ms
Max. fault:
Time reference:
6.000 s
fault inception
not active
no
1.000 %
no
.
Fault Inception:
Mode:
DC-offset:
random
no
.
Times:
Prefault:
Postfault:
.
Other:
Extended zones:
Load current enabled:
.
Search Settings:
Search res. rel.:
Ignore nominal
characteristics:
Search interval:
50.00 m
200.0 m
.
Auxiliary Binary Outputs:
Name
Ext. zones active
Fault inception
Delay time
n/a
Slope
Slope
Open
n/a
Open
Test Results
Shot Test: Fault Type L1-E
|Z|
8.333
1.667
5.000
1.055
Phi
24.67
40.00
80.00
-110.00
%
n/a
n/a
n/a
n/a
6.667
5.857
1.667
6.874
11.23
9.797
12.41
7.460
13.06
12.31
16.15
15.73
3.333
20.90
19.04
21.87
36.55
27.47
23.45
96.40
57.93
-40.00
122.21
50.00
84.27
109.00
-5.91
57.61
11.49
36.91
124.14
-150.00
54.23
54.52
102.69
48.95
110.60
-10.00
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
% of
t nom
30.00 ms
30.00 ms
30.00 ms
830.0 ms
t act.
32.30 ms
24.50 ms
30.40 ms
833.1 ms
Dev.
7.667 %
-18.33 %
1.333 %
0.3735 %
VTest
10.00 V
10.00 V
10.00 V
10.00 V
30.00 ms
30.00 ms
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
30.00 ms
430.0 ms
430.0 ms
430.0 ms
no trip
no trip
430.0 ms
430.0 ms
830.0 ms
no trip
no trip
no trip
29.10 ms
26.30 ms
no trip
no trip
31.90 ms
34.10 ms
424.0 ms
29.50 ms
433.9 ms
443.1 ms
443.7 ms
no trip
no trip
442.4 ms
434.7 ms
843.3 ms
no trip
no trip
no trip
-3 %
-12.33 %
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
6.333 %
13.67 %
-1.395 %
-1.667 %
0.907 %
3.047 %
3.186 %
2.884 %
1.093 %
1.602 %
Result
Passed
Passed
Passed
Passed
(overload)
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
X/
40
30
20
10
-10
-20
-10
10
20
30
40
R/
Phi
24.67
40.00
80.00
-110.00
%
n/a
n/a
n/a
n/a
6.667
5.857
1.667
6.874
11.23
9.797
12.41
7.460
13.06
12.31
16.15
15.73
3.333
20.90
19.04
21.87
36.55
27.47
23.45
96.40
57.93
-40.00
122.21
50.00
84.27
109.00
-5.91
57.61
11.49
36.91
124.14
-150.00
54.23
54.52
102.69
48.95
110.60
-10.00
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
% of
t nom
30.00 ms
30.00 ms
30.00 ms
830.0 ms
t act.
23.30 ms
22.20 ms
30.20 ms
833.0 ms
Dev.
-22.33 %
-26 %
0.6667 %
0.3614 %
VTest
10.00 V
10.00 V
10.00 V
10.00 V
30.00 ms
30.00 ms
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
30.00 ms
430.0 ms
430.0 ms
430.0 ms
no trip
no trip
430.0 ms
430.0 ms
830.0 ms
no trip
no trip
no trip
31.00 ms
29.00 ms
no trip
no trip
28.80 ms
33.00 ms
430.7 ms
29.60 ms
429.4 ms
442.8 ms
433.5 ms
no trip
931.2 ms
431.3 ms
438.2 ms
840.2 ms
no trip
no trip
no trip
3.333 %
-3.333 %
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
-4 %
10 %
0.1628 %
-1.333 %
-0.1395 %
2.977 %
0.814 %
0.3023 %
1.907 %
1.229 %
Result
Passed
Passed
Passed
Passed
(overload)
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
X/
40
30
20
10
-10
-20
-10
10
20
30
40
R/
Phi
24.67
40.00
80.00
-110.00
%
n/a
n/a
n/a
n/a
6.667
5.857
1.667
6.874
11.23
9.797
12.41
7.460
13.06
12.31
16.15
15.73
3.333
20.90
20.90
19.04
21.87
21.87
36.55
27.47
27.47
23.45
23.45
96.40
57.93
-40.00
122.21
50.00
84.27
109.00
-5.91
57.61
11.49
36.91
124.14
-150.00
54.23
54.23
54.52
102.69
102.69
48.95
110.60
110.60
-10.00
-10.00
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
% of
t nom
30.00 ms
30.00 ms
30.00 ms
830.0 ms
t act.
23.10 ms
25.00 ms
25.90 ms
831.9 ms
Dev.
-23 %
-16.67 %
-13.67 %
0.2289 %
VTest
10.00 V
10.00 V
10.00 V
10.00 V
30.00 ms
30.00 ms
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
30.00 ms
430.0 ms
430.0 ms
430.0 ms
no trip
no trip
430.0 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
no trip
no trip
no trip
no trip
29.70 ms
28.90 ms
no trip
no trip
31.40 ms
34.60 ms
429.3 ms
30.40 ms
434.5 ms
433.5 ms
442.3 ms
no trip
1.441 s
443.1 ms
436.3 ms
436.2 ms
843.3 ms
834.0 ms
no trip
no trip
no trip
no trip
no trip
-1 %
-3.667 %
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
4.667 %
15.33 %
-0.1628 %
1.333 %
1.047 %
0.814 %
2.86 %
3.047 %
1.465 %
1.442 %
1.602 %
0.4819 %
Result
Passed
Passed
Passed
Passed
(overload)
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
X/
40
30
20
10
-10
-20
-10
10
20
30
40
R/
Phi
10.00
20.00
-150.00
23.31
40.00
24.67
40.00
80.00
80.00
-110.00
-110.00
96.40
96.40
57.93
-40.00
122.21
50.00
84.27
109.00
-5.91
57.61
11.49
36.91
124.14
-150.00
54.23
54.52
102.69
%
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
% of
t nom
30.00 ms
30.00 ms
830.0 ms
30.00 ms
430.0 ms
830.0 ms
30.00 ms
30.00 ms
30.00 ms
830.0 ms
830.0 ms
430.0 ms
430.0 ms
30.00 ms
no trip
no trip
430.0 ms
430.0 ms
830.0 ms
830.0 ms
830.0 ms
no trip
no trip
no trip
no trip
no trip
no trip
no trip
t act.
30.70 ms
34.40 ms
832.4 ms
37.50 ms
437.4 ms
848.2 ms
28.40 ms
33.30 ms
37.30 ms
839.9 ms
838.8 ms
438.1 ms
436.8 ms
31.90 ms
no trip
no trip
439.7 ms
452.8 ms
842.4 ms
848.5 ms
841.5 ms
no trip
no trip
no trip
no trip
no trip
no trip
no trip
Dev.
2.333 %
14.67 %
0.2892 %
25 %
1.721 %
2.193 %
-5.333 %
11 %
24.33 %
1.193 %
1.06 %
1.884 %
1.581 %
6.333 %
2.256 %
5.302 %
1.494 %
2.229 %
1.386 %
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
36.55
27.47
23.45
48.95
110.60
-10.00
n/a
n/a
n/a
no trip
no trip
no trip
no trip
no trip
no trip
10.00 V
10.00 V
10.00 V
Passed
Passed
Passed
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
X/
40
30
20
10
-10
-20
-10
10
20
30
40
R/
Phi
24.67
40.00
80.00
-110.00
96.40
57.93
-40.00
122.21
50.00
84.27
109.00
-5.91
57.61
11.49
36.91
124.14
-150.00
54.23
54.52
102.69
48.95
110.60
-10.00
%
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
% of
t nom
830.0 ms
30.00 ms
30.00 ms
830.0 ms
430.0 ms
30.00 ms
no trip
no trip
430.0 ms
430.0 ms
830.0 ms
830.0 ms
830.0 ms
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
t act.
843.3 ms
30.40 ms
36.40 ms
839.3 ms
434.2 ms
35.10 ms
no trip
no trip
441.8 ms
435.9 ms
841.7 ms
841.8 ms
845.7 ms
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
Dev.
1.602 %
1.333 %
21.33 %
1.12 %
0.9767 %
17 %
2.744 %
1.372 %
1.41 %
1.422 %
1.892 %
X/
40
30
20
10
-10
-20
-10
10
20
30
40
R/
Phi
24.67
40.00
80.00
-110.00
96.40
57.93
-40.00
122.21
50.00
84.27
109.00
-5.91
57.61
11.49
36.91
124.14
-150.00
54.23
54.52
102.69
48.95
110.60
-10.00
%
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
% of
t nom
830.0 ms
30.00 ms
30.00 ms
830.0 ms
430.0 ms
30.00 ms
no trip
no trip
430.0 ms
430.0 ms
830.0 ms
830.0 ms
830.0 ms
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
t act.
842.5 ms
30.60 ms
33.70 ms
843.4 ms
434.5 ms
35.60 ms
no trip
no trip
446.7 ms
445.3 ms
842.2 ms
851.0 ms
847.9 ms
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
Dev.
1.506 %
2%
12.33 %
1.614 %
1.047 %
18.67 %
3.884 %
3.558 %
1.47 %
2.53 %
2.157 %
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
X/
40
30
20
10
-10
-20
-10
10
20
30
40
R/
Phi
24.67
40.00
80.00
-110.00
%
n/a
n/a
n/a
n/a
6.667
5.857
5.857
1.667
1.667
6.874
6.874
7.712
11.23
11.23
9.797
9.797
11.67
12.41
12.41
7.460
7.460
13.06
13.06
12.31
12.31
16.15
16.15
96.40
57.93
57.93
-40.00
-40.00
122.21
122.21
90.00
50.00
50.00
84.27
84.27
103.00
109.00
109.00
-5.91
-5.91
57.61
57.61
11.49
11.49
36.91
36.91
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
% of
t nom
830.0 ms
30.00 ms
30.00 ms
830.0 ms
t act.
831.9 ms
25.10 ms
31.90 ms
839.8 ms
Dev.
0.2289 %
-16.33 %
6.333 %
1.181 %
VTest
10.00 V
10.00 V
10.00 V
10.00 V
430.0 ms
30.00 ms
30.00 ms
no trip
no trip
no trip
no trip
430.0 ms
430.0 ms
430.0 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
830.0 ms
830.0 ms
830.0 ms
830.0 ms
830.0 ms
no trip
no trip
no trip
no trip
437.9 ms
31.90 ms
35.60 ms
no trip
no trip
no trip
64.30 ms
434.1 ms
439.6 ms
438.4 ms
445.3 ms
446.3 ms
837.3 ms
838.1 ms
833.2 ms
833.2 ms
834.0 ms
836.9 ms
836.9 ms
no trip
no trip
no trip
no trip
1.837 %
6.333 %
18.67 %
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
0.9535 %
2.233 %
1.953 %
3.558 %
3.791 %
0.8795 %
0.9759 %
0.3855 %
0.3855 %
0.4819 %
0.8313 %
0.8313 %
Result
Passed
Passed
Passed
Passed
(overload)
Passed
Passed
Passed
Passed
Passed
Passed
failed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
15.73
15.73
3.333
3.333
20.90
19.04
21.87
36.55
27.47
23.45
124.14
124.14
-150.00
-150.00
54.23
54.52
102.69
48.95
110.60
-10.00
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
no trip
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
X/
40
30
20
10
-10
-20
-10
10
20
30
40
R/
3.991
18.27
Phi:
%:
-150.00
n/a
Angle:
% of:
61.27
Result:
Passed
|Z|
3.926
2.868
2.269
2.204
2.130
4.098
9.154
12.79
| Z |:
Length:
Phi
-150.58
-164.99
175.30
171.23
164.69
91.65
74.36
70.60
11.67
22.32
t nom
no trip
no trip
830.0 ms
830.0 ms
no trip
30.00 ms
30.00 ms
430.0 ms
Phi:
%:
t act.
no trip
no trip
844.3 ms
842.2 ms
845.0 ms
28.10 ms
31.30 ms
436.0 ms
7.86
n/a
Dev.
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
144.73
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
|Z|
11.10
9.693
8.918
11.49
12.49
| Z |:
Phi
10.66
20.11
81.29
100.77
105.05
7.213
t nom
430.0 ms
30.00 ms
30.00 ms
430.0 ms
430.0 ms
Phi:
t act.
441.2 ms
32.20 ms
33.90 ms
428.8 ms
427.1 ms
-70.00
Dev.
VTest
2.605 %
10.00 V
7.333 %
10.00 V
13 %
10.00 V
-0.2791 %
10.00 V
-0.6744 %
10.00 V
Angle: 65.95
Result
Passed
Passed
Passed
Passed
Passed
Result:
Passed
1.723 %
1.47 %
-6.333 %
4.333 %
1.395 %
Angle:
% of:
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Length:
|Z|
5.937
5.422
5.086
5.579
12.91
16.24
19.44
23.34
25.46
31.79
| Z |:
Length:
|Z|
9.253
8.078
6.880
4.594
8.911
12.06
15.15
18.94
21.02
27.21
36.79
%:
Phi
-56.40
-46.39
-33.62
1.93
43.08
47.96
50.99
53.54
54.59
56.87
t nom
no trip
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
11.55
38.94
Phi
-40.11
-35.46
-28.65
5.71
81.56
89.81
94.35
97.82
99.18
101.97
Phi:
%:
t nom
no trip
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
n/a
t act.
no trip
no trip
no trip
27.70 ms
32.50 ms
429.4 ms
439.6 ms
842.5 ms
844.4 ms
no trip
-46.14
n/a
t act.
no trip
no trip
no trip
24.00 ms
34.00 ms
434.0 ms
430.9 ms
837.6 ms
839.6 ms
no trip
% of:
Dev.
-7.667 %
8.333 %
-0.1395 %
2.233 %
1.506 %
1.735 %
Angle:
% of:
Dev.
-20 %
13.33 %
0.9302 %
0.2093 %
0.9157 %
1.157 %
| Z |:
12.02
Phi:
-148.49
Angle:
Length:
51.93
%:
n/a
% of:
|Z|
3.951
2.909
2.286
1.890
1.831
1.345
Phi
-161.49
-168.83
-176.93
174.26
172.50
142.71
t nom
no trip
no trip
830.0 ms
830.0 ms
830.0 ms
no trip
t act.
no trip
no trip
839.1 ms
835.2 ms
845.2 ms
no trip
Dev.
2.350
12.79
17.69
17.75
21.08
26.60
33.46
71.29
43.55
41.93
41.92
41.25
40.52
39.94
30.00 ms
30.00 ms
430.0 ms
430.0 ms
430.0 ms
830.0 ms
no trip
28.20 ms
33.90 ms
434.0 ms
430.9 ms
495.9 ms
848.9 ms
no trip
-6 %
13 %
0.9302 %
0.2093 %
15.33 %
2.277 %
| Z |:
Length:
|Z|
21.07
16.18
13.19
12.51
11.72
10.63
10.00
12.09
15.36
22.60
28.27
24.72
51.37
Phi
-12.23
-2.67
8.01
11.62
16.79
27.20
61.80
85.99
100.45
114.39
119.80
Phi:
%:
t nom
no trip
830.0 ms
430.0 ms
430.0 ms
430.0 ms
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
no trip
-16.59
n/a
t act.
no trip
871.6 ms
459.5 ms
443.7 ms
434.5 ms
33.40 ms
31.60 ms
439.5 ms
436.6 ms
842.2 ms
no trip
1.096 %
0.6265 %
1.831 %
Angle:
% of:
Dev.
5.012 %
6.86 %
3.186 %
1.047 %
11.33 %
5.333 %
2.209 %
1.535 %
1.47 %
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
111.33
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
37.72
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
140.07
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
(overload)
Result
Passed
Passed
Passed
Passed
Passed
Passed
(overload)
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
X/
40
30
20
10
-10
-20
-10
10
20
30
40
R/
3.991
18.27
Phi:
%:
-150.00
n/a
Angle:
% of:
|Z|
3.926
2.868
2.269
2.204
2.130
4.098
9.154
12.79
| Z |:
Length:
Phi
-150.58
-164.99
175.30
171.23
164.69
91.65
74.36
70.60
11.67
22.32
t nom
no trip
no trip
830.0 ms
830.0 ms
no trip
30.00 ms
30.00 ms
430.0 ms
Phi:
%:
t act.
no trip
no trip
842.0 ms
839.0 ms
857.0 ms
26.00 ms
29.10 ms
430.0 ms
7.86
n/a
Dev.
|Z|
11.10
9.693
8.918
11.49
12.49
| Z |:
Length:
Phi
10.66
20.11
81.29
100.77
105.05
7.213
36.79
t nom
430.0 ms
30.00 ms
30.00 ms
430.0 ms
430.0 ms
Phi:
%:
t act.
442.9 ms
36.00 ms
33.90 ms
435.9 ms
430.8 ms
-70.00
n/a
Dev.
3%
20 %
13 %
1.372 %
0.186 %
Angle:
% of:
|Z|
5.937
5.422
5.086
5.579
12.91
16.24
19.44
23.34
25.46
31.79
Phi
-56.40
-46.39
-33.62
1.93
43.08
47.96
50.99
53.54
54.59
56.87
t nom
no trip
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
t act.
no trip
no trip
no trip
27.30 ms
33.30 ms
432.4 ms
431.2 ms
830.3 ms
845.4 ms
no trip
Dev.
1.446 %
1.084 %
-13.33 %
-3 %
0%
Angle:
% of:
-9 %
11 %
0.5581 %
0.2791 %
0.03614 %
1.855 %
61.27
Result:
Passed
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
144.73
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
65.95
Result
Passed
Passed
Passed
Passed
Passed
Result:
Passed
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
| Z |:
Length:
|Z|
9.253
8.078
6.880
4.594
8.911
12.06
15.15
18.94
21.02
27.21
11.55
38.94
Phi
-40.11
-35.46
-28.65
5.71
81.56
89.81
94.35
97.82
99.18
101.97
| Z |:
12.02
Length:
51.93
Phi:
%:
t nom
no trip
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
-46.14
n/a
t act.
no trip
no trip
no trip
25.80 ms
31.60 ms
434.7 ms
433.7 ms
834.6 ms
841.6 ms
no trip
Phi:
-148.49
%:
n/a
Angle:
% of:
Dev.
-14 %
5.333 %
1.093 %
0.8605 %
0.5542 %
1.398 %
Angle:
Phi
-161.49
-168.83
-176.93
174.26
172.50
142.71
t nom
no trip
no trip
830.0 ms
830.0 ms
830.0 ms
no trip
t act.
no trip
no trip
852.3 ms
839.2 ms
836.2 ms
no trip
Dev.
2.350
12.79
17.69
17.75
21.08
26.60
33.46
71.29
43.55
41.93
41.92
41.25
40.52
39.94
30.00 ms
30.00 ms
430.0 ms
430.0 ms
430.0 ms
830.0 ms
no trip
25.10 ms
36.10 ms
430.1 ms
431.0 ms
441.8 ms
857.0 ms
no trip
-16.33 %
20.33 %
0.02326 %
0.2326 %
2.744 %
3.253 %
|Z|
21.07
16.18
13.19
12.51
11.72
10.63
10.00
12.09
15.36
22.60
28.27
24.72
51.37
Phi
-12.23
-2.67
8.01
11.62
16.79
27.20
61.80
85.99
100.45
114.39
119.80
Phi:
%:
t nom
no trip
830.0 ms
430.0 ms
430.0 ms
430.0 ms
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
no trip
-16.59
n/a
t act.
no trip
845.5 ms
453.6 ms
436.6 ms
430.7 ms
29.40 ms
30.60 ms
426.4 ms
433.5 ms
836.5 ms
no trip
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
37.72
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
(overload)
% of:
|Z|
3.951
2.909
2.286
1.890
1.831
1.345
| Z |:
Length:
111.33
2.687 %
1.108 %
0.747 %
Angle:
% of:
Dev.
1.867 %
5.488 %
1.535 %
0.1628 %
-2 %
2%
-0.8372 %
0.814 %
0.7831 %
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
140.07
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
Result
Passed
Passed
Passed
Passed
Passed
Passed
(overload)
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
X/
40
30
20
10
-10
-20
-10
10
20
30
40
R/
8.287
Phi:
-130.00
Angle:
Length:
40.15
%:
n/a
% of:
|Z|
4.284
3.294
2.824
1.707
1.489
Phi
-139.00
-144.83
-149.19
-172.93
174.24
t nom
no trip
830.0 ms
830.0 ms
830.0 ms
830.0 ms
t act.
no trip
841.0 ms
845.2 ms
839.1 ms
840.0 ms
1.378
137.94
no trip
no trip
3.192
9.540
13.29
16.81
21.05
23.35
30.16
84.42
67.52
65.22
63.99
63.06
62.70
61.95
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
26.80 ms
33.80 ms
429.7 ms
438.8 ms
831.7 ms
843.5 ms
no trip
| Z |:
Length:
|Z|
35.22
25.72
16.70
14.41
11.69
9.250
7.433
7.395
7.550
| Z |:
Length:
38.02
43.40
Phi
43.64
39.06
29.50
24.91
16.57
2.78
-27.62
-37.45
-46.33
3.991
18.27
Phi:
%:
t nom
no trip
830.0 ms
430.0 ms
430.0 ms
430.0 ms
30.00 ms
no trip
no trip
no trip
Phi:
%:
44.54
n/a
t act.
no trip
894.2 ms
460.6 ms
438.4 ms
433.4 ms
36.40 ms
no trip
no trip
no trip
-150.00
n/a
59.38
Dev.
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
1.325 %
1.831 %
1.096 %
1.205 %
10.00 V
-10.67 %
12.67 %
-0.06977 %
2.047 %
0.2048 %
1.627 %
Angle:
% of:
Dev.
7.735 %
7.116 %
1.953 %
0.7907 %
21.33 %
Angle:
% of:
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
235.74
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
61.27
Result:
Passed
(overload)
Result
Passed
Passed
Passed
Passed
Passed
(overload)
Passed
(overload)
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
|Z|
3.926
2.868
2.269
2.204
2.130
4.098
9.154
12.79
| Z |:
Length:
Phi
-150.58
-164.99
175.30
171.23
164.69
91.65
74.36
70.60
11.67
22.32
t nom
no trip
no trip
830.0 ms
830.0 ms
no trip
30.00 ms
30.00 ms
430.0 ms
Phi:
%:
t act.
no trip
no trip
843.5 ms
847.7 ms
838.5 ms
24.60 ms
29.60 ms
431.6 ms
7.86
n/a
Dev.
VTest
10.00 V
10.00 V
1.627 %
10.00 V
2.133 %
10.00 V
10.00 V
-18 %
10.00 V
-1.333 %
10.00 V
0.3721 %
10.00 V
Angle: 144.73
% of:
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
|Z|
11.10
9.693
8.918
11.49
12.49
| Z |:
Length:
Phi
10.66
20.11
81.29
100.77
105.05
7.213
36.79
t nom
430.0 ms
30.00 ms
30.00 ms
430.0 ms
430.0 ms
Phi:
%:
t act.
440.4 ms
35.60 ms
30.50 ms
431.6 ms
432.5 ms
-70.00
n/a
Dev.
VTest
2.419 %
10.00 V
18.67 %
10.00 V
1.667 %
10.00 V
0.3721 %
10.00 V
0.5814 %
10.00 V
Angle: 65.95
% of:
Result
Passed
Passed
Passed
Passed
Passed
Result:
Passed
|Z|
5.937
5.422
5.086
5.579
12.91
16.24
19.44
23.34
25.46
31.79
Phi
-56.40
-46.39
-33.62
1.93
43.08
47.96
50.99
53.54
54.59
56.87
t nom
no trip
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
t act.
no trip
no trip
no trip
28.80 ms
34.90 ms
435.9 ms
436.8 ms
831.8 ms
830.8 ms
no trip
Dev.
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
| Z |:
Length:
|Z|
9.253
8.078
6.880
4.594
8.911
12.06
15.15
18.94
21.02
27.21
11.55
38.94
Phi
-40.11
-35.46
-28.65
5.71
81.56
89.81
94.35
97.82
99.18
101.97
Phi:
%:
t nom
no trip
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
-46.14
n/a
t act.
no trip
no trip
no trip
26.50 ms
32.40 ms
440.2 ms
435.1 ms
831.4 ms
842.0 ms
no trip
-4 %
16.33 %
1.372 %
1.581 %
0.2169 %
0.09639 %
Angle:
% of:
Dev.
-11.67 %
8%
2.372 %
1.186 %
0.1687 %
1.446 %
| Z |:
12.02
Phi:
-148.49
Angle:
Length:
51.93
%:
n/a
% of:
|Z|
3.951
2.909
2.286
1.890
1.831
1.345
Phi
-161.49
-168.83
-176.93
174.26
172.50
142.71
t nom
no trip
no trip
830.0 ms
830.0 ms
830.0 ms
no trip
t act.
no trip
no trip
845.8 ms
836.8 ms
834.8 ms
no trip
Dev.
2.350
12.79
17.69
17.75
21.08
26.60
33.46
71.29
43.55
41.93
41.92
41.25
40.52
39.94
30.00 ms
30.00 ms
430.0 ms
430.0 ms
430.0 ms
830.0 ms
no trip
28.80 ms
33.70 ms
438.6 ms
442.8 ms
448.5 ms
853.5 ms
no trip
-4 %
12.33 %
2%
2.977 %
4.302 %
2.831 %
| Z |:
24.72
Phi:
-16.59
1.904 %
0.8193 %
0.5783 %
Angle:
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
111.33
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
37.72
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
140.07
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
(overload)
Result
Passed
Passed
Passed
Passed
Passed
Passed
(overload)
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
Length:
|Z|
21.07
16.18
13.19
12.51
11.72
10.63
10.00
12.09
15.36
22.60
28.27
51.37
%:
n/a
Phi
-12.23
-2.67
8.01
11.62
16.79
27.20
61.80
85.99
100.45
114.39
119.80
t nom
no trip
830.0 ms
430.0 ms
430.0 ms
430.0 ms
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
no trip
% of:
t act.
no trip
859.1 ms
455.2 ms
437.2 ms
437.3 ms
34.10 ms
30.20 ms
439.9 ms
431.1 ms
847.9 ms
no trip
Dev.
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
3.506 %
5.86 %
1.674 %
1.698 %
13.67 %
0.6667 %
2.302 %
0.2558 %
2.157 %
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
X/
40
30
20
10
-10
-20
-10
10
20
30
40
R/
3.991
18.27
Phi
138.40
132.85
125.73
106.57
82.76
79.64
73.06
71.52
70.42
69.24
11.67
22.32
Phi
16.68
25.98
26.76
Phi:
%:
t nom
no trip
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
830.0 ms
830.0 ms
-150.00
n/a
t act.
no trip
no trip
no trip
32.30 ms
41.40 ms
438.9 ms
438.4 ms
840.3 ms
845.2 ms
no trip
7.86
n/a
t act.
no trip
844.0 ms
844.1 ms
Angle:
% of:
Dev.
7.667 %
38 %
2.07 %
1.953 %
1.241 %
1.831 %
Angle:
% of:
Dev.
1.687 %
1.699 %
61.27
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
144.73
VTest
10.00 V
10.00 V
10.00 V
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Result
Passed
Passed
Passed
Passed
8.438
8.262
8.073
7.977
9.704
11.19
12.79
15.19
| Z |:
Length:
|Z|
5.016
5.017
5.029
5.098
5.229
5.429
6.570
10.97
11.44
17.61
| Z |:
Length:
|Z|
6.170
6.021
5.586
5.044
4.634
6.168
6.839
9.751
11.05
12.29
13.99
| Z |:
Length:
|Z|
1.420
1.358
1.308
1.491
7.606
8.947
10.27
12.25
12.44
14.94
| Z |:
Length:
|Z|
10.91
10.20
10.16
9.863
10.37
11.23
12.30
14.05
35.68
39.63
45.83
54.18
89.45
99.26
106.16
113.05
7.213
36.79
Phi
-24.69
-22.67
-19.88
-13.72
-7.64
-1.54
16.18
38.74
39.95
49.40
11.55
38.94
Phi
-22.86
-21.38
-16.30
-7.37
4.01
65.50
71.02
84.35
87.73
90.22
92.90
12.02
51.93
Phi
151.48
144.55
134.08
98.35
47.56
46.07
44.98
43.81
43.71
42.71
24.72
51.37
Phi
23.93
33.81
34.60
43.29
69.31
79.41
87.30
95.87
430.0 ms
430.0 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
no trip
no trip
30.00 ms
430.0 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
no trip
no trip
430.0 ms
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
830.0 ms
830.0 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
435.1 ms
440.9 ms
65.10 ms
436.8 ms
438.0 ms
837.9 ms
845.7 ms
no trip
-70.00
n/a
t act.
no trip
no trip
no trip
137.4 ms
445.5 ms
437.3 ms
441.1 ms
845.4 ms
838.3 ms
no trip
-46.14
n/a
t act.
no trip
no trip
no trip
449.6 ms
39.00 ms
40.70 ms
440.9 ms
457.5 ms
839.7 ms
838.6 ms
no trip
-148.49
n/a
t act.
no trip
no trip
no trip
29.10 ms
40.10 ms
445.1 ms
436.9 ms
841.0 ms
844.9 ms
no trip
-16.59
n/a
t act.
no trip
840.5 ms
837.8 ms
461.3 ms
446.6 ms
839.6 ms
847.5 ms
no trip
1.186 %
2.535 %
117 %
1.581 %
1.86 %
0.9518 %
1.892 %
Angle:
% of:
Dev.
358 %
3.605 %
1.698 %
2.581 %
1.855 %
1%
Angle:
% of:
Dev.
4.558 %
30 %
35.67 %
2.535 %
6.395 %
1.169 %
1.036 %
Angle:
% of:
Dev.
-3 %
33.67 %
3.512 %
1.605 %
1.325 %
1.795 %
Angle:
% of:
Dev.
1.265 %
0.9398 %
7.279 %
3.86 %
1.157 %
2.108 %
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
65.95
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
111.33
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
37.72
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
140.07
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
X/
40
30
20
10
-10
-20
-10
10
20
30
40
R/
3.991
18.27
Phi
138.40
132.85
125.73
106.57
82.76
79.64
73.06
71.52
70.42
69.24
11.67
22.32
Phi
16.68
25.98
26.76
35.68
39.63
45.83
54.18
89.45
99.26
106.16
113.05
7.213
36.79
Phi
-24.69
-22.67
Phi:
%:
t nom
no trip
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
830.0 ms
830.0 ms
430.0 ms
430.0 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
no trip
-150.00
n/a
t act.
no trip
no trip
no trip
34.00 ms
47.80 ms
440.8 ms
439.1 ms
836.0 ms
835.9 ms
no trip
7.86
n/a
t act.
no trip
844.5 ms
848.3 ms
448.7 ms
436.5 ms
56.40 ms
435.5 ms
450.4 ms
848.4 ms
844.2 ms
no trip
-70.00
n/a
t act.
no trip
no trip
Angle:
% of:
Dev.
13.33 %
59.33 %
2.512 %
2.116 %
0.7229 %
0.7108 %
Angle:
% of:
Dev.
1.747 %
2.205 %
4.349 %
1.512 %
88 %
1.279 %
4.744 %
2.217 %
1.711 %
Angle:
% of:
Dev.
61.27
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
144.73
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
65.95
VTest
10.00 V
10.00 V
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Result
Passed
Passed
Passed
5.029
5.098
5.229
5.429
6.570
10.97
11.44
17.61
| Z |:
Length:
|Z|
6.170
6.021
5.586
5.044
4.634
6.168
6.839
9.751
11.05
12.29
13.99
| Z |:
Length:
|Z|
1.420
1.358
1.308
1.491
7.606
8.947
10.27
12.25
12.44
14.94
| Z |:
Length:
|Z|
10.91
10.20
10.16
9.863
10.37
11.23
12.30
14.05
-19.88
-13.72
-7.64
-1.54
16.18
38.74
39.95
49.40
11.55
38.94
Phi
-22.86
-21.38
-16.30
-7.37
4.01
65.50
71.02
84.35
87.73
90.22
92.90
12.02
51.93
Phi
151.48
144.55
134.08
98.35
47.56
46.07
44.98
43.81
43.71
42.71
24.72
51.37
Phi
23.93
33.81
34.60
43.29
69.31
79.41
87.30
95.87
no trip
30.00 ms
430.0 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
no trip
no trip
430.0 ms
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
830.0 ms
830.0 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
no trip
393.7 ms
448.8 ms
444.1 ms
440.7 ms
839.4 ms
846.1 ms
no trip
-46.14
n/a
t act.
no trip
no trip
no trip
445.6 ms
51.10 ms
51.90 ms
439.9 ms
452.2 ms
843.8 ms
834.9 ms
no trip
-148.49
n/a
t act.
no trip
no trip
no trip
29.60 ms
37.50 ms
436.5 ms
436.6 ms
843.3 ms
843.6 ms
no trip
-16.59
n/a
t act.
no trip
838.0 ms
841.2 ms
438.0 ms
441.0 ms
831.5 ms
836.1 ms
no trip
1212 %
4.372 %
3.279 %
2.488 %
1.133 %
1.94 %
Angle:
% of:
Dev.
3.628 %
70.33 %
73 %
2.302 %
5.163 %
1.663 %
0.5904 %
Angle:
% of:
Dev.
-1.333 %
25 %
1.512 %
1.535 %
1.602 %
1.639 %
Angle:
% of:
Dev.
0.9639 %
1.349 %
1.86 %
2.558 %
0.1807 %
0.7349 %
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
111.33
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
37.72
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
140.07
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
X/
40
30
20
10
-10
-20
-10
10
20
30
40
R/
3.991
18.27
Phi
138.40
132.85
125.73
106.57
82.76
79.64
73.06
71.52
70.42
69.24
11.67
22.32
Phi
16.68
25.98
26.76
35.68
39.63
45.83
54.18
89.45
99.26
106.16
113.05
7.213
36.79
Phi
-24.69
-22.67
Phi:
%:
t nom
no trip
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
830.0 ms
830.0 ms
430.0 ms
430.0 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
no trip
-150.00
n/a
t act.
no trip
no trip
no trip
28.70 ms
40.40 ms
433.3 ms
440.6 ms
846.3 ms
842.5 ms
no trip
7.86
n/a
t act.
no trip
842.1 ms
849.0 ms
454.0 ms
441.9 ms
170.9 ms
441.0 ms
438.1 ms
842.1 ms
856.2 ms
no trip
-70.00
n/a
t act.
no trip
no trip
Angle:
% of:
Dev.
-4.333 %
34.67 %
0.7674 %
2.465 %
1.964 %
1.506 %
Angle:
% of:
Dev.
1.458 %
2.289 %
5.581 %
2.767 %
469.7 %
2.558 %
1.884 %
1.458 %
3.157 %
Angle:
% of:
Dev.
61.27
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
144.73
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
65.95
VTest
10.00 V
10.00 V
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Result
Passed
Passed
Passed
5.029
5.098
5.229
5.429
6.570
10.97
11.44
17.61
| Z |:
Length:
|Z|
6.170
6.021
5.586
5.044
4.634
6.168
6.839
9.751
11.05
12.29
13.99
| Z |:
Length:
|Z|
1.420
1.358
1.308
1.491
7.606
8.947
10.27
12.25
12.44
14.94
| Z |:
Length:
|Z|
10.91
10.20
10.16
9.863
10.37
11.23
12.30
14.05
-19.88
-13.72
-7.64
-1.54
16.18
38.74
39.95
49.40
11.55
38.94
Phi
-22.86
-21.38
-16.30
-7.37
4.01
65.50
71.02
84.35
87.73
90.22
92.90
12.02
51.93
Phi
151.48
144.55
134.08
98.35
47.56
46.07
44.98
43.81
43.71
42.71
24.72
51.37
Phi
23.93
33.81
34.60
43.29
69.31
79.41
87.30
95.87
no trip
30.00 ms
430.0 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
no trip
no trip
430.0 ms
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
830.0 ms
830.0 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
no trip
178.3 ms
441.3 ms
436.1 ms
449.2 ms
841.0 ms
844.2 ms
no trip
-46.14
n/a
t act.
no trip
no trip
no trip
445.3 ms
39.80 ms
48.00 ms
435.0 ms
449.7 ms
837.6 ms
843.5 ms
no trip
-148.49
n/a
t act.
no trip
no trip
no trip
28.70 ms
50.70 ms
436.9 ms
438.2 ms
843.9 ms
838.9 ms
no trip
-16.59
n/a
t act.
no trip
842.4 ms
841.6 ms
461.5 ms
450.3 ms
842.7 ms
857.3 ms
no trip
494.3 %
2.628 %
1.419 %
4.465 %
1.325 %
1.711 %
Angle:
% of:
Dev.
3.558 %
32.67 %
60 %
1.163 %
4.581 %
0.9157 %
1.627 %
Angle:
% of:
Dev.
-4.333 %
69 %
1.605 %
1.907 %
1.675 %
1.072 %
Angle:
% of:
Dev.
1.494 %
1.398 %
7.326 %
4.721 %
1.53 %
3.289 %
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
111.33
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
37.72
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
140.07
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
X/
40
30
20
10
-10
-20
-10
10
20
30
40
R/
2.727
17.72
Phi:
%:
-130.00
n/a
Angle:
% of:
|Z|
2.063
1.763
669.6 m
428.3 m
309.7 m
237.8 m
672.8 m
7.510
8.932
9.950
12.29
12.51
| Z |:
Length:
Phi
-128.39
-127.27
-114.29
-101.45
-85.18
-38.92
24.44
43.22
43.51
43.66
43.92
43.94
3.333
16.89
t nom
no trip
830.0 ms
830.0 ms
830.0 ms
830.0 ms
no trip
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
Phi:
%:
t act.
no trip
849.3 ms
n/a
n/a
n/a
n/a
n/a
49.70 ms
437.4 ms
437.1 ms
841.7 ms
843.1 ms
-44.74
n/a
Dev.
|Z|
2.570
2.420
2.228
1.746
5.618
6.468
9.742
11.11
12.38
| Z |:
Length:
Phi
-34.18
-31.06
-26.06
-0.83
87.62
89.96
95.08
96.32
97.22
3.991
18.27
t nom
no trip
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
Phi:
%:
t act.
no trip
no trip
no trip
26.30 ms
44.30 ms
431.6 ms
450.3 ms
837.3 ms
842.5 ms
-150.00
n/a
Dev.
|Z|
2.125
Phi
138.40
t nom
no trip
t act.
no trip
45.02
Passed
Result
Passed
Passed
Out of range
Out of range
Out of range
Out of range
Out of range
Passed
Passed
Passed
Passed
Passed
Result:
Passed
VTest
10.00 V
10.00 V
10.00 V
-12.33 %
10.00 V
47.67 %
10.00 V
0.3721 %
10.00 V
4.721 %
10.00 V
0.8795 %
10.00 V
1.506 %
10.00 V
Angle: 61.27
% of:
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
Dev.
Result
Passed
2.325 %
65.67 %
1.721 %
1.651 %
1.41 %
1.578 %
Angle:
% of:
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
105.01
Result:
VTest
10.00 V
2.184
2.297
2.915
5.658
6.575
10.14
11.64
13.04
14.95
| Z |:
Length:
|Z|
10.13
9.098
9.031
8.438
8.262
8.073
7.977
9.704
11.19
12.79
15.19
| Z |:
Length:
|Z|
5.016
5.017
5.029
5.098
5.229
5.429
6.570
10.97
11.44
17.61
| Z |:
Length:
|Z|
6.170
6.021
5.586
5.044
4.634
6.168
6.839
9.751
11.05
12.29
13.99
| Z |:
Length:
|Z|
1.420
1.358
1.308
1.491
7.606
8.947
10.27
12.25
12.44
132.85
125.73
106.57
82.76
79.64
73.06
71.52
70.42
69.24
11.67
22.32
Phi
16.68
25.98
26.76
35.68
39.63
45.83
54.18
89.45
99.26
106.16
113.05
7.213
36.79
Phi
-24.69
-22.67
-19.88
-13.72
-7.64
-1.54
16.18
38.74
39.95
49.40
11.55
38.94
Phi
-22.86
-21.38
-16.30
-7.37
4.01
65.50
71.02
84.35
87.73
90.22
92.90
12.02
51.93
Phi
151.48
144.55
134.08
98.35
47.56
46.07
44.98
43.81
43.71
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
830.0 ms
830.0 ms
430.0 ms
430.0 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
no trip
no trip
30.00 ms
430.0 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
no trip
no trip
430.0 ms
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
Phi:
%:
t nom
no trip
no trip
no trip
30.00 ms
30.00 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
no trip
29.80 ms
52.60 ms
427.8 ms
445.7 ms
832.8 ms
840.6 ms
no trip
7.86
n/a
t act.
no trip
838.3 ms
833.6 ms
441.5 ms
437.5 ms
52.40 ms
432.4 ms
437.3 ms
832.2 ms
834.0 ms
no trip
-70.00
n/a
t act.
no trip
no trip
no trip
72.70 ms
434.6 ms
435.7 ms
432.4 ms
834.4 ms
845.6 ms
no trip
-46.14
n/a
t act.
no trip
no trip
no trip
289.8 ms
35.10 ms
32.90 ms
430.0 ms
449.9 ms
836.7 ms
834.7 ms
no trip
-148.49
n/a
t act.
no trip
no trip
no trip
25.50 ms
46.10 ms
433.1 ms
441.1 ms
843.0 ms
843.3 ms
-0.6667 %
75.33 %
-0.5116 %
3.651 %
0.3373 %
1.277 %
Angle:
% of:
Dev.
1%
0.4337 %
2.674 %
1.744 %
74.67 %
0.5581 %
1.698 %
0.2651 %
0.4819 %
Angle:
% of:
Dev.
142.3 %
1.07 %
1.326 %
0.5581 %
0.5301 %
1.88 %
Angle:
% of:
Dev.
-32.6 %
17 %
9.667 %
0%
4.628 %
0.8072 %
0.5663 %
Angle:
% of:
Dev.
-15 %
53.67 %
0.7209 %
2.581 %
1.566 %
1.602 %
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
144.73
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
65.95
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
111.33
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
37.72
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Result:
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
14.94
| Z |:
Length:
|Z|
10.91
10.20
10.16
9.863
10.37
11.23
12.30
14.05
42.71
no trip
24.72
51.37
no trip
Phi:
%:
Phi
23.93
33.81
34.60
43.29
69.31
79.41
87.30
95.87
t nom
no trip
830.0 ms
830.0 ms
430.0 ms
430.0 ms
830.0 ms
830.0 ms
no trip
-16.59
n/a
t act.
no trip
838.0 ms
841.7 ms
439.3 ms
445.8 ms
832.4 ms
833.5 ms
no trip
10.00 V
Angle:
% of:
140.07
Dev.
Result:
VTest
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
10.00 V
0.9639 %
1.41 %
2.163 %
3.674 %
0.2892 %
0.4217 %
Passed
Passed
Result
Passed
Passed
Passed
Passed
Passed
Passed
Passed
Passed
X/
40
30
20
10
-10
-20
-10
10
20
30
40
R/
24.72
51.37
Phi:
%:
-16.59
n/a
Angle:
% of:
140.07
Result:
Passed
t/s
6.0
5.0
4.0
3.0
2.0
1.0
5
10
15
20
25
30
35
40
45
0.0
Shot Details:
.
Parameters:
Fault Type:
| Z |:
R:
%:
VTest
L1-L2-L3
14.05
-1.438
n/a
10.00 V
Phi:
X:
% of:
95.87
13.98
no trip
no trip
800.0 ms
Assessment:
Dev.:
t max:
Passed
.
Results:
t act.:
t nom:
t min:
no trip
10.00 V
10.00 V
10.00 V
711.8 mA
711.8 mA
711.8 mA
10.00 V
711.8 mA
V0:
V1:
V2:
I0:
I1:
I2:
0.000 V
10.00 V
0.000 V
0.000 A
711.8 mA
0.000 A
Fault
n/a
0.00
n/a
n/a
-95.87
n/a
Z/
V/V
80
60
40
20
0
-20
-0.9 -0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1 -0.0
0.1
0.2
0.3
0.4
0.1
0.2
0.3
0.4
-0.9 -0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1 -0.0
0.1
0.2
0.3
0.4
-0.9 -0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1 -0.0
0.1
0.2
0.3
0.4
t/s
-40
-60
-80
VL1
VL2
VL3
I/A
0.75
0.50
0.25
0.00
-0.25
-0.9 -0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1 -0.0
t/s
-0.50
-0.75
-1.00
IL1
IL2
IL3
Trip
Start
t/s
.
Cursor Data
Cursor 1
Cursor 2
C2 - C1
Time
Signal
Value
0.000 s
6.000 s
6.000 s
<none>
<none>
n/a
n/a
n/a
.
.
Test State:
Test failed
Overload occurred during testing!
t/s